MPAC 1500 Controller
|
|
|
- Adelia Terry
- 9 years ago
- Views:
Transcription
1 Model KSS/KSP Specific-Breaker Rated ATS Ratings Voltage: Current: VAC 50/60 Hz Amps (standard transition) Amps (programmed transition) Transfer Switch Standard Features UL 1008 listed at VAC file # E58962 (automatic), # E86894 (nonautomatic) CSA certification available Available with either automatic or non-automatic control Available in 2, 3, or 4 pole configurations High withstand/closing ratings, for use with specific breakers only Electrically operated, mechanically held mechanism Double-throw, mechanically interlocked design (break-before-make power contacts) Enclosed arc chambers with arc chutes Standard-transition model KSS and programmed-transition KSP model available Silver tungsten alloy contacts on amp models (Model KSS) Silver alloy main contacts (Model KSP) Front-accessible contacts for easy inspection Programmed-transition operation provides a center OFF position that allows residual voltages in the load circuits to decay (Model KSP) Main shaft auxiliary position-indicating contacts, one set Normal and one set Emergency MPAC 1500 Controller Standard Features Microprocessor-based controller Environmentally sealed user interface LCD display, 4 lines x 20 characters, backlit Dynamic function keypad with tactile feedback pushbuttons allows complete programming and viewing capability at the door LED indicators: Source available, transfer switch position, service required (fault), and not in auto Broadrange voltage sensing ( VAC) on all phases Phase-to-phase sensing and monitoring with 0.5% accuracy on both sources Frequency sensing with 0.5% accuracy on both sources Anti-single phasing protection Phase rotation sensing for three-phase systems Real-time clock with automatic adjust for daylight saving time and leap year Time-stamped event log Fail-safe transfer for loaded test and exercise functions DIP switches: password disable and maintenance Modbus RTU and Modbus TCP/IP protocols (Modbus register map available) RJ45 connector for 10/100 ethernet connection USB port with read/write compatibility Isolated RS-485 ports One-year limited warranty Programmable Features Programming and monitoring methods: Monitoring and password-protected programming at the door using the keypad and display Program and monitor using a PC with Monitor III integrated generator set and ATS monitoring software Transfer files through the USB port System voltage and frequency Voltage unbalance Over/undervoltage and over/underfrequency for all phases of the normal and emergency sources Adjustable time delays Load/no load/auto-load test and load/no-load exercise functions Programmable inputs and outputs Time-based and current-based* load control Load bank control for exercise or test Pre/post-transfer, nine individual time delays for selected loads ABC/BAC/none phase rotation selection with error detection Resettable historical data In-phase monitor Password protection, three security levels * Requires current sensing kit. G (Model KSS/KSP Transfer Switch) 3/12j Page 1
2 MPAC 1500 Controller Features User Interface LED Indicators Contactor position: source N and source E Source available: source N and source E Service required (fault indication) Not in automatic mode LCD Display System status Line-to-line voltage Line-to-neutral voltage Active time delays Source frequency Preferred source selection System settings Common alarms Load current, each phase Inputs and outputs Faults Time/date Address Event history Maintenance records Exerciser schedule Exerciser mode Time remaining on active exercise Dynamic Function Tactile Keypad Operations Scroll up/down/forward/back Increase/decrease/save settings End time delay Start/end test or exercise Reset fault Lamp test DIP Switches Maintenance mode Password disable Event History View up to 99 time and date-stamped events on the display or on a personal computer equipped with optional Monitor III software. Download up to 2000 events with Monitor III software or download complete event history file to a PC or a memory device connected to the USB port. Main Logic Board Inputs and Outputs Two (2) programmable inputs Two (2) programmable outputs, isolated form C (SPDT) contacts rated 1 30 VDC, 500 VAC Main Board I/O Specifications Output contact type Isolated form C (SPDT) Output contact rating 1 30 VDC, 500 VAC I/O terminals wire size range # AWG Communications USB port with read/write capability Isolated RS-485 ports RJ-45 connector for 10/100 ethernet connection Modbus RTU and Modbus TCP/IP protocols (Modbus register map available) USB Port. Upload or download files from a PC or a memory device through the USB port. Application software Event history files Language files Parameter settings Usage reports Feature configuration USB Data Logger Time-stamped voltage and frequency readings Minimum and maximum current and voltage readings for a selected time period Programmable Features System voltage, VAC * System frequency, 50/60 Hz * Single/three-phase operation * Standard/programmed-transition operation * Preferred source selection Phase rotation: ABC/BAC/none selection with error detection Voltage and frequency pickup and dropout settings Voltage