2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units
|
|
|
- Bathsheba Welch
- 10 years ago
- Views:
Transcription
1 2004 Standard For Performance Rating Of Positive Displacement Refrigerant Compressors And Compressor Units ANSI/AHRI Standard 540 (formerly ARI Standard 540)
2 IMPORTANT SAFETY RECOMMENDATIONS ARI does not set safety standards and does not certify or guarantee the safety of any products, components or systems designed, tested, rated, installed or operated in accordance with this standard/guideline. It is strongly recommended that products be designed, constructed, assembled, installed and operated in accordance with nationally recognized safety standards and code requirements appropriate for products covered by this standard/guideline. ARI uses its best efforts to develop standards/guidelines employing state-of-the-art and accepted industry practices. ARI does not certify or guarantee that any tests conducted under its standards/guidelines will be non-hazardous or free from risk. Note: This standard supersedes ARI Standard Price $10.00 (M) $20.00 (NM) Printed in U.S.A. Copyright 2004, by Air-Conditioning, Heating, and Refrigeration Institute Registered United States Patent and Trademark Office
3 SECTION TABLE OF CONTENTS PAGE Section 1. Purpose... 1 Section 2. Scope... 1 Section 3. Definitions... 1 Section 4. Test Requirements... 3 Section 5. Rating Requirements... 3 Section 6. Minimum Data Requirements for Published Ratings... 3 Section 7. Operating Requirements... 7 Section 8. Marking and Nameplate Data... 7 Section 9. Conformance Conditions... 7 TABLES Table 1. Table 2. Standard Rating Conditions for Compressors and Compressor Units for Commercial Refrigeration Applications... 5 Standard Rating Conditions for Compressors and Compressor Units Used In Air Conditioners and Heat Pumps... 6 APPENDICES Appendix A. References - Normative... 8 Appendix B. References - Informative... 8 Appendix C. Method to Handle Zeotropic Mixtures - Informative... 9 FIGURES Figure C1. Cycle Process for Single Component Refrigerants and Azeotropic Mixtures... 9 Figure C2. Cycle Process for Zeotropic Refrigerant Mixtures Figure C3. Definitions of Subcooling and Superheating... 11
4
5 ANSI/AHRI STANDARD PERFORMANCE RATING OF POSITIVE DISPLACEMENT REFRIGERANT COMPRESSORS AND COMPRESSOR UNITS Section 1. Purpose 1.1 Purpose. The purpose of this standard is to establish, for single and variable capacity positive displacement refrigerant compressors and compressor units: definitions; test requirements; rating requirements; minimum data requirements for Published Ratings; operating requirements; marking and nameplate data and conformance conditions Intent. This standard is intended for the guidance of the industry, including manufacturers, engineers, installers, contractors and users Review and Amendment. This standard is subject to review and amendment as technology advances. Section 2. Scope 2.1 Scope. This standard applies to electric motor driven, single and variable capacity positive displacement refrigerant compressors and compressor units. This standard also applies to the presentation of performance data for positive displacement refrigerant compressors and compressor units for air-cooled, evaporatively-cooled or water-cooled air-conditioning, heat pump and refrigeration applications Refrigerant. The rating points in this standard are based on commonly used refrigerants. 2.2 Exclusions This standard does not apply to compressors and compressor units employing ammonia, as covered in ARI Standard This standard does not apply to compressors and compressor units intended for use in: a. Household refrigerators and freezers b. Automotive air-conditioners c. Dehumidifiers Section 3. Definitions All terms in this document will follow the standard industry definitions in the current edition of ASHRAE Terminology of Heating, Ventilation, Air Conditioning and Refrigeration unless otherwise defined in this section. 3.1 Compressor or Compressor Unit Efficiency. The efficiency is defined by the following equation: = 100 m C (h 2s - h 1 ) / P where: m = mass flow of volatile refrigerant, lb/h [kg/s] h 1 = specific enthalpy of the refrigerant vapor entering the compressor or compressor unit, Btu/lb [kj/kg] h 2s = specific enthalpy of the refrigerant vapor at the discharge pressure and the specific entropy of the refrigerant vapor entering the compressor or compressor unit, Btu/lb [kj/kg] C = W/Btu/h [1.0 kw/kj/s] 1
6 ANSI/AHRI STANDARD P = measured motor input power, W [kw] = compressor or compressor unit efficiency, %. 3.2 Positive Displacement Refrigerant Compressor. A compressor in which an increase in vapor pressure is attained by changing the internal volume of the compression chamber Hermetic Refrigerant Motor-Compressor. A compressor and motor assembly, both of which are enclosed in the same housing, with the motor operating in the refrigerant. 3.3 Positive Displacement Refrigerant Compressor Unit. A Positive Displacement Compressor with accessories, such as strainers, service valves, check valves, suction filters, oil separators, as provided by the manufacturer. This will also include variable capacity controls, electronic or electro-mechanical, as supplied or specified by the manufacturer External-Drive Refrigerant Compressor Unit. An External-Drive Refrigerant Compressor with motor mounted on a structural base and with accessories as provided by the manufacturer Hermetic Refrigerant Motor-Compressor Unit. A Hermetic Refrigerant Motor-Compressor with accessories as provided by the manufacturer. 3.4 Power Input. The power required from the incoming power source for the compressor(s) only, not including the power required for capacity control of the compressor or compressor unit including the oil heaters, motor starters, unloaders, frequency converters and other controls as specified by the manufacturer, expressed in W[kW]. 