Why is my air conditioner dripping on my customers?
|
|
|
- Roland Anderson
- 10 years ago
- Views:
Transcription
1 De-Mystifying HVAC Why is my air conditioner dripping on my customers? By Ron Prager One of the most frequent emergency service requests is a call for an air conditioner leaking water into the store. These leaks (called condensate leaks,) damage merchandise, equipment, ceiling tiles and make it extremely difficult to do business. They can also create a hazard for customers and store staff. What is condensate? An air conditioner cools the air by passing it over a finned coil that is maintained at approximately 45º F. As the tempature of the air is lowered, it reaches a temperature known as the dew point. At this temperature, the air reaches its limit as to the amount of water vapor it can hold, and the excess water vapor condenses on the cold fins of the indoor coil. This condensed moisture is called condensate. The condensate runs down the fins of the coil and falls into a drain pan located under the bottom of the coil. As the pan fills, the condensate flows through an outlet in the pan into the condensate piping. The piping usually contains a device called a P trap that separates the air in the blower compartment from the outdoor air. The function is similar to that of a sink trap which separates the air in a building from the sewer gases in the drainage piping. In both cases, a column of water within the trap forms a barrier that separates the air on one side of the water column from the air on the other side of the water column. The condensate piping may drain into a building drainage system or it may drain directly onto the roof. If the unit is located indoors, the condensate may discharge into a receptacle or sump that contains a small pump. The condensate is then pumped to a building drainage system. Why does it leak? There are four basic causes of condensate leaks. These are: 1. Restricted or missing drainage components. 2. Incorrect pitch of equipment or piping.
2 3. Coil icing. 4. Carry-over of moisture. 1. Restricted drainage components: Restricted drainage components are by far the leading cause of condensate leaks. As air passes over the cooling coil, droplets of water condense on the coil. Although the air is filtered it still contains dust particles. These particles adhere to the wet coil surface and most are carried down into the drain pan under the coil with the condensate. Eventually, a thick gunk forms in the drain pan. During extended cooling periods (months) algae and mold can grow on the gunk. During intermittent cooling and heating periods, the gunk dries out and forms clumps of scale in the drain pan. As the gunk or scale is carried through the drainage piping it builds up in sufficient quantities to restrict the piping or the drain pan outlet. When the piping becomes restricted, the water level in the drain pan rises until the pan overflows into the base pan of the unit and eventually into the store. In most cases, it s the P trap or the pan outlet that becomes clogged. A technician responding to this type of situation will use pressurized nitrogen or carbon dioxide to blow through the drain line from the pan outlet, removing the clog. He should then clean the gunk out of the condensate pan and flush the piping and pan with water. In areas where algae or mold growth is a problem, he should place use an algaecide and detergent to clean the pan and place chemical tabs in the drain pan that prevent future growth. In some cases, the installing contractor neglects to install a P trap at the outlet of the pan. Sometimes, during the winter, water freezes in the trap and the trap breaks away from the pan outlet. With no trap in place, outdoor air is sucked into the pan outlet and this prevents the water from draining out. Once again, the unit drips into the store as the pan overflows. If one trap is required, two traps are a problem. We see more and more local codes requiring condensate to be piped from the unit to a drainage system. This is to prevent standing water ponding on the roof that can encourage the growth of Legionella (the cause of Legionaire s Disease,) as well as algae. All too often, the drainage piping consists of PVC pipe strapped to 4x4 sleepers laid on the roof. As the sun bakes the plastic piping it sags between the sleepers. When the sag becomes deep enough it forms a second trap albeit an un-vented trap. At best, the velocity of the water slows at this trap and restrictions develop over time. At worst, because the trap is not vented, it prevents water from flowing completely. The pan overflows and leaks into the store.
