APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 15kVA and 20kVA Smart-UPS RT 230VAC Uninterruptible Power Supply
|
|
|
- Adrian McCarthy
- 9 years ago
- Views:
Transcription
1 APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 15kVA and 20kVA Smart-UPS RT 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality of a continuous duty, dual input feed with configurable single-phase or three-phase input and output power (1:1, 3:1 or 3:3), solid-state, static Uninterruptible Power System (UPS) hereafter referred to as the UPS. B. The UPS shall utilize double conversion online topology designed to protect electronic equipment by supplying reliable, network-grade power with extremely tight voltage and frequency regulation. The UPS shall feature an internal static bypass and input power factor correction. C. Configuration Specifics: 1. The UPS shall be available in the following configurations: MODEL SKU # UPS APC Smart-UPS RT 15,000VA RM 230V SURT15KRMXLI APC Smart-UPS RT 20,000VA RM 230V SURT20KRMXLI BATTERY PACK APC Smart-UPS RT192V RM Battery Pack 2 Rows SURT192RMXLBP2 2. The system power train shall comprise of, input disconnect and filter stage, input PFC power stage, energy storage stage (DC bus capacitor bank), output power stage (inverters), static bypass switch for connecting bypass line to the output, and battery charger. 3. The system shall also include field-replaceable output power distribution panels (when battery module is utilized), field-replaceable fan module, field-replaceable battery modules, removable input/output wiring trays, battery disconnects, an LCD interface display, EPO, and an integrated UPS network management card with temperature monitoring. D. In addition, this specification describes the performance, functionality, and design of the UPS Service Bypass Panel, hereafter referred to as the SBP, the external Battery Systems, and connectivity solutions.
2 E. The UPS and associated equipment shall operate in conjunction with a primary power supply and an output distribution system to provide quality uninterrupted power for mission critical, electronic equipment load. F. All programming and miscellaneous components for a fully operational system as described in this specification shall be available as part of the UPS. 1.2 STANDARDS A. EN / EN/IEC B. EN / IEC C. EN55022 Class A D. EN E. EN60950 F. IEC G. GOST H. CE I. VDE J. C-tick K. ISO 9001 L. ISO MODES OF OPERATION A. Normal: The input Power Factor Corrector (PFC) stage and output inverter stage shall operate in an on-line manner to continuously regulate power to the critical load. The input and output converters shall be capable of full battery recharge while simultaneously providing regulated power to the load for all line and load conditions within the range of the UPS specifications. B. Battery: Upon failure of the AC input source, the critical load shall continue being supplied by the output inverters, which shall derive their power from the battery system. There shall be no interruption in power to the critical load during either transfer to or from battery operation back to normal operation. C. During the re transfer from battery to on-line operation, the load shall be softly transferred from battery back on-line within 10 seconds, to avoid step load changes on the mains supply.
3 D. Recharge: Upon restoration of the AC input source, the input converters and output inverters shall simultaneously provide regulated power to the critical load and recharge the battery. E. Bypass operation: Bypass mode shall be reached either as a user selection or automatically. 1. Bypass mode can be selected through the Control menu screen on the PowerView display 2. The UPS will automatically switch into bypass mode if: a. Both normal and battery operation modes are unavailable b. An output overload condition occurs c. The UPS has an internal fault During bypass operation the utility power is connected to the load, bypassing the internal converters. If the bypass mode becomes unavailable the UPS will automatically switch to mains power. In the event that mains power is unavailable the system will switch to battery power. With the UPS supplied from dual feeds and operating on battery, due to a mains failure, it shall be possible to request the unit to go to bypass, in addition to automatically transfer to bypass when the batteries are depleted. In this bypass mode the inverter shall become a PFC and back-feed the DC busses. This allows the charger to continue charging the batteries. F. External Service Bypass Panel (SBP): A maintenance service bypass cabinet shall provide power to the critical load bus from the bypass source, during times where maintenance or service of the UPS frame is required or when removal of the whole unit is desired. The SBP shall provide a mechanical means of complete isolation of the UPS from the electrical wiring of the installation. The SBP shall be constructed in a freestanding, rack mounted or wall-mounted enclosure unless otherwise stated in this specification. It shall be designed for either three phase input and output or single phase input and output with a no break transfer between bypass and UPS power. 1.4 SUBMITTALS A. Proposal Submittals: 1. As bid system bill of materials. 2. Product catalog sheets or equipment brochures. 3. Product guide specifications. 4. System single-line operation diagram. 5. Installation information, including weights and dimensions.
