Polymeric membrane for roof waterproofing
|
|
|
- Francine Floyd
- 9 years ago
- Views:
Transcription
1 Product Data Sheet Edition Revision no: 0 Identification no: Sarnafil TS Polymeric membrane for roof waterproofing Construction Product Description Uses Characteristics / Advantages Tests Approval / Standards (thickness 1.2 mm) is a Polyester reinforced, multi-layer, synthetic roof waterproofing sheet based on premium-quality flexible polyolefins (FPO) containing ultraviolet light stabilizers, flame retardant and an inlay of glass non-woven according to EN is a hot air weldable roof membrane formulated for direct exposure and designed to use in all global climatic conditions. is produced with an inlay of glass non-woven for dimensional stability and a polyester reinforcement for high strength. is provided for mechanically attached roof systems. has no built-in stress at the time of production and has a fully encapsulated carrier with no risk to delamination or water-wicking. The dimensional stability of is excellent. Waterproofing membrane for: Mechanically fastened roofs Outstanding resistance to weathering, including permanent UV irradiation Excellent flexibility in cold temperatures No built-in stress at the time of production High dimensional stability High resistance against impact load Excellent weldability No risk of delamination or water-wicking Compatible to old bitumen Recyclable is designed and manufactured to meet the most international recognised standards. Polymeric sheets for roof waterproofing according to EN 13956, certified by notified body 1213-CPD-3915 and provided with the CE-mark. Reaction to fire according to EN External fire performance tested according to ENV 1187 and classified according to EN : BROOF(t1). Official Quality Approvals and Agrement Certificates and approvals. Monitoring and assessment by approved laboratories. Quality Management system in accordance with EN ISO 9001/ /6
2 Product Data Form Appearance / Colours Surface: matt Colours: Packaging Top surface: beige grey (nearest RAL 7040) Bottom surface: black standard rolls are wrapped individually in a blue PE-foil. Packing unit: Roll length: Roll width: Roll weight: up to 27 rolls per pallet m 2.00 m kg Storage Storage Conditions Rolls must be storaged in horizontal position on pallet and protected from direct sunlight, rain and snow. Product does not expire during correct storage. 2 2/6
3 Technical Data Product Declaration EN Visible Defects Pass EN Length m (-0% / +5%) EN Width 2.00 m (-0.5% / +1%) EN Straightness 30 mm EN Flatness 10 mm EN Effective Thickness 1.2 mm (- 5 % / + 10 %) EN Mass per unit area 1.32 kg/m² (- 5 % / + 10 %) EN Water tightness Pass EN 1928 Effects of liquid chemicals, including water On request EN 1847 External fire performance Part 1-4 B ROOF(t1) <20 ENV 1187 / EN Reaction to fire Class E EN ISO , classification to EN Hail resistance Rigid substrate Flexible substrate 17 m/s 25 m/s EN Joint peel resistance 300 N/50 mm EN Joint shear resistance 500 N/50 mm EN Water vapour transmission properties µ = EN 1931 Tensile strength Elongation Resistance to impact hard substrate soft substrate Tear strength Dimensional stability 1000 N/50 mm 900 N/50 mm 13 % 13 % 600 mm 800 mm 300 N 300 N 0.2 % 0.1 % EN EN EN EN EN Foldability at low temperature C EN UV exposure Pass (> h) EN 1297 Exposure to bitumen 3) Pass EN ) md = machine direction 2) cmd = cross machine direction 3) Sarnafil T is compatible to old bitumen 3 3/6
4 System Information System Structure Wide range of accessories is available e.g. prefabricated parts, roof drains, scuppers and walkway pads. The following materials are strongly recommended: Sarnafil T D Sheet for detailing Sarnafil TS 77 strips Sarnafil T Metal Sheet Sarnabar Sarnafil T Welding Cord Sarnafil T Prep / Sarnafil T Wet Task Set Sarnacol T 660 Solvent T 660 Sarnafil T Clean Application Details Substrate Quality The substrate surface must be uniform, smooth and free of any sharp protrusions or burrs, etc. The supporting layer must be compatible to the membrane, solvent resistant, clean, dry and free of grease and dust. Metal sheets must be degreased with Solvent T 660 before adhesive is applied. Application Conditions / Limitations Temperature Compatibility The use of Sarnafil TS membranes is limited to geographical locations with average monthly minimum temperatures of -50 C. Permanent ambient temperature during use is limited to +50 C. may be installed on all thermal insulations and levelling layers suitable for roofing. No additional separation layer is required. Probably a fire protection layer is necessary. is suitable for installation directly on top of existing, carefully cleaned, levelled bituminous roofing, e.g. re-roofing over old flat roofs. Colour changes in membrane surface may occur in case of direct contact with bitumen. In case of existing roof build up needs to be removed, can be adhered directly on to the bituminous vapour control layer for partitioning and protection of the day work. 4 4/6
