December 24, SEDA Construction Attn: Ted Walker 2120 Corporate Square Boulevard Jacksonville, Florida 32216
|
|
- Rosalyn Rosamund Armstrong
- 8 years ago
- Views:
Transcription
1 December 24, 2008 SEDA Construction Attn: Ted Walker 2120 Corporate Square Boulevard Jacksonville, Florida RE: Georgetown Community 2C - Revised Assessment Date: October 27, 2008 Revision Date: December 17, 2008 SkyeTec Project No: Dear Mr. Walker: SkyeTec has completed a limited water intrusion assessment at the living room windows and kitchen sliding glass door at the above-referenced property. The purpose of this assessment was to determine the source of the moisture that has been observed within those areas. SkyeTec visited the property on October 27, 2008 and December 17, Our assessment included visual observations, water testing, thermal imaging evaluation, and a moisture survey. This report summarizes the findings of our assessment and provides our conclusions. Observations and Measurements For reporting purposes the front entrance of the residence is assumed to face due east. Interior walls and the ceilings were finished with gypsum board. A visual assessment of the living room and kitchen and adjacent areas was conducted to determine the extent of microbial growth and unusual moisture conditions. Moisture measurements were obtained using a Protimeter MMS BLD5800 moisture meter. Moisture measurements are obtained by inserting the pins of the moisture meter into the material being evaluated, or by placing the flat surface of the meter onto the material being evaluated. For wood, the moisture content is expressed as percent moisture content (%MC); for other materials the measurement is expressed as percent moisture equivalent (%WME). Generally,
2 %MC or %WME measurements of less than 17 are considered to be dry ; measurements between 18 and 20 are considered to be at risk for moisture damage; and measurements of 21 percent or greater are considered to be wet. The non-invasive mode of the meter provides a qualitative measurement in general accordance with the above scale. We made the following observations during our site visit: Kitchen 1. We observed moisture staining and damage on the upper portion of the sliding glass door return. 2. A water test, utilizing a garden hose, was conducted on the northern portion of the third floor window. The water test resulted in moisture intrusion in the kitchen, water was observed seeping from the upper portion of the sliding glass door return adjacent to the security component. Living Room 1. We observed moisture staining and damage on the upper portion of the center window return in the living room. (1 square foot) 2. A water test was unable to be performed at the time of the assessment. Conclusions Based on the available information, we conclude the following: 1. The moisture impacted building materials in the kitchen adjacent to the sliding glass door is consistent with moisture intrusion through the northern portion of the third floor window penetration during periods of rain fall. 2. Seda construction conducted removal of the stucco along the rear of the residence at the second floor sliding glass door assembly extending to the third floor and visual moisture staining and damage was observed on the OSB adjacent to the lower window corners. It appears that moisture has intruded at these areas during rain events. 3. Seda construction conducted removal of the stucco along the front of the residence at the second floor sliding glass door assembly extending to the third floor and visual moisture staining and damage was observed on the OSB below the roof overhang. It appears that moisture has intruded at the roof flashing during rain events.
3 SkyeTec appreciates the opportunity to provide professional services for SEDA Construction. If you have any questions regarding the assessment or would like a follow up inspection, please feel free to contact us at Sincerely, Joe Barron Industrial Hygienist
4 ATTACHMENT A SITE IMAGES Exterior - Kitchen moisture intrusion observed after water test of the northern portion of the third floor window. Exterior - Kitchen moisture intrusion observed after water test of the northern portion of the third floor window. Kitchen moisture intrusion observed after water test of the northern portion of the third floor window. Exterior Living Room inaccessible area.
5 flashing of the overhang. flashing of the overhang. third floor window corners. third floor window corners.
6 ATTACHMENT B Limitations This assessment was conducted following standard practices and guidelines. Regardless of the thoroughness of an assessment, it is possible that some areas containing visible mold growth, water damage, and/or elevated moisture content or other indicators of poor indoor air quality were inaccessible or not evident during the assessment. The findings and recommendations included represent conditions evident at the time of the assessment. Building conditions related to indoor air quality, microbial growth and moisture intrusion may be subject to change on a daily basis. Therefore, the conditions observed and reported herein may not be evident in the future. If additional information becomes available which may affect SkyeTec s findings and recommendations, we request the opportunity to evaluate the information and modify our findings and recommendations as appropriate. SkyeTec has endeavored to meet what it believes is the applicable standard of care ordinarily exercised by others in conducting this assessment. No other warranty, express or implied, is made regarding the information contained in this report. This report has been prepared for the sole and exclusive use of the Client subject to previously agreed-upon terms and conditions. This report may not be suitable for the needs of others. Therefore, any reliance by other parties on the contents of this report is not granted and any such reliance shall be at the sole risk of the user.
