1 BICSI 002 / TIA 942 / Uptime Which Data Center Standard Should I Follow Phil Isaak, PE, P.Eng., RCDD, DCDC President, Master Instructor Isaak Technologies Inc.

2 Standards Who are these People Standards Distribution & Grounding Network Standards Protocols IT Hardware Manufacturers Media Standards Cabling Manufacturers Design & Installation Standards End Users, Contractors, Consultants, Manufacturers

3 Uptime TIA BICSI Uptime Institute (2010) Data Center Site Infrastructure Tier Standard: Topology 12 pages For Profit Privately Held NOT a Standard ANSI/TIA 942 A (2012) Telecommunications Infrastructure Standard for Data Centers 118 pages Open Industry Standard NOT Vendor Neutral ANSI/BICSI Data Center Design and Implementation Best Practices 392 pages Open Industry Standard Vendor Neutral

4 ANSI Certified Standard Requirements Openness: Participation shall be open to all persons who are directly and materially affected by the activity in question. Lack of Dominance: The standards development process shall not be dominated by any single interest category, individual or organization. Balance: Participants from diverse interest categories shall be sought with the objective of achieving balance.

5 BICSI Subject Matter Experts More than 150 subject matter experts from around the world participated in developing the standard. Perspectives: Data Center Managers Data Center Operators Consultants Contractors Risk Assessors Manufacturers Commissioning Agents Expertise: Facility Engineers/Architects IT Engineers/Architects System Administrators Telecommunications Security Fire Protection Project Managers

6 Design Guide vs Benchmarking ANSI/BICSI Provides a reference of common terminology and design practices a framework for determining the recommended facility and technology redundancy to meet the operational requirements, achieve IT objectives and to develop optimum design & implementation solutions Uptime Tiers Only data center benchmarking system developed by and for data center owners, not a checklist, design menu, or cookbook Source: Uptime Institute: Tier Classification System & Operational Sustainability presented by Dana Smith, Director of Development, Uptime Institute at BICSI Andino 2012

7 Uptime Benchmarks Uptime Institute Tier I Tier II Tier III Tier IV Scheduled Outages / Year 2 x 12hrs 1 x 12hrs None None Ave Failures / Year (4hrs / failure) Ave Annual Downtime Hours Availability 99.67% 99.75% 99.98% 99.99% ** Basis is on top 10% of sites as determined by Uptime Institute Benchmarking **

8 Comparing the Standards TIA 942 A chapters (normative) Data center design overview Data center cabling system infrastructure Data center telecommunications spaces & related topologies Data center cabling systems Data center cabling pathways Data center redundancy TIA 942 A annexes (informative) Cabling design considerations Access provider information Coordination of equipment plans with other engineers Data center space considerations Data center site selection and building design considerations Data center infrastructure tiers Data center design examples

9 Comparing the Standards BICSI 002 sections Space planning Site selection Architectural Structural Electrical systems Fire protection BICSI 002 annexes Design process Reliability and availability Security Building automation systems Telecommunications Information technology Commissioning Data center maintenance

10 Comprehensive Data Center Standard ANSI/BICSI

11 Methodology to Define Reliability Define Operational Requirements Annual Planned Downtime Operational Level > 400 hrs hrs hrs hrs 3 0 hrs 4

12 Methodology to Define Reliability Define Operational Requirements Define Availability Requirements Minutes Number of 9 s > 5,000 > 99% 500 5,000 99% 99.9% % 99.99% % % % %

13 Methodology to Define Reliability Define Operational Requirements Define Availability Requirements Define Impact of Downtime Description Local in scope, affecting only a single function or operation, resulting in a minor disruption or delay in achieving non critical organizational objectives. Local in scope, affecting only a single site, or resulting in a minor disruption or delay in achieving key organizational objectives. Regional in scope, affecting a portion of the enterprise or resulting in a moderate disruption or delay in achieving key organizational objectives. Multiregional in scope, affecting a major portion of the enterprise or resulting in a major disruption or delay in achieving key organizational objectives. Affecting the quality of service delivery across the entire enterprise, or resulting in a significant disruption or delay in achieving key organizational objectives. Classification Isolated Minor Major Severe Catastrophic

14 Methodology to Define Reliability Define Operational Requirements Define Availability Requirements Define Impact of Downtime Recommended Performance Identified Class 0 Class 1 Class 2 Class 3 Class 4

15 Class 0/1 Single Path Alternate Source Transfer Utility N Chiller, Pumps & Condenser Electrical Distribution Static Bypass UPS Maint. Bypass Carrier Piping and valve redundancy not required. N CRAH Modules PDU Critical Non-Critical Edge Edge Internet Core Aggregation RPP A A 1 Access Switch Server 1 Large Frame Processing Server n A POU NAS Disk Array Disk Array A PSU B PSU 2013 Isaak Technologies Inc.