unbalance, enable/disable In-phase monitor: enable/disable and phase angle Transfer commit/no commit Source/source mode: utility/gen, gen/gen, utility/utility, or utility/gen/gen for 3-source systems Passwords, system and test Time, date, automatic daylight saving time enable/disable Time delays (see table) Exerciser: calendar mode, loaded/unloaded up to 21 events Test: loaded/unloaded/auto load (1--60 minutes) Remote test: loaded/unloaded Automatic override on generator failure (loaded test and exercise) Peak shave delay enable/disable Current monitoring Pre/post-transfer, 9 individual time delays for selected loads Current-based load control settings: high/low current levels and load add/remove priority for 9 separate loads Prime power sequence alternates between two generator sets Resettable historical data * System parameters factory-set per order Requires optional current sensing kit. Modbus is a registered trademark of Schneider Electric. G (Model KSS/KSP Transfer Switch) 3/12j Page 2
3 MPAC 1500 Controller Features, continued Programmable Inputs External time delay input External battery fault External common fault Inhibit transfer Load shed to force transfer to OFF (programmed- transition models only; requires optional load shed kit) Peak shave/area protection input External test Three-source system disable Programmable Outputs Chicago alarm control Common alarm events Contactor position Exercise active Failure to acquire standby source Failure to transfer Generator engine start, source N and E I/O module faults Load bank control Load control active (pre/post transfer delay, up to 9 outputs) Loss of phase fault, source N and E External battery fault Non-emergency transfer Not in automatic mode Over/underfrequency faults, source N and E (generator) Over/undervoltage faults, source N and E Peak shave/area protection active Phase rotation error, source N and E Preferred source supplying load Software-controlled relay outputs (four maximum) Source available, preferred and standby Standby source supplying load Synchronizing output Test active Transfer switch auxiliary contact fault Transfer switch auxiliary contact open Voltage unbalance Parameter Voltage and Frequency Sensing Default Adjustment Range Undervoltage dropout 90% of pickup 75%--98% Undervoltage pickup 90% of nominal 85%--100% Overvoltage dropout * 115% of nominal* 106%--135% Overvoltage pickup 95% of dropout 95%--100% Unbalance enable Disable Enable/Disable Unbalance dropout 20% 5%--20% Unbalance pickup 10% 3%--18% Voltage dropout time 0.5 sec sec. Underfrequency dropout 99% of pickup 95%--99% Underfrequency pickup 90% of nominal 80%--95% Overfrequency dropout 101% of pickup 101%--115% Overfrequency pickup 110% of nominal 105%--120% Frequency dropout time 3 sec sec. * 690 volts, maximum. Default = 110% for 600 volt applications. Adjustable Time Delays Time Delay Default Adjustment Range Engine start, Source S2 Engine start, Source S1 (gen/gen) Engine cooldown, Source S2 Engine cooldown, S1 (gen/gen) Fail to acquire standby source Fail to acquire preferred source Transfer, preferred to standby Transfer, standby to preferred Transfer, off to standby Transfer, off to preferred 3 sec. 3 sec. 5 sec. 2 sec. 1 min. 1 min. 3 sec. 15 min. 1 sec. 1 sec sec min. 1sec.--60min. Fail to synchronize 60 sec. 10 sec min. Auto load test duration Prime power run duration 30 min. 6 min min. (1 min. increments) 6 min days (6 min. increments) Load Control Time Delays: Pretransfer to preferred Post-transfer to preferred Pretransfer to standby Post-transfer to standby Load add Source1/Source2 Load remove Source1/Source2 0 sec. 0 sec. 0 sec. 0 sec. 0 sec. 0 sec min. Note: Time delays are adjustable in 1 second increments, except as noted. Engine starttime delay can be extended to 60 minutes with an External Battery Supply Module Kit. G (Model KSS/KSP Transfer Switch) 3/12j Page 3
4 Model KSS KSP Application Data UL-Listed Solderless Screw-Type Terminals for External Power Connections Normal, Emergency, and Load Terminals Switch Rating, Cables per Pole Range of Wire Sizes, Copper or Aluminum* #8 to 3/0 AWG #6 AWG to 250 MCM #6 AWG to 350 MCM #4 AWG to 600 MCM 2 #1/0 AWG to 250 MCM #2 AWG to 600 MCM #1/0 AWG to 750 MCM #2 AWG to 600 MCM #14 to 1/0 AWG #6 AWG to 250 MCM /0 AWG to 250 MCM 1 #4 AWG to 600 MCM #2 AWG to 600 MCM * Use 60 C minimum wire for #14 to #1 AWG. Use 75 C minimum wire for 1/0 AWG and larger. Operating Temperature Storage Temperature Humidity Component Environmental Specifications C to 70 C (--4 F to 158 F) C to 85 C (--40 F to 185 F) 5% to 95% noncondensing Input and Output Connection Specifications Main board I/O terminals I/O module terminals Wire Size Range # AWG # AWG Codes and Standards The ATS meets or exceeds the requirements of the following specifications: Underwriters Laboratories UL 508, Standard for Industrial Control Equipment Underwriters Laboratories UL 1008, Standard for Automatic Transfer Switches for Use in Emergency Standby Systems file # E58962 (automatic), # E86894 (nonautomatic) CSA C22.2 No. 178 certification available, file #LR58301 NFPA 70, National Electrical Code NFPA 99, Essential Electrical Systems for Health Care Facilities NFPA 110, Emergency and Standby Power Systems