LVA Take Offs in Bid Manager



Similar documents
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:

UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation

FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid

SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.

Sample - No Commercial Use

Masterclad Medium Voltage Passive Arc-Resistant Switchgear

Secondary Unit Substations

SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions

8146/5 Series Breaker Panelboards

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

QUESTIONS and ANSWERS RFB , Metal Clad Switchgear and Power Control Room

Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services

The following components are common to most cubicles; this example is an ABB HK cubicle.

Decision-Maker Paralleling System. Power Distribution Switchboards and Circuit Breakers. Standard Features

SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR

Bolted contact switches. Pringle switches

SECTION 16426C ARC RESISTANT DRAWOUT SWITCHGEAR (MAGNUM DS) LOW VOLTAGE

BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET

SECTION POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL

Tmax MCCBs. Molded case circuit breakers. Tmax

Primary and Secondary Electrical Distribution Systems

Arc Terminator Active Arc-Resistant Switchgear

PIP ELSSG02 Design and Fabrication of Medium Voltage Metal-Clad Switchgear from 4.76 kv to 38 kv

Instructions for Magnum DS T

How To Test A Power Switch On A Power Supply

Introduction. Upon completion of Basics of Switchboards you should be able to: Explain the role of switchboards in a distribution system

MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV

MCC Ratings. Voltage Rating

IRRIGATION PUMPING Table of Contents - Section 900

SENTRON Switching and Protection Devices Air Circuit Breakers

Suitable for Emergency, Peak and Prime Power System Applications. Low Voltage Automatic Transfer Switch Systems

01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A

LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE

Learning Module 13: Panelboards and Switchboards. 101 Basic Series

Doc Ref: baselayer.com 2015 BASELAYER TECHNOLOGY, LLC

3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & Instructions For Installation, Operation & Maintenance

Sentron Series Circuit Breakers

Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms

Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.

CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH

Masterpact NW Circuit breakers and switch-disconnectors from 800 to 6300 A

Installation Instructions

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

Unit substation solutions with type SIMOSEC primary switches quick reference guide E50001-F710-A389-X-4A00. Answers for energy.

Extend the Life of Existing Switchgear

Reverse-feed applications for circuit breakers

Unified requirements for systems with voltages above 1 kv up to 15 kv

Contents. Description. Product Selection Guide

A. Shop Drawing submittals shall include, but not be limited to, the following:

Distribution Dry Type Transformers

Mini Power-Zone Unit Substation

Enhancing Personnel Safety with Arc Resistant Equipment

SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B

Cabinets 101: Configuring A Network Or Server Cabinet

Generator DoCKInG StatIonS

INDUSTRIAL AND COMMERCIAL SERVICE TRANSFORMER & METERING INSTALLATION SPECIFICATION

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

Mini Power-Zone Unit Substation Product Description. Product Description. Features. Typical Applications

Miniature Circuit Breakers and Supplementary Protectors

Dimensions, Inches (mm) No. of Poles Width Height Depth 2, (210) 16 (407) 5.5 (140) (283) 16 (407) 5.5 (140)

Part 1 System Modeling & Studies for Existing Systems

Eaton Safety & Reliability Solutions in the Oil & Gas Industry Electrical

SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches

Power-Zone 4 Arc Resistant Low Voltage Switchgear

PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors

A Comparison of Contemporary Electrical Distribution Equipment Standards. San Francisco IEEE Industry Applications Society May 26, 2009

Medium voltage VCP-W MR2 (integral racking)

SHORE POWER. Safely Connecting Ships to Shore SAFETY QUALITY INNOVATION VALUE CUSTOMER SERVICE

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

INSTALLATION INSTRUCTIONS

Instructions for Eaton 7.2kV AMPGARD Arc Resistant Motor Control Centers

Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution

How To Get A Power Line Extension

Low Voltage Switchgear

Circuit Breakers. Next Generation of Protection Capabilities

ELEKTROTEHNI KO PODJETJE Leskoπkova cesta 12, 1000 Ljubljana, SLOVENIA

HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

Masterclad 5 15 kv Arc Resistant Metal-Clad Indoor Switchgear

e 2 ALPHA Medium Voltage Switchgear Data Sheet K EN

Engineers Edge, LLC PDH & Professional Training

GE Power Controls. MiniFORM Switchboards

DATA CENTER UNIQUE CHARACTERISTICS AND THE ROLE OF MEDIUM VOLTAGE VACUUM CIRCUIT BREAKERS

Power IT MV Air Insulated Switchgear. Technical Information and Application Guide Featuring Advance TM and SafeGear TM Technology

IZM ACB/Circuit-breakers. Robust safety. Extract from Main Catalogue HPL2010 IZM26 Circuit-breakers IN26 Switch-disconnectors