4 6. Information about terminal locations for power and control connections. B. Delivery Submittals: 1. Installation manual, which includes instructions for storage, handling, examination, preparation, installation, and start-up of UPS. 2. User manual, which includes operating instructions. PART 2 - PRODUCT 2.1 MECHANICAL DESIGN A. The UPS shall be contained in two rugged steel cabinets one containing the power electronics and the other containing the batteries and single phase distribution outlets; B. The UPS and battery cabinets shall be capable of conversion between Tower / Stack and Rack-Mount configurations; C. The power electronics cabinet dimensions including terminations shall be Rack or stack configuration 263 x 432 x 773mm (10.35 x 17 x in.) (Height x Width x Depth), requires 6U of rack space and the side rack mounting brackets shall increase the overall width to 482mm (19 in); D. The battery cabinet dimensions including terminations shall be Rack or stack configuration 263 x 432 x 739 mm (10.35 x 17 x 29.1 in.) (Height x Width x Depth), requiring 6U of rack space and the side rack mounting brackets shall increase the overall width to 482mm (19 in); 2.2 SYSTEM CHARACTERISTICS A. System Capacity: B. Input: 1. The system shall be rated for.8 Pf output: a. 15,000VA or 12,000W whichever limit is reached first (15kVA model). b. 20,000VA or 16,000W whichever limit is reached first (20kVA model). 1. AC input nominal voltage:
5 a. 220/230/240VAC, single phase, 3 wire (L + N + G) or b. 380/400/415VAC, three phase, 5 wire (L1+L2+L3+N+G); 2. AC input voltage window: a. Full Load, V (Line-Neutral) for single phase input or V (Line-Line) for three phase input; b. Half Load, V (Line-Neutral) for single phase input or V (Line-Line) for three phase input; 3. Input frequency range: 40-70Hz; 4. Input Power Factor; > 0.98 at 100% load 5. Input Current Distortion: < 4% at 100% load, 230VAC (<7% for 3 phase output) 6. Crest factor: 3:1. C. UPS Output: 1. AC Output Nominal Output: (Customer configurable) a. 220VAC, 230VAC or 240VAC, Single Phase three wire, 50/60Hz; b. 380VAC, 400VAC or 415VAC, Three phase five wire, 50/60Hz; 2. AC output voltage distortion: Max. 100% linear load; Max. 100% non-linear Load; 3. AC output voltage regulation (Static): +/-1%; 4. Voltage Transient Response : +/- 8% maximum for 100% load step 5. Voltage Transient Recovery within < 10ms recovery time; 6. Output Voltage Harmonic Distortion: a. <2% THD maximum for a 100% linear load b. <5% THD maximum for a 100% non-linear load 7. Overload Rating: a. Online: 105% - infinite; 125% - 1 minute; 150% - 30 seconds; b. In bypass: Overload is limited by the external input circuit breaker feeding the UPS. 8. System AC-AC Efficiency: >94% at >50% load 9. Output Power Factor Rating: lagging, nominal: 0.8 lagging. 10. Output frequency: 50/60 +/- 3Hz tracking or 50/60 +/- 0.1Hz tracking (user selectable);
6 11. Output connectors: a. Single phase: Hardwire 3-wire (Phase + N + G), 8 IEC 320 C19 (when battery module is utilized); b. Three phase: Hardwire 5-wire (3 Phase + N + G) 12. Output frequency Slew rate : 1.0Hz/Sec, 0.5Hz/Sec 0.25Hz/Sec 2.3 ENVIRONMENTAL 1. Storage Ambient Temperature: a. -15 to +45 C (+5 to +113 F) charge the UPS battery every 6 months. b. +30 to +70 C (+86 to +158 F) charge the UPS battery every 3 months. 2. Operating Ambient Temperature: 0 C to +40 C (+32 F to +104 F). (+25 C (+77 F) is ideal for most battery types). 3. Relative Humidity: 0 to 95% non-condensing 4. Storage altitude: 15,240m (50,000 feet) above sea level 5. Operating altitude: 3,000m (10,000 feet) above sea level. At an altitude of 3,000 m the UPS shall be capable of supporting a load of up to 90% of its nominal capacity. 6. Audible noise: a. For 15kVA: <50dBA at 100 % load at 1m b. For 20kVA: <50dBA at <70 % load at 1m, <60dBA at >75 % load at 1m 2.4 INPUT PFC POWER STAGE A. The input PFC power stage of the UPS shall constantly rectify the power imported from the mains input of the system, converting the input mains AC power to DC power for precise regulation of the DC bus voltage, battery charging, and output power stage (inverter) regulated output power. B. Input Current Total Harmonic Distortion: The input current THD I shall be held to 6% or less at full system load, while providing conditioned power to the critical load bus, and charging the batteries under steady-state operating conditions. This shall be true while supporting loads of both a linear or non-linear type. This shall be accomplished with no additional filters, magnetic devices, or other components. C. Input Current Limit:
7 1. The input converter shall control and limit the input current drawn from the utility supply to: a. 15kVA unit 95A (single phase), 31.6A per phase (three phase) b. 20kVA unit 121A (single phase), 40.3A per phase (three phase) 2. Overloads at low line input voltages shall draw power from the battery, (battery assist mode) in order to support the load and maintain the input current below the set current limit points. D. Charging: 1. The battery charging shall maintain the DC bus float voltage of +/-219V, +/-1% at the nominal temperature of 20 C (68 F) 2. The battery charging circuit shall contain a temperature monitoring circuit, which will regulate the battery charging current to optimize battery life. 3. The battery charging circuit shall remain active when in automatic Bypass and in Normal Operation. 4. The battery charging system shall adjust the charging current by automatically sensing the number of battery modules and by monitoring the individual battery current. Maximum charger power shall be 3kW. 2.5 OUTPUT POWER STAGE (INVERTER) A. The UPS output power stage (inverter) shall constantly recreate the UPS output voltage waveform by converting the DC bus voltage to AC voltage through a set of IGBT switches. In both online operation and battery operation, the output power stage (inverter) shall create an output voltage waveform independent of the mains input voltage waveform. Input voltage anomalies such as brown-outs, spikes, surges, sags, and outages shall not affect the amplitude or sinusoidal nature of the recreated output voltage sine wave of the output power stage (inverter). B. Overload Capability: The output power stage (inverter) shall be capable of withstanding 150% overload for 30 seconds or 125% overload for 1 minute or 105% overload for an indefinite length of time. The system shall transfer to bypass if the overload persist and then return back on-line when the overload is removed. C. Battery Protection: The UPS shall have monitoring and control circuits to limit the level of discharge on the battery system. 2.6 AUTOMATIC BYPASS A. As part of the UPS, a system automatic bypass switch shall be provided. The system automatic bypass shall provide a transfer of the critical load from the Inverter output to the automatic bypass input source during times when the inverter cannot support the
