PERFORMANCE OF STANDING SEAM METAL ROOFS UNDER REALISTIC WIND LOADING
|
|
|
- Clinton Bennett
- 9 years ago
- Views:
Transcription
1 PERFORMANCE OF STANDING SEAM METAL ROOFS UNDER REALISTIC WIND LOADING Filmon Habte, Maryam Asghari Mooneghi, Peter Irwin, Arindam Gan Chowdhury ABSTRACT: A full-scale experimental investigation was conducted to study the behavior of wind loads on the surfaces of two types of standing seam metal roofs (i.e. vertical-leg and trapezoidal) and evaluate their performance under high wind speeds. Pressure measurements on the roof surface and roof panel deflection measurements were conducted under realistic wind loading in Wall of Wind (WOW) facility at Florida International University (FIU). Roof profile and eave details were observed to have significant effect on the magnitude and distribution of the wind-induced pressures at the surface of the metal roofs. Comparison of experimental results with ASCE 7-10 provisions showed that the ASCE 7-10 might in some cases underestimate the wind loading on a mono-sloped trapezoidal-leg standing seam roof. Significantly higher deflections were experienced by the trapezoidal roof, and the metal panels were observed to become increasingly stiffer at high deflections. Roof failure occurred on the trapezoidal roof only, and the main mode of failure was clip rupture/breakage. The clip failures are assumed to be caused by excessive vibration at the free end. KEYWORDS: Standing seam metal roof; Full-scale testing; Aerodynamics; Deflection; Roof failure.
2 1 Performance of Standing Seam Metal Roofs under Realistic Wind Loading Filmon Habte 1, Maryam Asghari Mooneghi 2, Arindam Gan Chowdhury 1, and Peter Irwin 1 1 Department of Civil Eng., College of Engineering, Florida International University, Miami, FL, USA 2 Advanced Technology and Research, Arup, San Francisco, CA, USA [email protected], [email protected], [email protected], [email protected] ABSTRACT: A full-scale experimental investigation was conducted to study the behavior of wind loads on the surfaces of two types of standing seam metal roofs (i.e. vertical-leg and trapezoidal) and evaluate their performance under high wind speeds. Pressure measurements on the roof surface and roof panel deflection measurements were conducted under realistic wind loading in Wall of Wind (WOW) facility at Florida International University (FIU). Roof profile and eave details were observed to have significant effect on the magnitude and distribution of the wind-induced pressures at the surface of the metal roofs. Comparison of experimental results with ASCE 7-10 provisions showed that the ASCE 7-10 might in some cases underestimate the wind loading on a mono-sloped trapezoidal-leg standing seam roof. Significantly higher deflections were experienced by the trapezoidal roof, and the metal panels were observed to become increasingly stiffer at high deflections. Roof failure occurred on the trapezoidal roof only, and the main mode of failure was clip rupture/breakage. The clip failures are assumed to be caused by excessive vibration at the free end. KEY WORDS: Standing seam metal roof; Full-scale testing; Aerodynamics; Deflection; Roof failure. 1 INTRODUCTION Roofs have been observed to be the most hurricane vulnerable components of a building envelope. Roof damage during a storm event can result in myriad of problems ranging from water leakage to complete failure of the building structure. Current methodology for investigating the performance of a metal roof systems under wind loads involves: 1) determining the design loads using wind provisions of codes and standards; and 2) undertaking physical test on the roof system to test its adequacy in withstanding the design load, in which, loading is applied to the roof system in the form of a uniform static pressure and the deflections versus loading are recorded up to failure. This method of using uniform static wind loading may not be truly representative of real conditions, and might on one hand set higher minimum design requirements for the entire system than necessary or on the other hand it could underestimate effects of localized peak pressures on critical locations. Most physical testing protocols for evaluating the adequacy of metal roof panels in withstanding design wind loads use defined pressures to evaluate the uplift capacity of metal roof panels. They do not include temporal and spatial variations that are inherent in real wind loading; nor do such tests necessarily include realistic boundary conditions provided by the supports in actual applications. Moreover, the failure modes observed during static pressure tests might not be true representatives of field failures ([1];[2]) Identification of the roof component that fails first and correct simulation of actual roof failure modes are important as they determine the ultimate strength of the roof assembly. The method of using static uniform loading has been the center of continuous debates and appraisals by structural design engineers, wind engineering specialists, and scientific researchers. Several researches have been conducted to relate high local loads to their corresponding uniform static loads ([2]; [3]; [4]; [5]; [6]). Most of those previous researches used scaled models of metal panels which may introduce scaling errors due to Reynolds number mismatch and not being able to reproduce the effects of architectural features of the standing seams. Large- and fullscale experiments in properly simulated flows can circumvent these issues related to adverse scale effects, but such studies have been limited. Understanding the response of actual metal roof panels to wind loading, as well as identifying the different failure mechanisms, can facilitate the development of improved designs and design guidelines which can reduce roof system damages during wind storms. To this end, the objectives of this work are to understand the behavior of standing seam metal roof panels under realistic wind loading and to evaluate their performance under high wind speeds. Aerodynamic pressure and deflection measurement tests were carried out on mono-sloped full-scale vertical-leg and trapezoidal standing seam metal roof panels under simulated turbulent wind loading. Observation of roof failure mechanism and comparison of the pressure results with minimum design loads for building and other structures given in ASCE 7-10 [7] provisions for wind loading were also performed.