5 Application Instructions Application Method / Tools Notes on Application / Limitations Installation procedure: According to the valid installation instructions for Sarnafil TS 77-types system for mechanically fastened roofs. Fixing Method, linear fastening (Sarnabar): Unroll the membrane, overlap by 80 mm, weld immediately and fix to the substructure by means of Sarnabars. The type of fastening will be advised by Sika. The spacing of the fasteners is in accordance with the project specific calculations made by Sika. The perimeter piece ends must be secured with the Sarnafil Load Distribution Plate. For protection fasten a piece of Sarnafil TS under bar end and plate. Leave a 10 mm clearance between bar ends. Do not fasten in hole nearest bar end. Cover the bar ends with a piece of Sarnafil TS and weld. After installation the Sarnabars must immediately be made watertight with a Sarnafil cover strip. At upstands and at all penetrations, the Sarnafil TS membrane must be secured with a Sarnabar. The Sarnafil T Welding Cord protects the roof covering against tearing and peeling of by wind uplift. Fixing Method, spot fastening (Sarnafast): must always be installed at right angles to the deck direction. is fixed by means of the Sarnafast fasteners and barbed washers along the marked line, 35 mm from the edge of the membrane. Sarnafil TS is overlapped by 120 mm. Welding Method: Before welding the seams are prepared with Sarnafil T Prep. Overlap seams are welded by electric hot air welding equipment, such as manual hot air welding machines and pressure rollers or automatic hot air welding machines with controlled hot air temperature. Recommended type of equipment: Leister Triac PID for manual welding Sarnamatic 661 plus for automatic welding Welding parameters including temperature, machine speed, air flow, pressure and machine settings must be evaluated, adapted and checked on site according to the type of equipment and the climatic situation prior to welding. The effective width of welded overlaps by hot air should be minimum 20 mm. The seams must be mechanically tested with screw driver to ensure the integrity / completion of the weld. Any imperfections must be rectified by hot air welding. Installation works must be carried out only by Sika instructed contractors for roofing. Temperature limits for the installation of the membrane: Substrate temperature: -30 C min. / +60 C max. Ambient temperature: -20 C min. / +60 C max. Installation of some ancillary products, e.g. contact adhesives/thinners is limited to temperatures above +5 C. Please refer to the respective Product Data Sheets. Special measures may be compulsory for installation below +5 C ambient temperature due to safety requirements in accordance with national regulations. 5 5/6
6 Construction Value Base Local Restrictions Health and Safety Information Legal Notes All technical data stated in this Product Data Sheet are based on laboratory tests. Actual measured data may vary due to circumstances beyond our control. Please note that as a result of specific local regulations the performance of this product may vary from country to country. Please consult the local Product Data Sheet for the exact description of the application fields. For information and advice on the safe handling, storage and disposal of chemical products, users shall refer to the most recent Material Safety Data Sheet containing physical, ecological, toxicological and other safety-related data. The information, and, in particular, the recommendations relating to the application and end-use of Sika products, are given in good faith based on Sika's current knowledge and experience of the products when properly stored, handled and applied under normal conditions in accordance with Sika s recommendations. In practice, the differences in materials, substrates and actual site conditions are such that no warranty in respect of merchantability or of fitness for a particular purpose, nor any liability arising out of any legal relationship whatsoever, can be inferred either from this information, or from any written recommendations, or from any other advice offered. The user of the product must test the product s suitability for the intended application and purpose. Sika reserves the right to change the properties of its products. The proprietary rights of third parties must be observed. All orders are accepted subject to our current terms of sale and delivery. Users must always refer to the most recent issue of the local Product Data Sheet for the product concerned, copies of which will be supplied on request. Sika Yapı Kimyasalları A.Ş. Deri Org. San. Böl. 2. Yol J 7 Parsel, Aydınlı, Orhanlı Mevkii, Tuzla, İstanbul, Türkiye Çağrı Merkezi Telefon Faks [email protected] /6
Roofing. Sarnafil S 327-15EL. Polymeric membrane for roof waterproofing. Product Description
Roofing Product Data Sheet Edition 02.2015 Identification no: 02 09 01 01 201 0 150000 Version no. 04 Sarnafil S 327-15EL Polymeric membrane for roof waterproofing Product Description Sarnafil S 327-15EL
Construction. SikaProof A-08 Edge, A-12 Edge. Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing system. Product Description
