SUGGESTED SPECIFICATION For Medium Voltage Automatic Transfer Switches
|
|
|
- Jody Norris
- 9 years ago
- Views:
Transcription
1 SUGGESTED SPECIFICATION For Medium Voltage Automatic Transfer Switches Division 26 - Electrical PART 1 GENERAL 1.01 Scope A. Furnish and install automatic transfer switches (ATS) with number of poles, amperage, voltage, withstand and close-on ratings as shown on the plans. Each automatic transfer shall consist of Medium voltage (5 kv through 15 kv) freestanding metal-clad switchgear with vacuum circuit breakers and a microprocessor controller to provide automatic operation. All transfer switches and controllers shall be the products of the same manufacturer Codes and Standards The automatic transfer switches and controls shall conform to the requirements of: A. UL 1008A Standard for Medium Voltage Transfer Switches, 1 st Edition, for transfer switches rated greater than 750 volts up to 46 kv. B. ANSI/IEEE C Standard for Metal-Clad Switchgear. C. ANSI/IEEE C37.04 Standard Rating Structure for AC High-Voltage Circuit Breakers. D. ANSI/IEEE C37.06 Standard for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis Preferred Ratings an Related Required Capabilities for Voltages Above 1000V. E. ANSI/IEEE C37.11 Standard Requirements for electrical control for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis or a total current basis. F. ANSI/IEEE C37.09 Standard Test Procedure for AC High-Voltage Circuit Breakers Rated on a Symmetrical Current Basis. G. ANSI Z55.1 Gray Finishes for Industrial Apparatus and Equipment. H. ANSI/IEEE C57.13 Standard Requirements for Instrument Transformers. I. NEMA SG4 Alternating Current High Voltage Circuit Breakers Publication 3260
2 J. NEMA SG5 Power Switchgear Assemblies. K. IEEE C Standard of Common Requirements for High Voltage Power Switchgear Rated Above 1000 V. L. NFPA 99 - Essential Electrical Systems for Health Care Facilities. M. NFPA Emergency and Standby Power Systems. N. IEEE Standard IEEE Recommended Practice for Emergency and Standby Power Systems for Commercial and Industrial Applications. O. NEMA Standard ICS10 (formerly ICS2-447) AC Automatic Transfer Switches. P. UL 508 Industrial Control Equipment Acceptable Manufacturers A. Automatic transfer switches shall be ASCO 7000 Series. Any alternate shall be submitted for approval to the consulting engineer at least 10 days prior to bid. Alternate bids must list any deviations from this specification. B. The metal-clad switchgear and circuit breaker shall be manufactured by Square D, Siemens or an approved equal Warranty ASCO product is warranted to be free of defects in material and workmanship for a period of eighteen (18) months from date of shipment from ASCO provided that the product has been stored in a suitable environment prior to installation. The product shipment date will be determined only from the ASCO bill of lading. If any part or portion of the ASCO product fails to conform to the Warranty within the Warranty period, ASCO, at its option, will furnish new or factory remanufactured products for repair or replacement of that portion or part Extra Materials/Accessories A. Submit [one] [ ] racking handle(s)* per Medium Voltage ATS line-up. Charging handle to be furnished on each breaker mechanism. * Any additional racking handles shall be specified. B. [Provide [one] [ ] circuit breaker lifting device.] C. Following are Recommended Spare Parts for Medium Voltage ATS up to 5 kv. ASCO Part No. Qty. Description A500T2E1 3 Shawmut, Fuse Type A500T 2 Amp, 5KV ABB, Control Relay, 2NO/2NC, V, 50/60Hz Coil, 600VAC, 10A Cont., 7200VA Make, 720VA Break, ABB Type NF22E ASCO Harness GRP1/5 Y-Adapter ASCO Group 5 Control Panel ASCO, Dual Operator Control (DOC) Publication 3260
3 Bussman, Fuse Type KTK 1 Amp, 600V Bussman, Fuse Type KTK 6 Amp, 600V Chint, Circuit Breaker, 2P, 10A, 125VDC Deltrol Controls, Relay DPDT 24VDC Coil Electro Switch Green LED s for Circuit Breaker Control Switch Electro Switch Red LED s for Circuit Breaker Control Switch Electro Switch Yellow LED s for Circuit Breaker Control Switch A 3 IDEC, PL Green LED, 16mm, 24VAC/VDC Pilot Light A 3 IDEC, PL Red LED, 16mm, 24VAC/VDC Pilot Light PK61SP 2 Square D Spray Paint, ANSI VAC 1 Timemark Corp., Capacitor Trip Device, Auto Charge, 120VAC 60Hz Input, 380VDC Min. Output D. Following are Recommended Spare Parts for Medium Voltage ATS up to 15 kv. ASCO Part No. Qty. Description 15.5CAVH1E 3 Bussman, Fuse Type CAV 1 Amp, 15.5KV ABB, Control Relay, 2NO/2NC, V, 50/60Hz Coil, 600VAC, 10A Cont., 7200VA Make, 720VA Break, ABB Type NF22E ASCO Harness GRP1/5 Y-Adapter ASCO Group 5 Control Panel ASCO, Dual Operator Control (DOC) Bussman, Fuse Type KTK 1 Amp, 600V Bussman, Fuse Type KTK 6 Amp, 600V Chint, Circuit Breaker, 2P, 10A, 125VDC Deltrol Controls, Relay DPDT 24VDC Coil Electro Switch Green LED s for Circuit Breaker Control Switch Electro Switch Red LED s for Circuit Breaker Control Switch Electro Switch Yellow LED s for Circuit Breaker Control Switch A 3 IDEC, PL Green LED, 16mm, 24VAC/VDC Pilot Light A 3 IDEC, PL Red LED, 16mm, 24VAC/VDC Pilot Light PK61SP 2 Square D Spray Paint, ANSI 61 Timemark Corp., Capacitor Trip Device, Auto Charge, 120VAC VAC 1 60Hz Input, 380VDC Min. Output PART 2 PRODUCTS Publication 3260
4 2.01 Metal-Clad Switchgear Assembly A. The metal-clad switchgear shall consist of a [Type 1 Indoor] [Type 3R Outdoor Non-Walk-In] enclosure containing circuit breakers and the necessary accessory components all factory assembled (except for necessary shipping splits) and operationally checked. The assembly shall be a self-supporting and floor mounted on a level concrete pad. The integrated switchgear assembly shall withstand the effects of closing, carrying and interrupting currents up to the assigned maximum short circuit rating. B. System Voltage: [ ] kv nominal, three-phase [grounded**][ungrounded], [50] [60] Hz. C. Maximum Design Voltage: [4.76] [15.0] kv. D. Impulse Withstand (Basic Impulse Level): [60] [95] kv. E. Power Frequency Withstand: [19] [36] kv, 1 minute test. F. Main Bus Ampacity: [1200] [2000] [3000] amps, continuous. G. Momentary Current Ratings: Equal to the circuit breaker close and latch rating, [[25] [40] 5 kv] [[40] [50] 15 kv]. **Specifier to insert description, either "solidly grounded" or a specific type of impedance grounding. NOTE: This will be important when specifying Surge Arresters Components A. Stationary Structure 1. The switchgear shall comprise a minimum of [two (for 1200A)] [three (for 2000/3000A)] sections including one breaker compartment and one auxiliary compartment with potential assemblies for Normal and Emergency sources assembled to form a rigid self-supporting completely enclosed structures providing steel barriers between sections. 