Thermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet

Size: px
Start display at page:

Download "Thermostatic expansion valves type TR6 REFRIGERATION AND AIR CONDITIONING. Technical leaflet"

Transcription

1 Thermostatic expansion valves type REFRIGERATION AND AIR CONDITIONING Technical leaflet

2 Thermostatic expansion valves, type Contents Page Introduction Features Valve program Technical data Identification Design and function Application Ordering Check valve capacity Capacity Sizing Dimensions and weights RD1BA122 Danfoss A/S (RC-CMS / HBS),

3 Thermostatic expansion valves, type Introduction thermostatic expansion valves have been designed and developed with features especially for use in application such as: Residential air conditioning systems Split systems Roof top units Heat pumps Light commercial air conditioning systems Chillers Their hermetic tight design meets environmental demands for today and the future. The program is available for R22 and R410A and can be used in systems ranging in capacity up to 6 TR R22 (up to 21 kw). The can be used for all fluorinated refrigerants. Models for other refrigerants can be produced to order. The TR design incorporates a hot-pressed brass body with the entire power element, including the capillary tube and bulb, fabricated from stainless steel. The valves are supplied as standard in straightway versions with fixed orifice and with external equalization. They can be delivered with or without internal check valves and with external superheat adjustment spindle for field retrofit. All valves are in balanced port design making it ideal also for bi-flow operation. is uniquely for OEM s and their applications. The valves can be delivered with special connections and fittings both at the inlet and outlet and at the equalizer connection. The can be delivered with a fixed setting in accordance with the customers' requirement for optimized unit operation for the different applications within air conditioning. Features Compact size - hermetic design. Developed and designed for R22 and R410A. A complete program with or without internal check valve. An internal check valve with a very low pressure drop at full flow. MOP function. Non-adjustable with factory setting. Non-adjustable per customer s specification. Laser-welded power element: longer diaphragm life. high pressure tolerance and working pressure. Stainless steel power element, capillary tube and bulb: high corrosion resistance high strength and vibration resistance fast installation and good thermal contact and transmission Bleed function as an option. With internal check valve for heat pump systems. Without check valve for normal and bi-flow function. Danfoss A/S (RC-CMS / HBS), RD1BA122 3

4 Thermostatic expansion valves, type Valve program Standard versions Refrigerants: R22 and R410A. Range: N 40 F to +50 F / 40 C to +10 C MOP: With or without MOP. Versions for fixed settings: Static superheat in accordance with customers' specifications. Packing in boxes of 16 to 24 pcs. dependent on configuration. Versions for adjustable settings: Static superheat of 7.2 F / 4 K. Packing in single pack boxes. Versions All valves are in straightway versions. With or without internal check valve. Standard connections: 3 /8 in. ODF inlet x 1 /2 in. ODF outlet x 1 /4 in. ODF equalizer. Capillary tube length: 20 in. / 0.5 m Variant versions on request Refrigerants: Other refrigerants. Range: Other temperature ranges. MOP: Other MOP-points. Capillary tube lengths: 12 in. / 0.3 m 31.5 in. / 0.8 m 59 in. / 1.5 m Options for Connections: Inlet/Outlet: 3 /8 in., 5 /16 in., 1 /2 in., 5 /8 in. ODF, ODM, Chatleff, Rotolock, Aeroquip, Flare. Equalizer: Cap tube size: 3 /32 in., 1 /8 in., 3 /16 in., 1 /4 in. Length: 12 in. to 25 in. With or without Flare nut or Nib stub. Technical data Max. operating temperature - Thermostatic element: 212 F / 100 C (R410A max. 155 F / 68 C) - Valve body: 230 F / 110 C Max. working pressure MWP 610 psig / PS = 42 bar Max. test pressure 680 psig / p' = 47 bar MOP valves MOP-points Refrigerant R22 Range N F / C 100 psig / 6.9 bar To avoid charge migration when MOP valves are used, the bulb temperature must be lower than the thermostatic element temperature. R410A 165 psig / 11.5 bar Identification Essential valve data is given on the element label. Main valve data example: = Valve type R410A = Refrigerant 3.0 TR = Rated capacity Q nom. in Tons of Refrigeration MOP 165 = Max. operating pressure MWP 610 psig/ PS 42 bar = Max. working pressure in psig and bar 067L5000 = Code number 464B = Date marking (week 46, year 2004, weekday B = Tuesday) 40 / +50 F = Evaporating temperature range in F 40 / +10 C = Evaporating temperature range in C Fig. 1 4 RD1BA122 Danfoss A/S (RC-CMS / HBS),

5 Thermostatic expansion valves, type Design and function Fig. 2 with fixed setting 1. Bulb 2. Thermostatic element 3. Pressure pin seal 4. Balanced port 5. Check valve 6. Setting spindle for adjustment of static superheat (SS) 7. Equalizer 8. Inlet connection 9. Outlet connection Fig. 3 with adjustable setting Fig. 4 The central pressure pin is fitted with a robust seal (pos. 3) that ensures maximum tightness and minimum friction through the lifetime of the valve. The balanced port (pos. 4) ensures minimal superheat changes when differential pressure varies. This feature makes the valve ideal for biflow operation. Static superheat (SS) can be adjusted with the setting spindle (see fig. 3, pos. 6). The standard superheat setting is 7.2 F / 4K for valves with and without MOP. Valves can also be supplied with a fixed setting. Terminology (fig.4) SS = Static superheat OS = Opening superheat OSH = SS + OS = Operating superheat Example Static superheat SS = 7.2 F (4K) (factory setting) or according to customer specification. Opening superheat OS = 7.2 F (4K) The opening superheat is 7.2 F, i.e. from the point the valve begins to open up to nominal capacity. Opening superheat is determined by the design and cannot be changed. Operating superheat OSH = SS + OS OSH = 7.2 F F = 14.4 F (8K) Operating superheat OSH (fig. 4) can be changed by changing the static superheat (by using the setting spindle). Danfoss A/S (RC-CMS / HBS), RD1BA122 5

