VOLTAGE REGULATOR AND PARALLEL OPERATION

Size: px
Start display at page:

Download "VOLTAGE REGULATOR AND PARALLEL OPERATION"

Transcription

1 VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by selecting only sufficient generators to carry the load demand at any given time. By operating each generator near its full capacity, fuel is utilized efficiently. Power system reliability is improved by availability of generators not in use as backup for units on line. In addition, protective systems can be designed to detect a faulty element and isolate it from the healthy part while maintaining power to the remaining system. With multiple generators carrying the load, a generator that develops a problem can be shut down, allowing the remaining generators to carry the load. Because of advantages of parallel operation, multiple generator installation has become common in applications for standby and prime power, portable and stationary power, commercial and military power; and they continue to grow. Operating generators in parallel required attention to the two control systems of the generator set - the voltage regulator and the speed governor. This discussion is limited to the control of the voltage regulator. PARALLEL OPERATION AND THE VOLTAGE REGULATOR An example to illustrate the effect of the voltage regulator on the generator system can be seen using two batteries and a load. In Figure 1, two batteries with voltages exactly equal (open circuit) could divide load equally, with each battery pulling its share. If the two voltages are not exactly equal, the load will not be shared equally, and the benefit of two batteries will be lost. Figure 1: Paralleled Batteries - Equal Voltage Further, the load division is very sensitive to voltage unbalance. In Figure 2, the battery with an output voltage of 102 (B2) will determine the load voltage, and the load sees a proportionally higher current. Battery B1 is being charged by B2 at a 5 ampere rate because its terminal voltage is lower. This charging current is obviously not proportional to the voltage level and results in a load current on B2 in excess of 6 Amperes. 1

2 Figure 2: Paralleled Batteries - Unequal Voltage In Figure 3, B1 is higher in voltage than B2 by 2 volts, causing B1 to supply the load and charge B2 for a total load current of 6 Amperes. Figure 3: Paralleled Batteries - Unequal Voltage Please note that the voltage referred to in the diagrams is the open-circuit voltage. As soon as the batteries are paralleled, the voltage at the terminals of the batteries becomes identical. Two generators operating in parallel to supply a common load operate in a similar manner. If voltage (open-circuit) is exactly the same on both generators, they will divide the load equally between them. See Figure 4. Any small difference between generator voltages will result in unbalanced load division (Figure 5) or, in the extreme, circulating current (Figure 6). Figure 4: Paralleled Generators - Figure 5: Paralleled Generators - Balanced Voltage Voltage Unbalanced 2

3 Figure 6: Paralleled Generators - Voltage Unbalanced In practice, the precise matching of voltages is not possible. Some means must be provided to make load sharing between paralleled generators simple to control. Because circulating current or load unbalance described above is the result of voltage mismatch, you might look to the voltage regulator for some help. The regulator can provide this help using paralleling compensation circuits called reactive droop compensation or reactive crosscurrent compensation. Both types will be described in detail in later papers. The principle of operation of the reactive droop circuit, which is the simplest and most commonly used circuit, can be described by the curve in Figure 7. Figure 7: Reactive Droop Curves Using a regulator designed to maintain precise voltage regulation, a circuit is added that accepts a current signal from the generator s output. This current signal is combined with the generator s sensing voltage signal to develop a vector summed voltage proportional to reactive load. For example, if voltage decreases from 480 volts down to 458 voltage from no load to rated reactive (kvar) load, the voltage droop is -4.3% droop. If two generators are operated in parallel, with their droop curves set the same and their voltage setpoints adjusted to proportionally share the reactive load, any unbalance that would increase the load on one machine and decrease the load on the other would cause the droop circuits to change the voltage setpoints in a direction to bring the load back into balance. With droop compensation, the bus voltage will droop with changing reactive load. 3

4 Figure 8: AVR with Droop By building this characteristic into the regulator of each generator operating in parallel, sharing of the load is controllable and uncomplicated. To parallel two generators, voltages should be matched prior to closing the breaker to minimize the current surge at breaker closing. Figure 9: Paralleled Generators - Balanced Voltage With voltages balanced and 100 Amperes load, each generator will supply its share of the load. If G2 voltage is increased, its output current will try to increase. This increase will cause a voltage droop, which counteracts the voltage increase. G1 will see its output current decrease, resulting in a droop circuit action to increase voltage. The result is a load balance control action that works to hold loading balanced when two or more generators are operating in parallel. WHY CONTROL TWO VARIABLES? KW, KVAR, KVA In the dc analogy with batteries in parallel, only the voltage had to be controlled to allow for load sharing. In the mechanical ac analogy, only the torque had to be controlled. To parallel ac generators, both variables must be controlled properly. Torque applied to the generator must be controlled in order to divide real power (kilowatts); excitation to the generator must be controlled to divide the reactive power. 4

5 Real power is work done by the electrical energy of the generator. This power is supplied by the prime mover in the form of torque. The generator converts mechanical torque to electrical energy. This energy is supplied to a load to be converted to the desired form of energy, such as heat, light, mechanical energy (motor), etc. Reactive power is that power required by loads with inductance or capacitance to store energy on each half cycle. In the example of Figure 10, the load is purely resistive, such as a heating element. Because no reactive power is required at any point on the sine wave, current is directly proportional to the voltage at that point. The real power can be calculated using Ohm s Law. Figure 10: Resistive Load If an inductance (Figure 11) is connected to the generator output, the relationship between voltage and current is different. The inductor will not allow current to flow without first building up lines of flux in its magnetic circuit. Thus, the current through the inductor is proportional to voltage, but the current lags the voltage by 90 electrical degrees (Figure 12). Figure 11: Inductive Load Figure 12: Current Lags Volts The capacitor, on the other hand, will not allow voltage across its terminals until some charge has been deposited on its plates (Figure 13). For this reason, the current must flow before a voltage can exist. Thus the capacitor current leads the voltage by 90 electrical degrees (Figure 14). Figure 13: Capacitive Load Figure 14: Current Leads Volts 5

6 For a load containing all three elements in parallel (Figure 15), it is convenient to calculate the real or reactive power in each element separately. The Law of Superposition (Figure 16) allows the addition of the three separate calculations vectorially to determine the total load. Figure 15: Combined RLC Load Figure 16: Law of Superposition A look at I 1 and I 2 indicates that these currents are always opposite in polarity. If the currents are equal, the net result is zero! For this reason, inductive loads are said to accept reactive power, while capacitors are said to supply reactive power. Power Factor correction capacitors use this principle to compensate for inductive loading. The reactive power flow is illustrated in Figure 17. 6

7 Figure 17: LC Loads Thus, the reactive power, expressed in Vars, can be computed by: Q = E 2 Q = VARS X L - X C X - X L C And the real power, expressed in watts, can be computed by: 2 P = E R P= Real Power, Watts A third parameter can be computed by using the voltage of the generator and the current I L in Figure 18. This parameter is known as apparent power. S = EI L (NO VECTORS) S = APPARENT POWER, VOLT-AMPERES Figure 18: Combined RLC Load These three parameters, real, reactive, and apparent power, are related. Knowing any two, the third can be calculated using the Pythagorean Theorem: Or they may be calculated using vector arithmetic (Figure 19): Figure 19A: Power Figure 19B: Real Power - Figure 19C: Apparent Triangle kilowatts Power - KVA 7

