1 Transmissão em Corrente Contínua Panorama Atual e Perspectivas Futuras no Brasil
2 Multi-Terminal HVDC Classic Some Considerations Brazilian SC B4 Paulo Fischer de Toledo, ABB
3 Basic considerations Traditional 2-terminal control at converter level Many operation modes become possible (In 2-terminal case, only bipolar and monopolar) Somewhat larger dimensioning of main circuit Additional functions needed in the control
4 The technology is not new 1963 paper on tapping (Uno Lamm et al) 1978 analog simulator study (Göte Liss et al) 1989 Italy Sardinia adds tap in Corsica Québec New England. The first large scale multi-terminal transmission system Paralleling used in Inga-Shaba Itaipú Nelson River North East Agra. The newest large scale multi-terminal transmission system
5 The SACOI transmission - Italy Sardinia Corsica Italia By Ansaldo / GE and CGEE.Alsthom Supply to both islands Sardinia 300 MW Corsica 50 MW Mainland 300 MW
6 Québec New England (QNE) - Canada
7 Québec New England (QNE) Started as 2-terminal transmission (Des Cantons Comerford) Went on to 5-terminal (Radisson, Nicolet and Sandy Pond added) Went on to 3-terminal (The original stations were decommissioned) Technical Data: In operation: DC Voltage: +/- 450 kv DC Line: 1480 km Power Rating: Radisson 2250 MW; Nicolet 2138 MW; Sandy Point 1800 MW
8 North East Agra (India) Indian Power Systems
9 Multi-terminal HVDC classic, configurations Bipolar Multiterminal 12-pulse groups Hybrid Multiterminal Metallic Return 12-pulse groups
10 Tapping of HVDC
11 Québec New England (QNE) DC switching arrangement with switching type
12 Québec New England (QNE) DC switching arrangement with switching type High speed disconnect switches Combine the following functions High speed converter isolation DC line sectionalizing DC transfer switches Circuit breaker with full DC current commutating capability used for converter DC neutral side isolation For metallic return transfer For ground return transfer Motor operated disconnect switches used for Isolation Connecting the metallic return path Polarity reversal
13 Québec New England (QNE) DC switching arrangement Each configuration allows bipolar/monopolar operating modes with/without metallic return Multi-terminal configurations allows hybrid bipolar monopolar metallic return
14 Basic control principles The current margin control principle is used as for a conventional 2-terminal system One terminal must be appointed as Voltage Setting Terminal (VST) Characteristics below assume DC line resistance neglected Ud Ud Ud Ud Id Id Id Id Id
15 Basic control principles Voltage control All stations are in parallel Only one station is allowed to control the voltage (VST = Voltage Setting Terminal) The VST is normally a large inverter in a large ac system The Master Controller orders the voltage reference at the VST The Master Controller checks that all stations are within tolerances
16 Basic control principles Current control All stations are in parallel All stations but one (VST) can control their currents The VST is normally a large inverter in a large ac system The Master Controller orders the power references
17 Control: Some additional control functions for multi-terminal Current order balancing Voltage control (not really additional, but different) Stabilization/modulation control (not really additional, but different) Power order ramping coordination Post fault recovery & reconfiguration Possible faulted areas/components analysed before-hand, as well as the best post-fault configurations The Master Controller calculates best load flows and power orders The Master Controller suggests configuration(s) and power order(s) The Master Controller executes, if operator accepts suggestions
18 Master Control Simplified Block Diagram, Multi-Terminal Power Control
19 Master Control Some key functions part 1 Balancing the Power Order Sum of Power Orders to all involved rectifies is equal to the sum of the Power Orders to all involved inverters Weighting factors C1-C3 are set by operators
20 Master Control Some key functions part 2 Coordinate the power order ramping Load flow change may result the involvement from more than two converters ramping speed must be coordinated All stations that are designated to contributed with power must be ramped accordingly to reach the new power at the same time
21 Master Control Some key functions part 3 Current Order calculation Current order calculation is performed by dividing balanced power order by direct voltage Voltage measurement values are transmitted from converter stations to Master Control Voltage measurement is smoothed by long time-constant to avoid stability problems if converters are connected to weak AC system
