ULC Design No. R806 August 01, 2005 Unrestrained Assembly Rating - 1 h

Similar documents
Design No. P736 September 26, Restrained Assembly Ratings 1, 1-1/2 or 2 Hr. (See Items 3, 7 and 8A)

UL Online Certifications Directory

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

CHAPTER 7: Building Systems ROOFING SYSTEMS

AUTHORIZATION TO MARK

Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.

RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000

APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE

STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES

PRODUCT CONTROL SECTION

ROOF CONSTRUCTION SCIENCE (METCT092)

COMMERCIAL BUILDING APPLICATIONS

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS

Laboratory Report P Simulated Wind Uplift Testing of Adhered Single-Ply Roofing Systems in accordance with FM Standard 4470, Appendix C

HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS

CHESTERFLEX ROOF WATERPROOFING MEMBRANES

1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.

Smooth cap sheet SQ $ Smooth cap sheet SQ $ Smooth cap sheet SQ $ Smooth cap sheet SQ $ 36.

FAST FACTS ADVANTAGES OF MULTI PLY BUILT-UP ROOFING. Asphalt Roofing Manufacturers Association

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.

Asphalt Shingle Application Requirements

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs

Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5

Durapax Coal Tar BUR Application Guide

Best Practices in Roof Design: Sustainable Energy Efficient Reroofing

R-Value and Densities Chart

CHICAGO ROOFING CONTRACTORS ASSOCIATION

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

Roofing Systems. New Applications / Re-Roofing / Maintenance

Please read the entire document before purchasing and installing any of these products

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: SHOP APPLIED WOOD COATINGS SECTION: SHEATHING REPORT HOLDER:

Fire Protection. CANADIAN STEEL CONSTRUCTION COUNCIL 201 Consumers Road, Suite 300 Willowdale, Ontario, M2J 4G8. Floor Assembly No.

COMPARATIVE PERFORMANCE OF EPDM RUBBER ROOFING MEMBRANE AS PROTECTION AGAINST HAIL DAMAGE

Final inspections are completed by site visit only. Access to fenced yards shall be planned.

COMMERCIAL ROOFING. Learning Objectives. Commercial Roofing Fundamentals May 2, 2012

ICC-ES Evaluation Report. ESR-3493 Reissued September 2014 This report is subject to renewal September 2015.

Asphalt-Applied and Cold Application Built-Up Roofing Application Guide

LEGACY REPORT. (800) (562) A Subsidiary of the International Code Council RETAINED ON U.S.

Sika Membran System For Sealing and Waterproofing Construction Gaps in Building Façades

The existing roof angle change terminations and flashings when sound and intact can be reused.

Firestone Modified Bitumen Roofing Systems DURABLE. RELIABLE. SUSTAINABLE

Section 2.3. Flat Roofs. Warm deck single ply membrane. Warm deck single ply membrane. Warm deck built-up felt/ mastic asphalt. Protected membrane

Clark roofing

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

HOT ASPHALT BUILT-UP ROOFING SYSTEMS MORE LAYERS MEANS MORE PROTECTION

TARRANT COUNTY DETAIL STANDARDS

Low-slope reroofing guidelines

CertainTeed. Self-Adhering Roof Systems for Low Slope Residential Roofs

Building Owners Guide to a Duro-Last System!

Regulations Detail Sheet 1

INSTALLATION INSPECTION GUIDE FOR 3RD PARTY INSPECTORS FOR PAREX USA EXTERIOR INSULATION AND FINISH SYSTEMS

CRS Sales & Marketing

The Kingspan Insulation Price List 1 st January 2013

Renovating Your Basement

BITUMEN-POLYMER WATERPROOFING MEMBRANE, MADE FROM SELECT APP AND DISTILLED BITUMEN, REINFORCED WITH SPUNBOND POLYESTER FABRIC.