RDH Building Sciences Inc.
MAK LTR 2007 03 26 Proposal for Building Enclosure Consulting Services RDH Building Sciences Inc. 509 FAIRVIEW AVENUE N SEATTLE WA 98109-5507 TEL 206 324 2272 FAX 206 324 6339 SEA@RDHBE.COM WWW.RDHBE.COM
More informationNon Invasive Roof Leak Detection Using Infrared Thermography
Non Invasive Roof Leak Detection Using Infrared Thermography Scott Wood Four Star Cleaning and Restoration, Inc. ABSTRACT Residential roofs without attics are typically inspected for leaks by installing
More informationHEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com
HEDDERMAN ENGINEERING, INC. www.heddermanengineering.com Office 281-355-9911, Fax 281-355-9903 office@heddermanengineering.com, 2011 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,
More informationHomeSpec REPORT SUMMARY
HomeSpec 04/25/2007 Ms. Rachel Trujeque Re: 13038 West Plum Road Lot #1225 - Peoria, AZ. 85383 - Pre Drywall Inspection Dear Ms. Trujeque, At your request, a visual pre drywall inspection of the above
More informationInspecting to a higher standard.
Inspecting to a higher standard. Rob Hopkin Silver Spring, MD 20902 Monday, June 2, 2014 ProTec Inspection Services Inc. 19736 Selby Ave Poolesville, MD 20837 301-972-8531 www.protec-inspections.com rob@protec-inspections.com
More informationRE: MOULD SURVEY BASEMENT APARTMENT WINNIPEG, MANITOBA
Practical Health and Safety Solutions Doug Wylie, CIH, ROH, CRSP, CRM 121 Keedian Drive, East St. Paul, MB R2E 0K3 Phone (204) 668-3141 Fax (204) 654-9583 Email: winnipegairtesting@shaw.ca RE: MOULD SURVEY
More informationLighthouse Engineering, L.L.C.
Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: Office@LighthouseEng.com Thursday, September 04, 2014 TO: Our Client RE: Engineering Evaluation
More informationInfrared Moisture Detection
What it can do for you... what it can t and why 1. Infrared camera basics 2. Examples Lew Harriman MoistureDM.com 3. Summary - The 4 most important facts about infrared moisture detection 1 of 19 Infrared
More informationVision Home Inspection
Vision Home Inspection 324 Rams Run Shepherdsville KY 40165-7877 Inspector: James McFadden Property Inspection Report Client(s): Property address: Inspection date: View report summary This report is the
More informationLighthouse Engineering, L.L.C.
Wednesday, August 20, 2014 Lighthouse Engineering, L.L.C. Michael Gandy, P.E. Registered Professional Engineer (TX: 95672) Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website:
More informationPROFESSIONAL ENGINEERING INSPECTIONS, INC.
PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX 271492 HOUSTON, TEXAS 77277 Registered Engineering Firm #1503 http://www.profengineering.com (713) 664-1264 July 8, 2004 Mr. Simple Samson 2831 Octoberfest
More informationNational Home Builder - Name Wednesday, August 20, 2014 Regional Customer Care Manager 1234 Main Street Houston, Texas 77067
Lighthouse Engineering, L.L.C. Michael Gandy, P.E. Registered Professional Engineer (TX: 95672) Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com
More informationSTRUCTURAL ASSESSMENT
STRUCTURAL ASSESSMENT Project: 1432-1434 East Commerce St. Job. No: 122200 Location: San Antonio, TX Date: Dec. 10, 2012 Weather: Sunny, Windy,60 deg Performed by: Jeff Haughton and Frank Lamas, Alpha
More informationFIELD TESTING SERVICES
FIELD TESTING SERVICES Chris Leach Director of Testing Baton Rouge, Louisiana Destin, Florida Scott Leach David Nichols Field Testing Representative Field Testing Representative 17485 Opportunity Avenue
More informationOSMA, Inc. 300 SW 74 Terrace Plantation, FL 33317 (754) 244 6653
Have Microscope Will Travel OSMA, Inc. 300 SW 74 Terrace Plantation, FL 33317 (754) 244 6653 Report of Findings and Recommendations Based on Visual Inspection for Water Damage and Limited Microbial Assessment
More informationProScan v.1.2. Owner s Manual
