EVALUATION OF FAULT ANALYSIS IN TRANSMISSION LINES USING RELAY SETTINGS



Similar documents
TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v Spring web.itu.edu.tr/yumakk. Distance Protection

Prepared By: Sheilani Binti Shaari Department of Electrical Engineering/PKB

DISTRIBUTION TRANSFORMER OVERLOAD PROTECTION TRIPPING CIRCUIT

Three phase circuits

Numerical Differential Protection

Protection and Substation Automation. Training Programmes

Circulating Current Relay. Type IRXm

Current and voltage measuring relays

Pilot-wire differential relay for lines with two or more terminals

Transmissão em Corrente Contínua

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

PRE COMMISSIONING TESTS ON EQUIPMENT AT 33/11 KV SUB STATIONS

Disturbance Recoder SPCR 8C27. Product Guide

The following table shows approximate percentage wise the

NC-12 Modbus Application

Equipment: Power Supply, DAI, Variable resistance (8311), Variable inductance (8321)

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

Radial Distribution Test Feeders

Electron S.R.L. A29 ELECTRICAL POWER SYSTEM TRAINERS. Production Transmission Distribution

Remote Monitoring and REC 501 Control Unit Product Guide

Voltage Regulator SPAU 341 C. Product Guide

T Substation Maintenance and Commissioning Test Equipment

Study on Differential Protection of Transmission Line Using Wireless Communication

TDMS Test & Data Management Software

TECHNICAL DESCRIPTION OF THE DISTRIBUTION SUBSTATION REMOTE MONITORING SYSTEM

For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V V V (at 50 Hz)

Electric utilities may vary in their application of end-to-end testing

Test & Data Management Software

Transmission Protection Overview

ends of transmission line are used for relay operation [70]. Another type of

Physical Address: City: State: Zip Code:

APPLICATION CASE OF THE END-TO-END RELAY TESTING USING GPS-SYNCHRONIZED SECONDARY INJECTION IN COMMUNICATION BASED PROTECTION SCHEMES

Generator Differential Relay Electrical Apparatus

The electrical energy produced at the gen

FREJA Win Software for FREJA relay testing system

AUTOMATIC NIGHT LAMP WITH MORNING ALARM USING MICROPROCESSOR

PROGRAM CRITERIA FOR ELECTRICAL ENGINEERING TECHNOLOGY

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

Earth Fault Detection Basics in Theory

CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE

Trip circuit supervision relay. Type RXTCS

Chapter 2 Logic Gates and Introduction to Computer Architecture

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

ANCILLARY EQUIPMENT AND ELECTRICAL EQUIPMENT Power Supply Systems and Electrical Equipment for Desalination Plants - Y.M. Hamud and A.H.

Teleprotection Schemes and Equipment. James W. Ebrecht Young Power Equipment Scottsdale, AZ

The Application and Benefits of Multi-phase Auto-reclosing

Requirements for Offshore Grid Connections. in the. Grid of TenneT TSO GmbH

INSTRUMENTATION AND CONTROL TUTORIAL 3 SIGNAL PROCESSORS AND RECEIVERS

Basic Electrical Technology Dr. L. Umanand Department of Electrical Engineering Indian Institute of Science, Bangalore. Lecture phase System 4

Equipment: Power Supply, DAI, Transformer (8341), Variable resistance (8311), Variable inductance (8321), Variable capacitance (8331)

Relion. Power system protection and automation reference Extending substation life cycle with IEC 61850

FREJA 300 Relay Testing System

Electrical Considerations for HVDC Transmission Lines. Joe Mooney, PE

Both variants can be used for measuring the positive sequence voltage Up or the negative sequence voltage Un.

Power Monitoring for Modern Data Centers

Impulse G+/VG+ Series 3, 24 VDC Interface Card Terminal Designations

Occupational Profile: Electrical & Electronics Engineering Technician

2. A conductor of length 2m moves at 4m/s at 30 to a uniform magnetic field of 0.1T. Which one of the following gives the e.m.f. generated?