IEEE Standard 446, IEEE Recommended Practice for Emergency and Standby Power Systems for Commercial and Industrial Applications NEMA Standard ICS , Electromechanical AC Transfer Switch Equipment EN Fast Transient Immunity Severity Level 4 IEC , Low Voltage Switchgear and Control Gear; Multifunction Equipment; Automatic Transfer Switching Equipment EN Surge Immunity Class 4 (voltage sensing and programmable inputs only) IEC Specifications for EMI/EMC Immunity: CISPR 11, Radiated Emissions IEC , Electrostatic Discharge IEC , Radiated Electromagnetic Fields IEC , Electrical Fast Transients (Bursts) IEC , Surge Voltage IEC , Conducted RF Disturbances IEC , Magnetic Fields IEC , Voltage Dips and Interruptions IEEE 472 (ANSI C37.90A) Ring Wave Test Contact Ratings Motor Load Resistive Load Inductive Load NC NO Engine Start Contacts 2A@30VDC N/A N/A N/A Auxiliary Contacts, KSS ( A) VAC N/A N/A N/A Auxiliary Contacts, KSS ( A) VAC VAC; VAC Auxiliary Contacts, KSP VAC VAC; VAC VAC; VAC; VAC VAC; VAC; VAC VAC; VAC; VAC VAC; VAC; VAC G (Model KSS/KSP Transfer Switch) 3/12j Page 4
5 Weights and Dimensions Weights and dimensions are shown for transfer switches in NEMA type 1 and type 3R enclosures, and open units. Consult the factory for open units and other enclosures. Note: Weights and dimensions are provided for reference only and should not be used for planning installation. See your local distributor for submittal drawings. Standard-Transition Models Dimensions mm (in.) Weight kg (lb.) Amps NEMA Type Height Width Depth * 2-Pole 3-Pole 4-Pole , 3R 791 (31.1) 450 (17.7) 316 (12.5) 28 (62) 30 (65) 31 (68) , 3R 1223 (48.1) 560 (22.0) 362 (14.3) 52 (115) 56 (123) 59 (131) 600 1, 3R 1702 (67.0) 610 (24.0) 514 (20.2) 179 (395) 183 (403) 186 ( 410) 800 1, 3R 1932 (76.1) 864 (34.0) 515 (20.3) N/A 226 (498) 236 (520) , 3R 1932 (76.1) 864 (34.0) 515 (20.3) N/A 231 (509) 241 ( 531) * Allow enough room to fully open the door for inspection and service per NEC and local codes. The NEMA type 3R enclosures have a security cover on the controller that extends 54 mm (2.1 in.) beyond the door. Programmed-Transition Models Dimensions mm (in.) Weight kg (lb.) Amps NEMA Type Height Width Depth * 2-Pole 3-Pole 4-Pole , 3R 1223 (48.1) 560 (22.0) 362 (14.3) 52 (115) 56 (123) 59 (131) 400 1, 3R 1223 (48.1) 560 (22.0) 362 (14.3) 52 (115) 56 (123) 59 (131) 600 1, 3R 1702 (67.0) 610 (24.0) 514 (20.2) 179 (395) 183 (403) 186 ( 410) * Allow enough room to fully open the door for inspection and service per NEC and local codes. The NEMA type 3R enclosures have a security cover on the controller that extends 54 mm (2.1 in.) beyond the door. G (Model KSS/KSP Transfer Switch) 3/12j Page 5
6 Withstand and Close-On Ratings (WCR), Standard-Transition Models Ratings Summary The transfer switch is rated for use on a circuit capable of delivering not more than the RMS symmetrical amperes listed at the specified maximum voltage below, but no greater than the interrupting capacity of the selected circuit breaker or fuse. Circuit breakers and fuses are supplied by the customer. Switch Rating, Amps Certified Withstand Current Ratings in RMS Symmetrical Amperes (480 V maximum) * Maximum Fuse Size, Amps With Current-Limiting Fuses Fuse Class Maximum Circuit Amps at 480 VAC Specific Coordinated Breaker Rating, (see the following tables) Maximum Voltage Maximum Circuit Amps at 480 VAC Short-Time Withstand Ratings Maximum Voltage Maximum Circuit Amps at 480VAC Short Time Duration, Cycles J 200, V/60 Hz 30, V/60Hz 10, N/A N/A N/A 480 V/60 Hz 35, J 200,000 RK5, RK1 100, V/60 Hz 50, V/60 Hz 35, N/A N/A N/A L 200, V/60 Hz 65,000 N/A N/A N/A * All values are available symmetrical RMS amperes and tested in accordance with the withstand/closing requirements of UL G (Model KSS/KSP Transfer Switch) 3/12j Page 6
7 Ratings with Specific Manufacturers Circuit Breakers, Standard-Transition Models Withstand and close-on ratings (WCR) in RMS symmetrical amperes for specific manufacturers circuit breakers. Switch Rating, WCR, RMS 30, , Voltage, Max. Manufacturer Type Cutler-Hammer Square D ITE/Siemens GE Cutler-Hammer Square D ITE/Siemens GE Molded-Case Circuit Breakers Max. Size, FDC, HFD 150 HJD, JDC 250 HKD, KD, KDB, KDC, LA TRI--PAC, LCL 400 FC, FI 100 KC, KH, KI 250 LA, LC, LE, LH, LI, LX, LXI 400 CED6, HED4, HED6 125 CFD6, FD6, FXD6, HFD6 250 CJD6, HJD6, HHJD6, HHJXD6, JD6, JXD6, SCJD6, SHJD6, SJD6 400 TB1 100 SEL, SEP, TEL, THLC1 150 TFL, THLC2 225 SFL, SFP 250 SGL4, SGP4, TB4, THJK4, THLC4, TJJ, TJK4, TLB4 400 FDC, HFD 150 HJD, JDC 250 HKD, KD, KDB, KDC, LA TRI--PAC, LCL 400 FC, FI 100 KC, KH, KI 250 LA, LC, LE, LH, LI, LX, LXI 400 CED6, HED4, HED6 125 CFD6, FD6, FXD6, HFD6 250 CJD6, HJD6, HHJD6, HHJXD6, JD6, JXD6, SCJD6, SHJD6, SJD6 400 TB1 100 SEL, SEP, TEL, THLC1 150 TFL, THLC2 225 SFL, SFP 250 SGL4, SGP4, TB4, THJK4, THLC4, TJJ, TJK4, TLB4 400 G (Model KSS/KSP Transfer Switch) 3/12j Page 7
