Power Cable Accessories Catalogue & Price List
Foreword The U.K Electricity industry has changed beyond recognition over the last 20 years with the privatisation of the distribution sector, the consolidation of the old regional electricity companies, the emergence of independent network operator licenses and the proliferation of renewable energy projects as the country drives to create more green power. The power cable accessories product portfolio has also changed with the emergence of cold applied products to facilitate quicker installations, separable connectors which enable the easy connection and disconnection of cables from switchgear and more universally sized components that cover a wider range of cables. Jointing Technologies has prospered through this period of change to become the U.K. s leading power cable accessories distributor. The company s development has been achieved through its partnerships with market leading manufacturers, an in depth understanding of the power cables accessories market, a total coitment to stock and most importantly by putting the customer first. This focus on customers old and new remains integral to our business now and in the future. Adam Lloyd Managing Director
Contents Company Capability 2 Cable Glands 7 Cable Lugs & Connectors 27 Cable Cleats 47 Cable Ties & Marking Systems 63 LV Jointing 73 HV Jointing & Terminating 89 Separable Connectors 127 Tapes, Aerosols & Accessories 137 Cable Laying Products 149 Earthing, Lightning & Surge Protection 157 Cable Transits 175 Tools & Equipment 183 Trace & Underfloor Heating Systems 197 Cable Data 205 Product Index 217 Number Index 218 1
Company Capability SCOPE OF ACTIVITY Cable Accessories account for the least capital expenditure in the electricity distribution network when compared with switchgear, transformers and cable. They can however, prove to be the weakest part of it; as they require assembly on site. Therefore the correct product selection, technical advice and installation of power cable accessories are essential to ensure the safe running of the U.K. electricity network. Jointing Technologies are a specialist power cable accessories distributor with a national coverage operating in the electricity and associated markets at voltages up to and including 132KV. Jointing Technologies operates nationally across a 3 branch network... We hold in excess of 3 million of stock nationwide to ensure we negate the long lead times from manufacturers and fulfil customer demand quickly. The Jointing Technologies fleet of 6 vans is utilised to ensure we offer same and next day deliveries nationwide and provide a unrivalled service to our customers. We employ 5 Sales Engineers who are tasked with the development and support of our expanding customer base in addition to providing the right technical advice to aid with product selection. Please contact your nearest sales office for details of your local Sales Engineer. We work in partnership with market leading manufacturers to service the core electricity segments like the Distribution Network Operators (DNOs), Independent Network Service Operators (IDNOs), Power Contractors, Cable Pullers and HV Jointers to ensure that the right products are selected and best technical advice is offered relative to each application. We are also in a unique position based on our knowledge and insight at higher voltages to supply LV products to the general electrical market. The product portfolio consists of Cable Glands, Cable Lugs & Connectors, Cable Cleats, Cable Ties & Marking Systems, LV Jointing, HV Joints & Terminations, Separable Connectors, Tapes, Aerosols & Accessories, Cable Laying Products, Earthing, Lightning & Surge Protection, Cable Transits, Tooling & Equipment & Trace & Underfloor Heating Systems. Jointing Technologies operates a 24 hour call out service to ensure materials are available in an emergency to support our customers who work late or over the weekend. 2
Company Capability MARKET KNOWLEDGE Jointing Technologies knowledge of the U.K. electricity network puts us in a unique position to advise on the most suitable products and technologies based on each LV & HV application to ensure all customers find the safest and most reliable solutions. We have a unique understanding of the product profiles used by each customer segment and work closely with the market leading manufactures to advise what products have been approved for use on each respective DNO network. The U.K electricity distribution network is divided up by distribution network operator (DNO) and region as shown on the map below. Power Distribution Power Distribution The electricity network and the cables installed have changed significantly over the last 50 years; which has created challenges for power contractors when jointing or terminating cables. Therefore an in depth knowledge of cable construction is essential in identifying the correct cable accessory product. Jointing Technologies has the technical knowledge and expertise to advise the power contracting market on product selection and find a solution when OLD cables (Paper or Lead sheathed etc) are found buried and manufacturers don t have an off the shelf product available We have over 35 years experience working with the electricity market to provide power contracting solutions and offer product training, in conjunction with our market leading manufacturers, to our customer base. 3
Company Capability CASE STUDIES Greater Gabbard Wind Farm Greater Gabbard is one of the world s largest offshore wind farm with a 500MW capacity consisting of an onshore facility linked by three 45km cables to an offshore substation. This is supplied by 140 turbines located 23km off the Suffolk coast and the facility is expected to provide power to around 530,000 homes. SSE & RWE NPower Renewables are developing this project with Balfour Beatty who have been coissioned to undertake all the electrical installation work for the project covering voltages up to 132kV. Jointing Technologies have worked with Balfour Beatty design and installation teams to ensure that the right power cable accessories products were specified and supplied for the application in addition to providing on site training where necessary on the installation of these materials. Jointing Technologies scope of supply included Pfisterer Connex terminations, a comprehensive range of MV joints and terminations from Tyco Electronics and single and trefoil cleats from Prysmian. Jointing Technologies at the time of print have supplied over 1M of materials into Greater Gabbard project and have demonstrated our ability to work on one of the largest and most prestigious projects in the world. The Shard Shard London Bridge is a skyscraper constructed in south London which is the tallest building in the European Union. The tower will stand 1,017ft (310m) tall with 72 floors, plus 15 further radiator floors in the roof. The building has been designed with an irregular triangular shape from the base to the top. It will be clad entirely in glass and have an open-air observation deck on the top floor. The building will consist of Office space, a Spa, Residential Apartments and a Shangri-La Hotel. Jointing Technologies worked in conjunction with the main contractor to ensure the right products were selected for the application and supplied many products on this project including MV terminations from Tyco Electronics, Separable Connectors for 22kV cables from ABB in addition to a range of cast iron cleats for FP cables from Prysmian and cable support systems from Band-IT. This is one of the many prestigious projects in the U.K currently supplied by Jointing Technologies. Photo by Enkhtur DAVAASUREN 4
Company Capability CUSTOMER TESTIMONIALS For many years now Jointing Technologies has proven to be reliable throughout our many projects. Their excellent customer service, product knowledge and their wide range of competitively priced products make Jointing Technologies a company that we will rely on time and time again. Mike Watts Buyer Jointing Technologies has been a principal supplier of jointing accessories and components to SSE Contracting for many years; their reliable performance assists us in providing our clients with the service they expect from a leading UK mechanical & electrical contractor. Richard Hunt HV Manager We have used Jointing Technologies for many years and have found they offer a very professional service in the supply of power cable accessories. Their products are of high quality, from market leading brands. Their flexible approach and attention to detail has been greatly appreciated over the years. David Loftus Buyer - Power Division Jointing Technologies offer a range of power cable accessories nationally from market leading brands which is stocked in depth and supported technically to ensure that our medium and high voltage contracts are completed on time and within budget. This is why Jointing Technologies have become the supplier of choice for power cable accessories to Murphy Ltd for more than 10 years with materials used extensively across the U.K electricity network on contracts including EDF & CE Electric. Martin Goodger Group Procurement Manager 5
Company Capability MANUFACTURER S BRANDS Tyco Electronics, with an annual turnover of $12 billion, is a global provider of engineered components for thousands of consumer and industrial products; network solutions and systems for telecounications and energy markets, undersea telecounication systems, and speciality products. The Tyco Electronics Energy division is the leading manufacturer of power cable accessories that includes the internationally recognised Raychem brand, connectors and fittings, insulators and surge protectors, insulation enhancement and many more. Tyco Electronics has been at the forefront of the energy industry for the last 50 years and through continual innovation and product development is still the brand of choice today. 3M is a large multi national with a turnover of over $24 billion worldwide. They supply a wide variety of products for use in the home, in the health care sector and in industry. 3M has a strong reputation for quality and innovation and currently supplies products in almost every country in the world. The 3M Electrical Markets division boasts a broad portfolio of LV & MV products consisting of joints, terminations, tapes & accessories and are the market leader for coldshrink technology products worldwide. ABB is a Global Leader in Power and Automation technologies with 117,000 employees in over 100 Countries. ABB s business unit for Power Cable Accessories is located in Alingsås, Sweden and was started in 1888 by a Swedish cable manufacturer. The portfolio consists of a range of Kabeldon branded Joints, terminations, connectors, tools and accessories for power cables for voltages up to and including 420 kv. Cembre is one of the largest European manufacturers of electrical compression connectors and related installation tooling. Extensive know-how in the field, strong R&D activity and continuous innovation in manufacturing technologies and product specification, matched with expert and efficient international sales teams and sharp focus on customer needs, guarantee high-quality products that are reliable, durable and safe. Cembre Ltd is a key manufacturing unit within the Cembre group, with offices, laboratory and plant located near Birmingham, while an active sales force is available to customers throughout the UK and Ireland. A worldwide leader in the energy and telecounication cables industry with a strong position in high technology market segments, a global presence across 39 countries with 56 plants and 12,000 employees. Prysmian was formed by the Pirelli Group following its acquisition of BICC in 2000 and continues to invest and develop the market leading portfolio of BICON branded cable accessories which consists of Cable Glands, Cable Cleats, Cable Lugs in addition to LV/MV Joints and Accessories. Pfisterer are world renowned specialists for the design and manufacture of contact elements and distribution systems in low-, medium- and high-voltage networks. Our range of cable accessories, components and overhead line products offer solutions for virtually all applications in the area of medium-voltage and high-voltage engineering currently up to 300 kv for cable systems. Pfisterer have a comprehensive portfolio of products for virtually all terminating and jointing applications as well as worldwide training/installation and advisory services. Thomas & Betts is a global leader with over 100 years experience successfully supplying quality products by using innovative design and manufacturing techniques. With leading brands such as Furse, Emergi-Lite, Ty-Rap, Adaptaflex, Kopex and PMA. The Thomas & Betts product solutions portfolio includes earthing and lightning protection, emergency lighting and fire detection, cable management, electrical products and flexible conduit systems. Roxtec was founded in Sweden in 1990. Today it is the world s leading manufacturer of innovative cable and pipe transit systems, supplying many of the globe s biggest firms. It has a global turnover of 96m Euros and is active in 70 countries working in a diverse range sectors which include Marine, Oil and Gas, Telecoms, Construction, Power Generation, Transmission and Distribution. 6
Cable Glands CONTENTS Product Selection Data Tables 8 Stuffing Glands 9 Industrial Glands 11 Integral Earth Glands 16 Hazardous Area Glands 18 Accessories 25 7
Cable Glands PRODUCT SELECTOR CABLE GLAND & CLEAT SELECTOR FOR XLPE/SWA/PVC AND LSF 600/1000 VOLT POWER CABLES CABLE SPEC GLANDS CLEATS Conductor area 2 Number of cores BW Indoor CW Outdoor E1W E1WF Telcleats 385AA Hook Cleats 371AA Aluminium Claw Cleats 370BA Plastic LSF Cleats E Aluminium Cleats SW1/2B 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 2 20S 20SS 20SS 1-1 0-3 20S 20SS 20SS 1-1 0-4 20S 20S 20S 1-1 0-7 20S 20S 20S 2-2 1 2 12 20 20 20 3-3 2 3 19 25 25 25 4-4 3 4 27 25 25 25 5-5 4 5 37 32 32 32 6 5 6 5 6 48 32 32 32 6 5 6 5 6 2 20S 20S 20S 1-2 0 2 3 20S 20S 20S 1-2 1 2 4 20S 20S 20S 2-2 1 2 7 20 20 20 2-3 2 3 12 25 25 25 4-4 3 4 19 25 25 25 5-5 4 5 27 32 32 32 6 5 6 5 6 37 40 40 40 6 5 6 6 6 2 20S 20S 20S 2-2 1 2 3 20 20 20 2-2 1 2 4 20 20 20 3-3 2 3 2 20 20 20 3-3 2 3 3 20 20 20 3-3 2 3 4 20 20 20 4-4 3 4 2 25 25 25 4-4 3 4 3 25 25 25 4-4 3 4 4 25 25 25 4-5 4 5 2 25 25 25 4-4 3 4 3 25 25 25 4-5 4 5 4 25 25 25 5 5 6 4 6 2 25 25 25 4-4 4 4 3 32 32 32 5 5 6 5 6 4 32 32 32 5 5 6 5 6 2 32 32 32 5-5 5 5 3 32 32 32 5 5 6 5 6 4 32 32 32 6 5 6 5 6 2 32 32 32 5 5 6 5 6 3 32 32 32 6 5 6 5 6 4 40 40 40 6 5 6 6 6 2 32 32 32 6 5 6 5 6 3 40 40 40 6 6 7 6 7 4 40 40 40 7 6 7 7 7 2 40 40 40 6 6 7 6 7 3 40 40 40 7 6 7 7 7 4 50 50 50S 8 7 8 7 8 2 40 40 40 7 6 7 6 7 3 50 50 50S 7 7 8 7 8 4 50 50 50 8 8 9 8 9 2 50 50 50S 7 7 8 7 8 3 50 50 50S 8 8 9 8 9 4 50 50 50-9 10 9 10 2 50 50 50S 8 8 9 8 9 3 50 50 50 8 9 9 9 9 4 63 63 63S - 9 10 10 10 2 50 50 50 8 8 9 8 9 3 63 63 63S - 9 10 10 10 4 63 63 63-10 11 11 11 2 63 63 63S - 9 10 9 10 3 63 63 63-10 11 11 11 4 75 75 75S - 11 12 12 12 2 63 63 63-10 11 10 11 3 75 75 75S - 11 12 12 12 4 75 75 75-12 13 14 13 Gland size recoendations only apply to Prysmian Glands and Cleats - as stocked by Jointing Technologies 8
Cable Glands PRODUCT SELECTOR/STUFFING GLANDS SINGLE CORE ARMOURED CABLE RECOMMENDATIONS XLPE/AWA/PVC 600/1000 VOLT COPPER CONDUCTORS Product Aluminium Gland Gacw Brass Stuffing Gland A1/A2 Copper Conductor 2 50 70 95 120 150 185 240 300 400 500 630 800 1000 25 25 25 25 32 32 40 40 50S 50 50 63 63 32 32 40 40 40 40 50S 50 50 63S 63S 75S 75 SINGLE CORE UNARMOURED CABLE RECOMMENDATIONS XLPE/PVC 600/1000 VOLT COPPER CONDUCTORS Product Brass Stuffing Gland A1/A2 Copper Conductor 2 50 70 95 120 150 185 240 300 400 500 630 800 1000 25 25 25 32 32 32 40 40 50S 50 50 63S 63 nylon STUFFING GLANDS Indoor/outdoor for unarmoured cables Designed to provide sealing and retention for use with unarmoured cables Suitable for indoor & outdoor use Manufactured from Polyamide PA6.6 Sealing ring manufactured from Neoprene 50 sh A Available in black as standard and light grey and dark grey on request All prices are per single gland Diameter Range A2 Nylon 16 16 5-10 2.05 A2 Nylon 20 20 7-13 2.42 A2 Nylon 25 25 10-17 3.26 A2 Nylon 32 32 13-21 5.99 A2 Nylon 40 40 19-28 16.91 A2 Nylon 50 50 27-35 25.41 A2 Nylon 63 63 34-45 31.24 Temperature range -20 C to + 90 C Flaability rating UL 94 - V2 IP68 rated B PAGE 9 - NOT DRAWN AT 100% (THIS IS GLAND 70%) DETAILS Ø A L C P P Fixing Hole Diameter Diameter A Min-Max B Spanner C PAGE 11 L Min-Max 16 M16 x 1.5 16.5 5-10 19 8 22-27 20 M20 x 1.5 20.5 7-13 25 9 24-30 25 M25 x 1.5 25.5 10-17 30 10 28-39 32 M32 x 1.5 32.5 13-21 36 10 33-44 40 M40 x 1.5 40.5 19-28 46 10 36-45 50 M50 x 1.5 50.5 27-35 55 12 PAGE 13 43-52 63 M63 x 1.5 63.5 34-45 66 12 45-55 PAGE 14 9
r Gland C Cable Glands STUFFING GLANDS A2 - BRASS GLANDS F Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series D verall ia. B Max E Gland Dimensions Braid Approx. Hexagon EN 50262 Wire Length Dia. C BS 6121:Pt D A/C A/F 1:1989 E F Gland rated to IP66 with use of suitable sealing washer or thread 15.8 20.8 0.2 / 0.3 sealant 67 at gland 34.0 interface30.5 0.2 / 0.3 64 34.0 30.5 Service temperature -20 C to +90 C 27.2 0.2 / 0.45 65 42.2 37.6 33.5 CuZn39Pb3 extruded brass alloy 0.3 / 0.45 77 53.6 47.3 used for guaranteed strength and 39.9 0.3 / 0.45 77 performance 61.5 56.4 52.6 0.3 / 0.45 84 77.2 70.1 65.3 0.3 / 0.45 90 87.4 80.0 78.0 0.3 / 0.45 96 109.2 98.8 88.0 0.3 / 0.45 108 126.0 115.0 Indoor/outdoor for unarmoured cables Brass indoor and outdoor cable gland and accessories Application For circular, unarmoured plastic or rubber sheathed cables Suitable for most climatic conditions, weatherproof and Features waterproof & Benefits Kit comprises: A1/A2 gland, brass locknut and shroud Available in LSF version All prices are per single gland kit > Indoor/Outdoor for Unarmoured Cable > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland - Brass locknut - PVC shroud > 2 per kit size up to and including 25 Standard LSF Standard LSF Technical Data > EN 50262 > BS6121:Pt 1:1989 > Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface > Service temperature -20 C to +90 C > CuZn39Pb3 extruded brass alloy used for guaranteed strength and performance A1/A2 20SS A1/A2 20Ss Lsf 20SS 4.70 5.35 A1/A2 20S A1/A2 20S Lsf 20S 5.30 5.35 A1/A2 20 A1/A2 20 Lsf 20 5.50 6.05 A1/A2 25 A1/A2 25 Lsf 25 8.25 9.85 A1/A2 32 A1/A2 32 Lsf 32 13.75 14.85 A1/A2 40 A1/A2 40 Lsf 40 23.10 25.85 A1/A2 50S A1/A2 50S Lsf 50S 29.70 33.00 A1/A2 50 A1/A2 50 Lsf 50 31.35 38.50 A1/A2 63S A1/A2 63S Lsf 63S 48.40 57.20 A1/A2 63 A1/A2 63 Lsf 63 52.80 59.40 A1/A2 75S A1/A2 75S Lsf 75S 82.50 88.00 A1/A2 75 A1/A2 75 Lsf 75 88.00 97.90 Ref: A1A2/03/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk GLAND DETAILS A B E D C F Cable Dimensions Overall Diameter A Min Max B Entry Thread Length C Please refer to product selection table on page 8 to size product relative to cable type Gland Dimensions Approx. Length from Shoulder D Across Flats E Hexagon Across Corners F 20SS 3.5 8.5 M20 1.5 10 20 22.0 24.9 20S 8.0 11.5 M20 1.5 10 22 22.0 24.9 20 11.0 13.5 M20 1.5 10 22 24.0 26.8 25 13.0 19.5 M25 1.5 10 25 30.5 34.0 32 19.0 25.5 M32 1.5 10 25 42.4 48.0 40 25.0 32.0 M40 1.5 15 33 47.2 53.6 50S 31.5 37.0 M50 1.5 15 30 55.0 60.0 50 36.5 43.0 M50 1.5 15 30 56.4 61.5 63S 42.5 50.0 M63 1.5 15 34 70.1 77.2 63 49.5 55.0 M63 1.5 15 32 75.0 83.0 75S 54.5 61.0 M75 1.5 15 32 80.0 87.4 75 60.5 67.0 M75 1.5 15 40 85.0 95.0 9PH, UK 10
BARR-X EEx d IIC Brass Barrier Gland Cable Glands C INDUSTRIAL GLANDS BW GLAND KIT - INDOOR USE Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series B A F Indoor type for SWA cable Brass indoor gland and accessories Application > Indoor/Outdoor for Unarmoured Cable For galvanized-steel single-wire armour plastic or rubber sheathed cables For use in dry, dust free, situations Features & Benefits > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof Provides mechanical cable retention and electrical continuity via armour locking mechanism > Kit comprises: - A1/A2 Gland - Brass locknut Kit comprises: BW gland, brass earth tag, zinc plated steel locknut and shroud - PVC shroud > 2 per kit size up to and including 25 Available Gland References in LSF version & Thread s Cable Dimensions Gland Dimensions Basic All prices Metric are per single gland kitnpt Max. Max. No. of Inner Sheath Overall Braid Approx. Hexagon EN 50262 Dia. Technical Over Data Conductors > EN 50262 Dia. A Dia. B Wire Length Design Thread Design Thread > BS6121:Pt 1:1989 Conductors Dia. C D A/C A/F > Gland rated to IP66 with use of suitable sealing washer or thread sealant No. * No. BS 6121:Pt 1 :1989 E F Standard LSF Standard at gland interface MinLSF Max Min Max > Service temperature -20 C to +90 C Bw20s Bw20s Lsf 20S 2.90 CuZn39Pb3 extruded brass alloy > CuZn39Pb3 extruded brass alloy 4.00 used for guaranteed strength and performance Bw20 Bw20 Lsf 20 3.45 4.95 used for guaranteed strength and 20S 424TX52 M20 1.5 424TX02 ½ - 14 NPT 11.0 30 11.5 8.0 15.8 performance 0.2 / 0.3 67 34.0 30.5 Bw25 Bw25 Lsf 25 5.40 7.65 20 424TX53 M20 1.5 424TX03 ½ - 14 NPT 11.0 30 12.5 11.7 20.8 0.2 / 0.3 64 34.0 30.5 Bw32 Bw32 Lsf 32 8.60 10.95 Service temperature range -20 C to 25 Bw40 424TX55 M25 Bw40 1.5 Lsf 424TX05 ¾ - 14 NPT 4016.0 17.40 42 11.5 24.7518.0 17.0 27.2 +90 C0.2 / 0.45 65 42.2 37.6 32 424TX56 M32 1.5 424TX06 1-11½ NPT 22.1 60 17.0 25.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3 Gland Details Bw50 Bw50 Lsf 50 31.20 35.75 Bw63 Bw63 Lsf 63 51.65 59.40 Bw75s Bw75s Lsf 75S 77.85 109.95 Bw75 Bw75 Lsf 75 77.85 109.95 40 424TX57 M40 1.5 424TX07 1¼ - 11½ NPT 28.2 100 24.0 31.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4 50 424TX59 M50 1.5 424TX09 2-11½ NPT 37.1 200 30.0 41.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1 63 424TX61 M63 1.5 424TX11 2½ - 8 NPT 48.4 400 40.0 54.0 46.5 65.3 0.3 / 0.45 90 87.4 80.0 75 424TX63 M75 1.5 424TX13 3-8 NPT 58.6 400 53.0 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 85 424TX64 M85 2 424TX14 Ref: A1A2/03/07 3-8 NPT Systems Limited, Coercial 65.8 Road, Wrexham 8345, Fax: +44 400 Wrexham, LL13 9HP, 60.0 74.0 68.0 88.0 0.3 / 0.45 108 GLAND 126.0 DETAILS 115.0 Prysmian Cables & Components Unit, Oak Industrial Estate, UK Enquiries, Tel +44 (0) 845 767 (0) 23 8029 5465 www.prysmian.co.uk D E * 1.5 Pitch threads are supplied 15 long, 2 pitch threads are supplied 20 long NPT thread lengths comply with new UL2225 requirements A F E D H G Cable Dimensions Under Armour Diameter A Max D Entry Thread Length E Gland Dimensions Approx. Length from Shoulder F Across Flats G Hexagon Across Corners H 20S 11.6 M20 1.5 10 24 22.0 24.9 20 13.9 M20 1.5 10 25 27.0 30.5 25 19.9 M25 1.5 10 26 37.6 42.2 32 26.2 M32 1.5 10 28 47.3 53.6 40 32.1 M40 1.5 15 25 50.0 57.0 50 44.0 M50 1.5 15 36 70.1 77.2 63 55.9 M63 1.5 15 30 80.0 87.4 75S 61.9 M75 1.5 15 40 85.0 95.0 75 67.9 M75 1.5 15 40 98.8 109.2 Please refer to product selection table on page 8 to size product relative to cable type Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 11 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
r Gland C Cable Glands INDUSTRIAL GLANDS CW GLAND KIT - OUTDOOR USE F Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series D Gland Dimensions verall Braid EN 50262 Approx. Hexagon ia. B Wire Length Dia. C D A/C A/F BS 6121:Pt 1:1989 E F Max Gland rated to IP66 with use of suitable sealing washer or thread 15.8 0.2 / 0.3 sealant 67 at gland 34.0 interface30.5 20.8 0.2 / 0.3 64 34.0 30.5 Service temperature range -20 C to 27.2 0.2 / 0.45 +90 C 65 42.2 37.6 33.5 0.3 / 0.45 77 53.6 47.3 CuZn39Pb3 extruded brass alloy 39.9 0.3 / 0.45 used for 77guaranteed 61.5 strength 56.4 and 52.6 0.3 / 0.45 performance 84 77.2 70.1 65.3 0.3 / 0.45 90 87.4 80.0 78.0 0.3 / 0.45 96 109.2 98.8 88.0 0.3 / 0.45 108 126.0 115.0 E Indoor/outdoor type for SWA cable Brass indoor and outdoor cable gland & accessories For circular, galvanized-steel single-wire-armour plastic or rubber sheathed cables Outer seal grips sheath of cable For use in most climatic conditions, weatherproof and waterproof - Brass locknut Three part amour lock with separate armour locking ring, ideal for checking electrical continuity Kit comprises: CW gland, brass earth tag, zinc plated steel locknut and shroud Available in LSF version All prices are per single gland kit Application Features & Benefits Technical Data > EN 50262 > Indoor/Outdoor for Unarmoured Cable > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland - PVC shroud > 2 per kit size up to and including 25 > BS6121:Pt 1:1989 > Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface > Service temperature -20 C to +90 C Standard LSF Standard LSF > CuZn39Pb3 extruded brass alloy used for guaranteed strength and cw20ss cw20ss lsf 20ss performance 6.25 6.95 cw20s cw20s lsf 20s 5.65 6.95 cw20 cw20 lsf 20 6.25 8.75 cw25 cw25 lsf 25 8.50 12.45 cw32 cw32 lsf 32 16.30 18.50 cw40 cw40 lsf 40 28.15 34.00 cw50s cw50s lsf 50s 44.00 56.00 cw50 cw50 lsf 50 44.00 56.00 cw63 cw63 lsf 63 71.00 96.00 cw75 cw75 lsf 75 Ref: A1A2/03/07 118.00 142.00 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 cw85 cw85 lsf 85 www.prysmian.co.uk 249.00 335.00 GLAND DETAILS G F E D H Under Armour Diameter Max Cable Dimensions Overall Diameter Min Max Armour Wire Diameter D Entry Thread Length E Gland Dimensions Approx. Length from Shoulder F Across Flats G Hexagon Across Corners H 20SS 8.6 8.0 13.2 0.9 M20 1.5 10 44 23.4 26.7 20S 11.6 8.0 15.8 0.9 M20 1.5 10 46 25.7 29.2 20 13.9 11.7 20.8 0.9/1.25 M20 1.5 10 46 30.5 34.0 25 19.9 17.0 27.2 1.25/1.6 M25 1.5 10 51 37.6 42.2 32 26.2 23.5 33.5 1.6/2.0 M32 1.5 10 56 47.3 53.6 40 32.1 29.0 39.9 1.6/2.0 M40 1.5 15 59 56.4 61.5 50S 38.1 38.0 46.2 2.0/2.5 M50 1.5 15 64 65.5 72.1 50 44.0 39.5 52.6 2.0/2.5 M50 1.5 15 64 70.1 77.2 63 55.9 51.3 65.3 2.5 M63 1.5 15 67 80.0 87.4 75 67.9 62.5 78.0 2.5 M75 1.5 15 76 98.8 109.2 85 74.0 68.0 88.0 3.15 M85 2 20 110 115.0 126.0 Please refer to product selection table on page 8 to size product relative to cable type 9PH, UK 12
BARR-X EEx d IIC Brass Barrier Gland Cable Glands C INDUSTRIAL GLANDS CW ALUMINIUM GLAND KIT Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series B A F Indoor/outdoor type for aluminium wire armoured cable Aluminium indoor and outdoor cable gland & accessories Application > Indoor/Outdoor for Unarmoured Cable For circular, aluminium single-wire-armour plastic or rubber sheathed cables Outer seal grips sheath of cable Features & Benefits > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof For use in most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland - Brass locknut Three part amour lock with separate armour locking ring, ideal for checking electrical continuity - PVC shroud > 2 per kit size up to and including 25 Kit Gland comprises: References CW aluminium & Threadgland, saluminium earth tag, aluminium locknut Cable and Dimensions shroud Gland Dimensions Basic Available Metric in LSF version NPT Max. Max. No. of Inner Sheath Overall Braid Approx. Hexagon EN 50262 Dia. Technical Over Data Conductors > EN 50262 All prices are per single gland kit Dia. A Dia. B Wire Length Design Thread Design Thread > BS6121:Pt 1:1989 Conductors Dia. C D A/C A/F > Gland rated to IP66 with use of suitable sealing washer or thread sealant No. * No. BS 6121:Pt 1:1989 E F at gland interface Min Max Min Max > Service temperature -20 C to +90 C Gland rated to IP66 with use of Standard LSF Standard > CuZn39Pb3 extruded brass alloy LSF used for guaranteed strength and performance suitable sealing washer or thread 20S GACW20S 424TX52 M20 GACW20SLSF 1.5 424TX02 ½ - 14 NPT 20S 11.0 20.48 30 21.0011.5 8.0 15.8 sealant 0.2 at / gland 0.3 interface 67 34.0 30.5 GACW20 GACW20LSF 20 20.48 24.15 20 424TX53 M20 1.5 424TX03 ½ - 14 NPT 11.0 30 12.5 11.7 20.8 0.2 / 0.3 64 34.0 30.5 GACW25 GACW25LSF 25 20.48 25.20 Service temperature range -20 C to 25 424TX55 M25 1.5 424TX05 ¾ - 14 NPT 16.0 42 11.5 18.0 17.0 27.2 +90 C0.2 / 0.45 65 42.2 37.6 GACW32 GACW32LSF 32 25.20 33.60 32 GACW40 424TX56 M32 GACW40LSF 1.5 424TX06 1-11½ NPT 4022.1 32.03 60 17.0 39.9025.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3 6082 extruded aluminium alloy 40 GACW50S 424TX57 M40 GACW50SLSF 1.5 424TX07 1¼ - 11½ NPT 50S 28.2 45.15 100 24.0 57.7531.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4 used for guaranteed strength and 50 GACW50 424TX59 M50 GACW50LSF 1.5 424TX09 2-11½ NPT 5037.1 45.68 200 30.0 60.9041.5 36.0 52.6 performance 0.3 / 0.45 84 77.2 70.1 GACW63 GACW63LSF 63 71.93 88.20 63 424TX61 M63 1.5 424TX11 2½ - 8 NPT 48.4 400 40.0 54.0 46.5 65.3 0.3 / 0.45 90 87.4 80.0 Gland Details GACW75 GACW75LSF 75 147.00 168.00 75 424TX63 M75 1.5 424TX13 3-8 NPT Ref: A1A2/03/07 58.6 Systems Limited, 400 Road, Wrexham 53.0 Wrexham, LL13 9HP, 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 Prysmian Cables & Components Unit, Oak Industrial Estate, UK 85 424TX64 M85 2 424TX14 3-8 NPT Coercial 65.8 8345, Fax: +44 www.prysmian.co.uk 400 60.0 74.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 Enquiries, Tel +44 (0) 845 767 (0) 23 8029 5465 GLAND DETAILS D E * 1.5 Pitch threads are supplied 15 long, 2 pitch threads are supplied 20 long NPT thread lengths comply with new UL2225 requirements F E D H G Under Armour Diameter Max Cable Dimensions Overall Diameter Min Max Armour Wire Diameter D Entry Thread Length E Gland Dimensions Approx. Length from Shoulder F Across Flats G Hexagon Across Corners H 20 13.9 11.7 20.8 0.9/1.25 M20 1.5 10 46 30.5 34.0 25 19.9 17.0 27.2 1.25/1.6 M25 1.5 10 51 37.6 42.2 32 26.2 23.5 33.5 1.6/2.0 M32 1.5 10 56 47.3 53.6 40 32.1 29.0 39.9 1.6/2.0 M40 1.5 15 59 56.4 61.5 50S 38.1 38.0 46.2 2.0/2.5 M50 1.5 15 64 65.5 72.1 50 44.0 39.5 52.6 2.0/2.5 M50 1.5 15 64 70.1 77.2 63 55.9 51.3 65.3 2.5 M63 1.5 15 67 80.0 87.4 75 67.9 62.5 78.0 2.5 M75 1.5 15 76 98.8 109.2 Please refer to product selection table on page 9 to size product relative to cable type Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 13 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
r Gland C Cable Glands INDUSTRIAL GLANDS CX GLAND - WIRE BRAIDED CABLE F Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series D Gland Dimensions verall Braid Approx. Hexagon EN 50262 ia. B Wire Length Dia. C D A/C A/F BS 6121:Pt 1:1989 E F Max Gland rated to IP66 with use of suitable sealing washer or thread 15.8 0.2 / 0.3 sealant 67 at gland 34.0 interface30.5 20.8 0.2 / 0.3 64 34.0 30.5 Service temperature range -20 C to 27.2 0.2 / 0.45 +90 C 65 42.2 37.6 33.5 0.3 / 0.45 77 53.6 47.3 CuZn39Pb3 extruded brass alloy 39.9 0.3 / 0.45 77 61.5 56.4 used for guaranteed strength and 52.6 0.3 / 0.45 performance 84 77.2 70.1 65.3 0.3 / 0.45 90 87.4 80.0 78.0 0.3 / 0.45 96 109.2 98.8 GLAND DETAILS 88.0 0.3 / 0.45 108 126.0 115.0 E Indoor/outdoor type for wire braided cable Brass indoor and outdoor cable gland & accessories For circular, wire braid armour plastic or rubber sheathed cables Outer seal grips sheath of cable For use in most climatic conditions, weatherproof and waterproof - Brass locknut Three part amour lock with separate armour locking ring, ideal for checking electrical continuity Kit comprises: CX gland, brass earth tag, brass locknut and shroud All prices are per single gland kit Ref: A1A2/03/07 Application Features & Benefits Technical Data > EN 50262 > Indoor/Outdoor for Unarmoured Cable > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland - PVC shroud > 2 per kit size up to and including 25 > BS6121:Pt 1:1989 > Gland rated to IP66 with use of suitable sealing washer or thread sealant CX20SS at gland interface > Service temperature 20SS CuZn39Pb3 extruded -20 C +90 C 9.95 to strength and CX20S > 20S brass alloy used for guaranteed 9.95 performance Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk CX20 20 12.75 CX25 25 18.00 CX32 32 25.00 CX40 40 47.00 CX50 50 70.00 CX63 63 120.00 CX75 75 180.00 A G F E D H Under Armour Diameter Max Cable Dimensions Overall Diameter Min Max Armour Wire Diameter D Entry Thread Length E Gland Dimensions Approx. Length from Shoulder F Across Flats G Hexagon Across Corners H 20SS 8.6 8.0 13.2 0.2/0.3 M20 1.5 10 44 23.4 26.7 20S 11.6 8.0 15.8 0.2/0.3 M20 1.5 10 46 25.7 29.2 20 13.9 11.7 20.8 0.2/0.3 M20 1.5 10 46 30.5 34.0 25 19.9 17.0 27.2 0.2/0.45 M25 1.5 10 51 37.6 42.2 32 26.2 23.5 33.5 0.3/0.45 M32 1.5 10 56 47.3 53.6 40 32.1 29.0 39.9 0.3/0.45 M40 1.5 15 59 56.4 61.5 50 44.0 39.5 52.6 0.3/0.45 M50 1.5 15 64 70.1 77.2 63 55.9 51.3 65.3 0.3/0.45 M63 1.5 15 67 80.0 87.4 75 67.9 62.5 78.0 0.3/0.45 M75 1.5 15 76 98.8 109.2 9PH, UK 14
BARR-X EEx d IIC Brass Barrier Gland Cable Glands C INDUSTRIAL GLANDS E1W BRASS GLAND KIT Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series B A F Brass indoor and outdoor cable gland & accessories Application > Indoor/Outdoor for Unarmoured Cable For circular plastic or rubber sheathed cables with extruded bedding Outer seal grips sheath of cable Features & Benefits > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof Inner seal grips bedding layer of cable > Kit comprises: - A1/A2 Gland - Brass locknut For use in most climatic conditions, weatherproof and waterproof - PVC shroud > 2 per kit size up to and including 25 Three Glandpart References armour lock & Thread with separate s armour locking ring, ideal for checking Cable electrical Dimensions Gland Dimensions continuity Metric NPT Max. Max. No. of Inner Sheath Overall Braid Approx. Hexagon Kit comprises: E1W gland, brass earth tag, zinc plated Dia. steel Over locknut Conductors and shroud EN 50262 Technical Data > EN 50262 Dia. A Dia. B Wire Length Design Thread Design Thread > BS6121:Pt 1:1989 Conductors Dia. C D A/C A/F No. Available in LSF * version > Gland rated to IP66 with use of suitable sealing washer or thread sealant No. BS 6121:Pt 1:1989 E F at gland interface Min Max Min Max > Service temperature -20 C to +90 C All prices are per single gland kit Inner and outer seal rated to IP66 Gland Details Basic Indoor/outdoor weatherproof for SWA cables > CuZn39Pb3 extruded brass alloy used for guaranteed strength and performance 20S 424TX52 M20 1.5 424TX02 ½ - 14 NPT 11.0 30 11.5 8.0 15.8 Gland 0.2 rated / 0.3 to IP66 67 with use 34.0 of 30.5 20 Standard 424TX53 M20 LSF 1.5 424TX03 ½ - 14 NPT 11.0 Standard 30 LSF suitable sealing washer or thread 12.5 11.7 20.8 0.2 / 0.3 64 34.0 30.5 E1W20SS E1WLSF20SS 20SS 10.50 17.50 sealant at gland interface 25 424TX55 M25 1.5 424TX05 ¾ - 14 NPT 16.0 42 11.5 18.0 17.0 27.2 0.2 / 0.45 65 42.2 37.6 E1W20S E1WLSF20S 20S 10.50 16.95 Service temperature range -20 C to 32 424TX56 M32 1.5 424TX06 1-11½ NPT 22.1 17.0 25.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3 E1W20 E1WLSF20 20 12.60 21.00 +90 C 40 E1W25 424TX57 M40 E1WLSF25 1.5 424TX07 1¼ - 11½ NPT 2528.2 18.90 100 24.0 29.0031.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4 50 E1W32 424TX59 M50 E1WLSF32 1.5 424TX09 2-11½ NPT 32 CuZn39Pb3 extruded brass alloy 37.1 26.00 200 30.0 39.0041.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1 used for guaranteed strength and 63 E1W40 424TX61 M63 E1WLSF40 1.5 424TX11 2½ - 8 NPT 4048.4 47.60 400 40.0 71.3054.0 46.5 65.3 0.3 / 0.45 90 87.4 80.0 performance E1W50S E1WLSF50S 50S 67.00 104.00 75 424TX63 M75 1.5 424TX13 3-8 NPT 58.6 400 53.0 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 E1W50 E1WLSF50 Ref: A1A2/03/07 Prysmian Cables 50 & Systems Limited, Components Unit, 69.00 Oak Road, Wrexham Industrial Estate, Wrexham, 117.00 LL13 9HP, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 85 424TX64 M85 2 424TX14 3-8 NPT 65.8 400 60.0 74.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 www.prysmian.co.uk E1W63S E1WLSF63S 63S 117.00 158.00 E1W63 E1WLSF63 63 119.00 175.00 E1W75S E1WLSF75S 75S 148.80 237.00 * 1.5 Pitch threads are supplied 15 long, 2 pitch threads are supplied 20 long E1W75 E1WLSF75 75 197.00 280.00 NPT thread Discount lengths on application comply with new UL2225 requirements D E GLAND DETAILS G F E D H Under Armour Diameter Max Cable Dimensions Overall Diameter Min Max Min Max Armour Wire Diameter D Entry Thread Length E Gland Dimensions Approx. Length from Shoulder F Across Flats G Hexagon Across Corners H 20SS 6.3 8.6 8.0 13.2 0.9 M20 1.5 15 44 23.4 26.7 20S 8.7 11.6 8.0 15.8 0.9/1.25 M20 1.5 15 46 25.7 29.2 20 11.7 13.9 11.7 20.8 0.9/1.25 M20 1.5 15 46 30.5 34.0 25 13.0 19.9 17.0 27.2 1.25/1.6 M25 1.5 15 51 37.6 42.2 32 20.0 26.2 23.5 33.5 1.6/2.0 M32 1.5 15 56 47.3 53.6 40 26.3 32.1 29.0 39.9 1.6/2.0 M40 1.5 15 59 56.4 61.5 50S 32.2 38.1 38.0 46.2 2.0/2.5 M50 1.5 15 64 60.0 66.0 50 38.2 44.0 39.5 52.6 2.0/2.5 M50 1.5 15 64 70.1 77.2 63S 44.1 50.0 50.0 58.9 2.5 M63 1.5 15 67 75.0 83.0 63 50.1 55.9 51.3 65.3 2.5 M63 1.5 15 67 80.0 87.4 75S 56.0 61.9 62.0 71.6 2.5 M75 1.5 15 76 90.2 99.1 75 62.0 67.9 62.5 78.0 2.5 M75 1.5 15 76 98.8 109.2 Please refer to product selection table on page 8 to size product relative to cable type Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 15 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
r Gland C Cable Glands INTEGRAL EARTH GLANDS CW BRASS GLAND WITH INTEGRAL EARTH F Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series D verall ia. B Max E Gland Dimensions Braid Approx. Hexagon EN 50262 Wire Length Dia. C D A/C A/F Gland rated to IP66 E with use F of suitable sealing washer or thread sealant at gland interface 15.8 0.2 / 0.3 Service 67 temperature 34.0range 30.5-20 C to 7 20.8 0.2 / 0.3 +90 C 64 34.0 30.5 27.2 0.2 / 0.45 Integral 65 earth connection 42.2 37.6 complies 0 33.5 0.3 / 0.45 with GDCD 77 190 Category 53.6 47.3 A (43.3kA 5 39.9 0.3 / 0.45 for 1 second) 77 61.5 56.4 0 52.6 0.3 / 0.45 84 77.2 70.1 5 65.3 0.3 / 0.45 90 87.4 80.0 0 78.0 0.3 / 0.45 96 109.2 98.8 GLAND DETAILS 0 88.0 0.3 / 0.45 108 126.0 115.0 For steel wire armour cable Brass indoor and outdoor cable gland with earth bonding connection Application > Indoor/Outdoor for Unarmoured Cable Suitable for circular galvanised steel single wire armoured, plastic or rubber sheathed cables Outer seal grips sheath of cable Features & Benefits For use in most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland - Brass locknut Three part armour lock with separate armour locking ring - PVC shroud > 2 per kit size up to and including 25 Kit comprises CW brass gland with integral earth & locknut All prices are per single gland kit Technical Data > EN 50262 For use in high fault current applications Ref: A1A2/03/07 > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > BS6121:Pt 1:1989 > Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface > Service temperature -20 C to +90 C > CuZn39Pb3 extruded brass alloy used for guaranteed strength and performance CWCIEL20S 20S 25.00 CWCIEL20 20 34.00 CWCIEL25 25 40.50 CWCIEL32 32 58.50 CWCIEL40 40 77.00 CWCIEL50 50 95.00 CWCIEL63 63 136.00 CWCIEL75 75 205.00 CWCIEL85 85 430.00 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk H D G F E Under Armour Diameter Max Cable Dimensions accoodated Overall Diameter Min Max Min Max Armour Wire Diameter D Entry Thread Length E Gland Dimensions Approx. Length from Shoulder F Across Flats G Hexagon Across Corners H 20S - 11.6 8.0 15.8 0.9/1.25 M20 1.5 10 56 30.5 34.0 20-13.9 11.7 20.8 0.9/1.25 M20 1.5 10 56 30.5 34.0 25-19.9 17.0 27.2 1.25/1.6 M25 1.5 10 63 42.4 48.0 32-26.2 23.5 33.5 1.6/2.0 M32 1.5 10 73 56.4 61.5 40-32.1 29.0 39.9 1.6/2.0 M40 1.5 15 77 56.4 61.5 50-44.0 39.5 52.6 2.0/2.5 M50 1.5 15 84 70.1 77.2 63-55.9 51.3 65.3 2.5 M63 1.5 15 84 90.1 100.0 75-67.9 62.5 78.0 2.5 M75 1.5 15 94 106.2 117.0 85-74.0 68.0 88.0 3.15 M85 2 20 125 115.0 126.0 3 9PH, UK 16
BARR-X EEx d IIC Brass Barrier Gland Cable Glands INTEGRAL EARTH GLANDS C Industrial Gland Kits CW ALUMINIUM GLAND WITH INTEGRAL EARTH A1/A2 Brass Gland Kit KM409 Series B A F For aluminium wire armour cable Aluminium indoor and outdoor cable gland with earth bonding connection Application > Indoor/Outdoor for Unarmoured Cable Suitable for circular aluminium single wire armoured, plastic or rubber sheathed cables Outer seal grips sheath of cable Features & Benefits > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof For use in most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland - Brass locknut Three part armour lock with separate armour locking ring - PVC shroud > 2 per kit size up to and including 25 Kit Gland comprises References CW aluminium & Threadgland swith integral earth & locknut Cable Dimensions Gland Dimensions Basic All prices Metric are per single gland kitnpt Max. Max. No. of Inner Sheath Overall Braid Approx. Hexagon EN 50262 Dia. Technical Over Data Conductors > EN 50262 For use in high fault current applications Dia. A Dia. B Wire Length Design Thread Design Thread > BS6121:Pt 1:1989 Conductors Dia. C D A/C A/F > Gland rated to IP66 with use of suitable sealing washer or thread sealant No. * No. Gland rated to IP66 with use of E F at gland interface Min Max Min Max suitable sealing washer or thread > Service temperature -20 C to +90 C > CuZn39Pb3 extruded brass alloy used for guaranteed strength and sealant at gland interface performance GACWCIEL32 32 62.00 20S 424TX52 M20 1.5 424TX02 ½ - 14 NPT 11.0 30 11.5 8.0 15.8 0.2 / 0.3 67 34.0 30.5 GACWCIEL40 40 84.00 Service temperature range -20 C to 20 424TX53 M20 1.5 424TX03 ½ - 14 NPT 11.0 30 12.5 11.7 20.8 0.2 / 0.3 64 34.0 30.5 GACWCIEL50 50 94.00 +90 C 25 GACWCIEL63 424TX55 M25 1.5 424TX05 ¾ - 14 NPT 16.0 6342 11.5 123.0018.0 17.0 27.2 Integral 0.2 earth / 0.45connection 65 complies 42.2 37.6 32 GACWCIEL75 424TX56 M32 1.5 424TX06 1-11½ NPT 22.1 7560 17.0 183.0025.0 19.0 33.5 with GDCD 0.3 / 0.45 190 Category 77 A (43.3kA 53.6 47.3 40 Discount 424TX57on application M40 1.5 424TX07 1¼ - 11½ NPT 28.2 100 24.0 31.5 26.5 39.9 for 1 second) 0.3 / 0.45 77 61.5 56.4 Gland Details 50 424TX59 M50 1.5 424TX09 2-11½ NPT 37.1 200 30.0 41.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1 GLAND DETAILS 63 424TX61 M63 1.5 424TX11 2½ - 8 NPT 48.4 400 40.0 54.0 46.5 65.3 0.3 / 0.45 90 87.4 80.0 75 424TX63 M75 1.5 424TX13 3-8 NPT 58.6 400 53.0 65.5 58.0 78.0 0.3 / 0.45 C 96 109.2 98.8 Ref: A1A2/03/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 85 424TX64 M85 2 424TX14 3-8 NPT 65.8 www.prysmian.co.uk 400 60.0 74.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 H A D D E * 1.5 Pitch threads are supplied 15 long, 2 pitch threads are supplied 20 long G F E NPT thread lengths comply with new UL2225 requirements Cable Dimensions accoodated Under Armour Diameter A Max Overall Diameter B Min Max Min Max Armour Wire Diameter C D Entry Thread Length E Gland Dimensions Approx. Length from Shoulder F Across Flats G Hexagon Across Corners H 32-26.2 23.5 33.5 1.6/2.0 M32 1.5 10 73 56.4 61.5 40-32.1 29.0 39.9 1.6/2.0 M40 1.5 15 77 56.4 63.2 50-44.0 39.5 52.6 2.0/2.5 M50 1.5 15 84 70.1 77.2 63-55.9 51.3 65.3 2.5 M63 1.5 15 84 90.2 99.1 75-67.9 62.5 78.0 2.5 M75 1.5 15 94 106.2 117.0 Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 17 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
r Gland C Cable Glands HAZARDOUS AREA GLANDS A2EX EEXD IP68 GLAND F Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series D verall ia. B Max E Gland Dimensions Braid Approx. Hexagon Certified II 2GD, EEx e II & EEx d II Wire Length Dia. C under ATEX D directive A/C 94/9/EC A/F E F Service temperature range 50 C to +200 C 15.8 0.2 / 0.3 May be 67 used in: 34.0 30.5 20.8 0.2 / 0.3 - Zones 64 0, 1 & 2 34.0 with EEx 30.5 ia IIA, B & 27.2 0.2 / 0.45 C equipment 65 42.2 37.6 33.5 - Zones 1 & 2 with EEx ib IIA, B & C 0.3 / 0.45 77 53.6 47.3 equipment 39.9 0.3 / 0.45 77 61.5 56.4 - Zones 1 & 2 with EEx e II 52.6 0.3 / 0.45 equipment 84 77.2 70.1 65.3 0.3 / 0.45 - Zones 90 1 & 2 with 87.4EEx p 80.0 II 78.0 equipment 0.3 / 0.45 96 109.2 98.8 - Zone 2 with EEx na II equipment 88.0 0.3 / 0.45 108 126.0 115.0 - Zones 21 & 22 with EEx td II equipment For unarmoured and braided cable Brass indoor and outdoor cable gland for use in hazardous areas Application > Indoor/Outdoor for Unarmoured Cable Suitable for circular unarmoured cables with extruded oversheath Fitted with silicone rubber low smoke, zero halogen seal Features & Benefits Achieves IP66, IP68 (1 bar) and deluge proof (DTS01:1991) seal onto cable and to enclosure > Kit comprises: - A1/A2 Gland with suitable sealing washer or thread sealant - Brass locknut - PVC shroud > 2 per kit size up to and including 25 Suitable for most climatic conditions weatherproof, waterproof and deluge proof Dual seal option (A2EXP) available to special order Nickel plated versions also available Technical Data > EN 50262 > BS6121:Pt 1:1989 All prices are per single gland > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface > Service temperature -20 C to +90 C > CuZn39Pb3 extruded brass alloy used for guaranteed strength and performance A1/A2EX 20SS 20SS 13.17 A1/A2EX 20S 20S 14.00 A1/A2EX 20 20 14.67 A1/A2EX 25 25 7.94 A1/A2EX 32 32 20.76 A1/A2EX 40 40 39.46 A1/A2EX 50 50 54.52 A1/A2EX 63 63 91.31 A1/A2EX 75S 75S 121.07 A1/A2EX 75 Oak Road, Wrexham 767 8345, 75 www.prysmian.co.uk Wrexham, LL13 9HP, UK 130.39 Ref: A1A2/03/07 Prysmian Cables & Systems Limited, Components Unit, Industrial Estate, Coercial Enquiries, Tel +44 (0) 845 Fax: +44 (0) 23 8029 5465 GLAND DETAILS D B C Basic Thread * Cable Dia. Gland Dimensions A Approx. length Hexagon Min Max from shoulder B Across Corners C Across Flats D 20SS M20 1.5 3.5 8.5 36 24.9 22.0 20S M20 1.5 8.0 11.5 36 24.9 22.0 20 M20 1.5 8.0 16.0 34 28.7 25.7 25 M25 1.5 11.5 21.0 44 36.9 33.0 32 M32 1.5 18.5 27.5 38 42.2 37.5 40 M40 1.5 24.0 34.0 46 53.6 47.2 50 M50 1.5 31.0 41.0 44 61.5 56.4 63 M63 1.5 40.0 52.5 61 77.2 70.0 75S M75 1.5 52.5 58.0 46 87.4 80.0 75 M75 1.5 54.5 65.5 66 87.4 80.0 * 1.5 Pitch threads are supplied 15 long, 2 pitch threads are supplied 20 long 9PH, UK 18
BARR-X EEx d IIC Brass Barrier Gland Cable Glands HAZARDOUS AREA GLANDS C E1WF BRASS GLAND Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series B A F Gland Details oversheath Basic For steel wire armoured cable Brass indoor and outdoor cable gland for use in hazardous areas Application Suitable for circular, galvanised steel wire armour cables with extruded polymeric bedding and Features & Benefits > Indoor/Outdoor for Unarmoured Cable > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables Achieves IP66 seal onto cable and to enclosure with suitable sealing washer > Suitable for or most thread climatic conditions, sealant weatherproof and waterproof > Kit comprises: - A1/A2 Gland Three part armour lock provides mechanical cable retention and electrical continuity - Brass locknut - PVC shroud > 2 per kit size up to and including 25 Inner Glandseal References grips cable & bedding Thread and s provides additional ingress protection Cable Dimensions Gland Dimensions Suitable for most climatic conditions - weatherproof and waterproof Metric NPT Max. Max. No. of Inner Sheath Overall Braid Approx. Hexagon Nickel plated versions also available Certified II 2GD, EEx e II & EEx d IIC Dia. Technical Over Data Conductors > EN 50262 Dia. A Dia. B Wire Length Design Thread Design Thread > BS6121:Pt 1:1989 Conductors under Dia. ATEX C directive D 94/9/ECA/C A/F No. Kit comprises E1WF * brass No. gland, earth tag, locknut & shroud > Gland rated to IP66 with use of suitable sealing washer or thread sealant E F at gland interface Min Max Min Max > Service temperature -20 C to +90 C All prices are per single gland kit Service temperature range 60 C to > CuZn39Pb3 extruded brass alloy used for guaranteed strength and +90 C 20S 424TX52 M20 1.5 424TX02 ½ - 14 NPT 11.0 30 Price Each 11.5 8.0 15.8 0.2 / 0.3 67 34.0 30.5 May be used in: 20 424TX53 M20 1.5 424TX03 ½ - 14 NPT 11.0 30 12.5 11.7 20.8 - Zones 0.20, / 10.3 & 2 with 64EEx ia IIA, 34.0B & 30.5 E1WF20SS 20SS 14.60 25 424TX55 M25 1.5 424TX05 ¾ - 14 NPT 16.0 42 11.5 18.0 17.0 27.2 C equipment 0.2 / 0.45 65 42.2 37.6 E1WF20S 20S 14.60 - Zones 1 & 2 with EEx ib IIA, B & C 32 E1WF20 424TX56 M32 1.5 424TX06 1-11½ NPT 22.1 2060 17.0 16.4025.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3 equipment 40 E1WF25 424TX57 M40 1.5 424TX07 1¼ - 11½ NPT 28.2 25100 24.0 24.6031.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4 - Zones 1 & 2 with EEx e II 50 E1WF32 424TX59 M50 1.5 424TX09 2-11½ NPT 37.1 32200 30.0 34.0041.5 36.0 52.6 equipment 0.3 / 0.45 84 77.2 70.1 E1WF40 40 65.00 63 424TX61 M63 1.5 424TX11 2½ - 8 NPT 48.4 400 40.0 54.0 46.5 65.3 - Zones 0.31 /& 0.45 2 with EEx 90 p II 87.4 80.0 E1WF50S 50S 85.00 equipment 75 424TX63 M75 1.5 424TX13 3-8 NPT 58.6 400 53.0 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 E1WF50 50 85.00 Ref: A1A2/03/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK - Zones 2 with EEx na II equipment Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 85 E1WF63S 424TX64 M85 2 424TX14 3-8 NPT 65.8 www.prysmian.co.uk 63S 400 60.0 170.0074.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 Zone 21 & 22 with EEx td II E1WF63 63 170.00 equipment E1WF75S 75S 235.00 * 1.5 E1WF75 Pitch threads are supplied 15 long, 2 pitch threads are supplied 75 20 285.00 long NPT thread Discount lengths on application comply with new UL2225 requirements GLAND DETAILS performance D E F D E Basic Thread Cable dimensions Gland Dimensions Inner Sheath Diameter Overall Diameter Approx. length Max Hexagon from shoulder Armour Thickness Min Max Min Max D Across corners E Across flats F 20SS M20 1.5 3.81 8.74 8.0 13.2 0.9 41 26.7 23.4 20S M20 1.5 8.0 11.79 8.0 15.8 0.9/1.4 43 29.2 25.7 20 M20 1.5 11.79 14.15 11.7 20.8 0.9/1.4 43 34.0 30.5 25 M25 1.5 14.0 20.12 17.0 27.2 1.25/1.6 48 42.2 37.6 32 M32 1.5 19.70 26.55 23.5 33.5 1.6/2.0 53 53.6 47.2 40 M40 1.5 26.55 32.42 29.0 39.9 1.6/2.0 56 61.5 56.4 50S M50 1.5 32.42 38.39 38.0 46.2 2.0/2.5 61 66.0 60.0 50 M50 1.5 38.39 44.33 39.5 52.6 2.0/2.5 61 77.2 70.1 63S M63 1.5 44.33 50.27 50.0 58.9 2.5 64 83.0 75.0 63 M63 1.5 50.27 56.24 51.3 65.3 2.5 64 87.4 80.0 75S M75 1.5 56.24 62.18 62.0 71.6 2.5 73 99.1 90.2 75 M75 1.5 62.18 68.13 62.5 78.0 2.5 73 109.2 98.8 Please refer to product selection table on page 8 to size product relative to cable type Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 19 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
r Gland C Cable Glands HAZARDOUS AREA GLANDS E1XF BRASS GLAND F Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series D verall ia. B Max E Gland Dimensions Braid Approx. Hexagon Certified II 2GD, EEx e II & EEx d IIC Wire Length Dia. C under ATEX D directive A/C 94/9/EC A/F E F Service temperature range 60 C to +90 C 15.8 0.2 / 0.3 May be 67 used in: 34.0 30.5 20.8 0.2 / 0.3 - Zones 64 0, 1 & 2 34.0 with EEx 30.5 ia IIA, B & 27.2 0.2 / 0.45 C equipment 65 42.2 37.6 33.5 - Zones 1 & 2 with EEx ib IIA, B & C 0.3 / 0.45 77 53.6 47.3 equipment 39.9 0.3 / 0.45 77 61.5 56.4 - Zones 1 & 2 with EEx e II 52.6 0.3 / 0.45 equipment 84 77.2 70.1 65.3 0.3 / 0.45 - Zones 90 1 & 2 with 87.4EEx p 80.0 II 78.0 equipment 0.3 / 0.45 96 109.2 98.8 - Zone 2 with EEx na II equipment 88.0 0.3 / 0.45 108 126.0 115.0 - Zones 21 & 22 with EEx td II equipment For wire braid cable Brass indoor and outdoor cable gland for use in hazardous areas Suitable for circular, wire braid armour cables with extruded polymeric bedding & oversheath Achieves IP66 seal onto cable and to enclosure with suitable Features & sealing Benefits washer or thread sealant Three part armour lock provides mechanical cable retention and electrical continuity Inner seal grips cable bedding and provides additional ingress protection Suitable for most climatic conditions weatherproof and waterproof Nickel plated versions also available All prices are per single gland Application Technical Data > EN 50262 > Indoor/Outdoor for Unarmoured Cable > Brass indoor and outdoor cable gland & accessories Kit consists of E1XF brass gland, earth tag, locknut, shroud and nylon sealing washer > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland - Brass locknut - PVC shroud > 2 per kit size up to and including 25 > BS6121:Pt 1:1989 > Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface > Service temperature -20 C to +90 C > CuZn39Pb3 extruded brass alloy used for guaranteed strength and performance E1XF63S 63S Oak Road, Wrexham 168.70 Wrexham, LL13 9HP, UK Ref: A1A2/03/07 Prysmian Cables & E1XF63 Systems Limited, Components Unit, Industrial Estate, Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk 63 168.70 E1XF20SS 20SS 15.80 E1XF20S 20S 15.80 E1XF20 20 17.40 E1XF25 25 25.80 E1XF32 32 39.75 E1XF40 40 67.40 E1XF50S 50S 95.82 E1XF50 50 95.82 E1XF75S 75S 278.77 E1XF75 75 278.77 GLAND DETAILS F D E Basic Thread Cable dimensions Gland Dimensions Inner Sheath Diameter Overall Diameter Approx length Max Hexagon from shoulder Min Max Min Max Armour Thickness D Across corners E Across flats F 20SS M20 1.5 3.81 8.74 8.0 13.2 0.2/0.3 41 26.7 23.4 20S M20 1.5 8.00 11.79 8.0 15.8 0.2/0.3 43 29.2 25.7 20 M20 1.5 11.79 14.15 11.7 20.8 0.2/0.3 43 34.0 30.5 25 M25 1.5 14.00 20.12 17.0 27.2 0.2/0.45 48 42.2 37.6 32 M32 1.5 19.70 26.55 23.5 33.5 0.3/0.45 53 53.6 47.2 40 M40 1.5 26.55 32.42 29.0 39.9 0.3/0.45 56 61.5 56.4 50S M50 1.5 32.42 38.39 38.0 46.2 0.3/0.45 61 66.0 60.0 50 M50 1.5 38.39 44.33 39.5 52.6 0.3/0.45 61 77.2 70.1 63S M63 1.5 44.33 50.27 50.0 58.9 0.3/0.45 64 83.0 75.0 63 M63 1.5 50.27 56.24 51.3 65.3 0.3/0.45 64 87.4 80.0 75S M75 1.5 56.24 62.18 62.0 71.6 0.3/0.45 73 99.1 90.2 75 M75 1.5 62.18 68.13 62.5 78.0 0.3/0.45 73 109.2 98.8 Please refer to product selection table on page 8 to size product relative to cable type 9PH, UK 20
BARR-X EEx d IIC Brass Barrier Gland Cable Glands HAZARDOUS AREA GLANDS C E1WXL BRASS GLAND Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series B A F Flameproof Universal Gland Exd & Exe Double seal gland for Outdoor and Indoor use. Application > Indoor/Outdoor for Unarmoured Cable For use with single wire armour W, wire braid X, elastomer and plastic insulated cables. Gland Details Seals on to and electrically bonds lead inner sheath. Features & Benefits > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof Suitable for Zone 1 and 2 Hazardous areas. > Kit comprises: - A1/A2 Gland - Brass locknut Nickel plated versions available - PVC shroud > 2 per kit size up to and including 25 All Gland prices References are per single & Thread gland s Cable Dimensions Gland Dimensions Basic Metric NPT Max. Max. No. of Inner Sheath Overall Flameproof BraidExd and Approx. Increased Hexagon Safety Dia. Technical Over Data Conductors > EN 50262 Dia. A Dia. B Wire Length Design Thread Design Thread > BS6121:Pt 1:1989 Conductors Exe Certified Dia. C II 2GD D A/C A/F > Gland rated to IP66 with use of suitable sealing washer or thread sealant E1WXL20SS No. * No. 20SS 14.60 E F at gland interface Min Max Min Max E1WXL20S 20S > Service temperature -20 C to 14.60 Ingress protection: IP66, IP67 (sealing +90 C > CuZn39Pb3 extruded brass alloy used for guaranteed strength and E1WXL20 20 performance 16.40 washer required between gland and 20S E1WXL25 424TX52 M20 1.5 424TX02 ½ - 14 NPT 11.0 2530 11.5 8.0 15.8 equipment) 24.60 0.2 / 0.3 67 34.0 30.5 20 E1WXL32 424TX53 M20 1.5 424TX03 ½ - 14 NPT 11.0 3230 34.0012.5 11.7 20.8 Operating 0.2 / Temperature 0.3 64-60 C 34.0 to 30.5 E1WXL40 40 25 424TX55 M25 1.5 424TX05 ¾ - 14 NPT 16.0 42 11.5 65.0018.0 17.0 27.2 +90 C0.2 / 0.45 65 42.2 37.6 E1WXL50S 50S 85.00 32 424TX56 M32 1.5 424TX06 1-11½ NPT 22.1 60 17.0 25.0 19.0 33.5 May be 0.3 used / 0.45 in: 77 53.6 47.3 E1WXL50 50 85.00 40 424TX57 M40 1.5 424TX07 1¼ - 11½ NPT 28.2 100 24.0 31.5 26.5 39.9 - Zones 0.30, / 1, 0.45 2 with EEx 77 ia IIA, 61.5 B & C E1WXL63S 63S 56.4 170.00 equipment 50 E1WXL63 424TX59 M50 1.5 424TX09 2-11½ NPT 37.1 63200 30.0 170.0041.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1 - Zones 1 & 2 with EEx ib IIA, B & C 63 E1WXL75S 424TX61 M63 1.5 424TX11 2½ - 8 NPT 48.4 75S 400 40.0 235.0054.0 46.5 65.3 equipment 0.3 / 0.45 90 87.4 80.0 E1WXL75 75 75 424TX63 M75 1.5 424TX13 3-8 NPT 58.6 400 53.0 285.0065.5 58.0 78.0 - Zones 0.31 /& 0.45 2 with EEx 96 e II equipment 109.2 98.8 Ref: A1A2/03/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 85 424TX64 M85 2 424TX14 3-8 NPT 65.8 www.prysmian.co.uk 400 60.0 74.0 68.0 88.0 - Zones 0.31 /& 0.45 2 with EEx 108 p II equipment 126.0 115.0 - Zone 2 with EEx na II equipment - Zone 21 & 22 with EEx ID II * 1.5 Pitch threads are supplied 15 long, 2 pitch threads are supplied 20 long equipment D E NPT thread lengths comply with new UL2225 requirements C GLAND DETAILS D E Basic Thread Cable Dimensions Gland Dimensions Inner Sheath Diameter Overall Diameter Approx length Hexagon from shoulder Min Max Min Max C Across corners D Across flats E 20SS M20 1.5 3.81 8.74 8.0 13.2 41.0 26.7 23.4 20S M20 1.5 8.00 11.79 8.0 15.8 43.0 29.2 25.7 20 M20 1.5 11.79 14.15 11.7 20.8 43.0 34.0 30.5 25 M25 1.5 14.00 20.12 17.0 27.2 48.0 42.2 37.6 32 M32 1.5 19.70 26.55 23.5 33.5 53.0 53.6 47.2 40 M40 1.5 26.55 32.42 29.0 39.9 56.0 61.5 56.4 50S M50 1.5 32.42 38.39 38.0 46.2 61.0 66.0 60.0 50 M50 1.5 38.39 44.33 39.5 52.6 61.0 77.2 70.1 63S M63 1.5 44.33 50.27 50.0 58.9 64.0 83.0 75.0 63 M63 1.5 50.27 56.24 51.3 65.3 64.0 87.4 80.0 75S M75 1.5 56.24 62.18 62.0 71.6 73.0 99.1 90.2 75 M75 1.5 62.18 68.13 62.5 78.0 73.0 109.2 98.8 Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 21 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
PAGE 11 Cable Glands HAZARDOUS AREA GLANDS PAGE 12 PAGE 13 BARR-A EEXD BARRIER GLAND PAGE 14 PAGE Certified 16 II 2GD, EEx e II & EEx d IIC underatex directive 94/9/EC Service temperature range 60 C to +90 C May be used in: Zones 0, 1 & 2 with EEx ia IIA, B & C equipment PAGE 18 - Zones 1 & 2 with EEx ib IIA, B & C equipment - Zones 1 & 2 with EEx d IIA, B & C equipment with any volume - Zones 1 & 2 with EEx e II equipment - Zones 1 & 2 with EEx p II PAGE equipment 20 - Zone 2 with EEx na II equipment - Zone 2 with EEx nr II equipment - Zones 21 & 22 with EEx td II equipment For unarmoured cables Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series Brass indoor and outdoor cable gland for use in Zone 1 and Zone 2 hazardous areas Application > Indoor/Outdoor for Unarmoured Cable Suitable for circular unarmoured cables with extruded polymeric oversheath Achieves IP66 seal onto cable and to enclosure with suitable Features & Benefits sealing washer or thread sealant Provides mechanical cable retention > Kit comprises: - A1/A2 Gland - Brass locknut Suitable for most climatic conditions - weatherproof and waterproof - PVC shroud > 2 per kit size up to and including 25 Nickel plated versions also available All prices PAGE are 17 per single gland > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > BS6121:Pt 1:1989 at gland interface > Service temperature -20 C to +90 C BARR-A-20 20 22.12 BARR-A-25 25 33.52 performance BARR-A-32 32 51.31 BARR-A-40 40 95.18 BARR-A-50 50 129.08 PAGE 19 BARR-A-63 63 234.25 BARR-A-75 75 346.21 Ref: A1A2/03/07 Technical Data > EN 50262 PAGE 21 > Gland rated to IP66 with use of suitable sealing washer or thread sealant > CuZn39Pb3 extruded brass alloy used for guaranteed strength and Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk PAGE 15 PAGE GLAND 22 DETAILS - NOT DRAWN AT 100% (THIS IS 60%) A D PAGE 22 - NOT DRAWN AT 100% (THIS IS 60%) B C Basic Thread Cable Dimensions Overall Diameter Max. Dia. Over Conductors Min Max Gland Dimensions Hexagon Approx. Length Across corners B C 20 M20 1.5 11.0 8.9D 15.7 E 56 40.0 36.0 B A Across flats D 25 M25 1.5 16.0 13.0 19.3 59 48.0 42.4 PAGE 22 32 - NOT DRAWN M32 1.5 AT 100% (THIS IS 22.1 60%) 17.0 25.4 59 53.6 47.2 40 M40 1.5 28.2 24.1 30.0 63 61.5 56.4 50 M50 1.5 37.1 29.0 41.9 66 77.2 70.1 63 M63 1.5 48.4 40.9 52.8 69 87.4 80.0 75 M75 1.5 58.6 49.8 59.9 80 109.2 98.8 B A D E F F 22
BARR-X EEx d PAGE IIC 13 Brass Barrier Gland Cable Glands HAZARDOUS AREA GLANDS C BARR-W EEXD BARRIER GLAND Industrial Gland PAGE Kits 14 A1/A2 Brass Gland Kit KM409 Series B A F For steel wire armoured cables Brass indoor and outdoor cable gland for use in Zone 1 and Zone 2 hazardous areas Application > Indoor/Outdoor for Unarmoured Cable Suitable for circular, galvanised steel single wire armour PAGE cables 16 with extruded polymeric PAGE 17 Gland Details oversheath and extruded or taped bedding Features & Benefits > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables Achieves IP66 seal onto cable and to enclosure with suitable sealing washer > Suitable for or most thread climatic conditions, sealant weatherproof and waterproof > Kit comprises: - A1/A2 Gland Provides mechanical cable retention and electrical continuity through the armour - Brass wire locknut - PVC shroud termination > 2 per kit size up to and including 25 Gland References & Thread s Cable Dimensions Gland Dimensions Suitable for most climatic conditions weatherproof & waterproof Basic Metric NPT Max. Max. No. of Inner Sheath Overall Braid Approx. Hexagon Nickel plated versions also available Certified II 2GD, EEx e II & EEx d IIC Dia. Technical Over Data Conductors > EN 50262 Dia. A Dia. B Wire Length Design Thread Design Thread PAGE 18 > BS6121:Pt 1:1989 Conductors Dia. C D A/C A/F All prices are per single gland under ATEX PAGE directive 19 94/9/EC > Gland rated to IP66 with use of suitable sealing washer or thread sealant No. * No. E F at gland interface Min Max Min Max Service temperature range -60 C to > Service temperature -20 C to +90 C > CuZn39Pb3 extruded brass Price alloy used Each for guaranteed strength and +90 C performance 20S BARR-W-20S 424TX52 M20 1.5 424TX02 ½ - 14 NPT 11.0 20S 30 11.5 8.0 15.8 0.2 / 0.3 67 34.0 30.5 19.63 May be used in: 20 BARR-W-20 424TX53 M20 1.5 424TX03 ½ - 14 NPT 11.0 2030 23.0512.5 11.7 20.8 - Zones 0.20, / 10.3 & 2 with 64EEx ia IIA, 34.0B & 30.5 25 BARR-W-25 424TX55 M25 1.5 424TX05 ¾ - 14 NPT 16.0 2542 11.5 34.9218.0 17.0 27.2 C equipment 0.2 / 0.45 65 42.2 37.6 BARR-W-32 32 424TX56 M32 1.5 424TX06 1-11½ NPT 22.1 PAGE 20 32 60 17.0 53.46 - Zones 1 & 2 with EEx ib IIA, B & C 25.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3 BARR-W-40 40 99.15 equipment 40 424TX57 M40 1.5 424TX07 1¼ - 11½ NPT 28.2 100 24.0 31.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4 BARR-W-50 50 134.47 - Zones 1 & 2 with EEx d IIA, B & C 50 BARR-W-63 424TX59 M50 1.5 424TX09 2-11½ NPT 37.1 63200 30.0 41.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1 244.03 equipment with any volume 63 BARR-W-75 424TX61 M63 1.5 424TX11 2½ - 8 NPT 48.4 75400 40.0 360.6454.0 46.5 65.3 - Zones 0.31 /& 0.45 2 with EEx 90 e II 87.4 80.0 75 Discount 424TX63on application equipment M75 1.5 424TX13 3-8 NPT 58.6 400 53.0 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 Ref: A1A2/03/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK - Zones 1 & 2 with EEx p II Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 85 424TX64 M85 2 424TX14 3-8 NPT 65.8 PAGE 22 - NOT www.prysmian.co.uk 400 DRAWN 60.0 AT 100% 74.0 (THIS 68.0 IS 60%) 88.0 0.3 / 0.45 108 126.0 115.0 equipment - Zone 2 with EEx na II equipment - Zone 2 with EEx nr II equipment * 1.5 Pitch threads are supplied 15 long, 2 pitch threads are supplied 20 long - Zones 21 & 22 with EEx td II NPT thread lengths comply with new UL2225 requirements equipment B C PAGE 22 - NOT DRAWN AT 100% (THIS IS 60%) D A E GLAND DETAILS D B A F D E PAGE 22 - NOT DRAWN AT 100% (THIS IS 60%) Cable Dimensions Gland Dimensions Basic Thread Inner Sheath Dia. A Overall Dia. B Approx Hexagon Max. Dia. Over Armour Wire length from Conductors Min Max Min Max Diameter Across Across flats shoulder D corners E F 20S M20 1.5 11.0 12.5 8.0 15.8 0.9/1.4 67 34.0 30.5 20 M20 1.5 11.0 12.5 11.7 20.8 0.9/1.4 64 D 34.0 E 30.5 25 M25 1.5 16.0 11.5 18.0 17.0 27.2 1.25/1.6 65 42.2 37.6 32 M32 1.5 22.1 17.0 25.0 19.0 33.5 1.6/2.0 77 53.6 47.3 40 M40 1.5 28.2 24.0 31.5 26.5 39.9 1.6/2.0 77 61.5 56.4 50 M50 1.5 37.1 30.0 41.5 36.0 52.6 2.0/2.5 84 77.2 70.1 63 M63 1.5 48.4 40.0 54.0 46.5 65.3 2.5 90 87.4 80.0 75 M75 1.5 58.6 53.0 65.5 58.0 78.0 2.5/3.15 96 109.2 98.8 B A F Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 23 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
