MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015
|
|
|
- Lenard Nicholson
- 10 years ago
- Views:
Transcription
1 MAJOR 2015 MN RESIDENTIAL CODE CHANGES Effective Date: January 24 th, 2015 **Disclaimer: This document is to serve as informational purposes only. This is not a code book or a final interpretation of the code by the building official. This is to serve as a guide for some of the major code changes that will go into effect on January 24 th, Restrictions on Existing Building minimum ceiling heights R305.2 Minimum ceiling heights, existing buildings. Alterations to existing basements or portions thereof shall have a ceiling height of not less than 6 feet 4 inches including obstructions. Minimum headroom in all parts of the stairway shall not be less than 6 feet 4 inches Summary: existing basement finishes will have to follow this code. Anything shorter than the minimum will not qualify as a finished floor, and will be treated as a crawl space. R Replacement Windows. Emergency Escape and Rescue Openings Replacement windows installed in buildings regulated by International Residential Code shall be exempt from the maximum sill height requirements of Sections R310.1, including subsections R , R , and R if the replacement window is the manufacturer's largest standard size window that will fit within the existing frame or existing rough opening. The replacement window shall be the same operating style as the existing window or a style that provides for an equal or greater window opening area than the existing window. R Licensed facilities. Windows in rooms used for foster care or day care licensed or registered by the State of Minnesota shall comply with the provisions of section R , or all of the following conditions, whichever is more restrictive: 1. Minimum of 20 inches in clear opening width; 2. Minimum of 20 inches in clear opening height; 3. Minimum of 648 square inches (4.5 square feet) clear opening; and 4. Maximum of 48 inches from the floor to the sill height.
2 The replacement window shall be the same operating style as the existing window or a style that provides for an equal or greater window opening area than the existing window. Summary: This is similar to the existing 2007 codes, however licensed facilities are addressed specifically in this section. Any windows installed in any of the listed facilities above must meet the requirements of R The operating style mentioned in the amendment language refers to the type of window (i.e. casement, double-hung ) as well as the operating style of the hardware. Guards and Window Fall Protection R Where required. Guards shall be located along the open sides of floors, stairs, ramps and landings, that are located more than 30 inches (762 mm) measured vertically to the floor or grade below. Insect screening shall not be considered as a guard. R312.2 Window fall protection. Window fall protection shall be provided in accordance with Section R and R R Window sills. In dwelling units, where the lowest part of the opening of an operable window is located more than 72 inches (1829 mm) above the finished grade or surface below, the lowest part of the window opening shall be a minimum 36 inches (914 mm) above the finished floor of the room in which the window is located. Operable sections of windows shall not permit openings that allow passage of a 4-inch-diameter (102 mm) sphere where such openings are located within 36 inches (914 mm) of the finished floor. 1. Windows whose openings will not allow a 4-inch-diameter (102 mm) sphere to pass through the opening when the opening is in its largest opened position. 2. Openings that are provided with window fall prevention devices that comply with ASTM F Windows that are provided with window opening control devices that comply with Section R Replacement windows.
3 Summary: When there is a window that is installedd more than 72 inches above the exterior grade or floor, it must be a minimum of 36 from the floor. If it is lower than the minimum, it can t allow passage of a 4 sphere unless it meets the requirements of the exceptions listed. Residential Fire Sprinklers R313.1 Townhouse automatic fire sprinkler systems. An automatic residential fire sprinklerr system shall be installed in townhouses. Exception: An automatic residential fire sprinkler system shall not be required when additions or alterations are made to existing townhouses that do not have an automatic residential fire sprinkler system installed. R Design and installation. Automatic residential fire sprinkler systems for townhouses shall be designedd and installed in accordance with Section P2904 or NFPA 13D.