6 Thermostatic expansion valves, type Application without check valve EVR/EVRH SGI/SGN/SGH DCL/DML Fig. 5. Traditional air conditioning system, cooling only Indoor coil 4-way valve Outdoor coil with check valve SGI/SGN/SGH DCB/DMB with check valve Fig. 6. Traditional air conditioning / heat pump system Indoor coil 4-way valve Outdoor coil DCR without check valve Fig. 7. Simplified air conditioning / heat pump system (bi-flow) Fig. 5 illustrates the diagram of a traditional air conditioning system where the is controlling liquid injection in one direction only. Fig. 6 illustrates a split air conditioning/heat pump system with cooling/heating mode and two thermostatic expansion valves, one for cooling mode and one for heating mode. The thermostatic expansion valves each has a built-in check valve, which has the function of preventing flow in one direction and allowing the flow in the opposite direction. It means that one thermostatic expansion valve is controlling liquid injection into the evaporator and the other thermostatic expansion valve has an open check valve allowing the liquid refrigerant flow in the liquid line. Fig. 7 illustrates a similar system as the previous one, but this time it is a compact unit with a short distance between the evaporator and the condenser, the bi-flow feature of the thermostatic expansion valve can be used. The two thermostatic expansion valves have, therefore, been replaced by one bi-flow valve controlling liquid injection in both directions. The normal flow direction marked with an arrow should be used for the primary function, i.e. cooling or heating. 6 RD1BA122 Danfoss A/S (RC-CMS / HBS),

7 Thermostatic expansion valves, type Ordering Fixed setting Adjustable setting Range N = 40 F +50 F Refrigerant R22 R410A Rated capacity Q nom 1) Orifice no. R22 and R410A Connection 3 /8 in. x 1 /2 in. x 1 /4 in. ODF Inlet Outlet TR kw Fixed setting Adjustable setting LXXXX 067LXXXX LXXXX 067LXXXX LXXXX 067LXXXX LXXXX 067LXXXX LXXXX 067LXXXX LXXXX 067LXXXX LXXXX 067LXXXX LXXXX 067LXXXX Pressure equalisation = ¼ in. ODF 1 ) The rated capacity is based on: Evaporating temperature, t e = 5 C Liquid temperature, t l = 28 C Condensing temperature, t c = 32 C Opening superheat, OS = 4K Check valve capacity Mass flow lb/h Fig. 8 p (psi) Internal check valve for orifice bypass in reverse flow (flow rate as a function of pressure differential) Danfoss A/S (RC-CMS / HBS), RD1BA122 7

8 Thermostatic expansion valves, type Capacity Capacity in TR for range N = F and opening superheat OS = 7.2 F R22 Type Orifice no. Pressure drop across valve delta psi Pressure drop across valve delta psi Evaporating temperature 50 F Evaporating temperature 40 F Evaporating temperature 20 F Evaporating temperature 0 F Evaporating temperature 20 F Evaporating temperature 40 F Capacity in TR for range N = F and opening superheat OS = 7.2 F R410A Type Orifice no. Pressure drop across valve psi Pressure drop across valve psi Evaporating temperature 50 F Evaporating temperature 40 F Evaporating temperature 20 F Evaporating temperature 0 F Evaporating temperature 20 F Evaporating temperature 40 F Correction for subcooling t sub The evaporator capacity used must be corrected if subcooling deviates from 7.2 F. The corrected capacity can be obtained by dividing the evaporator capacity by the correction factor given below. Note: Insufficient subcooling can produce flash gas. Correction factor for subcooling t sub Correction factor 4K 10K 15K 20K 25K 30K 35K 40K 7.2 F 18 F 27 F 36 F 45 F 55 F 63 F 72 F R R410A t sub 8 RD1BA122 Danfoss A/S (RC-CMS / HBS),

9 Thermostatic expansion valves, type Sizing p e ~t e EVR/EVRH Q e SGI/SGN/SGH DCL/DML Fig. 9 Example: Refrigerant R22 Evaporating temperature t e = 40 F P e = 79 psi Condensing temperature t c = 118 F P c = 256 psi Pressure drop in liquid line, drier and distributor system p = 27 psi The corrected evaporator capacity then becomes 4:0/1.06 = 3.77 TR As the selected valve must be equal to or slightly larger than the corrected evaporator capacity of 3.77 TR, the with orifice 5 having a table capacity of 4.1 TR would be a suitable choice. Pressure drop in valve p = = 150 psi Subcooling t sub = 18 F Evaporator capacity = 4.0 TR Correction factor from table = 1.06 Capacity in TR for range N = F and opening superheat OS = 7.2 F R22 Type Orifice no. Pressure drop across valve delta psi Pressure drop across valve delta psi Evaporating temperature 50 F Evaporating temperature 40 F Danfoss A/S (RC-CMS / HBS), RD1BA122 9

10 Thermostatic expansion valves, type Dimensions and weights Fixed setting Fig. 10 Weight 0.57 lbs Adjustable setting Fig. 11 Weight 0.67 lbs 10 RD1BA122 Danfoss A/S (RC-CMS / HBS),

11 Thermostatic expansion valves, type Danfoss A/S (RC-CMS / HBS), RD1BA122 11

12 Thermostatic expansion valves, type 12 RD1BA122 Danfoss A/S (RC-CMS / HBS),

D A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction

D A T A S H E E T. TX6 Thermo Expansion Valves. Alco Controls TX6. Features. Introduction. Construction ALCO s series of Thermo -Expansion Valves are designed for air conditioning, chillers, rooftops, close control, A/C transportation, heat pumps, industrial cooling process and refrigeration applications.