2. The [first (for 1200A)] [first and third (for 2000A)] [first and third (for 3000A)] section(s) is/are divided by metal barriers into the following compartments: [(a.) Circuit breaker, main bus and cable. The section may have up to two circuit breaker compartments for a 1200 ampere rating] [(a.) Circuit breaker, one set of transformer assembly, main bus and cable. The section may have up to one circuit breaker compartment and one set of potential transformer assembly compartment for a 2000 ampere rating] [(a.) Circuit breaker, main bus and cable. The section may have up to one circuit breaker compartment for a 3000 ampere rating]. 3. The [second (for 1200A/2000A/3000A)] section is divided by metal barriers into the following compartments: [(a.) Two sets of potential transformer assembly, load bus and cable. The section may have up to two sets of potential transformer assembly compartments for a [1200] [3000] ampere rating] [(a.) Load bus and cable. The section is for a 2000 ampere rating] Publication 3260
5 B. Circuit Breaker Compartment 1. Each circuit breaker compartment shall be designed to house a horizontal drawout metal-clad vacuum circuit breaker. The stationary primary disconnecting contacts are to be silver-plated copper and mounted within glass polyester support bushings. The movable contacts and springs shall be mounted on the circuit breaker element for ease of inspection/maintenance. 2. Entrance to the stationary primary disconnecting contacts shall be automatically covered by metal shutters when the circuit breaker is withdrawn from the connected position to the test or disconnected position or removed from the circuit breaker compartment. Extend a ground bus into the circuit breaker compartment to automatically ground the breaker frame with high-current spring type grounding contacts located on the breaker chassis when in the test and connected positions. Guide rails for positioning the circuit breaker and all other necessary hardware are to be an integral part of the circuit breaker compartment. Blocking devices shall interlock breaker frame sizes to prevent installation of a lower ampere rating or interrupting capacity element into a compartment designed for one of a higher rating. It shall be possible with indoor switchgear to install a circuit breaker into a bottom compartment without use of a transport truck or lift device. C. Ground Bus 1. A ¼ inch x 2 inch copper ground bus shall extend through the entire length of the transfer switch. D. Main Bus Compartment Note to Specifier: All 3000 A bus will be silver-plated copper 1. The main bus is to be rated [1200] [2000] [3000] amps and be fully insulated for its entire length with an epoxy coating by the fluidized bed process. The conductors are to be [silver-plated copper] and be of a bolted [not welded] design. Access to this compartment is gained from the front or rear of the structure by removing a steel barrier. Provide standard provisions for future extension, as applicable. E. Doors and Panels 1. Relays, control switches, etc., shall be mounted on a formed front-hinged panel for each circuit breaker compartment. Front doors shall include features to facilitate quick and complete removal or reinstallation of entire front door assembly. Door hinges shall have removable pins. Where allowable, all control circuits (except, for example, current transformers and grounding) shall be wired via plugs/receptacles prior to termination. F. Circuit Breakers 2. The circuit breakers shall be rated [ ] nominal volts, [4760] [15000] maximum volts, 60 Hz, with a continuous current rating of [1200] [2000] Publication 3260
6 [3000] amps and a maximum symmetrical interrupting rating* of [40kA/250mVA kv system] [50kA/350MVA kv system] [25kA/500MVA - 15 kv system] [40kA/750MVA - 15 kv system] [50kA/1000MVA - 15 kv system]. Furnish vacuum circuit breakers with one vacuum interrupter per phase. Breakers of same type and rating shall be completely interchangeable. The circuit breaker shall be operated by means of a stored energy mechanism which is normally charged by a universal motor but can also be charged by the manual handle supplied on each breaker for manual emergency closing or testing. The closing speed of the moving contacts is to be independent of both the control voltage and the operator. Provide a full front shield on the breaker. Secondary control circuits shall be connected automatically with a selfaligning, self-engaging plug and receptacle arrangement when the circuit breaker is racked into the connected position. Provision shall be made for secondary control plug to be manually connected in test position. A minimum of 4 auxiliary contacts (2a 2b), shall be provided for external use. 6 additional cell-mounted auxiliary contacts MOC type for external use shall be provided. [Provisions shall be made for 6 additional cell-mounted auxiliary contacts TOC type for external use.] The racking mechanism to move the breaker between positions shall be operable with the front door closed and position indication shall be visible with door closed. * Maximum symmetrical ka interrupting ratings are based on Table 1 of C MVA ratings are nominal reference values for comparison only. 3. An interlocking system shall be provided to prevent racking a closed circuit breaker to or from any position. An additional interlock shall automatically discharge the stored-energy operating mechanism springs upon removal of the breaker out of the compartment. 4. The circuit breaker control voltage shall be: 250 volts DC, 120 volts ac - one capacitor trip unit provided for each circuit breaker with ac control power. G. Instrument Transformers 1. Voltage transformers are drawout mounted with primary current-limiting fuses and shall have ratio as indicated. The transformers shall have mechanical rating equal to the momentary rating of the circuit breakers and shall have metering accuracy per ANSI Standards. 2. Current transformers*: Each breaker compartment shall have provision for mounting of optional current transformers per phase* (ANSI standard relay accuracy). The current transformer assembly shall be insulated for the full voltage rating of the switchgear. The current transformers wiring shall be Type SIS [#16] [ ] AWG minimum. [Shorting terminal blocks shall be provided; ring tongue connectors shall be used.] *Relaying and metering accuracy shall conform to ANSI Standards. H. Control Wiring Publication 3260