BASIC ELECTRONICS AC CIRCUIT ANALYSIS. December 2011

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Single and Three Phase Transformer Testing Using Static Motor Circuit Analysis Techniques

VOLTAGE REGULATOR AND PARALLEL OPERATION

LAB1 INTRODUCTION TO PSS/E EE 461 Power Systems Colorado State University

Instruction Manual Service Program ULTRA-PROG-IR

Measurement of Power in single and 3-Phase Circuits. by : N.K.Bhati

Power measurement in balanced 3 phase circuits and power factor improvement. 1 Power in Single Phase Circuits. Experiment no 1

... Electronic Softstarter...

GPS Interfacing of Banediya Feeder (M.P) Using MI Power Software

Capacitor Protection Relay SPAJ 160 C. Product Guide

Hyperlinks are Inactive

E&I MAINTENANCE ENTRY TEST ENABLING OBJECTIVES. DESCRIBE hazards and precautions taken to avoid injury in the workplace.

Power Electronics. Prof. K. Gopakumar. Centre for Electronics Design and Technology. Indian Institute of Science, Bangalore.

CAPACITOR BANK TESTING SWP

OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS

Date Rev. Details Author

Cahier technique no. 196

Higher National Unit Specification. General information for centres. Transmission of Measurement Signals. Unit code: DX4T 35

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

Substation Automation Products Relion 670/650 series IEC and ANSI Hardware

An overview of Computerised Numeric Control (C.N.C.) and Programmable Logic Control (P.L.C.) in machine automation

Permissible ambient temperature Operation Storage, transport

Network Theory Question Bank

Step Voltage Regulators

DRIVING LOOOONG CABLES

TECHNICAL BRIEF. Commercial PV in Australia and New Zealand Using the Enphase Microinverter System

Arc Protection Relay REA 101. Operator s Manual

GLOLAB Two Wire Stepper Motor Positioner

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

EEL303: Power Engineering I - Tutorial 4

PHYSICS 111 LABORATORY Experiment #3 Current, Voltage and Resistance in Series and Parallel Circuits

Design of Strong-motion Monitoring System for Dam-reservoir D s e i s gn of Stro r ng-mo m tion Monito t ri r ng Syst s em

Unified requirements for systems with voltages above 1 kv up to 15 kv

TURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

MINISTERIE VAN ECONOMISCHE ZAKEN GENERAL COST COMPARISON BETWEEN UNDERGROUND CABLES AND O.H. LINE SYSTEMS FOR H.V. TRANSMISSION

Engineering innovation

Unit/Standard Number. High School Graduation Years 2010, 2011 and 2012

Transcription:

EVALUATION OF FAULT ANALYSIS IN TRANSMISSION LINES USING RELAY SETTINGS N.VIJAYSIMHA 1*, CH.CHENGAIAH 2 1* M-TECH (PSOC), Department of Electrical and Electronics Engineering, Sri Venkateshwara University college of Engineering-Tirupati-7502-INDIA. 2 Associate Professor, Department of Electrical and Electronics Engineering, Sri Venkateshwara University college of Engineering-Tirupati-7502-INDIA. ABSTRACT This paper reports on the analysis of EHT (Extra High Tension) transmission line protection using distance relay settings of TYPE: RAZOA and TYPE: REL-100 (MAKE: ABB COMPANY). The calculations of relay settings for the distance schemes have also been performed, using MATLAB program. Keywords: Power system; Relay setting; RAZOA; REL-100; Matlab. (1) INTRODUCTION: There is a rapid development in the field of electrical power systems, in which large amount of interconnection involved for consuming continuity of supply good voltage regulation. Generation, Transmission and Distribution are three main stages in power system. Among these the performance and maintenance of transmission play an important role in the field of power system. Analysis of fault is very pivotal for the stable operation power system. The cause of the faults makes damage to power systems, due to not properly protected using relay settings. Faults on the power system can be analyzed using required relay settings. To meet this requirement a high speed protection system is required for 132 KV and above level which can be achieved by using RAZOA and REL-100 protection schemes. The RAZOA distance has been taken for line protection and REL-100 a non-switched distance schemes is taken for protecting line. The main focus of this paper is to calculate relay settings for these distance schemes. (2) Operating Principle of Protecting Relays Schemes: 2.1 Operating principle of RAZOA Relay: The operating principle of RAZOA relays is a voltage retained over current relay. It is basically switched scheme three-phase distance relay with three directional zones and contain microprocessor based three under impedance starter and one measuring unit as shown in Fig Fig 1 Block diagram of RAZOA Relay 126