ProScan v.1.2 Owner s Manual TABLE OF CONTENTS INTRODUCTION.... 2 SWITCH KEY FUNCTIONS.....3 OPERATION.....4 TIPS FOR USING PROSCAN TO MEASURE WOOD.. 5 TIPS FOR USING PROSCAN TO MEASURE RELATIVE MOISTURE....6
More informationJanuary 23, 2009 Reference No. 055643
1412 Oakbrook Drive, Suite #180. Norcross, GA 30093 Telephone: (770) 441-0027 Fax: (770) 441-2050 www.craworld.com January 23, 2009 Reference No. 055643 Chief Deputy Stan Copland Douglas County Sheriffs
More informationRoof Inspection. Summary Report
www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,
More informationRe: Addendum to Preliminary Water Damage Report, Mendocino Public Health Branch, 1120 South Dora Street, Ukiah, CA
IAS 960 Ms. Kristin McMenomey Risk Manager County of Mendocino 841 Low Gap Road Ukiah, CA 95482 Re: Addendum to Preliminary Water Damage Report, Mendocino Public Health Branch, 1120 South Dora Street,
More informationPROPERTY INSPECTION OR ASSESSMENT OF DAMAGES
PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: Somewhere, FL CLIENT: GAIA GC ID No: 2015000 DATE: 12/31/2015 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792 FLORIDA
More informationPhotos showing the change in condition from 2006 to 2012 are located in Appendix A.
January 27, 2012 Ms. Theresa Gallavan Economic Development Director City of Lompoc 100 Civic Center Plaza Lompoc, California 93436 RE: Lompoc Theater Limited Visual Condition Assessment Dear Theresa: Representatives
More informationPELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT. November 2007
PELHAM MEMORIAL HIGH SCHOOL STONE FAÇADE REPORT November 2007 PURPOSE OF INVESTIGATION Determine possible locations of moisture intrusion into and through facade. Determine cause of horizontal and vertical
More informationCONSTRUCTION PROGRESS MONITORING REPORT
CONSTRUCTION PROGRESS MONITORING REPORT Windermere Memory Care 1060 Tomyn Boulevard Ocoee, FL 34787 Partner Project Number: 15-133494.16 Prepared for: ORIX USA Corporation 1717 Main Street, Suite 1100
More informationSignature on File For Custodial Supervisor Use Only
THE SCHOOL BOARD OF BROWARD COUNTY, FLORIDA ENVIRONMENTAL HEALTH & SAFETY DEPARTMENT TELEPHONE (754) 321-4200 FACSIMILE: (754) 321-4285 August 13, 2015 Signature on File For Custodial Supervisor Use Only
More informationwww.citiesinspection.com October 5, 2015 Dear Client,
www.citiesinspection.com October 5, 2015 Dear Client, On 9/14/2015, Cities Inspection Service, Inc. completed a building inspection of the property located at 123 Oak Street, Someplace, Minnesota for you.
More informationLighthouse Engineering, L.L.C.
Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website: www.lighthouseeng.com Email: Office@LighthouseEng.com Thursday, September 04, 2014 TO: Our Client RE: Initial Engineering
More informationExterior Elevated Elements Inspection Guidelines
Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code
More informationMold Investigation Summary Report
Gold Health and Safety Consulting, Inc. 4001 Inglewood Ave., Suite 101-292, Redondo Beach, CA 90278 (310) 219-1955 (310) 219-1934 - Fax SUBJECT PROPERTY LOCATED AT: 4405 Tomorrowland Ave., Disneyland,
More informationWilliamson and Associates, Inc. Report of Building Exterior Condition Evaluation, dated January 2 nd, 2013. (68 pages)
INNOVATIVE BUILDING AND ARCHITECTURE CONSULTANTS Mr. Bud Hall Senior Vice President of construction Turnberry Associates 19501 Biscayne Boulevard, Suite 400 Aventura, FL 33180 Subject: The Nashville Hilton
More informationMarch 14, 2007. Installation of Bay, Bow and Garden Windows
March 14, 2007 Re: Installation of Bay, Bow and Garden Windows Attached are the Atrium Companies, Inc recommendation for the installation of bay, bow and garden windows. These instructions were developed
More informationCLIENT. Inspection Report. 271 Front St. Alert Bay, B.C. Island Building Inspections V ANCOUVER I SLAND B. C.