3 2 2 EXPERIMENTAL SETUP AND TESTING PROTOCOL In this study, two types of standing seam metal roofs (i.e. vertical-leg and trapezoidal) each with plan dimensions of 3.1 m by 4.6 m were used. The roofs were attached to a 1.52 m high base structure which was designed to support interchangeable monosloped roofs with slope of 4.6 deg. (Figure1). The vertical-leg standing seam metal roof (henceforth referred to as vertical-leg roof for brevity) had 0.5 m wide panels with 50.8 mm high ribs and floating clips were used to attach the panels to the purlins. The trapezoidal standing seam metal roof (henceforth referred to as trapezoidal roof for brevity) had 0.6 m wide panel with 76.2 mm high ribs, and sliding clips were used as attachments. As can be seen in Figure1, based on the manufacturers specifications, perimeter eave trims (attachments) were placed on all four sides of the vertical-leg roof while the trapezoidal roof had eave trims only along its two sloping edges. Moreover, in the vertical-leg roof the top levels of the eave attachments only extended to the level of the panel flat pan sections, but in the trapezoidal roof the eave attachments were raised to about 76.2 mm above the surface of the panel flat pan sections. The 12-fan Wall of Wind (WOW) open jet facility at Florida International University (FIU) was used for this experimental investigation. The WOW has the capability of generating up-to Category 5 hurricane wind speeds with desired wind flow characteristics. The WOW has 12 electric fans arranged in a two row by six-column pattern which produce a wind field 6.1 m wide and 4.3 m high, allowing aerodynamic testing of large-scale models or full-scale portions of buildings. Figure 2 shows WOW simulated mean wind speed and turbulence intensity profiles for open country condition (target power law coefficient of α = 1/6.5), used during the experiments. Figure1. Standing seam metal roof mock-ups used in testing: Vertical-leg (left) and Trapezoidal (right) Aerodynamic pressure measurement tests were conducted on both roofs for twelve wind directions at a low-eave height wind speed of 24.7 m/s. Each roof system was instrumented with external and internal pressure taps. The time-histories of windinduced external and internal pressures were collected using 6.35 mm ID polyurethane pressure tubes and a DSA 4000, ZOC 33 Scanivalve data acquisition system. One minute duration time history pressure data were collected for each test at a sampling frequency of 512 Hz. A transfer function designed for the tubing [8] was used to correct for tubing effects. Metal panel and seam line (panel rib) deflection measurements were also conducted to evaluate the structural performance of the roof specimens under high wind speeds. During deflection measurement experiments, the two sloping roof edges and the low-eave end were fastened using self-drilling steel screws, but the high eave end was left open and only one screw was used at each panel rib. This fixed free boundary condition was intended to represent a continuous roof property at the open end, and simulate a set-up condition followed in the American Society for Testing and Materials (ASTM) E1592 [9] to enable comparison of the results (which will be done in future work). The deflection measurement tests were conducted at several WOW mean wind speeds which ranged from 30.5 m/s to 65.7 m/s and at different wind directions. The deflections were recorded using RDP Electrosense LDC3000A linear variable differential transformers (LVDTs) and Celecso SP2 type string pots. Deflection measurement was conducted for an effective duration of 1 minute (i.e. excluding fan ramp up times), at sampling rate of 100 Hz. Reference (baseline) deflection measurements at zero wind speed were conducted before each deflection measurement test.
4 3 Figure 2: Simulated open terrain atmospheric boundary layer (ABL) in the WOW: Mean wind speed profile (left) and Turbulence intensity profile (right) 3 RESULTS 3.1 Aerodynamic Pressure Results The pressure results are presented in the form of mean and peak pressure coefficients in different roof regions. The uplift pressure in a roof region was computed by area-averaging time-histories of pressures from pressure taps within that region. The mean pressure coefficients C p mean were then obtained using Equation (1) C p mean Pmean (1) 1 2 Vmean 2 where P mean is the mean of 1 minute duration area-averaged pressure data obtained on the surface of the metal panels; V mean is the mean upstream wind speed at model low-eave height, and ρ is the density of air. The peak pressure coefficients were obtained using Equation (2) and were normalized to the 3-sec gust dynamic pressure: C p peak Ppeak 1 (2) V 2 3sec 2 where P peak is the estimated peak pressure obtained from 1 minute duration area-averaged pressure data obtained on the surface of the metal panels and V 3 sec is the 3-sec gust dynamic pressure at model low-eave height. The tests were performed in partial turbulence simulation, hence the turbulence intensity at roof height was lower than that of atmospheric boundary layer (ABL) which contains full spectrum of turbulence. In order to calculate the estimated peak pressures, a method called Partial Turbulence Simulation was used. In this method, the turbulence is divided into two distinct statistical processes, one at high frequencies which can be simulated correctly in WOW, and one at low frequencies which can be treated in a quasi-steady manner. The joint probability of load from the two processes is derived, with part coming from the WOW data and the remainder from the Gaussian behavior of the missing low frequency component. For the evaluation of these estimated values, the peak value with 95% probability of not being exceeded in one hour of full spectrum wind was selected [10, 11].
5 4 Figure 3. Roof layout and wind direction: trapezoidal standing seam roof Although the plan dimensions, eave height, roof slope and test setup in the vertical-leg and trapezoidal roofs were identical, much higher pressures with larger non-uniformity were observed in the trapezoidal roof specimen. For illustration purposes pressure results in the high-eave corner regions (shaded region in Figure 3) are shown. The pressures in the high eave corner regions were computed by averaging time-series of pressure readings from four pressure taps constituting a total area of 0.35 m 2 and 0.5 m 2 in the vertical-leg and trapezoidal roofs respectively. Figure 4 shows the mean and peak pressure coefficients versus wind direction for the high-eave corner roof region in both vertical-leg and trapezoidal roofs (definition of wind direction is shown in Figure 3). The corresponding external GC p value specified by ASCE 7-10 for this roof region is also shown in Figure 4. It should be noted that equivalent pressure coefficients GCp eq were calculated using the method explained in [12] before comparison with ASCE 7-10 provisions was performed. Higher pressures, exceeding the ASCE 7-10 provision, were observed in the trapezoidal roof. The significant difference in roof pressures between the two roof models is a clear indication that roof architectural features and eave attachment details highly affect the magnitude and distribution of wind pressures on roofs. This is similar in theory with findings of previous researches on roof-tiles ([13];[14]) which showed high dependence of wind pressure on the roof architectural features, and the fact that using bare decked roof models in aerodynamic testing might underestimate the actual roof pressures. Note that the effects of such finer geometrical details are generally better addressed using large or fullscale tests. Figure 4. Mean (top) and Peak (bottom) pressure coefficients for high-eave roof region It s important to mention that in contrast to the vertical-leg roof that had eave trims/attachments on all its 4 edges, the trapezoidal roof had eave trims/attachments installed at its two sloping edges only. Hence, the significantly lower uplift pressure at the surface of the vertical-leg roofs might be due to the effect of rounding or chamfering eaves which is known to alleviate