This is a static type Electronic relay. An input supply of 220 V DC is being given to electronic relay as auxiliary supply. This 220 V DC will be stepped down to 12V, because all electronic cards present in this relay work for 12 V DC supply only. 18 terminals present in this relay for inputs and operation of relay shown in Fig 1 and terminals used in RAZOA relays are explained in APPENDIX-1. The RAZOA relay is tested at 220 KV level substation by ZFB kit.from these test the performance of relays have been analyzed. The procedure of analyzing the performance of relay is at first theoretical values are calculated with help of replica impendence and then relay is tested with ZFB kit. The values are taken for phase-neutral, phasephase of three zones. The actual values should be ±10% to the theoretical values. The theoretical values and actual values are shown in APPENDIX-2 Fig 2 Line diagram of 220 KVSubStationA- 220 KVSubStationB Fig 2 shows the arrangement of RAZOA relay in the line diagram. The relays are placed at sending end and receiving end of the feeders. The sending end is at substation A and receiving end is at substation B.The relay setting are calculated for the RAZOA relay at 220 KV substation A and the relay available on this feeders are RAZOA ( MAKE: ABB COMPANY). From the Fig 2, There are two 220 KV lines emanating from substation A (Feeder 1 & Feeder 2) to substation B. These feeders will feed 220 KV load to substation B. At the 220 KV substation B another two 220 KV feeders (Feeder 3 & Feeder 4) which feed 220 KV load to substation C and substation D.Another two 100 MVA 220/132 KV transformers are also connected to substation B.The following impedances are to be calculated for the RAZOA relay settings. 1. Impedance of the protected line i.e. 220 KV transmission lines of substation A and substation B (Feeder 1 & Feeder 2). 2. Impedance of Feeder 3 3. Impedance of Feeder 4 4. Impedance of Transformers For calculating Relay setting for any distance scheme we need the following data. 1. Conductor used 2. Voltage levels 3. Current to be carried. 4. Line length 5. Shortest data line connected to the protected line 6.longest data line connected to the protected line 7.Transformer data which is connected to line Operating Characteristic of the RAZOA relay: The directional measuring unit have quadrilateral characteristic with independent settings in resistive and reactive directions. Which have resistance (R) and reactance (X) 127

can be set independently. R-X diagram is shown in Fig 3.The impedances can be made to operate with a circle or oval characteristic with a selectable switch present in RAZOA relay. The setting range is from 0.16 to 64 Ohms. Fig 3 shows the operating characteristic of RAZOA relay We use oval characteristics for long transmission lines and circular characteristics for short, medium transmission lines. If we set relay in the short transmission lines, the resistances values are kept more to avoid reactance effect.if we set relay in the long transmission lines, the reactance values are kept more to avoid power swing problems. So, there is possibility of changing the characteristic in RAZOA relays. 2.2 Operating principle of REL-100 Relay: The different types of faults in impendence zones can be analyzed using protection terminal in REL-100 relay.the relay includes three forward and one reverse impedance zone, measuring technique used in REL-100 is based on signal processors which operate with numerical signal derived from the analogue to digital converter (A/D) shown in Fig 4. Fig 4 Block diagram of REL 100 Relay Eight scheme communication logic is included in the basic version together with current reversal logic. These are selectable independently of one another during setting procedure. Four groups setting parameter are available in REL-100.They are completely independent of one another. The self supervision function is performed continuously and includes as fallows: -normal microprocessor watch-dog function -checking of digitized measuring signals -checksum verification of PROM contents -checksum verification on all signal communications -Read-write read write cycling of memory cells and internal registers. Transformer unit present in REL 100 consists of a total of ten analogue input quantities. All measuring currents enter the transformer unit via plugs and sockets. The line protection is automatically short circuited when the transformer unit withdrawn its input quantities. In A/D converter unit all of the analogue signals are filtered in analogue 128