r Gland C PAGE 14 Cable Glands HAZARDOUS AREA GLANDS PAGE 16 BARR-X EEXD BARRIER GLAND F PAGE 17 Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series D E Brass indoor and outdoor cable gland for use in Zone 1 and Zone 2 hazardous areas Application > Indoor/Outdoor for Unarmoured Cable Suitable for circular, wire braid armour cables with extruded polymeric oversheath and extruded PAGE 18 or taped PAGE bedding 19 Features & Benefits > Brass indoor and outdoor cable gland & accessories Achieves IP66 seal onto cable and to enclosure with suitable sealing washer or thread sealant > Kit comprises: - A1/A2 Gland Provides mechanical cable retention and electrical continuity through the braid wire - Brass locknut termination - PVC shroud > 2 per kit size up to and including 25 Gland Dimensions Suitable for most climatic conditions weatherproof & waterproof Nickel plated versions also available verall Braid Approx. Hexagon Certified II 2GD, EEx e II & EEx d IIC ia. B Wire Length All prices are per single gland Technical Data > EN 50262 Dia. C under ATEX D directive A/C 94/9/EC A/F > BS6121:Pt 1:1989 PAGE 21 PAGE 20 E F Max at gland interface Service temperature range 60 C to > Service temperature -20 C to +90 C +90 C BARR-X-20S 20S performance 18.84 15.8 0.2 / 0.3 May be 67 used in: 34.0 30.5 BARR-X-20 20 22.12 20.8 0.2 / 0.3 - Zones 64 0, 1 & 2 34.0 with EEx 30.5 ia IIA, B & BARR-X-25 25 33.52 27.2 0.2 / 0.45 C equipment 65 42.2 37.6 BARR-X-32 32 52.95 PAGE - 22 Zones - NOT 1 & DRAWN 2 with EEx AT ib 100% IIA, B (THIS & C IS 60%) 33.5 0.3 / 0.45 77 53.6 47.3 BARR-X-40 40 95.18 equipment BARR-X-50 50 129.08 39.9 0.3 / 0.45 77 61.5 56.4 - Zones 1 & 2 with EEx d IIA, B & C BARR-X-63 63 234.25 52.6 0.3 / 0.45 equipment 84 with 77.2 any volume 70.1 BARR-X-75 75 346.21 65.3 0.3 / 0.45 - Zones 90 1 & 2 with 87.4EEx e 80.0 II B C equipment 78.0 0.3 / 0.45 96 109.2 98.8 PAGE - 22 Zones - NOT 1 & DRAWN 2 with EEx AT p 100% II (THIS IS 60%) Ref: A1A2/03/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 88.0 0.3 / 0.45 108 126.0 115.0 www.prysmian.co.uk equipment - Zone 2 with EEx na II equipment - Zone 2 with EEx nr II equipment - Zones 21 & 22 with EEx td II equipment D E GLAND PAGE 22 DETAILS - NOT DRAWN AT 100% (THIS IS 60%) For wire braided cables A B A F D > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > Gland rated to IP66 with use of suitable sealing washer or thread sealant > CuZn39Pb3 extruded brass alloy used for guaranteed strength and B A F D E Basic Thread Max. Dia. Over Conductors Cable Dimensions Inner Sheath Dia. A Overall Dia. B Braid Wire Min Max Min Max Diameter Approx length from shoulder D Gland Dimensions Hexagon Across corners E 20S M20 1.5 11.0 11.5 8.0 15.8 0.2/0.3 67 34.0 30.5 20 M20 1.5 11.0 12.5 11.7 20.8 0.2/0.3 64 34.0 30.5 25 M25 1.5 16.0 11.5 18.0 17.0 27.2 0.2/0.45 65 42.2 37.6 32 M32 1.5 22.1 17.0 25.0 19.0 33.5 0.3/0.45 77 53.6 47.3 40 M40 1.5 28.2 24.0 31.5 26.5 39.9 0.3/0.45 77 61.5 56.4 50 M50 1.5 37.1 30.0 41.5 36.0 52.6 0.3/0.45 84 77.2 70.1 63 M63 1.5 48.4 40.0 54.0 46.5 65.3 0.3/0.45 90 87.4 80.0 75 M75 1.5 58.6 53.0 65.5 58.0 78.0 0.3/0.45 96 109.2 98.8 Across flats F 9PH, UK 24
BARR-X EEx d IIC Brass Barrier Gland Cable Glands C ACCESSORIES INSULATED ADAPTOR Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series B A F Insulated adaptors provide a method of insulating cable glands from the equipment to which they are fixed D E Application > Indoor/Outdoor for Unarmoured Cable They are used where the enclosure is not relied upon for bonding the cable to the earth, for Gland Details example Features & Benefits To prevent the heating effects of circulating currents To segregate low voltage and high voltage earth fault paths > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland - Brass locknut - PVC shroud > 2 per kit size up to and including 25 Gland References & Thread s Cable Dimensions Gland Dimensions Basic Metric NPT Max. Max. No. of Inner Sheath Overall Braid Approx. Hexagon 481AA53 20 Dia. Over Conductors Dia. 25.66 Impact resistance: 7 Joules Technical Data > EN 50262 A Dia. B Wire Length Design Thread Design Thread > BS6121:Pt 1:1989 481AA55 Conductors 25 32.65 Dia. C D A/C A/F > Gland rated to IP66 with use of suitable sealing washer or thread sealant No. * No. Ambient Temperature: -50 C to E F 481AA56 at gland 32 interface Min46.24 Max Min Max +85 C > Service temperature -20 C to +90 C 481AA57 40 > CuZn39Pb3 extruded brass alloy 50.35 used for guaranteed strength and performance 481AA59 50 78.12 Material: Brass (481AA - Series) or 20S 424TX52 M20 1.5 424TX02 ½ - 14 NPT 11.0 30 11.5 8.0 15.8 0.2 / 0.3 67 34.0 30.5 481AA61 63 113.44 Aluminium (481AL - Series) 20 481AA63 424TX53 M20 1.5 424TX03 ½ - 14 NPT 11.0 3075 12.5 186.31 11.7 20.8 0.2 / 0.3 64 34.0 Insulator: 30% glass filled nylon 12 30.5 25 Discount 424TX55on application M25 1.5 424TX05 ¾ - 14 NPT 16.0 42 11.5 18.0 17.0 27.2 0.2 / 0.45 65 42.2 37.6 Certified: EExd llc for hazardous area 32 424TX56 M32 1.5 424TX06 1-11½ NPT 22.1 60 17.0 25.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3 INSULATED ADAPTOR DETAILS applications 40 424TX57 M40 1.5 424TX07 1¼ - 11½ NPT 28.2 100 24.0 31.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4 Equipment 50 424TX59 Reference M50 1.5 424TX09 2-11½ NPT Total 37.1 Male 200Female Thread Hex A/F Hex A/C 30.0 Bore41.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1 Number Length Length Depth 63 424TX61 M63 1.5 424TX11 2½ - 8 NPT 48.4 400 40.0 54.0 46.5 65.3 0.3 / 0.45 90 87.4 80.0 481AA 53 M20 30.5 35.5 54.0 16.0 17.0 13.5 75 424TX63 M75 1.5 481AA 55 M25 424TX13 37.6 3-8 NPT 43.2 Ref: A1A2/03/07 58.6 54.0 16.0 400 17.0 53.0 65.5 19.0 58.0 78.0 0.3 / 0.45 96 109.2 98.8 Prysmian Cables & Systems Limited, Components Unit, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK Oak Road, 85 424TX64 481AA 56 M85 M32 2 424TX14 47.2 3 54.3-8 NPT Coercial Enquiries, 54.0 65.8 Tel +44 (0) 16.0 www.prysmian.co.uk 8345, Fax: +44 (0) 23 8029 40017.0 60.0 25.074.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 845 767 5465 481AA 57 M40 55.9 64.1 54.0 16.0 17.0 30.0 481AA 59 M50 70.1 80.8 54.0 16.0 17.0 40.5 * 1.5 Pitch 481AA threads 61 M63 are supplied 80.0 15 long, 92.02 pitch 54.0threads 16.0 are supplied 17.0 20 long 53.0 NPT thread 481AA lengths 63 comply M75 with 95.3 new UL2225 109.5 requirements 54.0 16.0 17.0 65.0 EExd & EExe Adaptors and Reducers FLAMEPROOF EEXDZONE 1 BRASS REDUCERS Problems caused by dissimilar threads can occur in both hazardous and industrial environments Adaptors provide a means of connection between dissimilar thread forms or sizes Reducers effectively reduce the threaded entry diameter of an enclosure to accept a gland or fitting with a smaller thread. Reducers may also be supplied to accept smaller glands of alternative threads forms Male Thread Female Thread MR2016 M20 M16 25.66 MR2520 M25 M20 32.65 MR3220 M32 M20 46.24 MR3225 M32 M25 50.35 MR4025 M40 M25 78.12 MR4032 M40 M32 113.44 MR5032 M50 M32 186.31 MR5040 M50 M40 366.44 MR6350 M63 M50 463.31 Also available in other sizes and stainless steel, aluminium or nylon EExd and EExe certified as ATEX, CSA, IECE and GOST Standards Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 25 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
Cable Glands ACCESSORIES Brass & aluminium earth tags Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series Ensures earth continuity is maintained between the gland and the equipment Aluminium earth tags should be used with aluminium glands Application > Indoor/Outdoor for Unarmoured Cable > Brass indoor and outdoor cable gland & accessories Brass Aluminium Features & Benefits Brass Aluminium > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland 428ET53 458ET53 20 0.80 0.85 - Brass locknut 428ET55 458ET55 25 0.98 - PVC shroud 1.04 > 2 per kit size up to and including 25 428ET61 458ET61 Technical Data > EN 50262 63 5.60 > BS6121:Pt 1:1989 2.25 > Gland rated to IP66 with use of suitable sealing washer or thread sealant 428ET65 458ET65 85/90 at gland interface 11.89 > Service temperature 13.14-20 C to +90 C 428ET51 458ET51 16 0.80 0.85 428ET56 458ET56 32 1.64 1.07 428ET57 458ET57 40 1.97 1.47 428ET59 458ET59 50 4.11 1.55 428ET63 458ET63 75 6.28 8.32 > CuZn39Pb3 extruded brass alloy used for guaranteed strength and performance brass, steel & aluminium locknuts Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series Used to secure cable gland to the equipment where entry hole is not tapped Brass backnuts recoended for most corrosive environments Aluminium backnuts should be used with aluminium glands Steel locknuts are primarily for dry, low humidity environments Ref: A1A2/03/07 Application Features & Benefits > Indoor/Outdoor for Unarmoured Cable > Brass indoor and outdoor cable gland & accessories Prysmian Cables & Systems Limited, Components Unit, Oak Road, > Wrexham For circular, Industrial unarmoured Estate, Wrexham, plastic LL13 9HP, or rubber UK sheathed cables Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 > Suitable for most climatic conditions, weatherproof and waterproof www.prysmian.co.uk Price > Kit comprises: Each - A1/A2 Gland Brass Steel Aluminium Brass Steel - Brass locknut Aluminium 429AA51 439AA51 459AA51 16 0.77 > 2 per kit size 0.77 - PVC shroud to and including 25 1.45 up 429AA53 439AA53 459AA53 20 0.77 0.77 1.92 429AA55 439AA55 459AA55 25 1.00 1.00 2.31 429AA56 439AA56 459AA56 32 Technical 1.57 Data > EN 50262 1.57 2.60 > BS6121:Pt 1:1989 429AA57 439AA57 459AA57 40 2.87 2.87 4.25 with use washer or thread sealant 429AA59 439AA59 459AA59 50 4.41 > Gland rated to IP66 at gland interface 4.41 of suitable sealing 8.92 > Service temperature -20 C to +90 C 429AA61 439AA61 459AA61 63 6.95 6.95 10.91 brass strength and 429AA63 439AA63 459AA63 75 12.08 > CuZn39Pb3 extruded performance 12.08 alloy used for guaranteed 35.99 429AA69 439AA69 459AA69 85 42.00 42.00 65.00 SEALING WASHERS Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series High performance sealing washers Improves the IP rating between the gland and the equipment. Fibre to BS6091 Pt1 Nylon 6.6 Ref: A1A2/03/07 Application Prysmian Cables & Systems Limited, Components Unit, Oak Road, > Wrexham Indoor/Outdoor Industrial Estate, for Wrexham, Unarmoured LL13 9HP, Cable UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 Features & Benefits www.prysmian.co.uk > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland Fibre Nylon Fibre - Brass locknut Nylon - PVC shroud 41702-57 25111-007 Technical Data > EN 50262 40 0.50 > BS6121:Pt 1:1989 0.50 41702-59 25111-009 50 > Gland 0.55at use of suitable 0.55 rated to IP66 with sealing washer or thread sealant gland interface 41702-61 25111-011 63 > Service 0.60 to +90 C 0.60 temperature -20 C brass guaranteed strength and 41702-63 25111-013 75 > CuZn39Pb3 extruded 0.65performance alloy used for 0.65 41702-53 25111-003 20 > 2 per 0.35 including 25 0.35 kit size up to and 41702-55 25111-005 25 0.40 0.40 41702-56 25111-006 32 0.45 0.45 41702-64 - 85 0.70-41702-65-90 0.75-26 Please contact your nearest sales office for details of the Jointing Technologies FULL range of shrouds
Cable Lugs & Connectors CONTENTS Pre-Insulated Terminals 28 LV lugs & Splices 29 HV lugs & Splices 35 LV Mechanical lugs 38 LV Mechanical Connectors 39 HV Mechanical lugs & Connectors 41 27
Cable Lugs & Connectors PRE-INSULATED TERMINALS RING TERMINALS Pre-insulated halogen free ring type terminal with funnel entry Colour Hole Conductor Price per 100 RF-M Red 3, 3.5, 4, 5, 6, 8, 10, 12 0.25-1.5 2 9.90 BF-M Blue 3, 3.5, 4, 5, 6, 8, 10, 12 1.5-2.5 2 9.95 GF-M Yellow 3.5, 4, 5, 6, 8, 10, 12 4-6 2 12.90 BUTT CONNECTORS Pre-insulated straight connectors with funnel entry Colour Conductor Price per 100 PL03-M Red 0.25-1.5 2 9.15 PL06-M Blue 1.5-2.5 2 9.95 PL1-M Yellow 4-6 2 13.95 PIN TERMINALS Pre insulated halogen free pin type terminal with funnel entry Colour Pin Length Conductor Price per 100 RF-P Red 9, 10, 12 0.25-1.5 2 7.95 BF-P Blue 9, 10, 12 1.5-2.5 2 7.95 GF-P Yellow 14 4-6 2 11.95 BLADE TERMINALS Pre insulated halogen free blade type terminal with funnel entry Colour Blade Length Conductor Price per 100 RF-PP Red 13,18 0.25-1.5 2 9.95 BF-PP Blue 13,18 1.5-2.5 2 9.95 GF-PP Yellow 14, 18 4-6 2 11.90 FORK TERMINALS Pre insulated halogen free blade fork type terminal with funnel entry Colour Hole Conductor RF-U Red 3, 3.5, 4, 5, 6 0.25-1.5 2 8.50 BF-U Blue 3, 3.5, 4, 5, 6 1.5-2.5 2 8.95 GF-U Yellow 3.5, 4, 5, 6, 8 4-6 2 10.95 28
Cable Lugs & Connectors LV lugs & SPLICES LV COPPER lugs LV copper tube crimping lugs Designed to be crimped onto a conductor to facilitate the termination of the cable via the lug hole Copper lugs are electrolytically tin plated to avoid oxidation Each terminal has a sight hole for visual inspection of the conductor inserted Please refer to our tooling and equipment section on page 183-196 for dies and tooling Hole Conductor A03-M 3.5, 4, 5, 6 1.5 2 0.20 A06-M 3.5, 4, 5, 6, 8 2.5 2 0.20 A1-M 3.5, 4, 5, 6, 8 4-6 2 0.30 A2-M 3, 4, 5, 6, 8,10 10 2 0.40 A3-M 4, 5, 6, 8,10,12 16 2 0.45 A5-M 4, 5, 6, 8,10,12 25 2 0.60 A7-M 5, 6, 8,10,12 35 2 0.95 A10-M 6, 8,10,12, 14,16 50 2 1.50 A14-M 6, 8,10,12, 14,16 70 2 1.95 A19-M 8,10,12, 14,16, 20 95 2 2.40 A24-M 8,10,12, 14,16, 20 120 2 2.95 A30-M 8,10,12, 14,16, 20 150 2 5.95 A37-M 8,10,12, 14,16, 20 185 2 6.50 A48-M 10,12, 14,16, 20 240 2 11.95 A60-M 10,12, 14,16, 20 300 2 14.95 A80-M 12,16,20 400 2 22.00 A100-M 16, 20 500 2 28.50 A120-M 16, 20 630 2 40.00 A160-M 16, 20 800 2 70.00 A200-M 16, 20 1000 2 84.00 1000V Rated Manufactured from electrolytic copper tube to EN 12735 Tested to BS EN 61238 UL Listed (up to 300) CE Approved DEF Standard 59-71 Approved LV NARROW PALM COPPER lugs LV narrow palm copper tube crimping lugs Designed to be crimped onto a conductor to facilitate the termination of the cable via the lug hole in tight spaces and reduced space terminal blocks Copper lugs are electrolytically tin plated to avoid oxidation Each terminal has a sight hole for visual inspection of the conductor inserted Please refer to our tooling and equipment section on page 183-196 for dies and tooling Palm Width Hole Conductor BTN10-M 9 5 10 2 2.95 BTN16-M 9 5 16 2 2.95 BTN25-M 9 5 25 2 3.95 BTN35-M 11.5 6 35 2 3.95 BTN50-M 11.5 6 50 2 3.95 BTN70-M 11.5 6 70 2 4.95 BTN95-M 15.5 8 95 2 6.80 BTN120-M 19 8, 10 120 2 9.20 BTN150-M 19 8, 10 150 2 12.50 BTN185-M 24.5 10 185 2 16.70 BTN240-M 31 10,12,16 240 2 24.00 BTN300-M 31 12 300 2 30.00 1000V Rated Manufactured from electrolytic copper tube to EN 12735 Tested to BS EN 61238 UL Listed CE Approved DEF Standard 59-71 Approved 29
r Gland C Cable Lugs & Connectors LV lugs & SPLICES LV COPPER lugs F Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series D verall ia. B Max Gland Dimensions Braid Approx. Hexagon 1000V Rated Wire Length Dia. C Manufactured D A/C A/F from E electrolytic F copper tube to EN 12735 Tested to BS EN 61238, 4579 & 15.8 0.2 / 0.3 BS 760967 34.0 30.5 20.8 0.2 / 0.3 64 34.0 30.5 27.2 0.2 / 0.45 65 42.2 37.6 33.5 0.3 / 0.45 77 53.6 47.3 39.9 0.3 / 0.45 77 61.5 56.4 52.6 0.3 / 0.45 84 77.2 70.1 65.3 0.3 / 0.45 90 87.4 80.0 78.0 0.3 / 0.45 96 109.2 98.8 88.0 0.3 / 0.45 108 126.0 115.0 E LV copper tube crimping lugs Designed to be crimped onto a conductor to facilitate the termination of the cable via the lug Application > Indoor/Outdoor for Unarmoured Cable hole Copper lugs are electrolytically tin plated to avoid prevent Features corrosion, & Benefits this makes them suitable for temperatures up to 150C > Kit comprises: - A1/A2 Gland Each terminal has a sight hole for visual inspection of the conductor inserted - Brass locknut - PVC shroud Please refer to our tooling and equipment section on page 183-196 for > dies 2 per kit and size up to tooling and including 25 > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof Hole Conductor BT1C 3.5, 5 1.5 2 0.20 Technical Data > EN 50262 > BS6121:Pt 1:1989 > Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface > Service temperature -20 C to +90 C > CuZn39Pb3 extruded brass alloy used for guaranteed strength and performance BT2C 3.5, 4, 5, 6, 8 2.5 2 0.20 BT6C 3.5, 4, 5, 6, 8 4-6 2 0.30 BT10C 5, 6, 8,10 10 2 0.40 BT16C 5, 6, 8,10 16 2 0.45 BT25C 5, 6, 8,10,12 25 2 0.60 BT35C 6, 8,10,12 35 2 0.95 BT50C 6, 8,10,12, 50 2 1.50 BT70C 6, 8,10,12,16 70 2 1.95 BT95C 8,10,12,16 95 2 2.40 BT120C 10,12,16 120 2 2.95 BT150C 10,12,16 150 2 5.95 BT185C 10,12, 16, 20 185 2 6.50 BT240C Ref: A1A2/03/07 Prysmian Cables & 10,12,16, 20 Components Unit, Oak Road, Wrexham +44 (0) 845 767 8345, www.prysmian.co.uk 240 2 Wrexham, LL13 9HP, UK 11.95 Systems Limited, Industrial Estate, Coercial Enquiries, Tel Fax: +44 (0) 23 8029 5465 BT300C 10,12, 16, 20 300 2 14.95 BT400C 16,20 400 2 22.00 BT500C 16, 20 500 2 28.50 BT630C 16, 20, 22 630 2 40.00 BT800C 20 800 2 70.00 BT1000C 22 1000 2 84.00 LV SHEET TERMINALS LV sheet terminals with large stud holes Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series 1000V Rated Manufactured from electrolytic copper tube to EN 12735 Tested to BS EN 61238 Designed to be crimped onto a conductor to facilitate the termination of small diameter cables Application > Indoor/Outdoor for Unarmoured Cable via large lug holes Copper lugs are electrolytically tin plated to avoid prevent Features corrosion, & Benefits making them suitable for temperatures up to 150C > Kit comprises: - A1/A2 Gland Each terminal has a sight hole for visual inspection of the conductor inserted - Brass locknut - PVC shroud Please refer to our tooling and equipment section on page 183-196 for > dies 2 per kit size and up to tooling and including 25 > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof Hole Conductor ST10C 16,20 10 2 4.95 Technical Data > EN 50262 > BS6121:Pt 1:1989 > Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface > Service temperature -20 C to +90 C > CuZn39Pb3 extruded brass alloy used for guaranteed strength and performance ST16C 16,20 16 2 4.95 ST25C 16,20 25 2 6.75 ST35C 16,20 35 2 8.25 ST50C 16,20 50 2 10.90 ST70C 16,20 70 2 12.60 9PH, UK 30 Ref: A1A2/03/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
BARR-X EEx d IIC Brass Barrier Gland C Cable Lugs & Connectors LV lugs & SPLICES LV 2 BOLT COPPER lugs B A F LV 2 bolt copper tube crimping lugs Designed to be crimped onto a conductor to facilitate the termination of the cable via two lug holes Hole A37-2M12 2 x 12 185 2 15.95 ces & Thread s A48-2M12 Cable Dimensions 2 x 12 240 2 Gland Dimensions 19.80 d NPT A60-2M12 Max. Max. No. of 2 x Inner 12 Sheath Overall 300 2 Braid20.50 Approx. Hexagon 1000V Rated A80-2M12 Dia. Over Conductors2 x 12 Dia. A 400 Dia. B Wire Length Design Thread 29.45 Conductors Dia. C D A/C A/F Tested to BS EN 61238 No. A100-2M12 2 x 12 500 2 51.95 E F Min Max Min Max.5 424TX02 Discount ½ - 14 on NPT application11.0 30 11.5 8.0 15.8 0.2 / 0.3 67 34.0 30.5.5 424TX03 ½ - 14 NPT 11.0 30 Industrial Gland 12.5 Kits 11.7 20.8 A1/A2 0.2 / 0.3 Brass Gland 64 Kit 34.0 30.5.5 424TX05 LV ¾ - 214 BOLT NPT COPPER 16.0 lugs42 11.5 18.0 17.0 27.2 0.2 / KM409 0.45 Series 65 42.2 37.6.5 424TX06 1-11½ NPT 22.1 60 17.0 25.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3.5 424TX07 1¼ - 11½ NPT 28.2 100 24.0 31.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4.5 424TX09 2-11½ NPT 37.1 200 30.0 41.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1.5 424TX11 2½ Designed - 8 NPTto be crimped 48.4 onto a conductor 400 to facilitate 40.0 the 54.0 termination 46.5 of 65.3 the cable 0.3 via / 0.45 two lug holes 90 87.4 80.0 Application > Indoor/Outdoor for Unarmoured Cable.5 424TX13 3-8 NPT 58.6 400 53.0 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 Hole Conductor Features & Benefits > Brass indoor and outdoor cable gland & accessories 2 424TX14 3-8 NPT 65.8 400 60.0 74.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof Kit comprises: BT150C12B2 2 x 12 > 150 2 - A1/A2 Gland - Brass locknut 12.95 BT185C12B2 2 x 12 185 2 > - PVC shroud to and including 15.95 25 2 per kit size up supplied 15 long, 2 pitch threads are supplied 20 long ply with new UL2225 BT240C12B2 requirements 2 x 12 240 2 19.80 BT300C12B2 2 x 12 300 2 20.50 BT400C12B2 2 x 12 Technical Data > EN 50262 400 2 > BS6121:Pt 1:1989 29.45 > Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface BT630C12B2 2 x 12 630 2 > Service temperature -20 C 62.90 to +90 C D Conductor A24-2M8 2 x 8 120 2 9.90 A30-2M12 2 x 12 150 2 12.95 A120-2M12 2 x 12 630 2 62.90 A160-2M12 2 x 12 800 2 81.50 LV 2 bolt copper tube crimping lugs BT120C8B2 2 x 8 120 2 9.90 BT500C12B2 2 x 12 500 2 51.95 BT800C12B2 2 x 12 800 2 81.50 performance LV COPPER PIN TERMINAL LV copper reducing pin terminal Designed to be crimped to reduce Conductor size for termination into contact blocks > CuZn39Pb3 extruded brass alloy used for guaranteed strength and E 1000V Rated Tested to BS EN 61238 Pin Diameter Ref: A1A2/03/07 Conductor Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk L10PIN 3.8 10 2 1.90 L16PIN 3.7 16 2 2.10 L25PIN 5 25 2 7.60 L35PIN 5 35 2 7.95 L50PIN 7.5 50 2 8.25 L70PIN 8 70 2 8.75 L95PIN 8 95 2 9.55 L120PIN 10 120 2 12.70 L150PIN 10 150 2 17.60 L185PIN 14 185 2 19.90 L240PIN 14 240 2 26.40 L300PIN 16 300 2 32.95 L400PIN 16 400 2 45.00 1000V Rated Tested to BS EN 12449 n Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 31 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
Brass Barrier Gland Cable Lugs & Connectors LV lugs & SPLICES C B A LV 4 BOLT COPPER lugs D F LV 4 bolt fixing transformer lugs E Designed to be crimped to a conductor to facilitate the termination of a cable onto a transformer Cable Dimensions Max. No. of Inner 1000V Sheath Rated Overall Conductors Dia. A Dia. B Tested to BS EN 61238 Min Max Min Max UL Listed (up to 300 2 ) LV 4 BOLT COPPER lugs Hole Conductor A37-4ESI 4 x 8 185 2 25.20 A48-4ESI 4 x 8 240 2 25.20 A60-4ESI 4 x 8 300 2 25.20 A80-4ESI 4 x 8 400 2 28.70 A100-4ESI Hexagon 4 x 8 500 2 35.00 A120-4ESI 4 x 8 630 2 49.00 A/C A/F A160-4ESI E F 4 x 8 800 2 79.80 A200-4ESI 4 x 8 1000 2 105.00 60 17.0 25.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3 LV 4 bolt fixing transformer lugs 100 24.0 31.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4 200 30.0 41.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1 400 40.0 54.0 46.5 65.3 0.3 / 0.45 90 Designed 87.4 to 80.0 be crimped to a conductor to facilitate the termination of a cable onto a transformer 400 53.0 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 Hole Features & Benefits Conductor 400 60.0 74.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 BT120C8B4 4 x 8 120 2 12.65 Kit comprises: BT150C8B4 4 x 8 150 2 > - A1/A2 Gland - Brass locknut 14.95 supplied 20 long BT185C8B4 4 x 8 185 2 > - PVC shroud to and including 18.10 25 2 per kit size up 1000V Rated Tested to BS EN 61238 Braid Wire Dia. C Gland Dimensions Approx. Length D 30 11.5 8.0 15.8 0.2 / 0.3 67 34.0 30.5 30 12.5 11.7 20.8 0.2 / 0.3 64 34.0 30.5 42 11.5 18.0 17.0 27.2 0.2 / 0.45 65 42.2 37.6 Industrial Gland Kits Application A1/A2 Brass Gland Kit KM409 Series > Indoor/Outdoor for Unarmoured Cable > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof BT240C8B4 4 x 8 240 2 18.40 BT300C8B4 4 x 8 300 2 19.55 BT400C8B4 4 x 8 Technical Data > 400 2 EN 50262 26.45 > BS6121:Pt 1:1989 > Gland rated to IP66 with use of suitable sealing washer or thread sealant BT500C8B4 4 x 8 500 2 27.60 BT630C8B4 4 x 8 630 2 > -20 C 36.80 to +90 C at gland interface Service temperature BT800C8B4 4 x 8 800 2 67.30 BT1000C8B4 4 x 8 performance 1000 2 79.95 > CuZn39Pb3 extruded brass alloy used for guaranteed strength and LV Copper lugs - Angled 90 LV copper tube crimping lugs angled at 90 Designed to be crimped onto a conductor Ref: A1A2/03/07 to facilitate Prysmian Cables the & Systems termination Limited, Components Unit, Oak Road, of Wrexham a cable Industrial Estate, where Wrexham, LL13 9HP, a UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk 90 angle is required. Copper lugs are electrolytically tin plated to avoid oxidation 1000V Rated Tested to BS EN 61238 UL Listed Hole Conductor LR50-M 6, 8, 10, 12 50 2 4.95 LR70-M 8, 10, 12 70 2 5.35 LR95-M 8, 10, 12 95 2 6.50 LR120-M 10, 12 120 2 7.45 LR150-M 10, 12 150 2 16.50 LR185-M 10, 12 185 2 17.95 LR240-M 12 240 2 22.50 LR300-M 12 300 2 35.00 Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 32 45, Fax: +44 (0) 23 8029 5465.uk
BARR-X EEx d IIC Brass Barrier Gland C Cable Lugs & Connectors LV lugs & SPLICES LV COPPER SPLICES B A F LV copper crimp splices D E Designed to be crimped onto same size conductors to connect and create a straight connection ces & Thread s d Design No. Conductor L03-M 1.5 2 0.45 L06-M 2.5 2 0.45 L1-M 4-6 2 0.45 Cable Dimensions L2-M 10 2 0.50 NPT L3-M Max. Max. No. of Inner Sheath Overall 16 2 Braid 0.60 L5-M Dia. Over Conductors Dia. A Dia. 25 B 2 Wire Thread 1.00 Conductors Dia. C L7-M 35 2 1.35 Min Max Min Max L10-M 50 2 1.60 L14-M 70 2 2.25 L19-M 95 2 2.90 L24-M 120 2 3.50 L30-M 150 2 6.10 L37-M 185 2 7.50 L48-M 240 2 9.95 L60-M 300 2 16.00 L80-M 400 2 19.50 L100-M 500 2 40.00 L120-M 630 2 49.00 L160-M 800 2 69.00 L200-M 1000 2 89.00 Gland Dimensions Approx. Hexagon 1000V Rated Length D A/C A/F E Tested F to BS EN 61238 UL Listed.5 424TX02 ½ - 14 NPT 11.0 30 11.5 8.0 15.8 0.2 / 0.3 67 34.0 30.5.5 424TX03 ½ - 14 NPT 11.0 30 12.5 11.7 20.8 0.2 / 0.3 64 34.0 30.5.5 424TX05 ¾ - 14 NPT 16.0 42 11.5 18.0 17.0 27.2 0.2 / 0.45 65 42.2 37.6.5 424TX06 1-11½ NPT 22.1 60 17.0 25.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3.5 424TX07 1¼ - 11½ NPT 28.2 100 24.0 31.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4.5 424TX09 2-11½ NPT 37.1 200 30.0 41.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1.5 424TX11 2½ - 8 NPT 48.4 400 40.0 54.0 46.5 65.3 0.3 / 0.45 90 87.4 80.0.5 424TX13 3-8 NPT 58.6 400 53.0 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 2 424TX14 3-8 NPT 65.8 400 60.0 74.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 supplied 15 long, 2 pitch threads are supplied 20 long Industrial Gland Kits ply with new UL2225 requirements LV COPPER SPLICES A1/A2 Brass Gland Kit KM409 Series LV copper tube crimp splices Designed to be crimped onto same size conductors to connect and create a straight connection Application > Indoor/Outdoor for Unarmoured Cable Features & Benefits Conductor 1CS 1.5 2 0.60 Kit comprises: 2CS 2.5 2 > - A1/A2 Gland - Brass locknut 0.60 > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof 6CS 4-6 2 > - PVC shroud to and including 0.60 25 2 per kit size up 10CS 10 2 1.20 16CS 16 2 1.60 25CS Technical Data 25 2 > EN 50262 1.95 > BS6121:Pt 1:1989 > Gland rated to IP66 with use of suitable sealing washer or thread sealant 35CS 35 2 2.90 50CS 50 2 > -20 C to 3.25 +90 C at gland interface Service temperature 70CS 70 2 4.50 performance 95CS 95 2 4.95 120CS 120 2 6.50 150CS 150 2 8.90 185CS 185 2 10.70 240CS 240 2 19.20 300CS 300 2 23.95 400CS 400 2 26.00 500CS 500 2 44.00 630CS 630 2 55.00 800CS 800 2 Components Unit, Oak Road, Wrexham Wrexham, 75.00 LL13 9HP, UK Ref: A1A2/03/07 Prysmian Cables & Systems Limited, Industrial Estate, > CuZn39Pb3 extruded brass alloy used for guaranteed strength and 1000CS Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk 1000 2 90.00 1000V Rated Tested to BS EN 61238, BS 4579 & BS 7609 UL Listed n Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 33 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
Cable Lugs & Connectors LV lugs & SPLICES LV ALUMINIUM lugs 1000V Rated Tested to BS EN 61238 LV aluminium tube crimping lugs Designed to be crimped onto a conductor to facilitate the termination of the cable via the lug hole Aluminium lugs are made from 99.5% pure aluminium Barrels are capped and filled with grease so as to avoid oxidation of the aluminium Non-circular conductors may require pre-rounding prior to the introduction to the terminal Increased barrel length and internal taper to ease the introduction of the conductor Please refer to our tooling and equipment section on page 183-196 for dies and tooling Conductor AA16-M 8 16 2 7.60 AA25-M 8 25 2 7.70 AA35-M 8, 10 35 2 7.95 AA50-M 12, 14 50 2 8.45 AA70-M 12, 14 70 2 8.95 AA95-M 12, 14 95 2 9.50 AA120-M 12, 14 120 2 9.90 AA150-M 12, 14 150 2 12.00 AA185-M 12, 14 185 2 14.95 AA240-M 12, 14 240 2 15.50 AA300-34-M 12 300 2 16.90 LV ALUMINIUM SPLICES LV aluminium tube crimp splices 1000V Rated Tested to BS EN 61238 CE Approved Designed to be crimped onto same size conductors to connect and create a straight connection Aluminium splices are made from 99.5% pure aluminium They feature a solid stop which creates a barrier between the two conductors Barrels are capped and filled with grease so as to avoid oxidation of the aluminium Non-circular conductors may require pre-rounding prior to the introduction to the splice Increased barrel length and internal taper to ease the introduction of the conductor Please refer to our tooling and equipment section on page 183-196 for dies and tooling Conductor MTMA10-GC 10 2 10.70 MTMA16-GC 16 2 11.40 MTMA25-GC 25 2 12.15 MTMA35-GC 35 2 12.85 MTMA50-GC 50 2 13.60 MTMA70-GC 70 2 14.20 MTMA95-GC 95 2 14.75 MTMA120-GC 120 2 15.20 MTMA150-GC 150 2 17.75 MTMA185-GC 185 2 20.50 MTMA240-GC 240 2 22.50 MTMAD300-GC 300 2 24.70 34
BARR-X EEx d IIC Brass Barrier Gland Cable Lugs & Connectors C HV lugs & SPLICES HV COPPER lugs B A F HV copper tube crimping lugs D E Designed to be crimped onto a conductor to facilitate the termination of the cable via the lug hole HV copper lugs are electrolytically tin plated to avoid oxidation HV copper lugs have a double length barrel for enhanced electrical & mechanical performance. Please refer to our tooling and equipment section on page 183-196 for dies and tooling Conductor ces & Thread s Cable Dimensions Gland Dimensions 2A3-M 6, 8, 10 16 NPT Max. Max. No. of Inner Sheath Overall 2 Braid 6.95 Approx. Hexagon 2A5-M 8, 10, 12 25 2 6.95 33kV rated Dia. Over Conductors Dia. A Dia. B Wire Length d Design Thread 2A7-M Conductors 8, 10, 12 35 2 Dia. C 6.95 D A/C A/F * No. E Tested F to BS EN 61238 2A10-M 10, 12, 14, Min16Max Min 50Max 2 7.95 2A14-M 10, 12, 14, 16 70 UL Listed (up to 300 2 14.95 ) 1.5 424TX02 2A19-M ½ - 14 NPT 11.0 30 10, 12, 14, 16, 20 11.5 8.0 95 15.8 2 0.2 / 0.3 14.95 67 34.0 DEF 30.5 Standard 59-71 Approved 2A24-M 10, 12, 14, 16, 20 120 2 19.00 1.5 424TX03 ½ - 14 NPT 11.0 30 12.5 11.7 20.8 0.2 / 0.3 64 34.0 30.5 2A30-M 10, 12, 14, 16, 20 150 2 19.00 1.5 424TX05 2A37-M ¾ - 14 NPT 16.0 42 12, 14, 16, 11.5 20 18.0 17.0 185 27.2 2 0.2 / 0.45 65 19.00 42.2 37.6 1.5 424TX06 2A48-M 1-11½ NPT 22.1 60 12, 14, 16, 17.02025.0 19.0 24033.5 2 0.3 / 0.45 29.75 77 53.6 47.3 1.5 424TX07 1¼ 2A60-M - 11½ NPT 28.2 10012, 14, 16, 24.0 2031.5 26.5 30039.9 2 0.3 / 0.45 29.75 77 61.5 56.4 1.5 424TX09 2A80-M 2-11½ NPT 37.1 200 12, 14, 16, 30.0 20 41.5 36.0 400 52.6 2 0.3 / 0.45 38.00 84 77.2 70.1 2A100-M 12, 14, 16, 20 500 2 60.00 1.5 424TX11 2½ - 8 NPT 48.4 400 40.0 54.0 46.5 65.3 0.3 / 0.45 90 87.4 80.0 2A120-M 12, 16, 20 630 2 73.00 1.5 424TX13 2A160-M 3-8 NPT 58.6 400 16, 20 53.0 65.5 58.0 800 78.0 2 0.3 / 0.45 96 118.00 109.2 98.8 2 424TX14 2A200-M 3-8 NPT 65.8 400 20 60.0 74.0 68.0 1000 88.0 2 0.3 / 0.45 129.00108 126.0 115.0 e supplied 15 long, 2 pitch threads are supplied 20 Industrial longgland Kits HV COPPER lugs ply with new UL2225 requirements HV copper tube crimping lugs A1/A2 Brass Gland Kit KM409 Series Designed to be crimped onto a conductor to facilitate the termination of the cable via the lug hole Application > Indoor/Outdoor for Unarmoured Cable HV copper lugs are made from 99.5% pure copper > Brass indoor and outdoor cable gland & accessories HV copper lugs are manufactured from thick wall copper Features tube & Benefits and have a polyurethane resin > For circular, unarmoured plastic or rubber sheathed cables block > Suitable for most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland HV copper lugs have a double length barrel for enhanced electrical & mechanical - Brass performance locknut - PVC shroud > 2 per kit size up to and including 25 Please refer to our tooling and equipment section on page 183-196 for dies and tooling Hole Conductor Technical Data > EN 50262 > BS6121:Pt 1:1989 > Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface > Service temperature -20 C to +90 C > CuZn39Pb3 extruded brass alloy used for guaranteed strength and performance BTHW16C 10, 12 16 2 13.50 BTHW25C 10, 12 25 2 14.25 BTHW35C 10, 12 35 2 14.90 BTHW50C 10, 12 50 2 15.95 BTHW70C 10, 12 70 2 22.50 BTHW95C 10, 12, 16 95 2 24.00 BTHW120C 12, 16 120 2 29.55 BTHW150C 12, 16 150 2 33.00 BTHW185C 12, 16 185 2 35.00 BTHW240C 12, 16 240 2 38.95 BTHW300C 12, 16 300 2 41.00 BTHW400C 12, 16, 20 400 2 43.00 BTHW500C 12, 16, 20 Ref: A1A2/03/07 Prysmian Cables 500 2 Components Unit, Oak Road, Wrexham Wrexham, 50.00 LL13 9HP, UK & Systems Limited, Industrial Estate, Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk BTW630C 16, 20 630 2 60.00 BTW800C 16 800 2 80.00 BTW1000C 16 1000 2 110.00 n Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk 33kV rated Tested to BS 4579 35
Brass Barrier Gland Cable Lugs & Connectors HV lugs & SPLICES C B A HV 2 Bolt Copper lugs D HV 2 bolt copper tube crimping lugs E F Designed to be crimped onto a conductor to facilitate the termination of the cable via the 2 lug holes HV copper lugs are electrolytically tin plated to avoid oxidation HV copper lugs have a double length barrel for enhanced electrical & mechanical performance Please refer to our tooling and equipment section on page 183-196 for dies and tooling Cable Dimensions Max. No. of Inner 33kV Sheath rated Overall Conductors Dia. A Dia. B Tested to BS EN 61238 Min Max Min Max UL Listed (up to 300 2 ) Gland Dimensions Approx. Hexagon Length D A/C A/F E F Hole Conductor CA25-2M 8, 12 25 2 13.60 CA35-2M 12 35 2 15.30 CA50-2M 12 50 2 17.00 CA70-2M 12 70 2 29.35 CA95-2M 12 95 2 29.35 30 DEF Standard 11.5 59-71 8.0 Approved 15.8 0.2 / 0.3 67 34.0 30.5 CA120-2M 12 120 2 33.30 30 12.5 11.7 20.8 0.2 / 0.3 64 34.0 30.5 CA150-2M 12 150 2 33.30 42 11.5 18.0 17.0 27.2 0.2 / 0.45 65 CA185-2M 42.2 37.6 12 185 2 33.30 60 17.0 25.0 19.0 33.5 0.3 / 0.45 77 CA240-2M 53.6 47.3 12 240 2 53.45 100 24.0 31.5 26.5 39.9 0.3 / 0.45 77 CA300-2M 61.5 56.4 12 300 2 53.45 2A80-2M 12, 14, 16 400 2 74.00 200 30.0 41.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1 2A100-2M 14, 16 500 2 81.50 400 40.0 54.0 46.5 65.3 0.3 / 0.45 90 87.4 80.0 2A120-2M 14, 16 630 2 96.80 400 53.0 65.5 58.0 78.0 0.3 / 0.45 96 Discount 109.2 on application 98.8 400 60.0 74.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 supplied 20 long HV 2 Bolt Copper lugs 33kV rated Tested to BS 4579 Braid Wire Dia. C HV 2 bolt copper tube crimping lugs Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series Designed to be crimped onto a conductor to facilitate the termination of the cable via the 2 lug Application > Indoor/Outdoor for Unarmoured Cable holes HV copper lugs are made from 99.5% pure copper Features & Benefits > Brass indoor and outdoor cable gland & accessories HV copper lugs are manufactured from thick wall copper tube and have a polyurethane resin > Kit comprises: - A1/A2 Gland block - Brass locknut - PVC shroud HV copper lugs have a double length barrel for enhanced electrical & mechanical > 2 per kit size up to and performance including 25 Please refer to our tooling and equipment section on page 183-196 for dies and tooling Technical Data > EN 50262 > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof Hole Conductor > BS6121:Pt 1:1989 BTHW70C12D 12 70 2 at gland interface POA > Service temperature -20 C to +90 C BTHW95C12D 12 95 2 POA > Gland rated to IP66 with use of suitable sealing washer or thread sealant > CuZn39Pb3 extruded brass alloy used for guaranteed strength and performance BTHW120C12D 12 120 2 POA BTHW150C12D 12 150 2 POA BTHW185C12D 12 185 2 POA BTHW240C12D 12 240 2 POA BTHW300C16D 16 300 2 POA BTHW400C16D 16 400 2 POA BTHW500C16D 16 500 2 POA BTHW630C16D 16 630 2 POA Ref: A1A2/03/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 36 45, Fax: +44 (0) 23 8029 5465.uk
BARR-X EEx d IIC Brass Barrier Gland C Cable Lugs & Connectors HV lugs & SPLICES HV COPPER SPLICES B A F HV copper tube crimping splices D E Designed to be crimped onto same size conductors to connect and create a straight connection HV copper splices are electrolytically tin plated to avoid oxidation HV copper splices have extended tube length for simplified crimping Waterblocked type available on request Please refer to our tooling and equipment section on page 183-196 for dies and tooling ces & Thread s Cable Dimensions Gland Dimensions Conductor NPT Max. Max. No. of Inner Sheath Overall Braid Approx. Hexagon 33kV rated MT16-TD Dia. Over Conductors Dia. A Dia. 16 B 2 Wire11.00Length d Design Thread MT25-TD Conductors 25 2 Dia. C D A/C A/F No. 11.95 E Tested F to BS EN 61238 Min Max Min Max MT35-TD 35 2 13.00 UL Listed (up to 300 2 ) MT50-TD 50 2 14.50.5 424TX02 MT70-TD ½ - 14 NPT 11.0 30 11.5 8.0 7015.8 2 0.2 / 0.3 16.00 67 34.0 DEF 30.5 Standard 59-71 Approved.5 424TX03 MT95-TD ½ - 14 NPT 11.0 30 12.5 11.7 95 20.8 2 0.2 / 0.3 17.30 64 34.0 30.5 MT120-TD 120 2 18.90.5 424TX05 ¾ - 14 NPT 16.0 42 11.5 18.0 17.0 27.2 0.2 / 0.45 65 42.2 37.6 MT150-TD 150 2 19.25.5 424TX06 MT185-TD 1-11½ NPT 22.1 60 17.0 25.0 19.0 185 33.5 2 0.3 / 0.45 77 24.00 53.6 47.3.5 424TX07 1¼ MT240-TD - 11½ NPT 28.2 100 24.0 31.5 26.5 24039.9 2 0.3 / 0.45 32.00 77 61.5 56.4.5 424TX09 MT300-TD 2-11½ NPT 37.1 200 30.0 41.5 36.0 30052.6 2 0.3 / 0.45 35.00 84 77.2 70.1 MT400-TD 400.5 424TX11 2½ - 8 NPT 48.4 400 40.0 54.0 46.5 65.3 2 0.3 / 0.45 45.00 90 87.4 80.0 MT500-TD 500 2 48.00.5 424TX13 3-8 NPT 58.6 400 53.0 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 MT630-TD 630 2 69.50 2 424TX14 Discount 3-8 NPT on application 65.8 400 60.0 74.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 supplied 15 HV long, COPPER 2 pitch SPLICES threads are supplied 20 long ply with new UL2225 requirements HV copper tube crimping splices Designed to be crimped onto same size conductors to connect and create a straight connection Application > Indoor/Outdoor for Unarmoured Cable HV copper lugs are made from 99.5% pure copper HV copper splices have extended tube length for simplified Features crimping & Benefits > Brass indoor and outdoor cable gland & accessories Waterblocked type available on request > Kit comprises: - A1/A2 Gland - Brass locknut Please refer to our tooling and equipment section on page 183-196 for dies and tooling Industrial Gland Kits Conductor A1/A2 Brass Gland Kit KM409 Series > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof - PVC shroud > 2 per kit size up to and including 25 BTH16CS Technical Data 16 2 > EN 50262 11.00 BTH25CS 25 2 > BS6121:Pt 1:1989 11.95 BTH35CS 35 2 at gland interface > Service temperature -20 C 13.00 to +90 C BTH50CS 50 2 14.50 performance BTH70CS 70 2 16.00 BTH95CS 95 2 17.30 BTH120CS 120 2 18.90 BTH150CS 150 2 19.25 BTH185CS 185 2 24.00 BTH240CS 240 2 32.00 BTH300CS 300 2 35.00 BTH400CS 400 2 45.00 BTH500CS 500 2 48.00 BTH630CS 630 2 Components Unit, Oak Road, Wrexham Wrexham, 69.50 LL13 9HP, UK Ref: A1A2/03/07 Prysmian Cables & Systems Limited, Industrial Estate, Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk > Gland rated to IP66 with use of suitable sealing washer or thread sealant > CuZn39Pb3 extruded brass alloy used for guaranteed strength and 33kV rated Tested to BS 4579 n Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 37 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
Cable Lugs & Connectors LV MECHANICAL lugs LV Brass Mechanical lugs LV brass mechanical lugs for use on copper/aluminium conductors Designed to be connected onto a conductor to facilitate the termination of the cable without the need for crimping. Low torque shear head bolts. Blocked barrel to prevent water ingress Range taking Designed to meet BS 4579 and Engineering Recoendation C79 MECHANICAL LUGS DATA Stud Conductor BET35C 12, 16 up to 35 2 7.50 BET60C 12, 16 up to 60 2 9.50 BET120C 12, 16 up to 120 2 17.90 L W Dimensions Maximum Conductor Installation Tool L H W 2 BET35C 55 25 20 35 3 allen BET60C 70 34 25 60 13 socket BET120C 86 46 28 120 16 socket I LV Aluminium Mechanical lugs LV aluminium mechanical lugs for use on solid sectoral aluminium conductors Designed to be connected onto a conductor to facilitate the termination of the cable without the need for crimping Low torque shear head bolts Solid moisture block between palm and barrel Range taking Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 1000V Rated 40 36 49 35-95 13 Designed to meet BS 4579 3 and Engineering Recoendation C79 54 45 66 35-185 19 54 52 77 70-300 19 MECHANICAL LUGS DATA I D W Stud Dimensions L I D W Conductor Spanner or Socket A/F LVET120 86 40 28 32 13 LVET185 104 56 35 39 19 LVET300 116 56 41 43 19 LVET120 12, 16 95-120 2 16.00 LVET185 12, 16 120-185 2 20.00 LVET300 12, 16 240-300 2 24.00 able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. L DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A 38 Our coitment. Your advantage.
BARR-X EEx d IIC Brass Barrier Gland Cable Lugs & Connectors C LV MECHANICAL CONNECTORS LV Mechanical Connectors - Straight B A F LV mechanical connector for inline joints Designed to facilitate a simple connection between conductors inline without the need for crimping Shear bolt technology to ensure a good electrical connection Can be used as a transition connector between cables with different conductor constructions D E Manufacturer Conductor nces & Thread s Cable Dimensions Gland Dimensions JP1 Tyco up to 35 2 4.50 NPT Max. Max. No. of Inner Sheath Overall MCB25 Tyco 4-25 2 Braid Approx. Hexagon 13.50 Dia. Over Conductors Dia. A Dia. B Wire Length ad Design MCB50 Thread Conductors Tyco 10-50 2 Dia. 14.25 C D A/C A/F * No. MCB70 Tyco 10-70 2 E F Min Max Min Max 15.30 UST95 Tyco 35-95 2 16.95 1.5 UST185 Tyco 35-185 2 26.50 424TX02 ½ - 14 NPT 11.0 30 11.5 8.0 15.8 UST300 Tyco 70-300 2 0.2 / 0.3 29.00 67 34.0 30.5 1.5 424TX03 UST400 ½ - 14 NPT 11.0Tyco 30 12.5 185-400 11.7 20.8 2 0.2 / 35.00 0.3 64 34.0 30.5 1.5 424TX05 BM95M ¾ - 14 NPT 16.0 Prysmian 42 11.5 18.0 16-95 17.0 27.2 2 0.2 / 18.00 0.45 65 42.2 37.6 1.5 424TX06 BM185M 1-11½ NPT 22.1 Prysmian 60 17.0 25.0 16-185 19.0 33.5 2 0.3 / 26.20 0.45 77 53.6 47.3 BM300M Prysmian 95-300 2 29.95 1.5 424TX07 1¼ - 11½ NPT 28.2 100 24.0 31.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4 ALL PAGE 39 - NOT DRAWN AT 100% 1.5 424TX09 2-11½ NPT 37.1 200 30.0 41.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1 THIS IS 50% T 1.5 424TX11 2½ - 8 NPT 48.4 400 40.0 54.0 46.5 65.3 0.3 / 0.45 90 87.4 80.0 JP1 DATA 1.5 424TX13 3-8 NPT 58.6 400 53.0 Dimensions 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 Reference 2 424TX14 3-8 NPT 65.8 A 400 60.0 74.0 B 68.0 88.0 0.3 / C0.45 108 126.0 115.0 JP1 14.5 24 20 re supplied 15 long, 2 pitch threads are supplied 20 long mply with new UL2225 requirements MCB DATA Dimensions PAGE 40 - NOT DRAWN AT 100% Reference THIS IS 67% Length Height ALL PAGE 39 - NOT DRAWN Width AT 100% MCB25 38 14 12 MCB50 45 THIS 16 IS 50% 14 THIS IS 100% Length THIS Width IS 44% MCB70 ALL 53 PAGE 39 - NOT DRAWN 18 AT 100% 16 Tyco Electronics UK Ltd Energy Division Freebournes Road THIS IS 50% Witham, Essex CM8 3AH Phone: +44 (0)870 870 7500 ian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, Fax: +44 (0)870 LL13 9PH, 240 5289 UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 http://energy.tycoelectronics.com www.prysmian.co.uk THIS IS 50% THIS IS 100% THIS IS 44% UST DATA THIS IS 60% Reference PN TCPN Dimensions () Conductor size Socket/ L H W `L' ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 'C' BAH-023000024 'A' 416318-000 54 52 77 70-300 19 Dimensions Reference L H W UST95 80 25 25 PAGE 42 - NOT DRAWN AT 100% UST185 108 32 34 THIS IS 50% `W' UST300 ALL PAGE 39 - NOT DRAWN 108 AT 100% 36 40 UST400 108 'C' 'A' 47 41 THIS IS 50% THIS IS 100% PAGE 40 - NOT DRAWN THIS AT IS 100% 44% THIS IS 60% PAGE 40 - NOT DRAWN AT 100% `W' THIS IS 67% `L' THIS IS 53% BM DATA PAGE 40 - NOT DRAWN Dimensions AT 100% PAGE 40 - NOT DRAWN AT 100% Reference Length THIS IS 67% Height Width THIS IS 53% BM95 80 26 30 PAGE 43 - NOT DRAWN AT 100% BM185 110 31 37.5 Length Width THIS IS 60% 'C' 'A' BM300 110 36 44 'B' PAGE 40 - NOT DRAWN AT 100% THIS IS 67% 'B' PAGE 42 - NOT DRAWN AT 100% While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations `W' are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division PAGE economical 40 solutions - NOT for the DRAWN electrical power AT industry: 100% cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Email: ukutilities@tycoelectronics.com 39 'B' PAGE 42 - NOT DRAWN AT 100% THIS IS 50% THIS IS 53% `H' PAGE 43 - NOT DRAWN AT 100% `H' 'D' PAGE 42 - NOT DRAWN AT 100% THIS IS 45% 'C' 'L' 'A' Our coitment. Your advantage. 'B' DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A PAGE 42 ' I -' NOT DRAWN AT 100% THIS IS 45% All PAGE 45 - NOT DRAWN AT 100% THIS IS 67% `H' PAGE 44 - NOT DRAWN AT 100% `L' Height Height PAG THIS
Brass Barrier Gland Cable Lugs & Connectors LV MECHANICAL CONNECTORS C B A lv MECHANICAL CONNECTORS - BRANCH F LV mechanical connector for branch joints D E ALL PAGE 39 - NOT DRAWN AT 100% THIS IS 50% THIS IS 100% Designed to facilitate THIS a simple IS 44% connection between THIS conductors IS 60% in branch formation without the need for crimping `L' Shear bolt technology to ensure a good electrical connection Can be used as a transition connector between cables with different conductor constructions 'B' Conductor Cable Dimensions Gland Dimensions 'C' 'A' BM95B 35-95 2 19.30 ax. No. of Inner Sheath Overall Braid Approx. Hexagon onductors Dia. A Dia. B Wire LengthBM185B `W' 16-185 2 28.00 Dia. C D BM300B A/C A/F 95-300 2 32.00 E F PAGE Min 40 - NOT MaxDRAWN Min AT Max 100% Discount on PAGE application 40 - NOT DRAWN AT 100% THIS BRANCH IS 67% JOINT CONNECTORS DATA THIS IS 53% Dimensions 30 11.5 8.0 15.8 0.2 / 0.3 67 Reference 34.0 30.5 Length Height Width 30 12.5 11.7 20.8 0.2 / 0.3 64 34.0 30.5 BM95B 40 40 57 42 11.5 18.0 17.0 27.2 0.2 / 0.45 65 BM185B 42.2 37.6 55 49 72 60 17.0 25.0 19.0 33.5 0.3 / 0.45 77 BM300B 53.6 47.3 55 57 84 100 24.0 31.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4 200 30.0 Length 41.5 36.0 Width 52.6 0.3 / 0.45 84 77.2 70.1 400 40.0 54.0 46.5 65.3 0.3 / 0.45 90 87.4 80.0 PAGE 42 - NOT DRAWN AT 100% PAGE 42 - NOT DRAWN AT 100% 400 THIS IS 53.0 50% 65.5 58.0 78.0 0.3 / 0.45 96 THIS 109.2IS 45% 98.8 400 60.0 74.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 LV Mechanical Connectors - Branch Height `H' PAGE 43 - NOT DRAWN AT 100% THIS IS 80% upplied 20 long PAGE 43 - NOT DRAWN AT 100% THIS IS 60% LV mechanical connector for branch joints Designed to facilitate a simple connection between conductors in branch formation without the need PAGE for 44 crimping - NOT DRAWN AT 100% Shear THIS bolt IS 67% technology to ensure a good electrical connection Can be used as a transition connector between cables with different conductor constructions 'D' ' I ' 'L' Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 THIS IS 67% 54 45 66 35-185 19 54 52 77 70-300 19 L H All PAGE 45 - NOT DRAWN AT 100% BRANCH JOINT CONNECTORS DATA 'D' ' I ' All PAGE 46 - NOT ' DRAWN AT 100% THIS IS 53% W Reference Dimensions L H W Conductor Conductor 2 Socket/ Spanner A/F UBR95 40 38 50 35-95 13 UBR185 54 42 67 35-185 19 UBR300 54 54 78 70-300 19 JP1 up to 35 2 4.50 UBR95 35-95 2 18.00 UBR185 35-185 2 26.00 UBR300 70-300 2 28.75 able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 40 5, Fax: +44 (0) 23 8029 5465 Our coitment. Your advantage. k
Cable Lugs & Connectors HV MECHANICAL lugs & CONNECTORS HV Mechanical lugs - 11-42KV HV mechanical lug for copper & aluminium conductors Designed to be connected onto a conductor to facilitate the termination of the cable without the need for crimping High tensile tin plated aluminium alloy Shear bolt technology to ensure a good electrical connection Solid moisture block between palm and barrel Smooth profile prevents damage to insulation or sealing sleeves No elongation during installation Wide application range 42KV Rated Compact design Designed to meet BS 4579 1 Larger sizes available on request. ALL PAGE 39 - NOT DRAWN AT 100% For solid copper and aluminium conductors please contact your nearest sales office THIS IS 50% THIS IS 100% THIS IS 44% THIS IS 60% Stud Conductor Type Conductor `L' BLMT-25/95 12, 16 Cu / Ali 25-95 2 9.95 BLMT-35/150 12, 16 Cu / Ali 35-150 2 13.50 BLMT-95/240 12, 16 Cu / Ali 95-240 2 18.70 BLMT-120/300 12, 16 Cu / Ali 120-300 2 20.00 BLMT-185/400 12, 16, 20 'C' Cu / Ali 'A' 185-400 2 29.95 BLMT-500/630 12, 16, 20 Cu / Ali 500-630 2 55.00 BLMT-800 20 Cu / Ali 800 2 143.00 PAGE 40 - NOT DRAWN AT 100% THIS IS 67% 'B' `H' `W' PAGE 40 - NOT DRAWN AT 100% THIS IS 53% MECHANICAL LUGS DATA AF LB L1 L2 D2 D1 Conductor Hole Dimensions Contact bolts PAGE 42 - NOT DRAWN AT 100% PAGE 42 - NOT DRAWN AT 100% Range Head size AF THIS IS 2 LB50% THIS IS 45% L1 L2 D1 D2 Quantity BLMT-25/95-13 25-95 13 60 30 24 12.8 1 13 BLMT-25/95-17 25-95 17 60 30 24 12.8 1 13 BLMT-35/150-13 35-150 13 86 35 28 15.8 1 17 BLMT-35/150-17 35-150 17 86 35 28 15.8 1 17 BLMT-95/240-13 95-240 13 112 60 33 20 2 19 BLMT-95/240-17 95-240 17 112 60 33 20 2 19 BLMT-120/300-13 120-300 PAGE 43 13 - NOT DRAWN PAGE 44 - NOT DRAWN AT 100% 115 AT 100% 65 37 THIS IS 67% 24 2 22 THIS IS 60% BLMT-120/300-17 120-300 17 115 65 37 24 2 22 BLMT-185/400-13 185-400 13 137 80 42 25.5 3 22 Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 BLMT-185/400-17 185-400 17 137 80 42 25.5 3 22 BLMT-185/400-21 185-400 21 137 80 42 25.5 3 22 BLMT-500/630-13 500-630 13 ' I ' 150 95 50 33 3 27 BLMT-500/630-17 500-630 17 'L' 150 95 50 33 3 27 BLMT-500/630-21 500-630 21 150 95 50 33 3 27 BLMT-800 800 All PAGE 20 45 - NOT DRAWN 227 AT 100% 177 THIS IS 67% 56 36 4 27 'D' 'D' ' I ' While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 41 All PAGE 46 - NOT ' DRAWN AT 100% THIS IS 53% http://energy.tycoelectronics.com Our coitment. Your advantage. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A
Cable Lugs & Connectors HV MECHANICAL lugs & CONNECTORS HV Mechanical Connectors - 11-36KV ALL PAGE 39 - NOT DRAWN AT 100% HV mechanical connectors for copper & aluminium conductors THIS IS 50% THIS IS 100% THIS IS 44% THIS IS 60% 'C' 'A' 'B' `L' Designed to connect two HV conductors inline without the need for crimping High tensile tin plated aluminium alloy Solid moisture block between conductors Larger sizes available on request. `H' Conductor size based on circular stranded copper and aluminium 36kV Rated PAGE 40 - NOT DRAWN AT 100% THIS IS Tested 67% to IEC61238-1 PAGE MECHANICAL 42 - NOT DRAWN LUGS DATA AT 100% THIS IS 50% AF Conductor Type Conductor BSMB-10/35 PAGE 40 - NOT DRAWN AT 100% Cu / Ali 10-35 2 9.95 BSMB-25/95 THIS IS 53% Cu / Ali 25-95 2 14.50 BSMB-35/150 Cu / Ali 35-150 2 18.50 BSMB-95/240 Cu / Ali 95-240 2 25.90 BSMB-120-300 Cu / Ali 120-300 2 29.00 BSMB-185/400 Cu / Ali 185-400 2 37.00 BSMB-500 Cu / Ali 500 2 48.50 BSMB-630 Cu / Ali 630 2 79.00 BSMB-800 Cu / Ali 800 2 128.00 PAGE 42 - NOT DRAWN AT 100% THIS IS 45% Cross-sectional range 2 Blocked `W' PAGE 43 - NOT DRAWN AT 100% THIS IS 80% Dimensions L1 L2 D1 D2 BSMB-10/35 10-35 yes 45 20 19 8.5 BSMB-35/150 35-150 yes 80 35 28 15.8 L2 L2 D2 BSM-95/240 95-240 yes 125 60 33 20 L1 D1 BSMB-120/300 120-300 yes 140 65 37 24 BSM-185/400 185-400 yes 170 80 42 25.5 PAGE 43 - NOT DRAWN AT 100% PAGE 44 - NOT DRAWN AT 100% BSMB-500 500 yes 190 90 46 30 THIS IS 60% THIS IS 67% IS IS 100% THIS IS 44% THIS BSMB-630 IS 60% 630 yes 200 95 50 33 BSMB-800 800 yes 270 130 56 36 Dimensions () Conductor size Socket/ L H THIS W IS 67% ( 2 ) spanner `W' A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 70-300 19 able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty THIS regarding IS 45% the information contained AF2 ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. 42 'D' HV ReducING Mechanical Connectors - 11-36KV All PAGE 45 - NOT DRAWN AT 100% 'D' TECHNICAL ' I ' DATA All PAGE 36kV 46 - Rated NOT ' DRAWN AT 100% THIS IS 53% Tested to IEC61238-1 PAGE MECHANICAL 42 - NOT CONNECTORS DRAWN AT 100% DATA D2 ' I ' 'L' `H' PAGE 40 - NOT DRAWN AT 100% THIS IS 53% L2 L1 Our coitment. Your advantage. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A PAGE 44 - NOT DRAWN AT 100% THIS IS 67% `L' L2 AF1 D1 HV reduction mechanical connectors for copper & aluminium conductors Designed to connect dissimilar sized HV conductors inline without the need for crimping High tensile tin plated aluminium alloy with solid moisture block between conductors Conductor size based on circular stranded copper and aluminium Conductor Type PAGE 43 - NOT DRAWN AT 100% THIS IS 80% Conductor Range Product 2 Blocked reference Conductor Dimensions BSMB-25/95-95/240 Cu / Ali 25-95 2 / 95-240 2 34.00 BSMB-95/240-185/400 Cu / Ali 95-240 2 / 185-400 2 49.00 BSMB-185/400-500 Cu / Ali 185-400 2 / 500 2 84.00 BSMB-185/400-630 Cu / Ali 185-400 2 / 630 2 87.00 BSMB-500/630 Cu / Ali 500 2 / 630 2 89.00 Side 1 Side 2 L1 L2 D1 D2 D3 D4 BSMB25/95-95/240 25-95 95-240 yes 125 60 24 12.8 33 20 BSMB95/240-185/400 95-240 185-400 yes 170 80 33 20 42 25.5 BSMB185/400-500 185-400 500 yes 190 90 42 25.5 46 30 BSMB185/400-630 185-400 630 yes 200 95 42 25.5 50 33 BSMB500-630 500 630 yes 200 95 46 30 50 33
ALL PAGE 39 - NOT DRAWN AT 100% Cable Lugs & Connectors HV MECHANICAL lugs & CONNECTORS THIS IS 50% THIS IS 100% THIS IS 44% THIS IS 60% HV MECHANICAL LUGS - UP TO 33KV `L' HV 2 bolt mechanical lug for copper & aluminium conductors 'C' 'A' 'B' Designed to be connected onto a conductor to facilitate the termination of the cable without `W' the need for crimping PAGE Shear 40 bolt - NOT technology DRAWN to ensure AT 100% a good electrical connection PAGE 40 - NOT DRAWN AT 100% THIS Solid IS moisture 67% block between palm and barrel THIS IS 53% `H' Hole Spacing Conductor Type Conductor VETB21-OHUTB 44 Cu / Ali 50-185 2 34.40 VETB28-OHUTB 44 Cu / Ali 185-400 2 68.70 VETB33-OHUTB 44 Cu / Ali 400-630 2 109.00 VETB37-OHUTB 44 Cu / Ali 800 2 148.00 PAGE 42 - NOT DRAWN AT 100% THIS IS 50% PAGE 42 - NOT DRAWN AT 100% THIS IS 45% 33kV Rated Designed to meet BS4579 1 MECHANICAL PAGE CONNECTORS 43 - NOT DRAWN DATA AT 100% THIS IS 80% B L ALL PAGE 39 - NOT DRAWN AT 100% THIS IS 50% HC 44 End Termination Dimensions PAGE 43 - NOT DRAWN AT 100% PAGE 44 - NOT DRAWN AT 100% L B HC Bore Dia Bore Depth Palm Hole Dia VETB21-OHUTB THIS IS 60% THIS IS 67% 148.5 62 25 21.0 59.5 13.0 VETB28-OHUTB 164 73 24.9 28.0 65.5 'C' 13.0'A' VETB33-OHUTB 157.5 70 25 33.5 65.5 13.0 VETB37-OHUTB 200 94 35 37.5 84.0 13.0 ' I ' PAGE 40 - NOT DRAWN AT 100% 'L' THIS IS 67% 'D' HV Mechanical Connectors - SPLIT BLOCKED - UP to 33KV All HV PAGE mechanical 45 - NOT connectors DRAWN AT 100% for copper & aluminium conductors THIS IS 67% Designed to be connect two HV conductors inline without bending the cable to make the connection Shear bolt technology to ensure a good electrical connection. Solid moisture block between palm and barrel 'D' V interface ensures alignment and reduces connector resistance ' I ' All PAGE 46 - NOT ' DRAWN AT 100% THIS Conductor Type Conductor IS 53% Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 THIS IS 50% 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 Dimensions While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any ' I incidental, ' indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended 'L' application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. L ØD I VTPB21-UTB 148 41 62 VTPB27-UTB 174 47 74 VTPC28-UTB 173 47 74 VTPC36-UTB 178 55 76 Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 43 http://energy.tycoelectronics.com VTPB21-UTB Cu / Ali 50-240 2 61.00 VTPB27-UTB Cu / Ali 95-300 2 79.70 VTPC28-UTB Cu 120-400 2 107.50 VTPC36-UTB Cu 400-645 2 205.00 33kV Rated Designed to meet BS 4579 1 PAGE 43 - NOT DRAWN AT 100% MECHANICAL THIS IS 60% LUGS DATA Our coitment. Your advantage. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A 'B' PAGE 42 - NOT DRAWN AT 100% 'D' All PAGE 45 - NOT DRAWN AT 100% THIS IS 67% 'D'
Cable Lugs & Connectors HV MECHANICAL lugs & CONNECTORS HV MECHANICAL LUGS - up to 72kv 72kV Rated Contact technology type tested electrically and mechanically to iec 61238-1 Up to 30% increased contact force compared to conventional type terminals SICON HV mechanical lug for copper and aluminium conductors New from Pfisterer is the Stepless shear bolt Lug. The special design feature has no predetermined breaking point allowing the bolt to shear evenly no matter the cross sectional area. Large clamping range Suitable for use on copper or aluminium conductors Conductor channels with transverse grooves and protection against conductor oxidisation Blind hole designed as pressure-resistant oil barrier for oil cable Compact design, rounded edges and flat transitions, suitable for slide on and shrink sleeves Centring sleeves Bolt base plate for uniform friction and increased contact force Nothing protrudes, no need for filing Full utilisation of the thread loading for any size of conductor Suitable for fine stranded class 5 cables Smooth breaking of the shear bolt simplifies tightening process No need for specialist tooling Suitable for use with most 3M joints 11 & 33KV - contact our sales team for more information Axial type lug (centralised palm) also available Conductor size based on circular stranded copper and aluminium For other conductor types please refer to table below SICON CONNECTORS DATA Hole Conductor 332 604 010 13 10-95 2 14.75 332 599 010 13 25-150 2 15.20 332 595 010 13 50-185 2 18.55 332 595 011 16 50-185 2 20.34 332 605 010 13 95-300 2 23.25 332 605 011 16 95-300 2 25.50 332 625 010 12 185-400 2 51.15 332 625 011 16 185-400 2 55.20 332 606 010 16 300-630 2 76.80 dø DØ 2 1 L1 L1 DØ dø 332 604 010 10-95 2 10-95 2 50-95 2 35-70 2 10-95 2 70 24 13 332 599 010 25-150 2 25-150 2 35-120 2 35-120 2 25-150 2 91 28 16.3 332 595 010 50-240 2 50-185 2 50-185 2 50-150 2 50-240 2 115 33 20 332 595 011 50-240 2 50-185 2 50-185 2 50-150 2 50-240 2 115 33 20 332 605 010 95-400 2 95-300 2 95-240 2 95-240 2 95-300 2 120 38 24 332 605 011 95-400 2 95-300 2 95-240 2 95-240 2 95-300 2 120 38 24 332 625 010 185-500 2 185-400 2 185-240 2 185-240 2 185-400 2 138 42 26 332 625 011 185-500 2 185-400 2 185-240 2 185-240 2 185-400 2 138 42 26 332 606 010 300-800 2 300-630 2-300-400 2 300-630 2 180 50 33.3 44
Cable Lugs & Connectors HV MECHANICAL lugs & CONNECTORS HV MECHANICAL CONNECTORS - STRAIGHT - up TO 72kv SICON HV straight mechanical connectors for copper and aluminium conductors Suitable for use on copper or aluminium conductors Smooth breaking of the shear bolt simplifies tightening process Suitable for use with most 3m joints 11 & 33kV - contact our sales team for more information Conductor size based on circular stranded copper and aluminium For other conductor types please refer to table below Conductor Range 332 601 010 10-95m 2 11.55 332 607 010 (2 bolt) 25-150 2 11.70 332 593 010 (4 bolt) 25-150 2 16.40 332 592 010 50-185 2 18.30 332 614 010 50-240 2 23.85 332 602 010 95-300 2 28.50 332 617 010 185-400 2 62.70 332 603 010 300-630 2 94.00 72kV Rated Contact technology type tested electrically and mechanically to iec 61238-1 Up to 30% increased contact force compared to conventional type terminals BLOCKED STRAIGHT CONNECTORS DATA dø DØ 1 2 4 3 L1 L1 DØ dø 332 601 010 10-95 2 10-95 2 50-95 2 35-70 2 10-95 2 65 24 13 332 607 010 25-150 2 25-150 2 35-120 2 35-120 2 25-150 2 68 28 16.3 332 593 010 25-150 2 25-150 2 35-120 2 35-120 2 25-150 2 102 28 16.3 332 592 010 50-240 2 50-185 2 50-185 2 50-150 2 50-240 2 126 33 20 332 614 010 50-240 2 50-240 2 50-240 2 50-240 2 50-240 2 126 35 21 332 602 010 95-400 2 95-300 2 95-240 2 95-240 2 95-300 2 140 38 24 332 617 010 185-500 2 185-400 2 185-240 2 185-240 2 185-400 2 170 42 26 332 603 010 300-800 2 300-630 2-300-400 2 300-630 2 230 50 33.3 hv mechanical connectors - branch - up to 72kv SICON HV branch mechanical connectors for copper and aluminium conductors Suitable for use on aluminium or copper conductors Compact design, rounded edges and flat transitions, suitable for slide on and shrink sleeves Conductor size based on circular stranded copper and aluminium For other conductor types please refer to table below Conductor Range 332 447 010 50-185 2 57.60 L1 DØ dø 332 447 010 50-240 2 50-185 2 50-185 2 50-150 2 50-240 2 162 68/33 20 72kV Rated Contact technology type tested electrically and mechanically to iec 61238-1 BRANCHED CONNECTORS DATA DØ dø L1 45
T DRAWN AT 100% T DRAWN AT 100% Cable THIS IS Lugs 100% & Connectors THIS IS 44% THIS IS 60% THIS IS 100% THIS IS 44% THIS IS 60% 'A' ' 'B' 'B' `L' HV MECHANICAL lugs AND CONNECTORS `L' PAGE PAGE 42 42 - NOT NOT DRAWN DRAWN AT AT 100% 100% THIS THIS IS IS 50% 50% HV Mechanical Connectors - up to 72KV PAGE PAGE 42 42 - NOT NOT DRAWN DRAWN AT AT 100% 100% THIS THIS IS IS 45% 45% `W' HV `W' mechanical connectors for copper & aluminium conductors PAGE PAGE 43 43 - NOT NOT DRAWN DRAWN AT AT 100% 100% THIS THIS IS IS 80% 80% RAWN AT 100% PAGE 40 - NOT DRAWN 100% AWN AT 100% PAGE 40 - NOT DRAWN AT 100% THIS IS 53% Designed to be connected onto a conductor to facilitate the termination of the cable without PAGE PAGE 43 43 - NOT NOT DRAWN DRAWN AT AT 100% 100% THIS IS 53% PAGE PAGE 44 44 - NOT NOT DRAWN DRAWN AT AT 100% 100% the need for crimping THIS THIS IS IS 60% 60% THIS THIS IS IS 67% 67% High tensile tinned aluminium alloy Shear bolt technology to ensure a good electrical connection Solid moisture block between palm and barrel ' I ' 'L' 'L' Fast & safe installation Variety of different palms available 72kV Rated PAGE 43 - NOT DRAWN AT 100% AWN AT 100% All All PAGE PAGE 45 45 - NOT NOT DRAWN DRAWN PAGE AT AT 42 100% 100% - NOT DRAWN AT 100% PAGE 43 - NOT DRAWN AT 100% WN AT 100% Tested to IEC61238-1 Description THIS THIS IS IS 67% 67% PAGE 42 - NOT DRAWN AT 100% THIS IS 80% THIS IS 45% THIS IS 80% THIS IS 45% EPPA-052-xx/XX Cable Lug Single Hole M18 POA EPPA-051-xx/XX Cable Lug 2 Hole Palm M17 POA EPPA-054-xx/XX Cable Lug 4 Hole Palm M18 POA EPPA-047-xx/XX Straight Connection POA EPPA-047-xx/XX-yy/YY Transition POA ' I ' AWN AT 100% PAGE 44 - NOT DRAWN AT 100% WN AT 100% MECHANICAL lugs DATA All All PAGE PAGE 46 46 - NOT NOT ' DRAWN DRAWN PAGE THIS AT AT 44 IS 100% 100% - NOT DRAWN AT 100% 67% EPPA-052 THIS THIS IS IS 53% 53% THIS IS 67% L Dimensions B L A B D E F D EPPA-052-XX/XX 190 100 50 18 25 64 F X, Y according to cable dimensions 'D' 'D' 'D' 'D' A `H' `H' Y X DRAWN AT 100% RAWN AT 100% EPPA-051 F L C A D B E Dimensions L A B C D E F EPPA-051-XX/XX 190 100 27.5 45 18 25 64 X, Y according to cable dimensions Y X E DRAWN AT 100% RAWN AT 100% Dimensions () Conductor size Socket/ L H W EPPA-054( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 E 54 52 77 70-300 19 L D Y A X F C B A Dimensions EPPA-054-XX/XX L A B C D E F Contact plate 100 x 100 190 100 27.5 45 18 25 64 Contact plate 80 x 80 212 80 17.5 25 45 14.5 112 X, Y according to cable dimensions EPPA-047 able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any Y reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding X the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. L DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Dimensions L L EPPA-047-XX/XX 130 180 X, Y according to cable dimensions 46 Our coitment. Your advantage.
