Data Center Efficiency Metrics: mpue, Partial PUE, ERE, DCcE
|
|
|
- Cuthbert Tucker
- 10 years ago
- Views:
Transcription
1 Data Center Efficiency Metrics: mpue, Partial PUE, ERE, DCcE Dan Azevedo, Symantec Jud Cooley, Oracle Michael Patterson, Intel Mark Blackburn, 1E Join The Green Grid Technical Forum conversation on Twitter! As you are tweeting, use #TGG11.
2 Presenters Dan Azevedo, Symantec Director of Data Center Architecture, Strategy & Innovation Board Member and Metrics & Measurements Chairman, The Green Grid Jud Cooley, Oracle Senior Director, Design for the Data Center Alternate Board Member, The Green Grid Michael K. Patterson, Intel Senior Power & Thermal Architect Technology & Strategy Chairman, The Green Grid Mark Blackburn, 1E Co-Founder & Chief Technologist Metrics & Measurements Vice Chairman, The Green Grid
3 The United States of America, European Union, and Japan have successfully completed harmonization efforts around one data center energy efficiency metric
4 Power Usage Effectiveness (PUE)
5 U.S. Data Center Industry Session 13 Jan 2010 Attendees: Session Objectives: Data Center Efficiency Metrics: Develop common definitions for key metrics and seek consensus on guiding principles for metrics Measurement Protocols: Define current status and gaps and coordinate plans for further development Tools: Review status and coordinate development
6 U.S. Data Center Industry Session Taskforce Results Released two memos: Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics (Feb 2010) Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers (Jul 2010) US Consensus Achieved with Public Announcement for PUE with Guidance and Refinement Work in Progress Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE in a Mixed Use Facility
7 Global Metric Harmonization Meetings 26 Mar 2009, 02 Feb 2010, 26 Oct 2010, 15 Feb 2011 Attendees: Ministry of Economy, Trade and Industry Green IT Promotional Council The U.S. Department of Energy s Save Energy Now and Federal Energy Management Programs The U.S. Environmental Protection Agency s ENERGY STAR Program The European Commission Joint Research Center Data Centers Code of Conduct The Green Grid Session Objectives: Share global lessons and practices with an objective of arriving at a set of metrics, indices, and measurement protocols which can be formally endorsed or adopted by each participant organization to improve data center energy efficiency globally.
8 Global Metric Harmonization Meetings Taskforce Results Released two memos: The United States of America, European Union and Japan Reach Agreement on Guiding Principles for Data Center Energy Efficiency Metrics (Feb 2010) Global Taskforce Reaches Agreement on Measurement Protocols for PUE Continues Discussion of Additional Energy Efficiency Metrics (Feb 2011) The United States of America, European Union and Japan Successfully Complete Harmonizing PUE Work in Progress: Prioritized further areas of work to drive Data Center Energy Efficiency (see appendix) 8
9 Influences Specific to PUE Global Harmonization of Metrics U.S. Industry Data Center Taskforce The Green Grid
10 Partial PUE (ppue)
11 Rationale for Partial PUE PUE can be used to compare data center designs Often PUE's are presented that do not take into account all of the infrastructure components in order to highlight one particular portion of a data center Container only PUE Cooling system PUE Power delivery PUE These comparisons have value, but are not truly PUE Partial PUE provides a formal language for this Partial PUE is abbreviated ppue
12 ppue Definition PUE = Total Facility Energy divided by the IT Equipment Energy This takes into account energy use within a facility Partial PUE is for energy use within a boundary ppue = Total Energy within a boundary divided by the IT Equipment Energy within that boundary
13 Example 1 PUE = 600/475 = 1.26 ppue of Container = 500/475 = 1.05
14 Example 2 PUE = 2700/2000 = 1.35 PPUE 1 = 1700/1500 = 1.13 PPUE 2 = 700/500 = 1.40 Zones 1 and 2 have the same chiller power, but different IT loads So their Partial PUE's are different
