Understanding Delta Conversion Online "Output Power Factor Ratings" - Part 7



Similar documents
Understanding Delta Conversion Online "Power Regulation" - Part 2

Considering the effects of UPS operation with leading power factor loads

Experts speak on UPS output Watt, VA, and Power Factor ratings.

Variable Frequency Drives - a Comparison of VSI versus LCI Systems

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction

Power Factor Correction for Power Systems First Semester Report Spring Semester 2007

ELECTRONIC POWER SYSTEMS

The Different Types of UPS Systems

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

Inverter technology. bulletin

Motor Efficiency and Power Factor ME 416/516

The Different Types of UPS Systems

Product Data Bulletin

Ametek Prestolite Power AC power / Charger / Battery terms

415V DISTRIBUTION FOR GREEN DATA CENTERS

The Different Types of UPS Systems

415V DISTRIBUTION FOR GREEN DATA CENTERS

DC-DC Converter Basics

Design a Phase Interleaving PFC Buck Boost Converter to Improve the Power Factor

ABB PSPS Erich Steinmann; Generator control-2013

Series 7400 M (10/20/30/40/60 kva) Maximum Protection For Mission Critical Network Applications. Series 7400 M

VOLTAGE REGULATOR AND PARALLEL OPERATION

HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS

Power to the adaptable data center

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

GAMATRONIC ELECTRONIC INDUSTRIES LTD.

Three-phase AC circuits

Variable Frequency Drives and Energy Savings

7-41 POWER FACTOR CORRECTION

Power Electronic Circuits

> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents.

TECHNICAL SPECIFICATIONS FOR 1.5 KVA ONLINE UPS

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 15kVA and 20kVA Smart-UPS RT 230VAC Uninterruptible Power Supply

Wireless Networks and Power Quality

City of Leesburg, Florida I.T. Data Center APPENDIX A TOSHIBA UPS INFORMATION

Single-Stage High Power Factor Flyback for LED Lighting

Fundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder

APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.

TLE Series. Product Description kva / 400Vac / S1 KEY BENEFIT APPLICATIONS FEATURES

SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION

Modeling Grid Connection for Solar and Wind Energy

Pulse Width Modulated (PWM) Drives. AC Drives Using PWM Techniques

Impact of Leading Power Factor on Data Center Generator Systems

Modelling, Simulation and Performance Analysis of A Variable Frequency Drive in Speed Control Of Induction Motor

1ED Compact A new high performance, cost efficient, high voltage gate driver IC family

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

Renewable Energy Applications: Photovoltaic and Wind Energy Conversion Systems (WECS)

Energy Cost Reduction through Load Balancing & Load Shedding

Eaton 93PM UPS Where aesthetics meet intelligence.

Three phase circuits

Improvement of Power Factor for Industrial Plant with Automatic Capacitor Bank

Five Nines and Infrared (IR) Testing at Data Centers

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity

Calculating Total Power Requirements for Data Centers

Yam Hong 施 耐 德 電 機 亞 太 日 本 區 (APJ) 三 相 關 鍵 電 源 市 場 開 發 經 理. Schneider Electric - Division - Name Date

TLE Series UPS kva/kw three phase 400 Vac with best-in-class efficiency

SYNCHRONOUS MACHINES

Introduction to Paralleling of LTC Transformers by the Circulating Current Method

GE Digital Energy. TLE Series UPS kw three phase 400 Vac. with best-in-class efficiency. gimagination at work

DC UPS. RTB.e A. IMB.e/ITB.e kva. E2001.e/E3001.e kva. Input voltage: 110/125/220 Vdc. 115/120/230 Vac, 1-phase (IMB.