More information

D A T A S H E E T. TX3 Thermo Expansion Valves. Alco Controls TX3. Features. Introduction. Description of bulb charges

D A T A S H E E T. TX3 Thermo Expansion Valves. Alco Controls TX3. Features. Introduction. Description of bulb charges ALCO s TX3 series of Thermo -Expansion Valves are designed for air conditioning, heat pumps and commercial refrigeration applications. The TX3 is ideal for those applications requiring hermetic / compact

More information

Solenoid valves Type EVU

Solenoid valves Type EVU Data sheet Solenoid valves EVU EVU solenoid valves are designed to fit into compact refrigeration systems. Available in direct and pilot operated versions, they can be applied in liquid, suction, and hot

More information

NOTE: If the HF body is stamped HFK, then the cage is replaceable. HF N E S C B 2 H C 5 FT 3/8 x 1/2 ODF S/T Valve Series

NOTE: If the HF body is stamped HFK, then the cage is replaceable. HF N E S C B 2 H C 5 FT 3/8 x 1/2 ODF S/T Valve Series The HF series is a balanced ported valve designed for refrigeration, air conditioning and heat pump applications. Features Stainless steel replaceable power element eliminates corrosion and prevents valve

More information

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls

Geothermal Alliance of Illinois. TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls Geothermal Alliance of Illinois TXVs Theory and Fundamentals John Haug Senior Application Engineer Emerson Climate Technologies - Flow Controls Thermal Expansion Valve Topics Anatomy Operation Terms &

More information

Refrigeration Basics 101. By: Eric Nelson

Refrigeration Basics 101. By: Eric Nelson Refrigeration Basics 101 By: Eric Nelson Basics Refrigeration is the removal of heat from a material or space, so that it s temperature is lower than that of it s surroundings. When refrigerant absorbs

More information

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014

ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 ASHRAE Boston Chapter Meeting Designing AC Refrigeration Systems Lessons Learned February 11, 2014 Explanation of the refrigeration cycle. Compressors. Benefits and operating characteristics. -Reciprocating

More information

Application Feature Valve Nominal Liquid Capacity R-22 (in tons)*

Application Feature Valve Nominal Liquid Capacity R-22 (in tons)* EMERSON CLIMATE TECHNOLOGIES-Solenoid Valves & Coils Quick Select Guide Applications Application Feature Valve Nominal Liquid Capacity R-22 (in tons)* Nominal Liquid Capacity R-410A (in tons)* Liquid Line

More information

POLICY BULLETIN Tecumseh Compressor Company Compressor Group

POLICY BULLETIN Tecumseh Compressor Company Compressor Group to Bulk Milk Coolers and Other System Page 1 of 5 Overall reliability can be enhanced if there exists a complete understanding of the features, system design, installation requirements, processing, charging

More information

MAKING MODERN LIVING POSSIBLE. Thermostatic valve AVTA. Technical brochure

MAKING MODERN LIVING POSSIBLE. Thermostatic valve AVTA. Technical brochure MAKING MODERN LIVING POSSIBLE Thermostatic valve AVTA Technical brochure 2 IC.PD.500.A3.02-520B3728 Danfoss A/S 07-2009/ RA-MC/mr Contents Page Features............................................................................................4

More information

DESIGN STANDARDS SECTION 23 60 00

DESIGN STANDARDS SECTION 23 60 00 PART 1 - GENERAL 1.01 Work included: A. Piping, tubing and fittings. B. Piping specialties. C. Special duty valves. D. Refrigerants. E. Chillers. F. Refrigerant monitors. 1.02 General requirements: A.

More information

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents.

It will be available soon as an 8.5 X 11 paperback. For easier navigation through the e book, use the table of contents. The System Evaluation Manual and Chiller Evaluation Manual have been revised and combined into this new book; the Air Conditioning and Refrigeration System Evaluation Guide. It will be available soon as

More information

Alco Controls. Electronic Control. Conventional Control. Page. Electrical Control Valves 5. Electronic Controllers and Sensors 31

Alco Controls. Electronic Control. Conventional Control. Page. Electrical Control Valves 5. Electronic Controllers and Sensors 31 Electrical Control Valves Electronic Controllers and Sensors Thermo -Expansion Valves Solenoid Valves Mechanical Pressure Regulators Pressure Controls and Thermostats System Protectors and Moisture Indicators

More information

VALVES FOR REFRIGERATING SYSTEMS

VALVES FOR REFRIGERATING SYSTEMS VALVES FOR REFRIGERATING SYSTEMS FROM QUALITY OUR NATURAL DEVELOPMENT Achieved the goal of fi fty years working in the industry of Refrigeration and Air Conditioning, Castel Quality Range of Products is