3 Proper drainage requires that the condensate piping have a minimum continuous pitch of ¼ per foot away from the unit. A vented P trap must be installed, and the drainage components must be kept clean 2. Incorrect Pitch All air conditioning units are designed to be installed dead level in both directions. Failure to level a unit can impede the flow of condensate. In extreme cases condensate can overflow the drain pan before it reaches the pan outlet that is now located at a higher point than the edge of the pan. The roofs on the buildings we occupy are pitched to a greater or lesser degree to provide drainage of rainwater. The curb a rooftop unit sits on is designed to sit on a level steel frame. If the steel frame is installed directly on the steel that supports the roof, or the curb sits directly on the corrugated steel decking which forms the roof, the unit will be pitched to the same degree the roof is pitched. Depending on the direction the unit is facing, the pitch of the roof, and the location of the drain pan outlet, this situation can lend to condensate leaks. A unit that is installed on a pitch, rather than being installed level, also exacerbate carry-over, which will be discussed later in the article. Condensate piping must be installed with a continuous pitch of ¼ per foot away from the unit. Keep in mind that many times the condensate piping is laying on sleepers on a pitched roof. If the piping runs opposite to the pitch of the roof, it must be inclined enough to make up for the roof pitch plus 1/4 per foot. When the piping is not pitched sufficiently, the velocity of the condensate slows, and dirt particles that were carried in the condensate collect forming a restriction. 3. Coil Icing: Air conditioning equipment that employs mechanical refrigeration (a compressor) for cooling contains an indoor coil that operates at a temperature of approximately 40ºF. The actual coil temperature is dependent on the refrigerant pressure within the cooling coil and the heat load being transferred to the coil. If the operating pressure within the coil drops too low or the heat load transferred by the coil drops too low, the coil temperature drops below 32ºF. When this occurs, the condensate that forms on the coil as water droplets turns into ice. Eventually this ice covers the entire face of the coil, which further decreases the amount of heat being transferred to the coil and causes the operating pressures to drop to the point where the unit shuts down on its low pressure safety control. When the unit shuts down, the block of ice covering the coil defrosts. The ice overhangs the drain pan and the water from the defrosting ice falls into the store.
4 The two causes of coil icing (low refrigerant pressure and low heat load,) can be further broken down into their component causes. Low refrigerant pressure with a normal heat load is caused by an insufficient refrigerant charge, a restriction in the refrigerant circuit, or by operating the unit at outdoor temperatures that are lower than the temperatures the unit was designed to operate at. Low ambient temperature operation lowers the pressure in the unit condenser which lowers the operating pressure in the units cooling coil. Air conditioning units can be modified to operate at low outdoor temperatures by installing low ambient controls that maintain normal pressures in the condenser at reduced outdoor temperatures. Reduced coil load can be caused by dirty air filters, a dirty indoor coil, restricted ductwork, a loose belt, or a faulty blower motor. In other words, anything that reduces the airflow quantity, causes the cooling coil to ice up. In addition, anything that causes the temperature of the air approaching the cooling coil to drop below 68 F can cause the unit to ice. If the unit is attempting to cool cold outdoor air, or if the return air from the store is too cold, the load is reduced and the coil ices. If a manager sets the thermostat in a store to 65 F and the temperature of the store actually gets down to 68 F, the load on the coil is reduced to the point where the unit can ice. When the coil is completely iced, the store gets hot, the unit shuts-down and the waterfall into the store begins. For this reason, the cooling setpoint on a thermostat should never be set below 70ºF. 4. Carry-Over As mentioned earlier, air passing over a cold cooling coil deposits droplets of water on the fins of the cooling coil. In a perfect world, the water droplets drop down the fins of the coil into the drain pan. Sometimes, the cooling coil is installed at an angle within the unit, but the water still drops down the fins into the pan due to an effect called surface tension. This works well as long as the velocity of the air moving through the coil does not exceed a particular threshold. (Usually