16 Class 2 Redundant Components Alternate Source Alternate Source Transfer Utility Electrical Distribution N+1 Chillers, Pumps & Condensers Static Bypass UPS UPS Carrier Piping and valve redundancy not required outside computer room. PDU Critical Maint. Bypass Non-Critical Edge Edge Internet Refer to Chiller Piping and Valve Redundancy section for computer room recommendations N CRAH Modules Core RPP A Aggregation +1 CRAH Module More than N+1 redundancy is recommended as the number of modules to meet N increases A 1 A 2 Access Switch Server 1 Server n NAS Disk Array Large Frame Processing A POU B POU Disk Array A PSU B PSU 2013 Isaak Technologies Inc.

17 Class 3 Concurrent Maintainability Utility Alternate Source Alternate Source Electrical Distribution Electrical Distribution Static Bypass UPS UPS N+1 Chillers, Pumps & Condensers Output Distribution Switchboard Maint. Bypass Alternate Switchboard Carrier 1 Carrier 1 Carrier 2 Carrier 2 Piping and valve redundancy not required, but recommended, outside computer room. PDU Switchboard Switchboard PDU Edge1 Edge1 Internet Edge2 Internet Edge2 Critical Fans/Pumps Core1 Core2 Non-Critical Critical Non-Critical Aggregation1 Aggregation2 N CRAH Modules PDU A1 RPP A1 PDU B1 RPP B1 Access Switch 1 Server 1 Server n Access Switch 2 Large Frame Processing NAS Disk Array Refer to Chiller Piping and Valve Redundancy section for computer room recommendations RPP A1 1 RPP A1 2 RPP B1 1 RPP B1 2 SAN Switch1 SAN Switch2 +1 CRAH Module More than N+1 redundancy is recommended as the number of modules to meet N increases STS A STS B A B Disk Array1 Disk Array n POU POU A PSU B PSU 2013 Isaak Technologies Inc.

18 Class 4 Fault Tolerant Utility Alternate Source Alternate Source Utility Alternate Source Alternate Source Electrical Distribution Electrical Distribution N+2 Chillers, Pumps & Condensers Static Bypass UPS UPS Maint. Bypass Static Bypass UPS UPS Maint. Bypass Piping and valve redundancy required outside computer room. Output Distribution Switchboard Output Distribution Switchboard Carrier 1 PDU Critical Fans/Pumps PDU Edge1 Carrier 1 Carrier 2 Edge1 Edge2 Internet Internet Carrier 2 Edge2 N CRAH Modules Non-Critical Critical Non-Critical Core1 Core2 Refer to Chiller Piping and Valve Redundancy section for computer room recommendations Aggregation1 Aggregation2 PDU A1 PDU A2 PDU B1 PDU B2 RPP 1 Panel A Panel B RPP 2 Panel A Panel B Access Switch 1 Server 1 Server n Access Switch 2 Large Frame Processing NAS Disk Array +2 CRAH Module More than N+2 redundancy is recommended as the number of modules to meet N increases RPP 1A 1 RPP 1B 1 STS A RPP 2A 1 RPP 2B 1 SAN Switch1 SAN Switch2 STS B A B POU POU Disk Array1 Disk Array n A PSU B PSU 2013 Isaak Technologies Inc.

19 End to End Reliability Applications Systems Network Cabling Infrastructure Facility Applications Data Processing & Storage Systems Network Cabling Infrastructure Facility

20 DC125 Data Center Design Course 4 Day Course In Depth Review of Standard Prepare for DCDC Exam Data Center Design Consultant Contact FiberOpto Asia Pte Ltd for course dates and locations available in South East Asia

21 BICSI Data Center Documents ANSI/BICSI Data Center Design and Implementation Best Practices BICSI International Standards Supplemental Information 001 Methodology for Selecting Data Center Design Class Utilizing Performance Criteria Available from BICSI

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD Data Center Standards Roundup BICSI, TIA, CENELEC, ISO Steve Kepekci, RCDD Introduction Regardless of business activity or size, all information technology (IT) groups have similar needs Provide secure,

More information

Data Center Commissioning: What you need to know

Data Center Commissioning: What you need to know Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,

