SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE WELDERS
|
|
|
- Rosa Henderson
- 9 years ago
- Views:
Transcription
1 SIZING THE PRIMARY POWER SYSTEM FOR RESISTANCE S By Jack Farrow, May, 2004 WELDING TECHNOLOGY CORPORATION ABSTRACT Information on how to select the correct size of substation transformer and 480V bus to power one to one thousand resistance welding machines is presented. Powerline voltage drop, light flicker, power factor correction and harmonic currents are discussed. Strategies to allow more welders to operate on a given power system are explained. Techniques to improve the efficiency of the power system and reliability of the welding process are identified. Consideration is given to selecting the correct sizes and types of fuses. Useful reference material will be available to attendees. INTRODUCTION Because resistance welders draw large currents on an intermittent basis, they present special problems to the primary power system in a manufacturing plant. This paper answers the following questions related to these problems. 1. What size does the three-phase power system need to be to support the number of welders I have? 2. How is a welder power bus different from other power buses? 3. What can be done to improve power system efficiency and capacity utilization? 4. What is the proper size and type of fuse to use? For the purposes of discussion in this paper, spotwelding of steel sheet of thickness between 0.5 and 3 mm. is assumed. The power system supplying the welders is 480VAC, 60 HZ, three-phase. In general, the discussion is centered around standards and practices most commonly used in the North American automobile industry. I. What size does the three-phase power system need to be to support the number of welders I have? A typical resistance spotwelder draws between 100,000 and 200,000 watts when welding! To avoid problems of cold welds due to insufficient power, the 480 VAC power system must be capable of supplying this power with less than 10% voltage drop. Now, 10% voltage drop doesn t sound like much, but consider this: The amount of power available in a circuit is proportional to the voltage squared divided by the resistance. If the voltage drops by 10% (to 0.9 times the original value) the available power drops by 19% (0.9 times 0.9 equals 0.81). A 19% drop in energy to the weld has some serious effects on weld quality! Most modern resistance welding controls have systems to compensate for powerline voltage drop, but when the powerline voltage drops by more than 10% and the available energy drops by more than 19%, there may not be enough energy left to make the weld, even after the welding control has done all the compensation it can do. For this reason, powerline voltage drops should be limited to 10% or less. 1
2 In order to calculate powerline voltage drop, the current draw of the welders and the impedance of the power system must be known. In the absence of actual measurements of powerline draw and voltage drop during weld, the following assumptions can be used: 1. Where there are several single-phase AC spotwelders connected to the same three-phase power bus, the connection of the welders to the power bus is distributed as equally as possible between the three phases so as to make the average power draw equal on all three phases. 2. For a hanging gun welder (single-phase transformer suspended from the ceiling with a kickless cable going to the welding gun), the equivalent three-phase current draw during welding is 400 amperes. 3. For a single-phase AC fixture welding gun or a robotic hip-mounted transformer welder, the equivalent three-phase current draw during welding is 270 amperes. 4. For a single-phase AC integral transformer welding gun, the equivalent threephase AC current draw during welding is 170 amperes. 5. For a three-phase MFDC welding gun, the equivalent three-phase current draw during weld is 150 amperes. 6. The duty cycle of the welders is 5%. 7. The impedance of the three-phase power system is 7%. That is, When the power system is loaded to its full continuous duty current rating, the voltage will drop by 7%. In other words, if you draw 400 amperes on a 480 V 400 amp bus with a 7% impedance factor, the voltage will drop from 480V (unloaded) to 446V (Fully loaded). The above assumptions are valid for spotwelders welding sheet steel (galvanized or bare) over the thickness range of 0.5 to 3 mm. For small numbers of welders (4 or fewer) actuated manually, there is a very high probability that all will be welding simultaneously at least several times a day. Where 4 or fewer welders are involved, the power system should be sized so the voltage doesn t drop by more than 10% when all welders weld simultaneously. If the power system cannot be sized to handle all the welders welding simultaneously, some sort of interlock can be used to assure that only one welder at a time is allowed to weld. A simple interlock circuit, consisting of only two relays per welder, is shown in Figure 1. For small shop and/or low production requirements, this simple relay circuit works well up to 5 welders. With the use of this interlock circuit, the power system only needs to be sized to handle the current of one welder with no more than 10% voltage drop. So long as the duty cycle of the welders is 5% or less, this interlock circuit slows the production rate by much less than 1%. 2
3 FIRST WELDING CONTROL MIDDLE WELDING CONTROL(S) LAST WELDING CONTROL RY2C RY2C RY2 TO NEXT WELDING CONTROL FROM PREVIOUS WELDING CONTROL RY2 TO NEXT WELDING CONTROL FROM PREVIOUS WELDING CONTROL RY2 RY1A RY1A RY1A SEPARATE 120/24VAC SOURCE RY2A RY2A TO STAGE 2 OR PRESSURE SWITCH INPUT RY2B TO STAGE 2 OR PRESSURE SWITCH INPUT RY2B TO STAGE 2 OR PRESSURE SWITCH INPUT RY2B RY1 RY1 RY1 TO WELD VALVE OUTPUT TO WELD VALVE OUTPUT TO WELD VALVE OUTPUT FIGURE 1: Simple interlock circuit for 5 or fewer welders For 5 or more welders, running at duty cycles of 5%, it becomes very unlikely that all of the welders will weld at the same time, assuming random initiation times by human operators. For 5 or more welders, statistical techniques may be used to estimate the number of welders welding at any instant of time and size the power bus accordingly. The spreadsheet associated with this paper implements a statistical method to estimate, give a certain number of welders, how often the powerline voltage will dip by more than 10% and how many welds per 1000 will be affected by the voltage drops of greater than 10%. The data values are entered in column E. These values can be changed as desired for what if calculations. For example, with the values already entered, if the average duty cycle is increased from 5% to 10% (a very high value for spotwelding), it will show that the number of welds likely to have one or more cycles of low line voltage will increase from 2 per 1000 (acceptable for most applications) to 247 per 1000 (good only for making scrap). The what if calculations can also be used to make estimates of the lowest line voltage that will occur with a given number of welders. The value for the minimum allowable 3