6 5 suction at the leading edge [15]. It can also be hypothesized that since the eave attachments and ribs in the trapezoidal roofs extend to about 76 mm above the surface of the roof, they might act as low-parapets which have been observed to significantly increase the roof corner suction pressures by strengthening vortices ([16]; [17]; [18]). Nevertheless, detailed flow measurement investigation is needed to precisely identify the actual causes of such significant pressure differences. According to the ASCE 7-10 wind loading provisions for components and cladding, the roof is divided into three zones namely Zone 3, Zone 3 and Zone 2 with external GC p of -2.60, and respectively. A detailed comparison of these GC p values with pressures measured in different roof regions with averaging-area of 0.93 m 2 showed that the ASCE 7-10 might produce un-conservative pressures in the case of the trapezoidal roof. For a further comparison of the experimentally measured external roof pressures with the ASCE 7-10 provisions, peak pressures of different roof regions within Zones 3 and 3 having different averaging areas were computed. Note that in this experimental model, Zones 3 and 3 represent 1.8 m wide strips near the low-eave and high-eave ends respectively. Figure 5 and Figure 6 show maximum Cp peak computed for different averagingarea within roof Zone 3 and 3 respectively, along with their ASCE 7-10 pressure coefficients. The Cp peak value for a specific averaging area (shown in Figure 5 and Figure 6) represents the highest peak pressure coefficient from all pressure taps combinations with similar sizes of averaging area. It can be seen that changing the averaging area highly affects the evaluated uplift pressures. In Zone 3, the ASCE 7-10 pressure coefficients were observed to be conservative for the vertical-leg roof for all considered averaging areas, the opposite was true in the case of the trapezoidal roof. Similarly, for Zone 3 the ASCE 7-10 pressure coefficients were conservative for all averaging areas used in the vertical-leg roof. But in the trapezoidal roof, the ASCE 7-10 pressure coefficients were shown to be un-conservative for averaging areas less than 0.93 m 2. Figure 5. Peak pressure coefficient versus averaging area, Zone 3 Figure 6. Peak pressure coefficient versus averaging area, Zone 3
7 6 3.2 Deflection Measurement Results Under real wind loading, metal roofs experience vibratory deflections that are either upward or downward dominated depending on the direction of the fluctuating wind-induced force at their surface. The wind-induced vibrations are unsteady as well as highly non-uniform, and increase with increasing wind pressure until permanent failure of the roof occurs. During an uplift deflection, the metal panels assume the shape of a cylindrical shell spanning between the ribs, with highest deflection usually occurring at the center of the flat-pan section. Relative to the flat pan sections, vibrations with lower amplitude but higher frequency were observed along the panel ribs and lower amplitudes were recorded at the ribs near the purlins (i.e. at structural supports). The deflections experienced by a roof region were highly dependent on wind direction, and were relatively higher at the edge panels. Net deflections were computed by deducting the baseline deflections (deflection measured before each test at zero wind speed) from the measured deflection during testing. In both standing seam roofs, the highest deflections were observed at the free end of the edge panels when they were situated at the upwind position and normal to the direction of approaching wind. The deflections experienced by the trapezoidal roof were significantly higher than the vertical leg-standing seam roof. These higher deflections might be justified by the higher (in magnitude) aerodynamic pressure on the trapezoidal roof. Moreover, the span between adjacent ribs in the trapezoidal seam roof was longer than that of the vertical-leg seam roof, making it less rigid hence more susceptible to high deflections. Mean and maximum deflections versus wind directions for the deflection measurement devices that recorded the highest mid-flat pan (mid-panel) and panel-rib deflections are shown in Figure 7 and Figure 8 for the vertical-leg and trapezoidal roofs respectively. The mid-panel deflections were recorded using linear variable differential transformers (LVDT) while panel-rib deflections were recorded using String Pots. The location of the LVDTs and SPs is shown in Figure 3. It should be noted that the deflections in Figure 7 and Figure 8 were recorded at a low-eave height mean wind speed of 57 m/s and positive values represent upward deflection. Figure 7. Mid-panel and panel-rib deflections in vertical-leg roof Figure 8. Mid-panel and panel-rib deflections in trapezoidal roof As previously indicated, Figure 7 and Figure 8 show that both roofs tended to experience the highest mid-panel and panel-rib deflections when their longer sides (the sloping sides) were situated approximately normal to the direction of the approaching wind, slightly different from the directions producing highest local uplift pressures, a fact probably attributable to details of pressure distribution over the roof surface combined with roof stiffness characteristics. The deflections were also observed to
8 7 increase as a panel s distance frame the edges reduces. Both mid-panel and panel-rib deflections of the trapezoidal roof were higher than those observed in the vertical-leg roofs. Increasing the wind speed increases the wind-induced pressures which in turn increases the vibratory deflections experienced by the roofs. The maximum deflections versus mean low-eave height wind speeds for vertical-leg roof (for critical wind directions of 85 o ) and trapezoidal roof (for critical wind directions of 275 o ) are shown in Figure 9. For both roofs results of the LVDTs and SPs which registered the highest deflections are shown here. In the vertical-leg roof the deflection increased at a relatively lower rate with increasing wind speed, but in the trapezoidal roof the deflection increased sharply up to wind speed of 47.8 m/s but at higher wind speeds it was almost constant. At low mid-panel deflections, the roof panel vibrations were observed to be mainly limited to the flat metal pan section only. But as wind speed increased, the vibrations started creeping into the panel-ribs and at a sufficiently high wind speed, the flat pan section lifted off entirely and the whole metal panel section started vibrating from the ribs. At this stage, the rate at which deflections increased with increasing wind speed reduced significantly and the dominant frequency of vibration also changed. In a sense, at very high deflections the metal panel assembly became increasingly stiffer until failure was encountered. For the range of wind speeds shown in Figure 9, metal panel stiffening was observed in the trapezoidal roof panels around mean wind speed of 40 m/s while in the vertical-leg roof the deflection were predominantly within the flat pan sections. Figure 9. Deflection versus wind speed in Vertical-leg and Trapezoidal roofs 3.3 Observations of Roof Failure The ability of a metal panel to undergo high deflections without any permanent deformation or failure to the roof structure might vary depending on several factors including metal panel property, spacing of clips, width of panel, etc. In the vertical-leg standing seam no roof failure was observed for the full range of wind speeds and directions tested. Failures in the trapezoidal roof occurred at wind speed of 65.7 m/s when the wind direction was approximately normal to the sloping edges. Failures occurred at the high eave sides of the upwind end panel. Figure 10. Panel ballooning (left) and clip rupture (right) failures Panel ballooning, seam disengagement and panel rib rupture were observed and the mode of failure was clip breakage/rupture (Figure 10). The dominant type of failure in ASTM E1592 tests is clip slippage from seam, but this protocol doesn t account for the non-uniform vibratory loading that might cause fatigue failures at joints of the roof, which is believed to have happened in this case. The interlocking property of standing seam roofs gives them strength, but makes them susceptible to progressive failure. Once clip-breakage occurred, patterns of progressive failure were observed, seam-clip separation started to initiate in the neighboring clips and ballooning continued to the next panel. It should be noted here that the free condition used at one end of