CLIENT Inspection Report 271 Front St. Alert Bay, B.C. Island Building Inspections 2013 V ANCOUVER I SLAND B. C. Elevation Photos For the Property at 271 Front Street Alert Bay, BC ELEVATION PICTURES Front
More informationBuilding Condition Assessment: 109-111 North Howard Street Baltimore, Maryland
KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,
More informationStructure Survey Findings:
Structure Survey Findings: Visible portions of the following were observed: foundations; structure to walls, columns, floors, roofs, overhang posts, and columns; attached or firmly abutting decks, balconies,
More informationMold Management Plan Operations & Maintenance
Document #: SAFETY_015 Revision Date: October 4, 2010 Mold Management Plan Operations & Maintenance Developed by: Environmental Health & Safety Approved by: Associate VP of Facilities & Campus Services
More informationENVIRONMENTAL HEALTH CONSULTANTS
Ti Forensic Analytical ENVIRONMENTAL HEALTH CONSULTANTS Mold Investigation Report Findings of Initial Assessment Emerson Elementary School 2800 Forest Avenue Berkeley, CA July 18, 2013 Prepared for: Kevin
More informationWATER DAMAGE INVESTIGATION. Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts
WATER DAMAGE INVESTIGATION Massachusetts Department of Public Utilities 1 South Station Boston, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental Health Indoor
More informationStucco Moisture Inspection Report
Stucco Moisture Inspection Report For the Property Located At: Sample Inspection St. Report Prepared Ecusively For: Potential Buyer Pace FL. 32571 >< 850.393.6106 >< ofc- 850-941-8600 > Email: pat@moistureconsultantsinc.com
More informationE-mail: m-skaria@tamu.edu. http://primera.tamu.edu/kcchome/faculty/ms.htm. Moisture Challenges & Solutions: Proactive Construction Strategies
E-mail: m-skaria@tamu.edu http://primera.tamu.edu/kcchome/faculty/ms.htm Moisture Challenges & Solutions: Proactive Construction Strategies 62 nd Annual Convention of the International Builders Show Orange
More informationFoundation Evaluation Report for PROPERTY ADDRESS Houston, Texas 77089. August 30, 2012. Prepared for:
A Full Service Real Estate Inspection & Engineering Firm for Houston, Texas 77089 August 30, 2012 Prepared for: CLIENT S NAME MAILING ADDRESS Houston, Texas 77089 Prepared by: Charles J. Jenkins, P.E.
More informationMold Assessment. 816 Seabury Street Modular Units A & B Effingham, Kansas
11AY-3j-2005 TUE 02: 09 PM tleta FAX NO, 785 842 6993 p, 01....' ~.:. "". Mold Assessment of 816 Seabury Street Modular Units A & B Effingham, Kansas Corporate Office P,O, Box 786 Lawrence, KS 66044 785,842.6382
More informationAssessing Curtain Walls
Assessing Curtain Walls Considerations and Best Practices Paul E Beers GCI Consultants, LLC pbeers@gciconsultants.com What is a Curtain Wall System? A curtain wall system is an outer covering of a building
More informationStuccoSpec Moisture Testing Inspection
e-mail - stuccospec@juno.com StuccoSpec Moisture Testing Inspection Property Located At: 265 Elm Street, Anywhere, USA 01/27/02 Ordered by: Mr. & Mrs. John Doe #2 Song Sparrow Place, The Woodlands, T 77381281-364-0012
More informationWATER DAMAGE/MOLD INVESTIGATION. Massachusetts Department of Developmental Services 68 North Main Street Carver, Massachusetts
WATER DAMAGE/MOLD INVESTIGATION Massachusetts Department of Developmental Services 68 North Main Street Carver, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of Environmental
More informationBlock Lofts Condominiums
Block Lofts Condominiums Building Envelope Condition Assessment 747 Ralph McGill Boulevard Atlanta, Georgia Presented to: Block Lofts Condominium Home Owners Association C/o Heritage Property Management
More informationBUREAU OF ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program
BUREAU OF ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program Use of Moisture Measuring Devices in Evaluating Water Damage in Buildings July 2007 The evaluation of mold colonization of building
More informationCadmus Environmental. 713.252.8549 Wendy@CadmusEnvironmental.com. Mold Inspection Report. Mold Inspection Report Example Page 1 of 12
Cadmus Environmental 713.252.8549 Wendy@CadmusEnvironmental.com Mold Inspection Report Mold Inspection Report Example Page 1 of 12 Background Information A mold inspection and assessment was conducted
More informationPROPERTY INSPECTION OR ASSESSMENT OF DAMAGES
PROPERTY INSPECTION OR ASSESSMENT OF DAMAGES ADDRESS: 123 MAIN ST MIAMI, FL CLIENT: BUYER ID No: 2014193 DATE: 5/13/2014 INSPECTION OR ASSESSMENT BY: GAIA CONSTRUCTION INC. CGC 1516136 FLORIDA HI-2792
More informationHEDDERMAN ENGINEERING, INC. 3011 Carrie Cove Ct., Spring, TX 77386 281-355-9911, fax 281-355-9903 Tim@heddermanengineering.com
HEDDERMAN ENGINEERING, INC. 3011 Carrie Cove Ct., Spring, TX 77386 281-355-9911, fax 281-355-9903 Tim@heddermanengineering.com 2007 TO: Mr. REF: CONDITION OF PROPERTY SURVEY Dear Mr. : At your request,
More informationOctober 30, 2014. Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR. Report of Findings, Structural Investigation, Benton, Arkansas, Dear Mr.