TP-C2 Motor Operator CLEAVELAND / PRICE INC. Bulletin DB-111B12

OVR-3SP Recloser with PCD Control Style Guide 1VAL SG March 30, 2009 Revision B

Eaton s E-Series protective relay family

Atlanta Chapter IEEE Industry Applications Society

Bypass transfer switch mechanisms

-1- SPECIFICATIONS CONE SETTER PLATFORM ATTACHMENT INDEX

Alternate Methods to Short Circuit Breaker Coordination

Top Commercial / Residential Electrical Requirements *

Power Plant Electrical Distribution Systems

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers

GROWTH MANAGEMENT DEPARTMENT 201 SE 3 rd ST, (Second Floor), Ocala, FL (352) ; FAX: (352)

SECTION LOW VOLTAGE LIGHTING CONTROLS

UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution

Transcription:

Electrical Sales and Distributor Training Low Voltage Assemblies (LVA) LVA Take Offs in Bid Manager This job aid helps to define some of the common selection questions that are encountered when configuring Low Voltage Assemblies (LVA) in Bid Manager. System Tab Guide 100% neutral should be selected when 4 wire loads are required. None should be selected when high resistance grounding is required. UL1558 and UL891 are available in drawout construction. Magnum DS breakers are provided in UL1558 and Magnum SB breakers are provided in UL891. PRLC Switchboards can be integrated into either UL1558 or UL891 assemblies and the PRLC structures will always be labeled UL891. See the Consulting and Application Guide (CAG) for breaker details. Typical service voltage is 480V or 480/277V. 600V rating has limited breaker options, see CAG for breaker details. Selection of voltage and short circuit (kaic) have implications on available layouts when arc construction is required. This is the interrupt rating of the gear, kaic. The interrupt rating determines the lowest possible breaker rating available in the gear. Short circuit (kaic) have implications on available layouts when arc construction is required. Select other to have all possible options available when using the layout tab. Provides notes on the bill of material (BOM), consult your district sales engineer (DSE) prior to selecting. Select 4 wire and neutral (#3) as none when high resistance grounding is required. This determines the number of incoming connections, not necessarily the distribution, load and connections. This is the main, horizontal, bus. The bus is not tapered, and the vertical risers may be rated less than the main bus unless otherwise noted. Configure close coupled connections to transformers, other gear and other equipment. Contact your district sales engineer prior to proceeding with any selection other than an Eaton-sourced transformer. Typical hertz is 60 for North America. Consult your district sales engineer prior to selecting 50. Select Power Xpert Gateway. Selection of non-standard nameplate background and text colors. Contact your district sales engineer prior to proceeding. Select miscellaneous control devices including customersupplied control power and 86 lockout relays.

System Tab Guide Insulation selection is for epoxy coated (3 mil thick) bus with insulating boots over maintainable joints. This is an environmental insulation system, and the epoxy coating does not provide electrical insulation. The neutral and ground busses are never insulated. This is not fluidized bed insulation. Insulation is not required to achieve required electrical clearances in Eaton Low Voltage Switchgear. Insulated runbacks only are selected on the options tab. Standard thicknesses of silver and tin plating. 0002 thick silver plating is not provided as standard, contact DSE prior to proceeding. Contact sales engineer prior to proceeding with any selection other than standard. 1000A/sq.in. is not standard. Standard bus bracing (not interrupt rating, kaic) is 100ka. 150ka is available on all orders. 200ka bus bracing rating is only available when used in conjunction with 200 kaic systems and 200kaic breakers. Do not use. Ground bus options. Contact sales engineer prior to proceeding with any selection other than standard. Contact your district sales engineer and the Consulting and Application Guide for details of layout requirements for arc construction. Select type 2B, do not select type 2. Type 2B secondary door above the breaker is standard with 2B selection. Arc exhaust defaults to direct vent to room. Exhaust plenum and additional exhaust duct are selected on the option tab. Structures Tab Guide Enclosure type become active if NEMA 1 or EEMAC/N/A is selected within structures type. Labeled per UL requirements. Meets all seismic requirements of the California Building Code for zone and application. 54-90 is rear access. 54-66 has limited cable space depending on the number of breakers chosen in each structure. Recommend 72 or deeper for proper cable spacing. Floor plate material becomes active if floor plates is selected. Check to include screens and floor plates in gear. Filtered louvers is automatically checked when outdoor gear is selected. Check to include screens on all vents. Becomes active if cable selection pull box is checked. Two depths are available 18 and 30 inch.