8 load. Such times may be due to prolonged or severe overloads, or UPS failure. The UPS shall constantly monitor the output current, as well as the bypass source voltage, and inhibit potentially unsuccessful transfers to automatic bypass from taking place. B. The design of the automatic bypass switch power path shall consist of an electromechanical bypass contactor and series SCR s. C. Automatic Transfers: An automatic transfer of load to bypass shall take place whenever the load on the critical bus exceeds the overload rating of the UPS. Automatic transfers of the critical load from bypass back to normal operation takes place when the overload condition is removed from the critical bus output of the system. Automatic transfers of load to bypass shall also take place if for any reason the UPS cannot support the critical bus. D. Manual Transfers: Manually initiated transfers to and from bypass shall be initiated through the UPS interface display or via the serial communications port. 2.7 DISPLAY AND CONTROLS A. Control Logic: The UPS shall be controlled by an embedded microcontroller which performs the following functions: 1. Monitoring quality of input, bypass and output voltages; 2. Monitoring vital parameters of the UPS; 3. Executing the state machine; 4. Intelligent battery management; 5. Remaining runtime calculation; 6. Self-diagnostics, self-test and proactive fault detection; 7. Communication to the host server via serial port; 8. Communication to the Network Interface Card or another SmartSlot accessory card if equipped. B. Display Unit: A microprocessor controlled display unit shall be located at the front of the system. The display shall consist of an alphanumeric display with backlight, providing system status, LED alarm indicators and a keypad consisting of pushbutton switches for control and status reading selection. C. Metered Data: The following metered data, shall be available on the alphanumeric display: 1. Year, Month, Day, Hour, Minute, Second of occurring events
9 2. Source and Bypass Input Voltages 3. Output AC voltage 4. Input, Bypass and Output AC currents 5. Input, Bypass and Output Frequency 6. Battery voltages and currents 7. Internal and battery pack temperature D. Event log: The display unit shall allow the user to display a time and date stamped log of the 100 most recent status and alarm events. E. Alarms: The display unit shall allow the user to display a log of all active alarms. The following minimum set of alarm conditions shall be available: 1. Input Frequency outside configured range 2. AC adequate for UPS but not for Bypass 3. Low/No AC input, startup on battery 4. Number of Batteries changed since last ON 5. Number of Batteries increased 6. Number of Batteries decreased 7. Need Battery Replacement 8. UPS Fault 9. On Battery 10. Shutdown or unable to transfer to battery due to overload 11. Load Shutdown from Bypass. Input Frequency Volts outside limits 12. Fault, Internal Temp exceeded system normal limits 13. System level fan failed 14. Bad Battery Module 15. Runtime is below alarm threshold 16. Load is above alarm threshold
10 17. Load is no longer above alarm Threshold 18. Minimum Runtime restored 19. Bypass is not in range (either frequency or voltage) 20. UPS in Bypass due to Internal Fault 21. UPS in Bypass due to overload 22. Low Battery Shutdown 23. Low Battery Warning F. Controls: The following controls or programming functions shall be accomplished by use of the display unit. Pushbutton switches shall facilitate these operations. 1. Silence audible Alarm 2. Display or set the date and time 3. Transfer critical load to and from bypass 4. Test battery condition on demand 5. Set intervals for automatic battery tests 6. Adjust set points for different alarms G. Communication Interface Board: A communication interface shall provide the following communication ports which can be used simultaneously: 1. RS232 Serial Port #1 2. RJ-45 Interface port for PowerView Display 3. RJ-45 Ethernet connection, on installed Network Management Card 2.8 BATTERY A. The UPS battery system shall comprise of user replaceable, hot swappable, battery modules. Minimum four battery module pairs must be installed, two sets providing 192VDC nominal for the positive DC bus rail, two sets providing 192VDC nominal for the negative DC bus rail. B. The battery blocks housed within each removable battery module shall be of the Valve Regulated Lead Acid (VRLA) type.
11 C. The UPS shall incorporate an Intelligent Battery Management system to continuously monitor the health of the battery system and notify the user if that system is weak or needs replacing. D. It shall be possible to add additional battery modules to increase runtime. These modules shall be hot-pluggable, allowing for easy and quick installation or replacement without the need for electrical wiring, electrician services or powering down of the UPS. The maximum number of external battery packs, XLBP2, that may be connected to the UPS shall be limited to 10. E. Battery modules shall have an embedded intelligent Microcontroller that will retain the modules serial number as well as diagnostic information. F. Each UPS Battery Module shall have a means of DC disconnect for transportation and to disconnect the battery module completely from the internal bus while installed in the UPS system. G. Charging: 1. The intelligent battery management system shall contain a temperature monitoring circuit and compensation algorithm that regulates the battery charging current so as to optimize battery life. The UPS shall monitor the temperature of all battery packs and use the highest one as a reference to adjust the battery float voltage. 2. The battery charging circuit shall remain active when in bypass or on-line. 3. Charging system shall automatically adjust the maximum charger power, up to 3kW, based on the installed battery capacity and current through each battery string to avoid excessive charging that could result in blotted batteries. Each battery pack shall report its battery currents and temperature to UPS through CAN communication H. The UPS shall be shipped with battery modules preinstalled but disconnected. PART 3 - PART 3 ACCESSORIES 3.1 SERVICE BYPASS PANEL (SBP) A. The service bypass panel shall provide power to the critical load from the bypass source, during times where maintenance or service of the UPS is required. The SBP shall provide a mechanical means of complete isolation of the UPS from the electrical wiring of the installation. The SBP shall be constructed in a free-standing, rack mounted or wall-mounted enclosure unless otherwise stated in this specification.
