Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls
|
|
- Ronald Haynes
- 7 years ago
- Views:
Transcription
1 Geothermal Alliance of Illinois TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls
2 Thermal Expansion Valve Topics Anatomy Operation Terms & Features Superheat
3 Thermal Expansion Valve Anatomy Sensing Bulb Diaphragm External Equalizer Power Element Valve Packing Metering Pin Valve Inlet Valve Outlet Pin Carrier S.H. Adjusting Stem (Optional) Internal Check (Optional) Superheat Spring
4 Thermal Expansion Valve Power Assembly Thermal Thermal Ballast Ballast Diaphragm Stainless Steel Stainless Steel P.E. Buffer Plate
5 Thermal Expansion Valve Metering Pin & Port Valve Inlet Metering Pin Valve Port Pin Carrier Valve Outlet
6 Thermal Expansion Valve Topics Anatomy Operation Terms & Features Superheat
7 Why Do You Need A TXV It regulates the flow of liquid refrigerant into the coil to match the heat load on the coil. This is accomplished by controlling the superheat temperature of the refrigerant vapor leaving the coil.
8 Purpose Of A TXV Controls Evaporator Superheat Responds To Temperature And Pressure Only Does Not Control: Space Temperature Head Pressure Capacity Suction Pressure Humidity
9 Thermal Expansion Valve Valve Operation (Separates high side from low side) High Pressure Liquid Low Pressure Liquid and Vapor
10 Thermal Expansion Valve Valve Operation High Pressure Liquid 100 F 100 F 40 F 40 F Low Pressure Liquid and Vapor
11 Thermal Expansion Valve Valve Operation Remote Bulb And Power Assembly Pressure (Only Opening Force) P 1 P 2 Evaporator Pressure (Closing Force) Valve is in Balance When P 1 =P 2 +P 3 P 3 Superheat Spring (Closing Force)
12 Thermal Expansion Valve Topics Anatomy Operation Superheat Terms & Features
13 1 pound of Water BTU = (Sensible Heat) 1 pound of Water pound of Water BTU = (Latent Heat) 1 pound of Steam pound of Steam BTU = (Sensible Heat) 1 pound of Steam 220
14 Superheat Is A Temperature Difference Not Just A Temperature F Superheat 10 F Superheat
15 Superheat Measurement R PSIG = 40 F 65.6 PSIG = 38 F Actual Temp. 40 F 58.5 PSIG = 33 F Saturated Suction Pressure 58.5 PSIG Note: Turn Clockwise To Increase S/H P T CHART 33 F Actual Superheat = 7 F
16 Thermal Expansion Valves Normal Superheat Settings High Temp = 10 to 12 F (>30 F Evap. ) Medium Temp = 5 to 10 F (0 to 30 F Evap.) Low Temp = 2 to 5 F (Below 0 F Evap.) Follow System Manufacturers Recommended Superheat
17 Thermal Expansion Valves Superheat Adjustments Turn Adjustment Stem Clockwise To Increase Superheat. Adjustment (Superheat Change) Varies By: Valve manufacturer Valve family Refrigerant Evaporator Temperature NXT
18 Thermal Expansion Valve Topics Anatomy Operation Superheat Terms & Features
19 Thermal Expansion Valve Fixed Vs Adjustable Superheat
20 Thermal Expansion Valve Internal Vs External Equalizers Internal Equalizer Separate Equalizer Connection Outlet Connection External Equalizer
21 Thermal Expansion Valve Internal Bleed Option A Bleed Port Is An Internal Passage Directly Between The Valve Inlet And Outlet. Allows High And Low Side System Pressures To Equalize During The Off Cycle Thereby Allowing The Use Of Low Start Torque Compressors Adds To Total Valve Capacity 15% To 20% Typical Bleed Rate
22 Water Source HP Bi-Flow Cooling
23 Water Source HP Bi-Flow Heating
24 Thermal Expansion Valve Internal Check Option Flow Flow Forward (Closed) Flow (Low Leak) Reverse (Open) Flow (High Flow)
25 Water Source HP Dual TXVs Cooling
26 Water Source HP Dual TXVs Heating
27 Emerson valves, controls and system protectors. Other Emerson products including Copeland compressors and White-Rogers thermostats. Additional training and educational material.