9 8 the roof to replicate the end condition used in ASTM testing was not a condition that would normally occur in real installations. The vibration behavior in this area may have been somewhat exaggerated as a result. Further testing would be desirable using a more realistic end condition Even though the highest roof uplift pressure was measured at the low eave corner region, failure occurred at the high eave corners because the high eave edge was not fastened. To check whether roof failure occurred because of the free boundary condition at high eave side, the free high eave ends of the two edge panels were fastened to the purlin (Figure 11) and the testing at the wind speed causing failure and critical wind direction was repeated. When the end panel s high-eave and low-eave ends were fastened, the shape of the uplift deflection changed and the uplift force was concentrated on the two middle clips of the upwind edge panel, and eventually clip-slippage occurred at the middle clip near the high eave end (Figure 11). Moreover, under this boundary condition the deflections of the metal panel adjacent to the upwind edge panel were observed to be higher than the case when the edge panel was free. This might be due to the fact that the edge panel, in its fixed- free boundary condition might have been acting as an aerodynamic shield to its neighboring panel. At high deflections the roof geometry changes can affect the mean pressure distribution and uplift forces experienced. Figure 11. Clip failures with free (upper) and fixed (lower) edge panel boundary conditions 4 CONCLUSION An experimental investigation was performed to study the behavior of wind loads on the surfaces of two types of standing seam metal roofs and evaluate their performance under high wind speeds. When compared to the vertical-leg roofs, significantly higher uplift pressures were recorded on the trapezoidal roof. This showed that roof architectural details and perimeter eave trims have significant effect on the magnitude and distribution of the wind-induced pressures at the surface of the metal roofs. The results point to the need for more experimental investigation aimed at identifying the effects of such significant differences in uplift pressures. This will assist in identifying and designing aerodynamically favorable roof profiles and eave details. Comparison with experimental results showed that the wind loading provisions in ASCE 7-10 (which is based on bare deck models), might in some cases underestimate the actual uplift on a mono-sloped trapezoidal-leg standing seam roof. Owing to the elastic property of the metal panels, high panel deflections may not necessarily cause permanent deformation or roof failures, as observed in the vertical-leg roof which did not fail. The trapezoidal roof experienced higher suction pressures and higher deflections which led to progressive connection and panel roof failure. The main mode of failure in the trapezoidal roof was clip breakage/rupture. This failure mode is very different from clip slippage, which is the dominant type of failure in testing protocols that use uniform pressure load, and is hypothesized to have occurred due to excessive vibrations at the free end. It should be noted that the vibration experienced at the failing high-eave ends were exaggerated due to the fixed-free boundary conditions used. ACKNOWLEDGMENTS The authors greatly appreciate the cooperation of Jaime Gascon of Miami-Dade County Regulatory and Economic Resources Department (RER); Ken Buchinger and Jason Allen of MBCI; Richard Starks and Trey Herren of BRS, Inc.; Terry Wolfe and Brandon Jasek of Force Engineering & Testing, Inc.; and Dale Nelson of Roof Hugger, Inc. This research was supported by the Florida Division of Emergency Management (DEM) and the National Science Foundation (NSF) (NSF Award no. CMMI ). The help offered by Walter Conklin, Roy Liu-Marquis and Alvaro Mejia is greatly acknowledged. The findings expressed in this paper are those of the authors only and do not necessarily represent the views of the sponsors.
10 9 REFERENCES [1] Surry, D., Kopp, GA., Bartlett, FM., (2005). Wind load testing of low buildings to failure at model and full scale, Natural Hazards Review, 6, [2] Surry, D., Sinno, R.R., Nail, B., Ho, TC., Farquhar, S., Kopp, GA., (2007). Structurally effective static wind loads for roof panels, Journal of Structural Engineering, 133, [3] Prevatt, DO., Schiff, SD., Sparks, PR., (1995). A technique to assess wind uplift performance of standing seam metal roofs, 11th Conference on Roofing Technology, September 21-22, Gaithersburg, Maryland, USA. [4] Sinno, RR., Nail, B., Fowler, S., (2005). MBMA final report- Simulation of non-uniform unsteady wind pressures. [5] Sinno, RR., (2008). Response of metal roofs to uniform static and true hurricane wind loads, 9th International Specialty Conference on Cold- Formed Steel Structures, St. Louis, Missouri, USA. [6] Farquhar, S., Kopp, GA., Surry, D., (2005). Wind tunnel and uniform pressure tests of a standing seam metal roof model, Journal of Structural Engineering,131, [7] ASCE. (2010). Minimum design loads for buildings and other structures, American Society of Civil Engineers, Reston, VA. [8] Irwin, H., Cooper, KR., Girard, R., (1979). Correction of distortion effects caused by tubing systems in measurements of fluctuating pressures, Journal of Wind Engineering and Industrial Aerodynamics, 5, [9] ASTM E , (2001). Standard test method for structural performance of sheet metal roof and siding systems by uniform static air pressure difference, West Conshohocken, PA. [10] Asghari Mooneghi, M., Irwin, P., Gan Chowdhury, A. (2015). Partial turbulence simulation method for small structures, 14th International Conference on Wind Engineering, Porto Alegre, Brazil, June 21-26, [11] Asghari Mooneghi, M., (2014), "Experimental and analytical methodologies for predicting peak loads on building envelopes and roofing systems", FIU Electronic Theses and Dissertations. Paper [12] St Pierre, LM., Kopp, GA., Surry, D., Ho, TCE., (2005). The UWO contribution to the NIST aerodynamic database for wind loads on low buildings: Part 2. Comparison of data with wind load provisions, Journal of Wind Engineering and Industrial Aerodynamics, 93, [13] Huang, P., Mirmiran, A., Chowdhury, AG., Abishdid, C., Wang, T-L., (2009). Performance of roof tiles under simulated hurricane impact. Journal of Architectural Engineering, 15, [14] Li, R., Chowdhury, AG., Bitsuamlak, G., Gurley, KR., (2014). Wind effects on roofs with high-profile tiles: Experimental study, Journal of Architectural Engineering: Special Section: Housing and Residential Building Construction, 20. [15] Kopp, GA., Mans, C., Surry, D., (2005). Wind effects of parapets on low buildings: Part 4. Mitigation of corner loads with alternative geometries, Journal of Wind Engineering and Industrial Aerodynamics, 93, [16] Stathopoulos, T., Baskaran, A., (1987). Wind pressures on flat roofs with parapets, Journal of Structural Engineering, 113, [17] Kopp, GA., Surry, D., Mans, C., (2005). Wind effects of parapets on low buildings: Part 1. Basic aerodynamics and local loads, Journal of Wind Engineering and Industrial Aerodynamics, 93, [18] Asghari Mooneghi, M., Irwin, P., Gan Chowdhury, A., (2014). Large-scale testing on wind uplift of roof pavers, Journal of Wind Engineering and Industrial Aerodynamics, 128:22 36.