22 Master Control Some key functions part 4 Compensation for DC line losses Due to losses in the DC line current order are unbalanced even if Power Orders are balanced The sum of current order with different signals (for rectifier or inverter operation) is added to one of Current Order (with suitable signal) and the losses will be compensated in that station
23 Master Control Some key functions part 5 Balancing taking maximum limitations into consideration Sum of current orders coming from all rectifiers must be equal to the sum of current fed into all inverters A current order balancing function is needed taking into account the maximum limitations for current orders By the weighting factors K1-K3 and the feedback loop, an unbalance in input Current Order is eliminated so that the output orders are balanced
24 Master Control Some key functions part 6 Coordination of Power Modulation Different projects require different Power Modulation Master Control can activate/deactivate specific modulating function with/without intervention of the operator Typical Modulating Functions: Frequency Control for generators (case of isolated system) Network stabilization for specific network conditions Damping Control in case of inter-area oscillations
25 Master Control Some key functions part 7 Voltage Control DC system voltage is determined by one converter station (VST Voltage Setting Terminal) VST station is the inverter with highest power and operating in local feedback voltage control mode. Master Control supervises the voltage profile of the DC system and may order a reduction of the voltage reference in the VST if voltage in any station tends to be too high
26 Master Control Some key functions part 8 Post fault recovery and re-configuration Loss of a converter or Line section the remaining parts of the affected pole can often still be operated current orders are then re-arranged to obtain balance values For loss of converter Current Order are rearranged by balancing function in accordance with the weighting factors K1-K3 Master Control can assist the operator in making a decision for a new configuration if is pre-programmed for such assignment
27 Master Control Telecommunication part 1 Telecommunication (Control and Protection) of a Multi-Terminal is more complex than a 2-terminal system All the stations must have a direct communication to the Master Control For reliability reasons the communication channels are duplicated
28 Master Control Telecommunication part 2 There are two different types of redundant telecommunication links The Master Telecommunication (MTCOM) transmits information such as: Current Order set-point Current Order limit Orders Status of Master Control and each converter on a per pole basis
29 Master Control Telecommunication part 3 Protective telecommunication (PTCOM) transmits protective orders from faulted converter directly to all other converters: Force retards Block signals Line protective inter-lockings
30 Master Control Telecommunication part 4 Current Order Synchronization New current order (ramping, limitations, modulations) are synchronized to prevent loss of current margin Synchronization consists of transmission of current orders with checkback for security Synchronization logic differs for current order increase or decrease to avoid reduction in the current margin Trip of converter new current order are transmitted without synchronization during isolation time for maximum speed
31 Master Control Telecommunication failure (Local Control) part 1 Absence of communication Back-up controls are activated locally Back-up controls allows: Starting of converter Stopping of converter Power change Frequency Control modulation Re-allocation of power following forced outage However Operator flexibility is reduced Slow recovery from certain system faults (typically DC line faults)
32 Master Control Telecommunication failure (Local Control) part 2 Current Order Memory Normal operation Current Order Memory fallows thr master current order During telecommunication failure the current Order Memory is in effect and can be changed by the operator Frequency control modulation is allowed to operate but has to preserve the current margin Current order in the VST tracks the current response except during disturbances like faults or mode shifts
33 Master Control Telecommunication failure (Local Control) part 3 Decentralized Dynamic Voltage Controlled Recovery (DDVCR) Purpose: Case of converter trip without MTCOM Avoid possible overload Preserve the Current Margin Ensure an active VST
34 Conclusions Multi-terminal configurations in HVDC are not new The technology exists and has been time tested The main circuit equipment can become marginally more expensive The control becomes, internally, more complex, but the operator gets more help from the control system.
