1 Green field data center design 11 Jan 2010 by Shlomo Novotny Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. explores water cooling for maximum efficiency - Part 1 Overview Data centers are an ever-growing part of our economy. The IT community is experiencing constantly increasing demands in areas such as Internet media and video, banking and finance, research, and government, just to name a few. Consequently, data centers continue to grow in both size and numbers. In addition, the performance of IT servers continues to follow Moore s law; this improves the performance per dollar spent on IT equipment, but also increases the heat density inside the data center equipment. Driven by these factors, the cost of running a data center continues to grow, even as the cost of the IT performance continues to decline. Historically, data center management has been focused on growth, performance, uptime, and reliability. IT organizations generally had responsibility for data center management. Facility organizations were responsible for much of the infrastructure surrounding the IT equipment. As a result of the significant growth and the lack of a holistic view of the economics of data centers, data center facilities today can be compared to factories of the 1970s and 1980s: ripe for significant cost, design, and process improvements. With attention from C-level executives today, data centers are driven to be lean, scalable, cost effective, and green. One of the most inefficient issues with many data centers today revolves around cooling. Typically, data center operators have managed heat density issues by spreading the load and under populating racks. This has come about because of the limitations of air cooling, which creates a very costly, complex, and inefficient infrastructure. Localized, passive, low-power dissipation liquid cooling devices at either rack level or rack proximity, when compared to traditional air-cooled methods, have the capability of reducing the power consumption of inroom cooling devices by as much as 90%. In addition, by allowing data centers to operate with higher-density racks, rack-level liquid cooling can reduce the data center IT footprint by as much as 80%. Liquid-cooling technology also permits a pay as you go cooling implementation, saving significant CAPEX when constructing a new data center. Present air-cooled data center construction requires an implementation from day 1 of all the cooling hardware for proper operation of the IT room. Localized liquid cooling would be implemented with IT expansion. Cooling hardware is modular and is purchased at the same rate as the IT hardware. This white paper addresses the emergence of localized liquid cooling, rack level or rack proximity, as the basis of data-center design, which will provide the most effective, efficient, and sustainable method to cool today s high-performance data centers.
2 Data Center Equipment Power Trends By the year 2000, the IT industry had accelerated its transition from CPU speed based performance to high-density system-level performance. The competitive focus moved to performance per cubic foot of packaging. Two popular server packaging form factors have evolved rapidly: the 1U and the blade. These two form factors populate rack structures in order to obtain maximum packaging density and maximum performance at lower cost per computer operation. Roger Schmidt, Christian Belady, and the author of this paper, Shlomo Novotny, identified the major challenges that the need to obtain maximum performance per volume packaging introduces to system cooling in data centers. Fully populated rack power dissipation had grown dramatically from an average of KW per rack to an average rack-level design from IT companies of 12 25KW per rack by 2000; however, these designs were not implementable because of the high power and cooling requirements. Typical data centers at that time, with a cooling capacity of 100 W/ft2, were limited to cooling 1 3 KW per rack without major investments. Many, if not most, data centers still operate in that range today. To create awareness of this challenge, an industry consortium initially led by Schmidt, Belady, and Novotny was created and developed the power dissipation charts that were then published by the Uptime Institute. To further bring this problem to the industry s attention and promote the introduction of new technologies that would mitigate this problem in data centers, the consortium s efforts were moved to a new group, TC 9.9 (Technical Committee), within ASHRAE. Because it represents a larger cross section of industries, including IT, construction, and HVAC, all of which relate to data centers, ASHRAE was the appropriate institution to carry the charter to create guidelines for data center designs. To date, ASHRAE has published multiple books dealing with the densification and energy savings in data centers, including liquid cooling and free cooling. In 2005, ASHRAE published Datacom Equipment Power Trends and Cooling Applications (Reference 2) with the power curves first published by the Uptime Institute and updates that included blade servers, which were not in the original plot. Figure 1 depicts the extent of the power density problem. It shows that from a maximum of approximately 5 KW/server-rack in the year 2000, the maximum power was projected to jump to KW/server-rack in Of course, the extreme high-performance computers (mainframes) are shown as dissipating even higher power levels.