12 3.2 REMOVABLE INPUT/OUPUT ELECTRICAL TERMINAL A. The input and output terminal connections shall be designed to be removable trays for easy electrical connection and unit removal. B. The removable input and output trays shall contain a means of configuring the system for 1 or 3 phase input and output as well as for single or dual feed input. 3.3 SOFTWARE AND CONNECTIVITY A. Network Adaptor: APC SmartSlot Network Management Card shall allow one or more network management systems (NMS) to monitor and manage the UPS in TCP/IP network environments. B. Unattended Shutdown 1. The UPS, in conjunction with a network interface card, shall be capable of gracefully shutting down one or more operating systems when the UPS is operating in the battery mode. APC PowerChute Network Shutdown software shall be available with the UPS. 2. The UPS shall also be capable of using an RS232 port to communicate with the host computer by means of serial communications so as to gracefully shut down one or more operating systems during an on battery situation. APC PowerChute Business Edition software shall be available separately. 3.4 REMOTE UPS MONITORING, CONFIGURATION AND CONTROL A. The following three methods of remote UPS control, configuration and monitoring are available: 1. Web Monitoring: Remote monitoring shall be available via a web browser such as Internet Explorer. 2. RS232 Monitoring: Remote UPS monitoring shall be possible via either RS232 or contact closure signals from the UPS. 3. Simple Network Management Protocol (SNMP): Remote UPS Monitoring shall be possible through a standard MIB II compliant platform. 3.5 SOFTWARE COMPATIBILITY A. The UPS manufacturer shall have available software to support graceful shutdown and remote monitoring for the systems detailed on the following web link: Operating System and Processor Compatibility Chart
13 PART 4 - Part 4 - EXECUTION 4.1 FACTORY ASSISTED START-UP If a factory assisted UPS start-up is requested, factory trained service personnel shall perform the following inspections, test procedures, and on-site training: A. Visual Inspection: 1. Inspect equipment for signs of damage. 2. Verify installation per manufacturer s instructions. 3. Inspect cabinets for foreign objects. 4. Inspect battery chassis and modules. 5. Inspect power chassis B. Mechanical Inspection 1. Check all UPS and external service bypass panel internal power wiring connections. 2. Check all UPS and external service bypass panel terminal screws, nuts, and/or spade lugs for tightness. C. Electrical Inspection: 1. Verify correct input and bypass voltage. 2. Verify correct UPS control wiring and terminations. 3. Verify voltage of all battery modules. 4. Verify neutral and ground conductors are properly landed. 5. Inspect external service bypass panel for proper terminations. D. Site Testing: 1. Ensure proper system start-up. 2. Verify proper control functions. 3. Verify proper bypass operation.
14 4. Verify system set points. 5. Verify proper inverter operation and regulation circuits. 6. Simulate utility power failure. 7. Verify proper charger operation. 8. Document, sign, and date all test results. E. On-Site Operational Training: During the factory assisted start-up, operational training for site personnel shall include key pad operation, LED indicators, start-up and shutdown procedures, maintenance bypass and AC disconnect operation, and alarm information. 4.2 MANUFACTURER FIELD SERVICE A. Worldwide service: The UPS manufacturer shall have a worldwide service organization available, consisting of factory trained field service personnel to perform start-up, preventative maintenance, and service of the UPS system and power equipment. The service organization shall offer 24 hours a day, 7 days a week, 365 days a year service support. B. Replacement parts: Parts shall be available through the worldwide service organization 24 hours a day, 7 days a week, 365 days a year. The worldwide service organization shall be capable of shipping parts within 4 working hours or on the next available flight, so that the parts may be shipped to the customer site within 24 hours. 4.3 MAINTENANCE CONTRACTS A. A complete offering of preventative and full service maintenance contracts for the UPS system and the battery system shall be available from APC. All contract work shall be performed by APC factory trained service personnel. 4.4 TRAINING A. UPS service training workshop: A UPS service training workshop shall be available from APC. The service training workshop shall include a combination of lecture and practical instruction with hands-on laboratory sessions. The service training workshop shall include instruction about safety procedures, UPS operational theory, sub-assembly identification and operation, system controls and adjustment, preventative maintenance, and troubleshooting. End of Section 16611
APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply
APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 3000VA, 5000VA and 6000 VA Smart-UPS RT 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality
APC Smart-UPS RT. GUIDE SPECIFICATIONS FOR 1000VA, 2000VA & 3000VA Smart-UPS RC 230VAC Uninterruptible Power Supply
APC Smart-UPS RT GUIDE SPECIFICATIONS FOR 1000VA, 2000VA & 3000VA Smart-UPS RC 230VAC Uninterruptible Power Supply PART 1 - GENERAL 1.1 SUMMARY A. This specification describes the operation and functionality
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass
AIS 3000 APC AIS 3000 15kVA 208V w/2 Batt. Module Exp. To 4, Start-Up 5X8, Internal Maintenance Bypass APC AIS 3000, 12 kw / 15 kva,input 208V 3PH / Output 120V, 208V, 208V 3PH, Interface Port DB-9 RS-232,
APC by Schneider Electric Smart-UPS RT Uninterruptible Power Supply 5 kva, 6 kva, 8 kva, 10 kva 230 V Solution
APC by Schneider Electric Smart-UPS RT Uninterruptible Power Supply 5 kva, 6 kva, 8 kva, 10 kva 230 V Solution THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS INSTITUTE
PowerGem Pro Uninterruptible Power Supply
Uninterruptible Power Supply User-friendly Intelligent Ultra reliable Range The Most Intelligent On-Line Double Conversion Power Protection System The range achieves higher reliability and greater immunity
Dell Smart-UPS 1,500 3,000 VA
Dell Smart-UPS,00,000 VA 0 V Advanced line interactive power protection for servers and network equipment Reliable. Intelligent. Efficient. Manageable. Engineered by APC by Schneider Electric, the Dell
NEW APC Smart-UPS. Advanced line interactive power protection for servers and network equipment. The world s most popular network and server UPS.
NEW APC Smart-UPS Advanced line interactive power protection for servers and network equipment. > The world s most popular network and server UPS. Award-winning Smart-UPS protects critical data by supplying
DC UPS. RTB.e 50-1000 A. IMB.e/ITB.e 5-200 kva. E2001.e/E3001.e 5-200 kva. Input voltage: 110/125/220 Vdc. 115/120/230 Vac, 1-phase (IMB.
Oil & Gas Energy Catalogue DC UPS RTB.e 50-1000 A 3 phase rectifier battery chargers voltage: 400 Vac, 3-phase, 50/60 Hz voltage: 24/48/110/220 Vdc RMB.e/RCB.e 50-100-150 A 1 and 3 phase compact rectifier
NEW APC Smart-UPS. Advanced line interactive power protection for servers and network equipment. The world s most popular network and server UPS.
