1 Data Center Designs and Hospital Operations Designing for Data Center Availability and the Effect on Daily Operations Joe Harris, PE, RCDD Senior Engineer, AECOM Data Centers and Hospitals June 10, 2015
2 AECOM Healthcare Practice Industry Leader ENR RANKING 400 Hospitals 300 Ambulatory Care Centers 200 Medical Group Practice Centers 40 Academic Medical Centers 10,000 Patient Rooms #1 DESIGN FIRM #1 PURE DESIGN #1 HEALTH CARE #1 GENERAL BUILDING Top 10 Worldwide, Modern Healthcare Survey 2014 Page 2
3 About Me 20+ Years Industry Experience Data Center Design across multiple industries: Healthcare Military Commercial Industrial Professional Engineer (Ohio) Registered Communications Distribution Designer Registered Telecommunications Project Manager Page 3
4 Learning Objectives: Understand the reliance on the data center Learn why we need to design for reliability and availability Understand how design decisions affect availability based on: Space planning Infrastructure Security concerns Services and Maintenance June 10, 2015 Data Centers and Hospitals Page 4 Client logo
5 Agenda Data Center Definition Hospital and Data Center Trends Availability and Reliability Design Considerations Conclusion Page 5 Client logo
6 Industry Acronyms TIA Telecommunications Industry Association ANSI American National Standards Institute BICSI Building Industry Consulting Service International PUE Power Usage Effectiveness ASHRAE American Society of Heating, Refrigerating, and Air- Conditioning Engineers NEC National Electric Code NFPA National Fire Protection Association NEBS Network Equipment-Building System CRAC Computer Room Air Conditioner Page 6 Client logo
7 Data Center Defined
8 The Data Center Is: Large Heat Source Mechanical Engineer Large Electrical Load Electrical Engineer The Heart of Our Network Hospital IT Staff Our Most Critical Space CIO Expensive CFO RISK! Security Director It Depends On your Viewpoint Page 8
9 Official Definition Data Center A building or portion of a building whose primary function is to house a computer room and its support areas ANSI/BICSI Page 9
10 Data Center Components Computer Room Network Core Switching Servers Storage Cabling Power Distribution Cooling Distribution (Most Critical IT Space) Support Areas Entrance Room(s) Electrical Room(s) Mechanical Rooms(s) Operations Center Crisis Response Room Maintenance Areas Support Staff Offices Loading Docks Receiving/Storing Areas Battery Rooms Telecommunications Rooms (Enables everything that happens) Page 10
11 Expanded (Functional) Definition Data Center A building or portion of a building whose primary function is to house a computer room and its support areas 1, designed as a set of interdependent systems operating together to create the processing and networking capabilities required to meet the current business demands. 1. ANSI/BICSI Page 11
12 Hospital and Data Center Trends
13 Hospital Trends Electronic Health Records More Processing More Bandwidth More Storage More Risk Big Data Electronic Health Information Exchange Radiology reports Lab results Clinical Care Summaries Medication lists F Data sharing inside and outside of the creating organization Page 13
14 Hospital Trends Bottom Line It s a connected world Healthcare providers rely on connected systems to provide and receive patient information Services are being delivered electronically Patient diagnostics and historical data are online Critical systems are integrated Everything Relies on the Availability of Electronic Data Page 14
15 Data Center Trends THE OLD DAYS (15 Years Ago) Simple Backups 24 Hour Replacement Contracts Disaster Recovery Fire, flood, tornado Checklist Management Anticipate every disaster Hot sites TODAY Tier IV = 2(N+1),.4 hour, % Worms, Hackers, Backdoors Terrorism Political Concerns Power grid failure Liability and Regulatory Compliance Cascading Events Handle unexpected disaster Fwithout downtime Page 15
16 Data Center General Trends Greater focus on availability and reliability Extreme power and cooling requirements Increased Focus on preventing Data Loss Consolidation of servers Virtualization Struggles with predicting growth rates Converging low-voltage systems More Focus on Efficiency and Cost of Operations PUE Dark Data Centers Page 16
17 Coming Together Electronic Data Bandwidth Connectivity Complexity Availability Reliability Services Efficiency Everything Relies on the Availability of Electronic Data Page 17
18 Availability and Reliability
19 What Happens When our Data Center Goes Down? We lose: Link to the outside world Server based applications Storage availability Ability to work remotely Connectivity Systems availability Reputation Everything Relies on the Availability of Electronic Data Page 19
20 Availability vs Reliability Reliability is the ability of a system or component to perform its required functions under stated conditions for a specified period of time Availability is the probability that a component or system is in a condition to perform its intended function affected by more events than a failure requiring repair or replacement of a component or system Availability = Uptime / Total Time (within the observation interval) Page 20