8 Metering is commonly provided to measure volts, amps and frequency for generators operating alone. For parallel application, monitoring current gives an indication of loading, but there is no indication of the type of current flow, making load sharing adjustment impossible. A meter to monitor real power in addition to current will enable power to be balanced by the governor adjustment, followed by balancing of current using voltage regulator adjustment. A better scheme adds an additional meter for reactive power, the Var meter. With a kw and Kvar meter on each generator, optimal adjustment of the governor and the voltage regulator are easily accomplished, and load sharing is easily monitored. Another metering option is the power factor meter, often used instead of the Kvar meter. Power factor is the ratio of real power to apparent power: PF = P S P = REAL POWER, WATTS S = APPARENT POWER, VOLT-AMPERES Figure 19D: Reactive Power - KVAR Power factor, because it is affected by both real power and reactive power levels, is more difficult to interpret for monitoring load sharing performance. Providing good instrumentation is very helpful for operating systems of paralleled generators. THE VOLTAGE REGULATOR AND PARALLEL GENERATOR OPERATION The function of the voltage regulator is to provide precise regulated generator voltage at no load and with changing loads. When generators are connected together in parallel operation, a parallel compensation circuit is required to assist the voltage regulators in controlling the generator reactive loads. Reactive loads between generators can become unbalanced when the voltage regulator varies the excitation to the generator exciter field due to load changes, prime mover speed variation, thermal drift, etc. This change in excitation may cause large circulating currents to flow between generators (Figure 20). Figure 20: Circulating Currents This causes the generator with the higher field excitation to try and power the generator with the lower field excitation in an effort to force the generator to have the same output voltage as the generator with the higher excitation. 8

9 The parallel compensation circuit will cause the voltage regulator to increase the field excitation on the generator with the lower field excitation and decrease the field excitation on the generator with the higher field excitation. By controlling the reactive load, the parallel compensation circuit can eliminate the undesired circulating currents. Figure 21: Equal Pressure - A Unequal Pressure - B An analogy of how one generator tries to power another generator with circulating currents can be compared to two water pipes of equal diameter feeding into one pipe. When the two water pipes have the same water pressure, both water pipes will be supplying the same amount of water to the common water pipe (Figure 21A). If one water pipe suddenly lost a small amount of pressure, the second water pipe would begin to supply more water to the common pipe to help maintain the water flow (Figure 21B). Also, because the water pressure in the second water pipe is now greater than the first water pipe, water will begin to flow from the second water pipe to the first water pipe in effort to force the water pressure to be the same as the second pipe. REACTIVE DROOP COMPENSATION AND REACTIVE DROOP DIFFERENTIAL COMPENSATION There are two forms of parallel compensation circuit. The most often used type of paralleling compensation is the parallel droop compensation or using the IEEE designation, reactive droop compensation. The other type is crosscurrent compensation or, again using IEEE terminology, reactive differential compensation. Figure 22: Reactive Droop Compensation 9

10 When reactive droop compensation is used to parallel two or more generators, each parallel droop circuit is independent of the other (Figure 22). A typical parallel droop circuit is made up of a current transformer and paralleling module. The paralleling module consists of a burden resistor and a switch connected across the primary of a transformer (Figure 23). Figure 23: Paralleling Module A switch located on the primary of the transformer in the paralleling module is used to short the secondary of the current transformer and the burden resistor to allow the generator to operate independently of the paralleling generating system. The secondary of the current transformer is connected to the paralleling circuit. Connection to the paralleling circuit places a burden resistor across the output terminals of the current transformer (Figure 24). The secondary current of the current transformer induces a voltage across the burden resistor that is vectorially added to the line voltage to produce an error signal to the voltage regulator. Voltage across the burden resistor is proportional in magnitude and has the same phase as the line current through the primary of the current transformer. Figure 24: Burden Resistor 10

11 Figure 25: Current Transformer Error Signal Development The error signal produced across the current transformer burden resistor must be applied so that when the load is a unity power factor load, no corrective signal will be produced and no excitation change will occur because of the load. By arranging the burden resistor voltage so that it will be 90 electrical degrees out of phase with the system voltage when the power factor of the load on the generator is unity, an appropriate error signal can be produced. Figure 25 shows the vector representation of system voltage and burden resistor voltage needed to produce the error signal. The three phase voltages (line to neutral), regardless of their internal connections, produce output voltages that are displaced from each other by 120 electrical degrees. By taking advantage of the phase displacement, it is possible to sense the system voltage from line to line and produce a line voltage that is displaced from the phase voltage by 30 electrical degrees. The voltage signal from the current transformer burden resistor at unity power factor (resistive loads) will be displaced by 90 electrical degrees from the system or line voltage (Figure 26A). 11

12 Figure 26: Phase Displacement Under unity power factor, the vector diagram (Figure 26B) representation of the burden resistor voltage (V B ) and the sensing voltage (Vac) can be seen to be 90 electrical degrees apart. When a reactive load is applied to the generator, the burden resistor voltage arrow will swing either clockwise or counterclockwise depending upon the type of load, capacitive or inductive (Figure 26C). Figure 27: Vector Diagram of Capacitive Load If the generator load has a leading power factor (capacitive load), the vector diagram of the burden resistor voltage will rotate counterclockwise from its unity power factor position (Figure 27). The phase angle between the line voltage and burden resistor voltage will become more out of phase, which will decrease the regulator sensing voltage. The regulator will receive a smaller sensing signal and thus increase generator excitation. 12

13 Figure 28: Vector Diagram of Inductive Load When the load is a lagging power factor or inductive load, the vector diagram of the burden resistor voltage will be rotated clockwise from its unity power factor position (Figure 28). The phase angle between the line voltage and burden resistor voltage will become more in phase and the voltage sensing signal to the regulator will be increased. The regulator will receive the larger signal and respond by decreasing generator excitation. The parallel module will supply an error signal to the voltage regulator that will control the excitation level of the generator. When the generators are paralleled, the regulator responds to this small increase in sensing voltage by reducing excitation to the generator field, which will produce a droop in the generator output voltage. The amount a generator system will droop can be adjusted by the burden resistance and the current transformer ratio. A typical burden resistor has a resistance of one ohm and has an adjustable slide tap contact so that the voltage developed across the resistor can be varied. The amount of error signal sent to the voltage regulator is proportional to the magnitude of the voltage across the resistor and the vector angle of that voltage. The amount of voltage across the burden resistor is determined by the secondary or output current of the current transformer. Typical current transformers are designed for a 5 ampere secondary current with a 25VA maximum burden rating. Ohm s Law (Voltage = Current X Resistance) will show the maximum voltage across the one ohm burden resistor to be 5 volts. It can then be seen that the relative magnitude of the voltage developed across the burden resistor with full load on the generator is typically 5 percent of the system output voltage (120/ / /600) to minimize circulating currents. When generators are paralleled with reactive droop compensation, most generators are set to operate with maximum droop. The burden resistor is adjusted for maximum resistance or maximum voltage across the resistor. Allowing the generating system to operate at maximum droop allows for the best control of circulating currents. Setting the burden resistor for a system voltage droop of less than three percent may result in the regulator and paralleling circuit being unable to control circulating currents satisfactorily. Voltage regulators with single phase sensing provide approximately 8% maximum droop while three phase sensing regulators provide approximately 6% droop. Single phase sensing provides greater droop because the average value of the error signal is proportionally greater compared to the average value of the single phase sensing voltage than to the average value of the three phase sensing voltage. When generators are paralleled on the same bus and have different type sensing, care must be taken to compensate for sensing differences using the adjustable burden resistor. 13