NEW APC Smart-UPS Advanced line interactive power protection for servers and network equipment. > The world s most popular network and server UPS. Award-winning Smart-UPS protects critical data by supplying
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS, 3750 Watts / 5000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model Includes: CD with software,
Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V
Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V APC Smart-UPS, 670 Watts / 1000 VA,Input 230V / Output 230V, Interface Port DB-9 RS-232, SmartSlot, USB Includes: CD with software, Smart UPS signalling
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION
City of Leesburg, Florida I.T. Data Center 130551 APPENDIX A TOSHIBA UPS INFORMATION This Appendix A includes technical documents and specifications for the Toshiba 4200 FA 30 kva Uninterruptable Power
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU5000RT4UHV Description Tripp Lite SU5000RT4UHV 5000VA / 5kVA /
LAP ENERGIA PARA DATACENTERS
LAP ENERGIA PARA DATACENTERS Latin American Power. CABA, Argentina. 2 UPS INDOOR Latin American Power. CABA, Argentina. ALI ELITE SERIES Line Interactive UPS Tower/19 Rack Mount Versions 19 Rack Mount
SmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial
SmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SMX1000RT2U Highlights 1kVA / 1000VA / 900W line-interactive 2U rack/tower UPS, Sine
Uninterruptible Power Supply
96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features
SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial
SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SMART500RT1U Description Tripp Lite's SMART500RT1U intelligent, line-interactive rack/tower uninterruptible
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection. AC Power for Business-Critical Continuity
Liebert GXT MT+ CX UPS, 1000VA - 3000VA Intelligent, Reliable UPS Protection AC Power for Business-Critical Continuity Liebert GXT MT+ CX UPS, 1000VA -3000VA Intelligent, Reliable UPS Protection Liebert
Smart-UPS On-Line 230 V
Smart-UPS On-Line 230 V Unity output power factor single-phase, double-conversion online UPS with advanced management features A versatile UPS developed for unstable power conditions worldwide Smart-UPS
Galleon 6-10K Online UPS. Voltronic Power Technology Corporation
Galleon 6-10K Online UPS Voltronic Power Technology Corporation Features Galleon online UPS series delivers optimal power quality, provides superior power management, resolves utility power protection
SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial
SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial MODEL NUMBER: SMART2200RM2U Highlights 2.2kVA / 2200VA / 1920W line interactive 2U
SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial
SmartPro 230V 3kVA 2.25kW Line-Interactive UPS, Extended Run, SNMP, Webcard, Tower, USB, DB9 Serial MODEL NUMBER: SMARTINT3000VS Highlights 3kVA / 3000VA / 2250W line interactive tower UPS system 230V
Thyristor-controlled power supplies and battery chargers
Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /
Daker DK 1, 2, 3 kva. Manuel d installation Installation manual. Part. LE05334AC-07/13-01 GF
Daker DK 1, 2, 3 kva Manuel d installation Installation manual Part. LE05334AC-07/13-01 GF Daker DK 1, 2, 3 kva Index 1 Introduction 24 2 Conditions of use 24 3 LCD Panel 25 4 Installation 28 5 UPS communicator
SECTION 16260 STATIC UNINTERRUPTIBLE POWER SUPPLY SYSTEM
1 0 1 0 1 SECTION 0 PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Uninterruptible power supply (UPS) system. B. Related Sections include but are not necessarily limited to: 1. Owner s - Bidding
D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.
SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.
Model #: SMART2200CRMXL
Tripp Lite 1111 West 35th Street Chicago, IL 60609 USA Telephone: +(773) 869 1234 E-mail: [email protected] Model #: SMART2200CRMXL SmartPro Compact Rackmount UPS System - Precision Protection for
SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial
SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial MODEL NUMBER: SMART1000RM1U Description Tripp Lite SMART1000RM1U 1000VA / 1kVA / 800 watt line interactive,
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial MODEL NUMBER: SMART750RM1U Highlights.75kVA / 750VA / 600W line interactive 1U rackmount UPS, Sine
TAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial
TAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial MODEL NUMBER: SM1000RM1UTAA Description Tripp Lite SM1000RM1UTAA 1000VA / 1kVA / 800 watt line
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P
Technical Data Industrial Tower Uninterruptible Power Supply Specifications Bulletin Numbers 1609-P Topic Page 1609-P Specifications 2 1609-P Approximate Dimensions and Shipping Weights 3 Additional Resources
SmartPro 100/110/120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMP, Webcard, USB, DB9 Serial
SmartPro 100/110/120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMP, Webcard, USB, DB9 Serial MODEL NUMBER: SMART1500SLT Highlights 1.5kVA / 1500VA line interactive tower UPS; Sine wave output
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial MODEL NUMBER: SMART750RM1U Highlights.75kVA / 750VA / 600W line interactive 1U rackmount UPS,
SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications
SmartOnline Expandable Rack / Tower UPS System Online, double-conversion protection for mission critical applications Model #: SU3000RTXL3U 3000VA online 3U rack / tower UPS Enhanced serial communications
Smart-UPS 120 V. Advanced line interactive power protection for servers and network equipment. The world s most popular network and server UPS
Smart-UPS Advanced line interactive power protection for servers and network equipment The world s most popular network and server UPS The award-winning Smart-UPS unit from APC by Schneider Electric is
Back-UPS Pro 1300/1500 Installation and Operation
Back-UPS Pro 1300/1500 Installation and Operation Inventory Safety Do not install the Back-UPS in direct sunlight, in excessive heat, humidity, or in contact with fluids. Connect the battery bu059a bu058a
TOSHIBA G9000 80/100/160/225 kva
CORPORATE OFFICE 13131 WEST LITTLE YORK ROAD HOUSTON, TX 77041 PHONE: (713) 466-0277 (800) 231-1412 FACSIMILE: (713) 896-5226 TOSHIBA G9000 80/100/160/225 kva GUIDE SPECIFICATION THREE PHASE UNINTERRUPTIBLE
SmartPro 230V 750VA 500W Line-Interactive Sine Wave UPS, SNMP, Webcard, Tower, USB, DB9 Serial
SmartPro 230V 750VA 500W Line-Interactive Sine Wave UPS, SNMP, Webcard, Tower, USB, DB9 Serial MODEL NUMBER: SMX750SLT Highlights 750VA line interactive tower UPS; Sine wave output 220/230/240V nominal