15 Notations N is for non-it power I is for IT power PUE = (N 0 + N 1 + N 2 + I 1 + I 2 ) (I 1 + I 2 ) ppue 1 = ppue 2 = (N 1 + I 1 ) (I 1 ) (N 2 + I 2 ) (I 2 ) Zone 0 has no IT, so ppue is undefined
16 ppue Relative to PUE Zones 1 and 2 each hold a portion of the IT load: (I 1 ) (I 2 ) r 1 = r (I 1 + I 2 ) 2 = (I 1 + I 2 ) PUE = (N 0 ) (I 1 + I 2 ) + (r 1 * ppue 1 ) + (r 2 * ppue 2 ) (The proof is in the White Paper, note that r 1 + r 2 = 100%) The PUE is the overhead seen by all zones plus the Partial PUE of each zone multiplied by the percentage of that zone's contribution to the overall IT load
17 What It Means PUE = (N 0 ) (I 1 + I 2 ) + (r 1 * ppue 1 ) + (r 2 * ppue 2 ) If one of the ppue's is bad, work on that But if one of the r's is very large, the payback for working on that is great
18 Example 3 This is the same as example 2 except that Zone 1 is 10 times as large PUE = 20,000/15,500 = 1.29 ppue 1 = 17,000/15,000 = 1.13 ppue 2 = 700/500 = 1.40 r 1 = 15,000/15,500 = 0.97 r 2 = 500/15,500 = 0.03
19 Summary Partial PUE can be used to describe the PUE contribution of a subset of facility components Partial PUE refers to components within a boundary The boundary can be physical or logical, for example: All cooling components All power components All Tier II components All baseline load components All departmental components PUE is a valuable metric for monitoring and managing data center power If only a portion of the facility is being analyzed, use partial PUE
20 Energy Reuse Effectiveness (ERE)
21 I am re-using waste heat from my data center on another part of my site and my PUE is 0.8!
22 I am reusing waste heat from my data center on another part of my site and my PUE is 0.8! While re-using excess energy from the data center can be a good thing to do, it should not be rolled into PUE The definition of PUE does not allow this There is a metric to do this! ERE
23 ERE Definition PUE = PUE = Total Energy IT Energy Cooling + Power + Lighting IT + IT ERE = ERE = Total Energy - Reused Energy IT Energy Cooling + Power + Lighting IT + IT - Reused
24 ERE Alternate Development Define energy reuse factor (ERF) as: Then: ERE ERF = And finally: = Reuse Energy Total Energy Cool + Pwr + Light IT ERE + IT - Reused = (1- ERF) PUE (1 ERF) PUE ERF and PUE are mathematically related, but differ and need to be defined and reported clearly.
25 PUE and ERF Ranges 1 PUE PUE = Cooling + Power + Lighting IT + IT 0 ERF 1 ERF = Reuse Energy Total Energy 0 ERE ERE = Cool + Pwr + Light IT + IT - Reused
26 Data Center Boundary Consideration and ERF Cooling E Waste A Utility IT F B UPS C PDU D PUE = A + B D Data Center Boundary
27 Use of ERE Non-DC space waste H Utility A Cool E ICT G Absorp Chiller F I B UPS C PDU D PUE = A + B D ERE = Both PUE & ERE valid metrics A + B- F D Data Center Boundary
28 Improper Use of ERE waste H Utility A Cool E ICT G AbsorpC hiller F I B UPS C PDU D PUE = A + B D ERE = A + B- F D Data Center Boundary PUE is still the right metric; note that A (and PUE) will be less than in the design w/o added recovery and absorption chiller
29 Comparison with PUE One view of PUE is that is the tax or burden in energy costs you must pay above the IT load to run the data center; ERE allows the same vision PUE = 1.0 means 100% of the energy you bring in to the data center goes to the IT ERE = 1.0 means you only need to bring into the site an amount equal to 100% of the IT energy to support the data center We need both! Case 1 Case 2 PUE = 2.0 PUE = 1.2 ERF= 0.55 ERF=0.25 ERE = 0.9 ERE=0.9 Case 1 focuses on PUE, Case 2 focuses on ERF
30 Data Center Compute Efficiency (DCcE)
31 Unused Servers ~15% of servers powered on but not being used CPU utilization doesn t tell the whole story Virtualization doesn t cure the problem it can make it worse Removing unused servers will increase data center efficiency Reduce power for physical servers Reduce resource usage for virtual servers
32 How to Find Unused Servers Servers are procured to provide a primary service If they are no longer providing this service then they are no longer needed and should be decommissioned or repurposed. Useful work <> CPU utilization Secondary & tertiary services can cause utilization Virus scanning Disk indexing / defragmentation Backup Etc..