Product Data Sheet Edition 15/10/2014 Identification no: 02 07 04 10 300 0 000002 SikaProof A Edge SikaProof A-08 Edge, A-12 Edge Fully bonded FPO sheet membrane in L-shape for the SikaProof A waterproofing
Elastic, 1-part-polyurethane, liquid waterproofing membrane
Product Data Sheet Edition 15.04.2008 Revision no.: 1 Identification no: 01 07 02 03 002 0 000005 Sikalastic -450 Elastic, 1-part-polyurethane, liquid waterproofing membrane Construction Product Description
High-performance, 2-part epoxy anchoring adhesive
Product Data Sheet Edition 27/04/2009 Revision no: 0 Identification no: 01 04 02 06 001 0 000030-3+ -3+ High-performance, 2-part epoxy anchoring adhesive Construction Product Description Uses Solvent-free,
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12
WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12 87 88 GOOD INDUSTRY PRACTICES 12 WATERPROOFING OF REINFORCED CONCRETE FLAT ROOF 12.1 BACKGROUND Most roofs in Singapore are constructed using reinforced
Construction. Sikadur-Combiflex. Sealing system for cracks and problem joints with large movements DESCRIPTION
Sikadur-Combiflex REVISED JULY 2002 Sealing system for cracks and problem joints with large movements Construction DESCRIPTION USES ADVANTAGES The Sikadur-Combiflex joint sealing system consists of two
Sika Membran System For Sealing and Waterproofing Construction Gaps in Building Façades
Construction Sika For Sealing and Waterproofing Construction Gaps in Building Façades Waterproof and Airtight Flexible Seal Controlled Vapour Diffusion Bonds to any Building Substrate Prevents Interstitial
HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS
BSW HIGH PERFORMANCE PRE-APPLIED SYSTEM FOR BLIND SIDE & BELOW GRADE WATERPROOFING APPLICATIONS BSW is a fully reinforced Pre-Applied system membrane designed for horizontal and vertical external blind-side
CERTIFICATE NAME OF PRODUCT MANUFACTURER PRODUCT DESCRIPTION CERTIFICATION PROCEDURE. No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011
CERTIFICATE NAME OF PRODUCT No VTT C-6044-10 Date of issue 11.10.2010, Updated July 1, 2011 H-CONTROL REFLEX+ reflective insulating vapour control layer for roof and wall applications MANUFACTURER ACTIS
Construction. 3-part thixotropic epoxy patching mortar. Product Description. Tests
Product Data Sheet Edition 05/12/2014 Identification no: 020204030010000044 Sikadur -41 CF Rapid 3-part thixotropic epoxy patching mortar Construction Product Description Uses Characteristics / Advantages
CHESTERFLEX ROOF WATERPROOFING MEMBRANES
CI/SfB (47) Ln2 Chesterfelt Ltd CHESTERFLEX ROOF WATERPROOFING MEMBRANES Certificate No 94/3062 DETAIL SHEET 2 Product THIS DETAIL SHEET RELATES TO CHESTERFLEX ROOF WATERPROOFING MEMBRANES, POLYESTER REINFORCED
NEW ELECTRICAL SUBSTATION Building 300 SECTION 07 53 23 ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK
ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK PART 1 GENERAL 1.1 REFERENCES The publications listed below form a part of this specification to the extent referenced. The publications are referred to within
SARNAFIL WATERPROOFING MEMBRANES SARNAFIL ADHERED ROOF WATERPROOFING MEMBRANES
Sika Limited Target Market Roofing Watchmead Welwyn Garden City Hertfordshire AL7 1BQ Tel: 01707 394444 Fax: 01707 329129 e-mail: [email protected] website: www.sarnafil.co.uk APPROVAL INSPECTION
Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology. Modern Efficient Performance Cost Effective Flat Roofing Systems
Memtec Single Ply PVC Membrane Roofing and Waterproofing Technology Modern Efficient Performance Cost Effective Flat Roofing Systems Introduction A complete range of Memtec Roofing and Waterproofing Single
European Technical Approval ETA 12/0419
FM Approvals Limited 1 Windsor Dials Windsor Berkshire SL4 1RS United Kingdom Tel.: +44 (0)1753 750000 Fax: +44 (0)1753 868700 E-mail: [email protected] Internet: www.fmapprovals.com Member of EOTA European
SikaProof A Technology
SikaProof A Technology The fully bonded waterproofing system Keep your basements durably and securely watertight What is SikaProof A? How does it work? Where can it be used? What are the advantages of
Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5
Cl Sfb (27-9) Rn7 M2 December 2004 Built-up roofing solutions with rigid insulation boards on concrete decks for new-build and refurbishment E-a5 Fesco, Fesco S, Retrofit, Retrofit S, Fesco Fillet, PF,
ITEM 599.06060008 THERMOPLASTIC MEMBRANE ROOFING
DESCRIPTION Construct adhered membrane roofing system, roof insulation, and vapor retarder in accordance with these specifications. MATERIALS: General: Provide installed roofing membrane and base flashings
Low viscosity, solvent free elastic adhesive for wood flooring
Product Data Sheet Edition 25/06/2012 Identification no: 01 05 02 01 250 0 000009 SikaBond -54 54 Wood Floor Low viscosity, solvent free elastic adhesive for wood flooring Construction Product Description
SIKA TANKING MEMBRANES SIKAPROOF A MEMBRANES
Sika Limited Watchmead Welwyn Garden City Hertfordshire AL7 1BQ Tel: 01707 394 444 Fax: 01707 329 129 e-mail: [email protected] website: www.sika.co.uk APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL
Cavity Drain R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high.
