Data Center Commissioning: What you need to know

Size: px
Start display at page:

Download "Data Center Commissioning: What you need to know"

Transcription

1 Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E., CxA, ATD Power Management Corporation

2 AIA Stuff: 2 Credit(s) earned on completion of this course will be reported to AIA CES for AIA members. Certificates of Completion for both AIA members and non-aia members are available upon request. This course is registered with AIA CES for continuing professional education. As such, it does not include content that may be deemed or construed to be an approval or endorsement by the AIA of any material of construction or any method or manner of handling, using, distributing, or dealing in any material or product.

3 Course Description 3 Data centers have become a critically important facility type in our modern economy. Because of their unique requirements, commissioning them properly requires some specific knowledge and skills. This practical session will discuss uptime tier classifications, working in live data centers, balancing reliability vs efficiency, and much more. Also featured will be a review of example datacenter-specific functional performance and integrated system tests.

4 Learning Objectives: 4 At the end of this course, participants will. 1. Be familiar with the Uptime Institute Tier classifications 2. Understand the 5 levels of data center Cx 3. Be able to differentiate Integrated Systems Testing from Functional Performance Testing 4. Understand challenges associated with Cx in a live data center

5 Data Center 5 A facility used to house computer systems and associated components, such as telecommunications and storage systems. It generally includes redundant or backup power supplies, redundant data communications connections, environmental controls (e.g., air conditioning, fire suppression) and various security devices.- -Wikipedia 2015 Internet Enterprise Telecommunications Colocation (wholesale and retail) Server/computer room Telecom closets

6 Critical Infrastructure 6 Physical systems designed and constructed specifically to support the hardware, network, and applications that make up the data center : Electrical Power Mechanical Cooling Fire Suppression Automation Monitoring

7 Critical Infrastructure 7 Building Automation System UPS systems Chillers Power Distribution Modules Cooling Towers Remote Power Panels Pumps/VFDs/Loop Critical Distribution Busway Outside Air Units EPO Economizers CRAHs/CRACs/IRCs Makeup water and Pressure reducer valves Power and Environmental Monitoring Systems Liquid Detection Systems Lighting Control Systems Electrical Substations Generators and Fuel Delivery Systems Fire Alarm and Detection Systems Preaction Sprinkler Systems Transfer gear/ats Distribution Switchboards/Switchgear Gaseous Fire Suppression Systems

8 Capacity Component 8 Capacity Component is any power producing and energy storage equipment, such as: Electrical power generator UPS and Battery system Chiller Cooling Tower Chilled water pump CRAC/CRAH units Fuel storage Water Storage

9 Distribution path 9 A distribution path is the means by which the power is transferred from the capacity component to the load, such as: Transformers Electrical feeders ATS, Switchgear, PDUs Hydronic piping Refrigerant piping Valves

10 ITEQ Load 10 The load (expressed in Kilo-Watts) of the users Information Technology Equipment. What s in The Rack. Telecommunications provider equipment Firewalls Routers Network switches Servers Storage arrays (SANs) And others..

11 11 Uptime Institute Tier Classification System

12 Uptime Institute Tier Classification System 12 An International Standard developed by The UTI that defines criteria for the critical infrastructure design based on four levels of classification: Tier I Basic Capacity Tier II Redundant Capacity Components Tier III Concurrently Maintainable Tier IV Fault Tolerant/Continuous Cooling

13 Uptime Institute Tier Classification System 13 Tier levels are defined at a specific ITEQ load using ASHRAE Handbook Extreme outdoor design conditions for the specific location (n=20 years) Nashville, TN Typical Cooling Design (0.4%) = 94.4 DB Extreme (20 year high) = DB Las Vegas, NV Typical Cooling Design (0.4%) = DB Extreme (20 year high) = DB

14 Uptime Institute - Tier I 14 Tier I Basic Capacity Self sustaining for 12 hours - Does not rely on utilities Number and size of capacity components is sufficient to maintain the operation of the business between maintenance intervals Maintenance requires shutting down the data center Subject to planned and un-planned outages

15 Uptime Institute - Tier I hour Water Storage N Generator(s)

16 Uptime Institute - Tier I 16 N Chiller(s) N AC Unit(s)

17 Uptime Institute - Tier I Electrical Oneline 17 From UTI white paper: Tier Classifications Define Site Infrastructure Performance Note: Example only, not prescriptive

18 Uptime Institute - Tier II 18 Tier II Redundant Capacity Components Tier I, plus: Number of capacity components provides redundancy (N+1) for: unexpected failure maintenance without system shutdown Maintenance of pathways requires shutdown Subject to planned and un-planned outages

19 Uptime Institute - Tier II 19 N+1 UPS N+1 Generators

20 Uptime Institute - Tier II 20 N+1 Chillers N+1 Cooling Towers

21 Uptime Institute - Tier II Electrical Oneline 21 From UTI white paper: Tier Classifications Define Site Infrastructure Performance Note: Example only, not prescriptive