5 400 feet per minute). If we exceed the manufacturer s specified air flow quantity (volume) for the coil, we cause the velocity (speed) of the air moving through the coil to increase. Eventually, if the velocity is high enough the air passing through the coil carries the water droplets forming on the fins with it. Sometimes the high velocity air can even blow water out of the drain pan as it passes through the coil just above the surface of the water. The effect is similar to producing wind-driven rain inside your air conditioning unit. The result is a soggy ceiling. If the unit is not leveled properly, carry-over can occur at air velocities that are lower than the threshold set by the manufacturer. Units must operate below their maximum rated airflow and must be installed level in order to prevent carry-over. Indoor Units: Many retail locations are served by indoor HVAC units located above the ceilings of the stores. When you install a unit above a ceiling, you must assume that sometime during the units life, a condensate leak will occur and the unit will drip on whatever is located below it. Good practice dictates that all indoor units have a secondary drain pan installed below the unit. This is normally a galvanized steel pan that extends at least 2 beyond the perimeter of the unit. This pan is sometimes fitted with a water detector that shuts the unit down if water overflows into the secondary pan. An alternative method is to provide piping from the secondary pan to a safe location (sink) where people will notice the discharge of water and call a service technician. Roof Leaks: There are many situations where it is extremely difficult to distinguish between roof leaks and condensate leaks. To make matters more difficult, wind driven rain can find its way into a store through an air conditioning unit, and, condensate discharged onto a roof can find its way into the store through an opening in the roof membrane. Obviously, if the leak occurs during periods of rain, it s prudent to look for a roof leak. However, if there is no obvious area where water is getting through the membrane, there are several things that should be checked. Water can enter an air conditioning unit as wind driven rain or it can be sucked into the unit by the unit s blower. A technician should look for signs of wet insulation within the unit immediately after a rain to determine if rainwater is entering the store through the unit. Manufacturers provide electrical knockouts for power and control wiring in an area of the unit that should never be exposed to rain. Sometimes electricians find these knockouts to be in an inconvenient location, and they bring the electrical service to the unit by penetrating the base pan of the outdoor portion of the unit. Rainwater invariably finds its way into the store though the hole the electrician made, even if the penetration was caulked to prevent leakage. Another
6 thing to keep in mind is that periods of rain by definition mean periods of 100% outdoor humidity. The higher the outdoor humidity, the greater the amount of condensate that the unit will remove from the air, and the greater the condensate load on the unit. It is possible to have condensate leaks occur only during periods of extremely high humidity. The solution to unsolved ongoing leaks from above usually involves a meeting between your roofer and your air conditioning technician. They should be prepared to flood the roof around the unit and to spray all exposed surfaces of the air conditioner with a hose. This usually resolves the issue one way or the other. While you will never eliminate all condensate leaks, to summarize the preceding paragraphs, there are certain steps you can take to minimize the number of leaks you experience. 1. Replace filters regularly. 2. Replace drive belts annually. 3. Inspect units and clean drain pans at least twice annually. 4. Make certain indoor coils and blower wheels are kept clean. 5. Make certain drainage lines have continuous pitch. 6. Make certain, all units have P traps connected. 7. Have a certified test and balance contractor measure and set the air flow when the unit is installed. 8. Make certain all HVAC units are installed completely level. 9. Perform full operational checks on HVAC units at least twice annually. 10. Make certain all indoor units are installed with secondary drain pans. 11. Make certain thermostat cooling set points are never set below 70ºF. Or you can star selling umbrellas.
Chilled Water HVAC Systems
Chilled Water HVAC Systems By Ron Prager, Brinco Mechanical Services, Inc. Types of water based systems: There are three types of HVAC systems that utilize water as a heat transfer medium. The first system,
How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.
Demystifying HVAC Test Your HVAC Knowledge By Ron Prager How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. 1)
HVAC Checklist - Long Form
HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,
Air Conditioner Maintenance
Central air conditioning systems are wonderful features of many homes in the US. In hot and humid climates it s hard to imagine living without AC, although this convenience has been common in only the
THREE. Heating and Cooling
THREE Heating and Cooling 17 Condensation Drain Line The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. If your unit is located in the attic,
Water Management & Damage Prevention:
Water Management & Damage Prevention: A Guide for Homeowners This article provides homeowners with basic information to make these decisions and take the appropriate actions to keep their homes dry and
heating 3 & cooling heating and cooling 2010 PulteGroup, Inc. All Rights Reserved.
3 & cooling 17 heating 2010 PulteGroup, Inc. All Rights Reserved. condensation The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. Air conditioning
Controlling HVAC Costs By Ron Prager President, Brinco Mechanical Services, Inc.