antailiasing low pass filters before entering the multiplexer and analogue to digital converter. A separate signal processor in the analogue to digital converter unit performs digital low pass filtering. The total bandwidth of the filtering signal is suitable for protection purpose; these information signals are converted parallel to serial mode and transmitted to measuring unit. The measuring unit consists of 32-bit microcontroller and three signal processor which decode or change the encoded serial information into parallel information. The impendence measuring function performed by three basic signal processors which calculate the impendence for different fault zones. The 32-bit microcontroller collects all the information from the different signal processors, analogue to digital converters and the input signaling circuits as well as performing different logical functions, built into REL-100 line protection terminals. It also controls output unit as well as three communication ports. The communication ports are MMC unit (Man Machine Communication), SMS (Substation Monitoring System), SCS (Substation Control System). The REL-100 relay is tested at 220KV level substation by TURH kit.from these testing the performance of relays have been analyzed. The reached values of reactive and resistive values have been taken from the testing of REL-100 relay. At first theoretical values are calculated with help of these values and then relay is tested with TURH kit. The actual values are taken for phase-neutral, phasephase of three zones. The actual values should be ±10% to the theoretical values. The theoretical values and actual values of resistive and reactive reaches values are plotted in APPENDIX-3 and APPENDIX-4. Fig 5 Line diagram of 220 KVSubstation A- 220 KV Substation B Fig 5 shows the arrangement of REL-100 relay in the line diagram. The relays are placed at starting and ending of the feeders. The sending end is at Substation A and receiving end is at Substation B.The relay settings calculated for the REL-100 relay at 220 KV substations A. The relay available on this feeders are REL - 100 (MAKE: ABB COMPANY).Only one 220 KV line is emanating from Substation A (Feeder 1) to Substation B.This feeder will feed 220KV load to substation B.At the Substation B there are two 220 KV feeders (i.e. feeder 2 and feeder 3) which feed 132 KV load to substation C and substation 3. Another two 100 MVA 220/132 KV transformers are also connected to substation B. The following impedance are to be calculated for the REL-100 relay settings. 1. Impendence of the protected line i.e. 220 KV transmission line of substation A and substation B (Feeder1). 2. Impendence of Feeder 2 3. Impendence of Feeder 3 129

4. Impendence of Transformers Operating Characteristic of the REL 100 Relay: It is a numerical relay with quadrilateral impedance units for phase and earth faults. Each measuring unit has individual and independent setting in resistive (R) and reactive(x) directions. Entire Zone-3 REACH i.e. zone 3R (in forward direction) which is available in reverse direction with a separate timer T 3R. R-X diagram is as indicated in Fig 6 Fig 6 shows operating characteristics of REL-100 relay Four groups of setting parameters are possible to suit different system conditions. Only one of the groups will be in service by choice. It is a continuous self monitoring of resistance and reactive values, self testing. Which indicate the same by using Relay Available LED (Light Emitting Device) on the relay. By using MMC (Man-Machine Communication), we can edit the relay settings, and read the values of line voltage, current, real, reactive power and frequency. The Setting ranges are from 0.1 upto 150 Ohms and the Timers are from 0 upto 10 Secs. 4. SIMULATION AND RESULTS The RAZOA and REL -100 Relays have been simulated by using MATLAB program. Case (i) Input Data for calculating the relay settings of RAZOA: Parameters values Enter primary voltage 220000 Enter secondary voltage 110 Enter primary current 800 Enter secondary current 1 Enter line length in KMS 81.58 Enter shortest line length in KMS 26.75 Enter longest line length in KMS 75 Enter transformer-i percentage 8.44 impedance Enter transformer-ii percentage 8.44 impedance Enter Transformer-I MVA 100 Enter Transformer-II MVA 100 Enter frequency 50 Results of RAZOA relay for 220 KV: Conductor to be used is zebra (ACSR) Conductor size is 61/3.19 Operating characteristic is circular Resistive Reach : 29.966160 a) Line Reactance : 0.305602 b) Distance Steps : X1 : 10.431118 X2 : 15.176618 X3 : 18.169427 1. Adopted Voltage Ratio : 2000.000000 2. Adapted Current Ratio : 800.000000 3. Line Length : 81.580000 130

