Universal Dimmer. 31E2PUD Series PUSH BUTTON. Installation Instructions. Integrally Switched Push-Button INTEGRALLY SWITCHED 240V



Similar documents
C-Bus. Single Zone Thermostat. 5070THB Series. Installation Instructions REGISTERED DESIGN REGISTERED PATENT

Passive Infrared Motion Detector 5420/90. Installation Instructions

Motion Detector 360 Degrees 5420/360. Installation Instructions REGISTERED DESIGN REGISTERED PATENT

15 Series - Electronic step relay and dimmer. Features SERIE

Dimmer and Bulb Compatibility

Do the products you use comply?

Datasheet - DS0002 Indice Semiconductor Pty Ltd

90 Degree PIR Wireless Security Sensor. Installation Instructions 5420/90F

LED DIMMING A HELPFUL GUIDE...

FL ballasts Electronic dimming. PCA T5 EXCEL one4all lp Y, 3x14/24 W and 4x14/24 W EXCEL T5

Installation and Operation Back-UPS 1250, 1300, 1500

REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16

NSI DIGITAL DIMMING SYSTEM DDS 9800 DIMMER PACKS

Installation and Operation Manual Back-UPS BX800CI-AS/BX1100CI-AS

Back-UPS 650 VA 120 V with AVR (BX650CI-LM)

TROUBLESHOOTING LED DOWNLIGHTS

Die-Cast Metal, Motion- Activated Post Light

Flarm LED indicator. Version 1.1

FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, W BASIC T5

LUCCI AIRFUSION QUEST II CEILING FAN

Product and functional description

ST Series POWER SUPPLIES USER INSTRUCTIONS

Installation Manual. Features SMART SWITCH OCCUPANCY SENSOR. Maximum Energy savings

Medical Lighting. XL4 Patient Light

IVIOS LED III. LUM Technical Information

Operational Overview and Controls Guide. Two or Three Pump IronHeart Lite with Variable Frequency Drives

RF Maestro Local Controls

User Manual. English. APC Smart-UPS 500 VA 100 VAC 750 VA 100/120/230 VAC. Tower Uninterruptible Power Supply

5W LED Energy Saver PIR Bulkhead

User s Manual Before using the inverter, you need to read and save the safety instructions.

Installation and operating instructions: Radio dimmer Type: DALI DM ADVANCED LI

IMPORTANT SAFETY INSTRUCTIONS WARNING READ AND SAVE THESE OPERATING AND SAFETY INSTRUCTIONS BEFORE USING THIS HEATER.

FL ballasts Electronic dimming. PCA T5 EXCEL one4all lp Y II, W EXCEL T5

Basics of Dimming. ISC Learning Centre

Mini Timer Owner's Manual. Model MT13A

D4 HP Dimmer User s Manual Rev City Theatrical, Inc.

Operation Manual. 150 Watt Halogen Light Source for Endoscopy Model # s ESS-150, ESS-150A ESS-220, ESS-220A

Owner s Manual. Not suitable for mobile applications. Important Safety Instructions 2. Quick Installation 3. Basic Operation 4. Storage & Service 7

Square D Clipsal DIN-Rail Four-Channel Auxiliary Input Unit

CSP Combined Series. Telephone Door Entry. with. Proximity Keyfob Access

Indoor Remote Controlled Power Points

User Manual. English. APC Smart-UPS SC. 1000/1500 VA 110/120/230 Vac. 2U Tower/Rack-Mount Uninterruptible Power Supply

Ecomind Electricity Monitoring Software 2.1. Software Manual

60W Security Twinspot. 754HB2/180/ Outdoor Motion Sensor. Installation Instructions. Please leave these instructions at the installation site.

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

Mini Power Bank and Charger

Touch Tone Controller. Model TR16A. Owner s Manual

Inwall 4 Input / 4 Output Module

ClearView+ User Manual

Operating instructions IV / 2007

Vertical Display and Storage B SKOPE Gen2: Three Door Chiller

Installing the Broadband Global Area Network (BGAN) Fixed Mount Kit

RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

Transmitter Actuator 230V wave UP 560. Operation

Model: v2 Quick Setup Guide DC: Atomic Projection Alarm with Indoor and Outdoor Temperature

Drayton Digistat +2RF/+3RF

CR Band Auto Set Dual Alarm Clock Radio ROBERTS. Sound for Generations. Please read this manual before use

User Manual THR840DUK Digital Thermostat

Bubble King. User Manual

FL ballasts Electronic dimming. PCA T5 ECO lp Y II, W ECO T5

Speedflow Undersink Unvented Water Heater. Models SF10K and SF15K. Instruction Manual

Name of Equipment Silver King Model SKMCD1P/C1. This equipment chapter is to be inserted in the appropriate section of the Equipment Manual.

