Model KGS/KGP. Automatic Transfer Switches Bypass/Isolation. Transfer Switch Standard Features. Controller. Standard Transition Models (KGS) Ratings
|
|
|
- Basil McCarthy
- 9 years ago
- Views:
Transcription
1 Model KGS/KGP Automatic Transfer es Bypass/Isolation Controller D Decision-Makerr MPAC 1500 Ratings Model Current Voltage, Frequency Transfer Standard Features D UL 1008 listed at 480 VAC, file #E D CSA certification available D IBC seismic certification available (NEMA 1 enclosures only) D Bypass/isolation switches for uninterrupted power to the load during switch maintenance and testing D Standard-transition or programmed-transition modes of operation D Ratings of bypass switch and automatic transfer switch identical D Available in 2, 3, or 4 pole configurations D Electrically operated, mechanically held mechanism D Double-throw, interlocked operation with mechanical and electrical interlocks D Drawout mechanism to facilitate maintenance D Quick-make, quick-break bypass switch operation for load transfer between live sources D Silver tungsten alloy contacts D Silver-plated, copper bus interconnection for the automatic transfer switch and bypass switch D Suitable for emergency and standby applications on all classes of load, 100% tungsten rated through 400 D NEMA type 1 enclosure D Exceeds UL 1008 requirements for temperature rise after overload and endurance tests in unventilated enclosure D Main shaft auxiliary position-indicating contacts rated15a@240vac D Engine start contacts rated VDC D Solid or switched neutral D Standard one-year limited warranty. Extended warranties are available. Standard Transition Models (KGS) D Standard-transition transfer time less than 100 milliseconds (6 60 Hz) KGS KGP VAC 50/60 Hz Programmed Transition Models (KGP) D Programmed-transition operation provides a center OFF position that allows residual voltages in the load circuits to decay D Programmable OFF time D Dual DC solenoid drive G (Model KGS/KGP Transfer ) 3/14 Page 1
2 Automatic Transfer Controller The Decision-Makerr MPAC 1500 Automatic Transfer Controller is used on bypass/isolation transfer switch models. Decision-Makerr MPAC 1500 Controller D LCD display, 4 lines x 20 characters, backlit D Complete programming and viewing capability at the door using the keypad and LCD display D LED indicators: Source available, transfer switch position, service required (fault), and not in auto D Modbus communication is standard D Programmable voltage and frequency pickup and dropout settings D Programmable time delays D Programmable generator exerciser D Time-based load control D Current-based load control (current sensing kit required) D Two programmable inputs and two programmable outputs D Up to four I/O extension modules available D RS-485 communication standard D Ethernet communication standard D Three-source system D Prime power For more information about Decision-Makerr MPAC 1500 features and functions, see specification sheet G Codes and Standards The ATS meets or exceeds the requirements of the following specifications: D CSA C22.2 No. 178 certification at 600 VAC available, file # LR58301 D EN Fast Transient Immunity Severity Level 4 D EN Surge Immunity Class 4 (voltage sensing and programmable inputs only) D IEC Specifications for EMI/EMC Immunity: d CISPR 11, Radiated Emissions d IEC , Electrostatic Discharge d IEC , Radiated Electromagnetic Fields d IEC , Electrical Fast Transients (Bursts) d IEC , Surge Voltage d IEC , Conducted RF Disturbances d IEC , Magnetic Fields d IEC , Voltage Dips and Interruptions D IEC , Low Voltage gear and Control Gear; Multifunction Equipment; Automatic Transfer ing Equipment D IEEE Standard 446, IEEE Recommended Practice for Emergency and Standby Power Systems for Commercial and Industrial Applications D IEEE 472 (ANSI C37.90A) Ring Wave Test D NEMA Standard ICS , Electromechanical AC Transfer Equipment D NFPA 70, National Electrical Code D NFPA 99, Essential Electrical Systems for Health Care Facilities D NFPA 110, Emergency and Standby Power Systems D Underwriters Laboratories UL 508, Standard for Industrial Control Equipment D Seismic certification in accordance with the International Building Code is available. (Accessory kit is required for seismic certification.) d IBC 2000, referencing ASCE 7-98 and ICC AC-156 d IBC 2003, referencing ASCE 7-02 and ICC AC-156 d IBC 2006, referencing ASCE 7-05 and ICC AC-156 d IBC 2009, referencing ASCE 7-05 and ICC AC-156 d IBC 2012, referencing ASCE 7-10 and ICC AC-156 D Underwriters Laboratories UL 1008, Standard for Automatic Transfer es for Use in Emergency Standby Systems, file # E G (Model KGS/KGP Transfer ) 3/14 Page 2