4. Line Constants per Phase per Circuit a) Positive Sequence Parameters in Ohms Rl : 6.256289, Xl : 32.597244 Zl : 33.19219 b) Zero Sequence Parameters in Ohms R0 : 22.737986 X0 : 109.200767 Z0 : 111.542922 c) Line Angle : 79.175652 d) Power Factor : 0.188487 5. Impendence Ratio : 2.500000 6. Secondary circuit data in Ohms 7. SETTINGS: a) 1.starter unit characteristic C = Circular Characteristic 2. Neutral Current Starter ins = 0.2 b) Measuring Unit 1. Current Factor Settings Inductive Reach a: 99.000000 Resistive Reach b: 29.966160 2. Voltage Factor Settings p1= 30.370666 p2= 20.874216 p3= 17.435883 c) Zero Seq. Compensation kn: 0.783333 d) Time Settings in seconds Zone-I Inst Zone-II 0.3 Zone-III 0.6 Zone-IV 1.2 Case (ii) Input Data for calculating the relay settings of REL-100: Parameters values Enter primary voltage 220000 Enter secondary voltage 110 Enter primary current 800 Enter secondary current 1 Enter line length in KMS 84.4 Enter shortest line length in KMS 40.6 Enter longest line length in KMS 92.3 Enter transformer-i percentage 8.44 impedance Enter transformer-ii percentage 8.44 impedance Enter Transformer-I MVA 100 Enter Transformer-II MVA 100 Enter frequency 50 Enter Fault Resistance at Earth 30 Faults/loop Enter Fault Resistance at two phase 1 faults/phase The MATLAB program is developed to calculate the relay setting of relays between one substation feeders to another substation feeder. Results of REL-100 relay upto 220KV Conductor to be used is zebra (ACSR) Conductor size is 61/3.19 1. Adopted Voltage Ratio : 2000.00 2. Adopted Current Ratio : 800.000 3. Line Length : 84.400000 4. Line Constants per Phase per Circuit a) Positive Sequence Parameters in Ohms Rl : 2.589021 Xl : 13.489617 Zl : 13.73582 131