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

Thermostatic valve Type AVTA

Thermostatic valve Type AVTA MAKING MODERN LIVING POSSIBLE Data sheet Thermostatic valve Type AVTA Thermostatic valves are used for proportional regulation of flow quantity, depending on the setting and the sensor temperature. The

More information

Why and How we Use Capacity Control

Why and How we Use Capacity Control Why and How we Use Capacity Control On refrigeration and air conditioning applications where the load may vary over a wide range, due to lighting, occupancy, product loading, ambient weather variations,

More information

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A

M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A Bulletin 20-20.2 / July 2012 M SERIES REFRIGERANT COIL MODULE REFRIGERANT COILS for R-22, R-407C, R-410A ➀ ➁ ➂ Model Number Key M 2430 C L 1 - A - ➀ Unit Type M=Modular Nominal Capacity 2430=24000 to 30000

More information

Characteristics of Evaporators

Characteristics of Evaporators Characteristics of Evaporators Roger D. Holder, CM, MSME 10-28-2003 Heat or Energy In this paper, we will discuss the characteristics of an evaporator coil. The variance of the operational condenses of

More information

Air Conditioning & Refrigeration Master Catalog. Catalog CIC-2003-1/USA April 2003

Air Conditioning & Refrigeration Master Catalog. Catalog CIC-2003-1/USA April 2003 Air Conditioning & Refrigeration Master Catalog Catalog CIC-2003-1/USA April 2003 Table of Contents Table of Contents Service Valves Frontseating Valves... page 115 RB01 Series Ball Valves... page 117

More information

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX

INSTALLATION INSTRUCTIONS Fan Coil Replacement Coil Kit EBX & EBXX Fan Coil Replacement Coil Kit EBX & EBXX These instructions must be read and understood completely before attempting installation. These instructions covers the installation of replacement coil kit into

More information

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air

technical data air conditioning systems RXS20-25-35E (single phase) FBQ-B8V1-B8V3B Split Heat Pump Condensing Units Split Sky Air technical data RXS20-25-35E FBQ-B8V-B8V3B (single phase) Split Heat Pump Condensing Units air conditioning systems Split Sky Air Outdoor Units R-40A RXS-E2VB Split Sky Air Outdoor Units Features O u t

More information

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling

Water Fired Chiller/Chiller-Heater. WFC-S Series: 10, 20 and 30 RT Cooling Water Fired Chiller/Chiller-Heater WFC-S Series: 1, 2 and 3 RT Cooling W E A R E F R I E N D L Y T O T H E E A R T H Water Fired SINGLE-EFFECT Chiller or Chiller-Heater Absorption Principle Cooling Cycle

More information

ice 3 FLUID TO FLUID HEAT PUMP

ice 3 FLUID TO FLUID HEAT PUMP ice 3 FLUID TO FLUID HEAT PUMP SUBMITTAL DATA (888) 530-7713 P O Box 5, Wentworth, H 03282 Rev.3 (5-30-14) ice 3, IC-2040 Fluid-to-Fluid R-410a Heat Pump Engineering Guide Specifications General otes:

More information

Data sheet Radiator Thermostats type RA 2000 Valve bodies type RA-FN and RA-G

Data sheet Radiator Thermostats type RA 2000 Valve bodies type RA-FN and RA-G Data sheet Radiator Thermostats type RA 2000 Valve bodies type RA-FN and RA-G EN 215-1 HD 1215-2 Application RA 2910 built-in sensor RA 2920 tamperproof RA 5062 remote sensor temperature adjuster RA-FN

More information

MAC-120HE-01 Air-Cooled Chiller

MAC-120HE-01 Air-Cooled Chiller MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01

More information

Solenoid valves 2/2-way direct-operated Type EV210A

Solenoid valves 2/2-way direct-operated Type EV210A Solenoid valves 2/2-way direct-operated Type EV210A Features EV210A NC and NO Very compact valves for industrial application, such as control and dosage For water, oil, compressed air and similar neutral

More information

Automatic Bypass Control AVDO

Automatic Bypass Control AVDO Application AVDO is a self-acting constant flow control primarily used either to maintain minimum flow rates through e.g. a low-capacity gas boiler or to control the differential pressure in a central

More information

Accumulators and Receivers

Accumulators and Receivers aerospace climate control electromechanical filtration fluid & gas handling hydraulics pneumatics process control sealing & shielding Accumulators and Receivers Catalog C-1, October 2007 Page 2 / Catalog

More information

COIL INPUT SCREENS. ITEM NUMBER: Always use a 1 through? In this field you might also use a dash and place quantity of coils here.

COIL INPUT SCREENS. ITEM NUMBER: Always use a 1 through? In this field you might also use a dash and place quantity of coils here. COIL INPUT SCREENS Example of a Water Coil Input Screen: (*please see the appendix for an example of an Evaporator, Steam or Condenser Coil input screen) PHYSICAL DATA ITEM NUMBER: Always use a 1 through?

More information

Water valves REFRIGERATION AND AIR CONDITIONING. Fitters notes

Water valves REFRIGERATION AND AIR CONDITIONING. Fitters notes REFRIGERATION AND AIR CONDITIONING Fitters notes Contents Page Application...3 Identification...3 Installation...5 Setting...6 Maintenance...6 Spare parts...8 Fault location...9 2 RZ4DA202 DKRCC.PF.D00.A1.02

More information

Thermostatic actuator RAVV - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16)

Thermostatic actuator RAVV - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16) - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16) Description RAVV can be combined with 2-way valves RAV- /8, VMT-/8 or VMA 15. Controller closes on rising temperature. There is a special

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It.

