1 Data Center Designs and Hospital Operations Designing for Data Center Availability and the Effect on Daily Operations Joe Harris, PE, RCDD Senior Engineer, AECOM Data Centers and Hospitals June 10, 2015

2 AECOM Healthcare Practice Industry Leader ENR RANKING 400 Hospitals 300 Ambulatory Care Centers 200 Medical Group Practice Centers 40 Academic Medical Centers 10,000 Patient Rooms #1 DESIGN FIRM #1 PURE DESIGN #1 HEALTH CARE #1 GENERAL BUILDING Top 10 Worldwide, Modern Healthcare Survey 2014 Page 2

3 About Me 20+ Years Industry Experience Data Center Design across multiple industries: Healthcare Military Commercial Industrial Professional Engineer (Ohio) Registered Communications Distribution Designer Registered Telecommunications Project Manager Page 3

4 Learning Objectives: Understand the reliance on the data center Learn why we need to design for reliability and availability Understand how design decisions affect availability based on: Space planning Infrastructure Security concerns Services and Maintenance June 10, 2015 Data Centers and Hospitals Page 4 Client logo

5 Agenda Data Center Definition Hospital and Data Center Trends Availability and Reliability Design Considerations Conclusion Page 5 Client logo

6 Industry Acronyms TIA Telecommunications Industry Association ANSI American National Standards Institute BICSI Building Industry Consulting Service International PUE Power Usage Effectiveness ASHRAE American Society of Heating, Refrigerating, and Air- Conditioning Engineers NEC National Electric Code NFPA National Fire Protection Association NEBS Network Equipment-Building System CRAC Computer Room Air Conditioner Page 6 Client logo

7 Data Center Defined

8 The Data Center Is: Large Heat Source Mechanical Engineer Large Electrical Load Electrical Engineer The Heart of Our Network Hospital IT Staff Our Most Critical Space CIO Expensive CFO RISK! Security Director It Depends On your Viewpoint Page 8

9 Official Definition Data Center A building or portion of a building whose primary function is to house a computer room and its support areas ANSI/BICSI Page 9

10 Data Center Components Computer Room Network Core Switching Servers Storage Cabling Power Distribution Cooling Distribution (Most Critical IT Space) Support Areas Entrance Room(s) Electrical Room(s) Mechanical Rooms(s) Operations Center Crisis Response Room Maintenance Areas Support Staff Offices Loading Docks Receiving/Storing Areas Battery Rooms Telecommunications Rooms (Enables everything that happens) Page 10

11 Expanded (Functional) Definition Data Center A building or portion of a building whose primary function is to house a computer room and its support areas 1, designed as a set of interdependent systems operating together to create the processing and networking capabilities required to meet the current business demands. 1. ANSI/BICSI Page 11

12 Hospital and Data Center Trends

13 Hospital Trends Electronic Health Records More Processing More Bandwidth More Storage More Risk Big Data Electronic Health Information Exchange Radiology reports Lab results Clinical Care Summaries Medication lists F Data sharing inside and outside of the creating organization Page 13

14 Hospital Trends Bottom Line It s a connected world Healthcare providers rely on connected systems to provide and receive patient information Services are being delivered electronically Patient diagnostics and historical data are online Critical systems are integrated Everything Relies on the Availability of Electronic Data Page 14

15 Data Center Trends THE OLD DAYS (15 Years Ago) Simple Backups 24 Hour Replacement Contracts Disaster Recovery Fire, flood, tornado Checklist Management Anticipate every disaster Hot sites TODAY Tier IV = 2(N+1),.4 hour, % Worms, Hackers, Backdoors Terrorism Political Concerns Power grid failure Liability and Regulatory Compliance Cascading Events Handle unexpected disaster Fwithout downtime Page 15

16 Data Center General Trends Greater focus on availability and reliability Extreme power and cooling requirements Increased Focus on preventing Data Loss Consolidation of servers Virtualization Struggles with predicting growth rates Converging low-voltage systems More Focus on Efficiency and Cost of Operations PUE Dark Data Centers Page 16

17 Coming Together Electronic Data Bandwidth Connectivity Complexity Availability Reliability Services Efficiency Everything Relies on the Availability of Electronic Data Page 17

18 Availability and Reliability

19 What Happens When our Data Center Goes Down? We lose: Link to the outside world Server based applications Storage availability Ability to work remotely Connectivity Systems availability Reputation Everything Relies on the Availability of Electronic Data Page 19