Controlling HVAC Costs By Ron Prager President, Brinco Mechanical Services, Inc. Facilities managers for retail chains deal with a multitude of issues on a daily basis. Invariably, when asked, most facilities
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101
GLYCOL CHILLER SYSTEM TROUBLESHOOTING 101 By Jim VanderGiessen Jr, Pro Refrigeration Inc. There is a good chance your glycol chiller system is often completely forgotten about, until that dreaded day you
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER:
HEAT PUMP FREQUENTLY ASKED QUESTIONS HEAT PUMP OUTDOOR UNIT ICED-UP DURING COLD WEATHER: It is normal for a heat pump to have a build up of white frost on the outside coil during cold damp weather. The
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503. Re-Roofing: Asphalt Shingles
CITY OF WHITE BEAR LAKE BUILDING INSPECTION DEPARTMENT 4701 Highway 61 White Bear Lake, MN 55110 Fax: 651-429-8503 Re-Roofing: Asphalt Shingles This is a summary of the standard requirements based on the
Troubleshooting Your Refrigerator
Troubleshooting Your Refrigerator With conscientious care, a refrigerator will perform for years with little or no repairs. Refrigerators are categorized according to the way frost is removed from them.
Preventive Maintenance. State Energy Assessment Workshop By: DTE Energy Partnership & Services
Preventive Maintenance State Energy Assessment Workshop By: DTE Energy Partnership & Services Do you know? World wide research has shown that one of the reasons causing 80% of the accidents is deficient
Water Damage Prevention Risk Management Guidebook
Water Damage Prevention Risk Management Guidebook PIC Loss Control Services IMPORTANT NOTICE: The enclosed loss control information is for your consideration in your loss prevention efforts. They are not
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries
AIR CONDITIONING EFFICIENCY F8 Energy eco-efficiency opportunities in Queensland Foundries Hot tips and cool ideas to save energy and money! Air conditioning units or systems are often used by foundries
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)
Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety
Solving Persistent Moisture Problems and Moisture Damage
B etter buildings Solving Persistent Moisture Problems and Moisture Damage Summary This three-storey, 15-unit, 1,300 square metre (13,993 sq. ft) walk-up was built in 1958. In the 1980s, the building started
WINDOW ROOM AIR CONDITIONER
WINDOW ROOM AIR CONDITIONER Installation and Operation Manual Electromechanical Remote Control CAPACITIES 220V - 60 HZ. 12,000; 18,000; 24000 BTU/HR 220V-240V - 50 HZ. 12,000; 18,000; 24000 BTU/HR Please
Dehumidification Frequently Asked Questions
Dehumidification Basics Why do you want to keep indoor Rh between 30-60%? ASHRAE recommends keeping the relative humidity in a home between 30-60% to limit the effects of many unwanted conditions and harmful
Heat Pump USER S INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW RESIDENTIAL HEAT PUMP
Heat Pump USER S INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW RESIDENTIAL HEAT PUMP NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER. WELCOME TO EFFICIENT YEAR-ROUND
Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.
Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water
Home inspectors are not mold inspectors, however they do inspect for defects that
CONDENSATION IN THE WALLS Home inspectors are not mold inspectors, however they do inspect for defects that can result in mold. Mold grows in wet or damp environments. Defects that result in a wet or damp
Glossary of Heating, Ventilation and Air Conditioning Terms
Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment
Service Guide. Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines. ORDER No: UN-SVG001A-EN DATE: October 9, 2007
Service Guide Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines ORDER No: UN-SVG001A-EN DATE: October 9, 2007 Introduction This document defines American Standard and Trane s recommendations
Central Air Conditioner
Central Air Conditioner USER S INFORMATION MANUAL FOR THE OPERATION AND MAINTENANCE OF YOUR NEW RESIDENTIAL AIR CONDITIONER NOTE TO INSTALLER: THIS MANUAL MUST BE LEFT WITH THE EQUIPMENT USER. WELCOME
CONDENSATION IN REFRIDGERATED BUILDINGS
CONDENSATION IN REFRIDGERATED BUILDINGS By: Steve Salisbury Nov. 10, 2010 (revised Nov. 14, 2013) Introduction The following discussion reviews the basic causes of condensation in refrigerated buildings
WET/DAMP BASEMENTS ANSWER: BASEMENT WALLS AND FLOORS CAN BECOME WET BY A LEAK, CAPILLARY SUCTION OR CONDENSATION.