3.5 Published Rating. A statement of the assigned values of those performance characteristics, under stated rating conditions, by which a unit may be chosen to fit its application. These values apply to all units of like nominal size and type (identification) produced by the same manufacturer. The term Published Rating includes the rating of all performance characteristics shown on the unit or published in specifications, advertising or other literature controlled by the manufacturer, at stated rating conditions Application Rating. A rating based on tests performed at application Rating Conditions (other than Standard Rating Conditions) Standard Rating. A rating based on tests performed at Standard Rating Conditions. 3.6 Rating Conditions. Any set of operating conditions under which a single level of performance results and which causes only that level of performance to occur Standard Rating Conditions. Rating conditions used as the basis of comparison for performance characteristics. 3.7 Refrigerating Capacity. The capacity associated with the increase in total enthalpy between the liquid refrigerant entering the expansion valve and superheated return gas multiplied by the mass flow rate of the refrigerant Maximum Capacity. The highest displacement capacity by the compressor or compressor unit expressed in ft 3 /min [m 3 /sec] Minimum Capacity. The lowest displacement capacity obtainable by the compressor or compressor unit expressed in ft 3 /min [m 3 /sec]. 3.8 "Shall" or "Should," shall be interpreted as follows: Shall. Where "shall" or "shall not" is used for a provision specified, that provision is mandatory if compliance with the standard is claimed Should. "Should" is used to indicate provisions which are not mandatory, but which are desirable as good practice. 2
7 ANSI/AHRI STANDARD Section 4. Test Requirements 4.1 Test Requirements. All Published Ratings shall be verified by tests conducted in accordance with ASHRAE Standard 23. Section 5. Rating Requirements 5.1 Standard Ratings. The Standard Ratings of a compressor or compressor unit shall consist of standard mass flow ratings, lb/h [kg/s] identified at the Standard Rating Conditions, plus its associated Power Input rating W[kW] and efficiency rating, percent, when tested as specified by the manufacturer Standard Rating of a Commercial Refrigerating Compressor or Compressor Unit. The rating when operated under one of the Standard Rating Conditions presented in Table Standard Rating of a Compressor and Compressor Unit Used in an Air-Conditioner or Heat Pump. The ratings when operated under one of the Standard Rating Conditions presented in Table Application Ratings of Compressor and Compressor Units. Application Ratings shall consist of a mass flow rating and associated Power Input rating when tested at stated conditions other than those presented in Table 1 or 2, as specified by the manufacturer. 5.3 Nameplate Voltages for Rating. Rating tests shall be performed at the nameplate rated voltage and frequency. For dual nameplate voltage ratings, rating tests shall be performed at both voltages, or at the higher of the two voltages, if only a single rating is to be published. 5.4 Tolerances. To comply with this standard, measured test results shall not be less than 95% of Published Ratings for capacity and energy efficiency and power input shall be no more than 105% of the rated values. Section 6. Minimum Data Requirements for Published Ratings 6.1 Minimum Data Requirements for Published Ratings. As a minimum, Published Ratings shall include all Standard Ratings. All claims to ratings within the scope of this standard shall include the statement Rated in accordance with ARI Standard 540. All claims to ratings outside the scope of this standard shall include the statement Outside the scope of ARI Standard 540. Wherever Application Ratings are published or printed, they shall include a statement of the conditions at which the ratings apply. 6.2 Tabular Data. General performance data, covering the operational spectrum of the equipment, shall be presented in tabular form within defined accuracies and ranges of operation. The tables shall include: a. Suction dew point temperature range, F [ C] b. Discharge dew point temperature range, F [ C] c. Applicable superheat, F [ C] d. Power Input, W [W] e. Compressor or Compressor Unit Efficiency, percent f. Refrigerant mass flow rate, lb/h [kg/s] g. Current, A [A] h. Refrigerant designation per ASHRAE Standard 34 The manufacturer's tabular data shall be based on data obtained from tests performed or calculated by whatever means or methods deemed necessary at conditions within the range of application usage specified in 6.3.1, 6.3.2, or Data to be Reported. The tabular data shall be reported at the following conditions for the compressor or compressor unit application usage intended. The extreme ends of the tabular data may be omitted and not reported due to limits of acceptable 3
8 ANSI/AHRI STANDARD operation of the compressor or compressor unit as determined by the manufacturer Air-Conditioning (including heat pumps): -10 F to 55 F [-23 C to 13 C] suction dew point temperature in 5 F [3 C] increments 80 F to 140 F [27 C to 60 C] discharge dew point temperature in 10 F [5.6 C] increments Return gas temperature per Table High Temperature (water coolers and walk-in coolers, for example): 20 F to 50 F [-7 C to 10 C] suction dew point temperature in 5 F [3 C] increments 80 F to 140 F [27 C to 60 C] discharge dew point temperature in 10 F [5.6 C] increments Return gas temperature per Table Medium Temperature (display cases, for example): -10 F to 32 F [-23 C to 0 C] suction dew point temperature in 5 F [3 C] increments 80 F to 140 F [27 C to 60 C] discharge dew point temperature in 10 F [5.6 C] increments Return gas temperature per Table Low Temperature (freezer cases, for example): -40 F to 10 F [-40 C to -12 C] suction dew point temperature in 5 F [3 C] increments 80 F to 140 F [27 C to 60 C] discharge dew point temperature in 10 F [5.6 C] increments Return gas temperature per Table Polynomial Equation. The polynomial equation that shall be used to represent the tabular data is a third degree equation of ten coefficients in the form of: where: X = C1 +C2 (S) + C3 D +C4 (S 2 ) + C5 (S D) + C6 (D 2 ) + C7 (S 3 ) + C8 (D S 2 ) +C9 (S D 2 ) + C10 (D 3 ) 1 C = Equation coefficient, represents compressor performance S = Suction dew point temperature, F [ C] D = Discharge dew point temperature, F [ C] X can represent any of the following variables: Power Input, W or kw [kw] Mass flow rate, lb/h [kg/s] Current, A [A] Compressor or Compressor Unit Efficiency 4