14 Since the burden resistance voltage is dependent on the line current of the generator through the current transformer, any changes in power factor due to the load will be reflected on the burden resistor voltage. Consequently, when a reactive lagging power factor load is increased, the bus voltage will droop by an increased amount. If a capacitive leading power factor load is increased, the bus voltage will increase. The magnitude of the change depends upon the magnitude of the load and power factor. In order to prevent the voltage from increasing or decreasing with the power factor of the load, another circuit can be used where the current transformers of the individual regulators are interconnected. Crosscurrent compensation (reactive differential compensation) allows operation in parallel without voltage droop caused by the error signal. Figure 29 shows two generators paralleled with reactive differential compensation. Interconnection of the current transformers can be seen. On generator number one, the current transformer (CT1) terminal with the polarity mark is connected to the current transformer (CT2) on generator number two at the terminal with no polarity mark. On generator number two, the current transformer (CT2) terminal with the polarity mark is connected to the current transformer (CT1) on generator number one at the terminal with no polarity mark. Figure 29: Two Generators Paralleled with Reactive Differential Compensation Even though the voltage involved is ac, a better understanding of the operation of the closed crosscurrent loop can be obtained by using a dc voltage analysis. First of all, the polarity marks on the generator line and current transformer indicate the current direction. The line current always flows into the polarity mark on the generator line and the current flows out of the polarity mark on the current transformer (Figure 30). 14

15 Figure 30: Burden Resistor The current leaving the polarity marks of the current transformer are divided into two current paths (Figure 29). One circuit path flows through the burden resistor in the paralleling module. The second circuit path flows through the crosscurrent loop. The current that flows in the crosscurrent loop will enter the burden resistor in the adjoining parallel circuit and will oppose the current through the burden resistor set up by the paralleling circuit s own current transformer. The resulting current flow through the burden resistor in each paralleling circuit will be zero because the opposing currents will cancel each other out. Thus, there will be no voltage developed across the burden resistor and no droop associated with the line voltage. If one generator begins to assume more reactive load than the other generator, the line current will increase and the current from the secondary of the current transformer will also increase. The result will cause a greater voltage across the burden resistor of the paralleling circuit, which will cause the voltage regulator to reduce the excitation in that particular generator, thus decreasing line current. An increase in current through the crosscurrent connect loop caused by the imbalance of the first generator will develop a voltage across the second generator s paralleling burden resistor that is opposite in polarity to the normal voltage developed by the second generator s own current transformer. Instead of causing a droop in line voltage, the opposite polarity will cause an increase in line voltage. The resulting increase in one generator and a decrease in the other generator will cause the parallel generating system to balance itself out. For the reactive differential compensation to perform properly, all of the paralleling current transformers on all of the generators delivering power to the bus must be connected into the crosscurrent loop. The current transformer connected in the loop must have the same ratios so that each current transformer supplies the same amount of current to properly cancel the voltage across the burden resistor. In the case where different size generators are paralleled, current transformer ratios must be changed to give approximately the same secondary current as the other current transformer(s). Otherwise, cancellation of the currents in the crosscurrent loop will not occur, and the imbalance of current will force the generators to have circulating currents between them. In addition to having the same current transformer ratios, all generators must have the same burden resistor setting in the voltage regulator paralleling circuit. Having the same burden resistor setting ensures that when an imbalance exists in the generators, the current that flows in the crosscurrent loop will setup a proportional voltage across each burden resistor that will balance the generator system s reactive load. 15

16 Figure 31: Reactive Differential Compensation Connection In order to perform properly, the crosscurrent loop must have all the generators tied into the loop. It is virtually impossible to parallel with an infinite bus (utility). If the crosscurrent connected generating system was paralleled with the utility outside the crosscurrent loop, a switch contact installed at any point in the loop may be opened, and all generators will operate in droop mode. For compliance with most safety codes, a ground connection is placed on the CT secondary. Only one ground can be installed on the loop, the current transformers will be shorted out (Figure 31). Some means of isolation between the regulator sensing circuit and the current transformer circuit must be used with crosscurrent compensation circuits. Basler regulators and paralleling circuits include isolation transformers used to effectively isolate the crosscurrent loop from the input voltage circuit of the regulator. THE CURRENT TRANSFORMER UNIT-PARALLEL SWITCH A switch is placed on the secondary of the current transformer to short circuit the current transformer and the burden resistor, which will negate any signal to the generator. The switch in the Unit position allows the generator to operate independently of the parallel generating system without the effect of the droop circuit. 16

17 When a generator is operating independently in a parallel droop system and the short circuit switch is not in the Unit position, the generator will have an unwanted droop in the generator output voltage. The same effect will happen in a crosscurrent system only the droop will be smaller because other burden resistors in series act as a voltage divider to decrease the amount of voltage proportionally. When generators are operating in a crosscurrent loop and one generator is taken out of parallel with the other generators to operate independently, the unit parallel switch is important to maintaining the stability of the remaining generators paralleled. If the nonparalleled generator is disconnected from the line with the current transformer and the burden resistor not shorted, the parallel system voltage will fluctuate. The generator not paralleled will be rotating at a different speed and frequency compared to the paralleled generators. The current through the burden resistor of the non-paralleled generator will have a constantly varying phase angle compared to the current through the paralleled generator burden resistors. The constantly changing phase angle across the burden resistor current of the non-paralleled generator will cause the non-paralleled regulator to alternately raise and lower the excitation of the non-paralleled generator. This will produce a small periodic change in excitation, which will increase and decrease that generator s output voltage. The rate at which the voltage will fluctuate is equal to the difference in frequency from the non-paralleled generator and the paralleled generators. Figure 32: Unit - Parallel Switch If a unit-parallel switch is to be added externally to a paralleling circuit, attention must be made to the distance the switch is to be placed from the current transformer secondary terminals (Figure 32). If a considerable distance is required for connection of the switch, resistance from the wire to and from the switch might be great enough to allow some of the current to pass through the burden resistor. If a small current is allowed to flow through the burden resistor, an equally small voltage will be produced across the burden resistor and produce a small droop in the system voltage, if the system is paralleled with reactive droop compensation. If so, reactive differential compensation is used to produce an effect similar to that just described for the crosscurrent loop in the preceding paragraph. Connections to the shorting switch should be made as short as possible. 17