4 line voltage (Cell E9) can be decreased until the number of welds per million with one or more cycles of low line voltage reaches 1 per million. This allows the worst case voltage drop to be found. General case estimates for the current draw for different types of resistance spotwelding machines are in cells G2 through G5. These current draw estimates are for the welding of steel (bare or coated) only. If you know the exact value of current draw for the welding machines in your plant, then the known values should be entered here. In general, however, these estimated values should suffice for welding steel in all but the most unusual cases. The current draws for welding aluminum are about 3 times the assumed values for steel shown in cells G2 through G5. For weld time, use 5 cycles. For duty cycle, use 3%. The estimates of this spreadsheet are not accurate for a mixture of some machines welding steel and some welding aluminum. If your situation involves a mix of this sort, another analysis method should be used. Please notice that the calculations are based on the number of welding machines (welding guns), not necessarily the number of welding controls or the number of welding transformers. For example if multiple welding transformers are connected to one welding control or multiple welding guns are connected to a single welding transformer, the number entered in cell E5 should reflect the total number of welding guns or pairs of welding electrodes. The estimates in this spreadsheet are slightly biased toward worst case. If you size a welding power bus so that the number of welds with low voltage is about 1 or 2 per thousand, then it is very unlikely you will get cold welds due to low powerline voltage. The statistical assumptions and approximations in this spreadsheet are accurate with 5 or more welders. With more than 250 welders and/or if the welders have a very high duty cycle, you may find that the Average Bus current (Cell D29) is larger than the 3- phase power system continuous duty rating (Cell E11). If this happens, use the higher value in cell D29 to size the power system. Once the required supply current is calculated by any of the previous methods, the necessary substation transformer KVA is calculated with the following equation: SUBKVA = CURR*LV* where: SUBKVA is the required substation transformer KVA CURR is the required supply current LV is the powerline nominal voltage (480VAC, 390VAC, etc.) For example, with a required current of 600 amperes and a 480V bus, the necessary size substation transformer would be KVA. 4
5 II. How is a welder power bus different from other power buses? Resistance welders are probably the worst loads that can be placed on a three-phase power bus. They draw large amounts of current for short periods on a very intermittent basis. The waveform of the current they draw is almost never a smooth sine wave and it is almost never balanced between the three phases. Harmonic currents, powerline waveform distortion and rapidly changing powerline voltage are the result. For the above reasons and more, it is not a good idea to put resistance welders on the same power bus as other equipment. A power bus separate from any other in the plant, fed by a separate substation transformer is recommended for powering resistance welding machines. If a large proportion of the resistance welders in your plant are single-phase, a DELTA connected substation made with three single-phase transformers, rather than a single three-phase transformer is recommended. There are several reasons for this: 1. In a DELTA connected system, the effective impedance presented to a singlephase load is lower. 2. In a DELTA power system, which has no neutral conductor, the imbalance and harmonic currents are forced to flow through the bus, which is sized to handle the current, rather than the neutral conductor which may not be big enough to handle the current. 3. In a DELTA power bus, the three separate single-phase substation transformers rather than a single three-phase transformer reduce the coupling between phases which results in an unloaded phase increasing in voltage when another is loaded down. This reduces voltage fluctuations. This becomes particularly important in a resistance welding power bus where occasional voltage drops reach 15%. Single-phase AC welders usually have a power factor below 70%; power factors of 50% or less are not unusual. Part of this poor power factor is due to inductance in the secondary loop of the welding machines and part is due to the current waveform distortion caused by the phase control action of the welding control. Three-phase MFDC welders have a power factor in the 85-95% range. All of the poor power factor is caused by current waveform distortion and none is caused by inductance in the secondary loop of the welding machine. The usual methods of adding power factor correction capacitors to the bus simply don t work for resistance welders for several reasons: 1. The current draw of resistance welders is extremely intermittent and changes from second to second. Any constant value of power factor correction capacitor will be wrong for the load current almost all the time. 2. Due to the phase control action of the welding controls, there are a lot of harmonic currents generated, primarily 3 rd, 5 th and 7 th order. Due to the intermittent action of resistance welding, the inductance present on the power bus is constantly changing, as some welders start welding and others stop. For any reasonable value of power factor correction capacitors, there will be times when the capacitors and the inductance on the power bus form a tuned circuit, resonant at the 3 rd, 5 th, or 7 th harmonic of the powerline. The resonant action will cause severe waveform distortion on the powerline voltage and 5