21 Reliability Risk Metrics Failure Risks Mean Time to Failure (MTTF) Mean Time to Repair (MTTR) Susceptibility to natural disasters Fault tolerance Single Points of Failure in a system Maintainability Maintenance Programs Page 21
22 Availability Classifications % Availability = 5 Minutes of Downtime per Year ANSI/BICSI and TIA Classes, 5 Sub groups New Industry Standard 0 = No redundancy 4 = Component AND System Redundancy Uptime Institute Tier Standards and Certifications Proprietary to Uptime Institute Tier 1 = Basic Site Tier 4 = Fault Tolerant 2N+1 Redundancy = 2 Complete Systems + 1 extra component Page 22
23 Tiering For Dummies TIER I/Class 0 and 1 Car without a spare tire. Stop the car and wait for it to be fixed. TIER II/Class 2 Four tires and a spare. Stop, fix the flat, drive on. TIER III/Class 3 Run Flat tires. Drive slower until you can replace the tire. TIER IV/Class 4 Change the tires, transmission, and engine while driving at 60MPH. Page 23
24 9 s and N s 9 s of availability Measure of uptime expressed as a percentage (i.e. 99.9%) Five 9 s = % Availability o Equates to five minutes of downtime per year o Each additional 9 adds 50% to the data center cost. N s of redundancy Redundancy applied to components, systems, services, etc. Can be UPS systems, Switches, CRACs, etc. 2N+1 = 2 times the required number + 1 extra Page 24
25 How Much Redundancy is EnoughE ETo Guarantee Availability? Page 25
26 Design Considerations
27 Design Considerations Space Planning Infrastructure Security Services and Maintenance Page 27
28 Design Considerations Space Planning Infrastructure Security Services and Maintenance Page 28
29 Space Planning Site Selection Where should you put the DC? Adjacencies What should be near the DC? What should not? Layout How should the DC space be arranged? Page 29
30 Space Planning Site Selection Stand Alone DC Location Criteria Availability of and access to reliable Telecommunications Availability of and access to reliable Power Other Utilities (Water, Sanitation, Natural Gas, Etc.) Transportation Access Property adjacencies Environmental Influences (Seismic, Flooding, Air Quality, Wind) Separation from your primary or backup data center Page 30
31 Space Planning Site Selection DC in a Hospital Location Criteria No patient access Not on ground floor or below Protected from outside walls Access to freight elevator Not near EMI/RFI sources Not near sensitive equipment No foreign piping systems in/over the space Away from large equipment (air handlers, MV Transformers, etc.) No Drains running through the computer room! (Avoid all water sources) Page 31
32 Space Planning Site Selection Inside a Hospital Public Space Secure Hospital Staff Secure IT Staff Computer Room Semi-Private Semi-Public Page 32
33 Space Planning Adjacencies Computer Room Control Room Data Storage Symb Adjacency Computer Room Control Room Data Storage Lobby X X Z X Y Z X Y N Lobby Z Z N X Y Z N Connected Near Away From No Relation Page 33
34 Space Planning Data Center Layout Work Room Secure Storage Unpacking Staging Computer Room HVAC / ELEC Computer Room Secure Corridor Control Room WAR Data Storage Telecom Entrance Room Secure Receiving Security Center IT Personnel Spaces Page 34
35 Design Considerations Space Planning Infrastructure Security Services and Maintenance Page 35
36 Infrastructure Power UPS Systems Power Distribution Cooling Computer Room Air Conditioners (CRACs) Hot (or cold) Air Containment Structured Cabling Fiber, Copper, Routing Page 36
37 Power Power Company Generators Uninterruptable Power Supply Automatic Transfer Switches Power Distribution Units Power Whips and Strips Power Cords Redundancy Redundancy Page 37
38 Cooling ASHRAE TC 9.9, ANSI/TIA-942, NEBS GR-3160 All slightly different Operational Temp Max Rate of Change Operational RH Max Dew point ANSI/TIA ºF 77ºF 9ºF/hour 40% - 55% 69.8ºF NEBS GR ºF 80ºF 54ºF/Hour 55% Max 82ºF ASHRAE TC ºF 80.6ºF 9ºF/Hour 60% Max 42ºF - 59ºF Page 38
39 Cooling / Thermal Management The primary goal is to deliver properly cooled air, in the correct volume, directly in front of all active equipment. Page 39
40 Without Isolation of Return Air Path Page 40
41 Return Air Path Isolation Hot air is physically segregated from cold air in return air duct Rear door is sealed to prevent exhaust air from leaking into room Air Dams and filler panels in front of cabinet prevent air recirculation inside cabinet Room A/C is easy to manage, with little regard to concentrated heat loads Cabinets can be placed and oriented any way desired Cold air delivery can be shared throughout room with fewer zone issues Page 41
42 Cooling / Thermal Management HVAC Design should provide for Control Filtration Direct cooled equipment Avoidance of recirculation and bypass air Redundant cooling systems to meet the class design. Page 42