Solicitation DTFACN-11-R Attachment #9

ROOF ASSEMBLIES CHAPTER 9

CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C Date of issue , Updated July 1, 2011

Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology. Modern Efficient Performance Cost Effective Flat Roofing Systems

ITEM THERMOPLASTIC MEMBRANE ROOFING

GENERAL REQUIREMENTS HENRY WARRANTED COMMERCIAL ROOFING SYSTEMS

GYPSUM BOARD AND PLASTER

H-Stud Area Separation Wall System

System 5000 FLAME-FREE, FELT SYSTEM, INSTALLED USING HOT AIR, TOTALLY ELIMINATING FIRE RISK AND PROVIDING A BITUMEN ALTERNATIVE TO SINGLE PLY

Fire Resistance of Brick Masonry

A. Roofing Terminology: Definitions in ASTM D 1079 and glossary in NRCA's "The NRCA Roofing and Waterproofing Manual" apply to work of this Section.

Roof Systems Overview

The better way to build TM. Installation Manual. EXTERIOR WALL SIPs

GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: ICYNENE, INC.

ANSI/SPRI WD-1 Wind Design Standard Practice for Roofing Assemblies. Table of Contents. 1.0 Introduction Methodology...2

Roofing. Sarnafil S EL. Polymeric membrane for roof waterproofing. Product Description

THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150

Firestone RubberGard The EPDM reference

FIRESTONE BUILT-UP ROOFING SYSTEMS APPLICATION GUIDE 3/14/2011

Roof Insulation Building. Energy. Environment friendly e-library

Commercial Roof Systems Selection Guide

Design No. L556. Design No. L556

NEW ELECTRICAL SUBSTATION Building 300 SECTION ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK

2.1 DEFINITION OF INSULATION GENERIC TYPES AND FORMS OF INSULATION PROPERTIES OF INSULATION MAJOR INSULATION MATERIALS 4

Low Energy Low Carbon Buildings

Read and understand all installation instructions and precautions before installing. GENERAL APPLICATION INSTRUCTIONS

03/05/14 REVISOR RSI/JC RD3945

SECTION SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings.

2.18 INTERIOR & EXTERIOR FINISHES VAPOR & AIR BARRIERS

CHAPTER 6 ASPHALT ROLL ROOFING

VA25014B0516 VA CINCINNATI PROJECT NO INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION GYPSUM BOARD

Polymeric membrane for roof waterproofing

Avoiding the Landfill: The Recycling of Vinyl Roof Membranes

FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING

DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION

SPECIFICATIONS FOR BRIDGE CONSTRUCTION SECTION 16 BRIDGE DECK WATERPROOFING General Materials Equipment...

BLACK JACK ALL WEATHER ROOF COATING

Epdm Flat Roofing Systems

SHINGLE APPLICATION GUIDE

UL Online Certifications Directory

CONTENTS. General conditions 2. Material requirements 3. Terms 4. Estimating shingle requirements 4. Roof preparation 6. Shingle application

European Organisation for Technical Approvals

Multi-layer Insulation Blanket for Roofs

Transcription:

ULC Design No. R806 August 01, 2005 Unrestrained Assembly Rating - 1 h ROOF CONSTRUCTION A 1A. (i) Roof Covering - TGFUC (Guide No. 360 O18). Class A, B or C built-up roof covering, consisting only of felt and asphalt in alternate layers, as specified in the General Information Section under TGFUC (Guide No. 360 O18). (ii) Roof Covering - TGFUC (Guide No. 360 O18). Class A built-up roof covering, consisting of Sarnafil G410-1.2 or G441-2.4 roofing membrane, adhered to glass-fibre rigid roof insulation, Item 2A(i), with Sarnacol 2170 adhesive, applied at rate of 2.5 to 10 L/10 m 2. Class C built-up roof covering, consisting of Sarnafil G442-1.2, G410-1.2 or G441-2.4 roofing membrane loosely laid on glass-fibre rigid roof insulation, Item 2A(i), and surfaced with 15 mm to 40 mm diameter commercial grade gravel, washed and well rounded, applied at a rate of not less than 590 kg/10 m 2. As an option, polyester felt weighing 0.3 kg/m 2 (Sarnafelt 400), or 13 mm thick wood fibreboard, 254 kg/m3 density, or 13 mm (minimum) thick exterior grade plywood, sanded one side, may be used between insulation and roofing membrane. When these roofing membranes are used, 1200 mm by 2400 mm by 15.9 mm thick gypsum wallboard, 10.3 kg/m 2 minimum area density, must be applied with adhesive to steel roof deck SARNAFIL LTD Page 1 of 7