7 2.03 Fabrication 1. The switchgear shall be wired with Type SIS [#14] [ ] AWG minimum. The control wiring shall be UL listed and have VW-1 flame retardant rating. Wires shall terminate on terminal blocks with marker strips numbered in agreement with detailed connection diagrams. A. Construction: Each equipment bay shall be a separately constructed cubicle assembled to form a rigid freestanding unit with sufficient bracing to minimize distortion. Minimum sheet metal thickness shall be 11 gauge steel on all exterior surfaces. Adjacent bays shall be securely bolted together to form an integrated rigid structure. The rear covers shall be removable to assist installation and maintenance of bus and cables. B. The metal-clad switchgear shall be fully assembled, inspected and tested at the factory prior to shipment. Large line-ups shall be split to permit normal shipping and handling as well as for ease of rejoining at the job site Factory Finishing A. All steel parts, shall be cleaned and a [zinc-phosphate (outdoor equipment)] [iron phosphate (indoor equipment)] pre-treatment applied prior to paint application. B. Paint color shall be ANSI-61 [light grey]; TGIC polyester powder applied electro statically through air. Following paint application, parts shall be baked to produce a hard durable finish. The average thickness of the paint film shall be 2.0 mils. Paint film shall be uniform in color and free from blisters, sags, flaking and peeling. C. Adequacy of paint finish to inhibit the buildup of rust on ferrous metal materials shall be tested and evaluated per paragraphs of ANSI C Salt spray withstand tests in accordance with ASTM #D-1654 and #B-117 shall be periodically performed on a sample to confirm conformance with the corrosion resistance standard of at least [2500 hours minimum (outdoor equipment)] [600 hours minimum (indoor equipment)] Microprocessor Controller A. The controller's sensing and logic shall be provided by a single built-in microprocessor for maximum reliability, minimum maintenance, and the ability to communicate serially through an optional serial communication module. B. The controller shall be connected to the transfer switch by an interconnecting wiring harness. The harness shall include a keyed disconnect plug to enable the controller to be disconnected from the transfer switch for routine maintenance. Sensing and control logic shall be provided on multi-layer printed circuit boards. Interfacing relays shall be industrial grade plug-in type with dust covers. The panel shall be enclosed with a protective cover and be mounted separately from the transfer switch unit for safety and ease of maintenance. The protective cover shall include a built-in pocket for storage of the operator s manuals Publication 3260
8 C. All customer connections shall be wired to a common terminal block to simplify field-wiring connections. D. The controller shall meet or exceed the requirements for Electromagnetic Compatibility (EMC) as follows: EN EN EN ENV EN EN EN EN EN Enclosure Emission standard - Group 1, Class A Generic immunity standard, from which: Electrostatic discharge (ESD) immunity Radiated Electro-Magnetic field immunity Radiated RF Electromagnetic Field Immunity Electrical fast transient (EFT) immunity Surge transient immunity Conducted Radio-Frequency field immunity Voltage Dips, Interruption and Variations Immunity A. All standard and optional door-mounted switches and pilot lights shall be 16- mm industrial grade type or equivalent for easy viewing & replacement. PART 3 OPERATIONS 3.01 Controller Display and Keypad A. A four line, 20 character LCD display and keypad shall be an integral part of the controller for viewing all available data and setting desired operational parameters. Operational parameters shall also be available for viewing and limited control through the serial communications input port. The following parameters shall only be adjustable via DIP switches on the controller: 1. Nominal line voltage and frequency 2. Single or three phase sensing 3. Operating parameter protection 4. Transfer operating mode configuration (Open transition, Closed transition, or Delayed transition) To appropriately trained operators, all instructions and controller settings shall be easily accessible, readable and accomplished without the use of codes, calculations, or instruction manuals Voltage, Frequency and Phase Rotation Sensing A. Voltage and frequency on both the normal and emergency sources (as noted below) shall be continuously monitored, with the following pickup, dropout, and trip setting capabilities (values shown as % of nominal unless otherwise specified): Parameter Sources Dropout / Trip Pickup / Reset Undervoltage N&E,3 70 to 98% 85 to 100% Overvoltage N&E,3 102 to 115% 2% below trip Publication 3260
9 Underfrequency N&E 85 to 98% 90 to 100% Overfrequency N&E 102 to 110% 2% below trip Voltage unbalance N&E 5 to 20% 1% below dropout B. Repetitive accuracy of all settings shall be within ± 0.5% over an operating temperature range of -20 C to 60 C. C. Voltage and frequency settings shall be field adjustable in 1% increments either locally with the display and keypad or remotely via serial communications port access. D. The controller shall be capable (when activated by the keypad or through the serial port) of sensing the phase rotation of both the normal and emergency sources. The source shall be considered unacceptable if the phase rotation is not the preferred rotation selected (ABC or CBA). E. Source status screens shall be provided for both normal & emergency to provide digital readout of voltage on all 3 phases, frequency, and phase rotation Automatic and User Supervised Non-Automatic Control A. Open, Closed, and Delayed Transition Switching Solutions provide complete automatic control of the transfer switch. Because ASCO 7000 Series Transfer Switches are constructed as Metal-Clad Switchgear, they also include full function Non-Automatic Control to permit safe, electrically interlocked user supervised operation. B. A Transfer Switch Automatic-Manual selector switch allows the user to place the transfer switch in a fully manual mode of operation. The Normal and Emergency Source Circuit Breakers may then be operated using the circuit breaker control switches on the front of each circuit breaker compartment. This provides electrically interlocked operation to ensure that both circuit breakers cannot be closed simultaneously. Additionally, the Normal or Emergency Source Circuit Breakers may be tripped open by the circuit breaker control switches at any time during Automatic or Manual operation. C. Included Components: 3.04 Time Delays 1. Transfer Switch Auto-Man Utility Quality Selector Switch. 