3 Application Data Environmental Specifications Screw-Type Terminals for External Power Connections Operating Temperature C to70 C (--4 F to 158 F) Range of Wire Sizes * Storage Temperature Humidity Component C to85 C (--40 F to 185 F) 5% to 95% noncondensing Input and Output Connection Specifications Main board I/O terminals I/O module terminals Amps Wire Size Range # AWG # AWG Auxiliary Position Indicating Contacts (rated 240 VAC) Number of Contacts Indicating Normal, Emergency KGS KGP , 3 3, , 2 2, 2 Amps Normal, Emergency, and Load Terminals (per phase) (2) 1/0 to 250 KCMIL or (1) #4 AWG to 600 KCMIL Neutral (2) 1/0 to 250 KCMIL or (1) #4 AWG to 600 KCMIL 600 (2) #2 AWG to 600 KCMIL (6) #2 AWG to 600 KCMIL (4) #2 AWG to 600 KCMIL (12) #2 AWG to 600 KCMIL (8) 1/0 to 750 KCMIL (24) 1/0 to 750 KCMIL (12) 1/0 to 750 KCMIL (36) 1/0 to 750 KCMIL * Use 60 C minimum wire for #14 to #1 AWG. Use 75 C minimum wire for 1/0 AWG and larger. Note: Use copper wire only. Weights and Dimensions Weights and dimensions are shown for standard-transition bypass/isolation switches in NEMA type 1 enclosures. Consult the factory for other available enclosures. Note: Weights and dimensions are provided for reference only and should not be used for planning installation. See your local distributor for submittal drawings. Bypass/Isolation es in NEMA 1 Enclosures Number of Poles 2, 3 Amps Height Dimensions, mm (in.) Width Depth Weight, kg (lb.) 150, 225, 260, (89.00) * 762 (30.00) 787 (31.00) 340 (750) (93.00) * 914 (36.00) 718 (28.25) [ 553 (1220) (93.00) * 1016 (40.00) 718 (28.25) [ 615 (1355) 1000, (93.00) * 1016 (40.00) 718 (28.25) [ 615 (1355) , (90.00) 1016 (40.00) 1552 (61.12) 1406 (3100) 2600, (90.00) 1016 (40.00) 1857 (73.12) 1769 (3900) 150, 225, 260, (89.00) * 762 (30.00) 787 (31.00) 386 (850) (93.00) * 1016 (40.00) 718 (28.25) [ 619 (1365) 4 800, 1000, (93.00) * 1168 (46.00) 718 (28.25) [ 712 (1570) 1600, (90.00) 1270 (50.00) 1552 (61.12) 1815 (4000) 2600, (90.00) 1270 (50.00) 1857 (73.12) 2268 (5000) * Height includes removeable 76 mm (3 in.) lifting eyes on amp models. [ Optional adapter bay for bottom cable entry adds 356 mm (14.0 inches) to the depth. ( amp models only.) G (Model KGS/KGP Transfer ) 3/14 Page 3
4 Withstand and Close-On Ratings (WCR) Withstand Current Ratings, Current in RMS Symmetrical Amperes When Coordinated with: Current-Limiting Fuses Molded-Case Circuit VAC Specific Manufacturers (see separate tables) Any Breaker Ratings Fuse Size, Class Class 480 VAC 600 VAC 480 VAC 600 VAC Time Duration (sec. max.) ,000 J , , RK5, RK1 J, L, RK1, RK5 N/A N/A 50,000 42,000 35,000 35, ,000 J, L, RK1, RK5 65,000 50, ,000 L N/A N/A 85,000 65, ,000 L L 50,000 42,000 N/A N/A N/A N/A 100,000 85, * UL 1008 and CSA listed at 480 VAC and 600 VAC. Withstand and Close-On Ratings with Coordinated Circuit Breakers, 480 V, UL Listed and CSA Certified The following chart lists contactor withstand and close-on ratings (WCR) with specific manufacturer s circuit breakers. Rating 150, 225, 260, 400 Molded-Case Circuit Breakers WCR, RMS Symmetrical Amperes Manufacturer Type or Class Size, FDC, HFD 225 HJD, JDC, JGC, JGH, JGU, JGX ,000 CHKD, CHLD4, CHMDL4, CLDC4, CMDL4, HKD, HLD4, HMDL4, KDC, LDC4, MDL4, NB TRI-PAC 400 CHLD6, CHMDL6, CMDL6, HLD6, HMDL6, LCDC6, LDC6, MDL6, NB TRI-PAC 600 CHMDL8, CMDL8, HMDL8, MDL8, NB TRI-PAC 800 HJ, HL, HR 150 JJ, JL, JR 250 LJ, LL, LR 400 LJ, LL, LR 600 MJ,PJ,PK,PL,RJ,RK,RL 800 CFD6, HFD6, HFXD6, HHFD6, HHFXD6 250 CJD6, HHJD6, HHJXD6, HJD6, HJXD6, SCJD6, SHJD6 400 CLD6, HHLD6, HHLXD6, HLD6, HLXD6, SCLD6, SHLD6 600 CMD6, HMD6, HMXD6, MD6, MXD6, SHMD6, SCMD6, SMD6 800 SEL, SEP, TEL, TEML, THLC1 150 FEH, FEL, FEN, SFL, SFP 250 FGH4,FGL4,FGP4,SGL4,SGP4,TB4,THLC4,TJL4,TLB4 400 FGH6, FGL6, FGN6, FGP6, SGL6, SGP6, TB6, TJL6 600 SKH8, SKL8, SKP8, TB8 800 G (Model KGS/KGP Transfer ) 3/14 Page 4
5 Molded-Case Circuit Breakers Rating WCR, RMS Symmetrical Amperes Manufacturer Type or Class Size, HLD, CHLD, LDC, CLDC 600 HMDL, CHMDL, NB TRI-PAC, DSL LC, LE, LI, LX, LXI 600 ME, MH, MX, NC, NE, NX ,000 CLD6, SCLD6, HLD6, SHLD6 600 CMD6, SCMD6, HMD6, SHMD6 800 TB6, TJL, SGL6, SGP6 600 TB8, TP, THP, TC, THC, SKL8, SKP8 800 NB TRI-PAC 800 NDC, CNDC 1200 RDC, CRDC, PC, PCC, PB TRI-PAC 1600 NC, NE, NX 1200 PCF, PEF, PHF, PXF 1600 CMD6, SCMD , 85,000 CND6, SCND CPD THP, THC, TB8, SKP8 800 SKP THP, THC, TRP 1600 Merlin Gerin CK1000L 1200 CM NDC, CNDC 1200 RDC, CRDC, PC, PCC, PB TRI-PAC 1600 NC, NE, NX 1200 PCF, PEF, PHF, PXF ,000 CND6, SCND CPD SKP THP, THC, TRP 1600 Merlin Gerin CK1000L 1200 CM ,000 MASTERPACT NW 1600 SHD G (Model KGS/KGP Transfer ) 3/14 Page 5