CI/SfB Tn6 L6813 September 2013 RIW CAVITY DRAIN R20 R20 is manufactured from1.0mm thick black high density polyethylene with studs approximately 20mm high. Other systems are available for specific uses,
System 5000 FLAME-FREE, FELT SYSTEM, INSTALLED USING HOT AIR, TOTALLY ELIMINATING FIRE RISK AND PROVIDING A BITUMEN ALTERNATIVE TO SINGLE PLY
CI/SfB Oct 12 (47) Ln Uniclass L524 FLAME-FREE, FELT SYSTEM, INSTALLED USING HOT AIR, TOTALLY ELIMINATING FIRE RISK AND PROVIDING A BITUMEN ALTERNATIVE TO SINGLE PLY Bailey Flame-free felt roofing Bailey
4 Product Data Sheets
4 Product Data Sheets Firestone has developed a complete range of roofing products, including EPDM membranes, flashings, adhesives, QuickSeam products, sealants, cleaning agents, fasteners and a variety
FLAGON PVC SINGLE-PLY ROOF WATERPROOFING SYSTEMS FLAGON SFc, SFb AND SV ROOF WATERPROOFING SYSTEMS
Flag-Soprema UK Ltd Unit 640, Avenue West Skyline 120 Great Notley Essex CM77 7AA Tel: 0845 194 8727 Fax: 0845 194 8728 e-mail: [email protected] website: www.flag-soprema.co.uk APPROVAL INSPECTION
Firestone RubberGard The EPDM reference
Firestone RubberGard The EPDM reference EPDM Roofing Systems 1.000.000.000 m 2 of proven performance The Firestone heritage of success and quality is extended to the construction industry through the Firestone
CHAPTER 7: Building Systems ROOFING SYSTEMS
ROOFING SYSTEMS Purpose Examples 1. Shingle roof system 2. Metal roof with blanket insulation 3. Metal roof with rigid insulation 4. Built-up asphalt roof system 5. Single-ply roof system 6. Modified Bitumen
Read and understand all installation instructions and precautions before installing. GENERAL APPLICATION INSTRUCTIONS
AC TOPSEAL SELF-ADHERED, GRANULAR SURFACED, SINGLE PLY, LOW SLOPE ROLLED ROOFING 3 X 33.3 = 100 SQ. FT. 10 YEAR MATERIAL LIMITED WARRANTY For Use on Porches / Sheds / Utility Buildings / Accessory Buildings
Colorado State University. Durrell Center Roof Repair
Colorado State University Durrell Center Roof Repair SPECIFICATION: POLYURETHANE FOAM ROOFING l.0 GENERAL REQUIREMENTS The successful application of a polyurethane foam roofing system is dependent upon
PRODUCT DATA SHEET Sika Cable System
PRODUCT DATA SHEET Corrosion protection for bridge cables of steel and galvanized steel PRODUCT DESCRIPTION The Sika Cable System consists of coating materials as well as a sealing respectively injection
How To Test A Wrap N Drain X Dampproofing System
National Research Council Canada Institute for Research in Construction Conseil national de recherches Canada Institut de recherche en construction CCMC 13094-R &&0& EVALUATION DIVISION 07111 REPORT Issued
Building Owners Guide to a Duro-Last System!
Building Owners Guide to a Duro-Last System Table of Contents Section 1: Introduction to Duro-Last Roofing Systems Section 2: Benefits of a Duro-Last Roofing System Section 3: Comparing a Duro-Last Roof
Roofing Systems. There are many different systems, each with it's own special requirements and benefits. Browse through all the options below.
Roofing Systems There are many different systems, each with it's own special requirements and benefits. Browse through all the options below. BUR (Built-Up Roofing) Built-Up-Roofing, BUR is a roof that
Roofing hand tools overview 47
36 Roofing VARIMAT V2 38 / 39 UNIROOF E 40 TRIAC DRIVE PID / guiding help 41 X 84 42 BITUMAT B2 43 COMET SUB-ROOF 44 Roofing welders overview 45 EXAMO 46 Roofing hand tools overview 47 Flach- Roofing und
SECTION 07530 SINGLE PLY MEMBRANE ROOFING. 4. Minor repair to adjacent clay tile roofing and flashings.
