Electrical Systems. <Presenter>

Similar documents
Data Center Energy Efficiency. SC07 Birds of a Feather November, 2007 Bill Tschudi wftschudi@lbl.gov

Energy Efficient High-tech Buildings

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

Data Centre Testing and Commissioning

Data Center Energy Profiler Questions Checklist

Yam Hong 施 耐 德 電 機 亞 太 日 本 區 (APJ) 三 相 關 鍵 電 源 市 場 開 發 經 理. Schneider Electric - Division - Name Date

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY

Data Center Energy Use, Metrics and Rating Systems

Qualitative Analysis of Power Distribution Configurations for Data Centers

Opportunity of Energy Saving in electrical path is lesser as compared to other areas

Calculating Total Power Requirements for Data Centers

Energy Strategic Plan Los Angeles Community College District Community College League Conference

The Different Types of UPS Systems

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0

The Different Types of UPS Systems

UNINTERRUPTIBLE POWER SUPPLIES >9900AUPS UNINTERRUPTIBLE POWER SUPPLIES

The Different Types of UPS Systems

High-Efficiency AC Power Distribution for Data Centers

DOE Data Center Energy Efficiency Program

ENERGY EFFICIENT DATACENTERS ELECTRICAL DESIGN

Phase Modular Finally the benefits of Modular ups are for all

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers

Re Engineering to a "Green" Data Center, with Measurable ROI

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint

Mixing Sodium and Lead Battery Technologies in Telecom Applications

Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary

Alternative data center power

Data Center Facility Basics

Recommendation For Incorporating Data Center Specific Sustainability Best Practices into EO13514 Implementation

DC UPS. RTB.e A. IMB.e/ITB.e kva. E2001.e/E3001.e kva. Input voltage: 110/125/220 Vdc. 115/120/230 Vac, 1-phase (IMB.

Managing Data Centre Heat Issues

Green Computing: Datacentres

(EMR) system in resource-constrained settings. The use of the EMR at point-of-care (POC)

Power Management of Cell Sites

Increasing safety, reliability and efficiency for today s data centers

National Grid Your Partner in Energy Solutions

Energy Efficiency and Availability Management in Consolidated Data Centers

Intelligent Power Distribution in the Data Center

The Quest for Energy Efficiency. A White Paper from the experts in Business-Critical Continuity

Electrical Efficiency Modeling for Data Centers

Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications

Data Center Combined Heat and Power Benefits and Implementation. Justin Grau, Google Inc. Sam Brewer, GEM Energy

Green Computing: Datacentres

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

CRITICAL COOLING FOR DATA CENTERS

Server Technology, Inc.

Public Overview of the EMerge Alliance Data/Telecom Center Standard Version 1.0

Recommendations for Measuring and Reporting Overall Data Center Efficiency

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

Data Centers: How Does It Affect My Building s Energy Use and What Can I Do?

High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.

Totally Integrated Power SIESTORAGE. The modular energy storage system for a reliable power supply.

NO-BREAK KS 7e. Concentrated Energy kva (50Hz) 3000 kva (60Hz) DIESEL ROTARY UNINTERRUPTIBLE POWER SUPPLY SYSTEM

Power protection for data centers

COMPARATIVE ANALYSIS OF DATACENTER ELECTRICAL DISTRIBUTION ARCHITECTURES. Emmanuel J. Taylor

415V DISTRIBUTION FOR GREEN DATA CENTERS

Selecting a UPS Topology for your Data Center. by Dr. Daniel Becker, Ph.D., Methode Active Energy Solutions

ALL STAR ELECTRIC COMPANY 10,000 Trumbull SE, Suite #F Albuquerque, NM (505) voice & fax NM License

SiteRanger tm. Power quality / site monitoring. Comm/net Systems, Inc.

Power to the adaptable data center

Power Quality. Uninterruptible Power Supply

AC versus DC Power Distribution in the Data Center

Analysis of the Brazilian Data Center Power Supplies Market

Guidance for Calculation of Efficiency (PUE) in Data Centers

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics

Recommendations for Measuring and Reporting Overall Data Center Efficiency

An Improved Architecture for High-Efficiency, High-Density Data Centers

Emergency Power System Services Industrial UPS, Batteries, Chargers, Inverters and Static Switches

Welcome to the Tripp Lite UPS Systems Basics training module, part of Tripp Lite's "Products Expert" training course Tripp Lite.