6 Withstand and Close-On Ratings with Coordinated Circuit Breakers, 600 V, CSA Certified The following chart lists contactor withstand and close-on ratings (WCR) with specific manufacturer s circuit breakers Molded-Case Circuit Breakers WCR, RMS Symmetrical Amperes Manufacturer Type or Class 42, , , ,000 Size, JGU, JGX 250 CLDC6,KDC, LDC4, NB TRI-PAC 400 CLDC6, LDC6, NB TRI-PAC 600 NB TRI-PAC 800 HL, HR 150 JL, JR 250 LL, LR 400 LL, LR 600 PK, RK, RL 800 CFD6 250 CJD6, HHJD6, HHJXD6, SCJD6 400 CLD6, HHLD6, HHLXD6, SCLD6 600 CMD6, HMD6, HMXD6, SCMD6, SHMD6 800 THLC1 150 FGL4, FGP4, SGL4, SGP4, TB4, THLC4, TJL4, TLB4 400 FGL6, FGP6, SGL6, SGP6, TB6 600 SKL8, SKP8, TB8 800 LDC, CLDC 600 NB TRI-PAC, DSL LI, LXI 600 NC, NE, NX 800 CLD6, SDLD6 600 CMD6, SCMD6, HMD6, SHMD6 800 TB6, SGL6, SGP6 600 TB8, THP, THC, SKP8 800 NB TRI-PAC 800 RDC, CRDC, PC, PCC, PB TRI-PAC 1600 NC, NE, NX 1200 PCF, PEF, PHF, PXF 1600 CMD6, SCMD6 800 CND6, SCND CPD6, HPD6, HRD THP, THC, TB8, SKP8 800 SKP THP, THC, TRP 1600 Merlin Gerin MP16H1, MP16H2, MC16H RDC, CRDC, PC, PCC, PB TRI-PAC 1600 NC, NE, NX 1200 PCF, PEF, PHF, PXF 1600 CND6, SCND CPD6, HPD6, HRD SKP THP, THC, TRP 1600 Merlin Gerin MP16H1, MP16H2, MC16H G (Model KGS/KGP Transfer ) 3/14 Page 6
7 Accessories Accessories are available either factory-installed or as loose kits, unless otherwise noted. - Adapter Bays D Available for amp models - CSA Certification - Digital Meter D Measure and display voltage, current, frequency, and power for both sources D Programmable visual alarms for high voltage, low voltage, and high current D Three digital outputs D Serial port for optional network connections D Password-protected programming menus D Joystick operation D Factory-installed - Extended Warranties D 2-year basic D 5-year basic D 5-year comprehensive D 10-year major components - Export Packaging - Heater, Anti-Condensation D Hygrostat-controlled 120 VAC strip heater (customer-supplied voltage source required) D 100 or 250 watts (sized for enclosure) D Protective 15 Amp circuit breaker - Literature Kits D Production literature kit (one kit is included with each transfer switch) D Overhaul literature kit - Neutral Assembly D Available as loose kit for open units - RSA III Remote Serial Annunciator D Monitors the generator set D Monitors Normal and Emergency source status and connection D Monitors ATS common alarm D Allows remote testing of the ATS D For more information, see specification sheet G Pull Box D Optional for amp units D Required for bottom cable entry on amp units - Seismic Certification D Certification depends on application and geographic location. Contact your distributor for details. D Available for Amp KGS and KGP models with NEMA 1 enclosures - Surge Protection Device (SPD) D SPD available for the normal source supply D Surge protection reduces transient voltages to harmless levels D Protection modes: L-L / L-N / L-G / N-G D Replaceable phase and neutral cartridges for service D Frequency: Hz D Operating Temperature Range: --40 to 176_F (--40to80_C) D Remote contacts for customer-supplied status indicators: Contacts: 1 NO, 1 NC Min Load: 12VDC / 10 ma Max. Load: 250 VAC / 1 A Wire Size (max.): 16AWG D Fuse protection: 30 / 600 V D UL 1449, 3rd Edition for Type 2 applications D IEC , 2nd Edition T2/11 D See additional specifications below Additional Controller Accessories See the controller specification sheet for more information. - Accessory Modules D Alarm Module D External Battery Supply Module D Input/Output Module D High-Power Input/Output Module - Controller Disconnect - Current Sensing Kit - Line-to-Neutral Voltage Monitoring - Padlockable User Interface Cover - Supervised Transfer Control Nominal Voltage (V ±15%) Max. Discharge Current (ka) Phase Poles UL VPR 3rd Ed (L-N/N-G/L-G) (kv) SPD Specifications Limiting Voltage, (L-N/N-G/L-G) (kv) Short Circuit Withstand Current (ka) Continuous Operating Voltage (VAC) at 3kAmps at 10kAmp 240 / Split / 1.2 / / 0.4 / / 0.7 / / / Wye / 1.2 / / 0.4 / / 0.7 / / / Wye / 1.2 / / 0.4 / / 0.7 / / / HLD / 1.2 / / 0.4 / / 0.7 / / / Wye / 1.2 / / 0.4 / / 0.7 / / 880 G (Model KGS/KGP Transfer ) 3/14 Page 7