More information

Building a Tier 4 Data Center on a Tier 1 Budget

Building a Tier 4 Data Center on a Tier 1 Budget Building a Tier 4 Data Center on a Tier 1 Budget A Walk Through of TIA-942 Peter P. Charland III, RCDD/NTS/WD, CET RTKL Associates Inc. March 27, 2008 BICSI South Central Region Meeting Denver, CO TIA-942

More information

plantemoran.com {Data center. } Design standards

plantemoran.com {Data center. } Design standards plantemoran.com {Data center. } Design standards IT systems have become critical for the day-to-day operations of today s organizations. {Data center.} Design standards IT systems are critical for the

More information

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

How To Determine Data Center Reliability

How To Determine Data Center Reliability DATA CENTER INDUSTRY WHITE PAPER Data Center Services End-To-End Reliability Published by: Isaak Technologies, Inc. TABLE OF CONTENTS 1. Overview... 1 2. Reliability Classifications... 2 Reliability Class-0...

More information

COMMODITIZING THE DATACENTER. Exploring the Impacts of the Shift to Virtualization and Cloud Computing

COMMODITIZING THE DATACENTER. Exploring the Impacts of the Shift to Virtualization and Cloud Computing COMMODITIZING THE DATACENTER Exploring the Impacts of the Shift to Virtualization and Cloud Computing 3/5/2015 AGENDA Changing Environments What Is The Datacenter Why Do We Use Them Adapting To A Changing

More information

Data Center Management. Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM

Data Center Management. Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM Data Center Management Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM A physical place that houses a computer network's most critical systems, including back-up power supplies, air conditioning, and

More information

DATA CENTER CABLING DESIGN FUNDAMENTALS

DATA CENTER CABLING DESIGN FUNDAMENTALS DATA CENTER CABLING DESIGN FUNDAMENTALS Telecommunications Cabling Infrastructure Requirements according to the Availability Classes I-IV of Abstract INTRODUCTION With the completion by end of 2015, the

More information

Specialty Environment Design Mission Critical Facilities

Specialty Environment Design Mission Critical Facilities Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,

More information

Only a matter of power supply and air conditioning? Joachim Faulhaber TÜV Informationstechnik GmbH

Only a matter of power supply and air conditioning? Joachim Faulhaber TÜV Informationstechnik GmbH Data Center Availability Only a matter of power supply and air conditioning? Joachim Faulhaber TÜV Informationstechnik GmbH Agenda Security Assessment Uptime Approach Risks and Threats Availability Principles

More information

BICSI NxtGEN & Global Data Center Standards Update

BICSI NxtGEN & Global Data Center Standards Update BICSI NxtGEN & Global Data Center Standards Update Bob Faber, RCDD/NTS Siemon Global Accounts Manager Chair NEMA High Performance Wire & Cable Chair BICSI Standards Committee Vice Chair BICSI TI&M Committee

More information

Uptime Institute Tier Classification System & Operational Sustainability

Uptime Institute Tier Classification System & Operational Sustainability Uptime Institute Tier Classification System & Operational Sustainability April 17, 2012 Dana L. Smith data center management and engineering consultants http://uptimeinstitute.com/professional-services

More information

Data Center Designs and Hospital Operations

Data Center Designs and Hospital Operations Data Center Designs and Hospital Operations Designing for Data Center Availability and the Effect on Daily Operations Joe Harris, PE, RCDD Senior Engineer, AECOM Data Centers and Hospitals June 10, 2015

More information

A Quick Primer on Data Center Tier Classifications

A Quick Primer on Data Center Tier Classifications A Quick Primer on Data Center Tier Classifications What You Should Know Before Starting a Data Center Project White Paper Abstract Data center facility projects are often driven by the Uptime Institute

More information

Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group

Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group The data center industry has experienced several evolutions over the past 20 years. One principal change has been the development of the

More information

Data Center Availability Class Summary

Data Center Availability Class Summary Data Center Availability Class Summary The following availability classifications and reliability characteristics for data center facilities is incorporated in the recently published ANSI/BICSI Data Center

More information

Data Center Colocation Build vs. Buy

Data Center Colocation Build vs. Buy Data Center Colocation Build vs. Buy Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for

More information

C24 - Inside the Data Center Andrew J. Luca

C24 - Inside the Data Center Andrew J. Luca C24 - Inside the Data Center Andrew J. Luca Inside the Data Center What an auditor needs to know Course Objectives Understand the looks and feel of a data center Know what to look for and what questions

More information

Introduction to Datacenters & the Cloud

Introduction to Datacenters & the Cloud Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview

More information

BICSI Data Center Standard. Presented by: Stephen Banks, RCDD CDCDP

BICSI Data Center Standard. Presented by: Stephen Banks, RCDD CDCDP BICSI Data Center Standard Presented by: Stephen Banks, RCDD CDCDP BICSI Data Center Standard BICSI 002, Data Center Design and Implementation Best Practices Used in conjunction with other standards ANSI/TIA-942

More information

TIA-942 Data Centre Standards Overview WHITE PAPER

TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and

More information

Tier Standards. Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI. Consultant EMEA

Tier Standards. Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI. Consultant EMEA Tier Standards Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI Consultant EMEA Uptime Institute Unbiased and vendor neutral Global thought leadership for the data center industry Founded 1993 Standards and

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center

More information

Hosting Infrastructure. Overview and Benefits of Hosting Infrastructure

Hosting Infrastructure. Overview and Benefits of Hosting Infrastructure Hosting Infrastructure Overview and Benefits of Hosting Infrastructure Data Centre definition In it's simplest form, a data centre is a facility that houses IT equipment Servers, and networking kit. The

More information

ABOUT ANIXTER UNIVERSITY

ABOUT ANIXTER UNIVERSITY Q3 2015 ABOUT ANIXTER UNIVERSITY Anixter University TM is the educational initiative of Anixter, a leading global supplier of communications and security products, electrical and electronic wire and cable,

More information

The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements

The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements Edward P Rafter, P.E. CxAP Tier IV Consulting Group Synopsis The data center industry has experienced

More information

So you want to build a data centre? Look what s coming from BICSI! Matt Flowerday Capitoline FZC mflowerday@capitoline.org

So you want to build a data centre? Look what s coming from BICSI! Matt Flowerday Capitoline FZC mflowerday@capitoline.org So you want to build a data centre? Look what s coming from BICSI! Matt Flowerday Capitoline FZC mflowerday@capitoline.org So you want to build a data centre? Who do you contact? How do you work out what

More information

Data Center Site Infrastructure Tier Standard: Topology

Data Center Site Infrastructure Tier Standard: Topology U P T I M E I N S T I T U T E, L L C Data Center Site Infrastructure Tier Standard: Topology Prepared by Uptime Institute Professional Services, LLC Copyright 2010 by Uptime Institute, LLC 20 West 37th

More information

Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc jew@j-and-m.com

Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc jew@j-and-m.com Data Center Standards Making Progress on Many Fronts Jonathan Jew J&M Consultants, Inc jew@j-and-m.com J&M Consultants - 2008 Speaker Jonathan Jew Co-chair TIA TR-42.1.1 Data Center working group ANSI/TIA-942

More information

The Aspect Unified IP Five 9s Environment

The Aspect Unified IP Five 9s Environment Technical Overview The Aspect Unified IP Five 9s Environment Technical Overview Aspect Unified IP 7 is a next-generation customer contact solution that enables companies to interact with consumers through

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

Sovereign. The made to measure data centre

Sovereign. The made to measure data centre Sovereign D ATA C O N N E C T The made to measure data centre Prime Location Within touching distance of everything that s important. 2 Your Customer-Centric Data Centre For the vast majority of organisations

More information

Introduction to IT Infrastructure Components and Their Operation. Balázs Kuti

Introduction to IT Infrastructure Components and Their Operation. Balázs Kuti Introduction to IT Infrastructure Components and Their Operation Balázs Kuti Agenda Challenges faced by enterprises today, scale of the IT plant Diversity of an IT plant Key Server Infrastructure Components

More information

Building a data center. C R Srinivasan Tata Communications

Building a data center. C R Srinivasan Tata Communications Building a data center C R Srinivasan Tata Communications Introduction Data Center as defined by TIA 942 A building or a portion of a building whose primary function is to house a computer room and its

More information

Electrical Systems. <Presenter>

Electrical Systems. <Presenter> Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF

More information

Consulting Engineering Outsourcing

Consulting Engineering Outsourcing Consulting Engineering Outsourcing Opportunities, challenges and strategies 5.º Fórum Lusófono das Comunicações Maputo, 24 de Abril de 2014 Maksen 2014 Consulting Engineering Outsourcing AGENDA 01. Data

More information

Data Center Cabling Design Trends

Data Center Cabling Design Trends Data Center Cabling Design Trends BICSI Regional Meeting Maurice Zetena Fiber Connect Infrastructure Trends Infrastructure Trends Any to All Trunk Cabling Trends: Data Center Infrastructure Media Choice:

More information

Blackboard Managed Hosting SM Disaster Recovery Planning Document

Blackboard Managed Hosting SM Disaster Recovery Planning Document BLACKBOARD MANAGED HOSTING Blackboard Managed Hosting SM Disaster Recovery Planning Document Prepared By: MH Services Modified Date: March 2009 Revision: 1.8 1. OBJECTIVES... 3 2. SCOPE... 3 3. ASSUMPTIONS...