(iii) Roof Covering - TGFUC (Guide No. 360 O18). Class A built-up roof covering, consisting of Carlisle Standard EPDM or UltraGuard EPDM roofing membrane loosely laid on glass-fibre rigid roof insulation, Item 2A(i), and surfaced with 20 mm to 40 mm diameter commercial grade gravel, washed and well rounded, applied at a rate of not less than 490 kg/10 m 2. Class A built-up roof covering, consisting of Carlisle FR EPDM or UltraGuard EPDM roofing membrane 1.5 mm thick, adhered to glass-fibre rigid roof insulation, Item 2A(i), with Carlisle 90-8-30A adhesive, applied at a rate of 5.3 L/10 m 2. As an option, 13 mm thick wood fibreboard may be used between insulation and roofing membrane. When these roofing membranes are used, 1200 mm by 2400 mm by 15.9 mm thick gypsum wallboard, 10.3 kg/m 2 minimum area density, must be applied with adhesive to steel roof deck. CARLISLE SYNTEC INCPATED (iv) Roof Covering - TGFUC (Guide No. 360 O18). Class A built-up roof covering, consisting of Firestone Standard or Standard Reinforced Rubbergard EPDM roofing membrane, 1.1 to 1.5 mm thick, loosely laid on rigid roof insulation, Items 2A(i), (ii) and (iv), and surfaced with 25 to 38 mm diameter commercial grade gravel, washed and well rounded, applied at a rate of not less than 490 kg/10 m 2. As an option, 13 mm thick wood fibreboard may be used between insulation and roofing membrane. When these roofing membranes are used, 1200 by 2400 by 15.9 mm thick gypsum wallboard, 10.3 kg/m 2 minimum area density, must be applied with adhesive to steel roof deck. FIRESTONE BUILDING PRODUCTS CO, DIV OF FIRESTONE TIRE & RUBBER CO (v) Roof Covering - TGFUC (Guide No. 360 O18). Class C built-up roof covering consisting of wood fibreboard, base, and cap sheets. One layer of 12.7 mm thick wood fibreboard, 2.6 kg/m 2 minimum area density, back-mopped to glass-fibre or phenolic rigid roof insulation, Items 2A(i) and (iv), with Type 2 or 3 asphalt applied at a maximum rate of 0.67 kg/m 2. One layer of Elastophene sanded or Elastophene PS base sheet adhered to wood fibreboard with either Type 2 or 3 hot-mopped asphalt applied at a maximum rate of 1.05 kg/m 2, or Bakor Vapor-Block Adhesive applied at a maximum rate of 1.0 L/m 2. One layer of Sopralene 180 granules or Sopralene 250 granules cap sheet adhered with either Type 2 or 3 hotmopped asphalt applied at a maximum rate of 1.2 kg/m 2. Alternatively, one layer of Sopralene Flam 180 granules or Sopralene Flam 250 granules cap sheet torched to base sheet. SOPREMA INC (vi) Roof Covering - TGFUC (Guide No. 360 O18). Class A built-up roof covering, consisting of one ply of IKO "Glass Type IV, IKO""Glass Type 6", or "IKO No. 25 Glass Base Sheet", hotmopped with Type 2 or 3 hot-mopping asphalt at a rate of 1.2 kg/m 2 maximum or mechanically fastened with the manufacturer\'s accepted steel plate and screw fasteners to polyisocyanurate, perlite, fibreglass, wood fibre or polystyrene (covered with wood fibre or perlite) insulation. One ply of ""Modiflex MP-180-SS-Base", "Modiflex MP-180-FS-Base", "Modiflex MF-95-SS-Base", "Modiflex MF-95-FS-Base", hot-mopped with Type 2 or 3 hotmopping asphalt at a rate of 1.2 kg/m 2 maximum, or "Torchflex TF-95-FF-Base", "Torchflex TF-95-FF 2.2", "Torchflex TP-180-FF-Base", torched to the base or ply sheet (optional). One ply of "Modiflex MP-180-CAP FR" or "Modiflex MF-95-CAP FR" hot-mopped with Type 2 or 3 hot-mopping asphalt at a rate of 1.2 kg/m 2 maximum or "Torchflex TP-180-CAP FR" or "Torchflex TF-95-CAP FR" torched to the base or ply sheet. Page 2 of 7