8 KOHLER CO., Kohler, Wisconsin USA Phone , Fax For the nearest sales and service outlet in the US and Canada, phone KOHLERPower.com Kohler Power Systems Asia Pacific Headquarters 7 Jurong Pier Road Singapore Phone (65) , Fax (65) Model Designation Model Mechanism Transition Controls Voltage Poles Enclosure Current Rating Miscellaneous Record the transfer switch model designation in the boxes. The transfer switch model designation defines characteristics and ratings as explained below. Sample Model Designation: KGS-DCTA-0400S Model K: Kohler Mechanism G: Bypass/Isolation Transition S: Standard P: Programmed Controller D: Decision-Makerr MPAC 1500, Automatic Voltage/Frequency C: 208 Volts/60 Hz K: 440 Volts/60 Hz D: 220 Volts/50 Hz M: 480 Volts/60 Hz F: 240 Volts/60 Hz N: 600 Volts/60 Hz G: 380 Volts/50 Hz P: 380 Volts/60 Hz H: 400 Volts/50 Hz R: 220 Volts/60 Hz J: 416 Volts/50 Hz Number of Poles/Wires N: 2 Poles/3 Wires, Solid Neutral T: 3 Poles/4 Wires, Solid Neutral V: 4 Poles/ 4 Wires, ed Neutral Enclosure A: NEMA 1* * Contact the factory for other enclosure types. Current, Amps [ [ Some selections are not available on all models. Connections S: Standard F: Front (800 amp only) Note: Some selections are not available on all models. Contact your Kohler distributor for availability. DISTRIBUTED BY: Availability is subject to change without notice. Kohler Co. reserves the right to change the design or specifications without notice and without any obligation or liability whatsoever. Contact your local Kohlerr Power Systems distributor for availability by Kohler Co. All rights reserved. G (Model KGS/KGP Transfer ) 3/14 Page 8
Model KSS. Transfer Switch Standard Features. Available Controllers. Ratings. Automatic Transfer Switches Standard Specific-Breaker Rated
Model KSS Automatic Transfer Switches Standard Specific-Breaker Rated Available Controllers D Decision-Makerr MPAC 750 D Decision-Makerr MPAC 1200 Transfer Switch Standard Features D UL 1008 listed at
Model: RXT. Model RXT Automatic Transfer Switch. Standard Features. Standard Interface Board. Available Models
Model: RXT Automatic Transfer Switch 100 - Amps Covers have been removed for illustration. Available Models D 100,, and amp standard and service entrance models are available. D 150 and 300 amp service
MPAC 1500 Controller
Model KSS/KSP Specific-Breaker Rated ATS Ratings Voltage: Current: 208--480 VAC 50/60 Hz 40--1000 Amps (standard transition) 100--600 Amps (programmed transition) Transfer Switch Standard Features UL 1008
Controller Features. Modbus link to define inputs and outputs. Programmable Outputs Auxiliary switch fault Common fault.
Model KCT Automatic Transfer Switches Ratings Voltage: 208--600 VAC 50/60 Hz Current: 30--3000 amps Standard Contactor Features Open-transition operation with either automatic or non-automatic control
RXT. Model: Model RXT Automatic Transfer Switch
Model: RXT Automatic Transfer Switch -- Model RXT Automatic Transfer Switch The Model RXT automatic transfer switch is designed for use only with Kohlerr generator sets equipped with RDC2 or DC2 generator
Model: RDT. Automatic Transfer Switch 100-400 Amps. 200 amp load center models use up to 24 circuit breakers
Model: RDT Automatic Transfer Switch 100-400 Amps MPAC 500 Controller Features User-friendly interface with easy-to-read international symbols Source available and contactor position indicators LED indication
Automatic Transfer Switch Controller
Automatic Transfer Switch Controller Decision-Makerr MPAC 1500 Model KBS with Decision-Makerr MPAC 1500 Controller Applicable Models Model Description KCS Standard-Transition Any Breaker ATS ] KCP Programmed-Transition
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH
CAT ATC POWER BREAKER & POWER CASE SWITCH AUTOMATIC TRANSFER SWITCH Cat transfer switches are designed for a variety of standby power applications. They provide flexibility, reliability and value in a
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches
SUGGESTED SPECIFICATION for Series 185 Service Entrance Rated Automatic Transfer Switches PART 1 GENERAL 1.01 Scope Optional Standby Power Generator Systems A. Furnish and install automatic transfer switches
Decision-Maker Paralleling System. Power Distribution Switchboards and Circuit Breakers. Standard Features
Decision-Maker Paralleling System Power Distribution Switchboards and Circuit Breakers Power Distribution Switchboards and Circuit Breakers The generator paralleling circuit breakers for the Kohler Decision-Maker
GTEC transfer switch open transition
GTEC transfer switch open transition 40-1250 Amp Description The GTEC automatic transfer switch combines reliability and flexibility in a small, economical package for transferring loads between a utility
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out
APC Matrix-UPS 5kVA 208V/240V In 120/208/240V Out APC Matrix-UPS, 3750 Watts / 5000 VA,Input 208V / Output 120V, 208V, Interface Port DB-9 RS-232, SmartSlot, Extended runtime model Includes: CD with software,
Dimensions, Inches (mm) No. of Poles Width Height Depth 2, 3 8.25 (210) 16 (407) 5.5 (140) 4 11.125 (283) 16 (407) 5.5 (140)