22 Uptime Institute - Tier III 22 Tier III Concurrently Maintainable Tier II, plus: Multiple distribution pathways for power and cooling (one may be passive) All IT equipment has redundant power supplies Generator must be rated for continuous operation Each and Every single component and distribution pathway can be removed for service/replaced without shutting down the data center Maintenance requires shudown

23 Uptime Institute - Tier III 23 Double Isolation Valves

24 Uptime Institute - Tier III Redundant Pathways 24

25 Uptime Institute - Tier III Redundant Pathways 25

26 Uptime Institute - Tier III 26 Main-Tie-Tie-Main

27 Uptime Institute - Tier III Electrical Oneline 27 From UTI white paper: Tier Classifications Define Site Infrastructure Performance Note: Example only, not prescriptive

28 Uptime Institute - Tier IV 28 Tier IV Fault Tolerant Tier III, plus: Multiple distribution paths - both active Compartmentalization between redundant components/pathways Class-A Continuous Cooling is required Failures are self healing Unexpected failure of any single component will not interrupt the operation of the data center The site is not subject to outages from a planned event, or a single unplanned event

29 Uptime Institute - Tier IV 29 Continuous Cooling during loss of utility

30 Uptime Institute - Tier IV 30 Compartmentalization

31 Uptime Institute - Tier IV Electrical Oneline 31 From UTI white paper: Tier Classifications Define Site Infrastructure Performance Note: Example only, not prescriptive

32 Uptime Institute Tier Availability Matrix 32 Planned Shutdowns for maintenance* Unplanned Equipment or Distribution Failures ** Tier I Tier II Tier III Tier IV 2 every year 1.2 per year 3 every 2 years Not required 1 per year 1 every 2.5 years Not Required 1 every 5 years Annual hours of downtime** Availability 99.67% 99.75% 99.98% 99.99% * Based on recommended practice ** Historical data from Uptime Institute members Source: Data Center Site Infrastructure Tier Standard: Topology Uptime Institute, LLC

33 33 Data Center Commissioning aka Level 5 Commissioning

34 Level 5 Commissioning 34 Level 0: Design Review Level 1: Planning Level 2: Factory Acceptance Testing Level 3: Pre-Functional Inspections/Startup Level 4: Functional Testing Level 5: Integrated Systems Testing

35 Level 0: Design Review 35 CxA will assist with defining the OPR: What is your target ITEQ Load? What are your Resiliency Goals (Tier Level)? Phasing? How will the site be tested? Make sure testing requirements are in the specifications Photo source:

36 Level 0: Design Review 36 Review the Basis of Design: Compare to OPR Sequence of operations Piping flow diagram Electrical oneline diagram Back-check at CDs

37 Level 0: Design Review A few pointers regarding controls: 37 Keep sequences simple Fewer control points means fewer failures Consider resiliency vs. efficiency The fallacy of UPS backup All capacity components should self sustainable

38 Level 1: Planning 38 Begins in design phase Prepare outline of testing scripts Test for maintenance modes (Tier III) Test for failure modes (Tier IV)

39 Level 1: Planning 39 Load bank placement for heat run test? How will the different failure modes be tested? How does the testing plan integrate with construction schedule?

40 Level 1: Planning 40 Existing Data Center Modifications: Identify Critical MOPS (Methods of Procedure) Is the sequence of construction integrated with Cx activities? What is the user s tolerance for risk?

41 Level 2: Factory Acceptance 41 Generators Paralleling Gear UPS Systems Static Switches Chillers Custom HVAC equipment

42 Level 2: Factory Acceptance 42 Full sequence demonstrated Safeties and alarms Heat Run at full load Transients recorded Chillers: Quick Start Low load

43 Level 2: Factory Acceptance 43 Why? Testing performed by factory technicians Deficiencies identified and corrected prior to shipment Test Drive: Owner becomes familiar with system before owning it

44 Level 3: Pre-Functional Overall readiness for FPTs 44 Equipment matches submittals Installation per construction drawings SVCs complete Manufacturer startup complete Electrical Acceptance Testing Photo source:

45 Level 4: Functional Testing 45 Cooling Equipment: Controls interface Alarm notification Team-work mode Heat Run for containment systems Failure modes Run Enable Failsafe Loss of Comm Power restore

46 Level 4: Functional Performance Test 46 Example: Chiller Plant Add/Drop Chiller New DC3 Expansion (1,800 kw total ITEQ) Added a 5 th chiller to existing plant of 4 Replaced all primary CHW pumps (2N) Installed active secondary CHW loop (Tier III) Live Data Center

47 47

48 48

49 49

50 Level 4: Functional Testing 50 Generator/Transfer Equipment: Test individual generators Transients, load steps Alarm notification Thermal Imaging Test parallel gear/ats Full Heat Run at rated load Entire plant

51 Level 4: Functional Testing 51 UPS and STS Equipment: Test individual modules Inverter/Bypass Maint Bypass Battery discharge Alarm notification Thermal Imaging Test parallel gear Full Heat Run at rated load Entire plant Interaction with Generator(s)

52 Level 4: Functional Testing 52 Emergency Power Off (EPO): Document how to restore Confirm control power source Avoid normally closed circuits for UPS/PDU equipment Interface with smoke dampers Is there a way to bypass for maintenance?