2. Breaker Control Utility Quality Switch. One each for Normal & Emergency Circuit Breaker. a. Trip, Close, and Pull to Lock b. Closed LED Red c. Open LED Green d. Tripped LED Amber (When Optional Protective Relaying is provided) 3. Controls Not In Auto LED (Indicates Automatic Operating Mode Disabled). A. An adjustable time delay of 0 to 6 seconds shall be provided to override momentary normal source outages and delay all transfer and engine starting signals. Capability shall be provided to extend this time delay to 60 minutes by providing an external 24 VDC power supply Publication 3260
10 B. A time delay shall be provided on transfer to emergency, adjustable from 0 to 60 minutes, for controlled timing of transfer of loads to emergency. C. Two time delay modes (which are independently adjustable) shall be provided on re-transfer to normal. One time delay shall be for actual normal power failures and the other for the test mode function. The time delays shall be adjustable from 0 to 10 hours. Time delay shall be automatically bypassed if the emergency source fails and the normal source is acceptable. D. A time delay shall be provided on shut down of engine generator for cool down, adjustable from 0 to 60 minutes. E. A time delay activated output signal shall also be provided to drive an external relay(s) for selective load disconnect control. The controller shall have the ability to activate an adjustable 0 to 5 minute time delay in any of the following modes: 1. Prior to transfer only. 2. Prior to and after transfer. 3. Normal to emergency only. 4. Emergency to normal only. 5. Normal to emergency and emergency to normal. 6. All transfer conditions or only when both sources are available. F. All time delays shall be adjustable in 1 second increments, except the extended parallel time, which shall be adjustable in.01 second increments. G. All time delays shall be adjustable by using the LCD display and keypad or with a remote device connected to the serial communications port Additional Features A. A three position momentary-type test switch shall be provided for the test / automatic / reset modes. The test position will simulate a normal source failure. The reset position shall bypass the time delays on either transfer to emergency or retransfer to normal. B. A SPDT contact, rated 5 amps at 30 VDC, shall be provided for a low-voltage engine start signal. The start signal shall prevent dry cranking of the engine by requiring the generator set to reach proper output, and run for the duration of the cool down setting, regardless of whether the normal source restores before the load is transferred. C. Auxiliary contacts, rated 10 amps, 250 VAC shall be provided consisting of one contact, closed when the ATS is connected to the normal source and one contact closed, when the ATS is connected to the emergency source. D. LED indicating lights (16 mm industrial grade, type 12) shall be provided; one to indicate when the ATS is connected to the normal source (green) and one to indicate when the ATS is connected to the emergency source (red). E. LED indicating lights (16 mm industrial grade, type 12) shall be provided and energized by controller outputs. The lights shall provide true source availability of the normal and emergency sources, as determined by the Publication 3260
11 voltage sensing trip and reset settings for each source. The following features shall be built-in to the controller, but capable of being activated through keypad programming or the serial port only when required by the user: F. Provide the ability to select commit/no commit to transfer to determine whether the load should be transferred to the emergency generator if the normal source restores before the generator is ready to accept the load. G. Engine Exerciser - The controller shall provide an internal engine exerciser. The engine exerciser shall allow the user to program up to seven different exercise routines. For each routine, the user shall be able to: 4. Enable or disable the routine. 5. Enable or disable transfer of the load during routine. 6. Set the start time: - Time of day - Day of week - Week of month (1st, 2nd, 3rd, 4th, alternate or every) 7. Set the duration of the run. At the end of the specified duration the switch shall transfer the load back to normal and run the generator for the specified cool down period. A 10-year life battery that supplies power to the real time clock in the event of a power loss will maintain all time and date information. The following feature shall be built - into the controller, but capable of being activated through keypad programming or the communications interface port. H. Terminals shall be provided for a remote contact which opens to signal the ATS to transfer to emergency. I. System Status - The controller LCD display shall include a System Status screen which shall be readily accessible from any point in the menu by depressing the ESC key a maximum of two times. This screen shall display a clear description of the active operating sequence and switch position. For example, Normal Failed Load on Normal TD Normal to Emerg 2min15s Controllers that require multiple screens to determine system status or display coded system status messages, which must be explained by references in the operator s manual, are not permissible. J. Self Diagnostics - The controller shall contain a diagnostic screen for the purpose of detecting system errors. This screen shall provide information on the status input signals to the controller which may be preventing load transfer commands from being completed. K. Communications Interface The controller shall be capable of interfacing, through an optional serial communication module, with a network of transfer Publication 3260