b) Zero Sequence Parameters in Ohms R0 : 9.409591 X0 : 45.190217 Z0 : 46.159464 c) Line Angle : 79.175652 d) Power Factor : 0.188487 5. Impedance Ratio : 2.500000 6. Secondary circuit data in Ohms 7. SETTINGS: Resistive reaches for Phase faults R1 : 3.671217 R2 : 5.186595 R3 : 6.583198 Reactive reaches for Phase faults X1 : 10.791694 X2 : 18.687293 X3 : 25.964039 Resistive reaches for Earth faults RN1 : 15.898175 RN2 : 18.750223 RN3 : 21.378729 Reactive reaches for Earth faults X1 : 10.791694 X2 : 18.687293 X3 : 25.964039 Zero sequence compensation KN1 : 0.786839 KN2 : 0.786839 KN3 : 0.786839 Phase sector for Earth faults : 13.119746 Phase sector for Earth faults : 38.566039 Phase sector for Phase faults : 13.119746 Phase sector for Phase faults : 38.566039 e) Time Settings in seconds Zone-I Inst Zone-II 0.3 Zone-III 0.6 Zone-IV 1.2 The results of these two relays i.e. RAZOA and REL-100,it was observed that RAZOA relays are based on transmission line characteristic i.e.short, medium, long transmission lines but the REL-100 are numerical relays, which provides back-up protection for 220 KV EHT transmission lines and above voltage levels with advanced relays setting. 4. CONCLUSION: It could be concluded that the protection of EHT transmission lines and calculations of the corresponding relay settings have been presented. Both relays have been tested at 220 KV level substation.with the help of the line diagrams of the substations relays setting are calculated with required parameter. The relays setting for both have been successively calculated using the MATLAB program for 220 KV level.with help of this MATLAB program we can calculate relays setting for 220 KV and above voltage levels. By analysis and calculation on both relays i.e. RAZOA and REL-100, it is noticed REL- 100 was the most successful relay for the EHT transmission line protection in power system. REFERENCES : [1]. Power System Analysis John Grainger and William Stevenson, Mc Graw Hill publications [2]. Power System Analysis Hadi Saadet, TMH Edition 132

[3]. Power System Protection and Switchgear B.Ravindranath and M.Chander, New Age International (P) limited [4]. Art and Science of Protective Relaying C.R.Mason, Wiley Eastern limited [5]. Switchgear and Protection Sunil S Rao [6]. Electrical Power Systems C.L.Wadhawa [7]. Protective Relays Application Guide [8]. Technical Reference Book AP TRANSCO [9]. Company manual for Distance Protection Scheme (RAZOA) ABB, Bangalore [10]. Company manual for Distance Protection Scheme (REL 100) ABB, Bangalore 15 Spare terminal 16 Spare terminal 17 To Energize Tripping Relay 18 220V DC supply(-ve) APPENDIX-2 Phase Selected RN YN BN RY YB BR Z I Z II Z III T A T A T A 35 35 35 34 33 34 50 39 39 56 56 39 39 56 56 39 39 56 56 61 61 61 60 61 60 68 68 68 66 68 67 APPENDIX-1 Terminal Purpose No 1 220V DC supply (+ve) 2 Used for Annunciation purpose 3 R-ph current input terminal 4 R-ph current return path terminal 5 Y-ph current input terminal 6 Y-ph current return path terminal 7 B-ph current input terminal 8 B-ph current return path terminal 9 N-ph current input terminal 10 N-ph current return path terminal 11 R-ph PT supply terminal 12 Y-ph PT supply terminal 13 B-ph PT supply terminal 14 N-ph PT supply terminal Phas e APPENDIX-3 Z- 1 Z 2 Z-3 T A T A T A RN 3.179 2.986 3.566 3.5 3.966 YN 3.179 2.95 3.566 3.49 3.966 BN 3.179 2.985 3.566 3.472 3.966 RY 1.468 1.397 1.876 1.793 2.164 YB 1.468 1.41 1.876 1.765 2.164 3.87 2 3.93 2 3.69 9 2.08 9 2.13 2 BR 1.468 1.42 1.876 1.8 2.164 2.15 RYB 0.734 0.82 0.938 1.02 1.082 1.32 133

APPENDIX-4 Phase Z-1 Z 2 Z- 3 T A T A T A RN 3.854 3.795 5.76 5.73 7.09 6.92 YN 3.854 3.841 5.76 5.75 7.09 6.89 BN 3.854 3.85 5.76 5.75 7.09 6.92 RY 4.313 4.296 6.48 6.39 7.94 7.94 YB 4.313 4.296 6.45 6.38 7.94 7.92 BR 4.313 4.123 6.46 6.39 7.94 7.92 RYB 2.156 2.23 3.22 3.12 3.97 3.87 Note: Z=Zone T=Theoretical A=Actual 134