Cable Cleats CONTENTS Product Selection Table 48 Plastic Cable Cleats 49 Aluminium Cable Cleats 53 Multiple Cable Cleats 57 Accessories 61 47
Cable Cleats PRODUCT SELECTION TABLE CABLE GLAND & CLEAT SELECTOR FOR XLPE/SWA/PVC AND LSF 600/1000 VOLT POWER CABLES CABLE SPEC CLEATS GLANDS Conductor Area 2 Number of cores Telcleats 385AA Hook Cleats 371AA Aluminium Claw Cleats 370BA Plastic LSF Cleats E Aluminium Cleats SW1/2B BW Indoor CW Indoor/ Outdoor E1W E1WF 1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300 400 2 1-1 0-20S 20SS 20SS 3 1-1 0-20S 20SS 20SS 4 1-1 0-20S 20S 20S 7 2-2 1 2 20S 20S 20S 12 3-3 2 3 20 20 20 19 4-4 3 4 25 25 25 27 5-5 4 5 25 25 25 37 6 5 6 5 6 32 32 32 48 6 5 6 5 6 32 32 32 2 1-2 0 2 20S 20S 20S 3 1-2 1 2 20S 20S 20S 4 2-2 1 2 20S 20S 20S 7 2-3 2 3 20 20 20 12 4-4 3 4 25 25 25 19 5-5 4 5 25 25 25 27 6 5 6 5 6 32 32 32 37 6 5 6 6 6 40 40 40 2 2-2 1 2 20S 20S 20S 3 2-2 1 2 20 20 20 4 3-3 2 3 20 20 20 2 3-3 2 3 20 20 20 3 3-3 2 3 20 20 20 4 4-4 3 4 20 20 20 2 4-4 3 4 25 25 25 3 4-4 3 4 25 25 25 4 4-5 4 5 25 25 25 2 4-4 3 4 25 25 25 3 4-5 4 5 25 25 25 4 5 5 6 4 6 25 25 25 2 4-4 4 4 25 25 25 3 5 5 6 5 6 32 32 32 4 6 5 6 5 6 32 32 32 2 5-5 5 5 32 32 32 3 5 5 6 5 6 32 32 32 4 6 5 6 5 6 32 32 32 2 5 5 6 5 6 32 32 32 3 6 5 6 5 6 32 32 32 4 6 5 6 6 6 40 40 40 2 6 5 6 5 6 32 32 32 3 6 6 7 6 7 40 40 40 4 7 6 7 7 7 40 40 40 2 6 6 7 6 7 40 40 40 3 7 6 7 7 7 40 40 40 4 8 7 8 7 8 50 50 50S 2 7 6 7 6 7 40 40 40 3 7 7 8 7 8 50 50 50S 4 8 8 9 8 9 50 50 50 2 7 7 8 7 8 50 50 50S 3 8 8 9 8 9 50 50 50S 4-9 10 9 10 50 50 50 2 8 8 9 8 9 50 50 50S 3 8 9 9 9 9 50 50 50 4-9 10 10 10 63 63 63S 2 8 8 9 8 9 50 50 50 3-9 10 10 10 63 63 63S 4-10 11 11 11 63 63 63 2-9 10 9 10 63 63 63S 3-10 11 11 11 63 63 63 4-11 12 12 12 75 75 75S 2-10 11 10 11 63 63 63 3-11 12 12 12 75 75 75S 4-12 13 14 13 75 75 75 Gland size recoendations only apply to Prysmian Glands - as stocked by Jointing Technologies 48
BARR-X EEx d IIC Brass Barrier Gland C Cable Cleats PLASTIC CABLE CLEATS TELCLEATS Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series B A F Indoor for 10-51 diameter cables Light duty wrap around cleat Overlapping self adjusting ranges Gland Details One piece, single fixing design Can be double stacked one fixing Black UV Resistant Application Features & Benefits > Indoor/Outdoor for Unarmoured Cable > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland - Brass locknut - PVC shroud 8 Gland sizes References in range & Thread s > 2 per kit size up to and including 25 Cable Dimensions Gland Dimensions Basic Metric Number NPT Max. Max. No. Price of Each Inner Sheath Overall Braid Approx. Hexagon Operating temperature -70ºC to Diameter Range Dia. Over Conductors Dia. A Dia. B Wire Length Technical Data > EN 50262 Standard Design Thread LSF Design Thread Conductors Standard LSF +70ºC > BS6121:Pt 1:1989 Dia. C D A/C A/F > Gland rated to IP66 with use of suitable sealing washer or thread sealant 385AA01 No. 385LSF01 * No. 10-15 E F 0.20 Min 0.40 Max Min at gland interface Max LSF type tested to LUL specification 385AA02 385LSF02 12-17 0.30 > Service temperature -20 C 0.60 to +90 C 20S > CuZn39Pb3 extruded brass alloy used for guaranteed strength and 385AA03 385LSF03 15-20 0.30 0.65 Black low-density polyethylene performance 424TX52 M20 1.5 424TX02 ½ - 14 NPT 11.0 30 11.5 8.0 15.8 - unaffected 0.2 / 0.3by corrosive 67 34.0 385AA04 385LSF04 18-24 0.35 0.75 30.5 20 385AA05 424TX53 M20 385LSF05 1.5 424TX03 ½ - 1422-29 NPT 11.0 0.35 30 0.85 12.5 11.7 20.8 environments, 0.2 / 0.3 oils and 64 many 34.0 30.5 25 385AA06 424TX55 M25 385LSF06 1.5 424TX05 ¾ - 1426-34 NPT 16.0 0.65 42 11.5 1.50 18.0 17.0 27.2 chemicals 0.2 / 0.45 65 42.2 37.6 32 385AA07 424TX56 M32 385LSF07 1.5 424TX06 1-11½ 32-42 NPT 22.1 0.80 60 17.0 1.80 25.0 19.0 33.5 Flaability 0.3 / 0.45rating 77 UL 94 - V2 53.6 47.3 385AA08 385LSF08 39-51 1.05 2.40 PAGE 49 - NOT DRAWN A 40 424TX57 M40 1.5 424TX07 1¼ - 11½ NPT 28.2 100 24.0 31.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4 THIS IS 55% 50 424TX59 M50 1.5 424TX09 2-11½ NPT 37.1 200 30.0 41.5 36.0 52.6 0.3 / 0.45 CABLE 84 CLEAT 77.2 DETAILS 70.1 B 63 424TX61 M63 1.5 424TX11 2½ - 8 NPT 48.4 400 40.0 54.0 46.5 65.3 0.3 / 0.45 90 87.4 80.0 75 424TX63 M75 1.5 424TX13 3-8 NPT 58.6 400 53.0 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 85 424TX64 M85 2 424TX14 3 Ref: - 8 A1A2/03/07 NPT Systems 65.8Limited, Road, 400 Wrexham Wrexham, 60.0 LL13 74.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 Prysmian Cables & Components Unit, Oak Industrial Estate, 9HP, UK C Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk D E * 1.5 Pitch threads are supplied 15 long, 2 pitch threads are supplied 20 long A NPT thread lengths comply with new UL2225 requirements D Cable & Cleat Section Number Cable Diameter Range Cleat Details Dimensions () B C D SWL (FOS 3) Min Max Max kgf PAGE 52 - NOT DRAWN A RoundheadTHIS IS 62% Woodscrew Screw for Masonry, Cable Concrete or Tray Wood ins x No 385AA01 10-15 15 18 32 12 17 2.3 1 1 4 x 8 M4 x 30 385AA02 12-17 17 22 36 14 22 3.4 1 1 2 x 8 M4 x 35 385AA03 15-20 21 26 43 16 32 5.5 1 3 4 x 8 M4 x 40 385AA04 18-24 25 31 51 18 40 8.6 2 x 8 M4 x 45 385AA05 22-29 30 37 57 20 47 12.4 2 1 4 x 12 M6 x 50 385AA06 26-34 35 43 65 22 59 16.4 2 1 2 x 12 M6 x 60 385AA07 32-42 42 52 78 25 79 24 2 PAGE 54 - NOT DRAWN A 4 x 12 M6 x 70 385AA08 39-51 50 62 91 26 82 35 3 THIS IS 40% 4 x 12 M7 x 80 Approx. Weight g PAGE 56 - NOT DRAWN A THIS IS 36% Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 49 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk PAGE 74 - THIS IS 100%
Cable Cleats PLASTIC CABLE CLEATS SINGLE BOLT CLAW CLEAT - LSF Indoor and outdoor for 8.5 to 50 diameter cables Operating temperature range 10 C to +120 C Flame retardant to UL 94 - V2 Limited oxygen index (LOI) V2 = 25%, V0 = 36% Chemical resistance - Resistance to most known chemicals PAGE 50 - NOT DRAWN AT 100% THIS IS 52% Low Smoke Fume (LSF) Product Compact mechanical properties offering high impact strength Self Extinguishing & Flame Retardant Can be double stacked Black UV Resistant 10 sizes in range Number Diameter Range CE00 8.5-11 1.40 CE0 11-13.5 1.40 CE1 13.5-16 1.45 CE2 16-19 1.60 CE3 19-22 1.70 CE4 22-26.5 2.00 CE5 26.5-32 2.30 CE6 32-38 2.65 CE7 38-44 2.75 PAGE CE8 51 - NOT DRAWN AT 100% 44-50 3.10 THIS Discount IS 52% on application CABLE CLEAT DETAILS C B A Cable Diameter Cleat Dimensions Approx. PAGE Number 53 - NOT DRAWN Min AT 100% Max A B C Weight g THIS E00IS 64% 8.5 11 43 47 33 34 E0 11 13.5 43 51 35 37 E1 13.5 16 43 54 38 42 E2 16 19 43 58 41 45 E3 19 22 43 60 44 50 E4 22 26.5 43 64 48 56 E5 26.5 32 43 70 54 62 E6 32 38 43 80 60 79 E7 38 44 43 85 66 83 E8 44 50 43 88 71 87 PAGE 55 - NOT DRAWN AT 100% THIS IS 76% THREADED ROD ASSEMBLIES (CUT STUDS) Fixing assemblies for cable cleats PAGE 57 - NOT DRAWN AT 100% THIS IS 59% Number Description F380AH19 Cut Studs (inc Nuts & Washers) M10 X 100 0.80 F380AH23 Cut Studs (inc Nuts & Washers) M10 x 125 0.85 F380AH29 Cut Studs (inc Nuts & Washers) M10 x 150 1.00 PAGE F380AH41 59 - NOT DRAWN Cut Studs (inc AT Nuts 100% & Washers) M10 x 205 1.40 THIS F380AJ29 IS 68% Cut Studs (inc Nuts & Washers) M12 x 155 1.70 F380AJ39 Cut Studs (inc Nuts & Washers) M12 x 205 3.35 50
Cable Cleats PLASTIC CABLE CLEATS TWO BOLT CLEAT - LSF Indoor and outdoor for 50 to 81 diameter cables Low Smoke Fume (LSF) Product Compact mechanical properties offering high impact strength Self Extinguishing & Flame Retardant Can be double stacked Available in black or red HV 10 sizes in range Diameter Black Red Range Black Red Operating temperature range 10 C to +120 C CE9 CEH9 50-54.5 4.25 5.50 Limited oxygen index (LOI) V2 = CE10 CEH10 54.5-59 4.40 5.55 25%, V0 = 36% CE11 CEH11 59-64 4.95 5.95 CE12 CEH12 64-68 5.85 7.15 Flame retardant to UL 94 - V2 or VO CE13 PAGE CEH1349 - NOT DRAWN AT 68-74 100% 7.25 PAGE 50 - NOT 9.95DRAWN AT 100% PAGE 51 - NOT DRAWN AT 100% Chemical resistance - Resistance to CE14 THIS CEH14 IS 55% 74-81 9.35 THIS IS 52% 12.95 THIS IS 52% most known chemicals CABLE CLEAT DETAILS C B A Cable Diameter Cleat Dimensions PAGE 53 - NOT DRAWN AT 100% Approx. NumberPAGE 52 - NOT MinDRAWN AT 100% Max A B C Weight g THIS IS 64% E9 THIS IS 62% 50 54.5 60 97 67 121 E10 54.5 59 60 97 72 131 E11 59 64 60 97 76 145 E12 64 68 60 116 80 166 E13 68 74 60 116 90 168 E14 74 81 60 116 90 188 THREADED ROD ASSEMBLIES (CUT STUDS) Fixing assemblies PAGE for 54 cable - NOT cleats DRAWN AT 100% THIS IS 40% Description Number PAGE 55 - NOT DRAWN AT 100% THIS IS 76% F380AH19 Cut Studs (inc Nuts & Washers) M10 X 100 0.80 F380AH23 Cut Studs (inc Nuts & Washers) M10 x 125 0.85 F380AH29 Cut Studs (inc Nuts & Washers) M10 x 150 1.00 F380AH41 Cut Studs (inc Nuts & Washers) M10 x 205 1.40 F380AJ29 Cut Studs (inc Nuts & Washers) M12 x 155 1.70 F380AJ39 Cut Studs (inc Nuts & Washers) M12 x 205 3.35 PAGE 56 - NOT DRAWN AT 100% PAGE 57 - NOT DRAWN AT 100% THIS IS 36% THIS IS 59% PAGE 59 - NOT DRAWN AT 100% THIS IS 68% PAGE 74 - THIS IS 100% PAGE 75 - NOT DRAWN AT 100% THIS IS 62% 51
r Gland C Cable Cleats PLASTIC CABLE CLEATS single bolt hook cleat - heavy duty F Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series D Gland Dimensions verall Braid Approx. Hexagon PAGE Operating 49 - NOT temperature DRAWN 20 C AT 100% to ia. B Wire Length Dia. THIS C +90 C IS 55% D A/C A/F E F Max Black low-density polyethylene - unaffected by corrosive 15.8 0.2 / 0.3 environments, 67 oils 34.0 and many 30.5 chemicals 20.8 0.2 / 0.3 64 34.0 30.5 27.2 0.2 / 0.45 65 42.2 37.6 33.5 0.3 / 0.45 77 53.6 47.3 39.9 0.3 / 0.45 77 61.5 56.4 52.6 0.3 / 0.45 84 77.2 70.1 65.3 0.3 PAGE / 0.45 52-90 NOT DRAWN 87.4 AT 80.0100% THIS CABLE IS CLEAT 62% DETAILS 78.0 0.3 / 0.45 96 109.2 98.8 B D 88.0 0.3 / 0.45 108 126.0 115.0 E E Indoor/Outdoor for 25 to 80 diameter cables Manufactured from Glass filled Nylon for superior safe working load Application > Indoor/Outdoor for Unarmoured Cable Can take a large range of cables Can be installed in a temporary open position Features & Benefits Two piece single fixing design > Kit comprises: - A1/A2 Gland - Brass locknut Can be double stacked on one fixing - PVC shroud > 2 per kit size up to and including 25 Black UV Resistant Available in Standard or LSF Version PAGE 50 - NOT DRAWN AT 100% PAGE 51 - NOT DRAWN AT 100% Available in 6 sizes Technical Data > EN 50262 THIS IS 52% THIS IS 52% > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof Number at Price gland interface Each Diameter Range > Service temperature -20 C to +90 C Standard LSF Standard LSF 384AA01 384LSF01 25-35 performance 1.85 2.80 384AA02 385LSF02 34-44 2.25 3.45 384AA03 384LSF03 43-53 2.70 4.10 384AA04 384LSF04 52-62 3.15 4.75 384AA05 384LSF05 61-71 3.55 5.35 384AA06 384LSF06 70-80 3.95 6.00 PAGE 53 - NOT DRAWN AT 100% THIS IS 64% Ref: A1A2/03/07 > BS6121:Pt 1:1989 > Gland rated to IP66 with use of suitable sealing washer or thread sealant > CuZn39Pb3 extruded brass alloy used for guaranteed strength and Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk C A PAGE 54 - NOT DRAWN Cable AT 100% Diameter A PAGE 55 - NOT DRAWN AT 100% Cleat Dimensions THIS IS 40% THIS IS 76% B Number C D E Min Max Min Max 384AA01 25 35 36 46 76 40 18 384AA02 34 44 44 54 85 40 18 384AA03 43 53 56.5 66.5 96 40 18 384AA04 52 62 65.5 75.5 106 40 18 384AA05 61 71 78 88 119 44 20 384AA06 70 80 87 97 129 44 20 PAGE 56 - NOT DRAWN AT 100% THIS IS 36% THREADED ROD ASSEMBLIES (CUT STUDS) PAGE 57 - NOT DRAWN AT 100% THIS IS 59% Fixing assemblies for cable cleats PAGE 59 - NOT DRAWN AT 100% THIS IS 68% PAGE 74 - THIS IS 100% Description Number F380AH19 Cut Studs (inc Nuts & Washers) M10 X 100 0.80 F380AH23 Cut Studs (inc Nuts & Washers) M10 x 125 0.85 F380AH29 Cut Studs (inc Nuts & Washers) PAGE 75 - NOT M10 x DRAWN 150 AT 100% 1.00 F380AH41 Cut Studs (inc Nuts & Washers) THIS IS 62% M10 x 205 1.40 F380AJ29 Cut Studs (inc Nuts & Washers) M12 x 155 1.70 F380AJ39 Cut Studs (inc Nuts & Washers) M12 x 205 3.35 9PH, UK 52 PAGE 76 - THIS IS 100% PAGE 77 - NOT DRAWN AT 100% THIS IS 62%
BARR-X EEx d IIC Brass Barrier Gland Cable Cleats ALUMINIUM CABLE CLEATS C single bolt hook cleat Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series B A F Indoor/Outdoor for 13 to 76 diameter cables Support cable in position during installation Application > Indoor/Outdoor for Unarmoured Cable Self adjusting ranges Gland Details Two piece, single fixing design Features & Benefits > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables Can be double stacked on one fixing > Suitable for most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland - Brass locknut Not designed to secure cables in long vertical routes - PVC shroud > 2 per kit size up to and including 25 Available Gland References in 12 sizes& Thread s Cable Dimensions Gland Dimensions Basic Metric NPT Max. Diameter Max. No. of Inner Sheath Overall Braid Approx. Hexagon Operating temperature -60 C to Number Dia. Over Conductors Dia. A Dia. B Wire Length Technical Design Thread Design Thread Range Data > EN 50262 Conductors +85 CDia. C D A/C A/F > BS6121:Pt 1:1989 371AA01 No. * No. 13-16 > Gland rated to IP66 with use 4.45 of suitable sealing washer or thread sealant E F Min Max Min Max at gland interface 371AA02 16-19 4.45 LM6 Grade Aluminium to BS 1490 > Service temperature -20 C to +90 C PAGE 49 - NOT DRAWN AT 100% PAGE 50 - NOT DRAWN AT 100% PAGE 5 371AA03 19-22 > CuZn39Pb3 extruded brass alloy used for guaranteed strength and 5.35 20S 424TX52 M20 1.5 424TX02 ½ - 14 NPT THIS IS 55% performance 11.0 30 11.5 8.0THIS 15.8 IS 52% 0.2 / 0.3 67 34.0 30.5 THIS IS 371AA04 22-25 6.95 20 371AA05 424TX53 M20 1.5 424TX03 ½ - 14 NPT 11.0 25-32 30 7.9512.5 11.7 20.8 0.2 / 0.3 64 34.0 30.5 25 371AA06 424TX55 M25 1.5 424TX05 ¾ - 14 NPT 16.0 32-38 42 11.58.3018.0 17.0 27.2 0.2 / 0.45 65 42.2 37.6 371AA07 38-44 9.35 32 424TX56 M32 1.5 424TX06 1-11½ NPT 22.1 60 17.0 25.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3 371AA08 44-51 10.45 40 371AA09 424TX57 M40 1.5 424TX07 1¼ - 11½ NPT 28.2 51-57 100 24.0 31.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4 11.65 50 371AA10 424TX59 M50 1.5 424TX09 2-11½ NPT 37.157-64 200 30.0 13.7541.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1 63 371AA11 424TX61 M63 1.5 424TX11 2½ - 8 NPT 48.4 64-70 400 40.0 16.6054.0 46.5 65.3 0.3 / 0.45 90 87.4 80.0 75 371AA12 424TX63 M75 1.5 424TX13 3-8 NPT 58.6 70-76 400 53.0 17.3565.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 85 424TX64 M85 2 424TX14 3 Ref: - 8 A1A2/03/07 NPT Prysmian Cables & Systems 65.8 Limited, Components Unit, Oak Road, 400 Wrexham Industrial Estate, Wrexham, 60.0 LL13 9HP, UK 74.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 PAGE 53 - NOT DRAWN AT 100% PAGE 52 - NOT DRAWN www.prysmian.co.uk AT 100% THIS IS 64% THIS IS 62% CABLE CLEAT DETAILS B D * 1.5 Pitch threads are supplied 15 long, 2 pitch threads are supplied 20 long F NPT thread lengths comply with new UL2225 requirements D E C E A Number Cable & Cleat Section Cleat Details Cable Diameter PAGE 54 - NOT DRAWN AT 100% Dimensions () PAGE 55 - NOT DRAWN AT 100% Approx. A () THIS IS 40% B Weight C D THIS IS 76% E F Min Max Min Max g 371AA01 13 16 23 28 51 38 21 19 55 371AA02 16 19 28 30 54 38 22 19 55 371AA03 19 22 29 33 57 38 24 19 55 371AA04 22 25 34 37 62 38 26 19 55 371AA05 25 32 37 45 74 45 29 24 55 371AA06 32 38 44 50 81 45 32 24 55 371AA07 38 44 PAGE 5056 - NOT DRAWN 57 AT 100% 88 45 PAGE 3557 - NOT DRAWN 24 AT 100% 55 371AA08 44 51 THIS 55 IS 36% 63 94 45 THIS 38 IS 59% 24 55 371AA09 51 57 64 72 103 45 43 24 55 371AA10 57 64 72 79 111 45 48 24 55 371AA11 64 70 80 91 124 45 53 25 65 371AA12 70 76 91 96 132 45 57 27 65 PAGE 5 THIS IS PAGE 74 - THIS IS 100% PAGE 75 - NOT THIS IS 62% Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 53 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
r Gland C Cable Cleats ALUMINIUM CABLE CLEATS D verall ia. B Max SINGLE BOLT CLAW CLEAT PAGE 49 - NOT DRAWN AT 100% THIS IS 55% E F PAGE 52 Gland - NOT Dimensions DRAWN AT 100% THIS IS 62% Braid Approx. Hexagon Operating temperature -60 C to Wire Length Dia. C +100 C D A/C A/F E F LM6 Grade Aluminium to BS 1490 15.8 0.2 / 0.3 67 34.0 30.5 20.8 0.2 / 0.3 64 34.0 30.5 27.2 0.2 / 0.45 65 42.2 37.6 33.5 0.3 / 0.45 77 53.6 47.3 39.9 0.3 / PAGE 0.45 5477 - NOT DRAWN 61.5 56.4 AT 100% 52.6 0.3 CABLE / THIS 0.45 CLEAT IS 40% 84DETAILS 77.2 70.1 65.3 0.3 / 0.45 C 90 87.4 80.0 78.0 0.3 / 0.45 E 96 109.2 98.8 88.0 0.3 / 0.45 108 126.0 D 115.0 Industrial Gland Kits A1/A2 Brass Gland Kit PAGE 50 - NOT DRAWN AT 100% PAGE 51 - NOT DRAWN AT 100% KM409 Series THIS IS 52% THIS IS 52% Indoor/Outdoor for 10 to 51 diameter cables High Grade LM6 Aluminium Can be used on all types of cable routes Two piece, single fixing design Single bolt can be stacked to a maximum of three on one fixing Features & Benefits > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland Available in 9 sizes - Brass locknut PAGE 53 - NOT DRAWN AT 100% - PVC shroud > 2 per kit size up to and including 25 THIS IS 64% Diameter Number Range C370BA01 Technical 10-13 Data > EN 50262 3.25 C370BA02 13-16 3.25 > BS6121:Pt 1:1989 C370BA03 16-19 3.25 at gland interface C370BA04 19-22 > Service temperature -20 C to +90 C 3.45 C370BA05 22-25 3.45 performance C370BA06 25-32 3.95 C370BA07 32-38 3.95 C370BA08 38-44 4.55 C370BA09 44-51 4.95 Discount PAGE on 55 application - NOT DRAWN AT 100% THIS IS 76% Ref: A1A2/03/07 Application > Indoor/Outdoor for Unarmoured Cable > Gland rated to IP66 with use of suitable sealing washer or thread sealant > CuZn39Pb3 extruded brass alloy used for guaranteed strength and Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk B A PAGE 56 - Table NOT & DRAWN Cleat Selection AT 100% PAGE 57 - NOT DRAWN AT Cleat 100% Details PAGE 59 - NOT DRAWN AT 100% THIS IS 36% Cable Diameter A THIS IS 59% Dimensions THIS IS 68% Approx. Stud Number Min Max B C D E Weight 370BA01 10 13 21 38 46 16 60 M10 370BA02 13 16 21 38 46 16 50 M10 370BA03 16 19 24 41 46 18 60 M10 370BA04 19 22 27 44 46 19 70 M10 370BA05 22 25 30 48 46 21 80 M10 370BA06 25 32 37 54 46 24 90 M10 370BA07 32 38 43 60 46 27 110 M10 PAGE 370BA08 74 - THIS IS 38 100% 44 49 67 46 PAGE 30 75 - NOT DRAWN 120 AT 100% M10 370BA09 44 51 56 73 46 THIS 34IS 62% 150 M10 PACKING PIECES Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series ADAPTOR PLATE Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series PAGE 76 - THIS IS 100% To enable stacking of claw cleats Application > Indoor/Outdoor for Unarmoured Cable To assist in fixing cleats to channel PAGE 77 - NOT DRAWN AT 100% THIS IS 62% Application > Indoor/Outdoor for Unarmoured Cable Features & Benefits > Brass indoor and outdoor cable gland & accessories Features & Benefits > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > Suitable for most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland > Kit comprises: - A1/A2 Gland - Brass locknut - Brass locknut - PVC shroud > 2 per kit size up to and including 25 Description Number 389AC03 Aluminium Alloy 1.95 Technical Data > EN 50262 > BS6121:Pt 1:1989 > Gland rated to IP66 with use of suitable sealing washer or thread sealant - PVC shroud > 2 per kit size up to and including 25 Description Number 380AG02 M10 (Galvanised) 1.75 Technical Data > EN 50262 > BS6121:Pt 1:1989 > Gland rated to IP66 with use of suitable sealing washer or thread sealant 9PH, UK 54 at gland interface > Service temperature -20 C to +90 C > CuZn39Pb3 extruded brass alloy used for guaranteed strength and performance at gland interface > Service temperature -20 C to +90 C > CuZn39Pb3 extruded brass alloy used for guaranteed strength and performance
Cable Cleats ALUMINIUM CABLE CLEATS SINGLE BOLT CLEAT Indoor/Outdoor for 13 to 70 diameter cables High grade aluminium LM6 Can be used on all types of cable routes Two piece, single fixing design Product can be double stacked Available on request in epoxy coated version for more hostile environments PAGE 49 - NOT DRAWN AT 100% THIS IS 55% PAGE 50 - NOT DRAWN A THIS IS 52% Diameter Number Range PAGE 53 - NOT DRA PAGE 52 - NOT DRAWN AT 100% Operating Temperature -60C to +85C SW1B2 13-16 3.25 THIS IS 64% THIS IS 62% Tested to BS EN 50383 SW1B3 16-19 3.25 SW1B4 19-22 3.45 SW1B5 22-25 3.45 SW1B6 25-32 3.95 SW1B7 32-38 3.95 SW1B8 38-44 4.55 SW1B9 44-51 4.95 SW1B10 51-57 6.60 SW1B11 57-64 6.95 SW1B12 64-70 9.45 PAGE 54 - NOT DRAWN AT 100% THIS IS 40% LM6 Grade Aluminium to BS 1432 PAGE 55 - NOT DRAWN AT 10 CABLE THIS CLEAT IS 76% DETAILS W H D Number Cable Range PAGE Dimensions 56 - NOT DRAWN AT 100% Fixing Min Dia Max Dia W THIS IS 36% H D Hole SW1B2 13 16 44 34 43 M10 80 SW1B3 16 19 48 36 43 M10 91 SW1B4 19 22 50 38 43 M10 98 SW1B5 22 25 53 40 43 M10 100 SW1B6 25 32 59 44 43 M10 120 SW1B7 32 38 65 50 43 M10 132 SW1B8 38 44 71 56 43 M10 152 SW1B9 44 51 78 PAGE 7463- THIS IS 100% 43 M10 168 SW1B10 51 57 84 73 43 M10 202 SW1B11 57 64 91 80 43 M10 189 SW1B12 64 70 97 89 43 M10 253 PAGE 57 - NOT DRAWN Item THIS Weight IS 59% g THREADED ROD ASSEMBLIES (CUT STUDS) Fixing assemblies for cable cleats Number Description PAGE 76 - THIS IS 100% F380AH19 Cut Studs (inc Nuts & Washers) M10 X 100 0.80 F380AH23 Cut Studs (inc Nuts & Washers) M10 x 125 0.85 F380AH29 Cut Studs (inc Nuts & Washers) M10 x 150 1.00 F380AH41 Cut Studs (inc Nuts & Washers) M10 x 205 1.40 F380AJ29 Cut Studs (inc Nuts & Washers) M12 x 155 1.70 F380AJ39 Cut Studs (inc Nuts & Washers) M12 x 205 3.35 55
r Gland C PAGE 49 - NOT DRAWN AT 100% THIS IS 55% Cable Cleats ALUMINIUM CABLE CLEATS PAGE 50 - NOT DRAWN AT 100% THIS IS 52% PAGE 51 - NOT DRAWN AT 100% THIS IS 52% TWO BOLT CLEAT F Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series D E PAGE 52 - NOT DRAWN AT 100% THIS IS 62% Gland Dimensions verall Braid Approx. Hexagon Operating temperature -60 C to ia. B Wire Length Dia. C +100 C D A/C A/F E F Max PAGE 54 - NOT DRAWN AT 100% Tested to BS EN 50368 THIS IS 40% - LM6 grade aluminium to BS 1490 15.8 0.2 / 0.3 67 34.0 30.5 20.8 0.2 / 0.3 64 34.0 30.5 27.2 0.2 / 0.45 65 42.2 37.6 33.5 0.3 / 0.45 77 53.6 47.3 39.9 0.3 / 0.45 77 61.5 56.4 52.6 0.3 / 0.45 84 77.2 70.1 PAGE 56 - NOT DRAWN AT 100% 65.3 0.3 CABLE / 0.45 CLEAT 90 DETAILS 87.4 80.0 THIS IS 36% 78.0 0.3 / 0.45 C 96 109.2 98.8 88.0 0.3 / 0.45 E 108 126.0 115.0 D Indoor/Outdoor for 51 to 114 diameter cables PAGE 53 - NOT DRAWN AT 100% THIS IS 64% High Grade Aluminium LM6 Can be used for all types of cable routes Two piece, two fixing design Can be double stacked on coon fixings Available in epoxy coated version for more hostile environments Available in 10 sizes Features & Benefits > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland - Brass locknut - PVC shroud > 2 per kit size up to and including 25 Number Diameter Technical Range Data > EN 50262 > BS6121:Pt 1:1989 370BA10 51-57 PAGE 55 - NOT DRAWN AT 100% 6.85 at gland interface 370BA11 57-64 THIS IS 76% 7.50 > Service temperature -20 C to +90 C 370BA12 64-70 9.25 370BA13 70-76 10.50 performance 370BA14 76-83 19.95 370BA15 83-89 31.95 370BA16 89-95 64.95 370BA17 95-101 85.00 370BA18 101-108 95.00 370BA19 108-114 99.00 PAGE 57 - NOT DRAWN AT 100% THIS IS 59% Ref: A1A2/03/07 Application > Indoor/Outdoor for Unarmoured Cable > Gland rated to IP66 with use of suitable sealing washer or thread sealant > CuZn39Pb3 extruded brass alloy used for guaranteed strength and PAGE 59 - NOT DRAWN AT 100% THIS IS 68% Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9HP, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk A B Table & Cleat Selection Cleat Details Design Cable Diameter A Dimensions Approx. Stud PAGE Number 74 - THIS IS 100% PAGE 75 - NOT DRAWN Min Max B C D E Weight AT 100% THIS IS 62% 370BA10 51 57 68 98 49 38 230 M10 370BA11 57 64 75 98 49 38 240 M10 370BA12 64 70 84 135 64 57 410 M10 370BA13 70 76 90 135 64 57 400 M10 370BA14 76 83 96 140 64 57 410 M12 370BA15 83 89 101 140 64 57 490 M12 370BA16 89 95 114 152 76 PAGE 63 77 - NOT DRAWN 650 AT 100% M12 PAGE 76 - THIS IS 100% 370BA17 95 101 120 152 76 THIS IS 63 62% 650 M12 370BA18 101 108 134 165 76 70 900 M12 370BA19 108 114 139 165 76 70 900 M12 THREADED ROD ASSEMBLIES (CUT STUDS) Fixing assemblies for cable cleats Number Description F380AH19 Cut Studs (inc Nuts & Washers) M10 X 100 0.80 F380AH23 Cut Studs (inc Nuts & Washers) M10 x 125 0.85 F380AH29 Cut Studs (inc Nuts & Washers) M10 x 150 1.00 F380AH41 Cut Studs (inc Nuts & Washers) M10 x 205 1.40 F380AJ29 Cut Studs (inc Nuts & Washers) M12 x 155 1.70 F380AJ39 Cut Studs (inc Nuts & Washers) M12 x 205 3.35 9PH, UK 56
THIS IS 55% THIS IS 52% T BARR-X EEx d IIC Brass Barrier Gland C Cable Cleats MULTIPLE CABLE CLEATS 376TR MV/HV Trefoil cleats Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series B A F Outdoor for 62 to 186 MV/HV diameter PAGE cable 52 - NOT in DRAWN AT 100% trefoil formation THIS IS 62% Gland Details D PAGE 53 - NOT DRAWN AT 100% THIS IS 64% E Application > Indoor/Outdoor for Unarmoured Cable Manufactured from solid aluminium Design for use with MV & HV cable designs Features & Benefits > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables Deep section bases aid cable installation > Suitable for most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland Clamping bolt can be used for pilot cables - Brass locknut - PVC shroud Gland Available References with single & or Thread two bolt s fixing > 2 per kit size up to and including 25 Cable Dimensions Gland Dimensions Available with rubber lining for HV installations Basic Metric NPT Max. Max. No. of Inner Sheath Overall Braid Approx. Hexagon Operating Temperature -60 C to + 6 sizes in range PAGE Dia. Over Conductors Dia. A Dia. B Wire Length Technical 54 - Data NOT DRAWN > EN 50262 AT 100% Design Thread Design Thread PAGE Conductors 85 C 55 - NOT DRAWN AT Dia. C D A/C 100% A/F > BS6121:Pt 1:1989 No. * No. THIS IS 40% > Gland rated to IP66 with use of suitable sealing washer or thread sealant THIS IS 76% E F Min Max Min Max at gland interface Cable Diameter Tested in accordance with Number > Service temperature -20 C to +90 C BS EN 50368 > CuZn39Pb3 extruded brass alloy used for guaranteed strength and 376TR06 62-75 performance POA 20S 424TX52 M20 1.5 424TX02 ½ - 14 NPT 11.0 30 11.5 8.0 15.8 0.2 / 0.3 67 34.0 30.5 376TR07 75-90 POA Impact Resistance (6.2, 6..2.5, 9.3) - 20 376TR08 424TX53 M20 1.5 424TX03 ½ - 14 NPT 11.0 90-107 30 POA12.5 11.7 20.8 V Heavy 0.2 > / 0.3 6.7kg at 64 300. 34.0 30.5 25 376TR09 424TX55 M25 1.5 424TX05 ¾ - 14 NPT 16.0 107-129 42 11.5 POA 18.0 17.0 27.2 Cleat 0.2 type / 0.45 (6.1, 6.3) 65 - metallic42.2 37.6 32 376TR10 424TX56 M32 1.5 424TX06 1-11½ NPT 22.1 129-155 60 17.0 POA 25.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3 376TR11 155-186 POA 40 424TX57 M40 1.5 424TX07 1¼ - 11½ NPT 28.2 100 24.0 31.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4 PAGE 56 - NOT DRAWN AT 100% PAGE 57 - NOT DRAWN AT 100% 50 424TX59 M50 1.5 424TX09 2-11½ NPT THIS 37.1 IS 36% 200 30.0 41.5 36.0 52.6 THIS 0.3 / IS 0.459% 84 77.2 70.1 CABLE CLEAT DETAILS 63 424TX61 M63 1.5 424TX11 2½ - 8 NPT 48.4 400 40.0 54.0 46.5 65.3 0.3 / 0.45C 90 87.4 A 80.0 75 424TX63 M75 1.5 424TX13 3-8 NPT 58.6 400 53.0 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 85 424TX64 M85 2 424TX14 3 Ref: - 8 A1A2/03/07 NPT Systems 65.8 Limited, Coercial Road, 400 Wrexham 8345, Fax: +44 Wrexham, 60.0 LL13 74.0 68.0 88.0 0.3 / 0.45B 108 126.0 115.0 Prysmian Cables & Components Unit, Oak Industrial Estate, 9HP, UK Enquiries, Tel +44 (0) 845 767 (0) 23 8029 5465 www.prysmian.co.uk P T * 1.5 Pitch threads are supplied 15 long, 2 pitch threads are supplied 20 long NPT thread lengths comply with new UL2225 requirements Design Number Cable Dimensions B PAGE Extrusion 74 Length - THIS IS 100% Width O/A A D Bolt CRS C Bolt Diameter 376TR06 62-75 80 260 216 12 376TR07 75-90 80 295 251 12 376TR08 90-107 100 340 296 12 376TR09 107-129 100 390 346 12 376TR10 129-155 125 450 406 12 376TR11 155-186 125 525 481 12 PAGE 76 - THIS IS 100% D PAGE 75 THIS IS PAGE 77 THIS IS 6 Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 57 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
r Gland C Cable Cleats MULTIPLE CABLE CLEATS ALUMINIUM TREFOIL CLEATS WITH SINGLE & TWO BOLT FIXING F Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series D E Indoor/Outdoor for 24 to 76 diameter cables in trefoil formation verall ia. B Max Gland Dimensions Braid Approx. Hexagon Operating temperature -60 C to Wire Length Dia. C +100 C D A/C A/F E F Tested to BS EN 50368 Short Circuit Withstand 30KA Rms 15.8 0.2 / 0.3 (76KA Peak) 67 34.0 30.5 20.8 0.2 / 0.3 64 34.0 30.5 LM6 grade aluminium to BS 1490 27.2 0.2 / 0.45 65 42.2 37.6 33.5 0.3 / 0.45 77 53.6 47.3 39.9 0.3 / 0.45 77 61.5 56.4 52.6 0.3 / 0.45 84 77.2 70.1 65.3 0.3 / 0.45 90 87.4 80.0 78.0 0.3 / 0.45 96 109.2 98.8 88.0 0.3 / 0.45 108 126.0 115.0 High Grade Aluminium LM6 Available in either a single bolt or two bolt fixing design Can be used for all types of cable routes Available in epoxy coated version for more hostile environments Fixed with either one or two M10 fixings Available in 33 sizes Application Features & Benefits > Indoor/Outdoor for Unarmoured Cable > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland - Brass locknut - PVC shroud > 2 per kit size up to and including 25 Technical Data > EN 50262 > BS6121:Pt 1:1989 > Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface > Service temperature -20 C to +90 C > CuZn39Pb3 extruded brass alloy used for guaranteed strength and performance Number Diameter Range Single Fixing Two Fixing Single Fixing Two fixing 376AC01 376AB01 24-25 17.90 19.70 376AC02 376AB02 25-27 17.90 19.70 376AC03 376AB03 27-28 17.90 19.70 376AC04 376AB04 28-30 17.90 19.70 376AC05 376AB05 30-32 17.90 19.70 376AC06 376AB06 32-34 17.90 19.70 376AC07 376AB07 34-35 18.10 19.90 376AC08 376AB08 35-36 18.10 19.90 376AC09 376AB09 36-38 18.10 19.90 376AC10 376AB10 38-40 18.10 19.90 376AC11 376AB11 40-41 18.40 20.25 376AC12 376AB12 Ref: A1A2/03/07 41-43 Prysmian Unit, 18.40 Oak Road, Wrexham Wrexham, 20.25 LL13 9HP, UK Cables & Systems Limited, Components Industrial Estate, Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk 376AC13 376AB13 43-44 18.90 20.80 376AC14 376AB14 44-46 18.90 20.80 376AC15 376AB15 46-48 19.25 21.20 376AC16 376AB16 48-49 19.25 21.20 376AC17 376AB17 49-51 20.70 22.80 376AC18 376AB18 51-53 20.70 22.80 376AC19 376AB19 53-54 20.70 22.80 376AC20 376AB20 54-55.5 27.15 29.90 376AC21 376AB21 55.5-57 27.15 29.90 376AC22 376AB22 57-59 30.00 33.00 376AC23 376AB23 59-60 30.00 33.00 376AC24 376AB24 60-62 32.20 35.50 376AC25 376AB25 62-63.5 33.55 36.90 376AC26 376AB26 63.5-65 34.30 37.75 376AC27 376AB27 65-66.5 35.95 39.60 376AC28 376AB28 66.5-68 37.75 41.60 376AC29 376AB29 68-70 39.25 43.20 376AC30 376AB30 70-71.5 41.10 45.30 376AC31 376AB31 71.5-73 43.00 47.30 376AC32 376AB32 73-74.5 45.00 49.50 376AC33 376AB33 74.5-76 47.00 51.70 9PH, UK 58
% BARR-X EEx d IIC Brass Barrier Gland C Cable Cleats MULTIPLE CABLE CLEATS ALUMINIUM TREFOIL CLEATS WITH SINGLE & TWO BOLT FIXING continued 100% PAGE 59 - NOT DRAWN AT 100% CABLE THIS IS CLEAT 68% DETAILS Single Fixing Two Fixings B A D E F Gland Details C 11 B D C E PAGE 75 - Gland NOT References DRAWN AT & 100% Thread s THIS IS 62% Basic Metric NPT Max. Dia. Over Design Table Thread & Cleat Selection Design Thread Conductors Cable Dimensions Gland Dimensions Max. No. of Inner Sheath Overall Braid Approx. Hexagon Conductors Dia. A Dia. B Wire Length Cleat Details Dia. C D A/C A/F Design No. Number * No. E F Cable Diameter Dimensions Min Max Min Max Approx. 376AC** Single Fixing Two Fixing Weight g B D 376AB** Min Max C C E Single Fixing Two Fixing 20S 424TX52 M20 1.5 424TX02 ½ - 14 NPT 11.0 30 11.5 8.0 15.8 0.2 / 0.3 67 34.0 30.5 01 24 25 94 38 75 128 102 234 276 PAGE 20 77424TX53 - NOT DRAWN M20 1.5 AT 100% 02 25 424TX03 27 ½ - 14 NPT 97 11.0 38 30 75 12.5 128 11.7 20.8 102 0.2 / 0.3 241 64 34.0 284 30.5 THIS IS 62% 25 424TX55 03 M25 1.527 424TX05 28 ¾ - 14 NPT 100 16.0 38 42 75 11.5 18.0 128 17.0 27.2 102 0.2 / 0.45 248 65 42.2 291 37.6 32 424TX56 04 M32 1.528 424TX06 30 1-11½ NPT 103 22.1 38 60 76 17.0 25.0 130 19.0 33.5 104 0.3 / 0.45 255 77 53.6 298 47.3 40 05 30 32 105 38 79 133 107 269 305 424TX57 M40 1.5 424TX07 1¼ - 11½ NPT 28.2 100 24.0 31.5 26.5 39.9 0.3 / 0.45 77 61.5 06 32 34 106 38 83 135 109 284 312 56.4 50 424TX59 07 M50 1.5 424TX09 34 2-11½ NPT 35 109 37.1 38 200 30.0 86 41.5 137 36.0 52.6 0.3 / 0.45 84 110 291 77.2 319 70.1 63 424TX61 08 M63 1.535 424TX11 36 2½ - 8 NPT 113 48.4 38 400 89 40.0 54.0 138 46.5 65.3 113 0.3 / 0.45 298 90 87.4 326 80.0 75 424TX63 09 M75 1.536 424TX13 383-8 NPT 116 58.6 38 400 92 53.0 65.5 140 58.0 78.0 114 0.3 / 0.45 305 96 109.2 333 98.8 85 424TX64 10 M85 2 38 424TX14 403-8 NPT 119 65.8 38 400 95 60.0 74.0 145 68.0 88.0 118 0.3 / 0.45 312108 126.0 340 115.0 11 40 41 122 38 99 147 121 319 347 12 41 43 124 38 105 149 123 326 354 * 1.5 Pitch 13 threads are supplied 43 15 44long, 2 pitch 127 threads are 38 supplied 20 108 long 150 124 340 369 14 44 46 130 38 112 154 128 354 383 NPT thread lengths comply with new UL2225 requirements 15 46 48 133 38 114 156 129 361 390 16 48 49 137 38 118 159 133 369 397 17 49 51 140 38 121 165 135 376 404 18 51 53 143 38 124 165 137 383 411 19 53 54 146 38 127 172 141 390 418 20 54 55.5 155 44 133 183 152 503 560 21 55.5 57 158 44 137 187 155 517 574 22 57 59 160 44 141 189 157 532 588 23 59 60 163 44 145 191 160 546 602 24 60 62 165 44 148 194 162 552 617 25 62 63.5 168 44 152 196 165 567 631 26 63.5 65 172 44 156 199 168 581 645 27 65 66.5 176 44 160 202 170 602 666 28 66.5 68 178 44 164 205 173 624 687 29 68 70 181 44 168 208 176 652 716 30 70 71.5 187 44 171 215 183 680 745 31 71.5 73 190 44 175 217 186 695 758 32 73 74.5 193 44 179 220 188 709 773 33 74.5 76 197 44 183 222 191 722 787 Recoended Max Spacings - Straight Runs - 900 - Vertical Bends - 300 - Horizontal bends - Cleat on each support with, if necessary, intermediate unanchored cleats to limit restraint spacing to 300 Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 59 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
r Gland C Cable Cleats MULTIPLE CABLE CLEATS MULTICLEAT SYSTEM F Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series D E Indoor/outdoor for 34 to 110 cable diameter for single cable and 24 to 145 in trefoil formation verall ia. B Max Gland Dimensions Braid Approx. Hexagon Operating Temperature Wire Length Dia. C - Aluminium D bases A/C-60 C A/F to + 100 C - Cast Iron & Stainless E Steel F bases + 1000 C for 2 hours 15.8 0.2 / 0.3 Tested BS 67 EN 50368 34.0 30.5 20.8 0.2 / 0.3 Short Circuit 64 Withstand 34.0 30.5 27.2 0.2 / 0.45 - Standard 65 1.8m 42.2 spacing= 37.6 43KA RMS 33.5 (Peak 114KA) 0.3 / 0.45 77 53.6 47.3 - Heavy 1.5m spacing = 50KA RMS 39.9 0.3 / 0.45 77 (Peak 130KA) 61.5 56.4 52.6 0.3 / 0.45 - Heavy 84 1.2m spacing 77.2 = 71KA 70.1 RMA 65.3 0.3 / 0.45 (Peak 184KA) 90 87.4 80.0 78.0 0.3 / 0.45 96 109.2 98.8 88.0 0.3 / 0.45 108 126.0 115.0 Application > Indoor/Outdoor for Unarmoured Cable Multicleat is a stainless steel multistrap with a base Multicleat bases are manufactured out of aluminium Features as standard & Benefits but are available in epoxy coated aluminium, stainless steel, hot dip galvanised & coated cast iron > Kit comprises: - A1/A2 Gland Can be used for all types of cable routes - Brass locknut - PVC shroud Exceptional overlapping ranges > 2 per kit size up to and including 25 Non magnetic materials used throughout Recoended spacing dictated by short circuit withstand (see Technical data) Technical Data > EN 50262 > BS6121:Pt 1:1989 Available in 26 products for each base type MULTICLEAT STANDARD & HEAVY DUTY Number Cable Diameter Cable Diameter performance Standard Heavy Duty for Singles for Trefoil Standard Heavy Duty 378AB01 378AB51 36-65 24-34 17.00 19.85 378AB02 378AB52 60-85 30-41 17.35 20.70 378AB03 378AB53 80-90 37-47 18.95 22.20 378AB04 378AB54 85-110 43-54 19.40 23.10 378AB05 378AB55 50-60 23.40 31.85 378AB06 378AB56 56-67 23.90 32.90 378AB07 378AB57 63-73 34.25 45.50 378AB08 378AB58 69-80 43.45 55.85 378AB09 378AB59 Ref: A1A2/03/07 105-120 & Systems Limited, Components Coercial Enquiries, Wrexham Industrial Estate, Fax: 23.40 +44 (0) 8029 5465 LL13 9HP, UK 30.00 Prysmian Cables Unit, Oak Road, Wrexham, Tel +44 (0) 845 767 8345, 378AB29 85-110 - 35.00 www.prysmian.co.uk 378AB36 72-85 - 56.95 378AB37 82-95 - 58.70 378AB38 92-105 - 59.40 378AB39 102-115 - 59.60 378AB40 112-125 - 61.10 378AB41 122-135 - 63.05 378AB42 132-145 - 69.45 MULTICLEAT STAINLESS STEEL - STANDARD & HEAVY DUTY > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables > Suitable for most climatic conditions, weatherproof and waterproof > Gland rated to IP66 with use of suitable sealing washer or thread sealant at gland interface > Service temperature -20 C to +90 C > CuZn39Pb3 extruded brass alloy used for guaranteed strength and Number Cable Diameter Cable Diameter Standard Heavy Duty for Singles for Trefoil Standard Heavy Duty 378JB01 378JB51 36-65 24-34 56.00 65.00 378JB02 378JB52 60-85 30-41 56.00 65.00 378JB03 378JB53 80-90 37-47 58.00 68.00 378JB04 378JB54 85-110 43-54 58.00 68.00 378JB05 378JB55 50-60 63.00 73.00 378JB06 378JB56 56-67 64.00 75.00 378JB07 378JB57 63-73 68.00 79.00 378JB08 378JB58 69-80 69.00 80.00 378JB09 378JB59 105-120 63.00 73.00 378JB29 85-110 - 85.00 378JB36 80-110 - 81.50 378JB37 82-95 - 84.00 378JB38 92-105 - 85.00 378JB39 102-115 - 85.00 378JB40 112-125 - 87.00 378JB41 122-135 - 90.00 378JB42 132-145 - 99.00 Please contact your nearest sales office for pricing on Multicleats with coated Aluminium, Hot dipped Galvanised and coated Cast Iron bases. 9PH, UK 60
BARR-X EEx d IIC Brass Barrier Gland Cable Cleats MULTIPLE CABLE CLEATS & ACCESSORIES C MULTISTRAP SYSTEM Industrial Gland Kits A1/A2 Brass Gland Kit KM409 Series B A F Indoor/Outdoor for Single & Trefoil cables 24-145 A multistrap is a strap complete with a tensioning clip, securing pin and winding key all made Application > Indoor/Outdoor for Unarmoured Cable from high corrosion resistant non-magnetic stainless steel Gland Details They are used as an intermediate restraint between Multicleats Features & Benefits > Brass indoor and outdoor cable gland & accessories > For circular, unarmoured plastic or rubber sheathed cables They may be used to bind cables together > Suitable for most climatic conditions, weatherproof and waterproof > Kit comprises: - A1/A2 Gland Multistraps are supplied in two strengths:- - Brass locknut - PVC shroud Standard duty, designed to have 2 loops of 0.38 thick strap around the cables > 2 per kit size up to and including 25 Gland References & Thread s Cable Dimensions Heavy duty, designed to have 3 loops of 0.38 thick strap around the cables Gland Dimensions Basic Metric NPT Max. Max. No. of Inner Sheath Overall Braid Approx. Hexagon MULTIstrap STANDARD & HEAVY DUTY Tested BS EN 50368 Dia. Over Conductors Dia. A Dia. B Wire Length Technical Data > EN 50262 Design Thread Design Thread Conductors Dia. C D A/C A/F > BS6121:Pt 1:1989 No. Number * No. Cable Diameter Cable Diameter Short Circuit Withstand > Gland rated to IP66 with use of suitable sealing washer or thread sealant E F Min Max Min Max For Singles For Trefoil at gland interface Standard Heavy Duty Standard Heavy Duty - Standard 1.8m spacing= 43KA RMS > Service temperature -20 C to +90 C 377AB01 377AB51 36-65 24-34 9.40 14.20 (Peak 114KA) > CuZn39Pb3 extruded brass alloy used for guaranteed strength and performance 20S 377AB02 424TX52 M20 377AB52 1.5 424TX0260-85 ½ - 14 NPT 30-41 11.0 30 9.75 15.10 11.5 8.0 15.8 - Heavy 0.21.5m / 0.3spacing 67= 50KA 34.0 RMS 30.5 20 377AB03 424TX53 M20 377AB53 1.5 424TX0380-90 ½ - 14 NPT 37-47 11.0 3010.20 16.15 (Peak 130KA) 12.5 11.7 20.8 0.2 / 0.3 64 34.0 30.5 377AB04 377AB54 85-110 43-54 25 424TX55 M25 1.5 424TX05 ¾ - 14 NPT 16.0 4210.70 11.517.00 - Heavy 1.2m spacing = 71KA RMA 18.0 17.0 27.2 0.2 / 0.45 65 42.2 37.6 377AB05 377AB55 50-60 (Peak 184KA) 11.10 17.90 32 424TX56 M32 1.5 424TX06 1-11½ NPT 22.1 60 17.0 25.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3 377AB06 377AB56 56-67 11.60 18.90 Operating Temperature 1000 C for 40 377AB07 424TX57 M40 377AB57 1.5 424TX07 1¼ - 11½ NPT 63-73 28.2 100 12.05 24.020.00 31.5 26.5 39.9 0.3 / 0.45 2 hours 77 61.5 56.4 50 377AB08 424TX59 M50 377AB58 1.5 424TX09 2-11½ NPT 69-80 37.1 200 12.50 30.020.90 41.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1 63 424TX61 M63 377AB29 1.5 424TX1185-110 2½ - 8 NPT 48.4 400-40.022.00 54.0 46.5 65.3 0.3 / 0.45 90 87.4 80.0 377AB36 72-85 75 424TX63 M75 1.5 424TX13 3-8 NPT 58.6 400-53.021.95 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 377AB37 82-95 - 23.05 85 424TX64 M85 2 424TX14 3 Ref: - 8 A1A2/03/07 NPT Prysmian Cables & Systems 65.8 Limited, Components Unit, Oak Road, 400 Wrexham Industrial Estate, Wrexham, 60.0 LL13 9HP, UK 74.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 377AB38 92-105 - 24.20 www.prysmian.co.uk 377AB39 102-115 - 25.45 377AB40 112-125 - 26.70 * 1.5 Pitch threads are supplied 15 long, 2 pitch threads are supplied 20 long 377AB41 122-135 - 28.05 NPT thread lengths 377AB42 comply with new UL2225 requirements 132-145 - 29.45 LSF LINER LSF liners are installed with multistraps to protect the cable sheaths Number Applicable Cleat s 377LSF01 01-04 & 51-54 4.45 377LSF02 05-09 & 29,39,55-59 7.00 D E THREADED ROD PROTECTIVE PLASTIC END CAPS Used for fixing cable cleats Used to protect exposed end of studding Number Description FTR10 Threaded Rod M10 x 1M 4.95 FTR12 Threaded Rod M12 x 1M 5.95 Number Description Hole PEC10 Protective Plastic End Caps 10 0.30 PEC12 Protective Plastic End Caps 12 0.45 Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 61 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
r Gland C Cable Cleats ACCESSORIES BOLTS F D verall ia. B Max General purpose fixing bolts E Braid Wire Dia. C Number Gland Dimensions 15.8 0.2 / 0.3 67 34.0 30.5 20.8 0.2 Discount / 0.3 on application 64 34.0 30.5 27.2 0.2 / 0.45 65 42.2 37.6 33.5 0.3 / 0.45 77 53.6 47.3 39.9 0.3 / 0.45 77 61.5 56.4 52.6 0.3 / 0.45 84 77.2 70.1 General purpose fixing nuts 65.3 0.3 / 0.45 90 87.4 80.0 78.0 0.3 / 0.45 96 Number 109.2 98.8 Price per 100 Bright Zinc Plated Nut Brass Nut Bright Zinc Plated Nut Brass Nut 88.0 0.3 / 0.45 108 126.0 115.0 Price per 100 Zinc Plated Brass Zinc Plated Brass FHB06X20 FBB06X20 M6 x 20 11.55 38.50 FHB06X30 FBB06X30 M6 x 30 15.40 47.25 FHB08X25 FBB08X25 M8 x 25 16.50 51.30 FHB08X30 FBB08X30 M8 x 30 16.80 87.75 FHB08X40 FBB08X40 M8 x 40 20.25 97.20 FHB10X25 FBB10X25 M10 x 25 24.70 121.50 FHB10X30 FBB10X30 M10 x 30 26.70 133.65 Approx. Hexagon FHB10X40 FBB10X40 M10 x 40 29.00 148.50 Length FHB10X50 D FBB10X50 A/C A/F M10 x 50 37.30 162.00 FHB12X35 FBB12X35 E F M12 x 35 51.15 202.50 FHB12X40 FBB12X40 M12 x 40 54.00 303.75 FHB12X50 FBB12X50 M12 x 50 60.50 337.50 FHB12X70 FBB12X70 M12 x 70 95.00 506.25 NUTS FHN06 FBN06 M6 7.00 14.85 FHN08 FBN08 M8 9.00 22.95 FHN10 FBN10 M10 12.50 60.75 FHN12 FBN12 M12 25.50 168.75 CHANNEL NUTS (ALL TYPES) Designed to fit into channel so brackets can be fitted Number Hole Price per 100 No Spring Short Spring Long Spring No Spring Short Spring Long Spring FCNN06 FCNS06 FCNL06 6 90.00 130.00 130.00 FCNN08 FCNS08 FCNL08 8 120.00 180.00 180.00 FCNN10 FCNS10 FCNL10 10 120.00 180.00 180.00 FCNN12 FCNS12 FCNL12 12 150.00 195.00 195.00 SPRING & FLAT WASHERS General purpose fixing washers Number Phosphor Bright Zinc Bright Zinc Bronze Spring Plated Flat Plated Spring Brass Flat Phosphor Bronze Spring Bright Zinc Plated Flat Price per 100 Bright Zinc Plated Spring Brass Flat FBSW06 FFW06 FSW06 FBW06 M6 10.00 1.85 3.20 6.00 FBSW08 FFW08 FSW08 FBW08 M8 25.00 2.70 4.00 12.00 FBSW10 FFW10 FSW10 FBW10 M10 45.00 4.00 4.10 18.00 FBSW12 FFW12 FSW12 FBW12 M12 75.00 5.20 5.30 30.00 9PH, UK 62
Cable Ties & Marking Systems CONTENTS Nylon Cable Ties 64 Nylon Cable Markers 66 Stainless Steel Cable Ties 67 Stainless Steel Banding System 70 All Round Band & Accessories 71 Stainless Steel Cable Markers 72 63
Cable Ties & Marking Systems NYLON CABLE TIES TY-RAP - premium cable ties Halogen & Silcone Free Operating Temperature - 40 C to 85 C Flaability Rating UL 94 V-2 Approved by UL, Lloyd Register, Germanischer Lloyd & Bureau Veritas TY-RAP cable ties for cable bundles from 2-229 Premium cable ties with steel locking barb designed for industrial applications Manufactured from virgin nylon 6.6 Rounded edges on the head and strap Ribbed and stippled surface to prevent the tie from slipping Angled tail for easy insertion into the locking head Non slip tail for easy grip Available as standard in UV Resistant Black & Natural and other colours on request Available in 9 sizes Bundle Tensile Pack Price per 100 Natural Black diameter in N Quantity Natural Black TY23M TY23MX 92 x 2.4 2-16 80 100 2.50 2.90 TY232M TY232MX 203 x 2.4 2-50 80 100 5.60 6.70 TY24M TY24MX 140 x 3.6 2-29 180 100 5.00 5.55 TY26M TY26MX 284 x 3.6 2-76 130 100 12.00 14.30 TY244M TY244MX 368 x 3.6 2-103 130 100 18.00 20.85 TY253M TY253MX 295 x 4.8 3.5-78 220 100 18.50 22.00 TY28M TY28MX 361 x 4.8 3.5-102 220 100 17.25 20.80 TY27M TY27MX 340 x 6.9 6-90 540 100 30.00 35.00 TY29M TY29MX 771 x 6.9 6-229 540 100 76.00 88.00 STANDARD CABLE TIES Cable Ties for cable bundles from 10-225 General purpose cable tie for cable bundling and everyday applications Manufactured from nylon 6.6 Available as standard in UV Resistant Black & Natural Available in 14 sizes Halogen & Silcone Free Operating Temperature - 40 C to +85 C - Flaability Rating UL 94 V-2 Bundle Tensile Pack Price per 100 Natural Black diameter in N Quantity Natural Black UB100A-N UB100A-B 100 x 2.5 22 80 100 0.70 0.70 UB140A-N UB140A-B 144 x 2.5 35 80 100 1.12 1.12 UB200A-N UB200A-B 200 x 2.5 55 80 100 1.70 1.70 UB150A-N UB150A-B 150 x 3.5 35 80 100 1.81 1.81 UB200B-N UB200B-B 198 x 3.5 50 135 100 1.95 1.95 UB160C-N UB160C-B 160 x 4.6 35 135 100 2.20 2.20 UB200C-N UB200C-B 200 x 4.6 50 225 100 2.41 2.41 UB250C-N UB250C-B 245 x 4.6 65 225 100 2.65 2.65 UB270C-N UB270C-B 270 x 4.6 73 225 100 2.74 2.74 UB300C-N UB300C-B 300 x 4.6 85 225 100 2.85 2.85 UB385C-N UB385C-B 390 x 4.7 110 225 100 4.50 4.50 UB760E-N UB760E-B 760 x 7.6 225 535 100 26.25 26.25 64
Cable Ties & Marking Systems NYLON CABLE TIES Flame retardant cable ties for cable bundles from 2-101 Flame retardant cable ties designed for use in low flaability and low smoke environments such as public transport, tunnels etc Manufactured from low smoke flame retardant nylon 6.6 FLAME RETARDANT cable ties Available in white in 6 sizes Colour Bundle diameter Tensile in N Pack Quantity Price per 100 TS1025-HF White 100 x 2.5 2-24 90 100 3.25 TS1435-HF White 140 x 3.5 2.5-36 180 100 6.00 TS2405-HF White 200 x 4.5 3-51 220 100 9.00 TS2845-HF White 280 x 4.5 5-76 220 100 23.60 TS3645-HF White 360 x 4.5 5-101 220 100 29.00 TS3675-HF White 360 x 7.5 5-101 540 100 39.00 Halogen & Silicone Free Operating Temperature 40 C to +85 C Flaability Rating UL94-V0 Approved by UL, Lloyd Register, Germanishcher Lloyd & Bureau Veritas IDENTIFICATION CABLE TIES/MARKING PEN Identification cable ties for cable bundles up to 44 Identification cable ties are designed for durable marking and tying of cable bundles Manufactured from virgin nylon 6.6 Available in natural in 2 sizes with special marking pen Colour Bundle diameter Tensile in N Pack Quanity Price per Pack L-4-18ID-9-C Natural 100 x 2.5 19 max 80 100 6.60 L-7-50ID-9-C Natural 200 x 4.7 44 max 220 100 12.70 WT163M-1 Black Ink - - - 1 870.00 Halogen & Silicone Free Operating Temperature 40 C to +85 C Flaability Rating UL94-V2 DELTEC CABLE SUPPORT SYSTEM Cable support system with metallic locking barb Cable support system available on a reel and cut to length based on cable bundle size. Manufactured from toughened acetal Available in UV resistant black on a reel with locking heads sold separately Colour Tensile in N Pack Quantity Price per Pack TYD-50R Black 15.2m x 12.7 1110 1 19.25 TYD-LH Black 21.6 x 19.1 N/A 100 22.70 Halogen & silicone free. Operating Temperature 40 C to +85 C Flaability Rating UL 94 - HB 65
Cable Ties & Marking Systems NYLON CABLE MARKERS STRAIGHT CUT WIRE MARKERS Z Type wire markers for cable diameters from 1.7-16 Straight Cut Wire Markers for cable identification and marking on small diameter cables Chevron design to interlock when fitted Available in various colours Standard figures available = A-Z, 0-9, +,-,/, earth & blank Add character suffix to part no when ordering item Operating Temperature 30 C to +70 C Flaability Rating UL94-V2 Conductor CSA Conductor Diameter Pack Quantity Price per Pack PZ02 0.5-0.75 2 1.7-2.8 1000 3 7.50 PZ1 0.75-4.0 2 2.5-5 1000 3 7.50 PZ2 2.5-16 2 4.0-10 250/500 4 3.75 PZ3 16-70 2 8.0-16 100 5 2.50 OVAL CUT WIRE MARKERS K Type wire markers for use with carrier strips Operating Temperature 30 C to +70 C Flaability Rating UL94-V2 Oval Wire Markers for cable identification and marking of larger diameter cables and pipes when used on carrier strips Oval design to interlock when fitted. Available in yellow PVC with black figures Standard figures available = A-Z, 0-9, +,-,/, earth & blank Add character suffix to part no when ordering item Conductor CSA Conductor Diameter Pack Quantity Price per Pack POK10 40-100 2 up to 7.0 500 6 6.50 CARRIER STRIPS Standard & Multipurpose carrier strips for larger cables Designed for use with K range of markers Standard & multipurpose carrier strips designed to be attached parallel to larger diameter cables or installed directly onto the cable secured with a cable tie Available in black PVC Operating Temperature 30 C to +70 C Flaability Rating UL94-V2 Description Pack Quantity Price per 100 POH7 7 digit carrier strip 100 2.75 POH12 12 digit carrier strip 100 4.25 POH18 18 digit carrier strip 100 5.95 POH30 30 digit carrier strip 100 9.45 PKH70 10 digit carrier strip 100 5.25 PKH110 20 digit carrier strip 100 6.75 66