35 Multi-terminal Challenges: Economical HVDC lines are less expensive than AC, This pays for terminals being more expensive Multi-terminal adds on the expensive side Converter stations for multi-terminal are more expensive than those for two-terminal operation: Larger steady state gamma and thereby Larger Udio More reactive power More switchyard equipment (disconnects, HSS s, DCCT s )
36 Multi-terminal Challenges: Control considerations Master controllers One in each station All are exact replicas, and kept live and updated Only one is in charge These principles are the same as in 2-terminal BUT There are more master controllers They are more complex and contain more functions Telecommunication plays an important role, but system can operate without it
Transmissão em Corrente Contínua em Ultra-Alta Tensão
Transmissão em Corrente Contínua Panorama Atual e Perspectias Futuras no Brasil Siemens AG 2012 Energy Sector Ultra-High Voltage Transmission Systems 2 Brazilian SC B4 Multiterminal HVDC Systems / VSC
More informationTopics. HVDC Fundamentals
Topics HVDC Fundamentals Conventional Converters Capacitor Commutated Converters Voltage Source Converters Reactive Power Requirements System Configurations Tapping Control basics High Power Transmission
More informationElectrical Considerations for HVDC Transmission Lines. Joe Mooney, PE
Electrical Considerations for HVDC Transmission Lines Joe Mooney, PE POWER Engineers has met the standards and requirements of the Registered Continuing Education Program. Credit earned on completion of
More informationCO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE
CO-ORDINATION OF PARALLEL AC-DC SYSTEMS FOR OPTIMUM PERFORMANCE Ana Diez Castro & Rickard Ellström Ying Jiang Häfner Christer Liljegren Vattenfall Utveckling AB ABB Power Systems Gotlands Energiverk AB
More informationBrochure Introducing HVDC
Brochure Introducing HVDC ABB and HVDC The world s first commercial high-voltage direct current (HVDC) link, situated between the Swedish mainland and the island Gotland, was delivered by ABB already in
More informationPOWER TRANSMISSION FROM OFFSHORE WIND FARMS
POWER TRNSMISSION FROM OFFSHORE WIND FRMS Thorsten Völker University of pplied Sciences Bremerhaven Germany BSTRCT The future for wind power generation in Germany is offshore wind energy. The preferred
More informationWide Area Monitoring Current Continental Europe TSOs Applications Overview
Wide Area Monitoring Current Continental Europe TSOs Applications Overview Version 5 System Protection & Dynamics Working Group 20th September 2015 1. Content 1. Content... 2 2. Introduction... 3 3. Main
More informationHVDC 2000 a new generation of high-voltage DC converter stations
HVDC 2000 a new generation of high-voltage DC converter stations Improved performance and robustness, shorter lead times and faster delivery, plus reduced maintenance needs, were the development goals
More informationTransformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager
Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager Introduction There is a growing trend in the UPS industry to create a highly efficient, more lightweight and smaller UPS
More informationVariable Frequency Drives - a Comparison of VSI versus LCI Systems
Variable Frequency Drives - a Comparison of VSI versus LCI Systems Introduction TMEIC is a leader in the innovative design and manufacture of large ac variable f requency drive systems. TMEIC has been
More informationStandards in Marine Power Systems. APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208
Standards in Marine Power Systems APEC 2014 Session IS2.1 Power Electronic Standards Roger Dougal University of South Carolina Columbia, SC 29208 Need is Driven by Electrification Oasis of the Seas DDG
More informationVoltage Source HVDC Overview Mike Barnes Tony Beddard
Voltage Source HVDC Overview Mike Barnes Tony Beddard Note: This is a version with images removed which have copyrighted other than from the University of Manchester, for web publication. Should a conference
More informationHVDC. A firewall against disturbances in high-voltage grids. Lennart Carlsson
A firewall against disturbances in high-voltage grids Lennart Carlsson Interconnections between grids are desirable because they not only permit economies through the sharing of reserves, but they also
More informationSystem Protection Schemes in Eastern Denmark
System Protection Schemes in Eastern Denmark Joana Rasmussen COWI A/S, Energy Department System Protection Schemes in Eastern Denmark 1.Advanced system protection schemes are investigated and perspectives
More information2012 San Francisco Colloquium
2012 San Francisco Colloquium http : //www.cigre.org Advances in voltage source converter (VSC) technologies B4-6 500 kv VSC Transmission System for lines and cables B. JACOBSON, B. WESTMAN, M. P. BAHRMAN*
More informationDC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS
DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS by Gunnar Asplund, Kjell Eriksson, Hongbo Jiang, Johan Lindberg, Rolf Pålsson, Kjell Svensson ABB Power Systems AB Sweden SUMMARY Voltage Source Converters
More informationThree Gorges - Changzhou HVDC : Ready to Bring Bulk Power to East
The 4 th International Conference on Power Transmission & Distribution Technology 2003 14-16 October, 2003, Changsha 2003 Three Gorges - Changzhou HVDC : Ready to Bring Bulk Power to East Abhay Kumar Mats
More informationHVDC-VSC: transmission technology of the future
A bi-pole ± 285 kv HVDC line sandwiched between 3-phase 400 kv HVAC lines. HVDC-VSC: transmission technology of the future A new hybrid HVDC circuit technology using voltage source converters is only half
More informationGeneral Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System
General Validation Test Program for Wind Power Plants Connected to the Hydro-Québec Transmission System Direction Planification des actifs et expertise de transport February 2011 TABLE OF CONTENTS 1. CONDUCTING
More informationINTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET)
INTERNATIONAL JOURNAL OF ELECTRICAL ENGINEERING & TECHNOLOGY (IJEET) International Journal of Electrical Engineering and Technology (IJEET), ISSN 0976 ISSN 0976 6545(Print) ISSN 0976 6553(Online) Volume
More informationHVDC Technology for Large Scale Offshore Wind Connections
HVDC Technology for Large Scale Offshore Wind Connections Nandan Mahimkar, Gunnar Persson,Claes Westerlind, ABB AB, SE-771 80, Ludvika, Sweden, nandan.mahimkar@in.abb.com, gunnar.persson@se.abb.com,claes.westerlind@se.abb.com,
More information..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...