8 Ratings with Specific Manufacturers Circuit Breakers, Standard-Transition, continued Switch Rating, WCR, RMS Molded-Case Circuit Breakers Voltage, Max. Manufacturer Type Max. Size, HJD, JDC 250 Cutler-Hammer HKD, CHKD, KDC, LCL, LA TRIPAC 400 HLD, CHLD, LDC, CLDC NB TRI--PAC KI, KC 250 Square D LI, LXI, LX, LE, LC 600 MX, ME, MH 800 CFD6, HFD6 250 CJD6, SCJD6, HHJD6, HHJXD6, SHJD6, HJD6 400 ITE/Siemens , CLD6, SCLD6, HHLD6, HHLXD6, SHLD6, HLD6 600 CMD6, SCMD6, HMD6, SHMD6, HMXD6, MD6, MXD6, SMD6 800 SFL, SFP, TFL, THLC2 250 GE SGL4, SGP4, TB4, THLC4, TLB4 400 SGL6, SGP6, TB6, TJL4V, TKL4V, TJL1S--6S 600 SKL8, SKP8, TB8, SKH8 800 CF250L, CF250H 250 Merlin Gerin CJ400L, CK400H, CJ400H, CK400N 400 CJ600H 600 CK800H, CK800N 800 ABB JHB 400 FDC, HFD 150 HJD, JDC 250 Cutler-Hammer CHKD, HKD, KDC, LA TRIPAC, LCL 400 HLD, CHLD, LDC, CLDC NB TRIPAC KI, KC 250 Square D LC, LE, LI, LX, LXI 400 LC, LE, LI, LX, LXI 600 ME, MH, MX 800 CFD6, HFD , CJD6, HJD6, HHJD6, HHJXD6, SCJD6, SHJD6 400 ITE/Siemens CLD6, HLD6, HHLD6, HHLXD6, SCLD6, SHLD6 600 CMD6, HMD6, HMXD6, MD6, MXD6, SCMD6, SHMD6, SMD6 800 SEL, SEP, THLC1 150 SFL, SFP, TFL, THLC2 250 GE SGL4, SGP4, TB4, THLC4, TJL, TLB4 400 SGL6, SGP6, TB6, TJL1S--6S, TJL4V, TKL4V 600 TB8, SKL8, SKP8, SKH8 800 CF250L, CF250H 250 Merlin Gerin CJ400L, CK400H, CJ400H, CK400N 400 CJ600H 600 CK800H, CK800N 800 Cutler-Hammer TRI-PAC NB, CHMDL, HMDL, CHND, HND, NDC, CNDC 800 TRI-PAC NB, CNDC, NDC, CRDC, TRI-PAC PB, RDC, CHND, HND 1200 MH, MH SERIES Square D MH SERIES , CMD6, HMD6, SCMD6, SHMD6, CND6, HND6, SCND6, SHND6, CPD ITE/Siemens CND6, HND6, SCND6, CPD6, SHND GE TB8, TC, THC, THP, TKL85, SKL8, SKP8, MICROVERSA TKL 12S, SKL12, SKP12 THC, THP, SKP12, TRP, MICROVERSA TKL, SKL G (Model KSS/KSP Transfer Switch) 3/12j Page 8
9 Withstand and Close-On Ratings (WCR), Programmed-Transition Models Suitable for emergency and standby applications on all classes of load, 30% tungsten rated on all amperages. The transfer switch is rated for use on a circuit capable of delivering not more than the RMS symmetrical amperes listed at 480 volts maximum, but no greater than the interrupting capacity of the selected circuit breaker. Circuit breakers are supplied by the customer. All WCR values are available symmetrical RMS amperes and tested in accordance with the withstand/closing requirements of UL Ratings with Specific Manufacturers Circuit Breakers, 480 Volts Switch Rating, Molded-Case Circuit Breakers WCR, RMS Voltage, Max. Manufacturer Type Max. Size, FCL, FB TRI-PAC 100 Cutler-Hammer FD, FDC, HFD 150 HJD, JD, JDB, JDC 250 HKD, KD, KDB, KDC, LA TRI--PAC, LCL, DK, CHKD 400 HLA 70, 100 Square D FC, FH, FI 100 KA, KC, KH, KI 250 LA, LC, LE, LH, LI, LX, LXI 400 CED6, ED6, HED4, HED6, ED4 125 ITE/Siemens CFD6, FD6, FXD6, HFD , CJD6, HJD6, HHJD6, HHJXD6, SCJD6, SHJD6, SJD6 400 TB1 100 SEL, SEP, TEL, THED, THLC1 150 GE TFL, THFK, THLC2 225 SFL, SFP, TFL 250 SGL4, SGP4, TB4, THJK4, THLC4, TJJ, TJK4, TLB4 400 CF250L, CF250H 250 Merlin Gerin CJ400L, CK400H, CJ400H, CK400N 400 CJ600H 600 CK800H, CK800N 800 ABB JHB 400 FCL, FB TRI-PAC 100 FD, FDC, HFD 150 Cutler-Hammer HJD, JD, JDB, JDC 250 HKD, KD, KDB, KDC, LA TRIPAC, LCL, DK, CHKD 400 HLD, CHLD, LDC, CLDC NB TRI--PAC FC, FH, FI 100 KA, KC, KH, KI 250 Square D LA, LC, LE, LH, LI, LX, LXI 400 LC, LE, LI, LXI, LX , MX, ME, MH 800 CED6, ED6, HED4, HED6, ED4 125 CFD6, HFD6, FD6, FXD6 250 ITE/Siemens CJD6, SCJD6, HHJD6, HHJXD6, SHJD6, HJD6, SJD6 400 CLD6, SCLD6, HHLD6, HHLXD6, SHLD6, HLD6 600 CMD6, SCMD6, HMD6, SHMD6, HMXD6, MD6, MXD6, SMD6 800 CF250L, CF250H 250 Merlin Gerin CJ400L, CK400H, CJ400H, CK400N 400 CJ600H 600 CK800H, CK800N 800 ABB JHB 400 S6 800 G (Model KSS/KSP Transfer Switch) 3/12j Page 9
10 Accessories Accessories are available either factory-installed or as loose kits, unless otherwise noted. Accessory Modules The mounting kit holds up to five optional modules. The maximum total current draw is 300 ma. If an External Battery Module is installed, there is no current restriction. Module Current Draw Specifications, ma Alarm Module 75 Standard I/O Module 75 High Power I/O Module 100 Standard Input/Output Module Inputs Available Inputs 2 Input Definition Current Connection Type Wire Size Max Distance Outputs Outputs Available 6 Contact Type Contact Voltage Rating Connection Type Wire Size Contact closure 5mAMax Terminal Strip # AWG 700 feet Form C (SPDT) 2A@30VDC VAC Terminal Strip # AWG High-Power Input/Output Module Inputs Available Inputs 2 Input Definition Current Connection Type Wire Size Max Distance Outputs Outputs Available 3 Contact Type Contact closure 5mAMax Terminal Strip # AWG 700 feet Form C (SPDT) VDC VAC Contact Voltage Rating VAC VAC Connection Type Terminal Strip Wire Size # AWG Environmental Specifications Temperature C to85 C (--40 F to 185 F) Humidity 35% to 85% noncondensing Alarm Module 90 db Audible alarm Any alarm function can be programmed to trigger the audible alarm Chicago alarm function Preferred source selection Supervised transfer control (supervised transfer control switch required) Connection for external alarm External Alarm Connection Specifications Wire Size # AWG Cu VAC Contact Voltage Rating VAC External Battery Supply Module Energizes the ATS controls using an external battery when no source power is available Allows extended engine start time delays Allows the use of any combination of accessory modules (no current draw restriction, maximum of five modules total) Connects to one or two batteries, 12 VDC or 24 VDC system Current draw, VDC, VDC Provides low external battery voltage indication to the transfer switch controller Reverse-polarity protected CSA Certification Current Sensing Kit Other Accessories Monitor current on all phases with 1% accuracy Digital Meter Measure and display for both sources: Voltage Current Frequency Power Programmable visual alarms: High voltage Low voltage High current Serial port for optional network connections Password-protected programming menus Available factory-installed See TT-1506, Digital Power Meters G (Model KSS/KSP Transfer Switch) 3/12j Page 10