3 Figure 1. Power Density Problem over Time For a bigger version of the image click here Part II: Key Drivers affecting energy consumption, the impact of power density on cooling. See our Thermal Management Knowledge bank for more cooling news, features and analysis About the author: Shlomo Novotny, is Vice President and Chief Technology Officer, Vette Corp. Keywords: Data centers, energy, consumption, EPA, US, liquid-cooling, power, Koomey, ASHRAE, Green field data center design water cooling for maximum efficiency - Part 2 14 Jan 2010 by Shlomo Novotny Key drivers for why water cooling shoudl be considered - Shlomo Novotny, Key Drivers J.G. Koomey in the United States Environmental Protection Agency s Report to Congress on Server and Data Center Efficiency, August 2007 (Reference 7) identified that data centers
4 consume 1% 2% of the total U.S. energy consumption. Energy consumption in data centers has been growing, according to the EPA, at 12% a year (Reference 7). Increasing heat density, which demands more cooling, and the cost of electricity are pushing data center operating costs to exceed the costs of the IT equipment itself. The energy cost per server operation is now larger than the server acquisition cost, as shown in Figure 2, generated by Christian Belady and included in the EPA s report to Congress (Reference 7). Figure 2. Server Energy Costs versus Acquisition Costs Looking at it another way, in a report published in September 2009 by Koomey et al. (Reference 3), as performance per dollar spent on IT hardware increases, the percentage of infrastructure and related costs increases relative to the cost of the infrastructure plus equipment. This trend is presented in Figure 3. Figure 3. Annual Infrastructure and Equipment Costs
5 In addition to the fact that infrastructure needs are increasing, one of the most significant costs, energy, will, by most predictions, continue to increase in price. Thus, the operational cost as related to energy consumption has become a major part of data center OPEX. Power infrastructure has been a major CAPEX in data center construction, according to the Uptime Institute. As a result, and in response to concerns regarding inefficient energy usage in the data center, the IT industry created and is heavily funding the Green Grid organization. This organization, jointly with ASHRAE, is promoting energy conservation and efficiency in IT equipment and in data centers. Data Center Cooling Today The traditional way to cool electronics in data centers has been with air, using computer room air conditioning (CRAC). A traditional data center has been designed to cool an average KW/ft2, which translates to 1 3 KW/rack. Newer, more expensive data centers are designed to cool an average 200KW/ft2, which still limits the power density per rack to 4 5 KW (recall that full rack capacity is 25 KW/rack). The traditional architecture employs CRAC units at the periphery of the data room, utilizing chilled water from an outdoor chiller as described below in Figure 4. Figure 4. CRAC Unit Deployment For a bigger version of the image click here The air is distributed through an air-pressurized raised floor plenum where the air arrives at the racks through perforated tiles in the floor in front of them. Most of the energy consumed inside the data center in this process is consumed by very powerful air blowers. The air itself is not an efficient heat carrier, and the airflow from the servers must be matched to the airflow coming from the perforated tiles in order to minimize air circulation and thus prevent overheating of the servers mounted on the upper part of the rack. Multiple papers have been written on these subjects, and the computational fluid dynamics companies modified their programs to enable efficient analyses of the airflow and optimization of server location and airflow distribution. As data centers install high-power-dissipation racks (up to 25 KW), air cooling is becoming challenging, if not impossible. The traditional way of cooling such high-power devices is through low-populated racks (low power per rack), rack spreading (getting more air from the floor), hot and cold aisle containment, and creation of small dedicated areas for high-power-density racks. The main problem with all the solutions optimizing and utilizing airflow and CRAC units is the thermal and energy inefficiency of heat transport by air, not to mention the overall complexity of the solutions. Thus, the solutions are typically costly from CAPEX and OPEX points of view and