Wireless Networks and Power Quality

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems

Data Center Technology: Physical Infrastructure

POWER EQUIPMENT AND DATA CENTER DESIGN

Reducing Data Center Loads for a Large-Scale, Net Zero Office Building

Increasing Data Center Efficiency by Using Improved High Density Power Distribution

Eaton 93PM UPS Where aesthetics meet intelligence.

47000 SERIES - ELECTRONIC TRANSFORMERS

BCA-IDA Green Mark for New Data Centres Version NDC/1.0

415V DISTRIBUTION FOR GREEN DATA CENTERS

GREEN DATA CENTER DESIGN

Tough Decision: On-Line or Line-Interactive UPS?

Residential & Commercial Use Of DC Power

UPS For Efficient Data Data Centers Centers

Optimum Climate Control For Datacenter - Case Study. T. Prabu March 17 th 2009

Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

UPS Applications and VRLA Battery Sizing

Overview of Green Energy Strategies and Techniques for Modern Data Centers

White Paper: Pervasive Power: Integrated Energy Storage for POL Delivery

Is an energy-wasting data center draining your bottom line?

Transcription:

<Presenter>

Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help.

ENERGY INEFFICIENCY OF DATA CENTERS ROOT CAUSES Physical Infrastructure is way OVERSIZED Power Requirements are greatly OVERSTATED Many Legacy INEFFICIENT Equipment are Incorporated Multi-stages of POWER CONVERSION Why did that happen

ENERGY INEFFICIENCY OF DATA CENTERS ROOT CAUSES (continue) Electrical Infrastructure: System Configuration Criteria: - Focus on Increased Reliability & Uptime to 99.999% - Fault Tolerant Design / Sizing Concept: - Designed IT Load based on IT Nameplate plus future growth - Data Center Floor Area based on Designed IT Load / (5-100 W/SF) - UPS System Rating based on Designed IT Load + (20 50%) - Standby Generator Sizing based on UPS system rating x 2 ++ - Lights based on (3 W / SF) x Data Center Floor Area - Physical Rooms size(s) of UPS / Battery / Switchgear based UPS systems physical sized ++ Power Protection: - Relying on UPS Power for voltage regulation and back-up Purchasing Process: - Lowest Bid / Cheaper Price Wins configuration sizing Protection process

ENERGY INEFFICIENCY OF DATA CENTERS Electrical Systems ROOT CAUSES (continue) Electrical Infrastructure: Standby Generators - Oversizing - Redundancy Exceeds N+1 Higher power consumption of Block heaters, and water & Oil pumps Up to 5% Transformers - Oversizing - Inefficient Higher transformers losses up to 3% UPS - Low Load Capacity Due To - Oversizing - Multi-Stage Redundancy 2 (N+) - Inefficient UPS Topology - Low Input Power Factor - High Input Current THD Higher UPS losses up to 25% Oversizing Redundancy Inefficient capacity

ENERGY INEFFICIENCY OF DATA CENTERS ROOT CAUSES (continue) Electrical Infrastructure: PDU - Excessive Use of PDUs. 4 6 X IT designed Load - Inefficient Transformers Higher transformers losses up to 3% Lights - Unused Floor Space - Use Of Inefficient Lights - No Lights Control Sensors Higher power consumption up to 5% IT - Sizing of IT load is based on Nameplate ++ growth - IT Low Power Factor - IT High Current Harmonic THD Higher cables & transformers losses Excessive No Sensors losses

ENERGY INEFFICIENCY OF DATA CENTERS Multi-stages of Power Conversions ROOT CAUSES (continue) AC DC AC DC 5V Internal Drive In Bypass Battery/Charger Rectifier Inverter Out AC/DC PWM/PFC Switcher Unregulated DC To Multi Output Regulated DC Voltages 12V 3.3V 12V 1.5/2. DC/DC 5V 12V 3.3V 1.1V- DC/DC 1.85V External Drive I/O Memory Controller μ Processor SDRAM 3.3V Graphics Controller Uninterruptible Power Supply (UPS) AC/DC Multi output Power Supply Voltage Regulator Modules Server Power Distribution Unit (PDU)

ENERGY INEFFICIENCY OF DATA CENTERS ROOT CAUSES (continue) Final Result IT Distribution losses + Lights, Gen kw 1000 400 Excessive Energy Waste up to 40% LOW (Poor) DCiE FACTOR NEED HELP PLEASE