4 R313.2 One- and two-family dwellings automatic fire systems. An automatic residential fire sprinkler system shall be installed in one- and two-family dwellings. 1. Detached one-family dwelling, less than 4500 square feet of floor area. Floor area shall include all floors and basements, excluding garages. 2. An automatic residential fire sprinkler system shall not be required if additions, or alterations, or repairs are made to existing buildings that do not have an automatic residential sprinkler system installed. R Design and installation. Automatic residential fire sprinkler systems shall be designed and installed in accordance with IRC section P2904 or NFPA 13D. R313.4 State-licensed facilities. One- and two-family dwellings and townhouse buildings containing facilities required to be licensed or registered by the state of Minnesota shall be provided with an automatic fire sprinkler system required by the applicable licensing provisions of that agency or according to this part, whichever is more restrictive. Summary: All New 2 family dwellings, such as duplexes and townhouses, must be sprinklered. All single family homes that have a square footage of 4500 sf or more must be sprinklered. Each system must be designed to meet the requirements of the IRC P2904 or NFPA 13D. See the attached chart to determine if the potential structure meets the requirements. Fire Protection of Floors R501.3 Fire protection of floors. Floor assemblies, not required elsewhere in this code to be fire-resistance rated, shall be provided with a 1/2-inch (12.7 mm) gypsum wallboard membrane, 5/8-inch (16 mm) wood structural panel membrane, or equivalent on the underside of the floor framing member. 1. Floor assemblies located directly over a space protected by an automatic sprinkler system in accordance with Section P2904, NFPA 13D, or other approved equivalent sprinkler system. 2. Floor assemblies located directly over a crawl space not intended for storage or fuel-fired appliances. 3.Portions of floor assemblies can be unprotected when complying with the following:
5 3.1. The aggregate area of the unprotected portions shall not exceed 80 square feet per story 3.2. Fire blocking in accordance with Section R shall be installed along the perimeter of the unprotected portion to separate the unprotected portion from the remainder of the floor assembly. 4. Wood floor assemblies using dimension lumber or structural composite lumber equal to or greater than 2-inch by 10-inch (50.8 mm by 254 mm) nominal dimension, or other approved floor assemblies demonstrating equivalent fire performance. Summary: Any dimensional or structural lumber that is smaller than a 2x10 or that is an engineered product must be protected by a minimum of ½ inch drywall or as noted above. See attached sheets for alternative products and installation methods that have been approved for this use. Smoke Alarms R Alterations, repairs and additions. An individual dwelling unit shall be equipped with smoke alarms located as required for new dwellings when: 1. alterations, repairs (including installation or replacement of windows or doors), or additions requiring a permit occur; or 2. one or more sleeping rooms are added or created in existing dwellings 1. Work involving the exterior surfaces of dwellings, such as the replacement of roofing or siding, or the addition of an open porch or deck, or chimney repairs. 2. Installation, alteration or repairs of plumbing or electrical, mechanical systems are exempt from the requirements of this section. Summary: Any time there is alterations or repairs done to a dwelling unit, including the replacement of windows or doors, the new requirements for smoke detectors must be followed, other than the exceptions listed above. Specified Compressive Strength of Concrete Footings Concrete in footings must meet the following requirements: 5,000 psi compressive strength concrete footing or; 3,000 psi compressive strength concrete footing with an approved admixture that provides a water and vapor resistance at least equivalent to 5,000 psi concrete. Summary: This will need to be verified at the jobsite for the strength and admixture.
Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers
City of Duluth Preparation for 2015 Residential Code Changes Discussion with Local Builders and Designers Thank you for taking the time to join us today. We know you are busy and your time is valuable.
The replacement or modification of existing windows shall comply with the following requirements:
City of La Habra Heights Building Division 1245 N. Hacienda Road La Habra Heights, CA 90631 Office: (562) 694-6302 ext. 228 Fax: (562) 690-5010 WINDOW REPLACEMENT 2010 CALIFORNIA RESIDENTIAL CODE (CRC)
WINDOW AND DOOR REPLACEMENT REQUIREMENTS
WINDOW AND DOOR REPLACEMENT REQUIREMENTS Should you have any questions after reading the following information, please call the Building Inspection Department at 651-439-4439 to discuss the topics of concern.