SECTION 07530 PART 1 - GENERAL 1.01 DESCRIPTION A. This Section includes the flowing: 1. Removal of existing roofing membrane. Existing bur roof has one overlay and penetration mastic is asbestos containing.
INNOVATIONS. Economic Flat Roof Refurbishment with NOVOPROOF Sealing Systems. A Company of the SAARGUMMI Group
INNOVATIONS Economic Flat Roof Refurbishment with NOVOPROOF Sealing Systems A Company of the SAARGUMMI Group OUR SOLUTION TO REFURBISH ROOFS FOR LONG-TERM DURABILITY Quality and Experience from the Innovation
DENSO WATERPROOFING SYSTEMS
DENSO WATERPROOFING SYSTEMS Approved Quality Management System AS/NZS ISO 9001:2008 Lloyds Register Certificate N o Mel 0927759 Denso (Australia) Pty Ltd A MEMBER OF WINN & COALES INTERNATIONAL 411 413
Test report P 7013-E. InoPaz H2O. Pazkar LTD. Alon Tavor Industrial Zone AFULA 18000 / Israel. J. Magner Dipl.-Ing. N. Machill.
Kiwa Polymer Institut GmbH Quellenstraße 3 65439 Flörsheim-Wicker Tel. +49 (0)61 45-5 97 10 Fax +49 (0)61 45-5 97 19 www.kiwa.de Test report P 7013-E Testing order: Test of the waterproofing system based
07 5423-1 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center
PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 5423 THERMOPLASTIC-POLYOLEFIN ROOFING (TPO) Data Center A. Tear off existing roof system down to wood deck and install new Thermoplastic membrane roofing
Division 9. SignaFlor Pad and Pour Flooring System
Division 9 SignaFlor Pad and Pour Flooring System SPECIFICATIONS Page 1. General... 2 1.1 Description 2 1.2 Quality Assurance 2 1.3 Submittals 2 1.4 Delivery and Storage 3 1.5 Warranty 3 1.6 Working Conditions
SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING
SECTION 07540 - THERMOPLASTIC MEMBRANE ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification
SEAMS SEAMING USING SEAM TAPE
SEAMING USING SEAM TAPE SEAMS The membrane should be positioned so that the width of the seam is 3. Remove excess chalk from a chalk line by snapping the line into the air and then chalk a line one-quarter
GreenGuard Housewrap Installation Guide
000768PACBPHW_Flashing Bro 5/23/03 2:52 PM Page 1 For the most current product information, go to www.green-guard.com. Pactiv Building Products believes the information and recommendations herein to be
Peel & Seal Self-Stick Roofing Solutions
Peel & Seal Self-Stick Roofing Solutions Ideal for Low Slope Applications Waterproof and Weatherproof Energy Efficient Tough and Durable Versatile, Effective Sealing Around Protrusions Perfect for Vents,
MILMAN & ASSOCIATES STRUCTURAL CONSULTING ENGINEERS/ PROJECT MANAGERS
MILMAN & ASSOCIATES STRUCTURAL CONSULTING ENGINEERS/ PROJECT MANAGERS May 29, 2013 Revision B Structural Guideline for Design and Installation Holes in Composite Floor Slab Terminal 3, Departure Level
1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.
SECTION 075416 - PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system. 1.2 PERFORMANCE REQUIREMENTS A. Solar Reflectance
SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE)
SECTION 07560 FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE) PART 1 GENERAL 1.1 DESCRIPTION 1. Fluid applied flexible acrylic waterproofing system over concrete. This work shall include the
Fire Barrier Duct Wrap 15A
3 Fire Barrier Duct Wrap 15A Commerical Kitchen Grease Duct Fire Protection System Product Data and Installation Instructions Compliance 1998 Edition Complies with International Mechanical Code Complies
DRAINAGE MATS For Vertical: Flow 15-P For Horizontal: Flow 18-H
DRAINAGE MATS For Vertical: Flow 15-P For Horizontal: Flow 18-H Soil Drainage Mat with Built-In Protection Layer POLYGUARD DRAINAGE MATS are three-part prefabricated geocomposite drain consisting of a
Commercial Roof Management
Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading
RECOATING AND RENEWING SPF ROOFING SYSTEMS
RECOATING AND RENEWING SPF ROOFING SYSTEMS Procedures, Regional Differences and type of coating systems Bruce Schenke Premium Spray Products REASONS TO RECOAT/RENEW Add a new coating layer to renew the
1.2.1 1.1.8 PRODUCTBLADEN GT ROCKPANEL STRUCTURE
1..1 1.1.8 PRODUCTBLADEN SHEETS GT page 1 to 6 Rockpanel Structure is a very durable panel with a lightly textured finish, specially developed for use in cladding, fascia, soffit applications. The basic
STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES
ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.