33 Determining Primary Service Usage Tracking primary services resource utilization is impractical too many different primary service apps Tracking secondary & tertiary services is easier typically a well known small set of applications Primary service work = All work secondary & tertiary work True for CPU & I/O Some applications do not lend themselves to measurement like this e.g. terminal services Track incoming network sessions for useful processes Track interactive logons always assumed to be useful
34 Calculating Primary Service Usage Over a time period If Or Or Or Then Else All CPU minus secondary & tertiary CPU > noise threshold All I/O minus secondary & tertiary I/O > noise threshold There have been incoming network sessions for primary services There has been an interactive logon Server was being useful Server was not being useful
35 Server Compute Efficiency (ScE) The proportion of samples that the server is providing primary services over time (as a percentage) Any server with an ScE of 0% over a prolonged period is not being used and can be decommissioned or repurposed Any servers with low ScE are worth investigation may be candidates for virtualization
36 Data Center compute Efficiency (DCcE) Data Center compute Efficiency (DCcE) aggregates ScE across all servers in the data center Provides a benchmark against which to improve (like PUE) DCcE is NOT a productivity metric it does not measure how MUCH work is done, just the proportion of work that is useful DCcE CANNOT and SHOULD NOT be compared between data centers due to the subjective determination of secondary and tertiary processes
37 Thank you for attending The Green Grid Technical Forum 2011 Join The Green Grid Technical Forum conversation on Twitter! As you are tweeting, use #TGG11.
ERE: A METRIC FOR MEASURING THE BENEFIT OF REUSE ENERGY FROM A DATA CENTER
WHITE PAPER #29 ERE: A METRIC FOR MEASURING THE BENEFIT OF REUSE ENERGY FROM A DATA CENTER EDITOR: MIKE PATTERSON, INTEL CONTRIBUTORS: BILL TSCHUDI, LAWRENCE BERKELEY NATIONAL LABORATORY OTTO VANGEET,
Harmonizing Global Metrics for Data Center Energy Efficiency
Harmonizing Global Metrics for Data Center Energy Efficiency Dan Azevedo, Symantec Chairman - Metrics & Measurements Work Group Industry Trends Energy Efficient IT The Climate Group: Smarter technology
Data Center Energy Efficiency Looking Beyond PUE
Data Center Energy Efficiency Looking Beyond PUE No Limits Software White Paper #4 By David Cole 2011 No Limits Software. All rights reserved. No part of this publication may be used, reproduced, photocopied,
Power Usage Effectiveness (PUE) & Data Center Infrastructure Efficiency (DCiE) Progress
Power Usage Effectiveness (PUE) & Data Center Infrastructure Efficiency (DCiE) Progress Dan Azevedo, Symantec Jon Haas, Intel Jud Cooley, Sun Microsystems, Inc. Mark Monroe, Sun Microsystems, Inc. Pam
ISSN : 0976-5166 333
THE GREEN GRID SAGA -- A GREEN INITIATIVE TO DATA CENTERS: A REVIEW PARTHA PRATIM RAY * Department of Electronics and Communication Engineering, Haldia Institute of Technology, Haldia, Purba Medinipur-721657,
Data Center Industry Leaders Reach Agreement on Guiding Principles for Energy Efficiency Metrics
On January 13, 2010, 7x24 Exchange Chairman Robert Cassiliano and Vice President David Schirmacher met in Washington, DC with representatives from the EPA, the DOE and 7 leading industry organizations
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 1 Measuring PUE at Dedicated Data Centers 15 July 2010 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations
Green Evaluation Metrics and Software Tool for Data Center