12 switches, locally (up to 4000 ft.) or remotely through modem serial communications. Standard software specific for transfer switch applications shall be available by the transfer switch manufacturer. This software shall allow for the monitoring, control and setup of parameters. L. Data Logging The controller shall have the ability to log data and to maintain the last 99 events, even in the event of total power loss. The following events shall be time and date stamped and maintained in a nonvolatile memory: 1. Event Logging a. Data and time and reason for transfer normal to emergency. b. Data and time and reason for transfer emergency to normal. c. Data and time and reason for engine start. d. Data and time engine stopped. e. Data and time emergency source available. f. Data and time emergency source not available. 2. Statistical Data a. Total number of transfers. b. Total number of transfers due to source failure. c. Total number of days controller is energized. d. Total number of hours both normal and emergency sources are available. O. Communications Module - A full duplex RS485 interface shall be installed in the ATS controller to enable serial communications. The serial communications shall be capable of a direct connect or multi-drop configured network. This module shall allow for the seamless integration of existing or new communication transfer devices. The serial communication interface shall be equal to ASCO Accessory 72A. PART 4 ADDITIONAL REQUIREMENTS 4.01 Tests and Certification A. The complete ATS shall be factory tested to ensure proper operation of the individual components and correct overall sequence of operation and to ensure that the operating transfer time, voltage, frequency and time delay settings are in compliance with the specification requirements. B. Upon request, the manufacturer shall provide a notarized letter certifying compliance with all of the requirements of this specification including compliance with the above codes and standards, and withstand and closing ratings. The certification shall identify, by serial number(s), the equipment involved. No exceptions to the specifications, other than those stipulated at the time of the submittal, shall be included in the certification. C. The ATS manufacturer shall be certified to ISO 9001:2008 International Quality Standard and the manufacturer shall have third party certification verifying quality assurance in design/development, production, installation and servicing in accordance with ISO 9001:2008. D. The equipment shall be factory tested to simulate a complete and integrated system. The circuit breakers supplied shall be installed in their actual positions and electrically and mechanically tested. A narrative of the system operation shall be provided and shall be utilized when testing the equipment Publication 3260
13 Copies of the test reports shall be provided. E. Upon request at order placement, the manufacturer shall provide upon completion of the order a certificate of seismic qualifications. F. Circuit breaker test reports [shall] [shall not] be provided. G. Customer inspection of equipment and witnessing of factory tests [shall] [shall not] be provided. H. All tests shall comply with applicable ANSI standards. 1. Dielectric Test: ANSI C37.20 Para , latest revision. 2. Mechanical Test: ANSI C37.20 Para , latest revision. 3. Grounding of Instrument Transformer Case Test: ANSI C37.20 Para , latest revision. 4. Electrical Operation & Control Wiring Test: ANSI C37.20 Para , latest revision. 5. Polarity Test: ANSI C37.20 Para , latest revision. 6. Sequence Test: ANSI C37.20 Para , latest revision Service Representation A. The ATS manufacturer shall maintain a national service organization of company-employed personnel located throughout the contiguous United States. The service center's personnel must be factory trained and must be on call 24 hours a day, 365 days a year. B. The manufacturer shall maintain records of each switch, by serial number, for a minimum of 20 years. *Note Spec Writer: The following section is optional and should be deleted if not used. PART 5 OPTIONAL FEATURES 5.01 POWER MANAGER 1. Furnish Power Managers at locations shown to monitor all functions specified below. 2. The Power Managers shall be listed to UL , CSA, CE Mark, and industrially rated for an operating temperature range of -20 C to 60 C. 3. The Power Manager shall be accurate to 1% measured, 2% computed values and display resolution to.1%. Voltage and current for all phases shall be sampled simultaneously to assure high accuracy in conditions of low power factor or large waveform distortions (harmonics). 4. The Power Manager shall be capable of operating without modification at nominal frequencies of 45 to 66 Hz and over a control power input range Publication 3260
14 of 20 32VDC. 5. Each Power Manager shall be capable of interfacing with an optional communications module to permit information to be sent to central location for display, analysis, and logging. 6. The Power Manager shall accept inputs from industry standard instrument trans-formers (120 VAC secondary PTs and 5A secondary CTs.) Direct phase voltage connections, 600 VAC and under, shall be possible without the use of PTs. 7. The Power Manager shall be applied in single, 3-phase, or three & four wire circuits. A fourth CT input shall be available to measure neutral or ground current. 8. All setup parameters required by the Power Manager shall be stored in non-volatile memory and retained in the event of a control power interruption. 9. The following metered readings shall be communicated by the Power Manager, via serial communication, when equipped with optional serial communications module: b. Current, per phase RMS and neutral (if applicable) c. Current Unbalance % d. Voltage, phase-to-phase and phase-to-neutral e. Voltage Unbalance % f. Real power (KW), per phase and 3-phase total g. Apparent power (KVA), per phase and 3-phase total h. Reactive power (KVAR), per phase and 3-phase total i. Power factor, 3-phase total & per phase j. Frequency k. Accumulated Energy, (MWH, MVAH, and MVARH) The following energy readings shall be communicated by the Power Manager: a. Accumulated real energy KWH b. Accumulated reactive energy KVAH c. Accumulated apparent energy KVARH NOTE: For real and reactive energy reported values, separate total for energy flow from each source shall be stored, including the arithmetic sum. 10. Power Manager Input/Output Options. a. Power Managers shall be equipped with the following I/O: 1) Provide (8) solid state status inputs. 2) Provide four (4) relay output contacts. *Note Spec Writer: The following section is optional and should be deleted if not used Publication 3260