18 Note: When operating with the reactive differential compensation circuit, it is desirable to have the unit parallel switch be an auxiliary contact on the main generator breaker. The auxiliary contact should be closed and the CT secondary shorted when the main generator breaker is open. The instant the main generator breaker closes connecting the generator in parallel, the auxiliary contact should open removing the short from the CT secondary allowing it to give the reactive load signal. This prevents any voltage droop from being introduced and eliminates the fluctuating voltage of the oncoming generator described earlier. Figure 33: Generator Phase Sequence/Current Transformer Polarity Relationship CURRENT TRANSFORMER PLACEMENT ON UNMARKED PHASES As mentioned before, the current transformer can be connected to any phase of the generator as long as the system voltage is taken from the appropriate line voltage to maintain a 90 electrical degree phase difference with the burden resistor voltage. If it cannot be determined which generator lines are phase A, B, and C, the paralleling current transformer should be placed on the generator phase that does not supply sensing voltage to the regulator. If the regulator is set up with the generator for three phase sensing, the current transformer must be placed on the phase where the voltage regulator senses the B phase (Figure 33). The polarity connection of the current transformer will be the determining factor to whether the generators are paralleled correctly if the phase rotation is undeterminable. If the current transformer is connected incorrectly, the generator will not droop but will rise in voltage under lagging inductive load. If crosscurrent compensation is used to parallel the generators, it is recommended that the crosscurrent connecting loop be left open at one point until proper parallel option is achieved with the parallel droop compensation. 18

19 CURRENT TRANSFORMER SELECTION Generators of different size KVA and line voltage have different line currents. When generators of different KVA are paralleled, current transformers used to parallel the generators must have correct current transformer ratios to provide nominal secondary current that is equal to other current transformers. A typical current transformer has a nominal 5 ampere secondary current with a maximum burden of 25VA. Obviously, to have a secondary current of 5 amperes, the primary current must be equal to the current rating of the primary. Matching current transformer ratios with line current to provide a nominal secondary current output from the current transformer is a detail that must not be overlooked. Table 1 shows the design specifications of typical current transformers. When selecting a current transformer to step-down generator line current, if the line current falls between the current transformer primary ratings of two current transformers, the current transformer with the higher primary current rating should be selected. The reason for selection of the higher primary rating is to keep the current transformer within its maximum limits. The problem caused by using a current transformer with a lower primary rating is that the higher line current will force a higher secondary current than the nominal 5 amperes. A secondary current that exceeds the nominal 5 ampere value can cause the burden of the paralleling circuit to be greater than the maximum designed burden rating of the current transformer. Excessive current can cause transformers to reach saturation, which will change inductance values of the transformers. The resulting change in inductance can alter the phase angle of the signal that is sent to the voltage regulator for paralleling, causing an improper response from the regulator. On the other hand, it is also possible to select a current transformer with a primary rating that is too high. In such a case, the secondary current supplied to the paralleling circuit will be insufficient and paralleling operation can run uncontrolled or weak. Sometimes selecting a higher current transformer ratio and doubling the primary turns of the generator line can achieve a closer secondary current to the nominal 5 amperes. For best selection of a current transformer, finding a current transformer with a current transformer ratio that will provide the closest possible current to the nominal 5 amperes is suggested. Satisfactory parallel operation can usually be achieved if a minimum of three amperes at full load rated power factor is provided. Current Transformer Requirements - Droop Instrument accuracy - accurate magnitude - accurate phase - may be shared Ratio selected for minimum 3 amps (0.6 Amps) Ratio selected for maximum 5 amps (1.0 Amps) 19

20 CT Requirements - Cross Current Compensation Ratios equal for equal genset ratings Ratios proportional if unequal ratings Burden resistors same for all units No groundings in each secondary CT Burden Requirements Basler s AVRs have burdens between 0.2 and 1 ohm, 5 amp or 1 amp nominal current. CT must have sufficient capacity to drive all loads, lead wire resistance. Breaker aux contact and wire must be low in resistance to short CT effectively. Model Number Current Ratio (Amper es) ANSI Relay Class ANSI Metering Class (60HZ) Winding Resistance Ohms (25 C) Net Weight (lbs) Shipping Weight (lbs.) BO.1 BO.2 BO.3 BO.4 BO.5 CT2 200:5 C :5 C CT3 300:5 C :5 C CT5 500:5 C :5 750:5 C20 C CT : CT : CT : CT : CT : CT : CT : Table 1: Electrical Ratings PARALLELING DIFFERENT SIZE GENERATORS When generators of different KVA are paralleled, each generator will have a different line current. To parallel the different size generators, current transformers of different ratios will have to be used to step-down the different line currents to a standard nominal secondary current. For droop operation, the droop adjustment is used so that each generator droops a like amount at its rated load. Then, the generators can be paralleled and each generator can be adjusted to carry its proportional share of the reactive load. For generators paralleled with reactive differential compensation, equal currents are needed to cancel opposite currents so that no droop in the generating system is present. The unequal currents presented by the current transformers will force the cross-current loop to operate at an imbalance and maintain circulating currents. To decrease the imbalance of current through the cross-current loop, have all burden resistors set at maximum resistance. Then the burden resistor across the current transformer with the smallest secondary current should be adjusted for a smaller resistance so more current can flow 20

21 through the resistor. The burden resistor should only be adjusted for a small amount. Decreasing the burden resistance causes the response of the generator to be less sensitive to imbalances in the loop due to reactive loading. The burden resistor should only be adjusted a small amount so as to maintain proper control of circulating currents and also to decrease the current imbalance of the loop due to the current transformers. It must be pointed out that if current transformer secondary current among generators varies only by a few tenths of an ampere, conditions will be such that the imbalance injected into the cross-current loop or parallel droop circuits will be neglectable. PARALLELING GENERATORS To illustrate the considerations and paralleling equipment necessary to parallel generator sets, the two following examples of parallel three generator systems are presented. Two generating systems composed of three generators connected for parallel operation are illustrated in Figures 34 and 35. In Figure 35, the three generators are connected for parallel droop compensation; and in Figure 34, the three generators are connected for cross-current compensation. Both parallel generator systems have two 625 KVA generators with a kilowatt rating of 500 kw and one 125 KVA generator with a kilowatt rating of 100 kw. 21

22 Figure 34: Cross-Current Compensation Connections Figure 35: Parallel Droop Compensation Connections 22

23 Each generator has a line-to-line voltage of 480 volts so the generators can be connected to a common bus. From the given information about the generators, the current for each generator is calculated from the apparent power (KVA) of the generator. KVA = 3 I L V L The current for the 500 KVA generators is 752 amperes, and the current for the 125 KVA generator is 150 amperes. The voltage regulators chosen for the generators operating with parallel droop compensation were selected to illustrate that voltage regulators do not necessarily have to be the same to operate with parallel droop. Both the 625 KVA generators are regulated with Basler SSR regulators, and the 125 KVA generator is regulated with a generic voltage regulator. Basler voltage regulators and paralleling modules feature a built-in isolation transformer for cross-current compensation. The isolation transformer is necessary to prevent the sensing circuit of the regulators from being paralleled by the cross-current connections between generators. To determine how to add paralleling provision to a Basler regulator, Figure 35 can be used to make the selection. The SSR regulators that are used on the 625 KVA generators are equipped with paralleling provision as an option. The generic regulator has no paralleling provisions built-in so a Basler APM 300 paralleling module will be selected. The SSR voltage regulators equipped with paralleling provisions do not have a built-in unit/ parallel switch to short out the current transformer and take the generator off-line or operate independent of the other generators. An external unit/parallel switch is added to the SSR voltage regulators. To further illustrate paralleling different size generators in the cross-current mode, Figure 33 shows two Basler SSRs with a regulator of a different manufacturer or a Basler regulator with a different burden resistor value. To allow these generators to be connected in cross current, the burden resistors must match. This figure shows adding external resistors to the SSRs paralleling circuit to match burdens with the APM 300. We calculated this value using the following method. 23