Green Evaluation Metrics and Software Tool for Data Center Wong Hui Shin Faculty of Computing and Informatics, Multimedia University, Cyberjaya, Selangor, Malaysia. [email protected] Saravanan Muthaiyah
Recommendations for Measuring and Reporting Overall Data Center Efficiency
Recommendations for Measuring and Reporting Overall Data Center Efficiency Version 2 Measuring PUE for Data Centers 17 May 2011 Table of Contents 1 Introduction... 1 1.1 Purpose Recommendations for Measuring
GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance. Chapter 8: 8 Guide for assessing GHG emissions of Data Centers
GHG Protocol Product Life Cycle Accounting and Reporting Standard ICT Sector Guidance Chapter : Guide for assessing GHG emissions of Data Centers DRAFT March 0 Table of Contents GHG Protocol ICT Sector
CIBSE ASHRAE Group. Data Centre Energy Efficiency: Who, What, Why, When, Where & How
CIBSE ASHRAE Group Data Centre Energy Efficiency: Who, What, Why, When, Where & How Presenters Don Beaty PE, FASHRAE Founder, President & Managing Director DLB Associates Consulting Engineers Paul Finch
ENERGY STAR Data Center Infrastructure Rating Development Update. Web Conference November 12, 2009
ENERGY STAR Data Center Infrastructure Rating Development Update Web Conference November 12, 2009 Web Conference Tips Background Noise Please mute your phone until you are ready to speak. Hold & Music
Global Green Data Center Best Practices In Action
Global Green Data Center Best Practices In Action DOUG WASHBURN VICE PRESIDENT & RESEARCH DIRECTOR September 25, 2013 Four questions I will answer 1 Why is green important to your business? 2 Why is green
Living Green in the Data Center. Dominick Regina Associate Director, Infrastructure Services
Living Green in the Data Center Dominick Regina Associate Director, Infrastructure Services The Challenge Design and build a new stand-alone data center Capacity for at least 10 years of normal growth
Data Centre Energy Efficiency: A Call To Action
Data Centre Energy Efficiency: A Call To Action Vic Smith, The Green Grid, EMEA Technical Work Group Chair Dell, Senior Strategic Technologist Agenda Overview of The Green Grid Mission Community of Members
USAGE AND PUBLIC REPORTING GUIDELINES FOR THE GREEN GRID S INFRASTRUCTURE METRICS (PUE/DCIE)
WHITE PAPER #22 USAGE AND PUBLIC REPORTING GUIDELINES FOR THE GREEN GRID S INFRASTRUCTURE METRICS (PUE/DCIE) EDITORS: JON HAAS, INTEL JAMIE FROEDGE, EMERSON NETWORK POWER CONTRIBUTORS: JOHN PFLUEGER, DELL
A Market Transformation Programme for Improving Energy Efficiency in Data Centres
A Market Transformation Programme for Improving Energy Efficiency in Data Centres Paolo Bertoldi, European Commission Joint Research Centre ABSTRACT The European Code of Conduct for Data Centres is a voluntary
Data Center Life Cycle Analysis. Christophe Garnier EMEA Technical Work Group Member Schneider Electric
Data Center Life Cycle Analysis Christophe Garnier EMEA Technical Work Group Member Schneider Electric V3 The 3 Pillars of Sustainability Sustainability = meet the needs of the present without compromising
World s Greenest High Performance Data Center
World s Greenest High Performance Data Center EcoDataCenter Sustainability for future generations Our Services Colocation Data Center for Mission Critical Requirements Lockable racks, cages, private rooms
Using Data Domain Storage with Symantec Enterprise Vault 8. White Paper. Michael McLaughlin Data Domain Technical Marketing
Using Data Domain Storage with Symantec Enterprise Vault 8 White Paper Michael McLaughlin Data Domain Technical Marketing Charles Arconi Cornerstone Technologies - Principal Consultant Data Domain, Inc.