28 TXV Troubleshooting
29 Sensing Bulb Location Bulb Should Be Clamp On A Horizontal Run Bulb Should Be Locate On The Pipe At: 12 O clock On Less Than 7/8" Pipe 8 Or 4 O clock On Greater Than 7/8" Pipe In All Cases The Bulb Should Be Insulated From The Ambient 12 O clock 8 O clock 4 O clock
30 Sensing Bulb Location In Most Cases The Bulb Can Be Mounted In Any Position On A Vertical Run In Most Cases It Is Not True That The Charge Will Leave Bulb If Mounted With Cap Tube Down OK Why Not OK? Horizontal Position Is Preferred Not OK
31 Proper Bulb and Equalizer Location The Bulb Should Be Located As Close As Possible To The Outlet Of The Evaporator Outlet The Bulb Should Be As Close As Possible To The Equalizer Tube The Bulb Should Be Located Up Stream Of The Equalizer To Prevent Being Effected By Any Liquid Leakage Through The Equalizer Tube
32 Improper Bulb and Equalizer Location The Bulb Should Not Be Mounted On The Evaporator Suction Header The Bulb Can Not Measure The Temperature On The Bottom Runs This Could Create A Possible Flood Back Situation
33 Improper Bulb and Equalizer Location If The Bulb And The Equalizer Are Not On The Same Side Of The P Trap Poor Superheat Control Can Result Equalizer On The Coil Side Can Result In High Superheat Bulb On The Coil Side Can Result In Low Superheat WRONG
34 Improper Bulb and Equalizer Location If A P-Trap Is Used The Equalizer And The Bulb Have To Be On The Same Side Of The Trap Coil Side Is Preferred If There Is Not Enough Room The Compressor Side Of The Trap Will Work
35 Valve Doesn t Feed Enough No Solid Column Of Liquid Valve Can t Make Capacity Results High Superheat Loss of Coil Efficiency The Valve Must Have a Solid Column of Liquid at the Inlet Corrective Action: Add Refrigerant
36 Valve Doesn t Feed Enough Cause: Flash Gas In The Liquid Line Diagnose By: Look For Flash Gas In The Sight Glass Listen For A Whistling Sound At The TXV. Results: High Superheat Loss Of Coil Efficiency 0 Flash Gas Bubbles At TXV Inlet Corrective Action: Remove Source Of Restriction Or Add Refrigerant
37 Valve Doesn t Feed Enough Cause: Incorrect Superheat Setting (High) High Setting Normal Setting Last Point of Liquid Refrigerant Last Point of Refrigerant Inefficient Corrective Action: Change Superheat Setting
38 Valve Doesn t Feed Enough Cause: Low or Lost Bulb Charge P1 The Loss Of P1 Means The Only Opening Force In The Valve Has Disappeared. This Means Little Or No Flow Through The Valve - High Superheat P2 Diagnose: Remove Bulb And Hold In Your Hand If No Change In Valve Flow, Then The Bulb Has Lost Charge P3 Corrective Action: Replace Power Head Or Valve
39 Superheat Is Erratic Or Hunts Bulb Location Reposition Bulb Too Large A Valve Replace Valve With The Proper Size Superheat Adjustment Adjust Superheat To Correct Setting Don t Jump to Conclusions to Quickly If the valve has been operating properly for a lengthy period of time it s probably not the conclusions listed above
40 TXV Troubleshooting Problem Sympton Cause Fix Overfeeding Overfeeding Overfeeding Overfeeding Overfeeding Low Superheat S/H Setting Oversize TXV Overcharge Bulb Location Dirty Evaporator Adjust Replace Remove Refrig. Relocate Clean Underfeeding Underfeeding Underfeeding Underfeeding Underfeeding High Superheat S/H Setting Undercharge Damaged Power Head Clogged Drier Ice Forming Adjust Add Refrig. Replace Change Change Drier Hunting Hunting Hunting Fluctuating S/H Bulb Location Oversize TXV S/H Setting Relocate Replace Adjust (See catalog section for more)
Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.
I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is
More informationRefrigeration Basics 101. By: Eric Nelson
Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs
More informationTroubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME
Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best
More informationTable V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
More informationTroubleshooting HVAC/R systems using refrigerant superheat and subcooling
Troubleshooting HVAC/R systems using refrigerant superheat and subcooling Application Note Troubleshooting and servicing refrigeration and air conditioning systems can be a challenging process for both
More informationIt will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.