24 METHOD FOR DETERMINING DROPPING RESISTOR VALUE WHEN CONNECTING DISSIMILAR REGULATORS IN CROSS-CURRENT COMPENSATION CONFIGURATION 1. Start with the VA rating and current signal of each regulator and find its equivalent resistance. Example: SSR Regulators: 10 VA, 5 Amps V = VA = 10 = 2 Volts; R = V = 2 = 0.4 ohms A 5 A 5 Other regulator: 25 VA, 5 Amps V = VA = 25 = 5 Volts; R = V = 5 = 1.0 ohms A 5 A 5 2. Take the regulator with the lowest VA rating (Voltage V ) and determine the value of series resistance necessary to drop the applied voltage from the larger VA rating to that required by the present regulator. See figure below. Figure 36: Voltage Regulator with External Matching Resistor 24

25 From previous example: 2V, 0.4 Ohms; 5V, 1.0 Ohms The required voltage is 2 volts but the supplied voltage is 5 volts; therefore, the series resistor should drop 3 volts: V Required = V Supplied RRegulator R Regulator + R Series 2 = R Series 2 (0.4 + R Series ) = 5 (0.4) R Series = 1 R Series = 0.6 Ohms The wattage of the series resistor can be calculated from: W = I 2 R W = = 15 Watts Since we derate our resistors by 50%, the required wattage will be 30 watts. The next standard wattage value is 50 watts. Figure 37: Parallel Generator Setup 25

26 TROUBLESHOOTING PARALLELING Abnormal indications Immediate increase in current Difficult to adjust voltage adjust for null Changing loads cause unbalance For immediate high current Check paralleling in droop only Verify that kw load is properly shared Check SENSING connections to AVR CT in correct phase?? Reverse CT secondary polarity Try to parallel again If all above is OK, try to close cross current loop Correct CT polarity?? Place CT on correct phase - No sensing connection, or - E2 sensing connection If CT is on correct phase, polarity is: - Correct, and closing breaker works okay, or - Reversed, and closing breaker causes immediate high current Wrong phase, possibilities MULTIPLY!!! Finding the problems Check for small voltage across droop input. CT may be shorted somewhere. Check droop adjust. Max or min?? Check polarity marks on PTs with small battery and voltmeter Verify PT connections, CT in correct phase Figure 38: Potential Transformer Polarity Check 26

27 Another test OK to parallel without any droop on one machine, with careful attention. Check to see that two machines can share load if only one of the droop CTs is not shorted. If loading is possible, check for direction of droop by increasing drooping AVR voltage adjust. Another test Connect oscilloscope to E1 and E3, channel 1 Connect channel 2 to Droop input, 1 and 2 With some resistive load current, observe 90 phase shift from voltage to current Figure 39: AVR with Droop 27

28 28

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER

More information

Three phase circuits

Three phase circuits Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors

More information

Introduction to Paralleling of LTC Transformers by the Circulating Current Method

Introduction to Paralleling of LTC Transformers by the Circulating Current Method TAPCHANGER CONTROLS Application Note #11 Introduction to Paralleling of LTC Transformers by the Circulating Current Method 1.0 ABSTRACT This Application Note discusses the elements of paralleling load

More information

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA What are phasors??? In normal practice, the phasor represents the rms maximum value of the positive half cycle of the sinusoid

More information

SYNCHRONOUS MACHINES

SYNCHRONOUS MACHINES SYNCHRONOUS MACHINES The geometry of a synchronous machine is quite similar to that of the induction machine. The stator core and windings of a three-phase synchronous machine are practically identical

More information

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt.

Equipment: Power Supply, DAI, Synchronous motor (8241), Electrodynamometer (8960), Tachometer, Timing belt. Lab 9: Synchronous motor. Objective: to examine the design of a 3-phase synchronous motor; to learn how to connect it; to obtain its starting characteristic; to determine the full-load characteristic of

More information

AC Generators. Basic Generator

AC Generators. Basic Generator AC Generators Basic Generator A basic generator consists of a magnetic field, an armature, slip rings, brushes and a resistive load. The magnetic field is usually an electromagnet. An armature is any number

More information

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only

ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only ATTACHMENT F CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category

More information

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321) Lab 4: 3-phase circuits. Objective: to study voltage-current relationships in 3-phase circuits; to learn to make delta and Y connections; to calculate and measure real, apparent, and reactive powers. Equipment:

More information

SX460. Generator Automatic Voltage Regulator Operation Manual

SX460. Generator Automatic Voltage Regulator Operation Manual SX460 Generator Automatic Voltage Regulator Operation Manual Self Excited Automatic Voltage Regulator Compatible with Newage SX460* * Use for reference purpose only and not a genuine Newage product. 1.

More information

Type SA-1 Generator Differential Relay

Type SA-1 Generator Differential Relay ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes

More information

Power Factor Correction for Power Systems First Semester Report Spring Semester 2007

Power Factor Correction for Power Systems First Semester Report Spring Semester 2007 Power Factor Correction for Power Systems First Semester Report Spring Semester 2007 by Pamela Ackerman Prepared to partially fulfill the requirements for EE401 Department of Electrical and Computer Engineering

More information

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392 1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of

More information

Lab 14: 3-phase alternator.

Lab 14: 3-phase alternator. Lab 14: 3-phase alternator. Objective: to obtain the no-load saturation curve of the alternator; to determine the voltage regulation characteristic of the alternator with resistive, capacitive, and inductive

More information

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements

More information

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS

More information

= V peak 2 = 0.707V peak

= V peak 2 = 0.707V peak BASIC ELECTRONICS - RECTIFICATION AND FILTERING PURPOSE Suppose that you wanted to build a simple DC electronic power supply, which operated off of an AC input (e.g., something you might plug into a standard

More information

Science and Reactor Fundamentals Electrical CNSC Technical Training Group. Table of Contents

Science and Reactor Fundamentals Electrical CNSC Technical Training Group. Table of Contents Electrical Science and Reactor Fundamentals Electrical i Table of Contents 1 Objectives... 1 1.1 BASIC ELECTRICAL THEORY... 1 1.2 TRANSFORMERS... 1 1.3 GENERATORS... 2 1.4 PROTECTION... 3 2 BASIC ELECTRICAL

More information

DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor.