Green Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
Heat Recovery from Data Centres Conference Designing Energy Efficient Data Centres
What factors determine the energy efficiency of a data centre? Where is the energy used? Local Climate Data Hall Temperatures Chiller / DX Energy Condenser / Dry Cooler / Cooling Tower Energy Pump Energy
Data Center Energy Use, Metrics and Rating Systems
Data Center Energy Use, Metrics and Rating Systems Steve Greenberg Energy Management Engineer Environmental Energy Technologies Division Lawrence Berkeley National Laboratory October 31, 2007 Today s s
AbSTRACT INTRODUCTION background
february 20, 2007 GREEN GRID METRICS: Describing Datacenter Power Efficiency Technical Committee White Paper white paper 1 Abstract The Green Grid is an association of IT professionals seeking to dramatically
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint
Measuring Power in your Data Center: The Roadmap to your PUE and Carbon Footprint Energy usage in the data center Electricity Transformer/ UPS Air 10% Movement 12% Cooling 25% Lighting, etc. 3% IT Equipment
Guidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 3 by Victor Avelar Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or other
Green Computing: Datacentres
Green Computing: Datacentres Simin Nadjm-Tehrani Department of Computer and Information Science (IDA) Linköping University Sweden Many thanks to Jordi Cucurull For earlier versions of this course material
Green Cloud Computing: Case Study Sri Lanka & Pakistan
Green Cloud Computing: Case Study Sri Lanka & Pakistan 28-30 July 2015 Colombo, Sri Lanka Sameer Sharma, Senior Advisor Regional Office Asia-Pacific Recalling ITU TRCSL Workshop in 2013 ITU TRCSL Workshop
Guideline for Water and Energy Considerations During Federal Data Center Consolidations
Guideline for Water and Energy Considerations During Federal Data Center Consolidations Prepared for the U.S. Department of Energy Federal Energy Management Program By Lawrence Berkeley National Laboratory
Managing Power Usage with Energy Efficiency Metrics: The Available Me...
1 of 5 9/1/2011 1:19 PM AUG 2011 Managing Power Usage with Energy Efficiency Metrics: The Available Metrics and How to Use Them Rate this item (1 Vote) font size Data centers consume an enormous amount
Green Data Centers. Energy Efficiency Data Centers. André ROUYER Director of Standardization & Environment. The importance of standardization
Green Data Centers GOING FORWARD ENERGY EFFICIENCY TRENDS André ROUYER Director of Standardization & Environment All content in this presentation is protected 2008 American Power Conversion Corporation
FNT EXPERT PAPER. // Data Center Business Value Dashboards AUTHOR. Data Center Infrastructure Management (DCIM) www.fntsoftware.
FNT EXPERT PAPER AUTHOR Oliver Lindner Head of Business Line DCIM FNT GmbH // Data Center Business Value Dashboards Data Center Infrastructure Management (DCIM) Energy efficiency is an important strategic
Storage Considerations for Database Archiving. Julie Lockner, Vice President Solix Technologies, Inc.