53 Level 5: Integrated Systems Testing 53 Integrated System Testing is a comprehensive test protocol that incorporates all electrical power, cooling, and control functions under design load IST is typically performed over multiple days IST requires participation from all contractors, vendors, the owner s agent, and the CxA

54 Level 5: Integrated Systems Testing 54 The Prove it Phase: Heat Run: Demonstrate ability for the IT equipment rooms to carry design load under steady state design conditions Low Load Conditions: Demonstrate ability of the infrastructure to carry Day One loads at steady state design conditions

55 Level 5: Integrated Systems Testing 55 The Prove it Phase: Loss of Utilities: Demonstrate the ability to automatically react to utility outages (this is NOT a failure Tier I) Maintenance: At load, demonstrate the ability to remove capacity components (Tier II) and pathways (Tier III) from service without interruption

56 Level 5: Integrated Systems Testing 56 Perform maintenance procedures: Remove a generator/ups from the bus Power down and isolate one electrical switchboard/ups/pdu completely Shut off one Distribution panel serving multiple CRAC units Isolate a chiller /pump Simulate a valve replacement Simulate a complete BAS controls outage

57 Level 5: Integrated Systems Testing 57 The Prove it Phase: Equipment Failure: Demonstrate the ability to automatically react to unplanned equipment failures (Tier II) Pathway Failure: Demonstrate the ability to automatically react to unplanned pathway failures (Tier IV) Example: Fire in a chiller room or electrical room Assume total loss of room

58 Level 5: Integrated Systems Testing 58 Example: Pull the Plug Low Load 3 Diesel Generators in parallel Dual bus UPS system (A /B) Dual Static Transfer Switches (A/B) Air cooled Chillers (N+1) Variable Primary pumping Computer Room Air Handlers (CRAH)

59 59

60 60

61 61

62 62

63 Level 5: Integrated Systems Testing 63 Example: Heat Run and BAS failure New DC3 Expansion (1,800 kw total ITEQ) Five air-cooled chillers in parallel Four primary CHW pumps (2N) DP control (five sensors fail safe) Computer Room Air Handlers (CRAH) Live Data Center Tier III Design

64 64

65 65

66 66

67 67 Commissioning within a live data center

68 Commissioning within a live data center 68 New Equipment Commissioning Outage/failures during the testing process impact the business Full load Systems Integration Testing is sometimes not feasible without scheduled downtime (Tier I and Tier II) Medium risks Full Facility Retro-Commissioning It s was never really commissioned before Usually using live load for the test load High Risks Especially Tier I and Tier II Facilities

69 Commissioning within a live data center 69 The CxA in a mission critical project will often be expected to prepare MOPs (Methods of Procedure) for all critical steps in construction and testing The CxA is typically best suited for this role, as he/she has the best understanding of the overall risks related to the procedure Critical MOPS must be identified early in the design process Team effort Must have sign off by owner, engineers, and contractors Perform a Dry Run in advance

70 Example MOP 70

71 Example MOP LOG 71

72 Questions and Discussion 72

BICSI 002 / TIA 942 / Uptime

BICSI 002 / TIA 942 / Uptime BICSI 002 / TIA 942 / Uptime Which Data Center Standard Should I Follow Phil Isaak, PE, P.Eng., RCDD, DCDC President, Master Instructor Isaak Technologies Inc. Standards Who are these People Standards

More information

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center

More information

Commissioning of Mission Critical Facilities

Commissioning of Mission Critical Facilities Commissioning of Mission Critical Facilities Terry L. Rodgers, CPE, CPMP VP of Sustainable Operations Primary Integration Solutions Paul Liesman SVP of FM & Commissioning Syska Hennessy Group AIA Quality

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center

More information

Data Centers. Data Center Commissioning

Data Centers. Data Center Commissioning The following article was published in ASHRAE Journal, April 2005. Copyright 2005 American Society of Heating, Refrigerating and Air- Conditioning Engineers, Inc. It is presented for educational purposes

More information

Data Center Site Infrastructure Tier Standard: Topology

Data Center Site Infrastructure Tier Standard: Topology U P T I M E I N S T I T U T E, L L C Data Center Site Infrastructure Tier Standard: Topology Prepared by Uptime Institute Professional Services, LLC Copyright 2010 by Uptime Institute, LLC 20 West 37th

More information

Data Center Infrastructure & Managed Services Outline

Data Center Infrastructure & Managed Services Outline Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists

More information

Data Center Site Infrastructure Tier Standard: Topology

Data Center Site Infrastructure Tier Standard: Topology U P T I M E I N S T I T U T E, L L C Data Center Site Infrastructure Tier Standard: Topology Prepared by Uptime Institute Professional Services, LLC Copyright 2009-2012 by Uptime Institute, LLC 20 West

More information

Applications for Infrared Thermography at Computer Centers

Applications for Infrared Thermography at Computer Centers Applications for Infrared Thermography at Computer Centers By Eric Stockton CompuSCANIR, a division of Stockton Infrared Thermographic Services, Inc. 8472 Adams Farm Road Randleman, NC 27317 http://www.compuscanir.com/

More information

PAYGO for Data Center -- Modular Infrastructure

PAYGO for Data Center -- Modular Infrastructure PAYGO for Data Center -- Modular Infrastructure Introduction The infrastructure costs for Data Centers are increasing at a significant pace. Construction costs and their environmental impact are also soaring.