Cable Ties & Marking Systems STAINLESS STEEL CABLE TIES Ball-Lok stainless steel cable ties for cable bundles from 50-305 Ball-Lok Ties - Uncoated Self locking stainless steel cable ties for use in hazardous area environments Material Bundle Diameter Tensile in N Pack Quantity Price per 100 KE1128 304 Grade S/S 201 x 4.6 50 890 100 42.65 KE1138 304 Grade S/S 259 x 4.6 69 890 100 47.35 KE1148 304 Grade S/S 360 x 4.6 102 890 100 51.90 KE1158 304 Grade S/S 520 x 4.6 152 890 100 62.70 KE1168 304 Grade S/S 679 x 4.6 203 890 100 76.35 KE1178 304 Grade S/S 838 x 4.6 254 890 100 91.70 KE1188 304 Grade S/S 1067 x 4.6 305 890 100 114.60 KE1328 304 Grade S/S 201 x 7.9 50 1335 100 48.95 KE1338 304 Grade S/S 259 x 7.9 69 1335 100 55.00 KE1348 304 Grade S/S 360 x 7.9 102 1335 100 61.25 KE1358 304 Grade S/S 520 x 7.9 152 1335 100 79.40 KE1368 304 Grade S/S 679 x 7.9 203 1335 100 94.60 KE1378 304 Grade S/S 838 x 7.9 254 1335 100 110.15 KE1388 304 Grade S/S 1067 x 7.9 305 1335 100 134.40 KE0128 316 Grade S/S 201 x 4.6 50 890 100 53.65 KE0138 316 Grade S/S 259 x 4.6 69 890 100 60.30 KE0148 316 Grade S/S 360 x 4.6 102 890 100 64.90 KE0158 316 Grade S/S 520 x 4.6 152 890 100 78.35 KE0168 316 Grade S/S 679 x 4.6 203 890 100 95.45 KE0178 316 Grade S/S 838 x 4.6 254 890 100 114.15 KE0188 316 Grade S/S 1067 x 4.6 305 890 100 143.25 KE0328 316 Grade S/S 201 x 7.9 50 1335 100 61.25 KE0338 316 Grade S/S 259 x 7.9 69 1335 100 68.80 KE0348 316 Grade S/S 360 x 7.9 102 1335 100 76.35 KE0358 316 Grade S/S 520 x 7.9 152 1335 100 99.25 KE0368 316 Grade S/S 679 x 7.9 203 1335 100 118.35 KE0378 316 Grade S/S 838 x 7.9 254 1335 100 137.55 KE0388 316 Grade S/S 1067 x 7.9 305 1335 100 168.00 Operating Temperature - 80 C to + 538 C UL, Lloyd Register, DNV and US Coast Guard approved. CE Marked Ball-Lok Ties - Coated Coated Ball-Lok stainless steel cable ties from cable bundles for 50-254 Self locking stainless steel cable ties for use in hazardous area environments Epoxy coated to avoid damage to cable sheaths Material Bundle Diameter Tensile in N Pack Quantity Price per 100 KE0228 Coated 316 Grade S/S 201 x 4.6 50 668 100 99.25 KE0238 Coated 316 Grade S/S 259 x 4.6 69 668 100 113.25 KE0248 Coated 316 Grade S/S 360 x 4.6 102 668 100 126.00 KE0258 Coated 316 Grade S/S 520 x 4.6 152 668 100 152.00 KE0268 Coated 316 Grade S/S 679 x 4.6 203 668 100 187.10 KE0278 Coated 316 Grade S/S 838 x 4.6 254 668 100 244.35 KE0428 Coated 316 Grade S/S 201 x 7.9 50 1112 100 103.25 KE0438 Coated 316 Grade S/S 259 x 7.9 69 1112 100 115.20 KE0448 Coated 316 Grade S/S 360 x 7.9 102 1112 100 129.90 KE0458 Coated 316 Grade S/S 520 x 7.9 152 1112 100 156.55 KE0468 Coated 316 Grade S/S 679 x 7.9 203 1112 100 194.70 KE0478 Coated 316 Grade S/S 838 x 7.9 254 1112 100 252.00 Operating Temperature - 80 C to + 538 C UL, Lloyd Register, DNV and US Coast Guard approved. CE Marked 67
Cable Ties & Marking Systems STAINLESS STEEL CABLE TIES TIE-LOK TIES - UNCOATED Tie-Lok stainless steel cable ties for cable bundles from 25-254 Low Profile stainless steel cable ties for use in hazardous area environments Operating Temperature - 80 C to + 538 C DNV approved Material Bundle Diameter Tensile in N Pack Quantity Price per 100 AS221 304 Grade S/S 164 x 4.5 25 668 100 35.30 As222 304 Grade S/S 254 x 4.5 51 668 100 37.00 as223 304 Grade S/S 406 x 4.5 102 668 100 42.05 as224 304 Grade S/S 572 x 4.5 152 668 100 53.80 as225 304 Grade S/S 737 x 4.5 203 668 100 62.25 as211 304 Grade S/S 254 x 6.35 51 1112 100 42.05 as212 304 Grade S/S 419 x 6.35 101 1112 100 47.10 as213 304 Grade S/S 572 x 6.35 152 1112 100 60.55 as214 304 Grade S/S 737 x 6.35 203 1112 100 70.65 as215 304 Grade S/S 889 x 6.35 254 1112 100 80.75 Multi-Lok Ties - Uncoated Multi-Lok stainless steel cable ties for cable bundles from 48-193 Multi locking stainless steel cable ties for use in hazardous area environments Operating Temperature - 80 C to + 538 C UL, Lloyd Register, DNV and US Coast Guard approved. CE Marked Material Bundle Diameter Tensile in N Pack Quantity Price per 100 AE601 316 Grade S/S 150 x 7 48 890 100 52.50 AE602 316 Grade S/S 225 x 7 71 890 100 63.00 AE603 316 Grade S/S 300 x 7 96 890 100 69.30 AE604 316 Grade S/S 450 x 7 144 890 100 82.95 AE605 316 Grade S/S 610 x 7 193 890 100 99.75 AE701 316 Grade S/S 150 x 12 48 1112 100 62.30 AE702 316 Grade S/S 225 x 12 71 1112 100 66.90 AE703 316 Grade S/S 300 x 12 96 1112 100 76.15 AE704 316 Grade S/S 450 x 12 144 1112 100 96.85 AE705 316 Grade S/S 610 x 12 193 1112 100 110.65 Multi-Lok Ties - coated Coated Multi-Lok stainless steel cable ties for cable bundles from 48-193 Multi locking stainless steel cable ties for use in hazardous area environments Nylon 11 black coated to avoid damage to the cable sheaths Operating Temperature - 80 C to + 538 C UL, Lloyd Register, DNV and US Coast Guard approved CE Marked Material Bundle Diameter Tensile in N Pack Quantity Price per 100 AE611 Coated 316 Grade S/S 150 x 7 48 890 100 84.40 AE612 Coated 316 Grade S/S 225 x 7 71 890 100 97.15 AE613 Coated 316 Grade S/S 300 x 7 96 890 100 99.75 AE614 Coated 316 Grade S/S 450 x 7 144 890 100 126.00 AE615 Coated 316 Grade S/S 610 x 7 193 890 100 141.75 AE711 Coated 316 Grade S/S 150 x 12 48 1112 100 89.95 AE712 Coated 316 Grade S/S 225 x 12 71 1112 100 106.00 AE713 Coated 316 Grade S/S 300 x 12 96 1112 100 110.65 AE714 Coated 316 Grade S/S 450 x 12 144 1112 100 136.05 AE715 Coated 316 Grade S/S 610 x 12 193 1112 100 159.10 68
Cable Ties & Marking Systems STAINLESS STEEL CABLE TIES Coated Band-It stainless steel cable ties for cable bundles from 38-185 Band It Ties - coated Releasable stainless steel cable ties for use in hazardous area environments PPA 571 black coated to avoid damage to the cable sheaths Available in 2 widths (6.4 & 9.6) Material Bundle Diameter Pack Quantity Price per 100 AE111 Coated 316 Grade S/S 152 x 6.4 38 100 72.60 AE112 Coated 316 Grade S/S 229 x 6.4 63 100 82.35 AE113 Coated 316 Grade S/S 305 x 6.4 86 100 93.05 AE114 Coated 316 Grade S/S 457 x 6.4 137 100 104.50 AE115 Coated 316 Grade S/S 610 x 6.4 185 100 122.35 AE311 Coated 316 Grade S/S 152 x 9.6 38 100 83.95 AE312 Coated 316 Grade S/S 229 x 9.6 63 100 91.25 AE313 Coated 316 Grade S/S 305 x 9.6 86 100 97.25 AE314 Coated 316 Grade S/S 457 x 9.6 137 100 133.50 AE315 Coated 316 Grade S/S 610 x 9.6 185 100 151.70 Operating Temperature - 80 C to + 538 C UL, Lloyd Register, DNV and US Coast Guard approved. CE Marked band-fast system Band-Fast cable restraint clamps for single, trefoil & quadfoil cable formations Designed for heavy duty cable bundling and clamping applications as an alternative to conventional cable cleats Low cost alternative to cable cleats - 50% labour saving No accessories required (fixing, liners, packers & studding etc) Zero halogen, low smoke and fume product PPA 571 black coated to avoid damage to the cable sheaths Independently tested for shock & short circuit characteristics Suitable for single, trefoil or quadfoil cable formations Available for single or double wrap applications DNV & GL Type Approved Material Temperature Rating 50 C to +538 C Type Material Max Cable Diameter Single/Trefoil/Quadfoil Pack Quantity BANDF11 Single Coated 316 Grade S/S 300x16 40/13/12 100 3.95 BANDF12 Single Coated 316 Grade S/S 400x16 75/28/25 100 3.95 BANDF13 Single Coated 316 Grade S/S 500x16 100/43/37 100 4.95 BANDF14 Single Coated 316 Grade S/S 600x16 130/57/50 100 6.25 BANDF15 Single Coated 316 Grade S/S 700x16 160/70/60 100 7.25 BANDF21 Double Coated 316 Grade S/S 300x16 25/10/9 100 4.95 BANDF22 Double Coated 316 Grade S/S 400x16 50/13/12 100 4.95 BANDF23 Double Coated 316 Grade S/S 500x16 55/21/18 100 5.25 BANDF24 Double Coated 316 Grade S/S 600x16 70/28/25 100 6.25 BANDF25 Double Coated 316 Grade S/S 700x16 85/35/31 100 7.45 BANDF26 Double Coated 316 Grade S/S 800x16 100/42/37 100 7.45 BANDF27 Double Coated 316 Grade S/S 1000x16 130/57/50 100 7.90 69
Cable Ties & Marking Systems STAINLESS STEEL BANDING SYSTEM Band & Buckle System - Banding Stainless Steel Banding for larger diameter cables and pipes Stainless steel banding for use with buckles to enable securing and bundling around large cables and pipes Applications include insulation fixing, cable bundling and sign erection Band & buckle can be quickly formed around virtually any diameter Superior corrosion resistance Available in 201, 316 grade stainless steel & nylon 11 coated version Material Price per Roll C201 201 Grade S/S 30.5m x 4.76 16.90 C202 201 Grade S/S 30.5m x 6.35 16.90 C203 201 Grade S/S 30.5m x 9.53 20.80 C204 201 Grade S/S 30.5m x 12.70 28.80 C205 201 Grade S/S 30.5m x 15.88 35.50 C206 201 Grade S/S 30.5m x 19.05 42.20 C402 316 Grade S/S 30.5m x 6.35 25.35 C403 316 Grade S/S 30.5m x 9.53 30.75 C404 316 Grade S/S 30.5m x 12.70 43.20 C405 316 Grade S/S 30.5m x 15.88 53.25 C406 316 Grade S/S 30.5m x 19.05 63.30 AE432 Ppa Coated 316 Grade S/S 25m x 6.35 55.90 AE433 Ppa Coated 316 Grade S/S 25m x 9.53 55.90 AE434 Ppa Coated 316 Grade S/S 25m x 12.70 72.80 AE435 Ppa Coated 316 Grade S/S 25m x 15.88 91.90 AE436 Ppa Coated 316 Grade S/S 25m x 19.05 110.25 Band & Buckle System - Buckles Stainless steel buckles for the fixing of banding to larger cables and pipes Stainless steel buckles for use with banding to enable securing and bundling around large cables and pipes Superior corrosion resistance Available in 201 and 316 grade stainless steel Material Pack Quantity Price per 100 C251 201 Grade S/S 4.76 100 11.35 C252 201 Grade S/S 6.35 100 11.35 C253 201 Grade S/S 9.53 100 12.80 C254 201 Grade S/S 12.70 100 18.30 C255 201 Grade S/S 15.88 100 22.30 C256 201 Grade S/S 19.05 100 27.95 C452 316 Grade S/S 6.35 100 17.00 C453 316 Grade S/S 9.53 100 19.20 C454 316 Grade S/S 12.70 100 27.45 C455 316 Grade S/S 15.88 100 33.45 C456 316 Grade S/S 19.05 100 41.95 AE452 316 Grade S/S 6.35 100 16.20 AE453 316 Grade S/S 9.53 100 16.70 AE454 316 Grade S/S 12.70 100 21.55 AE455 316 Grade S/S 15.88 100 26.90 AE456 316 Grade S/S 19.05 100 31.70 70
Cable Ties & Marking Systems ALL ROUND BAND & ACCESSORIES All Round Band Multi purpose all round band All Round Band is an all purpose fixing system suitable for hostile environments Easy to form around any section Available in galvanised steel, stainless steel uncoated and in PPA coated versions Available in 3 widths (12, 17 & 26) Material Colour Price per Roll AE505 Galvanised Steel Uncoated Metallic 10m x 12 9.80 AE506 Galvanised Steel Uncoated Metallic 10m x 17 11.16 AE507 Galvanised Steel Uncoated Metallic 10m x 26 20.20 AE565 Ppa Coated Galvanised Steel Black 10m x 12 16.80 AE566 Ppa Coated Galvanised Steel Black 10m x 17 19.95 AE567 Ppa Coated Galvanised Steel Black 10m x 26 36.25 AE405 Stainless Steel Uncoated Metallic 10m x 12 23.70 AE406 Stainless Steel Uncoated Metallic 10m x 17 41.95 AE407 Stainless Steel Uncoated Metallic 10m x 26 62.20 AE465 Stainless Steel Coated Black 10m x 12 45.30 AE466 Stainless Steel Coated Black 10m x 17 77.65 AE467 Stainless Steel Coated Black 10m x 26 104.70 ae575 Ppa Coated Galvanised Steel Black 25m x 12 42.15 ae576 Ppa Coated Galvanised Steel Black 25m x 17 51.35 ae577 Ppa Coated Galvanised Steel Black 25m x 26 93.40 AE425 Stainless Steel Uncoated Metallic 25m x 12 60.55 AE426 Stainless Steel Uncoated Metallic 25m x 17 107.00 AE427 Stainless Steel Uncoated Metallic 25m x 26 159.00 AE475 Stainless Steel Coated Black 25m x 12 115.75 AE476 Stainless Steel Coated Black 25m x 17 198.50 AE477 Stainless Steel Coated Black 25m x 26 268.00 CABLE SHEATH PROTECTOR ZHCP Cable sheath protector for use with metal cable ties Cable sheath protector is designed to fit underneath the metal cable ties to protect the sheath of the cable Suitable for low and high temperature environments Fire Tested (Def standard 07-247) Low smoke and fume product Available in 5 sizes Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 Material Colour Price per 100m ZHCP-NR-1-0 Nylon 6.6 Black 16 494.25 ZHCP-NR-2-0 Nylon 6.6 Black 10 385.60 ZHCP-NR-3-0 Nylon 6.6 Black 6 316.40 ZHCP-NR-4-0 Nylon 6.6 Black 5 182.90 ZHCP-NR-6-0 Nylon 6.6 Black 13 355.85 While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com http://energy.tycoelectronics.com 71 Our coitment. Your advantage.
Cable Ties & Marking Systems STAINLESS STEEL CABLE MARKERS EASY READ SYSTEM Made from 316 Stainless Steel Easy read stainless steel marking system Designed to provide a marking system in hazardous area environments Used with stainless steel cable tie range A complete range of letters, s & symbols Fits onto easy strips and carriers or directly on to cable ties Fasten strips & carriers to pipe and cable with cable ties Easy to read in dim light CHARACTERS Pack Price per 100 Description Quantity AE010* LETTERS A-Z (Add suffix * when ordering) - 100 18.00 Pack Price per 100 Description Quantity AE018* NUMBERS 1-10 (Add suffix * when ordering) - 100 18.00 Description Pack Quantity Price per 100 AE035 EASY MINUS/HYPHEN - - 100 18.00 AE036 EASY BLANK - 100 18.00 AE046 EASY PLUS + - 100 18.00 AE047 EASY EARTH - 100 18.00 AE048 EASY SINE - 100 18.00 AE049 EASY SLASH/ - 100 18.00 AE053 ARROW - 100 18.00 CARRIER STRIPS Description Pack Quantity Price per 100 AE043 EASY CARRIER 6 9.53 x 92.5 100 78.00 AE044 EASY CARRIER10 9.53 x 130.6 100 102.00 AE045 EASY CARRIER16 9.53 x 187.7 100 120.00 AE050 EASY STRIP Short 9.53 x 108 100 93.00 AE051 EASY STRIP Medium 9.53 x 146 100 130.00 AE052 EASY STRIP Long 9.53 x 203.2 100 158.00 EASY READ KIT Pack Description Quantity AE060 EASY READ Kit - Contains 50 of each character/carrier/strip - 1 1995.00 72
LV Jointing CONTENTS Resin Joints 74 Unarmoured, Pilot/Telecom Joints 78 Hazardous Area Joints 79 Resins 80 Heatshrink & Coldshrink Joints 81 Heatshrink LV Products 83 Coldshrink LV Products 86 Jointing Accessories 88 73
LV Jointing RESIN JOINTS PAGE 52 - NOT DRAWN AT 100% THIS IS 62% PAGE 53 - NOT DRAWN AT 100% THIS IS 64% LV Inline Resin Joints - Armoured Cables Inline Resin joints for LV armoured power cables PAGE 54 - NOT DRAWN AT 100% THIS IS 40% 1000V Rated (or 3.3kV with Mastic Patches) Tested to BS EN 50393 PAGE 56 - NOT DRAWN AT 100% THIS IS Tested 36% to Engineering Standard C81 PAGE STRAIGHT 74 - THIS JOINTS IS DATA 100% A Designed to connect LV power cables inline by encapsulating in a resin filled shell Excellent mechanical protection PAGE 55 - NOT DRAWN AT 100% THIS Clear IS rigid 76% joint shells to aid correct installation Large shell design allows the use of mechnical connectors Can be used at 3.3Kv with the use of mastic patches Available with NEW REACH compliant HDI resin on request Kit comprises mould shell, 2 part polyurethane MDI resin, earth continuity kit, PVC tapes, gloves and crimp ferrules (on request) Mechanical Connectors suitable for this range are available on page 39 PAGE 57 - NOT DRAWN AT 100% PAGE 59 - NOT DRAWN AT 100% THIS IS 59% Maximum Cable THIS IS 68% MDI Resin HDI Resin MDI HDI TSJ-6 TSJ-6-HDI 6 2 x 4 Core 36.50 POA TSJ-16 TSJ-16-HDI 16 2 x 4 Core 48.70 POA TSJ-35 TSJ-35-HDI 35 2 x 4 Core 52.35 POA TSJ-70 TSJ-70-HDI 70 2 x 4 Core 98.10 POA TSJ-120 TSJ-120-HDI 120 2 x 4 Core 128.05 POA TSJ-185 TSJ-185-HDI 185 2 x 4 Core 256.20 POA TSJ-300 TSJ-300-HDI 300 2 x 4 Core 358.70 POA PAGE 75 - NOT DRAWN AT 100% THIS IS 62% C B e d Dimensions Number PAGE 77 - NOT DRAWN AT 100% PAGE 76 - THIS IS 100% A B C ØD ØE THIS IS 62% TSJ-6 275 50 85 21 9 TSJ-16 295 60 95 27 15 TSJ-35 330 80 115 33 21 TSJ-70 395 110 140 41 29 TSJ-120 575 120 150 57 39 TSJ-185 670 135 170 67 49 TSJ-300 870 160 195 77 59 Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 70-300 19 STRAIGHT JOINTS SELECTION TABLE Number able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Cable conductor size 2 Cable entry diameter 2-core 3-core 4-core min max TSJ-6 1.5-10 1.5-10 1.5-6 9 21 TSJ-16 10-25 10-25 10-16 15 27 TSJ-35 35-50 35-50 25-35 21 33 TSJ-70 70-95 70-95 50-70 29 41 TSJ-120 120-150 120-150 95-120 39 57 TSJ-185 185-240 185-240 150-185 49 67 TSJ-300 300 300 240-300 59 77 Please contact the sales office to join other cable variations 74 Our coitment. Your advantage.
AGE 52 - NOT DRAWN AT 100% HIS IS 62% BARR-X EEx d IIC Brass Barrier Gland PAGE 53 - NOT DRAWN AT 100% THIS IS 64% C LV Jointing RESIN JOINTS LV Inline Resin Joints - Armoured Cables B A F Inline Resin joints for LV armoured power cables Gland Details Designed to connect LV power cables inline by encapsulating in a resin filled shell Excellent mechanical protection AGE 54 - NOT DRAWN Large transparent, AT 100% high impact resistant shells PAGE 55 - NOT DRAWN AT 100% HIS IS 40% Large, extra wide shell design allows THIS the IS use 76% of mechanical connectors Clear Resin bags to aid with mixing process Can Gland be References used at 3.3Kv & with Thread the s use of mastic patches Cable Dimensions Gland Dimensions Basic All resin Metric joints kit supplied with NEW NPT REACH compliant Max. JEM resin Max. No. of Inner Sheath Overall Braid Approx. Hexagon 1000V Rated (or 3.3kV with Mastic Kit comprises mould shell, JEM resin, earth continuity Dia. kit, Over PVC tapes, Conductors gloves and crimp Dia. ferrules A Dia. B Wire Length Design Thread Design Thread Conductors Patches) Dia. C D A/C A/F No. (on request) * No. E F Min Max Min Mechanical Connectors suitable for this range are available on page 39 Max Tested to BS EN 50393 AGE 56 - NOT DRAWN AT 100% PAGE 57 - NOT DRAWN AT 100% PAGE 59 - NOT Tested DRAWN to Engineering AT 100% Standard C81 20S 424TX52 M20 1.5 424TX02 ½ - 14 NPT 11.0 30 11.5 8.0 15.8 0.2 / 0.3 67 34.0 30.5 HIS IS 36% THIS IS 59% Maximum Cable THIS IS 68% NEW REACH compliant JEM resin 20 424TX53 M20 1.5 424TX03 ½ - 14 NPT 11.0 30 12.5 11.7 20.8 0.2 / 0.3 64 34.0 30.5 JST6 6 2 x 4 Core 43.80 25 424TX55 M25 1.5 424TX05 ¾ - 14 NPT 16.0 42 11.5 18.0 17.0 27.2 0.2 / 0.45 65 42.2 37.6 JST16 16 2 x 4 Core 58.45 32 JST35 424TX56 M32 1.5 424TX06 1-11½ NPT 22.1 35 2 x 4 Core 60 17.0 62.8025.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3 40 JST95 424TX57 M40 1.5 424TX07 1¼ - 11½ NPT 28.2 95 2 x 4 Core 100 24.0 154.0031.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4 50 JST185 424TX59 M50 1.5 424TX09 2-11½ NPT 185 37.1 x 4 Core 200 30.0 307.5041.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1 JST300 300 2 x 4 Core 430.45 63 424TX61 M63 1.5 424TX11 2½ - 8 NPT 48.4 400 40.0 54.0 46.5 65.3 0.3 / 0.45 90 87.4 80.0 JST400 400 2 x 4 Core 695.00 75 424TX63 M75 1.5 424TX13 3-8 NPT 58.6 400 53.0 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 AGE 74 85 - THIS 424TX64 IS 100% M85 2 424TX14 3-8 NPT 65.8 400 PAGE 60.0 7574.0 - NOT 68.0 DRAWN 88.0AT 0.3 100% / 0.45 108 126.0 115.0 THIS IS 62% STRAIGHT JOINTS DATA * 1.5 Pitch threads are supplied 15 long, 2 pitch threads are supplied 20 long NPT thread lengths comply with new UL2225 requirements D A D C E B E Dimensions PAGE 77 - NOT DRAWN AT 100% AGE 76 - THIS Number IS 100% A B THIS CIS 62% D E JST6 240 115 75 12 22 JST16 310 125 85 20 35 JST35 390 130 100 24 40 JST95 620 160 130 27 51 JST185 795 230 205 40 65 JST300 950 240 210 55 80 JST400 1100 275 260 56 92 STRAIGHT JOINTS SELECTION TABLE Cable conductor size 2 Cable entry diameter Number 2-core 3-core 4-core Min Max JST6 1.5-10 1.5-6 1.5-6 12 22 JST16 16-25 10-25 10-16 20 35 JST35 35 35 25-35 24 40 JST95 50-95 50-95 50-95 27 51 JST185 120-185 120-185 120-185 40 65 JST300 240-300 240-300 240-300 55 80 JST400 400 400 400 56 92 Please contact the sales office to join other cable variations Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 75 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
LV Jointing RESIN JOINTS LV Branch Resin Joints - Armoured Cables PAGE 54 - NOT DRAWN AT 100% THIS IS 40% PAGE 56 - NOT DRAWN AT 100% THIS IS 36% 1000V Rated (or 3.3kV with Mastic Patches) Tested to BS EN 50393 Tested to Engineering Standard C81 PAGE 74 - THIS IS 100% PAGE 55 - NOT DRAWN AT 100% THIS IS 76% Branch Resin joints for LV armoured power cables Designed to connect LV power cables in branch formation by encapsulating in a resin filled shell Excellent mechanical protection Clear rigid joint shells to aid correct installation Large shell design allows the use of mechnical connectors PAGE 57 - NOT DRAWN AT 100% PAGE 59 - NOT DRAWN AT 100% Can be used at 3.3Kv with the use of mastic patches THIS IS 59% THIS IS 68% Available with NEW REACH compliant HDI resin on request Kit comprises mould shell, 2 part polyurethane MDI resin, earth continuity kit, PVC tapes and gloves Mechanical Connectors suitable for this range are available on page 40 Maximum Cable MDI Resin HDI Resin MDI HDI TBJ-6 TBJ-6-HDI 6 2 x 4 Core 51.75 POA TBJ-16 TBJ-16-HDI 16PAGE 2 x 4 Core 75 - NOT DRAWN 73.25 AT 100% POA TBJ-35 TBJ-35-HDI 35THIS 2 x 4 Core IS 62% 85.40 POA TBJ-70 TBJ-70-HDI 70 2 x 4 Core 144.30 POA TBJ-120 TBJ-120-HDI 120 2 x 4 Core 202.00 POA TBJ-185 TBJ-185-HDI 185 2 x 4 Core 276.30 POA TBJ-300 TBJ-300-HDI 300 2 x 4 Core 512.50 POA PAGE BRANCH 76 - JOINTS THIS IS DATA 100% A PAGE 77 - NOT DRAWN AT 100% THIS IS 62% C B E D Dimensions Number A B C ØD ØE TBJ-6 245 60 120 21 9 TBJ-16 315 75 140 27 15 TBJ-35 380 100 170 33 21 TBJ-70 470 120 185 41 29 TBJ-120 595 150 220 57 39 TBJ-185 690 180 240 67 49 TBJ-300 870 195 275 77 59 Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 70-300 19 BRANCH JOINTS SELECTION TABLE Cable conductor size 2 Cable entry diameter Number 2-core 3-core 4-core min max TBJ-6 1.5-10 1.5-10 1.5-6 9 21 TBJ-16 10-25 10-25 10-16 15 27 TBJ-35 35-50 35-50 25-35 21 33 TBJ-70 70-95 70-95 50-70 29 41 TBJ-120 120-150 120-150 95-120 39 57 TBJ-185 185-240 185-240 150-185 49 67 TBJ-300 300 300 240-300 59 77 able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Please contact the sales office to join other cable variations 76 Our coitment. Your advantage.
BARR-X EEx d IIC Brass Barrier Gland C LV Jointing RESIN JOINTS PAGE 54 - NOT DRAWN AT 100% THIS IS 40% PAGE 55 - NOT DRAWN AT 100% THIS IS 76% LV Branch Resin Joints - Armoured Cables B A F Branch Resin joints for LV armoured power cables Designed to connect LV power cables in branch formation by encapsulating in a resin filled shell Excellent mechanical protection PAGE Gland 56 - NOT Details Large DRAWN transparent, AT 100% high impact resistant shells PAGE 57 - NOT DRAWN AT 100% PAGE 59 - NOT DRAWN AT 100% THIS IS 36% THIS IS 59% THIS IS 68% Large, extra wide shell design allows the use of mechanical connectors Clear Resin bags to aid with mixing process Can Gland be References used at 3.3Kv & with Thread the s use of mastic patches Cable Dimensions Gland Dimensions Basic All resin Metric joints kit supplied with NEW NPT REACH compliant Max. JEM resin Max. No. of Inner Sheath Overall Braid Approx. Hexagon 1000V Rated (or 3.3kV with Mastic Kit comprises mould shell, JEM resin, earth continuity Dia. Over Conductors Dia. A Dia. B Wire Length Design Thread Design Thread kit, PVC tapes and gloves Conductors Patches) Dia. C D A/C A/F No. Mechanical Connectors * No. suitable for this range are available on page 40 E F Min Max Min Max Tested to BS EN 50393 Maximum Cable Tested to Engineering Standard C81 PAGE 74 20S- THIS 424TX52 IS 100% M20 1.5 424TX02 ½ - 14 NPT 11.0 30 PAGE 75 11.5- NOT 8.0DRAWN 15.8 AT 0.2100% / 0.3 67 34.0 30.5 JBR-6 6 2 x 4 Core THIS 62.10 IS 62% NEW REACH compliant JEM resin 20 424TX53 M20 1.5 424TX03 ½ - 14 NPT 11.0 30 12.5 11.7 20.8 0.2 / 0.3 64 34.0 30.5 JBR-16 16 2 x 4 Core 87.90 JBR-35 35 2 x 4 Core 102.50 JBR-95 95 2 x 4 Core 242.40 JBR-185 185 2 x 4 Core 331.50 JBR-300 300 2 x 4 Core 615.00 25 424TX55 M25 1.5 424TX05 ¾ - 14 NPT 16.0 42 11.5 18.0 17.0 27.2 0.2 / 0.45 65 42.2 37.6 32 424TX56 M32 1.5 424TX06 1-11½ NPT 22.1 60 17.0 25.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3 40 424TX57 M40 1.5 424TX07 1¼ - 11½ NPT 28.2 100 24.0 31.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4 50 424TX59 M50 1.5 424TX09 2-11½ NPT 37.1 200 30.0 41.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1 63 424TX61 M63 1.5 424TX11 2½ - 8 NPT 48.4 400 PAGE 40.0 77 54.0 - NOT 46.5 DRAWN 65.3 AT 0.3100% / 0.45 90 87.4 80.0 PAGE 76 - THIS IS 100% 75 424TX63 M75 1.5 424TX13 3-8 NPT 58.6 400 THIS 53.0 IS 65.5 62% 58.0 78.0 0.3 / 0.45 BRANCH 96 JOINTS 109.2DATA 98.8 85 424TX64 M85 2 424TX14 3-8 NPT 65.8 400 60.0 74.0 A 68.0 88.0 0.3 / 0.45 108 126.0 115.0 D E * 1.5 Pitch threads are supplied 15 long, 2 pitch threads are supplied 20 long D C E B NPT thread lengths comply with new UL2225 requirements Dimensions Number A B C D E JBR-6 240 125 75 12 22 JBR-16 345 160 95 20 35 JBR-35 435 175 100 24 40 JBR-95 650 210 190 27 51 JBR-185 870 250 230 40 65 JBR-300 1020 300 310 55 80 BRANCH JOINTS SELECTION TABLE Cable conductor size 2 Cable entry diameter Number 2-core 3-core 4-core min max JBR-6 1.5-10 1.5-6 1.5-6 12 22 JBR-16 16-25 10-25 10-16 20 35 JBR-35 35 35 25-35 24 40 JBR-95 50-95 50-95 50-95 27 51 JBR-185 120-185 120-185 120-185 40 65 JBR-300 240-300 240-300 240-300 55 80 Please contact the sales office to join other cable variations Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 77 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
LV Jointing Unarmoured, Pilot & Telecom Resin Joints LV Inline Resin Joints - Unarmoured Cables 1000kV Rated (3.3kV with additional insulation tape) Tested to BS EN 50393 Supplied with re-formulated resin conforming to European legislation (REACH) Inline resin joints for LV unarmoured power cables Designed to connect inline unarmoured LV power cables by encapsulating in a resin filled shell One part mould body with a top seal and 5 fixing clips for a simpler installation process and reduces the chance of resin leakage - no need for extra taping Pre-cut foam ends which reduces the need for sawing and taping the end of the mould Fully integrated delivery system which significantly reduces the chance of resin waste Closed cap to prevent pollution Large shell design allows the use of mechanical connectors Clear resin bags to aid with the mixing process Supplied with European legislation (REACH) compliant 2 part polyetherurethane resin Kit comprises mould shell, Scotchcast 40G resin, snap in 5 core spacer, abrasive sponge, gloves and crimp ferrules (on request) Mechanical Connectors suitable for this range are available on page 39 LV Inline Resin Joints - Pilot & Telecom Cables Maximum cable size 2 91-NBA-0 4 2 x 4 Core 13.50 91-NBA-1 10 2 x 4 Core 15.60 91-NBA-3 35 2 x 4 Core 32.30 91-NBA-4 50 2 x 4 Core 40.00 91-NBA-5 95 2 x 4 Core 55.60 91-NBA-6 150 2 x 4 Core 117.80 91-NBA-7 240 2 x 4 Core 240.00 Inline resin joints for pilot and telecom cables ty 1000kV Rated (3.3kV with additional insulation tape) Tested to BS EN 50393 Supplied with re-formulated resin conforming to European legislation (REACH) Designed to connect inline pilot and telecom cables by encapsulating in a resin filled shell One part mould body with a top seal and 5 fixing clips for a simpler installation process and reduces the chance of resin leakage - no need for extra taping Pre-cut foam ends which reduces the need for sawing and taping the end of the mould Fully integrated delivery system which significantly reduces the chance of resin waste Closed cap to prevent pollution Large shell design allows the use of mechanical connectors Clear resin bags to aid with the mixing process Supplied with European legislation (REACH) compliant 2 part polyetherurethane resin Kit comprises mould shell, Scotchcast 470W resin, copper stocking, constant force springs, Scotch 23 tape, web spacer tape and crimp ferrules (on request) Mechanical Connectors suitable for this range are available on page 39 Maximum cable size 2 Telecom Pilot LVI-1/2-PT 2 Pair 0.9 2-28.20 LVI-1/3-PT 5-15 Pair 0.9 2 2-4 Core 1.5-2.5 2 46.17 LVI-1/4-PT 20-30 Pair 0.9 2 7-19 Core 1.5-2.5 2 67.25 LVI-1/5-PT 40-50 Pair 0.9 2 27-37 Core 1.5-2.5 2 118.40 LVI-1/6-PT 60-100 Pair 0.9 2-141.30 78
BARR-X EEx d IIC Brass Barrier Gland C LV Jointing HAZARDOUS AREA JOINTS LV Inline Petrochemical Resin Joints - Armoured Cables B A F d Details Inline petrochemical resin joints for LV armoured power cables Designed to connect inline multi-core, armoured polymeric, low voltage energy cables in hazardous areas Two part mould body with snap fit closing system for quick and easy handling Transparent flame retardant mould body for easy control of connector distances Flame retardant according to UL94 V0 Gland References Chemical & Thread resistant, s especially against hydro carbons Cable Dimensions Gland Dimensions Large shell design allows the use of mechanical connectors Metric NPT Max. Max. No. of Inner Sheath Overall Braid Approx. Hexagon Clear resin bags to aid with the mixing process 3.3kV Rated Dia. Over Conductors Dia. A Dia. B Wire Length Design Thread Design Thread Conductors Dia. C D A/C A/F No. Supplied * No. with NEW European standard (REACH) compliant 1402 FR hazardous area resin Tested to Cenelec E HD623 F (EN 50392) Min Max Min Max Kit comprises mould shell, Scotchcast 1402 resin, earth bonding kit, gloves and crimp ferrules Supplied with re-formulated resin 424TX52 (on request) conforming to European legislation M20 1.5 424TX02 ½ - 14 NPT 11.0 30 11.5 8.0 15.8 0.2 / 0.3 67 34.0 30.5 Mechanical Connectors suitable for this range 3M are available Electrical on page Markets 39 Division (REACH) 424TX53 M20 1.5 424TX03 ½ - 14 NPT 11.0 3M Scotchcast 30 Cable Joints 12.5 11.7 20.8 0.2 / 0.3 64 34.0 30.5 424TX55 M25 1.5 424TX05 ¾ - 14 NPT 16.0 42Maximum 11.5 cable 18.0 Price 17.0Each 27.2 size 2 0.2 / 0.45 65 42.2 37.6 424TX56 M32 1.5 424TX06 LVI-3/2-C 1-11½ NPT 22.1 60 6 2 17.0 x 4 core 25.0 19.0 33.5 80.14 0.3 / 0.45 77 53.6 47.3 424TX57 M40 LVI-3/3-C 1.5 424TX07 1¼ - 11½ NPT 28.2 100 16 2 x 424.0 core 31.5 109.26 26.5 39.9 0.3 / 0.45 77 61.5 56.4 424TX59 M50 LVI-3/4 1.5 424TX09 2-11½ NPT 37.1 200 35 2 x 430.0 core 41.5 164.00 36.0 52.6 0.3 / 0.45 84 77.2 70.1 424TX61 M63 LVI-3/5 1.5 424TX11 2½ - 8 NPT 48.4 400 70 2 x 440.0 core 54.0 288.79 46.5 65.3 0.3 / 0.45 90 87.4 80.0 LVI-3/6 120 2 x 4 core 655.06 424TX63 M75 1.5 424TX13 3-8 NPT 58.6 400 53.0 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 LVI-3/7 185 2 x 4 core 994.40 424TX64 M85 2 424TX14 3-8 NPT 65.8 400 LVI-3/8 400 2 60.0 74.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 x 4 core 1507.94 m Pitch threads are supplied 15 long, 2 pitch threads are supplied 20 long Inline fire retardant resin joints for LV armoured power cables LV Inline Fire Retardant Resin Joints - Armoured Cables thread lengths comply with new UL2225 requirements Speed The shell material is fire retardant, rigid thermo setting glass reinforced phenolic Designed to connect LV power cables in specialist applications where flame retardant materials are required because of expected fire hazard Excellent mechanical protection High impact resistant shells Designed for use with crimp connectors Kit comprises mould shell, JEM resin, earth bonding kit, gloves and crimp ferrules (on request) Branch joints available on request Mechanical connectors suitable for this range are available on page 39 Maximum cable size 2 Reliability ZHMPJ-2 10 2 x 4 Core 328.00 ZHMPJ-3 16 2 x 4 Core 348.00 ZHMPJ-4 25 2 x 4 Core 355.00 ZHMPJ-5 50 2 x 4 Core 427.00 ZHMPJ-6 120 2 x 4 Core 589.00 ZHMPJ-7 240 2 x 4 Core 647.00 ZHMPJ-8 400 2 x 4 Core 820.00 D Safety 3M Scotchcast LV Cable Jointing E 1000V Rated (or 3.3kV with Mastic Patches) Tested to Cenelec HD623 (EN 50392) Tested to BS6724 - Low smoke and acid gas emissions RX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 79 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
r Gland C LV Jointing RESINS Two Polyurethane Resin F D E Designed for cable joint encapsulation The resin consists of 2 parts: resin & hardener JSSC 7 litres 53.00 verall ia. B Max Gland Dimensions Braid Approx. Hexagon Type approved to CENELEC Wire Length Dia. C specification D EN A/C 50393 A/F E F JEM RESIN 15.8 0.2 / 0.3 67 34.0 30.5 20.8 0.2 / 0.3 64 34.0 30.5 27.2 0.2 / 0.45 65 42.2 37.6 33.5 0.3 / 0.45 77 53.6 47.3 39.9 0.3 / 0.45 77 61.5 56.4 52.6 0.3 / 0.45 84 77.2 70.1 65.3 0.3 / 0.45 90 87.4 80.0 78.0 0.3 / 0.45 96 109.2 98.8 88.0 0.3 / 0.45 108 126.0 115.0 Type approved to CENELEC specification EN 50393 Power Utility specification ENA TS C81/3 European legislation (REACH) compliant resin peed HAZARDOUS AREA RESIN Safety bility otchcast Cable Jointing Type approved to CENELEC specification EN 50393 European legislation (REACH) compliant resin Designed for cable joint encapsulation Supplied in clear pouches providing visibility during mixing Non-hazardous (non- irritant, non-sensitising, non-flaable) Independent testing has shown that no hazard labelling is required The resin consists of 2 parts: acrylic based resin & hardener Designed for cable joint encapsulation Supplied in clear pouches providing visibility during mixing Flame Retardant Chemical Resistant The resin consists of 2 parts: resin & hardener JEM 6 litres 58.00 1402-FR B 200ml 33.64 1402-FR C 370ml 50.22 1402-FR Mix PACK 7.18 litres 342.89 9PH, UK 80
LV Jointing HEATSHRINK JOINTS Heatshrink Joint - Multicore Cables Heatshrink joint for armoured multi-core cables Designed to connect LV armoured multi-core cables within a heatshrink joint Suitable for indoor or outdoor environments Excellent electrical insulation and mechanical strength from armour cage Simple & fast installation - no curing time Iediate backfill Maximum cable size 2 ECKJ-0017 1-2.5 2 x 7 Core 65.90 ECKJ-0018 1-2.5 2 x 14 Core 81.30 ECKJ-0019 1-2.5 2 x 21 Core 99.95 ECKJ-0020 1-2.5 2 x 40 Core 122.90 ECKJ-0021 1-2.5 2 x 75 Core 151.10 1000V Rated Tested to BS EN 50393 Temperature Rating 50 C to +50 C MULTI-CORE WITH ARMOUR DATA Number Number of Cores of Conductor 2 Diameter over Inner Sheath Overall Diameter ECKJ-0017 4-7 1-2.5 9-15 14-23 ECKJ-0018 8-14 1-2.5 10-18 15-26 ECKJ-0019 15-21 1-2.5 18-26 24-35 ECKJ-0020 22-40 1-2.5 23-26 30-45 ECKJ-0021 41-75 1-2.5 32-44 39-55 Heatshrink Joint - Multi-Pair Cables Heatshrink joint for armoured multi-pair cables Designed to connect LV armoured multi-pair cables within a heatshrink joint. Suitable for indoor or outdoor environments Excellent electrical insulation and mechanical strength from armour cage Simple & fast installation - no curing time Iediate backfill Maximum cable size 2 ECKJ-0140 0.6-1 2-1- 4 Pair 65.90 ECKJ-0141 0.6-1 2-5-7 Pair 81.30 ECKJ-0142 0.6-1 2-8-19 Pair 99.95 ECKJ-0143 0.6-1 2-20-37 Pair 122.90 ECKJ-0144 0.6-1 2-38-61 Pair 151.10 MULTI-PAIR WITH ARMOUR DATA Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 1000V Rated UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 Tested to BS EN 50393 Temperature Rating 50 C to +50 C Number Number of Pairs of Conductor Diameter over Overall Diameter 2 Inner Sheath ECKJ-0140 1-4 2 x 0.6-2 x 1.0 9-15 15-23 ECKJ-0141 5-7 2 x 0.6-2 x 1.0 10-18 15-26 ECKJ-0142 8-19 2 x 0.6-2 x 1.0 18-26 24-35 ECKJ-0143 20-37 2 x 0.6-2 x 1.0 23-26 30-45 ECKJ-0144 38-61 2 x 0.6-2 x 1.0 32-44 39-55 While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 81 http://energy.tycoelectronics.com Our coitment. Your advantage.
LV Jointing HEATSHRINK & COLDSHRINK JOINTS Straight Heatshrink Joint - Armoured Cables Straight heatshrink joints for LV armoured cables Designed to connect inline LV armoured cables within a heatshrink joint Ideal for vertical installations in indoor and outdoor environment Excellent electrical insulation and mechanical strength from armour cage Simple & fast installation - no curing time Iediate backfill 1000V Rated Tested to BS EN 50393 Temperature Rating 50 C to +50 C Maximum cable size AR101 1.5-4 2 4 core 24.00 AR102 6-16 2 4 Core 38.50 AR3 (RATED TO 3.3kW) 25-50 2 4 Core 69.50 AR4 (RATED TO 3.3kW) 70-150 2 4 Core 158.50 AR5 (RATED TO 3.3kW) 185-300 2 4 Core 244.00 LUL Approved Straight Heatshrink Joint - Armoured Cables 1000V Rated Tested to BS EN 50393 eed Safety Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 70-300 19 bility London Underground Approved Temperature Rating 50 C to +50 C Straight Coldshrink Joint Kit otchcast able effort to ensure the accuracy TECHNICAL of the information DATA contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding able Jointing the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or 3.3kV) misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A 1000V Rated (larger sizes up to Tested to BS EN 50393 Straight heatshrink joints for LV armoured cables Designed to connect inline LV armoured cables within a heatshrink joint Ideal for vertical installations in indoor and outdoor environment Excellent electrical insulation and mechanical strength from armour cage Simple & fast installation - no curing time Iediate backfill Low Smoke Zero Halogen Maximum cable size SMOE82051 185-300 2 364.00 SMOE82244 13 PAIR 1.5 2 385.00 SMOE82231 37 PAIR 1.5 2 420.00 Straight coldshrink joints for LV armoured and unarmoured cables Designed to connect inline LV armoured & unarmoured cables within a cold applied joint Low temperature installation - no heat required Faster installation time with pullout Improved rubber formulation withstands rough backfilling Waterproof seal Max Cable Diameter Diameter over Armour LC1 16.2-33.1 9-15 22.00 LC2 16.2-33.1 14-22 24.00 LC3 16.2-33.1 18.5-29 27.00 LC4 24.9-56.4 23.5-37 38.00 LC5 37.8-84.3 31-50 77.00 LC6 37.8-84.3 44-70 80.43 82 Our coitment. Your advantage.
LV Jointing HEATSHRINK LV PRODUCTS THIN WALL HEATSHRINK TUBING Heatshrinkable thin wall insulating tubing PE cross linked polyolefin single wall heatshrink tubing is designed for phase marking, bundling, strain relief & electrical insulation Flame Retardant and abrasion resistance Flexible rapid shrinkage with 2:1 shrink ratio Other colours available on request (MOQ may apply) Application Range Price per Metre Black, Brown, Green / Yellow Blue, Grey HT6.4-3.2 6.4-3.2 1.50 2.70 HT9.5-4.8 9.5-4.8 1.70 3.30 HT12.7-6.4 12.7-6.4 1.85 3.50 HT19-9.5 19.0-9.5 2.50 4.90 HT25.4-12.7 25.4-12.7 4.20 8.00 HT38-19 38.0-19.0 7.00 13.80 HT51-25.4 51.0-25.4 8.95 17.40 HT76.2-38 76.2-38.0 15.50 - HT101-51 101.0-51.0 25.00-1000V Rated Shrinking Temperature > 110C Dielectric Strength > 200kV/cm Medium Wall Heatshrink Tubing Heatshrinkable medium wall insulating tubing Cross linked polyolefin dual wall medium heatshrink tubing is designed for the cable jacketing sealing and electrical insulation of LV power cables Halogen free and resistant to UV light Resistant to temperature changes and iune to oils and solvents Flexible rapid shrinkage with 3:1 shrink ratio Available in 1500 length as standard Available in black only Available without internal tubing sealant on request Application Range MWTM10/3 9.0-3.5 1500 10.40 MWTM16/5 14.5-5.5 1500 11.85 MWTM25/8 22.5-9.0 1500 15.60 MWTM35/12 31.5-13.0 1500 20.20 MWTM50/16 45.0-17.5 1500 26.50 MWTM63/19 57.0-21.0 1500 33.65 MWTM75/22 68.0-24.0 1500 39.45 MWTM85/25 77.0-27.5 1500 44.75 MWTM95/29 86.0-32.0 1500 49.90 MWTM115/34 104.0-37.0 1500 64.75 MWTM140/42 126.0-46.0 1500 74.00 MWTM160/50 144.0-55.0 1500 86.50 MWTM180/60 162.0-66.0 1500 112.00 Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner Shrinking Temperature > 110C A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 Length UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 83 http://energy.tycoelectronics.com 1000V Rated Tensile Strength 14 MPa min Dielectric Strength > 200kV/cm Our coitment. Your advantage. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A
LV Jointing HEATSHRINK LV PRODUCTS THICK Wall Heatshrink Tubing Heatshrinkable thick wall insulating tubing 1000V Rated Shrinking Temperature > 110C Tensile Strength 12 MPa min Dielectric Strength > 170kV/cm Cross linked polyolefin dual wall thick heatshrink tubing is designed for the cable jacketing, sealing and electrical insulation of LV power cables in underground applications The tubings inner co-extruded hot melt adhesive wall gives a dependable moisture seal over most irregular shapes Halogen free and resistant to UV light Resistant to temperature changes and iune to oils and solvents Its mechanical strength enables iediate backfillling of cable trenches after jointing Flexible rapid shrinkage with 3:1 shrink ratio Available in 1500 length as standard Available in black only Application Range Length WCSM12/3 10-3.5 1500 16.40 WCSM16/4 14-4.5 1500 18.75 WCSM24/6 22-6.5 1500 24.30 WCSM34/8 31-9.0 1500 31.40 WCSM48/12 44-13 1500 40.65 WCSM56/16 50-17.5 1500 53.10 WCSM70/20 63-22 1500 60.35 WCSM90/25 81-27 1500 69.45 WCSM110/30 100-33 1500 72.50 WCSM130/35 118-38 1500 93.85 WCSM160/50 144-55 1500 125.40 WCSM180/50 162-55 1500 129.50 Heatshrink Wraparound Heatshrinkable wraparound for cable repairs Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 70-300 19 1000V Rated Shrinking Temperature > 110C Tensile Strength 17 MPa min Dielectric Strength > 180kV/cm able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Designed to be a fast and permanent cable repair and sealing system for insulation upto 1000V and jacketing applications upto 35Kv Ideal for repairing long buried cable where it would be impossible to use a tube A moisture-proof, insulating and tight-fitting repair is then obtained in one step by heating, which makes the sleeve diameter shrink and the adhesive coating melt and flow into the interstices Resistant to temperature changes and iune to oils and solvents Available in 1500 lengths as standard and 250, 500, 750 & 1000 on request Application Range Length CRSM34/10 21.0-11.0 1500 51.85 CRSM53/13 32.0-17.0 1500 57.00 CRSM84/20 50.0-24.0 1500 62.95 CRSM107/29 65.0-31.0 1500 66.10 CRSM143/36 86.0-33.0 1500 75.80 CRSM198/55 120.0-56.0 1500 87.10 CRSM250/98 150.0-103.0 1500 101.10 84 Our coitment. Your advantage.
LV Jointing HEATSHRINK LV PRODUCTS Heatshrink Wraparound Heatshrinkable wraparound for cable repairs Designed to be a fast and permanent cable repair and sealing system for insulation upto 1000V and jacketing applications upto 35Kv Ideal for repairing long buried cable where it would be impossible to use a tube A moisture-proof, insulating repair is obtained in one step by heating, which makes the sleeve diameter shrink and the adhesive coating melt and flow into the interstices Resistant to temperature changes and iune to oils and solvents Available in 250, 500, 750 & 1000 on request Diameter Range Length HDCW55/15 55.0-15.0 1500 50.85 HDCW80/25 80.0-25.0 1500 54.10 HDCW140/40 140.0-40.0 1500 3M Electrical Markets Division 60.40 3M Scotchcast Cable Joints Heatshrink Breakouts 4 Core Heatshrink cable breakouts for power cables Cross linked medium wall heatshrink breakouts are designed for sealing of cable cores Coated with hot melt adhesive which seals onto the cable sheath and core insulation Resistant to temperature changes and iune to oils and solvents Halogen free and resistant to UV light Available in 2 & 3 core version on request Application Range 4CB6-50 50.0-6.0 14.85 4CB35-70 70.0-35.0 16.70 4CB50-150 150.0-50.0 24.75 4CB185-300 300.0-185.0 26.50 Heatshrink Cable End Caps Heatshrink end caps for power cables 1000V Rated Shrinking Temperature 120C Dielectric Strength 220kV/cm 1000V Rated Shrinking Temperature 110C Speed Dielectric Strength 100kV/cm Safety Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 Reliability Cross linked medium wall heatshrink end caps are designed for sealing of cable ends Coated with a hot melt adhesive which seals onto the cable sheath Resistant to temperature changes and iune to oils and solvents Halogen free and resistant to UV light Application Range 3M Scotchcast While Tyco Electronics and its affiliates referenced herein have made every reasonable TECHNICAL effort to ensure the DATA accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any 1000V implied warranty Rated LV Cable Jointing regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited Shrinking to, the sale, resale, Temperature use or misuse of its 110C products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, Dielectric connectors Strength & fittings, 100kV/cm electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. EC4-9 9.0-4.0 2 1.50 EC8-18 18.0-8.0 2 1.90 EC18-36 36.0-18.0 2 3.25 EC28-50 50.0-28.0 2 5.30 EC38-70 70.0-38.0 2 6.45 EC55-95 95.0-55.0 2 7.95 EC70-110 110.0-70.0 2 11.50 Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 85 http://energy.tycoelectronics.com Our coitment. Your advantage.
LV Jointing COLDSHRINK LV PRODUCTS Coldshrink Tubes - Silicone Rubber Coldshrink tubes in silcone rubber for LV power cables Meets worldwide standards ANSI, IEEE, VDE, JCAA, REA & CSA Rated upto 1000V for cable insulation. MOD Approved Operating Temperature 55 C to +260 C Designed for the sealing and electrical insulation of LV power cables Improved tough rubber which is suitable for direct burial applications Simple installation no external heat source required Good thermal stability Excellent sealing properties; retaining its resiliency and pressure after prolonged ageing Hydrophobic, resistant to moisture Resists fire and will not support a flame Resistant to ozone and UV light Resistant to acids & alkalis Diameter Range Length 8443-2 14.22-6.86 39 4.95 8443-6.5 14.22-6.86 140 5.95 8445-2.5 18.29-8.89 48 4.95 8445-7.5 18.29-8.89 152 5.95 8447-3.2 24.13-12.19 64 5.95 8447-8 24.13-12.19 175 7.25 Coldshrink Tubes - EPDM Rubber Coldshrink tubes in EPDM rubber for LV power cables ty Meets worldwide standards ANSI, IEEE, VDE, JCAA, REA & CSA. Rated upto 1000V for cable insulation Designed for the sealing and electrical insulation of LV power cables Improved tough rubber which is suitable for direct burial applications Simple installation no external heat source required Good thermal stability Excellent sealing properties; retaining its resiliency and pressure after prolonged ageing Waterproof and resists fungi Resistant to ozone and UV light Resistant to acids & alkalis Diameter Range Length 8423-6 14.3-7.8 152 8.90 8425-8 20.8-10.2 203 9.25 8426-9 25.4-13.0 229 12.00 8426-11 25.4-13.0 279 13.95 8427-6 33.0-17.5 152 8.90 8427-12 33.0-17.5 305 17.50 8427-16 33.0-17.5 406 25.00 8428-6 49.3-24.0 152 13.50 8428-12 49.3-24.0 305 23.00 8428-18 49.3-24.0 609 36.50 8429-6 67.8-32.2 152 13.50 8429-9 67.8-32.2 229 20.90 8429-12 67.8-32.2 305 24.95 8429-18 67.8-32.2 457 42.00 8430-9 93.7-42.6 229 28.00 8430-18 93.7-42.6 457 49.50 86
LV Jointing COLD SHRINK LV PRODUCTS Coldshrink Tubes - Network Rail Approved Approved by Network Rail for terminal insulation and inline joints for track feeder applications Improved tough rubber which is suitable for direct burial applications Simple installation no external heat source required Good thermal stability Excellent sealing properties; retaining its resiliency and pressure after prolonged ageing Waterproof and resists fungi Resistant to ozone and UV light Resistant to acids & alkali COLDSHRINK END CAPS Min Cable Max Cable Length LO41 240 2 1000 2 228 24.95 LO42 150 2 240 2 191 8.90 LA11 380 2 1000 2 457 38.50 3M Electrical Markets Division 3M Scotchcast Cable Joints Meets worldwide standards ANSI, IEEE, VDE, JCAA, REA & CSA. Rated upto 1000V for cable insulation Coldshrink end caps for LV power cables Designed for the sealing and electrical insulation of cable ends Suitable for direct burial applications Simple installation no external heat source required Good thermal stability Excellent sealing properties; retaining it resiliency and pressure after prolonged ageing Waterproof and resists fungus Resistant to ozone and UV light Resistant to acids & alkalis Diameter Range EC-1 20.9-11.6 4.75 EC-2 30.1-15.9 6.50 EC-3 49.2-26.0 9.25 EC-4 84.3-45.5 11.95 Coldshrink Abandonment Kits Coldshrink Abandonment kits for LV power cables A complete kit to abandon LV cable either temporarily or permanently Improved tough rubber which is suitable for direct burial applications Simple installation no external heat source required Kit includes - coldshrink end cap & tube, armour continuity & tapes Diameter Range CSCAK/1 18.0-12.0 25.95 CSCAK/2 25.0-18.0 28.81 CSCAK/3 42.0-25.0 32.26 CSCAK/4 55.0-42.0 42.83 CSCAK/5 81.0-56.0 53.31 Speed Safety Reliability 3M Scotchcast LV Cable Jointing 87 Meets worldwide standards ANSI, IEEE, VDE, JCAA, REA & CSA Rated upto 1000V for cable insulation Tested up to 3.3Kv
LV Jointing LV JOINTING ACCESSORIES TINMANS M SOLDER Solder stick for tinning copper CORALINE FLUX Flux for copper conductors JTS 15.00 PLUMBERS D SOLDER Solder stick for plumbing applications J70131-02 0.45kg 19.50 BICAlFLUX Flux for aluminium conductors JPS 9.90 ALCA P SOLDER Solder stick for aluminium F71003-02 150cc 29.70 TALLOW Plumbers tallow JAP 7.50 UNIAL Universal jointing paste JTALLOW 0.3kg 13.50 R391 Electrical weatherproof compound 88 UNIAL 2.5kg 11.10 JR391 0.5kg 15.00
HV Jointing and Terminating CONTENTS 11kV Heatshrink Indoor & Outdoor Terminations 90 11kV Heatshrink Indoor Accessories 94 11kV Heatshrink Outdoor Accessories 97 33kV Indoor & Outdoor Heatshrink Terminations 99 33kV Heatshrink Indoor Accessories 101 33kV Heatshrink Outdoor Accessories 103 11kV Heatshrink Joints 105 11kV Shrinkset Joints 107 11 & 33kV Coldshrink Joints 109 33kV Heatshrink Joints 110 52-72kV Heatshrink Terminations & Joints 112 11 & 33kV Heatshrink Insulation Products 113 11kV Coldshrink Indoor & Outdoor Terminations 115 11 & 33kV Coldshrink Indoor & Outdoor Terminations 115 33kV Coldshrink Indoor & Outdoor Terminations 118 11 & 33kV Indoor & Outdoor Coldshrink Accessories 119 11kV Coldshrink Joints 120 33kV Coldshrink Joints 123 52-72kV Coldshrink Terminations & Joints 125 52-72kV Self Supporting Terminations & Joints 126 89
HV Jointing and Terminating 11kV HEATSHRINK INDOOR & OUTDOOR TERMINATIONS SINGLE CORE TERMINATION WITH INTEGRAL STRESS CONTROL FOR XLPE CABLE - INDOOR Tested in accordance with CENELEC specification HD 629 which encompasses IEC, BS and VDE etc. All IXSU/OXSU components have full traceability of raw materials and manufacture according to ISO 9001 & ISO 14001 Single core heatshrink termination for XLPE cables in indoor applications Designed to terminate single core, polymeric insulated 11kV cables in indoor applications to switchgear & cable end boxes Highly reliable U.K industry standard termination Range taking with few components needed New ceramic stress control Compact design No shelf life limitation Suitable for use on 11kV triplex cables Kit contents - Insulation tubing including co-extruded stress control, sealant tapes and installation instructions Conductor IXSU-F-3111 10-35 2 64.00 IXSU-F-3121 25-95 2 74.00 IXSU-F-3131 95-240 2 88.00 IXSU-F-3141 240-500 2 107.00 IXSU-F-3151 500-800 2 133.00 IXSU-F-3161 1000-1200 2 219.00 THREE CORE TERMINATION WITH INTEGRAL STRESS CONTROL FOR XLPE CABLE - INDOOR Three core heatshrink termination for XLPE cables in indoor applications Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 TECHNICAL 35-185 DATA 19 54 52 77 70-300 19 Tested in accordance with CENELEC specification HD 629 which encompasses IEC, BS and VDE etc. All IXSU/OXSU components have full traceability of raw materials and manufacture according to ISO 9001 & ISO 14001 able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Designed to terminate three core, polymeric insulated 11kV cables in indoor applications to switchgear & cable end boxes Highly reliable U.K industry standard termination Range taking with few components needed New ceramic stress control Compact design No shelf life limitation Conductive tubing allows the crossing of the cores below the screen cut. Additional tubing is available should the tail lengths need to be increased above 1200. Kit contents - Insulation tubing including co-extruded stress control, sealant tapes, conductive breakouts and installation instructions Conductor Tail Length IXSU-F-3301 10-16 2 650 94.00 IXSU-F-3304 10-16 2 1200 110.00 IXSU-F-3311 16-35 2 650 105.00 IXSU-F-3314 16-35 2 1200 125.00 IXSU-F-3321 25-70 2 650 123.00 IXSU-F-3324 25-70 2 1200 145.00 IXSU-F-3331 95-240 2 650 149.00 IXSU-F-3334 95-240 2 1200 176.00 IXSU-F-3341 240-500 2 650 162.00 IXSU-F-3344 240-500 2 1200 187.00 90 Our coitment. Your advantage.