Storage Considerations for Database Archiving Julie Lockner, Vice President Solix Technologies, Inc. SNIA Legal Notice The material contained in this tutorial is copyrighted by the SNIA. Member companies
ENERGY EFFICIENT DATA CENTRES AND STORAGE. Peter James University of Bradford
ENERGY EFFICIENT DATA CENTRES AND STORAGE Peter James University of Bradford ABOUT US 1998 Co-founded world s first NGO on GreenIT EU Expert Advisors/Project Managers on ICT & Energy Efficiency; Environmental
SURVEY RESULTS: DATA CENTER ECONOMIZER USE
WHITE PAPER #41 SURVEY RESULTS: DATA CENTER ECONOMIZER USE EDITOR: Jessica Kaiser, Emerson Network Power CONTRIBUTORS: John Bean, Schneider Electric Tom Harvey, Emerson Network Power Michael Patterson,
Metric of the Month: The Service Desk Balanced Scorecard
INDUSTRY INSIDER 1 Metric of the Month: The Service Desk Balanced Scorecard By Jeff Rumburg Every month, in the Industry Insider, I highlight one key performance indicator (KPI) for the service desk or
DATA CENTER ASSESSMENT SERVICES
DATA CENTER ASSESSMENT SERVICES ig2 Group Inc. is a Data Center Science Company which provides solutions that can help organizations automatically optimize their Data Center performance, from assets to
Selecting an Industry-Standard Metric for Data Center Efficiency
Selecting an Industry-Standard Metric for Data Center Efficiency By Neil Rasmussen White Paper #157 Executive Summary The development of standards for the measurement and specification of data center efficiency
EU Code of Conduct for Data Centre Efficiency
EU Code of Conduct for Data Centre Efficiency A Green Practice Accredited by British Computer Society (BCS) EU Code of Conduct for Data Centre Efficiency Local Organizer Practices in Data Centre Industry
The Green Grid, Metrics and DCMM. Presented by: Jay Taylor
The Green Grid, Metrics and DCMM Presented by: Jay Taylor About The Green Grid A not-for-profit international consortium committed to advancing resource efficiency in business computing ecosystems and
The Mission Critical Data Center Understand Complexity Improve Performance
The Mission Critical Data Center Understand Complexity Improve Performance Communications Technology Forum Fall 2013 Department / Presenter / Date 1 Rittal IT Solutions The State of the Data Center Market
Benchmarking results from Indian data centers
Benchmarking results from Indian data centers Data Center Energy Efficiency 24 February, ACREX 2011, New Delhi Madhav Kamath. A Energy Efficiency Finance Lead USAID ECO-III Project Data Center Benchmarking
Georgian Bay General Hospital Strategic Energy Management Plan 2014
Georgian Bay General Hospital Strategic Energy Management Plan 2014 TABLE OF CONTENTS TABLE OF CONTENTS... 2 INTRODUCTION... 3 ENERGY MANAGEMENT VISION... 4 GUIDING PRINCIPLES FOR STRATEGIC ENERGY MANAGEMENT...
Energy Efficiency Monitoring in Data Centers: Case Study at International Hellenic University. George Koutitas, Prof. L. Tassiulas, Prof. I.
UTH and IHU (CI)-WP4 Energy Efficiency Monitoring in Data Centers: Case Study at International Hellenic University Plenary Meeting Gent, February-2012 George Koutitas, Prof. L. Tassiulas, Prof. I. Vlahavas
THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE
THE GREEN GRID DATA CENTER POWER EFFICIENCY METRICS: PUE AND DCiE 2007 The Green Grid. All rights reserved. No part of this publication may be used, reproduced, photocopied, transmitted, or stored in any
SIEM Optimization 101. ReliaQuest E-Book Fully Integrated and Optimized IT Security
SIEM Optimization 101 ReliaQuest E-Book Fully Integrated and Optimized IT Security Introduction SIEM solutions are effective security measures that mitigate security breaches and increase the awareness
KWE Basic Philosophy. As of March 2010, KWE is ISO14001 certified at 6 locations in Japan and 8 locations overseas
Green Initiatives KWE Basic Philosophy As a total logistics provider, we aim to contribute to the development of a global society while using resources wisely, promoting harmony with nature, and taking
ICT and the Green Data Centre
ICT and the Green Data Centre Scott McConnell Sales Manager c/o Tanya Duncan MD Interxion Ireland Green Data Centres Our Responsibility Data centre greenhouse gas emissions are projected to quadruple by