6 eventually destroy the power factor correction capacitors by exceeding their current rating. 3. A large part of the poor power factor on a resistance welder bus is due to the chopping of the AC waveform which is done as part of phase control or by flat-topping of the powerline waveform caused by the rectifier input circuits of MFDC welders. Power factor correction capacitors cannot correct poor power factor due nonlinear (switched) current draw. For the above reasons, DO NOT put power factor correction capacitors on a welder power bus! DO NOT connect anything with power factor capacitors built-in (such as equipment containing motors or lighting circuits) to a welding bus. Except for one special case noted below, power factor correction capacitors on a welder bus are worse than useless. If power factor correction on a welder bus is necessary it can be done with harmonic filters (tuned to the 3 rd and 5 th harmonics) and/or active waveform correction devices. However these devices are far more expensive than simple power factor correction capacitors and are often not cost-effective. For smaller installations (50 welders or less) it is usually cheaper to pay the power factor penalty to the utility company. Only in larger installations (100 welders or more) are these devices cost-effective. There will be cases where installing a separate power bus for the resistance welding equipment simply cannot be done. This often occurs in small manufacturing plants where there are only two or three resistance welders. In this situation, there are several things that can be done to at least mitigate the negative consequences. 1. Use MFDC welding whenever possible. MFDC is much kinder to the threephase power bus and draws current from all three phases approximately equally. 2. Size the power bus so that even if all the welders weld at the same time, the voltage drop is only 5%. This will reduce light flicker and other undesirable effects on the other devices powered from the same power bus as the resistance welders. 3. Install some sort of system (such as the simple relay circuit mentioned previously) to make sure only one welder can weld at a time. 4. Install one set of very small power factor correction capacitors (1 KVAR maximum) on the power bus as close as possible to the welding machine(s) to help absorb any voltage spikes generated by the switching action of the resistance welders. 5. Put any computers or other electrically sensitive devices (such as telephone equipment) on a UPS (Uninterruptible Power Supply). 6. Get used to light flicker; it WILL happen! 6
7 III What can be done to improve power system efficiency and capacity utilization? Although resistance welders are possibly the worst load that can be placed on a threephase powerline, there are some things that can be done to make the situation better. When connecting single-phase welding machines to a three-phase powerline, DO NOT connect all the machines to the same phase of the powerline! Instead, distribute the connections approximately equally between all three phases. For example, if there are 10 welders to be installed, connect three to phase 1, three to phase 2 and four to phase 3. This distributes the average current draw more-or-less equally across all three phases. If multiple single-phase welders are welding simultaneously, try to run them in groups of three with each welder in the group of three on a different phase. This will present a more balanced load to the three-phase powerline. In general, try to run the welding transformers on the lowest tap that still gives a satisfactory weld without causing the weld control to give current regulation or voltage regulation faults. This reduces the current draw of the welder and improves its power factor, which results in lower electricity bills. A load scheduling system that limits the maximum number of welders that can weld at any instant of time can make a big difference in the maximum current draw and can allow more welders to operate on the same size power bus. The Excel spreadsheet associated with this paper allows a load scheduling system to be simulated and its effect on the production rate estimated. After entering the proper values for your system in cells E2 through E13, the maximum number of welders allowed to weld simultaneously by a load scheduling system is entered in cell E32. When this number is entered, the numbers reflecting the required bus size and the effect on production rate are calculated and displayed in cells C33 and C35. The mathematical approximation used to obtain these values is most accurate in the range of 5-60 seconds per hour of production time lost. Below 5 seconds, the lost production time tends to be overstated (bigger number than it really is) and above 60 seconds per hour, the lost production time tends to be understated (smaller than it really is). 7
8 IV. What is the proper size and type of fuse to use? For an individual welder, the general rule is that the fuse size in the bus disconnect and the wiring from the bus disconnect to the resistance welding control should match the ampere rating of the circuit breaker in the welding control. For example, if there is a 250 ampere circuit breaker in the weld control, then a 250 ampere fuse should be used in the bus disconnect and 250 MCM wire should be used between the bus disconnect and the weld control. The fuse should always be a weld limiter type of fuse which has a very slow-blow characteristic. Use of this rule assures compliance with the National Electrical Code in the USA. If the KVA of the welding transformer(s) is known for a particular installation, then all of the 480V wiring, from the bus disconnect to the welding control and from the welding control to the welding transformer can be sized according to the transformer KVA. The basic rule for single-phase welding transformers is that the minimum cable size is 1.7 amps ampacity per transformer KVA. For cable ampacity, the NFPA standard values should be used. For example, a 100KVA transformer requires a wire with an ampacity of 170 amperes, or AWG 2/0 wire. At the bus disconnect, a fuse appropriate to the wire size (200 amperes) is required. If the transformer KVA is such that the calculated ampacity is more than the rating of the circuit breaker in the resistance welding control, then the wire size and the bus disconnect fuses should be selected according to the circuit breaker rating. Two or three single-phase AC resistance welding controls can be powered from a single three-phase bus disconnect. When this is done, the following recommendations apply: 1. All three welding controls should be of the same type and have the same size circuit breakers. For example, it is not advisable to connect a multi-contactor cascade firing control with 6 welding transformers onto the same disconnect as two other single-contactor controls with one welding transformer each. 2. Each of the welding controls is connected to a different phase. 