HV Jointing and Terminating 11kV HEATSHRINK INDOOR & OUTDOOR TERMINATIONS SINGLE CORE TERMINATION WITH INTEGRAL STRESS CONTROL FOR XLPE CABLE - OUTDOOR Single core heatshrink termination for XLPE cables in outdoor applications Designed to terminate single core, polymeric insulated 11kV cables in outdoor applications such as pole top assemblies Highly reliable U.K industry standard termination Range taking with few components needed New ceramic stress control Compact design No shelf life limitation Suitable for use on 11kV triplex cables Kit contents - Insulation tubing including co-extruded stress control, sealant tapes and installation instructions Conductor OXSU-F-3111 10-35 2 108.00 OXSU-F-3121 25-95 2 118.00 OXSU-F-3131 95-240 2 135.50 OXSU-F-3141 240-500 2 155.00 OXSU-F-3151 500-800 2 182.00 OXSU-F-3161 1000-1200 2 277.00 Tested in accordance with CENELEC specification HD 629 which encompasses IEC, BS and VDE etc. All IXSU/OXSU components have full traceability of raw materials and manufacture according to ISO 9001 & ISO 14001 THREE CORE TERMINATION WITH INTEGRAL STRESS CONTROL FOR XLPE CABLE - OUTDOOR Three core heatshrink termination for XLPE cables in outdoor applications Designed to terminate three core, polymeric insulated 11kV cables in outdoor applications such as pole top assemblies Highly reliable U.K industry standard termination Range taking with few components needed New ceramic stress control Compact design No shelf life limitation Conductive tubing allows the crossing of the cores below the screen cut. Additional tubing is available should the tail lengths need to be increased above 1200. Kit contents - Insulation tubing including co-extruded stress control, sealant tapes, conductive breakouts and installation instructions Conductor Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 TECHNICAL 54 45 66DATA 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 Tail Length While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 91 http://energy.tycoelectronics.com OXSU-F-3301 10-16 2 650 145.00 OXSU-F-3304 10-16 2 1200 165.00 OXSU-F-3311 16-35 2 650 160.00 OXSU-F-3314 16-35 2 1200 183.00 OXSU-F-3321 25-70 2 650 191.00 OXSU-F-3324 25-70 2 1200 216.00 OXSU-F-3331 95-300 2 650 224.00 OXSU-F-3334 95-300 2 1200 255.00 OXSU-F-3341 240-500 2 650 246.00 OXSU-F-3344 240-500 2 1200 278.00 Tested in accordance with CENELEC specification HD 629 which encompasses IEC, BS and VDE etc. All IXSU/OXSU components have full traceability of raw materials and manufacture according to ISO 9001 & ISO 14001 Our coitment. Your advantage. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A
HV Jointing and Terminating 11kV HEATSHRINK INDOOR & OUTDOOR TERMINATIONS THREE CORE TERMINATIONS FOR XLPE CABLES - INDOOR Three core heatshrink termination for XLPE cables in indoor applications Designed to terminate three core, polymeric insulated 11kV cables in indoor applications to switchgear & cable end boxes Kit contents - stress control tubing, sealant coated breakouts and core insulation sleeves, sealant tapes, and installation instructions Tested in accordance with CENELEC specification HD 629 which encompasses IEC, BS and VDE etc Conductor Tail Length EPKT17A3XIH2 16-25 2 650 98.00 EPKT17A3XIH4 16-25 2 1200 118.00 EPKT17B3XIH2 35-70 2 650 116.00 EPKT17B3XIH4 35-70 2 1200 154.00 EPKT17C3XIH2 95-240 2 650 140.00 EPKT17C3XIH4 95-240 2 1200 184.00 EPKT17D3XIH2 300-400 2 650 169.00 EPKT17D3XIH4 300-400 2 1200 196.00 single core terminations PILC - INDOOR Single core heatshrink termination for PILC cable in indoor applications Designed to terminate single, paper insulated 11kV cables in indoor applications to switchgear & cable end boxes Kit contents - stress control tubing, core insulation sleeves, sealant tapes, and installation instructions Tested in accordance with CENELEC specification HD629 which encompasses IEC, BS & VDE etc Conductor SMOE61171 95-240 2 167.00 SMOE61172 300-400 2 205.00 SMOE61202 500-1000 2 249.00 THREE CORE TERMINATIONS FOR PILC CABLES - INDOOR Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 70-300 19 Three core heatshrink termination for PILC cables in indoor applications Designed to terminate three core, paper insulated 11kV cables in indoor applications to switchgear & cable end boxes Kit contents - stress control tubing, sealant coated breakouts and core insulation sleeves, sealant tapes, and installation instructions able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case TECHNICAL be liable for any incidental, DATA indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Tested in accordance with CENELEC specification HD629 which encompasses IEC, BS & VDE etc Conductor Tail Length EPKT17A3MIH2 16-25 2 650 122.00 EPKT17A3MIH4 16-25 2 1200 142.00 EPKT17B3MIH2 35-70 2 650 142.00 EPKT17B3MIH4 35-70 2 1200 166.00 EPKT17C3MIH2 95-240 2 650 166.00 EPKT17C3MIH4 95-240 2 1200 196.00 EPKT17D3MIH2 300-400 2 650 196.00 EPKT17D3MIH4 300-400 2 1200 216.00 92 Our coitment. Your advantage.
HV Jointing and Terminating 11kV HEATSHRINK INDOOR & OUTDOOR TERMINATIONS THREE CORE TERMINATIONS FOR XLPE CABLES - OUTDOOR Three core heatshrink termination for XLPE cables in outdoor applications Designed to terminate three core, polymeric insulated 11kV cables in outdoor applications such as pole top assemblies Kit contents - stress control tubing, sealant coated breakouts and core insulation sleeves, sealant tapes, and installation instructions Conductor Tail Length EPKT17A3XOH2 16-25 2 650 229.00 EPKT17A3XOH4 16-25 2 1200 286.00 EPKT17B3XOH2 35-70 2 650 275.00 EPKT17B3XOH4 35-70 2 1200 304.00 EPKT17C3XOH2 95-240 2 650 317.00 EPKT17C3XOH4 95-240 2 1200 351.00 EPKT17D3XOH2 300-400 2 650 350.00 EPKT17D3XOH4 300-400 2 1200 382.00 Tested in accordance with CENELEC specification HD629 which encompasses IEC, BS & VDE etc SINGLE CORE TERMINATIONS FOR PILC CABLES - OUTDOOR Single core heatshrink termination for PILC cable in outdoor applications Designed to terminate single core, paper insulated 11kV cables in outdoor applications such as pole top assemblies Kit contents - stress control tubing, core insulation sleeves, sealant tapes, and installation instructions Conductor SMOE61173 95-240 2 297.00 SMOE61174 300-400 2 374.00 SMOE61219 500-1000 2 444.00 Tested in accordance with CENELEC specification HD629 which encompasses IEC, BS & VDE etc Three core heatshrink termination for PILC cables in outdoor applications THREE CORE TERMINATIONS FOR PILC CABLES - OUTDOOR Designed to terminate three core, paper insulated 11kV cables in outdoor applications such as pole top assemblies Kit contents - stress control tubing, sealant coated breakouts and core insulation sleeves, sealant tapes, and installation instructions Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 Conductor Tail Length While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco TECHNICAL Electronics will in no case DATA be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, specification HD629 which instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 93 http://energy.tycoelectronics.com EPKT17A3MOH2 16-25 2 650 225.00 EPKT17A3MOH4 16-25 2 1200 283.00 EPKT17B3MOH2 35-70 2 650 258.00 EPKT17B3MOH4 35-70 2 1200 283.00 EPKT17C3MOH2 95-240 2 650 305.00 EPKT17C3MOH4 95-240 2 1200 336.00 EPKT17D3MOH2 300-400 2 650 337.00 EPKT17D3MOH4 300-400 2 1200 365.00 Tested in accordance with CENELEC encompasses IEC, BS & VDE etc Our coitment. Your advantage. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A
HV Jointing and Terminating 11kV INDOOR ACCESSORIES SINGLE CORE ARMOURED GLAND Aluminium gland kits for single core armoured cable Aluminium gland kit is designed to electrically earth the aluminium wire armours of the single core cables Suitable for use at 11 & 33kV Kit contents - three aluminium glands complete with heatshrink sleeve, jubilee clips and bolt pack Available with an insulating plate where separate earth facility is required (See insulating kit below) Conductor EAKT1608 50-630 2 225.00 THREE CORE ARMOURED GLAND Steel gland kits for three core armoured cable Steel gland kit is designed to electrically earth the steel wire armours of the multi-core cables Suitable for use at 11 & 33kV Kit contents - one steel gland complete with heatshrink sleeve, jubilee clips and bolt pack Available with an insulating plate where separate earth facility is required (See insulating kit below) Conductor EAKT1605 up to 70 2 49.50 EAKT1606 95-300 2 55.50 INSULATING KITS Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 70-300 19 Insulating plate to suit armoured glands Designed to allow the armour gland to be insulated from the enclosure Plate approx 10 thick Suitable for use at 11 & 33kV 3 kits should be ordered for single core applications (EAKT 1608) Kit contents - epoxy resin plate, plastic nuts and bolts able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Application EPPA-045-1 To fit EAKT1608 and 1605 27.00 EPPA-045-2 To fit EAKT1606 27.00 94 Our coitment. Your advantage.
HV Jointing and Terminating 11kV INDOOR ACCESSORIES Earth gland where plumbing of a lead sheath is required BRASS WIPING CONES Designed to mechanically earth the lead sheaths of PILC cables Kit includes: Brass cone, bolt pack, heatshrink sleeve and jubilee clips Gland can be cut to suit the relevant cable size Can be used with insulating plates EPPA-045-1 for X and EPPA-045-2 for Y Application GWCX Wiping Cone X 57.00 GWCY Wiping Cone Y 64.00 HEATSHRINK CABLE ENTRY SEALS Heatshrink glands for un-armoured cables Designed to provide a watertight seal where un-armoured cables enter enclosures All cable entry seals are adhesive lined to provide a suitable seal Kit contents - a rigid nylon nut, O ring, and a heat-shrinkable mould area SOLDERLESS EARTH SPRING KITS FOR 3 CORE XLPE CABLES Solderless earth connection system for XLPE cables Diameter Designed to mechanically earth the copper tape screens of XLPE cables Kit contents - tinned copper earth braids and a roll spring for each phase CES4 19.05-40.64 37.50 CES5 36.32-69.85 74.00 Conductor EAKT1655 16-50 2 22.45 EAKT1656 70-150 2 22.45 EAKT1657 185-240 2 24.15 EAKT1658 300-400 2 28.75 SOLDERLESS EARTH SPRING KITS FOR 3 CORE PILC CABLES Solderless earth connection system for PILC cables Designed to mechanically earth the lead sheaths of PILC cables Kit contents - tinned copper earth braid roll spring and a heatshrink sleeve Conductor EAKT1669 16-95 2 33.00 EAKT1670 120-185 2 34.50 EAKT1671 240-300 2 39.50 Tyco Electronics UK Ltd EAKT1672 Energy 400 Division 2 45.00 Freebournes Road Witham, Essex CM8 3AH Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in Price connection Each with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 95 http://energy.tycoelectronics.com Our coitment. Your advantage. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A
HV Jointing and Terminating 11kV INDOOR ACCESSORIES SOLDERLESS EARTH SPRING KITS FOR PICAS CABLES UNIVERSAL COLD APPLIED BOOT KIT STRAIGHT HEATSHRINK BOOTS Solderless earth connection system Designed to mechanically earth the aluminium armour of PICAS cables Simple to install, high reliability Insulating boots for straight or right angle applications Used in switchgear and transformers where the clearances are insufficient for operation in air or to protect against flash over due to rodents or extreme humidity Can be used as a straight or right angled boot Bushing kit available for smaller bushing styles Easy to remove (no mastic components) Application Conductor SMOE62803-10-400 2 97.90 RCAB-C-421 31-45 Bushing Kit For SMOE62803-16.50 Insulating boots for straight applications only Used in switchgear and transformers where the clearances are insufficient for operation in air or to protect against flash over due to rodents or extreme humidity Kit includes 3 straight boots and mastic kit Conductor SMOE61203 (MEC5) 95-300 2 49.50 Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 70-300 19 Conductor RSRB4022 (EAKT1505) 10-35 2 89.00 RSRB4024 (EAKT1506) 50-95 2 89.00 RSRB4026 (EAKT1507) 120-300 2 89.00 RIGHT ANGLE HEATSHRINK BOOTS Insulating boots for right angle applications only able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. 96 Our coitment. Your advantage. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Used in switchgear and transformers where the clearances are insufficient for operation in air or to protect against flash over due to rodents or extreme humidity Exceptional insulation and long term reliability even at high continuous operating temperatures Kit includes 3 right angle boots and mastic kit Conductor RSRB4042 (EAKT1508) 10-35 2 89.00 RSRB4044 (EAKT1509) 50-95 2 89.00 RSRB4046 (EAKT1510) 120-300 2 89.00
HV Jointing and Terminating 11kV OUTDOOR ACCESSORIES ARMOUR EARTHING KIT FOR SINGLE CORE ARMOURED PLASTIC & RUBBER INSULATED CABLES Armour earthing kit for single core armoured XLPE cables Designed to terminate wire armoured plastic cables by means of mechanical clamping rings Heat-shrinkable tubing for corrosion protection Conductor EAKT1636 16-70 2 97.90 EAKT1637 95-400 2 130.90 EAKT1638 500-800 2 143.00 ARMOUR EARTHING KIT FOR THREE CORE ARMOURED PLASTIC & RUBBER INSULATED CABLES Armour earthing kit for three core armoured XLPE cables Designed to terminate wire armoured plastic cables by means of mechanical clamping rings Heat-shrinkable tubing for corrosion protection Conductor EAKT1642 16-120 2 51.70 EAKT1643 150-240 2 61.60 EAKT1644 300-400 2 75.90 ARMOUR EARTHING KIT FOR THREE CORE ARMOURED PILC CABLES Armour earthing kit for three core armoured PILC cables Designed to terminate wire armoured paper cables by means of mechanical clamping rings Heat-shrinkable tubing for corrosion protection Conductor EAKT1641 16-120 2 45.10 EAKT1642 150-300 2 51.70 EAKT1643 400 2 61.60 SOLDERLESS EARTH SPRING KITS FOR 3 CORE XLPE CABLES Solderless earth connection system for XLPE cables Designed to mechanically earth the copper tape screens of XLPE cables The kit comes complete with a earthing braid and a mechanical roll spring for each phase Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 Conductor EAKT1655 16-50 2 22.45 EAKT1656 70-150 2 22.45 EAKT1657 185-240 2 24.15 EAKT1658 300-400 2 28.75 While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such Price information Each is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 97 http://energy.tycoelectronics.com Our coitment. Your advantage.
HV Jointing and Terminating 11kV OUTDOOR ACCESSORIES SOLDERLESS EARTH SPRING KITS FOR 3 CORE PILC CABLES Solderless earth connection system for PILC cables Designed to mechanically earth the lead sheaths of PILC cables The kit comes complete with a tinned copper earthing braid and a heatshrink sleeve Conductor EAKT1669 16-95 2 33.00 EAKT1670 120-185 2 34.50 EAKT1671 240-300 2 39.50 EAKT1672 400 2 45.00 POLE TOP BRACKET & CLEAT For outdoor applications Galvanised bracket and cleat for supporting cables Can be used with surge arrestors or insulators EXRM-0969-39 72.60 SUPPORT INSULATORS & BRACKETS Cable mounting bracket outdoor application The sheds of red, non tracking, flexible polymeric material are mounted on a porcelain core Set of three complete with steel T bracket Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66surge 35-185 arrestors 19 54 52 77 70-300 19 able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A EAKT1521 313.50 MV surge arrestor Designed to divert surges to earth and protect switchgear from the indirect effects of lightning Silicone moulded housing Reliable earth lead disconnect Safe mode of failure Set of three Contact your nearest sales office for more information Application DLA1 Series Outdoor standard class 1 application POA OCP2 Series Outdoor cable and substation protection POA 98 Our coitment. Your advantage.
HV Jointing and Terminating 33kV INDOOR & OUTDOOR HEATSHRINK TERMINATIONS SINGLE CORE TERMINATIONS FOR XLPE CABLES - INDOOR Single core heatshrink termination for XLPE cables in indoor applications Designed to terminate single, polymeric insulated 33kV cables in indoor applications to switchgear & cable end boxes U.K industry standard termination Outstanding reliability Range taking Few components needed Simplified cable preparation Simplified installation Compact design No shelf life limitation Kit contents - stress control tubings, non tracking sleeve with sealant layer and void filling mastic with installation instructions Tested in accordance with CENELEC specification HD 629 which encompasses IEC, BS and VDE etc Components have full traceability of raw materials and manufacture according to ISO 9001 & ISO 14001 Conductor EPKT36C1XI 50-95 2 249.50 EPKT36D1XI 120-185 2 285.00 EPKT36E1XI 240-500 2 325.00 EPKT36F1XI 630-1000 2 425.00 Three core heatshrink termination for XLPE cables in indoor applications THREE CORE TERMINATIONS FOR XLPE CABLES - INDOOR Designed to terminate three core, polymeric insulated 33kV cables in indoor applications to switchgear & cable end boxes U.K industry standard termination Outstanding reliability Range taking Few components needed Simplified cable preparation Simplified installation Compact design No shelf life limitation Kit contents -stress control tubings, non tracking sleeve with sealant layer, conductive breakout and void filling mastic with installation instructions Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 Conductor While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 99 http://energy.tycoelectronics.com EPKT36C3XIH2 50-95 2 345.00 EPKT36C3XIH4 50-95 2 397.00 EPKT36D3XIH2 120-185 2 365.00 EPKT36D3XIH4 120-185 2 420.00 EPKT36E3XIH2 240-500 2 485.00 EPKT36E3XIH4 240-500 2 557.00 Tested in accordance with CENELEC specification HD 629 which encompasses IEC, BS and VDE etc Components have full traceability of raw materials and manufacture according to ISO 9001 & ISO 14001 Our coitment. Your advantage. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A
HV Jointing and Terminating 33kV INDOOR & OUTDOOR HEATSHRINK TERMINATIONS SINGLE CORE TERMINATIONS FOR XLPE CABLES - OUTDOOR Single core heatshrink termination for XLPE cables in outdoor applications Tested in accordance with CENELEC specification HD 629 which encompasses IEC, BS and VDE etc Components have full traceability of raw materials and manufacture according to ISO 9001 & ISO 14001 Designed to terminate single core, polymeric insulated 36kV cables in outdoor applications such as pole top assemblies U.K industry standard termination Outstanding reliability Range taking Few components needed Simplified cable preparation Simplified installation Compact design No shelf life limitation Kit contents - stress control tubings, non tracking sleeve with sealant layer and void filling mastic with installation instructions Conductor EPKT36C1XO 50-95 2 355.00 EPKT36D1XO 120-185 2 390.00 EPKT36E1XO 240-500 2 465.00 EPKT36F1XO 630-1000 2 580.00 THREE CORE TERMINATIONS FOR XLPE CABLES - OUTDOOR Three core heatshrink termination for XLPE cables in outdoor applications Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 TECHNICAL 70-300 DATA 19 Tested in accordance with CENELEC specification HD 629 which encompasses IEC, BS and VDE etc Components have full traceability of raw materials and manufacture according to ISO 9001 & ISO 14001 able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Designed to terminate three core, polymeric insulated 11kV cables in outdoor applications such as pole top assemblies U.K industry standard termination Outstanding reliability Range taking Few components needed Simplified cable preparation Simplified installation Compact design No shelf life limitation Kit contents - stress control tubings, non tracking sleeve with sealant layer, conductive breakout and void filling mastic with installation instructions Conductor EPKT36C3XOH4 50-95 2 488.00 EPKT36D3XOH4 120-185 2 585.00 EPKT36E3XOH4 240-500 2 701.00 100 Our coitment. Your advantage.
HV Jointing and Terminating 33kV INDOOR ACCESSORIES Aluminium gland kits for single core armoured cable SINGLE CORE ARMOURED GLAND Aluminium gland kit is designed to electrically earth the aluminium wire armours of the single core cables Suitable for use at 11 & 33kV Kit contents - three aluminium glands complete with heatshrink sleeve, jubilee clips and bolt pack Available with an insulating plate where separate earth facility is required (See insulating kit below) Conductor EAKT1608 50-630 2 225.00 Steel gland kits for three core armoured cable Steel gland kit is designed to electrically earth the steel wire armours of the three core cables Suitable for use at 11 & 33kV Kit contents - one steel gland complete with heatshrink sleeve, jubilee clips and bolt pack THREE CORE ARMOURED GLAND Available with an insulating plate where separate earth facility is required (See insulating kit below) Conductor EAKT1605 up to 70 2 48.50 EAKT1606 95-300 2 48.50 INSULATING KITS Insulating plate to suit armoured glands Allows the armour gland to be insulated from the enclosure. Kit contains: 1 Epoxy resin plate, plastic nuts and bolts Please note 3 kits should be ordered for single core applications (EAKT1608) Plate approx 10 thick Suitable for use at 11 & 33kV Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 Application EPPA-045-1 To fit EAKT1605 & EAKT1608 27.00 EPPA-045-2 To fit EAKT1606 27.00 While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 101 http://energy.tycoelectronics.com Our coitment. Your advantage.
HV Jointing and Terminating 33kV INDOOR ACCESSORIES HEATSHRINK CABLE ENTRY SEAL Heatshrink glands for unarmoured cables Designed to provide a heatshrinkable watertight cable entry seal where un-armoured cables enter enclosures Manufactured from flame retardant polyolefin Temperature rated from -55 to 90C All cable entry seals are adhesive lined to provide a suitable seal Smaller sizes available on request Kit contents - a rigid nylon nut, O ring, and a heatshrinkable mould area Diameter CES4 50-120 2 37.50 CES5 150-630 2 74.00 SOLDERLESS EARTH SPRING KITS FOR 3 CORE XLPE CABLES Solderless earth connection system for XLPE cables Designed to mechanically earth the copper tape screens of XLPE cables Kit contents - tinned copper earth braids and a roll spring for each phase Conductor EAKT1656 25-35 2 22.45 EAKT1657 50-70 2 24.15 EAKT1658 95-300 2 28.75 EAKT1659 400-1000 2 32.85 RIGHT ANGLE HEATSHRINK BOOT KIT Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 70-300 19 Insulating boot kit for right angle applications Designed to be used in switchgear and transformers where the clearances are insufficient for operation in air or to protect against flash over due to rodents or extreme humidity Exceptional insulation and long term reliability even at high continuous operating temperatures High reliability heatshrink components Simplified installation Kit includes 3 right angle boots and mastic kit able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Conductor SMOE50383 95-300 2 730.00 102 Our coitment. Your advantage.
HV Jointing and Terminating 33kV OUTDOOR ACCESSORIES Armour earthing kit for single core armoured XLPE cables ARMOUR EARTHING KIT FOR SINGLE CORE ARMOURED PLASTIC & RUBBER INSULATED CABLES Designed to terminate wire armoured plastic cables by means of mechanical clamping rings Simple and high reliability installation Heat-shrinkable tubing for corrosion protection Conductor EAKT1637 16-185 2 130.90 EAKT1638 240-630 2 143.00 Armour earthing kit for three core armoured XLPE cables ARMOUR EARTHING KIT FOR THREE CORE ARMOURED PLASTIC & RUBBER INSULATED CABLES Designed to terminate wire armoured plastic cables by means of mechanical clamping rings Simple and high reliability installation Heat-shrinkable tubing for corrosion protection Conductor EAKT1642 16-25 2 51.70 EAKT1643 35-95 2 61.60 EAKT1644 120-185 2 75.90 EAKT1645 240-300 2 108.90 Solderless earth connection system for XLPE cables SOLDERLESS EARTH SPRING KITS FOR 3 CORE XLPE CABLES Copper tape screens on plastic cables can be earthed mechanically by using Tyco s solderless earth connection system Simple and high reliability installation The kit comes complete with a tinned copper earthing braid and a roll spring for each phase Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 Conductor EAKT1656 25-35 2 22.45 EAKT1657 50-70 2 24.15 EAKT1658 95-300 2 28.75 EAKT1659 400-1000 2 32.85 While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 103 http://energy.tycoelectronics.com Our coitment. Your advantage.
HV Jointing and Terminating 33kV OUTDOOR ACCESSORIES SOLDERLESS EARTH SPRING KITS FOR 3 CORE PILC CABLES Solderless earth connection system for PILC cables Designed to mechanically earth the lead sheaths of PILC cables The kit comes complete with a tinned copper earthing braid, roll spring and a heatshrink sleeve Conductor EAKT1671 50 2 39.50 EAKT1672 70-300 2 45.00 SUPPORT INSULATORS & BRACKETS Cable mounting bracket outdoor application The sheds of red, non tracking, flexible polymeric material are mounted on a porcelain core Set of three complete with galvanised steel bracket EAKT1524 511.50 POLE TOP BRACKET & CLEAT For outdoor applications Galvanised bracket and cleat for supporting cables. Can be used with surge arrestors or insulators EXRM-0969-39 72.60 Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 surge arrestors 54 45 66 35-185 19 54 52 77 70-300 19 able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A MV surge arrestor Designed to divert surges to earth and protect switchgear from the indirect effects of lightning Silicone moulded housing Reliable earth lead disconnect Safe mode of failure Contact your nearest sales office for more information Application DLA1 Series Outdoor standard class 1 application POA OCP2 Series Outdoor cable and substation protection POA 104 Our coitment. Your advantage.
HV Jointing and Terminating 11kV HEATSHRINK JOINTS Inline heatshrink joints for single core unarmoured XLPE cables INLINE JOINTS FOR SINGLE CORE UNARMOURED XLPE CABLES Designed to join inline single core 11KV unarmoured XLPE cables Highly reliable U.K industry standard joint. Can be used with crimp connectors Kit contents - Stress control and insulation tubing, wire shield, outer heatshrink sleeving, void, stress and moisture tapes Conductor SXSU-3111 35-70 2 141.00 SXSU-3121 95-185 2 148.00 SXSU-3131 185-300 2 165.00 SXSU-3141 300-500 2 175.00 Tested in accordance with CENELEC specification HD 629 or IEC 60502-4 for joints Network Rail Approved Inline heatshrink joints for single core unarmoured XLPE cables Designed to join inline single core 11KV unarmoured XLPE cables. Highly reliable U.K industry standard joint. INLINE JOINTS FOR SINGLE CORE UNARMOURED XLPE CABLES - MECHANICAL CONNECTORS Kit contents - Stress control and insulation tubing, wire shield, outer heatshrink sleeving, mechanical connectors, void, stress and moisture tapes Conductor MXSU-3111 35-95 2 149.00 MXSU-3121 70-150 2 154.00 MXSU-3131 95-240 2 160.00 MXSU-3132 150-300 2 171.00 MXSU-3141 240-400 2 182.00 MXSU-3151 500 2 198.00 MXSU-3161 630 2 209.00 MXSU-3171 800 2 243.00 MXSU-3181 1000 2 268.00 Exceeds international performance standards including CENELEC HD 629 or IEC 60502-4 for joints Network Rail Approved Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 INLINE JOINTS FOR SINGLE CORE ALUMINIUM WIRE ARMOURED XLPE CABLES Inline heatshrink joints for single core alumunium wire armoured XLPE cables Designed to join inline single core 11KV aluminium wire armoured XLPE cables. Highly reliable U.K industry standard joint. Kit contents - Stress control and insulation tubing, wire shield, outer heatshrink sleeving, void, stress and moisture tapes SXAW-3121 95-185 2 275.00 SXAW-3131 185-300 2 345.00 SXAW-3141 400-500 2 385.00 While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate Price the Each suitability of a product for a certain purpose and test each product for its intended application. Conductor TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH SXAW3151 630-800 2 429.00 Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 105 http://energy.tycoelectronics.com Tested in accordance with CENELEC specification HD 629 or IEC 60502-4 for joints Our coitment. Your advantage. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A
HV Jointing and Terminating 11kV HEATSHRINK JOINTS INLINE JOINTS FOR SINGLE CORE PILC CABLES Heatshrink inline joints for single core PILC cables Designed to join inline single core 11KV PILC cables Highly reliable U.K industry standard joint Unlimited shelf life Kit contents - Stress control and insulation tubing, lead sheath continuity, outer heatshrink sleeving, void, stress and moisture tapes Tested in accordance with CENELEC specification HD 629 or IEC 60502-4 for joints Conductor EPKJ 17A-1HL-1HL 35-70 2 223.00 EPKJ 17B-1HL-1HL 95-185 2 240.00 EPKJ 17C-1HL-1HL 240-400 2 278.00 EPKJ 17D-1HL-1HL 500-630 2 333.00 TRANSITION JOINTS FOR SINGLE CORE XLPE TO PILC CABLE Heatshrink transition joints for single core XLPE to PILC cables Designed to join inline single core 11kV XLPE to PILC cables Highly reliable U.K industry standard joint Unlimited shelf life Kit contents - Stress control and insulation tubing, wire shield, outer heatshrink sleeving, void, stress and moisture tapes Tested in accordance with CENELEC specification HD 629 or IEC 60502-4 for joints Conductor EPKJ 17A-1XU-1HL 35-70 2 206.00 EPKJ 17B-1XU-1HL 95-185 2 215.00 EPKT 17C-1XU-1HL 240-400 2 255.00 EPKJ 17D-1XU-1HL 500-630 2 302.00 Trifurcating JOINTS FOR SINGLE CORE XLPE TO THREE CORE XLPE CABLE Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 70-300 19 Heatshrink trifurcating joints for single core XLPE to three core XLPE cables Designed to join inline single core un-armoured 11kV XLPE to three core armoured XLPE cables Highly reliable U.K industry standard joint Unlimited shelf life Kit contents - Stress control and insulation tubing, wire shield, outer heatshrink sleeving, void, stress and moisture tapes Tested in accordance with CENELEC specification HD 629 or IEC 60502-4 able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco for Electronics' jointsonly obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Conductor PLEASE NOTE - OTHER VARIANTS OF THE EPKJ SYSTEM ARE AVAILABLE EPKJ 17A-1XU-3XU 35-70 2 315.00 EPKJ 17B-1XU-3XU 95-185 2 336.00 EPKJ 17C-1XU-3XU 240-400 2 424.00 EPKJ 17D-1XU-3XU 500-630 2 492.00 106 Our coitment. Your advantage.
HV Jointing and Terminating 11kV SHRINKSET JOINTS INLINE UNIVERSAL JOINTING SYSTEM FOR XLPE/PILC/PICAS THREE CORE CABLES Shrinkset - Inline universal jointing system for any combination of three core XLPE/PILC/PICAS cables Designed to provide a universal system for three core 11KV inline and transition jointing of polymeric or paper cables in one kit. Highly reliable U.K industry standard joint Proven in service with U.K REC s since 1991 1402 FR resin can be added to this kit for petrochemical environments Kit includes - stress control tubes, mechanical connectors, insulating sleeves, armour continuity, plastic shell & 2 part LDPU resin Conductor To Suit SHSS-12A-IND 35-185 2 Poly - 70-185 2 Paper - 358.00 SHSS-12B-IND 185-300 2 Poly - 185-300 2 Paper - 451.00 BU1 - SMOE 61745 16-25 2 Poly - 16-50 2 Paper Use with SHSS-12-A 22.00 BU2 - SMOE 61760 95-150 2 Poly - 95-150 2 Paper Use with SHSS-12-B 23.00 BU3 - SMOE 61798 16-70 2 Poly - 16-70 2 Paper Use with SHSS-12-B 26.50 Tested in accordance with CENELEC specification HD 629 or IEC 60502-4 for joints Shrinkset - Branch universal jointing system for any combination of three core XLPE/PILC/PICAS cables BRANCH UNIVERSAL JOINTING SYSTEM FOR XLPE/PILC/PICAS THREE CORE CABLES Designed to provide a universal system for three core 11KV branch jointing of polymeric or paper cables in one kit 1402 FR resin can be added to this kit for petrochemical environments Kit includes - stress control tubes, mechanical connectors, insulating sleeves, armour continuity, plastic shell & 2 part LDPU resin Conductor To Suit Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product TECHNICAL for a certain purpose and DATA test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for Price the electrical Each power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 107 http://energy.tycoelectronics.com SMOE61987 35-185 2 Poly - 95-185 2 Paper - 1183.00 SMOE61988 185-300 2 Poly - 185-300 2 Paper - 1320.00 BU1 - SMOE 61745 16-25 2 Poly - 16-50 2 Paper Use with SMOE61987 22.00 BU2 - SMOE 61760 95-150 2 Poly - 95-150 2 Paper Use with SMOE61988 23.00 BU3 - SMOE 61798 16-70 2 Poly - 16-70 2 Paper Use with SMOE61988 26.50 Shrinkset - Pot end universal jointing system for three core XLPE/PILC/PICAS cables Designed to provide a universal system for three core 11KV pot ending of polymeric or paper cables in one kit 1402 FR resin can be added to this kit for petrochemical environments Kit includes - stress control tubes, insulating sleeves, plastic shell & 2 part LDPU resin Tested in accordance with CENELEC specification HD 629 or IEC 60502-4 for joints POT END UNIVERSAL JOINTING SYSTEM FOR XLPE/PILC/PICAS THREE CORE CABLES Conductor SMOE62668 95-300 2 XLPE - 95-300 2 Paper 358.00 Below these sizes build up kits are required Tested in accordance with CENELEC specification HD 629 or IEC 60502-4 for joints Our coitment. Your advantage. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A
r Gland C HV Jointing and Terminating 11kV RESIN JOINTS Two Polyurethane Resin F D E Designed for cable joint encapsulation The resin consists of 2 parts: resin & hardener JSSC 7 litres 53.00 verall ia. B Max Gland Dimensions Braid Approx. Hexagon Type approved to CENELEC Wire Length Dia. C specification D EN A/C 50393 A/F E F JEM RESIN 15.8 0.2 / 0.3 67 34.0 30.5 20.8 0.2 / 0.3 64 34.0 30.5 27.2 0.2 / 0.45 65 42.2 37.6 33.5 0.3 / 0.45 77 53.6 47.3 39.9 0.3 / 0.45 77 61.5 56.4 52.6 0.3 / 0.45 84 77.2 70.1 65.3 0.3 / 0.45 90 87.4 80.0 78.0 0.3 / 0.45 96 109.2 98.8 88.0 0.3 / 0.45 108 126.0 115.0 Type approved to CENELEC specification EN 50393 Power Utility specification ENA TS C81/3 European legislation (REACH) compliant resin peed HAZARDOUS AREA RESIN Safety bility otchcast Cable Jointing Type approved to CENELEC specification EN 50393 European legislation (REACH) compliant resin Designed for cable joint encapsulation Supplied in clear pouches providing visibility during mixing Non-hazardous (non- irritant, non-sensitising, non-flaable) Independent testing has shown that no hazard labelling is required The resin consists of 2 parts: acrylic based resin & hardener Designed for cable joint encapsulation Supplied in clear pouches providing visibility during mixing Flame Retardant Chemical Resistant The resin consists of 2 parts: resin & hardener JEM 6 litres 58.00 1402-FR B 200ml 33.64 1402-FR C 370ml 50.22 1402-FR Mix PACK 7.18 litres 342.89 9PH, UK 108
HV Jointing and Terminating 11 & 33kV COLDSHRINK JOINTS INLINE JOINTS FOR 11KV SINGLE CORE UNARMOURED XLPE CABLES Inline coldshrink joints for 11kV single core unarmoured XLPE cables Designed to join inline single core 11kV unarmoured XLPE cable in All in One kit including mechanical connector Faster installation time than heatshrink joints Joint body, earthing system and re-jacketing pre-expanded on one holdout system Single piece silicone rubber joint body with high mechanical expansion capability allows a wide application range which enables smaller range of product to be stocked Short parking distance required Electrical stress control of the screen cut area by intergrated conductive geometrical stress cones Electrical stress control of the connector is by an integrated screened connection area (Faraday Cage) Kit contents - Stress control and insulation tubing, wire shield, outer coldshrink sleeving, void, stress and moisture tapes. For use on solid conductors please contact your nearest sales office Joint exceeds CENELEC HD 629.1 which includes IEC, BS, VDE and other international specifications Network Rail approved Mechanical Shear bolt connector to IEC 61238-1 Application Range Diameter over Diameter over core insulation outer sheath CSJA-12B/1XU-1XU-M 95-240 2 18.6-28.4 26.0-39.0 177.00 CSJA-12C/1XU-1XU-M 185-300 2 23.2-32.6 30.0-44.0 188.00 CSJA-12D/1XU-1XU-M 240-400 2 25.7-33.6 33.0-45.0 207.00 CSJA-12E/1XU-1XU-M1 500 2 34.4-36.2 43.0-48.0 307.00 CSJA-12E/1XU-1XU-M2 630 2 38.0-40.0 47.0-52.0 335.00 Inline coldshrink joints for 33kV single core unarmoured XLPE cables INLINE JOINTS FOR 33KV SINGLE CORE UNARMOURED XLPE CABLES Designed to join inline single core 33KV unarmoured XLPE cable in All in One kit including mechanical connectors Faster installation time than heatshrink joints Joint body, earthing system and re-jacketing pre-expanded on one holdout system Single piece silicone rubber joint body with high mechanical expansion capability allows a wide application range which enables smaller range of product to be stocked Short parking distance required Electrical stress control of the screen cut area by intergrated conductive geometrical stress cones Electrical stress control of the connector is by an integrated screened connection area (Faraday Cage) Kit contents - Stress control and insulation tubing, wire shield, outer coldshrink sleeving, void, stress and moisture tapes. For use on solid conductors please contact your nearest sales office Application Range Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Diameter Electronics Standard over Terms and Conditions of Sale. Tyco Diameter Electronics over will in no case be liable for any incidental, Price indirect Each or consequential damages arising from or connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own core judgement insulation to evaluate the suitability of a product outer for a certain sheath purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 109 http://energy.tycoelectronics.com Joint exceeds CENELEC HD 629.1 which includes IEC, BS, VDE and other international specifications Network Rail approved Mechanical Shear bolt connector to IEC 61238-1 CSJA-36D/1XU-1XU-M 95-240 2 27.8-37.6 35.0-48.0 268.00 CSJA-36E/1XU-1XU-M1 240-400 2 34.9-42.8 42.0-54.0 319.00 CSJA-36E/1XU-1XU-M2 500 2 42.6-45.6 51.0-57.0 336.00 CSJA-36E/1XU-1XU-M3 630 2 45.8-49.2 56.0-61.0 363.00 Our coitment. Your advantage. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A
HV Jointing and Terminating 33kV HEATSHRINK JOINTS INLINE JOINTS FOR SINGLE CORE UNARMOURED XLPE CABLES Tested in accordance with CENELEC specification HD 629 or IEC 60502-4 for joints Network Rail Approved Inline heatshrink joints for single core unarmoured XLPE cables Designed to join inline single core 33KV unarmoured XLPE cables Highly reliable U.K industry standard joint Can be used with either crimp or mechanical connectors Unlimited shelf life Kit contents - Stress control and insulation tubing, wire shield, outer heatshrink sleeving, void, stress and moisture tapes Conductor INLINE JOINTS FOR SINGLE CORE ALUMINIUM WIRE ARMOURED XLPE CABLES Inline heatshrink joints for single core alumunium wire armoured XLPE cables SXSU-6122 35-150 2 212.00 SXSU-6132 150-300 2 248.00 sxsu-6141 185-400 2 193.40 SXSU-6142 400-630 2 289.00 SXSU-6151 500-800 2 420.00 SXSU-6161 800-1200 2 467.00 INLINE JOINTS FOR SINGLE CORE UNARMOURED XLPE CABLES - MECHANICAL CONNECTORS Tested in accordance with CENELEC specification HD 629 or IEC 60502-4 for joints Network Rail Approved Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 70-300 19 Inline heatshrink joints for single core unarmoured XLPE cables Designed to join inline single core 33KV unarmoured XLPE cables Highly reliable U.K industry standard joint Unlimited shelf life Kit contents - Stress control and insulation tubing, wire shield, outer heatshrink sleeving, mechanical connectors, void, stress and moisture tapes Conductor MXSU-6111 35-95 2 220.00 MXSU-6121 70-150 2 237.00 MXSU-6131 150-300 2 248.00 MXSU-6141 240-400 2 281.00 MXSU-6151 500 2 292.00 MXSU-6161 630 2 321.00 MXSU-6171 800 2 362.00 able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Tested in accordance with CENELEC specification HD 629 or IEC 60502-4 for joints Designed to join inline single core 33KV aluminium wire armoured XLPE cables Highly reliable U.K industry standard joint Unlimited shelf life Kit contents - Stress control and insulation tubing, armour wire continuity, outer heatshrink sleeving, void, stress and moisture tapes Conductor SXAW-6132 120-240 2 499.00 SXAW-6142 300-630 2 665.00 110 Our coitment. Your advantage.
HV Jointing and Terminating 33kV HEATSHRINK JOINTS Heatshrink inline joints for single core PILC cables INLINE JOINTS FOR SINGLE CORE PILC CABLES Designed to join inline single core 33KV PILC cables Highly reliable U.K industry standard joint Unlimited shelf life Kit contents - Stress control and insulation tubing, armour wire continuity, outer heatshrink sleeving, void, stress and moisture tapes Conductor EPKJ 36A-1HL-1HL 50-70 2 385.00 EPKJ 36B-1HL-1HL 95-150 2 407.00 EPKJ 36C-1HL-1HL 185-400 2 451.00 EPKJ 36D-1HL-1HL 500-630 2 495.00 Tested in accordance with CENELEC specification HD 629 or IEC 60502-4 for joints Heatshrink transition joints for single core XLPE to PILC cables Designed to join inline single core 33KV PILC cables Highly reliable U.K industry standard joint Unlimited shelf life TRANSITION JOINTS FOR SINGLE CORE XLPE TO PILC CABLE Kit contents - Stress control and insulation tubing, wire shield, outer heatshrink sleeving, void, stress and moisture tapes Conductor EPKJ 36A-1XU-1HL 50-70 2 385.00 EPKJ 36B-1XU-1HL 95-150 2 407.00 EPKT 36C-1XU-1HL 185-400 2 451.00 EPKJ 36D-1XU-1HL 500-630 2 495.00 Tested in accordance with CENELEC specification HD 629 or IEC 60502-4 for joints Network Rail Approved Heatshrink inline joints for three core steel wire armoured cables Designed to join inline three core screened 33KV XLPE cables Highly reliable U.K industry standard joint Unlimited shelf life INLINE JOINTS FOR THREE CORE SCREENED XLPE CABLES Kit contents - Stress control and insulation tubing, armour wire continuity, outer heatshrink sleeving, void, stress and moisture tapes Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 Conductor EPKJ 36A-3XU-3XU-W 50-70 2 803.00 EPKJ 36B-3XU-3XU-W 95-150 2 864.00 EPKJ 36C-3XU-3XU-W 185-400 2 990.00 While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited for to, joints the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 111 http://energy.tycoelectronics.com Tested in accordance with CENELEC specification HD 629 or IEC 60502-4 Our coitment. Your advantage. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A
HV Jointing and Terminating 52-72kV HEATSHRINK TERMINATIONS & JOINTS SINGLE CORE TERMINATIONS FOR XLPE CABLES Tested to IEEE 404 1993, EDF HN-68-S-20, SEN 24 1434, ESI 09-16 & IEC 840 Network Rail approved Single core heatshrink termination for XLPE cables for outdoor applications Designed to terminate 52-72kV single core XLPE cables for outdoor applications to swichgear, cable boxes and pole top assemblies Industry standard high reliability termination Compact and modular design Heatshrinkable stress control sleeves No-tracking heat-shrinkable outer insulation Water and corrosion resistant Unlimited shelf life under normal storage conditions Suitable for use at 52 & 72 kv Suitable for indoor & outdoor applications Different creepage distance available Designed for use with mechanical connectors Kit contents - stress control tubes, insulating sleeves, mastics and rain sheds Please contact your nearest sales office with details of the full cable specification prior to order Sheds Creepage Length Voltage IHVT-5212 2 1220 52kV POA OHVT-5212 4 1430 52kV POA IHVT-72 4 1600 72kV POA OHVT-72 7 2200 72kV POA OHVT-72-L 10 3000 72kV POA INLINE JOINTS FOR SINGLE CORE UNARMOURED XLPE CABLES Inline heatshrink joints for single core unarmoured XLPE cables Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 Tested to IEEE 404 1993, EDF HN-68-S-20, SEN 24 1434, ESI 09-16 & IEC 840 54 45 66 35-185 19 54 52 77 70-300 19 Network Rail approved Designed to join inline single core 52-72kV unarmoured XLPE cables Industry standard high reliability joint Range taking design Unlimited shelf life Suitable for use at 52 & 72 kv Simplified installation Designed for use with mechanical connectors Kit includes - stress control tubes, insulating sleeves, mastics and outer heatshrink protection sleeve Cable joints for cross bonding/shield break applications also available Please contact your nearest sales office with details of the full cable specification prior to order able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Voltage ehvs-5221 52kV POA ehvs-72 72kV POA 112 Our coitment. Your advantage.
HV Jointing and Terminating 11 & 33kV HEATSHRINK INSULATION PRODUCTS HIGH VOLTAGE BUSBAR TAPE High voltage busbar insulation tape HVBT tape is an adhesive-coated, high-voltage, heat-shrinkable general purpose tape for insulating straight and bent bars in retrofit applications where tubing cannot be used Compatible with all other products in the Raychem MV insulation enhancement system Easy to apply using readily available equipment Suitable for both indoor and outdoor use Width Length per Roll HVBT-12-A 25 10m 59.00 HVBT-14-A 50 10m 93.00 HVBT-15-A 75 10m 123.00 HVBT-16-A 100 10m 153.00 Tested to ASTM D149, IEC 243, ISO 188, ASTM D2671, ASTM D257, IEC 93 and VDE 0370 Adhesive coated heat shrinkable sheet HIGH VOLTAGE BUSBAR INSULATION SHEET HVIS sheet is a biaxially expanded high voltage material designed to provide high performance insulation for complex geometries Easy to install on site using gas torch or hot air device Excellent UV & weather resistant properties Suitable for both indoor and outdoor use Description Sheet HV1S-05 0.5m x 660 (3 per kit) 212.00 HV1S-10 10.0m x 660 1197.00 HV1S-TOOLS-01 Installation Clamp Kit - 83.00 S1061-8-500 Filler Mastic - 8.50 Tested to ANSI C37.20c1976 for 15kV class equipment & IEC 298 for 36kV class equipment Heat-shrinkable busbar insulation tubing HIGH VOLTAGE HEATSHRINK BUSBAR TUBING FOR INSTALLATIONS UP TO 24KV BPTM tubing for use on straight or bent bars where some clearance reduction or 24 kv insulation is required Compatible with all other products in Raychem MV insulation enhancement system Flame retardant and halogen free Excellent flexibility can be installed on a wide range of curved or bent busbars without cracking Exceptional insulation and long term reliability even at continuous operating temperatures Additional range to suit 1000V application available on request Price per Metre Application Range Spool Length BPTM15/6-A/U 15.0-6.0 30m 15.50 BPTM30/12-A/U 30.0-12.0 30m 16.50 BPTM50/20-A/U 50.0-20.0 30m 20.00 BPTM75/30-A/U 75.0-30.0 30m 24.50 BPTM100/40-A/U 100.0-40.0 25m 38.50 BPTM120/50-A/U 120.0-50.0 25m 51.70 Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH BPTM175/70-A/U 15m 60.50 Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 113 http://energy.tycoelectronics.com Tested to IEC 216, ASTMD2671, IEC112, VDE 0303/1 & IEC 243 Our coitment. Your advantage. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A
HV Jointing and Terminating 11 & 33kV HEATSHRINK INSULATION PRODUCTS HIGH VOLTAGE HEATSHRINK BUSBAR TUBING FOR INSTALLATIONS UP TO 33KV Tested to IEC 216, ASTMD2671, IEC112, VDE 0303/1 & IEC 243 Heat-shrinkable busbar insulation tubing BBIT tubing for use on straight or bent bars where some clearance reduction or 33 kv insulation is required Compatible with all other products in Raychem MV insulation enhancement system Flame retardant and halogen free Can be installed on a wide range of curved or bent busbars without cracking or creasing Exceptional insulation and long term reliability even at continuous operating temperatures Additional range to suit 1000V application available on request COLD POUR INSULATING COMPOUND Application Range Spool Length BBIT25/10-A/U 25.0-10.0 30m 26.40 BBIT40/16-A/U 40.0-16.0 20m 29.70 BBIT65/25-A/U 65.0-25.0 15m 37.40 BBIT100/40-A/U 100.0-40.0 15m 59.40 BBIT150/60-A/U 150.0-60.0 15m 71.50 BBIT175/80-A/U 175.0-80.0 15m 88.00 Designed as a cold pour insulating compound for applications upto 33kV U.K Power Networks approved guroflex 5 LITRE 5 Litre 72.60 GUROFLEX 10 Litre 97.90 HOT POUR COMPOUND FOR JOINT & BOX FILLING Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 70-300 19 Designed as a hot pour insulating compound for applications upto 11kV - U.K Power Networks approved G101-123 10 kg 49.50 JOINT & BOX FILLING COMPOUNDS FOR PILC CABLES able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Designed to provide an oil resistant joint or box filling compound for PILC cables upto 33KV g38a 25 Litre 203.50 g83m 10 kg 567.00 114 Our coitment. Your advantage.
HV Jointing and Terminating 11kV COLDSHRINK INDOOR & OUTDOOR TERMINATIONS SINGLE CORE TERMINATIONS FOR XLPE COPPER WIRE SCREENED CABLES - INDOOR QTIII series single core coldshrink termination for XLPE cables indoor Designed to terminate single core, copper wire screened polymeric insulated 11kV cables in indoor applications to switchgear and cable end boxes No tools, easy install and ultra lightweight assembly Range taking with few components needed Inorganic coldshrink silicone insulation Kit contents - Termination body & mastic seal Conductor 92-EP621-1 50-95 2 86.40 92-EP631-1 120-400 2 128.85 92-EP641-1 500-630 2 177.00 92-EP656-1 630-1000 2 194.80 3M Electrical Markets Division 3M Scotchcast Cable Joints Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. QTIII series single core coldshrink termination for XLPE cables indoor SINGLE CORE TERMINATIONS FOR XLPE COPPER TAPE SCREENED CABLES - INDOOR Designed to terminate single core, copper tape screened armoured polymeric insulated 11kV cables in indoor applications to switchgear and cable end boxes No tools, easy install and ultra lightweight assembly Range taking with few components needed Inorganic coldshrink silicone insulation Kit contents - Termination body, earthing kit and mastic seal Conductor Tested in accordance CENELEC specification HD629 which 92-EP623-1 50-95 2 213.70 encompasses the BS, VDE etc. 92-EP633-1 120-150 2 Speed 218.70 92-EP643-1 185-400 2 322.40 92-EP653-1 500-630 2 334.70 Safety THREE CORE TERMINATIONS FOR XLPE COPPER TAPE SCREENED CABLES - INDOOR QTIII series three core coldshrink termination for XLPE cables indoor Reliability Designed to terminate three core, copper tape screened armoured polymeric insulated 11kV cables in indoor applications to switchgear & cable end boxes No tools, easy install and ultra lightweight assembly Range taking with few components needed Inorganic coldshrink silicone insulation Kit contents - Termination body, breakouts, rejacketing sleeve, earthing kit 3M and mastics Scotchcast Conductor 92-EP626-3 50-120 2 123.50 92-EP636-3 150-180 2 166.90 92-EP646-3 240-300 2 171.05 92-EP656-3 400 2 261.40 LV Cable Jointing Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. 115
HV Jointing and Terminating 11kV COLDSHRINK INDOOR & OUTDOOR TERMINATIONS THREE CORE TERMINATIONS FOR PILC/PICAS CABLES - INDOOR QTIII series three core coldshrink termination for PILC/PICAS cables indoor Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Designed to terminate three core, paper insulated 11kV cables in indoor applications to switchgear & cable end boxes No tools, easy install and ultra lightweight assembly Range taking with few components needed Inorganic coldshrink silicone insulation Use cold pour Scotchcast resin to fill and insulate crotch area Kit contents - Termination body, breakouts, rejacketing sleeve, earthing kit, mastics, Scotchcast resin & Scotch 70 tape Conductor MT16 70-300 2 281.60 SINGLE CORE TERMINATIONS FOR XLPE COPPER WIRE SCREENED CABLES - OUTDOOR QTIII series single core coldshrink termination for XLPE cables outdoor Designed to terminate single core, copper wire screened polymeric insulated 11kV cables in outdoor applications such as pole top assemblies No tools, easy install and ultra lightweight assembly Range taking with few components needed Inorganic coldshrink silicone insulation Kit contents - Termination body & mastic seal Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Conductor 92-EP621-2 50-95 2 114.80 92-EP631-2 120-400 2 148.25 92-EP641-2 500-630 2 189.75 ty SINGLE CORE TERMINATIONS FOR XLPE COPPER TAPE SCREENED CABLES - OUTDOOR QTIII series single core coldshrink termination for XLPE cables outdoor Designed to terminate single core, copper tape screened armoured polymeric insulated 11kV cables in outdoor applications such as pole top assemblies No tools, easy install and ultra lightweight assembly Range taking with few components needed Inorganic coldshrink silicone insulation Kit contents - Termination body, earthing kit and mastic seal Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Conductor 92-EP623-2 50-95 2 212.75 92-EP633-2 120-150 2 217.20 92-EP643-2 185-400 2 342.25 92-EP653-2 500-630 2 391.75 116
HV Jointing and Terminating 11 & 33kV COLDSHRINK INDOOR & OUTDOOR TERMINATIONS QTIII series three core coldshrink termination for XLPE cables outdoor THREE CORE TERMINATIONS FOR XLPE COPPER TAPE SCREENED CABLES - OUTDOOR Designed to terminate three core, copper tape screened polymeric insulated 11kV cables in outdoor applications such as pole top assemblies No tools, easy install and ultra lightweight assembly Range taking with few components needed Inorganic coldshrink silicone insulation Kit contents - Termination body, breakouts, rejacketing sleeve, earthing kit, mastics, Scotchcast resin & Scotch 70 tape Conductor 7691-S4-3W 16-50 2 258.20 7692-S4-3W 70-120 2 278.00 7693-S4-3W 3M Electrical 150-300 Markets Division 323.05 3M Scotchcast Cable Joints Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. QTII series three core coldshrink termination for PILC/PICAS cables outdoor THREE CORE TERMINATIONS FOR PILC/PICAS CABLES - OUTDOOR Designed to terminate three core, paper insulated 11kV cables in outdoor applications such as pole top assemblies No tools, easy install and ultra lightweight assembly Range taking with few components needed Inorganic coldshrink silicone insulation Use cold pour scotchcast resin to fill and insulate crotch area Kit contents - Termination body, breakouts, rejacketing sleeve, earthing kit, mastics, Scotchcast resin & Scotch 70 tape Conductor MO16 70-300 2 362.85 Speed Safety single CORE TERMINATIONS FOR XLPE COPPER WIRE SCREEN CABLES - INDOOR/OUTDOOR QTIII series single core coldshrink termination for XLPE copper wire screened cables indoor/outdoor Reliability Designed to terminate single core, copper wire screened polymeric insulated 33kV cables in indoor/outdoor applications to switchgear, cable end boxes and pole top assemblies No tools, easy install and ultra lightweight assembly Range taking with few components needed Designed for use with crimp lugs Kit contents - Termination body & mastic seal Conductor 94-EP610-2 35-120 2 239.95 94-EP620-2 50-150 2 281.90 94-EP630-2 120-300 2 332.55 94-EP640-2 240-630 2 610.75 3M Scotchcast LV Cable Jointing Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. 117
tyhv Jointing and Terminating 33kV COLDSHRINK INDOOR & OUTDOOR TERMINATIONS SINGLE CORE TERMINATIONS FOR XLPE COPPER WIRE SCREEN FOR MECHANICAL LUGS - INDOOR/OUTDOOR QTIII series single core coldshrink termination for XLPE copper wire screen indoor/outdoor Designed to terminate single core, copper wire screened polymeric insulated 33kV cables in indoor/outdoor applications to switchgear, cable end boxes and pole top assemblies No tools, easy install and ultra lightweight assembly Kit contents - Termination body & mastic seal Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Conductor 94-EP620-2 70-240 2 281.90 94-EP630-2 185-400 2 473.40 94-EP640-2 400-630 2 610.75 SINGLE CORE TERMINATIONS FOR XLPE COPPER TAPE SCREEN CABLES - INDOOR/OUTDOOR QTIII series single core coldshrink termination for XLPE copper tape screened cables armoured or lead indoor/outdoor Designed to terminate single core, copper tape screened polymeric insulated 33kV cables in indoor/outdoor applications to switchgear, cable end boxes and pole top assemblies No tools, easy install and ultra lightweight assembly Kit contents - Termination body, earthing kit and mastic seal Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Conductor 94-EP612-2 50-120 2 286.75 94-EP622-2 70-240 2 299.35 94-EP632-2 185-400 2 442.95 94-EP642-2 400-630 2 567.35 ty SINGLE CORE TERMINATIONS FOR XLPE LEAD SHEATHED CABLES - INDOOR/OUTDOOR QTIII series single core coldshrink termination for XLPE lead sheathed cables indoor/outdoor Designed to terminate single core, lead sheathed XLPE 33kV cables in indoor/outdoor applications to switchgear, cable end boxes and pole top assemblies No tools, easy install and ultra lightweight assembly Kit contents - Termination body, earthing kit and mastic seal Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Conductor 94-EP613-2 25-120 2 241.75 94-EP623-2 70-240 2 259.35 94-EP633-2 95-400 2 292.15 94-EP643-2 400-630 2 430.85 118
HV Jointing and Terminating 11 & 33kV INDOOR & OUTDOOR COLDSHRINK ACCESSORIES Pre-stretched tubing on a collapsible core for simple installation COLDSHRINK BARRIER TUBE Used in switchgear and transformers where the clearances are insufficient for operation in air or to protect against flash over due to extreme humidity Track resistant EPDM rubber 11kV rated product Complete coldshrink system - no heat required Application Range Application MB63 Up to 630 2 Cold Shrink in line boot 79.10 COLD APPLIED BARRIER BOOT SYSTEM 3M Electrical Markets Division 3M Scotchcast Cable Joints One Piece Cold Applied Boot Used in switchgear and transformers where the clearances are insufficient for operation in air or to protect against flash over due to rodents or extreme humidity Can be used as a straight or right angled boot Track resistant EPDM rubber 11kV rated product Complete cold applied system - no heat required 92EE717-1 Universal Push on boot 50-300 2 99.30 92-EE717-1-BSK Build up kit for bushings smaller than 50 2 38.85 GLAND KITS AND SEALS For terminating the armour on MV power cables To electrically earth the steel wire armours of multi-core cables Kit Contents - Steel gland, jubilee clips, bolt pack and coldshrink seal Coldshrink seal can bought separately Speed Reliability Application Range Diameter THG1 - X - 36-65 92.65 THG2 - Y - 53-94 95.65 THGS1 (Cold shrink seal) To fit THG1-29.80 THGS2 (Cold shrink seal) To fit THG2-42.90 Safety 3M Scotchcast LV Cable Jointing 119
HV Jointing and Terminating 11kV COLDSHRINK JOINTS INLINE JOINTS FOR SINGLE CORE UNARMOURED XLPE CABLES QS1000 series inline coldshrink joints for single core unarmoured XLPE cables Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Designed to join inline 11kV single core copper wire screen unarmoured XLPE cables Low temperature installation Faster installation time saving labour costs Kit contents - splice body, EPDM outer sleeve, mastic, earthing kit & mechanical connectors Conductor 92-AG611-1/C 70-150 2 188.50 92-AG621-1/C 185-240 2 232.20 92-AG631-1/C 300-400 2 323.85 INLINE JOINTS FOR SINGLE CORE ARMOURED XLPE CABLES QS1000 series inline coldshrink joints for single core armoured XLPE cables Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Designed to join inline 11kV single core copper tape screened armoured XLPE cables Low temperature installation Faster installation time saving labour costs Kit contents - splice body, EPDM outer sleeve, mastic, earthing kit & mechanical connectors Conductor 92-AG612-1/C 70-150 2 224.15 92-AG622-1/C 185-240 2 196.35 92-AG632-1/C 300-400 2 323.85 INLINE JOINTS FOR SINGLE CORE UNARMOURED XLPE CABLES ty Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. QS2000E series inline coldshrink joints for single core unarmoured XLPE cables Designed to join inline 11kV single core copper wire screen unarmoured XLPE cables Viable cost based alternative to heatshrink joints Faster installation time saving labour costs No inbuilt stress control so Scotch 13 tape is used to build up the electrode Kit contents - splice body, EPDM outer sleeve, mastic, earthing kit & mechanical connectors Conductor 92-AS610-1/C 50-150 2 167.90 92-AS620-1/C 120-240 2 189.85 92-AS621-1/C 240-400 2 232.55 92-AS630-1/C 500-630 2 345.90 92-AS631-1/C 800-1000 2 534.75 120
HV Jointing and Terminating 11kV COLDSHRINK JOINTS INLINE JOINTS FOR SINGLE CORE ARMOURED XLPE CABLES QS2000E series inline coldshrink joints for single core armoured XLPE cables Designed to join inline 11kV single core copper tape screened armoured XLPE cable Kit contents - splice body, EPDM outer sleeve, mastic, earthing kit & mechanical connectors Conductor 92-AS611-1/C 50-150 2 196.10 92-AS623-1/C 120-240 2 467.85 92-AS624-1/C 300-400 2 266.00 92-AS632-1/C 500-630 2 345.75 INLINE JOINTS FOR THREE CORE ARMOURED XLPE CABLES 3M Electrical Markets Division QS1000 series inline coldshrink joints for three core armoured XLPE cables 3M Scotchcast Cable Joints Designed to join inline 11kV three core copper tape screened armoured XLPE cables Outer protection sleeve or outer protection shell & resin are required to complete the joint Kit contents - splice body, mastics, earthing kit, Scotch 13 tape & mechanical connectors Conductor 92-AV610-3/C 50-120 2 398.55 92-AV620-3/C 150-185 2 469.60 92-AV630-3/C 300-400 2 576.95 Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Coldshrink transition joint for three core XLPE to three core PILC/PICAS cables Speed Designed to join inline three core 11kV copper tape screen armoured XLPE cables Safety Kit contents - Splice body, rubber tubes, mastic, earthing & mechanical connectors TRANSITION JOINT FOR THREE CORE XLPE TO THREE CORE PILC/PICAS CABLES OUTER PROTECTION SLEEVE Coldshrink EPDM protection sleeve Outer protection sleeve or outer protection shell & resin are required to complete the joint Conductor Designed to be used with 3M 92-AV6** range in polymeric installations To Suit 92-AV610-3/C + PILC1 50-120 2 471.40 92-AV620-3/C + PILC2 150-185 2 563.30 92-AV630-3/C + PILC3 300-400 2 655.25 encompasses the BS, VDE etc. Reliability 3M Scotchcast LV Cable Jointing CS 610-3 92-AV610 93.45 CS 620-3 92-AV620 97.15 CS 630-3 92-AV630 93.90 Tested in accordance CENELEC specification HD629 which 121
HV Jointing and Terminating 11kV COLDSHRINK JOINTS OUTER PROTECTION MOULDS TRIFURCATING TRANSITION JOINT FOR THREE CORE PILC TO SINGLE CORE XLPE CABLES COLDSHRINK BUILD UP KIT Mould Shell Designed to be used with 3M 92-AV6**-3 range Resins suitable for use with these moulds available on page 108 Application Resin Volume 1451 For 92AV 610-3 & 92AV 620-3 14 litres 29.20 1452 For 92AV 630-3 21 litres 33.00 Coldshrink trifurcating transition joint for three core PILC to single core XLPE cables Designed to join 11kV single core copper wire screened unarmoured XLPE to three core PILC/ PICAS cables Faster installation time saving labour cost Kit contents - splice body, EPDM tubes, earthing kit, mastics, Scotch 23 & mechanical connectors Conductor 92-FG411-3/C 50-95 2 408.90 92-FG421-3/C 120-240 2 555.55 92-FG431-3/C 300-400 2 615.20 Coldshrink build up kit for single core polymeric cables Designed as a build up kit when one or both cables fall below the minimum range of the joint ty Build Up Kit (Polymeric only) Range CSA ( 2 ) Insulation Diameter () 92-PG610-1 25-50 13.7-20.4 32.70 92-PG620-1 70-150 17.7-24.2 26.50 92-PG630-1 150-240 22.3-31.0 33.10 MECHANICAL EARTHING SYSTEM Mechanical earthing system for PILC/PICAS cables Designed to be used in 92-FG series range of joints to enable PILC/PICAS cables a means of mechanical earthing Kit Reference Number Application Range CSA 2 Cable Type MEH V0 Up to 35 2 PILC 67.50 MEH V1 50-95 2 PILC 67.50 MEH V2 120-300 2 PILC 67.50 MEH V3 Up to 95 2 PICAS 67.50 MEH V4 120-300 2 PICAS 67.50 122
HV Jointing and Terminating 33kV COLDSHRINK JOINTS INLINE JOINTS FOR SINGLE CORE UNARMOURED XLPE CABLES QSIII 7 QS2000 series inline coldshrink joints for single core unarmoured XLPE cables Designed to join inline 33kV single core copper wire screened unarmoured XLPE cables Low temperature installation Faster installation time saving labour costs Tool free installation Use build up kit 94-PG-620-1 when primary insulation is smaller than 28.4 Kit contents - splice body, EPDM outer sleeve, mastic, earthing kit & mechanical connectors Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Diameter over Primary Insulation Conductor 94-AP-630-1/C 28.4-42.0 120-240 2 391.35 94-AP-631-1/C 28.4-42.0 185-400 2 447.40 94-AP-640-1/C 31.5-52.6 3M Electrical 300-630 Markets 2 Division 499.90 94-PG-620-1 Smaller than 28.4 over primary 3Minsulation ScotchcastBuild Cable up kit Joints 20.70 INLINE JOINTS FOR THREE CORE ARMOURED XLPE CABLES QS2000 series inline coldshrink joints for three core armoured XLPE cables Designed to join inline 33kV three core copper tape screened armoured XLPE cables Low temperature installation Faster installation time saving labour costs Tool free installation Kit contents - splice body, heatshrink outer sleeve, mastic, earthing kit & mechanical connectors Conductor Speed INLINE JOINTS FOR SINGLE CORE UNARMOURED XLPE CABLES 94-AP230-3/C 120-240 2 1112.48 94-AP231-3/C 185-300 2 1226.12 QS2000E series inline coldshrink joints for single core unarmoured XLPE cables Designed to join inline 33kV single core copper wire screen unarmoured XLPE cables Viable cost based alternative to heatshrink joints Low temperature tool free installation Faster installation time saving labour costs No inbuilt stress control so Scotch 13 tape is used to build up the electrode Kit contents - splice body, EPDM outer sleeve, mastic, earthing kit & mechanical connectors Conductor 94-AS620-1/C 50-185 2 293.65 94-AS630-1/C 240-300 2 468.45 94-AS631-1/C 300-630 2 593.20 94-AS632-1/C 800-1000 2 642.40 Safety Reliability 3M Scotchcast LV Cable Jointing Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. 123
HV Jointing and Terminating 33kV COLDSHRINK JOINTS INLINE JOINTS FOR SINGLE CORE ARMOURED XLPE CABLES QS2000 series inline coldshrink joints for single core armoured XLPE cables Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Designed to join inline 33kV single core copper tape screened armoured XLPE cables Viable cost based alternative to heatshrink joints Low temperature tool free installation Faster installation time saving labour costs Use build up kit 94-PG-620-1 when primary insulation is smaller than 28.4 Kit contents - splice body, EPDM outer sleeve, mastic, earthing kit & mechanical connectors Diameter over Primary Insulation Conductor 94-AP635-1/C 28.4-42.0 120-240 2 464.85 94-AP636-1/C 28.4-42.0 185-300 2 531.05 94-PG-620-1 Smaller than 28.4 over primary insulation Build up kit 20.70 TRANSITION JOINT FOR SINGLE CORE XLPE TO PILC/PICAS CABLES Coldshrink transition joints for single core XLPE to PILC/PICAS cables Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Designed to join inline 33kV single core copper wire XLPE to single core PILC/PICAS cables Low temperature installation Faster installation time saving labour costs Tool free installation Kit contents - splice body, EPDM rubber tubes, mastics, earthing kit, Scotch 13 tape & mechanical connectors Conductor 94-FC 630-1/C 120-300 2 397.35 94-FC 631-1/C 185-300 2 670.95 94-FC 640-1/C 400-630 2 790.25 TRANSITION JOINT FOR SINGLE CORE XLPE TO THREE CORE PILC/PICAS CABLES tytrifurcating Coldshrink trifurcating transition joints for single core XLPE to three core PILC/PICAS cables Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Designed to join inline 33kV single core XLPE to three core PILC/PICAS cables Low temperature installation Faster installation time saving labour costs Tool free installation Kit contents - Mould shell, splice body, EPDM tubes, earthing kit, mastics, Scotch 23 & mechanical connectors Conductor 94-FP-435-3/C 120-240 2 1346.00 94-FP-436-3/C 185-400 2 1483.25 124
HV Jointing and Terminating 52-72kV COLDSHRINK TERMINATIONS & JOINTS QTEN series single core coldshrink terminations for lead sheathed XLPE cables for indoor and outdoor applications SINGLE CORE TERMINATION FOR LEAD SHEATHED XLPE CABLES - 72kV Designed to terminate 66kV single core lead sheathed XLPE cables in outdoor applications to swichgear, cable boxes and pole top assemblies Silicone body provides excellent electrical performance and superior low temperature handling Quicker installation time saving money on labour costs Low temperature tool free installation Range taking few components needed Suitable for use with mechanical lugs Kit contents - Termination body & mastic seal Please contact your nearest sales office with details of the full cable specification prior to order 3M Electrical Markets Voltage Division Application Range 3M Scotchcast Cable Joints 96-EP722-2 120-1000 2 72kV POA Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Network Rail Approved QTII & QTIII series single core coldshrink terminations for XLPE cables for indoor and outdoor applications SINGLE CORE TERMINATION FOR XLPE CABLES - 52kV Designed to terminate 52kV single core copper wire screened XLPE cables in indoor and outdoor applications to swichgear, cable boxes and pole top assemblies Kit contents - Termination body & mastic seal Please contact your nearest sales office with details of the full cable specification prior to order Application Range Voltage 95-EP631-2 (QTIII) 240-500 2 52kV POA Speed Safety INLINE JOINT FOR SINGLE CORE UNARMOURED XLPE CABLES 95-EB62-2 (QTII) 70-400 2 52kV POA 95-EB63-2 (QTII) 400-1000 2 52kV POA Reliability QSIII series inline coldshrink joints for single core un-armoured XLPE cables Designed to join inline single core 52kV & 66kV copper wire screened unarmoured XLPE cables Faster installation time saving costs Low temperature tool free installation Kit contents - splice body, EPDM outer sleeve, mastic, earthing kit & mechanical connectors Please contact your nearest sales office with details of the full cable specification prior to order Application Range Voltage 3M Scotchcast LV Cable Jointing 95-AC643-1 120-630 2 52kV POA 95-AC642-1/630 300-600 2 72kV POA 95-AC641-1/1000 800-1000 2 72kV POA Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. Network Rail Approved (95-EP631-2) Tested in accordance CENELEC specification HD629 which encompasses the BS, VDE etc. 125
HV Jointing and Terminating 52-72kV SELF SUPPORTING TERMINATIONS & JOINTS SINGLE CORE SELF SUPPORTING TERMINATIONS Single Core self supporting cable terminations for 52-72kV XLPE cables in outdoor applications Designed for terminate 52 & 72kV single core XLPE cables where the termination is to be used as fixed connection point and for installations where there is risk of very high continuous creepage currents The cable termination consist of porcelain or composite insulator installed on a box body made of alumunium castings Can be assembled horizontally on the ground before installation The composite termination is a lightweight shatter resistant version The porcelain insulator is available in brown and the composite insulator is available in grey A supporting plate with stand-off insulators are used for an insulated mounting Suitable for cable sizes upto 1200 2 Please contact your nearest sales office with details of the full cable specification prior to order Meets the requirements of SS, IEC & IEEE Insulator Creepage Distance Voltage APED 521B Porcelain 1340 52kV POA APED 722B Porcelain 2200 72kV POA APED 722P Composite 2330 72kV POA Accessories Description Use GAP-APED Rod Gap Protects against over voltage POA PIU-APED Post Insulator Kit When insulating mounting POA RE-APED-M Re-assembly Kit Used for re-assembly of a termination (Stress cone and top bolt to be ordered separately as required) POA RE-APED-T Re-assembly Kit Used for re-assembly of a termination (Stress cone and top bolt to be ordered separately as required) POA JSA Earthing Kit For cable with metallic screen (Not required for copper wire screen cables) POA SCK Screen Connection For radial waterproof cable with Al-foil and copper wire screen POA INLINE JOINTS FOR SINGLE CORE UNARMOURED XLPE CABLES Inline combination joints for single core unarmoured XLPE cables Meets the requirements of IEC 60840 including Annex H, NGTS TS 3.5.2 Designed to join inline single core 52 & 72kV unarmoured XLPE cables Premolded three layer rubber body supplied with (JX) or without (JS) screen interruption Prefabricated for safe and easy installation Compact joint for minimal cable stripping Please contact your nearest sales office with details of full cable specification prior to order Joint Type Conductor Voltage JS-52 Straight 150-1600 2 52kV POA JS-72 Straight 150-1600 2 72kV POA JX-52 Cross Bonded 150-1600 2 52kV POA JX-72 Cross Bonded 150-1600 2 72kV POA Accessories Description Use RKM145 Installation Tool For use with JS & JX cable joints POA 126
Separable Connectors CONTENTS Inner Cone Terminations 128 Installation Tooling & Accessories 129 Separable Connectors for Type A Bushing 130 Separable Connectors for Type B Bushing 130 Separable Connectors for Type C Bushing 131 Separable Connectors for Type A Bushing 133 Separable Connectors for Type B Bushing 133 Separable Connectors for Type C Bushing 134 HDC Cable Cabinets 136 127
Separable Connectors Inner Cone Terminations PFISTERER CONNEX CABLE TERMINATION SYSTEM Connex Plug in System for size 0, 1, 2, 3, 3S, 4, 5S, 6 & 6S The Plug In connector employs an insulated silicone bushing to control the electrical field present when the cable screen is removed Heatshrinkable sleeve provides a moisture barrier between the cable sheath and the alloy housing of the connector The termination is completed by plugging into the equipment and taking the cable screen to earth Sold in sets of three phases Installation tooling available to buy or hire (see page 129 and 193 for more information respectively) Training courses avaliable Designed to meet the requirements of EN 50180, 50181, DIN 47637 and are suitable for all cables to IEC 502 with graphite coated, bonded or Easy Peel semi-conducting screens Cone Max Voltage Max Current Cross Section Dia Core Insulation Voltage Tap SIZE 0 870-01X-XXX 12kV 250A 25-70 2 12.0-19.2 NO POA SIZE 0 870-02X-XXX 24kV 250A 25-50 2 15.0-23.5 NO POA SIZE 1 870-11X-XXX 12kV 630A 35-240 2 14.8-28.4 NO POA SIZE 1 870-12X-XXX 24kV 630A 35-240 2 19.0-32.6 NO POA SIZE 1 870-13X-XXX 36kV 630A 50-150 2 25.2-33.5 NO POA SIZE 1 850-11X-XXX 12kV 630A 35-240 2 14.8-28.4 YES POA SIZE 1 850-12X-XXX 24kV 630A 35-240 2 19.0-32.6 YES POA SIZE 1 850-13X-XXX 36kV 630A 50-150 2 25.2-33.5 YES POA SIZE 2 870-21X-XXX 12kV 800A 95-300 2 13.7-30.4 NO POA SIZE 2 870-22X-XXX 24kV 800A 50-300 2 20.2-34.6 NO POA SIZE 2 870-23X-XXX 36kV 800A 50-300 2 16.0-38.0 NO POA SIZE 2 850-21X-XXX 12kV 800A 95-300 2 13.7-30.4 YES POA SIZE 2 850-22X-XXX 24kV 800A 50-300 2 20.2-34.6 YES POA SIZE 2 850-23X-XXX 36kV 800A 50-300 2 16.0-38.0 YES POA SIZE 3 870-31X-XXX 12kV 1250A 240-630 2 26.5-39.6 NO POA SIZE 3 870-32X-XXX 24kV 1250A 150-630 2 26.5-45.6 NO POA SIZE 3 870-33X-XXX 36kV 1250A 95-630 2 28.5-50.0 NO POA SIZE 3 850-31X-XXX 12kV 1250A 240-630 2 26.5-39.6 YES POA SIZE 3 850-32X-XXX 24kV 1250A 150-630 2 26.5-45.6 YES POA SIZE 3 850-33X-XXX 36kV 1250A 95-500 2 28.5-50.0 YES POA SIZE 3S 850-350-XXX 52kV 1250A 120-630 2 32.0-50.0 NO POA SIZE 4 849-999-999 72.5kV 2500A 95-1600 2 22.4-33.6 NO POA SIZE 5S 859-999-999 145kV 2500A 95-1600 2 28.9-40.0 NO POA SIZE 6 869-999-999 170kV 2500A 240-2500 2 28.9-40.0 NO POA SIZE 6S 869-999-999 245kV 2500A 240-2500 2 28.9-40.0 NO POA VOLTAGE DETECTING SYSTEMS Continuous voltage detecting system Designed to show when operating voltages are present Needs to be connected to Pfisterer Connex voltage tap by means of a single pole interface Voltage indicator flashing red LED All-insulated system (IP66) made of impact resistant plastic Functioning test possible on 230V AC plug socket Description 827-1611-005 Dsa-2 continuous voltage indicator POA 827 668 001 Single pole interphase (can be mounted anywhere near the capacitive tap) POA 128
Separable Connectors Installation Tooling & Accessories CONNEX INSTALLATION TOOL Connex installation tool for sizes 1, 2 & 3 Designed to connect size 1, 2 & 3 PFISTERER connex plug in system Kit includes hand operated compression tool, accessories and carrying case Pfisterer tool is also available for hire please see our Toolout Section for more information on page 193 Please contact your nearest sales office for installations involving size 4, 5 & 6 Description PFISTERER TOOL For size 1, 2, 3 2810.00 ASSEMBLY ACCESSORIES Accessories for use with the PFISTERER Connex plug in system Description 559-224-001 Measuring Template 559-215-001 Measuring Template 559-215-002 Measuring Template 546-004-009 827-174-003 827-174-001 827-174-002 827-174-004 Hexagonal Wrench SW6 Plug In Assembly Bushings Plug In Assembly Bushings Plug In Assembly Bushings Plug In Assembly Bushings 827-130-001 Blind Cap 827-131-001 Blind Cap 827-132-001 Blind Cap 827-133-001 Blind Cap 827-150-005 827-150-002 827-150-003 827-150-004 Duy Cable Connector Duy Cable Connector Duy Cable Connector Duy Cable Connector 827-134-004 Protecting Cap 827-134-001 Protecting Cap 827-134-002 Protecting Cap 827-134-003 Protecting Cap Info Cut Back Dimensions For Cable Preparation Cut Back Dimensions For Cable Preparation Cut Back Dimensions For Cable Preparation For Tightening The Screws Of The Separable Connectors For The Pre-Assembly Of Pfisterer Connectors For The Pre-Assembly Of Pfisterer Connectors For The Pre-Assembly Of Pfisterer Connectors For The Pre-Assembly Of Pfisterer Connectors Protection Against Electric Shock For Live Connectors Protection Against Electric Shock For Live Connectors Protection Against Electric Shock For Live Connectors Protection Against Electric Shock For Live Connectors For Sealing And Voltage Proof Closing Of Connex Connectors For Sealing And Voltage Proof Closing Of Connex Connectors For Sealing And Voltage Proof Closing Of Connex Connectors For Sealing And Voltage Proof Closing Of Connex Connectors For Protecting Withdrawn Connex Connectors Against Dirt For Protecting Withdrawn Connex Connectors Against Dirt For Protecting Withdrawn Connex Connectors Against Dirt For Protecting Withdrawn Connex Connectors Against Dirt For use with cone size 0 1 & 2 3 All s 0 1 2 3 0 1 2 3 0 1 2 3 0 1 2 3 POA POA POA POA POA POA POA POA POA POA POA POA POA POA POA POA POA POA POA POA 129
Separable Connectors Separable ConnectorS for Type A & B BushingS SEPARABLE CONNECTOR SYSTEM FOR PIN TYPE A (200 SERIES) BUSHING Separable connector system for interface A bushing 12-24kV 250A The screened cable connector exceeds CENELEC HD 629.1 S1 requirements which includes BS, VDE and other international specifications Maximum System Voltage 24kV Continuous Current 250A Designed to facilitate the easy connection and disconnection of single core copper wire screened XLPE cables to medium voltage equipment like switchgear and transformers Manufactured from crosslinked EPDM and protected with a minimum 3 moulded conductive shield conected to earth These deadbreak adaptors are suitable for indoor and outdoor applications Their wide application range to cover several different cable cross sections without the need for additional cable adaptors Available in straight and elbow configuration Supplied with high strength bimetallic compression connectors to connect copper and aluminium conductors Adaptor Type Conductor Dia Core Insulation RSSS-5201 Straight 16 2 13.5-17.4 POA RSSS-5202 Straight 25 2 13.5-17.4 POA RSSS-5203 Straight 35 2 13.5-17.4 POA RSSS-5205 Straight 50 2 13.5-17.4 POA RSSS-5217 Straight 70 2 16.3-20.8 POA RSSS-5219 Straight 95 2 16.3-20.8 POA RSES-5201 Elbow 16 2 13.5-17.4 POA RSES-5202 Elbow 25 2 13.5-17.4 POA RSES-5203 Elbow 35 2 13.5-17.4 POA RSES-5205 Elbow 50 2 13.5-17.4 POA RSES-5217 Elbow 70 2 16.3-20.8 POA RSES-5219 Elbow 95 2 16.3-20.8 POA RSES-5224 Elbow 120 2 19.6-24.1 POA SEPARABLE CONNECTOR SYSTEM FOR PIN TYPE B (400 SERIES) BUSHING Separable connector system for interface B bushing 12-36kV 400A Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 70-300 19 The screened cable connector exceeds CENELEC HD 629.1 S1 requirements which includes BS, VDE and other international specifications Maximum System Voltage 36kV Continuous Current 400A able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Designed to facilitate the easy connection and disconnection of single core copper wire screened XLPE cables to medium voltage equipment like transformers and switchgear The insulation of the connector is made of a highly modified silicone rubber characterised by high tracking resistance, elongation at break and non flaability The screened connector need not be removed for over sheath testing The compact design supports the use of double T connections inside standard terminal boxes Easily accessible rear plug with capacitive test point Available with CU or AL compression lugs or mechanical connectors Cross Section Diameter RSES-6452 95-150 22.4-35.5 POA RSES-6453 120-240 28.9-42.0 POA RSES-6455 185-300 28.9-42.0 POA 130 Our coitment. Your advantage.
