conventional system operation



Similar documents
Fire Detection Systems

D287/D288/D292/D293A/D293E

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

AlarmSense 2-wire detection and alarm system. Product Guide

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

INTRODUCTION. The data provided is for The Standard Products and any variation will be dealt with at the end of this manual.

(68.52) X. June 2000 Supercedes February xenex CONVENTIONAL FIRE DETECTION & ALARM SYSTEM. we business differently

FIREDEX Conventional Fire Panels

Fire detection equipment

Fire. The Fire Installers Mate. A guide to fire alarm systems design

SFC-200 SERIES LCD FIRE ALARM PANEL

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

Reversing starter circuit for single phase induction motors Updated 1 st September 2008

CB200W Water Leak Detection Panel Application Guide

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

Conventional Fire Detection and Extinguishant Control System Specification

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

EDA-Z5008 & Z5020. Radio Fire Alarm System. User Manual

FC-72 SERIES FIRE ALARM SYSTEM

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February FA-300 SERIES Fire Alarm Control Panel

LPCB APPROVED CFP 2/4/8 ZONE FIRE ALARM CONTROL PANEL. installation & maintenance manual. Approved Document No. DFU Rev 1

CENTERLINE Motor Control Centers Bulletin 2100 Smoke Detector Unit

FIRE ALARM SYSTEM RECORD OF COMPLETION

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

A.1. a Division of Pittway Corporation. Documento: M MGAS-ENG. Edizione: 01/1997 Rev.:

ACTIVE 5 ENGINEERING MANUAL

FIRERAY 2000 Installation Guide

CFP 2/4/8 ZONE ECONOMY FIRE ALARM CONTROL PANEL. installation & maintenance manual. Approved Document No. DFU Rev 1

Premier M Plus & Infinity 8

FIRE ALARM SYSTEM RECORD OF COMPLETION

rpsa FIRE PROTECTION ENGINEERS

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS

Chapter 9 N.C. C. N.O. Single-Pole Double-Throw

Fire Alarm Control Panel. Family. Operating Manual

3. MOUNTING THE FIRE ALARM PANEL PLANNING CABLE ENTRY 3.2 FIXING THE BACKBOX TO THE WALL

Advanced Intelligent Modules. Overview. Description

TS510 & TS500. Installation & User Guide. Compatible Equipment

SECTION DETECTION AND ALARM

SSPI-APPN OTES: PARALLEL C ONNECTIONS

GST301. (Single Protection Zone) Operation Manual

AUTODIALLER / QUICKDIALLER - SA132

MSL1000 Monitored Serial Link Interface Manual V1.01

9452/9453 Installation and User Guide

PLAN REVIEW GUIDE FOR FIRE ALARM

CB Zone Conventional Control Panel

RP1r. Extinguishing Control Panel. User Manual (Software version 3.x) 3 zone control panel to protect 1 extinguishing risk

ANTI-THEFT SYSTEM Volvo 850 DESCRIPTION & OPERATION BASIC ALARM ACCESSORIES & EQUIPMENT Volvo Anti-Theft Systems

WD-AMX Water Detection Controllers

VEHICLE THEFT/SECURITY SYSTEMS

FIRE ALARM PANEL & SYSTEM OPERATION ID50 SYSTEM. The Fire Alarm System can be activated in the following ways :~

GSM ALARM SYSTEM USER MANUAL

IPX AUTOMATIC IP NETWORK LOSS BACKUP A/B SWITCH INSTRUCTION BOOK IB

Reyrolle Protection Devices. 7PG17 - XR Intertripping, Interposing, Supervision and Special Purpose Relays. Answers for energy

SILENT KNIGHT MODEL 5207

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

DELAWARE STATE FIRE MARSHAL FIRE ALARM SYSTEM CERTIFICATE OF INSTALLATION

25 Years of Manufacturing Excellence. Premier Quatro Addressable Fire Alarm System. Assessed to ISO 9001: 2008

GROUND DETECTION CIRCUITS FOR STATIONARY APPLICATIONS (IN PLAIN DOWN TO EARTH LANGUAGE)

The Challenger Version 8 User Guide

INTERFACING SECURITY SYSTEMS TO HOMEVISION

E-PDD Duct Smoke Detector Installation Sheet

SECURIT 800L+ CONTROL PANEL

Mobile Device Power Monitor Battery Connection Quick Start Guide

Fire & Security DETECTORS

Product Guide. Low voltage grounding system. Answers for industry.

BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEMS BURGLAR ALARM SYSTEM EURO ALARM WIRELESS BURGLAR ALARM SYSTEM OASIS

Original Document 10/16/07 Revised 01/30/09 2 nd Revision rd Revision- 12/18/14

Small Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work

Fire Alarm FAQs. Q: How many zone/circuit fire alarm panel do I need? Q: What candela strobes do I need?

User s Information Guide R1A

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

HM-W536 Install Guide

PFC-6030 Fire Alarm Control Panel

FIRE DETECTION AND ALARM SYSTEMS

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

ESL 1500 Series Fire Alarm Control Panel Installation and Operations Manual

Digital Keypad Use s Manual

Planning Instructions MEW01351 Revision -

ALARM ANNUNCIATOR ME INSTRUCTION MANUAL

INSTALLATION MANUAL PC2525. Version 1.1

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions V1 Rev A 11/12)

Manual for Fire Suppression & Methane Detection System

FireSeeker Fire Alarm Control Panel Model FS-250 Programming Manual

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

Fire Detection Product Range

Control/Communicator Installation Manual

..OR How To Protect your 3-Phase Equipment Investment with 3-Phase Monitors from Time Mark...

AM100 SECURITY SYSTEM INSTALLATION INSTRUCTIONS

Proposed changes to the Acceptable Solution for Building Code clause F7 (Warning Systems) Proposed amended Acceptable Solution for Warning Systems

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

INSTALLATION MANUAL CONTENTS

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description

INFINITY 8 INSTALLATION MANUAL FIRE ALARM CONTROL PANEL INSTALLATION MANUAL

Installation Manual for D1110 DigiCom2

Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

D200+ Auto-Dialler Installation/Operators Manual

DTW Works Master Specification Version 2006

Understanding Emergency Power Off (EPO)

Consultant s Guide for Designing Fire Detection & Alarm Systems

Transcription:

conventional system operation detection line operation Conventional detection systems normally operate on a 24VDC line. In the standby condition, the detectors will draw a low current, typically less than 100µA. When the detector senses a fire, it will switch into the alarm condition with it's LED illuminated, and will collapse the line voltage by drawing a larger current - dependant on the detectors and control panel, but typically 50-80mA. The control panel can sense this, and activate the appropriate alarms. The detector will remain latched in the alarm state with its LEDs illuminated, even if the smoke or heat is removed until it has been reset from the panel by momentarily removing power from the line. This allows the fire to be located even if the signal is intermittent, or to locate possible sources of nuisance alarms. For some control panel - detector combinations, when a standard base is used, there is an incompatibility between the current specifications of the detector and panel, leading to incorrect reporting by the control panel, for example signalling a fault in place of an alarm, and in some cases damage to the detector due to over current in the alarm state. In these cases it is necessary to use a base fitted with a resistor in series with the detector to limit the current draw in alarm. Resistors fitted into the detector base are also used in some cases to distinguish between a short circuit fault and an alarm. The value of the base resistor is dependant on the control panel, however a typical value is 470 Ohms. If in any doubt, contact the control panel manufacturer who should be able to specify which detector bases should be used with different detector brands. A manual call-point consists of a simple switch with a resistor in series with it, usually 470 Ohms or 680 Ohms. When the call point is activated, the resistor is switched across the line, and a current of 50-80mA, dependant on the control panel, is drawn. +24V 0V Figure 2: Resistive end of line operation Contact Closed when detector inserted in base detection line fault monitoring Standard conventional systems are able to monitor the zone for short circuit, open circuit and detector head removal. When a short circuit occurs on a zone, a high current will be drawn, and the line voltage will be pulled towards zero volts. The panel detects the low voltage/high current and a fault is signalled. In order to detect an open circuit, or detector head removal, a device is connected across the end of the zone, which can be monitored. This device can take various forms dependant on the control panel. Resistor 5