3. The transformers connected to the welding controls should all be the same total KVA. When two or three welding controls are powered from one three-phase bus disconnect, the disconnect and the fuses in it should be sized 1.5 times bigger than what would be required for a single control. For example, it is acceptable to connect three resistance welding controls with 250 ampere circuit breakers to a single 400 amp three-phase disconnect. For three-phase MFDC resistance welding controls, the bus disconnect fuses and the wiring between the bus disconnect and control should always be sized according to the circuit breaker size in the welding control. The wire used to connect the welding control to the welding transformer should have an ampacity equal to 1/3 rd of the rated current of the inverter at 10% duty cycle. For example, a 600 amp MFDC welding control equipped with a 150 amp circuit breaker should be installed with 150 amp bus fuses, AWG 0 wire between the bus disconnect and the circuit breaker and with AWG 3/0 wire (200 amps) between the welding control and the welding transformer. The bus disconnect fuses should be weld limiter (slow blow) type fuses. 8
9 The main power bus fuses feeding the welder bus should be sized according to the rated capacity of the power bus or the substation transformers, whichever is less. If the layout of the plant permits, it is advantageous to install the welder bus in a loop configuration with the beginning and end of the loop near the substation transformers. Power is fed from the substation transformers into both ends of the power bus. This both lowers the effective bus impedance by providing dual current paths to any load and it doubles the capacity of the bus. For example, if a 1200 amp welder bus is required, the requirement can be met with a looped 600 amp bus. A looped bus is particularly effective where there are a large number of welders, distributed more-or-less equally along the bus. Depending on the installation, this may save considerable amounts of money. Other bus configurations, such as the ladder configuration shown in Figure 2 can also be used. In Figure 2, the need for a 1200 amp welder bus is met with interconnected 400 amp buses. 9
10 1200 AMP SUBSTATION TRANSFORMERS 400 AMP FUSES 400 AMP BUSES = BUSES CONNECTED TOGETHER AT THESE POINTS FIGURE 2: Bus H configuration to obtain higher currents In order to meet local electrical code requirements, it may be necessary to add auxiliary fuses at the points where the power buses are interconnected. It is always good practice to have a proposed bus design reviewed by the local electrical code enforcement agency. 10
11 SUMMARY AND CONCLUSIONS The guidelines presented in this paper are directed toward resistance spotwelding equipment in an environment like an automobile body assembly line. The guidelines in this paper are not designed for resistance seam welders, very large welders (such as used to weld automobile rims or aircraft landing struts), three-phase DC welders, or to any welders with a 500 KVA or larger welding power supply. The guidelines of this paper assume that either steel or aluminum, but not a mix of the two, is being welded. For all but the most unusual installations of resistance welding equipment, the information presented in this paper should be sufficient to properly size the three-phase power bus so the welders can operate reliably. In addition to the information given in this paper, a number of articles and other material about powerlines for resistance welders are included in the appendix. This material was the basis of this paper. Because of size (over 100 pages with the appendix) this paper was distributed in electronic form (on a CDROM). If you are reading a paper copy of this paper, the electronic form, with all the appendices can be downloaded from the Welding Technology Corp. web site ( or can be obtained by contacting Jack Farrow at or [email protected]. 11
Product Data Bulletin
Product Data Bulletin Power System Harmonics Causes and Effects of Variable Frequency Drives Relative to the IEEE 519-1992 Standard Raleigh, NC, U.S.A. INTRODUCTION This document describes power system
Typical Data Requirements Data Required for Power System Evaluation
Summary 66 Carey Road Queensbury, NY 12804 Ph: (518) 792-4776 Fax: (518) 792-5767 www.nepsi.com [email protected] Harmonic Filter & Power Capacitor Bank Application Studies This document describes NEPSI
Three phase circuits
Three phase circuits THREE PHASE CIRCUITS THREE-PHASE ADVANTAGES 1. The horsepower rating of three-phase motors and the kva rating of three-phase transformers are 150% greater than single-phase motors
Line Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
VOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
POWER SYSTEM HARMONICS. A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS
A Reference Guide to Causes, Effects and Corrective Measures AN ALLEN-BRADLEY SERIES OF ISSUES AND ANSWERS By: Robert G. Ellis, P. Eng., Rockwell Automation Medium Voltage Business CONTENTS INTRODUCTION...
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
Introduction. Harmonics and IEEE 519 Page 1 of 19
Introduction In an ideal power system, the voltage supplied to customer equipment, and the resulting load current are perfect sine waves. In practice, however, conditions are never ideal, so these waveforms
EET272 Worksheet Week 9
EET272 Worksheet Week 9 answer questions 1-5 in preparation for discussion for the quiz on Monday. Finish the rest of the questions for discussion in class on Wednesday. Question 1 Questions AC s are becoming
FREQUENCY CONTROLLED AC MOTOR DRIVE
FREQUENCY CONTROLLED AC MOTOR DRIVE 1.0 Features of Standard AC Motors The squirrel cage induction motor is the electrical motor motor type most widely used in industry. This leading position results mainly
Diode Applications. by Kenneth A. Kuhn Sept. 1, 2008. This note illustrates some common applications of diodes.
by Kenneth A. Kuhn Sept. 1, 2008 This note illustrates some common applications of diodes. Power supply applications A common application for diodes is converting AC to DC. Although half-wave rectification
Rule 5.500 Fast Track Analysis for National Life Insurance Co.
