Siemens AG Switching Devices. Configuration Manual 10/2010 SENTRON. Answers for infrastructure.
|
|
|
- Adela O’Brien’
- 9 years ago
- Views:
Transcription
1 Siemens AG 20 Switching Devices Configuration Manual 0/200 SETRO Answers for infrastructure.
2 Siemens AG 20
3 Siemens AG 20 Switching Devices 4 Introduction 7 Control switches, 5TE8 9 Pushbuttons, 5TE4 Light indicators, 5TE5 2 O/OFF switches, 5TE8 5 DC isolators, 5TE2 7 Busbar systems, 5TE9 8 Remote control switches, 5TT4 24 Switching relays, 5TT4 Insta contactors 26 Insta contactors, DC technology, 5TT5 3 Insta contactors, AC technology, 5TT5 35 Soft-starting devices, 5TT3 37 Controls Timers 38 Digital time switches, 7LF4 44 Mechanical time switches, 7LF5 48 Timers for buildings, 7LF6 53 Timers for industry, 5TT3 Siemens 200
4 Switching devices Siemens AG 20 Introduction Overview Devices Page Application Standards Used in Control switches, 5TE8 7 For the switching of lighting and other electrical devices up to 20 A. For use in control cabinets for the logical linking of functions. IEC/E , (VDE ); IEC/E , (VDE 0632-); GB CCC on-residential buildings Residential buildings Industry Pushbuttons, 5TE4 9 To be used as pushbuttons in control systems, e.g. to switch on seal-in circuits or as pushbuttons with maintainedcontact function for manual use, as control switches or for the switching of loads up to 20 A. IEC/E , (VDE ); IEC/E , (VDE 0632-); GB CCC -- Light indicators, 5TE5, 5TT2 Light indicators for signaling switching states or faults in systems. DI VDE O/OFF switches, 5TE8 2 For the switching of lighting, motors and 6 A A and other electrical devices from 20 to 25 A. 40 A A: IEC/E , (VDE ); IEC/E , (VDE 0632-) 32 A and 25 A: IEC/E , (VDE ); GB CCC DC isolators, 5TE2 5 The DC isolator is a specific switch disconnector for activating the solar modules in photovoltaic systems according to DI VDE IEC/E , IEC/E Busbar systems, 5TE9 7 For fast and safe connection IEC/E , (VDE ) -- 4 Siemens 200
5 Siemens AG 20 Switching devices Introduction Devices Page Application Standards Used in onresidential Residential buildings Industry Remote control switches, 5TT4 8 For the switching of lighting up to 6 A in rooms using several pushbuttons and central O/OFF switches. IEC IEC IEC E (VDE 0632) E and E /A Switching relays, 5TT4 24 For the switching of small loads up to 6 A or as coupling devices in control systems. E (VDE ) -- Insta contactors Insta contactors, DC technology, 5TT5 26 Insta contactors 24, 40 and 63 A for the switching of heating, lighting, such as fluorescent lamps, incandescent lamps, ohmic or inductive loads. IEC IEC IEC 6095 E E E 6095 VDE 0660 UL 508 Insta contactors, AC technology, 5TT5 3 Insta contactors 20, 25, 40 and 63 A for the switching of heating, lighting, such as fluorescent lamps, incandescent lamps, ohmic or inductive loads. IEC IEC , IEC 6095, E E E 6095 VDE 0660 F C (F E 6095) Soft-starting devices, 5TT3 35 Protection of machines with transmission, belt or chain drives, conveyor belts, fans, pumps, compressors, packing machines or door operating mechanisms E (VDE ) I/I duration I2_07254a Controls 37 For the O/OFF switching of loads, contact selection for lighting installations, OFF switching of direct currents and the switching of safety extra-low voltages. A wide range of options for practical use. Siemens 200 5
6 Switching devices Siemens AG 20 Introduction Devices Page Application Standards Used in Timers Digital time switches, 7LF4 38 Minute-precise switching of devices and system components in day, week and year programs. Unique due to the wide variety of functions offered by the Mini and Top versions; for PC programming Astro, Profi and Expert IEC and IEC E and E VDE 063 Part and Part 2-7 on-residential buildings Residential buildings Industry 7LF5 mechanical time switches 44 Accurate and 5-minute switching accuracy. With automatic time setting during commissioning and automatic switching to daylight savings. IEC and IEC E and E VDE 063 Part and Part 2-7 UL Timers for buildings, 7LF6 48 Lighting controls with stairwell lighting timers ensure the safe use of stairwells and save energy. Expanded applications for common rooms and garages, as well as the time switching of ventilators and fluorescent lamps. IEC E 60669, DI 805 Timers for industry, 5TT3 53 Multifunctional, delay, wiper, flashing and OFFdelay timers in control circuits expand the use of distribution boards in both small and large plants. IEC E Siemens 200
7 Siemens AG 20 Switching devices Control switches, 5TE8 Overview Two-way switches are used in control cabinets and distribution boards for switching small loads on/off or over. Group switches with center position permit the positions open/stop/closed, for example to control anti-clockwise rotation - Off - clockwise rotation. Control switches in a range of contact versions have an integral control lamp for the O setting. The auxiliary switch (AS) signals the contact position of the switch. It has the same design as the auxiliary switch used for the miniature circuit breakers (see Chapter "Miniature Circuit Breakers"). Technical specifications 5TE8 Standards IEC/E (VDE ); IEC/E (VDE 0632-) Approvals E Rated operational current I e Per conducting path A 20 Rated operational voltage U e -pole V AC 230 Multipole V AC 400 Rated power dissipation P v Contact per pole VA 0.7 Thermal rated current I the A 20 Rated breaking capacity At p.f. = 0.65 A 60 Rated making capacity At p.f. = 0.65 A 60 Short-circuit strength In conjunction with fuse of the same E gl/gg ka 0 rated operational current Rated impulse withstand voltage U imp kv > 5 Clearances Open contacts mm 2 > 2 Between the poles mm > 7 Creepage distances mm > 7 Mechanical service life Switching cycles Electrical service life Switching cycles 0000 Minimum contact load V; ma 0; 300 Rated short-time currents Per conducting path at p.f. = 0.7 Up to 0.2 s A 650 Up to 0.5 s A 400 (The respective rated surge current can Up to s A 2 be calculated by multiplying by a factor of.5). Up to 3 s A 70 Terminals ±screw (Pozidriv) Max. tightening torque m.2 Conductor cross-sections Rigid mm Flexible, with end sleeve mm Permissible ambient temperature C Resistance to climate At 95 % relative humidity Acc. to DI 5005 C Siemens 200 7
8 Switching devices Siemens AG 20 Control switches, 5TE8 Dimensional drawings Two-way switches, group switches with center position, 20 A 5TE8 control switches, 20 A, with lamp L L L I2_07888a I2_08008a 5TE8 5 5TE8 52 5TE8 4 5TE8 42 5TE8 53 5TE8 6 5TE8 62 5TE8 control switches, 20 A, with lamp and auxiliary switch 5TE8 0 5TE8 02 5TE8 03 5TE TE8 05 5ST3 auxiliary switches / / I2_583a I2_06335e TE8 08 5ST3 00 5ST3 0 5ST3 02 Schematics Diagrams Two-way switches, group switches with center position, 20 A 5TE8 control switches, 20 A, with lamp 5TE8 5 5TE8 52 5TE8 53 5TE8 0 5TE TE8 05 5TE8 02 5TE8 03 5TE8 control switches, 20 A, with lamp and auxiliary switch TE8 4 5TE8 6 5TE8 08 5ST3 auxiliary switches 5TE8 42 5TE8 62 5TE3 00 5ST3 0 5ST Siemens 200
9 Siemens AG 20 Switching devices Pushbuttons, 5TE4 Overview The pushbuttons are used in control systems, e.g. to switch on seal-in circuits or as pushbuttons with maintained-contact function for manual use, as control switches or for the switching of loads up to 20 A. Technical specifications 5TE4 8 Standards IEC/E (VDE ); IEC/E (VDE 0632-) Approvals E Rated operational current I e Per conducting path A 20 Rated operational voltage U e -pole V AC 230 Multipole V AC 400 Rated power dissipation P v Per pole VA 0.6 Thermal rated current I the A 20 Rated breaking capacity At p.f. = 0.65 A 60 Rated making capacity At p.f. = 0.65 A 60 Rated impulse withstand voltage U imp kv > 5 Clearances Open contacts mm 2 > 2 Between the poles mm > 7 Creepage distances mm > 7 Mechanical service life Switching cycles Minimum contact load V; ma 0; 300 Rated short-time currents Per conducting path at p.f. = 0.7 Up to 0.2 s A 650 Up to 0.5 s A 400 (The respective rated surge current can Up to s A 2 be calculated by multiplying by a factor of.5). Up to 3 s A 70 Terminals ±screw (Pozidriv) Max. tightening torque m.2 Conductor cross-sections Rigid mm Flexible, with end sleeve mm Permissible ambient temperature C Resistance to climate At 95 % relative humidity Acc. to DI 5005 C Power loss of 5TG8 05. lamps 5TG TG8 05 5TG TG TG TG8 055 Rated operational voltage U e V AC Rated power dissipation P v mw Rated operational voltage U e V DC Rated power dissipation P v mw Power loss of 5TG LEDs 5TG Rated power dissipation P v LED VA 0.4 Color coding according to IEC Color Safety of people or environment Process state System state Red Danger Emergency Faulty Yellow Warning/Caution Abnormal Green Safety ormal Blue Stipulation White Gray o special significance assigned Black Siemens 200 9
10 Switching devices Siemens AG 20 Pushbuttons, 5TE4 Dimensional drawings 5TE4 8 pushbuttons / X X / L L2 5TE TE4 82 5TE TE4 82 5TE4 83 5TE4 84 5TE TE TE TE TE TE TE TE4 80 5TE I2_07875b 5TE4 804 pushbuttons 5TE4 8 double pushbuttons with maintained-contact function X5 5 7 X X I2_984a 5TE TE TE4 83 5TE TE X I2_07870b Schematics Diagrams 3 X5 5TE TE TE TE TE X6 5TE TE4 80 5TE TE TE TE4 8 5TE4 82 5TE TE TE4 83 5TE4 84 5TE TE4 82 5TE TE Siemens 200
11 Siemens AG 20 Switching devices Light indicators, 5TE5 Overview Light indicators are used to signal switching states or faults in systems. They are available as single, double or triple light indicators. The triple light indicators are used as phase or signal indicators. Technical specifications 5TE5 8 Standards DI VDE 070- Rated operational voltage U e Max. V AC 230 (for different voltages see 5TG8 lamps) Rated power dissipation P v VA See 5TG8 lamps Clearances Between the terminals mm > 7 Terminals ±screw (Pozidriv) Max. tightening torque m.2 Conductor cross-sections Rigid mm Flexible, with end sleeve mm Permissible ambient temperature C Resistance to climate At 95 % relative humidity Acc. to DI 5005 C Rated power dissipation P v LED VA 0.4 Glow lamp VA 0.4 5TG8 05. Color coding according to IEC Color Meaning Safety of people and environment Process state System state Red Danger Emergency Faulty Yellow Warning/Caution Abnormal Green Safety ormal Blue Stipulation White o special significance assigned Dimensional drawings X2 X2 67 X X TE TE5 804 X X 5TE5 80 5TE TE I2_07895a Schematics Diagrams X X3 X 5TE TE5 80 5TE TE5 803 X3 X2 X X 5TE5 804 Siemens 200
12 Switching devices Siemens AG 20 O/OFF switches, 5TE8 Overview The devices are used for the switching of lighting, motors and other electrical devices. The rated currents of the range are 20 A to 25 A. There is a compact series of space-saving devices with up to 4 O contacts in a single MW available for rated currents 20 A and 32 A. The O/OFF switches in the rated currents 32 A to 25 A can be used as switch disconnectors according to IEC/E A special version of the O/OFF switch with rated current 63 A is available for use in meter cabinets. This version can be locked in the "OFF" position using a special key. The clamping screws are mechanically covered so that they are no longer accessible. Technical specifications Standards IEC/E , (VDE ); IEC/E Approvals E TE8 5TE8 2 Rated operational current I e Per conducting path A Rated operational voltage U e -pole V AC 230 Multipole V AC 400 Rated power dissipation P v Per pole, max. VA 0.7 Thermal rated current I th A Rated breaking capacity At p.f. = 0.65 A Rated making capacity At p.f. = 0.65 A Rated short-circuit making capacity I cm In conjunction with fuse of the same rated E gl/gg ka 0 operational current Rated impulse withstand voltage U imp kv > 5 Clearances Open contacts mm 2 > 2 Between the poles mm > 7 Creepage distances mm > 7 Mechanical service life Switching cycles Electrical service life Switching 0000 cycles Minimum contact load V; ma 0; 300 Rated short-time withstand current I cw Per conducting path at p.f. = 0.7 Up to 0.2 s A Up to 0.5 s A (The corresponding rated surge current can be Up to s A 2 0 established by multiplying by factor.5.) Up to 3 s A Terminals ±screw (Pozidriv) Max. tightening torque m.2 Conductor cross-sections Rigid mm Flexible, with end sleeve mm Permissible ambient temperature C Resistance to climate At 95 % relative humidity Acc. to DI 5005 C IEC/E , (VDE ) 2 Siemens 200
13 Siemens AG 20 Switching devices O/OFF switches, 5TE8 5TE8 3 5TE8 4 5TE8 5 5TE8 6 5TE8 7 5TE8 8 Standards IEC/E (VDE ) -- IEC/E (VDE 0632-) -- Approvals E Rated operational current I e Per conducting path A Rated operational voltage U e -pole V AC 230 Multipole V AC 400 Rated power dissipation P v Per pole, max. VA Thermal rated current I th A Rated breaking capacity At p.f. = 0.65 A Rated making capacity At p.f. = 0.65 A Rated short-circuit making capacity I cm In conjunction with fuse of the same E gl/gg ka 0 rated operational current Rated impulse withstand voltage U imp kv > 5 Clearances Open contacts mm > 7 Between the poles mm > 7 Creepage distances mm > 7 Mechanical service life Switching cycles Electrical service life Switching cycles Minimum contact load V; ma 24; 300 Rated power -pole kw Switching of resistive loads 2-pole kw including moderate overload AC-2 3-/4-pole kw Rated short-time withstand current I cw Per conducting path at p.f. = 0.7 Up to 0.2 s A Up to 0.5 s A (The corresponding rated surge current can be Up to s A established by multiplying by factor.5.) Up to 3 s A Terminals ±screw (Pozidriv) 2 Max. tightening torque m 3.5 Conductor cross-sections Rigid mm Flexible, with end sleeve mm Permissible ambient temperature C Resistance to climate At 95 % relative humidity Acc. to DI 5005 C Dimensional drawings 5TE8 O/OFF switches, 20 A and 32 A / / I2_08002a I2_67a 5TE8 5TE8 2 5TE8 3 5TE8 4 5TE8 2 5TE8 22 5TE8 23 5TE8 24 5TE8 8 5TE8 28 Siemens 200 3