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY While Maintaining System Configuration Criteria Reliability & Uptime to 99.999% Fault Tolerant System OPTIMIZE POWER CONSUMPTION X OPTIMIZE TIME USAGE

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY Driving Directions Best Practices Alternative Energy Source Controls (Thermostat, Sensors, ETC)

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY Best Practices Managing UPS Load Capacity: UPS Sizing and Loading Can Significantly Affect UPS efficiency: Maximize UPS Load Capacity: < 30% for N+ X configuration < 40% for N configuration Specify / Consider UPS system that has higher Efficiency at 10 40% load capacity (Most UPS units in N or N+X configuration operate at 10% to 40% load capacity) Use / Evaluate Efficient UPS Topology: Double Conversion with Filter Delta Conversion Rotary Flywheel Consider Modular UPS (An Option to Maximize UPS Load Capacity)

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY Best Practices (continue) Managing UPS Load Capacity (continue:) Example: 10% difference in UPS efficiency per 1000 kw IT Load results in approx. 900 MWhr of Energy saving per year and approx $400K of Energy saving over 5 years. Result >> Overall Energy Effectiveness is high. Double Conversion UPS Delta Coversion UPS Rotary UPS Flywheel UPS 98.0% 96.0% 94.0% 92.0% 90.0% 88.0% 86.0% 84.0% 82.0% 80.0% 78.0% 76.0% Most UPS units in N or N+X configuration operate at 10% to 40% load capacity 74.0% 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100%

Best Practices (continue) ROADMAP TO MAXIMIZE ENERGY EFFICIENCY UPS Input Specs Specify / Consider UPS system with Lower Input Current THD at 10-40% load capacity Specify / Consider UPS system with higher Power Factor at 10 40% load capacity. NOTE: Input Current THD increases, and PF decreases when UPS operates at lower load capacity UPS without Filter Load % P.F. THD Losses 10 0.650 63.0 15.00% 25 0.695 60.5 12.80% 50 0.764 40.5 8.40% 75 0.800 30.0 7.30% UPS with Filter Load % P.F. THD Losses 10 0.770 25.0 15.00% 25 0.820 10.0 8.00% 50 0.840 6.0 6.00% 75 0.900 5.0 5.60% Example: 10% difference in Input current THD per 1000 kw IT Load results in approx. 900 MWhr of Energy saving per year and approx $400K of Energy saving over 5 years. Result >> Overall Energy Effectiveness is high

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY Best Practices (continue) Transformers & PDUs (with built-in Transformer): Specify / Consider Transformers with Higher Efficiency: Transformers with 80 C temperature rise. For example: A transformer with an 80 C temperature rise uses 13-21% less operating energy than a 150 C rise unit. The higher-efficiency 80 C rise transformers have a first-cost premium, but a shorter payback than the less-efficient 150 C rise transformers. NEMA TP1 Transformers. Higher Efficient Transformers that exceed Benchmarking Efficiency: ASHRAE 90.1, EPACT 2005, TP1 Install Low voltage (LV) transformers outside the raised floor area Reduce the number of PDUs (with built-in Transformer) inside the Data Center. Result >> Overall Energy Effectiveness is Medium / High

Energy Deficiency Typical 112.5kVA Nonlinear UL listed transformer 100% 99% 98% Efficiency (%) 97% 96% 95% 94% 93% 92% 91% 90% Typical Tx with Linear Load Typical Tx with Nonlinear Load 1 5 9 13172125293337414549535761656973778185899397101 % Loading Significant variation in efficiency over load range & concentration of electronic equipment Courtesy of PowerSmiths

High Performance vs. TP1 (EPACT 2005) transformer Electrical Systems 45kVA Efficiency Comparisons vs. Field Data & TP-1 99% 98% TP-1, 35% X 60 50 %Efficiency 97% 96% Field Load Data Pow ersmiths ESAVER-C3H TP1 Pow ersmiths ESAVER-C3L 40 30 20 # transformers 10 95% 0 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% 0 % loading ESAVER C3L -> > Light Load optimized, C3H -> > Heavy Load optimized Courtesy of PowerSmiths