APPLICATION NOTE. Increasing PV Hosting Capacity on LV Secondary Circuits with the Gridco System empower TM Solution

Pulse Width Modulated (PWM)

A Comparison of AC and DC Power Distribution in the Data Center Transcript

High-Efficiency AC Power Distribution for Data Centers

Ambient Temperature In Range Probe X

Power Distribution Considerations for Data Center Racks

The Basics of Digital Multimeters

GE Digital Energy. SG-CE Series UPS kva three phase 400 Vac Uninterruptible Power Supply (UPS) imagination at work

Electrical Systems. <Presenter>

WIND TURBINE TECHNOLOGY

What Is Regeneration?

A Low Cost Power Quality and Energy Savings Laboratory for Undergraduate Education and Research

POWER FACTOR CORRECTION

LEVEL 3 DATA CENTER ASSESSMENT

SECTION VARIABLE FREQUENCY DRIVES

DISTRIBUTED REDUNDANCY:

Power System Harmonics

LAP ENERGIA PARA DATACENTERS

98% Efficient Single-Stage AC/DC Converter Topologies

LTR Series Uninterruptible Power Systems 700 VA KVA. General Specification

Multi DIALOG MDM/MDT. MDM 10-20kVA single/single-phase and three/single-phase MDT 10-80kVA three/three-phase NETWORK RANGE

Using the Phoenix MultiPlus

GE Digital Energy. SG-CE Series UPS kva three phase 400 Vac Uninterruptible Power Supply (UPS) imagination at work

Power Quality. Uninterruptible Power Supply

LOW COST MOTOR PROTECTION FILTERS FOR PWM DRIVE APPLICATIONS STOPS MOTOR DAMAGE

APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply

Understanding Power Factor, Crest Factor, and Surge Factor. White Paper #17

A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER

RIELLO ELETTRONICA. Master HP

The full wave rectifier consists of two diodes and a resister as shown in Figure

POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS

13.10: How Series and Parallel Circuits Differ pg. 571

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

Opportunity of Energy Saving in electrical path is lesser as compared to other areas

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria

Power factor correction and harmonic filtering. Rectimat 2 Automatic capacitor banks. Catalogue. Building a New Electric World

Transcription:

Application Note #45 Understanding Delta Conversion Online "Output Power Factor Ratings" - Part 7 Introduction This application note is the seventh in a series on delta conversion theory of operation. For complete understanding of the engineering benefits of this technology we recommend that you read all the series in order and any of the supplemental white papers found on the APC web site. UPS Output Power Factor In part 6 with respect to UPS input power factor we said: "Power factor is the percentage of electricity that is being used to do useful work. It is expressed as a ratio. For example, a power factor of 0.72 would mean only 72% of your power was being used to do useful work. Perfect power factor is 1.0, (unity), meaning 100% of the power is being used for useful work." Power factor also applies to the UPS output, where we can say: "UPS output power factor rating is the percentage of electricity that is available to do useful work and its' also expressed as a ratio. For example, a power factor of 0.80 would mean only 80% of your power is available as real power to do useful work. Perfect output power factor is 1.0, (unity), meaning 100% of the power is available for useful work." However, like all things in life, there are some "caveat emptor's". A lot depends on the size and type of inverter used in the UPS system. The UPS Output Power Triangle Although it may not be clear at this time, figures 1 & 2 show the difference in output ratings. Where the Delta Conversion Online output rating is at PF =1.0 (500kVA/500kW). This PF 1.0 rating is feasible because the main inverter is a IGBT PWM that is 100% kw rated at 500kW. 1

Figure 1 - Delta Conversion Online 500kVA/500kW Figure 2 - Double Conversion 500kVA/400kW The double conversion system shown in figure 2, is an old design that is output rated at PF = -.80 (500kVA/400kW). This is feasible because the main inverter is 80% kw rated at 400kW and they either use an IGBT H-bridge inverter and flyback diodes or they have to add 300kVAR to the inverter filter capacitor. The flyback diodes or the capacitor supplies the reactive power (Q) and the main inverter supplies the real power (P). 2