..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark... TIME MARK CORPORATION 11440 EAST PINE STREET TULSA, OK 74116 USA tel 918 438-1220 fax 918 437-7584 www.time-mark.com
More informationFor a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690 V - 1000 V (at 50 Hz)
24 1. NETWORK CONFIGURATIONS definition Standard IEC 38 defines voltage ratings as follows: - Low voltage () For a phase-to-phase voltage between 100 V and 1000 V. The standard ratings are: 400 V - 690
More informationControl Development and Modeling for Flexible DC Grids in Modelica
Control Development and Modeling for Flexible DC Grids in Modelica Andreas Olenmark 1 Jens Sloth 2 Anna Johnsson 3 Carl Wilhelmsson 3 Jörgen Svensson 4 1 One Nordic AB, Sweden, andreas.olenmark@one-nordic.se.
More informationIntroduction to Paralleling of LTC Transformers by the Circulating Current Method
TAPCHANGER CONTROLS Application Note #11 Introduction to Paralleling of LTC Transformers by the Circulating Current Method 1.0 ABSTRACT This Application Note discusses the elements of paralleling load
More informationABB PSPS Erich Steinmann; Generator control-2013
ABB PSPS Erich Steinmann; Generator control-2013 GENERATOR CONTROL THE MODULAR SOLUTION FOR GENERATORS To make sure that power is efficiently converted into electric energy, it is necessary to supervise
More informationMagnus Callavik, ABB Power Systems, HVDC, 721 64 Västerås, Sweden Phone: +46(0)21323226. e-mail: magnus.callavik@se.abb.com
HVDC GRIDS FOR OFFSHORE AND ONSHORE TRANSMISSION Magnus Callavik, ABB Power Systems, HVDC, 721 64 Västerås, Sweden Phone: +46(0)21323226. e-mail: magnus.callavik@se.abb.com SUMMARY The objective with this
More informationOffshore Platform Powered With New Electrical Motor Drive System
Offshore Platform Powered With New Electrical Motor Drive System Authors: Jan O. Lamell, M.Sc E.E. ABB Automation Technologies Presenters: Thomas Johansson, M.Sc E.E. ABB Automation Technologies Timothy
More informationRelationship between large subject matter areas
H02M APPARATUS FOR CONVERSION BETWEEN AC AND AC, BETWEEN AC AND DC, OR BETWEEN DC AND DC, AND FOR USE WITH MAINS OR SIMILAR POWER SUPPLY SYSTEMS; CONVERSION OF DC OR AC INPUT POWER INTO SURGE OUTPUT POWER;
More informationPower Supplies. 1.0 Power Supply Basics. www.learnabout-electronics.org. Module
Module 1 www.learnabout-electronics.org Power Supplies 1.0 Power Supply Basics What you ll learn in Module 1 Section 1.0 Power Supply Basics. Basic functions of a power supply. Safety aspects of working
More informationand vice versa. This conversion is the key challenge for HVDC transmission and the HVDC story can be divided
12 ABB review special report High impact 60 years of HVDC has changed the power landscape BO PÄÄJÄRVI, MIE-LOTTE BOHL We are so used to the convenience of merely having to flick a switch to illuminate
More informationCOMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS
COMPARISON OF THE FACTS EQUIPMENT OPERATION IN TRANSMISSION AND DISTRIBUTION SYSTEMS Afshin LASHKAR ARA Azad University of Dezfoul - Iran A_lashkarara@hotmail.com Seyed Ali NABAVI NIAKI University of Mazandaran
More informationCurrent and voltage measuring relays
Current and voltage measuring relays RXIK 1, RXEEB 1 and Page 1 Issued June 1999 Changed since July 1998 Data subject to change without notice RXIK 1 RXEEB 1 (SE980082) (SE980081) (SE970869) Features Application
More information2012 San Francisco Colloquium
2012 San Francisco Colloquium http : //www.cigre.org HVDC and Power Electronic Systems for Overhead Line and Insulated Cable Applications B4-8 Trans Bay Cable A Breakthrough of VSC Multilevel Converters
More informationThree-Phase Electric Power Distribution for Computer Data Centers
Three-hase Electric ower Distribution for Computer Data Centers WHITE AER E901 Geist January 008 Summary This paper will describe the characteristics of three-phase power and outline the advantages of
More informationFACTS. Solutions to optimise network performance GRID
