TEST PROCEDURE FOR FIELD WITHDRAWAL RESISTANCE TESTING



Similar documents
STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES

ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS

STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS

PRODUCT CONTROL SECTION

CITY OF FLORIDA CITY Building and Zoning Department 404 West Palm Drive Florida City, FL ROOFING PERMIT APPLICATION

APPENDIX 1: ATTACHMENT REQUIREMENTS FOR WIND UPLIFT RESISTANCE

1. Adhered KEE membrane roofing system. 2. Mechanically fastened KEE membrane roofing system.

PART 1 GENERAL 1.1 SECTION INCLUDES

ANSI/SPRI WD-1 Wind Design Standard Practice for Roofing Assemblies. Table of Contents. 1.0 Introduction Methodology...2

Georgia State University. Urban Life Building Roof Replacement

Owner's Manual & Assembly Instructions

ICC-ES Evaluation Report

4 X 1 3/8 X 3/16 CHANNEL x 34.9 x 4.8 CHANNEL

foot skylight) is enough to knock a worker off their feet. A 10 mph wind gust on a 5 x 6 skylight develops a wind force of 270 lbs.

CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...

NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

Hilti KWIK HUS-EZ I (KH-EZ I) Internally Threaded Carbon Steel Screw Anchor

UPDATE October 8, 2012 Chicago Roofing Contractors Association CHICAGOLAND S ROOFING, INSULATION, AIR-BARRIER REQUIREMENTS

Residential Deck Safety, Construction, and Repair

Chapter 3 Pre-Installation, Foundations and Piers

AMERICAN GOTHIC PLAYHOUSE

UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC

SECTION ALUMINUM FRAMED ENTRANCES and STOREFRONTS. System 402 Flush-Glazed Screw Spline Storefront

Fastener Loads for Plywood Screws Number E830D August 2005

ROOF CONSTRUCTION SCIENCE (METCT092)


TEST REPORT. Report No.: A Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept

T 549. WORKING GROUP CHAIRMAN N/A; reaffirmed SUBJECT RELATED

TEST REPORT. Report No.: B Rendered to: CROFT, LLC. Magnolia, Mississippi. PRODUCT TYPE: Aluminum Single Hung Window SERIES/MODEL: 95

Roof Inspection Report 3840 Greenway Circle, Lawrence Kansas, Sauer-Danfoss Building

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC

APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET

SECTION STANDING SEAM METAL ROOF

SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION

Re-Cover Board-3. Insulation for Above the Deck ROOF WALL SPECIALTY

TABLE OF CONTENTS. Roof Decks 172 B, BA, BV Deck N, NA Deck. Form Decks FD,.6 FDV Deck 1.0 FD, 1.0 FDV Deck 1.5 FD Deck 2.0 FD Deck 3.

09/07/07 GLASSFIBER REINFORCED CEMENT (GRC) C. S. I. Spec Master Spec Page 1

Hilti, Inc South 122 nd East Avenue Tulsa, OK

Hilti, Inc South 122 nd East Avenue Tulsa, OK

NEW ELECTRICAL SUBSTATION Building 300 SECTION ETHYLENE-PROPYLENE-DIENE-MONOMER ROOFING WORK

COMMONLY USED RESIDENTIAL BUILDING CODES

PERFORMANCE TEST REPORT. Rendered to: BAMCO INC. PRODUCT TYPE: ACM Wall Panel Systems

Low-slope reroofing guidelines

Guidelines for Earthquake Bracing of Residential Water Heaters

Guidelines for Earthquake Bracing Residential Water Heaters

Design of Cold-Formed Steel Shear Walls

Introduction...COMB-2 Design Considerations and Examples...COMB-3

SMALL SCALE ASTM E 119/UL 263 ONE HOUR FIRE TESTING FOR MARINOWARE ON JOIST-RITE WITH ARMOROC FLOOR VTEC # TESTED: MAY 23, 2008 REVISION

SECTION MODIFIED BITUMINOUS MEMBRANE ROOFING. A. Vapor barrier (base ply); cover board at existing roof deck.

Window Installation Instructions

SECTION FLUID APPLIED ROOFING (LIGHT TRAFFIC DECKS OVER CONCRETE)

STAYFLEX CORROSION CONTROL AND THERMAL INSULATION SYSTEM

ENGINEERING SPECIFICATION FIBERGRATE MOLDED GRATING. January 24,

International Greenhouse Company

PERFORMANCE TEST REPORT. Rendered to: TREMCO INCORPORATED. SERIES/MODEL: Proglaze ETA PRODUCT TYPE: Engineered Transition Assembly

Ver. 2. Guide to. Inspecting Residential Brick Veneer

Discipline: Structural Issued

TEST REPORT. Rendered to: INTEX MILLWORK SOLUTIONS, LLC. For: Rigid Cellular PVC Guardrail System Hampton RS40

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

(800) (562) A Subsidiary of the International Code Council *Revised April 2014

Metal Roofing Practical Design

The project completion date has not been impacted by the work in this potential change item.