43 Cooling and Structured Cabling Heat is the #1 cause of electronic component failures Data Centers and Hospitals June 10, 2015 Page 43
44 Under Floor Separation of Media Page 44
45 Defined Cable Management Data Centers and Hospitals June 10, 2015 Page 45
46 Structured Cabling The fiber and copper cabling that connects all of the networked components and distribution areas of the computer room. Consists of: Fiber Single Mode and/or 50 Micron Laser Optimized Multi-Mode (OM4 Recommended) Copper Category 6A or better Proprietary Cabling (some switch manufacturers) 10 Gig backbone minimum Migration path to 40/100 gig (25 gig?) Pre-terminated cabling ORGANIZATION Page 46
47 Structured Cabling Areas of the Computer Room MDA Main Distribution Area Network Core and Cross Connect HDA Horizontal Distribution Area Backbone connections to serve multiple cabinets (typically end of row or middle of row) ZDA Zone Distribution Area Cross connect point similar to a consolidation point EDA Equipment Distribution Area Connections to the end equipment (servers, SAN, etc.) Page 47
48 FAN STATUS -48 V TO -60 V -40 A 1800 VA Cisco Systems, Inc INPUT OK FAN OK OUTPUT FAIL Switch must be in off "O" position to Install/Remove power supply. Fastener must be fully enaged prior to operating power supply. Power Supply 1 Power Supply 2 Catalyst 6500SERIES -48 V TO -60 V -40 A VA Cisco Systems, Inc. INPUT OK FAN OK OUTPUT FAIL Switch must be in off "O" position to Install/Remove power supply. Fastener must be fully enaged prior to operating power supply. MDA U47 U46 U45 U44 U43 U42 U41 U40 U39 U38 U37 U36 U35 U34 U33 U32 U31 U30 U29 U28 U27 U26 U25 U24 U23 U22 U21 U20 U19 U18 U17 U16 U15 U14 U13 U12 U11 U10 U09 U08 U07 U06 U05 U04 U03 U02 U01 Front View Catalyst 6500 SERIES U47 U46 U45 U44 U43 U42 U41 U40 U39 U38 U37 U36 U35 U34 U33 U32 U31 U30 U29 U28 U27 U26 U25 U24 U23 U22 U21 U20 U19 U18 U17 U16 U15 U14 U13 U12 U11 U10 U09 U08 U07 U06 U05 U04 U03 U02 U01 INSTALL RUN Rear View Fiber Termination INSTALL RUN Includes the core switching and main cross connect for the data center Hub of cabling infrastructure for the Data Center Has backbone cabling to all HAD s and TR s Page 48
49 HDA HDA A RACK #1 RACK #2 RACK #3 RACK #4 RACK #5 RACK #6 HDA B FIBER PATCH PANEL A 48 UTP PATCH PANEL A SIDE (28 ACTIVE) 48 UTP PATCH PANEL A SIDE (28 ACTIVE) 48 UTP PATCH PANEL A SIDE (28 ACTIVE) 48 UTP PATCH PANEL A SIDE (28 ACTIVE) 48 UTP PATCH PANEL A SIDE (28 ACTIVE) 48 UTP PATCH PANEL A SIDE (28 ACTIVE) FIBER PATCH PANEL ROUTE B UTP PATCH PANEL #1 48 UTP PATCH PANEL B SIDE (28 ACTIVE) 48 UTP PATCH PANEL B SIDE (28 ACTIVE) 48 UTP PATCH PANEL B SIDE (28 ACTIVE) 48 UTP PATCH PANEL B SIDE (28 ACTIVE) 48 UTP PATCH PANEL B SIDE (28 ACTIVE) 48 UTP PATCH PANEL B SIDE (28 ACTIVE) UTP PATCH PANEL #1 UTP PATCH PANEL #2 24 UTP PATCH PANEL KVM & MGMT 24 UTP PATCH PANEL KVM & MGMT 24 UTP PATCH PANEL KVM & MGMT 24 UTP PATCH PANEL KVM & MGMT 24 UTP PATCH PANEL KVM & MGMT 24 UTP PATCH PANEL KVM & MGMT UTP PATCH PANEL #2 UTP PATCH PANEL #3 UTP PATCH PANEL #3 UTP PATCH PANEL #4 UTP PATCH PANEL #4 UTP PATCH PANEL #5 UTP PATCH PANEL #5 UTP PATCH PANEL #6 UTP PATCH PANEL #6 UTP PATCH PANEL #7 UTP PATCH PANEL #7 UTP PATCH PANEL KVM & MGMT RACKS 1 & 2 SERVER SPACE SERVER SPACE SERVER SPACE SERVER SPACE SERVER SPACE SERVER SPACE UTP PATCH PANEL KVM & MGMT RACKS 7&8 UTP PATCH PANEL KVM & MGMT RACKS 3 & 4 UTP PATCH PANEL KVM & MGMT RACKS 9 &10 UTP PATCH PANEL KVM & MGMT RACKS 5 & 6 UTP PATCH PANEL KVM & MGMT RACKS 11 & 12 SWITCH SPACE SWITCH SPACE Contains the horizontal cross connect Distribution point for the equipment distribution areas Has horizontal cabling to all EDA s Typically contains switching equipment to support the EDA Page 49
50 ZDA Connection point between HAD and EDA Contains no active electronics Limited to 288 connections Can be installed in cabinet, under floor, over head, etc. Comparable to Consolidation point located in the Work Area in Page 50
51 EDA U47 U46 U45 U44 U43 U42 U41 U40 U39 Front View U47 U46 U45 U44 U43 U42 U41 U40 U39 Rear View Fiber Termination Area allocated for the end equipment Includes horizontal cable and connections to the HAD U38 U37 U36 U35 U34 U38 U37 U36 U35 U34 Point-to-point cabling permitted U33 U32 U31 U30 U29 U28 U27 U26 Space for Optional Keyboard & Monitor U33 U32 U31 U30 U29 U28 U27 U26 Comparable to the location of end equipment in 568 U25 U25 U24 U24 U23 U23 U22 U22 U21 U21 U20 U20 U19 U19 U18 U18 U17 U17 U16 U16 U15 U15 U14 U14 U13 U13 U12 U12 U11 U11 U10 U10 U09 U09 U08 U08 U07 U07 U06 U06 U05 U05 U04 U04 U03 U03 U02 U02 U01 U01 Page 51
52 Structured Cabling Areas of the Computer Room Page 52
53 Structured Cabling Redundancy Page 53
54 Design Considerations Space Planning Infrastructure Security Services and Maintenance Page 54
55 Security Three Main Components Architectural Electronic Operational Page 55
56 Data Center Security Accreditations? Courtesy Altus Technologies Page 56