AN500T, AN1000, AN1000T, AN1500, AN1500T AN2000, AN2000T

Stop Alert Flasher with G-Force sensor

Congratulations! Thank you!

Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)

INSTRUCTIONS FOR MAGNUM DS TRIP UNIT TESTING USING TEST KIT SYLES 140D481G02R, 140D481G02RR, 140D481G03 AND 140D481G04

OPERATING INSTRUCTIONS

RD-27 ROBERTS. FM RDS/DAB digital radio with. Sound for Generations. Please read this manual before use

DALI RC BASIC SO. Control unit Operating instructions

DALI DIM/CONVERTER CONTROL (DC NV) 1 10V (0-10 V) analog DALI Converter with (Multi-) Sensor-control and 1 and 2-Switch dim functions

contents Leading the way in intelligent automation INELS Wireless? Why Click Accessories Complete control

LT SERIES User s Manual

VX 2400 Dimmer User's Manual

PIR Motion Detector E-808

R22. K Control. Indoor Unit. Nomenclature. Compatibility PL H 3 G K H B. Unit style Heat Pump Horse Power

CR9986 ROBERTS. Dual Alarm CD Clock Radio. Sound for Generations. Please read this manual before use

Light Source User Guide

LED MOTION ACTIVATED FLOOD LIGHT

CelluLine CGW-TS GSM Cellular Gateway. Installation and Programming Manual

DOCUMENTATION PD16 CP3-SVE-M75DC-24

Installation and User Guide

BroadBand PowerShield. User Manual

Slimline Plus. Catalogue No. R6

Wireless 7 Day Programmable Room Thermostat

Instructions: Retain these instructions for future reference SmartChargePro35 RSCPR35-12v, 2 / 8 / 16 / 35A

, User s Manual

Digital Photo Picture Frame. Operation Manual

Back-UPS Pro 1300/1500 Installation and Operation

GAUGEMASTER PRODIGY EXPRESS

ADA COMPLIANT BOX STYLE TELEPHONE INSTALLATION, PROGRAMMING AND OPERATING INSTRUCTIONS FOR MODEL PBX

Applied Electronics. Commercial Dimming System UPDATE NOTICE

Wireless Indoor/ Outdoor Thermometer

Manual for Fire Suppression & Methane Detection System

Guide to Starters Guide to Starters Page 1 of 17

DUAL%CHANNEL BROADBAND%LINEAR%AMPLIFIER Model&A800D

GENERATOR START CONTROL MODULE - MINI (2 Wire to 3 Wire)

Sensi TM. Wi-Fi Programmable Thermostat MANUAL OPERATION. Version: March Emerson Electric Co. All rights reserved.

Short Range Wireless Switch System Handheld 8 Installation and Operations Guide

CAT AVR V2.3. Instruction Manual. Voltage regulator for generators. March 2008

Transcription:

PUSH BUTTON INTEGRALLY SWITCHED 240V Universal Dimmer Integrally Switched Push-Button 31E2PUD Series 350W Installation Instructions REGISTERED DESIGN REGISTERED PATENT

Table of Contents 1.0 Product Range...3 2.0 Description...3 3.0 Features...4 4.0 Dimmer Unit Operation...4 4.1 Push-Button Operation... 4 4.2 LED Indicator... 5 4.3 Button Cap... 5 5.0 Set-Up Mode...6 6.0 Load Compatibility...8 7.0 Incompatible Loads...9 8.0 Installation Instructions...9 8.1 Wiring Details... 9 8.2 Multi-Gang Derating... 9 8.3 Thermal Overload Protection Circuitry... 10 8.4 Short Circuit Protection... 10 8.5 Power-Up Status... 10 9.0 Wiring Diagram...10 10.0 Electrical Specifications...11 11.0 Warranty Statement...12 2 of 8 2013 Schneider Electric. All Rights Reserved.