14 Switching devices Siemens AG 20 O/OFF switches, 5TE8 5TE8 O/OFF switches, 32 A to 25 A / / I2_2563a TE8 3 5TE8 32 5TE8 33 5TE8 34 5TE8 35 5TE8 4 5TE8 42 5TE8 43 5TE8 44 5TE8 45 5TE8 5 5TE8 52 5TE8 53 5TE8 54 5TE8 55 5TE8 52 5TE TE TE TE TE8 6 5TE8 62 5TE8 63 5TE8 5TE8 65 5TE8 7 5TE8 72 5TE8 73 5TE8 74 5TE8 75 5TE8 72 5TE TE TE TE8 8 5TE8 82 5TE8 83 5TE8 84 5TE8 85 5ST3 auxiliary switches Phase connectors/-conductor connectors I2_06335e 2 I20_ ST3 00 5ST3 0 5ST3 02 5TE9 2 5TE9 3 Schematics Diagrams 5TE8 O/OFF switches! # % 5TE8 5TE8 2 5TE8 4 5TE8 24 5TE8 2 5TE TE8 8 5TE / /4 22 5TE8 3 5TE8 23 5TE8 34 5TE8 44 5TE8 54 5TE TE8 5TE8 74 5TE TE8 84 5ST3 auxiliary switches " 5TE8 35 5TE8 45 5TE8 55 5TE8 65 5TE8 75 5TE8 85 $ & 5TE8 3 5TE8 4 5TE8 5 5TE8 52 5TE8 6 5TE8 7 5TE8 72 5TE8 8 5TE8 32 5TE8 42 5TE8 52 5TE TE8 62 5TE8 72 5TE TE8 82 5TE8 33 5TE8 43 5TE8 53 5TE TE TE8 63 5TE8 73 5TE TE8 83 5ST3 00 5ST3 0 5ST Siemens 200
15 Siemens AG 20 Switching devices DC isolators, 5TE2 Overview DI VDE specifies the use of special switch disconnectors for isolating solar modules in photovoltaic systems. With a high rated voltage of 000 V DC, the 5TE2 55- switch disconnectors from Siemens go well above and beyond meeting these requirements. The optimally coordinated BETA Low-Voltage Circuit Protection product range which includes DC overvoltage protection and universal current-sensitive SIQUECE TYPE B RCCBs enables the quick and easy implementation of standard-conform protection for photovoltaic systems. Technical specifications 5TE2 55- Standards IEC/E , IEC/E Rated operational current I e A 63 Rated operational voltage U e For 4 poles in series V DC 000 Rated power dissipation P v Per pole, max. W 4.4 Rated short-circuit strength I cw 000 V DC, 4-pole A 760 Rated short-circuit making capacity I cm 000 V DC, 4-pole A 500 Rated impulse withstand voltage U imp kv > 5 Mechanical service life Switching 0000 cycles Electrical service life Switching 5000 cycles Utilization category DC-2B Minimum contact load V; ma 24; 300 Terminals ±screw (Pozidriv) PZ 2 Max. tightening torque m Conductor cross-sections Rigid mm Flexible, with end sleeve mm Permissible ambient temperature C Resistance to climate At 95 % relative humidity Acc. to DI 5005 C Siemens 200 5
16 Switching devices Siemens AG 20 DC isolators, 5TE2 Dimensional drawings 5TE2 DC isolator 5ST3 auxiliary switches I2_ TE2 55-5ST3 00 5ST3 0 5ST I2_06335e Schematics 5TE2 DC isolator TE2 55-5ST3 auxiliary switches 5ST3 00 5ST3 0 5ST3 02 Configuration For DC voltages up to 000 V, the four poles need to be connected in series. In contrast to normal flush-mounting switches, these devices are also fitted with arcing chambers and permanent solenoids to aid the positive quenching of the electric arc in direct currents. For this reason it is essential to comply with the polarity specifications of the switches when connecting the conductor. Suitable precautions should be taken during plant configuration to ensure there can be no polarity reversal in DC operation (e.g. photovoltaic plants) PV WR I2_4005 I2_4006 WR + - PV - + Legend: PV: Photovoltaic Inverter: Inverter 6 Siemens 200
17 Siemens AG 20 Switching devices Busbar systems, 5TE9 Overview Siemens has developed a rail-mounting concept which makes the linking of switching devices just as easy as that of miniature circuit breakers. The arrangement of the terminals on the devices is adapted to the bus mounting. With only two busbars, this saves considerable mounting time. Dimensional drawings 0, I2_3439a 4 3,5 220 I2_3440a 4 6,3 5TE9 00 5TE9 0 ote: Pin spacing in MW Dimensions of side views in mm (approx.) Siemens 200 7
18 Switching devices Siemens AG 20 Remote control switches, 5TT4 Overview Remote control switches are used in residential and nonresidential buildings, as well as the switchgear engineering sector. They trip in the event of current inrushes, i.e. pulses, and then electromechanically save the switching position (i.e. without auxiliary power), even in the event of a power failure. In residential and non-residential buildings, used in conjunction with pushbuttons, they facilitate installation of systems where, for example, a corridor light needs to be switched from more than one location. Because they save the switching position without standby losses, they enable the energy-efficient control of lighting. With special functions, such as central and group control, or series and shutter/blind control sequences, even high feature control tasks can be implemented easily and energy-efficiently. All the devices have the VDE mark and can also be equipped with an additional auxiliary switch. All devices have a switching position indicator and are operated manually. The switching noise is particularly quiet and meets the requirements of residential buildings. ote: Information about busbars to match the 5TT4 remote control switch can be found on page 7. Technical specifications Remote control switches 5TT4 0 5TT4 02 5TT4 05 5TT4 5 5TT4 03 5TT4 04 5TT4 2 5TT4 5 5TT4 3 5TT4 4 Auxiliary switches 5TT4 0 5TT4 Standards IEC , IEC , IEC , E (VDE 0632), E , E /A Approvals VDE 0632 Contact type O 3 O O Series CO CO 2 O 4 O 2 O Shutter/ blind O C 3 O O C Manual operation Yes -- Switching position indication Yes -- Rated control voltage U c V AC V DC Primary operating range U c Rated frequency f c (AC types) Hz Rated impulse withstand voltage U imp kv 4 Rated power dissipation P v Magnet coil, only pulse W/VA 4.5/7 9/3 4.5/7 -- Per contact at 6 A W.2 -- Minimum contact load V AC; ma 0; 00 0; 00 5 AC/DC; Rated operational current I e at p.f. ϕ = A Rated operational voltage U e O V AC AC/DC 2 O V AC O V AC O V AC O + C V AC Glow lamp load at 230 V ma 5 -- With 5TT4 920 compensator ma With 2x 5TT4 920 compensators ma -- Incandescent lamp load W Different phases between magnet coil/contact Permissible -- Contact gap mm >.2 <.2 Safe separation Creepage distances and clearances between magnet coil/contact mm > 6 Pushbutton malfunction Protected against continuous voltage, safe due to design Yes PTC Yes ) Yes -- Minimum pulse duration ms 50 Electrical service life In switching At I e /U e or specified lamp load cycles Terminals ±screw (Pozidriv) Conductor cross-sections Rigid mm Flexible, with end sleeve mm Resistance to climate At 95 % relative humidity Acc. to DI 5005 C 35 Permissible ambient temperature C Degree of protection Acc. to E IP20, with connected conductors Mounting position any ) For 2.5 MW 5TT devices with PTC. 8 Siemens 200
19 Siemens AG 20 Switching devices Remote control switches, 5TT4 Dimensional drawings 5TT4 remote control switches A A2 A A2 A A2 A A TT4 0 5TT4 02 5TT4 03 5TT4 04 5TT4 05 5TT4 5 5TT4 2 remote control switches with central O/OFF switching I2_ A 3 A 3 5 A 67 ZE 2 4 ZA 27 ZE 2 4 ZA ZE 5TT TT TT TT TT TT TT series remote control switches and 5TT4 42 shutter/blind remote control switches 6 ZA I20_285a Remote control switches with central and group O/OFF switching 23 A 3 A A A2 GA GE GA GE I2_ ZE ZE 2 ZA 2 4 ZA I2_ TT4 32 5TT4 42 5TT4 5 5TT4 52 Auxiliary switches Compensator " A A2 " # $ % ' 67 & " = ' % " " " $ " 8 I2_ TT4. 5TT4 920 Siemens 200 9
20 Switching devices Siemens AG 20 Remote control switches, 5TT4 Schematics Diagrams A A 3 A 3 5 A A 3 ZA ZE A ZA ZEA 3 A2 2 A2 2 4 A TT4 0 5TT4 02 5TT4 03 5TT4 04 5TT4 05 5TT4 5 ZAZE A 3 5 ZA ZE A 3 A 23 ZA ZE A ZA ZE A GAGE 2 GAGE 2 5TT TT TT4 32 5TT4 42 A A TT TT TT TT TT4 5 5TT4 52 5TT4. 5TT A A2 2 4 More information Mechanical storage Remote control switches are used to switch lighting by means of several pushbuttons. This makes complex cross/two-way switching unnecessary. With each pushbutton impulse, the remote control switch changes its contact position from "OFF" to "O", etc. In the event of a power failure, the last switching position is mechanically stored. Electromechanical remote control switches have no standby loss. Pushbutton malfunction Pushbuttons can jam, which may expose remote control switches to a continuous voltage. All remote control switches are protected against this type of malfunction through their design or through PTC. Central switching functions Versions with central O/OFF function allow the central switching of all connected remote control switches. This type of central switching can also be actuated using a time switch. All remote control switches can be switched to the O or OFF switching state, regardless of their current switching state. Contact sequences or means: 0: o contact closed : Only contact closed 2: Only contact 2 closed +2: Contact and Contact 2 are closed The contact positions are constantly changing with each pushbutton impulse. ote: Synchronous switching of the contacts cannot be guaranteed with parallel switching. Products with central/group switching must be used for the mutual control of several remote control switches. Busbar mounting All 5TT4 remote control switches can be bus-mounted with each other. This saves time and space. ote: Busbars to match the 5TT4 remote control switch can be found on page 7. Switching example: 5TT V AC L L2 A A2 2 Single-phase lighting circuit with 230 V AC actuation, e. g. in office buildings I20_375a 20 Siemens 200
21 Siemens AG 20 Switching devices Remote control switches, 5TT4 Switching example: 5TT with central O/OFF switching Switching example: 5TT4 0-4 L L2 L3 8 V AC 230 V AC L 3 x 230 V AC Central On/Off A A2 ZA ZE A 3 ZA ZE A I20_070d With the 2-pushbutton central "O" and "OFF" function, all remote control switches can be switched on or off from a central point, e.g. at the start and end of work. A time switch with a onesecond pulse (e.g. 7LF ) can also be used if desired. Once a central on/off switching operation has been executed, the remote control switches can also be switched on and off locally at any time. Remote control switches with central O/OFF switching can also be used to quickly and easily set up a panic circuit/panic lighting using conventional installation methods. The input terminals on the remote control switch need to be connected to the same phase (L, L2 or L3) and over the same residual current protective device. Otherwise residual current protective devices may be tripped unintentionally, or short circuits might occur. I2_280b Single-phase lighting circuit with safety extra-low voltage 8 V AC, illuminated pushbutton This circuit is also suitable for the control of circuits with a high number of illuminated pushbuttons. Switching example 5TT4 2-0 with central O/OFF switching and clock timer L 2 5TE V AC ZE ZA A 7LF TT4 2-0 I202_ TE6 800 Siemens 200 2
22 Switching devices Siemens AG 20 Remote control switches, 5TT4 Switching example: 5TT with central O/OFF switching and group O/OFF switching L L2 L3 3 x 230 V AC Central O/OFF Group O/OFF L 3 L 3 Group 2 O/OFF L 3 ZE ZA GEGA 2 4 ZE ZA GEGA 2 4 ZE ZA GEGA 2 4 I2_3695a With the 2-pushbutton central "O" and "OFF" function, all remote control switches can be switched on or off from a central point, e.g. at the start and end of work. With the 2-pushbutton group "O" and "OFF" function, all remote control switches assigned to a group can be switched on or off, e.g. corridor. A digital 7LF4 4 time switch with a switching command of s can also be used for the "Central" or "Group" function. Switching example: Glow lamp load and 5TT4 920 compensator ZA ZE A L L x 230 V AC ZA ZE A L3 Central On/Off Once a central on/off switching operation has been executed, the remote control switches can also be switched on and off locally at any time. The phase relations of ZA, ZE and GA, GE and L can be different. If contact /2 is used as check-back contact for the central "O" and "OFF" function, as shown above, terminal of all remote control switches must be in phase. The use of multiple illuminated pushbuttons, in particular 230 V AC glow lamps, could cause the remote control switch to trip accidentally, or no longer drop out, due to the current used by the lamps. This may also occur in the case of high line capacities. Switching a 5TT4 920 compensator parallel to the coil increases the glow lamp load of the remote control switch from 5 ma to 25 ma. The parallel switching of several compensators is also possible. The power consumption of 230 V 5TG7 3.. glow lamps for pushbuttons is: Low luminosity 0.8 ma medium 0.9 ma high.35 ma, the power consumption of LED 5SG7 35. lighting is approx..5 ma. To reduce capacitive coupling due to long cable lengths, we recommend using shielded cables. Particularly in systems with frequency converter controlled motors or with parallel cable routes (e.g. cable support systems), the induced current may impair the function of the devices. I2_280b 22 Siemens 200
