Power Usage Effectiveness (PUE) & Data Center Infrastructure Efficiency (DCiE) Progress

Size: px
Start display at page:

Download "Power Usage Effectiveness (PUE) & Data Center Infrastructure Efficiency (DCiE) Progress"

Transcription

1 Power Usage Effectiveness (PUE) & Data Center Infrastructure Efficiency (DCiE) Progress Dan Azevedo, Symantec Jon Haas, Intel Jud Cooley, Sun Microsystems, Inc. Mark Monroe, Sun Microsystems, Inc. Pam Lembke, IBM

2 Agenda PUE / DCiE Background & Next Steps DCiE Detailed Analysis PUE / DCiE Usage & Public Reporting Guidelines PUE / DCiE Calculation Tool Free Cooling Map Power Configuration Calculator 2

3 PUE / DCiE Background & Next Steps 3

4 DCiE Detailed Analysis Dan Azevedo, Symantec 4

5 Executive Summary The DCiE Detailed Analysis is to support and strengthen the Data Center infrastructure Efficiency (DCiE) metric. The intent is to enable data center managers collectively to derive and use DCiE as a global standard metric. 5

6 DCiE Detailed Analysis This White Paper represents the first in a series that will provide a more detailed analysis of the PUE / DCiE Metric and represents the Basic level in the below table with the assumption of a dedicated data center facility: IT Equipment Power Measurement From Total Facility Power Measurement From Minimum Measurement Interval Level 1 (Basic) Level 2 (Intermediate) Level 3 (Advanced) UPS PDU Server,. Data Center input power Data Center input less shared HVAC Data Center input less shared HVAC plus building lighting, security Monthly/Weekly Daily Continuous (xx min) 6

7 DCiE Detailed Analysis 7

8 DCiE Detailed Analysis 8

9 DCiE Detailed Analysis Table of Contents Introduction Background and Assumptions DCiE Overview DCiE Subcomponents Obtaining Required Data Estimating Power Consumption Measuring Power Consumption Power Metering Requirements Factors Affecting DCiE Dynamic Data Center Type of Data Center Climate and Location Data Center Design and Operation Measurement Period Sometimes DCiE Seems To Go The Wrong Way Driving DCiE Efficiency DCiE and Future Technology Advancements Multiuse Facilities Summary Conclusion 9

10 Summary This paper provides: Prescriptive information on how to calculate the efficiency metrics Multiple levels of implementation which enables a very simple basic approach to as much depth and complexity as desire Equipment categorization: infrastructure vs. IT equipment Power metering requirements Guidance on interpreting the metrics High-level guidance on multi-use facilities 10

11 Usage And Public Reporting Guidelines for The Green Grid s Infrastructure Metrics Jon Haas, Intel 11

12 Reasons for Guidelines PUE/DCiE have become commonly used metrics for data center efficiency Factors such as environmental conditions, a data center s physical characteristics, and timing and frequency of measurements can play a significant role in final results In addition, some individuals and organizations have used these metrics to promote design ideas that, while valuable, can provide misleading results Standard guidelines for the use and reporting of these metrics will: Enable a common language and nomenclature to compare results provide a process to support accurate, consistent results Provide additional transparency and accountabilitly in the process of measurement for public claims In addition, these guidelines will support The Green Grid in: develop an auditing/certification process for the industry around these metrics develop a recognition program for those organizations showing strong results and/or improvements in data center energy efficiency 12

13 Publicly reporting your Data The Green Grid will provide a means for organizations to publicly report their measurements record their PUE/DCiE measurement data to The Green Grid provide background information about the data center, reporting the results and the manner in which, and conditions under which, that data was collected provide a means to report any issues or difficulties in following TGG s proscribe processes and guidelines The Green Grid will also provide a portal through which organizations can view summary details on publicly reported PUE and DCiE results This portal will provide summary data on all registered reported results All reported results meeting TGG guidelines will be given a registration number that can be referenced A subset of provided data will be publicly visible (see appendix 2 of WP or consent form) TGG will offer members the opportunity to provide a link to additional information about their result or data center via additional optional reporting Organizations reporting results have the option to participate in TGG awards or recognition programs by complying with additional requirements 13

14 Classes of Measurement Results Class Description Benefit to Reporting Organization Unrecognized Reported Registered Certified 14 A publicly reported result with no claims of following TGG s guidelines. TGG will not comment on unrecognized results. A publicly reported result by the reporting organization claiming they followed TGG s measurement recommendations and nomenclature guidelines. TGG will not comment on Reported results. A publicly reported result, with key report contextual data provided to TGG by the reporting organization to TGG s data center performance database. A publicly reported result, with key additional data required for third-party validation or certification of results, provided to TGG by the reporting organization. Reporting organization can use standard materials from The Green Grid to explain process and results to audience. Official registration of reported result. Receipt of a registration number from TGG. Link to public report data from TGG s website. All benefits applicable to registered results, plus, consideration of reported results in future TGG award or recognition programs.