20 Availability vs Reliability Reliability is the ability of a system or component to perform its required functions under stated conditions for a specified period of time Availability is the probability that a component or system is in a condition to perform its intended function affected by more events than a failure requiring repair or replacement of a component or system Availability = Uptime / Total Time (within the observation interval) Page 20

21 Reliability Risk Metrics Failure Risks Mean Time to Failure (MTTF) Mean Time to Repair (MTTR) Susceptibility to natural disasters Fault tolerance Single Points of Failure in a system Maintainability Maintenance Programs Page 21

22 Availability Classifications % Availability = 5 Minutes of Downtime per Year ANSI/BICSI and TIA Classes, 5 Sub groups New Industry Standard 0 = No redundancy 4 = Component AND System Redundancy Uptime Institute Tier Standards and Certifications Proprietary to Uptime Institute Tier 1 = Basic Site Tier 4 = Fault Tolerant 2N+1 Redundancy = 2 Complete Systems + 1 extra component Page 22

23 Tiering For Dummies TIER I/Class 0 and 1 Car without a spare tire. Stop the car and wait for it to be fixed. TIER II/Class 2 Four tires and a spare. Stop, fix the flat, drive on. TIER III/Class 3 Run Flat tires. Drive slower until you can replace the tire. TIER IV/Class 4 Change the tires, transmission, and engine while driving at 60MPH. Page 23

24 9 s and N s 9 s of availability Measure of uptime expressed as a percentage (i.e. 99.9%) Five 9 s = % Availability o Equates to five minutes of downtime per year o Each additional 9 adds 50% to the data center cost. N s of redundancy Redundancy applied to components, systems, services, etc. Can be UPS systems, Switches, CRACs, etc. 2N+1 = 2 times the required number + 1 extra Page 24

25 How Much Redundancy is EnoughE ETo Guarantee Availability? Page 25

26 Design Considerations

27 Design Considerations Space Planning Infrastructure Security Services and Maintenance Page 27

28 Design Considerations Space Planning Infrastructure Security Services and Maintenance Page 28

29 Space Planning Site Selection Where should you put the DC? Adjacencies What should be near the DC? What should not? Layout How should the DC space be arranged? Page 29

30 Space Planning Site Selection Stand Alone DC Location Criteria Availability of and access to reliable Telecommunications Availability of and access to reliable Power Other Utilities (Water, Sanitation, Natural Gas, Etc.) Transportation Access Property adjacencies Environmental Influences (Seismic, Flooding, Air Quality, Wind) Separation from your primary or backup data center Page 30

31 Space Planning Site Selection DC in a Hospital Location Criteria No patient access Not on ground floor or below Protected from outside walls Access to freight elevator Not near EMI/RFI sources Not near sensitive equipment No foreign piping systems in/over the space Away from large equipment (air handlers, MV Transformers, etc.) No Drains running through the computer room! (Avoid all water sources) Page 31

32 Space Planning Site Selection Inside a Hospital Public Space Secure Hospital Staff Secure IT Staff Computer Room Semi-Private Semi-Public Page 32

33 Space Planning Adjacencies Computer Room Control Room Data Storage Symb Adjacency Computer Room Control Room Data Storage Lobby X X Z X Y Z X Y N Lobby Z Z N X Y Z N Connected Near Away From No Relation Page 33

34 Space Planning Data Center Layout Work Room Secure Storage Unpacking Staging Computer Room HVAC / ELEC Computer Room Secure Corridor Control Room WAR Data Storage Telecom Entrance Room Secure Receiving Security Center IT Personnel Spaces Page 34

35 Design Considerations Space Planning Infrastructure Security Services and Maintenance Page 35

36 Infrastructure Power UPS Systems Power Distribution Cooling Computer Room Air Conditioners (CRACs) Hot (or cold) Air Containment Structured Cabling Fiber, Copper, Routing Page 36

37 Power Power Company Generators Uninterruptable Power Supply Automatic Transfer Switches Power Distribution Units Power Whips and Strips Power Cords Redundancy Redundancy Page 37

38 Cooling ASHRAE TC 9.9, ANSI/TIA-942, NEBS GR-3160 All slightly different Operational Temp Max Rate of Change Operational RH Max Dew point ANSI/TIA ºF 77ºF 9ºF/hour 40% - 55% 69.8ºF NEBS GR ºF 80ºF 54ºF/Hour 55% Max 82ºF ASHRAE TC ºF 80.6ºF 9ºF/Hour 60% Max 42ºF - 59ºF Page 38

39 Cooling / Thermal Management The primary goal is to deliver properly cooled air, in the correct volume, directly in front of all active equipment. Page 39