6 do not minimize the thermal energy usage and cost. Furthermore, new data center construction requires that all cooling systems be purchased and installed prior to populating the room with IT equipment, thus requiring a large CAPEX expense prior to the actual cooling need. And in order for the cooling to operate properly and deliver the flow and pressure required by the racks at any location in the data center, all cooling equipment must be not just installed but fully operational from day 1, with resulting inefficient energy consumption until the data center is fully populated. Some hardware suppliers use water- or liquid-cooled cabinets or in-row units for cooling hot spots (localized high-power-density racks). Although more efficient than CRAC units, these liquid-cooling units still utilize very powerful air movers that dissipate a significant amount of power. Most present solutions are described in Datacom Equipment Power Trends and Cooling Applications, pages Water an Efficient Cooling Alternative The most energy-efficient and cost-effective way to remove the heat from the rack is by extracting the heat at the source (the rack), utilizing the airflow built in the rack through its servers and transporting the heat with liquid, which is significantly more efficient than air. Water is 3400 times more efficient than air in removing heat. This heat extraction at the rack level could be done by a passive rear door heat exchanger (RDHx) consisting of a liquid coil or by liquid-cooled cold plates mounted inside the servers for removal of heat from the powerdissipating components. Alternatively, a hybrid of passive rear doors and cold plates for highpower components inside the servers can be used. In any of these designs, one could eliminate or minimize the use of air cooling generated by the CRAC units. In addition, as much as 80% of the IT area could be reduced by densification utilizing liquid cooling. Furthermore, by fully populating the racks, one could obtain savings in CAPEX by eliminating excess racks and other ancillary equipment. Description of the Water Cooling System Figure 5 is an illustration of a rack-level water cooling system. Although the system is shown here with hoses running underneath the floor, a raised floor is not needed for its implementation, thus offering more installation flexibility and saving in CAPEX. In addition, this system could be used as a retrofit or as a basis for the design of new data centers. The chiller ( chilled water ) shown in the illustration could be eliminated or supplemented with a water-side economizer, thus obtaining free cooling.
7 Figure 5. Water-cooled Data Center Part III: Keywords: IT, Data Center, cooling, water cooling
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY. Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp.
GREEN FIELD DATA CENTER DESIGN WATER COOLING FOR MAXIMUM EFFICIENCY Shlomo Novotny, Vice President and Chief Technology Officer, Vette Corp. Overview Data centers are an ever growing part of our economy.
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling
Data Center Rack Level Cooling Utilizing Water-Cooled, Passive Rear Door Heat Exchangers (RDHx) as a Cost Effective Alternative to CRAH Air Cooling Joshua Grimshaw Director of Engineering, Nova Corporation
Managing Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
Enabling an agile Data Centre in a (Fr)agile market
Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without
Rittal Liquid Cooling Series
Rittal Liquid Cooling Series by Herb Villa White Paper 04 Copyright 2006 All rights reserved. Rittal GmbH & Co. KG Auf dem Stützelberg D-35745 Herborn Phone +49(0)2772 / 505-0 Fax +49(0)2772/505-2319 www.rittal.de
IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT
DATA CENTER RESOURCES WHITE PAPER IMPROVING DATA CENTER EFFICIENCY AND CAPACITY WITH AISLE CONTAINMENT BY: STEVE HAMBRUCH EXECUTIVE SUMMARY Data centers have experienced explosive growth in the last decade.
White Paper. Data Center Containment Cooling Strategies. Abstract WHITE PAPER EC9001. Geist Updated August 2010
White Paper Data Center Containment Cooling Strategies WHITE PAPER EC9001 Geist Updated August 2010 Abstract Deployment of high density IT equipment into data center infrastructure is now a common occurrence
High Density Data Centers Fraught with Peril. Richard A. Greco, Principal EYP Mission Critical Facilities, Inc.