More information

Guide Specification SECTION 23 08 00 - COMMISSIONING OF HVAC PART 1 - GENERAL 1.1 SUMMARY

Guide Specification SECTION 23 08 00 - COMMISSIONING OF HVAC PART 1 - GENERAL 1.1 SUMMARY SECTION 23 08 00 - COMMISSIONING OF HVAC PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. HVAC Commissioning description. 2. HVAC Commissioning responsibilities. 1.2 REFERENCES A. American Society

More information

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0.

CyberFortress Data Center at Innovation Park Infrastructure and Topology Guide. Innovation Park Charlotte. NC 28262. DRAFT V0. Innovation Park Charlotte. NC 28262 DRAFT V0.1 Page 2 CyberFortress Data Center at Innovation Park BECO South purchased Innovation Park in March 2010 and immediately launched a dramatic top-to-bottom $30M

More information

Building a Tier 4 Data Center on a Tier 1 Budget

Building a Tier 4 Data Center on a Tier 1 Budget Building a Tier 4 Data Center on a Tier 1 Budget A Walk Through of TIA-942 Peter P. Charland III, RCDD/NTS/WD, CET RTKL Associates Inc. March 27, 2008 BICSI South Central Region Meeting Denver, CO TIA-942

More information

AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA)

AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) AT&T Internet Data Center Site Specification San Diego Koll (San Diego, CA) Site Biography Market Area: San Diego, CA Location: San Diego, CA 92121 Address: 5732 Pacific Center Blvd CLLI,POP, NPA/NXX Code:

More information

COMMODITIZING THE DATA CENTER MARKET

COMMODITIZING THE DATA CENTER MARKET COMMODITIZING THE DATA CENTER MARKET Site Summary The building at 1360 Kifer Road has approximately 94,500 SF of server and support space and is currently divided into two independent data center areas.

More information

Chilled Water System Commissioning: Variable Primary Flow. John D. Villani, P.E. Associate Grumman/Butkus Associates

Chilled Water System Commissioning: Variable Primary Flow. John D. Villani, P.E. Associate Grumman/Butkus Associates Chilled Water System Commissioning: Variable Primary Flow John D. Villani, P.E. Associate Grumman/Butkus Associates AIA Quality Assurance Learning Objectives 1. History of chilled water system configurations

More information

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia

Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Case Study: Innovative Energy Efficiency Approaches in NOAA s Environmental Security Computing Center in Fairmont, West Virginia Prepared for the U.S. Department of Energy s Federal Energy Management Program

More information

Tier Classification of Data Centres. Eric Maddison Senior Consultant, The Uptime Institute

Tier Classification of Data Centres. Eric Maddison Senior Consultant, The Uptime Institute Tier Classification of Data Centres Eric Maddison Senior Consultant, The Uptime Institute Uptime Institute Unbiased and vendor neutral Global thought leadership for the data center industry Founded 1993

More information

Energy Efficient High-tech Buildings

Energy Efficient High-tech Buildings Energy Efficient High-tech Buildings Can anything be done to improve Data Center and Cleanroom energy efficiency? Bill Tschudi Lawrence Berkeley National Laboratory Wftschudi@lbl.gov Acknowledgements California

More information

A Quick Primer on Data Center Tier Classifications

A Quick Primer on Data Center Tier Classifications A Quick Primer on Data Center Tier Classifications What You Should Know Before Starting a Data Center Project White Paper Abstract Data center facility projects are often driven by the Uptime Institute

More information

Fundamentals of HVAC Control Systems

Fundamentals of HVAC Control Systems ASHRAE Hong Kong Chapter Technical Workshop Fundamentals of HVAC Control Systems 18, 19, 25, 26 April 2007 2007 ASHRAE Hong Kong Chapter Slide 1 Chapter 5 Control Diagrams and Sequences 2007 ASHRAE Hong

More information

How To Write An Infrastructural Standard For Data Center Infrastructure

How To Write An Infrastructural Standard For Data Center Infrastructure Infrastructure Standard for Data Centers ANSI/CSA/EIA/TIA-942 (PN-3-0092) Introduction When approved, the standard will be: ANSI/CSA/EIA/TIA-942 Telecommunications Infrastructure Standard for Data Centers

More information

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project. DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 08 02 PART 1 GENERAL 1.01 AUTHORITY (CxA) A. The Commissioning Authority (CxA) has been contracted or will be contracted directly

More information

About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services

About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services About Injazat Injazat Data Systems is an industry-recognized market leader in the region for Information Technology Outsourcing, Cloud and Data Center Managed Services delivered from the region s 1st Tier