15 Usage and Reporting Guidelines To receive a PUE or DCiE registration number from The Green Grid: Follow The Green Grid s measurement guidelines in the most recent revision of DCiE Detailed Analysis Report the process through which the data was collected (L1, L2, L3) using the nomenclature in the most recent revision of Usage and Public Reporting Guidelines for The Green Grid s Infrastructure Metrics Report your measurement data and input the required information into the Green Grid s Metrics Data Collection Database ( Agree to The Green Grid s metrics public reporting consent form If requesting to be considered for a TGG award, provide the extended data set information into the Green Grid s Data Collection Database for certified measurements Additionally Report to The Green Grid any issues or difficulties in following TGG s proscribed processes and guidelines (optional, co-promotion ) send the PUE or DCiE registration number, along with a link to any original source material or publication, to TGG at admin@thegreengrid.org 15

16 PUE/DCiE Nomenclature Structure All PUE and DCiE measurements should be reported with subscripts that identify: The accuracy level of the measurement See The Green Grid s Metrics: Data Center Infrastructure Efficiency Detailed Analysis The timeframe of the measurement E.g. yearly, monthly, weekly, daily The granularity of the measurement Frequency with which the data was collected E.g., monthly, weekly, daily, continuous Official PUE/DCiE reports will provide these information with subscripts appended to the Metric i.e. PUE x,y or DCiE x,y, where x describes the Level of the measurement (L1, L2, L3) L1, L2, and L3 are defined in the TGG White Paper: The Green Grid Metrics: Data Center Infrastructure Efficiency (DCiE) Detailed Analysis y describes the Timeframe and Granularity of the measurement y = timeframe identifier + frequency identifier 16

17 Measurement Accuracy Reporting (from DCiE Detailed Analysis WP) IT Equipment Power Measurement From Total Facility Power Measurement From Minimum Measurement Interval Level 1 (Basic) Level 2 (Intermediate) Level 3 (Advanced) UPS PDU Server,. Data Center input power Data Center input less shared HVAC Data Center input less shared HVAC plus building lighting, security Monthly/Weekly Daily Continuous (xx min) 17

18 Measurement Timescale and Granularity Reporting The y subscript on PUE or DCiE denotes the Timeframe and Granularity of the measurement y = timeframe identifier + frequency identifier [ M, W, D, C ] Frequency identifier: M for measurements taken monthly W for measurements taken weekly D for measurements taken daily C for measurements taken continuously (with frequency one hour or less) Except for those measurements collected with continuous data, all data points that are averaged in the final measurement must be taken at the same time of day Single measurements are reported with no frequency identifier 18

19 Example Reported Results 0.45 DCiE L1,-- Single DCiE measurement (0.45) taken using a Level 1 meter placement 0.51 DCiE L1,YM Yearly average DCiE (0.51), using data points gathered monthly with a Level 1 meter placement 1.6 PUE L1,MW Monthly average PUE (1.6) using data points gathered weekly with a Level 1 meter placement 0.43DCiE L1,WD Weekly average DCiE (0.43), using data points gathered daily with a Level 1 meter placement 1.8 PUE L2,WC Weekly average PUE using data points gathered continuously with a Level 2 meter placement. 2.1 PUE L3,YC Yearly average PUE (2.1) using continuous measurements with a Level 3 meter placement. 19

20 Specific Reporting Issues PUEs of < 1.0 and DCiEs of > 1.0 are *not* allowed Elements that go into the calculation Power consumed by IT equipment Power lost in distribution Power consumed by cooling equipment These elements are always 0 Accounting for re-use of waste heat Waste heat re-use *does not* get included in either PUE or DCiE TGG will look into creating an additional metric to cover this 20 Accounting for power generated on site PUE / DCiE is meant to cover areas of energy use in the data center Generation of power on-site is not incorporated into either the power distribution losses or cooling equipment requirements As such, it should not be considered in the PUE/DCiE calculation

21 Conclusion We are driving the right behaviour! The Green Grid Metrics for data center efficiency are gaining widespread adoption, use and visibility Organizations are publicly reporting their measurements and claiming highly efficient operations The Green Grid is implementing public reporting guidelines that includes standard processes and nomenclature to make the measured results more transparent and consistent Stay away from PUEs of < 1.0 and DCiEs of > 1.0, they are not viable 21

22 PUE Calculation Tool Jud Cooley, Sun Microsystems, Inc. 22

23 Rationale and Objectives Sponsor: Container Assessment Task Force to allow case study comparisons Easily and accurately compute PUE In a consistent manner Allowing for apples-apples comparisons Container boundaries Building or room boundaries Web based One sheet printed report Data archival/retrieval 23

24 PUE with Physical boundaries Management reporting to visualize overhead Power: Transfer Switch, UPS, Transformer, Generator, Lighting, etc. Cooling: Tower, Condenser, Chiller, Pumps, etc. Other: Fire Supression, Control, Security, etc. IT Equipment: Servers, etc. Facility equipment: air movers, power distribution, UPS, etc. IT Equipment: Servers, etc. Facility Boundary Container or Room Boundary 24

25 Web screen shot example (Spreadsheet Prototype, artificial data) Facility (kw) Seq Class Type Detail 1 Facility Power Transfer Switch 2 Facility Power UPS Facility Power DC Batteries / Rectifiers (non UPS Telco Nodes) 4 Facility Power Generator 5 Facility Power Transformer (step down) Facility HVAC Chillers Facility HVAC Return Fans IT Equipment Compute Devices Servers IT Equipment Network Devices Switches 32 IT Equipment Network Devices Routers 40 IT Equipment Other Other Total Facility + IT Power Total IT Power Total Facility Power (kw) 91.0 Total IT Power 54.0 PUE 1.69 DciE 0.59 Total Power (kw) at Container Boundary 59.0 Total IT Power in Container 52.0 Partial PUE (Container Boundary) 1.13 Partial DciE (Container Boundary) 0.88 Container (kw) 25