11 Accessories, continued Extended Warranties 2-year basic 5-year basic 5-year comprehensive 10-year major components Export Packaging Heater, Anti-Condensation Humidistat-controlled 120 VAC strip heater (customer-supplied voltage source required) 125 or 250 watts (sized for enclosure) Protective 15 Amp circuit breaker Line-to-Neutral Voltage Monitoring Monitors all line-to-neutral voltages Literature Kits Production literature kit (one kit is included with each transfer switch) Overhaul literature kit Load Shed Kit Forced transfer from Emergency to OFF Available for Amp programmed-transition models (KSP) only External hardware is required for the forced transfer to OFF function Factory-installed Logic Disconnect Switch Disconnects power to controller without disconnecting load Mounts inside the enclosure Monitor III Software Monitor and control the power system s generator sets and transfer switches from a personal computer using a single software package Monitor and control systems through a Windows -based graphical user interface Monitor and control systems over a local area network, remotely via a modem connection, or through an Ethernet connection Password-protected data access: Guest, User, and Supervisor levels Ethernet capability Start or stop a test from a remote PC View and adjust trip points, time delays, and system parameters Assign inputs and outputs Available as loose kits: Software kit with serial cable Software kit with device modem and cables Neutral Assembly Available as loose kit for open units Padlockable User Interface Cover With or without window Cover without window standard on NEMA 3R enclosures Remote Annunciator for ATS Allows remote monitoring and limited control of up to four transfer switches connected in an RS-485 network Includes surface and flush mounting provisions Supervised Transfer Control Switch Auto, Manual, and Transfer positions Automatic and non-automatic modes Alarm module required Surge Protection Device (SPD) SPD available for the normal source supply Surge protection reduces transient voltages to harmless levels Replaceable without disconnecting power High-performance EMI/RFI filtering: --75dB maximum 100 khz to 100 MHz Protection modes: L-L, L-N, L-G, N-G Thermal and short circuit fusing LED status indicators Remote contacts for customer-supplied status indicators Form C (NO, NC, C) 60 W DC, 120 VAC, 3A max. Audible alarm, 90 db Listed to UL 1449, Edition 3 See additional specifications below SPD Specifications Limiting Voltage, Surge VAC Current Working (I max ), UL SVR, at at Voltage Ph. ka VAC 3kAmps 10kAmp 120/240 Split / / / / / / / / G (Model KSS/KSP Transfer Switch) 3/12j Page 11
12 KOHLER CO., Kohler, Wisconsin USA Phone , Fax For the nearest sales and service outlet in the US and Canada, phone KohlerPower.com Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore Phone (65) , Fax (65) Model Designation Model Mechanism Transition Controls Voltage Poles Enclosure Current Rating Miscellaneous Record the transfer switch model designation in the boxes. The transfer switch model designation defines characteristics and ratings as explained below. Sample Model Designation: KSP-DCTA-0100S Model K: Kohler Transfer Switch Mechanism S: Specific-Breaker Rated Transition S: Standard P: Programmed Controls D: MPAC 1500 Microprocessor Controls, Automatic F: MPAC 1500 Microprocessor Controls, Non-Automatic Voltage/Frequency C: 208 Volts/60 Hz D: 220 Volts/50 Hz F: 240 Volts/60 Hz G: 380 Volts/50 Hz H: 400 Volts/50 Hz J: 416 Volts/50 Hz K: 440 Volts/60 Hz M: 480 Volts/60 Hz P: 380 Volts/60 Hz R: 220 Volts/60 Hz Number of Poles/Wires N: 2-pole, 3-wire, solid neutral T: 3-pole, 4-wire, solid neutral V: 4-pole, 4-wire, switched neutral Enclosure A: NEMA 1 B: NEMA 12 C: NEMA 3R NEMA 1 enclosure is standard. available to order. Miscellaneous S: Standard Connections D: NEMA 4 F: NEMA 4X G: Open unit Other types are Current Rating: Numbers indicate the current rating of the switch in amperes: Standard--transition models only DISTRIBUTED BY: Availability is subject to change without notice. Kohler Co. reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Kohler Power Systems distributor for availability. 2005, 2006, 2007, 2008, 2009, 2010, 2011, 2012 by Kohler Co. All rights reserved. G (Model KSS/KSP Transfer Switch) 3/12j Page 12
Automatic Transfer Switch Controller
Automatic Transfer Switch Controller Decision-Makerr MPAC 1500 Model KBS with Decision-Makerr MPAC 1500 Controller Applicable Models Model Description KCS Standard-Transition Any Breaker ATS ] KCP Programmed-Transition
Controller Features. Modbus link to define inputs and outputs. Programmable Outputs Auxiliary switch fault Common fault.