Rule 5.500 Fast Track Analysis for National Life Insurance Co. For a 500 kw Solar array to be located at 155 Northfield Street in Montpelier, Vermont Green Mountain Power Pam Allen Date: 5/31/13 SECTION
Power Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module
Module 1 www.learnabout-electronics.org Power Supplies 1.0 Power Supply Basics What you ll learn in Module 1 Section 1.0 Power Supply Basics. Basic functions of a power supply. Safety aspects of working
Radial Distribution Test Feeders
Radial Distribution Test Feeders Distribution System Analysis Subcommittee Report Abstract: Many computer programs are available for the analysis of radial distribution feeders. In 1992 a paper was published
> Executive summary. The Role of Isolation Transformers in Data Center UPS Systems. White Paper 98 Revision 0. Contents.
The Role of Isolation Transformers in Data Center UPS Systems White Paper 98 Revision 0 by Neil Rasmussen > Executive summary Most modern UPS systems do not include the internal s that were present in
CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN
CHAPTER 5 PHOTOVOLTAIC SYSTEM DESIGN 5.1 Introduction So far in the development of this research, the focus has been to estimate the available insolation at a particular location on the earth s surface
Power Quality Standards for Electric Service
Power Quality Standards for Electric Service Effective June 1, 2008 A transition period will exist from June 1 through December 31, 2008 in which installations may be approved and connected as long as
CHAPTER 2 EXAMPLES AND TABLES
CHAPTER 2 EXAMPLES AND TABLES COMMENTARY AT 210.20(A) EXCEPTION An overcurrent device that supplies continuous and noncontinuous loads must have a rating that is not less than the sum of 100 percent of
ELECTRONIC POWER SYSTEMS
ELECTRONIC POWER SYSTEMS TRADEOFFS BETWEEN SINGLE-PHASE & THREE-PHASE POWER WHITE PAPER: TW0057 1 Executive Summary Modern Electronic Systems are quite often powered from a three-phase power source. While
Considering the effects of UPS operation with leading power factor loads
Considering the effects of UPS operation with leading power factor loads Over the past five years, a new generation of data processing and communications equipment has become prevalent in modern data centers
Tamura Closed Loop Hall Effect Current Sensors
Tamura Closed Loop Hall Effect Current Sensors AC, DC, & Complex Currents Galvanic Isolation Fast Response Wide Frequency Bandwidth Quality & Reliability RoHs Compliance Closed Loop Hall Effect Sensors
Power Quality. Uninterruptible Power Supply
Quality Uninterruptible Supply In the electrical system environment, power disturbances will occur. These can be caused by faults on the distribution system, the operation of nearby equipment, lightning
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
SECTION DVD01: VOLTAGE DROP/VOLTAGE FLICKER AND TRANSFORMER SIZING GUIDELINES
Issued 06-01-07 DESIGN Section DVD00 INFORMATION SECTION Page 1 of 1 INDEX SECTION DVD01: VOLTAGE DROP/VOLTAGE FLICKER AND TRANSFORMER INTRODUCTION... Page 2 LOAD ESTIMATING AND TRANSFORMER SIZING GUIDELINES...Page
SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION
SAFETY PRECAUTIONS AND INSTRUCTIONS FOR USE OF TECHNICAL INFORMATION Please read and understand the product instruction manual before installing, servicing or operating Yaskawa products. Technical content
Power Electronics. Prof. K. Gopakumar. Centre for Electronics Design and Technology. Indian Institute of Science, Bangalore.