26 Output Single page PDF output Fileable report identifying configuration, date, data Useable for direct apples-apples comparisons Data saved in csv or a Data Base format TBD based on development discussion Consistent with other Green Grid tools Importable into spreadsheet Re-loadable 26

27 Controversy over air movers Fan-less servers with rack fans rely on those fans Rack-based air movers might be considered either IT or facility depending on your point of view Proposed position is that the air mover power is part of the IT equipment Needs to be discussed in Committees PUE Calculator Tool will allow a separate line to enter air mover power that is not included inside the physical boundary of the server, yet is required for the IT operation (to expose the ambiguity). That power will be allocated to IT, but will be left visible in the tool and the output. 27

28 Status and Timing Consultants hired In development now Alpha version to be tested by Green Grid Task Force members in Q Beta and release target is for Q

29 Free Cooling Map/Web Tool Mark Monroe, Sun Microsystems, Inc. 29

30 Concept and Features Estimate the number of hours of free cooling that may be possible based on weather data at any location in the U.S. Consider European and APAC data in the design so that data can be added in the future without major changes to the application or database. Climate data will be analyzed to determine the number of hours per year that either fresh air or evaporative cooling might be used in a data center. 30

31 Concept and Features (cont d) Two colorful maps must be produced; one showing the U.S. color-coded to show the number of hours of fresh air cooling possible, the second map will show the U.S. color-coded to show the number of hours of evaporative cooling possible. 31

32 Concept and Features (cont d) 32

33 Concept and Features (cont d) A web tool must be produced which allows a user to enter their own location, via zip code, and the data center set points for temperature and humidity that they which to examine for hours of free cooling 33

34 34

35 RFP Responses weatherbank.com selected to implement Response within budget estimates Approved by Board 21 Jan 09 Prototype ready now Seek approval from TC and Board in Feb Release in March 35

36 Roadmap/Futures 36 Individual maps available for $150 direct from weatherbank.com Feedback page allows users to consult directly Review in 3 months, determine enhancements Possibilities: European and APAC data/locations/calculations Simple model for water used by evaporative cooling Input location by latitude/longitude Redisplay map with user-input parameters Connect with DSIRE and other incentive databases More complex models, more accurate results

37 Power Distribution Configurations Online Efficiency Estimator Tool Pam Lembke, IBM 37

38 Tool Purpose The tool: Is for use as a companion to Qualitative Analysis of Power Distribution Configurations for Data Centers, TGG WP #4 and Quantitative Efficiency Analysis of Power Distribution Configurations for Data Centers, TGG WP #16 Reduces the need for paper rewrites, as the tool can be easily updated regularly Allows readers and users to test their own components and proposed system architectures

39 Features Users are able to: Compare two topologies at a time Input data points (load vs efficiency) of their own components for the calculations Create their own topologies based on their components or predefined TGG components Save components and topologies Print input and results in PDF Tool will automatically calculate full efficiency curves for components end-to-end efficiency curves for the two topologies

40 Tool Mock Up

41 Availability The tool is scheduled to be available around Q It will be accessible to members only via The Green Grid website

42 Thank you for attending The 2 nd Annual Green Grid Technical Forum For more information, please visit 42

USAGE AND PUBLIC REPORTING GUIDELINES FOR THE GREEN GRID S INFRASTRUCTURE METRICS (PUE/DCIE)

USAGE AND PUBLIC REPORTING GUIDELINES FOR THE GREEN GRID S INFRASTRUCTURE METRICS (PUE/DCIE) WHITE PAPER #22 USAGE AND PUBLIC REPORTING GUIDELINES FOR THE GREEN GRID S INFRASTRUCTURE METRICS (PUE/DCIE) EDITORS: JON HAAS, INTEL JAMIE FROEDGE, EMERSON NETWORK POWER CONTRIBUTORS: JOHN PFLUEGER, DELL

More information

Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM)

Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM) Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM) Salim Janbeh Physical Infrastructure Consultant uae-sj@panduit.com PANDUIT You Can t Manage What You Don t Measure:

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring

More information

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics

Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations

More information

Recommendations for Measuring and Reporting Overall Data Center Efficiency

Recommendations for Measuring and Reporting Overall Data Center Efficiency Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations

More information

Harmonizing Global Metrics for Data Center Energy Efficiency

Harmonizing Global Metrics for Data Center Energy Efficiency Harmonizing Global Metrics for Data Center Energy Efficiency Dan Azevedo, Symantec Chairman - Metrics & Measurements Work Group Industry Trends Energy Efficient IT The Climate Group: Smarter technology

More information

Data Center Efficiency Metrics: mpue, Partial PUE, ERE, DCcE

Data Center Efficiency Metrics: mpue, Partial PUE, ERE, DCcE Data Center Efficiency Metrics: mpue, Partial PUE, ERE, DCcE Dan Azevedo, Symantec Jud Cooley, Oracle Michael Patterson, Intel Mark Blackburn, 1E Join The Green Grid Technical Forum conversation on Twitter!