9-10N Supersedes Selection Data 9-10N, pages, 1-, dated dated March March 1995 1995 Mailed to: E, D, C/9-100A, 31-A, INTERRUPTING CAPACITY RATINGS IEC 947- Interrupting Capacity s➀ Interrupting Capacity
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
ASCO SERIES 185 Power Transfer Switches
ASCO SERIES 185 Power Transfer Switches 4-hour protection no matter when trouble strikes ASCO Series 185 Power Transfer Switches An Automatic Transfer Switch helps prevent... Your business or home from
Power-monitoring unit PowerLogic System. Technical data sheet. Power Meter Series 800
Power-monitoring unit PowerLogic System Technical data sheet 2003 Power Meter Series 800 Function and characteristics PB100313 The PowerLogic Power Meter Series 800 offers all the high-performance measurement
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options
BT300 HVAC Drives Conventional Bypass (C-Bypass) Options Description The BT300 Conventional Bypass is a companion package for the family of BT300 HVAC Drives. For information on the family of BT300 HVAC
Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500
Product Description Primary Resistance Starting Electric Fire Pump Controllers FTA1500 Description Firetrol FTA1500 Primary Resistance Fire Pump Controllers use resistors in the line to reduce line voltage
Power Meter Series 700
PowerLogic power-monitoring units Power Meter Series 700 Technical data sheet 2007 Functions and characteristics E90463 The PowerLogic Power Meter Series 700 offers all the measurement capabilities required
How To Operate A Gec Transfer Switch Open Transition 40 2000 Amp Power Supply
GTEC Transfer switch open transition 40 2000 amp Description GTEC transfer switches combine reliability and flexibility in a small, economical package for transferring loads between a utility and a generator
Applications. Remote Display Mounting Kits
June 200 Sheet 105 Surge Protection Products TVSS General Description Clipper Power System Visor Series.1-5 Clipper Power System Visor Series General Description Eaton s Cutler-Hammer leading-edge surge
LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA. General Specification
08/17/12 Rev2 LTR Series General Specification 700 VA to 2.1 KVA 1.0 General LTR Series Uninterruptible Power Systems 700 VA - 2.1 KVA General Specification This specification describes the features and
Series TS 870 100-1200 Amp. Automatic Transfer Switches
Series TS 870 100-1200 Amp Automatic Transfer Switches A Regal Brand TS 870 AUTOMATIC TRANSFER SWITCHES THOMSON POWER SYSTEMS TS 870 AUTOMATIC TRANSFER SWITCHES OFFER THE FOLLOWING OUTSTANDING FEATURES:
STRATO LED Drivers 70W, Single output
Features STRATO switch mode driver technology is designed to generate one constant current output from a wide range AC input. The size and performance of these products make them the ideal choice for LED
PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors
PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2
FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE
FTA1100-J DIESEL ENGINE FIRE PUMP CONTROLLERS STANDARD SUBMITTAL PACKAGE SBP1100J FTA1100J Diesel Engine Fire Pump Controllers Product Description Description Firetrol combined automatic and manual Mark
SWITCH! DESCRIPTION. ENVIRONMENTAL SPECIFICATIONS Operating Temperature: 0 C to +40 C SPECIFICATION SHEET:
SWITCH The Budderfly lighting switch is a Decora style, plug-and-play replacement for your existing building switches. Installing a Budderfly adapter transforms your building s existing wiring into the
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fi re pumps
Transfer switch BTPC open, closed or delayed transition
Transfer switch BTPC open, closed or delayed transition 150-4000 Amp Description The Cummins Power Generation BTPC series bypass isolation transfer switch combines an automatic transfer switch with a drawout
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 SERIES Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical
Bulletin 150 SMC Flex Smart Motor Controller Specifications
Specifications Specifications Standard Features Optional Features Installation Setup Communications Power Wiring Control Wiring Keypad Software Starting and Stopping Modes Protection and Diagnostics Metering
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial
SmartOnline 200-240V 5kVA 4.5kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 4U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SU5000RT4UHV Description Tripp Lite SU5000RT4UHV 5000VA / 5kVA /
38 SERIES. Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A. EMR Electromechanical Relays. Common features. SSR Solid State Relays. 6.