Structures Tab Guide Default is incandescent, optional is florescent. Becomes active for NEMA 3R gear, check when required. Interior default. Exterior default. Used to secure gear to housekeeping pad. Wiring Tab Guide Mainly used by OEM customers. Consult factory for confirmation. This option is selected based on customer spec, where a greater degree of flame retardancy is desired and tested. This selection is for the type of terminals required (standard, ringtongue or locking fork). Ring-tongue Locking-fork Once these selections are set, voltage selections in the breaker takeoffs will be automatically filled-in. This selection is for the type of terminal blocks required (standard, heavy duty or states). If states terminals are required, make sure there is enough instrument space in the lineup for allocation. Consult factory for confirmation and details.

Lugs/Mimic/Transfer/CPT Tab Guide This selection is for the type of lugs required (mechanical or compression). The actual size of the lugs are to be specified in the breaker takeoff. This selection is for the type of GND lugs required (mechanical or compression). This selection is for the type of mimic bus required. Always offer plastic screw-on type. Size is 3/8 standard. Colors red and black are standard. All other colors are considered special and should consult with factory for availability and pricing. When applicable, must check the box to make selection active before selecting desired scheme. This option gives you the ability to select multiple sources. With only (1) main breaker, a single source control power would be appropriate. If there are multiple power sources in the lineup with a transfer scheme, then you have the option to choose more than one. It can also be customer supplied control power if external source is available. Trip units other than DT520 require control power. Accessories Tab Guide Circuit breaker not shipped in the assemblies. This selection should be used when requested by customer. Breakers will be shipped outside of the switchgear in their own individual packaging. Overhead breaker lifter is included by default. The lifter is removed when NEMA 3R aisle-less enclosure is selected under structures. This option is used when space heaters are required. Default is 3 heaters per structure, placed in breaker, bus and cable compartments. Maximum of 5 structures per thermostat. Quantity of thermostat needs to be increased when there are 5+ structures in the lineup. Voltage can be selected as 120 or 240VAC, switchgear or customer supplied. If switchgear supplied, then it will impact sizing of the CPT.

Breaker Tab Guide Greyed-out fields containing text values are non-selectable and typically driven by other selections within the takeoff. Pay close attention to short time rating spec requirements, especially when MDN breakers are selected. At higher short circuit ratings, MDN short time ratings may be significantly lower than MDS ratings. When MDSL breakers with current limiters are selected, short time current will be blank (limiter selection will determine short time). Manual (MO) is the default selection. When changing from manual (MO) to electric (EO), go to control/options tab and select appropriate control switch and indication. When changing from EO to MO, go to control/options tab and set the breaker control switch to none. Provision - does not contain a breaker, but is fully equipped to receive a breaker without field conversion (plug and play). All secondary wiring is included with this option as well. Space - does not contain a breaker. Contains connections to riser bus, but no breaker cell. Requires field conversion and secondary wiring to accept a future breaker. The plant recommends using provisions in lieu of spaces, unless there is a specific reason to utilize a space. Storage compartment - used specifically for storing a spare breaker in a lineup. Cannot be converted to an active breaker. Interrupt rating defaults to minimum short circuit rating selection from system tab. In some cases, a higher rating may be selected here if needed. When 200KAIC is required, frame type must be set to standard frame. Breaker frame rating. Determines MDS or MDN frame. Consult factory when 4 pole configurations are required. 4 pole breakers should only be configured with MDS frame (not MDN). 520MC or 1150 must be used when ARMS feature and/or communication is required. Nonauto may be selected when specification requires external relay protection (available up to 85kA max). Set sensor and trip ratings as needed per customer specific requirements. Trip function should be set to LSI when system is Delta, or when there is an HRG in the system. Does not affect pricing. All trip units are provided with instantaneous feature, whether checked or not. This field is currently n/a. Service entrance is selected under the structures tab. Configures digitrip power supply (DPS) voltage for 520M, 520MC, and 1150 trip units. 120-VAC is the default value unless preselected to a different voltage on the wiring tab. Only applicable to MDSL breakers. Default limiter selections are automatically populated. Based on frame/sensor rating. Some configurations allow changing the limiter size to meet specific coordination requirements. Refer to CAG Section 26.1-10 for information regarding alternate selections and limiter characteristics. This selection will include a compartment (din-rail) mounted cap trip accessory. When cap trip box is checked, the shunt trip voltage under the related control/options tab will be fixed to 208V-250VAC/DC. Will be automatically set according to system tab (wye or delta, and 3W or 4W) selections, and trip function on this tab. For 4-wire systems that have 3-wire feeder loads, the default selections may be overridden. Source ground requires special consideration. If source or single point T ground system is required, consult the factory. Applicable to 1150 trip unit only. Allows user to configure whether PT connection is internally wired to the line side (upper terminals) or load side (lower terminals) of the breaker. The default is upper terminals and should generally not be changed except for special circumstances, such as when breaker is reverse-fed.