More information

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint

Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment

More information

Data Centre Energy Efficiency: A Call To Action

Data Centre Energy Efficiency: A Call To Action Data Centre Energy Efficiency: A Call To Action Vic Smith, The Green Grid, EMEA Technical Work Group Chair Dell, Senior Strategic Technologist Agenda Overview of The Green Grid Mission Community of Members

More information

Data Center Energy Use, Metrics and Rating Systems

Data Center Energy Use, Metrics and Rating Systems Data Center Energy Use, Metrics and Rating Systems Steve Greenberg Energy Management Engineer Environmental Energy Technologies Division Lawrence Berkeley National Laboratory October 31, 2007 Today s s

More information

CIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How

CIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How CIBSE ASHRAE Group Data Centre Energy Efficiency: Who, What, Why, When, Where & How Presenters Don Beaty PE, FASHRAE Founder, President & Managing Director DLB Associates Consulting Engineers Paul Finch

More information

ERE: A METRIC FOR MEASURING THE BENEFIT OF REUSE ENERGY FROM A DATA CENTER

ERE: A METRIC FOR MEASURING THE BENEFIT OF REUSE ENERGY FROM A DATA CENTER WHITE PAPER #29 ERE: A METRIC FOR MEASURING THE BENEFIT OF REUSE ENERGY FROM A DATA CENTER EDITOR: MIKE PATTERSON, INTEL CONTRIBUTORS: BILL TSCHUDI, LAWRENCE BERKELEY NATIONAL LABORATORY OTTO VANGEET,

More information

THE GREEN GRID METRICS: DATA CENTER INFRASTRUCTURE EFFICIENCY (DCIE) DETAILED ANALYSIS

THE GREEN GRID METRICS: DATA CENTER INFRASTRUCTURE EFFICIENCY (DCIE) DETAILED ANALYSIS WHITE PAPER #14 THE GREEN GRID METRICS: DATA CENTER INFRASTRUCTURE EFFICIENCY (DCIE) DETAILED ANALYSIS EDITOR: GARY VERDUN, DELL CONTRIBUTORS: DAN AZEVEDO, SYMANTEC HUGH BARRASS, CISCO STEPHEN BERARD,

More information

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America

7 Best Practices for Increasing Efficiency, Availability and Capacity. XXXX XXXXXXXX Liebert North America 7 Best Practices for Increasing Efficiency, Availability and Capacity XXXX XXXXXXXX Liebert North America Emerson Network Power: The global leader in enabling Business-Critical Continuity Automatic Transfer

More information

Data Center Infrastructure Management: How to Optimize Data Center Operations

Data Center Infrastructure Management: How to Optimize Data Center Operations Data Center Infrastructure Management: How to Optimize Data Center Operations Khaled Nassoura, PE khaled.nassoura@raritan.com General Manager Raritan, Inc. Question of the Day Question: Would any CFO run

More information

PUE : A COMPREHENSIVE EXAMINATION OF THE METRIC

PUE : A COMPREHENSIVE EXAMINATION OF THE METRIC WHITE PAPER #49 PUE : A COMPREHENSIVE EXAMINATION OF THE METRIC EDITORS: Victor Avelar, Schneider Electric Dan Azevedo, Disney Alan French, Emerson Network Power PAGE 2 The Green Grid Association would

More information

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres

Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy

More information

Comprehensive Data Center Energy Management Solutions

Comprehensive Data Center Energy Management Solutions FROM INSIGHT TO EFFICIENCY: Comprehensive Data Center Energy Management Solutions Since 1995, facility managers and BAS professionals have relied on the Niagara framework to provide full convergence of

More information

Re Engineering to a "Green" Data Center, with Measurable ROI

Re Engineering to a Green Data Center, with Measurable ROI Re Engineering to a "Green" Data Center, with Measurable ROI Alan Mamane CEO and Founder Agenda Data Center Energy Trends Benchmarking Efficiency Systematic Approach to Improve Energy Efficiency Best Practices

More information

THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE

THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any

More information

Comprehensive Data Center Energy Management Solutions

Comprehensive Data Center Energy Management Solutions FROM INSIGHT TO EFFICIENCY: Comprehensive Data Center Energy Management Solutions Since 1995, facility managers and BAS professionals have relied on the Niagara Framework to provide full convergence of

More information

Green Data Centers. Energy Efficiency Data Centers. André ROUYER Director of Standardization & Environment. The importance of standardization

Green Data Centers. Energy Efficiency Data Centers. André ROUYER Director of Standardization & Environment. The importance of standardization Green Data Centers GOING FORWARD ENERGY EFFICIENCY TRENDS André ROUYER Director of Standardization & Environment All content in this presentation is protected 2008 American Power Conversion Corporation

More information

Green Computing: Datacentres

Green Computing: Datacentres Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material

More information

Benchmarking results from Indian data centers

Benchmarking results from Indian data centers Benchmarking results from Indian data centers Data Center Energy Efficiency 24 February, ACREX 2011, New Delhi Madhav Kamath. A Energy Efficiency Finance Lead USAID ECO-III Project Data Center Benchmarking

More information

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0

BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied

More information

Green Computing: Datacentres

Green Computing: Datacentres Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material

More information

DOE Data Center Energy Efficiency Program

DOE Data Center Energy Efficiency Program DOE Data Center Energy Efficiency Program Paul Scheihing U.S. Department of Energy Energy Efficiency and Renewable Energy April 2009 1 DOE Industrial Technologies Program Worki king to improve th e energy

More information

GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance. Chapter 8: 8 Guide for assessing GHG emissions of Data Centers

GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance. Chapter 8: 8 Guide for assessing GHG emissions of Data Centers GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance Chapter : Guide for assessing GHG emissions of Data Centers DRAFT March 0 Table of Contents GHG Protocol ICT Sector