University of Melbourne Symposium on ICT Sustainability Dan Pointon 25 November 2008
University of Melbourne Symposium on ICT Sustainability Dan Pointon 25 November 2008 Contents Welcome and Introduction Chapter 1: Data centre energy recap Chapter 2: Co-generation Chapter 3: CTC case study
Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM)
Understanding Power Usage Effectiveness (PUE) & Data Center Infrastructure Management (DCIM) Salim Janbeh Physical Infrastructure Consultant [email protected] PANDUIT You Can t Manage What You Don t Measure:
ENERGY AUDITS (OR SURVEYS) & ENERGY MANAGEMENT PROGRAMS SECTION B
ENERGY AUDITS (OR SURVEYS) & ENERGY MANAGEMENT PROGRAMS SECTION B GOALS OF THE ENERGY AUDIT Clearly identify types and costs of energy use Understand how energy is being used--and possibly wasted Identify
FEAR Model - Review Cell Module Block
F.E.A.R. Returns: 5 Steps Toward Data Center Efficiency Today Objectives Benefits for ITS professionals Brief review of the FEAR data center Define data center efficiency Link efficiency to the FEAR data
DC Pro Assessment Tools. November 14, 2010
DC Pro Assessment Tools November 14, 2010 William Tschudi, PE Lawrence Berkeley National Laboratory [email protected] 510-495-2417 1 Slide 1 Assessment tools LBNL is developing tools to assist in performing
Data Center Infrastructure Management: ERP for the Data Center Manager
Data Center Infrastructure Management: ERP for the Data Center Manager 1 2 Topics What s DCIM & the ERP Analogy Why DCIM How DCIM Works How DCIM Helps 3 DCIM by Definition DCIM is a system that collects
PUE : A COMPREHENSIVE EXAMINATION OF THE METRIC
WHITE PAPER #49 PUE : A COMPREHENSIVE EXAMINATION OF THE METRIC EDITORS: Victor Avelar, Schneider Electric Dan Azevedo, Disney Alan French, Emerson Network Power PAGE 2 The Green Grid Association would
Guidance for Calculation of Efficiency (PUE) in Data Centers
Guidance for Calculation of Efficiency (PUE) in Data Centers White Paper 158 Revision 1 by Victor Avelar > Executive summary Before data center infrastructure efficiency can be benchmarked using PUE or
Case study: End-to-end data centre infrastructure management
Case study: End-to-end data centre infrastructure management Situation: A leading public sector organisation suspected that their air conditioning units were not cooling the data centre efficiently. Consequently,
This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits.
This 5 days training Course focuses on Best Practice Data Centre Design, Operation and Management leading to BICSI credits. DCD, DCOM, DCE DESIGN IMPLEMENTATION BEST PRACTICE OPERATION & MANAGEMENT DATA
Datacenter Efficiency
EXECUTIVE STRATEGY BRIEF Operating highly-efficient datacenters is imperative as more consumers and companies move to a cloud computing environment. With high energy costs and pressure to reduce carbon
Data Center Design Guide Overview and Status
Data Center Design Guide Overview and Status Jon Haas Data Center Design Guide Work Group Chair, Technical Committee Chair, and Board Member Intel Corporation George Navarro Data Center Design Guide Work
WATER USAGE EFFECTIVENESS (WUE ): A GREEN GRID DATA CENTER SUSTAINABILITY METRIC
WHITE PAPER #35 WATER USAGE EFFECTIVENESS (WUE ): A GREEN GRID DATA CENTER SUSTAINABILITY METRIC EDITOR: Michael Patterson, Intel CONTRIBUTORS: Dan Azevedo, Symantec Christian Belady, Microsoft Jack Pouchet,
San Francisco Chapter. Deborah Grove, Principal Grove-Associates
Deborah Grove, Principal Grove-Associates Why Green IT is Important 1. The energy consumed by servers in the US (and associated air -conditioning) is equivalent to the annual output of about 20 new coal-fired
How To Understand The Benefits Of Cloud Computing
Issue in Focus: Assessing the Cloud PLM Opportunity Evaluating Benefits, Requirements, and Considerations Tech-Clarity, Inc. 2012 Table of Contents Introducing the Issue... 3 The Cloud Meets PLM... 3 Evaluating
A Team Approach to Data Quality
A Team Approach to Data Quality A despicable data story! Presented by: Shane Downey & Sue Gardiner, Mater Health Services Outpatients: Accelerating Patient Flow and Improving Service Integration Change
General Recommendations for a Federal Data Center Energy Management Dashboard Display