23 Siemens AG 20 Switching devices Remote control switches, 5TT4 Switching of lamps Switching of transformers for halogen lamps Fluorescent and compact lamps in ballast operation Remote control switches 5TT4 0 5TT4 02 5TT4 05 5TT4 5 W 200 Uncorrected L8W Unit(s) L36W Unit(s) L58W Unit(s) Parallel-corrected L8W/4.5μF Unit(s) L36W/4.5μF Unit(s) L58W/7μF Unit(s) TT4 03 5TT4 04 DUO switching, 2-lamp L8W Unit(s) L36W Unit(s) L58W Unit(s) Fluorescent and compact lamps with electronic ballast (ECG) AC operation, -lamp L8W Unit(s) L36W Unit(s) L58W Unit(s) AC operation, 2-lamp L8W/4.5μF Unit(s) L36W/4.5μF Unit(s) L58W/7μF Unit(s) TT4 2 5TT4 5 5TT4 3 5TT4 4 The specified values are intended to serve as a guideline, the max. number of illuminants may vary, depending on the manufacturer. The values specified here refer to Osram illuminants and ballasts. Siemens
24 Switching devices Siemens AG 20 Switching relays, 5TT4 Overview Switching relays are used in residential, non-residential and industrial buildings for the purpose of contact multiplication. They can be used with safe isolation between coil voltage and contact. Switching relays for direct voltages in particular are seeing increasing use. With the 5TE9 00 and 5TE9 0 busbar, the switching relays can be mounted quickly and safely, e.g. by bus-mounting the conductor and/or infeed and this applies to the whole range of switching relays. ote: Busbars to match the 5TT4 2 switching relay can be found on page 7. Technical specifications 5TT TT TT TT TT TT TT Standards E , E Contact type O 2 O 4 O O + C CO 2 CO 2 CO Manual operation Yes Rated control voltage U c V AC V DC Primary operating range U c Rated frequency f c Hz 50 Rated impulse withstand voltage U imp kv 4 Rated power dissipation P v Magnet coil W/VA 2.4/ / / / / /3.0.7 Per contact at 6 A W.0 Minimum contact load V AC; ma 0; 00 Rated operational current I e At p.f.ϕ = A 6 Rated operational voltage U e Different phases Between magnet coil/contact Permissible Contact gap mm >.2 <.2 Safe separation Between creepage distances and clearances magnet coil/contact mm > 6 Electrical service life At I e /U e or specified lamp load Switching cycles Terminals ±screw (Pozidriv) Conductor cross-sections Rigid mm Flexible, with end sleeve mm Resistance to climate At 95 % relative humidity Acc. to DI 5005 C 35 Permissible ambient temperature C Degree of protection Acc. to E IP20, with connected conductors Mounting position Any 24 Siemens 200
25 Siemens AG 20 Switching devices Switching relays, 5TT4 Dimensional drawings 5TT4 2 switching relays!!!!!!! "!! ) ) ) ) ) ) ) ) ) ) ) ) " # $ % ' " & " " " " &! $! " " " 5TT4 20 5TT TT TT TT TT TT4 27 " & " & " " & &! = % " " " $ " % Schematics Diagrams A2 3 A A A2 3 2 A 4 A 4 24 A A TT4 20 5TT TT TT4 205 A2 A2 2 A 4 2 A TT TT TT4 27 More information 5TT Incandescent lamp load W 200 Switching of transformers for halogen lamps W 200 Fluorescent and compact lamps In ballast operation (KVG) Uncorrected L8W Unit(s) 27 L36W Unit(s) 24 L58W Unit(s) 5 Fluorescent and compact lamps With electronic primary switching device (ECG) AC operation, -lamp L8W Unit(s) 43 L36W Unit(s) 24 L58W Unit(s) 5 Metal-vapor and high-pressure mercury-vapor lamps Uncorrected 50 W Unit(s) 2 80 W Unit(s) 9 25 W Unit(s) W Unit(s) W Unit(s) W Unit(s) 000CO Unit(s) Halogen metal-vapor lamps Uncorrected 70 W Unit(s) 8 50 W Unit(s) W Unit(s) W Unit(s) High-pressure sodium-vapor lamps Uncorrected 50 W Unit(s) 0 70 W Unit(s) 8 0CO Unit(s) 6 50 W Unit(s) 4 250CO Unit(s) The specified values are intended to serve as a guideline, the max. number of illuminants may vary, depending on the manufacturer. The values specified here refer to Osram illuminants and ballasts. Busbar mounting All 5TT4 2 switching relays can be bus-mounted with each other. This saves time and space. ote: Busbars to match the 5TT4 2 switching relay can be found on page 7. Siemens
26 Switching devices Insta contactors Siemens AG 20 Insta contactors, DC technology, 5TT5 Overview Insta contactors are standard devices in installation technology and belong to the BETA switching device range. Insta contactors are particularly suitable for switching heating, lighting and motors. While Insta contactors have seen a considerable decline in use in the electrical heating sector in residential buildings, they have gained considerable significance for lighting circuits in buildings. Insta contactors are increasingly used in industry for motors where distribution technology plays a major role, e.g.in auxiliary installations for heat pumps and air conditioning technology. In addition to their basic function, they can also be used for the O/OFF switching of single-phase and three-phase electrical motors. The 5TT5 7 Insta contactors meet the requirements of E and are approved to UL Siemens 200
27 Siemens AG 20 Switching devices Insta contactors Insta contactors, DC technology, 5TT5 Technical specifications 5TT5 73 5TT5 74 5TT pole 4-pole 4-pole Standards E ; E ; E 6095; UL 508 Approvals UL 508; UL File o. E Rated frequency at AC f n Hz Rated control voltage U c V AC 24, 5, , 230 V DC 24, 0, , 220 Primary operating range U c Rated operational voltage U e V 440 Rated operational current I e at V AC Acc. to UL 480; acc. to IEC 440 AC-/AC-7a, O contacts A AC-/AC-7a, C contacts A AC-3/AC-7b, O contacts A AC-3/AC-7b, C contacts A Rated power dissipation P v Pick-up power VA/W 4/4 5/5 6.5/6.5 Holding power VA/W 4/4 5/5 4.2/4.2 Per contact AC-/AC-7a VA Switching times Closing (O contacts) ms 40 Opening (O contacts) ms 40 Rated impulse withstand voltage U imp kv 4 Contact gap (S contacts) min. mm Electrical service life At I e and load AC-/AC-7a For switching cycles AC-3/AC-7b For switching cycles Mechanical service life For switching million cycles Maximum switching frequency At load AC-/AC-7a Switching 300 cycles/h AC-3/AC-7b Switching 600 cycles/h Switching of resistive loads AC- V AC 230 for rated operational power P s (O contacts) Single-phase kw Three-phase kw Switching of three-phase asynchronous motors AC-3 V AC 400 for rated operational power P s (O contacts) Single-phase kw -- Three-phase kw 4 5 Minimum switching capacity V; ma 7; 200 Overload withstand capability Per conducting path (O contacts only) at 0 s A Short-circuit protection, according to coordination type Back-up fuse characteristic gl/gg A Terminals ±screw (Pozidriv) Coil connection Main connection 2 2 Tightening torques Coil connection m Main connection m Conductor cross-sections Coil connection -Solid mm Stranded, with end sleeve mm AWG cables AWG Tightening torques lb. in 8 Main connection -Solid mm Stranded, with end sleeve mm AWG cables AWG Tightening torques lb. in 9 20 Permissible ambient temperature For operation C For storage C Degree of protection Acc. to E IP20, with connected conductors According to UL 508 I n A UL 508 General Use 240 V/480 V FLA A UL 508 AC discharge lamps A UL 508 motor load 240 V Power hp UL 508 motor load 480 V Power hp UL 508 Short circuit at 480 V K5 fuses A ka 5 Siemens
28 Switching devices Insta contactors Siemens AG 20 Insta contactors, DC technology, 5TT5 Dimensional drawings 5TT5 7 Insta contactors 3A57 (3) 2 A A A 3 4 (4) 24A A A A I2_080a 7 43,5 ) ) Dimension without sealable terminal cover. 5TT TT5 73 5TT TT A 5 7 (3) 2 A A 33 4 (4) 2 4 A A A ) Dimension without sealable terminal cover. I2_592a 7 43,5 ) 5TT TT5 74 5TT TT TT5 75 5TT TT5 0 5TT5 Schematics Diagrams I2_593a ,5 ) ) Dimension without sealable terminal cover. A 3 5 7(3) A A (4) A TT TT TT5 750 A A A A TT5 73 5TT TT TT5 74 5TT5 75 A A A A TT TT TT5 0 5TT5 28 Siemens 200
29 Siemens AG 20 Switching devices Insta contactors Insta contactors, DC technology, 5TT5 More information Mounting position, Insta contactors, DC technology, 24 A, 40 A, 63 A There are no restrictions for normal mounting position (see figure, 0 to ). For mounting positions between 00 and 260, the level of control voltage must be at least 00 % of the rated value. 80 Heat dissipation If more than one Insta contactor with DC magnetic system is installed, a 5TG8 240 spacer must be installed after every second contactor. Spacers Spacers can be used as a compensating element and have a width of ½ MW. They come with an integrated wiring duct for the insertion of conductors. Two oppositely installed spacers thus offer space for large conductor cross-sections up to a 4 mm diameter I2_282b Switching of direct currents DC- and DC-3 Permissible DC switching currents for O contacts with resistive load 4 contacts in series are not recommended for 24 V due to unreliable contacts Switching of lamps Maximum number of lamps in units, per O contact at 230 V, 50 Hz. contact 2 contacts in series 3 contacts in series 4 contacts in series DC- DC-3 DC- DC-3 DC- DC-3 DC- DC-3 5TT5 73, 4-pole, 24 A I e at U e = 24 V DC A V DC A V DC A V DC A V DC A TT5 74, 4-pole, 40 A I e at U e = 24 V DC A V DC A V DC A V DC A V DC A TT5 75, 4-pole, 63 A I e at U e = 24 V DC A V DC A V DC A V DC A V DC A Incandescent lamp loads 5TT5 73, 4-pole, 24 A Per O contact W 500 5TT5 74, 4-pole, 40 A Per O contact W TT5 75, 4-pole, 63 A Per O contact W 5000 Siemens
30 Switching devices Insta contactors Siemens AG 20 Insta contactors, DC technology, 5TT5 Fluorescent and compact lamps in ballast operation (KVG) (permissible number of lamps in units per circuit at 230 V AC, 50 Hz) Uncorrected Parallel-corrected DUO circuit 2 lamps Lamp type W L8 L36 L58 L8 L36 L58 2 L8 2 L36 2 L58 Capacitor μf capacitance 5TT5 73, 4-pole 24 A Per O contact 5TT5 74, 4-pole 40 A Per O contact 5TT5 75, 4-pole 63 A Per O contact Fluorescent and compact lamps with electronic primary switching device (ECG) (permissible number of lamps in units per circuit at 230 V AC, 50 Hz) lamp 2 lamps Lamp type W L8 L36 L58 2 L8 2 L36 2 L58 5TT5 73, 4-pole 24 A Per O contact 5TT5 74, 4-pole 40 A Per O contact 5TT5 75, 4-pole 63 A Per O contact High-pressure mercury-vapor lamps (HQL) (permissible number of lamps in units per circuit at 230 V AC, 50 Hz) Uncorrected Parallel-corrected Lamp type W Capacitor μf capacitance 5TT5 73, 4-pole 24 A Per O contact 5TT5 74, 4-pole 40 A Per O contact 5TT5 75, 4-pole 63 A Per O contact Halogen metal-vapor lamps (HQI) (permissible number of lamps in units per circuit at 230 V AC, 50 Hz) Uncorrected Parallel-corrected Lamp type W Capacitor μf capacitance 5TT5 73, 4-pole 24 A Per O contact 5TT5 74, 4-pole 40 A Per O contact 5TT5 75, 4-pole 63 A Per O contact High-pressure sodium-vapor lamps (AV) (permissible number of lamps in units per circuit at 230 V AC, 50 Hz) Uncorrected Parallel-corrected Lamp type W Capacitor μf capacitance 5TT5 73, 4-pole 24 A Per O contact 5TT5 74, 4-pole 40 A Per O contact 5TT5 75, 4-pole 63 A Per O contact Siemens 200
31 Siemens AG 20 Switching devices Insta contactors Insta contactors, AC technology, 5TT5 Overview The 5TT5 8 Insta contactors are equipped with an AC magnetic system and are ideal for use under harsh conditions. The auxiliary switches can be mounted without tools. When equipped with terminal covers, the devices can also be sealed. Insta contactors without manual switch Insta contactors are playing an ever growing role in lighting circuits in buildings Insta contactors are increasingly used in industry for motors where distribution technology plays a major role, e.g. in installations for heat pumps and air conditioning technology. In addition to their basic function, they can also be used for the O/OFF switching of single-phase and three-phase electrical motors. Insta contactors with manual switch A key feature of Insta contactors with manual operation is the fact that users can switch consumers/loads on and off by hand. Siemens 200 3
32 Switching devices Insta contactors Siemens AG 20 Insta contactors, AC technology, 5TT5 Technical specifications ) For O contacts only. Insta contactors 5TT TT5 82., 5TT5 83. Auxiliary switches 5TT TT TT5 Standards IEC , IEC , IEC 6095; E , E , E 6095, VDE 0660 Approvals VDE 0637 umber of poles Rated frequency at AC Hz 50/60 Rated control voltage U c V AC 24, , 5, , , Primary operating range U c Rated operational voltage U e V AC /400 Rated operational current I e A /4 (230/400 V) Rated power dissipation P v Pick-up power (without manual switch VA/W 6/3.8 0/5 5.4/6 -- or manual switch in "I" position) Pick-up power (with manual switch in "AUTO" position) VA/W 2/0 33/25 62/50 -- Holding power VA/W 2.8/.2 5.5/.6 7.7/3 -- Per contact VA Switching times Closing (O contacts) ms Opening (O contacts) ms Closing (C contacts) ms Opening (C contacts) ms Rated impulse withstand voltage U imp kv 4 Rated insulation voltage U i V Contact gap, minimum mm Electrical service life At I e and load AC-/AC-7a For switching cycles AC-3/AC-7b Mechanical service life For switching cycles 3 million Maximum switching frequency At load In switching cycles/h Switching of resistive loads AC-/AC-7a For rated operational power P s Single-phase 230 V kw Three-phase 400 V kw Switching of three-phase asynchronous motors AC-3/AC-7b For rated operational power P s Single-phase 230 V kw.3 ) Three-phase 400 V kw Minimum switching capacity V; ma 7; 50 2; 5 Overload withstand capability Per conducting path (O contacts at 0 s only) A Short-circuit protection, according to coordination type Back-up fuse characteristic gl/gg A Terminals ±screw (Pozidriv) Coil connection.2 -- Main connection 3.5 Tightening torques Coil connection m Main connection m Conductor cross-sections Coil connection Rigid mm Flexible, mm with end sleeve Main connection Rigid mm Flexible, mm with end sleeve Permissible ambient temperature For operation C For storage C Degree of protection Acc. to E IP20, with connected conductors Siemens 200