More information

Data Centre Testing and Commissioning

Data Centre Testing and Commissioning Data Centre Testing and Commissioning What is Testing and Commissioning? Commissioning provides a systematic and rigorous set of tests tailored to suit the specific design. It is a process designed to

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power and cooling savings through the use of Intel

More information

Smarter Data Centers. Integrated Data Center Service Management

Smarter Data Centers. Integrated Data Center Service Management Smarter Data Centers Integrated Data Center Service Management Approx. 3.500 ton CO² is generated by: Diesel Car-6l /100 km 20.000 km Airplane 5 * Brussels-Barcelona Server, 1.5 A, 24*7*365*3.000 Kwhr

More information

Arch Rock Energy Optimizer in Action Data Center

Arch Rock Energy Optimizer in Action Data Center Arch Rock Energy Optimizer in Action Data Center Business Perspective Recent trends in Information Technology such as dense blade computing, server and storage virtualization, and cloud computing have

More information

Data Center Energy Efficiency Looking Beyond PUE

Data Center Energy Efficiency Looking Beyond PUE Data Center Energy Efficiency Looking Beyond PUE No Limits Software White Paper #4 By David Cole 2011 No Limits Software. All rights reserved. No part of this publication may be used, reproduced, photocopied,

More information

How High Temperature Data Centers and Intel Technologies Decrease Operating Costs

How High Temperature Data Centers and Intel Technologies Decrease Operating Costs Intel Intelligent Management How High Temperature Data Centers and Intel Technologies Decrease Operating Costs and cooling savings through the use of Intel s Platforms and Intelligent Management features

More information

Managing Power Usage with Energy Efficiency Metrics: The Available Me...

Managing Power Usage with Energy Efficiency Metrics: The Available Me... 1 of 5 9/1/2011 1:19 PM AUG 2011 Managing Power Usage with Energy Efficiency Metrics: The Available Metrics and How to Use Them Rate this item (1 Vote) font size Data centers consume an enormous amount

More information

StruxureWare TM Data Center Operation

StruxureWare TM Data Center Operation StruxureWare TM Data Center End to end Management (DCIM) software for monitoring, control of power, cooling, security and energy usage from the building through IT systems Part of StruxureWare for Data

More information

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems

How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems How Does Your Data Center Measure Up? Energy Efficiency Metrics and Benchmarks for Data Center Infrastructure Systems Paul Mathew, Ph.D., Staff Scientist Steve Greenberg, P.E., Energy Management Engineer

More information

SURVEY RESULTS: DATA CENTER ECONOMIZER USE

SURVEY RESULTS: DATA CENTER ECONOMIZER USE WHITE PAPER #41 SURVEY RESULTS: DATA CENTER ECONOMIZER USE EDITOR: Jessica Kaiser, Emerson Network Power CONTRIBUTORS: John Bean, Schneider Electric Tom Harvey, Emerson Network Power Michael Patterson,

More information

Metering and Managing University of Sheffield Data Centres. Chris Cartledge Independent Consultant C.Cartledge@sheffield.ac.uk

Metering and Managing University of Sheffield Data Centres. Chris Cartledge Independent Consultant C.Cartledge@sheffield.ac.uk Metering and Managing University of Sheffield Data Centres Chris Cartledge Independent Consultant C.Cartledge@sheffield.ac.uk Summary ICT Electricity Use Footprint Data Centre Electricity Use European

More information

DATA CENTER ASSESSMENT SERVICES

DATA CENTER ASSESSMENT SERVICES DATA CENTER ASSESSMENT SERVICES ig2 Group Inc. is a Data Center Science Company which provides solutions that can help organizations automatically optimize their Data Center performance, from assets to

More information

Improve competiveness of IDC and enterprise data centers with DCIM

Improve competiveness of IDC and enterprise data centers with DCIM Improve competiveness of IDC and enterprise data centers with DCIM This paper studies the implementation of modern DCIM systems for data centers to improve operational competitiveness with ATEN's DCIM

More information

Impact of Virtualization on Data Center Physical Infrastructure White Paper #27. Tom Brey, IBM Operations Work Group

Impact of Virtualization on Data Center Physical Infrastructure White Paper #27. Tom Brey, IBM Operations Work Group Impact of Virtualization on Data Center Physical Infrastructure White Paper #27 Tom Brey, IBM perations Work Group 1 Virtualization Two Steps WP #19 USING VIRTUALIZATIN T IMPRVE DATA CENTER EFFICIENCY

More information

DC Pro Assessment Tools. November 14, 2010

DC Pro Assessment Tools. November 14, 2010 DC Pro Assessment Tools November 14, 2010 William Tschudi, PE Lawrence Berkeley National Laboratory WFTschudi@lbl.gov 510-495-2417 1 Slide 1 Assessment tools LBNL is developing tools to assist in performing

More information

Guidance for Calculation of Efficiency (PUE) in Data Centers

Guidance for Calculation of Efficiency (PUE) in Data Centers Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 1 by Victor Avelar > Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or

More information

BYRNE DIXON HAS BRIGHT IDEAS. Reducing data centre energy usage

BYRNE DIXON HAS BRIGHT IDEAS. Reducing data centre energy usage BYRNE DIXON HAS BRIGHT IDEAS Reducing data centre energy usage 1.1 Introduction Agenda Data Centre Efficiency Data Centre Efficiency Byrne Dixon Background Data Centre Efficiency Theory Government Support

More information

Guidance for Calculation of Efficiency (PUE) in Data Centers

Guidance for Calculation of Efficiency (PUE) in Data Centers Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 3 by Victor Avelar Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or other

