Experts speak on UPS output Watt, VA, and Power Factor ratings.
|
|
|
- Chloe Hall
- 10 years ago
- Views:
Transcription
1 Experts speak on UPS output Watt, VA, and Power Factor ratings. DATA CENTER SOLUTIONS For More Information: (866) White Paper #13
2 Executive Summary Experts speak on the subject of UPS output ratings, and how the use of UPS with an output power factor rating of 1 reduces uncertainty of overloading the power system. 2
3 Computer Power Requirements are Changing Over the past several years, electrical requirements of computer systems have changed - dramatically. Unfortunately for consulting engineers, computer users and facility engineers, many UPS system designs have not kept pace with these changes. The overall power factor requirements of computers today is exceeding 95, even 97%, which is very high, says Peter Gross, Executive Principal and Managing Director for Mission Critical Facilities for Los Angeles- and New York-based EYP. This is almost entirely distortion power factor and very little displacement power factor. It s almost a unity power factor, as opposed to years ago when the power factor was typically.85,.86,.87. John Stapleton, Associate at the New York City-headquartered JB&B, agrees: Computer loads have gone up from a.8 power factor rating in recent years, he says. I think on average now we see.92 power factor-type loads. Almost every new computer design today requires a unity power factor, except for some of the very small PCs, adds Al Kesterson, Principal of Boca Raton, Florida-based Kamm Consulting, an electrical/mechanical consulting firm. Consequences of overload conditions A UPS is extremely unforgiving of overload, says Michael Fluegeman, Senior Project Engineer in the Los Angeles office of New York City-headquartered Syska & Hennessy. Unlike most equipment in a data or telecommunications center, circuit breakers, transformers, wiring and especially air conditioning systems, if you overload those systems, you may trigger alarms, but you are likely to have time to deal with the problem. If you overload a transformer, it emits more noise, it gets a little hotter, but it doesn t break, it doesn t shut itself down, at least not right away. If you overload a UPS, especially one with a double conversion design, it shuts down. It may stay on utility bypass until someone notices and corrects the problem. In the meantime, critical computing systems have no protection, no battery backup. UPS systems are very unforgiving of overload. Fluegeman advises computer users and their consultants: If a UPS becomes more than 90% loaded in today s dynamic computer operations, then most installed UPS systems may be in jeopardy of overloading. kw vs. kva Understanding the Importance of Real Power Kilowatts (kw) are a measure of the real power drawn by the equipment, whereas kilo volt-amps (kva) are a measure of apparent power. For an easy analogy, think of a glass of draft root beer. The liquid portion is the drinkable part or real component, akin to the kw. The foam plus the liquid comprise the sum total, or the kva. If a root beer is very carefully poured to result in all liquid and no foam, the drinkable portion is the entire glass of root beer (kw=kva). In this case, the ratio of kw to kva, known as the power factor, would be 1.0, or unity power factor. Herein lies the crux of the problem: While computer loads have been approaching unity power factor in recent years, many UPS systems are still being manufactured with.8 or.9 power factor ratings, with some as low as.66. To complicate the issue, many UPS manufacturers market 3
4 kva as the more important capacity measurement to users and consultants who may not be keenly aware of the effects of changing computer power requirements. When someone buys a 100 kva UPS designed with a.8 power factor, in reality he is buying the equivalent of an 80 kva UPS that has unity power factor rating, says Gross. They pay for a 100 kva UPS, but in reality, with the load approaching unity power factor, they only get an 80 kva system, only 80% of the UPS capacity they thought they were buying. This isn t a simple matter of wasting the company s money, as Gross explains. It can be very dangerous if users and consultants don t understand this concept because there is a risk of overloading the UPS. It is more likely to exceed the KW rating than the kva rating. When this happens, the UPS will need to transfer to bypass. That puts the computer load at risk. UPSs are designed to operate below both the kva and the kw ratings, he says. It s a kw overload that generates conditions for overheating the UPS. When you exceed the kw rating, you are going into a turmoil condition. Critical UPS components and assemblies can overheat and begin to degrade. If users not familiar with this issue solely focus on UPS kva nameplate capacity ratings, they run the risk of purchasing a UPS system that won t be able to deliver reliable