Power Electronics Prof. K. Gopakumar Centre for Electronics Design and Technology Indian Institute of Science, Bangalore Lecture - 1 Electric Drive Today, we will start with the topic on industrial drive
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
Figure. 1 - Split Phase 240/120V circuit (180 phase shift)
This technical note describes the option of connecting the 60Hz XW Inverter/Charger to a three-phase source by using a transformer to convert the AC source to split-phase 240/120V. INTRODUCTION: Split-phase
Short Circuit Current Calculations
Introduction Several sections of the National Electrical Code relate to proper overcurrent protection. Safe and reliable application of overcurrent protective devices based on these sections mandate that
Harmonics in your electrical system
Harmonics in your electrical system What they are, how they can be harmful, and what to do about them Abstract Harmonic currents, generated by non-linear electronic loads, increase power system heat losses
Precision Diode Rectifiers
by Kenneth A. Kuhn March 21, 2013 Precision half-wave rectifiers An operational amplifier can be used to linearize a non-linear function such as the transfer function of a semiconductor diode. The classic
Survey of Harmonics Measurements in Electrical Distribution Systems
Survey of Harmonics Measurements in Electrical Distribution Systems Leon M. Tolbert, Member, IEEE Oak Ridge National Laboratory* P.O. Box 28, Bldg Oak Ridge, TN 3783-6334 Alexandria, VA 2235-3862 Phone:
Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka
Improvements of Reliability of Micro Hydro Power Plants in Sri Lanka S S B Udugampala, V Vijayarajah, N T L W Vithanawasam, W M S C Weerasinghe, Supervised by: Eng J Karunanayake, Dr. K T M U Hemapala
Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO 250447392
1 Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading By Ramandeep Kaur Aujla S.NO 250447392 ES 586b: Theory and applications of protective relays Department of
Power System Harmonics
Pacific Gas and Electric Company Power System Harmonics What are power system harmonics? Ideally, voltage and current waveforms are perfect sinusoids. However, because of the increased popularity of electronic
Paralleling Power Sources Which Share a Common Neutral
Paralleling Power Sources Which Share a Common Neutral By: Tony Hoevenaars, P.E., President & CEO, Mirus International, Inc. Mike McGraw, President, NSOEM, Inc. When paralleling power sources that share
Specification Requirements DBL 700MX and 1000MX Series UPS
Specification Requirements DBL 700MX and 1000MX Series UPS Theory of Operation Upon loss of utility power, the UPS inverter shall continue to provide seamless pure sine-wave AC from the batteries without
The Facts About Harmonics and Power Factor. Power Quality: Harmonics & Power Factor Correction
The Facts About Harmonics and Power Factor Power Quality: Harmonics & Power Factor Correction 1 Agenda I. Harmonic Basics II. Harmonic Mitigation Methods III. Active Harmonic Filters IV. Applications V.
UPS Applications and VRLA Battery Sizing
TECHNICAL BULLETIN 41-7334 UPS Applications and VRLA Battery Sizing 41-7334/0213/CD www.cdtechno.com The uninterruptable power system (UPS) is used to protect critical equipment and processes from the
Specifying a Variable Frequency Drive s
Specifying a Variable Frequency Drive s Put on by Bruce Reeves and Jeremy Gonzales Dykman Electrical Covering the Western US For all of your VFD and Soft Start and Motor Needs How To Specify a Variable
GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)
GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE) Matthew Theriault Designer Hindle Power Inc. Easton, PA SCOPE AND PURPOSE OF THE PAPER Why do we bother to monitor
Neutral Currents in Three Phase Wye Systems
POWER SYSTEMS ENGINEERING DATA PUBLISHED BY SQUARE D, OSHKOSH, WISCONSIN Subject: Neutral Currents in Three Phase Wye Systems by Robert Arthur Square D Company Oshkosh, Wisconsin (414) 46-80 and R. A.
EXTENDING THE LIFE OF POWER FACTOR CAPACITORS
by John Houdek, President, Allied Industrial Marketing, Inc., and Cesar Chavez, Engineering Manager, ARTECHE / Inelap Abstract: The addition of power factor improvement capacitors to individual motors
PROGRAM CRITERIA FOR ELECTRICAL ENGINEERING TECHNOLOGY
PROGRAM CRITERIA FOR ELECTRICAL ENGINEERING TECHNOLOGY Scope These program criteria apply to programs having titles involving Electrical Engineering Technology including: electrical engineering, electrical
The full wave rectifier consists of two diodes and a resister as shown in Figure
The Full-Wave Rectifier The full wave rectifier consists of two diodes and a resister as shown in Figure The transformer has a centre-tapped secondary winding. This secondary winding has a lead attached
Primary Electric Distribution for Industrial Plants
PDH Course E242 Primary Electric Distribution for Industrial Plants Adolph A. Biss, P.E. 2007 PDH Center 2410 Dakota Lakes Drive Herndon, VA 20171-2995 Phone: 703-478-6833 Fax: 703-481-9535 www.pdhcenter.com
HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM
Technical Note No.3 March 2000 HARMONIC DISTORTION IN THE ELECTRIC SUPPLY SYSTEM This Technical Note discusses harmonic distortion, its causes and adverse effects, what levels are unacceptable and how
3. TYPES OF SERVICE AVAILABLE. 3.1 Scope
3. TYPES OF SERVICE AVAILABLE 3.1 Scope UI supplies 60 hertz, alternating current with different voltage and ampere ratings. Not all voltage and ampere ratings are available throughout the entire service
AC Direct Off-Line Power Supplies
AC Direct Off-Line Power Supplies r Introduction Many DC power supplies found in electronic systems, including those in this Tech School, rectify the 120 volts available at an electric outlet. The initial
Quantec Wiring Instructions
Approved Document No. DNUQ777 Rev Quantec Wiring Instructions GENERAL Quantec can be compared to a very sophisticated analogue addressable fire alarm system where the integrity of the wiring is of paramount
Transistor Characteristics and Single Transistor Amplifier Sept. 8, 1997
Physics 623 Transistor Characteristics and Single Transistor Amplifier Sept. 8, 1997 1 Purpose To measure and understand the common emitter transistor characteristic curves. To use the base current gain
POWER FACTOR CORRECTION
[CATALOGUE PFC-SFC] POWER FACTOR CORRECTION INDUSTRIAL SWITCHGEAR & AUTOMATION SPECIALISTS A component of nhp s green star solution... www.nhp.com.au Power Factor - What does it mean? Where open electricity
RC NETWORKS SALES GUIDE
SALES GUIDE INTRODUCTION TO Recent developments in electronic equipment have shown the following trends: Increasing demands for numerical control machines, robotics and technically advanced appliances
EMC STANDARDS STANDARDS AND STANDARD MAKING BODIES. International. International Electrotechnical Commission (IEC) http://www.iec.