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY Best Practices (continue) Stand-By Generators Right Sizing of Stand-by Generator Maintain N+1 Redundancy Check with the emergency generator manufacturer on how to reduce the overall energy consumption of heater water jacket(s) (HWJ), i.e. temperature control Result >> Overall Energy Effectiveness is low Lights Use energy Efficient Lights Lights in raised floor area are located above the aisles Maintain regular and proper maintenance includes periodic cleaning and re-lamping Replace older coil / core Ballasts type with new efficient electronic ones. Remove the Ballast from the fixture when the lamp is removed. (some Ballast types consume power even if the lamp is removed) Switch off lights in unused / occupied areas or rooms (UPS, Battery, S/Gear, etc) Result >> Overall Energy Effectiveness is low

Best Practices (continue) DC Power Distribution Eliminate two stages of power conversion. Result >> Overall Energy Effectiveness is High Electrical Systems ROADMAP TO MAXIMIZE ENERGY EFFICIENCY Facility-Level DC Distribution

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY Best Practices (continue) DC Power Distribution (continue) Rack-Level DC Distribution

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY Best Practices (continue) DC Power Distribution (continue) AC System Loss Compared to DC 480 VAC Bulk Power Supply AC/DC DC/AC UPS PDU 12 V AC/DC PSU DC/DC 12 V 5 V 3.3 V Loads using Legacy Voltages 1.2 V 7-7.3% measured improvement 2-5% measured improvement Server 1.8 V 0.8 V Loads using Silicon Voltages 480 VAC Bulk Power Supply AC/DC DC UPS or Rectifier 380 VDC Rotary UPS DC/DC PSU 12 V 12 V 5 V 3.3 V Loads using Legacy Voltages 1.2 V Server 1.8 V 0.8 V Loads using Silicon Voltages

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY Best Practices (continue) Purchasing Process Selection and Purchasing of Equipment should always be based not only on its initial purchase price or lowest bid but should also include its life operating energy cost, Any time there is a new Data Center Faculty is built, an existing facility is expanded, or equipment is being replaced there is a significant opportunity to save on energy costs by selecting and installing cost-effective, energy-efficient equipment. The least expensive equipment to buy may cost much more to operate. Result >> Overall Energy Effectiveness is High

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY Best Practices (continue) Awareness & Energy Management Raise awareness and develop understanding among Data Center staff about the financial and environment impact of energy savings. Develop Effective energy management Program. Perform Routine Energy saving opportunities and best practices for data centers Review full system operation, and efficiency on regular basis. Perform an Infra-Red (IR) test for the main transformers and other electrical systems Improve the load balance between the phases Change UPS DC capacitors if older than 5 years Metering: Install meters (EPMS) to measure instant DCiE values for the Data Center Install monitoring equipment to measure system efficiency and performance. install Meters in every RPP, PDU, STS, etc Install Metered Power Strip in every IT Rack Result >> Overall Energy Effectiveness is Medium

ROADMAP TO MAXIMIZE ENERGY EFFICIENCY Alternative Energy Source Employ alternate energy source to provide power for generator engine block heaters, lights (Data Center, UPS / Switchgear rooms, etc), etc.: Solar Wind Fuel Cells Distributed Generation (DG): Diesel or Gas- Fired Generators Gas Turbines Micro-Turbines Fuel Cells Wind Bio-Mass Controls (Thermostat, Sensors, ETC) Contact the Stand-by Genenerator Manufacturer on how to reduce the overall energy consumption of the block heaters per year by using temperature (thermostat) control. Employ lighting controls such as occupancy sensors for data center, emergency generator(s), UPS(s), and Battery rooms

Take Aways Distributing higher voltage (AC or DC) is more efficient Electrical power conversions are inefficient Highly efficient UPSs should be specified Highly efficient Transformers should be specified Highly efficient Lightings should be specified Highly efficient IT equipment power supplies should be specified Standby generation losses can be minimized On-site generation can improve reliability and efficiency Consider Alternative Energy Sources Raise awareness and develop Energy management Program Selection and Purchasing of Equipment should be based on operating energy cost.

Professional Help This curriculum is not intended to provide answers to all related questions. Professionals specialized in Energy Saving should be able to assist in identifying root causes of Energy Inefficiency / Waste, and maximizing Energy Efficiency.