APC. DIN Rail Control Panel Mounting Uninterruptible Power Supply. Catalog
APC DIN Rail Control Panel Mounting Uninterruptible Power Supply Catalog 2014 Contents Introduction, description... 4 Specifications...5 References....6 Dimensions...7 Wiring diagrams....8 Product reference
Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS
+ Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS Inventory Safety and General Information bu001c This unit is intended for indoor use only. Do not operate this unit in direct sunlight,
30-120 3 Phase Modular Finally the benefits of Modular ups are for all
MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion
TECHNICAL SPECIFICATIONS FOR 1.5 KVA ONLINE UPS
Capacity Technology Inverter Technology Noise Level Operating Temperature Humidity Harmonic Distortion Total DC bus voltage Battery recharge time (After Complete discharge) to 100% charge Crest Factor
Back-UPS 650 VA 120 V with AVR (BX650CI-LM)
Back-UPS 650 VA 120 V with AVR (BX650CI-LM) Overview Do not install the unit in direct sunlight, in areas of excessive heat or humidity, or in contact with fluids ON/OFF button Battery connector Circuit
Specification Requirements DBL 700MX and 1000MX Series UPS
Specification Requirements DBL 700MX and 1000MX Series UPS Theory of Operation Upon loss of utility power, the UPS inverter shall continue to provide seamless pure sine-wave AC from the batteries without
Single Phase, (3 to 20KVA) & (3 to 15 KW) Harsh Environment Outdoor Application NEMA 3R Cabinet
TECHNICAL SPECIFICATIONS for Single Phase, (3 to 20KVA) & (3 to 15 KW) Harsh Environment Outdoor Application NEMA 3R Cabinet Harsh Environment UPS (HE-UPS) 10/06/05 1. SCOPE A. The UPS shall be a solid-state
Audio/Video AVR Series UPS - Intelligent Automatic Voltage Regulated Power Management System
Audio/Video AVR Series UPS - Intelligent Automatic Voltage Regulated Power Management System MODEL NUMBER: HTR05-1U Description Tripp Lite's HTR05-1U AVR Series intelligent, Automatic Voltage Regulated
Liebert GXT3 Reliable On-Line UPS Protection In A Compact 2U Package 700VA -3000VA
Liebert GXT3 Reliable On-Line UPS Protection In A Compact 2U Package 700VA -3000VA Liebert GXT3 is a full feature UPS providing reliable protection for IT network equipment and data centers. It is a true
Multi DIALOG MDM/MDT. MDM 10-20kVA single/single-phase and three/single-phase MDT 10-80kVA three/three-phase NETWORK RANGE
Local Area Networks (LAN) Servers Data centers Internet centers (ISP/ASP/POP) Industrial PLCs EPOS (Electronic Point of Sale) Systems Emergency devices (lights/alarms) Electro-medical devices Telecommunication
User Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply
User Manual English APC Smart-UPS SC 1000/1500 VA 110/120/230 Vac 2U Tower/Rack-Mount Uninterruptible Power Supply 990-1851C, 10/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed
APC by Schneider Electric MGE GALAXY 3500 Uninterruptible Power Supply Guide Specifications 10 kva to 40 kva 3 400 in / 400-230 V Solution
APC by Schneider Electric MGE GALAXY 3500 Uninterruptible Power Supply Guide Specifications 10 kva to 40 kva 3 400 in / 400-230 V Solution THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION
Always On UPS Systems Inc., #100-150 Campion Road, Kelowna, BC Canada V1X 7S8
Door Mount UPS (Patent Pending) Shelf Mount UPS (Patent Pending) DESCRIPTION: The Always On NDM (door mount) and NSM (shelf mount) Series UPS s are dual conversion online UPS systems provided in slim,
UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES
UNINTERRUPTIBLE POWER SUPPLIES 9900A >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES 9900A The 9900A UPS system uses the most advanced IGBT in both the converter and inverter with Digital Signal Processor (DSP)
User Manual. English. APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC. Tower Uninterruptible Power Supply
User Manual English APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC Tower Uninterruptible Power Supply 990-1587A 12/2005 Introduction The APC Uninterruptible Power Supply (UPS) is designed to prevent
UPS UNINTERRUPTIBLE POWER SUPPLY GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES
UNINTERRUPTIBLE POWER SUPPLY GLOBAL SPECIALIST IN ELECTRICAL AND DIGITAL BUILDING INFRASTRUCTURES INDEX General characteristics page 4 Modular page 12 Conventional page 32 Line-interactive page 44 Communication
on-line LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTERS internet centers (isp/asp/pop) industrial plcs industrial applications
ZP110 on-line UPS 1, 2, 3, 6, 10kVA single/single phase LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTERS internet centers (isp/asp/pop) industrial plcs Emergency Devices (Lights/Alarms) Electro-Medical Devices
Installation Guide Smart-UPS X Tower/Rack-Mount 2U 2000/2200/3000 VA
Installation Guide Smart-UPS X Tower/Rack-Mount 2U 2000/2200/3000 VA Important Safety Messages Read the instructions carefully to become familiar with the equipment before trying to install, operate, service
Tender Technical Specification. For Three phase UPS, on line double conversion (VFI) 30 kva 30 kw
Tender Technical Specification For Three phase UPS, on line double conversion (VFI) 30 kva 30 kw 1 di 14 Index 1 GENERAL REQUIREMENTS... 4 1.1 SUBJECT AND AGREEMENT TYPE... 4 1.2 CONDITIONS... 4 2 GENERALI
RIELLO ELETTRONICA. Master HP
RIELLO ELETTRONICA Master HP LOCAL AREA NETWORKS (LAN) SERVERS DATA CENTRES TELECOM- MUNICATIONS DEVICES E-BUSINESS (Servers Farms, ISP/ASP/POP) INDUSTRIAL PROCESSES INDUSTRIAL PLCS ELECTRO- MEDICAL DEVICES
OmniVS Series 1500VA Line-Interactive Tower 120V UPS with USB port
OmniVS Series 1500VA Line-Interactive Tower 120V UPS with USB port MODEL NUMBER: OMNIVS1500 Highlights 1500VA / 1.5kVA tower 120V line-interactive UPS Corrects brownouts and overvoltages from 75 to 147V
Model #: SMART2200VS. 2200VA / 2.2kVA line interactive tower UPS. Maintains 120V nominal output over an input range of 79 to 147V
SmartPro VS Tower UPS System Intelligent, line-interactive power management system Model #: SMART2200VS 2200VA / 2.2kVA line interactive tower UPS Maintains 120V nominal output over an input range of 79
For protection from laptops to high availability facilities - and everything in between - APC is a partner you can count on
Home Sign In View Cart Order Status Search Solutions Products and Services Support Your Business Company Data Center Server Rooms Solutions for Small-Medium Data Center Large Data Centers Cloud & Co-location
Match. GE Digital Energy. Uninterruptible Power Supply 500-1500 VA. Technology for the Digital World. Match UPS. GE Digital Energy.