33 Siemens AG 20 Switching devices Insta contactors Insta contactors, AC technology, 5TT5 Dimensional drawings Insta contactors, AC technology Without manual switch I2_2837 I2_2838 I2_ TT TT With manual switching 5TT TT TT TT TT TT TT I2_284 I2_2842 I2_ TT TT Auxiliary switches 5TT TT TT TT TT I2_ TT5-0 5TT5 - Schematics Diagrams A 3 A 2 A 2 A 3 5 7(3) A A2 2 4 A A TT TT5 80 5TT TT TT TT TT5 850 A (4) A TT5 83 5TT5 84 5TT5 85 A A TT TT TT5 852 A A TT TT TT TT5-0 5TT5 - Siemens
34 Switching devices Insta contactors Siemens AG 20 Insta contactors, AC technology, 5TT5 More information Mounting position, Insta contactors, AC technology The installation of the devices is permissible in the positions shown in the following diagram (0 to, 270 to 0 ). There are no restrictions when the devices are installed in these normal mounting positions. 80 Manual switching with O/I/Automatic function The 5TT and 5TT versions also offer a manual switch. The knob allows preselection of 3 positions: Knob in the "AUTO" position Automatic mode normal protective function Knob in the "I" position Continuous operation switched on manually (without control signal, when a control signal is applied, the manual switch on reset, i.e. the knob is automatically reset to the "AUTO" position) Knob in the "O" position Off switched off (coil circuit interrupted) I2_2836b Heat dissipation If several Insta contactors with AC magnetic system are mounted in series in a distribution board, there are no restrictions for the types 25 A, 40 A and 63 A within the permissible ambient temperature range up to 55 C. For 20 A types within the temperature range up to 40 C, a 5TG8 240 spacer must be installed after every third Insta contactor, and in the temperature range over 40 C to 55 C, after every second contactor. Plant test without applying a control voltage Insta contactors with O/I/Automatic function enable the testing of a plant by manual switch without the need to apply a control voltage. Automatic resetting through control signal When applying a control signal to the terminals A and A2, the Insta contactors can be reset from continuous operation mode ("I" position) to automatic mode ("AUTO" position). 34 Siemens 200
35 Siemens AG 20 Switching devices Soft-starting devices, 5TT3 Overview The soft-starting device is an electronic control for the soft startup of one-phase asynchronous machines. A phase control causes the current to rise steadily. This also increases the motor torque and the drive starts up smoothly. Because drive elements are handled more gently they can be designed more costeffectively. As well as a considerable reduction in startup noise, this also helps prevent the tipping or sliding of materials to be transported. The starting current is minimized. There is no speed adjustment. There is no marked soft start behavior without a mechanically connected load. If the power semiconductor is to be protected against short circuits or ground faults during startup, a super-quick fuse must be installed. Otherwise, the usual line and motor protective measures must be used. In the case of high switching frequencies, we recommend installing a thermistor motor protection for monitoring the permissible motor temperature. The soft-starting device must not be operated with capacitive load. In order to ensure the safety of persons and systems, only suitably qualified personnel should work on these devices. To prevent losses in the device, the power electronics are bridged with relay contacts after startup. Existing plants can also be retrofitted at any time. See Technical Specifications Technical specifications 5TT TT3 44 Standards E (VDE ) Supply/motor voltage V AC Primary operating range U c Rated power VA Rated frequency Hz 50/60 Rated power dissipation P v Coil/drive contact ) per pole Rated output of motor - Max. At 400 V VA Min. At 400 V VA Startup voltage % Starting ramp s Recovery time ms Switching frequency 3 I, T A = 0 s, ν u = 20 % Switching 36 (up to 3kW) 0 cycles/h 3 I, T A = 0 s, ν u = 20 % Switching 20 (from kw) 0 cycles/h Semiconductor fuse Super quick A Conductor cross-sections Rigid max. mm Flexible, with end sleeve min. mm Permissible ambient temperature C Resistance to climate Acc. to E /60/4 20/55/4 ) For rated operational current. Dimensional drawings 5TT3 44. soft-starting devices L L L2 L3 T T2 I2_ TT3 44 5TT3 440 T T2 T3 I2_594 Siemens
36 Switching devices Siemens AG 20 Soft-starting devices, 5TT3 Schematics Switching example: 5TT3 44 L AC 230 V I2_0753a L F S R Q t acc M st T T2 t acc : Acceleration time K S2 K M st : Starting torque L Q T T2 M ~ 5TT3 44 K I2_07602a Switching example: 5TT3 440 L L2 L3 PE 3 AC 230/400 V L3 L2 L I2_0754a Reversing switch K K2 L S 0 R t acc M st T3 t acc : Acceleration time M st : Starting torque T2 T K2 K L L2 L3 T T2 T3 5TT3 440 K K2 M PE 3 ~ I2_0728b 36 Siemens 200
37 Siemens AG 20 Switching devices Controls Overview Connecting loads The increased starting currents of different loads and thus the risk of contacts welding is often underestimated. Resistive load: The resistive load, e.g. electrical heating, does not increase the starting current. Incandescent lamps: The cold coiled filament in incandescent lamps or halogen lamps causes a 6 to 0-fold starting current for approx. 0 ms. Uncorrected fluorescent lamps: When switched on over several periods, the heating current of the coiled filament and the operational current produce a 2 to 2.5-fold inductive current. I/I duration I2_07254a I/I I2_07255a Parallel corrected fluorescent lamps: When switched on, the capacitor causes an extreme, up to 3- fold, current for approx. 0 ms. I/I duration duration ,5 t t approx.3 I2_07256a I2_07258a L L V D V D L St L St Selecting contacts for lighting installations A wide range of different contacts are used for modular installation devices: Contacts with > 3 mm contact gap, as for Insta contactors, AC technology Switching relay contacts with m contacts (contact gap >.2 mm but < 3 mm) Manually operated contacts with > 3 mm contact gap, as for 5TE8 switches Relay contacts with μ contacts (contact gap >0.5 mm), like those used on the printed boards of electronic devices. The selection tables in the technical specifications help you to find the correct switching device for the different lighting installations. Disconnecting loads If a contact with current flowing through it opens, this always ignites an electric arc above 24 to 30 V. This electric arc depends on the voltage, the length of the isolating distance, contact speed, actuating angle and current intensity. The principle of the so-called zero cutoff is that after no more than ½ half-waves, the electric arc is quenched in the current zero. There are no further quenching aids or current limiters, as is the case with the miniature circuit breakers. Disconnecting direct currents When switching direct voltages, there is no zero-crossing of the current to quench the electric arc. In order to still be able to switch appreciable currents, contacts are connected in series to increase the isolating distance. Some switching devices are provided with planning data for switching direct currents. Compliance with these planning data is essential. If the data values are exceeded the electric arc is not reliably quenched and there is a risk of fire. t I2_07257a Safe separation Fluorescent lamps in Duo circuit: The series capacitor effects a correction. In spite of this, an increased starting current is produced over several periods, just as for uncorrected fluorescent lamps. I/I I2_07255a duration ,5 t V D L V D K When operating 230 V and safety extra-low voltage SELV voltage of bell transformers or transformers for permanent load on a device, it is essential to ensure "safe separation". This requires at least 8 mm creepage distances and clearances and a voltage endurance greater than 4 kv. If these conditions 8 mm or 4 kv are not fulfilled, the term "electrical separation" as "not SELV" is used instead of the term "safe separation". L St L St I2_07259a Siemens
38 Switching devices Timers Siemens AG 20 Digital time switches, 7LF4 Overview These days, time switching is taken for granted. In fact, it is now hard to imagine many process sequences and energy saving processes without time switching. It could also be argued that time switching satisfies a basic need in the electrical installation sector. The new generation of digital time switches have a much more diverse range of functions than earlier devices and, thanks to better solutions, are simpler to operate. They can be used for switching systems or system components, or for functions, such as: irrigation systems, greenhouses, public gardens, swimming pools, filtering installations, canopy controls, school bells, church bells, shop window lighting, advertising lighting, gym lighting, traffic signal controls, street lighting, illuminated signs, office lighting, lighting of stairwells and entrances, object illumination, preheating of industrial furnaces, spraying machines, ovens, heating systems, airconditioning systems, fans and ventilation systems, heating and circulation pumps and sauna systems. All devices have the VDE mark and are UL approved (not 7LF4 444). 38 Siemens 200
39 Siemens AG 20 Switching devices Timers Digital time switches, 7LF4 Technical specifications Mini Top Profi Astro Expert 7LF LF4 4 7LF4 42 7LF4 43 7LF LF4 42 7LF LF4 432 Standards E , -2-7; VDE 063-, -2-7; UL E , -2-7; VDE 063-, -2-7 Approvals VDE, UL ,-2-7/UL 97 CSA C22.2 o. 4 and 77 VDE Supply Rated control supply voltage U c V AC , , /230 V AC/DC Primary operating range U c ) V ) - Frequency ranges Hz ) ) Rated power dissipation P v VA /4 3) Channels/contacts Switching channels or Rated operational voltage U e V AC Rated operational current I e At p.f. = A 6 At p.f. = 0.6 A 0 Contacts CO or 2 CO 4 CO - Mechanical switching cycles (in millions) > Electrical switching cycles At p.f. = 6000 (20 A) Minimum contact load V; ma 2; 00 - Incandescent lamp load A Fluorescent lamp load At 7 μf VA Uncorrected VA Energy-saving lamp load W 00 Safety Different phases permissible between actuator/contact Yes Rated impulse withstand voltage U imp kv 4 - EMC: burst Acc. to IEC kv > EMC: surge Acc. to IEC kv > Electrostatic discharge Acc. to IEC kv > 8.0 Power reserve storage Mains/battery a 6/ Battery type Li primary cell Program memory Captive -- Yes Overvoltage category Acc. to E 600- III Function Minimum switching sequences min s Make and break cycles min s Clock errors per day Typical s/day +0.3 ± 4) ± 0.86 ± 0.2 Control input Terminal S -- Yes Memory spaces -Programs 5) (2 28) 28 (2 4) Pulse (alternatively) Pulse cycle -- s... < 60 min -- Connections Terminals ±screw (Pozidriv) PZ Conductor cross-sections of main current paths - Rigid, max. mm Rigid, min. mm Flexible with end sleeve Max. mm Environmental conditions Permissible ambient temperature C Storage temperature C Resistance to climate Acc. to E /055/2 20/055/2 Degree of protection Acc. to E IP20, with connected conductors Safety class Acc. to E II ) For 24 V devices (7LF4 42-2, 7LF and 7LF ): Tolerance -0/+0 %; operating range U c. 2) For 24 V devices (7LF4 42-2, 7LF and 7LF ): Frequency range Hz. 3) For 24 V device (7LF ): P v = 4 VA. 4) At 25 C a clock error of +0.3s is assumed. Accuracy may deviate by a further ±s around this value. 5) A program consists of an O time, an OFF time and assigned O and OFF days or day blocks. Siemens
40 Switching devices Timers Siemens AG 20 Digital time switches, 7LF4 Dimensional drawings I2_3954 I2_ LF LF4 4. 7LF LF I2_2835 7LF I2_ I2_ ,3 9,4 4,5 I2_2752 9, 7LF USB adapter Plug-in card for data key 7LF4 940-, 7LF Schematics Diagrams 5 3 L 4 2 L L I2_2409b I2_242b 2 I2_243b I2_2753b 7LF LF4 4 7LF4 42 7LF4 43 7LF4 42 7LF LF LF Siemens 200
