Green Computing: Datacentres
|
|
|
- Conrad Hancock
- 10 years ago
- Views:
Transcription
1 Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material January 26,
2 This lecture Datacentre design Efficiency metrics Energy-proportional computing Initiatives Seminar groups Datacentre visit 2
3 This lecture Datacentre design Efficiency metrics Energy-proportional computing Initiatives Chapter 4 and 5 of the 1 st Edition of the e-book on the course web (2009) Seminar groups Data centre visit 3
4 Datacentres Datacenters are buildings where multiple servers and communication gear are co-located because of their common environmental requirements and for physical security needs, and ease of maintenance. Barroso and Hölzle Luiz André Barroso and Urs Hölzle. The Datacenter as a Computer - An Introduction to the Design of Warehouse-Scale Machines. Morgan & Claypool Publishers, 2009 (120 pages). Note: a nd Edition of this book (156 pages) is also available with more Google-oriented updates. Most of the basic material in the 2009 is still worthwhile to study. 4
5 IT Architectural overview Server 5 Image (left) under CC license by MrLinsky on Wikimedia
6 Energy use at a datacentre Datacentre overhead Server consumption From Luiz André Barroso and Urs Hölzle, 2009, Data (Right chart) from one Google facility 2007.
7 Power and cooling systems 7 Graphic provided courtesy of DLB Associates
8 Power system components Primary switchgear Breakers for protection Transformers (10-20kV to V) Diesel generators Switched on in case of utility power failure Uninterruptible Power Supply (UPS) Batteries for short term energy provision Functionality Switch energy source between mains power (from utility) and power from Diesel generators Sustain system power with batteries during mains power failure Power feed conditioning 8
9 Power system components Power Distribution Units (PDUs) Break a higher voltage line into several circuits V line to many V circuits that feed the servers A ground short (in server or power supply) will only break one circuit Distribute energy to each rack Provide redundancy (A-side, B-side) so that with a power supply failure fast switching can take place 9
10 Cooling system Computer Room Air Conditioning (CRAC) Blows cold air under the floor plenum Cold air moves to front of server racks (cold aisle) Cold air flows through server racks Warm air is expelled in the back (warm aisle) 10
11 Cooling: operational range Datacentre cannot operate without cooling CRAC units cool the room's air Liquid coolant is pumped from chillers or cooling towers Coils are kept cool (12-14 ºC) with liquid coolant Warm air is pushed through the coils by fans Cold air (16-20 ºC) is moved to the floor plenum Air reaches the servers at ºC 11
12 Free cooling Much more efficient than chillers Cool the coolant to much lower temperatures before reaching the chiller Cooling tower Glycolbased radiator Fans to push air from outside 12 Image (left) under CC license by Frobles on Wikimedia Image (right) under CC license by cbpowerindustrial on Flickr
13 Redundancy and reliability Redundancy for fault tolerance and during maintenance Applied to both power and cooling systems Configurations: N+1, N+2, 2N Type Availability Description Tier I 99.67% Single path for power & cooling. No redundancy (N) Tier II 99.74% Single path for power & cooling. Redundancy (N+1) Tier III 99.98% Tier IV % Tier Classification (ANSI/TIA 942) Multiple paths for power & cooling (only one active). Concurrently maintainable. Redundancy (N+1) Multiple active paths for power & cooling. Redundancy in both paths (min (N+1)) W.Pitt Turner IV, J.H.Seader, K.G.Brill. Tier classifications define site infrastructure performance, Uptime Institute, White Paper 13
14 Container-based datacentres Server racks, power distribution and heat exchange inside a container!! Highly efficient cooling High server density 14 Image from Wikimedia by user Sun Microsystem
15 This lecture Datacentre design Efficiency metrics Energy-proportional computing Initiatives Seminar groups Datacentre visit 15
16 Sources of efficiency losses Power systems Element Losses Transformers 0.50% UPSs 7-12% Highly efficient UPSs 3% Low-voltage power ( V) cables 1-3% Cooling Fans that move cool and warm air Mix of cool and warm air during long paths Too low temperature selection ºC better than traditional 20 ºC 16
17 Energy efficiency metrics Power Usage Effectiveness (PUE) Proposed by The Green Grid association Efficiency of the IT support infrastructure PUE= Total facility power Total IT equipment power Historic data: PUEs between 1.5 and 2.0 Google, Microsoft, Apple have reported PUEs around 1.1X C. Beladi. Green Grid datacenter power efficiency metrics: PUE and DCiE. White paper