117 S. Market St. Benton, AR 72015 * 501-315-2626 * Fax 501-315-0024 October 30, 2014 Mr. & Mrs. Daniel Vick 101 Southwind Cove Benton, AR Re: Report of Findings,, Benton, Arkansas, Dear Mr. Vick: This
More informationFinal agency action regarding decision below: ALJFIN ALJ Decision final by statute IN THE OFFICE OF ADMINISTRATIVE HEARINGS
Final agency action regarding decision below: ALJFIN ALJ Decision final by statute IN THE OFFICE OF ADMINISTRATIVE HEARINGS MARSHA FAGIN, No. 0F-H00-BFS vs. Petitioner, ADMINISTRATIVE LAW JUDGE DECISION
More informationInspection Report of 1895 Jamesport Circle PSL, Fl 33953 Prepared for Yen Ho
Inspection Report of 1895 Jamesport Circle PSL, Fl 33953 Prepared for Yen Ho The State of Florida requires the builder to build in compliance with the Florida Building Code. Florida State Statutes 455
More informationSupplemental Investigation Summary Report
130 Liberty Street New York, New York Supplemental Investigation Summary Report Visual Mold Inspection Summary Prepared for: Lower Manhattan Development Corporation One Liberty Plaza, 20 th Floor, New
More informationWOOD DESTROYING PESTS AND ORGANISMS INSPECTION REPORT
` WOOD DESTROYING PESTS AND ORGANISMS INSPECTION REPORT Building No. Street City Zip Date of Inspection Number of Pages 1728 AVENIDA ELISA SAN JOSE 95131 1/5/2012 5 125 SOUTH CAPITOL AVENUE SAN JOSE, CA
More informationActive and Passive Sash Replacement
for Andersen Gliding Windows Read all instructions carefully before attempting this procedure. If you have any questions about your ability to complete the procedure, call Andersen at 1-888-888-7020 for
More informationCase Studies of the Cause and Origin of Fungal Growth in Residential and Commercial Structures
Case Studies of the Cause and Origin of Fungal Growth in Residential and Commercial Structures Stewart M. Verhulst, M.S., P.E. 1 Erik L. Nelson, Ph.D., P.E., M.ASCE 2 Deepak Ahuja, M.S., P.E.,M.ASCE 3
More informationHow To Prevent Water Damage To A Home
Having inspected about 800 homes in the last four years, I have seen a lot of problems with many homes. Most of these problems are minor; however, there are some problems that are quite serious. One of
More informationSolving Persistent Moisture Problems and Moisture Damage
B etter buildings Solving Persistent Moisture Problems and Moisture Damage Summary This three-storey, 15-unit, 1,300 square metre (13,993 sq. ft) walk-up was built in 1958. In the 1980s, the building started
More informationBuilding Condition Assessment: 215-219 West Lexington Street Baltimore, Maryland
KPA The Joint Venture of EBA Engineering, Inc. and Kennedy Porter & Associates, Inc. 4813 Seton Drive, Baltimore, MD 21215 Phone: (410-358-7171) Fax: (410)358-7213 Building Condition Assessment: Baltimore,
More informationTHIRD LAGUNA HILLS MUTUAL
THIRD LAGUNA HILLS MUTUAL SECTION 34 WINDOWS & WINDOW ATTACHMENTS MAY 1996, RESOLUTION M3-96-28 SEPTEMBER 2002, RESOLUTION M3-02-47 NOVEMBER 2002, RESOLUTION M3-02-62 OCTOBER 2004, RESOLUTION 03-04-27
More informationSECTION 3 ONM & J STRUCTURAL ANALYSIS
Historic Boynton Beach High School Existing Building Assessment City of Boynton Beach February 10, 2011 SECTION 3 ONM & J STRUCTURAL ANALYSIS STRUCTURAL ENGINEERS SPECIAL INSPECTORS STRUCTURAL CONDITION
More informationReference: BRM-00220488-A0 July 18 th, 2014. Cursory Visual Review of Various Below Grade Spaces and Exposed Foundation Walls
Reference: BRM-00220488-A0 July 18 th, 2014 Toronto Catholic District School Board 80 Sheppard Avenue East Toronto, Ontario M2N 6E8 Re: 1.0 Introduction Exp Services Inc. (exp) was retained by the Toronto
More information510 Madera Ave San Jose, CA 95112 (408) 993-1900 Fax (408) 993-1944