1.0 Product Range 31E2PUDM Universal Dimmer, ISPB, 220-240V, 50Hz, 350W (30 Series Mechanism) 2031E2PUD Universal Dimmer, ISPB, 220-240V, 50Hz, 350W (2000 Series) C2031E2PUD Universal Dimmer, ISPB, 220-240V, 50Hz, 350W (Classic Series) SC2031E2PUD Universal Dimmer, ISPB, 220-240V, 50Hz, 350W (Slimline Series) SL2031E2PUD Universal Dimmer, ISPB, 220-240V, 50Hz, 350W (Eclipse Series) 4061E2PUDM Universal Dimmer, ISPB, 220-240V, 50Hz, 350W (Saturn Mechanism) 4061E2PUDN Universal Dimmer, ISPB, 220-240V, 50Hz, 350W (Saturn Series) * Please note that these products are also available in other configurations and in a wide range of colours. For further information, please contact your nearest Clipsal Sales Representative. 2.0 Description The Clipsal 31E2PUDM Series Universal Dimmer is an Integrally Switched, Push-Button (ISPB), modular universal dimmer mechanism rated at 350W. Incorporating a built-in (integral) switch, up to six dimmer mechanisms can be installed in a plate. Designed for universal load compatibility, the unit utilises powerful and sophisticated dimming technology to provide full control of almost any type of load, whether it be incandescent lighting, mains voltage halogen or dichroic lamps, iron-core or electronic low voltage lighting transformers as used in downlight applications. Even small motor loads such as ceiling sweep and exhaust fans can be controlled. The Universal Dimmer also incorporates over-current and over-temperature protection devices and is capable of withstanding persistent short circuit conditions, making it the most rugged, robust and reliable dimmer mechanism ever produced. C-Thru : The Clear Choice helping you select the right dimmer, first time every time. 30 Series 60 Series Standard Mechanism Saturn Mechanism 31E2PUDM 4061E2PUDM 2013 Schneider Electric. All Rights Reserved. 3 of 8

3.0 Features Integrally switched modular dimming mechanism. Built using Clipsal Universal Dimming Technology. 350W power rating. Suitable for a wide range of load types: Incandescent (tungsten filament) lamps. 240V Halogen/Dichroic Lamps. Low voltage downlights using electronic transformers. Low voltage downlights using iron-core transformers. Small motor loads. Compatible with selected dimmable LED loads*. User selectable soft-start/kick-start operation. User adjustable minimum brightness. Multi-gang capacity up to six (6) dimmer mechanisms per plate. Wall or architrave mounting options. Wide range of plate styles and colour variants available. Suitable for new installations or retrofit applications. Inbuilt over-current and over-temperature protection. Full short circuit protection (!). Fitted with suppressors to minimise radio frequency interference. Complies with Australian and International EMC Standards. *Please visit clipsal.com/load for recommended loads. 4.0 Dimmer Unit Operation 4.1 Push-Button Operation SHORT PRESS Tap the push-button to turn the dimmer ON or OFF. The dimmer has memory and will remember the previous dim setting. When you tap the button to turn the light OFF, the unit will store the current setting in the memory. When you tap the button to turn the light ON, the dimmer will restore the previous dim setting. LONG PRESS DOUBLE-CLICK Press and hold the button to dim up and down. Release the button to stop dimming. The dimmer will cycle up and down alternately. When the light is ON, the dimmer will dim down by default. When the dimmer is OFF, it will dim upwards (increase brightness) by default. Subsequent long press will dim in the opposite direction. While dimming, if the dimmer reaches its maximum or minimum brightness level, the unit will pause for 1 second, then start dimming in the opposite direction. A single ramp cycle takes about 6 seconds to complete. If the button is not pressed for 15 seconds, the dimming is set to fade out by default again. Tap the button twice to turn the dimmer ON to maximum brightness. The dimmer will reach maximum brightness in approximately 1 second. 4 of 8 2013 Schneider Electric. All Rights Reserved.