Solutions to optimise network performance GRID Solutions to optimise your network Our worldwide presence: Better solutions for your network all around the world Tampere Philadelphia Stafford Konstanz Beijing
More informationEvolution of Control for the Smart Transmission Grid
Evolution of Control for the Smart Transmission Grid Anjan Bose Washington State University Pullman, WA SCE Smart Grid Research Symposium California Institute Of Technology October, 2011 The Past (before
More informationfactsheet High Voltage Direct Current electricity technical information
factsheet High Voltage Direct Current electricity technical information Introduction High voltage direct current (HVDC) technology is one of the technical options National Grid can consider for the future
More informationSmart Grid and Renewable Energy Grid Integration. Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems
Smart Grid and Renewable Energy Grid Integration Jian Sun, Professor and Director Department of ECSE & Center for Future Energy Systems 1 How Smart Can We Make This Grid? 2 Smart Grid Drivers Need to Use
More informationSP 4K/5K Efecto & SP 5K Brilliant Parallel Installation Guide 1. Introduction
SP 4K/5K Efecto & SP 5K Brilliant Parallel Installation Guide 1. Introduction This inverter can be used in parallel with two different operation modes. 1. Parallel operation in single phase with up to
More information4KVA/5KVA Parallel Installation Guide
4KVA/5KVA Parallel Installation Guide 1. Introduction This inverter can be used in parallel with two different operation modes. 1. Parallel operation in single phase with up to 4 units. The supported maximum
More informationSafety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
More informationfactsheet High Voltage Direct Current Electricity technical information
factsheet High Voltage Direct Current Electricity technical information Introduction High voltage direct current (HVDC) technology is one of the technical options National Grid can consider for the future
More informationTrip circuit supervision relay. Type RXTCS
Trip circuit supervision relay Type RXTCS ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while
More information3FBD DC Motor Drive User Manual
3FBD DC Motor Drive User Manual Via I. Alpi 6 - zona industriale - Lonato (BS) Tel. +39 30 9913491 r.a. Fax. +39 30 9913504 http://www.re-elettronica.it info@re-elettronica.it Pag. 1 Index Index... pag.1
More informationVOLTAGE REGULATOR AND PARALLEL OPERATION
VOLTAGE REGULATOR AND PARALLEL OPERATION Generator sets are operated in parallel to improve fuel economy and reliability of the power supply. Economy is improved with multiple paralleled generators by
More informationRenewable Energy Grid Integration
Renewable Energy Grid Integration Jian Sun Professor and Director Grid Integration Issues Cost, Reliability & Efficiency of Grid Interface Grid Congestion, Weak Grids Variability of Renewable Production
More informationElectron S.R.L. A29 ELECTRICAL POWER SYSTEM TRAINERS. Production Transmission Distribution
lectron S..L. Design Production & Trading of ducational quipment A29 LCTICAL POW SYSTM TAINS Production Transmission Distribution FAX 9065 980 - -mail: electron@electron.it Web: www.electron.it ev 02 Specifications
More informationWIND TURBINE TECHNOLOGY
Module 2.2-2 WIND TURBINE TECHNOLOGY Electrical System Gerhard J. Gerdes Workshop on Renewable Energies November 14-25, 2005 Nadi, Republic of the Fiji Islands Contents Module 2.2 Types of generator systems
More informationLocal Back-up Protection for an Electric Power System
MULTILIN GER-3178 GE Power Management Local Back-up Protection for an Electric Power System LOCAL BACK UP PROTECTION FOR AN ELECTRIC POWER SYSTEM J. BERDY TABLE OF CONTENTS Transmission Line Back-Up Protection...............................................
More informationBi-directional Power System for Laptop Computers
Bi-directional Power System for Laptop Computers Terry L. Cleveland Staff Applications Engineer Microchip Technology Inc. Terry.Cleveland@Microchip.com Abstract- Today the typical laptop computer uses
More informationLab 8: DC generators: shunt, series, and compounded.