Any Service Technician Can Fix It A Good Service Technician Can Figure Out What s Wrong With It. I Dave s Statement If the thermostat calls for cooling, and the furnace fan is running properly, and the coil airflow is adequate, and the condenser fan is running properly, and the condenser airflow is

More information

Produktguide 2004 Kyl- och värmepumpsprodukter

Produktguide 2004 Kyl- och värmepumpsprodukter Produktguide 2004 Kyl- och värmepumpsprodukter Subject to change without notice EN3H-0307GE23 R203 - Empty page in PDF - 2 Subject to change without notice EN3H-0307GE23 R203 Contents Overview Designation

More information

Thermostatic element RAVV for 2-way valves

Thermostatic element RAVV for 2-way valves Description / Application RAVV is a self-acting thermostatic element which can be combined with 2-way valve bodies RAV-/8, VMT-/8 or VMA 15. RAVV is used to control temperatures in small hot water cylinders

More information

How To Design A Refrigeration System

How To Design A Refrigeration System AIRAH Refrigeration (in HVAC) Back to Basics For the First Time Terms of Reference What this session is NOT about Detailed Refrigeration Design Detailed analysis of various Refrigants properties Comparison

More information

Waste Heat Recovery through Air Conditioning System

Waste Heat Recovery through Air Conditioning System International Journal of Engineering Research and Development e-issn: 2278-067X, p-issn : 2278-800X, www.ijerd.com Volume 5, Issue 3 (December 2012), PP. 87-92 Waste Heat Recovery through Air Conditioning

More information

Evaporator Coil Installation Instructions

Evaporator Coil Installation Instructions Part # 96654008 July 2010 Evaporator Coil Installation Instructions A-Coil Page 4 Multi-position A-Coil Page 4-7 Slab Coil Page 5 Horizontal A-Coil Top Connection Page 5 Horizontal A-Coil Side Connection

More information

Air Conditioners Technical Data

Air Conditioners Technical Data Air Conditioners Technical Data O u t d o o r U n i t E E D E N 2-0 0 RX-JV Outdoor Unit RX-JV TABLE OF CONTENTS RX-JV Features............................................................. 2 2 Specifications.......................................................

More information

Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03

Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03 Aluminum Cased Cooling Coils 2-5 Ton 4CXC PUB. NO. 22-1839-03 Aluminum Cooling Coil Nomenclature 4 C X C B 0 3 6 C C 3 C U A A Refrigerant Type 4 - R410A Product Family T-Premium (Heat Pump or Convertible

More information

Automation of Commercial Refrigeration Plant

Automation of Commercial Refrigeration Plant Automation of Commercial Refrigeration Plant REFRIGERATION AND AIR CONDITIONING Automation of commercial Refrigeration Plant The purpose of this manual is to show some examples of the use of Danfoss automatic

More information

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty

Indoor coil is too warm in cooling mode or too cold in heating mode. Reversing valve or coil thermistor is faulty Codes Room Air Conditioner range: Indoor unit alarm s If timer lamp flashes for 1 second on, 1 second off, this indicates pre heating on the coil during heating mode and is not an error. If timer lamp

More information

AIR-COOLED CHILLERS APPLIED SYSTEMS. www.daikin.eu EUWA*5-24KAZW - EUWY*5-24KAZW -

AIR-COOLED CHILLERS APPLIED SYSTEMS. www.daikin.eu EUWA*5-24KAZW - EUWY*5-24KAZW - AIR-COOLED CHILLERS APPLIED SYSTEMS www.daikin.eu Cooling Only Heat pump EUWA*5-24KAZW - EUWY*5-24KAZW - Environmental Awareness Daikin and the Environment In recent years, motivated by a global awareness

More information

ECOCIAT. Domestic hot water heat recovery unit

ECOCIAT. Domestic hot water heat recovery unit Heat recovery unit Domestic hot water High energy efficiency with R410A Compact and quiet Scroll compressors Brazed-plate heat exchangers Heating Heat recovery ENVIRONMENTALLY HFC R410A PROTECTION DE FRIENDLY

More information

Thermostatic actuator RAVK - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16) - for 3-way valves KOVM (PN 10), VMV (PN 16)

Thermostatic actuator RAVK - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16) - for 3-way valves KOVM (PN 10), VMV (PN 16) - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16) - for 3-way valves KOVM (PN 10), VMV (PN 16) Description RAVK can be combined with: - 2-way valves RAV-/8, VMT-/8, VMA, or - 3-way valves

More information

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS

SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences

More information

Thermostatic actuator RAVK - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16) - for 3-way valves KOVM (PN 10), VMV (PN 16)

Thermostatic actuator RAVK - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16) - for 3-way valves KOVM (PN 10), VMV (PN 16) - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16) - for 3-way valves KOVM (PN 10), VMV (PN 16) Description RAVK can be combined with: - 2-way valves RAV-/8, VMT-/8, VMA, or - 3-way valves

More information

Quick Select Guide 2013 Automatic controls, compressors and condensing units for HVAC/R wholesalers, contractors and installers

Quick Select Guide 2013 Automatic controls, compressors and condensing units for HVAC/R wholesalers, contractors and installers MAKING MODERN LIVING POSSIBLE Quick Select Guide 2013 Automatic controls, compressors and condensing units for HVAC/R wholesalers, contractors and installers 17 products in one quick select guide The most