STUDY 31E2PUDM UNIVERSAL DIMMER 350W 220-240v a.c. 50Hz 31E2PUD Series 4.2 LED Indicator The unit incorporates an LED indicator to display the status of the load. LOAD STATUS ON OFF INDICATOR STATUS ON OFF 4.3 Button Cap The push-button dimmer units incorporate a replaceable button cap. TYPE BUTTON CAP 1. Insert flathead screwdriver into recess on the side of the button cap. Light guide 30 Series 31E2PUDM Button cap 3. Press new button cap onto mechanism until it clicks into place. 2. Lever off the button cap leaving the light guide in place. The Clipsal 30 Series Push-Button Dimmer mechanisms features installer interchangeable button caps. Coloured button faces (sold separately) can be used to match the colour of the grid plate being used. Simply pop the existing button cap off using a screwdriver and snap the new button cap in place. 60 Series 4061E2PUDM 1. Remove encapsulated button with narrow object i.e. pen. 2. Replace button with a label button cap. 3. Vertical and horizontal orientation. The Clipsal Saturn Series features encapsulated buttons (selected models). Button orientation can be changed to suit horizontal or vertical mounting. Simply clasp the button front and back, and rotate it into the appropriate locking position. Interchangeable labelled ID button faces are also available (sold separately). 2013 Schneider Electric. All Rights Reserved. 5 of 8

5.0 Set-Up Mode The Push-Button Dimmer allows the user to select various operating characteristics to suit the application and to ensure compatibility with the connected load type. Soft-Start/Kick-Start (default Soft-Start) The user can select a Soft-Start or a Kick-Start to occur at start-up, depending on the connected load type. Start-Up Feature Soft-Start Used for normal light dimming applications providing a noticeably smooth lamp illumination at turn on. This feature also minimises lamp filament start-up stress, which may increase lamp life. Kick-Start When the dimmer is turned on, the output will briefly set to around 75%, before ramping back down to the set brightness level. Used with Dimmable CFL Loads to maximise the probability of lamp strike at turn-on. Also can be used with small motor loads to overcome initial inertia. Minimum Brightness (default setting at minimum) The user can configure the minimum output brightness to provide optimum performance with the connected load. Minimum Brightness Adjustment Feature Decrease the minimum brightness to maximise the available dimming range. Increase the minimum brightness to minimise flickering effects when connected to dimmable CFL and other sensitive lighting loads. When connecting to motor loads, you can also increase the minimum brightness to ensure that the motor starts reliably and does not stall at low speeds. 6 of 8 2013 Schneider Electric. All Rights Reserved.

NORMAL DIMMING OPERATIONS [SHORT PRESS] 5 x WITHIN 1.5 SECONDS SET-UP MODE LED INDICATOR FLASHING SLOW FLASH (1Hz): KICK START DISABLED FAST FLASH (2Hz): KICK START ENABLED SAVE CHANGES AND RESUME NORMAL OPERATION BUTTON PRESS WITHIN 10 SECONDS NO YES [SHORT PRESS] [LONG PRESS] TOGGLE KICK-START [ENABLE / DISABLE] SET NEW MINIMUM BRIGHTNESS 2013 Schneider Electric. All Rights Reserved. 7 of 8