Model KCT Automatic Transfer Switches Ratings Voltage: 208--600 VAC 50/60 Hz Current: 30--3000 amps Standard Contactor Features Open-transition operation with either automatic or non-automatic control
Model KSS. Transfer Switch Standard Features. Available Controllers. Ratings. Automatic Transfer Switches Standard Specific-Breaker Rated
Model KSS Automatic Transfer Switches Standard Specific-Breaker Rated Available Controllers D Decision-Makerr MPAC 750 D Decision-Makerr MPAC 1200 Transfer Switch Standard Features D UL 1008 listed at
Model KGS/KGP. Automatic Transfer Switches Bypass/Isolation. Transfer Switch Standard Features. Controller. Standard Transition Models (KGS) Ratings
Model KGS/KGP Automatic Transfer es Bypass/Isolation Controller D Decision-Makerr MPAC 1500 Ratings Model Current Voltage, Frequency Transfer Standard Features D UL 1008 listed at 480 VAC, file #E108981
RXT. Model: Model RXT Automatic Transfer Switch
Model: RXT Automatic Transfer Switch -- Model RXT Automatic Transfer Switch The Model RXT automatic transfer switch is designed for use only with Kohlerr generator sets equipped with RDC2 or DC2 generator
Model: RDT. Automatic Transfer Switch 100-400 Amps. 200 amp load center models use up to 24 circuit breakers
Model: RDT Automatic Transfer Switch 100-400 Amps MPAC 500 Controller Features User-friendly interface with easy-to-read international symbols Source available and contactor position indicators LED indication
Model: RXT. Model RXT Automatic Transfer Switch. Standard Features. Standard Interface Board. Available Models
Model: RXT Automatic Transfer Switch 100 - Amps Covers have been removed for illustration. Available Models D 100,, and amp standard and service entrance models are available. D 150 and 300 amp service
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
GTEC transfer switch open transition
GTEC transfer switch open transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between a utility
ATC-300 Automatic Transfer Switch Controller
ATC-300 Technical Data New Information Technical Data Page 2 Effective: May 2004 ATC-300 Introduction The Cutler-Hammer ATC-300 from Eaton s Electrical business is a comprehensive, multi-function, microprocessor-based
POWER SYSTEM ACCESSORIES
POWER SYSTEM ACCESSORIES Monitor III Software Applicable Controllers Software for Monitoring and Control of: Decision-Maker 550 generator set controller Decision-Maker 340 generator set controller Decision-Maker
How To Operate A Gec Transfer Switch Open Transition 40 2000 Amp Power Supply
GTEC Transfer switch open transition 40 2000 amp Description GTEC transfer switches combine reliability and flexibility in a small, economical package for transferring loads between a utility and a generator
Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500
Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage
Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800
Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement
ATC-900 Automatic Transfer Switch Controller
ATC-900 Automatic Transfer Switch Controller center industries. An intelligent control architecture allows the ATC-900 to address virtually any system requirements. Typical applications include utility-to-utility,
SUGGESTED SPECIFICATION for Service Entrance Automatic Transfer Switches
PART 1 GENERAL 1.01 Scope SUGGESTED SPECIFICATION for Service Entrance Automatic Transfer Switches Division 16 - Electrical Standby Power Generator Systems A. Furnish and install service entrance automatic
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140)
9-10N Supersedes Selection Data 9-10N, pages, 1-, dated dated March March 1995 1995 Mailed to: E, D, C/9-100A, 31-A, INTERRUPTING CAPACITY RATINGS IEC 947- Interrupting Capacity s➀ Interrupting Capacity
Applications. Remote Display Mounting Kits
June 200 Sheet 105 Surge Protection Products TVSS General Description Clipper Power System Visor Series.1-5 Clipper Power System Visor Series General Description Eaton s Cutler-Hammer leading-edge surge
ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories
2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used
ASCO SERIES 185 Power Transfer Switches
ASCO SERIES 185 Power Transfer Switches 4-hour protection no matter when trouble strikes ASCO Series 185 Power Transfer Switches An Automatic Transfer Switch helps prevent... Your business or home from
Transfer switch BTPC open, closed or delayed transition
Transfer switch BTPC open, closed or delayed transition 150-4000 Amp Description The Cummins Power Generation BTPC series bypass isolation transfer switch combines an automatic transfer switch with a drawout
Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable
Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window
Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930
Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930 Description Firetrol FTA1930 Digital Solid State Starting Fire Pump Controllers feature soft start, soft stop and
CTS SERIES AUTOMATIC TRANSFER SWITCH
CTS SERIES AUTOMATIC TRANSFER SWITCH The Cat CTS Series Automatic Transfer Switch (ATS) is configurable for applications requiring the dependability and ease of operation found in a full featured power
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC
FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE
FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP1100J FTA1100J Diesel Engine Fire Pump Controllers Product Description Description Firetrol combined automatic and manual Mark
CPS 100 480Y S K CPS 100 480Y S C
Ref. No. 1299 Visor Series Ordering Guidelines Table.1-4. Retrofit Surge Protection Products TVSS General Description Clipper Power System Visor Series CPS 100 480Y S K.1-9 Surge Ratings 100 = /phase 120