The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as
More informationWhy and How we Use Capacity Control
Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,
More informationPOLICY BULLETIN Tecumseh Compressor Company Compressor Group
to Bulk Milk Coolers and Other System Page 1 of 5 Overall reliability can be enhanced if there exists a complete understanding of the features, system design, installation requirements, processing, charging
More informationD A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction
ALCO s series of Thermo -Expansion Valves are designed for air conditioning, chillers, rooftops, close control, A/C transportation, heat pumps, industrial cooling process and refrigeration applications.
More informationHow To Understand Evaporator
SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.
More informationINSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL
INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA/WL44H WA/WLH WA/WL70*H NOTE: Electrical data presented in this manual supersedes any other data f the above listed models. Bard
More informationCharacteristics of Evaporators
Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of
More informationRefrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Emerson Climate CFC Technologies, Inc. does not advocate the HCFC wholesale
More informationSECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
More informationD A T A S H E E T. TX3 Thermo Expansion Valves. Alco Controls TX3. Features. Introduction. Description of bulb charges
ALCO s TX3 series of Thermo -Expansion Valves are designed for air conditioning, heat pumps and commercial refrigeration applications. The TX3 is ideal for those applications requiring hermetic / compact
More informationRefrigerant Changeover Guidelines R-22 to R-407C. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-22 to R-407C Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not CFC advocate the wholesale changeover of HCFC HCFC refrigerants
More informationTechnical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1
Technical Training Associates Presents Commercial Refrigeration Equipment Servicing Part 1 By Jim Johnson A Practical Approach To The Fundamentals Of Walk-Ins, Reach-In and, Display Cases: Restaurant,
More informationHow To Design A Refrigeration System
AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison
More informationAir Conditioning 101. STN Presentation AC101
Air Conditioning 101 What is Refrigeration? Refrigeration is Cooling by the Removal of Heat Heat is Measured In BTU s A BTU is a British Thermal Unit It is the Amount of Heat to Raise One Pound of Water,
More informationThermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet
Thermostatic expansion valves type REFRIGERATION AND AIR CONDITIONING Technical leaflet Thermostatic expansion valves, type Contents Page Introduction........................................................................................3
More informationDESIGN STANDARDS SECTION 23 60 00
PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.
More informationREGULATORS 175/153 Series
175/153 Series 175 HEATING 153 COOLING Watson McDaniel reserves the right to change the designs and/or materials of its products without notice. 2002 Watson McDaniel Company Revised 7/2002 175 / 153 Screwed
More informationEngineering Recommendation on: Accumulators Revised 6-17-99 Issued January 10, 1979 Page 1 of 7
Issued January 10, 1979 Page 1 of 7 Accumulators have long been recognized by the industry as an effective means of maintaining good system balance by storing excess refrigerant as the condenser or evaporator
More informationM SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A
Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000
More informationRusty Walker, Corporate Trainer Hill PHOENIX
Refrigeration 101 Rusty Walker, Corporate Trainer Hill PHOENIX Compressor Basic Refrigeration Cycle Evaporator Condenser / Receiver Expansion Device Vapor Compression Cycle Cooling by the removal of heat
More informationSolenoid Valves and Their Importance in Refrigeration Systems. October 2007
Solenoid Valves and Their Importance in Refrigeration Systems October 2007 Overview Introduction Solenoid valves play an important role within refrigeration and air conditioning systems, controlling the
More informationRefrigeration System Installation & Operation Manual
Refrigeration System Installation & Operation Manual Manitowoc Foodservice Walk-In Division 2915 Tennessee Avenue North P.O. Box 550 Parsons, TN 38363 Phone: 800-225-9916 www.manitowocfsusa.com 550001058-3
More informationTable Z. Troubleshooting Chart for Air Conditioners. Cause
Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause
More informationASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014
ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating
More information1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system
More informationUNDERSTANDING REFRIGERANT TABLES
Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 UNDERSTANDING REFRIGERANT TABLES INTRODUCTION A Mollier diagram is a graphical representation of the properties of a refrigerant,
More informationHeating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