BUILDING PERMIT SPECIFICATIONS
BUILDING PERMIT SPECIFICATIONS The below noted requirements are based upon La Plata County Building Code. These specifications are not intended as a complete set of requirements, but are intended to provide
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems. April 2013
Design Options (Tradeoffs) Allowed by the 2012 Building Codes for Properties with Sprinkler Systems April 2013 The National Multi Housing Council and the National Apartment Association (NMHC/NAA) have
COMMONLY USED RESIDENTIAL BUILDING CODES
COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 STAIRWAYS 46. LANDINGS. Section R311 IRC 2009 R311.7.5 Landings for stairways. There shall be a floor or
Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS
Florida Building Code 2004 SECTION 1009 STAIRWAYS AND HANDRAILS 1009.1 Stairway width. The width of stairways shall be determined as specified in Section 1005.1, but such width shall not be less than 44
Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited**
PHRC Webinar Series Tuesday, September 9, 2014 1:00 pm Requirements for Fire Protection of Light Weight Floor Systems **Act 1 Revisited** Presented by: Bryan Heitzmann Credit(s) earned on completion of
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us
http://www.iccsafe.org/
Sections R311 and R312 from the 2006 International Residential Code These sections of Chapter 3 of the 2006 International Residential Code for One and Two Family Dwellings (R311 and R312) including the
How To Make A House Safe
1 RESIDENTIAL Screen Enclosures Orange County Residential Code Compliance Alternative design method for screen enclosures R301.2.1.1.3 PLAN REVIEW Engineered plans must state that the Alternative Design
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Basement Finishing Guide Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
Residential Decks. Planning and Development Services Department
Building Safety Division 8500 Santa Fe Drive Overland Park, KS 66212 (913) 895-6225 Fax (913) 895-5016 Email: [email protected] Planning and Development Services Department Residential Decks
EXISTING BUILDINGS AND STRUCTURES
EXISTING BUILDINGS AND STRUCTURES There are no margin bars shown in this chapter due to its substantial revision. SECTION AJ1 ADMINISTRATION SECTION AJ101 PURPOSE AND INTENT AJ101.1 Scope. The provisions
Single Family Residential Building Permit Questions & Answers
Single Family Residential Building Permit Questions & Answers Prepared by Dept. of Public Works Revised 07/01/13 200 East Park Street Edwardsville, IL 62025 (618) 692-7535 (618) 692-7505(Fax) Hours: Monday
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS
RESIDENTIAL PLUMBING ALTERATIONS PERMIT REQUIREMENTS The following guidelines are intended to assist with the permit acquisition process with regard to Plumbing Alterations. Not all information, or additional
How To Build A Basement House
Single Family Basement Finish Purpose of Guide The purpose of this guide is to assist you in the permit process for your project. This handout is intended as a basic plan submittal under the 2009 International
H:\forms\handouts\bldg049 1 of 11 Revised Mar 2/15/dh
Accessory Apartment Construction Guide For Single Detached Dwelling and Semi-Detached Dwellings that have been in existence for at least five (5) years Notes: Buildings that are less than five (5) years
Building Codes Update: The 2009 International Fire Code and the Apartment Industry
! Building Codes Update: The 2009 International Fire Code and the Apartment Industry Apartment operators and developers should be aware of organizational changes in the 2009 edition of the International
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov
City of Riverside Building & Safety Division Phone: (951) 826-5697 www.riversideca.gov BUILDING CODE REQUIREMENTS FOR CHILD DAY CARE The purpose of this document is to provide the user with a basic level
2010 FLORIDA BUILDNG CODE, FIRE AND LIFE SAFETY i
2010 FLORIDA BUILDNG CODE, FIRE AND LIFE SAFETY i Changes between the 2006 and 2009 Editions of the International Codes account for the vast majority of changes to the 2010 Florida Building Code. In many
Building Code Clarifications - 7. Fire Resistance
Building Code Clarifications - 7. Fire Resistance 7.1 (15-12-030) Use of combustibles in Type III construction roof assemblies Code Section (15-12-030) Use of Combustibles was revised on May 17, 2000,
Chapter 20.10 LINCOLN RESIDENTIAL BUILDING CODE
Chapter 20.10 LINCOLN RESIDENTIAL BUILDING CODE Sections: 20.10.010 Adoption of International Residential Code. 20.10.015 Section R101 Amended; Title, Scope and Purpose. 20.10.020 Section R102.1 Amended;
FIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS
CHAPTER 46 FIRE AND LIFE SAFETY REQUIREMENTS FOR EXISTING BUILDINGS SECTION 4601 GENERAL 4601.1 Scope. The provisions of this chapter shall apply to existing buildings constructed prior to a state building
Certification: Building Plans Examiner. Exam ID: B3
Certification: Building Plans Examiner Exam ID: B3 Scope: A Building Plans Examiner will be responsible for reviewing submitted plans to determine if they meet the requirements of the various Building
CHAPTER 9 FIRE PROTECTION SYSTEMS
CHAPTER 9 FIRE PROTECTION SYSTEMS SECTION 901 GENERAL 901.1 Scope. Provisions of this chapter shall govern the application, design, installation, testing and maintenance of automatic sprinklers, standpipes
Applications for building permits will not be reviewed until all of the required information has been submitted.