WET/DAMP BASEMENTS PROBLEM. IS THIS BASEMENT LEAKING OR COULD WE HAVE ANOTHER PROBLEM? Water line arching up on wall in corners of basement. Water collecting on concrete floor starting in corners. ANSWER:
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS
NRDCA 400 GUIDELINE FOR FIELD APPLICATION of LIGHTWEIGHT INSULATING CONCRETE REROOFING/RECOVER SYSTEMS The (NRDCA) has prepared this document to provide customers and installers information that the industry
Table Z. Troubleshooting Chart for Air Conditioners. Cause
Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause
Single Zone LCD Thermostat Operating Instructions
Fan Cool Furnace *Heat Pump or Heat Strip On/Off F Single Zone LCD Thermostat Operating Instructions MODEL 3313192.XXX Cool/Furnace 3313193.XXX Cool/Furnace/Heat Pump 3313194.XXX Cool/Furnace/Heat Strip
PTAC Preventive Maintenance Guide. Step-by-step instructions and information to keep your units operating in peak condition
PTAC Preventive Maintenance Guide Step-by-step instructions and information to keep your units operating in peak condition The Importance of Proper PTAC Maintenance Welcome to the PTAC Preventive Maintenance
A Guide to Trouble-Free Cooling Towers
A Guide to Trouble-Free Cooling Towers A basic understanding of cooling tower operation and maintenance will help keep a cooling water system running in top condition, year after year By David M. Suptic
HVAC Design Requirements
Maintenance of HVAC HVAC Design Requirements Air Flow Diagram แบบ Recirculation Air Flow Diagram แบบ Once Through Definition Of Conditions As built At rest In operation air air air Maintenance GMP Requirements
Commercial Roof Management
Disclaimer: This material is designed and intended for general informational purposes only, and is not intended, nor shall it be construed or relied upon, as specific legal advice. Roof damage is a leading
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM
QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,
Meaco 30L and Meaco 40L dehumidifier instruction manual
Meaco 30L and Meaco 40L dehumidifier instruction manual Please read this instruction manual before using the dehumidifier and keep safe for future reference SAFETY INSTRUCTIONS PLEASE READ ALL INSTRUCTIONS
Coil Cleaning Program
Coil Cleaning Program Procedures and Calculations that Affect your Bottom Line Fact: Did you know that annually cleaning HVAC coils reduces energy consumption in most cases enough to pay for the cleaning
Accurate Home Inspection of Illinois. Property Inspection Report For Steve & Jenny Hynek 210 W.Chicago Ave., Westmont, Illinois
Accurate Home Inspection of Illinois 815-260-1727 1213 Norley st. Joliet, illinois 60435 [email protected] We Inspect to Protect!!! Property Inspection Report For Steve & Jenny Hynek 210 W.Chicago Ave.,
Roof Inspection. Summary Report
www.real-estate-inspections.com Roof Inspection Summary Report Subject Property Prepared for: File Number: Client in Detroit 05-15-RF-004 Inspector: Craig Milliken, PE # 32779 CPM Real Estate Inspections,
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
How to Prevent Liquid Damage Property Losses
1. The leading cause of property losses is from liquid damage. A review of Zurich North America claims data highlights the problem. 2. Water damage originates from a number of sources: Domestic water lines
CLOSED CRAWLSPACES. Have you ever been in your crawlspace? If not, have you ever even
CLOSED CRAWLSPACES What s In the Crawlspace? Wet Sagging Fiberglass Improper Drainage Have you ever been in your crawlspace? If not, have you ever even opened the door to look inside and see what it looked
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877. Recommendations for installation of cooling systems
1932 Lexington Houston, Texas 77098-4220 (713) 524-4877 The purpose for this information is to provide a better understanding of the HVAC equipment, components, designs, and installations, of HVAC system
Energy Efficiency. Energy Efficient Home Cooling:
Energy Efficiency Energy Efficient Home Cooling: Choosing an air conditioning system is an important decision. A poor choice may be costly to purchase and operate and yet fail to provide the desired cooling
Installation Instructions
CNPVU CNRVU Uncased Coils Upflow - Downflow Heating - Cooling Installation Instructions NOTE: Read the entire instruction manual before starting the installation. TABLE OF CONTENTS PAGE SAFETY CONSIDERATIONS...