High Density Data Centers Fraught with Peril Richard A. Greco, Principal EYP Mission Critical Facilities, Inc. Microprocessors Trends Reprinted with the permission of The Uptime Institute from a white
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre
Challenges In Intelligent Management Of Power And Cooling Towards Sustainable Data Centre S. Luong 1*, K. Liu 2, James Robey 3 1 Technologies for Sustainable Built Environments, University of Reading,
Data Center Environments
Data Center Environments ASHRAE s Evolving Thermal Guidelines By Robin A. Steinbrecher, Member ASHRAE; and Roger Schmidt, Ph.D., Member ASHRAE Over the last decade, data centers housing large numbers of
Elements of Energy Efficiency in Data Centre Cooling Architecture
Elements of Energy Efficiency in Data Centre Cooling Architecture Energy Efficient Data Center Cooling 1 STULZ Group of Companies Turnover 2006 Plastics Technology 400 Mio A/C Technology 200 Mio Total
Reducing Data Center Energy Consumption
Reducing Data Center Energy Consumption By John Judge, Member ASHRAE; Jack Pouchet, Anand Ekbote, and Sachin Dixit Rising data center energy consumption and increasing energy costs have combined to elevate
CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
Environmental Data Center Management and Monitoring
2013 Raritan Inc. Table of Contents Introduction Page 3 Sensor Design Considerations Page 3 Temperature and Humidity Sensors Page 4 Airflow Sensor Page 6 Differential Air Pressure Sensor Page 6 Water Sensor
How To Power And Cool A Data Center
Architecting the Green Data Center Viktor Hagen Field Business Development Data Center & High Performance Computing 1 Where we are Today Environmental sustainability is a major global trend for the 21st
APC APPLICATION NOTE #92
#92 Best Practices for Designing Data Centers with the InfraStruXure InRow RC By John Niemann Abstract The InfraStruXure InRow RC is designed to provide cooling at the row and rack level of a data center
Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources
Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources ALEXANDRU SERBAN, VICTOR CHIRIAC, FLOREA CHIRIAC, GABRIEL NASTASE Building Services
Dealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe [email protected] AGENDA Business Drivers Challenges
QUALITATIVE ANALYSIS OF COOLING ARCHITECTURES FOR DATA CENTERS
WHITE PAPER #30 QUALITATIVE ANALYSIS OF COOLING ARCHITECTURES FOR DATA CENTERS EDITOR: Bob Blough, Emerson Network Power CONTRIBUTORS: John Bean, APC by Schneider Electric Robb Jones, Chatsworth Products
The State of Data Center Cooling
White Paper Digital Enterprise Group The State of Data Center Cooling A review of current air and liquid cooling solutions. The challenges of increased data center density elevate the importance of the
Data Center Power Consumption
Data Center Power Consumption A new look at a growing problem Fact - Data center power density up 10x in the last 10 years 2.1 kw/rack (1992); 14 kw/rack (2007) Racks are not fully populated due to power/cooling
Green Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
Increasing Energ y Efficiency In Data Centers
The following article was published in ASHRAE Journal, December 2007. Copyright 2007 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes
Data center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential
TECHNICAL REPORT Sealing Gaps Under IT Racks: CFD Analysis Reveals Significant Savings Potential By Lars Strong, P.E., Upsite Technologies, Inc. Bruce Long, Upsite Technologies, Inc. +1.888.982.7800 upsite.com
Free Cooling in Data Centers. John Speck, RCDD, DCDC JFC Solutions
Free Cooling in Data Centers John Speck, RCDD, DCDC JFC Solutions Why this topic Many data center projects or retrofits do not have a comprehensive analyses of systems power consumption completed in the
BICSInews. plus. july/august 2012. + Industrial-grade Infrastructure. + I Say Bonding, You Say Grounding + Data Center Containment.
BICSInews m a g a z i n e july/august 2012 Volume 33, Number 4 plus + Industrial-grade Infrastructure and Equipment + I Say Bonding, You Say Grounding + Data Center Containment & design deployment The
W H I T E P A P E R. Computational Fluid Dynamics Modeling for Operational Data Centers
W H I T E P A P E R Computational Fluid Dynamics Modeling for Operational Data Centers 2 Executive Summary Improving Effectiveness of CFD Technology in Cooling of Data Centers IT managers continue to be
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER
DATA CENTER COOLING INNOVATIVE COOLING TECHNOLOGIES FOR YOUR DATA CENTER DATA CENTERS 2009 IT Emissions = Aviation Industry Emissions Nations Largest Commercial Consumers of Electric Power Greenpeace estimates
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably
Data Center 2020: Delivering high density in the Data Center; efficiently and reliably March 2011 Powered by Data Center 2020: Delivering high density in the Data Center; efficiently and reliably Review:
Green Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs
Green Data Centre: Is There Such A Thing? Dr. T. C. Tan Distinguished Member, CommScope Labs Topics The Why? The How? Conclusion The Why? Drivers for Green IT According to Forrester Research, IT accounts
The green data center.