Match Uninterruptible Power Supply 500-1500 VA Manufactured by: General Electric Company Telephone +41 (0)91 / 850 51 51 CH 6595 Riazzino (Locarno) Fax +41 (0)91 / 850 51 44 Switzerland Website www.gedigitalenergy.com
Schneider Electric GALAXY VM Data Center Grade Three Phase Uninterruptible Power Supply Guide Specifications 160-200 kva UPS
Schneider Electric GALAXY VM Data Center Grade Three Phase Uninterruptible Power Supply Guide Specifications 160-200 kva UPS THIS GUIDE SPECIFICATION IS WRITTEN IN ACCORDANCE WITH THE CONSTRUCTION SPECIFICATIONS
PC Personal 120V 600VA 375W Standby UPS with Pure Sine Wave Output, Tower, 6 Outlets
PC Personal 120V 600VA 375W Standby UPS with Pure Sine Wave Output, Tower, 6 Outlets MODEL NUMBER: BC600SINE Highlights 600VA tower 120V standby UPS with SINE WAVE output Maintains AC output during power
Smart Pro Rack/Tower UPS Intelligent, line interactive network power management system
Smart Pro Rack/Tower UPS Intelligent, line interactive network power management system Model #: SMART500RT1U 500VA line interactive 1U rack/tower UPS 7 outlets with 1 switchable load bank Simultaneous
3U, 2200 VA Audio/Video Pure Sine Wave UPS System
3U, 2200 VA Audio/Video Pure Sine Wave UPS System MODEL NUMBER: HTR22-3U Description Tripp Lite's HTR22-3U Pure Sine Wave 2200VA/1600W on-line, double-conversion UPS system prevents media data loss, equipment
Installation and Operation
Installation and Operation Smart-UPS ΤΜ SR1 Uninterruptible Power Supply SR18KXIET SR110KXIET 220/230/240 Vac Tower suo0759b Smart-UPS TM SR1 Uninterruptible Power Supply 8000/10000 VA 220/230/240 Vac
Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications
W H I T E P A P E R Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications Executive Summary One of the fundamental decisions in the design of data centers, server rooms
Installation and Operation Back-UPS 1250, 1300, 1500
Installation and Operation Back-UPS 1250, 1300, 1500 Inventory bu001a Safety and General Information This unit is intended for indoor use only. Do not operate this unit in direct sunlight, in contact with
User Manual. English. APC Smart-UPS RT. 8000/10000 VA 200-240 Vac Tower/Rack-Mount 6U Uninterruptible Power Supply
User Manual English APC Smart-UPS RT 8000/10000 VA 200-240 Vac Tower/Rack-Mount 6U Uninterruptible Power Supply 990-2689D 01/2007 Introduction The APC Smart-UPS RT is a high-performance, uninterruptible
MAJORSINE Power Inverter
MAJORSINE Power Inverter Product Features: 24, 48, 130 V 1 KVA/800 Watts Output 2 KVA/1600 Watts Output 100-120 VAC Range 208-240 VAC Range Standard 19 /23, Pure Sine Wave Output High Low EMI/RFI Emissions
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
4.0 UPS dedicated to ICT for unmatched energy savings
4.0 UPS dedicated to ICT for unmatched energy savings Introducing UPSaver by Borri, a new modular UPS series for the ICT industry, totally configurable, quickly scalable, with high efficiency and low TCO.
LIBRA USV-Anlagen von EBT (10-800KVA) LIBRA pro. UPS 10-100 kva three-phase / single-phase 10-800 kva three-phase / three-phase.
LIBRA USV-Anlagen von EBT (10-800KVA) LIBRA pro online UPS 10-100 kva three-phase / single-phase 10-800 kva three-phase / three-phase LOCAL AREA NETWORKS (LAN) INTERNET CENTERS (ISP/ASP/POP) ELECTRO-MEDICAL
UNINTERRUPTIBLE POWER SUPPLY (UPS)
Your Inspirations. Our Innovations. UNINTERRUPTIBLE POWER SUPPLY (UPS) Protecting Your Data CATALOGUE Revision 0 Table of Contents Table of Contents About Us - Company Profile Online UPS Professional
User Manual. English. APC Smart-UPS. 2200 VA 120/230 Vac. 3000 VA 100/120/208/230 Vac. 2U Rack Mount Uninterruptible Power Supply
User Manual English APC Smart-UPS 2200 VA 120/230 Vac 3000 VA 100/120/208/230 Vac 2U Rack Mount Uninterruptible Power Supply 990-1352A 11/2003 Introduction The APC Uninterruptible Power Supply (UPS) is
USER MANUAL Online UPS 1K/2K/3K
USER MANUAL EN Online UPS 1K/2K/3K Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning 2 1.1. Transportation 2 1.2. Preparation 2 1.3. Installation 2 1.4. Operation 2 1.5.