DC GENERATOR THEORY. LIST the three conditions necessary to induce a voltage into a conductor. DC Generators DC generators are widely used to produce a DC voltage. The amount of voltage produced depends on a variety of factors. EO 1.5 LIST the three conditions necessary to induce a voltage into

More information

Current Transformers Ratio / Polarity / Types

Current Transformers Ratio / Polarity / Types CT1 Current Ratio / Polarity / Types Application Current (CT s) are instrument transformers that are used to supply a reduced value of current to meters, protective relays, and other instruments. CT s

More information

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E. By Darrell G. Broussard, P.E. Introduction: As engineers, we are aware that electrical power systems have grown. How much have they grown? When was the last time you specified a 2400-volt system, a 4160-volt

More information

INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS

INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS INTRODUCTION TO SYNCHRONIZING AUTOMATIC SYNCHRONIZING CONSIDERATIONS AND APPLICATIONS INTRODUCTION It is the intention of this presentation to provide an explanation of the automatic synchronizing process,

More information

1. The diagram below represents magnetic lines of force within a region of space.

1. The diagram below represents magnetic lines of force within a region of space. 1. The diagram below represents magnetic lines of force within a region of space. 4. In which diagram below is the magnetic flux density at point P greatest? (1) (3) (2) (4) The magnetic field is strongest

More information

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT

EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT EDEXCEL NATIONAL CERTIFICATE/DIPLOMA UNIT 5 - ELECTRICAL AND ELECTRONIC PRINCIPLES NQF LEVEL 3 OUTCOME 4 - ALTERNATING CURRENT 4 Understand single-phase alternating current (ac) theory Single phase AC

More information

3-Phase AC Calculations Revisited

3-Phase AC Calculations Revisited AN110 Dataforth Corporation Page 1 of 6 DID YOU KNOW? Nikola Tesla (1856-1943) came to the United States in 1884 from Yugosiavia. He arrived during the battle of the currents between Thomas Edison, who

More information

Transformer Calculations

Transformer Calculations Transformer Calculations Transformers Transformers are one of the most basic yet practical devices used today. No matter where you are there is always a transformer nearby. They are used throughout alternating-current

More information

R438 A.V.R. Installation and maintenance R 438. This manual is to be given to. the end user T10. Armature 6- Field X2 Z1 X1 Z2 E+ E- 0V 110 220

R438 A.V.R. Installation and maintenance R 438. This manual is to be given to. the end user T10. Armature 6- Field X2 Z1 X1 Z2 E+ E- 0V 110 220 Armature 6- This manual is to be given to the end user 1 T5 Field Slow fuse 250V 8 A with LAM without LAM 10 Yellow 11 Red 12 Black 9 Green X2 Z1 X1 Z2 E+ E- 0V 110 220 T3 quency T10 50Hz 60Hz LAM 13 %

More information

W03 Analysis of DC Circuits. Yrd. Doç. Dr. Aytaç Gören

W03 Analysis of DC Circuits. Yrd. Doç. Dr. Aytaç Gören W03 Analysis of DC Circuits Yrd. Doç. Dr. Aytaç Gören ELK 2018 - Contents W01 Basic Concepts in Electronics W02 AC to DC Conversion W03 Analysis of DC Circuits (self and condenser) W04 Transistors and

More information

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21, 2012 1

Current Transformers. Bonneville Power Administration. Steve Laslo For the Hands On Relay School (3-12) Revision 1.1. February 21, 2012 1 Current Transformers Bonneville Power Administration Steve Laslo For the Hands On Relay School (3-12) Revision 1.1 February 21, 2012 1 Basic Theory: CT as a Voltage Transformer February 21, 2012 2 CT as

More information

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:

RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features: Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog

More information

Instrument Transformer Wiring Troubleshooting Guide Three Phase Meters Revision 0, Initial Issue, April 26, 1993

Instrument Transformer Wiring Troubleshooting Guide Three Phase Meters Revision 0, Initial Issue, April 26, 1993 R Instrument Transformer Wiring Troubleshooting Guide Three Phase Meters Revision 0, Initial Issue, April 26, 1993 CONTENTS I. How to Use This Guide II. Common Problems for 3-Wire and 4-Wire Systems III.

More information

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP PacifiCorp Original Sheet No. 476 APPENDIX 2 TO SGIP SMALL GENERATOR INTERCONNECTION REQUEST (Application Form) Transmission Provider: Designated Contact Person: Address: Telephone Number: An Interconnection

More information

Chapter 24. Three-Phase Voltage Generation

Chapter 24. Three-Phase Voltage Generation Chapter 24 Three-Phase Systems Three-Phase Voltage Generation Three-phase generators Three sets of windings and produce three ac voltages Windings are placed 120 apart Voltages are three identical sinusoidal

More information

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6

Effective: September 10, 2006 Vermont Attachment 1 to Rule 5.500 Public Service Board Page 1 of 6 Public Service Board Page 1 of 6 STANDARD APPLICATION FOR INTERCONNECTION OF GENERATION RESOURCES IN PARALLEL TO THE ELECTRIC SYSTEM OF: (Interconnecting Utility) Preamble and Instructions: An owner of

More information

Transformer circuit calculations

Transformer circuit calculations Transformer circuit calculations This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011 AM 5-202 BASIC ELECTRONICS AC CIRCUIT ANALYSIS December 2011 DISTRIBUTION RESTRICTION: Approved for Pubic Release. Distribution is unlimited. DEPARTMENT OF THE ARMY MILITARY AUXILIARY RADIO SYSTEM FORT

More information

UPS Applications and VRLA Battery Sizing

UPS Applications and VRLA Battery Sizing TECHNICAL BULLETIN 41-7334 UPS Applications and VRLA Battery Sizing 41-7334/0213/CD www.cdtechno.com The uninterruptable power system (UPS) is used to protect critical equipment and processes from the

More information

Diode Applications. As we have already seen the diode can act as a switch Forward biased or reverse biased - On or Off.

Diode Applications. As we have already seen the diode can act as a switch Forward biased or reverse biased - On or Off. Diode Applications Diode Switching As we have already seen the diode can act as a switch Forward biased or reverse biased - On or Off. Voltage Rectifier A voltage rectifier is a circuit that converts an

More information

Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture - 33 3 phase System 4

Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture - 33 3 phase System 4 Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore Lecture - 33 3 phase System 4 Hello everybody. So, in the last class we have been

More information

FAULT FINDING MANUAL For Self Excited and Separately Excited Generators

FAULT FINDING MANUAL For Self Excited and Separately Excited Generators FAULT FINDING MANUAL For Self Excited and Separately Excited Generators SAFETY PRECAUTIONS Before testing the generating set, read the generating set Installation Manual, and this Fault Finding Manual,

More information

Pow-R-Con Multi Function Control

Pow-R-Con Multi Function Control 37264 Pow-R-Con Multi Function Control Product Specification Product Specification 37264 Product Information DYNA Power Controls Pow-R-Con TM GENERAL The Barber-Colman Pow-R-Con TM represents an integrated

More information

DOE FUNDAMENTALS HANDBOOK ELECTRICAL SCIENCE Volume 3 of 4

DOE FUNDAMENTALS HANDBOOK ELECTRICAL SCIENCE Volume 3 of 4 DOE-HDBK-1011/3-92 JUNE 1992 DOE FUNDAMENTALS HANDBOOK ELECTRICAL SCIENCE Volume 3 of 4 U.S. Department of Energy Washington, D.C. 20585 FSC-6910 Distribution Statement A. Approved for public release;

More information

Automatic Voltage Regulator User s Manual

Automatic Voltage Regulator User s Manual Resp. dept. R&D We reserve all rights in this document and in the information contained therein. Reproduction, use or disclosure to third parties without express authority is strictly forbidden. Copyright

More information

R448 & R448 V50 A.V.R.