40 Without Isolation of Return Air Path Page 40

41 Return Air Path Isolation Hot air is physically segregated from cold air in return air duct Rear door is sealed to prevent exhaust air from leaking into room Air Dams and filler panels in front of cabinet prevent air recirculation inside cabinet Room A/C is easy to manage, with little regard to concentrated heat loads Cabinets can be placed and oriented any way desired Cold air delivery can be shared throughout room with fewer zone issues Page 41

42 Cooling / Thermal Management HVAC Design should provide for Control Filtration Direct cooled equipment Avoidance of recirculation and bypass air Redundant cooling systems to meet the class design. Page 42

43 Cooling and Structured Cabling Heat is the #1 cause of electronic component failures Data Centers and Hospitals June 10, 2015 Page 43

44 Under Floor Separation of Media Page 44

45 Defined Cable Management Data Centers and Hospitals June 10, 2015 Page 45

46 Structured Cabling The fiber and copper cabling that connects all of the networked components and distribution areas of the computer room. Consists of: Fiber Single Mode and/or 50 Micron Laser Optimized Multi-Mode (OM4 Recommended) Copper Category 6A or better Proprietary Cabling (some switch manufacturers) 10 Gig backbone minimum Migration path to 40/100 gig (25 gig?) Pre-terminated cabling ORGANIZATION Page 46

47 Structured Cabling Areas of the Computer Room MDA Main Distribution Area Network Core and Cross Connect HDA Horizontal Distribution Area Backbone connections to serve multiple cabinets (typically end of row or middle of row) ZDA Zone Distribution Area Cross connect point similar to a consolidation point EDA Equipment Distribution Area Connections to the end equipment (servers, SAN, etc.) Page 47

48 FAN STATUS -48 V TO -60 V -40 A 1800 VA Cisco Systems, Inc INPUT OK FAN OK OUTPUT FAIL Switch must be in off "O" position to Install/Remove power supply. Fastener must be fully enaged prior to operating power supply. Power Supply 1 Power Supply 2 Catalyst 6500SERIES -48 V TO -60 V -40 A VA Cisco Systems, Inc. INPUT OK FAN OK OUTPUT FAIL Switch must be in off "O" position to Install/Remove power supply. Fastener must be fully enaged prior to operating power supply. MDA U47 U46 U45 U44 U43 U42 U41 U40 U39 U38 U37 U36 U35 U34 U33 U32 U31 U30 U29 U28 U27 U26 U25 U24 U23 U22 U21 U20 U19 U18 U17 U16 U15 U14 U13 U12 U11 U10 U09 U08 U07 U06 U05 U04 U03 U02 U01 Front View Catalyst 6500 SERIES U47 U46 U45 U44 U43 U42 U41 U40 U39 U38 U37 U36 U35 U34 U33 U32 U31 U30 U29 U28 U27 U26 U25 U24 U23 U22 U21 U20 U19 U18 U17 U16 U15 U14 U13 U12 U11 U10 U09 U08 U07 U06 U05 U04 U03 U02 U01 INSTALL RUN Rear View Fiber Termination INSTALL RUN Includes the core switching and main cross connect for the data center Hub of cabling infrastructure for the Data Center Has backbone cabling to all HAD s and TR s Page 48

49 HDA HDA A RACK #1 RACK #2 RACK #3 RACK #4 RACK #5 RACK #6 HDA B FIBER PATCH PANEL A 48 UTP PATCH PANEL A SIDE (28 ACTIVE) 48 UTP PATCH PANEL A SIDE (28 ACTIVE) 48 UTP PATCH PANEL A SIDE (28 ACTIVE) 48 UTP PATCH PANEL A SIDE (28 ACTIVE) 48 UTP PATCH PANEL A SIDE (28 ACTIVE) 48 UTP PATCH PANEL A SIDE (28 ACTIVE) FIBER PATCH PANEL ROUTE B UTP PATCH PANEL #1 48 UTP PATCH PANEL B SIDE (28 ACTIVE) 48 UTP PATCH PANEL B SIDE (28 ACTIVE) 48 UTP PATCH PANEL B SIDE (28 ACTIVE) 48 UTP PATCH PANEL B SIDE (28 ACTIVE) 48 UTP PATCH PANEL B SIDE (28 ACTIVE) 48 UTP PATCH PANEL B SIDE (28 ACTIVE) UTP PATCH PANEL #1 UTP PATCH PANEL #2 24 UTP PATCH PANEL KVM & MGMT 24 UTP PATCH PANEL KVM & MGMT 24 UTP PATCH PANEL KVM & MGMT 24 UTP PATCH PANEL KVM & MGMT 24 UTP PATCH PANEL KVM & MGMT 24 UTP PATCH PANEL KVM & MGMT UTP PATCH PANEL #2 UTP PATCH PANEL #3 UTP PATCH PANEL #3 UTP PATCH PANEL #4 UTP PATCH PANEL #4 UTP PATCH PANEL #5 UTP PATCH PANEL #5 UTP PATCH PANEL #6 UTP PATCH PANEL #6 UTP PATCH PANEL #7 UTP PATCH PANEL #7 UTP PATCH PANEL KVM & MGMT RACKS 1 & 2 SERVER SPACE SERVER SPACE SERVER SPACE SERVER SPACE SERVER SPACE SERVER SPACE UTP PATCH PANEL KVM & MGMT RACKS 7&8 UTP PATCH PANEL KVM & MGMT RACKS 3 & 4 UTP PATCH PANEL KVM & MGMT RACKS 9 &10 UTP PATCH PANEL KVM & MGMT RACKS 5 & 6 UTP PATCH PANEL KVM & MGMT RACKS 11 & 12 SWITCH SPACE SWITCH SPACE Contains the horizontal cross connect Distribution point for the equipment distribution areas Has horizontal cabling to all EDA s Typically contains switching equipment to support the EDA Page 49