More information

How To Design A Data Center

How To Design A Data Center Data Center Design & Virtualization Md. Jahangir Hossain Open Communication Limited jahangir@open.com.bd Objectives Data Center Architecture Data Center Standard Data Center Design Model Application Design

More information

SPECIALIST IN DATA CENTRE & BUSINESS CONTINUITY SOLUTIONS

SPECIALIST IN DATA CENTRE & BUSINESS CONTINUITY SOLUTIONS SPECIALIST IN DATA CENTRE & BUSINESS CONTINUITY SOLUTIONS WE GIVE YOU THE COMPETITIVE EDGE In today s fast paced business world, one cannot overemphasise the need to expect the unexpected. While no system

More information

DDesign collaboration between the owner/operator. Good things happen when the design team organizes around a plan. BY KEITH LANE

DDesign collaboration between the owner/operator. Good things happen when the design team organizes around a plan. BY KEITH LANE Good things happen when the design team organizes around a plan. BY KEITH LANE Keith Lane has over 20 years of experience in the design and implementation of mission-critical facilities. He is a professional

More information

Expert Reference Series of White Papers. Understanding Data Centers and Cloud Computing

Expert Reference Series of White Papers. Understanding Data Centers and Cloud Computing Expert Reference Series of White Papers Understanding Data Centers and Cloud Computing 1-800-COURSES www.globalknowledge.com Understanding Data Centers and Cloud Computing Paul Stryer, Global Knowledge

More information

OVERVIEW. CEP Cluster Server is Ideal For: First-time users who want to make applications highly available

OVERVIEW. CEP Cluster Server is Ideal For: First-time users who want to make applications highly available Phone: (603)883-7979 sales@cepoint.com Cepoint Cluster Server CEP Cluster Server turnkey system. ENTERPRISE HIGH AVAILABILITY, High performance and very reliable Super Computing Solution for heterogeneous

More information

FLEXIBILITY THROUGH STABILITY

FLEXIBILITY THROUGH STABILITY DATACENTER FLEXIBILITY THROUGH STABILITY Your ICT environment, and your organization with it, hinges on your datacenter. Your MER, SER or datacenter not only has to guarantee the storage of huge amounts

More information

Data Center Site Infrastructure Tier Standard: Topology

Data Center Site Infrastructure Tier Standard: Topology U P T I M E I N S T I T U T E, L L C Data Center Site Infrastructure Tier Standard: Topology Prepared by Uptime Institute Professional Services, LLC Copyright 2009-2012 by Uptime Institute, LLC 20 West

More information

How To Write An Infrastructural Standard For Data Center Infrastructure

How To Write An Infrastructural Standard For Data Center Infrastructure Infrastructure Standard for Data Centers ANSI/CSA/EIA/TIA-942 (PN-3-0092) Introduction When approved, the standard will be: ANSI/CSA/EIA/TIA-942 Telecommunications Infrastructure Standard for Data Centers

More information

NIGERIA S PREMIUM DATA CENTRE

NIGERIA S PREMIUM DATA CENTRE NIGERIA S PREMIUM DATA CENTRE TIER III DESIGN CERTIFIED SECURE RELIABLE SCALABLE 1 WHY WOULD YOU WANT TO BUILD A DATA CENTRE? IT TAKES MILLIONS OF US DOLLARS TO BUILD AN EFFICIENT DATA CENTRE. A KEY ASSET,

More information

Cloud Based Document Management

Cloud Based Document Management Cloud Based Document Management WHY IS THE CLOUD IMPORTANT? The Information Explosion It is the information that is setting up competitive differentiation, not specifically products and processes. It is

More information

University of Central Florida Class Specification Administrative and Professional. Network Operations Manager (Enterprise)

University of Central Florida Class Specification Administrative and Professional. Network Operations Manager (Enterprise) Network Operations Manager (Enterprise) Job Code: 2552 Manage enterprise networks. Oversee the monitoring, testing, and trouble shooting of all network components (network software and hardware and network

More information

International Standards for Data Centre Electrical Design. Developed from The Uptime Institute & TIA942 concepts