R448 & R448 V50 A.V.R. Armature + 6- This manual is to be given to the end user F1 ST5 Field Slow fuse 250V 10 A with LAM without LAM 10 Yellow 11 Red 12 Black 9 Green X2 Z1 X1 Z2 E+ E- 0V 110 22 ST3 requency ST10 50Hz 60Hz

More information

Chapter 11. Inductors ISU EE. C.Y. Lee

Chapter 11. Inductors ISU EE. C.Y. Lee Chapter 11 Inductors Objectives Describe the basic structure and characteristics of an inductor Discuss various types of inductors Analyze series inductors Analyze parallel inductors Analyze inductive

More information

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49

Circuits with inductors and alternating currents. Chapter 20 #45, 46, 47, 49 Circuits with inductors and alternating currents Chapter 20 #45, 46, 47, 49 RL circuits Ch. 20 (last section) Symbol for inductor looks like a spring. An inductor is a circuit element that has a large

More information

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009

Impedance Matching and Matching Networks. Valentin Todorow, December, 2009 Impedance Matching and Matching Networks Valentin Todorow, December, 2009 RF for Plasma Processing - Definition of RF What is RF? The IEEE Standard Dictionary of Electrical and Electronics Terms defines

More information

FAULT FINDING MANUAL. For Stamford AC Generators

FAULT FINDING MANUAL. For Stamford AC Generators FAULT FINDING MANUAL For Stamford AC Generators 1 SAFETY PRECAUTIONS Test procedures recommended in this manual assume that the reader is fully conversant with electrical safety principles, and is familiar

More information

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies

The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing

More information

DIRECT CURRENT GENERATORS

DIRECT CURRENT GENERATORS DIRECT CURRENT GENERATORS Revision 12:50 14 Nov 05 INTRODUCTION A generator is a machine that converts mechanical energy into electrical energy by using the principle of magnetic induction. This principle

More information

Equipment: Power Supply, DAI, Universal motor (8254), Electrodynamometer (8960), timing belt.

Equipment: Power Supply, DAI, Universal motor (8254), Electrodynamometer (8960), timing belt. Lab 12: The universal motor. Objective: to examine the construction of the universal motor; to determine its no-load and full-load characteristics while operating on AC; to determine its no-load and full-load

More information

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION

Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Reactive Power and Importance to Bulk Power System OAK RIDGE NATIONAL LABORATORY ENGINEERING SCIENCE & TECHNOLOGY DIVISION Outline What is Reactive Power and where does it come from? Why is it important?

More information

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS

SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to

More information

Aircraft Electrical System

Aircraft Electrical System Chapter 9 Aircraft Electrical System Introduction The satisfactory performance of any modern aircraft depends to a very great degree on the continuing reliability of electrical systems and subsystems.

More information

TESLA Recorder Power Metering Setup Configuration for 3 and 2 Element Watt/VAR Metering

TESLA Recorder Power Metering Setup Configuration for 3 and 2 Element Watt/VAR Metering TESLA Recorder Power Metering Setup Configuration for 3 and 2 Element Watt/VAR Metering Introduction This application note will assist the user to set up 3-phase metering to monitor Watt, VAR and VA power

More information

Unit 33 Three-Phase Motors

Unit 33 Three-Phase Motors Unit 33 Three-Phase Motors Objectives: Discuss the operation of wound rotor motors. Discuss the operation of selsyn motors. Discuss the operation of synchronous motors. Determine the direction of rotation

More information

Lab 8: DC generators: shunt, series, and compounded.

Lab 8: DC generators: shunt, series, and compounded. Lab 8: DC generators: shunt, series, and compounded. Objective: to study the properties of DC generators under no-load and full-load conditions; to learn how to connect these generators; to obtain their

More information

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

3) What is the difference between Insulating, Isolating, and Shielded Winding transformers? Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer

More information

How To Understand And Understand The Theory Of Electricity

How To Understand And Understand The Theory Of Electricity DIRECT CURRENT AND ALTERNATING CURRENT SYSTEMS N. Rajkumar, Research Fellow, Energy Systems Group, City University Northampton Square, London EC1V 0HB, UK Keywords: Electrical energy, direct current, alternating

More information

Three-phase AC circuits

Three-phase AC circuits Three-phase AC circuits This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,

More information

Current Transformers

Current Transformers Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide

More information

Direct Current Motors

Direct Current Motors Direct Current Motors DC MOTORS The DC machine can operate as a generator and as a motor. Chap 5. Electrical Machines by Wildi, 6 e Lecturer: R. Alba-Flores Alfred State College Spring 2008 When a DC machine

More information

Fundamentals of Signature Analysis

Fundamentals of Signature Analysis Fundamentals of Signature Analysis An In-depth Overview of Power-off Testing Using Analog Signature Analysis www.huntron.com 1 www.huntron.com 2 Table of Contents SECTION 1. INTRODUCTION... 7 PURPOSE...

More information

PHASE CONVERSION TECHNOLOGY OVERVIEW

PHASE CONVERSION TECHNOLOGY OVERVIEW Dr. Larry Meiners, Ph.D. PHASE CONVERSION TECHNOLOGY OVERVIEW Introduction A wide variety of commercial and industrial electrical equipment requires three-phase power. Electric utilities do not install

More information

Slide 1 / 26. Inductance. 2011 by Bryan Pflueger

Slide 1 / 26. Inductance. 2011 by Bryan Pflueger Slide 1 / 26 Inductance 2011 by Bryan Pflueger Slide 2 / 26 Mutual Inductance If two coils of wire are placed near each other and have a current passing through them, they will each induce an emf on one

More information

Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt.

Equipment: Power Supply, DAI, Wound rotor induction motor (8231), Electrodynamometer (8960), timing belt. Lab 13: Wound rotor induction motor. Objective: to examine the construction of a 3-phase wound rotor induction motor; to understand exciting current, synchronous speed and slip in this motor; to determine

More information

Constructing a precision SWR meter and antenna analyzer. Mike Brink HNF, Design Technologist.

Constructing a precision SWR meter and antenna analyzer. Mike Brink HNF, Design Technologist. Constructing a precision SWR meter and antenna analyzer. Mike Brink HNF, Design Technologist. Abstract. I have been asked to put together a detailed article on a SWR meter. In this article I will deal

More information

Basics of Electricity

Basics of Electricity Basics of Electricity Generator Theory PJM State & Member Training Dept. PJM 2014 8/6/2013 Objectives The student will be able to: Describe the process of electromagnetic induction Identify the major components

More information

Physical Address: City: State: Zip Code:

Physical Address: City: State: Zip Code: Application for Small Generator Facility Interconnection Tier 2, Tier 3 or Tier 4 Interconnection (For Small Generator Facilities with Electric Nameplate Capacities of 10 MW and less) Applicant Contact

More information

Line Reactors and AC Drives

Line Reactors and AC Drives Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences

More information

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN

CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN 5.1 Introduction So far in the development of this research, the focus has been to estimate the available insolation at a particular location on the earth s surface

More information

Induced voltages and Inductance Faraday s Law

Induced voltages and Inductance Faraday s Law Induced voltages and Inductance Faraday s Law concept #1, 4, 5, 8, 13 Problem # 1, 3, 4, 5, 6, 9, 10, 13, 15, 24, 23, 25, 31, 32a, 34, 37, 41, 43, 51, 61 Last chapter we saw that a current produces a magnetic

More information

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS

SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive

More information

Lesson 3 DIRECT AND ALTERNATING CURRENTS. Task. The skills and knowledge taught in this lesson are common to all missile repairer tasks.