More informationHOW HVAC WORKS. How HVAC. Works PAGE 1
How HVAC Works PAGE 1 Heat - What is it? Heat is more than a physical concept - it is a feeling. Heat is taught to us at a very young age as a danger to be avoided. Yet, have you ever stopped and thought
More informationINSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX
Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into
More informationNO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS
INFORMATION INFORMATION ON THE TECHNOLOGY The -Frost refrigerators are different from the other static refrigerators in terms of their operational system. In normal refrigerators, in the freezing section,the
More informationFloat and Thermostatic Traps Series H, C and X
Hoffman Specialty Installation & Maintenance Instructions HS-(E) and Thermostatic Traps Series H, C and X Series C & NPT Series C NPT Series X NPT Series C NPT Series H Ratings Maximum Max. Operating NPT
More informationSTEAM HEATING SYSTEM TROUBLESHOOTING GUIDE
Page 1 of 9 PURPOSE Steam is the most commonly used heating medium for maintaining process temperatures. Compared to other heating media, steam contains a significant amount of heat energy, and this heat
More informationGUIDELINES ON AIRFLOW AND REFRIGERANT CHARGE VERIFICATION AND DIAGNOSTICS
GUIDELINES ON AIRFLOW AND REFRIGERANT CHARGE VERIFICATION AND DIAGNOSTICS Alliance for Residential Building Innovation David Springer, Davis Energy Group Context Airflow and refrigerant charge defects
More informationMAXIMUM HEAT LOAD TEMPERATURE TESTING ( Differential Temperature Testing )
MAXIMUM HEAT LOAD TEMPERATURE TESTING ( Differential Temperature Testing ) The Concept Maximum Heat Load Temperature Testing is a powerful air-conditioning diagnostic and evaluation technique. It is also
More informationEvaporator Coil. Installation Instructions GENERAL
IM-HAC-0966540-12 December 2013 Evaporator Coil Installation Instructions TABLE OF CONTENTS PAGE General... 1 Vertical... 2 Horizontal... 2 Multi-Position... 3-5 Metering Device... 6 Condensate Drain...
More information543-0032-00, 943-0032-00. User s Manual
543-0032-00, 943-0032-00 User s Manual 1 Comfort Alert Diagnostics Faster Service And Improved Accuracy The Comfort Alert diagnostics module is a breakthrough innovation for troubleshooting heat pump and
More informationA/C refrigerant system, overview
Page 1 of 19 87-18 A/C refrigerant system, overview A/C refrigerant system, identification Typical A/C refrigerant system with expansion valve and receiver drier 1 - Evaporator 2 - Expansion valve 3 -
More informationSteam System Best Practices Condensate System Piping
Steam System Best Practices Condensate System Piping Summary The best method for improving steam system energy efficiency, reducing chemical costs, and reducing make-up water costs is to return the maximum
More informationMAC-120HE-01 Air-Cooled Chiller
MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01
More informationSteam Coil Installation, Operation and Maintenance
Steam Coil Installation, Operation and Maintenance Guidelines for the installation, operation and maintenance of the Heatcraft brand of steam heating coils manufactured by Luvata in Grenada, MS have been
More informationFLASH TANK ECONOMIZER PRODUCT GUIDE
FLASH TANK ECONOMIZER PRODUCT GUIDE Overview A flash tank is used to recover blowdown energy in the form of flash steam and blowdown. This can only be used with a deaerator or some other pressurized device.
More informationGet the FACTS about SEER and Deliver Better Customer Value
What is SEER? SEER stands for Seasonal Energy Efficiency Ratio. It s a number that describes how well air-conditioning equipment works. A higher SEER means better efficiency and lower energy bills. SEER
More informationSECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
More informationSEALED SYSTEM DIAGNOSIS
CONSUMER SERVICES TECHNICAL EDUCATION GROUP PRESENTS R-105 SEALED SYSTEM DIAGNOSIS Liquid level varies but ly last couple of passes of condenser is filled with liquid when running TRAINING MANUAL Part
More informationRefrigerant Changeover Guidelines R-502 to R-402A/R-408A. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines R-502 to R-402A/R-408A Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not advocate the wholesale CFC changeover of CFC HCFC
More informationUA-NJ Air Conditioning & Refrigeration Division Training Curriculum
UA-NJ Air Conditioning & Refrigeration Division Training Curriculum 1st Year Basic Mathematics for HVAC Using formulas as an expression of logical sequence in solving problems. Measuring using a ruler
More informationHigh School Graduation years 2013, 2014, 2015. Unit/Standard Number
1 Secondary Task List 100 INTRODUCTION TO HVAC 101 Identify HVAC systems. 102 Describe career opportunities in the HVAC profession. 103 Demonstrate awareness of the occupational requirements. 104 Explain
More informationSERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS
SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS 2009 Tecumseh Products Company. All rights reserved. Page 1 of 8 Refrigerant R22 is widely used for residential and commercial air conditioning, as
More informationHow does solar air conditioning work?