41 Siemens AG 20 Switching devices Timers Digital time switches, 7LF4 More information Mini digital time switches The Mini digital time switch with a width of only MW and its hourly, daily and weekly program is ideal for replacement and use in distribution boards with limited space. The Mini digital time switch can be used flexibly as it can also be operated in battery mode with all its functionalities. Furthermore, the actuator of the clock can be removed from its enclosure for easy programming over the 5-way joystick prior to mounting. Top, Profi, Astro and Expert digital time switches Whether you are programming locally using the text-assisted programming, or sitting comfortably in front of your PC, the task is quicker and easier with the Top, Profi, Astro and Expert digital time switches. Simple operation: Four programming pushbuttons offer user-friendly assistance with a text menu. Easy-to-read display: And if you need to change the settings of the digital time switch at the back of a dark control cabinet, the integral background lighting of the display and the lighting of the control elements offer a clear overview. Easy commissioning: You can get started with the programming straight away. Profi, Astro and Expert are supplied with the time, date and automatic daylight savings for Central Europe already set. Clear contrast: In order to maintain an overview even in bad light conditions and extreme temperatures, the contrast of the display can be adjusted - practical down to the very last detail. Convenient programming: It has never been so easy and uncomplicated to operate and program a digital time switch. -channel time switches allow input of up to 56 switching programs, 2-channel time switches allow up to 28 programs per channel and 4-channel time switches up to 84 programs per channel. This means that the Profi, Astro and Expert time switches are ideally equipped for even the most complex of tasks. Each entry required is clearly indicated so no prolonged studying of the operating instructions. And, particularly practical: you don't even need a power supply to program the digital time switches. The Profi, Astro and Expert digital time switches offer more than reliable switching. umerous integrated convenience functions make them versatile and simple problem solvers. A data key enables easy programming of the Profi, Astro and Expert digital time switches at a PC, simplifies the setting of time switch programs and saves enormous amounts of time. This prevents human error and enables simple copying of complete time switch programs to different time switches. Astro function: The Astro and Expert time switches have one key strength: the Astro function. The exact time of sunrise and sunset is available for every location and every day in the year. This means, for example, that the connected outer lighting is only switched on when it is dark - whether it is winter when the days are shorter or in summer when the days are much longer. The benefits are obvious: Cost-savings, because electricity is only used when the lighting is really needed, and because this prolongs the service life of the lighting itself. Particularly in the case of dusk-dependent lighting controls. Safety and convenience, because the light is always switched on when it's dark Ease-of-use, because the digital time switch doesn't have to be reprogrammed throughout the year Installation couldn't be easier, because Astro digital time switches work in the distribution board. o further need for laborious cable laying to the light sensors. This means that it is not necessary to lay cables across the lightning protection zones. The compact 2-MW series is also ideally suited for retrofitting or replacement. It goes without saying that the digital time switches Astro and Expert don't just switch at dawn and dusk, complex, combined programs are also possible. You always have the choice between astronomically calculated and individually set switching times, or a combination of both. Siemens 200 4
42 Switching devices Timers Siemens AG 20 Digital time switches, 7LF4 PC programming: The Profi, Astro and Expert digital time switches support plug-in data keys. This provides even greater safety and convenience. For example, the data key lets you read out a program from a digital time switch, copy it to a PC, where it can be saved and edited - or simply transfer it to another time switch. You can also work with several data keys and it takes only a matter of seconds to change programs. A safety copy ensures fast service. So if a time switch has been interfered with, you can simply use the data key to transfer the stored program back to the time switch. Thanks to the standard operator interface, based on MS-Office, there is no need for laborious program training. Pulse function for -channel devices: With the pulse function, up to 84 start times and a pulse time can be programmed onto the time switch. The pulse duration can be selected between s and 59 min 59 s. Random function: If the random function is activated, the set switching times are shifted within a range of +/- 30 min. Operating hours meter: For commercial fields of application in particular, it is often necessary to establish the running time of the switched load, e.g. lighting. The operating hours meter shows the total O time per channel and the date of the last reset. Vacation period function: In the vacation program, the vacation period is set with start and end date. If the vacation program is activated, the digital time switch does not carry out any programmed switching commands during the relative period but, depending on the respective input, is set to "COTIUOUSLY OFF" or "COTIUOUSLY O" during the vacation period. At the end of the specified vacation period, the digital time switch automatically resumes execution of the switching commands according to the programmed switching times. Control input: The delay time that can be adjusted in the control input enables an additional switching of the relay, parallel to the switching program. Settable overtravel 0 min to 23 h 59 min, the delay time starts as soon as the voltage drops out at the control input. h test: The "H TEST" function can be used for simulating switching. If "H TEST" is activated, the switching outputs are switched for one hour. At the end of the specified time, the digital time switch automatically resumes execution of the switching commands according to the programmed switching times. PI code: Input and programming can be disabled using a four-digit PI code. Week programs: Programs that are designed to be repeated regularly every week, e.g. light control, heating control. A weekly program comprises an O/OFF time and assigned O/OFF days. Year programs: Programs that are only to be executed within a defined period of validity. They overlap with the week programs of the same channel according to an OR operation. The period of validity is specified by entering the start/end date. Validity from start date 00:00:00 to end date 24:00:00. The start date must be prior to the end date. Within their period of validity, these programs act as weekly programs. Outside their period of validity, these programs have no influence on the switching behavior. Exception programs: have a higher priority than week and year programs. Week and year programs of the same channel will not be executed within the period of validity of an exception program. However, within the period of validity other exception programs will be executed. The different exception programs overlap according to an OR operation. Cycle function: On the year time switch, channel has an additional option for "cyclic switching". The term "cyclic switching" means that within a specific period, the time switch is switched on for a specific duration (O time). The cycle time can be set between 2 seconds and 2 hours. The O time can be set between one second and one hour. 42 Siemens 200
43 Siemens AG 20 Switching devices Timers Digital time switches, 7LF4 USB adapters The Profi, Astro and Expert time switches are easy to program at the PC using the data key with the USB adapter and software. This enables the simple and fast creation of complicated time switch programs. Storing and copying time switch programs is also very easy and convenient. Clear data on the annual O time of the consumer enables a precise statement on the annual power consumption. You can create switching programs for digital time switches easily and conveniently at the PC in the comfort of your own home, store it on the data key and transfer it to the time switch on site. You save time not only when creating and transferring programs, but also during maintenance. Siemens
44 Switching devices Timers Siemens AG 20 Mechanical time switches, 7LF5 Overview These days, time switching is taken for granted. These days, energy savings through time switching have become a matter of course. In fact, it is now hard to imagine many process sequences without time switching. Mechanical time switches are used wherever the minimum switching interval is sufficient. The switching control pins can be set without the use of tools at minimum intervals of 5 minutes. They can be used for switching systems or system components, or for functions, such as: irrigation systems, greenhouses, public gardens, swimming pools, filtering installations, canopy controls, church bells, shop window lighting, advertising lighting, gym lighting, traffic signal controls, street lighting, illuminated signs, office lighting, lighting of stairwells and entrances, object illumination, preheating of industrial furnaces, spraying machines, ovens, heating systems, air-conditioning systems, fans and ventilation systems, heating and circulation pumps and sauna systems. All devices have the VDE mark and are approved to UL. 44 Siemens 200
45 Siemens AG 20 Switching devices Timers Mechanical time switches, 7LF5 Technical specifications Synchronous time switches without power reserve 7LF LF LF LF LF Quartz-clock time switches with power reserve Standards E , -2-7, UL 97 Approvals UL ,-2-7/UL 97 CSA C22.2 o. 4 and 77 Operating mode Synchronous Quartz Time program Day Day Week Hour Day Day Day Week Day Week Day Supply Rated control supply voltage U c V AC Primary operating range U c Rated frequency Hz Frequency ranges Hz 50 50/60 Rated power dissipation P v VA Channels/contacts Switching channels - Rated operational voltage U e V AC Rated operational current I e At p.f. = A 6 6 At p.f. = 0.6 A 4 4 Contacts O CO CO O CO O CO CO CO CO CO - Mechanical switching cycles in millions Electrical switching cycles at p.f. = Minimum contact load V; ma 4; 4; - Incandescent lamp load A Fluorescent lamps At 7 μa VA Uncorrected VA Safety Different phases permissible between actuator/contact Yes Yes Electrical isolation, creepage distances and clearances, actuator/contact mm 8/6 8/6 Rated impulse withstand voltage U imp kv 4 4 drive/contact - EMC: burst acc. to IEC kv > 4.4 > EMC: surge acc. to IEC kv > 2.0 > Electrostatic discharge acc. to IEC kv > 8.0 > 8.0 Power reserve storage a h 6 00 h - Minimum loading time h Battery type -- imh Li primary cell imh cell cell - Service life of battery At 20 C a At 40? a -- 5 Overvoltage category acc. to E 600- III III Function Minimum switching sequences min Make and break cycles min s Switching accuracy min ± 5 ± 30 ± 0.2 ± 5 ± 5 ± 30 ± 5 ± 30 ± 5 Clock errors per day System-synchronized ± 2.5 s ± 60/year ± 2.5 s Connections Terminals ±screw (Pozidriv) PZ PZ Conductor cross-sections of main current paths - Rigid, max. mm Rigid, min. mm Flexible, with end sleeve mm Flexible, without end sleeve mm Environmental conditions Permissible ambient temperature C Storage temperature C Resistance to Acc. to E /055/2 0/055/2 climate Degree of Acc. to E IP20, with connected conductors IP20, with connected conductors protection Safety class Acc. to E 0 II II 7LF5 30-7LF LF LF LF LF Siemens 200
46 Switching devices Timers Siemens AG 20 Mechanical time switches, 7LF5 Dimensional drawings I2_242 I2_ LF LF LF5 30-7LF LF LF LF LF LF I2_2426a LF LF Schematics Diagrams M L 4 7LF LF LF5 30- I2_249a M U 4 2 U2 7LF LF LF LF LF LF LF LF I2_2420a 46 Siemens 200
47 Siemens AG 20 Switching devices Timers Mechanical time switches, 7LF5 More information Mechanical time switches with day disk Synchronous time switches without power reserve The control gear is driven by a synchronous motor so it is dependent on the power supply frequency. If this frequency is unstable, the devices cannot be used. In the event of a power failure, the time switch will stop. Quartz-clock time switches with power reserve A quartz electronic circuit supplies the drive with a stabilized frequency so that the time switch is not dependent on the power supply frequency. In the event of a power failure, the time switch continues to operate on its power reserve. Automatic setting system This supports fast and easy installation of the 7LF and 7LF time switches. These time switches self-adjust during commissioning in fast mode to the correct time and correct day within the Central European zone. They also automatically set the correct time for daylight saving. A further advantage is the quartz-precise adjustment of the correct time and the correct day as soon as the supply voltage is reconnected after a power failure. Precision quartz mechanism Clock accuracy: The internal precision clockwork has an accuracy of ± min. per year. Until now, this level of accuracy and automatic operational safety was only possible using digital time switches. Optimization of power consumption due to minimum make and break cycles of 5 minutes: it is possible to set the switching times in 5-minute patterns, with a switching interval of at least 30 minutes. Mechanical time switches with week disk LED display The adjustment data for Central Europe are stored and an LED provides information on the current state. So: simply unpack, snap into place, connect and set the desired switching times - no tools required! This saves time and money. Clear design Extremely intuitive thanks to clear design. The switching times are easy to read. With the weekly time switch, the make and break cycles are only 20 minutes with a minimum switching interval of 240 minutes. Siemens