HomeGuard 510 Madera Ave San Jose, CA 95112 (408) 993-1900 Fax (408) 993-1944 Dear HomeGuard customer, Thank you for selecting HomeGuard to perform the termite inspection on your home. It is very common
More informationMoisture Control. System Solutions to Prevent Mold
System Solutions to Prevent Mold How a systems approach to managing moisture is the most effective strategy for minimizing the growth of mold. Moisture Control Architects, designers, contractors and maintenance
More informationPrestige Home Inspection LLC
Cover Page Prestige Home Inspection LLC IAC2/ESA - Mold Assessment and Water Damage Report 555 W. Brook ave., Client's town MI, 48059 Inspection prepared for: Client's name Inspection Date: 10/15/2012
More informationPRESERVATION PLANNING ASSOCIATES 519 Fig Avenue, Santa Barbara, CA 93101 Telephone (805) 450-6658 Email: accole5@yahoo.com
PRESERVATION PLANNING ASSOCIATES 519 Fig Avenue, Santa Barbara, CA 93101 Telephone (805) 450-6658 Email: accole5@yahoo.com June 17, 2015 Ms. Kimberley Heaton McCarthy Supervising Planner Building and Safety
More information14 September 2015. Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102
Sarah Zorn Planning and Economic Development 25 West Fourth Street, Ste. 1100 St. Paul, MN 55102 Project No.: 15538.00 Re: Structural Condition Review of the building at 700 4 th St. E. Dear Sarah: We
More informationINSPECTION PROPERTY ADDRESS: Fort Bend County, Texas
5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net INSPECTION PROPERTY ADDRESS: INSPECTION PERFORMED FOR: XXXX Drive Fort Bend County, Texas Mr. and Mrs. New Construction
More informationWATER DAMAGE/MOLD INVESTIGATION. Massachusetts Department of Transitional Assistance 160 W. Rodney French Blvd New Bedford, Massachusetts
WATER DAMAGE/MOLD INVESTIGATION Massachusetts Department of Transitional Assistance 160 W. Rodney French Blvd New Bedford, Massachusetts Prepared by: Massachusetts Department of Public Health Bureau of
More informationMold Inspection Report (Initial Assessment)
Morlin Home Services, LLC 4435 Nanticoke Court Sw Lilburn, GA. 30047 Phone: (770) 564-1505 Fax: (770) 564-1575 Cell: (770) 344-7416 InspectorRick@Bellsouth.net www.morlinpropertyinspections.com Mold Inspection
More informationSeptember 3, 2009. Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901
September 3, 2009 Ric Boyd, Public Works Director Ketchikan Gateway Borough 344 Front St. Ketchikan, AK 99901 RE: Ketchikan Gateway Borough Gateway Recreation Center Roof Observations and Intrusive Inspections
More informationJagger Enterprises, Inc. dba Buckeye Home Inspections 17204 Dorchester Drive Cleveland OH 44119-1302 (216) 486-4663 Fax (216) 486-9922
Jagger Enterprises, Inc. dba Buckeye Home Inspections 17204 Dorchester Drive Cleveland OH 44119-1302 (216) 486-4663 Fax (216) 486-9922 November 09, 2002 Name deleted, Esq. address deleted Your client:
More informationPoints of Construction
Points of Construction BCB Homes builds the best homes in America. Period. The physics of building in the South Florida hot, humid climate are hard enough on their own, but BCB executes the details better
More informationEstimated Cost of Repair
1 Applicant: Property: Home: Business: Assessor: Applicant Number: Type of Loss: Hurricane Date Contacted: 1/18/2014 Date of Loss: 10/29/2012 Date Received: 1/14/2014 Date Inspected: 2/4/2014 Date Entered:
More informationPrelease Schedule of Condition and Want of Repairs at Milton Keynes for May
Prelease Schedule of Condition and Want of Repairs at Milton Keynes for May Instruction To carry out Inspection of the Industrial Unit, to identify areas of repair to the Unit at commencement of the Lease.