50 ZDA Connection point between HAD and EDA Contains no active electronics Limited to 288 connections Can be installed in cabinet, under floor, over head, etc. Comparable to Consolidation point located in the Work Area in Page 50

51 EDA U47 U46 U45 U44 U43 U42 U41 U40 U39 Front View U47 U46 U45 U44 U43 U42 U41 U40 U39 Rear View Fiber Termination Area allocated for the end equipment Includes horizontal cable and connections to the HAD U38 U37 U36 U35 U34 U38 U37 U36 U35 U34 Point-to-point cabling permitted U33 U32 U31 U30 U29 U28 U27 U26 Space for Optional Keyboard & Monitor U33 U32 U31 U30 U29 U28 U27 U26 Comparable to the location of end equipment in 568 U25 U25 U24 U24 U23 U23 U22 U22 U21 U21 U20 U20 U19 U19 U18 U18 U17 U17 U16 U16 U15 U15 U14 U14 U13 U13 U12 U12 U11 U11 U10 U10 U09 U09 U08 U08 U07 U07 U06 U06 U05 U05 U04 U04 U03 U03 U02 U02 U01 U01 Page 51

52 Structured Cabling Areas of the Computer Room Page 52

53 Structured Cabling Redundancy Page 53

54 Design Considerations Space Planning Infrastructure Security Services and Maintenance Page 54

55 Security Three Main Components Architectural Electronic Operational Page 55

56 Data Center Security Accreditations? Courtesy Altus Technologies Page 56

57 Security Architectural Landscaping Lighting Doors/Locks/Glazing Building features that contribute to security Electronic Access Control Intrusion Detection CCTV Duress Operational Security Staffing Post Orders Guard Tours Policies and procedures Contingency Planning Page 57

58 Information Security (InfoSec) Confidentiality Availability Integrity The best configured firewall in the world can t stand up to a well placed brick. Page 58

59 Design Considerations Space Planning Infrastructure Security Services and Maintenance Page 59

60 Services and Maintenance Testing Periodically throughout the life of the system Include backup systems Scheduled for off peak times System Maintenance includes Cabling Electrical HVAC IT Equipment Security Page 60

61 Services and Maintenance Cleaning is critical and often overlooked All spaces (above and below) Part of maintenance contract Data Centers and Hospitals June 10, 2015 Page 61

62 Services and Maintenance An insufficient maintenance plan will result in extended downtime. Regularly scheduled maintenance must be carefully planned and performed by persons familiar with the entire system and all inter-dependencies Page 62

63 Conclusion

64 Design for Availability Hospitals require a high level of data availability to operate efficiently Data center designs need to focus on systems availability By designing for availability in the data center, we can help ensure hospital operations are not interrupted due to lack of electronic services and data Everything Relies on the Availability of Electronic Data Page 64

65 Thank You Data Centers and Hospitals June 10, 2015

Data center upgrade proposal. (phase one)

Data center upgrade proposal. (phase one) Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The

More information

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD Data Center Standards Roundup BICSI, TIA, CENELEC, ISO Steve Kepekci, RCDD Introduction Regardless of business activity or size, all information technology (IT) groups have similar needs Provide secure,