Separable Connectors Separable ConnectorS for Type C Bushing SEPARABLE CONNECTOR SYSTEM FOR BOLTED TYPE C (400 SERIES) BUSHING Separable connector system for interface C bushing 12-24kV 800A Designed to facilitate the easy connection and disconnection of single core copper wire screened XLPE cables to medium voltage equipment like transformers and switchgear The insulation of the connector is made of a highly modified silicone rubber characterised by high tracking resistance, elongation at break and non flaability The screened connector need not be removed for over sheath testing The compact design supports the use of double T connections inside standard terminal boxes Easily accessible rear plug with capacitive test point Available with CU or AL compression lugs or mechanical connectors AL Compression Lugs CU Compression Lugs Mechanical Connectors Conductor Dia Core Insulation - RSTI-5830-25 2 12.7-25 POA RSTI-5811 RSTI-5831 RSTI-5851 35 2 12.7-25 POA RSTI-5812 RSTI-5832 RSTI-5851 50 2 12.7-25 POA RSTI-5813 RSTI-5833 RSTI-5851 70 2 12.7-25 POA RSTI-5814 RSTI-5834 RSTI-5851 95 2 12.7-25 POA RSTI-5815 RSTI-5835 RSTI-5852 120 2 12.7-25 POA RSTI-5826 RSTI-5846 RSTI-5853 150 2 21.3-34.6 POA RSTI-5827 RSTI-5847 RSTI-5853 185 2 21.3-34.6 POA RSTI-5828 RSTI-5848 RSTI-5854 240 2 21.3-34.6 POA RSTI-5829 RSTI-5849 RSTI-5855 300 2 21.3-34.6 POA The screened cable connector exceeds CENELEC HD 629.1 S2 requirements which includes BS, VDE and other international specifications Maximum System Voltage 24kV Continuous Current 800A SEPARABLE CONNECTOR COUPLING SYSTEM FOR BOLTED TYPE C (400 SERIES) BUSHING Separable connector system for interface C bushing 12-24kV 800A Designed to facilitate the easy connection and disconnection of single core copper wire screened XLPE cables to medium voltage equipment like transformers and switchgear The insulation of the connector is made of a highly modified silicone rubber characterised by high tracking resistance, elongation at break and non flaability The screened connector need not be removed for over sheath testing The compact design supports the use of double T connections inside standard terminal boxes Easily accessible rear plug with capacitive test point Available with CU or AL compression lugs or mechanical connectors AL Compression Lugs CU Compression Lugs Mechanical Connectors Conductor Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 The 45 screened 66 cable 35-185 connector 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 Dia Core Insulation While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 131 http://energy.tycoelectronics.com RSTI-CC-5810 RSTI-CC-5830-25 2 12.7-25 POA RSTI-CC-5811 RSTI-CC-5831 RSTI-CC-5851 35 2 12.7-25 POA RSTI-CC-5812 RSTI-CC-5832 RSTI-CC-5851 50 2 12.7-25 POA RSTI-CC-5813 RSTI-CC-5833 RSTI-CC-5851 70 2 12.7-25 POA RSTI-CC-5814 RSTI-CC-5834 RSTI-CC-5851 95 2 12.7-25 POA RSTI-CC-5815 RSTI-CC-5835 RSTI-CC-5852 120 2 12.7-25 POA RSTI-CC-5826 RSTI-CC-5846 RSTI-CC-5853 150 2 21.3-34.6 POA RSTI-CC-5827 RSTI-CC-5847 RSTI-CC-5853 185 2 21.3-34.6 POA RSTI-CC-5828 RSTI-CC-5848 RSTI-CC-5854 240 2 21.3-34.6 POA RSTI-CC-5829 RSTI-CC-5849 RSTI-CC-5855 300 2 21.3-34.6 POA exceeds CENELEC HD 629.1 S2 requirements which includes BS, VDE and other international specifications Maximum System Voltage 24kV Continuous Current 800A Our coitment. Your advantage. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A
Separable Connectors Separable ConnectorS for Type C Bushing SEPARABLE CONNECTOR COUPLING SYSTEM FOR BOLTED TYPE C (400 SERIES) BUSHING The screened cable connector exceeds CENELEC HD 629.1 S1 requirements which includes BS, VDE and other international specifications Maximum System Voltage 36kV Continuous Current 800A Separable connector system for interface C bushing 12-36kV 800A Designed to facilitate the easy connection and disconnection of single core copper wire screened XLPE cables to medium voltage equipment like transformers and switchgear The insulation of the connector is made of a highly modified silicone rubber characterised by high tracking resistance, elongation at break and non flaability A thin walled screen is permanently bonded onto the insulation and the protects the connection system against accidental contact The screened connector need not be removed for over sheath testing The compact design supports the use of double T connections inside standard terminal boxes Easily accessible rear plug with capacitive test point Available with CU or AL compression lugs or mechanical connectors Screened Separable Coupling Connection system 36kV and 42kV with DIN compression LUGS AL Compression Lugs Number Cu Compression Lugs Mechanical Lugs and Shear Bolts Cross Section 2 Dia Core Insulation Min Max Price Each RSTI-CC-6811 RSTI-CC-6821-50 22.4 35.5 POA RSTI-CC-6812 RSTI-CC-6822-70 22.4 35.5 POA RSTI-CC-6813 RSTI-CC-6823-95 22.4 35.5 POA RSTI-CC-6814 RSTI-CC-6824-120 22.4 35.5 POA RSTI-CC-6815 RSTI-CC-6825-150 28.9 42 POA RSTI-CC-6816 RSTI-CC-6826-185 28.9 42 POA RSTI-CC-6817 RSTI-CC-6827-240 28.9 42 POA RSTI-CC-6818 RSTI-CC-6828-300 28.9 42 POA - - RSTI-CC-6851 33-95 22.4 35.5 POA - - RSTI-CC-6852 95-120 22.4 35.5 POA - - RSTI-CC-6853 150-240 28.9 42 POA - - RSTI-CC-6854 300 28.9 42 POA Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 70-300 19 Screened Separable Connection system 36kV and 42kV with DIN compression Lugs Number Cross Dia Core Insulation Price AL Compression Lugs Mechanical Lugs and Shear Section Each Bolts 2 Min Max RSTI-6811-50 22.4 35.5 POA RSTI-6812-70 22.4 35.5 POA RSTI-6813-95 22.4 35.5 POA RSTI-6814-120 22.4 35.5 POA RSTI-6815-150 28.9 42 POA RSTI-6816-185 28.9 42 POA RSTI-6817-240 28.9 42 POA RSTI-6818-300 28.9 42 POA - RSTI-6851 33-95 22.4 35.5 POA - RSTI-6852 95-120 22.4 35.5 POA - RSTI-6853 150-240 28.9 42 POA - RSTI-6854 300 28.9 42 POA able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A 132 Our coitment. Your advantage.
Separable Connectors SEPARABLE CONNECTORS FOR TYPE A & B BUSHINGS SEPARABLE CONNECTOR SYSTEM FOR PIN TYPE A (200 SERIES) BUSHING Separable connector system for interface A bushing 12-24kV 250A The screened cable connector exceeds CENELEC HD 629.1 S1 requirements which includes BS, VDE and other international specifications Maximum System Voltage 24kV Continuous Current 250A Designed to facilitate the easy connection and disconnection of single core copper wire screened XLPE cables to medium voltage equipment like transformers and switchgear The connectors are manufactured in three layers, a conductive inner layer, an insulation layer and a conductive outer layer The materials are vulcanised together to give the best possible interface between layers The cable connector includes a capacitive test point with protection and integrated earthing wire UV, ozone and tracking resistant Available in straight and elbow configuration Screen separation kit can be ordered separately for 3 core cables Supplied with bimetallic mechanical lugs to connect copper and aluminium conductor Conductor Type Voltage Core Insulation Diameter CSS-A 12250-01 10-16 2 STRAIGHT 12KV 10-12 POA CSS-A 12250-02 25-95 2 STRAIGHT 12KV 13-22 POA CSS-A 24250-01 10-16 2 STRAIGHT 24KV 13-22 POA CSS-A 24250-02 25-95 2 STRAIGHT 24KV 17-25.5 POA CSE-A 12250-01 10-16 2 ELBOW 12KV 10-12 POA CSE-A 12250-02 25-95 2 ELBOW 12KV 13-22 POA CSE-A 24250-01 10-16 2 ELBOW 24KV 13-22 POA CSE-A 24250-02 25-95 2 ELBOW 24KV 17-25.5 POA SEPARABLE CONNECTOR SYSTEM FOR PIN TYPE B (400 SERIES) BUSHING Separable connector system for interface B bushing 12-36kV 400A The screened cable connector exceeds CENELEC HD 629.1 S1 requirements which includes BS, VDE and other international specifications Maximum System Voltage 36kV Continuous Current 400A Designed to facilitate the easy connection and disconnection of single core copper wire screened XLPE cables to medium voltage equipment like transformers and switchgear The connectors are manufactured in three layers, a conductive inner layer, an insulation layer and a conductive outer layer The materials are vulcanised together to give the best possible interface between layers The cable connector includes a capacitive test point with protection and integrated earthing wire UV, ozone and tracking resistant Available in straight and elbow configuration Screen separation kit can be ordered separately for 3 core cables Supplied with bimetallic mechanical lugs to connect copper and aluminium conductor Conductor Voltage Core Insulation Diameter CSE-A 12400-01 25-70 2 12kV 13-20 POA CSE-A 12400-02 95-300 2 12kV 18.5-30.5 POA CSE-A 24400-01 25-70 2 24kV 17-24 POA CSE-A 24400-02 95-300 2 24kV 22.5-35 POA CSE-A 36400-01 25-70 2 36kV 24.5-34 POA CSE-A 36400-02 95-300 2 36kV 27.5-42 POA 133
Separable Connectors SEPARABLE CONNECTORS FOR TYPE C BUSHING SEPARABLE CONNECTOR SYSTEM FOR BOLTED TYPE C (400 SERIES) BUSHING The screened cable connector exceeds CENELEC HD 629.1 S1 requirements which includes BS, VDE and other international specifications Maximum System Voltage 36kV Continuous Current 630A Separable connector system for interface C bushing 12-36kV 630A Designed to facilitate the easy connection and disconnection of single core copper wire screened XLPE cables to medium voltage equipment like transformers and switchgear The connectors are manufactured in three layers, a conductive inner layer, an insulation layer and a conductive outer layer The materials are vulcanised together to give the best possible interface between layers The cable connector includes a capacitive test point with protection and integrated earthing wire UV, ozone and tracking resistant Available in straight and elbow configuration Screen separation kit can be ordered separately for 3 core cables Supplied with bimetallic mechanical lugs to connect copper and aluminium conductor Conductor Voltage Core Insulation Diameter CSE-A 12630-01 25-70 2 12kV 13-20 POA CSE-A 12630-02 95-300 2 12kV 18.5-30.5 POA CSE-A 12630-03 400-630 2 12kV 30.5-45 POA CSE-A 24630-01 25-70 2 24kV 17.0-24 POA CSE-A 24630-02 95-300 2 24kV 22.5-35 POA CSE-A 24630-03 400-630 2 24kV 30.5-45 POA CSE-A 36630-01 25-70 2 36kV 24.5-34 POA CSE-A 36630-02 95-300 2 36kV 27.5-42 POA CSE-A 36630-03 400-630 2 36kV 38.0-55 POA SEPARABLE CONNECTOR ACCESSORIES FOR BOLTED TYPE C BUSHINGS Suitable for use with the CSE-A Range of Separable Connectors The parallel coupling piece allows the joining of 2 elbows together Insulating sealing hood to be mounted on 630 switchgear or transformer to insulate it when a cable is temporarily disconnected but other cables are energised Bushing Style Voltage Description IP 630 C 12-24KV Screened Insulating Plug - allows cables to be energised if connector is disconnected POA PC 630-3 C 12-24KV Parallel Coupling Piece POA PC 630-3L C 36kV Parallel Coupling Piece POA 134
Separable Connectors SEPARABLE CONNECTORS FOR TYPE C BUSHING SEPARABLE CONNECTOR SYSTEM FOR BOLTED TYPE C (400 SERIES) BUSHING - SINGLE CORE COPPER TAPE SCREEN CABLES Separable connector system for interface C bushing 12-36kV 630A Designed to facilitate the easy connection and disconnection of single core copper tape screened XLPE cables to medium voltage equipment like transformers and switchgear The connectors are manufactured in three layers, a conductive inner layer, an insulation layer and a conductive outer layer The materials are vulcanised together to give the best possible interface between layers UV, ozone and tracking resistant Available in elbow configuration Supplied with bimetallic mechanical lugs to connect copper and aluminium conductor Conductor Voltage Core Insulation Diameter CSE-A 12630-01 R 25-70 2 12kV 13-20 POA CSE-A 12630-02 S 95-300 2 12kV 19-29 POA CSE-A 12630-03 T 400 2 12kV 30.5-37 POA CSE-A 24630-01 S 50-70 2 24kV 19-29 POA CSE-A 24630-02 T 95-300 2 24kV 27.5-37 POA CSE-A 24630-03 T 400 2 24kV 38-50 POA The screened cable connector exceeds CENELEC HD 629.1 S1 requirements which includes BS, VDE and other international specifications Maximum System Voltage 36kV Continuous Current 630A SEPARABLE CONNECTOR SYSTEM FOR BOLTED TYPE C (400 SERIES) BUSHING THREE CORE COPPER TAPE SCREEN CABLES Separable connector system for interface C bushing 12-36kV 630A Designed to facilitate the easy connection and disconnection of three core copper tape screened XLPE cables to medium voltage equipment like transformers and switchgear The connectors are manufactured in three layers, a conductive inner layer, an insulation layer and a conductive outer layer The materials are vulcanised together to give the best possible interface between layers UV, ozone and tracking resistant Available in elbow configuration Screen separation kit can be ordered separately for 3 core cables Supplied with bimetallic mechanical lugs to connect copper and aluminium conductor Conductor Voltage Core Insulation Diameter CSE-A 12630-01 RA 25-70 2 11KV 13-20 POA CSE-A 12630-02 SB 95-185 2 11KV 19-29 POA CSE-A 12630-02 TB 240-300 2 11KV 25-30.5 POA CSE-A 21630-03 TB 400 2 11KV 30.5-37 POA CSE-A 24630-01 SB 35-70 2 22KV 19-24 POA CSE-A 24630-02 TB 95-300 2 22KV 25-35 POA CSE-A 24630-03 TB 400 2 22KV 30.5-37 POA CSE-A 36630-01 SB 50-70 2 33KV 58-94 POA CSE-A 36630-02 TB 95-300 2 33KV 65-110 POA The screened cable connector exceeds CENELEC HD 629.1 S1 requirements which includes BS, VDE and other international specifications Maximum System Voltage 36kV Continuous Current 630A Please contact your nearest sales office for separable connectors for TYPE D & E (600 & 700 Series) bushings 135
Separable Connectors HDC CABLE CABINETS HDC CABLE CABINET 250A Enclosures meet the requirements of mechanical impact tests - iec 60439-5 Meets the requirements of electrical tests - SS424 14 45 Cenelec: hd 629.1 S1 HDC cable cabinets to join and branch 1-core & 3-core XLPE cables 12-24kV The enclosure is made of hot dip galvanised sheet steel with foundation base plate Additional corrosion protection for buried parts The screened separable cable connections are connected by coupling pieces which are mounted in the enclosure Any chosen cable can be disconnected for live sectioning or to be earthed The cabinet is supplied with padlocks and shackles For 3 core cables, screen separation kits must be used The cable cabinet is supplied with 3 x 3 phase kits, separable connectors, capacitive test point included Voltage Conductor HDC-A 12250 12kV 25-95 2 POA HDC-A 24250 24kV 25-95 2 POA HDC CABLE CABINET 630A HDC cable cabinets to join and branch 1-core & 3-core XLPE cables 12-36kV Enclosures meet the requirements of mechanical impact tests - iec 60439-5 Meets the requirements of electrical tests - SS424 14 45 Cenelec: hd 628.1 S1 & hd 629.1 S1 The enclosure is made of hot dip galvanised sheet steel with foundation base plate Additional corrosion protection for buried parts The screened separable cable connections are connected by coupling pieces which are mounted in the enclosure When branching parallel connector pc630 is required Any chosen cable can be disconnected for live sectioning or to be earthed The cabinet is supplied with padlocks and shackles For 3 core cables, screen separation kits must be used The cable cabinet is supplied with 2 x 3 phase kits, separable connectors, capacitive test point included Voltage Conductor HDC-A 12630-01 12kV 25-70 2 POA HDC-A 12630-02 12kV 95-300 2 POA HDC-A 12630-03 12kV 400-630 2 POA HDC-A 24630-01 24kV 25-70 2 POA HDC-A 24630-02 24kV 95-300 2 POA HDC-A 24630-03 24kV 400-630 2 POA HDC-A 36630-01 36kV 25-70 2 POA HDC-A 36630-02 36kV 95-300 2 POA HDC-A 36630-03 36kV 400-630 2 POA Description PSSK 1 Screen Separation kit (10-70 2 11kv, 10-35 2 24kv) POA PSSK 2 Screen Separation kit (95-300 2 11kv, 50-300 2 24kv) POA PC 630/250 Parallel Connector POA IP 250 Screened Insulation Plug POA MA 250 Measurement Adaptor POA KA 250 Busbar POA UKRA 90 Clamp for Fixing Cables POA 136
Tapes, Aerosols & Accessories CONTENTS PVC Insulating Tapes 138 Self Amalgamating, Insulating & Splicing Tapes 140 Mastic Sealing & Insulating Tapes 142 Marking & General Purpose Tapes 143 Corrosion & Protection Tapes 144 Glass Cloth & Cambric Tapes 145 Aerosol Sprays 146 Denso Products 148 137
Tapes, Aerosols & Accessories PVC INSULATING TAPES PHASE TAPES General purpose phase tapes General purpose phase tapes for colour coding and cable insulation Available in 8 colours Conforms to BS EN 3924 Number Material Colour Coil size TAPEBLACK PVC Black 19 x 0.15 25m 1.50 TAPEBLUE PVC Blue 19 x 0.15 25m 1.50 TAPEBROWN PVC Brown 19 x 0.15 25m 1.50 TAPEGREY PVC Grey 19 x 0.15 25m 1.50 TAPEGREEN/YELLOW PVC Green&Yellow 19 x 0.15 25m 1.50 TAPERED PVC Red 19 x 0.15 25m 1.50 TAPEWHITE PVC White 19 x 0.15 25m 1.50 TAPEYELLOW PVC Yellow 19 x 0.15 25m 1.50 scotch 35 tape High quality colour coding pvc tape Designed for use in phase identification and general purpose cable insulation Abrasion & weather resistant Joint, Termination & Connectors insulation upto 600V Resistant to moisture, alkalis, acids, U.V & corrosion Available in 8 fade resistant colours Conforms to BS 3924 & UL 510 Temperature Rating 80 C tyscotch 33 TAPE Conforms to BS 3924 & UL 510 Temperature Rating 80 C Number Material Colour Coil size Scotch35br PVC Brown 19 x 0.178 20m 5.45 Scotch35gr PVC Grey 19 x 0.178 20m 5.45 SCOTCH35OR PVC Orange 19 x 0.178 20m 5.45 Scotch35re PVC Red 19 x 0.178 20m 5.45 SCOTCH35VI PVC Violet 19 x 0.178 20m 5.45 Scotch35wh PVC White 19 x 0.178 20m 5.45 Scotch35ye PVC Yellow 19 x 0.178 20m 5.45 High quality general purpose pvc insulating tape Indoor/Outdoor insulations & for general purpose wiring applications & Cable Joints upto 600V Provides protective jacketeting for High Voltage cable joints and repairs Flame Retardant with excellent resistance to abrasion, moisture, alkalis, acid and copper corrosion Number Other sizes available on request Material Colour Coil size Scotch33-19 PVC Black 19 x 0.178 33m 7.15 Scotch33-25 PVC Black 25 x 0.178 33m 9.35 SCOTCH33-38 PVC Black 38 x 0.178 33m 14.20 138
Tapes, Aerosols & Accessories PVC INSULATING TAPES Premium grade all weather pvc insulating tape SCOTCH SUPER 33+ TAPE Designed for primary electrical insulation for cable splices and busbar applications ALL weather tape suitable for cold weather applications Flame retardant and highly conformable Excellent resistance to abrasion, moisture, alkalis, acid, copper corrosion. Provides protective jacketing for HV cable splices & repairs (upto 600V) Material Colour Coil size Number Scotch33+ PVC Black 19 x 0.178 20m 4.70 Conforms to BS 3924 & UL 510 Temperature Rating - 18 C - 105 C SCOTCH SUPER 88 TAPE Premium grade heavy duty all weather pvc tape 3M Electrical Markets Division 3M Scotchcast Cable Joints Designed for primary electrical insulation for cable splices and busbar applications Excellent abrasion and puncture resistance ALL weather tape suitable for cold weather applications Flame retardant and highly conformable Excellent resistance to moisture, alkalis, acid, copper corrosion Provides protective jacketing for HV cable splices & repairs (upto 600V) Number Material Colour Coil size Scotch88-19 PVC Black 19 x 0.216 20m 5.40 Scotch88-25 PVC Black 25 x 0.216 33m 10.80 Scotch88-38 PVC Black 38 x 0.216 33m 14.00 Speed Extra heavy duty pvc tape scotch 22 tape Designed for heavy duty applications, harnessing, cable sheath repair & sealing connectors Reliability High elastic memory, excellent abrasion and puncture resistance ALL weather tape suitable for cold weather applications Flame retardant and highly conformable Excellent resistance to moisture, alkalis, acid, copper corrosion Provides protective jacketing for HV cable splices & repairs (upto 600V) Number Material Colour Coil size Scotch22-12 PVC Black 12 x 0.254 33m 6.55 Scotch22-19 PVC Black 19 x 0.254 33m 10.10 Scotch22-25 PVC Black 25 x 0.254 33m 13.05 Scotch22-38 PVC Black 38 x 0.254 33m 15.70 Scotch22-50 PVC Black 50 x 0.254 33m 19.35 Safety 3M Scotchcast LV Cable Jointing Conforms to BS 3924 & UL 510 Temperature Rating 18 C to +105 C Conforms to BS 3924 & UL 510 Temperature Rating 10 C to +80 C 139
Tapes, Aerosols & Accessories SELF AMALGAMATING, INSULATING & SPLICING TAPES scotch 23 tape Rubber self amalgamating all voltage splicing tape Primary electrical insulation for cable jointing and terminating up to 69kV Suitable for jacketing on HV splices & terminations and end sealing on HV cables Can be stretched upto 100% to give void free, moisture resistant insulation Physical & electrical properties unaffected by the degree of stretch Temperature Rating 90 C Number Material Colour Coil size Scotch23-19 Rubber Black 19 x 0.76 9.15m 7.60 Scotch23-25 Rubber Black 25 x 0.76 9.15m 11.95 Scotch23-38 Rubber Black 38 x 0.76 9.15m 17.75 Scotch23-50 Rubber Black 50 x 0.76 9.15m 24.00 scotch 130C tape Linerless EPR self amalgamating all voltage splicing tape Temperature Rating 90 C Primary electrical insulation for cable jointing and terminating up to 69kV and building stress cones upto 35KV Suitable for jacketing on HV splices & terminations and end sealing on HV cables Flame retardant, UV & weather and corona resistant Can be stretched up to 75% to give void free, moisture resistant insulation Physical & electrical properties unaffected by the degree of stretch Number Material Colour Coil size SCOTCH130C-19 Rubber Black 19 x 0.762 9m 10.30 SCOTCH130C-25 Rubber Black 25 x 0.762 9m 14.15 SCOTCH130C-38 Rubber Black 38 x 0.762 9m 20.45 SCOTCH130C-50 Rubber Black 50 x 0.762 9m 27.80 ty SCOTCH 70 TAPE Temperature Rating 180 C (Class H) Self fusing arc & track resistant tape Designed as an over-wrap for protection of terminating high-voltage cables against arcing and tracking Excellent arc and track resistance Excellent performance in low and high temperature environments Instantaneous fusion and excellent conformability. High dielectric strength Material Colour Coil size Number Scotch70 Rubber Black 25 x 0.3 9m 40.90 140
Tapes, Aerosols & Accessories SELF AMALGAMATING, INSULATING & SPLICING TAPES SCOTCH 13 TAPE Semi-conducting rubber high voltage tape Electrically rounds-off high voltage connectors and lugs and provides screen continuation for high voltage joints and terminations Replaces semi-conducting layer beneath metallic shield of damaged cables Forms conductive portion of stress cones Non vulcanising and highly conformable to irregular shapes Resists cracking, solvents, UV and moisture Tape and liner boldly printed to distinguish from insulating tape Material Colour Coil size Number Scotch13 Mastic Black 19 x 0.762 4.5m 7.57 SCOTCH 2220 TAPE 3M Electrical Markets Division 3M Scotchcast Cable Joints Meets requirements of ASTM-D4388, Type IV Temperature Rating 130 C Stress control all voltage tape Designed to provide stress relief for all cable terminations and HV joints Reduces stress concentration to values found in continuous cables Changes voltage distribution in electrical field surrounding a HV termination or joint Number Material Colour Coil size Scotch2220 Mastic Black 19 x 0.762 4.5m 30.50 Temperature Rating 90 C Electrical insulation putty tape Recognised as a joint insulation for electrical conductors when over wrapped with either Super 33+ or Super 88 electrical tape To insulate low-voltage (600 volts and less) connections To build up cable joints and fill out major irregularities and voids in low-voltage joints (2300 volts and less) in order to obtain a uniform base for further taping Speed Safety PTP Reliability Excellent electrical and ageing properties SCOTCHFIL PUTTY Non corrosive synthetic rubber Material Colour Coil size Number Scotchfil Rubber Black 38 x 3.175 1.5m 9.80 UL recognised Temperature Rating 80 C 3M Scotchcast LV Cable Jointing 141
Tapes, Aerosols & Accessories MASTIC SEALING & INSULATING TAPES SCOTCH 2210 TAPE Self fusing vinyl mastic tape & pads Designed to insulate and moisture seal all connections upto 600V Excellent resistance to abrasion, moisture, alkalis, acid and copper corrosion Highly resistant to ultra violet light Flexible over wide range of temperatures Available in either tape or pads Temperature Rating 18 C to +38 C Number Material Colour Coil size Scotch 2210-19 PVC Black 19 6m 8.50 Scotch 2210-38 PVC Black 38 6m 15.20 Scotch 2200 Pads PVC Black 114 x 165-33.90 SCOTCH 2228 TAPE Self amalgamating rubber mastic tape Designed to insulate and moisture seal all connections upto 1000V Highly conformable for applications over irregular surfaces Excellent weather and moisture resistance Flexible over wide range of temperatures Temperature Rating 18 C to +90 C Material Colour Coil size Number Scotch2228 EPR Black 50 x 1.65 3.03m 18.80 SCOTCH 2229 TAPE Mastic tape ty Temperature Rating 34 C to +71 C Designed for insulating, padding and sealing of objects that need to be protected from adverse environmental conditions. Excellent corrosion protection properties. Highly conformable for applications over irregular surfaces Wide temperature stability while maintaining its sealing properties. Excellent chemical and UV resistance Material Colour Coil size Number Scotch2229 Mastic Black 95 x 3.2 3.08m 34.30 142
Tapes, Aerosols & Accessories MARKING & GENERAL PURPOSE TAPES scotch 9545 tape Pre-printed phase marking cloth tape Heavy-duty cloth tape, pre-printed with phase marking characters to assist with cable identification A good adhesive and non stretch strength for a reliable grip Available with either white or yellow background with black printing Number Material Colour Coil size Sl1-R Cloth Yellow 19 x 0.27 10m 14.70 Sl2-R Cloth Yellow 19 x 0.27 10m 14.70 Sl3-R Cloth Yellow 19 x 0.27 10m 14.70 Sn-R Cloth Yellow 19 x 0.27 10m 14.70 Sl-R Cloth Yellow 19 x 0.27 10m 14.70 Sl1-Rw Cloth White 19 x 0.27 10m 14.70 Sl2-Rw Cloth White 19 3M x Electrical 0.27 Markets 10m Division 14.70 Sl3-Rw Cloth White 19 3M x Scotchcast 0.27 Cable 10m Joints 14.70 Sn-Rw Cloth White 19 x 0.27 10m 14.70 Sl-Rw Cloth White 19 x 0.27 10m 14.70 Temperature rating 105 C SCOTCH TEMFLEX 1700P TAPE Pre-printed phase pvc marking tape PVC tape, pre-printed with phase marking characters to assist with cable identification Suitable for a wide temperature range Flame retardant Number Material Colour Coil size T1700pl PVC White 15 x 0.77 10m 2.40 T1700pl1 PVC White 15 x 0.77 10m 2.40 T1700pl2 PVC White 15 x 0.77 10m 2.40 T1700pl3 PVC White 15 x 0.77 10m 2.40 T1700pn PVC White 15 x 0.77 10m 2.40 scotch 2000 tape Duct tape Designed to be an electrician s utility tape for holding and bundling applications Does NOT absorb water Clean removal with minimal residue Number Material Colour Coil size Scotch2000 PVC/Rubber Grey 50 x 0.152 46m 4.85 Speed Safety Reliability 3M Scotchcast LV Cable Jointing Temperature rating 10 C to +80 C Temperature rating 80 C 143
Tapes, Aerosols & Accessories CORROSION & PROTECTION TAPES SCOTCHRAP 50 & 51 TAPE All weather corrosion protection tape Designed to resist corrosion of metal piping systems above and below ground. High electrical strength and insulating properties. Excellent resistance to impact abrasion, punctures and tears. Resistance to coon chemicals, salt water, acids, alkalis and salts Temperature Rating 48 C to +80 C Number Material Colour Coil size Scotch50-25 PVC Black 25 x 0.254 30.5m 11.10 Scotch50-50 PVC Black 50 x 0.254 30.5m 19.40 Scotch50-101 PVC Black 101 x 0.254 30.5m 38.20 Scotch50-152 PVC Black 152 x 0.254 30.5m 55.15 Scotch51-25 PVC Black 25 x 0.508 30.5m 17.15 Scotch51-50 PVC Black 50 x 0.508 30.5m 33.00 Scotch51-101 PVC Black 101 x 0.508 30.5m 68.25 Scotch51-152 PVC Black 152 x 0.508 30.5m 120.45 SCOTCHRAP PRIMER Corrosion protection pipe primer A rubber base primer that permeates metal surface pits and irregularities, preparing the surface for tape application Quick drying base primer Temperature Rating to 80 C Material Colour Number ScotChrap Primer Black 1 gallon 73.60 SCOTCH 77 TAPE ty Temperature Rating to 80 C Arc & fire proofing tape Designed to protect all types of electrical cables The elastomer expands in fire to provide a thick char build-up between the flame and cable Provides arc and fire proofing to high energy cables Resistant to UV, acids, salt water & sewage Material Colour Coil size Number Scotch 77-38 PVC Black 38 x 0.762 6m 8.60 Scotch 77-76 PVC Black 76 x 0.762 6m 16.95 144
Tapes, Aerosols & Accessories GLASS CLOTH & CAMBRIC TAPES SCOTCH 27 TAPE Glass cloth tape Applications include heat stable insulation for furnace and oven controls, motor leads and switches High mechanical strength. Resistance to high temperatures Treated and prepared to provide corrosion free protection The adhesive is a rubber pressure-sensitive thermosetting system Material Colour Coil size Number Scotch27 Glass Cloth White 12 x 0.178 20m 6.00 Temperature Rating 130 C SCOTCH 69 TAPE 3M Electrical Markets Division 3M Scotchcast Cable Joints Glass cloth tape with silcone adhesive Applications include induction type furnace power supply leads for high temperature To be used in conjunction with 77 Tape* for arc and fire proofing applications High mechanical strength Resistance to high temperatures The adhesive is a silicone high temperature thermosetting system Number Material Colour Coil size Scotch69-6 Glass Cloth White 6 x 0.177 33m 7.60 Scotch69-9 Glass Cloth White 9 x 0.177 33m 9.50 Scotch69-12 Glass Cloth White 12 x 0.177 33m 15.70 Scotch69-15 Glass Cloth White 15 x 0.177 33m 19.65 Scotch69-19 Glass Cloth White 19 x 0.177 33m 23.55 Scotch69-25 Glass Cloth White 25 x 0.177 33m 31.45 Scotch69-38 Glass Cloth White 38 x 0.177 33m 47.80 Speed Scotch69-50 Glass Cloth White 50 x 0.177 33m 62.85 Reliability Designed for insulating joints, connections, heavy split bolts and bus bars Cambric tape SCOTCH 2510 TAPE The fabric is oil primed and coated with a high-grade yellow electrical insulating varnish Flexible & moisture resistant with a smooth finish Excellent resistance to abrasion, puncture and cut through Number Material Colour Coil size Scotch2510 Woven Cambric Cotton Yellow 19 x 7.0 20m 11.90 Temperature Rating 200 C Safety 3M Scotchcast LV Cable Jointing Temperature Rating 105 C 145
Tapes, Aerosols & Accessories AEROSOL SPRAYS SCOTCH 1600 ANTI-CORROSION SPRAY Anti-corrosion protection spray Designed for corrosion protection on pipes and supports, switches and controls etc Rubber-asphalt base forms abrasion resistant protective covering Protection against rust, moisture, salt water spray etc Number Colour Scotch1600 Red 400ml 8.85 SCOTCH 1601 & 1602 INSULATION SPRAY Electrical insulation spray Designed to provide a protective coating in electrical connections Hardens into a flexible and resistant film Excellent adhesion to most coon surfaces such as metal, glass, plastic, wood Moisture and weatherproof and resistant to UV-rays, acids, oil and alkalis Available in Clear or Red Number Colour Scotch1601 Clear 400ml 8.95 Scotch1602 Red 400ml 8.95 SCOTCH 1605 DEHUMIDIFIER SPRAY Dehumidifier spray ty Designed to penetrate and displace moisture Forms a thin protective film and thus preventing renewed access of moisture Neutral toward paints, plastics, rubber and fabrics Number Colour Scotch1605 Clear 400ml 9.55 SCOTCH 1609 SILICONE SPRAY Silicone spray Designed as a general use product for protective, maintenance, protection and lubrication It lubricates moving parts without becoming resinous and can be used over a wide temperature range Neutral to paints, plastics, rubber, foamed materials, wood and fabrics Number Colour Scotch1609 Clear 400ml 7.75 146
Tapes, Aerosols & Accessories AEROSOL SPRAYS SCOTCH 1617 ZINC SPRAY Zinc spray Permanent protection against rust and corrosion Excellent adhesion to iron and steel Resistant to weathering, UV radiation, moisture, alkaline solutions and mineral oils Ideal primer for metal constructions Number Colour Scotch1617 Grey 400ml 16.85 SCOTCH 1625 ELECTRICAL CONTACT CLEANER SPRAY Electrical contact cleaner spray 3M Electrical Markets Division 3M Scotchcast Cable Joints Designed for general purpose cleaning applications Loosens dirt, light oxide layers and impurities of every kind in an effective gentle manner Electrically neutral Number Colour Scotch1625 Clear 400ml 10.20 SCOTCH 1626 DEGREASING CLEANER SPRAY Degreasing cleaner spray Designed for general purpose degreasing applications Ideal dissolving cleaner for greases, oils, lubricants, resins and tar Non-corroding Number Colour Scotch1626 Clear 400ml 9.60 SCOTCH 1633 RUST REMOVER SPRAY Rust remover spray It loosens rust, protects against moisture and renewed oxidation Forms a moisture barrier to prevent trouble before it starts Excellent lubrication properties Speed Reliability Colour Number Scotch1633 Clear 400ml 8.05 Safety 3M Scotchcast LV Cable Jointing 147
Tapes, Aerosols & Accessories DENSO PRODUCTS DENSOFIL Anti-corrosion putty Anti-corrosion putty designed for sealing, filling and caulking Insulates fittings preventing condensation which protects against corrosion Lightweight material perfect for fitting around awkward items Number DENSOFIL 2kg 31.50 denso paste Anti-corrosion primer A primer for denso tape & rust preventative for exposed metal It does not dry, harden or crack Number DENSO PASTE 2.5kg 31.50 denso mastic Anti-corrosion mastic Anti corrosion mastic for sealing, filling and caulking where protective waterproof insulation is required Suitable for application in a wide range of climatic conditions Number DENSO MASTIC 3kg 32.50 DENSO TAPE Anti-corrosion tape Anti-corrosion and sealing tape Suitable for application in a wide range of climatic conditions Number DENSO TAPE 50 50 x 10m 11.50 DENSO TAPE 75 75 x 10m 15.50 DENSO TAPE 100 100 x 10m 21.00 148
Cable Laying Products CONTENTS Cable Pulling Equipment 150 Cable Pulling Lubricants 152 Hand & Cable Cleaning Wipes 154 Cable Warning & Detection Tape 155 Cable Protection & Location Products 156 149
Cable Laying Products CABLE PULLING EQUIPMENT CABLE ROLLERS CABLE SCREW JACKS SPINDLES JACK PLINTHS To aid cable installation For cable pulling Corner rollers also available Lightweight roller for easy transportation Zinc plated heavy duty assembly Steel frame with steel roller on sealed ball bearings Weight Range TRN76 2.75 kg Max 76 cable diameter 55.12 TR5 4 kg Max 125 cable diameter 55.12 For supporting cable drums Easy to handle and simple operation Base plate designed to give stability even on soft ground Locking collars can be ordered on request Versatile and easily adjustable Robustly engineered for regular use Max Drum Diameter 3 TON JACK Base area - 1830 x 285 1600 652.50 6 TON JACK Base area - 1830 x 760 1900 681.75 8 TON JACK Base area - 2000 x 800 2200 742.50 Supporting cable on relevant jacks Solid bar construction Other sizes available on request Spindle Diameter Detail 4FT 6 TON 50 1219 long Suitable for use with the 3 ton jacks 90.00 6FT 6 TON 50 1800 long Suitable for use with the 6 ton jacks 117.00 7FT 8 TON 50 2100 long Suitable for use with the 8 ton jacks 236.00 For larger cable drums Used with the above cable jacks gives an additional 300 height Allows larger cable drums to be accoodated 150 Detail JACK PLINTH 1200 x 320 x 300 Plinths give an additional 300 lift safely 641.25
Cable Laying Products CABLE PULLING EQUIPMENT CABLE STOCKINGS - DOUBLE EYE For cable pulling Material - high tensile galvanised steel wire Larger sizes and special Triplex cable stockings are also available The stocking is connected at the end of the cable and can be used for cable pulling or supporting Also available in stainless steel wire or Kevlar Ideal method for supporting cables prior to cleating Actual Break Tonne Cable Diameter CS21 0.75 6-13 42.75 CS22 1.00 13-19 42.75 CS23 2.50 19-25 43.54 CS24 3.50 25-38 43.87 CS25 5.00 38-50 52.87 CS26 5.00 50-63 56.25 CS27 6.00 63-89 63.00 CS28 7.00 89-115 63.38 CS29 7.00 115-130 96.75 For cable pulling Material - high tensile galvanised steel wire Larger sizes and special Triplex cable stockings are also available SPLIT CABLE STOCKINGS - DOUBLE EYE The unique split / tie feature allows the stocking to be connected at any point along the cable for cable pulling or supporting Also available in stainless steel wire or Kevlar Ideal method for supporting cables prior to cleating Actual Break Tonne Cable Diameter CS31 0.75 6-13 47.25 CS32 1.00 13-19 47.25 CS33 2.50 19-25 50.62 CS34 3.50 25-38 51.41 CS35 5.00 38-50 59.63 CS36 5.00 50-63 64.13 CS37 6.00 63-89 66.38 CS38 7.00 89-115 76.60 CS39 7.00 115-130 99.00 triplex cable pulling stocking For Triplex cable pulling Suitable for use on 11 & 22kV Triplex cable Material - high tensile galvanised steel wire Made to order - so please advise cable size at time of order Also available in stainless steel wire or Kevlar 151
Cable Laying Products CABLE PULLING LUBRICANTS HIGH PERFORMANCE CABLE LUBRICANT High performance cable lubricant for heavy cable installations High performance, clean, slow drying, water based gel lubricant Recoended for longs pulls, multiple bends and hot environments Dries to form a thin lubricating film which retains its lubricity for months after use Lubricant J provides maximum tension reduction in all types of cable pulling It is harmless to humans and environmentally safe Temperature stable and does not promote flame propagation when used with fire retardant cables Available in cold weather (non freezing) formula UL & CSA listed J-640 18.9 litre 69.50 POURABLE HIGH PERFORMANCE CABLE LUBRICANT Pourable high performance cable lubricant for heavy cable installations High performance lubricant which is easy to install without the need to handle the lubricant Recoended for horizontal pulls typical in underground construction Easier to pump than conventional gel based lubricants Dries to form a thin lubricating film which retains its lubricity for months after use Lubricant J provides maximum tension reduction in all types of cable pulling It is harmless to human and environmentally safe Temperature stable and does not promote flame propagation when used with fire retardant cables Available in cold weather (non freezing) formula UL & CSA listed PJ-640 18.9 litre 69.50 DYNA-BLUE THICK GEL CABLE LUBRICANT Dyna-Blue thick gel cable lubricant for heavy cable installations Dyna-Blue is a clean, slow drying, easy to apply gel lubricant It is a thick gel with clingability for easy handling and application Dyna-Blue combines effectiveness with economy It is a good lubricant for everyday use in general electrical applications Stays slippery won t dry out It is harmless to human and environmentally safe Temperature stable UL & CSA listed D-640 18.9 litre 69.50 152
Cable Laying Products CABLE PULLING LUBRICANTS Premium silicone cable lubricant for heavy cables and difficult pulls PREMIUM SILICONE CABLE LUBRICANT High performance, clean, slow drying silicone based cable pulling lubricant Recoended for the longest most difficult cable pulls Excellent performance in water filled ducts Superior friction reduction with high cling factor Suitable for all coon cable jackets Suitable for pumping where large quantities are required It is harmless to human and environmentally safe Temperature stable Available in cold weather (non freezing) formula NN640 18.9 litre bucket 99.50 MULTIPURPOSE CABLE LUBRICANT Techlube multi is a multipurpose cable lubricant for all cable pulls Provides superior friction reduction between cable and all forms of conduit Dries slowly to form a thin friction reducing film Retains duct lubrication for several months allowing ease of any additional cable pulling Compatible with all forms of cable jacket High and low temperature stability Non-flaable & non-toxic Resistance to wash off PTT-TLMULTI-05 20 litre bucket 75.00 Techlube HD is a heavy duty cable for difficult cable pulls HEAVY DUTY CABLE PULLING LUBRICANT Provides superior friction reduction between cable and all forms of conduit including concrete duct Dries slowly to form a thin friction reducing film Retains duct lubrication for several months allowing ease of any additional cable pulling Compatible with all forms of cable jacket Where large quantities of lubricant are needed, Techlube HD is pumpable Non-flaable & non-toxic Biodegradable PTT-TLHD-05 20 litre bucket 99.50 153
Cable Laying Products HAND & CABLE CLEANING WIPES MULTI-PURPOSE CLEANING WIPES Grime-Away multipurpose cleaning wipes Grime-Away wipes are heavy duty towelettes premoistened with a multi-purpose cleaning solution Recoended for use on tools, transformer, work surfaces, machinery, skin and more. Moisturises and softens hands while cleaning tools and surfaces Small & portable Grime-Away towels feature a textured side to quickly remove greases dirt and grime. They also feature a soft side to be gentler on skin Quickly removes oil, cable gel, silicone grease, tar, adhesive and caulk HTC-D72 72 x 10" x 12" wipes 35.00 MULTIPURPOSE CLEANING / DEGREASING WIPES HP Multipurpose cleaning and degreasing wipes It is a multipurpose cleaning and degreasing wipe for cable cleaning, industrial and maintenance cleaning HP evaporates with no residue, is non-conductive, non-corrosive, non-freezing and non-staining Suitable for use on low, medium and high voltage applications Good general solvency power Contains no CFCs, HCFCs or hazardous solvents Residue free cleaning ensures no earth or local hotspots Please contact the sales office for special pricing based on bulk enquiries HPD72 72 x 10 x12 wipes 35.00 CABLE CLEANING WIPES PF solvent degreaser for cable cleaning It is a full strength solvent degreaser for cable cleaning prior to the jointing, terminating and for kitting of cables. Non conductive, non corrosive and non staining Suitable for use on low, medium and high voltage applications Good general solvency power Contains no CFCs, HCFCs or hazardous solvents Residue free cleaning ensures no earth or local hotspots JT250 250 wipes 90.00 JT400 400 wipes 115.00 154
Cable Laying Products CABLE WARNING & DETECTION TAPE UNDERGROUND WARNING TAPE Low cost cable warning system Economical way of warning excavators of buried cables Supplied in standard black on yellow for maximum visibility Also available in other colours Can be manufactured with specific text Each roll covers 365m Detail Description TAPECAUTION 150 x 1 x 365m Caution Electrical Cable Below Black on Yellow 17.19 Soil Tolerance ph2.5 to ph11.0 inclusive Material: Low Density Polyethylene UNDERGROUND WARNING & LOCATION TAPE Detectamesh - Cable protection and location system Suitable for use with cable and pipe locators and cable avoidence tools (CAT & GENNY) Manufactured from high strength rot resistant homopolymer polypropylene plastic with a traceable stainless steel wire Other colours and texts available to order Printed with Caution buried cable below text - black on yellow Each roll covers over 100m DETECTAMESH 200 x 1 x 100m Detail Description Caution Buried Black on Cable Below Yellow 89.88 STAINLESS STEEL CRIMPS 0.43 CRIMPING TOOL 109.91 Manufactured to BS EN 12613:2001 UNDERGROUND WARNING & LOCATION TAPE Wavelay - Cable protection and location system Printed with Caution Electric Cables Below text - black on yellow Manufactured using one or more stainless steel tracer wires Unique design allows wires to stretch 25% before breaking Top Printguard layer protects the wires and the warning message Suitable for use with cable and pipe locators and cable avoidance tools (Cat & Genny) Other colours and texts available Each roll covers over 100m WAVELAY 150 x 100m Detail Caution Electric Cable Below 106.31 STAINLESS STEEL CRIMPS 0.43 CRIMPING TOOL 109.91 Tensile strength 680 N/ 2 155
Cable Laying Products CABLE PROTECTION & LOCATION PRODUCTS CABLE PROTECTION - TAPE TILE Flexible high impact polyethylene tile Provides clear warning to third parties Damages to cables less likely, therefore reducing cable repair costs and supply disruption Rot proof and resistant to wide range of soil conditions Approved by utilities worldwide Complies with enats 12-23 CABLE PROTECTION COVERS CENTRITILE 150 CENTRITILE 200 Detail Description 2.5 x 150 x 40m 2.5 x 200 x 40m High level cable protection Caution Electric Cable Below Caution Electric Cable Below Red Brown Background with Yellow Tape and Black lettering Red Brown Background with Yellow Tape and Black lettering 35.95 49.03 Provides clear warning to third parties Lightweight and easy to install Damages to cables less likely, therefore reducing cable repair costs and supply disruption Rot proof and resistant to wide range of soil conditions Can be manufactured to suit application and Text Approved by utilities worldwide Meets impact requirement of bs 2484 Detail Description TILE 152-6 6 x 152 x 1m Caution Electric Red Background with Yellow Cable Below Tape and Black lettering 2.20 TILE 152-12 12 x 152 x 1m Caution Electric Red Background with Yellow Cable Below Tape and Black lettering 3.98 TILE 244-12 12 x 244 x 1m Caution Electric Red Background with Yellow Cable Below Tape and Black lettering 6.39 TILE 300-12 12 x 300 x 1m Caution Electric Red Background with Yellow Cable Below Tape and Black lettering 7.42 ELECTRONIC MARKER SYSTEM Ideal solution for marking cable routes Locate, read and write to ID Markers Pinpoint the exact depth and location of all existing models of properly installed underground passive EMS markers Direct depth reading of markers Locate two different marker frequencies simultaneously 1420E Description Range Description Locator - w Read/Write 1402-XR Ball Marker - Power 1251 1422-XR/Id Full Range Marker - Power Id Marker Ball For depth up to 1.5m For depth up to 2.44m For depth up to 1.5m Detector tool 1311.18 For cable marking 6.02 For cable marking 9.06 For cable marking and customer specific data 15.18 156
Earthing, Lightning & Surge Protection CONTENTS Conductors 158 Conductor Fixings 161 Bonding 163 Earthing 164 Earth Rod Clamps 165 Earth Inspection Pits & Accessories 167 Earth Bars 169 Exothermic Welding 172 Surge Protection 174 157
Earthing, Lightning & Surge Protection CONDUCTORS BARE copper tape Designed for use as conductor in earthing and lightning protection systems Conductor size determined by application and expected fault current High conductivity copper tape Other sizes available on request High conductivity copper tape to BS EN 13601 (formerly BS 1432) UL 96 (TC030-UL, TC040-UL, TC080) Weight per metre Coil Price per Metre TC030 25x3 0.67kg 25m POA TC040 25x6 1.33kg 40m POA TC065 38x6 2.02kg 25m POA TC066 40x4 1.42kg 30m POA TC075 50x4 1.78kg 30m POA TC080 50x6 2.68kg 20m POA PVC COVERED COPPER TAPE Designed for use as conductor in earthing and lightning protection systems Conductor size determined by application and expected fault current High conductivity copper tape Available in 7 colours High conductivity copper tape to BS EN 13601 (formerly BS 1432) PVC colours to BS 5252. * Green to BS 6746C Colour Weight per metre Coil Price per Metre TC105-FU Black 25x3 0.77kg 25m POA TC110 Green 25x3 0.77kg 25m POA TC115-FU Grey 25x3 0.77kg 25m POA TC120-FU Stone 25x3 0.77kg 25m POA TC125-FU White 25x3 0.77kg 25m POA TC130 Brown 25x3 0.77kg 25m POA TC111-FU Green & yellow 25x3 0.79kg 25m POA TC140-FU Green 25x6 1.53kg 40m POA TC145 Green 50x6 2.95kg 20m POA LSOH COVERED COPPER TAPE Designed for use as conductor in earthing and lightning protection systems Conductor size determined by application and expected fault current. High conductivity copper tape PVC sheath manufactured from LSOH material High conductivity copper tape to BS EN 13601 (formerly BS 1432) PVC colours to BS 6746C Colour Weight per metre Coil Price per Metre TC910 Green 25x3 0.77kg 25m POA TC940 Green 25x6 1.53kg 40m POA TC980 Green 50x6 2.95kg 20m POA Please note pricing may fluctuate based on the London Metal Exchange copper rate 158
Earthing, Lightning & Surge Protection CONDUCTORS HARD DRAWN COPPER BAR Designed for use in high voltage distribution and control applications including switchgear, transformers, control panels and panel boards. High conductivity hard drawn bar. Available bare or with tinned coating Other sizes available on request Copper Weight per metre Length Price per Metre BA205 Bare 25x3 0.67kg 3m POA BA210 Bare 25x6 1.33kg 4m POA BA225 Bare 38x6 2.03kg 4m POA BA230 Bare 50x6 2.67kg 3m POA BA231 Tinned 50x6 2.67kg 3m POA Hard drawn high conductivity copper bar to BS EN 12163 FLEXIBLE COPPER BRAID Designed for areas where expansion, contraction & vibration is a problem when connecting to LV or HV systems High conductivity copper braid Other sizes available on request Weight per metre Copper Price per Metre BD030 25x3.5 0.34kg Bare POA BD035 25x3.5 0.34kg Tinned POA High conductivity copper wire to BS 4109-C101 BARE STRANDED COPPER CABLE Designed for use as conductor in electrical, earthing and lightning protection systems High conductivity stranded copper cable Other sizes available on request Cross-sectional size Weight per metre Price per Metre CB016 16 2 0.15kg POA CB025 25 2 0.23kg POA CB035 35 2 0.32kg POA CB050-FU 50 2 0.43kg POA CB070 70 2 0.62kg POA CB095 95 2 0.86kg POA CB120 120 2 1.09kg POA CB240 240 2 2.20kg POA CB400-FU 400 2 3.53kg POA Soft drawn stranded copper cable to BS EN 60228 Please note pricing may fluctuate based on the London Metal Exchange copper rate 159
Earthing, Lightning & Surge Protection CONDUCTORS PVC COVERED STRANDED COPPER CABLE High conductivity PVC covered soft drawn stranded copper cable to BS 6004 PVC colours to BS 6746C Designed for use as conductor in electrical, earthing and lightning protection systems High conductivity stranded copper cable Green & Yellow sheath to identify as earth cable Colour Cross-sectional size Weight per metre Price per Metre CC016 Green & Yellow 16 2 0.19kg POA CC025 Green & Yellow 25 2 0.29kg POA CC035 Green & Yellow 35 2 0.41kg POA CC050 Green & Yellow 50 2 0.53kg POA CC070 Green & Yellow 70 2 0.73kg POA CC095 Green & Yellow 95 2 1.00kg POA CC120-FU Green & Yellow 120 2 1.16kg POA CC240 Green & Yellow 240 2 2.49kg POA CC400-FU Green & Yellow 400 2 3.90kg POA BARE ALUMINIUM TAPE Designed for use as conductor above ground in lightning protection systems. High conductivity bare aluminium tapes Weight per Price per Metre metre TA030 25x3 0.21kg POA Aluminium tape to BS 2898-1350 PVC COVERED ALUMINIUM TAPE Designed for use as conductor above ground in lightning protection systems. High conductivity aluminium tapes Available is 6 colours Aluminium tape to BS 2898-1350 PVC colours to BS 5252. * Green to BS 6746C Colour Cross-sectional size Weight per metre Price per Metre TA105 Black 25x3 0.30kg POA TA110 Green 25x3 0.30kg POA TA115 Grey 25x3 0.30kg POA TA120 Stone 25x3 0.30kg POA TA125 White 25x3 0.30kg POA TA130 Brown 25x3 0.30kg POA Please note pricing may fluctuate based on the London Metal Exchange copper rate 160
Earthing, Lightning & Surge Protection CONDUCTOR FIXINGS METALLIC DC TAPE CLIPS Designed to fix down conductors to a building or structure DC tape clips manufactured from high quality copper and aluminium alloys Excellent corrosion resistance and high pull off loads Material Weight each CP210-H Copper 25x3 0.07kg 2.70 CP220-H Copper 25x6 0.08kg 4.20 CP110-H Aluminium 25x3 0.03kg 2.40 CP120-H Aluminium 25x6 0.04kg 7.55 Tested to BS EN 50164 UL 96 (CP210-H, CP220-H) ADJUSTABLE METALLIC DC TAPE CLIPS Designed to be range taking and fix conductors to a building or structure DC tape clips manufactured from high quality copper and aluminium alloys Excellent corrosion resistance and high pull off loads Weight Material each CP240-H Copper 38x3-40x6 0.12kg 5.90 CP260-H Copper 50x3-50x6 0.16kg 5.90 Tested to BS EN 50164 UL 96 (CP260-H) NON-METALLIC DC TAPE CLIPS Designed to fix conductors to a building or structure. Manufactured from high grade polypropylene UV stabilised and non brittle with high pull off loads. Available in 6 colours to match bare & pvc covered copper and aluminium tapes Use With Colour Weight each CP015 Bare Tape Brown 25x3 0.01kg 0.75 CP020 Bare Tape Grey 25x3 0.01kg 0.75 CP065 Bare Tape Brown 50x6 0.02kg 1.85 CP025 PVC Covered Tape Brown 25x3 0.01kg 0.85 CP030 PVC Covered Tape Black 25x3 0.01kg 0.85 CP035 PVC Covered Tape Green 25x3 0.01kg 0.85 CP040 PVC Covered Tape Grey 25x3 0.01kg 0.85 CP045 PVC Covered Tape Stone 25x3 0.01kg 0.85 CP050 PVC Covered Tape White 25x3 0.01kg 0.85 Tested to BS EN 50164 161
Earthing, Lightning & Surge Protection CONDUCTOR FIXINGS CROSSOVER CLAMPS BS EN 50164-1 Class H Designed for forming cross joints in tapes fixed to a building or structure Screws are retained in 1 part of clamp with O rings when fitting conductor to prevent screws being lost and ensure a simple installation Manufactured from high quality copper & aluminium alloys Low resistance connection between overlapping tapes Available in copper or aluminium Weight Material each CX105-H Copper 25x3 0.09kg 6.95 CX005-H Aluminium 25x3 0.03kg 3.50 SQUARE TAPE CLAMPS BS EN 50164-1 Class H UL 96 (CT105H, CT110-H, CT115-H) Designed for forming cross, tee, through and right angle joints with tapes that are fixed to a building or structure Screws are retained in 1 part of clamp with O rings when fitting conductor to prevent screws being lost and ensure a simple installation Manufactured from high quality copper & aluminium alloys Low resistance connection between overlapping tapes Available in copper or aluminium Material Weight each CT105-H Copper 25x3 0.12kg 8.40 CT110-H Copper 25x6 0.30kg 39.60 CT115-H Copper 50x6 0.60kg 45.00 CT005-H Aluminium 25x3 0.06kg 5.25 OBLONG TEST CLAMPS Designed to connect lightning protection to earthing system & facilitate periodic testing Manufactured from high quality copper & aluminium alloys Low resistance connection between overlapping tapes Available in copper or aluminium BS EN 50164-1 Class H UL 96 (CN105-H) Weight Material each CN105-H Copper 25x3 0.29kg 12.00 CN005 Aluminium 25x3 0.12kg 11.00 162
Earthing, Lightning & Surge Protection BONDING b bonds Designed to facilitate bonding to steel structures onto a lightning protection system Manufactured from high quality copper & aluminium alloys Available in copper or aluminium Max Tape Weight Material Width each BN105 Copper 26 0.12kg 4.35 BN005 Aluminium 26 0.06kg 4.10 BS EN 50164-1 Class H, BS 7430 RWP BONDS Designed to facilitate bonding of rainwater pipes and handrails onto lightning protection system Manufactured from high quality copper & aluminium alloys Available in copper or aluminium Max Tape Weight Material Width each BN115 Copper 26 0.12kg 7.95 BN010 Aluminium 26 0.07kg 7.45 BS 7430 PIPE BONDS Designed to facilitate bonding of ducts & large diameter pipes onto lightning protection system Manufactured from high quality copper & aluminium alloys Available in copper or aluminium Material Max Cable Weight each BN175 Copper 8 0.46kg 44.00 BN176 Aluminium 8 0.25kg 29.85 BS EN 50164-1 Class H, BS 7430 BRAID BONDS Designed to facilitate the bonding of gates, doors & fences to lightning protection system Manufactured from high quality copper braids Weight Hole Centres each BN505 200 0.09kg 15.50 BN510 400 0.15kg 23.90 BS 7430 163
Earthing, Lightning & Surge Protection EARTHING COPPERBOND EARTH RODS BS EN 50164-2, BS 7430 COUPLING Designed to be driven into the ground to provide a low resistance to earth for the interconnected lightning protection system Manufactured by molecularly bonding 99.9% copper onto a low carbon steel core Copper thickness minimum 250 microns Material Weight each RB005 Copperbond 3 8 x 1200 0.62kg 12.65 RB205-FU Copperbond 5 8 x 1200 1.53kg 14.30 RB210 Copperbond 5 8 x 1500 1.88kg 17.60 RB215 Copperbond 5 8 x 1800 2.29kg 21.75 RB220-FU Copperbond 5 8 x 2100 2.51kg 25.70 RB225 Copperbond 5 8 x 2400 3.00kg 29.50 RB235 Copperbond 5 8 x 3000 3.79kg 36.25 Designed to interconnect earth rods to enable earth rod assembly to be driven deeper to lower resistance Manufactured from high copper content alloy Excellent resistance to corrosion BS EN 50164-1 Material Weight each CG270 Copper 5 8 0.46kg 6.05 DRIVING STUD Designed to be used in conjunction with a coupling to drive the earth rod into the ground and avoid damaging the threads of the rod Manufactured from carbon steel BS EN 50164-1 Material Weight each DST200 Steel 5 8 0.25kg 1.50 EARTH PLATES - LATTICE & SOLID COPPER Designed to be buried in the ground to provide a low resistance to earth for the interconnected lightning protection system Manufactured from high conductivity copper Available in either solid or lattice copper Lattice to BS EN 13601 Solid copper to BS EN 12163 Description Weight each PE110 Lattice 600 x 600 x 3 3.98kg POA PE120 Lattice 900 x 900 x 3 7.20kg POA PE010 Solid Copper 600 x 600 x 3 9.74kg POA PE020 Solid copper 900 x 900 x 3 21.74kg POA 164