More information

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME

Troubleshooting an Air Conditioning system. R D Holder Eng. Roger D Holder MSME Troubleshooting an Air Conditioning system R D Holder Eng. Roger D Holder MSME Troubleshooting of an air conditioning system is a step by step procedure. I have found that a 4 step procedure is the best

More information

Contents and Nomenclature

Contents and Nomenclature DX Coils Contents and Nomenclature Nomenclature... 1 Evaporator Coil Types EN... 2 EF... 2 ER... 2 EJ... 3 EK... 3 Evaporator Construction Connections... 4 Tubing... 4 Headers... 5 Tube Supports... 5 Coil

More information

Thermostatic actuator RAVI - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16) - for 3-way valves KOVM (PN 10), VMV (PN 16)

Thermostatic actuator RAVI - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16) - for 3-way valves KOVM (PN 10), VMV (PN 16) - for 2-way valves RAV-/8 (PN 10), VMT-/8 (PN 10), VMA (PN 16) - for 3-way valves KOVM (PN 10), VMV (PN 16) Description RAVI is self-acting thermostatic actuator primarily for use for temperature control

More information

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL

INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL INSTALLATION INSTRUCTIONS HOT GAS BYPASS SYSTEM DESIGN MANUAL MODELS: WA/WL44H WA/WLH WA/WL70*H NOTE: Electrical data presented in this manual supersedes any other data f the above listed models. Bard

More information

DESCRIPTION FEATURES HORIZONTAL DUCT HD. ISO 9001 Certified Quality Management System

DESCRIPTION FEATURES HORIZONTAL DUCT HD. ISO 9001 Certified Quality Management System TECHNICAL GUIDE ADD - ON COILS FOR USE WITH SPLIT-SYSTEM COOLING & HEAT PUMPS MODELS: MC, PC, FC, HD, UC 600-2000 CFM 1.5-5 TON COILS UPFLOW/DOWNFLOW FULL CASED FC UPFLOW PARTIAL CASED PC UPFLOW UNCASED

More information

Transcritical CO2 booster system How to control the system

Transcritical CO2 booster system How to control the system Application guide Transcritical CO2 booster system How to control the system EKC 326A 21 ICMTS CCM AK-SC 255/ AK-SM 350/ AK-SM 720/ AKA 245 DCR 32R AKD 102 Danfoss R64-2047.10 www.danfoss.com/co2 General

More information

Data sheet ECC 12 and 22

Data sheet ECC 12 and 22 Application ECC is an electronic room temperature controller for water-based systems. ECC can control - fan-coil units - inductions units - air conditioning systems - small ventilating systems - 2-pipe

More information

IV. Rear Mount System

IV. Rear Mount System Mobile Climate Control 45 MCC Reference Manual 2014 PN: 89-3069 Rearmount Air Conditioning System Eco RM Capacity, Reliability, and Serviceability MCC Eco RM unit, selected as preferred equipment by leading

More information

CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION

CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION Technology Fact Sheet CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION Buildings for the 21st Century Buildings that are more energy-efficient, comfortable, and affordable that s the goal of DOE s Office

More information

Optimized Thermal Expansion Valves for R-410A Systems. January 2008

Optimized Thermal Expansion Valves for R-410A Systems. January 2008 Optimized Thermal Expansion Valves for R-410A Systems January 2008 Overview Introduction By 2010, the United States must phase out ozone-depleting refrigerants and transition to hydrofluorocarbon (HFC)

More information

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE

INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE INNOVATIVE SOLUTION OF DOMESTIC HEATING SPLIT TYPE SPLIT DHW INTEGRATED TYPE MONOBLOC TYPE Fujitsu General realizes considerable energy saving operations by the Heat pump heating system using the ambient

More information

Get the FACTS about SEER and Deliver Better Customer Value

Get the FACTS about SEER and Deliver Better Customer Value What is SEER? SEER stands for Seasonal Energy Efficiency Ratio. It s a number that describes how well air-conditioning equipment works. A higher SEER means better efficiency and lower energy bills. SEER

More information

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur

Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Refrigeration and Airconditioning Prof. M. Ramgopal Department of Mechanical Engineering Indian Institute of Technology, Kharagpur Lecture No. # 22 Refrigeration System Components: Compressor (Continued)

More information

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS

SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS SERVICE GUIDELINES HCFC R22 TO HFC REFRIGERANT BLENDS 2009 Tecumseh Products Company. All rights reserved. Page 1 of 8 Refrigerant R22 is widely used for residential and commercial air conditioning, as

More information

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system.

ROOFTOP - HEAT PUMP UNIT. This document applies when installing into an air handler or as part of an air handling system. ROOFTOP - HEAT PUMP UNIT Technical data Applies to Model YNRA R410A This document applies when installing into an air handler or as part of an air handling system. CONTENTS 1. General description... 2

More information

CALEFFI. Compact automatic flow rate regulator with polymer cartridge. 127 series 01166/09 GB

CALEFFI. Compact automatic flow rate regulator with polymer cartridge. 127 series 01166/09 GB Compact automatic flow rate regulator with polymer cartridge 127 series REGISTERED BS EN ISO 9001:2000 Cert. n FM 21654 UNI EN ISO 9001:2000 Cert. n 0003 CALEFFI 01166/09 GB Function The AUTOFLOW devices

More information

Thermostatic Sensor RAS-C² with RA-FN Radiator Valve (Fixed Capacity)

Thermostatic Sensor RAS-C² with RA-FN Radiator Valve (Fixed Capacity) Data Sheet Thermostatic Sensor RAS-C² with RA-FN Radiator Valve (Fixed Capacity) Application RAS-C² thermostatic sensor RA-FN angle valve The RAS-C² thermostatic sensor is a selfactuating proportional

More information

COMPRESSOR REPLACEMENT PROCEDURE

COMPRESSOR REPLACEMENT PROCEDURE COMPRESSOR REPLACEMENT PROCEDURE Bard Manufacturing Company Bryan, Ohio 43506 Since 1914...Moving ahead just as planned Manual No.: 2100-003E Supersedes 2100-003D File: Volume I, Tab 1 Date: 06-25-02 Copyright

More information

System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING. Fitters notes

System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING. Fitters notes System Trouble Shooting Fault Location REFRIGERATION AND AIR CONDITIONING Fitters notes Contents Page Faults on refrigeration systems, general...3 Fault location without the use of instruments...3 Categorisation...3

More information

How Ground/Water Source Heat Pumps Work

How Ground/Water Source Heat Pumps Work How Ground/Water Source s Work Steve Kavanaugh, Professor Emeritus of Mechanical Engineering, University of Alabama Ground Source s (a.k.a. Geothermal s) are becoming more common as the costs of energy

More information

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2010 Impacts of Refrigerant Charge on Air Conditioner and Heat Pump Performance

More information

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water

VertiCool Space Saver 2 to 15 tons Water-Cooled and Chilled Water 2 to 15 tons Water-Cooled and Chilled Water Unique Solutions for Challenging HVAC Projects Your Choice for Limited Space Applications Water-Cooled Chilled Water The VertiCool Space Saver allows installation

More information

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29

Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29 Ground-breaking conversion of critical Data Room WaterChiller from R22 to R422D / MO29 A refrigerant retrofit project, involving the conversion of a large Data Room cooling system from R22 to R422D (DuPont

More information

Development and testing of a multi-type air conditioner without using AC inverters

Development and testing of a multi-type air conditioner without using AC inverters Energy Conversion and Management 46 (2005) 373 383 www.elsevier.com/locate/enconman Development and testing of a multi-type air conditioner without using AC inverters Shih-Cheng Hu *, Rong-Hwa Yang Department

More information

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75

Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Specifications COOLING ONLY / HEAT PUMP 005 006 007 Capacity (Eurovent) Cooling kw 5.2 6.0 7.1 Heating kw 5.65 6.35 7.75 Nominal input (Eurovent) Cooling kw 1.89 2.35 2.95 Heating kw 1.97 2.24 2.83 EER

More information

ARMSTRONG AIR HEAT PUMPS www.armstrongair.com

ARMSTRONG AIR HEAT PUMPS www.armstrongair.com INDEX ELECTRIC FURNACE MODULAR AIR SYSTEM EFC/EFV... 5-10 electric Heat Kits... 5-11 evaporator coils EC1P / EM1P UPFLOW / COUNTERFLOW APPLICATIONS and upflow / horizontal applications (CASED)... 5-6 5-7

More information

2016 HVAC Test and Repair Application Specifications

2016 HVAC Test and Repair Application Specifications 2016 HVAC Test and Repair Application Specifications HVAC Testing and Repair Measure: Performed on (2 ton and up) existing (DX) packaged or split systems - retrofit There are three separate incentive categories

More information

Integrated Presetting Valves - for Normal Volume Flows RA-N and for Small Volume Flows RA-U

Integrated Presetting Valves - for Normal Volume Flows RA-N and for Small Volume Flows RA-U Integrated Presetting Valves - for Normal Volume Flows RA-N and for Small Volume Flows Application Integrated valves, type RA-N (013G1382) and RA- U (013G1383), with built-in presetting are designed for

More information

Integrated Presetting Valves for Normal 013G0372 and Small 013G0373 Volume Flows

Integrated Presetting Valves for Normal 013G0372 and Small 013G0373 Volume Flows Integrated Presetting Valves for Normal 013G0372 and Small 013G0373 Volume Flows Application Integrated valves, type RA-N (013G0372) and RA- U (013G0373), with built-in presetting are designed for incorporation

More information

Technical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1

Technical Training Associates Presents. Commercial Refrigeration Equipment Servicing Part 1 Technical Training Associates Presents Commercial Refrigeration Equipment Servicing Part 1 By Jim Johnson A Practical Approach To The Fundamentals Of Walk-Ins, Reach-In and, Display Cases: Restaurant,

More information

HVAC Systems: Overview

HVAC Systems: Overview HVAC Systems: Overview Michael J. Brandemuehl, Ph.D, P.E. University of Colorado Boulder, CO, USA Overview System Description Secondary HVAC Systems Air distribution Room diffusers and air terminals Duct

More information

Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors

Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors Saving energy by solar collector and heat pump combination in hot water production in residential and hotel sectors Dr. Nguyen Nguyen An, HUST CONTENTS Energy consumption to produce hot water in residential

More information

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers

COMMERCIAL HVAC CHILLER EQUIPMENT. Air-Cooled Chillers COMMERCIAL HVAC CHILLER EQUIPMENT Air-Cooled Chillers Technical Development Programs (TDP) are modules of technical training on HVAC theory, system design, equipment selection and application topics. They

More information

Solenoid Valves and Their Importance in Refrigeration Systems. October 2007

Solenoid Valves and Their Importance in Refrigeration Systems. October 2007 Solenoid Valves and Their Importance in Refrigeration Systems October 2007 Overview Introduction Solenoid valves play an important role within refrigeration and air conditioning systems, controlling the

More information

HVAC-02, Air Conditioning Troubleshooting and Repair

HVAC-02, Air Conditioning Troubleshooting and Repair HVAC-02, Air Conditioning Troubleshooting and Introduction Since I'm constantly receiving questions on 944 air conditioning systems, I figured it's time to come up with come helpful troubleshooting tips.