Home Maintenance Checklist
Regular maintenance keeps your home functioning efficiently and safely and helps protect its value. We're happy to offer this checklist of ongoing and seasonal maintenance steps to help you safeguard your
CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION
Technology Fact Sheet CENTRAL HEAT PUMP AND AIR CONDITIONER INSTALLATION Buildings for the 21st Century Buildings that are more energy-efficient, comfortable, and affordable that s the goal of DOE s Office
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS
SECTION 5 COMMERCIAL REFRIGERATION UNIT 22 CONDENSERS UNIT OBJECTIVES After studying this unit, the reader should be able to explain the purpose of the condenser in a refrigeration system. describe differences
Operating Instructions Split System Air Conditioner
Operating Instructions Split System Air Conditioner Model No. Indoor Unit Type Indoor Unit Type Nominal Capacity 26 36 F2 Low Silhouette Ducted S-26PF2U6 S-36PF2U6 Connectable outdoor unit lineup This
SWIMMING POOL HEAT PUMP
SWIMMING POOL HEAT PUMP Installation & User Manual Model HP40B HP50B HP65B Hayward Pool Products Canada, Inc. T: 1-888-238-7665 www.haywardpool.ca CONTENT I. Application 4 II. Features 4 III. Technical
Energy Efficiency in Industrial HVAC Systems
Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards
EFFECTIVE FEBRUARY 2014. note: drainage permit required to call for a dampproof inspection
EFFECTIVE FEBRUARY 2014 note: drainage permit required to call for a dampproof inspection 1. ROOF DRAINS/DECK DRAINS (INTERIOR ) All roof and deck drains within the perimeter of the building shall be APPROVED
Molds and mildew are fungi that grow
Appendix C: Moisture, Mold and Mildew Molds and mildew are fungi that grow on the surfaces of objects, within pores, and in deteriorated materials. They can cause discoloration and odor problems, deteriorate
How to Maintain an Air Conditioner
How to Maintain an Air Conditioner by Fix-It Club How to Troubleshoot a Central Air Conditioning System Publications International, Ltd. Central air conditioners are made up of two separate components:
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
Attachment J-C18.1. HVAC Work Instructions
. RFP: Attachment J-C18.1 HVAC Work Instructions NNC13ZFD017J SOW Item No. Title Page C18-02 Control Air Systems Annual PM 2 C18-03 Split System AC Indoor Section Annual PM 3 C18-04 Condensing Unit Semi-Annual
Attic condensation during winter can
Housing Fact Sheet Causes and Cures of Attic Condensation and Roof Ice Damming Problems Attic condensation during winter can decrease the effectiveness of insulation and over time can cause significant
Homeowners Air Conditioning Troubleshoot Checklist
Homeowners Air Conditioning Troubleshoot Checklist Before calling for repairs for your central air conditioner here are a few things you can check yourself (this check list could save the cost of an unnecessary
Facts About Home Cooling
Facts About Home Cooling Energy Savings When keeping cool means air conditioning, keeping comfortable can often be expensive. Especially since air conditioning can add up to over 11% of your bill. But
How To Understand Evaporator
SECTION 5 COMMERCIAL REFRIGERATION UNIT 21 EVAPORATORS AND THE REFRIGERATION SYSTEM UNIT OBJECTIVES After studying this unit, the reader should be able to Define high-, medium-, and low-temperature refrigeration.
LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air. Trevor Wende Vice President, Marketing Advantix Systems, Inc.