9 ANSI/AHRI STANDARD Table 1. Standard Rating Conditions for Compressors and Compressor Units for Commercial Refrigeration Applications (Based on 95 F [35 C] Ambient Temperature) Suction Dew Point Temperature Compressor Type Discharge Dew Point Temperature Return Gas Temperature Subcooling F C F C F C F C All All* /65* 4.4/18* Hermetic All* /65* 4.4/18* All* /65* 4.4/18* 0 0 Note: If airflow across the compressor is used to determine ratings, it shall be specified by the compressor manufacturer. * 1) For hermetic type compressors, 40 F [4.4 C] return gas temperature shall be used. 2) For external drive and accessible hermetic type compressors, 65 F [18 C] return gas temperature shall be used. 5
10 ANSI/AHRI STANDARD Table 2. Standard Rating Conditions for Compressors and Compressor Units Used In Air Conditioners and Heat Pumps (Based on 95 F [35 C] Temperature Surrounding Compressor-- See Notes 1 and 3) Rating Test Point Intended Use Suction Dew Point Temperature Discharge Dew Point Temperature Return Gas Temperature Capacity Setting (Note 2) A B C D E F G H Air Source (Cooling) Air Source (Cooling) Air Source (Cooling & Heating) Air Source (Heating) Air Source (Heating) Air Source (Cooling) Air Source (Heating) Water Source (Cooling & Heating) F C F C F C MAX MAX MIN MAX MAX MIN MIN MAX. & MIN. NOTE: 1) If airflow across the compressor is used to determine ratings, it shall be specified by the compressor manufacturer. 2) The maximum and minimum capacity setting is the highest and lowest displacement capacity obtainable by the compressor or compressor unit. 3)15 F [8.3 C] degrees of subcooling To establish the coefficients to be used in the Equation 1, the method of Least Squares shall be used. For those conditions where the tabular data cannot be published due to the operating limits of the compressor, the compressor manufacturer will use test data or extrapolated values for the omitted points inside the range(s) specified in 6.3 so that the calculation may be completed and generate the coefficients to be used in the Equation Equation 1 shall not be used to extrapolate beyond the range of data specified in Superheat Corrections Superheat Range. For superheat, other than that specified, correction values will be provided upon request of the user for the following applications and ranges: Air-Conditioning: 15 F to 30 F [8.3 C to 16.7 C] High Temperature 15 F to 45 F [8.3 C to 25 C].
11 ANSI/AHRI STANDARD Med. Temperature 15 F to 75 F [8.3 C to 41.7 C] Low Temperature 15 F to 105 F [8.3 C to 58.3 C]. 6.6 Values Calculated Using Equation 1. Values of the same performance characteristics calculated from the ten coefficient third order equation and the coefficients provided by the compressor manufacturer shall agree with the tabular values within ± 1%. In the event that the compressor manufacturer determines that the values calculated from the ten coefficient equation may differ by more than 1% from the tabulated values in portions of the operating range, the compressor manufacturer will indicate this by shading, cross-hatching or otherwise identifying those affected data points in the table. Section 7. Operating Requirements 7.1 Loading Requirements. The compressor or compressor unit shall be capable of operating continuously at the maximum loading conditions stated in 7.2 for a minimum period of two hours at minimum and maximum utilization voltage as described in ARI Standard 110, Table Maximum Loading Conditions. The maximum suction dew point temperature limit shall be published. This limit shall be established with the compressor operating at conditions described below: a. Ambient temperature surrounding the compressor of 115 F [46.1 C] dry-bulb for all types. b. 145 F [62.8 C] discharge dew point temperature for compressors or compressor units for air cooled applications; 120 F [48.9 C] discharge dew point temperature for compressors and compressor units for water cooled applications. c. Superheated return gas temperature shall be no lower than 65 F [18 C]. Section 8. Marking and Nameplate Data 8.1 Compressor Electrical Marking. As a minimum, the voltage, phase, frequency, and locked-rotor current of all motors furnished as part of the compressor shall be clearly marked on the nameplate. Nameplate voltages for 60 Hertz systems shall include one or more of the utilization voltages shown in Table 1 of ARI Standard 110. Nameplate voltages for 50 Hertz systems shall include one or more of the equipment nameplate voltages shown in Table 1 of IEC Standard Compressor Unit Nameplate Marking. As a minimum, each compressor unit shall have a nameplate, affixed to its housing or base, on which the following information, in addition to that required under 8.1, shall be marked: a. Manufacturer's name and/or symbol b. Model number c. Refrigerant designation per ASHRAE Standard 34 d. Input voltage and frequency (Hz) e. Rated-load current (where applicable) Section 9. Conformance Conditions 9.1 Conformance. While conformance with this standard is voluntary, conformance shall not be claimed or implied for products or equipment within the standard s Purpose (Section 1) and Scope (Section 2) unless such product claims meet all of the requirements of the standard and all of the testing and rating requirements are measured and reported in complete compliance with the standard. Any product that has not met all the requirements of the standard shall not reference, state, or acknowledge the standard in any written, oral, or electronic communication. 7