WATERPROOFING SikaProof -A TECHNOLOGY
SikaProof -A TECHNOLOGY content What is SikaProof -A? 6 How does it work? 8 Where can it be used? 0 What are the advantages of SikaProof -A? 2 How should it be installed? SikaProof -A system components
APIB Test Specification No. 09 WATERPROOFING MEMBRANES SWISS HAIL IMPACT PROTECTION REGISTER HSR. 01.07.2015 / 07-15en Version 1.
Association of Public Insurance Companies (APIB) Association des établissements cantonaux d assurance incendie SWISS HAIL IMPACT PROTECTION REGISTER HSR APIB Test Specification No. 09 WATERPROOFING MEMBRANES
DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION
SECTION 230713- ALUMAGUARD ENGINEER SPECIFICATION DIVISION 23 HEATING, COOLING, AIR CONDITIONING AND VENTILATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract,
Asphalt Shingle Application Requirements
Alberta Allied Roofing Association Asphalt Shingle Application Requirements Section 1 Roof Decks 1.1 General Asphalt Shingles are not permitted to be installed directly over rigid insulation. When Asphalt
EPDM. Roofing systems
Roofing systems Our Promise Through ongoing interchange of experiences with contractors, Mule-Hide keeps on top of the latest roofing requirements and solutions Trusted in roofing since 1906, Mule-Hide
WATERPROOFING FOR CONCRETE STRUCTURES
MANUAL OF CONTRACT DOCUMENTS FOR ROAD WORKS VOLUME 1 SPECIFICATION FOR ROAD WORKS SERIES 2000 WATERPROOFING FOR CONCRETE STRUCTURES Contents Clause Title Page 2001 General 2 2002 Protection of Bridge Deck
CONTENTS. General conditions 2. Material requirements 3. Terms 4. Estimating shingle requirements 4. Roof preparation 6. Shingle application 9 - 1 -
CONTENTS General conditions Material requirements 3 Terms 4 Estimating shingle requirements 4 Roof preparation 6 Shingle application 9 Shingle Shingle application application guide guide - - b a 3a 3b
Pipe and Equipment Insulations. Zeston. PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems
Pipe and Equipment Insulations Zeston PVC Insulated Fitting Covers Installation Instructions for Hot, Cold and USDA Piping Systems Zeston PVC Insulated Fitting Covers Installation Instructions for Hot,
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
BAUDER BITUMINOUS ROOFING SYSTEMS BAUDERFLEX ROOF WATERPROOFING SYSTEMS
Bauder Ltd 70 Landseer Road Ipswich Suffolk IP3 0DH Tel: 01473 257671 Fax 01473 230761 e-mail: [email protected] website: www.bauder.co.uk APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL APPROVALS
INSTALLATION GUIDE. americanwick.com 800.242.WICK (9425)
INSTALLATION GUIDE americanwick.com 800.242.WICK (9425) American Wick Drain SITEDRAIN prefabricated drainage products may be installed in a variety of civil construction applications including: retaining
Reflectex TM Reflective Concrete Interlayer Geotextile INSTALLATION GUIDELINES
Reflectex TM Reflective Concrete Interlayer Geotextile INSTALLATION GUIDELINES Page 1 Table of Contents WHAT IS REFLECTEX TM?... 2 STORAGE AND HANDLING... 3 SITE PREPARATION... 3 PREPARATION OF EXISTING
DECLARATION OF PERFORMANCE
Flooring Declaration of Performance Edition 01.07.2013 Identification no. Version no. 01 EN 1504-2: 2004 08 0921 EN 13813: 2002 DECLARATION OF PERFORMANCE Declaration of performance 1. Product Type Unique
ENGINEERING SPECIFICATION FIBERGRATE MOLDED GRATING. January 24, 2014 06610-1
ENGINEERING SPECIFICATION FIBERGRATE MOLDED GRATING January 24, 2014 06610-1 SECTION 06610 FIBERGLASS REINFORCED PLASTICS (FRP) FABRICATIONS MOLDED GRATING PART 1 - GENERAL 1.1 SCOPE OF WORK A. The CONTRACTOR
Tunnels & Arches OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM
P r o d u c t a p p l i c a t i o n s a n d t e c h n i c a l i n f o r m a t i o n 5 Tunnels & Arches V OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM V Create dry usable space with the original X pattern
ALUMASC ROOF WATERPROOFING MEMBRANES EUROROOF MASTERGOLD ROOF WATERPROOFING MEMBRANE