Optimizing I T May 2007 The green data center. More than social responsibility: a foundation for growth, economic gain and operating stability Page 2 Contents 2 Introduction 4 Challenges facing CIOs 7
Airflow Simulation Solves Data Centre Cooling Problem
Airflow Simulation Solves Data Centre Cooling Problem The owner s initial design for a data centre in China utilized 40 equipment racks filled with blade servers spread out in three rows along the length
Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers. Sami Alkharabsheh, Bahgat Sammakia 10/28/2013
Modeling Rack and Server Heat Capacity in a Physics Based Dynamic CFD Model of Data Centers Sami Alkharabsheh, Bahgat Sammakia 1/28/213 2 ES2 Vision To create electronic systems that are self sensing and
Benefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
Unified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting
Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.
Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite
Alan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers
Information Technology and Data Centers HVAC Showcase November 26, 2013 Alan Matzka, P.E., Senior Mechanical Engineer Bradford Consulting Engineers Welcome. Today s webinar is being recorded and will be
FEAR Model - Review Cell Module Block
F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich
Data Center Technology: Physical Infrastructure
Data Center Technology: Physical Infrastructure IT Trends Affecting New Technologies and Energy Efficiency Imperatives in the Data Center Hisham Elzahhar Regional Enterprise & System Manager, Schneider
Design Best Practices for Data Centers
Tuesday, 22 September 2009 Design Best Practices for Data Centers Written by Mark Welte Tuesday, 22 September 2009 The data center industry is going through revolutionary changes, due to changing market
Specialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems. A White Paper from the Experts in Business-Critical Continuity
Blade Servers and Beyond: Adaptive Cooling for the Next Generation of IT Systems A White Paper from the Experts in Business-Critical Continuity Executive Summary In enterprise data centers, designers face
Steps to Achieve Green Data Center
Global Technology Services Oh Bee Joo IBM GTS/ITS - ASEAN-Site and Facilities Services Senior Project Manager, Subject Matter Expert Site and Facilities Services Where IT and the Building Meet Do you know
International Telecommunication Union SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES IN PUBLIC NETWORKS
International Telecommunication Union ITU-T TELECOMMUNICATION STANDARDIZATION SECTOR OF ITU Technical Paper (13 December 2013) SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF TELECOMMUNICATION CABLES
THE GREEN DATA CENTER
GREEN IT THE GREEN DATA CENTER WHERE ECOLOGY MEETS ECONOMY We truly live in an information age. Data Centers serve a very important purpose they provide the global community with nearly unlimited access
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
How To Improve Energy Efficiency Through Raising Inlet Temperatures
Data Center Operating Cost Savings Realized by Air Flow Management and Increased Rack Inlet Temperatures William Seeber Stephen Seeber Mid Atlantic Infrared Services, Inc. 5309 Mohican Road Bethesda, MD
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia
Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program
1. Data Centre Environment Why focus on Data Centres? Hitachi Eco-Friendly Data Centre Solutions
Hitachi Eco-Friendly Data Centre Solutions Why are efficient data centres a necessity and how can they be delivered 24 th September 2009 1 1. Data Centre Environment Why focus on Data Centres? Why are
Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant
RESEARCH UNDERWRITER WHITE PAPER LEAN, CLEAN & GREEN Wright Line Creating Data Center Efficiencies Using Closed-Loop Design Brent Goren, Data Center Consultant Currently 60 percent of the cool air that
How To Run A Data Center Efficiently
A White Paper from the Experts in Business-Critical Continuity TM Data Center Cooling Assessments What They Can Do for You Executive Summary Managing data centers and IT facilities is becoming increasingly
The New Data Center Cooling Paradigm The Tiered Approach