12 ANSI/AHRI STANDARD APPENDIX A. REFERENCES - NORMATIVE A.1 Listed here are all standards, handbooks, and other publications essential to the formation and implementation of the standard. All references in this appendix are considered as part of the standard. A.1.1 ANSI/ASHRAE Standard with Addenda, Number Designation and Safety Classification of Refrigerants, 2001, American National Standards Institute/American Society of Heating, Refrigerating and Air- Conditioning Engineers, 11 West 42 nd Street, New York, NY 10036, U.S.A./1791 Tullie Circle N.E., Atlanta, GA 30329, U.S.A. A.1.2 AHRI Standard (formerly ARI Standard ), Air-Conditioning and Refrigerating Equipment Nameplate Voltages, 2002, Air-Conditioning, Heating, and Refrigeration Institute, 2111 Wilson Boulevard, Suite 500, Arlington, VA 22201, U.S.A. A.1.3 AHRI Standard (formerly ARI Standard ), Ammonia Compressor Units, 1993, Air- Conditioning, Heating, and Refrigeration Institute, 2111 Wilson Boulevard, Suite 500, Arlington, VA 22201, U.S.A. A.14 ASHRAE Standard , Methods of Testing for Rating Positive Displacement Refrigerant Compressors and Condensing Units, 1993, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 1791 Tullie Circle N.E., Atlanta, GA 30329, U.S.A. A.1.5 ASHRAE Terminology of Heating, Ventilation, Air Conditioning and Refrigeration 1991 Second Edition, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc., 1791 Tullie Circle N.E., Atlanta, GA 30329, U.S.A. A.1.6 IEC Standard Publication 60038, IEC Standard Voltages, 2002, International Electrotechnical Commission, 3, rue de Varembe, P.O. Box 131, 1211 Geneva 20, Switzerland. A1.7 ISO 917: 1989, Testing of Refrigerant Compressors, 1989, International Organization for Standardization, Case Postale 56, CH-1211, Geneva 21 Switzerland. APPENDIX B. REFERENCES INFORMATIVE None. 8
13 ANSI/AHRI STANDARD APPENDIX C.METHOD TO HANDLE ZEOTROPIC MIXTURES INFORMATIVE C1 Cycle Process For reference, Figure C1 shows a typical single stage cycle for single component refrigerants and azeotropic mixtures. The description is consistent with the ISO 917 standard. As shown, the evaporating and condensing processes occur at fixed temperatures t o and t c. Figure C1: Cycle Process for Single Component Refrigerants and Azeotropic Mixtures 9
14 ANSI/AHRI STANDARD Figure C2: Cycle Process for Zeotropic Refrigerant Mixtures Figure C2 shows temperature glide for zeotropic refrigerant mixtures at the evaporation and condensation processes. Standard reference temperatures are the dew-point temperatures t " 0 at the evaporating pressure p g1 and t " c at the condensing pressure p g2. The following equations may be used to calculate the mean evaporating temperature, mean condensing temperature, refrigerant superheating, and refrigerant subcooling: mean evaporating temperature: t 0,m = (t 01 + t " 0 )/ 2 C1 mean condensing temperature: t c,m = (t ' c + t c)/ " 2 C2 refrigerant superheating: t Sg = t g1 - t " 0 ) C3 refrigerant subcooling: t Sf = t ' c - t f2 = t f1 - t f2 C4 Because t 01 = t " 0 and t ' c = t " c for single-component refrigerants and azeotropic multi-component refrigerants, the cycle process model represents a particular kind of model for zeotropic refrigerant mixtures. In all reference systems refrigerating capacity is: Q = m (h g1 h f2 ) C5 and Q 0 = m (h g1 h f1 ) C6 10
15 ANSI/AHRI STANDARD for refrigerating capacity converted to no subcooling. The reference systems described above allow one to calculate and present performance data for all kinds of refrigerants in a similar way. ISO 917 requires zero subcooling for the calculation of refrigerating capacity of the compressor. In this case h f1 and h f2 are equal. Note: In connection with zeotropic mixtures, different definitions of the expressions superheating and subcooling can be found in technical documentation (Figure C3). The Equations C3 and C4 are equivalent to A in Figure C3 and shall be used for the purpose of calculating ratings. For reference only, B in Figure C3 with mean temperatures as reference points, uses the following equations: refrigerant superheating: t Sg = t g1 - t 0,m C7 refrigerant subcooling t Sf = t cm - t f2 t f1 - t f2 C8 Figure C3: Definitions of Subcooling and Superheating 11
16 ANSI/AHRI STANDARD C2 Symbols and Subscripts Symbols: f 1 g 1 g 2 h f1 h f2 h g1 = Bubble point at condensing process. = Point where the refrigerant enters the compression process. = Point where the refrigerant leaves the compression process = Enthalpy of the refrigerant at bubble point of condensing process. = Enthalpy of the subcooled refrigerant liquid entering the expansion process. = Enthalpy of the refrigerant gas entering the compression process. m = Refrigerant mass flow rate. P g1 = Compressor suction dew point pressure. P g2 = Compressor discharge dew point pressure. Q = Refrigerating capacity. Q 0 = Refrigerating capacity assuming no subcooling. t c = Condensing temperature. t c' = Bubble point temperature at condensing process. t c'' = Dew point temperature at condensing process. t c,m = Mean condensing temperature. t f1 = Temperature at which the subcooled liquid exits the expansion process t f2 = Temperature at which the subcooled liquid enters the expansion process. t g1 = Temperature of the refrigerant entering the compression process. t 0 = Evaporating temperature. t 0 '' = Dew point temperature at evaporation process. t 01 = Temperature at the outlet of the expansion process and inlet to the evaporation process. t 0,m = Mean evaporating temperature. tsf = Refrigerant subcooling. tsg = Refrigerant superheat. Subscripts: c = Condensing process c = Bubble point of condensing process c = Dew point of condensing process c,m = Mean condensing process f1 = Bubble point of condensing process f2 = Point at which the subcooled refrigerant liquid enters the expansion process g1 = Dew point at compressor suction g2 = Dew point at compressor discharge 0 = Evaporating process 01 = Outlet of the expansion process and inlet to the evaporation process 0,m = Mean evaporating process tsf = Temperature, saturated fluid tsg = Temperature, saturated gas 12