48 Switching devices Timers Siemens AG 20 Timers for buildings, 7LF6 Overview In many installations there is great savings potential to be found in the lighting of corridors, stairwells and ancillary rooms. Many installations are in operation for hours without anyone being present. Lighting which is switched on unnecessarily in ancillary rooms often goes unnoticed for days. Due to the gradual phasing out of incandescent lamps starting in September 2009, it is crucial we switch to other types of lighting. In particular compact fluorescent lamps (energy-saving lamps such as the Osram Dulux EL) will be used more frequently in stairwells as in other areas. Our stairwell lighting timers offer different levels of convenience, depending on the range of functions. On stairwell lighting timers from Siemens, the required time can be precisely set without tools using the push-to-lock knurling wheel. With modern fourwire installations, stairwell lighting timers can always just be pressed again. A maintained light switch prevents the need for repeated pressing, for example when moving house. The various types are available either with or without warning prior to switch-off. Technical specifications 7LF6 0 7LF6 7LF6 3 5TT 303 7LF6 4 7LF6 5 7LF6 6 7LF6 2 Standards IEC 60669, E Supply Rated control supply voltage U c V AC Primary operating range At 50/60 Hz U c Rated power dissipation P v VA Approx. 5 Setting range min Accuracy s ±30 Manual switches Automatic/permanent Yes Minimum push duration ms 30 Voltage endurance At pushbutton input Yes (pushbutton malfunction) Short-circuit strength A Channels/contacts Switching channels - Rated operational voltage U e V AC Rated operational current I e At p.f. = A Contact gap mm > > 3 Minimum contact load V; ma 0; 300 Max. incandescent lamp load W Max. energy-saving lamp load 4 W Unit(s) Fluorescent lamp load 58 W - Uncorrected Unit(s) DUO circuit Unit(s) Siemens ECG lamp Unit(s) lamps Unit(s) Glow lamp load ma Max. fan load VA Connections Terminals ±screw (Pozidriv) PZ Conductor cross-sections of main current paths - Rigid mm Flexible, with end sleeve Min. mm 2 Environmental conditions Resistance to climate Acc. to E C Degree of protection Acc. to E IP20, with connected conductors 48 Siemens 200
49 Siemens AG 20 Switching devices Timers Timers for buildings, 7LF6 Dimensional drawings A3 4 B T B2 67 & & ' 7LF6 0 7LF6 7LF6 2 7LF6 3 7LF6 4 7LF6 5 7LF I2_09 A TT 303 I2_06708c 5 43 Schematics Switching example: 7LF6 timer in 4-wire circuit, L-momentary contact, resettable Usual circuit for new installation with separate cable routing for pushbuttons and lights. The additional DI switch allows external switching to continuous light. A time switch can also be used. An additional attic circuit is also available, which operates independently of the timer, but on the same electrical circuit. The timer can be restarted before the set time expires. Switching example: 7LF6 2 timer for fans up to 200 VA The switch switches the light on immediately, e.g. in a toilet. After a delay of approx. minute, the fan is switched on. When the light is switched off, the fan continues to run for the time set at the timer. L 230 V AC 2 I2_098 L 230 V AC L2 v Min L Min t e DE L I2_096a I2_092a t e = runtime Switching example: 7LF6 timer in 3-wire circuit, -momentary contact, resettable Can only be used with a limited number of wires. The timer can be restarted before the set time expires. While this 3-wire circuit with -momentary contact is technically possible, it does not comply with DI VDE However, it is used in old systems for replacement purposes. L L V AC L2 L2 e e e I2_097a I2_095a t e = runtime Switching example: 7LF6 5 energy-saving timer with advance warning The timer is connected in the same way as the 7LF6 timer in a 4-wire or 3-wire circuit. The energy-saving timer switches on if pressed once and switches off when it is pressed again. If it is not switched off manually, it is automatically switched off after the set time, max. 60 minutes. 20 and 40 seconds before expiry, the light flashes briefly twice (50 ms) to warn of the impending tripping. This allows time to reset the switch while the light is still on. Prior to the warning time, a push of the button ends the timing interval. L2 t e = runtime ca. 20s ca. ca. 40s 40s t e t e >t>t e -40s ca. 20s t e t e-40s>t I2_099b 2 e e e I2_093a t e = runtime Siemens
50 Switching devices Timers Siemens AG 20 Timers for buildings, 7LF6 Switching example: 7LF6 6 energy-saving timer The timer is connected in the same way as the 7LF6 5 timer in a 4-wire or 3-wire circuit. The energy-saving timer switches on if pressed once and switches off when it is pressed again briefly (less than second). U Resetting is possible by pressing a second time for longer (more than second). If it is not switched off manually, it is automatically switched off after the set time, max. 60 minutes. I202_02097 L/ t<s t>s L/2 t e t<t e t<t e t e t e = runtime Lighting in ancillary rooms and corridors In rooms which are entered only rarely (basements, ironing rooms, attics, heating oil storerooms) there is a risk of the lighting remaining on unnecessarily for lengthy periods. For such cases the 7LF6 5 and 7LF6 6 energy-saving timers can cut energy costs notably while increasing user-friendliness. When a user leaves the room he can switch off the light by pushbutton, as on an installation with remote control switch. If the user's hands are full or if he forgets to switch off, the lighting will go out automatically after a pre-set time. The 7LF6 5 and 7LF6 6 energy-saving timers can also be used in corridors, e.g. as replacements for remote control switches. In this case they combine the familiar functionality of a remote control switch with the energy-saving features of a stairwell lighting timer. Switching example: 7LF6 0 timer in 3-wire circuit, L-momentary contact, not resettable Circuit for new installation with shared cable routing for pushbuttons and lights. The timer can only be restarted after the set time expires. L 230 V AC Switching example: 7LF6 3 timer with advance warning The timer is connected in the same way as the 7LF6 timer in a 4-wire or 3-wire circuit. 20 and 40 seconds before expiry, the light flashes briefly twice (50 ms) to warn of the impending tripping. This allows time to reset the switch while the light is still on. L2 t e = runtime ca. 40s t e I2_092a ca. 20s Switching example: 7LF6 4 lighting timer with advance warning The timer is connected in the same way as the 7LF6 timer in a 4-wire or 3-wire circuit. When pressed, the lighting timer switches on for the set runtime, up to 0 minutes. If the switch is pressed for more than one second, the light is switched on for four times the set time, i.e. up to 40 minutes. The last press of the pushbutton is decisive. 20 and 40 seconds before expiry, the light flashes briefly twice (50 ms) to warn of the impending tripping. This allows time to reset the switch while the light is still on. The timing interval restarts each time the button is pressed. 2 L L2 t e I2_0920 L2 t <s t<s t>s ca. ca. ca. 20s ca. 20s ca. 40s 40s 40s t e t e >t t e >t 4 xt e I2_0922b ca. 20s t e = runtime I2_095a t e = runtime 50 Siemens 200
51 Siemens AG 20 Switching devices Timers Switching example: 5TT 303 ECG control switch L + - L + - L L 230 V AC 3 A2 A T + - B B2 Timers for buildings, 7LF6 The device is fitted with a direct voltage input for the control of an ECG. When the pushbutton is actuated, the power supply is released and the ECG is brightened for up to 0 minutes, depending on the setting of the timer. On expiry of this time, the ECG is dimmed according to the set dimmer level, if pressed again it brightens again. If the switch is not pressed for 30 minutes, the lighting switches off completely. In addition to these functions, the dimming time and brightness period can also be controlled using a separate pushbutton or time switch over the control inputs B and B2. Switching the ECG and the fluorescent lamp as little as possible extends the service life. B B2 I2_070a I2_0769a t t 3 t t 3 t t 3 t 3 4 t 2 t 2 t 2 t 2 B B2 t : Bright phase t 2 : Operating period t 3 : Dim phase Corridor lighting in homes for the elderly At meal times, from 5 to 7 p.m., the light in the corridors can be permanently switched on using a time switch (contact B). Between 7 p.m. and 0 p.m., the lighting is dimmed using switch B2. Simply press the corridor pushbutton again to return the lighting to the bright setting at any time. After 0 p.m., the light is switched off. It can be switched back on at any time by pressing the corridor pushbutton. Corridor lighting in hospitals During the day during peak periods, lunch times, visiting times, shift changes, doctor's rounds the light is switched on. During quiet periods, i.e. afternoons and nights, the light is switched to a dimmed state. A patient can switch the light back to the bright setting at any time by pressing the corridor pushbutton. In emergencies, the nurse can switch the light to "emergency operation", i.e. permanently bright, using switch B (no time limit of brightness period). Siemens 200 5
52 Switching devices Timers Siemens AG 20 Timers for buildings, 7LF6 More information Stairwell lighting This is required in DI "Electrical installations in residential buildings; ature and extent of minimum equipment". What is less known is that 00 lux is required according to E 24- "Lighting of workplaces" for traffic areas and corridors, section 5.3. This means that approx. 60 W incandescent lamps, 25 W energy-saving lamps or 25 W fluorescent lamps need to be used. It is hard to see why lesser requirements should apply to stairwells in residential buildings than stipulated in E wire circuit, L-momentary contact 4 conductors are installed within the building. The timing interval is started by pressing phase L. During the runtime, the timer can be reset at all times. 3-wire circuit, L-momentary contact 3 conductors are installed within the building. The timing interval is started by pressing phase L. o resetting is possible during the runtime as the pushbutton input and output are exposed to the same potential during this period. The glow lamps are switched off during the runtime. 3-wire circuit, -momentary contact 3 conductors are installed within the building. The timing interval is started by pressing the conductor. During the runtime, the timer can be reset at all times. However, this switching no longer corresponds to DI VDE 000 and is now only used in old systems. Safety through warning prior to switch-off DI "Electrical installations in residential buildings: ature and extent of minimum equipment" stipulates that the automatic lighting-off control in stairwells of appartment houses must be equipped with a warning function to prevent sudden darkness in the building. This contribution towards safety is offered by 4 device versions. The 7LF6 3 stairwell lighting timer, the 7LF6 4 lighting timer and the 7LF6 5 energysaving timer warn of an impending off by flashing, the 5TT 303 stairwell lighting timer ECG warns of an impending switch-off by dimming, allowing sufficient time for the light switch to be pressed again. Manual switches All timers have a manual switch for the function "Automatic/O". This allows the operator to switch to continuous light in the event of moving house or emergencies. Useful continuous contact Pushbuttons should never jam. For this reason, all our timers have a safeguard to prevent this type of malfunction. Even better, this feature can be used (e.g. by caretakers of properties) to switch to a continuous light in the event of moving house or emergencies. Setting accuracy The electronic remote control switches offer a high degree of accuracy. The runtime can be set precisely to +30 seconds using the push-to-lock knurling wheel setting. The factory settings ensure that the limit values of and 0 or 60 minutes can be reliably set. Short-circuit strength Stairwell lighting timers are primarily used for the switching of incandescent lamps, which may occasionally be subject to short circuits. A key feature of all devices is their high short-circuit strength without the contacts welding. Switching of fluorescent lamps In order to extend their service life as far as possible, fluorescent lamps should only be switched using a stairwell lighting timer if the switching frequency is not excessive. Using electronic ballast (ECG) to operate them is more gentle on the device and saves energy. The 5TT 303 stairwell lighting timer ECG switches the electronic ballast and warns of the impending switch-off by dimming. Switching of energy-saving lamps The switching of energy-saving lamps depends greatly on the lamp type used. Standard energy-saving lamps are generally unsuitable for warning by flashing or dimming prior to switch-off. The 7LF6 0 and 7LF6 stairwell timers and the 7LF6 6 energy-saving timers without warning of impending switch-off are suitable for the use of standard energy-saving lamps (e.g. OSRAM DULUX EL). For applications with warning of impending switch-off (7LF6 3 and 7LF6 4 stairwell lighting timers or 7LF6 5 energy-saving timers) we recommend the use of special energy-saving lamps such as OSRAM DULUX EL FACILITY or OSRAM DULUX EL VARIO. Download from the Internet: For more information please visit us on the Internet at: 52 Siemens 200