Testing Water Penetration Resistance of Window Systems Exposed to Realistic Dynamic Air Pressures
Testing Water Penetration Resistance of Window Systems Exposed to Realistic Dynamic Air Pressures R. A. Van Straaten 1, G. A. Kopp 2, J. F. Straube 3 1 Research Lab for Better Homes, University of Western
RenaissanceRe Wall of Wind Research -- Moving Innovations from Theory to Applications
RenaissanceRe Wall of Wind Research -- Moving Innovations from Theory to Applications by Arindam Gan Chowdhury, PhD Director, Laboratory for Wind Engineering Research, International Hurricane Research
Dynamic Wind Testing of Commercial Roofing Systems
Construction Technology Update No. 55 Dynamic Wind Testing of Commercial Roofing Systems by A. Baskaran Single-ply roofs (SPRs) behave differently than built-up roofs and a simple test method is needed
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)
MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER) 11805 SW 26 Street, Room 208 BOARD AND CODE ADMINISTRATION DIVISION Miami, Florida 33175-2474 T (786) 315-2590
APPLICATION INFORMATION FOR RESIDENTIAL ROOFING AND RESIDENTIAL ROOFING PACKET
Environmental Protection and Growth Management Department PERMITTING, LICENSING AND CONSUMER PROTECTION DIVISION 1 N. University Drive, Box #302 Plantation, Florida 33324 954-765-4400 www.broward.org/permittingandlicensing
STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS
ROOFING APPLICATION STANDARD (RAS) No. 133 STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS 1. Scope 1.1 This application standard has been developed to provide consistent information for the
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION
SINGLE FAMILY RESIDENCE HURRICANE MITIGATION APPLICATION As of October 1, 2007, this mitigation form must be submitted as part of the roofing permit application package. Secondary water barrier (if applicable)
Metal Roof Systems in High-Wind Regions
Metal Roof Systems in High-Wind Regions http://www.fema.gov HURRICANE IKE RECOVERY ADVISORY Purpose: To recommend practices for designing and installing metal roof systems that will enhance wind resistance
Prof. Dr. Zahid A. Siddiqi, UET, Lahore WIND LOAD
WIND LOAD Wind load is produced due to change in momentum of an air current striking the surface of a building. A building is less likely to experience the other design loads in its life but it is almost
(1) 2 TEST SETUP. Table 1 Summary of models used for calculating roughness parameters Model Published z 0 / H d/h
Estimation of Surface Roughness using CFD Simulation Daniel Abdi a, Girma T. Bitsuamlak b a Research Assistant, Department of Civil and Environmental Engineering, FIU, Miami, FL, USA, [email protected]
MacroFlo Opening Types User Guide <Virtual Environment> 6.0
MacroFlo Opening Types User Guide 6.0 Page 1 of 18 Contents 1. Introduction...4 2. What Are Opening Types?...5 3. MacroFlo Opening Types Manager Interface...5 3.1. Add... 5 3.2. Reference
Analysis of the Response Under Live Loads of Two New Cable Stayed Bridges Built in Mexico
Analysis of the Response Under Live Loads of Two New Cable Stayed Bridges Built in Mexico Roberto Gómez, Raul Sánchez-García, J.A. Escobar and Luis M. Arenas-García Abstract In this paper we study the
AIA PRESENTATION. Standing Seam Metal Roofing Seminar SSRLU2B 1 LU/HSW Hour
AIA PRESENTATION Standing Seam Metal Roofing Seminar SSRLU2B 1 LU/HSW Hour Best Practice MBCI is a Registered Provider with the American Institute of Architects Continuing Education Systems. Credit earned
ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: NORSE, INC. SERIES/MODEL: Flush Mount/Surface Mount PRODUCT TYPE: Hurricane Shutter Fastening System This report contains in its
CHAPTER 6 WIND LOADS
CHAPTER 6 WIND LOADS C6-1 CHAPTER 6 WIND LOADS Outline 6.1 General 6.1.1 Scope of application 6.1. Estimation principle 6.1.3 Buildings for which particular wind load or wind induced vibration is taken
Metal Roofing Practical Design
Metal Roofing Practical Design Metal Roofing Practical Design Learning Outcomes Minimum Requirements Design Resources Low Slope Metal Roofing Design Details Continuously Insulated (Ci) Systems Minimum
STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM
Chapter 9 STRUCTURAL CONCEPT FOR LIGHT GAUGE STEEL FRAME SYSTEM 9.1 BACKGROUND Steel is widely used in the construction of multi-storey buildings. However, steel construction is seldom used and is traditionally
TEST REPORT. Rendered to: DEXERDRY. For: Deck Weatherproofing System Installed with AZEK Deck Boards
TEST REPORT Rendered to: DEXERDRY For: Deck Weatherproofing System Installed with AZEK Deck Boards Report No.: E8122.01-119-19 Revision 1: 08/18/15 Report Date: 08/14/15 Test Record Retention Date: 07/16/19
SECTION 07400 STANDING SEAM METAL ROOF
SECTION 07400 STANDING SEAM METAL ROOF PART 1 - GENERAL 1.01 SECTION INCLUDES A. Work described in this section includes pre-formed standing seam metal roofing system complete with clips, perimeter and
UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC
UL 580 TEST REPORT Rendered to: ARMSTRONG WORLD INDUSTRIES SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC Report No.: Test Dates: 12/14/09 Through: 12/22/09 Report Date: 03/12/10 Expiration
Nucor VR16 II TM Vertical Rib Standing Seam Roof System
Nucor VR16 II TM Vertical Rib Standing Seam Ro System www.nucorbuildingsystems.com Nucor VR16 II Vertical Rib Standing Seam Ro Perfect for the Marketplace The Nucor Building Systems VR16 II Ro Panel is
Wind Effects of Hurricane Ike on Chase Tower in Downtown Houston
Wind Effects of Hurricane Ike on Chase Tower in Downtown Houston Rolando E. Vega, Ph.D., P.E., ABS Consulting ([email protected]) Robert C. Konz, P.E., ABS Consulting ([email protected]) On
INSTALLATION. General. Important Note. Design. Transport
General The roof trusses you are about to install have been manufactured to precise engineering standards. To ensure that the trusses perform as designed, it is essential that they be handled, erected
Natural Convection. Buoyancy force
Natural Convection In natural convection, the fluid motion occurs by natural means such as buoyancy. Since the fluid velocity associated with natural convection is relatively low, the heat transfer coefficient
Product and Package Testing Requirements for Transportation, Storage and Delivery
Product and Package Testing Requirements for Transportation, Storage and Delivery MN2-810.13 Revision 16 May 14, 2009 Created By: David Batz Chris Donnelly Mark James Dave Leinberger Paul McKenzie Bill
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES. Interpretations of the FTP
INTERNATIONAL ASSOCIATION OF CLASSIFICATION SOCIETIES Interpretations of the FTP CONTENTS FTP1 Adhesives used in A or B class divisions (FTP Code 3.1, Res A.754 para. 3.2.3) June 2000 FTP2 Pipe and duct
STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES
ROOFING APPLICATION STANDARD (RAS) No. 117 STANDARD REQUIREMENTS FOR BONDING OR MECHANICAL ATTACHMENT OF INSULATION PANELS AND MECHANICAL ATTACHMENT OF ANCHOR AND/OR BASE SHEETS TO SUBSTRATES Scope 1.1.