PART E SPECIFICATIONS

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: AMERICAN PRODUCTS, INC Tampa, Florida

Table of Contents. Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide

Residential Decks. Planning and Development Services Department

From the Office of: MAHLUM ARCHITECTS 71 Columbia Street Floor 4 Seattle, WA 98104

Dollars & Sense of Compliance!

Roof insulations must perform the basic function of helping to control fluctuations in building interior temperature

ROOF DRAINS TABLE OF CONTENTS

Owner's Manual & Assembly Instructions

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: EAGLE WINDOW & DOOR COMPANY

REQUEST FOR PROPOSALS

The following excerpt are pages from the North American Product Technical Guide, Volume 2: Anchor Fastening, Edition 16.

SECTION METAL ROOF & WALL PANELS

Product Guide Specification

Canvas Office Landscape Wall Strip Installation and Disassembly for Recycling Instructions

Owner's Manual & Assembly Instructions

AST M F /GSA TS01 T EST R EPO R T. Rendered to: UNI T E D ST A T ES A L U M INU M

MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015

Storage Store the siding in a dry and ventilated area. Do not place it directly on the ground. Always cover the siding after a day s work.

PERIMETER FLASHING. Table of Contents

Smooth cap sheet SQ $ Smooth cap sheet SQ $ Smooth cap sheet SQ $ Smooth cap sheet SQ $ 36.

Solicitation DTFACN-11-R Attachment #9

WATER PENETRATION TESTING OF STUCCO ON CONCRETE MASONRY CONSTRUCTION

LEGACY REPORT. (800) (562) A Subsidiary of the International Code Council RETAINED ON U.S.

PANELIZED HOME INSTALLATION GUIDELINE

PERFORMANCE TEST REPORT. Rendered to: UNITED STATES ALUMINUM CORPORATION. SERIES/MODEL: 450 Center Glaze PRODUCT TYPE: Aluminum Curtain Wall

SECTION ALUMINUM HANDRAIL AND RAILING SYSTEMS WITH DECORATIVE METAL PANEL INFILLS

RESEARCH REPORT RP04-2 NOVEMBER 2004 REVISION Committee on Specifications for the Design of Cold-Formed Steel Structural Members

Superform Products Ltd.

TSL Professional Services

THERMOTEK SELF ADHESIVE MEMBRANE +G2 OVER WOOD SYSTEM DESCRIPTION SELF ADHESIVE OVER WOOD (8YR) BS-SA/CS

PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC.

Wind Mitigation Inspection

Seismic Technical Guide

CHAPTER 7: Building Systems ROOFING SYSTEMS

EXPANDED POLYSTYRENE (EPS) INSULATION BOARD SPECIFICATIONS

Transcription:

TESTING APPLICATION STANDARD (TAS) No. 105-98 TEST PROCEDURE FOR FIELD WITHDRAWAL RESISTANCE TESTING 1. Scope 1.1 This Testing Application Standard (TAS) covers procedures for withdrawal resistance testing of fasteners used for attachment of various components to various substrate materials. 1.2 All testing shall be conducted by an approved testing agency, and all test reports shall be signed by a Professional Engineer or Registered Roof Consultant. 2 Definitions 2.1 For definitions of terms used in this application standard, refer to ASTM D 1079; Chapters 2, & 15 of the Florida Building Code, Building. 3. Referenced Documents 3.1 Testing Application Standard TAS 105 Appendix A, Field Withdrawal Resistance Test Results Report. 4. Terminology & Units 4.1 Initial Failure: The point at which the recorded load decreases by 5% or more of the most recent, highest reading. 4.2 Units - For conversion of U.S. customary units to SI units, refer to ASTM E 380. 5. Significance and Use 5.1 The test procedures outlined in this TAS provides a means of determining whether a particular mechanical fastener, when used to attach any Roofing Component to a specific substrate, provides sufficient resistance to static uplift force to meet the wind-load requirements of this code for a specific building. 6. Apparatus 6.1 Insulation and Membrane Attachment Testing 6.1.1 The test apparatus shall consist of a hydraulic or mechanically operated dynamometer ('pull-tester') fitted with a hydraulic gauge cell to measure force. The resulting force shall be recorded on a digital or analog gauge. For anchor or base sheet fasteners (commonly referred to as 'base ply' fasteners) and other fastener anchors with an anticipated withdrawal resistance less than 100 lbf., the tester and test procedure shall be in compliance with the requirements set forth in this TAS. 6.1.2 Hydraulic dynamometers shall be operated by a screw or pump handle or shall be automatically rising at 2 in. (50 mm) + 0.1 in. per minute for steel and wood decks and 1 / 2 in. (12.5 mm) + 0.1 in. per minute for concrete, gypsum and cementitious wood fiber decks. 6.2 Anchor or Base Sheet Attachment Testing 6.2.1 The test apparatus shall consist of a minimum 3 V2 in. x 3 V2 in. octagon nylon mesh or 15 mil coated polyester fabric test pad, with a center hole through which the fastener is driven into the deck. The internal hole shall be of sufficient size to allow the fastener legs to pass through without touching the test pad. 6.2.2 The test pad shall be reinforced where attached to the dynamometer to resist tearing. 6.2.3 The dynamometer shall be hydraulic or mechanical and shall be fitted with a hydraulic gauge cell. The resulting force shall be recorded on a digital or analog gauge. The dynamometer shall automatically rise at 1 / 2 in. (12.5 mm) + 0.1 in. per minute for lightweight concrete, gypsum and cementitious wood fiber testing and 2 in. (50 mm) + 0.1 in. per minute for all other nailable deck types. 6.3 Hydraulic dynamometers ('pull-testers') shall be calibrated within three (3) months prior to FLORIDA BUILDING CODE TEST PROTOCOL HVHZ (TAS) 105-98.1