More informationQuality Assurance and Diagnostic Water Leakage Field Check of Installed Storefronts, Curtain Walls and Sloped Glazing Systems
Method of Test Committee Approval Product Group Approval Approved via 5/21/15 MOT CC Out for Ballot (#805-15) PUBLICATION NO. AAMA 501.2-XX DRAFT #2 DATED 5/21/15 Quality Assurance and Diagnostic Water
More informationSpecifications for Removal and Replacement of Water Damaged/Mold Impacted Materials
Specifications for Removal and Replacement of Water Damaged/Mold Impacted Materials Park Potomac Place 12500 Park Potomac Avenue Potomac, Maryland 20854 KEM Project # 21703 Prepared for: Park Potomac Place
More informationHistoric Preservation Certification Application Part 2 343-345 Main Street West South Haven, Vermont NPS Project No. 12345
Exterior Features 1 site and drainage 2 foundation 3 wood siding and trim 4 exterior doors 5 windows / storm windows 6 porches front and rear 7 chimneys 8 roofing Interior Features 9 frame 10 basement
More informationHome Inspection Report
4949 Brownsboro Rd Suite 293 Louisville, KY 40223 (502) 414-1440 tripleainspections@gmail.com Inspected By: William Carter, HI-1956 Home Inspection Report Prepared For: Edward Cullen Property Address:
More informationINSTRUCTION FOR ASSEMBLY. 150x180 v Traditional sauna cabin
INSTRUCTION FOR ASSEMBLY 150x180 v Traditional sauna cabin 1. SAUNA PLAN 1800 LIGHT UNDER THE BENCH VENTILATION OUTLET UPPER BENCH 600 1500 LOWER BENCH 400 700 1656 956 HEATER 366 381 690 815 Light switch
More informationWOOD DESTROYING PESTS AND ORGANISMS INSPECTION REPORT
` WOOD DESTROYING PESTS AND ORGANISMS INSPECTION REPORT Building No. Street City Zip Date of Inspection Number of Pages 1142 ARBOR VISTA WY. SAN JOSE 95126 10/28/2013 9 125 SOUTH CAPITOL AVENUE SAN JOSE,
More informationWET/DAMP BASEMENTS ANSWER: BASEMENT WALLS AND FLOORS CAN BECOME WET BY A LEAK, CAPILLARY SUCTION OR CONDENSATION.
WET/DAMP BASEMENTS PROBLEM. IS THIS BASEMENT LEAKING OR COULD WE HAVE ANOTHER PROBLEM? Water line arching up on wall in corners of basement. Water collecting on concrete floor starting in corners. ANSWER:
More informationSimpson Engineering A state licensed engineering firm F-1607
Simpson Engineering A state licensed engineering firm F-1607 4126 Allencrest 13901 Midway Lane, Dallas, Road, Texas Ste.102-136 75244 Telephone: 214-351-1637 Dallas, - Fax: TX 214-351-1639 75244-4388 Telephone:
More information701210-393. 28 August 2014. Toronto Catholic District School Board Catholic Education Centre 80 Sheppard Avenue East North York, Ontario M2N 6E8
Toronto Catholic District School Board Catholic Education Centre 80 Sheppard Avenue East North York, Ontario M2N 6E8 Attention: Re: Ms. Kathleen Wilson Safety Officer, Accident Prevention, Occupational
More informationInfrared Thermography and Water Damage Assessment
Infrared Thermography and Water Damage Assessment Noah Ceteras / Scott Wood Four Star Cleaning and Restoration / Building Science Institute ABSTRACT Thermal imaging devices have many uses across a wide
More information5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net LIMITATIONS AND DISCLAIMERS
5006 Cherry Ridge Road Richmond, Texas 77406 281-342-9944 harris31@sbcglobal.net INSPECTION PROPERTY ADDRESS: INSPECTION PERFORMED FOR: XXXX Court Richmond, Texas Mr. Foundation Concerns INSPECTION DATE:
More informationThank You for selecting HomeGuard Incorporated to perform the termite inspection on your home.