More information

How To Manage Energy At An Energy Efficient Cost

How To Manage Energy At An Energy Efficient Cost Hans-Dieter Wehle, IBM Distinguished IT Specialist Virtualization and Green IT Energy Management in a Cloud Computing Environment Smarter Data Center Agenda Green IT Overview Energy Management Solutions

More information

Energy Management in a Cloud Computing Environment

Energy Management in a Cloud Computing Environment Hans-Dieter Wehle, IBM Distinguished IT Specialist Virtualization and Green IT Energy Management in a Cloud Computing Environment Smarter Data Center Agenda Green IT Overview Energy Management Solutions

More information

ENERGY STAR Data Center Infrastructure Rating Development Update. Web Conference November 12, 2009

ENERGY STAR Data Center Infrastructure Rating Development Update. Web Conference November 12, 2009 ENERGY STAR Data Center Infrastructure Rating Development Update Web Conference November 12, 2009 Web Conference Tips Background Noise Please mute your phone until you are ready to speak. Hold & Music

More information

Data Center Design Guide Overview and Status

Data Center Design Guide Overview and Status Data Center Design Guide Overview and Status Jon Haas Data Center Design Guide Work Group Chair, Technical Committee Chair, and Board Member Intel Corporation George Navarro Data Center Design Guide Work

More information

Reducing Data Center Loads for a Large-Scale, Net Zero Office Building

Reducing Data Center Loads for a Large-Scale, Net Zero Office Building rsed Energy Efficiency & Renewable Energy FEDERAL ENERGY MANAGEMENT PROGRAM Reducing Data Center Loads for a Large-Scale, Net Zero Office Building Energy Efficiency & Renewable Energy Executive summary

More information

AbSTRACT INTRODUCTION background

AbSTRACT INTRODUCTION background february 20, 2007 GREEN GRID METRICS: Describing Datacenter Power Efficiency Technical Committee White Paper white paper 1 Abstract The Green Grid is an association of IT professionals seeking to dramatically

More information

Analysis of the Brazilian Data Center Power Supplies Market

Analysis of the Brazilian Data Center Power Supplies Market Analysis of the Brazilian Data Center Power Supplies Market IT Infrastructure Outsourcing Services Compel New Trends for this Growing Market ND27-14 September 2013 Contents Section Slide Numbers Executive

More information

Data Centers: Definitions, Concepts and Concerns

Data Centers: Definitions, Concepts and Concerns Data Centers: Definitions, Concepts and Concerns Arash Mousavi DCC September 2013 Agenda 1. Introduction 2. Issues in Modern Data Centers: Siemens Integrated Data Center Solutions 3. Issues in Modern Data

More information

The Mission Critical Data Center Understand Complexity Improve Performance

The Mission Critical Data Center Understand Complexity Improve Performance The Mission Critical Data Center Understand Complexity Improve Performance Communications Technology Forum Fall 2013 Department / Presenter / Date 1 Rittal IT Solutions The State of the Data Center Market

More information

Datacenter Infrastructure Management (DCIM) Solution

Datacenter Infrastructure Management (DCIM) Solution Datacenter Infrastructure Management (DCIM) Solution Figure 1. Asset Management in 3D, Real-Time Reporting, CFD Modeling & Analysis Description Datacenter Clarity provides the tools to accurately and efficiently

More information

Optimizing the Efficiency of the NCAR-Wyoming Supercomputing Center Facility. Ademola Olarinde Mentor: Aaron Andersen

Optimizing the Efficiency of the NCAR-Wyoming Supercomputing Center Facility. Ademola Olarinde Mentor: Aaron Andersen Optimizing the Efficiency of the NCAR-Wyoming Supercomputing Center Facility Ademola Olarinde Mentor: Aaron Andersen August 2, 2013 1 Education: Mechanical Engineering Grad Student Texas A&M University

More information

Unleashing Stranded Power and Cooling Data

Unleashing Stranded Power and Cooling Data Unleashing Stranded Power and Cooling from New and Existing Data Centers An affordable, five-step approach to addressing power and cooling shortages By Dr. Kenneth Uhlman, P.E. Director of Data Center

More information

How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring

How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring How to Maximize Data Center Efficiencies with Rack Level Power Distribution and Monitoring Brian Rehnke e-pdu Business Development Manager November, 2011 The Problems Energy Usage in most data centers

More information

Electrical Systems. <Presenter>

Electrical Systems. <Presenter> Review Root Causes of Energy Inefficiency Roadmap to Maximize Energy Efficiency Best Practices Alternative Energy Sources Controls Take Aways Seek Professional Help. ENERGY INEFFICIENCY OF

More information

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions

How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Intel Intelligent Power Management Intel How High Temperature Data Centers & Intel Technologies save Energy, Money, Water and Greenhouse Gas Emissions Power savings through the use of Intel s intelligent

More information

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers

Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Energy Efficiency Opportunities in Federal High Performance Computing Data Centers Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory

More information

Energy Performance Optimization of Server Room HVAC System

Energy Performance Optimization of Server Room HVAC System International Journal of Thermal Technologies E-ISSN 2277 4114 2 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijtt/ Research Article Manoj Jadhav * and Pramod Chaudhari Department

More information

Increasing Data Center Efficiency through Metering and Monitoring Power Usage

Increasing Data Center Efficiency through Metering and Monitoring Power Usage White Paper Intel Information Technology Computer Manufacturing Data Center Efficiency Increasing Data Center Efficiency through Metering and Monitoring Power Usage To increase data center energy efficiency

More information

Data Centers: How Does It Affect My Building s Energy Use and What Can I Do?

Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? Data Centers: How Does It Affect My Building s Energy Use and What Can I Do? 1 Thank you for attending today s session! Please let us know your name and/or location when you sign in We ask everyone to

More information

Data centre energy efficiency metrics. Existing and proposed metrics to provide effective understanding and reporting of data centre energy

Data centre energy efficiency metrics. Existing and proposed metrics to provide effective understanding and reporting of data centre energy Existing and proposed metrics to provide effective understanding and reporting of data centre energy Liam Newcombe Data Centre Specialist Group 1 Introduction... 2 2 Summary... 6 3 Overview of metrics...

More information

Legacy Data Centres Upgrading the cooling capabilities What are the options?

Legacy Data Centres Upgrading the cooling capabilities What are the options? Legacy Data Centres Upgrading the cooling capabilities What are the options? Presentation Structure What is a Legacy Data Centre? What is CRAC cooling? ASHRAE Standards Overview Available Cooling Systems

More information

scalable data centre energy management solution

scalable data centre energy management solution scalable data centre energy management solution scalable data centre energy management solution EcoMeasure - Scalable Data Centre Energy Management & Efficiency Measurement Solution by Workspace Technology

More information

How To Improve Energy Efficiency In A Data Center

How To Improve Energy Efficiency In A Data Center Google s Green Data Centers: Network POP Case Study Table of Contents Introduction... 2 Best practices: Measuring. performance, optimizing air flow,. and turning up the thermostat... 2...Best Practice

More information

FNT EXPERT PAPER. // Data Center Business Value Dashboards AUTHOR. Data Center Infrastructure Management (DCIM) www.fntsoftware.

FNT EXPERT PAPER. // Data Center Business Value Dashboards AUTHOR. Data Center Infrastructure Management (DCIM) www.fntsoftware. FNT EXPERT PAPER AUTHOR Oliver Lindner Head of Business Line DCIM FNT GmbH // Data Center Business Value Dashboards Data Center Infrastructure Management (DCIM) Energy efficiency is an important strategic

More information

Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources

Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources Energy Recovery Systems for the Efficient Cooling of Data Centers using Absorption Chillers and Renewable Energy Resources ALEXANDRU SERBAN, VICTOR CHIRIAC, FLOREA CHIRIAC, GABRIEL NASTASE Building Services

More information

The Effect of Data Centre Environment on IT Reliability & Energy Consumption

The Effect of Data Centre Environment on IT Reliability & Energy Consumption The Effect of Data Centre Environment on IT Reliability & Energy Consumption Steve Strutt EMEA Technical Work Group Member IBM The Green Grid EMEA Technical Forum 2011 Agenda History of IT environmental

More information

BCA-IDA Green Mark for New Data Centres Version NDC/1.0

BCA-IDA Green Mark for New Data Centres Version NDC/1.0 BCA-IDA Green Mark for New Data Centres Version NDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied

More information

Capgemini UK Infrastructure Outsourcing

Capgemini UK Infrastructure Outsourcing Together. Free your energies Capgemini UK Infrastructure Outsourcing Project Arthur Improved Data Centre Efficiency Paul Feeney Capgemini Tony Mills Spie Matthew Hall Project Arthur The Toltec data centre,

More information

Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL

Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency. Steve Hammond NREL Bytes and BTUs: Holistic Approaches to Data Center Energy Efficiency NREL 1 National Renewable Energy Laboratory Presentation Road Map A Holistic Approach to Efficiency: Power, Packaging, Cooling, Integration

More information

Demonstration of Data Center Energy Use Prediction Software

Demonstration of Data Center Energy Use Prediction Software LBNL-6608E Demonstration of Data Center Energy Use Prediction Software Henry Coles, Steve Greenberg and William Tschudi Environmental Energy Technologies Division September 2013 DISCLAIMER This report

More information

University of St Andrews. Energy Efficient Data Centre Cooling

University of St Andrews. Energy Efficient Data Centre Cooling Energy Efficient Data Centre Cooling St. Andrews and Elsewhere Richard Lumb Consultant Engineer Future-Tech Energy Efficient Data Centre Cooling There is no one single best cooling solution for all Data

More information

Statement Of Work. Data Center Thermography Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary

Statement Of Work. Data Center Thermography Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary Statement Of Work Professional Services Data Center Thermography Assessment Data Center Thermography Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features & Benefits

More information

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015

I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015 I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility

More information

Direct Fresh Air Free Cooling of Data Centres

Direct Fresh Air Free Cooling of Data Centres White Paper Introduction There have been many different cooling systems deployed in Data Centres in the past to maintain an acceptable environment for the equipment and for Data Centre operatives. The

More information

EU Code of Conduct for Data Centre Efficiency

EU Code of Conduct for Data Centre Efficiency EU Code of Conduct for Data Centre Efficiency A Green Practice Accredited by British Computer Society (BCS) EU Code of Conduct for Data Centre Efficiency Local Organizer Practices in Data Centre Industry

More information

Improving Data Centers Energy Reliability & Efficiency. December 2015

Improving Data Centers Energy Reliability & Efficiency. December 2015 Improving Data Centers Energy Reliability & Efficiency December 2015 Background The challenges Alternative solutions SATEC approach Advantages Cases Summary Data Centers Energy Challenges Worldwide Data

More information

AIRAH Presentation April 30 th 2014

AIRAH Presentation April 30 th 2014 Data Centre Cooling Strategies The Changing Landscape.. AIRAH Presentation April 30 th 2014 More Connections. More Devices. High Expectations 2 State of the Data Center, Emerson Network Power Redefining

More information

How green is your data center?