Lab 8: DC generators: shunt, series, and compounded. Objective: to study the properties of DC generators under no-load and full-load conditions; to learn how to connect these generators; to obtain their
More informationLine Reactors and AC Drives
Line Reactors and AC Drives Rockwell Automation Mequon Wisconsin Quite often, line and load reactors are installed on AC drives without a solid understanding of why or what the positive and negative consequences
More informationA COMPARISON ON PERFORMANCE OF TCSC/SSSC FOR A RADIAL SYSTEM
IMPACT: International Journal of Research in Engineering & Technology (IMPACT: IJRET) ISSN(E): 31-8843; ISSN(P): 347-4599 Vol. 3, Issue 9, Sep 015, 7-18 Impact Journals A COMPARISON ON PERFORMANCE OF TCSC/SSSC
More informationTechnical Information POWER PLANT CONTROLLER
Technical Information POWER PLANT CONTROLLER Content The Power Plant Controller offers intelligent and flexible solutions for the control of all PV power plants in the megawatt range. It is suitable for
More informationDigital Signal Controller Based Automatic Transfer Switch
Digital Signal Controller Based Automatic Transfer Switch by Venkat Anant Senior Staff Applications Engineer Freescale Semiconductor, Inc. Abstract: An automatic transfer switch (ATS) enables backup generators,
More informationGrid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique
Grid Interconnection of Renewable Energy Sources Using Modified One-Cycle Control Technique NKV.Sai Sunil 1, K.Vinod Kumar 2 PG Student, GITAM University, Visakhapatnam, India. Asst.Professor, Department
More informationSummary of Electric Transmission Assessment Report
Summary of Electric Transmission Assessment Report January 2010 Assessment and Analysis of the State-Of-the-Art High-Voltage Electric Transmission Systems with Specific Focus on High-Voltage Direct Current
More informationSubstation Automation Systems. We are exceptional grid stability PSGuard Wide Area Monitoring System
Substation Automation Systems We are exceptional grid stability PSGuard Wide Area Monitoring System We are exceptional grid stability PSGuard Wide Area Monitoring System 2 We are exceptional grid stability
More informationSUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original
SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original A motor starter is a combination of devices to allow an induction motor to start, run and stop according
More informationA MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER
A MULTILEVEL INVERTER FOR SYNCHRONIZING THE GRID WITH RENEWABLE ENERGY SOURCES BY IMPLEMENTING BATTERY CUM DC-DC CONERTER 1 KARUNYA CHRISTOBAL LYDIA. S, 2 SHANMUGASUNDARI. A, 3 ANANDHI.Y 1,2,3 Electrical
More informationMICROGRIDS FOR DATA CENTERS
MICROGRIDS FOR DATA CENTERS Table of Contents Summary of Pareto Energy s Microgrid Business Model Understanding the Risks of On-Site Power for Critical Infrastructure The Pareto Energy GridLink Solution
More informationMathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors
Applied and Computational Mechanics 3 (2009) 331 338 Mathematical Modeling and Dynamic Simulation of a Class of Drive Systems with Permanent Magnet Synchronous Motors M. Mikhov a, a Faculty of Automatics,
More informationFlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3
FlexPak 3000 Digital DC Drive Software Reference Manual Version 4.3 Instruction Manual D2-3405-2 The information in this manual is subject to change without notice. Throughout this manual, the following
More informationIncreased power protection with parallel UPS configurations
Increased power protection with parallel UPS configurations Making the selection between Centralized Bypass and Distributed Bypass systems Janne Paananen Application Engineer, Large Systems Group Eaton
More informationThyristor-controlled power supplies and battery chargers
Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /
More informationNPCC Regional Reliability Reference Directory # 8 System Restoration
NPCC Regional Reliability Reference Directory # 8 Task Force on Coordination of Operations Revision Review Record: October 21, 2008 Adopted by the Members of the Northeast Power Coordinating Council, Inc.