How does solar air conditioning work? In a conventional air conditioning system; The working fluid arrives at the compressor as a cool, low-pressure gas. The compressor is powered by electricity to squeeze
More informationOptimized Thermal Expansion Valves for R-410A Systems. January 2008
Optimized Thermal Expansion Valves for R-410A Systems January 2008 Overview Introduction By 2010, the United States must phase out ozone-depleting refrigerants and transition to hydrofluorocarbon (HFC)
More informationON-VEHICLE INSPECTION
Sight Glass I11244 ONVEHICLE INSPECTION 1. INSPECT REFRIGERANT VOLUME Observe the sight glass on the liquid tube. AC3 AC22F05 Test conditions: Running engine at 1,500 rpm Blower speed control switch: HI
More informationINSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES. Split System Air Conditioner. Save these instructions for future reference WARNING
INSTALLATION AND MAINTENANCE INSTRUCTIONS 4AC16LT SERIES Split System Air Conditioner Save these instructions for future reference WARNING The equipment covered in this manual is to be installed by trained
More informationTube Size and Component Selection
Application Guide Tube Size and Component Selection for RAUC Split Systems (20 120 Tons) September 2001 SS-APG001-EN Preface This application guide provides refrigerant piping guidelines for Trane Model
More informationHeating Water by Direct Steam Injection
Heating Water by Direct Steam Injection Producing hot water by direct steam injection provides a solution where large volumes of hot water at precise temperatures are required, and where energy and space
More informationDehumidification Frequently Asked Questions
Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful
More informationApplication Feature Valve Nominal Liquid Capacity R-22 (in tons)*
EMERSON CLIMATE TECHNOLOGIES-Solenoid Valves & Coils Quick Select Guide Applications Application Feature Valve Nominal Liquid Capacity R-22 (in tons)* Nominal Liquid Capacity R-410A (in tons)* Liquid Line
More informationREMOTE RACK SYSTEM OWNERS MANUAL INSTALLATION OPERATIONS - MAINTENANCE
REMOTE RACK SYSTEM OWNERS MANUAL INSTALLATION OPERATIONS - MAINTENANCE 4401 Blue Mound Rd. Fort Worth, TX 76106 Phone: (714) 870-8661 Toll-Free: (800) 833-1106 Fax: (714) 870-6473 www.kairak.com KAIRAK,
More informationChilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
More informationHVAC-02, Air Conditioning Troubleshooting and Repair
HVAC-02, Air Conditioning Troubleshooting and Introduction Since I'm constantly receiving questions on 944 air conditioning systems, I figured it's time to come up with come helpful troubleshooting tips.
More informationRefrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507. Leading the Industry with Environmentally Responsible Refrigerant Solutions
Refrigerant Changeover Guidelines HCFC R-22 to HFC R-404A/R-507 Leading the Industry with Environmentally Responsible Refrigerant Solutions Copeland does not advocate the wholesale changeover of HCFCs
More informationEquivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Valve Sizing 408-409
Engineering Data Table of Contents Page No. I II Formulas, Conversions & Guidelines Equivalents & Conversion Factors 406 Capacity Formulas for Steam Loads 407 Formulas for Control Sizing 408-409 Steam
More informationBPI Air Conditioning & Heat Pump Professional Training Sample Slides ( ) Agenda
BPI Air Conditioning & Heat Pump Professional Training Sample Slides ( ) Photo of scott at AC with guages 1 Agenda Day I Refrigerants Introductions Verifying Charge Super Heat Paperwork & Sign-In Subcooling
More informationSystem Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING. Fitters notes
System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING Fitters notes Contents Page Faults on refrigeration systems, general...3 Fault location without the use of instruments...3 Categorisation...3
More informationComparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal
Technical Bulletin By Bruce I. Nelson, P.E., President, Colmac Coil Manufacturing, Inc. Comparing Air Cooler Ratings Part 1: Not All Rating Methods are Created Equal SUMMARY Refrigeration air coolers (evaporators)
More informationOpen Cycle Refrigeration System
Chapter 9 Open Cycle Refrigeration System Copy Right By: Thomas T.S. Wan 温 到 祥 著 Sept. 3, 2008 All rights reserved An open cycle refrigeration system is that the system is without a traditional evaporator.
More informationImpacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance
More informationCENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION
Technology Fact Sheet CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION Buildings for the 21st Century Buildings that are more energy-efficient, comfortable, and affordable that s the goal of DOE s Office
More informationChapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram
Chapter 2 P-H Diagram Refrigeration Cycle Analysis & Refrigerant Flow Diagram Copy Right By: Thomas T.S. Wan 温 到 祥 著 Sept. 3, 2008 All rights reserved Industrial refrigeration system design starts from
More informationEvaporator Coil Installation Instructions
Part # 96654008 July 2010 Evaporator Coil Installation Instructions A-Coil Page 4 Multi-position A-Coil Page 4-7 Slab Coil Page 5 Horizontal A-Coil Top Connection Page 5 Horizontal A-Coil Side Connection
More informationDESCRIPTION FEATURES HORIZONTAL DUCT HD. ISO 9001 Certified Quality Management System
TECHNICAL GUIDE ADD - ON COILS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: MC, PC, FC, HD, UC 600-2000 CFM 1.5-5 TON COILS UPFLOW/DOWNFLOW FULL CASED FC UPFLOW PARTIAL CASED PC UPFLOW UNCASED
More informationApplication Engineering
Application Engineering February 2012 Digital Capacity Control for Copeland Scroll Refrigeration Compressors INDEX Page 1. Introduction... 1 2. Theory of Operation... 1 3. Nomenclature... 1 4. Digital
More informationHeat Recovery In Retail Refrigeration
This article was published in ASHRAE Journal, February 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not
More informationOverview. Introduction Cooling Tower Basics Principles of Operation Types of Cooling Towers Common Applications Design Considerations
Stephen Lowe ASHRAE Hampton Roads Chapter Past President AECOM Design Mechanical Engineering Discipline Manager, Virginia Beach Division Professional Engineer Commonwealth of Virginia, NCEES BSME University
More informationDEFROSTING. Service Engineers Section Technical Bulletin No 3
Service Engineers Section Technical Bulletin No 3 DEFROSTING 1. INTRODUCTION This bulletin is presented to cover the methods used and problems experienced with defrosting of coils for chill and frozen
More informationHow Ground/Water Source Heat Pumps Work
How Ground/Water Source s Work Steve Kavanaugh, Professor Emeritus of Mechanical Engineering, University of Alabama Ground Source s (a.k.a. Geothermal s) are becoming more common as the costs of energy
More informationSpecific Volume of Liquid (Column 7). The volume per unit of mass in cubic feet per pound.
Steam Tables What They Are How to Use Them The heat quantities and temperature/ pressure relationships referred to in this Handbook are taken from the Properties of Saturated Steam table. Definitions of
More informationHow much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.