UPS power, particularly as a displacement power factor rated UPS is loaded to more than 90% - even if only temporarily. The reality is you re in less danger of inadvertently overloading an APC box than other designs because of the unity power factor that it can deliver, says Fluegeman. Everyone would like to have a capacity buffer of 20-25%, but with a UPS other than APC, the UPS may not be telling you that it is as close to being overloaded as it really is. It s not that kva is an unimportant rating, since it has crucial implications for wire, transformer and circuit breaker sizing, but it s not as reflective of a UPS s operational load limiting factor, says Fluegeman. The kw rating typically is. You want to hit both limits-kw and kva - at the same time, and APC s Delta Conversion technology design allows you to do that. With other UPS designs, you re going to max out on kw before you even get close to reaching maximum kva. With APC s design, because kw and kva capacities are equal, you have a far more accurate indication of the actual loading of the UPS, Fluegeman adds. APC s Delta Conversion s Edge Over Outdated Double Conversion Designs Fueled by competitive manufacturers, disagreement has emerged with some in the consulting engineering community as to whether Delta Conversion On Line UPS designs are true online systems. APC s technology is absolutely online, Kesterson confirms. There s no question about it. The fact that it s Delta Conversion doesn t change a thing. Legacy UPS systems use 30-year-old double conversion technologies, which convert utility power twice (AC to DC from the utility and DC to AC to the critical load). Delta Conversion On Line technology 4
5 eliminates this double conversion while providing a KW rating equal to the KVA rating; a significant advantage over legacy UPS systems. Delta Conversion On Line technology offers users and consultants other advantages: = Installation costs are much lower than those associated with double conversion, which requires oversized generators and supplementary distortion filters to cope with the current harmonic distortion and even over sizing of the UPS itself to handle the increasing power factor of new computer loads. = Less energy is lost and less heat is dissipated (meaning lower air conditioning costs). = With unity power factor, Delta Conversion On Line gives you a true measure of the real power - the real capacity of your UPS. The cost of Making Double Conversion Systems achieve unity power factor capability All the major manufacturers could build UPSs with capacity ratings like APC, says Fluegeman. They could and they probably will...in time. But the reason they are still rated at.7,.8,.9 rather than unity is that computer loads in the past pulled a lower power factor rating. At the same time, most engineers vastly oversized the UPS relative to the user s load anyway, which meant UPS manufacturers weren t compelled to improve their designs. Now that computer power factor requirements are approaching unity, it makes sense that the UPS power factor ratings should be higher as well. I think other UPS manufacturers haven t gotten around to adjusting to that. There is a lot of work being done to bring power factor ratings up, says Gross, but it s not easy. To move a box from.8 to.9, you have to find ways to dissipate 10% additional heat, which is not easy. You have to oversize the rectifier and other internal components. The IGBTs or SCRs may also need to be larger. It s a lot of work-and a lot of money. Kesterson agrees: Would I like to see the bar raised to higher power factor-rated UPSs? Absolutely. But costs go up when you do that. When you re talking about improving double conversion UPS technology, you re talking about increased costs because you have to deliver more real watts and it takes more of everything to do that. The other manufacturers are going to have to redesign and bring their power factor ratings up, Fluegeman asserts. Or they are going to simply have to lower the kva rating of the same box because with today s new computer loads kva isn t as important anymore. As computer manufacturers continue the trend to power factor-corrected loads, it will continue to bode well for Delta Conversion technologies like APC s. 5