Residential Roofing Guide
Residential Roofing Guide TABLE OF CONTENTS Building Detail and Accessories...... 1 Panel Introduction and Handling...... 2 Cutting and Trimming.... 3 Roof Preparation..... 3 Roof Slope..... 3 Re-roofing...
ICC-ES Evaluation Report Reissued March 1, 2011 This report is subject to renewal in one year.
ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-900* Reissued March, 20 This report is subject to renewal in one year. A Subsidiary of the International Code Council DIVISION:
CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...
Building Insulations - Walls and Ceilings (FM Approval Numbers 4411, 4651, 4880, 4881, 4882) Insulating materials may occur in building construction to reduce heat or sound transmission through a wall,
PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC.
PERFORMANCE TEST REPORT Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC. SERIES/MODEL: AMS ARMOR-LOCK PRODUCT TYPE: STANDING SEAM METAL ROOF PANEL SYSTEM Report No: 97123.02-901-44 Test Date: 05/17/10
determining wind and snow loads for solar panels America s Authority on Solar
determining wind and snow loads for solar panels America s Authority on Solar Determining wind and snow loads for solar panels 1 introduction As one of the largest and most established vertically integrated
Solar Water Heating and Solar Electric Generators Installed on One or Two Family Dwellings
Solar Water Heating and Solar Electric Generators Installed on Category: Residential Construction Revised: [Paul L. Scarlett], Director Responsible Bureau Section: Development Services Center 1900 SW Fourth
EDW + FS, VS, VSE, GGL, GGU, GHL. EDW Deck Mounted Skylight and Roof Window Flashing Installation Instructions VAS 452259-0509
EDW + FS, VS, VSE, GGL, GGU, GHL EDW Deck Mounted Skylight and Roof Window Flashing Installation Instructions VAS 4559-0509 a FS, VS, VSE For proper installation, remove cladding as shown b GGL, GGU, GHL
VERTICAL LOCK Table of Contents
Table of Contents TABLE OF CONTENTS Vertical Lock Product Data Sheet... 2 Vertical Lock Engineering Data... 3 General Information... 6 Material Testing... 7 Panel Overview... 8 Handling Material & Storage
Flow in data racks. 1 Aim/Motivation. 3 Data rack modification. 2 Current state. EPJ Web of Conferences 67, 02070 (2014)
EPJ Web of Conferences 67, 02070 (2014) DOI: 10.1051/ epjconf/20146702070 C Owned by the authors, published by EDP Sciences, 2014 Flow in data racks Lukáš Manoch 1,a, Jan Matěcha 1,b, Jan Novotný 1,c,JiříNožička
CH. 2 LOADS ON BUILDINGS
CH. 2 LOADS ON BUILDINGS GRAVITY LOADS Dead loads Vertical loads due to weight of building and any permanent equipment Dead loads of structural elements cannot be readily determined b/c weight depends
providing documentation that validates the year of construction. Acceptable documents include
902. WINDSTM MITIGATION FEATURES A. For policies that cover the peril of Windstorm or Hail, a premium credit may be available if one or more of the following loss mitigation features or construction techniques
Rain Penetration Tests on Manthorpe Mini Castellated Vent Tile with 15" x 9" Format Roof Tiles. Prepared for: Ben Hales
Rain Penetration Tests on Manthorpe Mini Castellated Vent Tile with 15" x 9" Format Roof Tiles Prepared for: Ben Hales Manthorpe Building Products Ltd. 24 th June 2014 Report number 295-318 1 Rain Penetration
INTERNATIONAL BUILDING CODE STRUCTURAL
S1-07/08 1502.1 INTERNATIONAL BUILDING CODE STRUCTURAL Proposed Change as Submitted: Proponent: Mike Ennis, SPRI, Inc. Revise as follows: 1502.1 General. The following words and terms shall, for the purposes
Protecting Roofing Systems Against Windstorm Damage
Protecting Roofing Systems Against Windstorm Damage This brochure is made available for informational purposes only in support of the insurance relationship between FM Global and its clients. This information
Experiment (13): Flow channel
Introduction: An open channel is a duct in which the liquid flows with a free surface exposed to atmospheric pressure. Along the length of the duct, the pressure at the surface is therefore constant and
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Panorama 8-mil Film PRODUCT TYPE: Fixed Window with Applied Film This
Report on. Wind Resistance of Signs supported by. Glass Fiber Reinforced Concrete (GFRC) Pillars
Report on Wind Resistance of Signs supported by Glass Fiber Reinforced Concrete (GFRC) Pillars Prepared for US Sign and Fabrication Corporation January, 2006 SUMMARY This study found the attachment of
Numerical Simulation of CPT Tip Resistance in Layered Soil
Numerical Simulation of CPT Tip Resistance in Layered Soil M.M. Ahmadi, Assistant Professor, [email protected] Dept. of Civil Engineering, Sharif University of Technology, Tehran, Iran Abstract The paper
ANSI/SPRI Wind Design Standard Practice for Roofing Assemblies
Approved September 19, 2007 ANSI/SPRI WD-1 ANSI/SPRI Wind Design Standard Practice for Roofing Assemblies TABLE OF CONTENTS Section Page 1.0 INTRODUCTION...........................................................
TABLE OF CONTENTS" SECTION 3: Comparing Standing Seam Metal to Other Metal Roofs PAGE 7"
2 TABLE OF CONTENTS SECTION 1: What is a Standing Seam Metal Roof PAGE 3 SECTION 2: Common Types of Standing Seam Metal Roofs..PAGE 5 SECTION 3: Comparing Standing Seam Metal to Other Metal Roofs PAGE
Table of Contents. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide. Notes to Designer /Installers..
Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3
oil liquid water water liquid Answer, Key Homework 2 David McIntyre 1
Answer, Key Homework 2 David McIntyre 1 This print-out should have 14 questions, check that it is complete. Multiple-choice questions may continue on the next column or page: find all choices before making
Assessing Curtain Walls
Assessing Curtain Walls Considerations and Best Practices Paul E Beers GCI Consultants, LLC [email protected] What is a Curtain Wall System? A curtain wall system is an outer covering of a building
Strip Flatness Prediction in a 4 High Tandem Mill Using a Dynamic Model.
Strip Flatness Prediction in a 4 High Tandem Mill Using a Dynamic Model. M. A. Bello-Gomez 1, M. P. Guerrero-Mata 1, L. A. Leduc Lezama 1, T. P. Berber- Solano 1, L. Nieves 2, F. Gonzalez 2, H. R. Siller
TEST REPORT. Report No.: A9814.01 109 44. Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept
Architectural Testing TEST REPORT Report No.: A9814.01 109 44 Rendered to: BAMCO INC. Middlesex, New Jersey PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept AAMA 508 07, Voluntary Test Method
CLOSED-CELL SPRAY FOAM Resisting Wind Uplift in Residential Buildings
CLOSED-CELL SPRAY FOAM Resisting Wind Uplift in Residential Buildings RICHARD S. DUNCAN, Ph.D., P.E. JINHUANG WU, Ph.D. NOTICE: All statements, information and data given herein are believed to be accurate
Compression load testing straw bale walls. Peter Walker Dept. Architecture & Civil Engineering University of Bath Bath BA2 7AY.
Compression load testing straw bale walls Peter Walker Dept. Architecture & Civil Engineering University of Bath Bath BA2 7AY May 2004 1. Introduction Over the last 10 years a growing number of loadbearing
Lift and Drag on an Airfoil ME 123: Mechanical Engineering Laboratory II: Fluids
Lift and Drag on an Airfoil ME 123: Mechanical Engineering Laboratory II: Fluids Dr. J. M. Meyers Dr. D. G. Fletcher Dr. Y. Dubief 1. Introduction In this lab the characteristics of airfoil lift, drag,
CITY OF FLORIDA CITY Building and Zoning Department 404 West Palm Drive Florida City, FL 33034 305-247-8222 ROOFING PERMIT APPLICATION
IF SUBSIDIARY, PROVIDE MASTER PERMIT NUMBER HERE: CITY OF FLORIDA CITY Building and Zoning Department 404 West Palm Drive Florida City, FL 33034 305-247-8222 ROOFING PERMIT APPLICATION Location of Improvements
RESIDENTIAL ROOF PERMITTING - 101. A REFRESHER WORKSHOP September 11, 2014
RESIDENTIAL ROOF PERMITTING - 101 A REFRESHER WORKSHOP September 11, 2014 Agenda Basics of Permit Application Use of Charlotte County GIS system Florida Product Approvals Top Application Mistakes Standard
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 32 16 CONCRETE ROOF TILES REPORT HOLDER:
0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 1900 Reissued 03/2016 This report is subject to renewal 03/2017. DIVISION: 07 00 00 THERMAL
STRUCTURAL OPTIMIZATION OF REINFORCED PANELS USING CATIA V5
STRUCTURAL OPTIMIZATION OF REINFORCED PANELS USING CATIA V5 Rafael Thiago Luiz Ferreira Instituto Tecnológico de Aeronáutica - Pça. Marechal Eduardo Gomes, 50 - CEP: 12228-900 - São José dos Campos/ São
In-situ Load Testing to Evaluate New Repair Techniques
In-situ Load Testing to Evaluate New Repair Techniques W.J. Gold 1 and A. Nanni 2 1 Assistant Research Engineer, Univ. of Missouri Rolla, Dept. of Civil Engineering 2 V&M Jones Professor, Univ. of Missouri
Mesh Moving Techniques for Fluid-Structure Interactions With Large Displacements
K. Stein Department of Physics, Bethel College, St. Paul, MN 55112 T. Tezduyar Mechanical Engineering, Rice University, MS 321, Houston, TX 77005 R. Benney Natick Soldier Center, Natick, MA 01760 Mesh
DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 32 16 CONCRETE ROOF TILES REPORT HOLDER: BORAL ROOFING
0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-1647 Reissued 08/2015 This report is subject to renewal 08/2016. DIVISION: 07 00 00 THERMAL
Load Design Charts. R-CONTROL SIPs STRUCTURAL INSULATED PANELS. www.r-control.com CONTROL, NOT COMPROMISE.
R-CONTROL s STRUCTURAL INSULATED PANELS Note: Information deemed reliable at time of printing. Please visit www.r-control.com for latest information. June 2012 CONTROL, NOT COMPROMISE. www.r-control.com
Conservatory Roof Structural Information Guide
Conservatory Roof Structural Information Guide Effective from ugust 8 Useful Information This guide displays data on the permissible roof member spans and for different roof loadings; it should be used
Commercial Residential Model Reviews
Commercial Residential Model Reviews Prepared by the Professional Team for The Florida Commission on Hurricane Loss Projection Methodology May 2002 I. Background and Items for Consideration In May, 2000,
Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood
Drexel Metals Inc. DMC 100SS 16oz min. Copper Mechanical Seam Metal Roof System over Plywood Section 07411 Metal Roof Panels Part 1 General 1.1 Summary A. This section includes the following: a. Factory-formed
Installation Manual for STANDING SEAM ROOFING
Installation Manual for STANDING SEAM ROOFING Absolute Steel Toll Free 877-833-3237 / Phone 480-768-1618 / Fax 480-768-1514 www.metalroofingsource.com Standing Seam features approximately one-inch high
www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council *Revised April 2014
ICC-ES Evaluation Report ESR-1647* Issued July 2013 This report is subject to renewal August 1, 2015. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council DIVISION:
NUMERICAL ANALYSIS OF THE EFFECTS OF WIND ON BUILDING STRUCTURES
Vol. XX 2012 No. 4 28 34 J. ŠIMIČEK O. HUBOVÁ NUMERICAL ANALYSIS OF THE EFFECTS OF WIND ON BUILDING STRUCTURES Jozef ŠIMIČEK email: [email protected] Research field: Statics and Dynamics Fluids mechanics
Mark Cramer Inspection Services, Inc.