Class C built-up roof covering, consisting of a minimum 11 mm wood fiber, or 3.2 mm or 4.5 mm "Protectoboard" or "PERMABOARD" mechanically attached, urethane adhesive adhered, or adhered with Type 2 or 3 hot-mopping asphalt at a rate of 1.2 kg/m 2 maximum (optional) to wood fibreboard, glass fibre, mineral fibre, polyurethane, perlite, polyisocyanurate, phenolic, or resol foam roof insulation. One or more plies IKO "Modiflex MF-95-FS Base", IKO "Modiflex MF-95-SS-Base", IKO "Glass Type IV", IKO "Glass Type 6", or "IKO No. 25 Glass Base Sheet" cold adhesive applied with Karnak 81AF SBS Cold Adhesive, Monsey-Bakor MBA Gold Adhesive, Henry Company #403 Cold-Ap Spray Grade Adhesive, or Henry Company #902 Permanent Bond Adhesive at a full coverage rate of 5.68 L /0.61 m 2 or spot attached at a rate of sixty spots per 9.3 m 2, with spots being 102 mm to 152 mm in diameter, for the first layer and either cold adhesive or heat fused for successive layers. One or more plies of "IKO No. 25 Glass Base Sheet" cold adhesive applied or heat fused (optional). One ply of "Modiflex MP-180-Cap", "Modiflex MP-250- Cap", Modiflex MP-180-Cap FR, "Modiflex MP-180-Cap FR Premium", "Modiflex MF-95- Cap", "Modiflex MF-95-Cap FR", or "Modiflex MF-95-Cap FR Premium", cold adhesive applied or "Torchflex TP-180-Cap", "Torchflex TP-250-Cap", "Torchflex TF-95- Cap", "Torchflex TP-180-Cap FR", "Torchflex TP-180-Cap FR Premium", Torchflex TF-95-Cap FR, or "Torchflex TF-95-Cap FR Premium" heat fused. (vii). Roof Covering - TGFUC (Guide No. 360 O18). Class C built-up roof covering consisting of wood fibreboard, base, and cap sheets. One layer of 12.7 mm thick wood fibreboard, 2.6 kg/m 2 minimum area density, back-mopped to glass-fibre or phenolic rigid roof insulation, Items 2A(i) and (iv) with Type 2 or 3 asphalt applied at a maximum rate of 0.67 kg/m 2. One layer of Ruberoid 20 Smooth SCF base sheet adhered to wood fibreboard with either Type 2 or 3 hot-mopped asphalt applied at a maximum rate of 1.05 kg/m 2, or Bakor Vapor-Block Adhesive applied at a maximum rate of 1.0 L/m 2. One layer of Ruberoid Mop Granule SCF or Ruberoid Mop Plus Granule SCF cap sheet adhered with either Type 2 or 3 hot-mopped asphalt applied at a maximum rate of 1.2 kg/m 2. Alternatively, one layer of Ruberoid SBS Heat-Weld Granule SCF or Ruberoid SBS Heat-Weld Plus Granule SCF cap sheet torched to base sheet. GAF MATERIALS CP 2A. Rigid Roof Insulation - CDETC (Guide No. 40 U18.9). (i) Glass-fibre boards, 915 mm by 1220 mm by 65 mm minimum thickness (no maximum) when applied with adhesive to vapour barrier or steel deck. The end joints of the boards shall be staggered. OWENS CNING CANADA INC (ii) Polyisocyanurate insulation boards 1200 by 2400 mm minimum size by 43 mm minimum thickness (no maximum). When this insulation is used, 1200 by 2400 by 15.9 mm thick gypsum wallboard, 10.5 kg/m 2 minimum area density, must be applied with adhesive to steel roof deck, and a ballasted roof covering must be employed. Insulation applied in single or multiple layers. Boards to be installed perpendicular to gypsum wallboard direction with end joints staggered 600 mm in adjacent rows. When applied in more than one layer, each layer of board to be offset in both directions from layer below a minimum of 300 mm in order to lap all joints. FIRESTONE BUILDING PRODUCTS CO, DIV OF FIRESTONE TIRE & RUBBER CO Page 3 of 7