Earthing, Lightning & Surge Protection EARTH ROD CLAMPS rod to tape clamp (type a) Designed to connect earth rod to copper tape to complete earth rod assembly Manufactured from high quality copper & aluminium alloys Phosphor bronze fitting Rod Diameter Conductor Weight each CR105 5 8 26 x 12 0.15kg 6.90 CR110 5 8 40 x 12 0.24kg 20.00 CR115 5 8 51 x 8 0.30kg 24.90 BS EN 50164-1 (Class H) BS 7430 UL 467 (CR105) rod to CABLE clamp (type G) Designed to connect earth rod to copper cable to complete earth rod assembly Manufactured from high quality copper & aluminium alloys Phosphor bronze fitting Rod Diameter Conductor Weight each CR515 5 8 16-700 2 0.06kg 3.00 BS EN 50164-1 (Class H) BS 7430 rod to CABLE LUG clamp (type B) Designed to connect earth rod to copper cable via lug to complete earth rod assembly. Manufactured from high quality copper & aluminium alloys Phosphor bronze fitting Rod Diameter Weight each CR205 3 8 0.09kg 9.95 CR215 5 8 0.30kg 33.95 BS 7430 165
Earthing, Lightning & Surge Protection EARTH ROD CLAMPS U BOLT ROD CLAMP (TYPE E) BS 7430 UL 467 (CR305) Designed to facilitate the connection of rod or rebar to copper cable with a lug Manufactured from high quality copper & aluminium alloys Phosphor bronze fittings Rod Diameter Hole Centres Weight each CR305 5 8 37 0.20kg 8.00 U BOLT ROD CLAMP (TYPE E) - CR320 Designed to facilitate the connection of rod or rebar to copper tape Includes additional back plate to allow the tape to be clamped without drilling Manufactured from high quality copper & aluminium alloys Phosphor bronze fittings BS 7430 UL 467 (CR305) Rod Diameter Conductor Width Hole Centres Weight each CR320 5 8 25 37 0.26kg 8.95 ROD TO CABLE CLAMP (TYPE GUV) Designed to facilitate the connection of rod or rebar to larger sizes of copper cable Manufactured from high quality copper & aluminium alloys. Phosphor bronze fittings BS EN 50164-1 Class H, BS 7430 UL 467 Rod Diameter Conductor Range Hole Centres Weight each CR700 5 8 16-95 2 37 0.39kg 14.25 CR705 5 8 70-185 2 37 0.39kg 14.25 CR730 5 8 150-300 2 37 0.62kg 17.95 166
Earthing, Lightning & Surge Protection EARTH INSPECTION PITS & ACCESSORIES CONCRETE INSPECTION PIT Designed to provide access to the earth rod assembly for periodic testing The concrete inspection pit is load rated to 3,500kg Not suitable in areas where high load small wheel vehicles are used Available with integral earth bars (see below) Weight Description Material each PT005 Concrete Inspection Pit Concrete 30kg 42.50 LIGHTWEIGHT INSPECTION PIT Designed to provide access to the earth rod assembly for periodic testing Suitable for most types of earthing & lightning protection installations Manufactured from high performance polymer, UV stable & chemically resistant The lightweight inspection pit is load rated to 5,000kg The lightweight earth pit has a lockable lid Available with integral earth bar (see below) Weight Description Material each PT205 Lightweight Inspection Pit Polymer 1.80kg 41.75 INSPECTION PIT EARTH BARS Designed to fit inside inspection pits to facilitate multiple terminations Pre-drilled high conductivity copper bar Inspection Pit Description Material Weight each PT004 Lightweight 5 Hole Earth Bar Copper 0.40kg 36.50 PT006 Concrete 5 Hole Earth Bar Copper 0.40kg 43.75 PT007 Concrete 7 Hole Earth Bar Copper 0.58kg 67.45 FurseCEM conductive aggregate Designed to be added in place of sand and aggregate to cement to provide a conductive aggregate which lowers the resistance to earth When used as a backfill for earth electrodes, FurseCEM impregnated concrete greatly increases the electrodes surface area Ideal for poor ground conditions where low resistances are problematical Available without or pre-mixed with cement Contact your nearest sales office and using the Furse Backfill software we will advise on the quantity required for each installation Type Weight each CM025 Standard 25kg 89.50 CM025-PM Pre-mixed with Concrete 25kg 89.50 167
Earthing, Lightning & Surge Protection EARTH INSPECTION PITS & ACCESSORIES bentonite moisture retaining clay Designed to be mixed with water to produce a moisture retaining clay which lowers the resistance to earth The clay is a sodium activated montmorillonite which when mixed with water swells to many times its dry volume Bentonite has the ability to hold moisture content for a considerable period of time and absorb moisture from the surrounding area Ideal for poor ground conditions where low resistances are problematical Available in powder and granules Contact your nearest sales office and using the Furse Backfill software we will advise on the quantity required for each installation Type Weight each CM015 Powder 25kg 21.95 CM015-PM Granules 25kg 23.50 SILFOS Self fluxing brazing compound used to make a permanent connection when joining copper conductors Used in substation earthing where space is restricted An alternative to tape to tape connections and exothermic welding Weight Coil FS005 50 x 12 0.50kg 8m 375.00 OXIDE INHIBITING COMPOUND Designed to stop oxides forming and prevent a galvanic reaction caused by dissimilar metals Recoended for use on all joint connections Description Weight CM005 Plastic 8oz Bottle 0.23kg 23.95 EARTH ROD HAMMER Designed to install earth electrodes when hand driving is uneconomical owing to a large quantity of rods and unfavourable ground conditions Earth rod haer can drastically reduce installation times Weight Description each HM005 Atlas Copco TT petrol driven haer 24kg POA HM010 Earth rod adapter (Suitable for 5 8 and 3 4 Earth rods) 0.7kg POA 168
Earthing, Lightning & Surge Protection EARTH BARS EARTH BARS Earth Bars are an efficient and convenient way of providing a coon earth point with integral disconnecting links which facilitate easy isolation for testing purposes Manufactured out of high conductivity 50x6 HD copper bar The PVC channel base is entirely corrosion proof - made with high impact upvc unlike the traditional galvanised steel channel Lighter and easier to handle - the use of a modern polymer channel has reduced the weight of the product making it easier to handle No need for insulators - spacers used as the PVC base is insulating M10 phosphor bronze stud assemblies Pre-drilled holes for ease of installation A range of four designs to meet most installation requirements Custom made earth bar service available STANDARD EARTH BAR A standard earth bar to facilitate multiple connections to earth No. of Ways Stud Weight each LK245-4 4 M10 300 x 90 x 90 1.4kg 123.75 LK245-6 6 M10 400 x 90 x 90 1.80kg 127.60 LK245-8 8 M10 500 x 90 x 90 2.20kg 132.85 LK245-10 10 M10 650 x 90 x 90 2.80kg 147.95 LK245-12 12 M10 750 x 90 x 90 3.20kg 160.35 LK245-16 16 M10 950 x 90 x 90 4.00kg 194.35 LK245-20 20 M10 1200 x 90 x 90 5.00kg 236.50 LK245-24 24 M10 1400 x 90 x 90 5.80kg 279.70 LK245-28 28 M10 1650 x 90 x 90 6.90kg 327.85 EARTH BAR WITH SINGLE DISCONNECTING LINK An earth bar with single disconnecting link to facilitate multiple connections to earth with the option of isolating for testing purposes No. of Ways Stud Weight each LK243-4 4 M10 375 x 90 x 96 1.9kg 136.40 LK243-6 6 M10 475 x 90 x 96 2.30kg 140.80 LK243-8 8 M10 575 x 90 x 96 2.70kg 145.20 LK243-10 10 M10 725 x 90 x 96 3.30kg 150.15 LK243-12 12 M10 825 x 90 x 96 3.70kg 174.80 LK243-16 16 M10 1025 x 90 x 96 4.50kg 211.75 LK243-20 20 M10 1275 x 90 x 96 5.50kg 258.25 LK243-24 24 M10 1475 x 90 x 90 6.30kg 300.30 LK243-28 28 M10 1725 x 90 x 90 7.40kg 342.65 169
Earthing, Lightning & Surge Protection EARTH BARS & ACCESSORIES EARTH BAR WITH TWIN DISCONNECTING LINK An earth bar with twin disconnecting links to facilitate multiple connections to earth with the option of isolating from either side of the earth bar for testing purposes No. of Ways Stud Weight each LK207-4 4 M10 400 x 90 x 96 tbc 141.35 LK207-6 6 M10 550 x 90 x 96 2.30kg 157.30 LK207-8 8 M10 650 x 90 x 96 2.70kg 173.80 LK207-10 10 M10 800 x 90 x 96 3.30kg 186.45 LK207-12 12 M10 900 x 90 x 96 3.70kg 206.95 LK207-16 16 M10 1100 x 90 x 96 4.50kg 251.15 LK207-20 20 M10 1350 x 90 x 96 5.50kg 304.45 LK207-24 24 M10 1550 x 90 x 90 6.80kg 346.85 lk207-28 28 M10 1800 x 90 x 90 7.90kg 391.00 DISCONNECTING LINK A disconnecting link to enable easy isolation for testing purposes Weight Description each LK205 Disconnecting Link 125 x 90 x 90 4.50kg 41.25 SWAN-NECK ACCESSORY Designed to facilitate an easy connection from the main earth bar to the earth ring without the need to bend the copper Manufactured from hard drawn copper bar Description Weight each LK004 Swan Neck 400 x 50 x 36 5.50kg 22.95 INSULATOR High quality zero halogen standoff insulator Manufactured from DMC with brass inserts Weight Description Thread size each IN005 Insulator with Stud Assembly M10 0.22kg 9.95 170
Earthing, Lightning & Surge Protection EARTH BARS CUSTOM MADE EARTH BARS Competitive Pricing Quick Delivery Service on ALL orders. High quality product Technical Backup (Design & Installation) Product datasheets available on request 6 5 4 3 2 1 50 50 50 50 50 50 50 50 50 D D This drawing and the information contained herein is the property of Thomas & Betts and shall not be copied, traced, photographed or reproduced in any manner nor used for any purpose whatsoever, except by written permission of Thomas & Betts. This drawing shall be returned to Thomas & Betts upon request. Copyright 2009, Thomas & Betts. All rights reserved. VIEW 3 SCALE 1 : 3 C C 252.5 252.5 252.5 252.5 1050 Corrosion proof, high impact upvc channel base Pre-drilled fixing holes 2 no. M10 terminations 50 x 6 high conductivity Copper bars VIEW 2 SCALE 1 : 3 70 20 90 77 B B 10 no. M10 terminations 50 x 6 high conductivity Copper ISOMETRIC disconnecting link Tolerences unless otherwise stated: X.XX = ±0.1 Ang. = ±1 X.X = ±0.2 X = ±0.5 FIRST ANGLE PROJECTION Original Date Name Drawn 24/02/2010 A. MERRILL Check'd 24/02/2010 G. BAKER Appr'd 24/02/2010 S. SNAPE CAD (INVENTOR) GENERATED DRAWING DO NOT CHANGE MANUALLY Sheet Ref: QADC4_A3 Rev 5 1 no. M10 SCALE 1 : 4 termination A A 50 x 6 high conductivity Copper disconnecting link 6 5 4 3 2 1 1. DO NOT SCALE 2. All dimensions in millimetres 3. All dimensions shown are before stated finish. 4. Remove all burrs and sharp edges. ISSUED FOR: PRODUCT LINE: MATERIAL: FINISH: INFORMATION FURSE E&LP VARIOUS SELF COLOUR 50 x 6 Copper earth bar 1 way + Link + 10 way + Link + 2 way (M10 ways) File: F:\Technical\2. ELP Documents\Controlled Documents\1. Production\Earth Bars\Inventor\LK207-1-10-2.idw TITLE: Earthing & Lightning Protection LK207-1-10-2 0 DRAWING NUMBER: REV: SIZE: A3 Earth Bar Selection Checklist a) No of Earth Connections Required b) Hole Centres (e.g. 50) c) of Hard Drawn Bar (e.g. 50x6) d) Type of Fittings (e.g. phosphor bronze) e) of Fittings (e.g. M10) f) Type of Base (e.g. PVC) Please contact your nearest sales office for more information 171
Earthing, Lightning & Surge Protection EXOTHERMIC WELDING FURSEWELD SYSTEM Exothermic welding system Furseweld exothermic welding is a cost efficient method of making a large or small of high quality electrical connections A simple self contained system that uses the high temperature reaction of powdered copper oxide and aluminium within a mould to form permanent electrical connections Typical applications include Earthing for power plants & substations, transmission and power distribution lines, cathodic protection and rail connections Requires no external power or heat source Is completely portable Can be used safely with minimum training PRODUCT SELECTION PROCESS l Pick the type of joint required from the connections illustrated below... l Confirm the size of conductors... l Contact your nearest Jointing Technologies sales office to confirm: Mould Powder size Accessories EXOTHERMIC JOINT SELECTOR Bar to bar BB1 BB3 BB7 BB14 BB41 Bar to earth rod BR1 Bar to steel surface BR2 BS1 BS2 BS3 Cable to bar CB1 CB4 CB5 Cable to cable CC1 CC2 CC4 CC6 CC7 172
Earthing, Lightning & Surge Protection EXOTHERMIC WELDING Cable to earth rod CR1 CR2 CR3 Cable to reinforcing bar CRE1 CRE2 CRE3 CRE6 CRE17 moulds Designed to encapsulate the conductors and enable an exothermic joint to be formed Extremely robust and capable of producing 50+ connections Price Key MOULD 1 3 89.00 MOULD 2 4 133.00 MOULD 3 5 284.00 POWDERS Designed to ignite and create a copper oxide & aluminium reaction to connect conductors Box Quantity 65P10 20 5.35 90P10 10 6.95 115P10 10 8.50 150P10 10 10.00 200P10 10 14.00 accessories A selection of accessories to aid with installation and maintenance of the items used in the Furseweld process Description HCPK4 Handle 127.00 B135 [ 1 ] Cable cleaning brush 114.00 BCM [ 2 ] Mould cleaning brush 4.50 BFC [ 3 ] Tape cleaning brush 15.00 DUXSEAL [ 4 ] Duxseal sealing compound (1lb) 35.00 FGUN [ 5 ] Flint gun 17.00 MJ4-MJ5 [ 6 ] Mould jacket 79.00 PACK-A [ 7 ] Packing 6.50 S102-S111 [ 8 ] Copper sleeve 1.35 S108A-S111A [ 8 ] Copper sleeve 1.35 STM1-FU [ 9 ] Mould cleaning scraper 14.00 TB100-FU [10] Welding toolbox 85.00 173
Earthing, Lightning & Surge Protection SURGE PROTECTION ESP D1 SERIES Tested to BS EN 61643 Enhanced protector to BS EN 62305 600V let through voltage in all modes (L-E, L-N, N-E) 20KA rated ESP M2/M4 SERIES D1 series type 1, 2 & 3 surge protection range Features Designed to protect electronic systems (e.g computer counications or control equipment) from overvoltages on the mains supply Very low let through voltage (enhanced protection to BS EN 62305) between all sets of conductors (phase to neutral, phase to earth, neutral to earth - full mode protection) Full mode design capable of handling partial lightning currents as well as allowing continual operation of protected equipment Three way visual indication of protection status and advanced pre-failure warning so you need never be unprotected Compact space saving DIN housing Available in single or three phase versions Three phase unit available in 4 versions with LCD and remote display ESP240D1 283.00 ESP415D1 561.00 ESP415D1R 623.00 ESP415D1/LCD 674.00 ESP415D1R/LCD 695.00 M2/M4 series type 1, 2 & 3 surge protection range Tested to BS EN 61643 Enhanced protector to BS EN 62305 600V let through voltage in all modes (L-E, L-N, N-E) 40KA & 80KA rated Features Designed to protect electronic systems (e.g computer counications or control equipment) from overvoltages on the mains supply in high intensity lightning areas Very low let through voltage (enhanced protection to BS EN 62305) between all sets of conductors (phase to neutral, phase to earth, neutral to earth - full mode protection) Full mode design capable of handling partial lightning currents as well as allowing continual operation of protected equipment Three way visual indication of protection status and advanced pre-failure warning so you need never be unprotected ESP415M2 1036.00 ESP415M4 1981.00 ENCLOSURES Weatherproof enclosures Features Enclosures are used to protect your SPD from damp and dirty environments Enclosure for SPD WBX D4 ESP240D1 70.00 WBX D8 ESP415D1 92.50 WBX M2 ESP415M2 134.50 WBX M4 ESP415M4 171.50 174
Cable Transits CONTENTS Roxtec Sealing System 176 Raychem Duct Seal 182 175
Cable Transits THE ROXTEC SEALING SYSTEM THE ROXTEC SEALING SYSTEM Roxtec sealing solutions for cables and pipes ensure safety, efficiency and long-term operational reliability in many different industries Multidiameter, is a solution based on rubber modules with removable layers. It allows for a perfect seal, regardless of the outside dimension of the cable or pipe. This simplifies design, speeds up installation and reduces the need for stock, material and logistics. It also provides built-in spare capacity for future upgrades The seals protect people and investments against risks caused by, for example, fire, gas, water, dust, pests, blast load, and electromagnetic interference. The system is tested and approved by all major classification societies and used in a wide range of applications We help you find the optimum solution for your needs. Our software, the Roxtec Transit Manager, is a useful tool when planning transits, purchasing and installing Roxtec products. We also offer local installation training for our customers all over the world PRODUCT SELECTION PROCESS What services need installing (Cable, Pipe or Duct) How many services will be installed What size of service will be installed Where will the service be installed (Wall, Roof or Duct) Is the installation a new build or retrofit Contact your nearest Jointing Technologies sales office to confirm: i) Frame ii) Modules iii) Accessories G FRAME G Frame for 60 x 120 to 240 x 120 packing space The Roxtec G frame is a flanged metal frame that can be cast, welded or bolted into place The frame is delivered without bolt holes, but pre-drilled standardised hole-patterns are available on request Single opening or in combinations with several openings in width and / or height Use with RM installation modules Available in primed, galv or AISI 316 stainless steel GE extension frame or casting moulds available on request Additional sizes available on request Frame Openings Packing Space Dimensions G2X1 1 60 x 120 221 x 241 POA G2X2 2 60 x 120 233 x 383 POA G4X1 1 120 x 120 280 x 241 POA G4X2 2 120 x 120 292 x 383 POA G6X1 1 180 x 120 338 x 241 POA G6X2 2 180 x 120 350 x 383 POA G6X3 3 180 x 120 350 x 514 POA G8X1 1 240 x 120 398 x 241 POA G8X2 2 240 x 120 410 x 383 POA G8X3 3 240 x 120 410 x 514 POA G8X4 4 240 x 120 410 x 644 POA 176
Cable Transits THE ROXTEC SEALING SYSTEM GHM FRAME GHM Frame for bolted installation with 60 x 120 to 120 x 120 packing space GHM frame is designed for installation through bolting where welding is not suitable Use with RM installation modules Mild steel with primed finish Additional sizes available on request Frame Openings Packing Space Dimensions GHM2X1 1 60 x 120 221 x 241 POA GHM2X2 2 60 x 120 233 x 383 POA GHM4X1 1 120 x 120 280 x 241 POA GHM4X2 2 120 x 120 292 x 383 POA B Frame for installation around existing services for 60 x 120 to 120 x 120 packing space b FRAME The Roxtec B frame is a flanged, bolted together metal frame. Frame parts are assembled to make different sizes and combinations of openings Suitable for installation also around existing cables and pipes Use with RM installation modules Galvanised mild steel Packing Space Dimensions LSZ2 Height 60 181 x 8 POA LSZ4 Height 120 240 x 8 POA LSZ6 Height 180 298 x 8 POA LSZ8 Height 240 358 x 8 POA PSZ2 Height 60 181 x 8 POA PSZ4 Height 120 240 x 8 POA PSZ6 Height 180 298 x 8 POA PSZ8 Height 240 358 x 8 POA SSZ Width 120 - POA R Frame for installation around existing services for 60 x 120 to 120 x 120 packing space R FRAME The Roxtec R frame is a round expansion frame with a square packing space for multiple cables, pipes and modules Compression is integrated into the frame to enable installation around existing cables/pipes Available in galvanised mild steel & AISI 316 stainless steel Packing Space Hole Diameter R100 60 x 60 100-102 POA R125 80 x 80 125-127 POA R127 80 x 80 127-129 POA R150 90 x 90 150-152 POA R200 120 x 120 200-202 POA 177
Cable Transits THE ROXTEC SEALING SYSTEM RS Frame with integrated seal RS entry seal for installation around existing services for 60 x 120 to 120 x 120 packing space The Roxtec RS is a round entry seal with integrated compression system for use with one cable or pipe RS entry seal has two halves and an adaptable centre with removable layers to allow installation around existing cable or pipe Manufactured out of AISI 316 stainless steel Casting mould & sleeve accessory available Cable/Pipe Diameter Hole Diameter RS25 3.6-12.0 25.0-26.0 POA RS31 4.0-17.0 31.0-32.0 POA RS43 4.0-23.0 43.0-45.0 POA RS50 8.0-30.0 50.0-52.0 POA RS68 26.0-48.0 68.0-70.0 POA RS75 24.0-54.0 75.0-77.0 POA RS100 48.0-70.0 100.0-102.0 POA RS125 66.0-98.0 125.0-127.0 POA RM MODULES - WITH CORE Adaptable RM sealing modules for cables and pipes 3.0 to 54.0 Adaptable RM sealing modules for use with frames. MultidiameterTM technology based on removable layers for perfect adaptation to a cable or pipe Made from Roxylon rubber When used with a solid core, the module functions as a spare module for future capacity Cable/Pipe Dia External Diameter RM15 3.0-11.0 15 x 15 POA RM20 4.0-14.5 20 x 20 POA RM30 10.0-25.0 30 x 30 POA RM40 21.5-34.5 40 x 40 POA RM60 28.0-54.00 60 x 60 POA RM MODULES - WITHOUT CORE Adaptable RM sealing modules without core for cables and pipes 28.0 to 99.0 Adaptable RM sealing modules without core for use with frames More cost effective solution based on less waste Made from Roxylon rubber Cores are available where blocks are to be used as spare capacity Cable/Pipe Dia External Diameter RM60WOC 28.0-54.0 60 x 60 POA RM90WOC 48.0-71.0 90 x 90 POA RM120WOC 67.5-99.0 120 x 120 POA 178
Cable Transits THE ROXTEC SEALING SYSTEM SOLID COMPENSATION MODULES Solid compensation modules Solid compensation modules to allow for additional spacing between cables and pipes. Made from Roxylon rubber External Dimension RM15/0 15 x 15 POA RM20/0 20 x 20 POA RM30/0 30 x 30 POA RM40/0 40 x 40 POA RM60/0 60 x 60 POA Compression units WEDGE KITS The Roxtec Wedge is a highly efficient compression unit, which saves valuable installation time both when it comes to installation and re-installation of the Roxtec sealing system The unit is compressed and decompressed by turning the screws in the front The Wedge kit includes one Roxtec Wedge 60 or 120, five stayplates, one Wedge Clip, one lubricant and installation instructions Available in galvanised or AISI 316 stainless steel External Diameter (W x H) WK60 60 x 48 POA WK120 120 x 48 POA Sleeves with flange for hole diameter from 160.0 to 739.0 Designed for use with Roxtec round R frames and RS entry seals Sleeves are installed by either bolting or casting Available in primed, galvanised or AISI 316 stainless steel Available without flange on request Please contact your nearest sales office for information about full range Round and rectangular casting moulds SLEEVES WITH FLANGE CASTING MOULDS Casting moulds are used together with regular frames, or for round frames/seals, when casting them into concrete structures When used with rectangular frames the casting mould gives the correct dimension of the passage through the wall which assures that stayplate and compression unit can work properly in the installation When used for round frames/seals the paper casting mould creates a hole with correct dimension for the corresponding frame/seal size Please contact your nearest sales office for information about full range 179
Cable Transits THE ROXTEC SEALING SYSTEM GE EXTENSION FRAME GE extension frame The GE extension frame is used as an extension when regular frames are not deep enough to protrude through the wall structure Manufactured in galvanised steel External Dimension GE21 215 x 234 POA GE41 274 x 234 POA GE42 274 x 365 POA GE43 274 x 496 POA GE44 274 x 627 POA GE45 274 x 758 POA GE46 332 x 889 POA GE61 332 x 234 POA GE62 332 x 365 POA GE63 332 x 496 POA GE64 332 x 627 POA GE65 332 x 758 POA GE66 332 x 889 POA GE81 392 x 234 POA GE82 392 x 365 POA GE83 392 x 496 POA GE84 392 x 627 POA Please contact your nearest sales office for information about full range SEALING STRIPS TSL sealing strip TSL sealing are designed for use with flanged frames TSL1 60 x 5 POA TSL2 50 x 18 POA PRE-COMPRESSION TOOL Pre-compression tool to make room for wedge Pre-compression tool is designed to help compress installed modules and stayplates to make room for the Roxtec wedge PCS PCL POA POA 180
Cable Transits THE ROXTEC SEALING SYSTEM BESPOKE SOLUTIONS Jointing Technologies are fully aware that not all installations where a sealing system is required can be supplied from the shelf based on standard materials. Therefore Jointing Technologies working alongside cable transit manufacture Roxtec can design and provide engineered solutions for our clients individual requirements. The Jointing Technologies design team work closely with the client to Understand the cable or pipe being installed in each application Arrange site visit to evaluate the conditions of the installation which may affect any recoendations made Introduce the manufacturer to the client so that a comprehensive dialogue can take place to ensure all the criteria for the installation are met Design a solution utilising Roxtec transit manager software Produce a prototype based on the design brief Ensure the bespoke solution is supplied to the customer for testing Manufacture sealing solution to agreed specification Where the client wishes to carry out the installation themselves, Jointing Technologies can provide all necessary training and advice required Jointing Technologies aim to provide the most practical and cost effective products to enable the client to complete the installation on time and within budget. INSTALLATION SERVICES Jointing Technologies are fully aware of the difficulties that can occur when designing and installing a system to seal cables travelling through a duct or wall. As with any installation there are certain skills that are unique to the product being installed and it is sometimes by using these services from an outside source that can enable a contractor to complete the project on time and within budgetary cost. Therefore Jointing Technologies offer a complete turnkey service on Roxtec cable transits involving design, supply, install and coissioning of each project to give our clients confidence and peace of mind in the total installation. The Jointing Technologies cable transit installation teams are: Trained and qualified in the use and installation of Roxtec products Experienced in installation in DNO power market sector, substation and transformer applications Health & Safety (Safe Contractor) accredited All cable transits installations carry an extended warranty period and on completion each project is coissioned by our engineers. Therefore should there be any subsequent problems arising from excess movement of the cable or the addition of extra cables or pipes with the transit frame then our installation team is on hand to provide advice and an on site solution. 181
Cable Transits RAYCHEM DUCT SEAL RDSS inflatable duct seal RDSS Rayflate inflatable duct seal for 32.5 to 180.0 ducts The Rayflate seal consists of an inflatable bladder with a sealing strip which is fitted around the power cable in a duct and inflated to create a watertight seal Ideal for both new and existing installations Extremely versatile and will adapt to most configurations independent of duct ovality Used in conjunction with an inflation tool and gas cylinder Please contact sales to confirm which products are suitable for empty ducts Duct Inside Diameter Cable Diameter RDSS-45 32.5-45.0 0-32.0 18.85 RDSS-60 45.0-60.0 0-45.0 25.80 RDSS-75 55.0-75.0 0-56.0 27.45 RDSS-100 75.0-120.0 0-100.0 30.10 RDSS-125 100.0-150.0 0-130.0 32.80 RDSS-150 125.0-180.0 60-160.0 35.25 ADAPTOR SEAL Adaptor seal for larger sizes of duct To seal ducts upto 210 this adaptor is used in conjunction with Rayflate duct sealing system Duct RDSS-AD-210 150-210 23.65 RDSS SEALING CLIP RDSS sealing clip for use with multiple cables Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 70-300 19 The sealing clip is used when three or more cables have to be sealed in the same duct Designed to be used in conjunction with inflatable duct seal Use with RDSS-CLIP-45 RDSS-45 3.90 RDSS-CLIP-75 RDSS-60 & RDSS-75 5.60 RDSS-CLIP-100 RDSS-100 5.95 RDSS-CLIP-125 RDSS-125 6.40 RDSS-CLIP-150 RDSS-150 6.75 Please note RDSS Clips must be installed with 2 cable configurations when larger cables are installed inflation tool & gas cylinders able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Inflation tool and gas cylinders Designed to inflate the RDSS Rayflate seals Description RDSS-IT-16 Inflation Tool 265.90 E7512-0160 Gas Cylinders (Box of 10) 16.05 182 Our coitment. Your advantage.
Tools & Equipment CONTENTS Crimp Tools and Pumps 184 Crimp Dies Selection Tables 186 Crimp Dies 187 Cutting Tools 188 Cable Preparation Tools 189 Toolout Hire 192 Pfisterer Installation Tooling 194 Spiking Tools 194 Miscellaneous Tools 194 Gas Torch Kits & Accessories 195 Band-It Tooling 196 183
Tools & Equipment CRIMP TOOLS AND PUMPS HAND/HYDRAULIC CRIMP TOOLS Hydraulic crimping tools Lightweight and compact Spring loaded handles Tool head can be rotated through 180 Built-in safety valve Pressure release system Die Range Conductor HT131 ME-C 10-400 2 699.00 Also available: HT45-E ME 10-150 2 395.00 HT51 ME-50 10-240 2 445.00 HYDRAULIC PRESSHEAD 10-400 2 RHC 131 type hydraulic presshead for 10-400 2 cables Max operating pressure 700 bar Comes complete with quick automatic coupler Reduced weight 3.8Kg For pre-insulated and manual crimp tools please contact our sales team Die Range Conductor RHC131 ME-C 10-400 2 415.00 HYDRAULIC PRESSHEAD 400-630 2 ECW-H3D type hydraulic presshead for 400-630 2 cables With use of adaptor die (au230-130) and me-c dies the ecw-h3d can cover 10-400 2 Max operating pressure of 700 bar Weight 5.5Kg Die Range Conductor ECW-H3D ME-3D 400-630 2 510.00 HYDRAULIC PRESSHEAD 400-1000 2 RHU-520 type hydraulic presshead for 400-1000 2 cables With use of adaptor die (au520-130) and me-c dies the rhu-520 can cover 10-400 2 Max operating pressure of 700 bar Weight 18kg 184 Die Range Conductor RHU-520 ME-520 400-1000 2 1395.00
Tools & Equipment CRIMP TOOLS AND PUMPS ELECTRIC PUMP Foot and electric hydraulic pumps Electrically driven hydraulic pump, powered by a 110v/ 50-60hz single phase electric motor The remote hand controller allows advancement and pressure release on completion of the crimping operation Description EP10 ELECTRIC PUMP 110 Volt 2750.00 FOOT PUMP PO-7000 hydraulic pump Foot operated double speed pump Complete with 3m long high pressure flexible hose complete with female quick lock coupler Description PO 7000 Foot Pump 745.00 ELECTRO-HYDRAULIC PUMP B70M-P24 lightweight pump Operating at 24v dc by battery for independent use and developing 700 bar pressure Complete with 3m hose and quick couplers, remote control, shoulder strap, external battery charger and canvas holdall for carrying accessories Also available in an insulated version - contact our sales team for more info Description B70M-P24 Hydraulic Electric Pump 2350.00 TRS-B70 Canvas Rucksack For B70m-P24 126.00 SPARE BATTERY For The B70m-P24 288.00 BATTERY CRIMP TOOLS Battery-operated hydraulic crimping tools Head rotates 180 for ease of operation Ni-MH battery Supplied with: basic tool with battery and wrist strap, spare battery, battery charger, battery adaptor and plastic carrying case suitable for storing the tool and accessories Conductor B135-C 10-400 2 1695.00 Also available: B35-45 10-150 2 1175.00 B51 10-240 2 1415.00 185
Brass Barrier Gland Tools & Equipment CRIMP DIE SELECTION TABLES C B A CEMBRE LV & HV COPPER TERMINALS F Conductor ( 2 ) Stranded D Cembre Lv Lugs Terminals Cembre Lv Splices E Cembre Hv Lugs HT45E / B35-45 HT50 / B51 / RH50 0.25-2.5 A03-M - L03-M - A06-M L06-M 4-6 A1-M L1-M ME1 ME1-50 10 A2-M L2-M ME2 ME2-50 Me2-c AU230-130D + ME2-C Au520-130C + Me2-C 16 A3-M L3-M 2A3-M ME3 ME3-50 Me3-c AU230-130D + ME3-C Au520-130C + Me3-C Cable Dimensions 25 A5-M L5-M Gland 2A5-M Dimensions ME5 ME5-50 Me5-c AU230-130D + ME5-C Au520-130C + Me5-C 35 A7-M L7-M 2A7-M ME7 ME7-50 Me7-c AU230-130D + ME7-C Au520-130C + Me7-C Max. No. of Inner 50 Sheath A10-M Overall L10-M Braid Approx. 2A10-M Hexagon ME10 ME10-50 Me10-c AU230-130D + ME10-C Au520-130C + Me10-C Conductors Dia. A Dia. B Wire Length 70 A14-M L14-M Dia. C 2A14-M D A/C ME14A/F ME14-50 Me14-c AU230-130D + ME14-C Au520-130C + Me14-C E F Min95 Max A19-M Min Max L19-M 2A19-M ME19 ME19-50 Me19-c AU230-130D + ME19-C Au520-130C + Me19-C 120 A24-M L24-M 2A24-M ME24 ME24-50 Me24-c AU230-130D + ME24-C Au520-130C + Me24-C 150 A30-M L30-M 2A30-M ME30 ME30-50 Me30-c AU230-130D + ME30-C Au520-130C + Me30-C 30 185 11.5 8.0 A37-M 15.8 0.2 / 0.3 L37-M 67 2A37-M 34.0 30.5 ME37-50 Me37-c AU230-130D + ME37-C Au520-130C + Me37-C 30 240 12.5 A48-M 11.7 20.8 L48-M 0.2 / 0.3 2A48-M 64 34.0 30.5 ME48-50 Me48-c AU230-130D + ME48-C Au520-130C + Me48-C 42 11.5 300 18.0 A60-M 17.0 27.2 L60-M 0.2 / 0.45 2A60-M 65 42.2 37.6 Me60-c AU230-130D + ME60-C Au520-130C + Me60-C 60 17.0 400 25.0 A80-M 19.0 33.5 L80-M 0.3 / 0.45 2A80-M 77 53.6 47.3 Me80-c ME80-3D Me80-520 100 500 A100-M L100-M 2A100-M ME100-3D Me100-520 24.0 31.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4 630 A120-M L120-M 2A120-M ME120-3D Me120-520 200 30.0 800 41.5 36.0 52.6 A160-M 0.3 / 0.45 L160-M 84 2A160-M 77.2 70.1 Me160-520 400 40.0 1000 54.0 A200-M 46.5 65.3 L200-M 0.3 / 0.45 2A200-M 90 87.4 80.0 Me200-520 400 53.0 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 400 Aluminium dies also available 60.0 74.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 Circumferential and Hex DIN dies also available Ht131 / b135 Tool ECW-H3D Rhu-520 supplied 20 long PRYSMIAN LV COPPER TERMINALS Conductor ( 2 ) Terminals Tool Stranded Prysmian Lv Lugs Prysmian LV Splices G10 G14 E22* 0.25-2.5 BT2-C 2CS 4-6 BT6-C 6CS 10 BT10-C 10CS UCHEX10 PUADP + UCHEX10 16 BT16-C 16CS UCHEX16 PUADP + UCHEX16 25 BT25-C 25CS UCHEX25 PUADP + UCHEX25 35 BT35-C 35CS UCHEX35 PUADP + UCHEX35 50 BT50-C 50CS UCHEX50 PUADP + UCHEX50 70 BT70-C 70CS UCHEX70 PUADP + UCHEX70 95 BT95-C 95CS UCHEX95 PUADP + UCHEX95 120 BT120-C 120CS UCHEX120 PUADP + UCHEX120 150 BT150-C 150CS UCHEX150 PUADP + UCHEX150 EDNX150C/EDP150-185C 185 BT185-C 185CS UCHEX185 PUADP + UCHEX185 EDNX185C/EDP150-185C 240 BT240-C 240CS UCHEX240 PUADP + UCHEX240 EDNX240C/EDP240-500C 300 BT300-C 300CS UCHEX300 PUADP + UCHEX300 EDNX300C/EDP240-500C 400 BT400-C 400CS UCHEX400 PNX400C - PP400-500 EDNX400C/EDP240-500C 500 BT500-C 500CS PNX500C - PP400-500 EDNX500C/EDP240-500C 630 BT630-C 630CS PP630C EDNX630C/EDP240-630C 800 BT800-C 800CS EDNX800C / EDP800-1000C 1000 BT1000-C 1000CS EDNX1000C / EDP800-1000C Aluminium dies also available Pre-rounding dies also available Din spec dies also available For E22 up to 500 2 use adaptor ED22 AD1 and 630-1000 2 use ED22 AD2 Please contact your nearest sales office for Prysmian HV & DIN die selection Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 186 45, Fax: +44 (0) 23 8029 5465.uk
BARR-X EEx d IIC Brass Barrier Gland Tools & Equipment C CRIMP DIES CEMBRE DIES B A F Gland Details LV Dies Gland For References Ecw-3D Head & Thread sme-3d 400-630 Copper Cable Dimensions 3 Hexagonal Gland Dimensions 145.00 Adaptor Die For Basic Metric NPT AU230-130D Max. Max. No. Copper of Inner Sheath 1 Overall G Type Braid 131 Head Approx. 230.00 Hexagon Dia. Over Conductors Dia. A Dia. B Wire Length Design Thread Design Thread MA-520 400-1000 Copper 5 Nest 230.00 Conductors Dia. C D A/C A/F No. * No. PA-520 400-1000 Copper 2 Indentor 230.00 E F Min Max Min Max LV Dies For Rhu-520 Head MK-520 400-1000 Copper 5 Hexagonal 375.00 Adaptor Die For AU520-130C Copper 1 20S 424TX52 M20 1.5 424TX02 ½ - 14 NPT 11.0 30 11.5 8.0 15.8 G Type 0.2131 / 0.3 Head 450.00 67 34.0 30.5 20 424TX53 HV Dies For G M20 Type 1.5 131 Heads 424TX03 ½ ME-C - 14 NPT 11.0 10-400 30 Copper 12.5 13 11.7 20.8 Hexagonal 0.2 / 0.3 64 34.0 49.50 30.5 HV Dies For Ecw-3D Head ME-3D 400-630 Copper 3 Hexagonal 145.00 25 424TX55 M25 1.5 424TX05 ¾ - 14 NPT 16.0 42 11.5 18.0 17.0 27.2 0.2 / 0.45 65 42.2 37.6 HV Dies For Rhu-520 Head MK-520 400-1000 Copper 5 375.00 32 424TX56 M32 1.5 424TX06 1-11½ NPT 22.1 60 17.0 25.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3 40 424TX57 M40 1.5 424TX07 1¼ - 11½ NPT 28.2 100 24.0 31.5 26.5 39.9 0.3 / 0.45 77 61.5 56.4 50 424TX59 M50 1.5 424TX09 2-11½ NPT 37.1 200 30.0 41.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1 63 424TX61 M63 1.5 424TX11 2½ - 8 NPT 48.4 400 40.0 54.0 46.5 65.3 0.3 / 0.45 90 87.4 80.0 To ensure the correct dies are selected please contact our sales team 75 424TX63 M75 1.5 424TX13 3-8 NPT 58.6 400 53.0 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 To ensure the correct dies are selected please contact our sales team Tool Type Number Conductor size Number of dies Conductor Die Type range 2 in range LV Dies For G Type 131 Heads MA-C 10-300 Copper 12 Nest 29.50 LV Dies For G Type 131 Heads PA-C 10-300 Copper 4 Indentor 59.50 LV Dies For G Type 131 Heads ME-C 10-400 Copper 13 Hexagonal 49.50 MA-3D 400-630 Copper 3 Nest 112.00 PA-3D 400-630 Copper 2 Indentor 112.00 PRYSMIAN DIES 85 424TX64 M85 2 424TX14 3-8 NPT Conductor 65.8 size 400 60.0Number 74.0of dies 68.0 88.0 0.3 / 0.45 108 Price 126.0 Each 115.0 Tool Type Number Conductor Die Type range 2 in range LV Dies For G10/Y35 Type Heads UNX-C 10-300 Copper 12 Nest POA * 1.5 LV Pitch Dies For threads G10/Y35 are Type supplied Heads 15 long, UP-C 2 pitch threads 10-300are supplied Copper 20 long 3 Indentor POA LV Dies For G10/Y35 Type Heads U-CHEX 10-400 Copper 13 Hexagonal POA NPT thread lengths comply with new UL2225 requirements LV Dies For G14/Y46 Type Heads PNX-C 400-630 Copper 2 Nest POA LV Dies For G14/Y46 Type Heads PP-C 400-630 Copper 2 Indentor POA LV Dies For G14/Y46 Type Heads PUADP Copper 1 Adaptor Die For G10/Y35 Type Heads POA LV Dies For E22 Type Head EDNX-C 150-1000 Copper 9 Nest POA LV Dies For E22 Type Head EDP-C 150-1000 Copper 4 Indentor POA LV Dies For E22 Type Head ED22AD Copper 2 Adaptor Die Edp-C Dies POA HV Dies For G10/Y35 Type Heads U-H 16-300 Copper 5 Circumferential POA HV Dies For G14/Y46 Type Heads P-H 120-500 Copper 4 Circumferential POA CEMBRE DIN SPEC HEXAGONAL DIES For use on elbow connections To ensure the correct dies are selected please contact our sales team D E Tool Type Number DIN Reference HT131/RHC131 MK8-C 8 49.00 HT131/RHC131 MK10C 10 49.00 HT131/RHC131 MK12-C 12 49.00 HT131/RHC131 MK14-C 14 49.00 HT131/RHC131 MK16-C 16 49.00 HT131/RHC131 MK18-C 18 49.00 HT131/RHC131 MK20-C 20 49.00 HT131/RHC131 MK22-C 22 49.00 Tool Type Number DIN Reference HT131/RHC131 MK25-C 25 49.00 HT131/RHC131 MK28-C 28 49.00 HT131/RHC131 MK32-C 32 49.00 ECW-H3D MK38-3D 38 195.00 ECW-H3D MK42-3D 42 250.00 ECW-H3D MK44-3D 44 250.00 rhu-520 MK52-520 52 375.00 Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 187 www.prysmian.co.uk
Tools & Equipment CUTTING TOOLS HAND CUTTING TOOLS Hand tools for cable core cutting upto 500 2 Long handles for easy cutting RATCHET CUTTING TOOLS Conductor 5116660250 6-250 2 115.00 5116660500 6-500 2 185.00 Ratchet cutting tools for cables Improved cutting mechanism Single hand operation HAND HYDRAULIC CUTTING TOOLS Max Conductor Diameter KT5 25 115.00 KT45 45 195.00 KT4 52 225.00 Hydraulic cutting heads Designed to cut copper, aluminium and telecounications cables up to 120 Head can be opened to cut running cables Complete with quick automatic coupler for connection to a hydraulic pump BATTERY CUTTING TOOLS Diameter TC 120 Up to 120 1185.00 Also available: HT-TC051 Up to 50 895.00 HT-TC0851 Up to 85 1295.00 14.4V cordless hydraulic cutting tools Designed for single hand operation Specifically designed to cut copper, aluminium, aluminium-steel cables and steel ropes, aluminium and steel rods up to 55 diameter Double speed action Fitted with a maximum hydraulic pressure valve Extremely quiet in operation Diameter B-TC095 Up to 95 1975.00 Also available: B-TC051 Up to 50 1900.00 188
Tools & Equipment CABLE PREPARATION TOOLS CABLE STRIPPING TOOLS A selection of cable stripping tools Miscellaneous tools for cable stripping low and medium voltage cables Description Length EXRM-0607 Wooden Handled Cable Stripping Knife 175 16.50 EXRM-0947 Hook Knife For Outersheath Stripping 44.00 120-CS Insulated Hack Knife 14.95 EXRM-1004 Paper Cable Insulation Stripping Pliers 190 66.00 UNIVERSAL PLASTIC SHEATH STRIPPER Outer sheath removal tool Single hand operation Complete with 2 depth fittings KMS 77.00 KMS BLADE 27.50 CORRUGATED ALUMINIUM SHEATH STRIPPER Aluminium sheath removal tool For removal of the corrugated aluminium sheath of PICAS cables Variable/adjustable blade depth Spare blades also available Conductor CASS 95/300 95-300 2 110.00 roller chain tongs Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 Armour wire removal tool For the removal of the steel wire or aluminium wire armour of power cables Adjustable to suit armour diameters up to 76 Over Armour Diameter RCT155 20-76 132.00 RCT SPARE CHAIN - 66.00 While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 189 http://energy.tycoelectronics.com Our coitment. Your advantage.
r Gland C Tools & Equipment CABLE PREPARATION TOOLS OUTERSHEATH STRIPPERS F D verall ia. B Max Braid Wire Dia. C E Gland Dimensions Approx. Length D Hexagon A/C E A/F F SCREEN SCORING TOOLS Outer sheath removal tool Can also be used for removal of primary insulation and lead alloy sheaths For circular and longitudinal cuts Sheath Diameter PG2-HTA 21-35 215.00 PG3-HTA 26-51 325.00 PG4-HTA 47-75 298.00 15.8 0.2 / 0.3 67 34.0 30.5 20.8 0.2 / 0.3 64 34.0 30.5 27.2 0.2 / 0.45 65 42.2 37.6 33.5 0.3 / 0.45 77 53.6 47.3 39.9 0.3 / 0.45 77 61.5 56.4 52.6 0.3 / 0.45 84 77.2 70.1 65.3 0.3 / 0.45 90 87.4 80.0 78.0 0.3 / 0.45 96 109.2 98.8 88.0 0.3 / 0.45 108 126.0 115.0 For use on easy peel cable screens The LHM tools allow simple and easy removal of peelable semi- conductor The tool works by creating a precise spiral incision with an offset circular blade on the semiconductor which allows it to be neatly unwrapped The remaining length of exposed semi-con can be set depending on the tool used Diameter over Screen LHM1R30/45 14-40 444.00 PRE-SET SCORING TOOL For use on easy peel cable conductive screens 2 Different tools for use at either 11 or 33KV Pre-set blade depth allows easy scoring and screen removal PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () BAH-023000001 733472-000 40 36 49 35-95 13 BAH-023000011 033548-000 54 45 66 35-185 19 BAH-023000024 416318-000 54 52 77 70-300 19 BONDED SCREEN REMOVAL TOOL Diameter Use with TT2352/1 0.4 For 11kV 42.95 TT2352/2 0.6 For 33kV 45.00 cs and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained co Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any fer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make he information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations yco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect ages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended ) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. conomical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, controls, insulators & insulation enhancement and surge arresters. UK Ltd d 8 3AH For removing bonded cable screen Blade length can be adjusted to suit the cable 25 strip length for 11KV 40 strip length for 33KV DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Diameter over Screen Strip Length ASC25R1 14-40 25 315.00 ASC40R1 14-40 40 315.00 ASC25R2 38-60 25 370.00 ASC40R2 38-60 40 370.00 0 870 7500 240 9PH, 5289UK tycoelectronics.com 190 electronics.com Our coitment. Your advantage.
Tools & Equipment CABLE PREPARATION TOOLS BODDINGTONS BONDED SCREEN REMOVAL TOOL Designed to remove the cable s bonded screen Longitudinal and circular cuts Depth adjustment from 0 to 1.5 Unlimited stripping length Insulation Diameter Depth of Cut BSR700 10-52 0-1.5 525.00 BSR700 SPARE BLADE - - 45.00 ADJUSTABLE INSULATION TAPERING TOOL Provides a chamfered finish at the screen removal points This tool allows cylinder and tapered stripping of high and very high voltage single-core dry cables The insulation cutting angle is fully adjustable by means of a graduated rule To make a Chamfer LHA 14-40 175.00 SCREEN AND INSULATION REMOVAL TOOL HVIA STRIPPER 35/90 Stripping tool for extruded and bonded cable screens and primary insulation for cable diameter from 35-90 or 75-150 For use on medium and high voltage cables Cable Diameter HVIA-STRIPPER 35-90 35-90 1962.16 HVIA-STRIPPER 75-150 75-150 1962.16 INSULATION CUTTING PLIERS Reference PN TCPN Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () UBR095 BAH-023000001 733472-000 40 36 49 35-95 13 UBR185 BAH-023000011 033548-000 54 45 66 35-185 19 UBR300 BAH-023000024 416318-000 54 52 77 70-300 19 For axial and radial cutting of the insulation of medium voltage cables For use on XLPE cables Adjustable depth stop Description 305 051 051 Stripping Pliers POA 305 063 063 Replacement Blade POA While Tyco Electronics and its affiliates referenced herein have made every reasonable effort to ensure the accuracy of the information contained in this catalogue, Tyco Electronics cannot assure that this information is error free. For this reason, Tyco Electronics does not make any representation or offer any guarantee that such information is accurate, correct, reliable or current. Tyco Electronics reserves the right to make any adjustments to the information at any time. Tyco Electronics expressly disclaims any implied warranty regarding the information contained herein, including, but not limited to, the implied warranties of merchantability or fitness for a particular purpose. Tyco Electronics' only obligations are those stated in Tyco Electronics Standard Terms and Conditions of Sale. Tyco Electronics will in no case be liable for any incidental, indirect or consequential damages arising from or in connection with, including, but not limited to, the sale, resale, use or misuse of its products. Users should rely on their own judgement to evaluate the suitability of a product for a certain purpose and test each product for its intended application. TE (logo) and Tyco Electronics are trademarks of the Tyco Electronics group of companies and its licensors. Energy Division economical solutions for the electrical power industry: cable accessories, connectors & fittings, electrical equipment, instruments, lighting controls, insulators & insulation enhancement and surge arresters. Tyco Electronics UK Ltd Energy Division Freebournes Road Witham, Essex CM8 3AH DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Phone: +44 (0)870 870 7500 Fax: +44 (0)870 240 5289 Email: ukutilities@tycoelectronics.com 191 http://energy.tycoelectronics.com Our coitment. Your advantage.
Tools & Equipment TOOLOUT HIRE Jointing Technologies have the largest hire fleet of crimping and cutting tools in the country All available on a next working day delivery (on orders placed before 4pm) All tools are calibrated and checked prior to dispatch to ensure they are in full working order HYDRAULIC CRIMPING hydraulic cutting Also available in hand tool version Dies available 10-1000 2 copper/aluminium LV/HV Please state cable type and size First Week Consecutive Weeks Daily Weekend 85.00 60.00 35.00 60.00 Also available in hand tool version TC120 cutting head - max cutting diameter of 120 HT-TC085 cutting hand tool - max cutting diameter of 85 First Week Consecutive Weeks Daily Weekend 85.00 60.00 35.00 60.00 BATTERY CRIMPING battery cutting Dies available 10-1000 2 copper/aluminium LV/HV Please state cable type and size TC120 cutting head - max cutting diameter of 120 First Week Consecutive Weeks Daily Weekend 125.00 90.00 50.00 90.00 First Week Consecutive Weeks Daily Weekend 125.00 90.00 50.00 90.00 hydraulic crimp & cut battery crimp & cut Dies available 10-1000 2 copper/aluminium LV/HV TC120 cutting head - max cutting diameter of 120 Please state cable type and size Dies available 10-1000 2 copper/aluminium LV/HV TC120 cutting head - max cutting diameter of 120 Please state cable type and size First Week Consecutive Weeks Daily Weekend 125.00 90.00 50.00 90.00 First Week Consecutive Weeks Daily Weekend 150.00 110.00 60.00 110.00 192
Tools & Equipment TOOLOUT HIRE Long term hire deals available - Please contact our sales department for further information All hire prices include die sets - to ensure the correct sizes are supplied please advise at time of order Dies are available for copper and aluminium cables, C-taps and elbow contacts CABLE SPIKING TOOL PFISTERER TOOL Used for spiking power cables prior to jointing, terminating or repair First Week Consecutive Weeks Daily Weekend 200.00 150.00 80.00 150.00 Standard size 1, 2, 3 tool Larger sizes 4-5S and 6 also available on request Tool First Week Consecutive Weeks Daily Weekend 1, 2, 3 200.00 150.00 80.00 150.00 4, 5, 6 250.00 200.00 100.00 200.00 CABLE JACK & SPINDLE TDUX DUCT SEAL INFLATION TOOL Both 3 or 6 ton versions available Due to size and weight additional carriage may apply on this item. Contact your local sales office for more information Complete with pressure gauge to ensure correct installation Please order gas separately - see page 182 First Week Consecutive Weeks Daily Weekend 85.00 65.00 35.00 60.00 First Week Consecutive Weeks Daily Weekend 60.00 45.00 30.00 50.00 TOOL REPAIR & CALIBRATION Cembre and Prysmian Approved Repairer Calibration certificates supplied Estimates provided prior to works Reconditioned tools available All tools must be calibrated after each hire to comply with BS7671 (U.K Wiring Regulations) 193
Tools & Equipment PFISTERER/SPIKING TOOL/MISCELLANEOUS TOOLS pfisterer tool SPIKING TOOL CORDLESS IMPACT WRENCH Connex installation tool Kit includes hand operated compression tool, accessories and carrying case For installation of Connex connectors size 1, 2 and 3. For sizes 4, 5 and 6 - please contact our sales team Description PFISTERER TOOL For size 1, 2, 3 2810.00 Cable spiker kit The Bowthorpe Cable Spiker is intended to prove that a selected cable, previously disconnected, is in fact dead before site work coences. Silent in operation and of a robust and rigid construction. The kit comprises a hand operated hydraulic pump connected by a fully insulated hose to a hydraulic ram which carries the diamond shaped chisel cable spike All component parts are supplied in a stout wooden carrying case Description SG1 Up to 102 cable diameter 2500.00 Cordless impact wrench for the installation of mechanical connectors and lugs using shear-head bolts Dimensions () Conductor size Socket/ L H W ( 2 ) spanner A/F () 40 36 49 35-95 13 54 45 66 35-185 19 54 52 77 70-300 19 Simplified, safer and faster installation No additional device needed 1700 g (~3.8 lbs) light, ergonomic and practical design Can be used for shear-head bolts up to 100 Nm Powerful battery sufficient for approx. 20 four-bolted mechanical connectors per battery charging cycle Everything included for all standard mechanical connectors and lugs Description IT-1000-023 For the installation of mechanical connectors 475.00 RUBBER SWITCHGEAR MATTING able effort to ensure the accuracy of the information contained r free. For this reason, Tyco Electronics does not make any reliable or current. Tyco Electronics reserves the right to make ims any implied warranty regarding the information contained ness for a particular purpose. Tyco Electronics' only obligations Electronics will in no case be liable for any incidental, indirect limited to, the sale, resale, use or misuse of its products. Users r a certain purpose and test each product for its intended cs group of companies and its licensors. le accessories, connectors & fittings, electrical equipment, rresters. 194 Our coitment. Your advantage. DATA SHEET Date: 01/11/2009 Number: EPP-1732 Revision: A Max coil size is 10 metres Can be cut to specific length - price always rounded up to next complete metre Thickness Tested to Working Voltage Price per metre LVRM6 6 15,000 volts 450 volts 40.00 LVRM9 9 15,000 volts 650 volts 41.00 HVRM 4 50,000 volts 11,000 volts 68.00
Tools & Equipment GAS TORCH KITS & ACCESSORIES GAS TORCH KIT COMPLETE WITH BURNER, HOSE AND HANDLE Gas torch kit FEATUREs Kit designed specifically for jointers 2 Different burners for the complete range of heat shrinking applications Kit Contents Complete safety handle, soft flame burner, 4m hose with all end fittings TOL/GTK attached, carry case and regulator 275.00 handle for gas torches Gas torch handle Piezo igniton with instant trigger on/off function Bayonet fitting for burners Valve for precise flame setting Hose connection BSP 3 8 LH Working Pressure Bar H3366 1.5-4 89.50 HOT AIR AND SOFT FLAME BURNERS Hot air burners Hot-air burners with powerful windproof hot-air streams for heat shrinking 3349 ideal for shrinking in confined spaces and fibre optic closures 3359 is an extra small hot-air burner incorporating a heat reflector, ideal for signal systems, traffic lights, alarm systems, marine applications, automobiles and other vehicle repairs Work pressure - 2 bar Soft flame design ideal for cable work and other heat shrinking applications Soft flame burners with sweeping, powerful yellow and blue soot-free windproof flames Type Burner Diameter HAB32-15 (3349) Hot Air Burner 32x15 85.00 HAB 25 (3359) Hot Air Burner 25 89.00 SFB28 (334791) Soft Flame Burner 28 65.00 SFB38 (334191) Soft Flame Burner 38 75.00 SFB50 (334891) Soft Flame Burner 50 87.00 REGULATOR for gas TORches Gas torch regulator Suitable for use with the H3366 handle Hose connection bsp 3 8 lh Working Pressure Bar 3091-21 2 45.00 195 Selection guide for LP gas heating tools
Tools & Equipment BAND-IT TOOLING LIGHT AND HEAVY DUTY APPLICATIONS CABLE TIE TENSIONING TOOL C001 tool is for light and heavy duty band and buckle products Tensions up to 2400lbs - for use on band up to 3/4 C007 tool is for light duty coated or uncoated band and bandfast clamps Hand ratchet mechanism C001 TOOL 110.00 co75 TOOL - bantam 445.00 Hand tension tool AE200 tensions all re-useable Band-it ties AE201 hook tool tensions all re-usable and multilock ties CABLE TIE TENSIONER WITH AUTO CUT MECHANISM AE200 tool 96.00 AE201 TOOL 25.00 For use with Band-it coated and uncoated Multi-lock ties M503 tool - adjustable/variable tension prevents over tensioning of Multi-lok ties Can be used on both coated and un-coated Multi-lok ties K502 tool - adjustable/variable tension prevents over tensioning of Ball-lok ties Can be used on both coated and uncoated Ball-lok ties KE922 manual tool for use with multi-lok and Ball-lok ties Automatic cut off Weight 0.43kg CABLE TIE TENSIONER AND CUTTER m503 tool 750.00 K502 TOOL 675.00 For use with Band-it Multi-lok and Ball-lok ties Variable/adjustable tension prevents over tensioning of ties Can be used on both coated and un-coated Ball-Lok ties Can be used on both coated and un-coated ties KE9229 195.95 196
Trace & Underfloor Heating Systems CONTENTS Hot Water Temperature Maintenance 198 Frost Protection for Pipes 199 Heating System for Ramps, Steps & Footpaths 200 Heating System for Gutters & Downpipes 201 Underfloor Heating Systems 202 Leak Detection & Location Systems 203 Trace & Underfloor Heating Overview 204 197
Trace & Underfloor Heating Systems Hot WATER Temperature Maintenance HWAT - PLUS SYSTEM OVERVIEW High reliability: instant hot water from every tap Reduced energy consumption: no heat loss on return pipes Space-saving: no return pipes Maintenance-free: no circulation pump Easy and flexible design: no pressure loss calculations Easy assembly: RayClic connection system HWAT-M: 9 W/M AT 55 C HWAT-R: 12.5 W/M AT 60 C Heating cable (HWAT-M or R) End seal (RayClic-E-02) T-connection (Rayclic-T-02) Control Unit (HWAT-ECO) Power connection (Rayclic-CE-02) Residual current device (rcd) (30mA) Circuit-breaker (C type) 198
Trace & Underfloor Heating Systems FROST PROTECTION FOR PIPES WINTERGARD SYSTEM OVERVIEW Aluminium tape for plastic pipework (AE-180) End seal (RayClic-E-02) For FS-A-2X and FS-B-2X only For FS-C-2X use CE20-01 Fibreglass tape (GT-66) T connection (RayClic-T-02) For FS-C-2X use junction box JB16-02 ETL label Heating cable (FS-A-2X/FS-B-2X/FS-C-2X) Power connection (RayClic-CE-02) Residual current device (30mA) Circuit breaker (C type) Reliability: protects your pipes from frost damage Maintenance-free FS-A-2X: 10 W/m at 5 C Thermostat (AT-TS-13) Temperature sensor FS-B-2X: 26 W/m at 5 C FS-C-2X: 31 W/m at 5 C 22 W/m at 40 199
Trace & Underfloor Heating Systems HEATING SYSTEM FOR RAMPS, STEPS & FOOTPATHS VIAGARD SYSTEM OVERVIEW High reliability: ice and snow protection assures safer access Long service life Robust design EM2-LR: 180 W/m 2 (35 W/m) at 0 C EM2-XR: 300 W/m 2 (90 W/m) at 0 C Connection and end seal kit (VIA-CE1) Temperature and moisture sensor (VIA-DU-02) Control unit (VIA-DU-20) Junction box (VIA-JB1) Connection cable (VIA-L1) Connection and end seal kit (VIA-CE1) Self-regulating heating cable (EM2-XR) 200