More information

Electrical Systems Commissioning

Electrical Systems Commissioning Electrical Systems Commissioning Catherine Melander, Questions & Solutions Engineering 21 st National Conference on Building Commissioning AIA Quality Assurance The Building Commissioning Association is

More information

Adaptive Cooling in Data Centers. Silicon Valley Leadership Group Energy Efficient Data Center Demonstration Project October, 2009

Adaptive Cooling in Data Centers. Silicon Valley Leadership Group Energy Efficient Data Center Demonstration Project October, 2009 Adaptive Cooling in Data Centers Silicon Valley Leadership Group Energy Efficient Data Center Demonstration Project October, 2009 Maximizing Cooling Efficiency in a Concurrently Maintainable and Fault

More information

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL)

AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) AT&T Internet Data Center Site Specification Chicago Area (Lisle, IL) Site Biography Market Area: Chicago, IL Location: Lisle, IL 60532 Address: 4513 Western Avenue CLLI,POP, NPA/NXX Code: LSLEILAA, EQLAILAA

More information

OPERATOR - FACILITY ADDRESS - DATE

OPERATOR - FACILITY ADDRESS - DATE . Facility Criteria (RFP).0 Location Characteristics Criteria Requirements 1 Ownership and Management: Please identify the owner(s) and managers of the property and indicate if there is on-site management.

More information

plantemoran.com {Data center. } Design standards

plantemoran.com {Data center. } Design standards plantemoran.com {Data center. } Design standards IT systems have become critical for the day-to-day operations of today s organizations. {Data center.} Design standards IT systems are critical for the

More information

Datacenter Hosting and Cloud Computing Services

Datacenter Hosting and Cloud Computing Services Datacenter Hosting and Cloud Computing Services Overview Background Founded in 1995, Lore Systems operates an international datacenter network which today includes full service 3+ datacenter facilities

More information

DDesign collaboration between the owner/operator. Good things happen when the design team organizes around a plan. BY KEITH LANE

DDesign collaboration between the owner/operator. Good things happen when the design team organizes around a plan. BY KEITH LANE Good things happen when the design team organizes around a plan. BY KEITH LANE Keith Lane has over 20 years of experience in the design and implementation of mission-critical facilities. He is a professional

More information

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015

Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Tour of new eircom Data Centre Blanchardstown by Dervan Engineering Consultants 11 th March 2015 Presentation Outline Mechanical Overview Chillers and Pumps Pipework and Ancillaries In Row Cooling Units

More information

Subject: County of Los Angeles Data Center Space Requirement

Subject: County of Los Angeles Data Center Space Requirement Subject: County of Los Angeles Data Center Space Requirement The County of Los Angeles, Chief Executive Office, Real Estate Division (CEO-RED) is issuing this Property Search for the purchase of a vacant,

More information

Introduction to Datacenters & the Cloud

Introduction to Datacenters & the Cloud Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview

More information

AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ)

AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) Site Biography Market Area: Phoenix, Mesa, Tempe, Chandler, Scottsdale, AZ Location: Mesa, AZ 85201 Address: 1301 University Blvd.

More information

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM

KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM KU DESIGN GUIDELINES APPENDIX XVI RECOMMENDED BAS I/O CONTROL POINTS BY EQUIPMENT / SYSTEM AIR HANDLING UNITS... 1 CHILLERS... 2 COOLING TOWERS... 2 CLOSED LOOP COOLERS... 2 MISCELLANEOUS SUPPLY FANS...

More information

Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011

Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011 Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011 Opportunities in Automating Infrastructure Why Automation in Data Center? Tiers, compartments and complexity Work

More information

Data Center Management. Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM

Data Center Management. Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM Data Center Management Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM A physical place that houses a computer network's most critical systems, including back-up power supplies, air conditioning, and

More information

Sovereign. The made to measure data centre

Sovereign. The made to measure data centre Sovereign D ATA C O N N E C T The made to measure data centre Prime Location Within touching distance of everything that s important. 2 Your Customer-Centric Data Centre For the vast majority of organisations

More information

Specialty Environment Design Mission Critical Facilities

Specialty Environment Design Mission Critical Facilities Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,

More information

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends

More information

Tier Standards. Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI. Consultant EMEA

Tier Standards. Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI. Consultant EMEA Tier Standards Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI Consultant EMEA Uptime Institute Unbiased and vendor neutral Global thought leadership for the data center industry Founded 1993 Standards and

More information

DATA CENTRE DATA CENTRE MAY 2015

DATA CENTRE DATA CENTRE MAY 2015 DATA CENTRE DATA CENTRE MAY 2015 CONCERTHOUSE MUSIC Concerthouse Music Data Centre services are located in the Equinix Internet Business Exchange (IBX ) Centre at Mascot. This IBX offers the highest level

More information

IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling

IT@Intel. Thermal Storage System Provides Emergency Data Center Cooling White Paper Intel Information Technology Computer Manufacturing Thermal Management Thermal Storage System Provides Emergency Data Center Cooling Intel IT implemented a low-cost thermal storage system that

More information

Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications

Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications W H I T E P A P E R Top 12 Questions to Consider When Choosing UPS Systems for Network/Server Applications Executive Summary One of the fundamental decisions in the design of data centers, server rooms

More information

SolveXia Business Continuity Planning

SolveXia Business Continuity Planning Business continuity planning is the term we use to describe all the steps we take at SolveXia to ensure that our service is up and running when you need it. As a 'Software as a Service' provider, our aim

More information

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify.