Lesson 3 DIRECT AND ALTERNATING CURRENTS. Task. The skills and knowledge taught in this lesson are common to all missile repairer tasks. Lesson 3 DIRECT AND ALTERNATING CURRENTS Task. The skills and knowledge taught in this lesson are common to all missile repairer tasks. Objectives. When you have completed this lesson, you should be able

More information

FREQUENCY CONTROLLED AC MOTOR DRIVE

FREQUENCY CONTROLLED AC MOTOR DRIVE FREQUENCY CONTROLLED AC MOTOR DRIVE 1.0 Features of Standard AC Motors The squirrel cage induction motor is the electrical motor motor type most widely used in industry. This leading position results mainly

More information

Eðlisfræði 2, vor 2007

Eðlisfræði 2, vor 2007 [ Assignment View ] [ Print ] Eðlisfræði 2, vor 2007 30. Inductance Assignment is due at 2:00am on Wednesday, March 14, 2007 Credit for problems submitted late will decrease to 0% after the deadline has

More information

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd 100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center Introduction Roger Hedding Steven Schoenherr, P.E. ABB Inc. Minnesota Power 598 N. Buth Rd 3215 Arrowhead Rd Dousman,

More information

Motor Fundamentals. DC Motor

Motor Fundamentals. DC Motor Motor Fundamentals Before we can examine the function of a drive, we must understand the basic operation of the motor. It is used to convert the electrical energy, supplied by the controller, to mechanical

More information

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated? Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux

More information

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated

More information

Using Current Transformers with the 78M661x

Using Current Transformers with the 78M661x A Maxim Integrated Products Brand Using Current Transformers with the 78M661x APPLICATION NOTE AN_661x_021 April 2010 Introduction This application note describes using current transformers (CT) with the

More information

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12

Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12 Table of Contents The Basics of Electricity 2 Using a Digital Multimeter 4 IDEAL Digital Multimeters An Introduction The Basics of Digital Multimeters is designed to give you a fundamental knowledge of

More information

Power Quality Standards for Electric Service

Power Quality Standards for Electric Service Power Quality Standards for Electric Service Effective June 1, 2008 A transition period will exist from June 1 through December 31, 2008 in which installations may be approved and connected as long as

More information

Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module

Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module Module 1 www.learnabout-electronics.org Power Supplies 1.0 Power Supply Basics What you ll learn in Module 1 Section 1.0 Power Supply Basics. Basic functions of a power supply. Safety aspects of working

More information

Reading assignment: All students should read the Appendix about using oscilloscopes.

Reading assignment: All students should read the Appendix about using oscilloscopes. 10. A ircuits* Objective: To learn how to analyze current and voltage relationships in alternating current (a.c.) circuits. You will use the method of phasors, or the vector addition of rotating vectors

More information

Electrical Fundamentals Module 3: Parallel Circuits

Electrical Fundamentals Module 3: Parallel Circuits Electrical Fundamentals Module 3: Parallel Circuits PREPARED BY IAT Curriculum Unit August 2008 Institute of Applied Technology, 2008 ATE310- Electrical Fundamentals 2 Module 3 Parallel Circuits Module

More information

By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document

By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document By Authority Of THE UNITED STATES OF AMERICA Legally Binding Document By the Authority Vested By Part 5 of the United States Code 552(a) and Part 1 of the Code of Regulations 51 the attached document has

More information

7. Reactive energy compensation

7. Reactive energy compensation 593 7. Reactive energy compensation 594 7. REACTIVE ENERGY COMPENSATION Reactive energy compensation is an important element for reducing the electricity bill and improving the quality of the electrical

More information

USE OF A SINGLE ELEMENT WATTMETER OR WATT TRANSDUCER ON A BALANCED THREE-PHASE THREE-WIRE LOAD WILL NOT WORK. HERE'S WHY.

USE OF A SINGLE ELEMENT WATTMETER OR WATT TRANSDUCER ON A BALANCED THREE-PHASE THREE-WIRE LOAD WILL NOT WORK. HERE'S WHY. USE OF A SINGLE ELEMENT WATTMETER OR WATT TRANSDUCER ON A BALANCED THREE-PHASE THREE-WIRE LOAD WILL NOT WORK. HERE'S WHY. INTRODUCTION Frequently customers wish to save money by monitoring a three-phase,

More information

Tamura Closed Loop Hall Effect Current Sensors

Tamura Closed Loop Hall Effect Current Sensors Tamura Closed Loop Hall Effect Current Sensors AC, DC, & Complex Currents Galvanic Isolation Fast Response Wide Frequency Bandwidth Quality & Reliability RoHs Compliance Closed Loop Hall Effect Sensors

More information

Application Note. So You Need to Measure Some Inductors?

Application Note. So You Need to Measure Some Inductors? So You Need to Measure Some nductors? Take a look at the 1910 nductance Analyzer. Although specifically designed for production testing of inductors and coils, in addition to measuring inductance (L),

More information

Buck - Boost Transformers

Buck - Boost Transformers Buck - Boost Transformers Contents Buck - Boost Transformers - Terms & Definitions... 48 Buck - Boost Transformers - Sizing... 50 Quick Reference Chart - 08, 0, 40 Volts Single & Three Phase... 5 Single

More information

Product Data Bulletin

Product Data Bulletin Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system

More information

Transistor Amplifiers

Transistor Amplifiers Physics 3330 Experiment #7 Fall 1999 Transistor Amplifiers Purpose The aim of this experiment is to develop a bipolar transistor amplifier with a voltage gain of minus 25. The amplifier must accept input

More information

Diodes have an arrow showing the direction of the flow.

Diodes have an arrow showing the direction of the flow. The Big Idea Modern circuitry depends on much more than just resistors and capacitors. The circuits in your computer, cell phone, Ipod depend on circuit elements called diodes, inductors, transistors,

More information

Inductors in AC Circuits

Inductors in AC Circuits Inductors in AC Circuits Name Section Resistors, inductors, and capacitors all have the effect of modifying the size of the current in an AC circuit and the time at which the current reaches its maximum

More information

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance

Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance ndustrial Circuits Application Note Drive circuit basics For a given size of a stepper motor, a limited space is available for the windings. n the process of optimizing a stepper motor drive system, an

More information

Fundamentals of Power

Fundamentals of Power Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At

More information

Step Voltage Regulators

Step Voltage Regulators Step Voltage Regulators Don Wareham Field Application Engineer Today s Agenda Introduction Voltage Regulator theory Voltage Regulator application considerations Installation and proper bypassing Wrap-up/questions

More information

High Voltage Power Supplies for Analytical Instrumentation

High Voltage Power Supplies for Analytical Instrumentation ABSTRACT High Voltage Power Supplies for Analytical Instrumentation by Cliff Scapellati Power supply requirements for Analytical Instrumentation are as varied as the applications themselves. Power supply

More information