NOTICE: Applications for building permits will not be reviewed until all of the required information has been submitted. Once all items are submitted a minimum of ten (10) working days are required to
INFORMATION BULLETIN NO.
Requirements for Plans Review Submittal, One- and Two-Family Dwellings INFORMATION BULLETIN NO. 100 (June 26, 1998, Revised March 26, 2009) City Planning & Development - Development Services City of Kansas
Building Department John Fiedler Construction Official Ext. 211. SAMPLE GUIDE FOR 1&2 FAMILY DWELLING BASEMENTS Rev 4-3-2014
TOWNSHIP OF HILLSBOROUGH COUNTY OF SOMERSET Hillsborough Township Municipal Complex The Peter J. Biondi Building 379 South Branch Road Hillsborough, NJ 08844 P: (908) 369-4313 F: (908) 369-3954 Building
2880 International Circle Colorado Springs, CO 80910 Telephone 719-327-2880. Executive Summary. 2011 Pikes Peak Regional Building Code Revisions
2880 International Circle Colorado Springs, CO 80910 Telephone 719-327-2880 Web address www.pprbd.org Executive Summary 2011 Pikes Peak Regional Building Code Revisions October 21 st 2015 This document
Single Family Residential Basement Finish
How to Use This Guide Building Guide Pottawattamie County Planning & Development Department Building & Safety Division Single Family Residential Basement Finish Provide two (2) sets of plans and complete
INTERNATIONAL RESIDENTIAL CODE 2006 Third Edition
WASHINGTON STATE BUILDING CODE CHAPTER 51-51 WAC INTERNATIONAL RESIDENTIAL CODE 2006 Third Edition Washington State Building Code Council Copies of the State Building Codes and complete copies of the 2006
FIRE-RESISTANCE-RATED CONSTRUCTION
CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY
MINNESOTA STATE DEPARTMENT OF PUBLIC SAFETY State Fire Marshal Division 444 Cedar Street, Suite 145, St. Paul, Minnesota 55101-5145 Phone: 651/201-7200 FAX: 651/215-0525 TTY: 651/282/6555 Internet: http://www.fire.state.mn.us
FIRE-RESISTANCE-RATED CONSTRUCTION
CHAPTER 7 FIRE-RESISTANCE-RATED CONSTRUCTION SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials and assemblies used for structural fire resistance and fire-resistance-rated
This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.
Residential Decks Community Development Department Building Inspections Division 5200 85 th Avenue North / Brooklyn Park, MN 55443 Phone: (763) 488-6379 / Fax: (763) 493-8171 6/15 www.brooklynpark.org
COMMON FOR ARCHITECTS AND ENGINEERS Excerpts from HB 2284, 82 nd R
Legislation passed by the 82 nd legislature has modified the Texas Engineering Practice Act and the Texas Architect Practice Act. In order to give the public a clearer understanding of these changes, the
Excerpts from the Canadian National Building Code (NBC)
Excerpts from the Canadian National Building Code (NBC) Reproduced here with Permission of the Copyright Owner, the National Research Council of Canada, Institute for Research in Construction. For more
Chapter 15.01 NORTH LIBERTY BUILDING CODE. 15.01.020 International Building Codes adopted.