Performance Rating of Room Fan- Coils
ANSI/AHRI Standard 440 with Addendum 1 (Formerly ARI Standard 440) 2008 Standard for Performance Rating of Room Fan- Coils ANSI/AHRI STANDARD 440-2008 WITH ADDENDUM 1, PERFORMANCE RATING OF ROOM FAN-COILS
Energy Recovery Ventilation Equipment
AHRI Standard 1060 (I-P) 2013 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not
AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps
AHRI Standard 325 (Formerly ARI Standard 325) 1998 Standard for Ground Water-Source Heat Pumps IMPORTANT SAFETY RECOMMENDATIONS It is strongly recommended that the product be designed, constructed, assembled
ANSI/AHRI Standard 880 (I-P) with Addendum 1. 2011 Standard for Performance Rating of Air Terminals
ANSI/AHRI Standard 880 (I-P) with Addendum 1 2011 Standard for Performance Rating of Air Terminals Approved by ANSI on October 27, 2011 WITH ADDENDUM 1, PERFORMANCE RATING OF AIR TERMILS June 2012 Note:
A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures
R2-1 A Comparison of an R22 and an R410A Air Conditioner Operating at High Ambient Temperatures W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building Environment
Specifications for Refrigerants
AHRI Standard 700 2015 Standard for Specifications for Refrigerants IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or guarantee the safety of any products, components
Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1
Rating Water-Source Heat Pumps Using ARI Standard 320 and ISO Standard 13256-1 W. Vance Payne and Piotr A. Domanski National Institute of Standards and Technology Building and Fire Research Laboratory
Low GWP Replacements for R404A in Commercial Refrigeration Applications
Low GWP Replacements for R404A in Commercial Refrigeration Applications Samuel YANA MOTTA, Mark SPATZ Honeywell International, 20 Peabody Street, Buffalo, NY 14210, [email protected] Abstract
SASO XXXX:2016. (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS
SASO XXXX:2016 (Including the modifications approved in Saudi Council Board No. XXX/2016) LARGE CAPACITY AIR CONDITIONERS PERFORMANCE REQUIREMENTS AND METHODS OF TESTING 1 LARGE CAPACITY AIR CONDITIONERS
Troubleshooting HVAC/R systems using refrigerant superheat and subcooling
Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Application Note Troubleshooting and servicing refrigeration and air conditioning systems can be a challenging process for both
UNIT 2 REFRIGERATION CYCLE
UNIT 2 REFRIGERATION CYCLE Refrigeration Cycle Structure 2. Introduction Objectives 2.2 Vapour Compression Cycle 2.2. Simple Vapour Compression Refrigeration Cycle 2.2.2 Theoretical Vapour Compression
COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers
COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They
2007 Standard for Performance Rating of Commercial and Industrial Unitary Air- Conditioning and Heat Pump Equipment
ANSI/AHRI Standard 340/360-2007 with Addenda 1 and 2 (Formerly ARI Standard 340/360-2007) 2007 Standard for Performance Rating of Commercial and Industrial Unitary Air- Conditioning and Heat Pump Equipment
AHRI Standard 1361 (SI) 2016 Standard for Performance Rating of Computer and Data Processing Room Air Conditioners
AHRI Standard 1361 (SI) 2016 Standard for Performance Rating of Computer and Data Processing Room Air Conditioners IMPORTANT SAFETY DISCLAIMER AHRI does not set safety standards and does not certify or
UNDERSTANDING REFRIGERANT TABLES
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 UNDERSTANDING REFRIGERANT TABLES INTRODUCTION A Mollier diagram is a graphical representation of the properties of a refrigerant,
Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal
Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO. SAUDI STANDARD DRAFT No. 3457/2005
KINGDOM OF SAUDI ARABIA SAUDI ARABIAN STANDARDS ORGANIZATION SASO SAUDI STANDARD DRAFT No. 3457/2005 NON-DUCTED AIR CONDITIONERS AND HEAT PUMPS TESTING AND RATING PERFORMANCE This standard is developed
Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur
Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 22 Refrigeration System Components: Compressor (Continued)
Development and testing of a multi-type air conditioner without using AC inverters
Energy Conversion and Management 46 (2005) 373 383 www.elsevier.com/locate/enconman Development and testing of a multi-type air conditioner without using AC inverters Shih-Cheng Hu *, Rong-Hwa Yang Department
Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Characteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME
Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best
Heat Recovery In Retail Refrigeration
This article was published in ASHRAE Journal, February 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not
Testing methods applicable to refrigeration components and systems
Testing methods applicable to refrigeration components and systems Sylvain Quoilin (1)*, Cristian Cuevas (2), Vladut Teodorese (1), Vincent Lemort (1), Jules Hannay (1) and Jean Lebrun (1) (1) University
Commercial refrigeration has been in the environmental. Refrigerant. as a. Basics Considerations PART 1:
PART 1: CO 2 Commercial refrigeration has been in the environmental spotlight for more than a decade, especially as leakage studies have revealed the true effects of hydrofluorocarbon (HFC) emissions.