Alumasc Exterior Building Products Ltd White House Works Bold Road Sutton St Helens Merseyside WA9 4JG Tel: 01744 648 400 e-mail: [email protected] website: www.alumascroofing.co.uk APPROVAL
AND MEMBRANES ROOFING UNDERLAYS. www.fakro.com
AND MEMBRANES 010 ROOFING UNDERLAYS 1 HO DOES YOUR ROOF BREATHe? MEMBRANES THE WAY to A WARM AND DRY ROOF HO HO HO HO HO HO WATERTIGHTNESS The FAKRO Company offers a wide range of membranes and underlays
INSTALLATION RECOMMENDATIONS. Outdoor Rubber Tiles
INSTALLATION RECOMMENDATIONS Outdoor Rubber Tiles Prior to Installation: The Outdoor Rubber Tiles and accessory transition pieces intended for this installation have been shipped to you via a freight carrier
Interior Walls below and above ground OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM
P r o d u c t a p p l i c a t i o n s a n d t e c h n i c a l i n f o r m a t i o n 2 below and above ground V OLDROYD THE ULTIMATE WATERPROOF MEMBRANE SYSTEM V The flexible, fast and cost-effective answer
FATRA ROOF COVERING SYSTEMS FATRAFOL FF807 AND FATRAFOL FF807/V ROOF COVERING SYSTEMS
Fatra UK Ltd Unit 12 The Timber Yard East Moors Road Ocean Park Cardiff CF24 5EE Tel: 029 2048 7954 Fax: 029 2048 9226 e-mail: [email protected] website: www.fatra.co.uk FATRA ROOF COVERING SYSTEMS APPROVAL
Roof Insulation Building. Energy. Environment friendly e-library
Roof Insulation Building Codes & Energy Efficiency Environment friendly e-library Building Code Driver Buildings consumer almost 50% of all energy. Experts believe that a 30% increase in building efficiency
Roofing Applicator Handbook
Roofing Applicator Handbook Introduction Welcome to Sika Sarnafil s Roofing Applicator Handbook. This pocket guide is intended to serve as a quick on the roof reference to the techniques used when installing
VC 104+ Rigid Grade / Rigid Grade Imagine VC 104 Rigid Grade Commercial Customised
Page 1 of 6 instructions VC 104+ Rigid Grade / VC 104+ Rigid Grade Imagine / (for the rest of this document referred to as VC 104) can be applied to new and used trucks and trailers with painted rigid
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING
FOUNDATION INSULATING SYSTEM, INCLUDING WATERPROOFING AND DAMP PROOFING insulation installed on foundation walls must be separated from the building interior with a code approved thermal barrier. Foam
SECTION 07550 - MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.
SECTION 07550 - PART I GENERAL 1.01 SECTION INCLUDES A. Vapor barrier (base ply); cover board at existing roof deck. B. Roof insulation at new roof deck. C. Modified bitumen membrane. D. Fluid applied
SECTION 07 54 23 PVC SINGLE PLY ROOFING
SECTION 07 54 23 PVC SINGLE PLY ROOFING PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Attached GENERAL CONDITIONS, GENERAL NOTES, INSTRUCTIONS TO BIDDERS, AND BID FORM are components of this section. B. Section
synthetic waterproofing systems
GreeN roofing Waterproofing systems with SINTOFOIL TpO/Fpa membranes synthetic waterproofing systems Recently, green roofing systems have been attracting increasing interest because of the significant
0845 0098 980 www.nicholsonsts.com
0845 0098 980 www.nicholsonsts.com ROOFTRAK The IFP is revolutionising the way we fix things to roofs. Technical Director of a leading UK roofing system manufacturer The ROOFTRAK-IFP A revolutionary solution
Maintenance & repair Solutions
Maintenance & repair Solutions low-slope ROOFING We ve got what you need in the sizes you need them and the options to match the results that building owners want Seal-fast Temporary roof sealer Now you
G VYCOR DECK PROTECTOR
G VYCOR DECK PROTECTOR Self-Adhered Flashing Contractor s Guide DECKS AND DETAIL AREAS For longer lasting decks, install Grace Vycor Deck Protector. FROM THE MAKERS OF G Ice & Water Shield What Self-Adhered
ENGINEERING SPECIFICATION PULTRUDED DYNAFORM FIBERGLASS STRUCTURAL SHAPES. July 1, 2008 Revision 2
ENGINEERING SPECIFICATION PULTRUDED DYNAFORM FIBERGLASS STRUCTURAL SHAPES 1 PART 1 - GENERAL 1.0 GENERAL 1.1 REFERENCES: SECTION 06610 FIBERGLASS REINFORCED PLASTICS (FRP) FABRICATIONS PULTRUDED FIBERGLASS
BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION
07560 BUR BUILT-UP ROOF COATING SMOOTH and GRANULE SURFACE SPECIFICATION PART 1: GENERAL 1.01 SCOPE: To extend the useful service life of the aged or new asphalt built-up roof system and to reduce cooling
The Perfect Fit For Metal Retrofit
D u r o - S h i e l d M e t a l R e t r o f i t R o o f i n g S y s t e m The Perfect Fit For Metal Retrofit Lock out leaks. Lock in your investment. Has time caught up with your metal roof? There are
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION
HEB 38 BLANCO AND WEST AVENUE FLUID APPLIED EPDM RUBBER ROOF RECOVERY SYSTEM APPLICATION David Marut TEST CASE REPORT July 1, 2014 Case Study Pro Guard EPDM Super Coat Liquid Rubber Membrane Roof System
SCENIC VIEW SV 10 SECTION 08 87 13 SOLAR CONTROL FILMS
PART 1 GENERAL SCENIC VIEW SV 10 SECTION 08 87 13 SOLAR CONTROL FILMS 1.1 SUMMARY A. Optically clear dual reflective, neutral sputtered and aluminum metallized polyester film for solar control. 1.2 RELATED
Multi-layer Insulation Blanket for Roofs
Multilayer Insulation Blanket for Roofs Thermal Insulation in a 40mm thin, flexible, multilayer membrane Meets requirements of L1A, L1B 2010 In accordance with BR443 NHBC Acceptance Pitched & Flat roof
peel adhesion 2 breaking load 4 rolling ball 6 shear adhesion 7 carton test 9 summary test methods 11
CONTENT peel adhesion 2 breaking load 4 rolling ball 6 shear adhesion 7 carton test 9 summary test methods 11 PEEL ADHESION Testing the peel adhesion on stainless steel 1. Definition Peel adhesion - The
Residential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
Product Guide Specification
Reef Industries, Inc. 9209 Almeda Genoa Rd. Houston, Texas 77075 Toll Free (800) 231-6074 Phone (713) 507-4251 Fax (713) 507-4295 Web Site www.reefindustries.com E-Mail [email protected] Product Guide
PVC ROOFING SYSTEMS BUILDING SOLUTIONS A SINGLE SOURCE FOR SINGLE-PLY ROOFING
V E R S I C O R O O F I N G S Y S T E M S PVC ROOFING SYSTEMS BUILDING SOLUTIONS A SINGLE SOURCE FOR SINGLE-PLY ROOFING Versico, PO Box 1289, Carlisle, PA 17013 Tel: 800.992.7663 Fax: 717.960.4036 Web:
Seamless Waterproofing. Systems
Seamless Waterproofing Systems Pitched/Corrugated Roofs Liquid Rubber Instant Set is the ideal solution for pitched roof waterproofing providing a seamless fully bonded finish. RapidRoof is suited to smaller
Regulations Detail Sheet 1
Designated by Government to issue European Technical Approvals Esha (UK) Ltd Esha House St Mary s Business Park Albany Road Market Harborough Leicestershire LE16 7EB Tel: 01858 410372 Fax: 01858 410572
LANGLEY S ROOF WATERPROOFING MEMBRANES PARADIENE/PARAFOR ROOF WATERPROOFING SYSTEMS
Langley Waterproofing Systems Ltd Bishop Crewe House North Street Daventry Northants NN11 4GH Tel: 01327 704778 Fax: 01327 704845 e-mail: [email protected] website: www.langley.co.uk APPROVAL INSPECTION
The existing roof angle change terminations and flashings when sound and intact can be reused.
January 2, 2015 Summary Specification Re-Skinning an Existing Roof Maintenance and Repair Warranty Upgrade for Up to 30 Years Re-Skinning Over an Existing Roof with a New C-EPDM Membrane Using The Existing
Your guide to home maintenance. Flat Roofs
Your guide to home maintenance Flat Roofs Your guide to home maintenance is a series of information leaflets that gives you all the information you need to keep your home in tiptop condition. Flat Roofs
BLACK JACK ALL WEATHER ROOF COATING
PAGE: 1 of 6 PRINT DATE: 16/09/2004 BLACK JACK ALL WEATHER ROOF COATING DESCRIPTION BLACK JACK ALL WEATHER ROOF COATING is a solvent based, full bodied black brushable compound with added fibres for reinforcement.
A. Roofing Terminology: Definitions in ASTM D 1079 and glossary in NRCA's "The NRCA Roofing and Waterproofing Manual" apply to work of this Section.
SECTION 075419 POLYVINYL CHLORIDE (PVC) ROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01