38 Relay interface modules 0.1-2 - 3-5 - 6-8 - 16 A 38 Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit 6.2 mm wide EMR - DC, AC or AC/DC
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A
38 Series - Relay interface modules 0.1-2 - 3-5 - 6-8 A Common features Instant ejection of relay by plastic retaining clip Integral coil indication and protection circuit EMR Electromechanical Relays
OmniVS Series 1500VA Line-Interactive Tower 120V UPS with USB port
OmniVS Series 1500VA Line-Interactive Tower 120V UPS with USB port MODEL NUMBER: OMNIVS1500 Highlights 1500VA / 1.5kVA tower 120V line-interactive UPS Corrects brownouts and overvoltages from 75 to 147V
DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS
Features: INSTALLATION Install in accordance with NFPA 70. DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS Up to 1.95 Amps Load Capacity Class 2 Rated Outputs Overload, Over Voltage, and Short
Project Name: Nortrax Section 26 41 00 Project No: 13-013 SURGE PROTECTION DEVICES Page 1
Page 1 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. General: Drawings and general provisions of the Contract, including General and Supplementary Conditions and Divisions 1 Specification sections apply to
Uninterruptible Power Supply
96-01101 / rev. 2e / 2-2-12 Uninterruptible Power Supply EXCEPTIONAL SUPPORT & PROTECTION Uninterruptible Power Supply with Energy Saver design that is optimized to address the needs of A/V systems Features
Thyristor-controlled power supplies and battery chargers
Thyristor-controlled power supplies and battery chargers Input voltage: 115 / 230 VAC, single phase, 50 / 60 Hz or 208 / 400 / 480 VAC, three phases, 50 / 60 Hz Output voltage: 12 / 24 / 48 / 60 / 72 /
3500/62 Process Variable Monitor
3500/62 Process Variable Monitor Description The 3500/62 Process Variable Monitor is a 6-channel monitor for processing machine critical parameters (pressures, flows, temperatures, levels, etc.) that merit
Single-phase (220...240 V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable
Features 70.11 70.31 70.41 Electronic voltage monitoring relays for single and three-phase applications Multifunctional types, providing the flexibility of monitoring Undervoltage, Overvoltage, Window
SUGGESTED SPECIFICATION for Service Entrance Automatic Transfer Switches
PART 1 GENERAL 1.01 Scope SUGGESTED SPECIFICATION for Service Entrance Automatic Transfer Switches Division 16 - Electrical Standby Power Generator Systems A. Furnish and install service entrance automatic
MAJORSINE Power Inverter
MAJORSINE Power Inverter Product Features: 24, 48, 130 V 1 KVA/800 Watts Output 2 KVA/1600 Watts Output 100-120 VAC Range 208-240 VAC Range Standard 19 /23, Pure Sine Wave Output High Low EMI/RFI Emissions
Continuous Power... Continuous Protection
Series 165 We Keep Your Power On Continuous Power... Continuous Protection An Automatic Transfer Switch helps prevent... Your business or home from losing power during bad weather or utility power equipment
PC Personal 120V 600VA 375W Standby UPS with Pure Sine Wave Output, Tower, 6 Outlets
PC Personal 120V 600VA 375W Standby UPS with Pure Sine Wave Output, Tower, 6 Outlets MODEL NUMBER: BC600SINE Highlights 600VA tower 120V standby UPS with SINE WAVE output Maintains AC output during power
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial
SmartPro 120V 2.2kVA 1.92kW Line-Interactive Sine Wave UPS, SNMP, Webcard option, 2U Rack/Tower, LCD, USB, DB9 Serial MODEL NUMBER: SMART2200RM2U Highlights 2.2kVA / 2200VA / 1920W line interactive 2U
CTS SERIES AUTOMATIC TRANSFER SWITCH
CTS SERIES AUTOMATIC TRANSFER SWITCH The Cat CTS Series Automatic Transfer Switch (ATS) is configurable for applications requiring the dependability and ease of operation found in a full featured power
WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE
WITH POWER TRANSFER SWITCH STANDARD SUBMITTAL PACKAGE SBP1930-61 FTA1930 Digital Solid State Starting Electric Fire Pump Controllers Product Description Fire Pump Controllers for Business-Critical Continuity
Low Voltage Products. Switches Automatic Transfer Switches
Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,
SECTION 13850 DETECTION AND ALARM
SECTION 13850 DETECTION AND ALARM PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. Control Panel 2 Associated Equipment B. Products Installed But Not Supplied Under This Section 1. Section 16140 - Wiring
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
Series AMEPR30-AZ up to 2.5A AC-DC / DC-DC LED Driver / Converter
FEATURES: Click on Series name for product info on aimtec.com Models Single output Model Max Output Power (W) 1 AC-DC Constant Current or Constant Over temperature protection Voltage LED Driver Over current
Internet Office 750VA Ultra-compact Standby 120V UPS with USB port
Internet Office 750VA Ultra-compact Standby 120V UPS with USB port MODEL NUMBER: INTERNET750U Highlights 750VA ultra-compact 120V standby UPS Maintains AC output during power failures 6 UPS battery supported
RISH EM 3490 DS Dual Source Energy Meter RISH EM 3490 DS. Application : Product Features:
Application : RISH Master 3490 DS measures important electrical parameters of Utility (in normal mode) & Generators (in Power back up) in three phase and single phase Network & replaces the multiple analog
APC. DIN Rail Control Panel Mounting Uninterruptible Power Supply. Catalog