Why and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
Refrigeration Basics 101. By: Eric Nelson
Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs
ANSI/AHRI Standard 1350 (I-P) 2014 Standard for Mechanical Performance Rating of Central Station Air-handling Unit Casings
ANSI/AHRI Standard 1350 (I-P) 2014 Standard for Mechanical Performance Rating of Central Station Air-handling Unit Casings Approved by ANSI on May 19, 2015 IMPORTANT SAFETY DISCLAIMER AHRI does not set
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration
PREFACE. Your comments or suggestions are welcome and appreciated. They should be sent to:
PREFACE Because of changes in installation codes, the increasing complexity of the equipment involved, and other factors, more and more markings are being used on electrical heating and cooling equipment.
Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems
Environmental and Safety Impacts of HFC Emission Reduction Options for Air Conditioning and Heat Pump Systems William M. Corcoran, George Rusch, Mark W. Spatz, and Tim Vink AlliedSignal, Inc. ABSTRACT
Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram
Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram Copy Right By: Thomas T.S. Wan 温 到 祥 著 Sept. 3, 2008 All rights reserved Industrial refrigeration system design starts from
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
COMMERCIAL HVAC EQUIPMENT. Condensers and Cooling Towers
COMMERCIAL HVAC EQUIPMENT Condensers and Cooling Towers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics.
Chapter 3.4: HVAC & Refrigeration System
Chapter 3.4: HVAC & Refrigeration System Part I: Objective type questions and answers 1. One ton of refrigeration (TR) is equal to. a) Kcal/h b) 3.51 kw c) 120oo BTU/h d) all 2. The driving force for refrigeration
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING
MODELLING AND OPTIMIZATION OF DIRECT EXPANSION AIR CONDITIONING SYSTEM FOR COMMERCIAL BUILDING ENERGY SAVING V. Vakiloroaya*, J.G. Zhu, and Q.P. Ha School of Electrical, Mechanical and Mechatronic Systems,
Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems
Performance of R-438A in R-22 Refrigeration and Air Conditioning Systems Dr. Charles C. Allgood 1, C. Curtis Lawson 2 1 DuPont Fluorochemicals, Wilmington, DE, USA E-mail: [email protected]
Lesson. 11 Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications. Version 1 ME, IIT Kharagpur 1
Lesson Vapour Compression Refrigeration Systems: Performance Aspects And Cycle Modifications Version ME, IIT Kharagpur The objectives of this lecture are to discuss. Performance aspects of SSS cycle and
PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION REFRIGERATION SYSTEM WITH R404A, R407C AND R410A
Int. J. Mech. Eng. & Rob. Res. 213 Jyoti Soni and R C Gupta, 213 Research Paper ISSN 2278 149 www.ijmerr.com Vol. 2, No. 1, January 213 213 IJMERR. All Rights Reserved PERFORMANCE ANALYSIS OF VAPOUR COMPRESSION
Engineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7
Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator
Table Z. Troubleshooting Chart for Air Conditioners. Cause
Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause
Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Theoretical Study on Separate Sensible and Latent Cooling Air-Conditioning
How To Calculate The Performance Of A Refrigerator And Heat Pump
THERMODYNAMICS TUTORIAL 5 HEAT PUMPS AND REFRIGERATION On completion of this tutorial you should be able to do the following. Discuss the merits of different refrigerants. Use thermodynamic tables for
TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #31 System Drop-in Test of Refrigerant R-32 in Split Air-conditioning
2011 Standard for Performance Rating Of Water-Chilling and Heat Pump Water-Heating Packages Using the Vapor Compression Cycle
ANSI/AHRI Standard 550/590 (I-P) with Addendum 3 2011 Standard for Performance Rating Of Water-Chilling and Heat Pump Water-Heating Packages Using the Vapor Compression Cycle Approved by ANSI on June 18,
Energy Efficiency Testing for HVAC/R Helping you comply with energy efficiency regulatory programs
HVAC/R EQUIPMENT Energy Efficiency Testing for HVAC/R Helping you comply with energy efficiency regulatory programs As global demand for energy consumption continues to increase, the race to build more
Centrifugal Water Chillers. Scott Meyerkord
Centrifugal Water Chillers Scott Meyerkord Trane Account Manager Chilled Water System absorption centrifugal helical-rotary Centrifugal Water Chillers Centrifugal Water Chillers Components components of
Increasing the evaporation temperature with the help of an internal heat exchanger
Increasing the evaporation temperature with the help of an internal heat exchanger A. TAMBOVTSEV (a), H. QUACK (b) (a,b) Technische Universität Dresden, D-01062, Dresden, Germany (a) Fax: (+49351) 463-37247,
Mohan Chandrasekharan #1
International Journal of Students Research in Technology & Management Exergy Analysis of Vapor Compression Refrigeration System Using R12 and R134a as Refrigerants Mohan Chandrasekharan #1 # Department
Optimal operation of simple refrigeration cycles Part I: Degrees of freedom and optimality of sub-cooling