International Standards for Data Centre Electrical Design. Developed from The Uptime Institute & TIA942 concepts International Standards for Data Centre Electrical Design Developed from The Uptime Institute & TIA942 concepts Benchmarking Data-Centre Quality There has long been the need to be able to measure the quality

More information

Designing Fault-Tolerant Power Infrastructure

Designing Fault-Tolerant Power Infrastructure Designing Fault-Tolerant Power Infrastructure System Analysis and New Standards Enable Maximization of Operating Dependability for Data Centers & Other Mission Critical Facilities J.F. Christin (Author)

More information

Data Centers, Information Technology and Low Current Services

Data Centers, Information Technology and Low Current Services Data Centers, Information Technology and Low Current Services 1 Data Centers and Low Current Services SDT offers a wide-ranging variety of professional services to Data Centres and Low Current operators.

More information

How to Meet 24 by Forever Cooling Demands of your Data Center

How to Meet 24 by Forever Cooling Demands of your Data Center W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the

More information

PAYGO for Data Center -- Modular Infrastructure

PAYGO for Data Center -- Modular Infrastructure PAYGO for Data Center -- Modular Infrastructure Introduction The infrastructure costs for Data Centers are increasing at a significant pace. Construction costs and their environmental impact are also soaring.

More information

COMMODITIZING THE DATA CENTER MARKET

COMMODITIZING THE DATA CENTER MARKET COMMODITIZING THE DATA CENTER MARKET Site Summary The building at 1360 Kifer Road has approximately 94,500 SF of server and support space and is currently divided into two independent data center areas.

More information

Applying Data Center Infrastructure Management in Collocation Data Centers

Applying Data Center Infrastructure Management in Collocation Data Centers Applying Data Center Infrastructure Management in Collocation Data Centers Infrastructure Management & Monitoring for Business-Critical Continuity TM Applying Data Center Infrastructure Management (DCIM)

More information

South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime

South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime GPX India Pvt Ltd The Leader In Carrier Neutral TIER IV IDC s In Emerging Markets Incorporated in

More information

DISTRIBUTED REDUNDANCY:

DISTRIBUTED REDUNDANCY: DISTRIBUTED REDUNDANCY: MAXIMUM AVAILABILITY AT MINIMAL COST A White Paper by: Liebert Corporation As the need for greater system availability intensifies across virtually every industry from global banking

More information

Data Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s"

Data Centre Issues supported in TIA-942 : Telecommunications Infrastructure for Data Centre s Data Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s" Data centre Standard EN50173-5 : "Telecommunications Infrastructure for Data Centre s Due, 2006 Gary Highton,

More information

Advanced Fire Protection in Data Centres

Advanced Fire Protection in Data Centres Advanced Fire Protection in Data Centres Jeff Klein, Honeywell Life Safety, 26 June 2012, Copyright 2012 System Sensor Europe. All rights reserved. The Challenge for Mission Critical Data Centres Fuel

More information

OPERATOR - FACILITY ADDRESS - DATE

OPERATOR - FACILITY ADDRESS - DATE . Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.

More information

South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime

South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime GPX India Pvt Ltd The Leader In Carrier Neutral TIER IV IDC s In Emerging Markets Incorporated in August 2002,

More information

Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company

Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company Data Centre Cabling 20 August 2015 Stefan Naude RCDD The SIEMON Company Agenda 1. Data Centre Standards 2. The Need for Speed 3. Copper in the Data Centre 4. Fibre in the Data Centre 5. Top of Rack vs

More information

ADVANCED NETWORK CONFIGURATION GUIDE

ADVANCED NETWORK CONFIGURATION GUIDE White Paper ADVANCED NETWORK CONFIGURATION GUIDE CONTENTS Introduction 1 Terminology 1 VLAN configuration 2 NIC Bonding configuration 3 Jumbo frame configuration 4 Other I/O high availability options 4

More information

30-120 3 Phase Modular Finally the benefits of Modular ups are for all

30-120 3 Phase Modular Finally the benefits of Modular ups are for all MUST 30-120 3 Phase Modular UPS Finally the benefits of Modular ups are for all MUST 30-120 MUST means Modular UPS System Three-phase MUST 30-120 is an uninterruptible power supply with double conversion

More information

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Unified Physical Infrastructure (UPI) Strategies for Thermal Management Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting

More information

Contents. Foreword. Acknowledgments

Contents. Foreword. Acknowledgments Foreword Preface Acknowledgments xv xvii xviii CHAPTER 1 Introduction 1 1.1 What Is Mission Critical? 1 1.2 Purpose of the Book 2 1.3 Network Continuity Versus Disaster Recovery 2 1.4 The Case for Mission-Critical

More information

Zone Distribution in the Data Center

Zone Distribution in the Data Center Zone Distribution in the Data Center By Jennifer Cline, RCDD As data centers face the continued need to expand and grow, the fundamental concerns and needs remain constant. Key concerns of the data cabling

More information

Statement Of Work. Data Center Thermography Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary

Statement Of Work. Data Center Thermography Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary Statement Of Work Professional Services Data Center Thermography Assessment Data Center Thermography Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits

More information

Qualitative Analysis of Power Distribution Configurations for Data Centers

Qualitative Analysis of Power Distribution Configurations for Data Centers Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,

More information

Colocation, Hot Seat Services, Disaster Recovery Services, Secure and Controlled Environment

Colocation, Hot Seat Services, Disaster Recovery Services, Secure and Controlled Environment Colocation, Hot Seat Services, Disaster Recovery Services, Secure and Controlled Environment 3 Company Overview Confisio DataCenter was formed to help organisations tackle the ever increasing challenges

More information

ASSET Connect. The next level in Critical Environment Operational Efficiency

ASSET Connect. The next level in Critical Environment Operational Efficiency Connect The next level in Critical Environment Operational Efficiency 10-30% is the potential efficiency gain from optimized Data Centers and Critical Environments Operational Efficiency of Your Critical

More information

Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011

Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011 Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011 Opportunities in Automating Infrastructure Why Automation in Data Center? Tiers, compartments and complexity Work

More information

Tier Classification of Data Centres. Eric Maddison Senior Consultant, The Uptime Institute

Tier Classification of Data Centres. Eric Maddison Senior Consultant, The Uptime Institute Tier Classification of Data Centres Eric Maddison Senior Consultant, The Uptime Institute Uptime Institute Unbiased and vendor neutral Global thought leadership for the data center industry Founded 1993

More information

TÓPICOS AVANÇADOS EM REDES ADVANCED TOPICS IN NETWORKS

TÓPICOS AVANÇADOS EM REDES ADVANCED TOPICS IN NETWORKS Mestrado em Engenharia de Redes de Comunicações TÓPICOS AVANÇADOS EM REDES ADVANCED TOPICS IN NETWORKS 2009-2010 Projecto de Rede / Sistema - Network / System Design 1 Hierarchical Network Design 2 Hierarchical

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

Subject: County of Los Angeles Data Center Space Requirement

Subject: County of Los Angeles Data Center Space Requirement Subject: County of Los Angeles Data Center Space Requirement The County of Los Angeles, Chief Executive Office, Real Estate Division (CEO-RED) is issuing this Property Search for the purchase of a vacant,

More information

Data Center Infrastructure & Managed Services Outline

Data Center Infrastructure & Managed Services Outline Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists

More information

Auditing a data centre but to what standard?

Auditing a data centre but to what standard? Auditing a data centre but to what standard? Matt Flowerday RCDD Capitoline LLP mflowerday@capitoline.co.uk www.capitoline.me Data centre auditing Capitoline has audited over 30 data centres in the UK,

More information

Which Data Center? Key factors in choosing who to trust with your IT Infrastructure

Which Data Center? Key factors in choosing who to trust with your IT Infrastructure Which Data Center? Key factors in choosing who to trust with your IT Infrastructure Tarif Abboushi Vice-President of Data Center Infrastructure NTT America May, 2009 Which Data Center? Key factors in choosing

More information

The Pros and Cons of Modular Systems

The Pros and Cons of Modular Systems The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated

More information

Certified TIA-942 Tier IV Data Center

Certified TIA-942 Tier IV Data Center Certified TIA-942 Tier IV Data Center Beltsville, MD AiNET 11710 Montgomery Road Beltsville, MD 20705 USA www.ai.net Data Center Standard TIA-942 Developed by Telecommunications Industry Association Leading,

More information

Tier Classifications Define Site Infrastructure Performance

Tier Classifications Define Site Infrastructure Performance W h i t e P a p e r Tier Classifications Define Site Infrastructure Performance By W. Pitt Turner IV, PE, John H. Seader, PE, Vince Renaud, PE, and Kenneth G. Brill Table of Contents Executive Summary...