How green is your data center? Siemens Answers: Sustainable Future How green is your data center? Istanbul June 01, 2010 Agenda 1 Solution 2 Siemens Data Center Approach 2 Designing with multiple power density zones can reduce energy

More information

Greening Data Centers

Greening Data Centers Greening Data Centers Dallas Thornton SDSC Division Director, Cyberinfrastructure Services March 2, 2011 Data Centers Are Enormous Users of Power US Data Centers (TeraWatt Hours per Year) 125 US Televisions

More information

Convergence of Complexity

Convergence of Complexity Convergence of Complexity Optimize Existing Data Center Space Measure And Allocate Energy Cost Plan for new data centers or additional capacity How to make your Data Center Last Longer, Gartner, December

More information

Analysis of data centre cooling energy efficiency

Analysis of data centre cooling energy efficiency Analysis of data centre cooling energy efficiency An analysis of the distribution of energy overheads in the data centre and the relationship between economiser hours and chiller efficiency Liam Newcombe

More information

Server room guide helps energy managers reduce server consumption

Server room guide helps energy managers reduce server consumption Server room guide helps energy managers reduce server consumption Jan Viegand Viegand Maagøe Nr. Farimagsgade 37 1364 Copenhagen K Denmark jv@viegandmaagoe.dk Keywords servers, guidelines, server rooms,

More information

Data Center Infrastructure Management: ERP for the Data Center Manager

Data Center Infrastructure Management: ERP for the Data Center Manager Data Center Infrastructure Management: ERP for the Data Center Manager 1 2 Topics What s DCIM & the ERP Analogy Why DCIM How DCIM Works How DCIM Helps 3 DCIM by Definition DCIM is a system that collects

More information

Specialty Environment Design Mission Critical Facilities

Specialty Environment Design Mission Critical Facilities Brian M. Medina PE Associate Brett M. Griffin PE, LEED AP Vice President Environmental Systems Design, Inc. Mission Critical Facilities Specialty Environment Design Mission Critical Facilities March 25,

More information

Code of Conduct on Data Centre Energy Efficiency. Endorser Guidelines and Registration Form. Version 3.0.0

Code of Conduct on Data Centre Energy Efficiency. Endorser Guidelines and Registration Form. Version 3.0.0 1 EUROPEAN COMMISSION DIRECTORATE-GENERAL JRC JOINT RESEARCH CENTRE Institute for Energy Renewable Energies Unit Ispra, 1 st January 2015 Code of Conduct on Data Centre Energy Efficiency Endorser Guidelines

More information

The Efficient Enterprise. Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric

The Efficient Enterprise. Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric Ee The Efficient Enterprise Juan Carlos Londoño Data Center Projects Engineer APC by Schneider Electric Keystrokes Kilowatts Heat OUT Electricity IN Need for bandwidth exploding Going hyperbolic! 30,000

More information

Energy Efficiency and Availability Management in Consolidated Data Centers

Energy Efficiency and Availability Management in Consolidated Data Centers Energy Efficiency and Availability Management in Consolidated Data Centers Abstract The Federal Data Center Consolidation Initiative (FDCCI) was driven by the recognition that growth in the number of Federal

More information

FEAR Model - Review Cell Module Block

FEAR Model - Review Cell Module Block F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data

More information

Foreseer Services. Product application guide. Table of contents

Foreseer Services. Product application guide. Table of contents Product application guide Foreseer Services Table of contents 1.0 General.......................................... 2 1.1 What are Foreseer Software and Engineering Services.... 3 1.1.1 Foreseer Service

More information

Qualitative Analysis of Power Distribution Configurations for Data Centers

Qualitative Analysis of Power Distribution Configurations for Data Centers Qualitative Analysis of Power Distribution Configurations for Data Centers White Paper #4 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted,

More information

Improving Sustainability in Campus Data Centers Click To Edit Master Title Style

Improving Sustainability in Campus Data Centers Click To Edit Master Title Style Improving Sustainability in Campus Data Centers Click To Edit Master Title Style March 31, 2015 12:10-1:00 PM ET Agenda Welcome and Better Buildings Overview Michigan State University Partnering with the

More information

ICT and the Green Data Centre

ICT and the Green Data Centre ICT and the Green Data Centre Scott McConnell Sales Manager c/o Tanya Duncan MD Interxion Ireland Green Data Centres Our Responsibility Data centre greenhouse gas emissions are projected to quadruple by

More information

Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary

Statement Of Work. Data Center Power and Cooling Assessment. Service. Professional Services. Table of Contents. 1.0 Executive Summary Statement Of Work Professional Services Data Center Power and Cooling Assessment Data Center Power and Cooling Assessment Service 1.0 Executive Summary Table of Contents 1.0 Executive Summary 2.0 Features

More information

Green Data Centre Design

Green Data Centre Design Green Data Centre Design A Holistic Approach Stantec Consulting Ltd. Aleks Milojkovic, P.Eng., RCDD, LEED AP Tommy Chiu, EIT, RCDD, LEED AP STANDARDS ENERGY EQUIPMENT MATERIALS EXAMPLES CONCLUSION STANDARDS

More information