6 Over sizing UPS Systems A Design Option that Costs Users More Money Before Delta Conversion On Line technology, the only thing a prudent engineer or user could do was compensate -or overcompensate - for the disparity between newer power factor-corrected computers and older double conversion UPS technologies with costly over design of UPS systems. Engineers are always going to design very conservatively to have a cushion. For fast-growing companies, like technology or dot-com companies, for example, it s easy for a UPS to reach a load condition of 90% or higher. When that happens the UPS is max ed out, Fluegeman cautions. If users gave us candid answers to what their UPS needs are, there would be no problem, adds Stapleton. What we wind up doing, however, or what people wind up causing, is wasting their organizations a lot of money because everyone is piling on load numbers. Most people will deny that, but I see it and I can certainly take you to sites where it happens. Dynamic Computer Room Environments Create Potential for Overload What you have today is a mix of old and new computer technology, which eases the problem some, says Stapleton. But once a user puts a new installation in and the computer systems change over to the better, more efficient, power factor-corrected supplies of today, then obviously the potential for problems increases. Users with dynamic computer environments may need to upsize their UPS capabilities because they know the danger they re getting into, Fluegeman adds. The person in charge of UPS reliability is challenged to deal with the entire infrastructure: The switchboard, circuit breakers and upgraded utility service, to name a few. Those upgrades could take months. Until those upgrades are made, the computers keep coming in and the watts keep going up, so they have to rush to get the new UPS upgrades done before they overload the old one. And we all know what happens when people are in a rush. Even in a company that isn t growing by leaps and bounds, changes and upgrades to computer and server hardware can occur on a daily, hourly and even minute-by-minute basis. Computers don t run at a constant speed or constant load draw. A computer s electrical appetite varies depending on how many users are logged on and the nature of their work. While 99% percent of the time computers operate at a relatively constant load, Fluegeman says, if you happen to get a room full of computers or servers that are all going full blast at the same time or you re upgrading hardware, loads may increase and a marginally-sized UPS can overload just when you need it the most. 6
7 Conclusions Advice for Consulting Engineers and UPS Users Engineers who knows their stuff know they have to pay more attention to kilo-watts, says Fluegeman. And those engineers have a responsibility to bring that knowledge to their clients. The reality is that most people who are making decisions on UPSs, especially in the range of kva, don t have a full comprehension and tend to get misled and start looking at the kva number when that s not the most important number to look at. They should be looking at kilowatts. In the past when you had a load of 400kVA, a 450kVA UPS was sufficient, says Gross. That s not sufficient anymore. You need to look at the kw rating of the machine compared to the load. If an engineer does not have a lot of experience with UPS systems or does not have a reference point based on the company s UPS needs in its existing facilities, Stapleton advises the consultant to pick a unity system. You don t know what the power supplies are in a lot of systems, Kesterson adds. The unity power solution eliminates a lot of potential problems where you can t find out what the loads are. It greatly simplifies things for a consulting engineer or facilities engineer who doesn t have a tremendous amount of experience with computer loading issues. No question about that. Simplifying the Issue for End Users and Engineers Select Unity Power Factor UPS Systems You have an awful lot of people coming into the market today who don t have vast experience with UPSs, but they re buying UPSs, says Kesterson. They are not familiar with the requirements. A unity power factor output eliminates all those concerns. Unity power factor eliminates the need for a complete understanding of what you re dealing with. Operating at unity power factor is so important, says Gross. If users and engineers don t understand that, they are going to run into problems. APC should be commended for addressing these issues. When all other factors are equal, unity power factor gives APC an edge over the competition. There is no question that it represents a major advantage for APC. Stapleton is unequivocal: The ultimate solution is just select a UPS with unity power factor. DATA CENTER SOLUTIONS For More Information: (866) [email protected] 7
Understanding Delta Conversion Online "Output Power Factor Ratings" - Part 7
Application Note #45 Understanding Delta Conversion Online "Output Power Factor Ratings" - Part 7 Introduction This application note is the seventh in a series on delta conversion theory of operation.
Understanding Power Factor, Crest Factor, and Surge Factor. White Paper #17
Understanding Power Factor, Crest Factor, and Surge Factor White Paper #17 Executive Summary This paper explains the technical terms of Power Factor, Crest Factor, and Surge Factor. The use of these terms
The Different Types of UPS Systems
The Different Types of UPS Systems By Neil Rasmussen White Paper #1 Revision 5 Executive Summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics.