LIQUID DESICCANT AIR CONDITIONING Saves energy, Controls humidity, Cleans air Trevor Wende Vice President, Marketing Advantix Systems, Inc. 0 Humidity: The Hidden Cost Driver Conventional A/C process Start
DEFROSTING. Service Engineers Section Technical Bulletin No 3
Service Engineers Section Technical Bulletin No 3 DEFROSTING 1. INTRODUCTION This bulletin is presented to cover the methods used and problems experienced with defrosting of coils for chill and frozen
SUMP PUMP DISCHARGES INFORMATIONAL PACKET
DEPARTMENT OF PUBLIC WORKS ENGINEERING DIVISION SUMP PUMP DISCHARGES INFORMATIONAL PACKET Background Many homes have sump pumps located in crawl spaces and basement areas. If it weren t for sump pumps
Best Practices for Crawl Space Insulation
Best Practices for Crawl Space Insulation Copyright 2011 Basement Systems Inc. All Rights Reserved Table of Contents I - Introduction II - Step By Step Guide 1 - Providing Adequate Drainage 2 - Controling
Old Dominion University Mold Management Plan
OFFICE OF ENVIRONMENTAL HEALTH AND SAFETY 5255 Hampton Blvd. Spong Hall, suite 2501 Norfolk, Virginia 23529 Phone: (757) 683-4495 Fax: (757) 683-6025 Occupational Safety & Health Environmental Health Laboratory
HVAC Preventative Maintenance Basics. Presented by Mike Crawley
HVAC Preventative Maintenance Basics Presented by Mike Crawley Air Handlers/Package Units: Coils have to be clean! The main purpose of any coil is to absorb or reject heat If coils are dirty; air flow
air conditioners how to choose a cooling system
air conditioners how to choose a cooling system taking responsibility As an individual, your efficient use of energy brings benefits such as lower bills, improved comfort levels in your home and a reduced
NEOGARD. Preventive Maintenance Manual
NEOGARD Preventive Maintenance Manual Fluid-Applied Roof Coating Systems December 2014 Notes NEOGARD luid-applied roof coating systems are designed to be long lasting, monolithic membranes which provide
123 street Salt Lake City, Utah 84092
Salt Lake City, Utah 84092 Prepared for: Sample AC inspection Prepared by: Page 1 of 8 Table of Contents Definitions 2 General Information 2 Air Conditioning 3 Heating System 6 Summary 8 Page 2 of 8 Definitions
OPTIONAL SLENDER REMOTE CONTROL
DAIKIN ROOM AIR CONDITIONER Operation Manual OPTIONAL SLENDER REMOTE CONTROL BRC944A2B READ BEFORE OPERATION Safety Precautions...2 Names of Functions of Parts...4 Preparation before Operation...5 OPERATION
SECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
Air Conditioning System
Owner s Information Manual Air Conditioning ystem NOTE TO EQUIPMENT OWNER: For your convenience, please record the model and serial numbers of your new equipment in the space provided. This information,
Thermwire. Selection Guide. Freeze Protection Heating Cable. Thermwire -Wrap. Pre-Assembled. Thermwire-Comp. Thermwire-Melt.
Thermwire Freeze Protection Heating Cable Selection Guide Pipe Freeze Protection Heating Cable Pre-Assembled Pipe Freeze Protection Heating Cable with Attached Cord & Plug Thermwire-Comp Refrigeration
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
Failure code manual. content
Failure code manual content 一 wall split AC series 2 二 floor standing AC series. 4 三 portable AC series.. 5 四 dehumidifer 6 五 DC inverter single split series...7 六 DC inverter multi-split series 10 1 一
Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan
Please read this owner s Manual carefully before operating the unit. - Cooling - Heating - Dehumidifying - Fan TABLE OF CONTENTS INTRODUCTION 2 IMPORTANT SAFEGUARDS...2 PACKAGE CONTAINS..2 NAMES OF PARTS.3
Condensate Trapping: Don't Get Caught in a Trap of Your Own! - From the Trane Inc Website 1
Condensate Trapping: Don't Get Caught in a Trap of Your Own! - From the Trane Inc Website 1 Background: The past 10 years have seen a dramatic change in the design and function of air handlers, due in
Attachment #23 Health Safety Table. Client Education Inform issue and document. How to clean & maintain gutters. How to adjust sprinklers
Exterior Visual Health & Safety Issue Allowable Action Site Drainage Exterior grade does not slope 2% within the first 10' Site drainage causing bulk moisture in crawl space or basement Repairs to existing
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide
SELF-INSPECTION CHECKLIST Maintain Your Roof and Identify Potential Issues With Bloom s Comprehensive Self-Inspection Guide Inspection Questions? Call Bloom At 800-483-9932 www.bloomroofing.com DISCLAIMER
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities.