More information

TIA-942 Data Centre Standards Overview WHITE PAPER

TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and

More information

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME

Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center

More information

Dealing with Thermal Issues in Data Center Universal Aisle Containment

Dealing with Thermal Issues in Data Center Universal Aisle Containment Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges

More information

ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers

ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers Jonathan Jew jew@j-and and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center committee Co-chair BICSI data centers

More information

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers

Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 techsupport@chatsworth.com www.chatsworth.com All products

More information

How To Write An Infrastructural Standard For Data Center Infrastructure

How To Write An Infrastructural Standard For Data Center Infrastructure Infrastructure Standard for Data Centers ANSI/CSA/EIA/TIA-942 (PN-3-0092) Introduction When approved, the standard will be: ANSI/CSA/EIA/TIA-942 Telecommunications Infrastructure Standard for Data Centers

More information

Building a Tier 4 Data Center on a Tier 1 Budget

Building a Tier 4 Data Center on a Tier 1 Budget Building a Tier 4 Data Center on a Tier 1 Budget A Walk Through of TIA-942 Peter P. Charland III, RCDD/NTS/WD, CET RTKL Associates Inc. March 27, 2008 BICSI South Central Region Meeting Denver, CO TIA-942

More information

Data Center Presentation

Data Center Presentation Data Center Presentation The NetSource Datacenter. Agenda General Layout of Data Center Policies and Procedures Designed to Latest Standards High Performance High Reliability High Security Design Details

More information

Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc jew@j-and-m.com

Data Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc jew@j-and-m.com Data Center Standards Making Progress on Many Fronts Jonathan Jew J&M Consultants, Inc jew@j-and-m.com J&M Consultants - 2008 Speaker Jonathan Jew Co-chair TIA TR-42.1.1 Data Center working group ANSI/TIA-942

More information

Data Center Cabling Design Trends

Data Center Cabling Design Trends Data Center Cabling Design Trends BICSI Regional Meeting Maurice Zetena Fiber Connect Infrastructure Trends Infrastructure Trends Any to All Trunk Cabling Trends: Data Center Infrastructure Media Choice:

More information

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center

More information

This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits.

This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits. This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits. DCD, DCOM, DCE DESIGN IMPLEMENTATION BEST PRACTICE OPERATION & MANAGEMENT DATA

More information

Data Center Optimization: Component Choice. Innovative Design. Enabling Infrastructure

Data Center Optimization: Component Choice. Innovative Design. Enabling Infrastructure Data Center Optimization: Component Choice and Innovative Design Combine to Allow the Creation of an Enabling Infrastructure Data Center Spaces Data Center Spaces as Defined by the TIA 942 Standard Source:

More information

Benefits of. Air Flow Management. Data Center

Benefits of. Air Flow Management. Data Center Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment

More information

Managing Data Centre Heat Issues

Managing Data Centre Heat Issues Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design

More information

Keyword: TIA 942, Tier level, Nuclear Data Center. Introduction

Keyword: TIA 942, Tier level, Nuclear Data Center. Introduction Nuclear Data Center International Standard Towards TSO Initiative Raja Murzaferi Raja Moktar, Mohd Fauzi Haris, Siti Nurbahyah Hamdan, Saaidi Ismail,Radhiah Jamaluddin, Nursuliza Samsudin. IT Center, Technical

More information

Telecommunications Infrastructure Standard for Data Centers. 802.3 Tutorial

Telecommunications Infrastructure Standard for Data Centers. 802.3 Tutorial Telecommunications Infrastructure Standard for Data Centers 802.3 Tutorial Prepared by: Jonathan Jew - J&M Consultants and Chris DiMinico - MC Communications - Co-chairs TR42.1.1 TR42: Data Center Standard

More information

Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011

Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011 Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011 Opportunities in Automating Infrastructure Why Automation in Data Center? Tiers, compartments and complexity Work

More information

TIA-942: Data Center Standards

TIA-942: Data Center Standards plantemoran.com TIA-942: Data Center Standards Sri Chalasani Merit 2010 Conference May 25, 2010 Objectives What are concerns in the data center? Data center standards & best Practices Data Center Definition

More information

Great Lakes Data Room Case Study

Great Lakes Data Room Case Study Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment

More information

ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers

ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers Jonathan Jew jew@j-and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center working group Co-chair BICSI data centers standards

More information

Energy-efficient & scalable data center infrastructure design

Energy-efficient & scalable data center infrastructure design Seminar am 30. September 2010 in Wetzlar Nachhaltigkeit durch UPI (Unified Physical Infrastructure) Vortrag von Stefan Fammler: Energieeffiziente Strategien im Rechenzentrum Energy-efficient & scalable