Chapter 15.01 NORTH LIBERTY BUILDING CODE 15.01.010 Short title. 15.01.020 International Building Codes adopted. 15.01.030 Amendments of the International Building Code and the International Residential
Measuring Single Family Dwellings Town homes Condominium Units. www.thompsonappraisals.com P)843-626-7625 ~ F)843-626-7627
Measuring Single Family Dwellings Town homes Condominium Units www.thompsonappraisals.com P)843-626-7625 ~ F)843-626-7627 You have been taught your whole career that the three most important factors concerning
*It is unlawful to occupy or use any project for which a permit was issued without first receiving final inspection approval from this department.
Department of Permitting Services 255 Rockville Pike, 2nd Floor Rockville, MD 20850-4166 Phone: 311 in Montgomery County or (240) 777-0311 Fax (240)-777-6262 http://www.montgomerycountymd.gov/permittingservices
How To Build A House In The United States
Georgia State Amendments to the International Residential Code for One- and Two- Family Dwellings (2012 Edition) Georgia Department of Community Affairs Community Development Division 60 Executive Park
RRIO Checklist. Use of checklist: Definitions: Limitations
CITY OF SEATTLE RENTAL REGISTRATION AND INSPECTION ORDINANCE (RRIO) RRIO Checklist Use of checklist: Property owners will use the RRIO Checklist to confirm that their rental housing properties and units
Additions and Alterations
Additions and Alterations Addition and alteration construction is a miscellaneous grouping of home improvement and renovation projects that are generally geared toward the enhancement of an existing principal
CITY OF BERKELEY BUILDING PERMIT DETAILED CHECKLIST
CITY OF BERKELEY DETAILED CHECKLIST This checklist will assist you in preparing plans for submittal with a building permit application. Alterations, additions and remodeling projects may not require all
Overview of Hotel Fire Safety Requirements
Overview of Hotel Fire Safety Requirements in the Fire Code Susan Clarke, P.Eng. Office of the Fire Marshal - January 10, 2012 1 Agenda Regulation History - Hotels Fire Code Overview (Parts 1 to 8) Defined
Number of Sides Required to Have a Handrail
Excerpt from 2012 B.C. Building Code HANDRAILS & GUARDS 9.8.7. Handrails 9.8.7.1. Required Handrails 1) Except as provided in Sentences (2) to (4), handrails shall be installed on stairs and ramps in accordance
New York City Department of Buildings
The New NYC Building Code Chapter 10 Means of Egress New York City Department of Buildings Technical Affairs Fatma M. Amer, P.E. Copyright Materials This presentation is protected by US and International
Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER:
Adult Family Home (AFH) LOCAL BUILDING INSPECTION CHECKLIST Code References: 2012 IRC Section R325 (WAC 51-51) APPLICATION NUMBER: SECTIONS 1, 2, 3, AND 4 MUST BE COMPLETED BY APPLICANT BEFORE INSPECTION
Errata has been identified as follows:
2009 IFC Performing Commercial Fire Inspections Inventory Number: 1424S09 Second Printing; July 2014 Changes HAVE been made- Third Printing: September 2014 Errata has been identified as follows: 1. Page
Duchesne County Department of Building Safety
Duchesne County Department of Building Safety 734 North Center St., P.O. Box 317 Duchesne, Utah 84021-0317 Phone (435) 738-1153 Karl D. Mott Building Official BUILDING PERMIT PROCESS DOCUMENTS TO BE SUBMITTED
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings
New Ontario Building Code Requirements for Mid-rise Wood Frame Buildings Note: This information addresses complex issues in a summary fashion. Consideration should be given to the official version of the
We hope these Frequently Asked Questions will be of use both to municipal officials and fire inspectors.
September 14, 2012 Dear AMM Member: Please see the attached Fire Code Frequently Asked Questions. This document was compiled by the Office of the Fire Commissioner at the AMM s request to help clarify
How To Install A Carbon Monoxide Detector
NASSAU COUNTY FIRE COMMISSION OFFICE OF THE FIRE MARSHAL Nassau County Public Safety Center 1194 Prospect Avenue Westbury, New York 11590 (516) 573-9900 / nassaucountyny.gov Chief Fire Marshal Scott D.