(iii) For use with Item 1A(ii) only. Polyisocyanurate insulation boards 1200 by 2400 mm minimum size by 43 mm minimum thickness (no maximum). When this insulation is used, 1200 by 2400 by 15.9 mm thick gypsum wallboard, 10.5 kg/m 2 minimum area density, must be applied with adhesive to steel roof deck, and a ballasted roof covering must be employed. Insulation applied in single or multiple layers. Boards to be installed perpendicular to gypsum wallboard direction with end joints staggered 600 mm in adjacent rows. When applied in more than one layer, each layer of board to be offset in both directions from layer below a minimum of 300 mm in order to lap all joints. (iv) Polystyrene foam boards 600 by 1200 mm by 50 mm minimum thickness (no maximum) applied in single or multiple layers with adhesive to 1200 mm by 2400 mm by 15.9 mm thick gypsum board, 9.75 kg/m 2 area density. The end and side joints of both the insulation and gypsum boards shall be staggered. The gypsum board is applied with adhesive to the steel roof deck and the ends of the gypsum board shall be supported by the deck. The top of the insulation boards shall be covered with a layer of wood fibreboard 12.7 mm thick (minimum) adhered to the insulation with adhesive. OC CELFTEC INC (v) Polyisocyanurate insulation boards designated "E'NRG'Y 2" or "ISO1"or "Sure-Seal ISO" insulation, minimum 50 mm thick (no maximum), applied in single or multiple layers using mechanical fasteners and/or fully adhered with "Duro Perm Adhesive" applied at a maximum rate of 0.16 kg/m 2 between the insulation layers and on top of the vapor retarder. The "Duro Perm Vapor Retarder" is applied over the steel deck with the adhesive at a rate of 0.33 kg/m 2. A layer of 12.7 mm thick wood fibreboard may be adhered with Type 3 hot-mopping asphalt at a rate of 1.25 kg/m 2 over the top of the insulation prior to the application of the built-up roof covering materials. CARLISLE SYNTEC INCPATED (vi) Polyisocyanurate insulation boards designated "E" RG'Y 2 or ISO1 insulation, minimum 25 mm thick (no maximum), applied in single layer using mechanical fasteners and/or hotmopped with Type 3 asphalt at a rate of 1.25 kg/m 2. When this insulation is used, 15.9 mm thick gypsum board shall be installed over the steel deck with "Duro Perm Adhesive" applied at a rate of 0.33 kg/m 2. The "Duro-Perm Vapor Retarder" is applied over the gypsum board with the adhesive at a rate of 0.16 kg/m 2. A layer of 12.7 mm thick wood fibreboard may be adhered with Type 3 hot-mopping asphalt at a rate of 1.25 kg/m 2 over the insulation prior to the application of the built-up roof covering materials. 3A. Sheathing Material - CHIZC (Guide No. 40 U18.17V). Vapour barrier applied with adhesive to steel deck, or gypsum board, adjacent sheets overlapped an average of 50 mm. BAK INC 4A. Adhesive - BYWRC (Guide No. 40 U18.1-1/2). Applied to steel deck, vapour barrier and rigid roof insulation at the rate specified in the manufacturer's listing. BAK INC 5A Fasteners, Mechanical - (not shown) - Glasfast steel screw and plastic plate fastener system installed through rigid roof insulation, sheathing material, gypsum wallboard and steel roof deck Page 4 of 7