More informationPilot-wire differential relay for lines with two or more terminals
Pilot-wire differential relay for lines with two or more terminals Page 1 Issued: March 2003 Revision: A Data subject to change without notice Pilot-wire differential relay with RXHL 401 Features Phase
More informationHIGH FREQUENCY TRANSFORMER WITH TRANSFORMER SWITCHOVER
OPTIMUM EFFICIENCY AND FLEXIBLE USE HIGH FREQUENCY TRANSFORMER WITH TRANSFORMER SWITCHOVER One of the many requirements of the modern inverter is a broad, coordinated input and MPP voltage range with a
More informationOPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS
OPTIMIZING POWER SYSTEM PROTECTION FOR MODERN DATA CENTERS Data center power systems are constructed with a premium on reliability at a significant cost. The return on this investment is realized if it
More informationFRCC Standards Handbook. FRCC Automatic Underfrequency Load Shedding Program. Revision Date: July 2003
F R C C FRCC Standards Handbook FRCC Automatic Underfrequency Load Shedding Program Revision Date: July 2003 FRCC Underfrequency Load Shedding Program Modification and Approval Process Requests to modify
More informationCircuit Breaker LTB D with Motor Drive. Motor Drive. ABB PP/H/HV - Page 1. Ed 2006-04
Circuit Breaker LTB D with Motor Drive Motor Drive ABB PP/H/HV - Page 1 Ed 2006-04 Technology Traditional technology Traditional spring operating mechanism: Closing mechanism ABB PP/H/HV - Page 2 Tripping
More informationDesigned for uptime. Defining data center availability via a tier classification system
Defining data center availability via a tier classification system MIETEK GLIKOWSKI All systems can fail this is a simple fact that every industry must deal with. The paramount concern for the data center
More informationTURBOtech srl. SED-635 Digital Excitation System. Industrial Electronics Sector FEATURES
SED-635 Digital Excitation System SED-635 is a complete excitation system capable of adapting to control synchronous generators of any size. The integration of the TOUCH SCREEN operator interface and a
More informationHVDC Light, a tool for electric power transmission to distant loads
Presented at VI Sepope Conference, Salvador, Brazil, May 1998 HVDC Light, a tool for electric power transmission to distant loads by Gunnar Asplund Kjell Eriksson* Ove Tollerz ABB Power Systems AB ABB
More informationProducts and solutions for pumping, irrigation and piping
Products and solutions for pumping, irrigation and piping 100% electricity www.lovatoelectric.com Tra dition and Innovation LOVATO Electric S.p.A. - Bergamo - Italy Since 1922 The first LOVATO Electric
More informationReport in respect of. Service Disruption on 9 April 2012
Report in respect of Service Disruption on 9 April 2012 1. Introduction On 9 April 2012, a power outage occurred in the Shatin Switching Centre, one of three switching centres deployed by SmarTone Mobile
More informationGeneric PCSR Sub-chapter 15.4 : Electrical Equipment
Form10/00 Document ID : GA91-9101-0101-15004 Document Number : EE-GDA-C284 Revision Number : A Generic Design Assessment Generic PCSR Sub-chapter 15.4 : Electrical Equipment Hitachi-GE Nuclear Energy,
More informationInverter / Charger Installation General Operations and AC and DC Connections
Inverter / Charger Installation General Operations and AC and DC Connections The Inverter is just one piece. Sometimes, a tendency is to mount the inverter and batteries, and make it work It is better
More informationAC COUPLED HYBRID SYSTEMS AND MINI GRIDS
, Michael; Hermes, Matthias SMA Technologie AG Hannoversche Str. 1-5 34266 Niestetal GERMANY E-mail: Michael.@SMA.de E-mail: Matthias.Hermes@SMA.de 1. INTRODUCTION Distributed supply based on renewable
More informationFundamentals of Power Electronics. Robert W. Erickson University of Colorado, Boulder
Robert W. Erickson University of Colorado, Boulder 1 1.1. Introduction to power processing 1.2. Some applications of power electronics 1.3. Elements of power electronics Summary of the course 2 1.1 Introduction
More information16 West Coast Regional Plan
16 West Coast Regional Plan 16.1 Regional overview 16.2 West Coast transmission system 16.3 West Coast demand 16.4 West Coast generation 16.5 West Coast significant maintenance work 16.6 Future West Coast
More informationMicro-Step Driving for Stepper Motors: A Case Study
Micro-Step Driving for Stepper Motors: A Case Study N. Sedaghati-Mokhtari Graduate Student, School of ECE, University of Tehran, Tehran, Iran n.sedaghati @ece.ut.ac.ir Abstract: In this paper, a case study
More informationType SA-1 Generator Differential Relay
ABB Automation Inc. Substation Automation and Protection Division Coral Springs, FL 33065 Instruction Leaflet 41-348.11C Effective: November 1999 Supersedes I.L. 41-348.11B, Dated August 1986 ( ) Denotes
More informationRotating Machinery Diagnostics & Instrumentation Solutions for Maintenance That Matters www.mbesi.com
13 Aberdeen Way Elgin, SC 29045 Cell (803) 427-0791 VFD Fundamentals & Troubleshooting 19-Feb-2010 By: Timothy S. Irwin, P.E. Sr. Engineer tsi@mbesi.com Rotating Machinery Diagnostics & Instrumentation
More informationHarmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies
Soonwook Hong, Ph. D. Michael Zuercher Martinson Harmonics and Noise in Photovoltaic (PV) Inverter and the Mitigation Strategies 1. Introduction PV inverters use semiconductor devices to transform the
More informationModified Cascaded Five Level Multilevel Inverter Using Hybrid Pulse Width Modulation
International Journal of Computer Sciences and Engineering Open Access Research Paper Volume-4, Special Issue-2, April 2016 E-ISSN: 2347-2693 Modified Cascaded Five Level Multilevel Inverter Using Hybrid
More informationTransient analysis of integrated solar/diesel hybrid power system using MATLAB Simulink
Transient analysis of integrated solar/diesel hybrid power system using ATLAB Simulink Takyin Taky Chan School of Electrical Engineering Victoria University PO Box 14428 C, elbourne 81, Australia. Taky.Chan@vu.edu.au
More informationHigh EMI immunity. I/O events are timestamped locally on each module.