18 Location matters One quarter of Singapore data centers have PUE higher than 3, Japan and Australia claim average PUE of 2.2 and 2.25 respectively (APAC datacenter survey, April 2013) Facebook Luleå: 1.08 (Computer Sweden, 7 Feb 2013) Image:
19 Facebook live dashboard
20 Energy efficiency metrics PUE has to be used carefully Example: Server fans in IT-PAC Microsoft data centre container module Facility power IT equipment power IT-PAC airflow management is improved Server fans are no longer required PUE increases Overall energy consumption reduced despite PUE increase Other aspects must be taken into account 20
21 Energy efficiency metrics Green Grid's Datacentre Performance Efficiency (DCPE) DCPE= Amount of computational work Total energy used Barroso and Hölze propose: DCPE = 1/PUE. 1/SPUE. Computation/Total energy to electronics Computing efficiency IT equipment efficiency Building facilities efficiency 21
22 Energy efficiency metrics Server Power Usage Effectiveness (SPUE) Efficiency of the IT infrastructure Losses in power supply, voltage regulator modules, server fans SPUE= Total server input power Total useful power Useful power Consumption of electronics directly involved in computation E.g. motherboard, disks, CPU, DRAM... Servers have SPUEs between 1.6 and 1.8 State of the art servers should be less than 1.2!!! 22
23 Energy efficiency metrics Total Power Usage Effectiveness (TPUE) Show efficiency of electromechanical overheads. TPUE= PUE SPUE Example: 2.0 PUE 1.6 SPUE TPUE= = 3.2 For each productive Watt another 2.2 W consumed!!! 23
24 This lecture Datacentre design Efficiency metrics Energy-proportional computing Initiatives Seminar groups Datacentre visit 24
25 Load and energy efficiency Most of the time spent in no energy-efficient load regions Activity profile of 5000 Google servers in 6 months Image from Luiz André Barroso and Urs Hölzle. The Datacenter as a Computer
26 Load and energy efficiency Almost no time in idle state In low load there are several hundreds of queries Load spread out over all available servers Optimised for performance and/or availability Sustainable approach Concentrate load in a few servers Switch off unused servers But!!! More software complexity Energy for data distribution 26
27 Recall from lecture 2 Consumption proportional to the load Ideal linear function without constants Energy (%) Load (%) Ideal energy proportional server Traditional server Traditional server data based on data from Barroso and Hölzle
28 Energy proportional computing Capacity to adapt consumption to load Device Dynamic power CPU 3.0x Memory 2.0x Disks 1.3x Network switches 1.2x More hardware improvements are required!!! Meanwhile only option is to switch off hardware!!! 28
29 Energy spent: revisited CPU a larger proportion of energy costs than that reported in 2009! Luiz André Barroso and Urs Hölzle. The Datacenter as a Computer, 2 nd Edition 2013
30 This lecture Datacentre design Efficiency metrics Energy-proportional computing Initiatives Seminar groups Datacentre visit 30
31 ENERGY STAR Future specifications Program Requirements for Computer Servers 2.0 Currently first draft available Industry drive: Microsoft joins Will include active consumption Facebook to lead the Open as opposed to just idle consumption Computer Project on servers Computer Sweden, 30 Jan microsoft-contributes-cloud-server-designs-to-the-open-compute-project.aspx Program Requirements for Datacenter Storage 1.0 establishes maximum consumption of storage products 31
32 EU Code of Conduct for Datacentres European action to reduce consumption of datacentres Best practices for datacentres operators V3.0 Guide (Feb 2011) Operators register and commit to their application Roles of applicant Participant Operator of datacentre or equipment in it Commitments Annual report of energy consumption Implementation of some of the best practices Endorser Support the initiative and participants 32
33 EU Code of Conduct for Data Centres Scope of the best practices Datacentre utilisation, management and planning IT equipment and services Cooling Datacentre power equipment Other equipment Building Monitoring Best practice expected implementation Immediate During software install or update During new IT introduction or replacement During building of datacenter or retrofit Optional 33
34 This lecture Datacentre design Efficiency metrics Energy-proportional computing Initiatives Seminar groups Datacentre visit 34
35 Seminar groups We have 56 students of which 50 registered in webreg 3 students had to be turned down, so make the best of the opportunity to attend the course! 35
36 Datacentre visit Currently discussing a visit at Ericsson Preliminary date: 10/3 afternoon Webreg will open for registering for the visit 36