More information

Data Center Management. Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM

Data Center Management. Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM Data Center Management Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM A physical place that houses a computer network's most critical systems, including back-up power supplies, air conditioning, and

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

BICSI 002 / TIA 942 / Uptime

BICSI 002 / TIA 942 / Uptime BICSI 002 / TIA 942 / Uptime Which Data Center Standard Should I Follow Phil Isaak, PE, P.Eng., RCDD, DCDC President, Master Instructor Isaak Technologies Inc. Standards Who are these People Standards

More information

CHICAGO S PREMIERE DATA CENTER

CHICAGO S PREMIERE DATA CENTER CHICAGO S PREMIERE DATA CENTER White City collocation was founded in June, 2010 by a highly experienced industry executive in conjunction with several investment companies. The strategy of White City is

More information

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers

CURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building

More information

Enabling an agile Data Centre in a (Fr)agile market

Enabling an agile Data Centre in a (Fr)agile market Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without

More information

Video Systems and Data Center Design Wiring Plant Designation Terminology Infrastructure Deployment

Video Systems and Data Center Design Wiring Plant Designation Terminology Infrastructure Deployment Video Systems and Data Center Design Wiring Plant Designation Terminology Infrastructure Deployment Steve Surfaro Group Manager Strategic Technical Liaison Panasonic System Solutions Company surfaros@us.panasonic.com

More information

Network Design. Yiannos Mylonas

Network Design. Yiannos Mylonas Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which

More information

Data Centre Design ready for your future

Data Centre Design ready for your future Data Centre Design ready for your future Introduction to Data Centres What is a Data Centre? The definition of a Data Centre according to TIA-942 is a building or portion of a building whose primary function

More information

So you want to build a data centre? Look what s coming from BICSI! Matt Flowerday Capitoline FZC mflowerday@capitoline.org

So you want to build a data centre? Look what s coming from BICSI! Matt Flowerday Capitoline FZC mflowerday@capitoline.org So you want to build a data centre? Look what s coming from BICSI! Matt Flowerday Capitoline FZC mflowerday@capitoline.org So you want to build a data centre? Who do you contact? How do you work out what

More information

Specialty Environment Design Mission Critical Facilities

Specialty Environment Design Mission Critical Facilities Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

What is a Datacenter?

What is a Datacenter? What is a Datacenter? Telecom Room Primarily Cross Connect Equipment and switches. Computer room A room whose primary function is to house computer equipment. (Servers, Storage) 5 or less cabinets Small

More information

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions

Data Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging

More information

Energy Efficiency in the Data Center

Energy Efficiency in the Data Center Energy Efficiency in the Data Center Maria Sansigre and Jaume Salom Energy Efficieny Area Thermal Energy and Building Performance Group Technical Report: IREC-TR-00001 Title: Energy Efficiency in the Data

More information

The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space.

The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. Terminology: Telco: Dmarc: NOC: SAN: GENSET: Switch: Blade

More information

Data Center Overview Document

Data Center Overview Document Overview NetSource is a Chicago area (Naperville) hosting company that owns and operates its own world class datacenter. The initial datacenter buildout was put into operation in 2007 and expanded in 2013.

More information

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009

Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room

More information

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER

Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack

More information

19 Site Location, Design and Attributes. Site Location, Design and Attributes

19 Site Location, Design and Attributes. Site Location, Design and Attributes 1 Site Location, Design and Attributes The Primary Data Center shall be physically located on Oahu, Hawaii. 2 Site Location, Design and Attributes The Primary Data Center shall be located at least 1 mile

More information

Zone Distribution in the Data Center

Zone Distribution in the Data Center Zone Distribution in the Data Center By Jennifer Cline, RCDD As data centers face the continued need to expand and grow, the fundamental concerns and needs remain constant. Key concerns of the data cabling

More information

Data Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s"

Data Centre Issues supported in TIA-942 : Telecommunications Infrastructure for Data Centre s Data Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s" Data centre Standard EN50173-5 : "Telecommunications Infrastructure for Data Centre s Due, 2006 Gary Highton,

More information

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.

in other campus buildings and at remote campus locations. This outage would include Internet access at the main campus. DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure

More information

Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company

Data Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company Data Centre Cabling 20 August 2015 Stefan Naude RCDD The SIEMON Company Agenda 1. Data Centre Standards 2. The Need for Speed 3. Copper in the Data Centre 4. Fibre in the Data Centre 5. Top of Rack vs