A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS
A ROAD MAP FOR YOUR CODE, SMOKE BARRIER & SMOKE PARTITION REQUIREMENTS International Code Council National Fire Protection Association Underwriters Laboratories Inc. 5203 Leesburg Pike, Suite 600 1 Batterymarch
Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842
Upper Southampton Township Department of Licenses and Inspections 939 Street Rd. Southampton, Pa. 18966 Phone: 215-322-9700 Fax: 215-322-5842 APPLICATION for ZONING and BUILDING PERMIT APPLICATION INSTRUCTIONS:
INTERNATIONAL RESIDENTIAL CODE 2012 Edition
WASHINGTON STATE BUILDING CODE CHAPTER 51-51 WAC INTERNATIONAL RESIDENTIAL CODE 2012 Edition Washington State Building Code Council Copies of the State Building Codes and complete copies of the 2012 International
Sample Drawing Package for One and Two Family Dwelling Applications
Sample Drawing Package for One and Two Family Dwelling Applications For a full list of submission requirements, refer to the relevant checklist for your application found on our website: http://vancouver.ca/home-property-development/application-forms-and-checklists.aspx
Uniform With Exceptions
3011 511 Uniform With Exceptions Many townships, boroughs, and cities in Pennsylvania have amended the state s Uniform Construction code (UCC) to impose additional requirements than those contained in
INFORMATION BULLETIN NO.
Requirements for Plans Review Submittal, One- and Two-Family Dwellings INFORMATION BULLETIN NO. 100 June 26, 1998 (Revised June 4, 2014) City Planning & Development - Development Services City of Kansas
Pennsylvania Uniform Construction Code Homeowner s Guide
Pennsylvania Uniform Construction Code Homeowner s Guide 3011 5/11 Information on the Uniform Construction Code is provided by the Pennsylvania Department of Community and Economic Development. For additional,
Page 4 of 17. Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology.
Page 1 of 17 Page 2 of 17 Committee Input NFPA 101 Coordinate Smoke detector versus smoke alarm terminology. CODE PARAGRAPH WITH SUGGESTED CHANGES: 6.4.6.1.2 Residents should be rated as response probable
General Fire Code Requirements Within Commercial Tenant Spaces
FIRE DEPARTMENT in cooperation with Scope: General Fire Code Requirements Within Commercial Tenant Spaces This handout is designed to assist owners, architects, contractors and others in understanding
FINISHED BASEMENT SUBMITTAL GUIDE
FINISHED BASEMENT SUBMITTAL GUIDE The text and illustrations included in this submittal guide represent the opinions of the Manheim Township Code Compliance Department. This guide is for education and
Schedule B to By-law 33-2009
Amended by By-law 8-2016 Note: This consolidation is prepared for convenience only. For accurate reference the original by-laws should be reviewed. Floor Area Calculation Floor area shall: Schedule B to
System Report SR-405B DECEMBER 2014
System Report SR-405 EEMER 2014 Fire Protection of Floors onstructed with Prefabricated Wood I-Joists for ompliance with the International Residential ode 1. SIS OF THE SYSTEM REPT n 2015 International
Building Code Inspections and Fees
St. Mary s County Department of Land Use & Growth Management Customer Assistance Guide 22 Building Code Inspections and Fees May 10, 2014 This guide is intended to assist in the proper construction sequence
2012 CODES SIGNIFICANT CHANGES 2012 IBC
2012 CODES SIGNIFICANT CHANGES 2012 IBC 1. Section 303.4 added language that includes commercial kitchens which are associated with restaurants, cafeterias, and similar dining facilities to be classified
Maximum Floor Area and Maximum Development Area
TOWN OF LOS ALTOS HILLS 26379 Fremont Road Los Altos Hills, CA 94022 Phone: (650) 941-7222 www.losaltoshills.ca.gov Maximum Floor Area and Maximum Development Area Revised-7/31/13 INSTRUCTIONS FOR WORKSHEET
Schedule B to By-law 33-2009 Part A Fees Payable for Permits