53 Siemens AG 20 Switching devices Timers Timers for industry, 5TT3 Overview Time relays are primarily used in series applications where the use of PLC controls is too labor and cost-intensive. Multifunction relays are now the market standard. Operation is clear, simple and offers a range of functions. Technical specifications Dimensional drawings 5TT3 85 5TT3 8 5TT3 82 5TT3 83 5TT3 84 Standards E 60255; DI VDE Supply Rated control supply voltage U c V AC V DC Primary operating range U c Rated frequency f n Hz /60 Rated power dissipation P v VA Approx..5 Approx. 5 Approx. Setting ranges See setting ranges, timing intervals Recovery time ms Approx. 40 Approx. 00 Contacts Switching channels - Rated operational voltage U e V AC Rated operational current I e A Contact gap mm μ contact - Minimum contact load V; ma 0; 300 Rated impulse withstand voltage U imp Input/output kv > 4 Electrical service life In switching cycles A At AC Connections Terminals ±screw (Pozidriv) 2 Conductor cross-sections of main current paths - Rigid, max. - Flexible, with end sleeve, min. Environmental conditions mm 2 mm Permissible ambient temperature C Resistance to climate Acc. to E /60/4 ) # $ & ) # $ & ) # $ & " # ' * ) & # "! ) & ) & $ # # = # "! $ " 5TT3 85 5TT3 8 5TT3 82 5TT3 83 5TT3 84 Schematics Diagrams A B 6 8 MF A2 5 5TT3 85 5TT3 8 5TT3 82 5TT3 83 5TT3 84 A 6 8 A8 6 A2 Z3 Z4 Z5 5 A2 5 Siemens
54 Switching devices Timers Siemens AG 20 Timers for industry, 5TT3 More information 5TT3 8 delay timers 5TT3 83 flashing timers A-A t V t V = Time delay I2_07026 Possible time setting rangest v 0.25 s s s... 0 s 8 s s s s -A2 8 6 t an t ab I2_07024 t an = Relay energized t ab = Relay de-energized Possible joint time setting range of t on = t off = t s... 0 s Response delay Flashing function 5TT3 82 wiper timers 5TT3 84 off-delay timers A-A t W t W = Wiping time I2_07023a Possible time setting rangest w s... 0 s A-A t t t < t t = Drop out delay I2_07025 A Possible time setting rangest s... 0 s t = interruption Wiper function OFF-delay 54 Siemens 200
55 Siemens AG 20 Switching devices Timers Timers for industry, 5TT3 5TT3 85 multifunctional timers Setting aids The period of the flashing of the green LED when set for a timing interval is s ± 4%, which can therefore be used as a setting aid. This is particularly useful in the lower time setting range and for long delay times because the multiplication factors between the individual time ranges are exact. Example: Delay time to be set: 40 min. Using the fine setting, this delay time can be set within the setting range min. However, in this case it takes a long time to check the time and requires several operational sequences in realtime. To speed up the setting process, the setting range will be switched to min. In this case, the required value corresponds to a delay time 0.4 min (= 24 s). The timing interval is triggered and the potentiometer is set to 24 flashing periods of the yellow LED 2. The device is then set back to the setting range min and the setting process is completed. Time operation interruption/time addition For the functions AV, EW, IE, BI, the timing interval can be interrupted at any time by activating B (+) and by removing the control voltage continued again (time addition). Control input B The functions RV, IF, AW, AV/RV can be controlled using the control input B (+) with potential against terminal A2. The auxiliary voltage of terminal A can be used for this purpose, as well as any other voltage within the range V AC/DC. The operation of parallel loads (e.g. contactors) from B (+) to A2 is also permissible. If voltage is simultaneously applied to the control input B (+) and A for the IF function, this triggers an output pulse with the set time interval t. Control S Response delay Passing make contact function Pulse generator, delayed Flashing relay, starting with impulse AV EW IE BI Position Function switch Contact c A-A2 St B-A t t t t t 0,5 s Possible time setting ranges t: s s s min min min h h A 5 Control S2 A-A2 6 8 OFF-delay Pulse shape Passing break contact function Response delay OFF-delay Control S S A L+ A2 RV IF AW AV/RV Contact S For the functions: response delay, passing make contact function, pulse generator delayed, clock generator (start with pulse) the timing interval is triggered by closing the switching contact S S2 B-A Control S2 L+ B(+) A A2 Control contact S2 The functions: off-delay, pulse shape, passing break contact function, response and off-delay are triggered by continuous power supply over the control contact S2 between A and B (+). t t t t t t t t t t t t t t I2_08b User interfaces LED Status display LED 2 Switching position indication E Setting range adjuster Z Fine adjuster for setting ranges E2 Function settings for timing intervals Device displays LED Lights up if operational voltage is applied (green) LED 2 indicates the timing interval and state of the equalizing relay (yellow) Continuous light - Off output relay not activated, no timing interval - On output relay not activated, no timing interval Flashing light - Short on, long off Output relay not activated, timing interval - Short on, long off Output relay activated, timing interval LED grün LED 2 gelb Front view B(+) A2 I20_970 E Z E2 LED green:status display LED 2 yellow:switching position indication E: Setting range adjuster Z: Fine adjuster for setting ranges E2: Function settings for timing intervals Siemens
56 Switching devices Siemens AG 20 otes 56 Siemens 200
57 Siemens AG 20
58 Siemens AG 20 Siemens AG Industry Sector Building Technologies Division Low Voltage Distribution Postfach REGESBURG GERMAY Subject to change without prior notice PDF only 3P PH En Siemens AG 20 The information provided in this configuration Manual contains descriptions or characteristics of performance which in case of actual use do not always apply as described or which may change as a result of further development of the products. An obligation to provide the respective characteristics shall only exist if expressly agreed in the terms of contract. Availability and technical specifications are subject to change without notice. All product designations may be trademarks or product names of Siemens AG or supplier companies whose use by third parties for their own purposes could violate the rights of the owners.
BETA Switching. Switching Devices. 5TT5 8 Insta contactors, AC technology. Overview
BETA Switching Siemens AG 200 5TT5 Insta contactors, AC technology Overview The 5TT5 Insta contactors are equipped with an AC magnetic system and are ideal for use under harsh conditions. The auxiliary
Switching Devices. 8/2 Introduction. 8/5 5TE8 control switches. 8/8 5TE4 pushbuttons. 8/11 5TE5 light indicators. 8/13 5TE On/Off switches
Siemens AG 2014 Switching Devices /2 Introduction /5 5TE control switches / 5TE4 pushbuttons /11 5TE5 light indicators /13 5TE On/Off switches /20 5TE DC isolators /22 5ST busbars for modular installation
Catalog. Modular DIN rail components Installation contactors
Catalog Modular DIN rail components Installation contactors 0 CDC00C00 Installation contactors Benefits and features Overview Ordering details ESB installation contactors ESB0 ESB ESB0 ESB 7 EN installation
Technical catalogue. Modular DIN rail components Installation contactors
Technical catalogue Modular DIN rail components Installation contactors Installation Contactors Overview... ESB Installation Contactors 0 A / AC-/AC-7a ESB0...4 4 A / AC-/AC-7a ESB4...5 40 A / AC-/AC-7a
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated. Ordering information
Type: DILM115(RAC240) Article No.: 239548 Sales text Contactor,55kW/400V,AC operated Ordering information Connection technique Description Description Rated operational current Screw terminals 3 pole AC
ABB i-bus KNX Fan Coil Actuator, MDRC FCA/S 1.1M, 2CDG 110 084 R0011
, 2CDG 110 084 R0011 2CDC 071 112 F0008 The Fan Coil Actuator is a modular installation device (MDRC) in pro M design. It is intended for installation in the distribution board on 35 mm mounting rails.
ABB i-bus KNX SA/S Switch Actuators Product Manual
ABB i-bus KNX SA/S Switch Actuators Product Manual Contents Contents Page 1 General... 5 1.1 Using the product manual...5 1.1.1 Structure of the product manual...6 1.1.2 Notes...6 1.2 Product and functional
Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
Safety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1
Product and functional description
Product and functional description The KNX / DALI gateway N 141/02 is a 4 MU wide, DINrail mounted KNX device with one DALI interface to which up to 64 DALI actuators (e.g. DALI ballasts) can be connected
38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.
38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC
Electronic overload relay EF65, EF96 and EF146
Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.
ABB i-bus KNX Switch Actuators SA/S Product Information
ABB i-bus KNX Switch Actuators SA/S Product Information ABB Stotz-Kontakt GmbH Your Partner with Know-How for Future-Oriented Electrical Installation Hugo Stotz, the company founder of ABB Stotz-Kontakt,
Installation Contactors. Technical Catalogue. Type ESB. abb. ABB STOTZ-KONTAKT GmbH 1 2CDC 103002 C0201
Technical Catalogue Installation Contactors Type ESB abb ABB STOTZ-KONTAKT GmbH 1 CDC 10300 C001 ABB STOTZ-KONTAKT GmbH CDC 10300 C001 Low Voltage Products and Systems We ensure safety and comfort for
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical
Electronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
ABB i-bus KNX Switch Actuator, x-fold, 16 A, MDRC SA/S x.16.2.1, 2CDG1101xxR0011
Technical Data 2CDC505051D0205 ABB i-bus KNX Product description Switch Actuators SA/S x.16.2.1, 16 A are modular installation devices in ProM design for installation in the distribution board. They are
Thermistor motor protection
Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor
ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
Mini Motor Contactor J7KNA Main contactor Accessories Approved Standards Standard Guide No (US,C) Ordering Information tage Model Number Legend gear
Mini Motor Contactor J7KNA ) Main contactor AC & DC operated Integrated auxiliary contacts Screw fixing and snap fitting (35 mm DIN-rail) Range from 4 to 5.5 (AC 3, 380/415V) 4 -main pole version (4 AC
BETA Protecting SITOR Semiconductor Fuses
BETA Protecting SITOR Semiconductor Fuses /2 Product overview /3 /17 SITOR, cylindrical fuse design /22 SILIZED, NEOZED and DIAZED design Siemens ET B1 /2008 Product overview Overview Devices Page Field
ABB i-bus KNX Switch Actuators SA/S Product Information
ABB i-bus KNX Switch Actuators SA/S Product Information ABB Stotz-Kontakt GmbH Your Partner with Know-How for Future-Oriented Electrical Installation Hugo Stotz, the company founder of ABB Stotz-Kontakt,
Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830
Type: DILM50(230V50HZ,240V60HZ) Article No.: 277830 Ordering information Rated operational current AC 3 400 V I e A 50 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase
Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous. 1 auxiliary contact (N/C), instantaneous
Safety relay for monitoring E-STOP pushbuttons. Approvals Unit features Positive-guided relay outputs: 3 safety contacts (N/O), instantaneous 1 auxiliary contact (N/C), instantaneous Safe separation of
Residual Current Protective Devices
Residual Current Protective Devices /2 Introduction / 5SM3 RCCBs /9 SIQUENCE, 5SM3 and 5SU1 universal -sensitive RCCBs, type B and type B+ /12 Additional components /1 5SM2 RC units /18 5SU1 RCBOs /25
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
Technicaldata General
Currenttransformer-operatedoverloadrelay,60-90A,1N/O+1N/C Partno. ZW7-90 Articleno. 002618 CatalogNo. XTOT090C3S Deliveryprogramme Product range ZW7 current transformer-operated overload relays Description
Type: DILM32 10(24V50HZ) Article No.: 277247
Type: DILM32 10(24V50HZ) Article No.: 277247 Ordering information Rated operational current AC 3 400 V I e A 32 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors,
Bimetallic Overload Relay Specifications
Technical Data Bimetallic Overload Relay Specifications Bulletin Number 193K, 193T1 Topic Page Product Overview 2 Standards compliance and Certifications 2 General Specifications 193K 3 Approximate Dimensions
Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1
Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input
5SV Residual Current Protective Devices
s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective
MasterINTERFACE 39 Series - Relay interface modules
MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy
E-STOP relays, safety gate monitors
Unit features Safety features Gertebild ][Bildunterschrift_NOT_Sch.tuer_Licht Safety relay for monitoring E-STOP pushbuttons, safety gates and light beam devices Approvals Gertemerkmale Positive-guided
PHOENIX CONTACT - 2012-12-14. Features
Electronic monitoring relay for phase sequence, phase failure, and asymmetry monitoring Data sheet 101748_en_03 1 Description PHOEIX COTACT - 2012-12-14 Features Increasingly higher demands are being placed
Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592. * see variants. Applications.