37 Questions?
Green Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
Cloud Computing Data Centers
Cloud Computing Data Centers Dr. Sanjay P. Ahuja, Ph.D. 2010-14 FIS Distinguished Professor of Computer Science School of Computing, UNF Warehouse-Scale Data Center (WSC) Design. Example: a data center
CarbonDecisions. The green data centre. Why becoming a green data centre makes good business sense
CarbonDecisions The green data centre Why becoming a green data centre makes good business sense Contents What is a green data centre? Why being a green data centre makes good business sense 5 steps to
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
AbSTRACT INTRODUCTION background
february 20, 2007 GREEN GRID METRICS: Describing Datacenter Power Efficiency Technical Committee White Paper white paper 1 Abstract The Green Grid is an association of IT professionals seeking to dramatically
Green Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs
Green Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs Topics The Why? The How? Conclusion The Why? Drivers for Green IT According to Forrester Research, IT accounts
Last time. Data Center as a Computer. Today. Data Center Construction (and management)
Last time Data Center Construction (and management) Johan Tordsson Department of Computing Science 1. Common (Web) application architectures N-tier applications Load Balancers Application Servers Databases
Green Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance. Chapter 8: 8 Guide for assessing GHG emissions of Data Centers
GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance Chapter : Guide for assessing GHG emissions of Data Centers DRAFT March 0 Table of Contents GHG Protocol ICT Sector
Data Centers: Definitions, Concepts and Concerns
Data Centers: Definitions, Concepts and Concerns Arash Mousavi DCC September 2013 Agenda 1. Introduction 2. Issues in Modern Data Centers: Siemens Integrated Data Center Solutions 3. Issues in Modern Data
SoSe 2014 Dozenten: Prof. Dr. Thomas Ludwig, Dr. Manuel Dolz Vorgetragen von Hakob Aridzanjan 03.06.2014
Total Cost of Ownership in High Performance Computing HPC datacenter energy efficient techniques: job scheduling, best programming practices, energy-saving hardware/software mechanisms SoSe 2014 Dozenten:
Data Center Equipment Power Trends
Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data
Energy Efficiency Monitoring in Data Centers: Case Study at International Hellenic University. George Koutitas, Prof. L. Tassiulas, Prof. I.
UTH and IHU (CI)-WP4 Energy Efficiency Monitoring in Data Centers: Case Study at International Hellenic University Plenary Meeting Gent, February-2012 George Koutitas, Prof. L. Tassiulas, Prof. I. Vlahavas
How To Improve Energy Efficiency In A Data Center
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY
AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical
Data Center Energy Use, Metrics and Rating Systems
Data Center Energy Use, Metrics and Rating Systems Steve Greenberg Energy Management Engineer Environmental Energy Technologies Division Lawrence Berkeley National Laboratory October 31, 2007 Today s s
Specialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
Datacenter Efficiency
EXECUTIVE STRATEGY BRIEF Operating highly-efficient datacenters is imperative as more consumers and companies move to a cloud computing environment. With high energy costs and pressure to reduce carbon
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.
Energy Efficiency and Availability Management in Consolidated Data Centers
Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal
EU Code of Conduct for Data Centre Efficiency
EU Code of Conduct for Data Centre Efficiency A Green Practice Accredited by British Computer Society (BCS) EU Code of Conduct for Data Centre Efficiency Local Organizer Practices in Data Centre Industry
DataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
Data Center Facility Basics
Data Center Facility Basics Ofer Lior, Spring 2015 Challenges in Modern Data Centers Management, Spring 2015 1 Information provided in these slides is for educational purposes only Challenges in Modern
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE
THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any
Enabling an agile Data Centre in a (Fr)agile market
Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore
Data Centre Energy Efficiency Operating for Optimisation Robert M Pe / Sept. 20, 2012 National Energy Efficiency Conference Singapore Introduction Agenda Introduction Overview of Data Centres DC Operational
Overview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
Energy Management Services
February, 2012 Energy Management Services Data centers & IT environments are often critical to today s businesses, directly affecting operations and profitability. General & Mechanical Services has the