APC DIN Rail Control Panel Mounting Uninterruptible Power Supply Catalog 2014 Contents Introduction, description... 4 Specifications...5 References....6 Dimensions...7 Wiring diagrams....8 Product reference
Cisco Unified IP Phone Power Injector
Data Sheet Cisco Unified IP Phone Power Injector The Cisco Unified IP Phone Power Injector (Figure 1) increases the deployment flexibility of Cisco Unified IP phones by providing an alternative powering
Redundancy Module QUINT-DIODE/40
Redundancy Module QUT DIODE provides: 00% decoupling of power supplies connected in parallel Can be installed in potentially explosive areas Load currents up to 60 A supported Easy assembly by snapping
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack-Mount, USB, DB9 Serial MODEL NUMBER: SMART750RM1U Highlights.75kVA / 750VA / 600W line interactive 1U rackmount UPS, Sine
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial
SmartPro 120V 750VA 600W Line-Interactive Sine Wave UPS, 1U Rackmount, SNMPWEBCARD Option, USB, DB9 Serial MODEL NUMBER: SMART750RM1U Highlights.75kVA / 750VA / 600W line interactive 1U rackmount UPS,
SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial
SmartPro 120V 500VA 300W Line-Interactive UPS, SNMP, Webcard, 1U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SMART500RT1U Description Tripp Lite's SMART500RT1U intelligent, line-interactive rack/tower uninterruptible
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments
Industrial-Grade UPS System Heavy-duty power protection for harsh industrial environments Model #: SM2000RMX Heavy-duty, industrial-grade metal housings Shock and vibration rated to MIL-STD-810D 19 inch
Features. Display. Measurements. Intelligent. Accuracy. Models. Installation DEIF A/S. Multi-instrument 4921210109D
7000/7000C/7020 Multi-instrument 4921210109D Features Measurements All 3-phase AC measurements True RMS Replaces analogue meters Demand on each phase current Accuracy U, I and F class 0.5 Other values
RISH CON - Hz. Salient Features : Application : Product Features: FREQUENCY TRANSDUCER
Application : The RISH CON - Hz transducer is used for frequency measurement. The output signal is proportional to measured frequency and is either load independent DC Current or load independent DC Voltage.
SmartPro 100/110/120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMP, Webcard, USB, DB9 Serial
SmartPro 100/110/120V 1.5kVA 900W Line-Interactive Sine Wave UPS, Tower, SNMP, Webcard, USB, DB9 Serial MODEL NUMBER: SMART1500SLT Highlights 1.5kVA / 1500VA line interactive tower UPS; Sine wave output
TAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial
TAA-Compliant SmartPro 120V 1kVA.8kW Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial MODEL NUMBER: SM1000RM1UTAA Description Tripp Lite SM1000RM1UTAA 1000VA / 1kVA / 800 watt line
CPS 100 480Y S K CPS 100 480Y S C
Ref. No. 1299 Visor Series Ordering Guidelines Table.1-4. Retrofit Surge Protection Products TVSS General Description Clipper Power System Visor Series CPS 100 480Y S K.1-9 Surge Ratings 100 = /phase 120
Type: EASY719 DC RC Article No.: 274119. Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description
Type: EASY719 DC RC Article.: 274119 Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC Description 12 digital inputs (4 inputs available as analog inputs) 6 relay outputs LCD display
Model #: SMART2200CRMXL
Tripp Lite 1111 West 35th Street Chicago, IL 60609 USA Telephone: +(773) 869 1234 E-mail: [email protected] Model #: SMART2200CRMXL SmartPro Compact Rackmount UPS System - Precision Protection for
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
Bimetallic Overload Relay Specifications
Technical Data Bimetallic Overload Relay Specifications Bulletin Number 193K, 193T1 Topic Page Product Overview 2 Standards compliance and Certifications 2 General Specifications 193K 3 Approximate Dimensions
MEDIUM VOLTAGE CE-BF SWITCHBOARDS. UP TO 40.5 kv. CE - BF - C - en - REV.00 2012.4
CE - BF - C - en - REV.00 2012.4 APPLICATION CE-BF Switchbords up to 40.5 kv are designed for use in public and industrial distribution system up to 40,5KV for the operation and protection of lines, transformers,
Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1
How to configure Part Numbers: Step : Select Switch Amperage Power Module Switch Rating (Amps) Power Module Switch Catalog No. 30 3 60 6 00 200 2 400 4 Step 2: Select Options Needed 5 Bussmann Power Module
Electronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial
SmartPro 120V 1kVA 800W Line-Interactive Sine Wave UPS, SNMP, Webcard, 1U Rack, USB, DB9 Serial MODEL NUMBER: SMART1000RM1U Description Tripp Lite SMART1000RM1U 1000VA / 1kVA / 800 watt line interactive,
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000
Product Description Full Voltage Starting Electric Fire Pump Controllers FTA1000 Description Firetrol FTA1000 Full Voltage Fire Pump Controllers are intended for use with electric motor driven fire pumps
NRG. Intelligent Engine Start Battery Charger. The Smart Choice for Mission-Critical Engine Starting
NRG Intelligent Engine Start Battery Charger The Smart Choice for Mission-Critical Engine Starting Fast, accurate, mission-critical charging gives best starting reliability 4-rate, temperature-compensated
CompactLogix Power Supplies Specifications