according to manufacturer's instructions. Limited to assemblies having a maximum fire resistance rating of 1 h. Adhesive or asphalt is not required to adhere fastened insulation boards. (i) Fasteners, Mechanical - "Duro-Lock Roof Fastener System" for use in conjunction with and as specified in Items 2A(v) and (vi). ROOF CONSTRUCTION B 1B(i) Roof Covering - TGFUC (Guide No. 360 O18). Class A, B or C built-up roof covering, consisting only of felt and asphalt in alternate layers, as specified in the General Information Section under TGFUC (Guide No. 360 O18). (ii) Roof Covering - TGFUC (Guide No. 360 O18). Class A built-up roof covering, consisting of Sarnafil G423 roofing membrane loosely laid on gypsum wallboard, and covered with rigid roof insulation (Item 2b). Rigid roof insulation must then be surfaced with 15 mm to 40 mm diameter commercial grade gravel, washed and well rounded, applied at a rate of not less than 590 kg/10 m 2. When roofing membrane is used, 1200 mm by 2400 mm by 19 mm thick gypsum wallboard, 12.3 kg/m 2 minimum area density, or two layers of 9.5 mm thick gypsum wallboard, 6.1 kg/m 2 minimum area density, must be applied with adhesive to steel roof deck. SARNAFIL LTD (iii) Roof Covering - TGFUC (Guide No. 360 O18). Class A built-up roof covering, consisting of Carlisle Standard EPDM or UltraGuard EPDM roofing membrane, loosely laid on gypsum wallboard and covered with rigid roof insulation. Rigid roof insulation must then be surfaced with 20 mm to 40 mm diameter commercial grade gravel, washed and well rounded, applied at a rate of not less than 490 kg/10 m 2. When roofing membrane is used, 1200 mm by 2400 mm by 19 mm thick gypsum wallboard, 12.3 kg/m 2 minimum area density, or two layers of 9.5 mm thick gypsum wallboard, 6.1 kg/m 2 minimum area density, must be applied with adhesive to steel roof deck. CARLISLE SYNTEC INCPATED (iv) Roof Covering - TGFUC (Guide No. 360 O18). Class A built-up roof covering, consisting of Firestone Standard or Standard Reinforced Rubbergard EPDM roofing membrane, 1.1 to 1.5 mm thick, loosely laid on gypsum wallboard and covered with rigid roof insulation. Rigid roof insulation must then be surfaced with 25 to 38 mm diameter commercial grade gravel, washed and well rounded, applied at a rate of not less than 490 kg/10 m 2. When roofing membrane is used, 1200 by 2400 by 19 mm thick gypsum wallboard, 12.3 kg/m 2 minimum area density, or two layers of 9.5 mm thick gypsum wallboard, 6.1 kg/m 2 minimum area density, must be applied with adhesive to steel roof deck. FIRESTONE BUILDING PRODUCTS CO, DIV OF FIRESTONE TIRE & RUBBER CO (v) Permeable Fabric - TGFUC (Guide No. 360 O18). A permeable fabric designated Fabrene Type VIE may be loosely laid in one layer on the loose applied rigid roof insulation and covered with 295 kg minimum of crushed or rounded stone per 10 m 2 of roofing area. FABRENE INC (vi) Roof Covering - TGFUC (Guide No. 360 O18). Class C built-up roof covering consisting of wood fibreboard, base, and cap sheets. One layer of 12.7 mm thick wood fibreboard, 2.6 kg/m 2 minimum area density, back-mopped to Rigid Roof Insulation, Item 2B(iii), with Type 2 or 3 asphalt applied at a maximum rate of 0.67 kg/m 2. One layer of Elastophene sanded or Elastophene PS base sheet adhered to wood fibreboard with either Type 2 or 3 hot-mopped Page 5 of 7