Breaker Tab Guide Cable quantities are pre-selected based on frame / sensor ratings. Phase / Neutral lug sizes default to 500kcmil cable. Sizes and quantities may be adjusted as necessary for the application. Use other when manual size and quantity selections need to be made. Cable is typically checked by default for mains and feeders. De-select when breaker is to be close-coupled to a transformer, or when busway connection is desired. The default selection will be determined by whether neutral has been selected on system tab. This selection will not be automatically updated if neutral is added (or removed) after breaker has been placed in the lineup. This determines line or load side cable terminations. The default setting for mains is line Side, and load side for feeder breakers. Both Line and load cables can be selected for special applications, such as single breaker cable in/cable out scenarios. However, the both line and load selection will not necessarily drive an accurate one line representation. If the breaker is to be busway connected instead of cable connected, the cable connection should first be unchecked. Typically, busway coordination details such as T direction and line number are unknown until after order entry. These details should not be pre-selected by sales unless coordination has been determined in advance. The following are limitations when busway connections are required and always consult the factory if there is any question regarding busway layout requirements: No A position busway connection is allowed when busway is top entry. Likewise, no D position allowed for bottom entry. When (top entry) busway connected breakers are stacked in the same vertical section with cable connected breakers, the busway connected breaker must be located above cable connected breakers. Contact the factory if two breakers stacked in a vertical section require busway connections. This situation can usually be accommodated with 84 or 90 depths. Non-segregated busway connections are preferred with arc-resistant switchgear assemblies. Contact the factory when non-segregated busway or non-eaton vendor is required. Non-segregated busway typically requires more layout consideration than Powerway III. 5000A connection maximum is currently available. Contact the factory for applications requiring >5000A busway connections. Contact the factory when aluminum busway is requested.

Breaker Tab Guide All breaker control voltages may be pre-selected by settings on the wiring tab. If control voltages are known, they should be set prior to populating breakers. Otherwise, the default setting is 120VAC, or 120VAC/DC for dual rated accessories. Motor, spring release, spring charge light applicable to EO breakers only. If second shunt trip is required, a maximum of 4a/4b aux contacts are available. Undervoltage (UVR) accessory is typically used for special applications, such as for E-Stop circuits or generator breaker applications. If spec requires an undervoltage trip, an 1150 trip unit with UPS or DC control should be considered in lieu of selecting UVR accessory. Latch check options provides indication that breaker is charged and trip latch is not engaged, or may prevent close signal from being applied until breaker is ready to close. Consult breaker IL for further details. Standard control switch and LED type is Eaton E34. When target and/or pistol grip switches are required per spec, W2 selection may be used for pricing purposes. In these cases (whenever possible), it should be noted in spec clarification that Electroswitch series 20 or 31 is preferred. W2 or Series 24 will not fit in breaker secondary compartment and require separate instrument compartment mounting space. Status lights may be selected for LED indication with MO breakers, or EO breakers with only remote open/close operation. White status LED supplied above breaker when selected. LED and remote contact supplied breaker when selected. These options typically auto-populated by other field selections. When selected in conjunction with UVR, includes separate instrument compartment (din rail) time delay module with selectable values of.1,.5, one and two seconds. Should only be used for specific applications. Indicator selection includes mechanical pop-out flag only. Select indicator with 2-Form C contacts, when local LED or remote overcurrent trip indication is required, or for any applications requiring multiple breaker interlocking. Set auxiliary contacts per specification requirements. For multiple breaker interlocking applications, 6a/6b contacts should be used. Set cell switch contacts per specification requirements. For multiple breaker interlocking applications, select 8-Form C cell switch contacts. Selectable when called for per specification requirements. Adds E34 2-position switch with padlockable cover and 30mm blue LED (located in compartment above corresponding breaker). Adds interposing relay in breaker wire way for remote activation of ARMS and local 30mm blue LED (located in compartment above corresponding breaker). Optional selection for EO breakers which are interlocked, or when pb close / open operation needs to be inhibited or padlocked out. Kirk is the default (and preferred) vendor for key lock when required. Note that key lock / cylinder assembly is cassette mounted in LVA assemblies (not breaker mounted). Only selectable when small remote control box is checked from the options tab. Includes wired receptacle for remote plug in in secondary compartment above corresponding breaker. If selected, trip units will be factory wired for zone interlock. Default selection for electrically interlocked breakers. Includes steel block plate over manual close pushbutton. Contact the factory if these selections need to be altered. Mechanical counter. Select when required per specification.

Eaton 1000 Eaton Boulevard Cleveland, OH 44122 United States Eaton.com 2015 Eaton All Rights Reserved Printed in USA October 2015 Eaton is a registered trademark. All other trademarks are property of their respective owners.