conducting the test procedures outlined in this TAS. Facsimiles of the calibration shall be kept with the tester for examination by the authority having jurisdiction, upon request. A copy of the calibration certificate shall be attached to each test report. Calibration shall be in compliance with ASTM E 74, Grade B. 7. Test Limitations and Precautions 9. Calculations 9.1 Mean Failure Load (F) and Sample Standard Deviation 9.1.1 Determine the mean failure load (F) and sample standard deviation (SF) using tabulated data and the following equations. 7.1 This TAS may involve hazardous operations and equipment. This TAS does not address all of the safety problems associated with its use. It is the responsibility of the user to consult and establish appropriate safety and health practices and determine the applicability of regulatory limitations prior to use. 8. Test Procedure for Anchor or Base Sheet, Insulation, and Membrane Attachment testing 8.1 On roof decks of 100 squares or less, ten (10) withdrawal resistance tests shall be conducted, not less than three (3) of which shall be in the perimeter areas @, three (3) in corner areas @, the remainders in the field areas as defined in ASCE 7-98. 8.2 For every additional 50 squares, an additional three (3) withdrawal resistance tests shall be conducted. (This ratio of 50:3 shall be maintained with each additional increase in samples.) F = mean failure load (lbf); S F = sample standard deviation (lbf); N = total number of pulls; Fi; = recorded failure load on pull number i; and, i = 1, 2, 3,, N = pull number 9.2 Minimum Characteristic Resistance Force (F') 9.2.1 Determine the minimum characteristic resistance force (F') using the following equation. 8.3 The number of test samples required shall be increased by an additional 25% for all gypsum, lightweight insulating concrete and cementitious wood fiber deck types. 8.4 Testing shall also take place in any low areas that are, or may be, subjected to ponding water. All such areas shall be noted on a roof plan attached to the final test report. 8.5 If more than one deck type is on a single roof area, each deck type shall be treated as a separate roof area. 8.6 Stair towers, mechanical penthouses and mechanical rooms shall have a minimum of four (4) withdrawal resistance tests, two of which shall be taken at perimeter areas 2 & 3, as defined in ASCE-7. where, F' _ F t vp v N P S = minimum characteristic resistance force (lbf); = mean failure load (lbf); = t-estimator based on 95% precision level; = degrees of freedom = (N-l); = total number of pulls; = probability level = 95%; and, = sample standard deviation. 9.2.1.1 The t-estimator noted above is a function of probability (P) and degrees of freedom (v). Values for a 95% probability level are noted in Table 1, below. (TAS) 105-98.2 FLORIDA BUILDING CODE TEST PROTOCOL HVHZ