Floor Area Calculation Floor area shall: Part A Fees Payable for Permits (Effective January 1, 2015) a) be calculated by measuring to the outer face of exterior walls and to the centre of party walls or
Estimated Cost of Repair
1 Applicant: Property: Home: Business: Assessor: Applicant Number: Type of Loss: Hurricane Date Contacted: 1/18/2014 Date of Loss: 10/29/2012 Date Received: 1/14/2014 Date Inspected: 2/4/2014 Date Entered:
Building Control Guidance Note
Issued 01/01/13 Rev Page 1 of 5 If you intend to convert an existing loft space into additional rooms you will need to apply for Building Regulation Approval. You may also need Planning Permission if you
FIRE AND SMOKE PROTECTION FEATURES
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated
2007 ICC FINAL ACTION AGENDA
907.2.1.1 System initiation in Group A occupancies with an occupant load of 1,000 or more. Activation of the fire alarm in Group A occupancies with an occupant load of 1,000 or more shall initiate a signal
RESIDENTIAL BUILDING CODE HANDOUT REFERENCES: 2009 Michigan Residential Code
CHEBOYGAN COUNTY DEPARTMENT OF BUILDING SAFETY 870 South Main Street P.O. Box 70 Cheboygan, Michigan 49721 Phone: (231) 627-8813 Fax: (231) 627-8454 www.cheboygancounty.net RESIDENTIAL BUILDING CODE HANDOUT
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL
RHODE ISLAND DIVISION OF STATE FIRE MARSHAL Smoke Alarm and Carbon Monoxide Brochure JOHN E. CHARTIER STATE FIRE MARSHAL 118 PARADE STREET PROVIDENCE, RI 02909 DAYS 401-462-4200 24 Hr. 401-222-2331 FAX#
MINNESOTA HEALTH CARE ENGINEERS IN ASSISTED LIVING FACILITIES
MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES September 13, 2012 MINNESOTA HEALTH CARE ENGINEERS FIRE/LIFE SAFETY IN ASSISTED LIVING FACILITIES WELCOME Exits Restrooms
2012 Ontario Building Code Requirements for New Construction. Bradford West Gwillimbury Building Division March 5, 2012
2012 Ontario Building Code Requirements for New Construction Bradford West Gwillimbury Building Division March 5, 2012 1 Ontario Building Code changes Applicable to permits applied for after December 31,
BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION CURRENT OWNER
BOROUGH OF NATIONAL PARK APPLICATION FOR A CERTIFICATE OF OCCUPANCY FOR CHANGE OF OCCUPANCY ADDRESS OF PROPERTY FOR INSPECTION # BLOCK LOT VACANT YES NO CURRENT OWNER NAME ADDRESS TELEPHONE # PROSPECTIVE
Code Requirements for Existing Buildings
Code Requirements for Existing Buildings Kevin S. Hastings, P.E., LEED AP R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS)
Minimum Housing and Health Standards
APPENDIX M.O. 57/2012 Minimum Housing and Health Standards Original version July 20, 1999. Revisions to Part lll, Housing Premises, sections 3 and 4, June 30, 2012 (all revisions are bolded and underlined).
FIRE AND SMOKE PROTECTION FEATURES
CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated
BUILDING PERMIT APPLICATION
MASON COUNTY PERMIT NO. DEPARTMENT OF COMMUNITY DEVELOPMENT BUILDING PLANNING FIRE MARSHAL WWW.CO.MASON.WA.US (360) 427-9670 Shelton ext.352 Mason County Bldg. III, 426 West Cedar Street (360) 275-4467
MEANS OF EGRESS CHAPTER 10
CHAPTER 10 MEANS OF EGRESS SECTION 1001 ADMINISTRATION 1001.1 General. Buildings or portions thereof shall be provided with a means of egress system as required by this chapter. The provisions of this
KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement KITCHEN AND BATH REMODELING BUILDING PERMIT REQUIREMENTS This guideline is intended to provide the homeowner/contractor with the
Area of Rescue Assistance Communication System ADA Code Applicable excerpts:
Area of Rescue Assistance Communication System ADA Code Applicable excerpts: CONTENTS (Guidelines and Definitions) Page 1 Area of Rescue Assistance Requirements Page 2 Emergency Communication Equipment
PARK COUNTY BUILDING PERMIT GUIDE PO Box 517 Fairplay, CO 80440 719-836-4255 Fax: 719-836-4268 Inspections: 719-836-4257 www.parkco.