D. Infrared scanning reports with pictures printed in a final report with any deficiencies and actions taken to rectify. SECTION 263354 STATIC UPS TESTING AND COMMISSIONING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes 1. System start-up services. 2. Battery charging. 3. Load bank testing. 4. Battery load testing. 5.

More information

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus. DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure

More information

LEVEL 3 DATA CENTER SERVICES IN OMAHA, NEBRASKA HIGH AVAILABILITY ENTERPRISE COMPUTING BUSINESS DEMANDS IT. LEVEL 3 DELIVERS IT.

LEVEL 3 DATA CENTER SERVICES IN OMAHA, NEBRASKA HIGH AVAILABILITY ENTERPRISE COMPUTING BUSINESS DEMANDS IT. LEVEL 3 DELIVERS IT. LEVEL 3 DATA CENTER SERVICES IN OMAHA, NEBRASKA HIGH AVAILABILITY ENTERPRISE COMPUTING BUSINESS DEMANDS IT. LEVEL 3 DELIVERS IT. THE SCALE TO SUPPORT GLOBAL ENTERPRISE IT Designed and equipped to meet

More information

Best Practices, Benefits and Economics of Load Testing IEEE PES Fort Worth, TX Chapter July 16, 2013

Best Practices, Benefits and Economics of Load Testing IEEE PES Fort Worth, TX Chapter July 16, 2013 Best Practices, Benefits and Economics of Load Testing IEEE PES Fort Worth, TX Chapter July 16, 2013 Mark Siira ComRent International 1 8/1/2013 Agenda Introduction Overview of Load Bank Testing Benefits

More information

Defining Quality. Building Comfort. Precision. Air Conditioning

Defining Quality. Building Comfort. Precision. Air Conditioning Defining Quality. Building Comfort. Precision Air Conditioning Today s technology rooms require precise, stable environments in order for sensitive electronics to operate optimally. Standard comfort air

More information

REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS

REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS REAL OPERATING COST SAVINGS FROM RETRO- COMMISSIONING OPPORTUNITIES FOR SAVINGS IN ACADEMIC MEDICAL CENTERS Ken L. Hansen P.E. University of Nebraska Medical Center hansenkl@unmc.edu 402-559- 5301 402-630-

More information

DATA CENTRE DATA CENTRE

DATA CENTRE DATA CENTRE DATA CENTRE DATA CENTRE v. OCT 2014 DJ CENTRAL DJ Central Data Centre services are located in the Equinix Internet Business Exchange (IBX ) Centre at Mascot. This IBX offers the highest level of service

More information

19 Site Location, Design and Attributes. Site Location, Design and Attributes

19 Site Location, Design and Attributes. Site Location, Design and Attributes 1 Site Location, Design and Attributes The Primary Data Center shall be physically located on Oahu, Hawaii. 2 Site Location, Design and Attributes The Primary Data Center shall be located at least 1 mile

More information

100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G

100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G 100 Locust Avenue, Berkeley Heights, New Jersey P R O P E R T Y O F F E R I N G The Opportunity Jones Lang LaSalle, Inc. (the Broker ) is please to offer the fee simple interest in 100 Locust Avenue (the

More information

AIR COOLED CHILLER CHILLED WATER PUMP CONTROL: The chilled water pump with the lowest runtime will automatically start when the outside air temperature rises above the system enable setpoint. When the

More information

Subject: ITN for Redundant High Speed Communications (Part II) Off Campus Equipment Location. Proposed Board Action

Subject: ITN for Redundant High Speed Communications (Part II) Off Campus Equipment Location. Proposed Board Action AGENDA ITEM: VIII D (ii) Florida Polytechnic University Board of Trustees August 26, 2013 Subject: ITN for Redundant High Speed Communications (Part II) Off Campus Equipment Location Proposed Board Action

More information

Data Centre Testing and Commissioning

Data Centre Testing and Commissioning Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to

More information

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing

More information

Designed for uptime. Defining data center availability via a tier classification system

Designed for uptime. Defining data center availability via a tier classification system Defining data center availability via a tier classification system MIETEK GLIKOWSKI All systems can fail this is a simple fact that every industry must deal with. The paramount concern for the data center

More information

Reference Guide: SmartDesign Approach: Common Data Center Challenges:

Reference Guide: SmartDesign Approach: Common Data Center Challenges: Smart Solutions Reference Guide Solutions For Business-Critical Continuity 1100kW Tier 3 With High Density Design Intelligent, Integrated Infrastructure for the Data Center Reference Guide: 1100kW Tier

More information

Guidance for Calculation of Efficiency (PUE) in Data Centers

Guidance for Calculation of Efficiency (PUE) in Data Centers Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 3 by Victor Avelar Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or other