Figure 3 - Double Conversion Real Power & Reactive Power Paths @ -.8PF Load Using some of the information about power factor from part 6 of this series, i.e., if you reviewed the bibliography. We can best understand this via understanding the trigonometric relationship, i.e., "power triangle". If we take our DPF equation from Part 6. Equation 1 P P PF = ---- = ------ = cos θ 1 S VI First we represent these output rating relationships mathematically. Then we can diagram the double conversion output rating, i.e., apparent power (S), real power (P), and reactive power (Q) relationships via a power triangle. Equation 2 P If: PF = ---- S 400kW = ------------ =.80 PF 500kVA Equation 3 P 400kW Therefore: S = ------ = ------------ = 500kVA cos θ 1.80 3

Equation 4 P = S cos θ 1 = 500 *.80 = 400kW Given we know S and P, we can calculate the reactive power (Q) and show their relationship to each other. Equation 5 Q = S 2 - P 2 = 500 2-400 2 = 300kVAR Equation 6 P = S 2 - Q 2 = 500 2-300 2 = 400kW Equation 7 S = P 2 + Q 2 = 400 2 + 300 2 = 500kVA Figure 4 - Double Conversion 500kVA/400kW Power Triangle We can also calculate the system output currents by converting the power quantities to amperes of current at a specific voltage. If we use 400V three-phase as our system voltage, the results are as follows: Equation 8 If: S = V * I * 3 Then: I S = S/V* 3 = 500000/692.8 = 721.7A Equation 9 If: P= VI * 3 * cos θ Then: I P = P/(V 3/ cosθ) = 500000/(692.8/.80) = 577.4A 4

Equation 10 I Q = I S 2 - I P 2 = 721.72-577.42 = 432.9A Now we can see the system output bus supplies 721.7A per/phase of apparent power (S) to the load. Of that apparent power (S), 577.4A per/phase is supplied by the main inverter as real power (P), and 432.9A per/phase is supplied by The flyback diodes or the 300kVAR capacitor as reactive power (Q). Neat trick! If they use a capacitor, can it handle additional heating from a harmonic PF load? The Double Conversion -.80PF Output Rating Problem To simplify all the above. A 500kVA/400kW double conversion system with it's output rating at -.80 PF, uses the 400kW main inverter combined with either flyback diodes or a 300kVAR of capacitor to boost the output apparent power (S) to 500kVA. The inverter supplies the real power (P) from the DC bus and the reactive power (Q) comes from the flyback diodes or capacitor. The combined effect at the output bus is 500kVA of available apparent power (S). For older designs where capacitors are used and the load power factor increases above.80pf, the capacitors become an increasing reactive load on the main inverter, rather than a reactive current source for the output. The capacitor's reactive power (car s) is fixed and the inverter power rating (kw) is also fixed. Therefore, if the actual UPS output load power factor increases above.80, it affects the overall available system kw output rating by lowering the amount of kw load the system can support. If the main inverter is rated to deliver 400kW from the DC bus, obviously it cannot support a continuous load greater than 400kW. In fact for the older step-wave and SCR technologies, if the load power factor is unity, i.e., PF = 1.0, the main inverter may have a hard time supporting more than ~ 265kW of real power (P) at the output bus load. This is shown below in figure 5. Figure 5 - Double Conversion Real Power & Reactive Power Paths @ 1.0PF Load Now our challenge is to figure out how much real power (P) can the older step-wave or SCR UPS support with an output load at PF 1.0? Calculating the effect is identical to solving the power triangle for kw when kva & kvar's are known. However, the inverter kw 5