Optimizing Power Distribution for High-Density Computing
Optimizing Power Distribution for High-Density Computing Choosing the right power distribution units for today and preparing for the future By Michael Camesano Product Manager Eaton Corporation Executive
Ambient Temperature In Range Probe X
List of Events This section lists all events that are written to the Event Log. Some of these events can be configured through the Configuring Events to Take Actions page, and these are listed in the first
Calculating Total Power Requirements for Data Centers
Calculating Total Power Requirements for Data Centers By Richard Sawyer White Paper #3 Executive Summary Part of data center planning and design is to align the power and cooling requirements of the IT
Electrical Systems. <Presenter>
Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
UPS Applications and VRLA Battery Sizing
TECHNICAL BULLETIN 41-7334 UPS Applications and VRLA Battery Sizing 41-7334/0213/CD www.cdtechno.com The uninterruptable power system (UPS) is used to protect critical equipment and processes from the
A Comparison of AC and DC Power Distribution in the Data Center Transcript
A Comparison of AC and DC Power Distribution in the Data Center Transcript Slide 1 Welcome to the Data Center University course on the A Comparison of AC and DC Power Distribution in the Data Center. Slide
The Different Types of UPS Systems
Systems White Paper 1 Revision 6 by Neil Rasmussen Contents Click on a section to jump to it > Executive summary There is much confusion in the marketplace about the different types of UPS systems and
Increasing Data Center Efficiency by Using Improved High Density Power Distribution
Increasing Data Center Efficiency by Using Improved High Density Power Distribution By Neil Rasmussen White Paper #128 Executive Summary A new approach to power distribution for high density server installations
The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity
The Quest for Energy Efficiency A White Paper from the experts in Business-Critical Continuity Abstract One of the most widely discussed issues throughout the world today is the rapidly increasing price
Selecting a UPS Topology for your Data Center. by Dr. Daniel Becker, Ph.D., Methode Active Energy Solutions
Selecting a UPS Topology for your Data Center by Dr. Daniel Becker, Ph.D., Methode Active Energy Solutions Uninterruptible Power Supplies (UPS) are both reaching into new markets and expanding in new ways
The Different Types of UPS Systems
White Paper 1 Revision 7 by Neil Rasmussen > Executive summary There is much confusion in the marketplace about the different types of UPS systems and their characteristics. Each of these UPS types is
Understanding Emergency Power Off (EPO)
Understanding Emergency Power Off (EPO) White Paper #22 Executive Summary Emergency Power Off (EPO) is the capability to power down a piece of electronic equipment or an entire installation from a single
Opportunity of Energy Saving in electrical path is lesser as compared to other areas
Data Centre Power Map ` Energy Optimization Techniques Data Center Power Chain Venkat Rao B Country Manager Power Products Data Center Power Draws Cooling About 35 40 % Sources of Energy Waste Fans / Blowers
AC vs DC for Data Centers and Network Rooms
AC vs DC for Data Centers and Network Rooms White Paper #63 Revision 1 Executive Summary The use of DC power distribution as an alternative to AC in data centers and network rooms is uncommon. The considerations
Power Factor Correction for Power Systems First Semester Report Spring Semester 2007
Power Factor Correction for Power Systems First Semester Report Spring Semester 2007 by Pamela Ackerman Prepared to partially fulfill the requirements for EE401 Department of Electrical and Computer Engineering
Dynamic Power Variations in Data Centers and Network Rooms
Dynamic Power Variations in Data Centers and Network Rooms By Jim Spitaels White Paper #43 Revision 2 Executive Summary The power requirement required by data centers and network rooms varies on a minute
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA -3000VA Intelligent, Reliable UPS Protection Liebert
> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents.
The Role of Isolation Transformers in Data Center UPS Systems White Paper 98 Revision 0 by Neil Rasmussen > Executive summary Most modern UPS systems do not include the internal s that were present in
Mitigating data center harmonics
Mitigating data center harmonics Patricia Matwijec Product Manager Eaton Ed Spears Product Marketing Manager Eaton Executive summary Line harmonics can have costly and disruptive effects on electrical
GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta
GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for
Energy Cost Reduction through Load Balancing & Load Shedding
white paper Energy Cost Reduction through Load Balancing & Load Shedding SCR controllers firing in phase angle degrade the power factor while increasing harmonics and electrical noise. A poor power factor
Power Factor The Basics
Power Factor The Basics OK. I ve heard a lot about this power factor stuff. What exactly is it? We hope to give you an easy explanation of what power factor is, and to answer the following most asked questions:
Dynamic Power Variations in Data Centers and Network Rooms
Dynamic Power Variations in Data Centers and Network Rooms White Paper 43 Revision 3 by James Spitaels > Executive summary The power requirement required by data centers and network rooms varies on a minute
Five Steps to Getting Started with Contract Management
Five Steps to Getting Started with Contract Management White Paper (281) 334-6970 [email protected] www.prodagio.com Contracts play a major role in your daily interactions with clients and suppliers alike.
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
Using the Phoenix MultiPlus
Using the Phoenix MultiPlus to reduce operating cost of a generator www.victronenergy.com 1. The traditional AC generator system Per Watt ac-power, an inverter is generally more expensive than a generator.