A discussion of condensate removal systems for clarifier and thickener drives for water and wastewater facilities. Richard L. Dornfeld, BSME, P.E. Staff Engineer September 25, 2014 Moisture can be a problem
First irst Co. Products
First irst Co. Products Recommended Maintenance Program PM1193 FIRST OPERATIONS,LP - P.O. Box 270969 - Dallas, Texas 75227 - www.firstco.com Table of Contents Introduction... 3 General Precautions... 3
Water Damage & Repair
Water Damage & Repair Chinatown Preservation Talks 2015 James Engler, P.A Glenn Mason, AIA Mason Architects Program Outline Terminology & Waterproofing Basics Discussion of why this is important Below
Preventing Ice Dams on Roofs
Preventing Ice Dams on Roofs Facility Manager November/December 2005 When a roof leaks, facility managers inevitably receive complaints from building occupants. If it is winter, ice dams are often the
Risk Bulletin. Mold Prevention and Control for Mechanical and HVAC Contractors. XL Group Insurance
XL Group Insurance Risk Bulletin Mold Prevention and Control for Mechanical and HVAC Contractors Mechanical contractors have an inherent risk of mold claims arising out of the heating, ventilation, and
Central Air Conditioning Plants
Central Air Conditioning Plants In our department, these plants (Air cooled or water cooled) are commonly available above 10 TR up to 100 TR. These types of plants are more suitable for large installations
How To Prevent And Manage A Flood And Mold
Flood Response and Mold Prevention Program Prepared by the Berea College Department of Environmental Health and Safety Revised May 2010 Contents I. Introduction II. III. IV. Flood and Mold Hazards Roles
Building and Grounds Maintenance Checklist
Building and Grounds Maintenance Checklist Name: School: Room or Area: Date Completed: Signature: Instructions 1. Read the IAQ Backgrounder and the Background Information for this checklist. 2. Keep the
CARING FOR YOUR WATER HEATER
http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected
KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS
KEY ELEMENTS IN PREVENTING AND MITIGATING MOLD CLAIMS By Jerome E. Spear, CSP, CIH Effective January 1, 2005, consultants who prepare mold management plans for buildings located in Texas must be licensed
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com
Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809
8 plumbing. plumbing. 2010 PulteGroup, Inc. All Rights Reserved.
8 90 2010 PulteGroup, Inc. All Rights Reserved. drains All the water you use leaves the home through a drain. Maintaining drains prevents clogging, overflows, water damage, and other problems. care and
This chapter is devided into two sections:
This chapter is devided into two sections: Page Installation requirements........................................................................ 127 The installation process..........................................................................
Split Air Conditioner
Split nditioner plit itsplit ir onditioner Split Split Split Split Split User s WNER'S 'S ER'S For s: AWI/AWO-21HPR1 Delta AWI/AWO-25HPR1 Delta AWI/AWO-32HPR1 Delta AWI/AWO-53HPR1 Delta AWI/AWO-65HPR1
Dehumidifier Users manual. For Models: DH45S DH65S
Dehumidifier Users manual For Models: DH45S DH65S 950-0062-revD Jan. 9 2007 FORWARD The appearance of the units that you purchase might be slightly different from the ones described in the Manual, but
SERVICE MANUAL. Room Air Conditioner Multi Split Wall-Mounted Type Indoor. FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2
SERVICE MANUAL Room Air Conditioner Multi Split Wall-Mounted Type Indoor FSAI-Pro-91AE2 FSAI-Pro-121AE2 FSAIF-Pro-181AE2 NOTE: Before servicing the unit, please read this at first. Always contact with
ROOF CONDENSATION: A COSTLY PROBLEM
ROOF CONDENSATION: A COSTLY PROBLEM CONTENTS 1. What is it? 2. How does it form? 3. What to look for 4. Repair options 5. Owner responsibilities and proactive measures 1. WHAT IS IT? Roof condensation