TABLE 1 VALUES FOR T-ESTIMATOR AT 95% PROBABILITY degrees ol freedom (v) t v'.95 9 2.26 10 2.23 11 2.20 12 2.18 13 2.16 14 2.15 15 2.13 16 2.12 17 2.11 18 2.10 19 2.09 20 2.09 21 2.08 22 2.07 23 2.07 24 2.06 25 2.06 26 2.06 27 2.05 28 2.05 29 2.05 30 2.04 40 2.02 60 2.00 1 degrees of freedom is equal to the number of pulls minus one (v = N-l) statistical analysis of the raw data, including the mean failure load; the sample standard deviation; and the minimum characteristic resistance force. 10.1.6 If a hole is pre-drilled, data on the size and type of bit shall be included together with the depth of the hole and the type of equipment used to pre-drill. 10.1.7 If the fastener is self-drilling, include the type and speed the installation tool. Literature on the fastening device shall be attached to the test report. 10.1.8 Failure of the fastener shall be recorded at 'initial failure load'. The ultimate failure load (the greatest resistance to pullout recorded prior to withdrawal) shall not be recorded. 10.1.9 Indicate on a roof plan the locations where all withdrawal resistance tests were taken with an 'identifier' and include the 'identifier' with the data submitted. 10. Report 10.1 The final test report shall include the following items: 10.1.1 Certification of dynamometer ('pulltester') calibration within three (3) months prior to conducting the test, including calibration data. 10.1.2 The final test report shall be signed and sealed by a Professional Engineer or Registered Roof Consultant. 10.1.3 A description of the name, location, height, dimensions and deck type(s) and/or substrate type(s) of the building on which the test is being conducted. 10.1.4 The fastener type and manufacturer and a description of the Roofing Component which the fastener is intended to secure. 10.1.5 The number of withdrawal resistance tests; the tabulated test results; and a FLORIDA BUILDING CODE TEST PROTOCOL HVHZ (TAS) 105-98.3

TESTING APPLICATION STANDARD (TAS) 105-98 APPENDIX A FIELD WITHDRAWAL RESISTANCE TEST RESULTS REPORT GENERAL INFORMATION: Job Name: Job Address: Contact Individual at job site (if any): TESTING AGENCY/EQUIPMENT INFORMATION: Note: The undersigned acknowledges that all testing has been conducted and results have been reported in compliance with TAS 105 or TAS 105 Appendix A. Testing Agency Address: Name: Telephone: ( ) - - Fax: ( )- - Representative Name: Title: Signature: Test Apparatus (General Description): (TAS) 105-98.4 FLORIDA BUILDING CODE TEST PROTOCOL HVHZ

(TAS) No. 105- BUILDING/ROOF SYSTEM INFORMATION: Area No. Roof Area Height: height = ft Roof Area Dimensions: length = ft second largest dimension = ft total roof area = ft 2 = sqs. perimeter area = ft 2 (see RAS 117) BUILDING/ROOF SYSTEM INFORMATION: Area No. Roof Area Height: height = ft Roof Area Dimensions: length = ft second largest dimension = ft total roof area = ft 2 = sqs. perimeter area = ft 2 (see RAS 117) BUILDING/ROOF SYSTEM INFORMATION: Area No. Roof Area Height: height = ft Roof Area Dimensions: length = ft second largest dimension = ft total roof area = ft 2 = sqs. perimeter area = ft 2 (see RAS 117) Note: If more than three roof areas are tested, attach additional page(s) having this format to identify all roof areas. FLORIDA BUILDING CODE TEST PROTOCOL HVHZ (TAS) 105-98.5

FASTENER INSTALLATION INFORMATION: Is the fastener a self driller? yes no If yes, list the type of tool used for fastener installation: Speed of Tool: rpm's TEST INFORMATION: Number of Test Conducted: n = See Section 8 of TAS 105 Note the location of all tests on 'Building Information' Detail #2, attached.. (TAS) 105-98.6 FLORIDA BUILDIND CODE TEST PROTOCOL HVHZ

FIELD WITHDRAWAL RESISTANCE TEST RECORDING SHEET Area No. Fastener Type: (Refer to deck dimensions referenced on page ) Fastener Manufacturer: Component to be secured : Pre-drilled? Yes No Insulation Membrane If Yes: Drill bit size: " dia. Anchor or Base Sheet Woodblocking Hole Depth: " Metal Profiles See Section 8 to determine number of tests (If drill bit is high tolerance, include range in1/1000"tolerances) SAMPLE NO. PLAN IDENTIFIER INITIAL FAILURE LOAD (Ibf) HELD PERIMETER OR CORNER AREA (circle one) FLORIDA BUILDING CODE TEST PROTOCOL HVHZ (TAS) 105-98.7

STATISTICAL ANALYSIS: Mean Failure Load: F = lbf Sample Standard Deviation: Sp = lbf Minimum-Characteristic Resistance Force: F' = lbf Notes: 1. Use of the results herein to determine the required number of fasteners for insulation attachment or an acceptable anchor or base sheet fastener spacing, as outlined in TAS 117, shall utilize the minimum characteristic resistance force (F'), determined in compliance with Section 9 of TAS 105. No margin of safety shall be applied to field withdrawal resistance test results determined in compliance with TAS 105. 2. A safety factor of 2 to 1 shall be applied to all results of laboratory testing. 3. The following pages shall be completed for each roof area and included with all Field Withdrawal Resistance Test Recording Sheets. Notes: (TAS) 105-98.8 FLORIDA BUILDING CODE TEST PROTOCOL HVHZ