15 The Power Manager shall flush mount to an enclosure. 1. The Power Managers shall be equipped with an optional continuous duty, long-life, 4 line x 20 character LCD backlit display to provide local access to the following metered quantities: a. Current, per phase RMS and neutral (if applicable) b. Current Unbalance % c. Voltage, phase-to-phase and phase-to-neutral d. Voltage Unbalance % e. Real power, per phase and 3-phase total f. Apparent power, per phase and 3-phase total g. Reactive power, per phase and 3-phase total h. Power factor, 3-phase total & per phase i. Frequency j. Accumulated Energy, (MWH, MVAH, and MVARH) 2. Displaying each of the Power Manager quantities shall be accomplished through the use of menu scroll buttons. 3. For ease in operator viewing, the display shall remain on continuously, with no detrimental effect on the life of the Power Manager. 4. Setup for system requirements shall be allowed from the front of the Power Manager. Setup provisions shall include: a. CT rating (xxxxx:5) b. PT rating (xxxxxxx:120) (if applicable; 14400V maximum) c. System type (single; three phase; 3 and 4 wire) d. Communication parameters 5. Reset of the following electrical parameters shall also be allowed from the front of the Power Manager: a. Real energy (MWH), apparent energy (MVAH) and reactive energy (MVARH). 6. All reset and setup functions shall have a means for protection against unauthorized/accidental changes Protective Relays: Provide relays as indicated on drawings for each circuit breaker. **Note to Specifier: Add details for protective relays, including relay types and model numbers for clarity. ** Publication 3260
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
SUGGESTED SPECIFICATION for Service Entrance Automatic Transfer Switches
PART 1 GENERAL 1.01 Scope SUGGESTED SPECIFICATION for Service Entrance Automatic Transfer Switches Division 16 - Electrical Standby Power Generator Systems A. Furnish and install service entrance automatic
Specification Guide. for RVAC. Direct Replacement. AC Medium Voltage. Circuit Breakers
Specification Guide for RVAC Direct Replacement AC Medium Voltage Circuit Breakers Table of Contents 1.0 General Work Scope...3 2.0 Standards...3 3.0 Supplier Qualifications...4 4.0 Circuit Breaker Element
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
GTEC transfer switch open transition
GTEC transfer switch open transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between a utility
MEDIUM VOLTAGE METAL CLAD SWITCHGEAR
MEDIUM VOLTAGE METAL CLAD SWITCHGEAR PART 1 - GENERAL 1.1 DESCRIPTION This section specifies the furnishing, installation, connection and testing of the medium voltage switchgear. 1.2 SWITCHGEAR FEATURES
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL
SECTION 26 09 13 - POWER MONITOR FOR ELECTRICAL, STEAM CONDENSATE, AND WATER PART I - GENERAL 1.1 SUMMARY A. This section describes the requirements for the installation of Power Monitors and associated
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS. Presented by SAI Advanced Power Solutions
SWITCHGEAR SOLUTIONS FOR MISSION CRITICAL APPLICATIONS POWER DISTRIBUTION RACKS IN A MISSION CRITICAL SYSTEM MODULES IN A MISSION CRITICAL SYSTEM UPS Convertor Main Inverter Load Battery BPC UPS & BATTERY
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
How To Operate A Gec Transfer Switch Open Transition 40 2000 Amp Power Supply
GTEC Transfer switch open transition 40 2000 amp Description GTEC transfer switches combine reliability and flexibility in a small, economical package for transferring loads between a utility and a generator
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Switchboards. Basis of Design. Design Evaluation
Basis of Design This section applies to the design relating to low voltage switchboards. Design Criteria UW Class N1 facilities main switchboards shall be rear accessible. The main, tie and feeder breakers
Sample - No Commercial Use
COMPLETE REVISION October 2010 Electrical PIP ELSSG01 Design and Fabrication of Low-Voltage Metal-Enclosed AC Power Circuit Breaker Switchgear PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort
ATC-300 Automatic Transfer Switch Controller
ATC-300 Technical Data New Information Technical Data Page 2 Effective: May 2004 ATC-300 Introduction The Cutler-Hammer ATC-300 from Eaton s Electrical business is a comprehensive, multi-function, microprocessor-based
ASCO SERIES 185 Power Transfer Switches
ASCO SERIES 185 Power Transfer Switches 4-hour protection no matter when trouble strikes ASCO Series 185 Power Transfer Switches An Automatic Transfer Switch helps prevent... Your business or home from
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
Primary and Secondary Electrical Distribution Systems
Primary and Secondary Electrical Distribution Systems Critical Facilities Round Table 12th Quarterly Membership Meeting June 2, 2006 David D. Roybal. P.E. Eaton Electrical Cutler-Hammer Products Utility
Masterclad Medium Voltage Passive Arc-Resistant Switchgear
Masterclad Medium Voltage Passive Arc-Resistant Switchgear Square D Masterclad medium voltage passive arc-resistant (AR) switchgear is designed with utilities and industrial customers in mind who demand
HVL 5 38 kv Load Interrupter Switchgear. The Standard for Performance, Protection and Dependability
HVL 5 38 kv Load Interrupter Switchgear The Standard for Performance, Protection and Dependability For a generation of engineers, Square D High Voltage Load (HVL ) Interrupter Switchgear by Schneider Electric
AMFA-27 AMFA-29. Operator s Manual & Installation Instructions. Rev. 2.5
AMFA-27 AMFA-29 Operator s Manual & Installation Instructions Rev. 2.5 Date: 17 July, 2010 Permanently-connected, utility Interactive, single-phase, inverters Model AMFA-27 WIND TURBINE INVERTER (240 VAC
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS
SECTION 26 09 26 LOW VOLTAGE LIGHTING CONTROLS PART 1 - GENERAL 1.01 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements", and Section
38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.