Dear HomeGuard customer, Thank You for selecting HomeGuard Incorporated to perform the termite inspection on your home. Enclosed you will find the inspection report that includes the findings, repair recommendations
More informationRoof Inspection. Summary Report
Phone: (561) 866 9956 www.real-estate-inspections.com Roof Inspection Summary Report Subject Property File Number: 05-15-RF-002 Inspector: Craig Milliken, PE CPM Real Estate Inspections, Inc. Date of Inspection:
More informationPANEL CONCEPTS LLLP.
The Small Cottage Company DO-IT-YOURSELF CABINS & COTTAGES PANEL CONCEPTS INC. PANEL CONCEPTS LLLP. 2826 Gold 331 Creek N. M-33, Road Mio, Gold Michigan Creek, Montana 4864759733 (989) 826-6511 (406) 288-8585
More informationPRE-PURCHASE INSPECTION REPORT
PRE-PURCHASE INSPECTION REPORT PREPARED FOR: PROPERTY ADDRESS: Waiheke Island DATE: 21 November 2012 Page 1 of 13 (a) This is a report of a visual only, non-invasive inspection of the areas of the building
More informationBUILDING ASSESSMENT QUESTIONNAIRE. B. TENANTS Is there more than one tenant in the building? YES
Department of Health and Human Services, Division of Public Health Occupational and Environmental Epidemiology Branch 1912 Mail Service Center, Raleigh, North Carolina 27699-1912 BUILDING ASSESSMENT QUESTIONNAIRE
More informationRODENT PROOFING CHECKLIST
RODENT PROOFING CHECKLIST The most important part of a rodent control job is a thorough inspection of the problem areas/building. Since we warranty the control of rodents with our standard pest control
More information(This report is endorsed) Industrivej 20, 9900 Frederikshavn, Danmark
Spectrum Laboratories Ltd is accredited by International Accreditation New Zealand (formerly Telarc). The tests reported herein have been performed in accordance with the terms of our accreditation. This
More informationEMR Shielding of single level home from 3G mobile phone tower
YSHIELD Shielding Paints EMR Shielding of single level home from 3G mobile phone tower Project carried out by YSHIELD Australia using HSF 54 shielding paint and Eco 30 shielding fabric. 1) Shielding paint
More informationCENTER FOR ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program
CENTER FOR ENVIRONMENTAL HEALTH Emergency Response/Indoor Air Quality Program Guidance Concerning Remediation and Prevention of Mold Growth and Water Damage in Public Schools/Buildings to Maintain Air
More informationFDIC ENVIRONMENTAL CHECKLIST OF. FDIC Asset Number 88310023. Multi-Family Residence 2120 South Fairfield Avenue Chicago, Illinois
FDIC ENVIRONMENTAL CHECKLIST OF FDIC Asset Number 88310023 Multi-Family Residence 2120 South Fairfield Avenue Chicago, Illinois ATC Project Number 301.75462.0102 September 29, 2012 Prepared by: Prepared
More informationLighthouse Engineering, L.L.C.
Monday, May 07, 2012 Lighthouse Engineering, L.L.C. Michael Gandy, P.E. Registered Professional Engineer (TX: 95672) Registered Engineering Firm (F: 9334) Phone: 214-577-1077 Fax: 214-224-0549 Website:
More informationHow To Repair A House
Assessing Structural Damages Please note-this presentation is only intended to be used as a basic educational tool and is by no means all encompassing. Each property should be treated on a case by case
More informationCONDENSATION IN REFRIDGERATED BUILDINGS
CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings
More informationAll CDBG-DR Program Subrecipients. Texas General Land Office. Date: August 20, 2014. Damage Assessment Guidelines
To: From: All CDBG-DR Program Subrecipients Texas General Land Office Date: August 20, 2014 RE: Damage Assessment Guidelines The Texas General Land Office (GLO) has revised the Damage Assessment requirements
More informationOrlando Home Inspection Services
PLEASE NOTE: Orlando Home Inspection Services Serving Central Florida since 1999 P O Box 915451, Longwood, Florida, 32791-5451 Phone: (321) 228-2493 Fax: (407) 374-8505 Web: http://www.orlando-home-inspections.com
More information