A VANTAGE DATA CENTER INFOPAPER. The Open Compute Project + Your Data Center: What you need to know
A VANTAGE DATA CENTER INFOPAPER The Open Compute Project + Your Data Center: What you need to know A VANTAGE DATA CENTER INFOPAPER The Open Compute Project + Your Data Center: What you need to know If
Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment
Efficiency and Other Benefits of 208 Volt Over 120 Volt Input for IT Equipment By Neil Rasmussen White Paper #27 Revision 2 Executive Summary Decisions made regarding the distribution of 208V or 120V power
Power Distribution Considerations for Data Center Racks
Power Distribution Considerations for Data Center Racks Power Distribution Considerations for Data Center Racks Table of Contents 3 Overview 4 At what voltage do you run all the IT equipment? 4 What electrical
Availability and Disaster Recovery: Basic Principles
Availability and Disaster Recovery: Basic Principles by Chuck Petch, WVS Senior Technical Writer At first glance availability and recovery may seem like opposites. Availability involves designing computer
VOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
Power Quality. Uninterruptible Power Supply
Quality Uninterruptible Supply In the electrical system environment, power disturbances will occur. These can be caused by faults on the distribution system, the operation of nearby equipment, lightning
Back-UPS 650 VA 120 V with AVR (BX650CI-LM)
Back-UPS 650 VA 120 V with AVR (BX650CI-LM) Overview Do not install the unit in direct sunlight, in areas of excessive heat or humidity, or in contact with fluids ON/OFF button Battery connector Circuit
Understanding Delta Conversion Online "Power Regulation" - Part 2
Application Note #40 Understanding Delta Conversion Online "Power Regulation" - Part 2 Introduction This application note is the second in a series on delta conversion theory of operation. For complete
SP 4K/5K Efecto & SP 5K Brilliant Parallel Installation Guide 1. Introduction
SP 4K/5K Efecto & SP 5K Brilliant Parallel Installation Guide 1. Introduction This inverter can be used in parallel with two different operation modes. 1. Parallel operation in single phase with up to
4KVA/5KVA Parallel Installation Guide
4KVA/5KVA Parallel Installation Guide 1. Introduction This inverter can be used in parallel with two different operation modes. 1. Parallel operation in single phase with up to 4 units. The supported maximum
Energy Efficient High-tech Buildings
Energy Efficient High-tech Buildings Can anything be done to improve Data Center and Cleanroom energy efficiency? Bill Tschudi Lawrence Berkeley National Laboratory [email protected] Acknowledgements California
Impact of Leading Power Factor on Data Center Generator Systems
Impact of Leading Power Factor on Data Center Generator Systems White Paper 200 Revision 0 by Neil Rasmussen Executive summary IT devices may exhibit electrical input current with a characteristic called
Five Nines and Infrared (IR) Testing at Data Centers
Five Nines and Infrared (IR) Testing at Data Centers By Gregory R. Stockton 99.999% uptime five nines. That is what IT (information technology) customers are looking for. Uptime or availability at data
Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications
W H I T E P A P E R Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications Executive Summary One of the fundamental decisions in the design of data centers, server rooms
RESILIENT PRODUCT LIFECYCLE MANAGEMENT STRATEGIES & SOLUTIONS FOR FUTURE-PROOFING PLM
RESILIENT PRODUCT LIFECYCLE MANAGEMENT STRATEGIES & SOLUTIONS FOR FUTURE-PROOFING PLM PLM systems hit the wall when they can t adapt to evolving business requirements and / or when they hold your business
Increasing safety, reliability and efficiency for today s data centers
Increasing safety, reliability and efficiency for today s data centers Products and expertise for data center success Drawing upon vast experience in complex industries where uptime is critical, ABB provides
Is an energy-wasting data center draining your bottom line?
Abstract Is an energy-wasting data center draining your bottom line? New technology options and power distribution strategies can dramatically reduce the cost and carbon footprint of your data center.
SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications
SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications Model #: SU3000RTXL3U 3000VA online 3U rack / tower UPS Enhanced serial communications
Sample only. STOP for Each Other. Unit 1: Introduction SAFETY TRAINING OBSERVATION PROGRAM. Name:
Unit 1: Introduction Name: SAFETY STOP for Each Other TRAINING OBSERVATION PROGRAM Note to Readers The authors, reviewers, editors and DuPont have made extensive efforts to ensure that the technology,
Energy, Work, and Power
Energy, Work, and Power This worksheet and all related files are licensed under the Creative Commons Attribution License, version 1.0. To view a copy of this license, visit http://creativecommons.org/licenses/by/1.0/,
Harmonics in your electrical system
Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses
Guideline for stresstest Page 1 of 6. Stress test
Guideline for stresstest Page 1 of 6 Stress test Objective: Show unacceptable problems with high parallel load. Crash, wrong processing, slow processing. Test Procedure: Run test cases with maximum number
Charger Output AC Ripple Voltage and the affect on VRLA batteries
TECHNICAL BULLETIN 41-2131 Charger Output AC Ripple Voltage and the affect on VRLA batteries Please Note: The information in this technical bulletin was developed for C&D Dynasty 12 Volt VRLA products.
TECHNICAL SPECIFICATIONS FOR 1.5 KVA ONLINE UPS
Capacity Technology Inverter Technology Noise Level Operating Temperature Humidity Harmonic Distortion Total DC bus voltage Battery recharge time (After Complete discharge) to 100% charge Crest Factor
HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS
White Paper: MIRUS-TP003-A January 15, 2014 HOW HARMONICS HAVE CONTRIBUTED TO MANY POWER FACTOR MISCONCEPTIONS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc.
Galleon 6-10K Online UPS. Voltronic Power Technology Corporation
Galleon 6-10K Online UPS Voltronic Power Technology Corporation Features Galleon online UPS series delivers optimal power quality, provides superior power management, resolves utility power protection
DC Power Solutions Overview. DC Power Solutions for EVERY Network Application.
DC Power Solutions Overview DC Power Solutions for EVERY Network Application. DC Power Solutions for Every Network Application Eaton recognizes the challenges that are unique to different customers applications.
Achieving the impossible
1 Achieving the impossible Taking control of shore power with the Phoenix Multi/MultiPlus from Victron Energy * Sometimes the features of a new product are so unique that the benefits are difficult to
Welcome to the Tripp Lite UPS Systems Basics training module, part of Tripp Lite's "Products Expert" training course. 2008 Tripp Lite.
Welcome to the Tripp Lite UPS Systems Basics training module, part of Tripp Lite's "Products Expert" training course. 2008 Tripp Lite. All rights reserved. The policy of Tripp Lite is one of continuous
Electrical Efficiency Modeling for Data Centers
Electrical Efficiency Modeling for Data Centers By Neil Rasmussen White Paper #113 Revision 1 Executive Summary Conventional models for estimating electrical efficiency of data centers are grossly inaccurate
Multi DIALOG MDM/MDT. MDM 10-20kVA single/single-phase and three/single-phase MDT 10-80kVA three/three-phase NETWORK RANGE
Local Area Networks (LAN) Servers Data centers Internet centers (ISP/ASP/POP) Industrial PLCs EPOS (Electronic Point of Sale) Systems Emergency devices (lights/alarms) Electro-medical devices Telecommunication
Power factor correction. An introduction to technology and techniques
Power factor correction An introduction to technology and techniques 2 Contents Understanding power factor 03 Power factor correction 05 Implementing power factor correction techniques 06 Glossary 07 Further
415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A1 October 1, 2010 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2005 Mirus International
REGULINE 600VA / 1000VA REGULATOR USER MANUAL
REGULINE 600VA / 1000VA REGULATOR USER MANUAL TUNÇMATİK REGULINE SERIES AUTOMATIC VOLTAGE REGULATOR Models: REGULINE 600VA / REGULINE 1000VA Principle of Operation Automatic Voltage Regulators regulate
POWER SUPPLY MODEL XP-15. Instruction Manual ELENCO
POWER SUPPLY MODEL XP-15 Instruction Manual ELENCO Copyright 2013 by Elenco Electronics, Inc. REV-A 753020 All rights reserved. No part of this book shall be reproduced by any means; electronic, photocopying,
FREE REPORT: Answers To The Top 5 Questions Business Owners Have About Cloud Computing
FREE REPORT: Answers To The Top 5 Questions Business Owners Have About Cloud Computing Discover What Most IT Consultants Don t Know Or Won t Tell You About Moving Your Company s Network To The Cloud By
Fundamentals of Power
Fundamentals of Power Fundamentals of Power 2008 American Power Conversion Corporation. All rights reserved. All trademarks provided are the property of their respective owners. Learning Objectives At
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
Technical Comparison of On-line vs. Line-interactive UPS designs
Technical Comparison of On-line vs. Line-interactive UPS designs By Jeffrey Samstad Michael Hoff White Paper #79 Executive Summary UPS systems below 5000VA are available in two basic designs: line-interactive
2012 San Francisco Colloquium
2012 San Francisco Colloquium http : //www.cigre.org HVDC and Power Electronic Systems for Overhead Line and Insulated Cable Applications B4-8 Trans Bay Cable A Breakthrough of VSC Multilevel Converters
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
DISTRIBUTED REDUNDANCY:
DISTRIBUTED REDUNDANCY: MAXIMUM AVAILABILITY AT MINIMAL COST A White Paper by: Liebert Corporation As the need for greater system availability intensifies across virtually every industry from global banking
Solar Power HourSM. Solar educa on for your community.