Symmetra LX. Operations Guide
Symmetra LX Operations Guide For use with Symmetra LX UPS Models: 200 V, 4 8 kva 208/240 V, 4 8 kva 220/230/240 V, 4 8 kva 200 V, 4 16 kva 208/240 V, 4 16 kva 220/230/240 V, 4 16 kva Symmetra LX Rack-mount
IBM 11000VA LCD 5U Rack Uninterruptible Power Supply IBM System x at-a-glance guide
IBM 11000VA LCD 5U Rack Uninterruptible Power Supply IBM System x at-a-glance guide The IBM 11000VA LCD 5U Rack uninterruptible power supply (UPS) optimizes for both efficiency and performance, providing
User Manual. Smart-UPS TM C. Uninterruptible Power Supply SRC250 SRC450. 110/120/230 Vac. Tower/Rack-Mount 1U
User Manual Smart-UPS TM C Uninterruptible Power Supply SRC250 SRC450 110/120/230 Vac Tower/Rack-Mount 1U Smart-UPS TM C Uninterruptible Power Supply 250/450 VA 110/120/230 Vac Tower/Rack-Mount 1U English
User Manual 1K/2K/3K Online UPS
User Manual 1K/2K/3K Online UPS Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning... 1 1-1. Transportation... 1 1-2. Preparation... 1 1-3. Installation... 1 1-4. Operation...
APC Smart-UPS 2400/3000 VA 100/110-120 VAC 3U. Uninterruptible Power Supply
User Manual English APC Smart-UPS 2400/3000 VA 100/110-120 VAC 3U Tower/Rack Mount Uninterruptible Power Supply 990-2233A 02/2005 Introduction/Before Installation Introduction/Before Installation About
USER MANUAL Online UPS 1K/2K/3K Rack
USER MANUAL EN Online UPS 1K/2K/3K Rack Uninterruptible Power Supply System Table of Contents 1. Important Safety Warning 2 1-1. Transportation 2 1-2. Preparation 2 1-3. Installation 2 1-4. Operation 2
Galaxy 7000: Unitary Specification guide: Single UPS, three-phase, 160 to 500 kva
Galaxy 7000: Unitary Specification guide: Single UPS, three-phase, 160 to 500 kva 1. UPS definition... 2 1.1. Purpose... 2 1.2. Brief description... 2 2. Operating principles... 2 2.1. Normal operation...
Specification CyberWave UPS Ver 1.05 02/01/00
GUIDEFORM SPECIFICATION FOR CyberWave UPS Systems 10-112 kva SINGLE-PHASE OUTPUT The attached specification is intended for use by consulting engineers to provide bidding specifications for products with
750VA/1000VA/1500VA 100/120/230VAC 2U
User s Manual English Smart-UPS 750VA/1000VA/1500VA 100/120/230VAC 2U Rack Mount Uninterruptible Power Supply 990-1194 5/02 Introduction The APC Uninterruptible Power Supply (UPS) is designed to prevent
Power Quality. Uninterruptible Power Supply
Quality Uninterruptible Supply In the electrical system environment, power disturbances will occur. These can be caused by faults on the distribution system, the operation of nearby equipment, lightning
User Manual. Smart-UPS. Uninterruptible Power Supply 750/1000/1500 VA. 100/120/230 Vac. Rack Mount 2U
User Manual Smart-UPS Uninterruptible Power Supply 750/1000/1500 VA 100/120/230 Vac Rack Mount 2U Smart-UPS TM Uninterruptible Power Supply 750/1000/1500 VA 100/120/230 Vac Rack-Mount 2U EN 990-1194E 08/2014
Specification guide no. 9 Active harmonic conditioner from 20 to 480 A
Active harmonic conditioner from 20 to 480 A Contents 1 - Installations concerned... 2 1.1 - New installations... 2 1.2 - Existing installations... 2 2 - General... 2 2.1 - Scope... 2 2.2 - Applicable
EATS16 EATS16N. Installation and user manual ENGLISH. Copyright 2015 EATON All rights reserved.
ENGLISH EATS6 EATS6N Installation and user manual Copyright 05 EATON All rights reserved. Service and suppt: Call your local service representative SAFETY INSTRUCTIONS SAVE THESE INSTRUCTIONS. This manual
User Manual. English. APC Smart-UPS 1000/1500 VA 100/120/230 VAC 750/1000XL VA 120/230 VAC. Tower Uninterruptible Power Supply
User Manual English APC Smart-UPS 1000/1500 VA 100/120/230 VAC 750/1000XL VA 120/230 VAC Tower Uninterruptible Power Supply 990-1074C 06/2012 Introduction American Power Conversion Corporation (APC) is
Eaton UPS 9355 20-30kVA. Energía. 20 kva/18 kw and 30 kva/27 kw 0.9 power factor. True double-conversion online UPS.
Eaton UPS 9355 20-30kVA Energía Rating 20 kva/18 kw and 30 kva/27 kw 0.9 power factor Topología True double-conversion online UPS Entrada eléctrica Nominal input voltage 208V/120V, 220V/127V+15, -20% 480V/277V,
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
User s Manual Before using the inverter, you need to read and save the safety instructions.
User s Manual Before using the inverter, you need to read and save the safety instructions. STI SERIES (STI200, STI300, STI500, STI700, STI1000) Power Frequency Pure Sine Wave Inverter The information
Series 7400 M (10/20/30/40/60 kva) Maximum Protection For Mission Critical Network Applications. Series 7400 M
Power Protection for Business Critical Continuity Series 7400 M (10/20/30/40/60 kva) Maximum Protection For Mission Critical Network Applications Compact Three-phase UPS with Optimum Load Performance And
Assembled in Florida, USA.
*some models Assembled in Florida, USA. Check our online UPS section at: www.olinsys.com/ups Descubra nuestra sección online de UPS en: www.olinsys.com/ups UPS Uninterruptible Power Supply / Alimentación
Eaton 93PM UPS Where aesthetics meet intelligence.
Brochure 100 kw Eaton 93PM UPS Where aesthetics meet intelligence. 93PM features and benefits The Eaton 93PM UPS combines unprecedented and reliability with eye-catching design. A space-saving, flexible