More information

Guidance for Calculation of Efficiency (PUE) in Data Centers

Guidance for Calculation of Efficiency (PUE) in Data Centers Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 1 by Victor Avelar > Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or

More information

Five Nines and Infrared (IR) Testing at Data Centers

Five Nines and Infrared (IR) Testing at Data Centers Five Nines and Infrared (IR) Testing at Data Centers By Gregory R. Stockton 99.999% uptime five nines. That is what IT (information technology) customers are looking for. Uptime or availability at data

More information

Energy Design Resources Commissioning Plan Outline Template

Energy Design Resources Commissioning Plan Outline Template IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC is not rendering advice concerning any commission project or practices. This document is neither approved nor intended

More information

Chiller-less Facilities: They May Be Closer Than You Think

Chiller-less Facilities: They May Be Closer Than You Think Chiller-less Facilities: They May Be Closer Than You Think A Dell Technical White Paper Learn more at Dell.com/PowerEdge/Rack David Moss Jon Fitch Paul Artman THIS WHITE PAPER IS FOR INFORMATIONAL PURPOSES

More information

Sample Company SECTION 019113 GENERAL COMMISSIONING REQUIREMENTS PART 1 GENERAL 1.1 SUMMARY AND CONTRACT RESPONSIBILITIES

Sample Company SECTION 019113 GENERAL COMMISSIONING REQUIREMENTS PART 1 GENERAL 1.1 SUMMARY AND CONTRACT RESPONSIBILITIES SECTION 019113 GENERAL COMMISSIONING REQUIREMENTS PART 1 GENERAL 1.1 SUMMARY AND CONTRACT RESPONSIBILITIES A. The Owner will contract separately and directly for the majority of the commissioning work

More information

Statement of Work. 3.0 Details of Service Pre Start-up. - 1 - Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary

Statement of Work. 3.0 Details of Service Pre Start-up. - 1 - Cooling Start-up Service. Installation Service. Table of Contents. 1.0 Executive Summary Installation Service Statement of Work - 1 - Cooling Start-up Service Cooling Start-up Service Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits 3.0 Details

More information

Calculating Total Power Requirements for Data Centers

Calculating Total Power Requirements for Data Centers Calculating Total Power Requirements for Data Centers By Richard Sawyer White Paper #3 Executive Summary Part of data center planning and design is to align the power and cooling requirements of the IT

More information

Scalable. Affordable. Flexible. Fast.

Scalable. Affordable. Flexible. Fast. Modular Data Center Solutions Scalable. Affordable. Flexible. Fast. Build the data center you need today with the flexibility to meet tomorrow s challenges The only constant in business is change. Fluctuations

More information

How To Visit An Internet Data Center

How To Visit An Internet Data Center AT&T Internet Data Center Site Specification Atlanta Area (Lithia Springs, GA) Site Biography Market Area: Atlanta and surrounding areas (Georgia, Alabama, Tennessee, Florida, North and South Carolina

More information

PHP/MySQL APPLicAtion HoSting

PHP/MySQL APPLicAtion HoSting PHP/MySQL Application Hosting Connectivity DMD PHP/MySQL Hosting is partnered with a Kansas City, USA based Data Center connected to the internet through multiple backbones to ensure that the data is transmitted

More information

san francisco//usa data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence

san francisco//usa data center specifications tel: +61 2 9948 8888 fax: +61 2 9948 1111 internet + intellectual property + intelligence internet + intellectual property + intelligence We thank you for the opportunity to work with you regarding your colocation needs in San Francisco, USA. We can colocate standard rack-mountable servers

More information

The Data Center Dilemma - A Case Study

The Data Center Dilemma - A Case Study Second Place: Industrial Facilities or Processes, Existing The TCS data center makes use of white cabinets and reflective surfaces as one method to reduce power for its lights and cooling. Data Center

More information

The Pros and Cons of Modular Systems

The Pros and Cons of Modular Systems The Pros and Cons of Modular Systems Kevin Brown, Vice President Global Data Center Offer Schneider Electric Schneider Electric 1 Foundational BUSINESS OVERVIEW Rev 2 Desired characteristics of pre-fabricated

More information

South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime

South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime South Asia s First Uptime Institute Certified TIER- IV IDC in Mumbai delivering 99.999% uptime GPX India Pvt Ltd The Leader In Carrier Neutral TIER IV IDC s In Emerging Markets Incorporated in August 2002,

More information

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS.

THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. THERMO KING TRUCK & TRAILER UNIT ALARM CODES THIS DOCUMENT SHOWS ALL CURRENT ALARM CODES FOR THERMO KING TRUCK AND TRAILER UNITS. NOT ALL CODES ARE POSSIBLE ON ANY INDIVIDUAL UNIT. IF THE ALARM APPLIES

More information

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures

Data Realty Colocation Data Center Ignition Park, South Bend, IN. Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Data Realty Colocation Data Center Ignition Park, South Bend, IN Owner: Data Realty Engineer: ESD Architect: BSA LifeStructures Project Overview Data Realty is a data center service provider for middle

More information

Data Center Colocation Build vs. Buy

Data Center Colocation Build vs. Buy Data Center Colocation Build vs. Buy Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for

More information

The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements

The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements Edward P Rafter, P.E. CxAP Tier IV Consulting Group Synopsis The data center industry has experienced

More information

Data Center Overview Document

Data Center Overview Document Overview NetSource is a Chicago area (Naperville) hosting company that owns and operates its own world class datacenter. The initial datacenter buildout was put into operation in 2007 and expanded in 2013.

