Fundamentals of Refrigeration Part 5 Refrigerants

Similar documents
UNIT 2 REFRIGERATION CYCLE

Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram

REFRIGERATION (& HEAT PUMPS)

Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1

Open Cycle Refrigeration System

Increasing the evaporation temperature with the help of an internal heat exchanger

UNDERSTANDING REFRIGERANT TABLES

How To Design A Refrigeration System

PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A

Characteristics of Evaporators

Refrigeration Basics 101. By: Eric Nelson

RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight Temperature glide o C Boiling point (1 atm)

2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

How To Calculate The Performance Of A Refrigerator And Heat Pump

Troubleshooting HVAC/R systems using refrigerant superheat and subcooling

How does solar air conditioning work?

Mohan Chandrasekharan #1

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

APPLIED THERMODYNAMICS TUTORIAL 1 REVISION OF ISENTROPIC EFFICIENCY ADVANCED STEAM CYCLES

PG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India.

COURSE TITLE : REFRIGERATION AND AIR CONDITIONING COURSE CODE : 4029 COURSECATEGORY : A PERIODS/WEEK : 5 PERIODS/SEMESTER : 90 CREDITS : 4 OBJECTIVES

DEVELOPMENT OF A TWIN SCREW EXPRESSOR AS A THROTTLE VALVE REPLACEMENT FOR WATER-COOLED CHILLERS

POSSIBILITY FOR MECHANICAL VAPOR RE-COMPRESSRION FOR STEAM BASED DRYING PROCESSES

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

THE REPLACEMENT OF R-22

Condensers & Evaporator Chapter 5

Rotary Compressors RK, RG and HG

High Pressure Ammonia Systems New Opportunities

DET: Mechanical Engineering Thermofluids (Higher)

COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers

Chapter 3.4: HVAC & Refrigeration System

AIR CONDITIONING TECHNOLOGY

How Ground/Water Source Heat Pumps Work

Rusty Walker, Corporate Trainer Hill PHOENIX

A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

DRAFT. Appendix C.2 - Air Conditioning Thermodynamics 1

Engineering Recommendation on: Accumulators Revised Issued January 10, 1979 Page 1 of 7

Analytical Study of Vapour Compression Refrigeration System Using Diffuser and Subcooling

Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:

FUNDAMENTALS OF ENGINEERING THERMODYNAMICS

Contents and Nomenclature

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Fundamentals of Mechanical Refrigeration Systems

HVAC and REFRIGERATION

Why and How we Use Capacity Control

THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A

D A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction

New Trends in the Field of Automobile Air Conditioning

Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions

Boiler Calculations. Helsinki University of Technology Department of Mechanical Engineering. Sebastian Teir, Antto Kulla

ThermoStar Refrigeration Air Dryers

Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems

Heat Recovery In Retail Refrigeration

Energy Analysis and Comparison of Advanced Vapour Compression Heat Pump Arrangements

Percent per Degree Rule of Thumb for Refrigeration Cycle Improvement

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)

Optimal operation of an Ammonia refrigeration cycle

Testing methods applicable to refrigeration components and systems

Optimal operation of simple refrigeration cycles Part I: Degrees of freedom and optimality of sub-cooling

How To Know If A Refrigeration System Is Efficient

Purpose of Refrigeration

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls

A comparison of heterogenous and homogenous models of two-phase transonic compressible

We will try to get familiar with a heat pump, and try to determine its performance coefficient under different circumstances.

Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications

National Grid Small Business Energy Efficiency Program Overview. Central New York Energy Expo March 30, 2010

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29

TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

Air-sourced 90 Hot Water Supplying Heat Pump "HEM-90A"

Product Catalog. Large Commercial Split System. Model RAUP - TTV MBH CFM 50 Hz

Guide to Good Commercial Refrigeration Practice. Part 2. System Design and Component Selection

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

D A T A S H E E T. TX3 Thermo Expansion Valves. Alco Controls TX3. Features. Introduction. Description of bulb charges

Development of a model for the simulation of Organic Rankine Cycles based on group contribution techniques