Safety Technique SAFEMASTER Emergency Stop Module BG 5924, IP 5924 Your Advantages For safety application up to PL e / Cat. 4 e.g. SIL 3 Manual or automatic start 0225592 BG 5924 IP 5924 Product Description
ESB and EN installation contactors Application handbook
ESB and EN installation contactors Application handbook 2 2CDC103022M0201 Content 1 Basic function of installation contactors 4 2 Modular DIN rail components 5 3 ESB/EN Installation contactors 6 4 Technical
Type: DILM9 10(24VDC) Article No.: 276705
Type: DILM9 10(24VDC) Article No.: 276705 Ordering information Rated operational current AC 3 400 V I e A 9 Max. rating for three phase motors, 50 60 Hz AC 3 230 V Max. rating for three phase motors, 50
MONITORING RELAYS. w VOLTAGE MONITORING RELAY UR5U1011. w SCHRACK-INFO. w TECHNICAL DATA
w VOLTAGE MONITORING RELAY UR5U1011 w SCHRACK-INFO AC/DC voltage monitoring in 1-phase mains Undervoltage monitoring 1 change over contact Width 17.5 mm Installation design w TECHNICAL DATA 502 1. Functions
MasterINTERFACE 39 Series - Relay interface modules
MasterINTERFACE 39 Series - 39 Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy ejection by plastic
Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
R.C.C.B. s two-pole LEXIC
87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...
Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
RM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
DEK-REL- 24/1/SEN. Extract from the online catalog. Order No.: 2964050
Extract from the online catalog DEK-REL- 24/1/SEN Order No.: 2964050 Relay terminal block for sensor, with soldered-in miniature relays, contact (AgNi+Au): small to medium loads, 1 N/O contact, input voltage
ABB i-bus KNX Switch Actuator, x-fold, 16/20 A, MDRC SA/S x.16.6.1, 2CDG 110 1xx R0011
, 2CDG 110 1xx R0011 SA/S 8.16.6.1 2CDC 071 006 S0010 The 16/20 A Switch actuators are modular installation devices in Pro M Design for installation in the distribution board. The devices are especially
Pluggable interface relays CR-P Pcb relays
2CDC 293 034 F0004 1 2 4 3 Features 9 different supply s: DC versions: 12 V, 24 V, 48 V, 110 V AC versions: 24 V, 48 V, 110 V, 120 V, 230 V Output contacts: 1 c/o (16 A) or 2 c/o (8 A) Cadmium-free contact
AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits
DALI RC BASIC SO. Control unit Operating instructions
DALI RC BASIC SO Control unit Operating instructions Contents Safety... 4 General instructions 4 Safety instructions 4 Description... 5 Purpose and application 5 Function 5 Light control 5 Brightness
48 SERIES Relay interface modules 10 A
48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply
Safety Relays ESM/ESM-F
Safety Relays ESM/ESM-F More than safety. Safety More than safety. Emil Euchner, the company s founder and inventor of the multiple limit switch, circa 1928. Around the world the Swabian specialists in
0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N
55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils
Series 8146/5-V37 and Series 8150/5-V37
www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection
Product and Applications Description. Application Programs. Example of Operation. GAMMA instabus Technical Product-Information.
Product and Applications Description The power supply units N 125/x2 can supply DC 24 V power from an additional pair of terminals (yellowwhite). This DC 24 V output voltage can be used to power e.g. an
ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories
2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used
Process modules Digital input PMI for 24 V DC inputs for 120 V AC inputs
E031026 000823 Process modules Digital input PMI for inputs for 120 V AC inputs PMI Input E4, E5, GND L- PMI 120 V AC Input E4, E5, Common C E6, E7, GND L- E6, E7, Common C LEDs for the inputs operation
AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A
AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components
RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
Bulletin 150 SMC Flex Smart Motor Controller Specifications
Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering
instabus KNX / EIB System System E F G H
Product name: Uninterruptible power supply (USV) 640 ma Design: REG (rail-mounted device) Article-no.: 1079 00 ETS search path: Gira Giersiepen / system components / power supply / power supply 640mA DRA
VEO. V4PF480Y/277VSYTK02 Art.Nr.: 2104200. V4PF480Y/277VSYTK02P Art.Nr.: 2104210 TECHNICAL DATA
Monitoring of phase sequence and phase loss Monitoring of asymmetry Temperature monitoring (PTC) Supply voltage 208-480 V AC Supply circuit = measuring circuit 2 change-over contacts Width 45 mm Control
Quick Connect. quick - simple - efficient. www.g-mw.de
Quick Connect quick - simple - efficient www.g-mw.de Phone: +49 9103 7129-0 Fax: +49 9103 7129-207 Innovative connection technology to plug three single-phase current transformers to multifunctional power
Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
How can a charging station for electric vehicles be set up simply and safely?
SB18 Building > Electromobility > Charging Station Design How can a charging station for electric vehicles be set up simply and safely? Requirement In order to supply electric vehicles with electric power,
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
15 Series - Electronic step relay and dimmer. Features 15.91 15.51 15.81 SERIE
Series - Electronic step relay and dimmer SERIE Features.91.51.81 Electronic step relay and dimmer for control of lighting levels Suitable for incandescent and halogen lighting loads (with or without transformer
LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 - <= 440 V 65 A - 220 V AC coil
Product data sheet Characteristics LC1D65AM7 TeSys D contactor - 3P(3 NO) - AC-3 -
Thermal-Magnetic Circuit Breaker 3120-...-M1-..
Thermal-Magnetic Circuit Breaker -...-M-.. Description Single or two pole rocker switch/thermal-magnetic circuit breaker with trip-free mechanism (S-type TM CBE to EN 34). The addition of a magnetic tripping
Emergency stop As an emergency switching off/emergency stop device. Standards According to IEC/EN 60204-1, VDE 0113 Part 1
MainswitchSurfacemounting Partno. P3-63/I4/SVB Articleno. 207343 CatalogNo. SP3-063-I4CRQ IP65 Deliveryprogramme Product range Switch-disconnectors Basic function Main switches Maintenance switches Manual
80 Series - Modular timers 16 A. Features 80.01 80.11
80 Series - Modular timers 16 A Features 80.11 Multi-function and mono-function timer range - Multi-function & multi-voltage 80.11 - On-delay, multi-voltage 17.5 mm wide Six time scales from 0.1s to 24h
48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.
48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according
Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable
Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window
49 Series - Relay interface modules 8-10 - 16 A. Features
Features 1 & 2 Pole relay interface modules 5 µm Gold plate contacts for low level switching capability 49.31-50x0-1 Pole 10 A (screw terminal) 49.52-50x0-2 Pole 8 A (screw terminal) 49.72-50x0-2 Pole
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: [email protected]
Product description Wide rated operational voltage 208 600 V AC Wide rated control supply voltage 100 250 V, 50/60 Hz Rated operational current 18 to 370 A Wide ambient temperature range, -25 to +60 ºC
Digital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS
SECTION 4 ELECTRIC MOTORS UNIT 17: TYPES OF ELECTRIC MOTORS UNIT OBJECTIVES After studying this unit, the reader should be able to Describe the different types of open single-phase motors used to drive
3RT1015-1BB41 CONTACTOR, AC-3 3 KW/400 V,
Automation Technology > Industrial Controls > Switching Devices > Contactors and Contactor Assemblies > Power Contactors for Switching Motors > Contactors SIRIUS 3RT10, 3-pole, 3... 250 kw 3RT1015-1BB41
Technical Manual Functional Description for S800-RSU-H / S800W-RSU 2CCC413022M0205. 8201 Schaffhausen 1 / 10
ABB ABB Schweiz AG Technical Manual Functional Description for S800-RSU-H / S800W-RSU 2CCC413022M0205 09.04.2014 Page: 8201 Schaffhausen 1 / 10 Please use also the assembly instruction S800-RSU-H Remote
E-STOP relays, safety gate monitors
Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Unit features Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous Connection
PNOZsigma - Base units
PNOZsigma - Base units Register Login Sensors Control and Communication Electronic monitoring relays Safety Relays PNOZ X PNOZsigma PNOZelog PNOZmulti PNOZpower Configurable control systems Programmable
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
Safety automation solutions
Operating principle, characteristics Preventa safety s types XPS AV,, For and switch monitoring Operating principle Safety s XPS AV, and are used for monitoring circuits conforming to standards EN/ISO
LINETRAXX VMD460-NA. Network and system protection (NS protection) for monitoring the power feed-in of power generation systems
LIETRAXX -A etwork and system protection (S protection) for monitoring the power feed-in of power generation systems TDB301021en/06.2013 LIETRAXX -A etwork and system protection (S protection) for monitoring
Magnetic and Hydraulic-Magnetic Circuit Breaker 8340-G2...
Magnetic and Hydraulic-Magnetic Circuit Breaker 840-G2... Description Single, two and three pole magnetic circuit breakers with trip-free mechanism and push/pull on/off manual actuation. A choice of fast
NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101433D0201 28/03/11 NF71E-.. / NFZ71E-.. Contactor Relays AC / DC Operated - with Screw Terminals NF(Z) contactor relays are used for switching auxiliary and control circuits.
13 SERIES. Electronic step relays 10-16 A 13.81 13.91
13 Electronic step relays 10-16 A 13 13.81 - Electronic step relay - Rail mount - 1 Pole 13.91 - Electronic step relay and timing step relay Switch box mount - 1 Pole Fixed time (10 minutes) timing function
SKR - industry relay
SKR - industry relay the universal relay SKR the time module STM the socket The strengths of the SKR industry relay lie in the mature and thoughtout construction. Over-average contact safety and life time,
Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)
Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,
Notes on Product Changeover
13 13/2 Notes on Product Changeover Introduction 13/3 Devices for delivery over the long term 13/4 devices with a mounting depth of 55 mm 13/5 devices with a mounting depth of 55 mm 13/15 devices with
93.68/93.69. Time scale: from 0.1s to 6h Multi-function For use with 34.51 (EMR) and 34.81 (SSR) relays. Screw terminal and push-in terminal
Series - Timed socket for 34 series Features.68/.69 Slim timed sockets for 34 series, 6.2 mm wide Timer adjustment via top mounted rotary knob accessible after assembly Control signal terminal DIP-switch
Relés e Contatores de Estado Sólido SIRIUS
Relés e Contatores de Estado Sólido SIRIUS Coletânea de dados técnicos ( product data sheet ) Agosto/212 SSR - 3RF21 22,5 mm Ponto Zero SSR - 3RF2 45 mm Ponto Zero SSR - 3RF22 45 mm Ponto Zero Trifásico
Fixed - Over/Under voltage limits, (0.75...1.2) U N respectivity Link selectable - 5 min or 10 min delay. Fixed limits
Features 71.11.8.230.0010 71.11.8.230.1010 1 - Phase 230 V Over & Under voltage monitoring relays 71.11.8.230.0010 - Fixed Over & Under voltage detection - Link selectable 5 or 10 minute lock-out delay
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
DC Motor control Reversing
January 2013 DC Motor control Reversing and a "Rotor" which is the rotating part. Basically there are three types of DC Motor available: - Brushed Motor - Brushless Motor - Stepper Motor DC motors Electrical
E-STOP relays, safety gate monitors
Gertebild ][Bildunterschrift Safety relay for monitoring E-STOP pushbuttons and safety gates. Approvals Unit features Gertemerkmale Positive-guided relay outputs: 2 safety contacts (N/O), instantaneous
STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase
Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff
PSR The compact range Description
Description The PSR range is the most compact of all the ABB softstarter ranges, thereby making it possible to fit many devices into the same enclosure. The system concept with Manual Motor Starters provides
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132