More information

World s Greenest High Performance Data Center

World s Greenest High Performance Data Center World s Greenest High Performance Data Center EcoDataCenter Sustainability for future generations Our Services Colocation Data Center for Mission Critical Requirements Lockable racks, cages, private rooms

More information

Strategic Data Centre Site Profiles Data Centre Co-Location London North

Strategic Data Centre Site Profiles Data Centre Co-Location London North Strategic Data Centre Site Profiles Data Centre Co-Location London North Document details Version: 1 Last Updated: 12/07/2013 Version 1.0 Page 1 of 6 Contents 1. LONDON NORTH...3 1.1 LOCATION...3 1.2 TECHNICAL

More information

vcloud SERVICE Virtual Tech in partnership with Equinix - vcloud Service

vcloud SERVICE Virtual Tech in partnership with Equinix - vcloud Service vcloud SERVICES vcloud SERVICE Virtual Tech offers competitive pricing on vcloud hosted services at our world class Tier 4 data centre facility fully equipped with redundant power, cooling, internet connectivity

More information

South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime

South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime South Asia s First Uptime Institute Certified TIER-IV IDC in Mumbai delivering 99.999% guaranteed uptime GPX India Pvt Ltd The Leader In Carrier Neutral TIER IV IDC s In Emerging Markets Incorporated in

More information

Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group

Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group The data center industry has experienced several evolutions over the past 20 years. One principal change has been the development of the

More information

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY

AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY AEGIS DATA CENTER SERVICES POWER AND COOLING ANALYSIS SERVICE SUMMARY The Aegis Services Power and Assessment Service provides an assessment and analysis of your data center facility and critical physical

More information

Is the Grass Greener on the other side? Examples of Cx south of the border. Jorge Torres Coto, Empirical Engineering

Is the Grass Greener on the other side? Examples of Cx south of the border. Jorge Torres Coto, Empirical Engineering Is the Grass Greener on the other side? Examples of Cx south of the border Jorge Torres Coto, Empirical Engineering 21 st National Conference on Building Commissioning AIA Quality Assurance The Building

More information

AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland

AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course

More information

Increasing safety, reliability and efficiency for today s data centers

Increasing safety, reliability and efficiency for today s data centers Increasing safety, reliability and efficiency for today s data centers Products and expertise for data center success Drawing upon vast experience in complex industries where uptime is critical, ABB provides

More information

The Different Types of Air Conditioning Equipment for IT Environments

The Different Types of Air Conditioning Equipment for IT Environments The Different Types of Air Conditioning Equipment for IT Environments By Tony Evans White Paper #59 Executive Summary Cooling equipment for an IT environment can be implemented in 10 basic configurations.

More information

Tier Classifications Define Site Infrastructure Performance

Tier Classifications Define Site Infrastructure Performance By W. Pitt Turner IV, P.E., John H. Seader, P.E., and Kenneth G. Brill Widely accepted within the uninterruptible industry, The Uptime Institute s Tier Performance Standards are an objective basis for

More information

DDC Sequencing and Redundancy

DDC Sequencing and Redundancy DDC Sequencing and Redundancy Presenter Sequencing Importance of sequencing Essen%al piece to designing and delivering a successful project Defines how disparate components interact to make up a system

More information

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings

Advanced Energy Design Guide LEED Strategies for Schools. and High Performance Buildings Advanced Energy Design Guide LEED Strategies for Schools and High Performance Buildings Today s Presenters Stephen Koontz, LEED AP Energy Services Leader Tampa Bay Trane Allen Irvine General Sales Manager

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Tier Classifications Define Site Infrastructure Performance

Tier Classifications Define Site Infrastructure Performance W h i t e P a p e r Tier Classifications Define Site Infrastructure Performance By W. Pitt Turner IV, PE, John H. Seader, PE, Vince Renaud, PE, and Kenneth G. Brill Table of Contents Executive Summary...

More information

HKEx Hosting Services

HKEx Hosting Services HKEx Hosting Services The cover illustrates an ecosystem where HKEx Exchange Participants as well as Technology and Communications providers are able to interact. In addition, HKEx s Next Generation Data

More information

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers

Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Case Study: Opportunities to Improve Energy Efficiency in Three Federal Data Centers Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National

More information

Tier Classifications Define Site Infrastructure Performance

Tier Classifications Define Site Infrastructure Performance By W. Pitt Turner IV, P.E., John H. Seader, P.E., and Kenneth G. Brill Widely accepted within the uninterruptible industry, The Uptime Institute s Tier Performance Standards are an objective basis for

More information