A car air-conditioning system based on an absorption refrigeration cycle using energy from exhaust gas of an internal combustion engine

THE PSYCHROMETRIC CHART AND ITS USE

Controlling a 2-phase CO 2 loop using a 2-phase accumulator

Low GWP Replacements for R404A in Commercial Refrigeration Applications

Energy Procedia Energy 00 Procedia (2011) (2012) 56 65

A/C refrigerant system, overview

Guidelines of how to instrument, measure and evaluate refrigeration systems in supermarkets PAU GIMÉNEZ GAVARRELL

A basic introduction to steam

Analysis of Ammonia Water (NH3-H2O) Vapor Absorption Refrigeration System based on First Law of Thermodynamics

MAKING MODERN LIVING POSSIBLE. Refrigeration - an introduction to the basics REFRIGERATION & AIR CONDITIONING DIVISION. Lecture

Thermodynamics - Example Problems Problems and Solutions

Ambient Energy Fraction of a Heat Pump

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

ENERGY SAVING WORT BOILING SISTEM IN BREWING FACTORY

Thermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Commercial CO 2 Refrigeration Systems

Waste Heat Recovery through Air Conditioning System

How To Understand Evaporator

Repair, Retrofit, or Replace Choices for Servicing R-22 Equipment

Desuperheater Online Program Sizing Guidance

Transcription:

Refrigerants PH Chart Fundamentals of Refrigeration Part 5 Refrigerants This diagram shows a simplified pressure/ enthalpy chart for a non specified refrigerant. The area contained within the envelope is for a liquid vapour mixture. The region to the left of the envelope represents liquid in a subcooled condition. The region to the right of the envelope represents vapour in a superheated condition.

Here we see a similar chart to the original but containing further information. It represents a single component refrigerant such as R22 and it can be seen that lines of constant temperature correspond with lines of constant pressure. That means that there is only one saturation temperature for a given pressure irrespective of the state of the fluid.

What can this chart tell us? Here is a chart with the expansion process drawn on it. The expansion process is represented by a vertical line which drops from the condensing condition to the evaporating condition. The enthalpy (which is the energy that the fluid possesses) does not change.the pressure of the fluid does drop from 17 bar to 3.5 bar. The line will intersect with a line of constant quality at the lower pressure which will be the ratio of vapour that the refrigerant contains. The reduction in pressure can be provided by an expansion valve or a capillary tube or a hand operated expansion valve.

On this chart we have added the expansion process. The line moves horizontally to the right until it reaches the saturated vapour line. The enthalpy has increased from A to B. This means that energy has been absorbed by the refrigerant and this energy has been removed from the air stream.

Now we can look at the compression process. The act of compression requires energy to be added in the form of mechanical work. This is transformed into heat and the compression process follows the line of constant entropy. The point where it reaches the condensing pressure defines its temperature and its energy content (enthalpy is now at point C).

This chart shows the final part of the cycle. Heat is removed from the refrigerant until the enthalpy is reduced to the level at A where the cycle begins again. Subcooling I have previously stated that subcooling of liquid refrigerant has a beneficial effect on the cooling obtained from a refrigeration system. This diagram shows a system with subcooled liquid entering the expansion device. You will note that the expansion phase has moved to the left of the saturation line and the entering liquid enthalpy has reduced. This means that the difference in energy between the entering liquid and leaving gas has increased. It follows that a fixed mass of refrigerant flowing around the system will now be able to absorb more heat in the evaporation part of the cycle. The other main use of subcooling is to overcome pressure losses created by liquid lifting. If the condenser is positioned below the level of the evaporator it will be subjected to the weight of the column of liquid refrigerant which is acting against the direction of the flow. This will reduce the pressure seen at the expansion device and would cause some of the refrigerant to boil off because the liquid is no longer saturated. The expansion valve will only pass sufficient refrigerant if there is not an excessive quantity of gas within it. By supplying the correct amount of subcooling to overcome this pressure loss it can be guaranteed that the valve will only see liquid at its inlet.