Product Footprint - Heat Density Trends The New Data Center Cooling Paradigm The Tiered Approach Lennart Ståhl Amdahl, Cisco, Compaq, Cray, Dell, EMC, HP, IBM, Intel, Lucent, Motorola, Nokia, Nortel, Sun,
DataCenter 2020: first results for energy-optimization at existing data centers
DataCenter : first results for energy-optimization at existing data centers July Powered by WHITE PAPER: DataCenter DataCenter : first results for energy-optimization at existing data centers Introduction
Energy Performance Optimization of Server Room HVAC System
International Journal of Thermal Technologies E-ISSN 2277 4114 2 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Manoj Jadhav * and Pramod Chaudhari Department
How to Meet 24 by Forever Cooling Demands of your Data Center
W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the
Impact of Virtualization on Data Center Physical Infrastructure White Paper #27. Tom Brey, IBM Operations Work Group
Impact of Virtualization on Data Center Physical Infrastructure White Paper #27 Tom Brey, IBM perations Work Group 1 Virtualization Two Steps WP #19 USING VIRTUALIZATIN T IMPRVE DATA CENTER EFFICIENCY
AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland
AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course
Choosing Close-Coupled IT Cooling Solutions
W H I T E P A P E R Choosing Close-Coupled IT Cooling Solutions Smart Strategies for Small to Mid-Size Data Centers Executive Summary As high-density IT equipment becomes the new normal, the amount of
Direct Contact Liquid Cooling (DCLC ) PRODUCT GUIDE. Industry leading data center solutions for HPC, Cloud and Enterprise markets.
Direct Contact Liquid Cooling (DCLC ) PRODUCT GUIDE Industry leading data center solutions for HPC, Cloud and Enterprise markets. Leadership, Collaboration & Expertise CooIIT Systems Innovates and Delivers
abstract about the GREEn GRiD
Guidelines for Energy-Efficient Datacenters february 16, 2007 white paper 1 Abstract In this paper, The Green Grid provides a framework for improving the energy efficiency of both new and existing datacenters.
Green Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
The Efficient Enterprise. Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric
Ee The Efficient Enterprise Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic! 30,000
Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. [email protected]
Minneapolis Symposium September 30 th, 2015 Fundamentals of CFD and Data Center Cooling Amir Radmehr, Ph.D. Innovative Research, Inc. [email protected] Learning Objectives 1. Gain familiarity with Computational
Driving Data Center Efficiency Through the Adoption of Best Practices
Data Center Solutions 2008 Driving Data Center Efficiency Through the Adoption of Best Practices Data Center Solutions Driving Data Center Efficiency Through the Adoption of Best Practices Executive Summary
Great Lakes Data Room Case Study
Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment
AisleLok Modular Containment vs. Legacy Containment: A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings
WH I TE PAPE R AisleLok Modular Containment vs. : A Comparative CFD Study of IT Inlet Temperatures and Fan Energy Savings By Bruce Long, Upsite Technologies, Inc. Lars Strong, P.E., Upsite Technologies,
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences
DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no significant differences November 2011 Powered by DataCenter 2020: hot aisle and cold aisle containment efficiencies reveal no
BRUNS-PAK Presents MARK S. EVANKO, Principal
BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS
IT White Paper MANAGING EXTREME HEAT: COOLING STRATEGIES FOR HIGH-DENSITY SYSTEMS SUMMARY As computer manufacturers pack more and more processing power into smaller packages, the challenge of data center
CIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How
CIBSE ASHRAE Group Data Centre Energy Efficiency: Who, What, Why, When, Where & How Presenters Don Beaty PE, FASHRAE Founder, President & Managing Director DLB Associates Consulting Engineers Paul Finch
Overview of Green Energy Strategies and Techniques for Modern Data Centers
Overview of Green Energy Strategies and Techniques for Modern Data Centers Introduction Data centers ensure the operation of critical business IT equipment including servers, networking and storage devices.