38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC
Continuous Power... Continuous Protection
Series 165 We Keep Your Power On Continuous Power... Continuous Protection An Automatic Transfer Switch helps prevent... Your business or home from losing power during bad weather or utility power equipment
PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors
PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2
Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable
Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window
AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A
AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components
UNIVERSITY OF WASHINGTON Facilities Services Design Guide. Electrical. Metering and Monitoring. Basis of Design
Basis of Design This section applies to the design, installation and integration of metering and monitoring equipment, including: hardware installed in the electrical service and distribution equipment,
The following components are common to most cubicles; this example is an ABB HK cubicle.
4.0 CIRCUIT BREAKER CUBICLE Learning Objectives The circuit breaker cubicle is the component of the switchgear that holds the circuit breaker, and the controls and cabling for the distribution system.
Transfer Equipment Controls
Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical
AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle
Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
SWITCHGEAR Section 16. SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less.
PART 1 - GENERAL SECTION INCLUDES This Section includes service and distribution switchboards rated 600 V and less. RELATED SECTIONS Division 16 Section "Basic Electrical Materials and Methods" for general
Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500
Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage
Bulletin 150 SMC Flex Smart Motor Controller Specifications
Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering
Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800
Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
Power Meter Series 700
PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required
This section applies to the design and installation of transformers.
ELECTRICAL: TRANSFORMERS BASIS OF DESIGN This section applies to the design and installation of transformers. Design Criteria 13.8-kV equipment shall be 15-kV class. Coordinate with short-circuit studies
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components
Fundamentals of Modern Electrical Substations Part 1: Mission of Electrical Substations and their Main Components Course No: E02-010 Credit: 2 PDH Boris Shvartsberg, Ph.D., P.E., P.M.P. Continuing Education
SECTION 16346A METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR
METAL-CLAD MEDIUM VOLTAGE ARC RESISTANT SWITCHGEAR PART 1 GENERAL 1.01 SCOPE A. The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. 1.02 RELATED
FFI. Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars. Presented By: Greg Pelster & Robert Schmid
Advances in Medium and Low Voltage Power Distribution ESS Metron Expo and Technical Seminars Presented By: Greg Pelster & Robert Schmid FFI Ferrie, Franzmann Industries LOW VOLTAGE SWITCHGEAR & LOW VOLTAGE
INTRUSION DETECTION SYSTEM Section 281600
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply to this Section.
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms
Dead Tank Circuit Breaker 72PM40-C Proven reliability through common platforms ABB innovations for changing demands ABB (www.abb.com) is a leader in power and automation technologies that enables utility
Voltage Regulator SPAU 341 C. Product Guide
Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations
Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance
Owner s Manual For Automatic Transfer Switch 100-200 Amp, Service Entrance/Non-Service Entrance Model Numbers RTST100A3 RTSP100A3 RTST150A3 RTST200A3 RTSP200A3 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED:
MasterINTERFACE 39 Series - Relay interface modules
MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A
SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1
Page 1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification sections apply to
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL
ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142
INSTALLATION INSTRUCTIONS
LIGHTING CONTROL PANELS 4 AND 8 RELAYS INSTALLATION INSTRUCTIONS INSTALLATION OVERVIEW The installation instructions contained in this document are provided as a guide for proper and reliable installation.
Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1
How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module
MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation
MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability
Transfer switch BTPC open, closed or delayed transition
Transfer switch BTPC open, closed or delayed transition 150-4000 Amp Description The Cummins Power Generation BTPC series bypass isolation transfer switch combines an automatic transfer switch with a drawout
Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank
Recommended Product Specifications Fuel Day Tank System Tramont UTRS Fuel Day Tank This specification describes requirements for a Diesel Fuel Day Tank System consisting of one or more fuel tanks, an Electronic
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.8 U N /0.5 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N 0.2 U N /0.1 U N
55 Series - General purpose relays 7-10 A Features 55.12 55.13 55.14 Printed circuit mount, general purpose 2, 3 & 4 Pole relays 55.12-2 Pole 10 A 55.13-3 Pole 10 A 55.14-4 Pole 7 A AC coils & DC coils
Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services.