Mark Cramer Inspection Services, Inc. 492 Twentieth Avenue, Indian Rocks Beach, FL 34635-2970 (727) 595-4211 Fax (727) 596-7583 Certified Member #12085 American Society of Home Inspectors Construction
Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings
Best2 Airtightness of Buildings Session WB6-2 Evaluating the Field Performance of Windows and Curtain Walls of Large Buildings Mario D. Gonçalves, Patenaude-Trempe and Robert Jutras, Air-Ins Introduction
HEAT TRANSFER ENHANCEMENT IN FIN AND TUBE HEAT EXCHANGER - A REVIEW
HEAT TRANSFER ENHANCEMENT IN FIN AND TUBE HEAT EXCHANGER - A REVIEW Praful Date 1 and V. W. Khond 2 1 M. Tech. Heat Power Engineering, G.H Raisoni College of Engineering, Nagpur, Maharashtra, India 2 Department
Experimental Evaluation of the Discharge Coefficient of a Centre-Pivot Roof Window
Experimental Evaluation of the Discharge Coefficient of a Centre-Pivot Roof Window Ahsan Iqbal #1, Alireza Afshari #2, Per Heiselberg *3, Anders Høj **4 # Energy and Environment, Danish Building Research
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000
RESIDENTIAL ROOFING & RE-ROOFING, ROOF VENTILATION AND ROOF SHEATHING REQUIREMENTS MICHIGAN RESIDENTIAL CODE 2000 SECTION R905 REQUIREMENTS FOR ROOF COVERINGS R905.1 Roof covering application. Roof coverings
MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up
MOCK-UP TEST REPORT Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up Report No: 85616.01-120-32 Test Completion Date: 01/15/09 Report Date: 02/11/09 Record Retention End Date: 01/15/13
4.3.5 - Breakaway Walls
4.3.5 - Breakaway Walls Elevation of a structure on a properly designed foundation reduces the potential for water damage from flooding. When the space below the lowest elevated floor is maintained free
Low Profile Raised Deck with Pedestal System: A Level Approach to Building Decks
Low Profile Raised Deck with Pedestal System: A Level Approach to Building Decks START www.bisondecksupports.com 1 Bison Deck Supports 2009 Introduction Adjustable Deck Support Systems Designed to level
How To Test For An Architectural Test
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: CORAL ARCHITECTURAL PRODUCTS SERIES/MODEL: PW 256 with Door Openings PRODUCT TYPE: Aluminum Impact Resistant Curtain Wall System
Wind effects on roof-mounted solar photovoltaic arrays: CFD and wind-tunnel evaluation
Wind effects on roof-mounted solar photovoltaic arrays: CFD and wind-tunnel evaluation Robert N. Meroney a and David E. Neff b a Colorado State University, Fort Collins, CO, USA, [email protected]
Table of Contents. Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide
Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide Table of Contents Section Page Section Page Notes to Designer /Installers.. 1 Fastener Placement and Selection.2-3
SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK
SECTION 07410 PREFORMED METAL STANDING SEAM ROOFING PART 1 - GENERAL 1.1 DESCRIPTION OF WORK A. This section covers the pre-finished, pre-fabricated Architectural standing seam roof system. All metal trim,
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B9460.01-109-18. Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Report No.: B9460.01-109-18 Rendered to: CAPTIVEAIRE, INC. Blue Bell, Pennsylvania PRODUCT TYPE: Roof Mounted Exhaust Fan SERIES/MODEL: CASRE
Practice Problems on Boundary Layers. Answer(s): D = 107 N D = 152 N. C. Wassgren, Purdue University Page 1 of 17 Last Updated: 2010 Nov 22
BL_01 A thin flat plate 55 by 110 cm is immersed in a 6 m/s stream of SAE 10 oil at 20 C. Compute the total skin friction drag if the stream is parallel to (a) the long side and (b) the short side. D =
CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER
International Journal of Advancements in Research & Technology, Volume 1, Issue2, July-2012 1 CFD SIMULATION OF SDHW STORAGE TANK WITH AND WITHOUT HEATER ABSTRACT (1) Mr. Mainak Bhaumik M.E. (Thermal Engg.)
STUDY OF DAM-RESERVOIR DYNAMIC INTERACTION USING VIBRATION TESTS ON A PHYSICAL MODEL
STUDY OF DAM-RESERVOIR DYNAMIC INTERACTION USING VIBRATION TESTS ON A PHYSICAL MODEL Paulo Mendes, Instituto Superior de Engenharia de Lisboa, Portugal Sérgio Oliveira, Laboratório Nacional de Engenharia
PERFORMANCE TEST REPORT. Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall
PERFORMANCE TEST REPORT Rendered to: FORMTECH ENTERPRISES, INC. SERIES/MODEL: Truline PRODUCT TYPE: PVC Seawall Report No.: Test Dates: 04/17/12 Through: 04/18/12 Report Date: 06/13/12 130 Derry Court
TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana
Architectural Testing TEST REPORT Report No.: D0162.02-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite
Discipline: Structural Issued 04-26-06
California Department of General Services. Division of the State Architect. Product Acceptance Report STRUCTURAL SHEAR PANEL SURE-BOARD SERIES 200 PANELS PA-132 Discipline: Structural Issued 04-26-06 This
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS
ROOFING APPLICATION STANDARD (RAS) No. 150 PRESCRIPTIVE BUR REQUIREMENTS 1. 2. 3. 3.0 Scope 1.1 This application standard shall be used where the authority having jurisdiction has adopted its use, and
ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider
ASTM E 1886 and ASTM E 1996 TEST REPORT Rendered to: Atrium Companies, Inc. SERIES/MODEL: 50/305 HS PRODUCT TYPE: Vinyl Horizontal Slider Report No.: Test Date: 5/21/07 Through: 5/23/07 Report Date: 5/30/07
Active noise control in practice: transformer station
Active noise control in practice: transformer station Edwin Buikema 1 ; Fokke D. van der Ploeg 2 ; Jan H. Granneman 3 1, 2, 3 Peutz bv, Netherlands ABSTRACT Based on literature and extensive measurements
Stylish, low maintenance, stain resistant, wear resistant alternative to concrete pavers
Stylish, low maintenance, stain resistant, wear resistant alternative to concrete pavers Single slab porcelain pavers offer an exceptional paving solution where high stain resistance, scratch resistance,
Protecting YOUR NEW HOME FROM Wind Damage
Protecting YOUR NEW HOME FROM Wind Damage Blueprint for Safety... A Blueprint for Life When severe weather threatens, protecting life and property automatically becomes top priority for millions of Florida