More information

marine/bespoke split applications

marine/bespoke split applications split applications marine/bespoke evaporators, condensers and split air conditioning systems suitable for a multitude of applications such as coastal, extreme high and low ambients, harsh dusty environments

More information

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH)

TEST REPORT #44. System Drop-in Tests of Refrigerant R-32 in Single Packaged Vertical Heat Pump (SPVH) Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #44 System Drop-in Tests of Refrigerant R-32 in Single Packaged

More information

Assisted lift operated 2/2-way solenoid valves Type EV250B

Assisted lift operated 2/2-way solenoid valves Type EV250B MAKING MODERN LIVING POSSIBLE Data sheet Assisted lift operated 2/2-way solenoid valves Type EV250B EV250B with assisted lift can operate from zero and up to 10 bar differential pressure. This 2/2-way

More information

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description

DERON Air/Water Swimming pool Heat Pump. CY/DY series for Heating/Cooling. Description Description Compact air/water heat pump for outside installation. With suction gas cooled rotary compressor. With extensive aluminium/cu lamellar tube evaporator and PVC Titanium condenser. Axial fan Refrigerant

More information

Installation Instructions

Installation Instructions CNPVU CNRVU Uncased Coils Upflow - Downflow Heating - Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...

More information

Evaporator Coil. Installation Instructions GENERAL

Evaporator Coil. Installation Instructions GENERAL IM-HAC-0966540-12 December 2013 Evaporator Coil Installation Instructions TABLE OF CONTENTS PAGE General... 1 Vertical... 2 Horizontal... 2 Multi-Position... 3-5 Metering Device... 6 Condensate Drain...

More information

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa

OPTIMIZING CONDENSER WATER FLOW RATES. W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa OPTIMIZING CONDENSER WATER FLOW RATES W. A. Liegois, P.E. Stanley Consultants, Inc. Muscatine, Iowa T.A. Brown, P.E. Thermal Energy Corporation Houston, Texas ABSTRACT Most chillers are designed for a

More information

1. RANGE OF APPLICATION 3. SAFETY INSTRUCTIONS 4 4. DESIGN 4

1. RANGE OF APPLICATION 3. SAFETY INSTRUCTIONS 4 4. DESIGN 4 Henco Snelselectie kaart EN IMPORTANT! Before starting work the fitter must carefully read this installation and operation manual, understand and observe its conditions. The water floor heating control

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems

1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems 1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system

More information

DOUBLE SEAT BRONZE BODY HIGH CAPACITY

DOUBLE SEAT BRONZE BODY HIGH CAPACITY PS593DB HEAVY DUTY BRONZE GLOBE CONTROL VALVES DB DOUBLE SEAT BRONZE BODY HIGH CAPACITY 1, 1-1/4, 1-1/2, and 2 Union Ends ANSI Class 250 Body Rating ANSI Class II Close off Bronze or Stainless Steel Trim

More information

Defining Quality. Building Comfort. Heating and Cooling Coils

Defining Quality. Building Comfort. Heating and Cooling Coils Defining Quality. Building Comfort. Heating and Cooling Coils Heating and Cooling Coils Heating and Cooling Coils For over 20 years, AAON has supplied the coil needs of industrial and commercial HVAC customers.

More information

Self-operated Temperature Regulators Type 1 to Type 9. PN 16 to 40 Class 125 to 300 DN 15 to 250 NPS ½ to 10 G ½ to 1 Up to 350 C Up to 660 F

Self-operated Temperature Regulators Type 1 to Type 9. PN 16 to 40 Class 125 to 300 DN 15 to 250 NPS ½ to 10 G ½ to 1 Up to 350 C Up to 660 F Self-operated Temperature Regulators Type 1 to Type 9 PN 16 to 40 Class 125 to 300 DN 15 to 250 NPS ½ to 10 G ½ to 1 Up to 350 C Up to 660 F Edition April 2012 Information Sheet T 2010 EN Self-operated

More information

V47 Series Temperature Actuated Modulating Water Valves

V47 Series Temperature Actuated Modulating Water Valves V47 Series Temperature Actuated Modulating Water Valves Master Catalog 125 Valves, Miscellaneous (Other Than Gas) Section V Product Bulletin V47 Issue Date 0286 Application The V47 modulating valves regulate

More information

TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System

TEST REPORT #31. System Drop-in Test of Refrigerant R-32 in Split Air-conditioning System Air-Conditioning, Heating, and Refrigeration Institute (AHRI) Low-GWP Alternative Refrigerants Evaluation Program (Low-GWP AREP) TEST REPORT #31 System Drop-in Test of Refrigerant R-32 in Split Air-conditioning

More information

FORMATION DAMAGE AND WELL TREATMENT SYSTEM

FORMATION DAMAGE AND WELL TREATMENT SYSTEM FORMATION DAMAGE AND WELL TREATMENT SYSTEM FDWTS-10K Includes ability to test Liquid Permeability & Gas Permeability Fines migration & critical velocity Static Filtration Drilling mud invasion evaluation

More information