asphalt applied at a maximum rate of 1.05 kg/m 2, or Bakor Vapor-Block Adhesive applied at a maximum rate of 1.0 L/m 2. One layer of Sopralene 180 granules or Sopralene 250 granules cap sheet adhered with either Type 2 or 3 hot-mopped asphalt applied at a maximum rate of 1.2 kg/m 2. Alternatively, one layer of Sopralene Flam 180 granules or Sopralene Flam 250 granules cap sheet torched to base sheet. SOPREMA INC (vii) Roof Covering - TGFUC (Guide No. 360 O18). Class A built-up roof covering, consisting of one ply of IKO "Glass Type IV, IKO "Glass Type 6", or "IKO No. 25 Glass Base Sheet", hotmopped with Type 2 or 3 hot-mopping asphalt at a rate of 1.2 kg/m 2 maximum or mechanically fastened with the manufacturer\'s accepted steel plate and screw fasteners to polyisocyanurate, perlite, fibreglass, wood fibre or polystyrene (covered with wood fibre or perlite) insulation. One ply of "Modiflex MP-180-SS-Base", "Modiflex MP-180-FS-Base", "Modiflex MF-95-SS-Base", "Modiflex MF-95-FS-Base", hot-mopped with Type 2 or 3 hotmopping asphalt at a rate of 1.2 kg/m 2 maximum, or "Torchflex TF-95-FF-Base", "Torchflex TF-95-FF 2.2", "Torchflex TP-180-FF-Base", torched to the base or ply sheet (optional). One ply of "Modiflex MP-180-CAP FR" or "Modiflex MF-95-CAP FR" hot-mopped with Type 2 or 3 hot-mopping asphalt at a rate of 1.2 kg/m 2 maximum or "Torchflex TP-180-CAP FR" or "Torchflex TF-95-CAP FR" torched to the base or ply sheet. Class C built-up roof covering, consisting of a minimum 11 mm wood fiber, or 3.2 mm or 4.5 mm "Protectoboard" or "PERMABOARD" mechanically attached, urethane adhesive adhered, or adhered with Type 2 or 3 hot-mopping asphalt at a rate of 1.2 kg/m 2 maximum (optional) to wood fibreboard, glass fibre, mineral fibre, polyurethane, perlite, polyisocyanurate, phenolic, or resol foam roof insulation. One or more plies IKO "Modiflex MF-95-FS Base", IKO "Modiflex MF-95-SS-Base", IKO "Glass Type IV", IKO "Glass Type 6", or "IKO No. 25 Glass Base Sheet" cold adhesive applied with Karnak 81AF SBS Cold Adhesive, Monsey-Bakor MBA Gold Adhesive, Henry Company #403 Cold-Ap Spray Grade Adhesive, or Henry Company #902 Permanent Bond Adhesive at a full coverage rate of 5.68 L /0.61 m 2 or spot attached at a rate of sixty spots per 9.3 m 2, with spots being 102 mm to 152 mm in diameter, for the first layer and either cold adhesive or heat fused for successive layers. One or more plies of "IKO No. 25 Glass Base Sheet" cold adhesive applied or heat fused (optional). One ply of "Modiflex MP-180-Cap", "Modiflex MP-250-Cap", "Modiflex MP-180-Cap FR", "Modiflex MP-180-Cap FR Premium", "Modiflex MF-95-Cap", "Modiflex MF-95-Cap FR", or "Modiflex MF-95-Cap FR Premium", cold adhesive applied or "Torchflex TP-180-Cap", "Torchflex TP-250-Cap", "Torchflex TF-95- Cap", "Torchflex TP- 180-Cap FR", "Torchflex TP-180-Cap FR Premium", "Torchflex TF-95-Cap FR", or "Torchflex TF-95-Cap FR Premium" heat fused. (viii). Roof Covering - TGFUC (Guide No. 360 O18). Class C built-up roof covering consisting of wood fibreboard, base, and cap sheets. One layer of 12.7 mm thick wood fibreboard, 2.6 kg/m 2 minimum area density, back-mopped to rigid roof insulation, Item 2B(iii), with Type 2 or 3 asphalt applied at a maximum rate of 0.67 kg/m 2. One layer of Ruberoid 20 Smooth SCF base sheet adhered to wood fibreboard with either Type 2 or 3 hot-mopped asphalt applied at a maximum rate of 1.05 kg/m 2, or Bakor Vapor-Block Adhesive applied at a maximum rate of 1.0 L/m 2. One layer of Ruberoid Mop Granule SCF or Ruberoid Mop Plus Granule SCF cap sheet adhered with either Type 2 or 3 hot-mopped asphalt applied at a maximum rate of 1.2 kg/m 2. Alternatively, one layer of Ruberoid SBS Heat-Weld Granule SCF or Ruberoid SBS Heat-Weld Plus Granule SCF cap sheet torched to base sheet. GAF MATERIALS CP Page 6 of 7