EMC STANDARDS The EMC standards that a particular electronic product must meet depend on the product application (commercial or military) and the country in which the product is to be used. These EMC regulatory
= V peak 2 = 0.707V peak
BASIC ELECTRONICS - RECTIFICATION AND FILTERING PURPOSE Suppose that you wanted to build a simple DC electronic power supply, which operated off of an AC input (e.g., something you might plug into a standard
Coordination of Telecommunications Surge Protective Devices in Countries with Unstable AC Power
App Notes ~ Outdoor Power System Design and Cost Considerations 1 Authors Peter Nystrom President TSi Power Corp. Coordination of Telecommunications Surge Protective Devices in Countries with Unstable
Diode Applications. As we have already seen the diode can act as a switch Forward biased or reverse biased - On or Off.
Diode Applications Diode Switching As we have already seen the diode can act as a switch Forward biased or reverse biased - On or Off. Voltage Rectifier A voltage rectifier is a circuit that converts an
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy
Power Quality Issues, Impacts, and Mitigation for Industrial Customers
Power Quality Issues, Impacts, and Mitigation for Industrial Customers By Kevin Olikara, Power and Energy Management Products Rockwell Automation, Inc. Now, more than ever, electronic equipment and computing
AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5
White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code June 2015 Revision 1.5 Shalhevet Bar-Asher; SolarEdge Technologies, Inc. Bill Brooks, PE; Brooks Engineering LLC
The following table shows approximate percentage wise the
SHORT-CIRCUIT CALCULATION INTRODUCTION Designing an electrical system is easy and simple, if only the normal operation of the network is taken into consideration. However, abnormal conditions which are
Modeling of Transmission Lines
Modeling of Transmission Lines Electric Power Transmission The electric energy produced at generating stations is transported over high-voltage transmission lines to utilization points. The trend toward
2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?
Extra Questions - 2 1. A straight length of wire moves through a uniform magnetic field. The e.m.f. produced across the ends of the wire will be maximum if it moves: a) along the lines of magnetic flux
Understanding Delta Conversion Online "Power Regulation" - Part 2
Application Note #40 Understanding Delta Conversion Online "Power Regulation" - Part 2 Introduction This application note is the second in a series on delta conversion theory of operation. For complete
Current Transformers
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 Current Transformers Current transformers (CT's) provide
Triplen Harmonics Mitigation 3 Phase Four-Wire Electrical Distribution System Using Wye- Zig-Zag Transformers
Journal Journal of of Emerging Emerging Trends Trends in in Engineering Engineering and and Applied Applied Sciences Sciences (JETEAS) (JETEAS) 1 1 (1): (1): 72-78 72-78 Scholarlink Research Institute
CITY OF LOS ANGELES CALIFORNIA
BOARD OF BUILDING AND SAFETY COMMISSIONERS VAN AMBATIELOS PRESIDENT E. FELICIA BRANNON VICE-PRESIDENT JOSELYN GEAGA-ROSENTHAL GEORGE HOVAGUIMIAN JAVIER NUNEZ CITY OF LOS ANGELES CALIFORNIA ERIC GARCETTI
DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT
DESIGNING MODERN ELECTRICAL SYSTEMS WITH TRANSFORMERS THAT INHERENTLY REDUCE HARMONIC DISTORTION IN A PC-RICH ENVIRONMENT by Philip J. A. Ling, P.Eng. Cyril J. Eldridge, B. Sc. POWERSMITHS INTERNATIONAL
Whale 3. User Manual and Installation Guide. DC Servo drive. Contents. 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty.
Whale 3 DC Servo drive User Manual and Installation Guide Contents 1. Safety, policy and warranty. 1.1. Safety notes. 1.2. Policy. 1.3. Warranty. 2. Electric specifications. 2.1.Operation ranges. 3. Connections
CONSTRUCTING A VARIABLE POWER SUPPLY UNIT
CONSTRUCTING A VARIABLE POWER SUPPLY UNIT Building a power supply is a good way to put into practice many of the ideas we have been studying about electrical power so far. Most often, power supplies are
GLOLAB Two Wire Stepper Motor Positioner
Introduction A simple and inexpensive way to remotely rotate a display or object is with a positioner that uses a stepper motor to rotate it. The motor is driven by a circuit mounted near the motor and
GenTech Practice Questions
GenTech Practice Questions Basic Electronics Test: This test will assess your knowledge of and ability to apply the principles of Basic Electronics. This test is comprised of 90 questions in the following
KNX Powerline PL 110. KNX Association
KNX Powerline PL 110 Table of Contents 1 Introduction...3 2 Standardisation...3 3 Transmission Process...4 3.1 Phase Coupling...5 3.2 Telegram Transmission...6 3.2.1 Training Sequence...6 3.2.2 Preamble
Drive circuit basics + V. τ e. Industrial Circuits Application Note. Winding resistance and inductance
ndustrial Circuits Application Note Drive circuit basics For a given size of a stepper motor, a limited space is available for the windings. n the process of optimizing a stepper motor drive system, an
Power surges can also be generated by equipment in your facility such as:
Power Quality Surge Suppressors What is Surge Protection A surge suppressor can be the first and best defense against the instant or gradual destruction of electrical equipment. Compared to the replacement
98% Efficient Single-Stage AC/DC Converter Topologies
16 POWER CONVERTERS www.teslaco.com 98% Efficient Single-Stage AC/DC Converter Topologies A new Hybrid Switching Method is introduced in this article which for the first time makes possible AC/DC power
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta
GENERATOR SELECTION Generators must be sized to handle their load based on the continuous KW, kilowatt load, and KVA, kilovoltamp load, and the worst case starting load KW + KVA. They must be derated for
APPLICATION NOTE TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION. Abstract.