6.0 Load Compatibility The Clipsal 31E2PUDM Series Dimmer is a part of the C-Thru Dimmer range. Each dimmer mechanism is colour coded to indicate load compatibility. LOAD SYMBOL COMPATIBLE LOADS Incandescent Lighting MV Halogen/Dichroic Lamps C-THRU COLOUR 31E2PUDM TRANSPARENT INTEGRALLY SWITCHED, PUSH BUTTON UNIVERSAL DIMMER ISPB Series 350W Low Voltage Halogen/Dichroic Lighting with Iron-Core Transformers 350W Low Voltage Halogen/Dichroic Lighting with Electronic Transformers Dimmable Compact Fluorescent Lamps (Selected makes/models only. Please contact CFL supplier for compatibility advice) 350W 150W Dimmable LED Lighting (Please visit clipsal.com/load for recommended loads. For other loads, contact the LED supplier for compatibility advice.) Small Motor Loads - Exhaust fans (shaded pole induction motors) - Ceiling fans (split-phase induction motors) 150W 350W IMPORTANT NOTES Dimming performance may vary between lamp manufacturers. Use only dimmable CFL/PL/LED lamp types, compatible with phase angle control dimming techniques. Due to the nature of dimmable CFL loads, lamp strike cannot be guaranteed upon start-up. To maximise the probability of successful lamp strike, the kick-start feature may be enabled. Some lamps may exhibit unexpected performance characteristics when cold. Dimming performance should improve once the lamp warms up. It is recommended that when using electronic transformers, each be loaded to at least 75% of its maximum rated load. This reduces the possibility of lamp flicker when dimming which is common with some transformers. Refer to the manufacturer s specifications for the transformer being used. Use only iron-core transformers compatible with electronic switches/phase controlled dimmers as recommended by the manufacturer. Any number of low voltage lighting transformers can be used, providing the total lamp wattage does not exceed the maximum load rating of the dimmer. Mixed load types are permitted, though not recommended. Test thoroughly to ensure normal operation throughout the dimming range. Use at own risk. When controlling small motor loads, occasionally audible noise (hum) may be heard as a characteristic of normal operation. This is largely a function of the motor construction, and is consequently excluded from the warranty conditions provided with this product. This product is rated for indoor use only. It is not suitable for outdoor use or installation in a roof space. Operation from elevated voltages or temperatures may cause the thermal protection circuitry to operate. In the case of significant overload, the thermal fuse may be blown, rendering the dimmer inoperable. This may occur if abnormal operating conditions are detected by the dimmer, even in the case where the lamp wattage does not exceed the dimmer rating. Reduce the size of the connected load or use a different brand of lamp to prevent reoccurrence. 8 of 8 2013 Schneider Electric. All Rights Reserved.

7.0 Incompatible Loads This dimmer is not compatible for use with non-dimmable linear/compact fluorescent lamps. Exercise care when using dimmable CFL/PL/LED load types. Use only lamps/ballasts that are compatible with phase angle control. Refer to the manufacturer s specifications for recommendations. Dimmer warranty is void when controlling incompatible load types as determined by Clipsal by Schneider Electric Australia. 8.0 Installation Instructions CAUTION: Electronic switches such as push-button dimmers do not provide a full off-state. Therefore, the circuit on the load side should be considered to be live. Turn off power at the switchboard before proper installation of the unit. Turn off power at the switchboard when changing the light source. It is illegal for persons other than an appropriately licenced electrical contractor or other persons authorised by legislation to work on the fixed wiring of any electrical installation. Penalties for conviction are severe! 8.1 Wiring Details 1. Disconnect power to the relevant circuit at the main switchboard. 2. Remove existing switch from wall. 3. Connect the dimmer in accordance with the wiring diagram shown on page 10. 4. Refit switch plate to wall. 5. Reconnect power. 6. Operate the dimmer and ensure satisfactory performance throughout the full control range. If necessary, adjust minimum brightness and enable/disable kick-start feature to suit the connected load. 8.2 Multi-Gang Derating For applications, where 31E2PUDM Series Dimmers are multi-ganged, derate the maximum load rating of the unit according to the table shown below. Number of Dimmers per Grid Plate Maximum Incandescent Load per Dimmer Nominal Voltage 240V Nominal Voltage 220V 1 350W 300W 2 240W 200W 3 200W 175W 4 150W 150W 5 125W 100W 6 100W 90W Multi-Gang Dimmer Derating Table 2013 Schneider Electric. All Rights Reserved. 9 of 8

8.3 Thermal Overload Protection Circuitry The 31E2PUDM Series Dimmers incorporate two levels of thermal overload protection: Thermal Overload Compensation Automatically reduces lamp brightness should the dimmer be inadvertently overloaded. Primary defence against overload or short circuit. Resets automatically once overload conditions are corrected. Thermal Cut-Out The unit contains a non-resettable thermal fuse device, designed to blow in case of catastrophic circuit failure. This is a secondary protection measure, intended to operate as a backup in case of persistent or prolonged overload conditions. If the thermal cut-out fuse blows, then the dimmer will be rendered permanently inoperable and must be replaced. Any significant overload should be avoided in order to prevent damage to the load, fixed wiring of the installation or other hardware connected to the affected circuit. 8.4 Short Circuit Protection The 31E2PUDM Series Dimmers feature short circuit protection, designed to protect the dimmer under most abnormal operating conditions and ensure the dimmer can survive in case of wiring fault or catastrophic failure of the load. 8.5 Power-Up Status In the event of a power failure, the dimmer will shut down. Upon restoration of power, the dimmer will always power-up in the OFF state. 9.0 Wiring Diagram A Dimmer LOAD N NOTE The 31E2PUDM Series Dimmers incorporate an integral switch and are designed for one-way operation only. If two-way switching is required, then a separately switched dimmer mechanism must be used (32E450UDM). Two or more dimmers cannot be connected in parallel or series to control the same load from two different locations. Dimmer should be wired using the terminal block supplied. Dimmer mechanism wiring is NOT polarity sensitive. It is illegal for persons other than an appropriately licensed electrical contractor or other persons authorised by legislation to work on the fixed wiring of any electrical installation. Penalties for conviction are severe! 10 of 8 2013 Schneider Electric. All Rights Reserved.