Overall power use in data centers Electrical Systems Courtesy of Michael Patterson, Intel Corporation

Electrical Systems Efficiency Electrical distribution systems Lighting Standby generation On-site generation

Electricity Flows in Data Centers HVAC system local distribution lines lights, office space, etc. uninterruptible load to the building, 480 V UPS PDU computer racks computer equipment backup diesel generators UPS = Uninterruptible Power Supply PDU = Power Distribution Unit;

Electrical Distribution Every power conversion (AC DC, DC AC, AC AC) loses some power and creates heat Distributing higher voltage is more efficient and saves capital cost (wire size is smaller) Uninterruptible power supplies (UPS s) efficiency varies Power supplies in IT equipment efficiency varies

Data center power conversions Electrical Systems AC D C AC DC 5V Internal Drive In Battery/Charger Rectifier Bypass Inverter Out AC/DC PWM/PFC Switcher Unregulated DC To Multi Output Regulated DC Voltages 12V 3.3V 12V 1.5/2. DC/DC 5V 12V 3.3V DC/DC 1.1V- 1.85V External Drive I/O Memory Controller μ Processor SDRAM 3.3V Graphics Controller Uninterruptible Power Supply (UPS) AC/DC Multi output Power Supply Server Voltage Regulator Modules Power Distribution Unit (PDU)

Electrical Power Conversions Observed conversion losses suggested other solutions 100% 95% Factory Measurements of UPS Efficiency (tested using linear loads) 90% Efficiency 85% 80% Flywheel UPS 85% 80% Double-Conversion UPS 75% Delta-Conversion UPS 70% 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% Percent of Rated Active Power Load 75% % Efficiency 70% 65% 60% 55% 50% Average of All Servers 45% 0% 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% % of Nameplate Power Output

LBNL DC Demonstration Today: AC Distribution 480 VAC building power supply 480 VAC Bulk Power Supply AC/DC DC/AC UPS PDU 12 V AC/DC DC/DC PSU 12 V 5 V 3.3 V Loads using Legacy Voltages 1.2 V Server 1.8 V 0.8 V Loads using Silicon Voltages

LBNL DC Demonstration 480 VAC Building Power 480 VAC Bulk Power Supply Facility-Level DC Distribution AC/DC DC UPS or Rectifier 380 VDC 380 VDC DC/DC PSU 12 V 12 V 5 V 3.3 V Loads using Legacy Voltages 1.2 V Server 1.8 V 0.8 V Loads using Silicon Voltages

LBNL DC Demonstration Rack-Level DC Distribution 480 VAC Buildin g Power 480 VAC Bulk Power Supply AC/DC DC/AC UPS PDU 12 V AC/DC DC/DC PSU 380 VDC 12 V 5 V 3.3 V Loads using Legacy Voltages 1.2 V 1.8 V 0.8 V Loads using Silicon Voltages Rack Server

DC Demonstration Physical Set-up Electrical Systems

Video of DC demonstration Electrical Systems

Measured UPS performance Electrical Systems

UPS factory measurements 100% 95% Factory Measurements of UPS Efficiency Typical Operation (tested using linear loads) Efficiency 90% 85% 80% Flywheel UPS 75% 70% Double-Conversion UPS Line-Interactive, Delta Conversion UPS 0% 20% 40% 60% 80% 100% Percent of Rated Active Power Load

UPS Draft Labeling Standard Based upon proposed European Standard Possible use in incentive programs

Redundancy Understand what redundancy costs is it worth it? Different strategies have different energy penalties (e.g. 2N vs. N+1) Redundancy in electrical distribution always puts you down the efficiency curve

Measured power supply efficiency Typical operation

Data center lighting Lights are on and nobody s home Lighting controls are well proven why not use them? Small benefit but easy to accomplish also saves HVAC energy DC lighting would compliment DC distribution

Standby generation loss Several load sources Heaters Battery chargers Transfer switches Fuel management systems Heaters (many operating hours) use more electricity than the generator will ever produce (few operating hours) Opportunity may be to reduce or eliminate heating, batteries, and chargers

Standby generator heater Electrical Systems

On-site generation On-site generation with utility back-up Thermal host required for combined heat and power Absorption or adsorption chillers Other campus use Renewable sources (future) Fuel cells Solar Wind

Best Electrical Practices UPS systems Self-generation AC-DC distribution Standby generation

Electrical take aways Distributing higher voltage (AC or DC) is more efficient Electrical power conversions are inefficient Highly efficient UPS s should be specified Highly efficient IT equipment power supplies should be specified Lighting is a small but low hanging opportunity Standby generation losses can be minimized On-site generation can improve reliability and efficiency