Computers and Chemical Engineering 31 (2007) 712 721 Optimal operation of simple refrigeration cycles Part I: Degrees of freedom and optimality of sub-cooling Jørgen Bauck Jensen, Sigurd Skogestad Department
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
How To Know If A Refrigeration System Is Efficient
Universitatea de Ştiinţe Agricole şi Medicină Veterinară Iaşi ASSESSMENT OF E SUBCOOLING CAPABILITIES OF A ERMOELECTRIC DEVICE IN A VAPOR COMPRESSION REFRIGERATION SYSTEM R. ROŞCA 1, I. ŢENU 1, P. CÂRLESCU
MAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2008 Scroll Compressor Development for Air-Source Heat Pump Water Heater Applications
RS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight 107.5 111.6 Temperature glide o C 0.5 0.2 Boiling point (1 atm)
RS-52 (R428A) COMPOSITION % HFC 125 77.5 HFC 143a 20.0 R600a 1.9 R290 0.6 HCFC replacement Temperature glide R22, 502 & interim blends Approximately 0.8 o C Drop-in or long term Both Lubricant MO/AB/POE
Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not CFC advocate the wholesale changeover of HCFC HCFC refrigerants
Optimization of Water - Cooled Chiller Cooling Tower Combinations
Optimization of Water - Cooled Chiller Cooling Tower Combinations by: James W. Furlong & Frank T. Morrison Baltimore Aircoil Company The warm water leaving the chilled water coils is pumped to the evaporator
Schedule 3(A) Room Air Conditioners
Schedule 3(A) Room Air Conditioners Revision : 1 Date : 21/08/15 1. Scope 1.1 This Standard specifies the energy labeling requirements for single-phase split air conditioners of the vapour compression
It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as
Refrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate CFC Technologies, Inc. does not advocate the HCFC wholesale
Measurement And Application of Performance Characteristics Of A Free Piston Stirling Cooler
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 00 Measurement And Application of Performance Characteristics Of A Free Piston
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
How does solar air conditioning work?
How does solar air conditioning work? In a conventional air conditioning system; The working fluid arrives at the compressor as a cool, low-pressure gas. The compressor is powered by electricity to squeeze
Air Conditioning 101. STN Presentation AC101
Air Conditioning 101 What is Refrigeration? Refrigeration is Cooling by the Removal of Heat Heat is Measured In BTU s A BTU is a British Thermal Unit It is the Amount of Heat to Raise One Pound of Water,
Solenoid Valves and Their Importance in Refrigeration Systems. October 2007
Solenoid Valves and Their Importance in Refrigeration Systems October 2007 Overview Introduction Solenoid valves play an important role within refrigeration and air conditioning systems, controlling the
PRE-ASSEMBLED REMOTE REFRIGERATION SYSTEMS
NOR-LAKE, INCORPORATED 727 Second Street P.O. Box 248 Hudson, Wisconsin 54016 800-955-5253 715-386-2323 866-961-5253 Parts 800-388-5253 Service 715-386-4291 FAX www.norlake.com Split-Pak Pre-Assembled
SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS
SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS 2009 Tecumseh Products Company. All rights reserved. Page 1 of 8 Refrigerant R22 is widely used for residential and commercial air conditioning, as
How To Clean Water From An Ammonia Refrigeration System
Water Contamination and Water Removal in Industrial Ammonia Refrigeration Systems By Ray Ficker, PE Effects of Water Contamination Water contamination in an industrial ammonia refrigeration system can
POLICY BULLETIN Tecumseh Compressor Company Compressor Group
to Bulk Milk Coolers and Other System Page 1 of 5 Overall reliability can be enhanced if there exists a complete understanding of the features, system design, installation requirements, processing, charging
National Grid Small Business Energy Efficiency Program Overview. Central New York Energy Expo March 30, 2010
National Grid Small Business Energy Efficiency Program Overview Central New York Energy Expo March 30, 2010 Agenda National Grid Cooler Retrofit Program Refrigeration 101 Smart Thermostat Controls, Anti-Sweat
THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A
THEORETICAL AND EXPERIMENTAL EVALUATION OF AUTOMOBILE AIR-CONDITIONING SYSTEM USING R134A Jignesh K. Vaghela Assistant Professor, Mechanical Engineering Department, SVMIT, Bharuch-392001, (India) ABSTRACT
Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.
I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is
HVAC and REFRIGERATION
This is a preview. Some pages have been omitted. PE principles and practice prracticce of engineering mechanical: HVAC and REFRIGERATION sample questions + solutions Copyright 2011 by NCEES. All rights
How To Design A Refrigeration System
AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison
Contents and Nomenclature
DX Coils Contents and Nomenclature Nomenclature... 1 Evaporator Coil Types EN... 2 EF... 2 ER... 2 EJ... 3 EK... 3 Evaporator Construction Connections... 4 Tubing... 4 Headers... 5 Tube Supports... 5 Coil
SECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
Sheet 5:Chapter 5 5 1C Name four physical quantities that are conserved and two quantities that are not conserved during a process.