More information

ENTERPRISE VIRTUALIZATION ONE PLATFORM FOR ALL DATA

ENTERPRISE VIRTUALIZATION ONE PLATFORM FOR ALL DATA ENTERPRISE VIRTUALIZATION ONE PLATFORM FOR ALL DATA ENTERPRISE VIRTUALIZATION ONE PLATFORM FOR ALL DATA SUMMARY ONE PLATFORM FOR ALL DATA WOULD YOU LIKE TO SAVE 20% TO 30% ON YOUR STORAGE SPEND? We can

More information

Opportunity of Energy Saving in electrical path is lesser as compared to other areas

Opportunity of Energy Saving in electrical path is lesser as compared to other areas Data Centre Power Map ` Energy Optimization Techniques Data Center Power Chain Venkat Rao B Country Manager Power Products Data Center Power Draws Cooling About 35 40 % Sources of Energy Waste Fans / Blowers

More information

Presented By: David J. Musto, Principal Thermo Systems L.L.C. East Windsor, NJ USA

Presented By: David J. Musto, Principal Thermo Systems L.L.C. East Windsor, NJ USA Designing Secure, Redundant Fiber Optic Networks for District Energy Systems: A case study of the Lulu Island network design in Manama, Kingdom of Bahrain. Presented By: David J. Musto, Principal Thermo

More information

Siemon 10G ip. Data Centre Solution WHITE PAPER. Executive Summary

Siemon 10G ip. Data Centre Solution WHITE PAPER. Executive Summary Siemon 10G ip Data Centre Solution Executive Summary The term data centre conjures up different meanings to different people. Some would argue that the data centre is the room where the servers are stored.

More information

Virtualizing the SAN with Software Defined Storage Networks

Virtualizing the SAN with Software Defined Storage Networks Software Defined Storage Networks Virtualizing the SAN with Software Defined Storage Networks Introduction Data Center architects continue to face many challenges as they respond to increasing demands

More information

Applications for Infrared Thermography at Computer Centers

Applications for Infrared Thermography at Computer Centers Applications for Infrared Thermography at Computer Centers By Eric Stockton CompuSCANIR, a division of Stockton Infrared Thermographic Services, Inc. 8472 Adams Farm Road Randleman, NC 27317 http://www.compuscanir.com/

More information

The Application of Circuit Breakers to Reduce Downtime in Datacentres

The Application of Circuit Breakers to Reduce Downtime in Datacentres The Application of Circuit Breakers to Reduce Downtime in Datacentres Tim Campbell BEng MIET. Marketing Manager, Terasaki Electric (Europe) Ltd. Abstract Circuit breakers fulfil several functions in the

More information

IKS Data Centres Conference Moscow 6 th September 2011 Mark Acton

IKS Data Centres Conference Moscow 6 th September 2011 Mark Acton IKS Data Centres Conference Moscow 6 th September 2011 Mark Acton data center management and engineering consultants professionalservices.uptimeinstitute.com 2011 Uptime Institute Professional Services,

More information

Tier Classifications Define Site Infrastructure Performance

Tier Classifications Define Site Infrastructure Performance By W. Pitt Turner IV, P.E., John H. Seader, P.E., and Kenneth G. Brill Widely accepted within the uninterruptible industry, The Uptime Institute s Tier Performance Standards are an objective basis for

More information

Modern Data Centers: Creating a New Value Proposition

Modern Data Centers: Creating a New Value Proposition Modern Data Centers: Creating a New Value Proposition América Latina 2008 Inter-secretarial Commission for the Development of Electronic Government Mexico City 24 May 2013 Data Center Consolidation Consolidating

More information

How To Connect Virtual Fibre Channel To A Virtual Box On A Hyperv Virtual Machine

How To Connect Virtual Fibre Channel To A Virtual Box On A Hyperv Virtual Machine Virtual Fibre Channel for Hyper-V Virtual Fibre Channel for Hyper-V, a new technology available in Microsoft Windows Server 2012, allows direct access to Fibre Channel (FC) shared storage by multiple guest

More information

White Paper. Optimizing the SAN Fiber Optic Physical Layer in Your Data Center

White Paper. Optimizing the SAN Fiber Optic Physical Layer in Your Data Center White Paper October 2012 Optimizing the SAN Fiber Optic Physical Layer in Your Data Center Deploying a structured cabling system for the SAN provides measurable results and long term value, whether you

More information

On Reliability of COTS Hardware

On Reliability of COTS Hardware On Reliability of COTS Hardware Dr. Li Mo Chief Architect, CTO Group Agenda Differences between Telecom Hardware and COTS Hardware Analysis Framework Enhancing ApplicaAon Reliability via Backups TheoreAcal

More information