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE
WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE SBP1930-61 FTA1930 Digital Solid State Starting Electric Fire Pump Controllers Product Description Fire Pump Controllers for Business-Critical Continuity
Series TS 870 100-1200 Amp. Automatic Transfer Switches
Series TS 870 100-1200 Amp Automatic Transfer Switches A Regal Brand TS 870 AUTOMATIC TRANSFER SWITCHES THOMSON POWER SYSTEMS TS 870 AUTOMATIC TRANSFER SWITCHES OFFER THE FOLLOWING OUTSTANDING FEATURES:
Power Meter Series 700
PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required
Sentron Series Circuit Breakers
Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS, 3750 Watts / 5000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model Includes: CD with software,
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
TSC 800 TRANSFER SWITCH CONTROLLER INSTALLATION, OPERATING & SERVICE MANUAL
TSC 800 TRANSFER SWITCH CONTROLLER INSTALLATION, OPERATING & SERVICE MANUAL Software Version 2.2 PM049 REV 11 14/01/23 9087A 198 th Street, Langley, BC Canada V1M 3B1 Telephone (604) 888-0110 Telefax (604)
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
Remote Monitoring and REC 501 Control Unit Product Guide
Remote Monitoring and Control Unit REC 501 Product Guide Issued: May 1999 Status: Updated Version: B/06.11.2001 Data subject to change without notice Features Remote control and monitoring unit for the
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
Eaton s E-Series protective relay family
E-Series protective relays Feeder distribution relays Motor relays Transformer relays Generator relays Eaton s E-Series protective relay family Microprocessor-based design Eaton s E-Series relay family
Decision-Maker Paralleling System. Power Distribution Switchboards and Circuit Breakers. Standard Features
Decision-Maker Paralleling System Power Distribution Switchboards and Circuit Breakers Power Distribution Switchboards and Circuit Breakers The generator paralleling circuit breakers for the Kohler Decision-Maker
Limited Service Fire Pump Controllers Features
Must Be Installed Per Applicable Code and Manufacturers Recommendations Limited Service Fire Pump Controllers Features 1-1 FD20 Full Voltage - Limited Service with Plus Microprocessor Power I/O Board Transformers
Transfer Equipment Controls
Control Types Manual Transfer Switches Nonautomatic Transfer Switches Automatic Transfer Switches The type of control system for the transfer switch will vary depending on the type of switching equipment
ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
Bulletin 150 SMC Flex Smart Motor Controller Specifications
Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering
PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors
PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES
SECTION 26 29 23 VARIABLE FREQUENCY DRIVES PART 1 GENERAL 1.01 SCOPE A. Furnish and install individual freestanding variable frequency AC drives (VFD) as shown on the Drawings and specified herein. 1.02
SWITCH! DESCRIPTION. ENVIRONMENTAL SPECIFICATIONS Operating Temperature: 0 C to +40 C SPECIFICATION SHEET:
SWITCH The Budderfly lighting switch is a Decora style, plug-and-play replacement for your existing building switches. Installing a Budderfly adapter transforms your building s existing wiring into the
Uninterruptible Power Supply
96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical
PowerCommand Paralleling System Digital MasterControl
PowerCommand Paralleling System Digital MasterControl Description The PowerCommand Digital MasterControl is a systemlevel controller designed to interface directly with Cummins Power Generation PowerCommand
Communicate and view data from meters with one simple device
Communicate and view data from meters with one simple device PowerLogic EGX300 integrated gateway-server Web Monitoring Communications Plug and Play Plug into your energy usage with a simple mouse click
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A
SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
STRATO LED Drivers 70W, Single output
Features STRATO switch mode driver technology is designed to generate one constant current output from a wide range AC input. The size and performance of these products make them the ideal choice for LED
AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A
AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components
Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D
7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values
VARIABLE FREQUENCY DRIVES Revised 4/30/2015 23 81 07-1 Mechanical Systems
SECTION 23 81 07 - VARIABLE FREQUENCY DRIVES PART 1 - GENERAL 1.1 SUMMARY A. This section includes all variable frequency drives. All standard and optional features shall be included within the VFD panel
38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.
38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC
Voltage Regulator SPAU 341 C. Product Guide
Issued: July 1998 Status: Updated Version: D/25.04.2006 Data subject to change without notice Features Comprehensive voltage regulation for power transformers with on-load tapchangers in distribution substations
Electronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
RM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
Rack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial
SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial MODEL NUMBER: SMART2200RM2U Highlights 2.2kVA / 2200VA / 1920W line interactive 2U
Data Bulletin. Choosing a Trip Unit for PowerPact H-, J-, and L-Frame Circuit Breakers. Introduction. Thermal-Magnetic or Electronic Trip Unit?