High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
The New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
Data Centre Testing and Commissioning
Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to
Analysis of data centre cooling energy efficiency
Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
ICT and the Green Data Centre
ICT and the Green Data Centre Scott McConnell Sales Manager c/o Tanya Duncan MD Interxion Ireland Green Data Centres Our Responsibility Data centre greenhouse gas emissions are projected to quadruple by
Best Practices. for the EU Code of Conduct on Data Centres. Version 1.0.0 First Release Release Public
Best Practices for the EU Code of Conduct on Data Centres Version 1.0.0 First Release Release Public 1 Introduction This document is a companion to the EU Code of Conduct on Data Centres v0.9. This document
Electrical Systems. <Presenter>
Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF
Metering and Managing University of Sheffield Data Centres. Chris Cartledge Independent Consultant [email protected]
Metering and Managing University of Sheffield Data Centres Chris Cartledge Independent Consultant [email protected] Summary ICT Electricity Use Footprint Data Centre Electricity Use European
THE GREEN DATA CENTER
GREEN IT THE GREEN DATA CENTER WHERE ECOLOGY MEETS ECONOMY We truly live in an information age. Data Centers serve a very important purpose they provide the global community with nearly unlimited access
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,
Data Center Energy Profiler Questions Checklist
Data Center Energy Profiler Questions Checklist Step 1 Case Name Date Center Company State/Region County Floor Area Data Center Space Floor Area Non Data Center Space Floor Area Data Center Support Space
Data centres that deliver [email protected]
Data centres that deliver [email protected] DATA CENTRE INFRASTRUCTURE MANAGEMENT (DCIM) DCIM solutions are designed to collect and manage information about a data centre s assets, resource use
Reducing the Annual Cost of a Telecommunications Data Center
Applied Math Modeling White Paper Reducing the Annual Cost of a Telecommunications Data Center By Paul Bemis and Liz Marshall, Applied Math Modeling Inc., Concord, NH March, 2011 Introduction The facilities
Increasing Data Center Efficiency through Metering and Monitoring Power Usage
White Paper Intel Information Technology Computer Manufacturing Data Center Efficiency Increasing Data Center Efficiency through Metering and Monitoring Power Usage To increase data center energy efficiency
Re Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
Australian Government Data Centre Strategy 2010-2025
Australian Government Data Centre Strategy 2010-2025 Better Practice Guide: Data Centre Power June 2013 17/06/2013 4:12 PM 17/06/2013 4:12 PM Contents Contents 2 1. Introduction 3 Scope 3 Policy Framework
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015
Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units
Direct Fresh Air Free Cooling of Data Centres
White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The
Introduction to Datacenters & the Cloud
Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
Optimization of energy consumption in HPC centers: Energy Efficiency Project of Castile and Leon Supercomputing Center - FCSCL
European Association for the Development of Renewable Energies, Environment and Power Quality (EA4EPQ) International Conference on Renewable Energies and Power Quality (ICREPQ 12) Santiago de Compostela
The Pros and Cons of Modular Systems
The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated
Greening Commercial Data Centres
Greening Commercial Data Centres Fresh air cooling giving a PUE of 1.2 in a colocation environment Greater efficiency and greater resilience Adjustable Overhead Supply allows variation in rack cooling
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
Server Room Thermal Assessment
PREPARED FOR CUSTOMER Server Room Thermal Assessment Analysis of Server Room COMMERCIAL IN CONFIDENCE MAY 2011 Contents 1 Document Information... 3 2 Executive Summary... 4 2.1 Recommendation Summary...
Data center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria
Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center
Office of the Government Chief Information Officer. Green Data Centre Practices
Office of the Government Chief Information Officer Green Data Centre Practices Version : 2.0 April 2013 The Government of the Hong Kong Special Administrative Region The contents of this document remain
Ch. 4 - Topics of Discussion
CPET 581 Cloud Computing: Technologies and Enterprise IT Strategies Lecture 6 Cloud Platform Architecture over Virtualized Data Centers Part -2: Data-Center Design and Interconnection Networks & Architecture
Data Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
Server Technology, Inc.