10.0 Electrical Specifications Parameter Nominal Operating Voltage Nominal Operating Frequency Maximum Load Minimum Load Dimming Technique Compatible Loads Value 220 240V 50Hz 350W @ 240V 300W @ 220V Derate for multi-gang applications (refer to table on page 9) 10W Leading Edge/Trailing Edge Phase Control (dynamically auto-selected) Incandescent Lighting Halogen 240V lamps Low Voltage Lighting with Iron-Core Transformers Low Voltage Lighting with Electronic Transformers Dimmable Compact Fluorescent Lamps (selected makes/models only, 150W max.) Dimmable LED Lighting (selected makes/models only, 150W max.) Small Motor Loads Incompatible Loads Non-Dimmable Fluorescent/Compact Fluorescent Lighting Mounting Centres 84mm Australian Pattern Plate Shipping Weight 25g Dimmer Mechanism Only Safety Compliance AS/NZS3100, AS/NZS3133, IEC60669 Series EMC Compliance AS/NZS CISPR15, IEC60669-2-1 (26.1,26.2), IEC61000-3-2 (except when used in conjunction with electronic loads, e.g. dimmable CFL loads) Specifications Typical @ 240V 25 o C Suitable for Indoor Use Only No User Serviceable Parts Inside 2013 Schneider Electric. All Rights Reserved. 11 of 8

11.0 Warranty Statement 1. This Clipsal by Schneider Electric product is guaranteed against faulty workmanship and materials for a period of two (2) years from the date of installation. 2. This warranty is expressly subject to the Clipsal by Schneider Electric product being installed, wired, tested, operated and used in accordance with the manufacturer s instructions. 3. The warrantor is Schneider Electric (Australia) Pty Ltd of 33-37 Port Wakefield Road, Gepps Cross, South Australia 5094. With registered offices in all Australian states. 4. Schneider Electric (Australia) Pty Ltd reserves the right, at its discretion, to either repair free of parts and labour charges, replace or offer refund in respect to any article found to be faulty due to materials, parts or workmanship. 5. All costs of a claim shall be met by Schneider Electric (Australia) Pty Ltd, however should the product that is the subject of the claim be found to be in good working order all such costs shall be met by the claimant. 6. When making a claim the consumer shall forward the Clipsal by Schneider Electric product to the nearest office of Schneider Electric (Australia) Pty Ltd with adequate particulars of the defect within 28 days of the fault occurring. The product should be returned securely packed, complete with details of the date and place of purchase, description of load and circumstances of malfunction. 7. The benefits conferred herein are in addition to, and in no way shall be deemed to derogate; either expressly or by implication, any or all other rights and remedies in respect to the Clipsal by Schneider Electric product, which the consumer has under the Commonwealth Competition and Consumer Act or any other similar State or Territory Laws. Schneider Electric (Australia) Pty Ltd Contact us: clipsal.com/feedback National Customer Care Enquiries: Tel 1300 2025 25 Fax 1300 2025 56 Schneider Electric (Australia) Pty Ltd reserves the right to change specifications, modify designs and discontinue items without incurring obligation and whilst every effort is made to ensure that descriptions, specifications and other information in this catalogue are correct, no warranty is given in respect thereof and the company shall not be liable for any error therein. 2013 Schneider Electric. All Rights Reserved. Trademarks are owned by Schneider Electric Industries SAS or its affiliated companies. F2248/05 CLIPCOM 26081 May 2013