rating becomes the hypotenuse of our power triangle (right triangle), the maximum output kw load becomes the base, and the capacitor kvar's remains as the altitude. Figure 6 - Double Conversion Power & Current Triangles @ 1.0PF Load Therefore, maximum allowable PF 1.0 load w/o overloading the inverter is easily found by either of the following equations: P max = P 2 Inv - Q 2 = 400 2-300 2 = 264.6kW or I P max = I 2 Inv - I 2 Q = Ö 577.42-432.92 = 382A This means if the inverter is rated to take 400kW of current from the DC bus, it can now only supply 66% of the system kw load rating (265/400 =.66) to the system output bus. Because the inverter is going into overload, a older design double conversion system will probably switch to static bypass if this 66% PF 1.0 load level is exceeded. If they don't switch to static bypass immediately, they will eventually be forced too, because of inverter over-temperature. What Does It Really Mean To the CE or Customer? The effect of loads with power factor greater than -.80PF, is usually transparent to most users and a great many CE's. That is until they experience the problem with older double conversion UPS designs. What are the potential risks? Some examples: CE designs system for small data center based on customer specified Watts/sq ft, and total calculations come to maximum of 350kW. CE selects a 500kVA/400kW system because he likes a little comfort zone. After facility is completed customer begins installing all large PFC servers. When actual load hits ~ 265kW, the UPS alarms on inverter overload, and transfers to static bypass. UPS vendor blames load PF, and customer blames CE. CE designs same small data center with distributed redundant design, 2-500kVA/400kW UPS systems using same 350kW facility maximum load. For redundancy each UPS system is feeding a separate output bus that feeds separate inputs to dual input static switch PDU's. After facility is completed, data center customers begin installing large PFC servers. The design is for each UPS to handle no greater than 50% load. After some time actual total connected load is ~300kW (150kW/ UPS system). Again what appears to be well within rating of the UPS system capacity? Major power failure, one module has inverter or battery failure. Remaining good module takes the 300kW load and shuts down on inverter overload.. UPS vendor blames load PF, and customer blames CE. The real problem is the CE can't control the loads or their power factor. The load in a data center changes daily as new equipment is installed. The typical data center load today has a combined PF better than.90, with many of them at.95 or above. This is because of the huge influx in power factor corrected (PFC) power supplies in the servers, routers and other data center equipment. 6

The CE has a couple of choices: Use next higher rated double conversion UPS. This would be 625kVA to 750kVA depending on the vendor. However, this also has huge impact on rest of the facility infrastructure. The service transformer, engine generator, generator transfer switch, feeder circuit breakers and feeder conductors are now oversized by ~ 100 to 200kW or +25 to +50% of actual design kw load, depending on the vendors available UPS ratings. Clearly the customer is paying for a compromised design caused by the UPS output rating @ -.80PF limitations. Use a UPS system that's not load power factor limited and can deliver its full power to any PF load. That's an APC's Delta Conversion Online 400kVA/400kW system with PF 1.0 output rating. By using a 400kVA/400kW unit we further reduce infrastructure cost by ~20% versus the original competitor's 500kVA/400kW unit, (400/500 = 80%) and ~ 36% versus oversized competitor's 625kVA/500kW (400/625= 64%). Clearly the CE can deliver a design that meets the performance requirements, at the lowest capital expense. He can also sleep at night and not worry about the future load PF. The customer will benefit from the UPS output power factor rating because he can safely connect any load within the UPS's output current rating. How much horsepower do you want? The easiest analogy to describe this difference in UPS output power factor rating is to compare two trucks. f. ex. You need a new truck to pull the brand new bass boat your wife just bought you. This sounds like a fantasy. Well actually the part about her buying you the bass boat is fantasy! Truck #1 has a 5.0L engine rated at 400HP, and Truck #2 has a 5.0L engine rated at 500HP. Which truck can pull more load? Oh yes truck #2 also has better fuel economy! The engine displacement in liters equates to our apparent power rating (S) in kva and the horsepower rating equates to our real power (P) rating in kw. Oh yes, they both have ~ same price! Which truck do you want? This is only one of the advantages of using a fully rated inverter for power factor 1.0 output rating. This concludes Part 7 of our series.. Bibliography Power Electronics- Converter, Applications, and Design. Mohan, Undeland, & Robbins - Second Edition - ISBN 0-471- 58408-8 http://www.nebulae.net/calypso/article5.htm 7