PARK COUNTY BUILDING PERMIT GUIDE PO Box 517 Fairplay, CO 80440 719-836-4255 Fax: 719-836-4268 Inspections: 719-836-4257 www.parkco.us Welcome to the Park County Building Department. The following information
When is a Permit Required? What Types of Permits are Required? The most common types of projects that require permits are:
When is a Permit Required? The most common types of projects that require permits are: -New Houses or buildings -Room Additions or Expansions -Structural repairs, remodeling and alterations -Accessory
Residential Plan Routing Information
Residential Plan Routing Information BUILDING INSPECTIONS 800 4th AVENUE EAST WEST FARGO, ND 58078 PHONE: 701-433-5480 The building Inspection s Department receives and issues all applications for building
M E M O R A N D U M. To: Partnership for Safer Buildings Date: 21 March 2003
M E M O R A N D U M To: Partnership for Safer Buildings Date: 21 March 2003 From: Codes Assessment Subcommittee Walter Smittle III, Chairman Re: Building Code Fire Safety Concerns: NFPA 5000, Building
CHAPTER 6, BUILDINGS AND BUILDING REGULATIONS, OF THE KANE COUNTY CODE
CHAPTER 6, BUILDINGS AND BUILDING REGULATIONS, OF THE KANE COUNTY CODE Adopted by the Kane County Board On December 11, 2012 Effective January 1, 2013 2012 International Building Code as amended 2012 International
REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
PLAN REVIEW FOR: PROJECT NAME: OWNER: ARCH/DESIGNER: ADDRESS: Ph/Fx: Plans Dated: E-mail: Sealed By: Estimated Project Cost - $ REVEWED BY: Ross Rogien B.O/P.R. ADDITIONAL REVIEW(S) REQ.-FIRE DEPT Y/N
Residential Deck Safety, Construction, and Repair
Juneau Permit Center, 4 th Floor Marine View Center, (907)586-0770 This handout is designed to help you build your deck to comply with the 2006 International Residential Building code as modified by the
CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov
CITY OF FAIRFAX CODE ADMINISTRATION 703-385-7830 / FAX 703-385-9265 www.fairfaxva.gov Finishing a basement to make additional living space in a house is a popular construction project for many homeowners.
Site Development Information Worksheet for single family residential development
Site Development Information Worksheet for single family residential development Project description: Address: Owner Name: Phone No. Date Signature & phone number of Individual who Completed this Worksheet
I N T E R N A T I O N A L R E S I D E N T I A L CO D E
Visual Interpretation Of The I N T E R N A T I O N A L R E S I D E N T I A L CO D E 2006 STAIR BUILDING CODE Portions of this document reproduce sections from the 2006 International Residential Code, International
Building Information Packet
Code Enforcement Department 882-9225 Building Information Packet The following information has been compiled to help you as a homeowner or contractor with the various steps and requirements for a building
A HOMEOWNERS GUIDE TO BUILDING IN GREY HIGHLANDS
A HOMEOWNERS GUIDE TO BUILDING IN GREY HIGHLANDS AIM AND APPLICATION OF THE GUIDE This guide is intended to help you better understand the requirements for building as set by applicable law, which could
BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS
DCD-0304 Identification # Rev. 9/08 County Date of Inspection NAME OF OPERATION BUILDING INSPECTORS INSPECTION FORM FOR CHILD CARE CENTERS ADDRESS TELEPHONE: CITY STATE ZIP BUILDING INSPECTORS CERTIFICATE
COMMONLY USED RESIDENTIAL BUILDING CODES
COMMONLY USED RESIDENTIAL BUILDING CODES INTERNATIONAL RESIDENTIAL CODE (2009) form revised 5/10 FOUNDATION 1. DESIGN OF FORMWORK. Section 1906.1 IBC 2009, Section R404.1.2.3.6 IRC 2009, ACI 318 Section