57 Security Architectural Landscaping Lighting Doors/Locks/Glazing Building features that contribute to security Electronic Access Control Intrusion Detection CCTV Duress Operational Security Staffing Post Orders Guard Tours Policies and procedures Contingency Planning Page 57
58 Information Security (InfoSec) Confidentiality Availability Integrity The best configured firewall in the world can t stand up to a well placed brick. Page 58
59 Design Considerations Space Planning Infrastructure Security Services and Maintenance Page 59
60 Services and Maintenance Testing Periodically throughout the life of the system Include backup systems Scheduled for off peak times System Maintenance includes Cabling Electrical HVAC IT Equipment Security Page 60
61 Services and Maintenance Cleaning is critical and often overlooked All spaces (above and below) Part of maintenance contract Data Centers and Hospitals June 10, 2015 Page 61
62 Services and Maintenance An insufficient maintenance plan will result in extended downtime. Regularly scheduled maintenance must be carefully planned and performed by persons familiar with the entire system and all inter-dependencies Page 62
63 Conclusion
64 Design for Availability Hospitals require a high level of data availability to operate efficiently Data center designs need to focus on systems availability By designing for availability in the data center, we can help ensure hospital operations are not interrupted due to lack of electronic services and data Everything Relies on the Availability of Electronic Data Page 64
65 Thank You Data Centers and Hospitals June 10, 2015
Data center upgrade proposal. (phase one)
Data center upgrade proposal (phase one) Executive Summary Great Lakes began a recent dialogue with a customer regarding current operations and the potential for performance improvement within the The
More informationDat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD
Data Center Standards Roundup BICSI, TIA, CENELEC, ISO Steve Kepekci, RCDD Introduction Regardless of business activity or size, all information technology (IT) groups have similar needs Provide secure,
More informationTIA-942 Data Centre Standards Overview WHITE PAPER
TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and
More informationSite Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME
Site Preparation Management Co., Ltd. March 1st 2013 By Nara Nonnapha, ATD UPTIME 2 AGENDA SESSION -1 What is Data Center? SESSION -2 Equipment and Components SESSION -3 Standard in designing Data Center
More informationDealing with Thermal Issues in Data Center Universal Aisle Containment
Dealing with Thermal Issues in Data Center Universal Aisle Containment Daniele Tordin BICSI RCDD Technical System Engineer - Panduit Europe Daniele.Tordin@Panduit.com AGENDA Business Drivers Challenges
More informationANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers
ANSI/TIA-942 Telecommunications Infrastructure Standards for Data Centers Jonathan Jew jew@j-and and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center committee Co-chair BICSI data centers
More informationSupporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers
CABINETS: ENCLOSED THERMAL MOUNTING MANAGEMENT SYSTEMS WHITE PAPER Supporting Cisco Switches In Hot Aisle/Cold Aisle Data Centers 800-834-4969 techsupport@chatsworth.com www.chatsworth.com All products
More informationHow To Write An Infrastructural Standard For Data Center Infrastructure
Infrastructure Standard for Data Centers ANSI/CSA/EIA/TIA-942 (PN-3-0092) Introduction When approved, the standard will be: ANSI/CSA/EIA/TIA-942 Telecommunications Infrastructure Standard for Data Centers
More informationBuilding a Tier 4 Data Center on a Tier 1 Budget
Building a Tier 4 Data Center on a Tier 1 Budget A Walk Through of TIA-942 Peter P. Charland III, RCDD/NTS/WD, CET RTKL Associates Inc. March 27, 2008 BICSI South Central Region Meeting Denver, CO TIA-942
More informationData Center Presentation
Data Center Presentation The NetSource Datacenter. Agenda General Layout of Data Center Policies and Procedures Designed to Latest Standards High Performance High Reliability High Security Design Details
More informationData Center Standards Making Progress on Many Fronts. Jonathan Jew J&M Consultants, Inc jew@j-and-m.com
Data Center Standards Making Progress on Many Fronts Jonathan Jew J&M Consultants, Inc jew@j-and-m.com J&M Consultants - 2008 Speaker Jonathan Jew Co-chair TIA TR-42.1.1 Data Center working group ANSI/TIA-942
More informationData Center Cabling Design Trends
Data Center Cabling Design Trends BICSI Regional Meeting Maurice Zetena Fiber Connect Infrastructure Trends Infrastructure Trends Any to All Trunk Cabling Trends: Data Center Infrastructure Media Choice:
More informationTitle: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria
Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center
More informationThis 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits.