Thermo 1 (MEP 261) Thermodynamics An Engineering Approach Yunus A. Cengel & Michael A. Boles 7 th Edition, McGraw-Hill Companies, ISBN-978-0-07-352932-5, 2008 Sheet 5:Chapter 5 5 1C Name four physical
REFRIGERATION (& HEAT PUMPS)
REFRIGERATION (& HEAT PUMPS) Refrigeration is the 'artificial' extraction of heat from a substance in order to lower its temperature to below that of its surroundings Primarily, heat is extracted from
Variable Capacity Compressors, a new dimension for refrigeration engineers to explore
Variable Capacity Compressors, a new dimension for refrigeration engineers to explore By: Marcos G. Schwarz, VCC Group Leader Corporate Research & Development, EMBRACO SA Abstract: This paper presents
Maintenance for Energy Efficiency
Maintenance for Energy Efficiency Institute of Hospital Engineering, Australia (IHEA) Seminar Asset Management & Energy Efficiency Exclusive Trane distributor Australia/New Zealand. The TRANE trade mark
Creating Efficient HVAC Systems
Creating Efficient HVAC Systems Heating and Cooling Fundamentals for Commercial Buildings Heating, ventilating, and air conditioning (HVAC) systems account for nearly half of the energy used in a typical
Thermodynamics - Example Problems Problems and Solutions
Thermodynamics - Example Problems Problems and Solutions 1 Examining a Power Plant Consider a power plant. At point 1 the working gas has a temperature of T = 25 C. The pressure is 1bar and the mass flow
PG Student (Heat Power Engg.), Mechanical Engineering Department Jabalpur Engineering College, India. Jabalpur Engineering College, India.
International Journal of Emerging Trends in Engineering and Development Issue 3, Vol. (January 23) EFFECT OF SUB COOLING AND SUPERHEATING ON VAPOUR COMPRESSION REFRIGERATION SYSTEMS USING 22 ALTERNATIVE
Test Code: 8297 / Version 1
Blueprint HVAC Maintenance Technology PA Test Code: 8297 / Version 1 Copyright 2014. All Rights Reserved. General Assessment Information HVAC Maintenance Technology PA Blueprint Contents General Assessment
Rusty Walker, Corporate Trainer Hill PHOENIX
Refrigeration 101 Rusty Walker, Corporate Trainer Hill PHOENIX Compressor Basic Refrigeration Cycle Evaporator Condenser / Receiver Expansion Device Vapor Compression Cycle Cooling by the removal of heat
Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps
Laboratory Test Report for Fujitsu 12RLS and Mitsubishi FE12NA Mini-Split Heat Pumps Jon Winkler, Ph.D. September 2011 NOTICE This report was prepared as an account of work sponsored by an agency of the
Nirvana. Cycling Refrigerated Dryers
Nirvana Cycling Refrigerated Dryers Nirvana Cycling Refrigerated Dryers Reliability Is Our Design Ingersoll Rand's Nirvana Cycling Refrigerated Dryer provides reliability like no other dryer in its class:
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
Research on the Air Conditioning Water Heater System
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 28 Research on the Air Conditioning Water Heater System Fei Liu Gree Electric
ThermoSorb Desiccant Dryers
ThermoSorb Desiccant Dryers Sierra Why dry compressed air? Contamination reduces efficiency The air we breathe contains contamination in the form of water vapour and airborne particles. During the compression
Guidelines of how to instrument, measure and evaluate refrigeration systems in supermarkets PAU GIMÉNEZ GAVARRELL
Guidelines of how to instrument, measure and evaluate refrigeration systems in supermarkets PAU GIMÉNEZ GAVARRELL Master of Science Thesis Stockholm, Sweden 2011 What is not measured does not exist; What
TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)
Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #44 System Drop-in Tests of Refrigerant R-32 in Single Packaged
WORKING DOCUMENT ON. Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS
WORKING DOCUMENT ON Possible requirements for air heating products, cooling products and high temperature process chillers TRANSITIONAL METHODS WORKING DOCUMENT in the framework of the implementation of
High Pressure Ammonia Systems New Opportunities
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 High Pressure Ammonia Systems New Opportunities Andy Pearson Star Refrigeration
Solenoid valves Type EVU
Data sheet Solenoid valves EVU EVU solenoid valves are designed to fit into compact refrigeration systems. Available in direct and pilot operated versions, they can be applied in liquid, suction, and hot
www.inspection-for-industry.com
Quality Control Form (TEST RUNNING RECORD FOR AIR HANDLING UNIT) SUB POWER SUPPLY: MAIN POWER V, Hz, CONTROL V, Blower 1 kw, Blower 2 kw, Compressor: (1) kw (2) kw (3) kw (4) kw Heating Element: kw 1.
Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida
Optimizing 100% Outside Air Systems with Heat Pipes Dr. Michael K. West, PE 1 Dr. Richard S. Combes, PE 2 Advantek Consulting / Melbourne, Florida Introduction To meet increasingly rigorous building codes
Large Energy Savings Per Installation VFDs for Large Chillers
This article was published in ASHRAE Journal, June 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Reprinted here by permission from ASHRAE at www.tiaxllc.com.
AIR-COOLED CHILLERS APPLIED SYSTEMS. www.daikin.eu EUWA*5-24KAZW - EUWY*5-24KAZW -
AIR-COOLED CHILLERS APPLIED SYSTEMS www.daikin.eu Cooling Only Heat pump EUWA*5-24KAZW - EUWY*5-24KAZW - Environmental Awareness Daikin and the Environment In recent years, motivated by a global awareness