Solar Power HourSM Solar educa on for your community. 1 Contents About. 1 Commonly Asked Questions.. 2-3 The Solar Site Assessment.. 3-4 Selecting a Solar Installer. 5-7 Certified Installers by State.
Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE
Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements
Power and Cooling Capacity Management for Data Centers
Power and Cooling Capacity for Data Centers By Neil Rasmussen White Paper #150 Executive Summary High density IT equipment stresses the power density capability of modern data centers. Installation and
Coordination of Telecommunications Surge Protective Devices in Countries with Unstable AC Power
App Notes ~ Outdoor Power System Design and Cost Considerations 1 Authors Peter Nystrom President TSi Power Corp. Coordination of Telecommunications Surge Protective Devices in Countries with Unstable
415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International
PV (photovoltaic) Basics There are generally two types of PV systems. The first and easiest (though the least flexible) is a grid tie system where
PV (photovoltaic) Basics There are generally two types of PV systems. The first and easiest (though the least flexible) is a grid tie system where the power generated by the solar panel (panels) runs an
GE Consumer & Industrial Power Protection. Digital Energy LP Series UPS. Uninterruptible Power Supply 3-30 kva. GE imagination at work
GE Consumer & Industrial Power Protection Digital Energy LP Series UPS Uninterruptible Power Supply 3-30 kva GE imagination at work For more than a century, GE has led the way with innovative technologies
BASIC NEC CODE RULES AND DESIGN PRACTICE
BASIC NEC CODE RULES AND DESIGN PRACTICE Wire Ampacity and Size Circuit Breaker Size 1. Maximum loading for any branch circuit is 80% of rating of circuit for ampacity of wire for any load. NEC 220-2,
Galaxy VM. Three-phase power protection. schneider-electric.com
Galaxy VM Three-phase power protection schneider-electric.com 2 schneider-electric.com schneider-electric.com 3 Galaxy VM trusted partner for your business continuity Features and benefits Highly efficient,
Calculating Total Cooling Requirements for Data Centers
Calculating Total Cooling Requirements for Data Centers By Neil Rasmussen White Paper #25 Revision 2 Executive Summary This document describes how to estimate heat output from Information Technology equipment
Considering the effects of UPS operation with leading power factor loads
Considering the effects of UPS operation with leading power factor loads Over the past five years, a new generation of data processing and communications equipment has become prevalent in modern data centers
Electrician s Math and Basic Electrical Formulas
UNIT 1 Electrician s Math and Basic Electrical Formulas INTRODUCTION TO UNIT 1 ELECTRICIAN S MATH AND BASIC ELECTRICAL FORMULAS In order to construct a building that will last into the future, a strong
Distributed versus centralized power backup strategies
Distributed versus centralized power backup strategies Choosing the right UPS deployment architecture for your data center By Ed Spears Product Manager, Eaton Power Quality Solutions Operation Eaton Corporation
VoIP 101: An introduction to the basics of Voice over Internet Protocol. How to guide
VoIP 101: An introduction to the basics of Voice over Internet Protocol How to guide Introduction You may have heard of VoIP that it s the future of telephone service, and that you can save a lot of money
Wireless Networks and Power Quality
Will installing wireless networking change my back-up power requirements? What data do I need to know in order to determine my wireless network back-up power requirements? What other issues should I consider