This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits. DCD, DCOM, DCE DESIGN IMPLEMENTATION BEST PRACTICE OPERATION & MANAGEMENT DATA
More informationData Center Optimization: Component Choice. Innovative Design. Enabling Infrastructure
Data Center Optimization: Component Choice and Innovative Design Combine to Allow the Creation of an Enabling Infrastructure Data Center Spaces Data Center Spaces as Defined by the TIA 942 Standard Source:
More informationBenefits of. Air Flow Management. Data Center
Benefits of Passive Air Flow Management in the Data Center Learning Objectives At the end of this program, participants will be able to: Readily identify if opportunities i where networking equipment
More informationManaging Data Centre Heat Issues
Managing Data Centre Heat Issues Victor Banuelos Field Applications Engineer Chatsworth Products, Inc. 2010 Managing Data Centre Heat Issues Thermal trends in the data centre Hot Aisle / Cold Aisle design
More informationKeyword: TIA 942, Tier level, Nuclear Data Center. Introduction
Nuclear Data Center International Standard Towards TSO Initiative Raja Murzaferi Raja Moktar, Mohd Fauzi Haris, Siti Nurbahyah Hamdan, Saaidi Ismail,Radhiah Jamaluddin, Nursuliza Samsudin. IT Center, Technical
More informationTelecommunications Infrastructure Standard for Data Centers. 802.3 Tutorial
Telecommunications Infrastructure Standard for Data Centers 802.3 Tutorial Prepared by: Jonathan Jew - J&M Consultants and Chris DiMinico - MC Communications - Co-chairs TR42.1.1 TR42: Data Center Standard
More informationAutomating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011
Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011 Opportunities in Automating Infrastructure Why Automation in Data Center? Tiers, compartments and complexity Work
More informationTIA-942: Data Center Standards
plantemoran.com TIA-942: Data Center Standards Sri Chalasani Merit 2010 Conference May 25, 2010 Objectives What are concerns in the data center? Data center standards & best Practices Data Center Definition
More informationGreat Lakes Data Room Case Study
Great Lakes Data Room Case Study WeRackYourWorld.com Problem: During a warm summer period in 2008, Great Lakes experienced a network outage due to a switch failure in the network enclosure. After an equipment
More informationANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers
ANSI/TIA-942 Telecommunications Infrastructure Standard for Data Centers Jonathan Jew jew@j-and-m.com J&M Consultants, Inc Co-chair TIA TR-42.1.1 data center working group Co-chair BICSI data centers standards
More informationEnergy-efficient & scalable data center infrastructure design
Seminar am 30. September 2010 in Wetzlar Nachhaltigkeit durch UPI (Unified Physical Infrastructure) Vortrag von Stefan Fammler: Energieeffiziente Strategien im Rechenzentrum Energy-efficient & scalable
More informationData Center Management. Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM
Data Center Management Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM A physical place that houses a computer network's most critical systems, including back-up power supplies, air conditioning, and
More information7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America
7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer
More informationBICSI 002 / TIA 942 / Uptime
BICSI 002 / TIA 942 / Uptime Which Data Center Standard Should I Follow Phil Isaak, PE, P.Eng., RCDD, DCDC President, Master Instructor Isaak Technologies Inc. Standards Who are these People Standards
More informationCHICAGO S PREMIERE DATA CENTER
CHICAGO S PREMIERE DATA CENTER White City collocation was founded in June, 2010 by a highly experienced industry executive in conjunction with several investment companies. The strategy of White City is
More informationCURBING THE COST OF DATA CENTER COOLING. Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers
CURBING THE COST OF DATA CENTER COOLING Charles B. Kensky, PE, LEED AP BD+C, CEA Executive Vice President Bala Consulting Engineers OVERVIEW Compare Cooling Strategies in Free- Standing and In-Building
More informationEnabling an agile Data Centre in a (Fr)agile market
Enabling an agile Data Centre in a (Fr)agile market Phil Dodsworth Director, Data Centre Solutions 2008 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without
More informationVideo Systems and Data Center Design Wiring Plant Designation Terminology Infrastructure Deployment
Video Systems and Data Center Design Wiring Plant Designation Terminology Infrastructure Deployment Steve Surfaro Group Manager Strategic Technical Liaison Panasonic System Solutions Company surfaros@us.panasonic.com
More informationNetwork Design. Yiannos Mylonas
Network Design Yiannos Mylonas Physical Topologies There are two parts to the topology definition: the physical topology, which is the actual layout of the wire (media), and the logical topology, which
More informationData Centre Design ready for your future
Data Centre Design ready for your future Introduction to Data Centres What is a Data Centre? The definition of a Data Centre according to TIA-942 is a building or portion of a building whose primary function
More informationSo you want to build a data centre? Look what s coming from BICSI! Matt Flowerday Capitoline FZC mflowerday@capitoline.org
So you want to build a data centre? Look what s coming from BICSI! Matt Flowerday Capitoline FZC mflowerday@capitoline.org So you want to build a data centre? Who do you contact? How do you work out what
More informationSpecialty Environment Design Mission Critical Facilities
Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,
More informationEnergy Efficiency Opportunities in Federal High Performance Computing Data Centers
Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
More informationWhat is a Datacenter?
What is a Datacenter? Telecom Room Primarily Cross Connect Equipment and switches. Computer room A room whose primary function is to house computer equipment. (Servers, Storage) 5 or less cabinets Small
More informationData Centers. Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions
Data Centers Mapping Cisco Nexus, Catalyst, and MDS Logical Architectures into PANDUIT Physical Layer Infrastructure Solutions 1 Introduction The growing speed and footprint of data centers is challenging
More informationEnergy Efficiency in the Data Center
Energy Efficiency in the Data Center Maria Sansigre and Jaume Salom Energy Efficieny Area Thermal Energy and Building Performance Group Technical Report: IREC-TR-00001 Title: Energy Efficiency in the Data
More informationThe following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space.
The following are general terms that we have found being used by tenants, landlords, IT Staff and consultants when discussing facility space. Terminology: Telco: Dmarc: NOC: SAN: GENSET: Switch: Blade
More informationData Center Overview Document
Overview NetSource is a Chicago area (Naperville) hosting company that owns and operates its own world class datacenter. The initial datacenter buildout was put into operation in 2007 and expanded in 2013.
More informationEducation Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009
Education Evolution: Scalable Server Rooms George Lantouris Client Relationship Manager (Education) May 2009 Agenda Overview - Network Critical Physical Infrastructure Cooling issues in the Server Room
More informationOptimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER
Optimizing Network Performance through PASSIVE AIR FLOW MANAGEMENT IN THE DATA CENTER Lylette Macdonald, RCDD Legrand Ortronics BICSI Baltimore 2011 Agenda: Discuss passive thermal management at the Rack
More information19 Site Location, Design and Attributes. Site Location, Design and Attributes
1 Site Location, Design and Attributes The Primary Data Center shall be physically located on Oahu, Hawaii. 2 Site Location, Design and Attributes The Primary Data Center shall be located at least 1 mile
More informationZone Distribution in the Data Center
Zone Distribution in the Data Center By Jennifer Cline, RCDD As data centers face the continued need to expand and grow, the fundamental concerns and needs remain constant. Key concerns of the data cabling
More informationData Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s"
Data Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s" Data centre Standard EN50173-5 : "Telecommunications Infrastructure for Data Centre s Due, 2006 Gary Highton,
More informationin other campus buildings and at remote campus locations. This outage would include Internet access at the main campus.
DATA CENTER The current Campus Data Center is located within historic Founders Hall which is in a less-than ideal location for a variety of reasons, but is typical of an existing campus IT infrastructure
More informationData Centre Cabling. 20 August 2015 Stefan Naude RCDD The SIEMON Company
Data Centre Cabling 20 August 2015 Stefan Naude RCDD The SIEMON Company Agenda 1. Data Centre Standards 2. The Need for Speed 3. Copper in the Data Centre 4. Fibre in the Data Centre 5. Top of Rack vs
More informationADC-APC Integrated Cisco Data Center Solutions
Advanced Infrastructure Solution for Cisco Data Center 3.0 Ordering Guide ADC-APC Integrated Cisco Data Center Solutions The evolution of data centers is happening before our eyes. This is due to the
More informationIntroduction to Datacenters & the Cloud
Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview
More informationUnified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers
Unified Physical Infrastructure SM (UPI) Strategies for Smart Data Centers Deploying a Vertical Exhaust System www.panduit.com WP-09 September 2009 Introduction Business management applications and rich
More informationPower and Cooling for Ultra-High Density Racks and Blade Servers
Power and Cooling for Ultra-High Density Racks and Blade Servers White Paper #46 Introduction The Problem Average rack in a typical data center is under 2 kw Dense deployment of blade servers (10-20 kw
More informationDesigning the Data Center
Designing the Data Center Asef Baddar, RCDD May -, 00 Talking points What are Data Centers? Why Data Centers? The components of the Data Center Approaching the Data Center design Breakdown of the components
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationUnified Physical Infrastructure (UPI) Strategies for Thermal Management
Unified Physical Infrastructure (UPI) Strategies for Thermal Management The Importance of Air Sealing Grommets to Improving Smart www.panduit.com WP-04 August 2008 Introduction One of the core issues affecting
More informationBRUNS-PAK Presents MARK S. EVANKO, Principal
BRUNS-PAK Presents MARK S. EVANKO, Principal Data Centers of the Future and the Impact of High Density Computing on Facility Infrastructures - Trends, Air-Flow, Green/LEED, Cost, and Schedule Considerations
More informationGreen Data Centre Design
Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS
More informationGUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY. Public Sector ICT Special Working Group
GUIDE TO ICT SERVER ROOM ENERGY EFFICIENCY Public Sector ICT Special Working Group SERVER ROOM ENERGY EFFICIENCY This guide is one of a suite of documents that aims to provide guidance on ICT energy efficiency.
More informationPresenters Brett Weiss, Gabe Martinez, Brian Kroeger.
1 Presenters Brett Weiss, Gabe Martinez, Brian Kroeger. Topics to be covered: Cable identification Purpose of the various cable types Installation techniques Building Infrastructure Overview of networking
More informationManaging Cooling Capacity & Redundancy In Data Centers Today
Managing Cooling Capacity & Redundancy In Data Centers Today About AdaptivCOOL 15+ Years Thermal & Airflow Expertise Global Presence U.S., India, Japan, China Standards & Compliances: ISO 9001:2008 RoHS
More informationAT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ)
AT&T Internet Data Center Site Specification - Phoenix Area (Mesa, AZ) Site Biography Market Area: Phoenix, Mesa, Tempe, Chandler, Scottsdale, AZ Location: Mesa, AZ 85201 Address: 1301 University Blvd.
More informationData Center Design Considerations. Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc.
Data Center Design Considerations Walter P. Herring, RCDD/LAN/OSP Senior Systems Specialist Bala Consulting Engineers, Inc. Data Center Design: Overall Expectations Need: Prime vs. Redundant vs. Mirrored
More informationTop of Rack: An Analysis of a Cabling Architecture in the Data Center
SYSTIMAX Solutions Top of Rack: An Analysis of a Cabling Architecture in the Data Center White paper Matthew Baldassano, Data Center Business Unit CommScope, Inc, June 2010 www.commscope.com Contents I.
More informationData Center Network Topologies
Data Center Network Topologies. Raj Jain Washington University in Saint Louis Saint Louis, MO 63130 Jain@cse.wustl.edu These slides and audio/video recordings of this class lecture are at: 3-1 Overview
More informationHow To Improve Energy Efficiency In A Data Center
Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice
More informationabstract about the GREEn GRiD
Guidelines for Energy-Efficient Datacenters february 16, 2007 white paper 1 Abstract In this paper, The Green Grid provides a framework for improving the energy efficiency of both new and existing datacenters.
More informationADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER
ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect WHITE PAPER ADC s Data Center Optical Distribution Frame: The Data Center s Main Cross-Connect Introduction The primary
More informationElement D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationwww.commscope.com Data Center Topology Guide
www.commscope.com Data Center Topology Guide Data Center Areas 1 Network Operations Center (NOC) The network operations center or NOC is the location where control of all data center networking, server
More informationConsiderations for choosing top-of-rack in today's fat-tree switch fabric configurations
From the April, 2014 Issue of Cabling Installation & Maintenance Magazine Considerations for choosing top-of-rack in today's fat-tree switch fabric configurations Pros and cons exist for each configuration,
More informationIBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com. 2011 IBM Corporation
IBM Twin Data Center Complex Ehningen Peter John IBM BS peter.john@de.ibm.com Overview Profile IBM owned facility 6447 m² IT-Space Infrastructure concurrent maintainable (Tier Level 3) Feed-ins of Power
More informationOnly a matter of power supply and air conditioning? Joachim Faulhaber TÜV Informationstechnik GmbH
Data Center Availability Only a matter of power supply and air conditioning? Joachim Faulhaber TÜV Informationstechnik GmbH Agenda Security Assessment Uptime Approach Risks and Threats Availability Principles
More informationData Center Commissioning: What you need to know
Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,
More informationData Center Components Overview
Data Center Components Overview Power Power Outside Transformer Takes grid power and transforms it from 113KV to 480V Utility (grid) power Supply of high voltage power to the Data Center Electrical Room
More informationFEAR Model - Review Cell Module Block
F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data
More informationThe Three Principles of Data Center Infrastructure Design WHITE PAPER
The Three Principles of Data Center Infrastructure Design WHITE PAPER The Three Principles of Data Center Infrastructure Design Understand These Three Principles and You ll: Lower your total cost of ownership
More informationData Center Knowledge, Vision Control
Data Center Knowledge, Vision Control Objective Overview of the progressive trends in Data Centers, driven by Intelligent Infrastructure Solutions Data Center Layout Secured Storage Back up Core Backbone
More informationLiquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED.