%,0%20,20 360 Page 1 Revision: - Issued: November 2002 Data subject to change without notice )HDWXUHV $SSOLFDWLRQ &RPPRQ High EMI immunity. I/O events are timestamped locally on each module. %LQDU\LQSXWV
More informationConverter Stations for 800 kv HVDC U Åström, and V. Lescale
1 Converter Stations for 800 kv HVDC U Åström, and V. Lescale Keywords 800 kv HVDC, Bulk power transmission, Converter stations, HVDC, HVDC External insulation, HVDC reliability, HVDC Equipment, HVDC Systems,
More informationFederal Wage System Job Grading Standards for Electric Power Controlling, 5407. Table of Contents
Federal Wage System Job Grading Standards for Electric Power Controlling, 5407 Table of Contents WORK COVERED... 2 WORK NOT COVERED...2 TITLES... 2 GRADE LEVELS... 2 SPECIAL ADDITIONAL RESPONSIBILITIES...
More informationChapter 9 Balanced Faults
Chapter 9 alanced Faults 9.1 Introduction The most common types of fault are (in order) single-line-to-ground fault, line-to-line fault, and double-line-to-ground fault. All of these are unbalanced faults.
More informationSCADA. The Heart of an Energy Management System. Presented by: Doug Van Slyke SCADA Specialist
SCADA The Heart of an Energy Management System Presented by: Doug Van Slyke SCADA Specialist What is SCADA/EMS? SCADA: Supervisory Control and Data Acquisition Retrieves data and alarms from remote sites
More informationA Practical Guide to Free Energy Devices
A Practical Guide to Free Energy Devices Device Patent No 29: Last updated: 7th October 2008 Author: Patrick J. Kelly This is a slightly reworded copy of this patent application which shows a method of
More informationLaboratory 4: Feedback and Compensation
Laboratory 4: Feedback and Compensation To be performed during Week 9 (Oct. 20-24) and Week 10 (Oct. 27-31) Due Week 11 (Nov. 3-7) 1 Pre-Lab This Pre-Lab should be completed before attending your regular
More information300 MW Variable Speed Drives for Pump-Storage Plant Application Goldisthal
May 24 MW Variable Speed Drives for Aurélie Bocquel APCG / 4BOC4 (MW-Goldisthal 1-5-24).PPT MW Variable Speed Drives for Content Major benefits of the cyclo-converter driven doubly-fed induction machines
More informationPower System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3
Power System review W I L L I A M V. T O R R E A P R I L 1 0, 2 0 1 3 Basics of Power systems Network topology Transmission and Distribution Load and Resource Balance Economic Dispatch Steady State System
More informationTest & Data Management Software
Test & Data Management Software TDMS protective relays energy meters transducers power quality CT-VT-PT transformers ground grid circuit breakers batteries surge arresters The Integrated Testing Solution
More information415V DISTRIBUTION FOR GREEN DATA CENTERS
White Paper: HMRP-WP001-A5 June 5, 2012 415V DISTRIBUTION FOR GREEN DATA CENTERS Prepared by: Anthony (Tony) Hoevenaars, P. Eng President and CEO Mirus International Inc. Copyright 2012 Mirus International
More informationThe Application and Benefits of Multi-phase Auto-reclosing
he Application and Benefits of Multi-phase Auto-reclosing etsuya Miyoshi*, Atsushi Kasai* Abstract - In this paper we explain the disadvantages in using single- and three-phase auto-reclosing on double
More information