TESTING PV MICRO INVERTERS USING A FOUR QUADRANT CAPABLE PROGRAMMABLE AC POWER SOURCE FOR GRID SIMULATION Abstract This application note describes the four quadrant mode of operation of a linear AC Power
ABR Brake Rectifier Instruction Manual
ABR Brake Rectifier Instruction Manual Part Number: 552074 Copyright 2012 Magnetek 1. Preface and Safety All rights reserved. This notice applies to all copyrighted materials included with this product,
CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008
CAT AVR V2.3 Voltage regulator for generators March 2008 Instruction Manual Warnings WARNING The system should not be installed, operated, serviced or modified except by qualified personnel who understand
1. The type of service available at any particular location should be determined by inquiry at PG&E's local office.
Revised Cal. P.U.C. Sheet No. 11257-E Cancelling Revised Cal. P.U.C. Sheet No. 6925-E ELECTRIC RULE NO. 2 Sheet 1 A. GENERAL 1. The type of service available at any particular location should be determined
CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR)
CATHODIC PROTECTION TRANSFORMER RECTIFIER (CPTR) Fig1. CPTR SMART CONTROL PRECISION CUSTOMIZED MANUAL OR AUTO SCR OR DIODE DRY TYPE SWITCH MODE DRY TYPE SCR OR DIODE OIL TYPE 1 INDEX PAGE 1. Cover 2. Index
Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE
Understanding Power Factor and How it Affects Your Electric Bill Presented by Scott Peele PE Understanding Power Factor Definitions kva, kvar, kw, Apparent Power vs. True Power Calculations Measurements
LM 358 Op Amp. If you have small signals and need a more useful reading we could amplify it using the op amp, this is commonly used in sensors.
LM 358 Op Amp S k i l l L e v e l : I n t e r m e d i a t e OVERVIEW The LM 358 is a duel single supply operational amplifier. As it is a single supply it eliminates the need for a duel power supply, thus
Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers
Technical Note Freedom/Fleet Power 512-0084-01-01 Rev 1 Troubleshooting Guide, Freedom and Fleet Power Inverter/Chargers Overview This document is a guide for troubleshooting inverters, battery chargers,
Simulation of Ungrounded Shipboard Power Systems in PSpice
Simulation of Ungrounded Shipboard Power Systems in PSpice Haibo Zhang IEEE Student Member Karen L.Butler IEEE Member Power System Automation Lab Electrical Engineering Department Texas A&M University
ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1
ES281 COMPANY-SPECIFIC APPENDICES TO ENA ENGINEERING RECOMMENDATION G81 PART 1 Design and Planning Specification for New Low Voltage Installations for Housing Developments 1. SCOPE This appendix to ENA
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
ATTACHMENT F. Electric Utility Contact Information Utility Name. For Office Use Only
ATTACHMENT F CATEGORY 2 GENERATOR INTERCONNECTION APPLICATION FOR ALL PROJECTS WITH AGGREGATE GENERATOR OUTPUT OF MORE THAN 20 KW BUT LESS THAN OR EQUAL TO 150 KW Also Serves as Application for Category
Rotary Phase Converters
FACTS from Ronk Electrical Industries, Inc. Bulletin 11981 Rotary Phase Converters ROTOVERTER Pat. No. 3,670,238 ROTO-CON Pat. No. 4,158,225 What are the ROTO-CON and ROTOVERTER power converters? The ROTO-CON
FACTS. Solutions to optimise network performance GRID
Solutions to optimise network performance GRID Solutions to optimise your network Our worldwide presence: Better solutions for your network all around the world Tampere Philadelphia Stafford Konstanz Beijing
Table of Contents. The Basics of Electricity 2. Using a Digital Multimeter 4. Testing Voltage 8. Testing Current 10. Testing Resistance 12
Table of Contents The Basics of Electricity 2 Using a Digital Multimeter 4 IDEAL Digital Multimeters An Introduction The Basics of Digital Multimeters is designed to give you a fundamental knowledge of
NC-12 Modbus Application
NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches
Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches Downtime Is Not An Option The industrial uninterruptible power supply (UPS) is the foundation of your
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance
WHITE PAPER Enphase Microinverters and Ungrounded Renewable Energy Systems: Canadian Electrical Code Compliance Overview Enphase has developed a new microinverter family that includes the M250 and new