Server Technology, Inc. Cabinet Power Monitoring, Management & Control Within the Data Center White Paper STI-100-011 2010-Sept-27 by Calvin Nicholson, Senior Director Software and Strategic Alliances,
Building a data center. C R Srinivasan Tata Communications
Building a data center C R Srinivasan Tata Communications Introduction Data Center as defined by TIA 942 A building or a portion of a building whose primary function is to house a computer room and its
GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCIE
WHITE PAPER #6 GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCIE EDITORS: CHRISTIAN BELADY, MICROSOFT CONTRIBUTORS: ANDY RAWSON, AMD JOHN PFLEUGER, DELL TAHIR CADER, SPRAYCOOL PAGE 2 ABSTRACT
White Paper RiZone The Rittal Management Software for IT infrastructures
White Paper RiZone The Rittal Management Software for IT infrastructures Bernd Hanstein Klaus Hendlmeier Thorsten Weller Copyright 2009 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg 35745
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied
Optimizing IT costs with Cloud. Tarmo Tikerpäe Datacenter SSP Microsoft Corporation
Optimizing IT costs with Cloud Tarmo Tikerpäe Datacenter SSP Microsoft Corporation BENEFITS Speed Scale Economics Cloud Trend: 70% 2 weeks to deliver new services vs. 6-12 months with traditional solution
2014 Best Practices. for the EU Code of Conduct on Data Centres
EUROPEAN COMMISSION DIRECTORATE-GENERAL JRC JOINT RESEARCH CENTRE Institute for Energy and Transport Renewable Energies Unit 2014 Best Practices for the EU Code of Conduct on Data Centres 1 Document Information
2014 Best Practices. The EU Code of Conduct on Data Centres
2014 Best Practices The EU Code of Conduct on Data Centres 1 Document Information 1.1 Version History Version 1 Description Version Updates Date 5.0.1 2014 Review draft Comments from 2013 stakeholders
Case Study. Cool and green: Citigroup s Frankfurt Data Center
Zug, April 16, 2015 Cool and green: Citigroup s Frankfurt Data Center In Frankfurt, Siemens helps optimize Citigroup s data center. When it comes to building automation, security technology and power supply,
How To Benchmark Power Production
Energy Benchmarking Service for Data Centre Industry in Hong Kong and Initial Findings Simon Lam Acting Deputy Director, Business Marketing & Development Department, CLP Power Agenda 1. Introduction: Why
Data Center Infrastructure Management: ERP for the Data Center Manager
Data Center Infrastructure Management: ERP for the Data Center Manager 1 2 Topics What s DCIM & the ERP Analogy Why DCIM How DCIM Works How DCIM Helps 3 DCIM by Definition DCIM is a system that collects
European Code of Conduct for Data Centre. Presentation of the Awards 2014
European Code of Conduct for Data Centre Presentation of the Awards 2014 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
Smarter Data Centers. Integrated Data Center Service Management
Smarter Data Centers Integrated Data Center Service Management Approx. 3.500 ton CO² is generated by: Diesel Car-6l /100 km 20.000 km Airplane 5 * Brussels-Barcelona Server, 1.5 A, 24*7*365*3.000 Kwhr
Server Technology, Inc.
Server Technology, Inc. Power Efficiency Gains by Deploying 415 VAC Power Distribution in North American Data Centers White Paper STI-100-008 2009-April-07 Headquarters Server Technology, Inc. 1040 Sandhill
Measuring Power in your Data Center
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Raritan Measuring Power in your Data Center Herman Chan, Director, Power Solutions Business Unit, and Greg More, Senior Product Marketing Manager There
About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services
About Injazat Injazat Data Systems is an industry-recognized market leader in the region for Information Technology Outsourcing, Cloud and Data Center Managed Services delivered from the region s 1st Tier
European Code of Conduct for Data Centre. Presentation of the Awards 2016
European Code of Conduct for Data Centre Presentation of the Awards 2016 Paolo Bertoldi European Commission DG JRC Institute for Energy and Transport 1 The Code of Conduct for Data Centre Results European
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
Capacity Planning in the Modern Datacenter
in the Modern Datacenter SERVER TECHNOLOGY - INDUSTRY BRIEF -001 July 2015 Executive Overview Today s datacenter managers oversee more infrastructure than ever, with an exponential increase in complexity
Power and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
Data Center Energy Efficiency Looking Beyond PUE
Data Center Energy Efficiency Looking Beyond PUE No Limits Software White Paper #4 By David Cole 2011 No Limits Software. All rights reserved. No part of this publication may be used, reproduced, photocopied,
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent
CIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How
CIBSE ASHRAE Group Data Centre Energy Efficiency: Who, What, Why, When, Where & How Presenters Don Beaty PE, FASHRAE Founder, President & Managing Director DLB Associates Consulting Engineers Paul Finch
Energy Performance Optimization of Server Room HVAC System
International Journal of Thermal Technologies E-ISSN 2277 4114 2 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Manoj Jadhav * and Pramod Chaudhari Department
abstract about the GREEn GRiD
Guidelines for Energy-Efficient Datacenters february 16, 2007 white paper 1 Abstract In this paper, The Green Grid provides a framework for improving the energy efficiency of both new and existing datacenters.
HPC TCO: Cooling and Computer Room Efficiency
HPC TCO: Cooling and Computer Room Efficiency 1 Route Plan Motivation (Why do we care?) HPC Building Blocks: Compuer Hardware (What s inside my dataroom? What needs to be cooled?) HPC Building Blocks: