2 IT systems have become critical for the day-to-day operations of today s organizations.

3 {Data center.} Design standards IT systems are critical for the day-to-day operations of today s organizations. Typically, IT systems within an organization are housed at a centralized location often referred to as the server room or the data center. With many organizations experiencing continued server sprawl or a significant increase in virtual machines, there are increased pressures on the data center in terms of cooling, electrical, airflow, and capacity. Whether you re building a new data center, evaluating your existing internal data center, or evaluating a hosted (commonly referred to as colo ) data center, being proactive in assessing the environment and capacity of the data center can have a significant impact on the uptime, thus impacting efficiency and effectiveness of an organization s IT operations and thus, the overall business. The availability and reliability of critical IT systems can be largely dependent upon the data center s design and its operational and maintenance practices. Typically, the availability of a data center is measured as a percentage of uptime. Generally, uptime of 90 percent or higher is viewed as being highly available; in the case of IT system or data center uptime, however, anything short of 99 percent availability due to unplanned interruptions is considered unacceptable (see Table 1). These inadequacies prevented organizations from responding to outages in a timely manner. According to this study, the per-incident cost of a data center outage can range between $38,969 and $1,017,746 per organization depending upon the industry and size. (Industries surveyed ranged from public sector to financial industries, and the costs included detection, recovery, equipment, IT and end-user productivity, third parties, lost revenue, and business disruption.) In a separate survey conducted by the Aperture Research Institute, the primary causes for data center outages were: human error (57.3 percent), improper controls/configurations (43.7 percent), cooling issues (22.3 percent), and electrical issues (26.2 percent). When coupled with best-in-class operational and maintenance practices, proper data center planning and design can help minimize downtime at the data center. Standardization in the data center According to Wikipedia, a data center is defined as a facility used to house computer systems and associated components, such as telecommunications and storage systems. It generally includes redundant Uptime % Est. Downtime/month Est. Downtime/year % (5-9 s) 0.44 minutes 5.26 minutes 99.99% (4-9 s) 4.38 minutes minutes 99.5% 39 minutes 1 day 19 hours 48 minutes 99.0% 7 hours 12 minutes 3 days 15 hours 36 minutes 95.0% 1 day 12 hours 0 minutes 18 days 6 hours 0 minutes Table 1 According to a study conducted by the Ponemon Institute, approximately 95 percent of the surveyed organizations experienced an unplanned data center outage that was either attributed to inadequate capacity planning, design, or operational practices. or backup power supplies, redundant data communications connections, environmental controls (e.g., air conditioning, fire suppression), and security devices. If you looked up any definition of a data center, it would typically contain terms such as redundancy, 1

4 capacity, power, cooling, monitoring, controls, and security. So what makes one data center different from another? It is the levels of redundancy, fault tolerance, and scalability provided for cooling, electrical, connectivity, the capacity for space, operational procedures in place, and other factors. In the absence of standards, it would be hard to compare one data center to another. Standards provide a methodology for comparing the capabilities of one data center to another and avoiding the dangers of ambiguities or unsubstantiated qualitative references. The Uptime Institute (TUI) provided a first attempt for standardization by using a tiering system a system that specifies the availability, reliability, and capacity of a data center. As the need for data center standardization gained more traction, variations of these standards have arisen. Currently, there are three commonly known tier systems: (1) Uptime Institute TUI, (2) Syska Hennessy Group, and (3) the TIA-942. A fourth standard by ANSI/BICSI is also gaining some traction in this area. The TIA-942 and TUI are the more commonly referenced standards; both provide a tier classification system to help assess a site s infrastructure. TUI and Syska Hennessy Group provide a framework for the disciplines in a data center but lack details, whereas the TIA-942 provides some depth into various aspects that go into a data center. This article focuses on the TIA-942 standard that can be used when planning or comparing data centers. This standard can be used as the benchmark and may be applied to a new environment, retrofitting or assessing an existing data center, or when evaluating co-location facilities. What is the TIA-942? The TIA-942 is a data center standard developed by the Telecommunications Industry Association (TIA); the TIA is accredited by the American National Standards Institute (ANSI) to develop voluntary standards for the telecommunications industry. Also referred to as the ANSI/TIA-942, the TIA-942 standard s purpose is to provide design standards for a data center. This standard takes multidisciplinary design approaches and addresses 20 different areas, thereby promoting cooperation between all parties involved in the design and construction of the data center. This standard may be used to benchmark an existing internal facility or a hosted facility. Given TIA-942 standard s roots, this standard has a strong emphasis on cabling specifications; however, it also details requirements for architectural, electrical, mechanical, security, and other site infrastructure requirements. These 20 areas of the site infrastructure can be broadly classified into the following seven core areas, as shown below in Table 2. Sizing & Selection 1. Design process Security & Protection 9. Fire protection Access Provider & Demarcation 16. Access providers 2. Space planning 10. Physical security 17. Telecom space 3. Site selection 11. Building automation 18. Telecom administration Table 2 Architectural & Structural 4. Architectural 5. Structural 6. Commissioning Cabling Infrastructure 12. Cabinets & racks 13. Cabling pathways 14. Cabling systems Operations 19. Information technology (DRP, Ops Center) 20. Maintenance Electrical & Mechanical 7. Electrical & grounding 15. Cabling field testing 8. HVAC/Mechanical systems 2

5 Based on the criticality or dependence upon the data center, redundancy and fault tolerance need to be built into the site s infrastructure. The level of redundancy and fault tolerance designed into each of these 20 areas of the data center s infrastructure determines its tier. The TIA-942 categorizes data centers into one of four tiers (Tiers 1 4), where higher tiers correspond to higher availability. Each individual area (mechanical, electrical, cabling pathways, etc.) can be assessed independently and categorized into a tier. For example, a data center may be rated Tier 4 for its electrical characteristics but only Tier 3 for its mechanical characteristics. Just like the weakest link in a chain, a data center s overall tier rating is the lowest rating across all aspects of its infrastructure. Annex G of the TIA-942 standard provides the tiering requirements for each of these core areas. What is the difference between the TIA-942 and The Uptime Institute standard? The TIA-942 was developed by ANSI, an industry association, whereas The Uptime Institute (TUI) is a commercial for-profit entity. The TIA-942 tiering scheme uses the TUI s idea of a four-tiered system but provides a prescriptive definition for each tier. The TIA-942 classifies the tiers using quantifiable methods while TUI uses a functional approach. TUI s definition of the tiering guideline is intentionally broad to allow for innovation in achieving the desired level of a site s infrastructure performance. TUI tiers evaluate data centers by their capability to allow maintenance and to withstand a system or sub-system failure. Only the TIA-942 offers a checklist form that can be used to assess the tier of a data center. The TIA-942 tiers are identified by the use of Arabic numbers 1 through 4 (e.g., Tier 3), whereas the Uptime Institute Tiers are identified by the use of Roman numerals I through IV (e.g., Tier III). Both standards identify recommendations for data center design components, but the TIA-942 also covers some operational and sustainability issues. The UTI provides a second document (Tier Standard: Operational Sustainability) to cover operational and sustainability issues. When it comes to the certification of a data center, only the TUI offers a certification program. As of this writing, TUI has awarded 149 certifications worldwide, of which approximately 30 data centers are certified as Tier IV centers based on their design documents, constructed facility, or operational sustainability. So, when data center vendors advertise that they re a Tier IV or Tier III certified data center, be aware how rare that is. On the TIA-942 side, there s no central authority that certifies data centers based on the use of the TIA-942 standard. Claims that a data center is TIA-942 Tier 4 or Tier 3 (notice the use of Arabic numbers) certified may be based on self-assessment or a third-party audit of the TIA-942 checklist. Both standards provide plenty of value, although each has a slightly different philosophy. When selecting a data center, it s advisable to consider both standards and then select the one that best meets your business objectives. 3

6 What is a data center tier classification? Both the TIA-942 and The Uptime Institute created the tier classification to consistently describe the site-level infrastructure required to sustain data center operations. Each individual tier represents the requirements for the data center design; the higher the tier, the greater the sophistication of the design and operating requirements, leading to increased data center availability. Assessing the criticality of the data center to your organization will help identify the desired tier level of your data center. If you have a low level of criticality, does it make sense to invest in a Tier 3 or Tier 4 data center? Probably not. Identifying the optimal criticality for the organization identifies the required balance between a data center s cost of ownership and the cost of downtime for the organization. Table 3 on the next page provides the business characteristics that define criticality and the overall effect on system design. Whatever the reason for your data center project (new build, retrofit, or selection of a co-location data center), it s in your best interest to become familiar with the terminology used in the data center industry to understand any ambiguities that may come your way. Any project involving the data center carries risk and expense and therefore should not be taken lightly. Conclusion The intent of this article is to give you a brief overview of the TIA-942 data center standard. With this understanding, you will have a basis to conduct further research or to understand some of the claims made by data center vendors. So, where do you go from here? First, you need to perform a risk assessment to determine hourly cost of downtime, which would help you to identify the criticality of the data center for your business. Understand TIA-942 (requirement and process). Assess the tier level of your current system and sub-systems. Work with facilities to improve the overall health of the data center. Work with finance to justify upgrades. Alternatively, if it fits the business model, an outsourced data center should be considered. Affordable co-location or hosted data centers and high uptime ( percent) are not mutually exclusive. Navigating these requirements can be daunting. You may want to consider seeking assistance from an outside professional before you act. Judy Wright judy.wright@plantemoran.com Sri Chalasani sri.chalasani@plantemoran.com How can we help? Whether you need help optimizing an existing IT infrastructure, implementing a new data center, or assessing a co-location facility to meet demands, Plante Moran can help. Professionals in the IT Infrastructure group can assist you with: Documenting an existing environment. Conducting a risk assessment and/or gap analysis of a current data center. Providing data center design and capacity planning (infrastructure, electrical, HVAC, layout, etc.). Working with architects in new/retrofit data center builds to ensure requirements are addressed. Data center migration management. Vendor management. SSAE16 (SAS70) readiness preparation and audit management. 4

7 Criticality 1 (Lowest) Business characteristics Typically small business. A small percentage of business revenue depends upon availability of IT systems. IT is an enhancement to internal business processes. Business can function without IT system or there is low dependence upon IT. View system downtime as a tolerable inconvenience. Principal use of web presence is for passive marketing. There are no enforceable financial or non-financial penalties due to loss of systems. Recommended Data Center Tier TIER 1 - Basic Infrastructure Non-redundant capacity components and distribution paths. Numerous single points of failure in all aspects of design. Any capacity component or distribution path failure will impact the computer systems. Planned work will require most or all of the systems to be shutdown. Extremely vulnerable to inclement weather conditions. Generally unable to sustain more than a 10-minute power outage. 2 Typically small to medium-sized business, mostly limited to traditional 9-5 business hours. A small percentage of business revenue depends upon availability of IT systems. Business relies upon availability of IT systems; has multiple and often inter-related systems within IT. Some tolerance for downtime but extended downtime becomes a business deterrent. Business does not provide real-time delivery obligations or call centers with multiple sites. TIER 2 - Redundant Components Infrastructure Redundant capacity components, but single non-redundant distribution paths serving the site s computer equipment (i.e., a distribution path failure will cause the computer equipment to shut down). Some redundancy in power and cooling systems. Redundant UPS modules and engine generators. Ability to sustain a 24-hour power outage. Minimal thought in site selection. Formal data room separate from other areas. There are limited financial or non-financial penalties due to loss of systems. 3 Business serves both internal and external customers 24/7. Business spans multiple time zones and corresponding geographic diversity of employees and customers. TIER 3 - Concurrently Maintainable Infrastructure Redundant capacity components and multiple distribution paths serving the site s computer equipment. Generally, only one distribution path serves the computer equipment at any time. Each and every capacity component and element of the distribution paths can be removed from service on a planned basis without causing any of the computer equipment to be shut down. Ability to sustain a 72-hour power outage. Careful site selection planning process. Structure provides one-hour fire rating (how long it takes flames to penetrate the structure). Table 3 IT resources support automation of business processes. The customer impact due to short outages is manageable. Business provides real-time delivery obligations or call centers with multiple sites. Business has significant financial exposure due to customer quality-of-service issues. There are financial or non-financial penalties due to loss of systems. 4 (Highest) Business operates in international markets, with a 24 by forever services commitment. Business processes and systems operation are continuous. TIER 4 - Fault Tolerant Infrastructure Redundant capacity systems and multiple distribution paths simultaneously serving the site s computer equipment, including utility power paths. There is 2N redundancy in power and cooling systems. Site is not susceptible to disruption of service from a single unplanned worst-case event. Infrastructure maintenance may be performed by using redundant capacity components and distribution paths to safely work on the remaining equipment. Ability to sustain a 96-hour power outage. Stringent site selection criteria. Structure has a minimum two-hour fire rating. High level of physical security systems implemented. Availability of qualified staff to provide 24/7 onsite maintenance. Majority of revenue comes from electronic transactions. Business needs to react to market transactions, financial settlement, and e-commerce. Customer or employee access to applications/ IT systems provides a competitive advantage. Extremely high cost of downtime. 5

8 plantemoran.com

A Quick Primer on Data Center Tier Classifications

A Quick Primer on Data Center Tier Classifications A Quick Primer on Data Center Tier Classifications What You Should Know Before Starting a Data Center Project White Paper Abstract Data center facility projects are often driven by the Uptime Institute

More information

The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements

The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements The Data Center Tier Performance Standards and Their Importance to the Owner s Project Requirements Edward P Rafter, P.E. CxAP Tier IV Consulting Group Synopsis The data center industry has experienced

More information

Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group

Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group Presented by Edward P. Rafter, P.E., CxAP Tier IV Consulting Group The data center industry has experienced several evolutions over the past 20 years. One principal change has been the development of the

More information

Guidelines for Specifying Data Center Criticality / Tier Levels

Guidelines for Specifying Data Center Criticality / Tier Levels Guidelines for Specifying Data Center Criticality / Tier Levels By Victor Avelar White Paper #122 Executive Summary A framework for benchmarking a future data center s operational performance is essential

More information

How To Write A Data Center Specification

How To Write A Data Center Specification Guidelines for Specifying Data Center Criticality / Tier Levels White Paper 122 Revision 2 by Victor Avelar > Executive summary A framework for benchmarking a future data center s operational performance

More information

BICSI 002 / TIA 942 / Uptime

BICSI 002 / TIA 942 / Uptime BICSI 002 / TIA 942 / Uptime Which Data Center Standard Should I Follow Phil Isaak, PE, P.Eng., RCDD, DCDC President, Master Instructor Isaak Technologies Inc. Standards Who are these People Standards

More information

Building a Tier 4 Data Center on a Tier 1 Budget

Building a Tier 4 Data Center on a Tier 1 Budget Building a Tier 4 Data Center on a Tier 1 Budget A Walk Through of TIA-942 Peter P. Charland III, RCDD/NTS/WD, CET RTKL Associates Inc. March 27, 2008 BICSI South Central Region Meeting Denver, CO TIA-942

More information

TIA-942 Data Centre Standards Overview WHITE PAPER

TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview WHITE PAPER TIA-942 Data Centre Standards Overview For the past 20 years, cabling standards have been the cornerstone of ensuring proper design, installation, and

More information

Data Center Management. Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM

Data Center Management. Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM Data Center Management Didik Partono Rudiarto CDCP, ITIL-F, COBIT5, CITM A physical place that houses a computer network's most critical systems, including back-up power supplies, air conditioning, and

More information

Data center outages impact, causes, costs, and how to mitigate

Data center outages impact, causes, costs, and how to mitigate Data center outages impact, causes, costs, and how to mitigate Data centers sometimes fail. You can build in safeguards and fail safe mechanisms and redundancy through backup systems but like all engineered

More information

Which Data Center? Key factors in choosing who to trust with your IT Infrastructure

Which Data Center? Key factors in choosing who to trust with your IT Infrastructure Which Data Center? Key factors in choosing who to trust with your IT Infrastructure Tarif Abboushi Vice-President of Data Center Infrastructure NTT America May, 2009 Which Data Center? Key factors in choosing

More information

Data Center Site Infrastructure Tier Standard: Topology

Data Center Site Infrastructure Tier Standard: Topology U P T I M E I N S T I T U T E, L L C Data Center Site Infrastructure Tier Standard: Topology Prepared by Uptime Institute Professional Services, LLC Copyright 2010 by Uptime Institute, LLC 20 West 37th

More information

6Your Guide to a Superior

6Your Guide to a Superior Data Center Pillars 6Your Guide to a Superior Data Center Solution 6 Data Center Pillars I. Classification Level: Tier III Compliance Assures Performance II. Backed by SAP: SSAE 16 Type II Certification

More information

Jan Kremer s Data Center Design Consultancy

Jan Kremer s Data Center Design Consultancy Jan Kremer s Data Center Design Consultancy Datacenter Design Jan Kremer has designed a Tier Level 3 Datacenter for one of the main banks in Saudi Arabia This included Floor Plans, Power Requirements,

More information

Data Center Site Infrastructure Tier Standard: Topology

Data Center Site Infrastructure Tier Standard: Topology U P T I M E I N S T I T U T E, L L C Data Center Site Infrastructure Tier Standard: Topology Prepared by Uptime Institute Professional Services, LLC Copyright 2009-2012 by Uptime Institute, LLC 20 West

More information

Data Center Commissioning: What you need to know

Data Center Commissioning: What you need to know Data Center Commissioning: What you need to know Course # CXENERGY1511 AIA Provider # 50111116 AABC Commissioning Group CxEnergy Conference Henderson, NV April 30, 2015 Presented by: Judson H. Adams, P.E.,

More information

DATA CENTER COLOCATION

DATA CENTER COLOCATION DATA CENTER COLOCATION An easy decision, a difficult choice Differentiating one colocation provider from another can be a challenge. They all promise much the same service and it is tempting to select

More information

Sovereign. The made to measure data centre

Sovereign. The made to measure data centre Sovereign D ATA C O N N E C T The made to measure data centre Prime Location Within touching distance of everything that s important. 2 Your Customer-Centric Data Centre For the vast majority of organisations

More information

7QUESTIONSYOUNEEDTOASKBEFORE CHOOSINGACOLOCATIONFACILITY FORYOURBUSINESS

7QUESTIONSYOUNEEDTOASKBEFORE CHOOSINGACOLOCATIONFACILITY FORYOURBUSINESS 7QUESTIONSYOUNEEDTOASKBEFORE CHOOSINGACOLOCATIONFACILITY FORYOURBUSINESS ExecutiveBrief P a g e 1 Executive Brief 7 Questions You Need to Ask Before Choosing a Colocation Facility for Your Business Choosing

More information

Managing business risk

Managing business risk Managing business risk What senior managers need to know about business continuity bell.ca/businesscontinuity Information and Communications Technology (ICT) has become more vital than ever to the success

More information

The Difference Between Disaster Recovery and Business Continuance

The Difference Between Disaster Recovery and Business Continuance The Difference Between Disaster Recovery and Business Continuance In high school geometry we learned that a square is a rectangle, but a rectangle is not a square. The same analogy applies to business

More information

Uptime Institute Tier Classification System & Operational Sustainability

Uptime Institute Tier Classification System & Operational Sustainability Uptime Institute Tier Classification System & Operational Sustainability April 17, 2012 Dana L. Smith data center management and engineering consultants http://uptimeinstitute.com/professional-services

More information

NIGERIA S PREMIUM DATA CENTRE

NIGERIA S PREMIUM DATA CENTRE NIGERIA S PREMIUM DATA CENTRE TIER III DESIGN CERTIFIED SECURE RELIABLE SCALABLE 1 WHY WOULD YOU WANT TO BUILD A DATA CENTRE? IT TAKES MILLIONS OF US DOLLARS TO BUILD AN EFFICIENT DATA CENTRE. A KEY ASSET,

More information

Finding Your Cloud: A down-to-earth guide to planning your cloud investment. Getting the full benefit of a key strategic technology investment

Finding Your Cloud: A down-to-earth guide to planning your cloud investment. Getting the full benefit of a key strategic technology investment Finding Your Cloud: A down-to-earth guide to planning your cloud investment Getting the full benefit of a key strategic technology investment Finding Your Cloud: A down-to-earth guide to planning your

More information

Tier Standards. Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI. Consultant EMEA

Tier Standards. Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI. Consultant EMEA Tier Standards Eric Maddison CEng. CEnv. MBA MSc. MCIBSE MEI Consultant EMEA Uptime Institute Unbiased and vendor neutral Global thought leadership for the data center industry Founded 1993 Standards and

More information

TIA-942: Data Center Standards

TIA-942: Data Center Standards plantemoran.com TIA-942: Data Center Standards Sri Chalasani Merit 2010 Conference May 25, 2010 Objectives What are concerns in the data center? Data center standards & best Practices Data Center Definition

More information

Colocation Buyer s Guide. Learn the benefits of colocation and decide if a third party data center makes sense for your business.

Colocation Buyer s Guide. Learn the benefits of colocation and decide if a third party data center makes sense for your business. Colocation Buyer s Guide Learn the benefits of colocation and decide if a third party data center makes sense for your business. Size does matter. Where do you fit? Colocation is not total outsourcing.

More information

Overcoming the Causes of Data Center Outages

Overcoming the Causes of Data Center Outages Overcoming the Causes of Data Center Outages Executive Summary A data center s main function should be to provide constant uptime for the mission-critical applications it houses. However, unplanned outages

More information

Hosting Infrastructure. Overview and Benefits of Hosting Infrastructure

Hosting Infrastructure. Overview and Benefits of Hosting Infrastructure Hosting Infrastructure Overview and Benefits of Hosting Infrastructure Data Centre definition In it's simplest form, a data centre is a facility that houses IT equipment Servers, and networking kit. The

More information

THE DATA CENTER COMPLIANCE ACRONYMS YOU NEED TO KNOW

THE DATA CENTER COMPLIANCE ACRONYMS YOU NEED TO KNOW THE 22 DATA CENTER COMPLIANCE ACRONYMS YOU NEED TO KNOW In today s world, data center compliance is no joke, and firewalls aren t enough to keep your data safe. Whether you re outsourcing or housing your

More information

CHOOSING A RACKSPACE HOSTING PLATFORM

CHOOSING A RACKSPACE HOSTING PLATFORM CHOOSING A RACKSPACE HOSTING PLATFORM Rackspace has years of experience in hosting and has learnt that the unique needs of our customers businesses often determines the level of accountability and project

More information

Tier Classifications Define Site Infrastructure Performance

Tier Classifications Define Site Infrastructure Performance W h i t e P a p e r Tier Classifications Define Site Infrastructure Performance By W. Pitt Turner IV, PE, John H. Seader, PE, Vince Renaud, PE, and Kenneth G. Brill Table of Contents Executive Summary...

More information

ACI ON DEMAND DELIVERS PEACE OF MIND

ACI ON DEMAND DELIVERS PEACE OF MIND DELIVERS PEACE OF MIND SERVICE LINE FLYER ACI ON DEMAND ACCESS TO THE LATEST RELEASES OF FEATURE-RICH SOFTWARE AND SYSTEMS, INCLUDING INTEGRATION WITH VALUE- ADDED THIRD PARTIES IMPLEMENTATION CONFIGURED

More information

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD

Dat Da a t Cen t Cen er t St andar St d andar s d R o R undup o BICSI, TIA, CENELEC CENELE, ISO Steve Kepekci, RCDD Data Center Standards Roundup BICSI, TIA, CENELEC, ISO Steve Kepekci, RCDD Introduction Regardless of business activity or size, all information technology (IT) groups have similar needs Provide secure,

More information

All Clouds Are Not Created Equal THE NEED FOR HIGH AVAILABILITY AND UPTIME

All Clouds Are Not Created Equal THE NEED FOR HIGH AVAILABILITY AND UPTIME THE NEED FOR HIGH AVAILABILITY AND UPTIME 1 THE NEED FOR HIGH AVAILABILITY AND UPTIME All Clouds Are Not Created Equal INTRODUCTION Companies increasingly are looking to the cloud to help deliver IT services.

More information

Redundancy and Reliability for an HPC Data Centre

Redundancy and Reliability for an HPC Data Centre Available online at www.prace-ri.eu Partnership for Advanced Computing in Europe Redundancy and Reliability for an HPC Data Centre Erhan Yılmaz* 1 Ladina Gilly** 2 * National High Performance Computing

More information

Data Center Infrastructure & Managed Services Outline

Data Center Infrastructure & Managed Services Outline Data Center Infrastructure & Managed Services Outline The 360 Technology Center Solutions Data Center is located in Lombard, IL, USA. We are 20 minutes outside of downtown Chicago. The 360TCS staff consists

More information

i. Maintenance of the operating system, applications, content on the server, or fault tolerant network connections

i. Maintenance of the operating system, applications, content on the server, or fault tolerant network connections Physical Co-location Service Level Agreement 1. Agreement This agreement is to define Physical Server Co-location services provided to a Customer. Typically, service definitions include hours, availability,

More information

Building a data center. C R Srinivasan Tata Communications

Building a data center. C R Srinivasan Tata Communications Building a data center C R Srinivasan Tata Communications Introduction Data Center as defined by TIA 942 A building or a portion of a building whose primary function is to house a computer room and its

More information

Data Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s"

Data Centre Issues supported in TIA-942 : Telecommunications Infrastructure for Data Centre s Data Centre Issues supported in TIA-942 : "Telecommunications Infrastructure for Data Centre s" Data centre Standard EN50173-5 : "Telecommunications Infrastructure for Data Centre s Due, 2006 Gary Highton,

More information

ASSET Connect. The next level in Critical Environment Operational Efficiency

ASSET Connect. The next level in Critical Environment Operational Efficiency Connect The next level in Critical Environment Operational Efficiency 10-30% is the potential efficiency gain from optimized Data Centers and Critical Environments Operational Efficiency of Your Critical

More information

White Paper. Co-location. Co-location. Co-location. Considerations That Impact Your Business

White Paper. Co-location. Co-location. Co-location. Considerations That Impact Your Business White Paper Co-location. Co-location. Co-location. Considerations That Impact Your Business Your Business is Dynamic - Is your IT Infrastructure Keeping Pace? Whether you operate a small or medium-sized

More information

Business resilience: The best defense is a good offense

Business resilience: The best defense is a good offense IBM Business Continuity and Resiliency Services January 2009 Business resilience: The best defense is a good offense Develop a best practices strategy using a tiered approach Page 2 Contents 2 Introduction

More information

DISASTER RECOVERY PLANNING GUIDE

DISASTER RECOVERY PLANNING GUIDE DISASTER RECOVERY PLANNING GUIDE AN INTRODUCTION TO BUSINESS CONTINUITY PLANNING FOR JD EDWARDS SOFTWARE CUSTOMERS www.wts.com WTS Disaster Recovery Planning Guide Page 1 Introduction This guide will provide

More information

DISASTER RECOVERY ebook FACING DISASTERS HEAD ON

DISASTER RECOVERY ebook FACING DISASTERS HEAD ON DISASTER RECOVERY ebook FACING DISASTERS HEAD ON CHAPTER 1: Facing Reality CHAPTER 2: Disaster Recovery Considerations CHAPTER 3: Making the Best Choices CHAPTER 4: A Single, Unified Solution CHAPTER 5:

More information

Tier Classifications Define Site Infrastructure Performance

Tier Classifications Define Site Infrastructure Performance By W. Pitt Turner IV, P.E., John H. Seader, P.E., and Kenneth G. Brill Widely accepted within the uninterruptible industry, The Uptime Institute s Tier Performance Standards are an objective basis for

More information

So you want to build a data centre? Look what s coming from BICSI! Matt Flowerday Capitoline FZC mflowerday@capitoline.org

So you want to build a data centre? Look what s coming from BICSI! Matt Flowerday Capitoline FZC mflowerday@capitoline.org So you want to build a data centre? Look what s coming from BICSI! Matt Flowerday Capitoline FZC mflowerday@capitoline.org So you want to build a data centre? Who do you contact? How do you work out what

More information

Data Center Colocation Build vs. Buy

Data Center Colocation Build vs. Buy Data Center Colocation Build vs. Buy Comparing the total cost of ownership of building your own data center vs. buying third-party colocation services Executive Summary As businesses grow, the need for

More information

A Vendor s Journey to SaaS & the Cloud

A Vendor s Journey to SaaS & the Cloud A Vendor s Journey to SaaS & the Cloud Mark Sherry Partner Marval North America ITIL Expert ISO 20000 Consultant MBA, MA, BComm 25+ ITIL implementations Trained Service Managers Globally 10 Years in Industry

More information

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria

Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Tier 3+ 1 Title: Design of a Shared Tier III+ Data Center: A Case Study with Design Alternatives and Selection Criteria Abstract: Schoolcraft College is constructing a High Availability (HA) Data Center

More information

COMMODITIZING THE DATACENTER. Exploring the Impacts of the Shift to Virtualization and Cloud Computing

COMMODITIZING THE DATACENTER. Exploring the Impacts of the Shift to Virtualization and Cloud Computing COMMODITIZING THE DATACENTER Exploring the Impacts of the Shift to Virtualization and Cloud Computing 3/5/2015 AGENDA Changing Environments What Is The Datacenter Why Do We Use Them Adapting To A Changing

More information

About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services

About Injazat. Enterprise Cloud Services. Premier Data Center. IT Outsourcing. Learning and Development Services. Enterprise Application Services About Injazat Injazat Data Systems is an industry-recognized market leader in the region for Information Technology Outsourcing, Cloud and Data Center Managed Services delivered from the region s 1st Tier

More information

Top 10 Disaster Recovery Pitfalls

Top 10 Disaster Recovery Pitfalls Top 10 Disaster Recovery Pitfalls The key to successful disaster recovery is good planning. But with so much at stake for your business, how do you plan with confidence and ensure all stakeholders know

More information

Colocation, Hot Seat Services, Disaster Recovery Services, Secure and Controlled Environment

Colocation, Hot Seat Services, Disaster Recovery Services, Secure and Controlled Environment Colocation, Hot Seat Services, Disaster Recovery Services, Secure and Controlled Environment 3 Company Overview Confisio DataCenter was formed to help organisations tackle the ever increasing challenges

More information

A Framework for Developing and Evaluating Data Center Maintenance Programs

A Framework for Developing and Evaluating Data Center Maintenance Programs A Framework for Developing and Evaluating Data Center Maintenance Programs White Paper 178 Revision 0 by Bob Woolley > Executive summary Inadequate maintenance and risk mitigation processes can quickly

More information

Specialty Environment Design Mission Critical Facilities

Specialty Environment Design Mission Critical Facilities Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,

More information

Introduction to Datacenters & the Cloud

Introduction to Datacenters & the Cloud Introduction to Datacenters & the Cloud Datacenter Design Alex M. Hurd Clarkson Open Source Institute March 24, 2015 Alex M. Hurd (COSI) Introduction to Datacenters & the Cloud March 24, 2015 1 / 14 Overview

More information

Modern Data Centers: Creating a New Value Proposition

Modern Data Centers: Creating a New Value Proposition Modern Data Centers: Creating a New Value Proposition América Latina 2008 Inter-secretarial Commission for the Development of Electronic Government Mexico City 24 May 2013 Data Center Consolidation Consolidating

More information

The Production Cloud

The Production Cloud The Production Cloud The cloud is not just for backup storage, development projects and other low-risk applications. In this document, we look at the characteristics of a public cloud environment that

More information

Security Solutions to Meet NERC-CIP Requirements. Kevin Staggs, Honeywell Process Solutions

Security Solutions to Meet NERC-CIP Requirements. Kevin Staggs, Honeywell Process Solutions Kevin Staggs, Honeywell Process Solutions Table of Contents Introduction...3 Nerc Standards and Implications...3 How to Meet the New Requirements...4 Protecting Your System...4 Cyber Security...5 A Sample

More information

PROTECTING YOUR VOICE SYSTEM IN THE CLOUD

PROTECTING YOUR VOICE SYSTEM IN THE CLOUD PROTECTING YOUR VOICE SYSTEM IN THE CLOUD Every enterprise deserves to know what its vendors are doing to protect the data and systems entrusted to them. Leading IVR vendors in the cloud, like Angel, consider

More information

Brivo OnAir TOTAL COST OF OWNERSHIP (TCO) How Software-as-a-Service (SaaS) lowers the Total Cost of Ownership (TCO) for physical security systems.

Brivo OnAir TOTAL COST OF OWNERSHIP (TCO) How Software-as-a-Service (SaaS) lowers the Total Cost of Ownership (TCO) for physical security systems. Brivo OnAir TOTAL COST OF OWNERSHIP (TCO) How Software-as-a-Service (SaaS) lowers the Total Cost of Ownership (TCO) for physical security systems. WHITE PAPER Page 2 Table of Contents Executive summary...

More information

Consulting Engineering Outsourcing

Consulting Engineering Outsourcing Consulting Engineering Outsourcing Opportunities, challenges and strategies 5.º Fórum Lusófono das Comunicações Maputo, 24 de Abril de 2014 Maksen 2014 Consulting Engineering Outsourcing AGENDA 01. Data

More information

COLOCATION A BUYERS GUIDE

COLOCATION A BUYERS GUIDE COLOCATION A BUYERS GUIDE INTRODUCTION Colocation in a data centre offers organisations a place to securely house their IT equipment, as opposed to storing and running it on-site, which can be both expensive

More information

Evaluating Datacenter Colocation

Evaluating Datacenter Colocation 1/14 Evaluating Datacenter Colocation Flexibility and Security for Business Growth 2/14 The Advantages of Colocation Colocation is a service that allows customers to install and operate computer server

More information

penelope athena software SOFTWARE AS A SERVICE INFORMATION PACKAGE case management software

penelope athena software SOFTWARE AS A SERVICE INFORMATION PACKAGE case management software penelope case management software SOFTWARE AS A SERVICE INFORMATION PACKAGE athena software "I've worked with major corporations and universities and I am really impressed with Athena's hosted server and

More information

Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011

Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011 Automating Infrastructure A connectivity perspective for BICSI SEA meeting, November 2011 Opportunities in Automating Infrastructure Why Automation in Data Center? Tiers, compartments and complexity Work

More information

Transition From Virginia Interactive

Transition From Virginia Interactive Transition From Virginia Interactive Transition Webinar October 2012 1 1 Authors VITA SiteVision CyberData BroadPoint AIS Hosting O & M Hosting topics include: Network Server performance Backups Patches

More information

Tier Classifications Define Site Infrastructure Performance

Tier Classifications Define Site Infrastructure Performance By W. Pitt Turner IV, P.E., John H. Seader, P.E., and Kenneth G. Brill Widely accepted within the uninterruptible industry, The Uptime Institute s Tier Performance Standards are an objective basis for

More information

HOW TO SELECT A COLOCATION PROVIDER

HOW TO SELECT A COLOCATION PROVIDER HOW TO SELECT A COLOCATION PROVIDER THE TOP 10 CRITERIA TO DISCUSS WHEN TOURING A DATA CENTER Choosing a data center or colocation provider to house your company s critical IT infrastructure is a huge

More information

Executive s Guide to Selecting a Mainframe Disaster Recovery Provider

Executive s Guide to Selecting a Mainframe Disaster Recovery Provider Executive s Guide to Selecting a Mainframe Disaster Recovery Provider What to Look for in a Disaster Recovery Services Provider Accelerate Outsourcing, Inc. www.accelout.com 1 Improve the Chance of a Successful

More information

Level I - Public. Technical Portfolio. Revised: July 2015

Level I - Public. Technical Portfolio. Revised: July 2015 Level I - Public Technical Portfolio Revised: July 2015 Table of Contents 1. INTRODUCTION 3 1.1 About Imaginatik 3 1.2 Taking Information Security Seriously 3 2. DATA CENTER SECURITY 3 2.1 Data Center

More information

Data Center Checklist

Data Center Checklist Data Center Checklist The use of colocation and services has continued to increase, rapidly becoming the solution of choice for organizations requiring an efficient, secure, cost-effective way to manage

More information

Data Center Knowledge, Vision Control

Data Center Knowledge, Vision Control Data Center Knowledge, Vision Control Objective Overview of the progressive trends in Data Centers, driven by Intelligent Infrastructure Solutions Data Center Layout Secured Storage Back up Core Backbone

More information

Colocation. Scalable Solutions for a Shared IT Infrastructure. Enterprise. Colocation

Colocation. Scalable Solutions for a Shared IT Infrastructure. Enterprise. Colocation Scalable Solutions for a Shared IT Infrastructure Global and domestic competition, rising real estate and power costs, and shrinking IT budgets are causing today s businesses to seek alternatives to building

More information

Designing Fault-Tolerant Power Infrastructure

Designing Fault-Tolerant Power Infrastructure Designing Fault-Tolerant Power Infrastructure System Analysis and New Standards Enable Maximization of Operating Dependability for Data Centers & Other Mission Critical Facilities J.F. Christin (Author)

More information

C24 - Inside the Data Center Andrew J. Luca

C24 - Inside the Data Center Andrew J. Luca C24 - Inside the Data Center Andrew J. Luca Inside the Data Center What an auditor needs to know Course Objectives Understand the looks and feel of a data center Know what to look for and what questions

More information

7 key considerations in selecting a colocation provider

7 key considerations in selecting a colocation provider 1 / 9 7 key considerations in selecting a colocation provider CONSIDERATIONS CHECKLIST 2 / 9 Executive Summary Faced with the need to optimize, every aspect of their department, IT organizations are recognizing

More information

Colocation. Scalable Solutions for Shared IT Infrastructure. Enterprise. Colocation

Colocation. Scalable Solutions for Shared IT Infrastructure. Enterprise. Colocation Scalable Solutions for Shared IT Infrastructure Global competition, rising real estate and power costs, and shrinking IT budgets are causing today s businesses to seek alternatives to building their own

More information

How To Determine Data Center Reliability

How To Determine Data Center Reliability DATA CENTER INDUSTRY WHITE PAPER Data Center Services End-To-End Reliability Published by: Isaak Technologies, Inc. TABLE OF CONTENTS 1. Overview... 1 2. Reliability Classifications... 2 Reliability Class-0...

More information

CA Cloud Overview Benefits of the Hyper-V Cloud

CA Cloud Overview Benefits of the Hyper-V Cloud Benefits of the Hyper-V Cloud For more information, please contact: Email: sales@canadianwebhosting.com Ph: 888-821-7888 Canadian Web Hosting (www.canadianwebhosting.com) is an independent company, hereinafter

More information

Matthias Machowinski, Directing Analyst for Enterprise Networks and Video, Infonetics Research, 20152

Matthias Machowinski, Directing Analyst for Enterprise Networks and Video, Infonetics Research, 20152 The Cold, Hard Facts About Uptime Executive Summary By the year 2020, when the Internet of Things is in full swing and Internet-connected devices and data are as important as electricity, data center uptime

More information

The Importance of Software License Server Monitoring White Paper

The Importance of Software License Server Monitoring White Paper LicenseMonitor The Importance of Software License Server Monitoring The Importance of Software License Server Monitoring White Paper Introduction In the electronic design automation (EDA) and other CAD

More information

Elliptical Mobile Solutions Data Center Solutions

Elliptical Mobile Solutions Data Center Solutions Elliptical Mobile Solutions Data Center Solutions The Next Genera-on of Modular Data Centers Copyright Ellip.cal Mobile Solu.ons 2010 www.ellip.calmobilesolu.ons.com 1 EMS CURRENT PRODUCTS BENEFITS We

More information

Hosting Options. White paper last updated January 2013 For more information: www.scalefactory.com Or get in touch: info@scalefactory.

Hosting Options. White paper last updated January 2013 For more information: www.scalefactory.com Or get in touch: info@scalefactory. Hosting Options Or get in touch: info@scalefactory.com 1 Introduction When building an infrastructure for your web application, choosing a hosting provider is an important part of the process. This decision

More information

High-performance. High-density. Highly committed. Built for tomorrow. Ready today.

High-performance. High-density. Highly committed. Built for tomorrow. Ready today. High-performance. High-density. Highly committed. Built for tomorrow. Ready today. Built for tomorrow. Ready today. In today s environment, the focus should be on investing time in your company and not

More information

Intensive Hosting. Intensive Hosting Overview. Why Intensive Hosting?

Intensive Hosting. Intensive Hosting Overview. Why Intensive Hosting? Rackspace is the world s leader in hosting. We deliver websites, web-based IT systems, and computing as a service. Our rapid growth is the result of our commitment to serving our customers, known as Fanatical

More information

How To Get The Best Out Of Your It Investments On Mtn.Com

How To Get The Best Out Of Your It Investments On Mtn.Com MTN Data Centre services. MTN Business Data Centre Services. Getting the best out of your IT investments For forward looking 21st century organisations, outsourcing IT infrastructure and services has become

More information

Security+ Guide to Network Security Fundamentals, Fourth Edition. Chapter 13 Business Continuity

Security+ Guide to Network Security Fundamentals, Fourth Edition. Chapter 13 Business Continuity Security+ Guide to Network Security Fundamentals, Fourth Edition Chapter 13 Business Continuity Objectives Define environmental controls Describe the components of redundancy planning List disaster recovery

More information

ABOUT ANIXTER UNIVERSITY

ABOUT ANIXTER UNIVERSITY Q3 2015 ABOUT ANIXTER UNIVERSITY Anixter University TM is the educational initiative of Anixter, a leading global supplier of communications and security products, electrical and electronic wire and cable,

More information

How To Choose Data Center Colocation Over Cloud Computing

How To Choose Data Center Colocation Over Cloud Computing White Paper Cloud vs. Colo: Colo Wins on 4 out of 5 Key Criteria of new security threats, hacking attacks and data breaches every week. Couple that with major service interruptions and outages experienced

More information

BICSI Data Center Standard. Presented by: Stephen Banks, RCDD CDCDP

BICSI Data Center Standard. Presented by: Stephen Banks, RCDD CDCDP BICSI Data Center Standard Presented by: Stephen Banks, RCDD CDCDP BICSI Data Center Standard BICSI 002, Data Center Design and Implementation Best Practices Used in conjunction with other standards ANSI/TIA-942

More information

How to Obtain the Uptime, Security and Robust Connectivity Financial Services Firms

How to Obtain the Uptime, Security and Robust Connectivity Financial Services Firms EXECUTIVE REPORT How to Obtain the Uptime, Security and Robust Connectivity Financial Services IT Service Management Framework & Interconnection for Financial Services The many different entities that

More information

Data Center Overview Document

Data Center Overview Document Overview NetSource is a Chicago area (Naperville) hosting company that owns and operates its own world class datacenter. The initial datacenter buildout was put into operation in 2007 and expanded in 2013.

More information

How Proactive Business Continuity Can Protect and Grow Your Business. A CenturyLink White Paper

How Proactive Business Continuity Can Protect and Grow Your Business. A CenturyLink White Paper How Proactive Business Continuity Can Protect and Grow Your Business For most companies, business continuity planning is instantly equated with disaster recovery the reactive ability of a business to continue

More information

Server Consolidation. Report to the Joint Legislative Oversight Committee on Information Technology

Server Consolidation. Report to the Joint Legislative Oversight Committee on Information Technology Server Consolidation Report to the Joint Legislative Oversight Committee on Information Technology Chris Estes State Chief Information Officer December 2013 This page left blank intentionally Contents

More information

Organizations remain under intense pressure to reduce costs To reduce costs we must increase efficiency in resource allocation

Organizations remain under intense pressure to reduce costs To reduce costs we must increase efficiency in resource allocation Total Cost of Ownership: What is it Really? August 11, 2003 The Challenge How do I optimize my IT investments? Organizations remain under intense pressure to reduce costs To reduce costs we must increase

More information

Datacenter Assessment

Datacenter Assessment The Netmagic team has compiled this Checklist to help you evaluate, compare and select datacenter facilities to meet your hosting, business continuity and disaster recovery needs. Based on industry best

More information

Exhibit to Data Center Services Service Component Provider Master Services Agreement

Exhibit to Data Center Services Service Component Provider Master Services Agreement Exhibit to Data Center Services Service Component Provider Master Services Agreement DIR Contract No. DIR-DCS-SCP-MSA-002 Between The State of Texas, acting by and through the Texas Department of Information

More information

Preparing for the Worst: Disaster Recovery and Business Continuity Planning for Investment Firms An Eze Castle Integration ebook

Preparing for the Worst: Disaster Recovery and Business Continuity Planning for Investment Firms An Eze Castle Integration ebook Preparing for the Worst: Disaster Recovery and Business Continuity Planning for Investment Firms An Eze Castle Integration ebook Table of Contents 1. Introduction to Business Continuity Planning and Disaster

More information