More information

ADC-APC Integrated Cisco Data Center Solutions

ADC-APC Integrated Cisco Data Center Solutions Advanced Infrastructure Solution for Cisco Data Center 3.0 Ordering Guide ADC-APC Integrated Cisco Data Center Solutions The evolution of data centers is happening before our eyes. This is due to the

More information

Introduction to Datacenters & the Cloud

Introduction to Datacenters & the Cloud Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview

More information

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers

Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich

More information

Power and Cooling for Ultra-High Density Racks and Blade Servers

Power and Cooling for Ultra-High Density Racks and Blade Servers Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw

More information

Designing the Data Center

Designing the Data Center Designing the Data Center Asef Baddar, RCDD May -, 00 Talking points What are Data Centers? Why Data Centers? The components of the Data Center Approaching the Data Center design Breakdown of the components

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

Unified Physical Infrastructure (UPI) Strategies for Thermal Management

Unified Physical Infrastructure (UPI) Strategies for Thermal Management Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting

More information

BRUNS-PAK Presents MARK S. EVANKO, Principal

BRUNS-PAK Presents MARK S. EVANKO, Principal BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group

GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.

More information

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. 1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking

More information

Managing Cooling Capacity & Redundancy In Data Centers Today

Managing Cooling Capacity & Redundancy In Data Centers Today Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS

More information

AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ)

AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) Site Biography Market Area: Phoenix, Mesa, Tempe, Chandler, Scottsdale, AZ Location: Mesa, AZ 85201 Address: 1301 University Blvd.

More information

Data Center Design Considerations. Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc.

Data Center Design Considerations. Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc. Data Center Design Considerations Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc. Data Center Design: Overall Expectations Need: Prime vs. Redundant vs. Mirrored

More information

Top of Rack: An Analysis of a Cabling Architecture in the Data Center

Top of Rack: An Analysis of a Cabling Architecture in the Data Center SYSTIMAX Solutions Top of Rack: An Analysis of a Cabling Architecture in the Data Center White paper Matthew Baldassano, Data Center Business Unit CommScope, Inc, June 2010 www.commscope.com Contents I.

More information

Data Center Network Topologies

Data Center Network Topologies Data Center Network Topologies. Raj Jain Washington University in Saint Louis Saint Louis, MO 63130 Jain@cse.wustl.edu These slides and audio/video recordings of this class lecture are at: 3-1 Overview

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

abstract about the GREEn GRiD

abstract about the GREEn GRiD Guidelines for Energy-Efficient Datacenters february 16, 2007 white paper 1 Abstract In this paper, The Green Grid provides a framework for improving the energy efficiency of both new and existing datacenters.

More information

ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER

ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect Introduction The primary

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

www.commscope.com Data Center Topology Guide

www.commscope.com Data Center Topology Guide www.commscope.com Data Center Topology Guide Data Center Areas 1 Network Operations Center (NOC) The network operations center or NOC is the location where control of all data center networking, server

More information

Considerations for choosing top-of-rack in today's fat-tree switch fabric configurations

Considerations for choosing top-of-rack in today's fat-tree switch fabric configurations From the April, 2014 Issue of Cabling Installation & Maintenance Magazine Considerations for choosing top-of-rack in today's fat-tree switch fabric configurations Pros and cons exist for each configuration,

More information

IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com. 2011 IBM Corporation

IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com. 2011 IBM Corporation IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com Overview Profile IBM owned facility 6447 m² IT-Space Infrastructure concurrent maintainable (Tier Level 3) Feed-ins of Power

More information

Only a matter of power supply and air conditioning? Joachim Faulhaber TÜV Informationstechnik GmbH

Only a matter of power supply and air conditioning? Joachim Faulhaber TÜV Informationstechnik GmbH Data Center Availability Only a matter of power supply and air conditioning? Joachim Faulhaber TÜV Informationstechnik GmbH Agenda Security Assessment Uptime Approach Risks and Threats Availability Principles

More information

Data Center Commissioning: What you need to know

Data Center Commissioning: What you need to know Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,

More information

Data Center Components Overview

Data Center Components Overview Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room

More information

FEAR Model - Review Cell Module Block

FEAR Model - Review Cell Module Block F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data

More information

The Three Principles of Data Center Infrastructure Design WHITE PAPER

The Three Principles of Data Center Infrastructure Design WHITE PAPER The Three Principles of Data Center Infrastructure Design WHITE PAPER The Three Principles of Data Center Infrastructure Design Understand These Three Principles and You ll: Lower your total cost of ownership

More information

Data Center Knowledge, Vision Control

Data Center Knowledge, Vision Control Data Center Knowledge, Vision Control Objective Overview of the progressive trends in Data Centers, driven by Intelligent Infrastructure Solutions Data Center Layout Secured Storage Back up Core Backbone

More information

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.

Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling

More information

Siemon 10G ip. Data Centre Solution WHITE PAPER. Executive Summary

Siemon 10G ip. Data Centre Solution WHITE PAPER. Executive Summary Siemon 10G ip Data Centre Solution Executive Summary The term data centre conjures up different meanings to different people. Some would argue that the data centre is the room where the servers are stored.

More information

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com

Cooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends

More information

Re Engineering to a "Green" Data Center, with Measurable ROI

Re Engineering to a Green Data Center, with Measurable ROI Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices

More information

Data Center Colocation Build vs. Buy

Data Center Colocation Build vs. Buy Data Center Colocation Build vs. Buy Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for

More information

A Quick Primer on Data Center Tier Classifications

A Quick Primer on Data Center Tier Classifications A Quick Primer on Data Center Tier Classifications What You Should Know Before Starting a Data Center Project White Paper Abstract Data center facility projects are often driven by the Uptime Institute

More information

Subject: County of Los Angeles Data Center Space Requirement

Subject: County of Los Angeles Data Center Space Requirement Subject: County of Los Angeles Data Center Space Requirement The County of Los Angeles, Chief Executive Office, Real Estate Division (CEO-RED) is issuing this Property Search for the purchase of a vacant,

More information

How To Power And Cool A Data Center

How To Power And Cool A Data Center Architecting the Green Data Center Viktor Hagen Field Business Development Data Center & High Performance Computing 1 Where we are Today Environmental sustainability is a major global trend for the 21st

More information

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.

Our data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management. AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled

More information

How to Meet 24 by Forever Cooling Demands of your Data Center

How to Meet 24 by Forever Cooling Demands of your Data Center W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the

More information

Data Center Solutions

Data Center Solutions Data Center Solutions Delivering Solutions to Maximize Data Center Efficiencies Featured Brand Belden Meeting the Critical Needs of the Data Center Belden solutions meet the primary challenges of today

More information

AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland

AIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course

More information

disaster recovery - the importance of having a plan

disaster recovery - the importance of having a plan disaster recovery - the importance of having a plan Disasters, whether manmade or acts of nature, can strike anywhere at any time with little or no warning. In fact, companies that do not have a Disaster

More information

plantemoran.com {Data center. } Design standards

plantemoran.com {Data center. } Design standards plantemoran.com {Data center. } Design standards IT systems have become critical for the day-to-day operations of today s organizations. {Data center.} Design standards IT systems are critical for the

More information

How green is your data center?

How green is your data center? Siemens Answers: Sustainable Future How green is your data center? Istanbul June 01, 2010 Agenda 1 Solution 2 Siemens Data Center Approach 2 Designing with multiple power density zones can reduce energy

More information

Data Center Solutions

Data Center Solutions Data Center Solutions Delivering Solutions to Maximize Data Center Efficiencies One Enterprise. One Infrastructure. One Partner. Belden Meeting the Critical Needs of the Data Center Belden solutions meet

More information

Navigating the Pros and Cons of Structured Cabling vs. Top of Rack in the Data Center

Navigating the Pros and Cons of Structured Cabling vs. Top of Rack in the Data Center May 2013 Navigating the Pros and Cons of Structured Cabling vs. Top of Rack in the Data Center Executive Summary There is no single end-all cabling configuration for every data center, and CIOs, data center

More information

THE GREEN DATA CENTER

THE GREEN DATA CENTER GREEN IT THE GREEN DATA CENTER WHERE ECOLOGY MEETS ECONOMY We truly live in an information age. Data Centers serve a very important purpose they provide the global community with nearly unlimited access

More information

How To Determine Data Center Reliability

How To Determine Data Center Reliability DATA CENTER INDUSTRY WHITE PAPER Data Center Services End-To-End Reliability Published by: Isaak Technologies, Inc. TABLE OF CONTENTS 1. Overview... 1 2. Reliability Classifications... 2 Reliability Class-0...

More information

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.

Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite

More information

Colocation. Introduction. Structure of the service. Service Description

Colocation. Introduction. Structure of the service. Service Description Introduction IP-Only provides colocation services for customers with very high reliability and availability requirements. In combination with its transmission and IP services, IP-Only offers space in high-security

More information

Building a data center. C R Srinivasan Tata Communications

Building a data center. C R Srinivasan Tata Communications Building a data center C R Srinivasan Tata Communications Introduction Data Center as defined by TIA 942 A building or a portion of a building whose primary function is to house a computer room and its

More information