Data Centers That Deliver Better Results. Bring Your Building Together
Data Centers That Deliver Better Results Bring Your Building Together 1 Meeting the high demands of your data center Meeting the increasing heat loads associated with growing computational needs requires
Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings
WHITE PAPER Cooling Capacity Factor (CCF) Reveals Stranded Capacity and Data Center Cost Savings By Lars Strong, P.E., Upsite Technologies, Inc. Kenneth G. Brill, Upsite Technologies, Inc. 505.798.0200
Green Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
Data Center & IT Infrastructure Optimization. Trends & Best Practices. Mickey Iqbal - IBM Distinguished Engineer. IBM Global Technology Services
Data Center & IT Infrastructure Optimization Trends & Best Practices Mickey Iqbal - IBM Distinguished Engineer IBM Global Technology Services IT Organizations are Challenged by a Set of Operational Issues
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
In Row Cooling Options for High Density IT Applications
In Row Cooling Options for High Density IT Applications By Ramzi Y. Namek, PE, LEED AP, BD+C; Director of Engineering 1 Users wishing to deploy high density IT racks have several In Row Cooling solutions
11 Top Tips for Energy-Efficient Data Center Design and Operation
11 Top Tips for Energy-Efficient Data Center Design and Operation A High-Level How To Guide M e c h a n i c a l a n a l y s i s W h i t e P a p e r w w w. m e n t o r. c o m When is Data Center Thermal
Managing Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions
Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel
Re Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
Effect of Rack Server Population on Temperatures in Data Centers
Effect of Rack Server Population on Temperatures in Data Centers Rajat Ghosh, Vikneshan Sundaralingam, Yogendra Joshi G.W. Woodruff School of Mechanical Engineering Georgia Institute of Technology, Atlanta,
Data Center Efficiency in the Scalable Enterprise
FEATURE SECTION: POWERING AND COOLING THE DATA CENTER Data Center Efficiency in the Scalable Enterprise 8 DELL POWER SOLUTIONS Reprinted from Dell Power Solutions, February 2007. Copyright 2007 Dell Inc.
Energy Efficiency Best Practice Guide Data Centre and IT Facilities
2 Energy Efficiency Best Practice Guide Data Centre and IT Facilities Best Practice Guide Pumping Systems Contents Medium-sized data centres energy efficiency 3 1 Introduction 4 2 The business benefits
Data Center Cooling Critical Facility & Infrastructure Optimization. Presented by. Greg Stover SVP NER Data Corporation
Data Center Cooling Critical Facility & Infrastructure Optimization Presented by Greg Stover SVP NER Data Corporation About NER Data Corporation Data Center Infrastructure Optimization NER has been a leading
Data Center Design Guide featuring Water-Side Economizer Solutions. with Dynamic Economizer Cooling
Data Center Design Guide featuring Water-Side Economizer Solutions with Dynamic Economizer Cooling Presenter: Jason Koo, P.Eng Sr. Field Applications Engineer STULZ Air Technology Systems jkoo@stulz ats.com
Reducing the Annual Cost of a Telecommunications Data Center
Applied Math Modeling White Paper Reducing the Annual Cost of a Telecommunications Data Center By Paul Bemis and Liz Marshall, Applied Math Modeling Inc., Concord, NH March, 2011 Introduction The facilities
Cloud Computing Data Centers
Cloud Computing Data Centers Dr. Sanjay P. Ahuja, Ph.D. 2010-14 FIS Distinguished Professor of Computer Science School of Computing, UNF Warehouse-Scale Data Center (WSC) Design. Example: a data center
Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers
CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 [email protected] www.chatsworth.com All products
Scalable. Affordable. Flexible. Fast.
Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001
Verizon SMARTS Data Center Design Phase 1 Conceptual Study Report Ms. Leah Zabarenko Verizon Business 2606A Carsins Run Road Aberdeen, MD 21001 Presented by: Liberty Engineering, LLP 1609 Connecticut Avenue