Data Bulletin 011DB110 07/01 Choosing a Trip Unit for PowerPact H-, J-, and L-Frame Circuit Breakers ENGLISH Inoduction Thermal-Magnetic or Eleconic Trip Unit? Thermal-Magnetic Trip Units 01171 t 0119
Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
Low Voltage Products. Switches Automatic Transfer Switches
Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,
Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
Thermistor motor protection relays CM-MSS.22 and CM-MSS.23
Data sheet Thermistor motor protection relays CM-MSS.22 and CM-MSS.23 The thermistor motor protection relays CM-MSS.22 and CM-MSS.23 monitor the winding temperature of motors and protect them from overheating,
Telephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC EXTERNAL SIDEMOUNT SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671B SECTION 16671B
SURGE PROTECTIVE DEVICES (SPDs) EXTERNAL SIDEMOUNT UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective
Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers
Thermal-Magnetic / Magnetic Only Molded Case Circuit Breakers Catalog 2004 Class 601 CONTENTS Description..............................................Page INTRODUCTION.............................................
Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1
How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module
CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE. General purpose single phase thyristors and solid state relays Product data.
425 CONTROLS DATA MANAGEMENT PROCESS AUTOMATION EUROCUBE General purpose single phase thyristors and solid state relays Product data abc 425 EUROCUBE A complete range of low cost solid state relays and
MasterINTERFACE 39 Series - Relay interface modules
MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU5000RT4UHV Description Tripp Lite SU5000RT4UHV 5000VA / 5kVA /
How To Test A Power Switch On A Power Supply
transfer switches Soft load Innovative, reliable, integrated solution Built with years of experience Powered with innovation Delivered with reliability A history of experience, innovation and reliability
Disturbance Recoder SPCR 8C27. Product Guide
Issued: April 1999 Status: Updated Version: C/26.04.2006 Data subject to change without notice Features Versatile digital disturbance recorder module for recording various phenomena in the electric power
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fire pumps
CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING
PART 1-GENERAL 1.01 DESCRIPTION A. This specification is to cover a complete Variable Frequency motor Drive (VFD) consisting of a pulse width modulated (PWM) inverter designed for use on a standard NEMA
Electronic overload relay EF65, EF96 and EF146
Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.
Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
Waveguide Access Point WGA631. Product Guide
Waveguide Access Point Product Guide Waveguide Access Point Contents 1. Description............................ 3 2. Application............................ 3 3. Technical data... 4 4. Physical interfaces......................
Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1
Page 1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification sections apply to
Always On UPS Systems Inc., #100-150 Campion Road, Kelowna, BC Canada V1X 7S8
Door Mount UPS (Patent Pending) Shelf Mount UPS (Patent Pending) DESCRIPTION: The Always On NDM (door mount) and NSM (shelf mount) Series UPS s are dual conversion online UPS systems provided in slim,
RM17TE 183...528 V AC. Main. Product or component type. Product specific application. Relay monitored parameters 250 V DC 5 A DC
Characteristics multifunction control relay RM17-TE - range 183..528 V AC Complementary Reset time Maximum switching voltage Minimum switching current Maximum switching current [Us] rated supply voltage
AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL
ATS-220 AUTOMATIC TRANSFER SWITCH CONTROL UNIT OPERATOR S MANUAL For Use in 208 to 240 Volts Single and 3 Phase ATS Systems With 110Volt AC or DC Control Motors and selenoids 4501 NW 27 ave Miami FL 33142
3500/22M Transient Data Interface
3500/22M Transient Data Interface Bently Nevada* Asset Condition Monitoring Description The 3500 Transient Data Interface (TDI) is the interface between the 3500 monitoring system and GE s System 1* machinery
SM6 Series Circuit Breaker Monitors CONSOLIDATED. Electronics, Inc. MONITORING THE FUTURE
Series Circuit Breaker Monitors CONSOLIDATED Electronics, Inc. MONITORING THE FUTURE Why SF Gas Density Monitors? 6 Cut Maintenance Costs Your capital investment may be recovered with the elimination of
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
O & M Manual for the 50-400A EGSX Transfer Switch
Contents Description Page 1. Introduction...2 2. Receiving, Handling, and Storage... 5 3. Equipment Description... 6 4. Installation and Wiring... 6 5. Functional Testing... 18 6. Maintenance and Component
Gain energy insight and control with PowerLogic. PowerLogic EGX300 integrated gateway-server
Gain energy insight and control with PowerLogic PowerLogic EGX300 integrated gateway-server Plug into your energy usage with a simple mouse click The PowerLogic EGX300 is an integrated gateway-server that
Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V
Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V APC Smart-UPS, 670 Watts / 1000 VA,Input 230V / Output 230V, Interface Port DB-9 RS-232, SmartSlot, USB Includes: CD with software, Smart UPS signalling
MasterINTERFACE 39 Series - Relay interface modules
MasterINTERFACE 39 Series - 39 Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy ejection by plastic
PowerCommand 3201 digital generator set control
PowerCommand 3201 digital generator set control Description The PowerCommand 3201 Control is a microprocessorbased generator set monitoring, metering and control system. The control provides an operator
Safety technique. Emergency stop module BO 5988 safemaster
Safety technique Emergency stop module BO 5988 safemaster 0221562 Function diagram Pushbutton on Mains or emergencystop () K1 According to EC Directive for machines 98/37/EG According to IEC/E 60204-1