2B. Rigid Roof Insulation - CDETC (Guide No. 40 U18.9). (i) Foamed plastic in boards 600 by 1200 mm by 50 mm minimum thickness (no maximum). DOW CHEMICAL CANADA INC (ii) Polystyrene foam boards 600 by 1200 mm by 50 mm minimum thickness (no maximum). OC CELFTEC INC 3B.(i) Gypsum Wallboard - CKNXC (Guide No. 40 U18.23). 15.9 mm thick supplied in 1200 mm wide sheets. Installed perpendicular to steel roof deck with end joints on crests of deck, staggered 600 mm and offset from steel roof deck sidelap joints. Secured to crests of steel roof deck with adhesive. G-P GYPSUM CP, SUB OF GEGIA-PACIFIC CP (ii) Gypsum Board - In lieu of Item 3B(i), 15.9 mm thick gypsum board of minimum density 9.8 kg/m 2 supplied in sheets nominally 1200 mm by 2400 mm may be used. 4B. Adhesive - BYWRC (Guide No. 40 U18.1-1/2). Applied to steel deck and gypsum board at the rate specified in the manufacturer's listing. BAK INC 5. Steel Roof Deck - Fluted steel deck, minimum 0.76 mm thick galvanized steel, nominally 38 mm deep and 915 mm width. Attached to joists and beam with 20 mm diameter plug welded at 150 mm OC. The interlocking flanges of the adjacent units to be button-punched together on 350 mm centres. 6. Beam - W200x31, minimum size. 7. Joist - 250 mm deep, open-web steel joist 8.8 kg/m minimum size designed in accordance with the relevant provisions of Part 4 of the National Building Code of Canada, spaced 1525 mm OC. 8. Bridging - Designed in accordance with the relevant provisions of Part 4 of the National Building Code of Canada. 9. Spray-Applied Fire-Resistive Material (see table below) - CHPXC (Guide No. 40 U18.6). Applied with or without adhesive to steel surfaces to final untamped thicknesses as shown in table. Tamping is optional. Fibre to have a minimum average density of 165 kg/m 3 with a minimum individual value of 145 kg/m 3. For method of density determination, refer to General Information Section under heading "Fire Resistance Ratings". Steel surfaces must be clean and free of dirt, loose scale and oily deposits. A/D FIRE PROTECTION SYSTEMS INC Location Min Protection Thickness, mm Deck 25 Joists 29 Beam 25 Bridging 19