Spending too much to maintain aging switchgear? Circuit breaker solutions from Square D Services. Spending too much time and money on equipment maintenance? Square D Services: Your source for circuit breaker
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
NC-12 Modbus Application
NC-12 Modbus Application NC-12 1 Table of Contents 1 Table of Contents... 2 2 Glossary... 3 SCADA...3 3 NC-12 Modbus in general... 3 4 Entire system... 4 4.1 PFC to PC connection alternatives...4 4.1.1
Mobile Data Power Model: MDP-25
Mobile Data Power Model: MDP-25 Topic Section Features... 2 Operational Features Summary... 2 Back-up Battery Power Internal Charger Voltage Spike Protection RF Noise Filtering Warning of Imminent Loss
Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution
Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is
PowerCommand Paralleling System Digital MasterControl
PowerCommand Paralleling System Digital MasterControl Description The PowerCommand Digital MasterControl is a systemlevel controller designed to interface directly with Cummins Power Generation PowerCommand
Product Specification instalert Rapid Messenger Variable Message Sign
instalert 2 units to cover any application instalert 18 (ia18): 18 x 28 full matrix instalert 24: (ia24): 24 x 60 full matrix Size, Weight without battery ia18: 30 x 20 x 2.74, 29 lbs ia24: Folds to fits
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET
BERTHOLD ELECTRIC GENERATOR CONNECTION CABINET Berthold Electric Company s Generator Connection Cabinet provides a quick and convenient station to connect a portable generator to a facility s main service
MasterINTERFACE 39 Series - Relay interface modules
MasterINTERFACE 39 Series - 39 Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy ejection by plastic
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B
SURGE PROTECTIVE DEVICES (SPDs) EXTERNAL SIDEMOUNT UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
Eaton s E-Series protective relay family
E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family
Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930
Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930 Description Firetrol FTA1930 Digital Solid State Starting Fire Pump Controllers feature soft start, soft stop and
01.4IB.51200B PowlVac-AR Arc Resistant Switchgear. 5kV & 15kV 1200A, 2000A, 3000A, & 4000A Forced Cooled. Powered by Safety
PowlVac-AR Arc Resistant Switchgear 1200A, 2000A, 3000A, & 4000A Forced Cooled Powered by Safety PowlVac-AR Arc Resistant Switchgear 01.4IB.51200B Contact Information Powell Electrical Systems, Inc. www.powellind.com
48 SERIES Relay interface modules 10 A
48 Relay interface modules 10 A 1 CO relay interface modules, mm wide Ideal interface for PLC and electronic systems Type 48.P3 1 CO 10 A s Type 48.31 1 CO 10 A s AC coils or DC sensitive coils Supply
Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in
Inductive Sensors Single or Dual Loop Detectors Type LD with teach-in Single or Dual loop detector Automatically adjustment of detection level Manual sensitivity for compensations of variations Easy installation
Low Voltage Transformers Sealed, General Purpose, Dry Type
Low Voltage Transformers Sealed, General Purpose, Dry Type Catalog 7400CT9601R4/08 08 Class 7400 CONTENTS Description..............................................Page Introduction.................................................
80 Series - Modular timers 16 A. Features 80.01 80.11
80 Series - Modular timers 16 A Features 80.11 Multi-function and mono-function timer range - Multi-function & multi-voltage 80.11 - On-delay, multi-voltage 17.5 mm wide Six time scales from 0.1s to 24h
ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories
2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used
How To Build A Germany Power Plant
Medium Voltage Air Insulated Motor Control Featuring AdvanceTM Technology. Medium Voltage Motor Control Center Product Description Contemporary Design Advance TM medium voltage motor control center (MVMCC)
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
Digital input modules
8 172 TX-I/O Digital input modules TXM1.8D TXM1.16D Two fully compatible versions: TXM1.8D: 8 inputs, each with a three-color LED (green, yellow or red) TXM1.16D: As TXM1.8X, but 16 inputs, each with a
SECTION 26 1316 MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR
SECTION 26 1316 MEDIUM-VOLTAGE FUSIBLE INTERRUPTER SWITCHGEAR PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and
RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
Arc Terminator Active Arc-Resistant Switchgear
Arc Terminator Active Arc-Resistant Switchgear Increasing safety and productivity by extinguishing internal arcing faults within the switchgear. The Square D Arc Terminator from Schneider Electric offers
SECTION 16341 MEDIUM VOLTAGE SWITCHGEAR
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes metal-enclosed
FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10
TECHNICAL SPECIFICATIONS Page 1 of 10 FIRE DETECTION AND ALARM SYSTEM Scope Furnish a complete 24V DC conventional, electrically supervised, zone annunciated, fire detection and alarm system as specified
FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE
FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP1100J FTA1100J Diesel Engine Fire Pump Controllers Product Description Description Firetrol combined automatic and manual Mark
ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
Master Time Clock MTC-200 MTC-400 MTC-600. Users Manual
Master Time Clock MTC-200 MTC-400 MTC-600 Users Manual Toll Free (888)713-0373 Phone (972)987-4408 FAX (877)720-9291 www.midwest-time.com [email protected] TABLE OF CONTENTS TOPIC PAGE GENERAL DESCRIPTION
Medium Voltage Motor Control Assemblies
Medium Voltage Motor Control Assemblies Arc Resistant AMPGARD.1 Product............................................. 2 Application........................................... 2 Features, Benefits and Functions...................................
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
Capacitor Protection Relay SPAJ 160 C. Product Guide
Issued: April 1999 Status: Updated Version: C/19.04.2006 Data subject to change without notice Features One-, two- and three-phase overload stage with definite time characteristic One-, two- and three-phase
48.12. 2 pole, 8 A Safety relay. Screw terminal. 35 mm rail (EN 60715) mounting. 2 CO (DPDT) 8/15 250/400 2,000 500 0.37 8/0.65/0.
48 Series - Relay interface modules 8 A Features 48.12 2 Pole Safety relay interface modules, 15.8 mm wide 48.12-2 Pole 8 A (screw terminal) DC sensitive coils Relay with forcibly guided contacts according
Applications. Remote Display Mounting Kits
June 200 Sheet 105 Surge Protection Products TVSS General Description Clipper Power System Visor Series.1-5 Clipper Power System Visor Series General Description Eaton s Cutler-Hammer leading-edge surge