Liquid Cooling Solutions for DATA CENTERS - R.M.IYENGAR BLUESTAR LIMITED. Presentation Goals & Outline Power Density Where we have been- where we are now - where we are going Limitations of Air Cooling
More informationSiemon 10G ip. Data Centre Solution WHITE PAPER. Executive Summary
Siemon 10G ip Data Centre Solution Executive Summary The term data centre conjures up different meanings to different people. Some would argue that the data centre is the room where the servers are stored.
More informationCooling Small Server Rooms Can Be. - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com
Cooling Small Server Rooms Can Be Inexpensive, Efficient and Easy - Jim Magallanes Computer Room Uptime: www.cruptime.com Uptime Racks: www.uptimeracks.com Server Rooms Description & Heat Problem Trends
More informationRe Engineering to a "Green" Data Center, with Measurable ROI
Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices
More informationData Center Colocation Build vs. Buy
Data Center Colocation Build vs. Buy Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for
More informationA Quick Primer on Data Center Tier Classifications
A Quick Primer on Data Center Tier Classifications What You Should Know Before Starting a Data Center Project White Paper Abstract Data center facility projects are often driven by the Uptime Institute
More informationSubject: County of Los Angeles Data Center Space Requirement
Subject: County of Los Angeles Data Center Space Requirement The County of Los Angeles, Chief Executive Office, Real Estate Division (CEO-RED) is issuing this Property Search for the purchase of a vacant,
More informationHow To Power And Cool A Data Center
Architecting the Green Data Center Viktor Hagen Field Business Development Data Center & High Performance Computing 1 Where we are Today Environmental sustainability is a major global trend for the 21st
More informationOur data centres have been awarded with ISO 27001:2005 standard for security management and ISO 9001:2008 standard for business quality management.
AIMS is Malaysia and South East Asia s leading carrier neutral data centre operator and managed services provider. We provide international class data storage and ancillary services, augmented by an unrivaled
More informationHow to Meet 24 by Forever Cooling Demands of your Data Center
W h i t e P a p e r How to Meet 24 by Forever Cooling Demands of your Data Center Three critical aspects that are important to the operation of computer facilities are matching IT expectations with the
More informationData Center Solutions
Data Center Solutions Delivering Solutions to Maximize Data Center Efficiencies Featured Brand Belden Meeting the Critical Needs of the Data Center Belden solutions meet the primary challenges of today
More informationAIA Provider: Colorado Green Building Guild Provider Number: 50111120. Speaker: Geoff Overland
AIA Provider: Colorado Green Building Guild Provider Number: 50111120 Office Efficiency: Get Plugged In AIA Course Number: EW10.15.14 Speaker: Geoff Overland Credit(s) earned on completion of this course
More informationdisaster recovery - the importance of having a plan
disaster recovery - the importance of having a plan Disasters, whether manmade or acts of nature, can strike anywhere at any time with little or no warning. In fact, companies that do not have a Disaster
More informationplantemoran.com {Data center. } Design standards
plantemoran.com {Data center. } Design standards IT systems have become critical for the day-to-day operations of today s organizations. {Data center.} Design standards IT systems are critical for the
More informationHow green is your data center?
Siemens Answers: Sustainable Future How green is your data center? Istanbul June 01, 2010 Agenda 1 Solution 2 Siemens Data Center Approach 2 Designing with multiple power density zones can reduce energy
More informationData Center Solutions
Data Center Solutions Delivering Solutions to Maximize Data Center Efficiencies One Enterprise. One Infrastructure. One Partner. Belden Meeting the Critical Needs of the Data Center Belden solutions meet
More informationNavigating the Pros and Cons of Structured Cabling vs. Top of Rack in the Data Center
May 2013 Navigating the Pros and Cons of Structured Cabling vs. Top of Rack in the Data Center Executive Summary There is no single end-all cabling configuration for every data center, and CIOs, data center
More informationTHE GREEN DATA CENTER
GREEN IT THE GREEN DATA CENTER WHERE ECOLOGY MEETS ECONOMY We truly live in an information age. Data Centers serve a very important purpose they provide the global community with nearly unlimited access
More informationHow To Determine Data Center Reliability
DATA CENTER INDUSTRY WHITE PAPER Data Center Services End-To-End Reliability Published by: Isaak Technologies, Inc. TABLE OF CONTENTS 1. Overview... 1 2. Reliability Classifications... 2 Reliability Class-0...
More informationHot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc.
Business Management Magazine Winter 2008 Hot Air Isolation Cools High-Density Data Centers By: Ian Seaton, Technology Marketing Manager, Chatsworth Products, Inc. Contrary to some beliefs, air is quite
More informationColocation. Introduction. Structure of the service. Service Description
Introduction IP-Only provides colocation services for customers with very high reliability and availability requirements. In combination with its transmission and IP services, IP-Only offers space in high-security
More informationBuilding a data center. C R Srinivasan Tata Communications
Building a data center C R Srinivasan Tata Communications Introduction Data Center as defined by TIA 942 A building or a portion of a building whose primary function is to house a computer room and its
More information