Demystifying HVAC Test Your HVAC Knowledge By Ron Prager How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. 1)
More informationLower Energy Costs with Rooftop Air-Conditioning Package Units
Lower Energy Costs with Rooftop Air-Conditioning Package Units Sponsored by Mike West, PhD, PE Advantek Consulting, Inc Package Unit Efficiency Factors Sensible and latent performance ratings Unit efficiency
More informationTrouble Shooting BD & TW Compressor Systems 12 and 24 Volt
Trouble Shooting BD & TW Compressor Systems 12 and 24 Volt Determine the Model. The data plate is on the left end near the wiring entrance. BD - BD air* TW - Tradewinds air** BDAW - BD air/water TWAW -
More informationGLYCOL CHILLER SYSTEM TROUBLESHOOTING 101
GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101 By Jim VanderGiessen Jr, Pro Refrigeration Inc. There is a good chance your glycol chiller system is often completely forgotten about, until that dreaded day you
More informationCOMPRESSOR REPLACEMENT PROCEDURE
COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003E Supersedes 2100-003D File: Volume I, Tab 1 Date: 06-25-02 Copyright
More informationRS-52 (R428A) RS-52: PHYSICAL PROPERTIES RS-52 R502 Molecular weight 107.5 111.6 Temperature glide o C 0.5 0.2 Boiling point (1 atm)
RS-52 (R428A) COMPOSITION % HFC 125 77.5 HFC 143a 20.0 R600a 1.9 R290 0.6 HCFC replacement Temperature glide R22, 502 & interim blends Approximately 0.8 o C Drop-in or long term Both Lubricant MO/AB/POE
More informationTYPE E Main Valve Sizes 3 /8 through 12
SD 3001F PRINTED IN U.S.A. SD 3001F/0707 A B TYPE E MAIN VALVE C D E TYPE E Main Valve Sizes 3 /8 through 12 The Spence Type E Main Valve is of normally closed, single seat design featuring packless construction,
More informationTotal Heat Versus Sensible Heat Evaporator Selection Methods & Application
Total Heat Versus Sensible Heat Evaporator Selection Methods & Application Scope The purpose of this paper is to provide specifying engineers, purchasers and users of evaporators in industrial refrigeration
More informationR22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power
R22. K Control. Indoor Unit. Nomenclature. PL H 3 G K H B Compatibility Unit style Heat Pump Horse Power Control Boost Heaters R22. K Control. Outdoor Unit. Nomenclature. PU H 3 Y K A Compatibility Outdoor
More informationOwners Manual. Refrigerated Air Dryer. HX75 thru HX2400
Owners Manual Refrigerated Air Dryer HX75 thru HX2400 IMPORTANT: READ THIS MANUAL CAREFULLY. IT CONTAINS INFORMATION ABOUT SAFETY AND THE SAFETY OF OTHERS. ALSO BECOME FAMILIAR WITH THE PROPER INSTALLATION
More informationAutomobile Air Conditioning Primer
Automobile Air Conditioning Primer An air conditioner is basically a refrigerator without the insulated box. It uses the evaporation of a refrigerant, like Freon, to provide cooling. The mechanics of the
More informationMechanical Seal Piping Plans
Mechanical Seal Piping Plans Single Seals plans 01, 02, 03, 11, 13, 14, 21, 23, 31, 32, 41 Dual Seals plans 52, 53A, 53B, 53C, 54, 55 Quench Seals plans 62, 65A, 65B, 66A, 66B Gas Seals plans 72, 74, 75,
More informationVACUUM REFRIGERATION SYSTEMS
VACUUM REFRIGERATION SYSTEMS CHILL VACTOR The Croll-Reynolds CHILL-VACTOR is a chiller that uses a vapor flashing process. Water has a pressure-temperature relationship which is its boiling point. If its
More informationPerkins Statewide Articulation Agreement. Documentation item: Secondary Competency Task List Coversheet
Perkins Statewide Articulation Agreement Documentation item: Secondary Task List Coversheet The Secondary School agrees to: A. Implement the approved PDE Program(s) of Study. B. Provide assessment of student
More informationVacuum. How It Relates to Refrigeration And Air Conditioning Service
Vacuum How It Relates to Refrigeration And Air Conditioning Service Moisture In A Refrigeration System Visible Moisture Water Droplets Uncommon, but it can occur Invisible Moisture Water Vapor Found in
More informationTechnical Help Guide
Technical Help Guide Thermal Expansion Valves Electronic Valves & Controls Solenoid Valves System Protectors Regulators Oil Controls Temperature Pressure Controls Basic Rules of Good Practice Troubleshooting
More informationENGINE COOLING SYSTEM
ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,
More informationAE21-1319 R6 December 2013. Digital Capacity Control for Copeland Scroll Refrigeration Compressors AE21-1319 R6
AE21-1319 R6 December 2013 Digital Capacity Control for Copeland Scroll Refrigeration Compressors TABLE OF CONTENTS Section Page Section Page Safety Safety Instructions...2 Safety Icon Explanation...2
More informationSi10-417_C. Pocket Manual. Service Diagnosis SPLIT & MULTI
Pocket Manual Service Diagnosis SPLIT & MULTI Service Diagnosis SPLIT & MULTI 1. Troubleshooting with LED...5 1.1 Indoor Unit... 5 1.2 Outdoor Unit... 10 2. Troubleshooting by Symptoms...11 2.1 Air conditioner
More information