Technical Data CompactLogix Power Supplies Specifications 1768 CompactLogix Power Supplies Catalog Numbers 1768-PA3, 1768-PB3 1769 Compact I/O Power Supplies Catalog Numbers 1769-PA2, 1769-PB2, 1769-PA4,
Always On UPS Systems Inc., #100-150 Campion Road, Kelowna, BC Canada V1X 7S8
Door Mount UPS (Patent Pending) Shelf Mount UPS (Patent Pending) DESCRIPTION: The Always On NDM (door mount) and NSM (shelf mount) Series UPS s are dual conversion online UPS systems provided in slim,
Circuit Breakers and Switchgear. Thomas Greer Director of Engineering TLG Services
Circuit Breakers and Switchgear Thomas Greer Director of Engineering TLG Services Presentation Outline Switchgear Definition Overcurrent Protection Devices Circuit Breaker Trip Curves and Coordination
MCR1900 Media Converter 19-Slot Chassis
MCR1900 Media Converter 19-Slot Chassis Installation Guide Part #5500304-11 Copyright Statement This document must not be reproduced in any way whatsoever, either printed or electronically, without the
Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
RM4TG20 three-phase network control relay RM4-T - range 200..500 V
Characteristics three-phase network control relay RM4-T - range 200..500 V Complementary [Us] rated supply voltage Output contacts Setting accuracy of time delay Delay at power up Measuring cycle Marking
Chassis, Power Supply, and Element Management
Chassis, Power Supply, and Element Management C-COR CHP Max5000 Converged Headend Platform Accelerate deployment of new, revenue generating advanced services Innovative technology creating converged high-
Telephone- and leased line modem for industrial applications TD-36
Telephone- and leased line modem for industrial applications TD-36 Modem for industrial PSTN- and leased line applications The TD-36 is an analogue V.34 PSTN modem as well as an industrial 2-wire leased
SmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial
SmartPro 230V 1000VA 900W Line-Interactive Sine Wave UPS, SNMP, Webcard, 2U Rack/Tower, USB, DB9 Serial MODEL NUMBER: SMX1000RT2U Highlights 1kVA / 1000VA / 900W line-interactive 2U rack/tower UPS, Sine
26 3213.13 Diesel Engine Driven Generators Page 1 of 6
Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at
Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1
Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input
Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930
Product Description Digital Solid State Starting Electric Fire Pump Controllers FTA1930 Description Firetrol FTA1930 Digital Solid State Starting Fire Pump Controllers feature soft start, soft stop and
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
Rack mounted telephone- and leased line modem for industrial applications
Rack mounted telephone- and leased line modem for industrial applications TR-6 Rack modem for industrial PSTNand /-wire leased line applications The TR-6 is an analogue V. 9 -rack PSTN modem as well as
CONSTRUCTION STANDARDS DIVISION 23 HEATING VENTILATING AND AIR CONDITIONING
PART 1-GENERAL 1.01 DESCRIPTION A. This specification is to cover a complete Variable Frequency motor Drive (VFD) consisting of a pulse width modulated (PWM) inverter designed for use on a standard NEMA
Owner s Manual. For Automatic Transfer Switch. 100-200 Amp, Service Entrance/Non-Service Entrance
Owner s Manual For Automatic Transfer Switch 100-200 Amp, Service Entrance/Non-Service Entrance Model Numbers RTST100A3 RTSP100A3 RTST150A3 RTST200A3 RTSP200A3 MODEL NUMBER: SERIAL NUMBER: DATE PURCHASED:
MasterINTERFACE 39 Series - Relay interface modules
MasterINTERFACE 39 Series - Relay interface modules Common features Space saving 6.2 mm wide Connections for 16-way jumper link Integral coil indication and protection circuit Secure retention and easy
Analog signal converters CC-E I/I Current / current isolators
ata sheet Analog signal converters CC-E I/I Current / current isolators The CC-E I/I is an isolator for the electrical isolation of current signals without auxiliary supply. It allows the isolation between
Agilent 87421A/87422A Power Supply
Agilent 87421A/87422A Power Supply Technical Overview Designed specifically for Agilent Technologies microwave system amplifiers Bias cable permits remote placement Compact size for easy system integration
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire
SmartOnline 200-240V 6kVA 4.2kW On-Line Double-Conversion UPS, Extended Run, SNMP, Webcard, 6U Rack/Tower, DB9 Serial, Hardwire MODEL NUMBER: SU6000RT3UHV Highlights 6000VA / 6kVA / 4200W on-line double-conversion
AUTOMATIC TRANSFER SWITCH. Changeover Type from 250A to 2500A
AUTOMATIC TRANSFER SWITCH Changeover Type from 250A to 2500A Table of Contents Preamble 1.1 Theoretical base 1.2 Selection the size of automatic transfer switch 1.3 Automatic transfer switch components
Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V
Smart-UPS APC Smart-UPS 1000VA USB & Serial 230V APC Smart-UPS, 670 Watts / 1000 VA,Input 230V / Output 230V, Interface Port DB-9 RS-232, SmartSlot, USB Includes: CD with software, Smart UPS signalling
SURGE PROTECTIVE DEVICES (SPDs) LOW VOLTAGE AC INTEGRATED SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS SECTION 16671A SECTION 16671A
SURGE PROTECTIVE DEVICES (SPDs) INTEGRATED UNITS LOW VOLTAGE AC SURGE PROTECTION FOR ELECTRICAL DISTRIBUTION SYSTEMS PART 1 GENERAL 01 02 03 SCOPE The Contractor shall furnish and install the Surge Protective