The simplest end of line device is a resistor, which will draw a current distinct from the quiescent and alarm currents drawn by the detectors. Installation of detectors into their bases closes a contact in the base supplying the remainder of the zone. Thus if the line is broken, or if a detector head is removed, the current drawn by the zone will fall, and a fault will be signalled (See figure 2). Example zone current and voltage figures are given in figure 3. Condition Open Circuit Normal Fire Short Circuit The problem with a simple resistive end of line is that should a detector head be removed, the remainder of the zone beyond that detector is lost and no alarm can be signalled beyond this point. Should a call point be mounted beyond the +24V 0V Contact Closes when detector inserted in base removed detector, it will no longer work, which contravenes the requirements of BS5839 part1. To overcome this either all call points must be mounted at the start of each zone, or in completely separate zones (both of these solutions are often impractical and too costly), or head removal monitoring can be employed. Active monitoring uses bases fitted with a diode across the contact in the base (fig 4). Whilst the detector Monitoring of detection line (example only) Current <3mA 5mA (dependant on EOL device) 50mA (dependant on control panel) High (dependant on control panel) Figure 3: Example resistive conventional system current and voltage figures Figure 4: Active end of line monitoring circuit is mounted in the base, the base contact connects directly across the diode, and links it out. There is usually provision for manually linking the diode out to permit continuity testing during commissioning. When the detector E.O.L. Voltage 24V 18V 4-15V 0V head is removed, the diode is connected across the contact, allowing power to continue to be supplied to the remainder of the zone, whilst still permitting the removed detector to be monitored. This is achieved in a number of ways. An active end of line device uses a switched resistor at the end of line and can thus be used with a standard control panel. It sends a periodic signal back along the detection line, which is normally quenched by the control panel. When a head is removed, the base diode is switched into the line, and pulse can be seen. The Active end of line then switches the resistor out of the line, and a fault is signalled. If a capacitive end of line is used, the panel periodically drops the line voltage for a few milliseconds, and looks for the line voltage being held up by the capacitor. When a head is removed, the panel will see the line voltage drop immediately as the capacitor's discharge will be inhibited by the diode, and thereby a fault can be signalled. A third type of end of line device is a diode. With this the panel periodically reverses the line voltage for a few milliseconds: If the line is broken by the diode in the detector base, then no current can flow in the reverse direction. The type of end of line monitoring used on a system will depend on the control panel. However it is important, particularly when using active end of line monitoring 6

to ensure that the detectors are compatible with the type of monitoring being used. Reference must be made to the panel manufacturer to ensure compatibility. remote LEDs Most system smoke detectors are equipped with a terminal to allow the connection of a remote LED. Remote LEDs are often used outside bedroom doors in hotels so that in case of a fire, it is easy for the fire brigade to identify the location of the fire without needing to enter every room in the building. They may also be used where a detector is located in a hidden position, such as a floor or roof void or cable tunnel, for example, to provide a visual indication that the detector is in an alarm state. wires, see figure 5. In this instance, a base incorporating a change over relay is used. This configuration is known as a four-wire system, and is often seen when a fire zone is integrated into a security panel. Figure 5 shows the simplest form of four-wire system, as used with most security panels. This is used where the monitor line is able only to register an open or closed circuit - there is no distinction between a fault and a fire. By using a normally closed relay at the end of the power line, it is possible to monitor for a power failure to the detectors. The MAINTENANCE RELAY (N/C) +24VDC IN FAULT RELAY (N/C) 24VDC OUT - 24VDC IN + 24VDC OUT - ALARM RELAY (N/O) relay contacts are wired in series with the normally closed contacts of the detector relay base(s). Thus in the normal state the detection circuit is closed; in the case of fire or power failure the relevant relay contacts will open. Normally after an alarm, the detectors are reset by disconnecting the power to the relevant zone for a short period by pressing a central panel reset button. Fire panels have this facility built in, however many security panels are unable to do this without turning the entire panel off. Therefore to allow the use of MAINTENANCE RELAY (N/C) +24VDC IN - 24VDC IN FAULT RELAY (N/C) - - 24VDC POWER SUPPLY END OF LINE + 24VDC RELAY COIL BEAM DETECTOR #1 24VDC OUT + 24VDC OUT BEAM DETECTOR #2 ALARM RELAY (N/O) four-wire system operation In some cases it is necessary that the power to the detectors and the fire detection signal be on separate DETECTION CIRCUIT Resistor Resistor EOL Figure 6: 4-wire system with full monitoring Detection Line (Open Circuit for Alarm and Fault) FIRE ALARM CONTROL PANEL Power Supply (Nominal 12V or 24V System) C NO NC C NO NC End of Line Monitoring Relay detectors with security panels, non-latching versions of the relay bases are usually made available, which automatically isolate the detector from the supply every few seconds. Thus once the fire condition has passed the detector will automatically reset (note that the alarm condition should be latched at the control panel.) Figure 5: Typical 4 wire system wiring Four-wire type systems are also often used with devices such as beam detectors where an auxiliary 7