General Recommendations for a Federal Data Center Energy Management Dashboard Display Prepared for the U.S. Department of Energy s Federal Energy Management Program Prepared By Lawrence Berkeley National
Boost your VDI Confidence with Monitoring and Load Testing
White Paper Boost your VDI Confidence with Monitoring and Load Testing How combining monitoring tools and load testing tools offers a complete solution for VDI performance assurance By Adam Carter, Product
How AWS Pricing Works
How AWS Pricing Works (Please consult http://aws.amazon.com/whitepapers/ for the latest version of this paper) Page 1 of 15 Table of Contents Table of Contents... 2 Abstract... 3 Introduction... 3 Fundamental
Introduction to IT Infrastructure Components and Their Operation. Balázs Kuti
Introduction to IT Infrastructure Components and Their Operation Balázs Kuti Agenda Challenges faced by enterprises today, scale of the IT plant Diversity of an IT plant Key Server Infrastructure Components
The EU Code of Conduct on Data Centres
The EU Code of Conduct on Data Centres Liam Newcombe BCS Data Centre Specialist Group Secretary EU CoC Data Centres Chair, Best Practice Working Group Development Becoming a Signatory Best Practices Use
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0
BCA-IDA Green Mark for Existing Data Centres Version EDC/1.0 To achieve GREEN MARK Award Pre-requisite Requirement All relevant pre-requisite requirements for the specific Green Mark Rating are to be complied
Page 1. White Paper, December 2012 Gerry Conway. How IT-CMF can increase the Energy Efficiency of Data Centres
Page 1 White Paper, December 2012 Gerry Conway How IT-CMF can increase the Energy Efficiency of Data Centres Abstract Data centres and their management are under increasing pressure; to increase the efficiency
Design issues For Net Zero Energy Buildings. Laura Aelenei 26 de Junho de 2012
Design issues For Net Zero Energy Buildings Laura Aelenei 26 de Junho de Summary 1.Context Building regulation/policy requirements Scientific advancements 2. Design issues for NZEB General ideas Solar
Oracle Maps Cloud Service Enterprise Hosting and Delivery Policies Effective Date: October 1, 2015 Version 1.0
Oracle Maps Cloud Service Enterprise Hosting and Delivery Policies Effective Date: October 1, 2015 Version 1.0 Unless otherwise stated, these Oracle Maps Cloud Service Enterprise Hosting and Delivery Policies
I-STUTE Project - WP2.3 Data Centre Cooling. Project Review Meeting 8, Loughborough University, 29 th June 2015
I-STUTE Project - WP2.3 Data Centre Cooling Project Review Meeting 8, Loughborough University, 29 th June 2015 Topics to be considered 1. Progress on project tasks 2. Development of data centre test facility
Measuring Energy Efficiency in a Data Center
The goals of the greening of the Data Center are to minimize energy consumption and reduce the emission of green house gases (carbon footprint) while maximizing IT performance. Energy efficiency metrics
Office of the Government Chief Information Officer. Green Data Centre Practices
Office of the Government Chief Information Officer Green Data Centre Practices Version : 2.0 April 2013 The Government of the Hong Kong Special Administrative Region The contents of this document remain
COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) CHARTERED BANK ADMINISTERED INTEREST RATES - PRIME BUSINESS*
COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) 2 Fixed Rates Variable Rates FIXED RATES OF THE PAST 25 YEARS AVERAGE RESIDENTIAL MORTGAGE LENDING RATE - 5 YEAR* (Per cent) Year Jan Feb Mar Apr May Jun
COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) CHARTERED BANK ADMINISTERED INTEREST RATES - PRIME BUSINESS*
COMPARISON OF FIXED & VARIABLE RATES (25 YEARS) 2 Fixed Rates Variable Rates FIXED RATES OF THE PAST 25 YEARS AVERAGE RESIDENTIAL MORTGAGE LENDING RATE - 5 YEAR* (Per cent) Year Jan Feb Mar Apr May Jun
THE EUROPEAN GREEN BUILDING PROGRAMME. Technical Module on Combined Heat and Power
THE EUROPEAN GREEN BUILDING PROGRAMME Technical Module on Combined Heat and Power Contents Foreword...1 1. Introduction...2 2. Inventory of the CHP system...3 3. Assessment of technical energy saving measures...5