This final chart shows a non azeotrope. That is a mixture of refrigerants which do not operate as a single component. You can see the isotherms (which are lines of constant temperature) do not line up with the lines of constant pressure. The effect of this is to have a liquid saturation pressure and a separate vapour saturation pressure for any given temperature. The difference between the two temperatures for a given pressure is known as the glide. Glide is important for the following reasons. Expansion valves have historically been controlled by superheat. This is on the basis that if the refrigerant is superheated there can be no liquid present. Now look at this situation where the pressure remains constant at 3.5 bar on R 407C this equates to a liquid saturation temperature of -15 C, a vapour saturation temperature of 8 C and a temperature at the point where it enters the evaporator of 13 C. Now,if we measure the temperature of the fluid leaving the evaporator the minimum temperature that we can safely say that all the refrigerant has boiled off is 8 C. We also need a quantity of superheat to drive the valve. This is always greater than 3 C. So we are saying that the minimum temperature that the refrigerant should be leaving the coil is 5 C. It has always been standard practice to specify pressures in the form of their saturation temperature. This was always acceptable because we had a fixed relationship between temperatures and pressures. With non azeotropes this is not the case. There are a range of temperatures associated with every pressure. A refrigeration system is only capable of providing a quantity of refrigerant at a single pressure in to the evaporator. The decision

now needs to be made as to which point is going to be taken as the evaporating temperature. If we take the liquid saturation point as the evaporating temperature this gives us a temperature of -15 C. If we take the vapour saturation temperature this gives an evaporating temperature of -8 C. Some manufacturers adopt the mid point as the representative temperature which would be -11.5 C.The operating point of the equipment has not changed. All of these points relate to R407C evaporating at 3.5 bara. So what is the evaporating temperature at these conditions? The answer is that they are all valid providing that we explain which one we are using. We also need to look at the effect of a non azeotrope on the condenser. Once again for any given pressure there will be a range of temperatures. At 17 bara the vapour saturation temperature is 43 C,however, the liquid saturation temperature is 37.5 C. To guarantee that all the refrigerant has turned to liquid at 17 bara the fluid must be at a lower temperature than 37.5 C. It is very important that we appreciate that this is the case and use the liquid saturation line temperature as the condensing pressure. It is also important that we inform our customer what we have done so that he can compare quotations on a fair basis. Coefficient of performance COP This is a representation of the efficiency of the system. It is the ratio of the refrigeration effect to the power input. So in our diagram the COP will be B-A/C-B.

Importance of pressure drop We have now established that there will be changes in temperature as a result of the pressures within any system. Let us now consider the effect of the dynamic pressure losses around the system caused by friction in pipework and components. Our compressor is running and sucking a fixed volume of refrigerant at a pressure determined by the system and discharging this refrigerant at high pressure into the discharge line. There will be a difference in pressure at this point which will be the driving force for the system. All flow requires a difference in pressure. If there is no pressure difference across components there will be no flow. One point in the system that requires high pressure drops to work correctly is the expansion process. There is a dramatic change in the entering and leaving pressures through the expansion device in order to produce the required effect in the evaporator. The evaporator and the tubing connecting it to the suction of the compressor should be as small as possible,whilst still maintaining the necessary velocities for oil entrainment. If the pressure drop through the evaporator and suction piping is too high the compressor will be operating at a lower pressure than the evaporator and the system efficiency will be reduced. The discharge pipework should be sized for minimum pressure drop whilst maintaining gas velocities sufficiently high to entrain the oil. The reason for this is the same as that for the evaporator in that the discharge pressure at the compressor will be higher than that at the entry to the condenser which will reduce the system efficiency.. Generally tubing and major components are sized with a maximum pressure drop that is equivalent to 1 C change. E.g. The compressor will have a pressure equal to 45 C. The pressure at the inlet to the condenser will be equal to 44 C. The evaporating pressure in the coil will be equal to 5 C and the suction pressure at the compressor will be equivalent to 4 C. The duty obtained from the compressor will be that applicable at 45 C SDT and 4 C SST. The duty available at the condenser will be that applicable when condensing at 44 C and the duty at the evaporator will be that obtainable when evaporating at 5 C.