Trace & Underfloor Heating Systems HEATING SYSTEM FOR GUTTERS & DOWNPIPES icestop system overview Reliable protection against winter damage No danger of icicle formation or snow avalanches Protects buildings and persons Maintenance-free Junction boxes Power connection (RayClic-CE-02) GM-2X: 36 W/m in iced water and 18 W/m in the air at 0 C Fixing bracket (GM-RAKE) Moisture sensor Control unit (EMDR-10) Temperature sensor (EMDR-1-01) Heating cable (GM-2X) Residual current device (rcd) (30mA) Circuit-breaker (C type) End seal (RayClic-E-02) End seal (E-06) Junction boxes (JB16-02) DRAIN TRACING Connection kit (C16-29) Self-regulating heating cable for drains (8BTV2-CT) 201
Trace & Underfloor Heating Systems UNDERFLOOR HEATING SYSTEMS T2 QUICKNET SYSTEM T2 RED SYSTEM Fast & simple installation Ultra thin heating mat ideal solution for retrofit installations Available in two outputs 90W SQM & 160W SQM T2 Red can be cut to length no cold lead required ideal for all shapes of rooms Can be installed on all sub floors Self regulating heater cable can be installed under any type of floor surface without risk of overheating T2 REFLECTA SYSTEM T2 Reflecta combines self regulating T2 Red heating cable with pre-grooved T2 Reflecta 20% Extra energy saving through integrated insulation Integrated insulation enables quick heat up time T2 Reflecta combines self regulating T2 Red heating cable with pre-grooved T2 Reflecta 1st choice for wooden & laminate floors Self-regulating system ensures there is no risk for overheating under furniture or rugs etc 202
Trace & Underfloor Heating Systems LEAK DETECTION AND LOCATION SYSTEMS TRACETEK SYSTEM OVERVIEW Monitoring of large surfaces Pinpointing of leaks Pre-assembled and ready to use TT1000 Water Sensor Cable Alarm Module (TTDM) Water Sensor cable (TT1000) 203
Trace & Underfloor Heating Systems TRACE & UNDERFLOOR HEATING OVERVIEW Registered Supplier ID 16470 Registered Supplier ID 16470 COMPANY CAPABILITY The mechanical services industry has seen a steady move away from the provision of flow and return hot water pipes which relied on a fully pumped system. This meant that to hold a constant temperature within the pipes the boiler worked on a continual basis to provide the necessary hot water. Therefore by switching to a one pipe design with a self regulating trace heating cable on it the contractor could install a much more efficient and economical system. To take advantage of this changing market Jointing Technologies became a main stockist and distributor of TYCO Thermal s market leading Raychem branded trace heating products. The success of this venture brought further expansion and the creation of a NEW specialist trace heating division. Working with our clients and utilising the experience of Tyco Thermal, we now offer a full estimating, supply and installation service to the industry and can assist in the design of bespoke solutions for particular applications. Our trace heating portfolio encompasses the following disciplines: Hot Water Temperature Maintenance Using Tyco Thermal s self regulating HWAT-M or HWAT-R range of maintenance tapes we can ensure your system provides the hot water you need at the turn of a tap. Frost Protection The combination of air or pipe controlled thermostats with FS-A-2X, FS-B-2X or FS-C-2X tape stops the freezing of mains cold water or chilled water pipes in extreme temperatures either in roof or site temporary situations. Leak Detection Essential to detect moisture within a controlled environment, such as computer rooms, where any form of water or coolant leak could prove disastrous to the equipment. Underfloor Heating Widely used in the coercial or housing market to provide either a heating system for the entire room or merely as a background comfort. Jointing Technologies installation teams are qualified trace heating engineers giving you total assurance and peace of mind with a 10 year guarantee on the materials used and the work undertaken. COMING SOON! Jointing Technologies are Tyco Thermal s largest distributor and installer of coercial and industrial trace heating products with the experience to handle any project, no matter the size or complexity. JOINTING TECHNOLOGIES BRANCHES AT WOKING Unit 19, Woking Business Park Albert Drive Woking GU21 5JY Tel: 01483 747747 Fax: 01483 747001 BRISTOL The Alpha Centre, Armstrong Way, Great Western Business Park, Yate, JOINTING TECHNOLOGIES BRANCHES AT WOKING Bristol. BS37 5NG Unit 19, Woking Business Park Albert Drive Tel: 01454 322555 Woking GU21 5JY Fax: 01454 323555 Tel: 01483 747747 WOLVERHAMPTON Whatever your requirements, Jointing Technologies can estimate, install and coission the system that you need. Aspley Close, Four Ashes, Wolverhampton, West Midlands. WV10 7DE Tel: 01902 790777 Fax: 01902 790666 Fax: 01483 747001 BRISTOL The Alpha Centre, Armstrong Way, Great Western Business Park, Yate, Bristol. BS37 5NG Tel: 01454 322555 Fax: 01454 323555 WOLVERHAMPTON Aspley Close, Four Ashes, Wolverhampton, West Midlands. WV10 7DE Tel: 01902 790777 Fax: 01902 790666 Trace & Underfloor Heating Systems Tra H TOOL OUT LIMITED Registered in London No. 2281668 TOOL OUT LIMITED Registered in London No. 2281668 204
Cable Data CONTENTS LV Single Core XLPE Cables 206 LV Two & Three Core XLPE Cables 207 LV Four Core XLPE Cables 208 3.3kV Three Core XLPE Cables 208 LV & 3.3kV Three & Four Core PILC Cables 209 Multi-core & Multi-paired Cables 210 Fire Proof Cables 211 11kV XLPE Cables 212 22kV XLPE Cables 213 33kV XLPE Cables 214 11kV PILC & PICAS Cables 215 11 & 22kV Triplex Cables/Wavecom Cables 216 205
r Gland C Cable Data LV Single Core XLPE Cables SINGLE CORE 6491X, STRANDED COPPER CONDUCTOR PVC OR LSF 450/750V F D verall ia. B Max Braid Wire Dia. C Conductor size E 2 Approx overall diameter Voltage drop DC mv/a/m Voltage drop DC single phase mv/a/m Voltage drop three phase AC mv/a/m Approx cable weight kg/km 1.5 3.0 29 29 25 23 2.5 3.6 18 18 15 35 4 4.2 11 11 9.5 51 6 4.7 7.3 7.3 6.4 71 10 6.1 4.4 4.4 3.8 120 16 7.2 2.8 2.8 2.4 180 25 Gland Dimensions 8.4 1.75 1.8 1.55 280 35 9.5 1.25 1.3 1.1 380 Approx. Hexagon 50 Length 11.3 0.93 1.0 0.85 490 70 D A/C A/F 12.6 0.63 0.72 0.61 710 E F 95 14.7 0.46 0.56 0.48 980 120 16.2 0.36 0.47 0.41 1210 150 18.1 0.29 0.41 0.36 1510 185 20.2 0.23 0.37 0.32 1900 240 22.9 0.18 0.33 0.29 2490 300 27.0 0.145 0.31 0.27 3050 400 32.0 0.105 0.29 0.25 3900 15.8 0.2 / 0.3 67 34.0 30.5 20.8 0.2 / 0.3 64 34.0 30.5 27.2 0.2 / 0.45 65 42.2 37.6 33.5 0.3 / 0.45 77 53.6 47.3 39.9 0.3 / 0.45 77 61.5 56.4 52.6 0.3 / 0.45 84 77.2 70.1 SINGLE CORE UNARMOURED, STRANDED COPPER CONDUCTOR LSF - 600/1000V BS5467 65.3 0.3 / 0.45 90 87.4 80.0 78.0 0.3 / 0.45 96 109.2 98.8 Conductor size 88.0 0.3 / 0.45 108 2 126.0 115.0 Approx overall diameter Approx diameter under armour Nominal diameter of armour wires Approx cable weight kg/km 150 25.8 19.5 1.6 1950 185 28.0 21.6 1.6 2350 240 30.5 23.9 1.6 3000 300 33.5 26.5 1.6 3675 400 37.8 30.4 2.0 4700 500 41.1 33.9 2.0 5925 630 45.3 38.2 2.0 7450 800 54.8 43.7 2.5 9400 1000 58.4 48.5 2.5 11400 SINGLE CORE - ALUMINIUM WIRE ARMOURED, STRANDED COPPER CONDUCTOR, LSF - 600/1000V BS6724 Conductor size 2 Approx overall diameter Average Thickness Of Insulation ( 2 ) Approx diameter under armour Nominal Diameter Of Armour Wire ( 2 ) Approx cable weight kg/km 70 20 1.1 14.7 1.25 950 95 21.6 1.1 16.3 1.25 1225 120 23.2 1.2 17.9 1.25 1500 150 25.8 1.4 19.8 1.6 1950 185 28 1.6 22 1.6 2350 240 30.5 1.7 24.5 1.6 3000 300 33.5 1.8 27.3 1.6 3675 400 37.4 2 30.2 2 4700 500 40.7 2.2 33.3 2 5925 630 44.9 2.4 37.3 2 7450 800 54.8 2.6 45.8 2.5 9400 1000 58.4 2.8 49.2 2.5 11400 DISCLAIMER Please note all the cable data in this section and selection charts are based on information provided by Prysmain Cables Limited and intended as a guide only. Jointing Technologies recoend that dimensional data is taken from the actual cable being used to ensure the correct accessories are selected. Jointing Technologies cannot be held responsible for errors in selection where incorrect cable dimension are used. 9PH, UK 206
BARR-X EEx d IIC Brass Barrier Gland Cable Data LV Two & Three Core XLPE Cables C TWO CORE XLPE - STRANDED COPPER CONDUCTOR, STEEL WIRE ARMOURED, LSF - 600/1000V BS5467 Conductor size 2 Approx overall diameter Approx diameter under armour Nominal diameter of armour wires THREE CORE XLPE - STRANDED COPPER CONDUCTOR, STEEL WIRE ARMOURED, LSF - 600/1000V BS5467 Approx cable weight kg/km 1.5 11.5 7.1 0.9 320 2.5 12.9 8.3 0.9 365 4 14.4 9.8 0.9 440 6 15.6 11 0.9 470 10 16.8 12 0.9 810 Gland References 16 & Thread s 19.6 14.1 Cable Dimensions 1.25 Gland 1025 Dimensions 25 20.9 15.6 1.25 1000 Basic Metric NPT Max. Max. No. of Inner Sheath Overall Braid Approx. Hexagon 35 23 Dia. Over Conductors 17 Dia. A 1.6 Dia. B Wire Length 1400 Design 50 Thread Design Thread 25.3 Conductors 19.3 1.6 Dia. C D 1750 A/C A/F No. * No. E F 70 28.5 22.3 Min Max Min 1.6 Max 2300 95 32.3 25.1 2 3100 20S 424TX52 120 34.8 27.4 2 3700 M20 1.5 424TX02 ½ - 14 NPT 11.0 30 11.5 8.0 15.8 0.2 / 0.3 67 150 37.9 30.3 2 4400 34.0 30.5 20 424TX53 M20 1.5 185 424TX03 ½ - 14 NPT 42.5 11.0 30 33.5 12.5 11.7 2.5 20.8 0.2 / 0.3 64 5700 34.0 30.5 25 424TX55 M25 240 1.5 424TX05 ¾ 46.5-14 NPT 16.0 37.342 11.5 18.0 17.0 2.5 27.2 0.2 / 0.45 657100 42.2 37.6 32 424TX56 M32 300 1.5 424TX06 1-50.3 11½ NPT 22.1 40.960 17.0 25.0 19.0 2.5 33.5 0.3 / 0.45 778500 53.6 47.3 40 424TX57 M40 400 1.5 424TX07 1¼ - 54.7 11½ NPT 28.2 45.1 100 24.0 31.5 26.5 2.5 39.9 0.3 / 0.45 7710700 61.5 56.4 Gland Details 50 424TX59 M50 1.5 424TX09 2-11½ NPT 37.1 200 30.0 41.5 36.0 52.6 0.3 / 0.45 84 77.2 70.1 63 424TX61 M63 1.5 424TX11 2½ - 8 NPT 48.4 400 40.0 54.0 46.5 65.3 0.3 / 0.45 90 87.4 80.0 75 424TX63 M75 1.5 424TX13 3-8 NPT 58.6 400 53.0 65.5 58.0 78.0 0.3 / 0.45 96 109.2 98.8 85 424TX64 M85 2 424TX14 3-8 NPT 65.8 400 60.0 74.0 68.0 88.0 0.3 / 0.45 108 126.0 115.0 Conductor size Approx overall Approx diameter Nominal diameter of Approx cable 2 diameter under armour * 1.5 Pitch threads are supplied 15 long, 2 pitch threads are supplied 20 long armour wires weight kg/km 1.5 12 8 0.9 280 NPT thread lengths 2.5 comply with new UL2225 13 requirements 9 0.9 350 4 15 10 0.9 450 6 16 11 0.9 550 10 18 13 1.25 800 16 21 15 1.25 1100 25 26 19 1.6 1700 35 28 22 1.6 2100 50 30 23 1.6 2400 70 34 26 1.6 3100 95 36 29 2 4100 120 40 32 2 5000 150 45 36 2.5 6300 185 49 40 2.5 7600 240 54 44 2.5 9600 300 59 49 2.5 11600 400 65 55 2.5 14400 B A D E F Ref: BARRX/04/07 DISCLAIMER Please note all the cable data in this section and selection charts are based on information provided by Prysmain Cables Limited and intended as a guide only. Jointing Technologies recoend that dimensional data is taken from the actual cable being used to ensure the correct accessories are selected. Jointing Technologies cannot be held responsible for errors in selection where incorrect cable dimension are used. Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 207 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
r Gland C Cable Data LV Four Core XLPE Cables/3.3kV Three Core XLPE Cables D FOUR CORE XLPE - STRANDED COPPER CONDUCTOR, STEEL WIRE ARMOURED, LSF - 600/1000V BS5467 E Conductor size 2 F 1.5 12.0 8.1 0.9 310 2.5 13.7 9.6 0.9 400 4 15.0 10.9 0.9 510 6 17.3 12.3 1.25 730 10 19.8 14.6 1.25 930 16 Gland Dimensions 25 22.3 27.6 17.1 21.6 1.25 1.6 1260 2000 verall Braid Approx. 35 Hexagon 30.6 24.1 1.6 2500 ia. B Wire Length Dia. C 50 D A/C A/F 32.7 26.4 1.6 3000 E F Max 70 38.0 30.6 2.0 4120 95 41.3 34.1 2.0 5280 120 46.4 37.6 2.5 6790 15.8 0.2 / 0.3 150 67 34.0 30.5 50.5 41.6 2.5 8060 20.8 0.2 / 0.3 185 64 34.0 30.5 55.3 46.0 2.5 9770 27.2 0.2 / 0.45 240 65 42.2 37.6 61.1 51.6 2.5 12270 33.5 0.3 / 0.45 300 77 53.6 47.3 66.7 56.8 2.5 14900 39.9 0.3 / 0.45 400 77 61.5 56.4 75.3 63.6 3.15 19270 52.6 0.3 / 0.45 84 77.2 70.1 65.3 0.3 / 0.45 90 87.4 80.0 THREE CORE XLPE - STRANDED COPPER CONDUCTOR, STEEL WIRE ARMOURED, LSF - 1900/3300V BS5467 78.0 0.3 / 0.45 96 109.2 98.8 88.0 0.3 / 0.45 108 126.0 115.0 Approx overall diameter Approx diameter under armour Nominal diameter of armour wires Approx cable weight kg/km Conductor size 2 Approx overall diameter Average thickness of insulation Approx diameter under armour Nominal diameter of armour wires Approx cable weight kg/km 25 31.3 2 25.3 1.6 1125 35 33.9 2 27.7 1.6 1650 50 35.1 2 27.9 2 2250 70 38.4 2 31 2 2750 95 41.5 2 33.9 2 3600 120 45.7 2 36.9 2.5 4500 150 48.3 2 39.3 2.5 5800 185 51.6 2 42.5 2.5 6500 240 56.1 2 46.8 2.5 7500 300 60.4 2 50.9 2.5 9375 400 65.3 2 55.4 2.5 10700 DISCLAIMER Please note all the cable data in this section and selection charts are based on information provided by Prysmain Cables Limited and intended as a guide only. Jointing Technologies recoend that dimensional data is taken from the actual cable being used to ensure the correct accessories are selected. Jointing Technologies cannot be held responsible for errors in selection where incorrect cable dimension are used. 9PH, UK 208
BARR-X EEx d IIC Brass Barrier Gland Cable Data LV & 3.3kV Three & Four Core PILC Cables C Gland Details Basic THREE CORE PILC - STRANDED COPPER CONDUCTOR, STEEL WIRE ARMOURED - 600/1000V BS6480 B A Conductor size Approx overall Approx diameter Nominal diameter Approx cable 2 diameter over lead of armour wire weight kg/km 25 27.6 17.8 1.6 2650 35 29.9 20.1 1.6 3200 50 32.4 22.4 1.6 3850 70 36.4 25.4 1.6 5000 95 40 28.8 2 6210 120 43.2 31.8 2 7350 Gland References & Thread s Cable Dimensions Gland Dimensions 150 48.4 35.6 2.5 9280 Metric 185 NPT 52 Max. Max. 39 No. of Inner Sheath 2.5 Overall Braid Approx. 10910 Hexagon Dia. Over Conductors Dia. A Dia. B Wire Length Design 240 Thread Design Thread 57.4 44.2 2.5 13500 Conductors Dia. C D A/C A/F No. 300 * No. 62.1 48.5 2.5 16030 E F Min Max Min Max 400 67.9 53.9 2.5 19570 D E F 20S 424TX52 M20 1.5 424TX02 ½ - 14 NPT 11.0 30 11.5 8.0 15.8 0.2 / 0.3 67 34.0 30.5 FOUR CORE PILC - STRANDED COPPER CONDUCTOR, STEEL WIRE ARMOURED - 600/1000V BS6480 20 424TX53 M20 1.5 424TX03 ½ - 14 NPT 11.0 30 12.5 11.7 20.8 0.2 / 0.3 64 34.0 30.5 25 424TX55 M25 1.5 424TX05 ¾ - 14 NPT 16.0 42 11.5 18.0 17.0 27.2 0.2 / 0.45 65 42.2 37.6 32 424TX56 M32 1.5 424TX06 1-11½ NPT 22.1 60 17.0 25.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3 40 424TX57 Conductor M40 size 1.5 424TX07 Approx 1¼ - 11½ overall NPT 28.2 Approx diameter 100 24.0 31.5 Nominal 26.5 diameter 39.9 0.3 / 0.45 Approx 77 cable 61.5 56.4 50 424TX59 2 diameter over lead of armour wire weight kg/km M50 1.5 424TX09 2-11½ NPT 37.1 200 30.0 41.5 36.0 52.6 0.3 / 0.45 84 77.2 25 30.2 23.4 1.6 3170 70.1 63 424TX61 M63 1.5 35 424TX11 2½ - 8 NPT 32.9 48.4 400 25.9 40.0 54.0 46.5 1.6 65.3 0.3 / 0.45 90 3770 87.4 80.0 75 424TX63 M75 50 1.5 424TX13 3 36.6-8 NPT 58.6 28.6400 53.0 65.5 58.0 1.6 78.0 0.3 / 0.45 964840 109.2 98.8 85 424TX64 M85 70 2 424TX14 3 40.6-8 NPT 65.8 32.4400 60.0 74.0 68.0 1.6 88.0 0.3 / 0.45 1086140 126.0 115.0 95 44.9 36.5 2 7650 120 49.5 39.9 2 9530 * 1.5 Pitch threads 150 are supplied 15 long, 54.32 pitch threads are supplied 44.3 20 long 2.5 11490 185 58.5 48.3 2.5 13560 NPT thread lengths comply with new UL2225 requirements 240 65.2 54.6 2.5 17050 300 70.5 59.7 2.5 20280 400 78.8 66.1 2.5 25660 THREE CORE PILC - STRANDED COPPER CONDUCTOR, STEEL WIRE ARMOURED - 1900/3300V BS6480 Conductor size 2 Approx overall diameter Average thickness of insulation Approx diameter under armour Nominal diameter of armour wire Approx cable weight kg/km 25 30.1 1.4 20.3 1.6 2570 35 32.4 1.4 22.4 1.6 2900 50 35.7 1.4 24.7 2 3580 70 39.2 1.4 28 2 4260 95 42.8 1.4 31.4 2 5020 120 46.9 1.4 34.3 2.5 6120 150 49.9 1.8 37.1 2.5 6890 185 53.5 1.8 40.5 2.5 7860 240 58.5 2 45.1 2.5 9290 300 63.2 2 49.6 2.5 10850 400 70.3 2 55 2.5 13690 DISCLAIMER Please note all the cable data in this section and selection charts are based on information provided by Prysmain Cables Limited and intended as a guide only. Jointing Technologies recoend that dimensional data is taken from the actual cable being used to ensure the correct accessories are selected. Jointing Technologies cannot be held responsible for errors in selection where incorrect cable dimension are used. Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 209 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
Cable Data Multi-core & Multi-paired Cables MULTI CORE XLPE, STEEL WIRE ARMOURED, STRANDED COPPER CONDUCTOR, LSF - 600/1000V BS6724 FIVE CORE Nominal cross sectional area 2 Approx overall diameter Approx diameter under armour Nominal diameter of armour wires Approx cable weight kg/km 1.5 14.9 9.8 0.9 400 2.5 16.5 11.4 0.9 490 4 18.9 12.9 1.25 715 6 20.4 14.4 1.25 900 10 23.2 17 1.25 1200 16 27.3 20.2 1.6 1650 25 30 24 1.6 2200 35 32.9 26.7 1.6 2700 SEVEN CORE 1.5 15.8 10.7 0.9 500 2.5 17.6 12.5 0.9 730 4 20.1 14.1 1.25 840 TWELVE CORE 1.5 20 14 1.25 820 2.5 22.8 16.6 1.25 1020 4 26.1 19.2 1.6 1390 NINETEEN CORE Nominal cross sectional area 2 Approx overall diameter TWENTY-SEVEN CORE 1.5 27.3 20.0 1.6 1300 2.5 31.3 24 1.6 1900 4 34.8 27.3 1.6 2420 THIRTY-SEVEN CORE Approx diameter under armour Nominal diameter of armour wires Approx cable weight kg/km 1.5 22.6 16.4 1.25 1080 2.5 27 19.9 1.6 1530 4 29.7 22.6 1.6 1850 1.5 29.9 22.5 1.6 1700 2.5 34.3 27 1.6 2200 4 39.6 31.1 2 3320 FORTY-EIGHT CORE 1.5 33.5 26 1.6 2900 2.5 40.1 31.4 2 3550 4 44.7 35.8 2 4850 MULTI PAIRED PVC, STEEL WIRE ARMOURED, STRANDED COPPER CONDUCTOR - PART 2 TYPE 2 BS5308 INDIVIDUALLY SCREENED Cable CSA Outside Diameter 1 PAIR 2 PAIR (QUAD) 5 PAIR 10 PAIR 20 PAIR 30 PAIR 50 PAIR Under Armour Outside Diameter Under Armour Outside Diameter Under Armour Outside Diameter Under Armour Outside Diameter Under Armour Outside Diameter Under Armour Outside Diameter 0.5 2 - - 15.8 11.0 19.9 14.2 26.9 20.1 33.3 26.3 39.5 31.3 50.5 40.7 0.75 2 - - 16.6 11.8 21.0 15.3 28.5 21.7 36.8 28.8 42.9 34.5 54.0 44.0 1.5 2 - - 19.4 13.7 24.4 17.8 32.5 25.5 41.6 33.4 49.8 40.0 61.6 51.2 COLLECTIVELY SCREENED Cable CSA Outside Diameter 1 PAIR 2 PAIR (QUAD) 5 PAIR 10 PAIR 20 PAIR 30 PAIR 50 PAIR Under Armour Outside Diameter Under Armour Outside Diameter Under Armour Outside Diameter Under Armour Outside Diameter Under Armour Outside Diameter Under Armour Outside Diameter 0.5 2 11.4 7.0 12.3 7.9 17.9 13.1 22.9 17.2 29.1 22.3 33.9 26.9 42.1 33.9 0.75 2 11.7 7.3 12.9 8.3 19.8 14.3 25.3 18.7 31.3 24.5 37.5 29.5 47.0 37.4 1.5 2 12.9 8.3 14.3 9.7 22.1 16.4 28.4 21.6 35.7 28.5 42.5 34.3 53.4 43.6 INDIVIDUALLY & COLLECTIVELY SCREENED Cable CSA Outside Diameter 1 PAIR 2 PAIR (QUAD) 5 PAIR 10 PAIR 20 PAIR 30 PAIR 50 PAIR Under Armour Outside Diameter Under Armour Outside Diameter Under Armour Outside Diameter Under Armour Outside Diameter Under Armour Outside Diameter Under Armour Outside Diameter 0.5 2 - - 16.8 12.0 20.9 15.2 27.9 21.1 34.3 27.3 40.5 32.3 51.5 41.7 0.75 2 - - 17.6 12.8 22.0 16.3 29.5 22.7 37.8 29.8 43.9 35.5 55.0 45.0 1.5 2 - - 20.4 14.7 25.4 18.8 33.5 26.5 42.6 34.4 50.8 41.0 62.6 52.5 Under Armour Under Armour Under Armour DISCLAIMER Please note all the cable data in this section and selection charts are based on information provided by Prysmain Cables Limited and intended as a guide only. Jointing Technologies recoend that dimensional data is taken from the actual cable being used to ensure the correct accessories are selected. Jointing Technologies cannot be held responsible for errors in selection where incorrect cable dimension are used. 210
Cable Data Fire Proof Cables FIRE PROOF CABLE - FP400 THREE & FOUR CORE THREE CORE Nominal cross sectional area 2 Approx overall dia Approx diameter under armour Approx cable weight kg/km Current rating Three phase AC Clipped direct Amps Current rating Three phase AC Free Air Amps Volt drop Three phase AC mv/a/m 1.5 13.4 8.8 340 23 25 27 2.5 14.8 10.2 430 31 33 16 4 16.1 11.5 510 42 44 10 6 17.4 12.8 620 53 56 6.8 10 20.3 14.8 930 73 78 4.0 16 22.8 17.1 1210 94 99 2.5 25 27.4 20.8 1800 124 131 1.65 35 29.2 22.4 2100 154 162 1.15 50 33.0 26.2 2600 187 197 0.87 70 37.0 30.0 3400 238 251 0.60 95 40.6 32.4 4500 289 304 0.45 120 43.8 35.4 5500 335 353 0.37 150 48.0 38.4 6900 386 406 0.30 185 52.0 42.2 8200 441 463 0.26 240 57.1 46.9 10200 520 546 0.21 300 63.0 52.6 12200 599 628 0.185 400 69.5 58.7 15000 673 728 0.165 FOUR CORE Nominal cross sectional area 2 Approx overall dia Approx diameter under armour Approx cable weight kg/km Current rating Three phase AC Clipped direct Amps Current rating Three phase AC Free Air Amps Volt drop Three phase AC mv/a/m 1.5 14.3 9.7 390 23 25 27 2.5 16.0 11.4 490 31 33 16 4 17.3 12.7 590 42 44 10 6 19.6 14.1 830 53 56 6.8 10 21.8 16.3 1040 73 78 4.0 16 24.6 18.9 1370 94 99 2.5 25 29.1 22.5 2100 124 131 1.65 35 32.2 25.4 2500 154 162 1.15 50 35.0 28.0 3200 187 197 0.87 70 40.2 32.0 4500 238 251 0.60 95 44.0 35.6 5600 289 304 0.45 120 48.4 38.8 7200 335 353 0.37 150 52.5 42.7 8500 386 406 0.30 185 57.1 46.9 10300 441 463 0.26 240 62.7 52.3 12800 520 546 0.21 300 69.6 58.8 15600 599 628 0.185 400 78.0 65.3 20400 673 728 0.165 FIRE PROOF CABLE - FP600S THREE & FOUR CORE THREE CORE Nominal cross sectional area 2 Approx overall dia Approx diameter under armour Nominal diameter of armour wires Approx cable weight kg/km Recoended accessories Claw Cleat Ref No Brass Gland Ref No 4 21 15 1.25 800 370CG04 LSF25CW 6 21 15 1.25 820 370CG04 LSF25CW 10 23 17 1.25 1050 370CG05 LSF25CW 16 24 19 1.25 1400 370CG06 LSF25CW 25 29 22 1.6 2000 370CG06 LSF32CW 35 31 24 1.6 2300 370CG07 LSF32CW 50 32 25 1.6 2800 370CG07 LSF40CW 70 36 29 1.6 3600 370CG08 LSF50SCW 95 40 32 2.0 4500 370CG08 LSF50SCW 120 43 35 2.0 5400 370CG08 LSF50SCW 150 48 39 2.5 6900 370CG09 LSF50CW 185 52 43 2.5 8200 370CG09 LSF63CW 240 57 47 2.5 10100 370CG09 LSF63CW 300 62 52 2.5 12200 370CG11 LSF63CW 400 69 58 2.5 15000 370CG12 LSF75CW FOUR CORE Nominal cross sectional area 2 Approx overall dia Approx diameter under armour Nominal diameter of armour wires Approx cable weight kg/km Recoended accessories Claw Cleat Ref No Brass Gland Ref No 4 21 15 1.25 800 370CG04 LSF25CW 6 23 17 1.25 950 370CG05 LSF25CW 10 24 19 1.25 1200 370CG05 LSF25CW 16 27 20 1.25 1600 370CG06 LSF25CW 25 32 24 1.6 2400 370CG07 LSF32CW 35 35 27 1.6 2800 370CG07 LSF40CW 50 36 29 1.6 3200 370CG08 LSF40CW 70 41 32 2.0 4500 370CG08 LSF50SCW 95 44 36 2.0 5700 370CG09 LSF50SCW 120 49 40 2.5 7300 370CG09 LSF50CW 150 55 44 2.5 8600 370CG10 LSF63CW 185 59 48 2.5 10500 370CG11 LSF63CW 240 64 54 2.5 12900 370CG12 LSF75CW 300 70 59 2.5 15500 370CG13 LSF75CW 400 79 66 3.15 20100 370CG14 CW85K DISCLAIMER Please note all the cable data in this section and selection charts are based on information provided by Prysmain Cables Limited and intended as a guide only. Jointing Technologies recoend that dimensional data is taken from the actual cable being used to ensure the correct accessories are selected. Jointing Technologies cannot be held responsible for errors in selection where incorrect cable dimension are used. 211
r Gland C Cable Data 11kv XLPE Cables D verall ia. B Max 11KV SINGLE CORE, STRANDED COPPER CONDUCTOR, COPPER WIRE SCREEN, NON-ARMOURED - BS6622/BS7835 Conductor size 2 E F Overall cable diameter Average thickness of insulation Copper wire screen Diameter over insulation Minimum bending radius Cable weight kg/m 70 25.7 3.4 16 18.8 450 1.3 95 27.4 3.4 16 20.5 500 1.5 120 29.2 3.4 16 22.0 500 1.8 150 30.5 3.4 16 23.3 550 2.1 185 32.5 3.4 16 25.1 600 2.5 Gland Dimensions 240 34.9 3.4 16 27.3 600 3.1 Braid 300 Approx. Hexagon 37.2 3.4 16 29.6 650 3.7 Wire 400Length Dia. C D A/C 40.1 A/F 3.4 35 32.3 700 4.7 500 E 43.2 F 3.4 35 35.2 750 5.7 630 46.9 3.4 35 38.6 800 7.0 15.8 0.2 / 0.3 67 34.0 30.5 11KV SINGLE CORE, STRANDED COPPER CONDUCTOR, COPPER TAPE SCREEN, ALUMINIUM WIRE ARMOURED - BS6622/BS7835 20.8 0.2 / 0.3 64 34.0 30.5 27.2 0.2 / 0.45 65 42.2 37.6 33.5 0.3 / 0.45 77 53.6 47.3 39.9 0.3 / 0.45 77 61.5 Overall 56.4 cable Average thickness of Diameter over Minimum bending Conductor size Cable weight diameter insulation insulation radius 52.6 0.3 / 0.45 2 84 77.2 70.1 kg/m 65.3 0.3 / 0.45 90 70 87.4 80.0 29.7 3.4 18.8 450 1.6 78.0 0.3 / 0.45 95 96 109.2 98.8 31.4 3.4 20.5 500 1.9 88.0 0.3 / 0.45 120108 126.0 115.0 33.1 3.4 22.0 500 2.2 150 35.4 3.4 23.3 550 2.6 185 37.2 3.4 25.1 600 3.0 240 39.8 3.4 27.3 600 3.6 300 42.3 3.4 29.6 650 4.3 400 45.2 3.4 32.3 700 5.2 500 49.5 3.4 35.2 750 6.5 630 53.3 3.4 38.6 800 7.9 11KV THREE CORE, STRANDED COPPER CONDUCTOR, COPPER TAPE SCREEN, STEEL WIRE ARMOURED - BS6622/BS7835 Conductor size 2 Overall cable diameter Average thickness of insulation Diameter over insulation Minimum bending radius Cable weight kg/m 70 57.1 3.4 18.8 700 6.4 95 61.2 3.4 20.5 750 7.5 120 65.0 3.4 22.0 800 8.6 150 68.0 3.4 23.3 850 9.6 185 72.3 3.4 25.1 900 11.2 240 79.0 3.4 27.3 950 14.2 300 84.5 3.4 29.6 1050 16.5 400 90.9 3.4 32.3 1100 19.7 DISCLAIMER Please note all the cable data in this section and selection charts are based on information provided by Prysmain Cables Limited and intended as a guide only. Jointing Technologies recoend that dimensional data is taken from the actual cable being used to ensure the correct accessories are selected. Jointing Technologies cannot be held responsible for errors in selection where incorrect cable dimension are used. 9PH, UK 212
BARR-X EEx d IIC Brass Barrier Gland C Cable Data 22kv XLPE Cables Gland Details Basic 22KV SINGLE CORE, STRANDED COPPER CONDUCTOR, COPPER WIRE SCREEN, NON-ARMOURED - BS6622/BS7835 Conductor size 2 Overall cable diameter Average thickness of insulation B A Diameter over insulation Minimum bending radius 70 30.6 5.5 16 23.4 600 1.5 95 32.5 5.5 16 25.1 600 1.8 120 34.0 5.5 16 26.6 650 2.0 150 35.5 5.5 16 27.9 650 2.4 185 37.3 5.5 16 29.7 700 2.7 Gland References & Thread s Cable Dimensions Gland Dimensions 240 39.7 5.5 25 31.9 750 3.4 Metric 300 42.2 NPT 5.5 Max. Max. 25No. of Inner Sheath 34.2 Overall 800 Braid Approx. 4.1 Hexagon Dia. Over Conductors Dia. A Dia. B Wire Length Design 400 Thread Design 45.2 Thread 5.5 35 36.9 850 5.0 Conductors Dia. C D A/C A/F No. 500 * No. 48.3 5.5 35 39.8 900 6.1 E F Min Max Min Max 630 51.9 5.5 35 43.2 950 7.4 D Cable weight kg/m E F Cable Weight 20S 424TX52 M20 1.5 424TX02 ½ - 14 NPT 11.0 30 11.5 8.0 15.8 0.2 / 0.3 67 34.0 30.5 22KV SINGLE CORE, STRANDED COPPER CONDUCTOR, COPPER TAPE SCREEN, ALUMINIUM WIRE ARMOURED - BS6622/BS7835 20 424TX53 M20 1.5 424TX03 ½ - 14 NPT 11.0 30 12.5 11.7 20.8 0.2 / 0.3 64 34.0 30.5 25 424TX55 M25 1.5 424TX05 ¾ - 14 NPT 16.0 42 11.5 18.0 17.0 27.2 0.2 / 0.45 65 42.2 37.6 32 424TX56 M32 1.5 424TX06 1-11½ NPT 22.1 60 17.0 25.0 19.0 33.5 0.3 / 0.45 77 53.6 47.3 40 424TX57 M40 1.5 424TX07 Overall 1¼ cable - 11½ NPT Average 28.2 thickness of 100 Diameter 24.0over 31.5 26.5 Minimum 39.9 bending 0.3 / 0.45 77 61.5 56.4 Conductor size Cable weight diameter insulation insulation radius 50 424TX59 M50 2 1.5 424TX09 2-11½ NPT 37.1 200 30.0 41.5 36.0 52.6 0.3 / 0.45 84 kg/m 77.2 70.1 63 424TX61 70M63 1.5 424TX11 35.32½ - 8 NPT 48.4 5.5 400 23.4 40.0 54.0 46.5 65.3 550 0.3 / 0.45 90 1.9 87.4 80.0 75 424TX63 95M75 1.5 424TX13 37.2 3-8 NPT 58.6 5.5 400 25.1 53.0 65.5 58.0 78.0 600 0.3 / 0.45 96 2.3109.2 98.8 85 424TX64 120M85 2 424TX14 38.7 3-8 NPT 65.8 5.5 400 26.6 60.0 74.0 68.0 88.0 600 0.3 / 0.45 108 2.6126.0 115.0 150 40.4 5.5 27.9 650 2.9 185 42.2 5.5 29.7 650 3.4 * 1.5 Pitch threads 240 are supplied 15 44.6 long, 2 pitch threads 5.5 are supplied 20 31.9 long 700 4.0 300 48.3 5.5 34.2 750 4.9 NPT thread lengths 400 comply with new 51.2 UL2225 requirements 5.5 36.9 800 5.8 500 54.5 5.5 39.8 850 7.0 630 58.3 5.5 43.2 900 8.4 22KV THREE CORE, STRANDED COPPER CONDUCTOR, COPPER TAPE SCREEN, STEEL WIRE ARMOURED - BS6622/BS7835 Conductor size 2 Overall cable diameter Average thickness of insulation Diameter over insulation Minimum bending radius Cable weight kg/m 70 68.1 5.5 23.4 850 7.8 95 72.3 5.5 25.1 900 9.1 120 77.1 5.5 26.6 950 11.0 150 80.3 5.5 27.9 1000 12.1 185 84.7 5.5 29.7 1050 13.8 240 89.9 5.5 31.9 1100 16.1 300 95.2 5.5 34.2 1150 18.4 400 101.9 5.5 36.9 1250 21.7 DISCLAIMER Please note all the cable data in this section and selection charts are based on information provided by Prysmain Cables Limited and intended as a guide only. Jointing Technologies recoend that dimensional data is taken from the actual cable being used to ensure the correct accessories are selected. Jointing Technologies cannot be held responsible for errors in selection where incorrect cable dimension are used. Ref: BARRX/04/07 Prysmian Cables & Systems Limited, Components Unit, Oak Road, Wrexham Industrial Estate, Wrexham, LL13 9PH, UK 213 Coercial Enquiries, Tel +44 (0) 845 767 8345, Fax: +44 (0) 23 8029 5465 www.prysmian.co.uk
r Gland C Cable Data 33kv XLPE Cables D verall ia. B Max 33KV SINGLE CORE, STRANDED COPPER CONDUCTOR, COPPER WIRE SCREEN, NON-ARMOURED - BS6622/BS7835 Conductor size 2 E F Overall cable diameter Average thickness of insulation Copper wire screen Diameter over insulation Minimum bending radius Cable weight kg/m 70 36.5 8.0 16 28.9 800 1.5 95 38.4 8.0 16 30.6 850 1.8 120 39.9 8.0 16 32.1 850 2.0 150 41.2 8.0 16 33.4 900 2.4 185 43.2 8.0 16 35.2 950 2.7 Gland Dimensions 240 45.7 8.0 25 37.4 1000 3.4 Braid 300 Approx. Hexagon 48.2 8.0 25 39.7 1050 4.1 Wire 400Length Dia. C D A/C 51.1 A/F 8.0 35 42.4 1100 5.0 500 E 54.0 F 8.0 35 45.3 1150 6.1 630 57.8 8.0 35 48.7 1250 7.4 15.8 0.2 / 0.3 67 34.0 30.5 33KV SINGLE CORE, STRANDED COPPER CONDUCTOR, COPPER TAPE SCREEN, ALUMINIUM WIRE ARMOURED - BS6622/BS7835 20.8 0.2 / 0.3 64 34.0 30.5 27.2 0.2 / 0.45 65 42.2 37.6 33.5 0.3 / 0.45 77 53.6 47.3 39.9 0.3 / 0.45 77 61.5 Overall 56.4 cable Average thickness of Diameter over Minimum bending Conductor size Cable weight diameter insulation insulation radius 52.6 0.3 / 0.45 2 84 77.2 70.1 kg/m 65.3 0.3 / 0.45 90 70 87.4 80.0 41.4 8.0 28.9 650 2.4 78.0 0.3 / 0.45 95 96 109.2 98.8 43.3 8.0 30.6 650 2.7 88.0 0.3 / 0.45 120108 126.0 115.0 44.8 8.0 32.1 700 3.1 150 47.5 8.0 33.4 750 3.6 185 49.5 8.0 35.2 750 4.0 240 51.7 8.0 37.4 800 4.7 300 54.4 8.0 39.7 850 5.5 400 57.3 8.0 42.4 900 6.4 500 60.6 8.0 45.3 950 7.6 630 64.2 8.0 48.7 1000 9.1 33KV THREE CORE, STRANDED COPPER CONDUCTOR, COPPER TAPE SCREEN, STEEL WIRE ARMOURED - BS6622/BS7835 Conductor size 2 Overall cable diameter Average thickness of insulation Diameter over insulation Minimum bending radius Cable weight kg/m 70 82.6 8 28.9 1000 10.7 95 86.7 8 30.6 1050 12.0 120 90.3 8 32.1 1100 13.3 150 93.3 8 33.4 1150 14.4 185 97.6 8 35.2 1200 16.1 240 102.9 8 37.4 1250 18.4 300 108.5 8 39.7 1300 21.0 400 114.9 8 42.4 1400 24.2 DISCLAIMER Please note all the cable data in this section and selection charts are based on information provided by Prysmain Cables Limited and intended as a guide only. Jointing Technologies recoend that dimensional data is taken from the actual cable being used to ensure the correct accessories are selected. Jointing Technologies cannot be held responsible for errors in selection where incorrect cable dimension are used. 9PH, UK 214
Cable Data 11kv PILC & PICAS Cables 11KV SINGLE CORE PILC, STRANDED COPPER CONDUCTOR, PVC - BS6480 Conductor size 2 Nominal outside diameter Lead alloy sheath thickness Over lead diameter Minimum bending radius Cable weight kg/km 50 21.1 1.2 18.0 350 1500 70 23.1 1.3 20.0 350 1900 95 25.0 1.3 21.9 400 2200 120 26.8 1.4 23.7 450 2600 150 28.3 1.4 25.2 450 3000 185 30.4 1.5 27.3 500 3600 240 33.0 1.5 30.0 500 4300 300 357 1.6 32.6 550 5100 400 39.0 1.7 35.8 600 6300 500 43.3 1.7 39.8 650 7500 630 47.7 1.8 44.0 750 9300 800 52.4 1.9 48.4 800 11500 1000 57.6 2.1 53.4 900 14200 11KV THREE CORE PILC (BELTED), STRANDED COPPER CONDUCTOR, STEEL WIRE ARMOURED - BS6480 Conductor size 2 Nominal outside diameter Armour wire diameter Armour wire cross sectional area Over lead diameter Minimum bending radius Cable weight kg/km 25 43.4 2.0 160 32.4 550 5100 35 42.3 2.0 157 31.3 550 5300 50 45.6 2.5 212 33.6 550 6500 70 48.9 2.5 226 36.9 600 7600 95 52.3 2.5 246 40.3 650 9000 120 55.0 2.5 261 43.0 700 10100 150 57.8 2.5 275 45.8 700 11500 185 61.2 2.5 295 49.2 750 13200 240 66.0 2.5 320 54.0 800 16000 300 71.6 3.15 278 58.3 900 19400 400 77.0 3.15 303 63.7 950 23100 11KV THREE CORE PICAS (SCREENED) - BS6480 Conductor size 2 Approx diameter overall 2 Approx overall thickness of aluminium sheath 2 Approx cable weight kg/km 95 49 2 3400 185 60.7 2 5200 300 72.5 2.5 7500 DISCLAIMER Please note all the cable data in this section and selection charts are based on information provided by Prysmain Cables Limited and intended as a guide only. Jointing Technologies recoend that dimensional data is taken from the actual cable being used to ensure the correct accessories are selected. Jointing Technologies cannot be held responsible for errors in selection where incorrect cable dimension are used. 215
Cable Data 11 & 22kv Triplex Cables/WAVEFORm Cables 11KV TRIPLEX CABLE Conductor size 2 Average thickness of insulation Copper wire screen nominal area 2 Approx diameter per cable 2 Approx triplexed diameter 2 95 3.4 35 27.5 59 185 2 3.4 35 32 69.5 300 2 3.4 35 37 79.5 22KV TRIPLEX CABLE Conductor size 2 Average thickness of insulation 2 Copper wire screen nominal area 2 Approx diameter per cable 2 Approx triplexed diameter 2 95 2 5.5 35 31.5 68 185 2 5.5 35 36.5 79 300 2 5.5 35 41.5 89 WAVEFORM CABLES 3 CORE Nominal cross-sectional area 2 4 CORE Minimum average thickness of insulation Concentric neutral/earth conductor: Approx of wires Approx diameter of wires Minimum average thickness of oversheath Approx overall diameter Approx cable weight kg/m Minimum bending radius 35 0.9 26 1.04 1.8 26.3 1.1 450 95 1.1 22 1.85 2.1 33.5 2.0 550 185 1.6 41 1.85 2.5 45.3 3.6 700 300 1.8 41 1.85 2.8 53.4 4.9 850 Nominal cross-sectional area 2 Minimum average thickness of insulation Concentric neutral/earth conductor: Approx of wires Approx diameter of wires Minimum average thickness of oversheath Approx overall diameter Approx cable weight kg/m Minimum bending radius 95 1.1 22 1.85 2.2 37.5 2.5 600 185 1.6 41 1.85 2.6 49.9 4.5 800 240 1.7 41 1.85 2.8 56.9 5.6 900 300 1.8 41 1.85 3.1 62.3 6.6 1000 DISCLAIMER Please note all the cable data in this section and selection charts are based on information provided by Prysmain Cables Limited and intended as a guide only. Jointing Technologies recoend that dimensional data is taken from the actual cable being used to ensure the correct accessories are selected. Jointing Technologies cannot be held responsible for errors in selection where incorrect cable dimension are used. 216
Index CONTENTS Company Capability 2 Cable Glands 7 Product Selection Data Tables 8 Stuffing Glands 9 Industrial Glands 11 Integral Earth Glands 16 Hazardous Area Glands 18 Accessories 25 Cable Lugs & Connectors 27 Pre-Insulated Terminals 28 LV Lugs & Splices 29 HV Lugs & Splices 35 LV Mechanical lugs 38 LV Mechanical Connectors 39 HV Mechanical Lugs & Connectors 41 Cable Cleats 47 Product Selection Table 48 Plastic Cable Cleats 49 Aluminium Cable Cleats 53 Multiple Cable Cleats 57 Accessories 61 Cable Ties & Marking Systems 63 Nylon Cable Ties 64 Nylon Cable Markers 66 Stainless Steel Cable Ties 67 Stainless Steel Banding System 70 All Round Band & Accessories 71 Stainless Steel Cable Markers 72 LV Jointing 73 Resin Joints 74 Unarmoured, Pilot/Telecom Joints 78 Hazardous Area Joints 79 Resins 80 Heatshrink & Coldshrink Joints 81 Heatshrink LV Products 83 Coldshrink LV Products 86 Jointing Accessories 88 HV Jointing & Terminating 89 TYCO ELECTRONICS 11kV Heatshrink Indoor & Outdoor Terminations 90 11kV Heatshrink Indoor Accessories 94 11kV Heatshrink Outdoor Accessories 97 33kV Indoor & Outdoor Heatshrink Terminations 99 33kV Heatshrink Indoor Accessories 101 33kV Heatshrink Outdoor Accessories 103 11kV Heatshrink Joints 105 11kV Shrinkset Joints 107 11 & 33kV Coldshrink Joints 109 33kV Heatshrink Joints 110 52-72kV Heatshrink Terminations & Joints 112 11 & 33kV Heatshrink Insulation Products 113 3M 11kV Coldshrink Indoor & Outdoor Terminations 115 11 & 33kV Coldshrink Indoor & Outdoor Terminations 115 33kV Coldshrink Indoor & Outdoor Terminations 118 11 & 33kV Indoor & Outdoor Coldshrink Accessories 119 11kV Coldshrink Joints 120 33kV Coldshrink Joints 123 52-72kV Coldshrink Terminations & Joints 125 ABB 52-72kV Self Supporting Terminations & Joints 126 Separable Connectors 127 PFISTERER Inner Cone Terminations 128 Installation Tooling & Accessories 129 TYCO ELECTRONICS Separable Connectors for Type A Bushing 130 Separable Connectors for Type B Bushing 130 Separable Connectors for Type C Bushing 131 ABB Separable Connectors for Type A Bushing 133 Separable Connectors for Type B Bushing 133 Separable Connectors for Type C Bushing 134 HDC Cable Cabinets 136 Tapes, Aerosols & Accessories 137 PVC Insulating Tapes 138 Self Amalgamating, Insulating & Splicing Tapes 140 Mastic Sealing & Insulating Tapes 142 Marking & General Purpose Tapes 143 Corrosion & Protection Tapes 144 Glass Cloth & Cambric Tapes 145 Aerosol Sprays 146 Denso Products 148 Cable Laying Products 149 Cable Pulling Equipment 150 Cable Pulling Lubricants 152 Hand & Cable Cleaning Wipes 154 Cable Warning & Detection Tape 155 Cable Protection & Location Products 156 Earthing, Lightning & Surge Protection 157 Conductors 158 Conductor Fixings 161 Bonding 163 Earthing 164 Earth Rod Clamps 165 Earth Inspection Pits & Accessories 167 Earth Bars 169 Exothermic Welding 172 Surge Protection 174 Cable Transits 175 Roxtec Sealing System 176 Raychem Duct Seal 182 Tools & Equipment 183 Crimp Tools and Pumps 184 Crimp Dies Selection Tables 186 Crimp Dies 187 Cutting Tools 188 Cable Preparation Tools 189 Toolout Hire 192 Pfisterer Installation Tooling 194 Spiking Tools 194 Miscellaneous Tools 194 Gas Torch Kits & Accessories 195 Band-It Tooling 196 Trace & Underfloor Heating Systems 197 Hot Water Temperature Maintenance 198 Frost Protection for Pipes 199 Heating System for Ramps, Steps & Footpaths 200 Heating System for Gutters & Downpipes 201 Underfloor Heating Systems 202 Leak Detection & Location Systems 203 Trace & Underfloor Heating Overview 204 Cable DATA 205 LV Single Core XLPE Cables 206 LV Two & Three Core XLPE Cables 207 LV Four Core XLPE Cables 208 3.3kV Three Core XLPE Cables 208 LV & 3.3kV Three & Four Core PILC Cables 209 Multi-core & Multi-paired Cables 210 Fire Proof Cables 211 11kv XLPE Cables 212 22kV XLPE Cables 213 33kV XLPE Cables 214 11kv PILC & PICAS Cables 215 11 & 22kv Triplex Cables/ Waveform Cables 216 217
Index PART NUMBER INDEX Number Page Number Page Number Page Number Page Number Page Number Page 1251 156 332 602 010 45 376AB29 58 377AB53 61 384AA02 52 439AA61 26 1451 122 332 603 010 45 376AB30 58 377AB54 61 384AA03 52 439AA63 26 1452 122 332 604 010 44 376AB31 58 377AB55 61 384AA04 52 439AA69 26 1000CS 33 332 605 010 44 376AB32 58 377AB56 61 384AA05 52 458ET51 26 10CS 33 332 605 011 44 376AB33 58 377AB57 61 384AA06 52 458ET53 26 115P10 173 332 606 010 44 376AC01 58 377AB58 61 384LSF01 52 458ET55 26 120-CS 189 332 607 010 45 376AC02 58 377LSF01 61 384LSF03 52 458ET56 26 120CS 33 332 614 010 45 376AC03 58 377LSF02 61 384LSF04 52 458ET57 26 1402-FR B 80, 108 332 617 010 45 376AC04 58 378AB01 60 384LSF05 52 458ET59 26 1402-FR C 80, 108 332 625 010 44 376AC05 58 378AB02 60 384LSF06 52 458ET61 26 1402-FR Mix 332 625 011 44 376AC06 58 378AB03 60 385AA01 49 458ET63 26 PACK 80, 108 35CS 33 376AC07 58 378AB04 60 385AA02 49 458ET65 26 1402-XR 156 370BA10 56 376AC08 58 378AB05 60 385AA03 49 459AA51 26 1420E 156 370BA11 56 376AC09 58 378AB06 60 385AA04 49 459AA53 26 1422-XR/Id 156 370BA12 56 376AC10 58 378AB07 60 385AA05 49 459AA55 26 150CS 33 370BA13 56 376AC11 58 378AB08 60 385AA06 49 459AA56 26 150P10 173 370BA14 56 376AC12 58 378AB09 60 385AA07 49 459AA57 26 16CS 33 370BA15 56 376AC13 58 378AB29 60 385AA08 49 459AA59 26 185CS 33 370BA16 56 376AC14 58 378AB36 60 385LSF01 49 459AA61 26 1CS 33 370BA17 56 376AC15 58 378AB37 60 385LSF02 49 459AA63 26 200P10 173 370BA18 56 376AC16 58 378AB38 60 385LSF02 52 459AA69 26 240CS 33 370BA19 56 376AC17 58 378AB39 60 385LSF03 49 481AA53 25 25111-003 26 371AA01 53 376AC18 58 378AB40 60 385LSF04 49 481AA55 25 25111-005 26 371AA02 53 376AC19 58 378AB41 60 385LSF05 49 481AA56 25 25111-006 26 371AA03 53 376AC20 58 378AB42 60 385LSF06 49 481AA57 25 25111-007 26 371AA04 53 376AC21 58 378AB51 60 385LSF07 49 481AA59 25 25111-009 26 371AA05 53 376AC22 58 378AB52 60 385LSF08 49 481AA61 25 25111-011 26 371AA06 53 376AC23 58 378AB53 60 389AC03 54 481AA63 25 25111-013 26 371AA07 53 376AC24 58 378AB54 60 400CS 33 4CB185-300 85 25CS 33 371AA08 53 376AC25 58 378AB55 60 41702-53 26 4CB35-70 85 2A10-M 35 371AA09 53 376AC26 58 378AB56 60 41702-55 26 4CB50-150 85 2A100-2M 36 371AA10 53 376AC27 58 378AB57 60 41702-56 26 4CB6-50 85 2A100-M 35 371AA11 53 376AC28 58 378AB58 60 41702-57 26 4FT 6 TON 150 2A120-2M 36 371AA12 53 376AC29 58 378AB59 60 41702-59 26 500CS 33 2A120-M 35 376AB01 58 376AC30 58 378JB01 60 41702-61 26 50CS 33 2A14-M 35 376AB02 58 376AC31 58 378JB02 60 41702-63 26 5116660250 188 2A160-M 35 376AB03 58 376AC32 58 378JB03 60 41702-64 26 5116660500 188 2A19-M 35 376AB04 58 376AC33 58 378JB04 60 41702-65 26 546-004-009 129 2A200-M 35 376AB05 58 376TR06 57 378JB05 60 428ET51 26 559-215-001 129 2A24-M 35 376AB06 58 376TR07 57 378JB06 60 428ET53 26 559-215-002 129 2A3-M 35 376AB07 58 376TR08 57 378JB07 60 428ET55 26 559-224-001 129 2A30-M 35 376AB08 58 376TR09 57 378JB08 60 428ET56 26 6 TON JACK 150 2A37-M 35 376AB09 58 376TR10 57 378JB09 60 428ET57 26 630CS 33 2A48-M 35 376AB10 58 376TR11 57 378JB29 60 428ET59 26 65P10 173 2A5-M 35 376AB11 58 377AB01 61 378JB36 60 428ET61 26 6CS 33 2A60-M 35 376AB12 58 377AB02 61 378JB37 60 428ET63 26 6FT 6 TON 150 2A7-M 35 376AB13 58 377AB03 61 378JB38 60 428ET65 26 70CS 33 2A80-2M 36 376AB14 58 377AB04 61 378JB39 60 429AA51 26 7691-S4-3W 117 2A80-M 35 376AB15 58 377AB05 61 378JB40 60 429AA53 26 7692-S4-3W 117 2CS 33 376AB16 58 377AB06 61 378JB41 60 429AA55 26 7693-S4-3W 117 3 TON JACK 150 376AB17 58 377AB07 61 378JB42 60 429AA56 26 7FT 8 TON 150 300CS 33 376AB18 58 377AB08 61 378JB51 60 429AA57 26 8 TON JACK 150 305 051 051 191 376AB19 58 377AB29 61 378JB52 60 429AA59 26 800CS 33 305 063 063 191 376AB20 58 377AB36 61 378JB53 60 429AA61 26 827 668 001 128 3091-21 195 376AB21 58 377AB37 61 378JB54 60 429AA63 26 827-130-001 129 332 447 010 45 376AB22 58 377AB38 61 378JB55 60 429AA69 26 827-131-001 129 332 592 010 45 376AB23 58 377AB39 61 378JB56 60 439AA51 26 827-132-001 129 332 593 010 45 376AB24 58 377AB40 61 378JB57 60 439AA53 26 827-133-001 129 332 595 010 44 376AB25 58 377AB41 61 378JB58 60 439AA55 26 827-134-001 129 332 595 011 44 376AB26 58 377AB42 61 378JB59 60 439AA56 26 827-134-002 129 332 599 010 44 376AB27 58 377AB51 61 380AG02 54 439AA57 26 827-134-003 129 332 601 010 45 376AB28 58 377AB52 61 384AA01 52 439AA59 26 827-134-004 129 218
Index PART NUMBER INDEX Number Page Number Page Number Page Number Page Number Page Number Page 827-150-002 129 91-NBA-6 78 94-AS631-1/C 123 A1/A2EX 20S 18 AE018 72 AE605 68 827-150-003 129 91-NBA-7 78 94-AS632-1/C 123 A1/A2EX 20SS 18 AE035 72 AE611 68 827-150-004 129 92-AG611-1/C 120 94-EP610-2 117 A1/A2EX 25 18 AE036 72 AE612 68 827-150-005 129 92-AG612-1/C 120 94-EP611-2 118 A1/A2EX 32 18 AE043 72 AE613 68 827-1611-005 128 92-AG621-1/C 120 94-EP612-2 118 A1/A2EX 40 18 AE044 72 AE614 68 827-174-001 129 92-AG622-1/C 120 94-EP613-2 118 A1/A2EX 50 18 AE045 72 AE615 68 827-174-002 129 92-AG631-1/C 120 94-EP620-2 117 A1/A2EX 63 18 AE046 72 AE701 68 827-174-003 129 92-AG632-1/C 120 94-EP620-2 118 A1/A2EX 75 18 AE047 72 AE702 68 827-174-004 129 92-AS610-1/C 120 94-EP622-2 118 A1/A2EX 75S 18 AE048 72 AE703 68 8423-6 86 92-AS611-1/C 121 94-EP623-2 118 A10-M 29 AE049 72 AE704 68 8425-8 86 92-AS620-1/C 120 94-EP630-2 117 A100-2M12 31 AE050 72 AE705 68 8426-11 86 92-AS621-1/C 120 94-EP630-2 118 A100-4ESI 32 AE051 72 AE711 68 8426-9 86 92-AS623-1/C 121 94-EP632-2 118 A100-M 29 AE052 72 AE712 68 8427-12 86 92-AS624-1/C 121 94-EP633-2 118 A120-2M12 31 AE053 72 AE713 68 8427-16 86 92-AS630-1/C 120 94-EP640-2 117 A120-4ESI 32 AE060 72 AE714 68 8427-6 86 92-AS631-1/C 120 94-EP640-2 118 A120-M 29 AE111 69 AE715 68 8428-12 86 92-AS632-1/C 121 94-EP642-2 118 A14-M 29 AE112 69 APED 521B 126 8428-18 86 92-AV610-3 121 94-EP643-2 118 A160-2M12 31 AE113 69 APED 722B 126 8428-6 86 92-AV610-3/C + 94-FC-630-1/C 124 A160-4ESI 32 AE114 69 APED 722P 126 8429-12 86 PILC1 121 94-FC-631-1/C 124 A160-M 29 AE115 69 AR101 82 8429-18 86 92-AV620-3 121 94-FC-640-1/C 124 A19-M 29 AE200 tool 196 AR102 82 8429-6 86 92-AV620-3/C + 94-FP-435-3/C 124 A2 Nylon 16 9 AE201 TOOL 196 AR3 82 8429-9 86 PILC2 121 94-FP-436-3/C 124 A2 Nylon 20 9 AE311 69 AR4 82 8430-18 86 92-AV630-3 121 94-PG-620-1 A2 Nylon 25 9 AE312 69 AR5 82 8430-9 86 92-AV630-3/C + 123, 124 A2 Nylon 32 9 AE313 69 as211 68 8443-2 86 PILC3 121 95-AC641-1/1000 A2 Nylon 40 9 AE314 69 as212 68 8443-6.5 86 92-EE717-1-BSK 119 125 A2 Nylon 50 9 AE315 69 as213 68 8445-2.5 86 92-EP621-1 115 95-AC642-1/630 125 A2 Nylon 63 9 AE405 71 as214 68 8445-7.5 86 92-EP621-2 116 95-AC643-1 125 A2-M 29 AE406 71 as215 68 8447-3.2 86 92-EP623-1 115 95-EB62-2 (QTII) 125 A200-4ESI 32 AE407 71 AS221 68 8447-8 86 92-EP623-2 116 95-EB63-2 (QTII) 125 A200-M 29 AE425 71 As222 68 849-999-999 128 92-EP626-3 115 95-EP631-2 (QTIII) 125 A24-2M8 31 AE426 71 as223 68 850-11X-XXX 128 92-EP631-1 115 95CS 33 A24-M 29 AE427 71 as224 68 850-12X-XXX 128 92-EP631-2 116 96-EP722-2 125 A3-M 29 AE432 70 as225 68 850-13X-XXX 128 92-EP633-1 115 A03-M 29 A30-2M12 31 AE433 70 ASC25R1 190 850-21X-XXX 128 92-EP633-2 116 A06-M 29 A30-M 29 AE434 70 ASC25R2 190 850-22X-XXX 128 92-EP636-3 115 A1-M 29 A37-2M12 31 AE435 70 ASC40R1 190 850-23X-XXX 128 92-EP641-1 115 A1/A2 20 10 A37-4ESI 32 AE436 70 ASC40R2 190 850-31X-XXX 128 92-EP641-2 116 A1/A2 20 Lsf 10 A37-M 29 AE452 70 AU230-130D 187 850-32X-XXX 128 92-EP643-1 115 A1/A2 20S 10 A48-2M12 31 AE453 70 AU520-130C 187 850-33X-XXX 128 92-EP643-2 116 A1/A2 20S Lsf 10 A48-4ESI 32 AE454 70 B-TC051 188 850-350-XXX 128 92-EP646-3 115 A1/A2 20SS 10 A48-M 29 AE455 70 B-TC095 188 859-999-999 128 92-EP653-1 115 A1/A2 20Ss Lsf 10 A5-M 29 AE456 70 B135 173 869-999-999 128 92-EP653-2 116 A1/A2 25 10 A60-2M12 31 AE465 71 B135-C 185 869-999-999 128 92-EP656-1 115 A1/A2 25 Lsf 10 A60-4ESI 32 AE466 71 B35-45 185 870-01X-XXX 128 92-EP656-3 115 A1/A2 32 10 A60-M 29 AE467 71 B51 185 870-02X-XXX 128 92-FG411-3/C 122 A1/A2 32 Lsf 10 A7-M 29 AE475 71 B70M-P24 185 870-11X-XXX 128 92-FG421-3/C 122 A1/A2 40 10 A80-2M12 31 AE476 71 BA205 159 870-12X-XXX 128 92-FG431-3/C 122 A1/A2 40 Lsf 10 A80-4ESI 32 AE477 71 BA210 159 870-13X-XXX 128 92-PG610-1 122 A1/A2 50 10 A80-M 29 AE505 71 BA225 159 870-21X-XXX 128 92-PG620-1 122 A1/A2 50 Lsf 10 AA120-M 34 AE506 71 BA230 159 870-22X-XXX 128 92-PG630-1 122 A1/A2 50S 10 AA150-M 34 AE507 71 BA231 159 870-23X-XXX 128 92EE717-1 119 A1/A2 50S Lsf 10 AA16-M 34 AE565 71 BANDF11 69 870-31X-XXX 128 94-AP-630-1/C 123 A1/A2 63 10 AA185-M 34 AE566 71 BANDF12 69 870-32X-XXX 128 94-AP-631-1/C 123 A1/A2 63 Lsf 10 AA240-M 34 AE567 71 BANDF13 69 870-33X-XXX 128 94-AP-640-1/C 123 A1/A2 63S 10 AA25-M 34 ae575 71 BANDF14 69 90P10 173 94-AP230-3/C 123 A1/A2 63S Lsf 10 AA300-34-M 34 ae576 71 BANDF15 69 91-NBA-0 78 94-AP231-3/C 123 A1/A2 75 10 AA35-M 34 ae577 71 BANDF21 69 91-NBA-1 78 94-AP635-1/C 124 A1/A2 75 Lsf 10 AA50-M 34 AE601 68 BANDF22 69 91-NBA-3 78 94-AP636-1/C 124 A1/A2 75S 10 AA70-M 34 AE602 68 BANDF23 69 91-NBA-4 78 94-AS620-1/C 123 A1/A2 75S Lsf 10 AA95-M 34 AE603 68 BANDF24 69 91-NBA-5 78 94-AS630-1/C 123 A1/A2EX 20 18 AE010 72 AE604 68 BANDF25 69 219
Index PART NUMBER INDEX Number Page Number Page Number Page Number Page Number Page Number Page BANDF26 69 BN505 163 BT630C8B4 32 BU2 - SMOE 61760 CA240-2M 36 CP015 161 BANDF27 69 BN510 163 BT6C 30 107 CA25-2M 36 CP020 161 BARR-A-20 22 BPTM100/40-A/U 113 BT70C 30 BU2 - SMOE 61760 CA300-2M 36 CP025 161 BARR-A-25 22 BPTM120/50-A/U 113 BT800C 30 107 CA35-2M 36 CP030 161 BARR-A-32 22 BPTM15/6-A/U 113 BT800C12B2 31 BU3 - SMOE 61798 CA50-2M 36 CP035 161 BARR-A-40 22 BPTM175/70-A/U 113 BT800C8B4 32 107 CA70-2M 36 CP040 161 BARR-A-50 22 BPTM30/12-A/U 113 BT95C 30 BU3 - SMOE 61798 CA95-2M 36 CP045 161 BARR-A-63 22 BPTM50/20-A/U 113 BTH120CS 37 107 CASS 95/300 189 CP050 161 BARR-A-75 22 BPTM75/30-A/U 113 BTH150CS 37 Bw20 11 CB016 159 CP065 161 BARR-W-20 23 BSMB-10/35 42 BTH16CS 37 Bw20 Lsf 11 CB025 159 CP110-H 161 BARR-W-20S 23 BSMB-120-300 42 BTH185CS 37 Bw20s 11 CB035 159 CP120-H 161 BARR-W-25 23 BSMB-185/400 42 BTH240CS 37 Bw20s Lsf 11 CB050-FU 159 CP210-H 161 BARR-W-32 23 BSMB-185/400-500 BTH25CS 37 Bw25 11 CB070 159 CP220-H 161 BARR-W-40 23 42 BTH300CS 37 Bw25 Lsf 11 CB095 159 CP240-H 161 BARR-W-50 23 BSMB-185/400-630 BTH35CS 37 Bw32 11 CB120 159 CP260-H 161 BARR-W-63 23 42 BTH400CS 37 Bw32 Lsf 11 CB240 159 CR105 165 BARR-W-75 23 BSMB-25/95 42 BTH500CS 37 Bw40 11 CB400-FU 159 CR110 165 BARR-X-20 24 BSMB-25/95-95/240 BTH50CS 37 Bw40 Lsf 11 CC016 160 CR115 165 BARR-X-20S 24 42 BTH630CS 37 Bw50 11 CC025 160 CR205 165 BARR-X-25 24 BSMB-35/150 42 BTH70CS 37 Bw50 Lsf 11 CC035 160 CR215 165 BARR-X-32 24 BSMB-500 42 BTH95CS 37 Bw63 11 CC050 160 Cr305 166 BARR-X-40 24 BSMB-500/630 42 BTHW120C 35 Bw63 Lsf 11 CC070 160 Cr320 166 BARR-X-50 24 BSMB-630 42 BTHW120C12D 36 Bw75 11 CC095 160 CR515 165 BARR-X-63 24 BSMB-800 42 BTHW150C 35 Bw75 Lsf 11 CC120-FU 160 CR700 166 BARR-X-75 24 BSMB-95/240 42 BTHW150C12D 36 Bw75s 11 CC240 160 CR705 166 BBIT100/40-A/U 114 BSMB-95/240- BTHW16C 35 Bw75s Lsf 11 CC400-FU 160 CR730 166 BBIT150/60-A/U 114 185/400 42 BTHW185C 35 C001 TOOL 196 CE0 50 CRIMPING TOOL 155 BBIT175/80-A/U 114 BSR700 191 BTHW185C12D 36 c075 tool 196 CE00 50 CRSM107/29 84 BBIT25/10-A/U 114 BSR700 SPARE BTHW240C 35 C201 70 CE1 50 CRSM143/36 84 BBIT40/16-A/U 114 BLADE 191 BTHW240C12D 36 C202 70 CE10 51 CRSM198/55 84 BBIT65/25-A/U 114 BT1000C 30 BTHW25C 35 C203 70 CE11 51 CRSM250/98 84 BCM 173 BT1000C8B4 32 BTHW300C 35 C204 70 CE12 51 CRSM34/10 84 BD030 159 BT10C 30 BTHW300C16D 36 C205 70 CE13 51 CRSM53/13 84 BD035 159 BT120C 30 BTHW35C 35 C206 70 CE14 51 CRSM84/20 84 BET120C 38 BT120C8B2 31 BTHW400C 35 C251 70 CE2 50 CS 610-3 121 BET35C 38 BT120C8B4 32 BTHW400C16D 36 C252 70 CE3 50 CS 620-3 121 BET60C 38 BT150C 30 BTHW500C 35 C253 70 CE4 50 CS 630-3 121 BF-M 28 BT150C12B2 31 BTHW500C16D 36 C254 70 CE5 50 CS21 151 BF-P 28 BT150C8B4 32 BTHW50C 35 C255 70 CE6 50 CS22 151 BF-PP 28 BT16C 30 BTHW630C16D 36 C256 70 CE7 50 CS23 151 BF-U 28 BT185C 30 BTHW70C 35 C370BA01 54 CE8 50 CS24 151 BFC 173 BT185C12B2 31 BTHW70C12D 36 C370BA02 54 CE9 51 CS25 151 BLMT-120/300 41 BT185C8B4 32 BTHW95C 35 C370BA03 54 CEH10 51 CS26 151 BLMT-185/400 41 BT1C 30 BTHW95C12D 36 C370BA04 54 CEH11 51 CS27 151 BLMT-25/95 41 BT240C 30 BTN10-M 29 C370BA05 54 CEH12 51 CS28 151 BLMT-35/150 41 BT240C12B2 31 BTN120-M 29 C370BA06 54 CEH13 51 CS29 151 BLMT-500/630 41 BT240C8B4 32 BTN150-M 29 C370BA07 54 CEH14 51 CS31 151 BLMT-800 41 BT25C 30 BTN16-M 29 C370BA08 54 CEH9 51 CS32 151 BLMT-95/240 41 BT2C 30 BTN185-M 29 C370BA09 54 CENTRITILE 150 156 CS33 151 BM185B 40 BT300C 30 BTN240-M 29 C402 70 CENTRITILE 200 156 CS34 151 BM185M 39 BT300C12B2 31 BTN25-M 29 C403 70 CES4 95 CS35 151 BM300B 40 BT300C8B4 32 BTN300-M 29 C404 70 CES4 102 CS36 151 BM300M 39 BT35C 30 BTN35-M 29 C405 70 CES5 95 CS37 151 BM400B 40 BT400C 30 BTN50-M 29 C406 70 CES5 102 CS38 151 BM95B 40 BT400C12B2 31 BTN70-M 29 C452 70 CG270 164 CS39 151 BM95M 39 BT400C8B4 32 BTN95-M 29 C453 70 Cm005 168 CSCAK/1 87 BN005 163 BT500C 30 BTW1000C 35 C454 70 CM015 168 CSCAK/2 87 BN010 163 BT500C12B2 31 BTW630C 35 C455 70 CM015-PM 168 CSCAK/3 87 BN105 163 BT500C8B4 32 BTW800C 35 C456 70 CM025 167 CSCAK/4 87 BN115 163 BT50C 30 BU1 - SMOE 61745 107 CA120-2M 36 CM025-PM 167 CSCAK/5 87 BN175 163 BT630C 30 BU1 - SMOE 61745107 CA150-2M 36 CN005 162 CSE-A 12250-01 133 BN176 163 BT630C12B2 31 CA185-2M 36 CN105-H 162 CSE-A 12250-02 133 220
Index PART NUMBER INDEX Number Page Number Page Number Page Number Page Number Page Number Page CSE-A 12400-01 133 CSJA-36E/1XU- DUXSEAL 173 EAKT1521 98 ECKJ-0021 81 EPKT17A3MOH2 93 CSE-A 12400-02 133 1XU-M3 109 E1W20 15 EAKT1524 104 ECKJ-0140 81 EPKT17A3MOH4 93 CSE-A 12630-01 134 CSS-A 12250-01 133 E1W20S 15 EAKT1605 94 ECKJ-0141 81 EPKT17A3XIH2 92 CSE-A 12630-01 R CSS-A 12250-02 133 E1W20SS 15 EAKT1605 101 ECKJ-0142 81 EPKT17A3XIH4 92 135 CSS-A 24250-01 133 E1W25 15 EAKT1606 94 ECKJ-0143 81 EPKT17A3XOH2 93 CSE-A 12630-01 RA CSS-A 24250-02 133 E1W32 15 EAKT1606 101 ECKJ-0144 81 EPKT17A3XOH4 93 135 CT005-H 162 E1W40 15 EAKT1608 94 ECW-H3D 184 EPKT17B3MIH2 92 CSE-A 12630-02 134 CT105-H 162 E1W50 15 EAKT1608 101 ED22AD 187 EPKT17B3MIH4 92 CSE-A 12630-02 S CT110-H 162 E1W50S 15 EAKT1636 97 EDNX-C 187 EPKT17B3MOH2 93 135 CT115-H 162 E1W63 15 EAKT1637 97 EDP-C 187 EPKT17B3MOH4 93 CSE-A 12630-02 SB cw20 12 E1W63S 15 EAKT1637 103 ehvs-5221 112 EPKT17B3XIH2 92 135 cw20 lsf 12 E1W75 15 EAKT1638 97 ehvs-72 112 EPKT17B3XIH4 92 CSE-A 12630-02 TB cw20s 12 E1W75S 15 EAKT1638 103 EP10 ELECTRIC EPKT17B3XOH2 93 135 cw20s lsf 12 E1WF20 19 EAKT1641 97 PUMP 185 EPKT17B3XOH4 93 CSE-A 12630-03 134 cw20ss 12 E1WF20S 19 EAKT1642 97 EPKJ 17A-1HL-1HL EPKT17C3MIH2 92 CSE-A 12630-03 T cw20ss lsf 12 E1WF20SS 19 EAKT1642 97 106 EPKT17C3MIH4 92 135 cw25 12 E1WF25 19 EAKT1642 103 EPKJ 17A-1XU-1HL EPKT17C3MOH2 93 CSE-A 21630-03 TB cw25 lsf 12 E1WF32 19 EAKT1643 97 106 EPKT17C3MOH4 93 135 cw32 12 E1WF40 19 EAKT1643 97 EPKJ 17A-1XU-3XU EPKT17C3XIH2 92 CSE-A 24250-01 133 cw32 lsf 12 E1WF50 19 EAKT1643 103 106 EPKT17C3XIH4 92 CSE-A 24250-02 133 cw40 12 E1WF50S 19 EAKT1644 97 EPKJ 17B-1HL-1HL EPKT17C3XOH2 93 CSE-A 24400-01 133 cw40 lsf 12 E1WF63 19 EAKT1644 103 106 EPKT17C3XOH4 93 CSE-A 24400-02 133 cw50 12 E1WF63S 19 EAKT1645 103 EPKJ 17B-1XU-1HL EPKT17D3MIH2 92 CSE-A 24630-01 134 cw50 lsf 12 E1WF75 19 EAKT1655 95 106 EPKT17D3MIH4 92 CSE-A 24630-01 S cw50s 12 E1WF75S 19 EAKT1655 97 EPKJ 17B-1XU-3XU EPKT17D3MOH2 93 135 cw50s lsf 12 E1WLSF20 15 EAKT1656 95 106 EPKT17D3MOH4 93 CSE-A 24630-01 SB cw63 12 E1WLSF20S 15 EAKT1656 97 EPKJ 17C-1HL-1HL EPKT17D3XIH2 92 135 cw63 lsf 12 E1WLSF20SS 15 EAKT1656 102 106 EPKT17D3XIH4 92 CSE-A 24630-02 134 cw75 12 E1WLSF25 15 EAKT1656 103 EPKJ 17C-1XU-3XU EPKT17D3XOH2 93 CSE-A 24630-02 T 135 cw75 lsf 12 E1WLSF32 15 EAKT1657 95 106 EPKT17D3XOH4 93 CSE-A 24630-02 TB cw85 12 E1WLSF40 15 EAKT1657 97 EPKJ 17D-1HL-1HL EPKT36C1XI 99 135 cw85 lsf 12 E1WLSF50 15 EAKT1657 102 106 EPKT36C1XO 100 CSE-A 24630-03 134 CWCIEL20 16 E1WLSF50S 15 EAKT1657 103 EPKJ 17D-1XU-1HL EPKT36C3XIH2 99 CSE-A 24630-03 T CWCIEL20S 16 E1WLSF63 15 EAKT1658 95 106 EPKT36C3XIH4 99 135 CWCIEL25 16 E1WLSF63S 15 EAKT1658 97 EPKJ 17D-1XU-3XU EPKT36C3XOH4 100 CSE-A 24630-03 TB CWCIEL32 16 E1WLSF75 15 EAKT1658 102 106 EPKT36D1XI 99 135 CWCIEL40 16 E1WLSF75S 15 EAKT1658 103 EPKJ 36A-1HL-1HL EPKT36D1XO 100 CSE-A 36400-01 133 CWCIEL50 16 E1WXL20 21 EAKT1659 102 111 EPKT36D3XIH2 99 CSE-A 36400-02 133 CWCIEL63 16 E1WXL20S 21 EAKT1659 103 EPKJ 36A-1XU-1HL EPKT36D3XIH4 99 CSE-A 36630-01 134 CWCIEL75 16 E1WXL20SS 21 EAKT1669 95 111 EPKT36D3XOH4 100 CSE-A 36630-01 SB CWCIEL85 16 E1WXL25 21 EAKT1669 98 EPKJ 36A-3XU- EPKT36E1XI 99 135 CX005-H 162 E1WXL32 21 EAKT1670 95 3XU-W 111 EPKT36E1XO 100 CSE-A 36630-02 134 CX105-H 162 E1WXL40 21 EAKT1670 98 EPKJ 36B-1HL- EPKT36E3XIH2 99 CSE-A 36630-02 TB CX20 14 E1WXL50 21 EAKT1671 95 1HL 111 EPKT36E3XIH4 99 135 CX20S 14 E1WXL50S 21 EAKT1671 98, 104 EPKJ 36B-1XU- EPKT36E3XOH4 100 CSE-A 36630-03 134 CX20SS 14 E1WXL63 21 EAKT1672 95 1HL 111 EPKT36F1XI 99 CSJA-12B/1XU-1XU-M CX25 14 E1WXL63S 21 EAKT1672 98, 104 EPKJ 36B-3XU- EPKT36F1XO 100 109 CX32 14 E1WXL75 21 EC-1 87 3XU-W 111 EPPA-045-1 94 CSJA-12C/1XU-1XU-M CX40 14 E1WXL75S 21 EC-2 87 EPKJ 36C-1HL- EPPA-045-1 101 109 CX50 14 E1XF20 20 EC-3 87 1HL 111 EPPA-045-2 94 CSJA-12D/1XU-1XU-M CX63 14 E1XF20S 20 EC-4 87 EPKJ 36C-3XU- EPPA-045-2 101 109 CX75 14 E1XF20SS 20 EC18-36 85 3XU-W 111 EPPA-047-xx/XX 46 CSJA-12E/1XU- D-640 152 E1XF25 20 EC28-50 85 EPKJ 36D-1HL- EPPA-047-xx/XX- 1XU-M1 109 DENSO MASTIC 148 E1XF32 20 EC38-70 85 1HL 111 yy/yy 46 CSJA-12E/1XU- DENSO PASTE 148 E1XF40 20 EC4-9 85 EPKJ 36D-1XU- EPPA-051-xx/XX 46 1XU-M2 109 DENSO TAPE 100 148 E1XF50 20 EC55-95 85 1HL 111 EPPA-052-xx/XX 46 CSJA-36D/1XU- DENSO TAPE 50 148 E1XF50S 20 EC70-110 85 EPKT 17C-1XU- EPPA-054-xx/XX 46 1XU-M 109 DENSO TAPE 75 148 E1XF63 20 EC8-18 85 1HL 106 ESP240D1 174 CSJA-36E/1XU- DENSOFIL 148 E1XF63S 20 ECKJ-0017 81 EPKT 36C-1XU- ESP415D1 174 1XU-M1 109 DETECTAMESH 155 E1XF75 20 ECKJ-0018 81 1HL 111 ESP415D1/LCD 174 CSJA-36E/1XU- DLA1 Series 98, 104 E1XF75S 20 ECKJ-0019 81 EPKT17A3MIH2 92 ESP415D1R 174 1XU-M2 109 DTS200 164 E7512-0160 182 ECKJ-0020 81 EPKT17A3MIH4 92 ESP415D1R/LCD 174 221
Index PART NUMBER INDEX Number Page Number Page Number Page Number Page Number Page Number Page ESP415M2 174 FHB06X20 62 GE21 180 HT76.2-38 83 JST95 75 L100-M 33 ESP415M4 174 FHB06X30 62 GE41 180 HT9.5-4.8 83 Jt250 154 L10PIN 31 EXRM-0607 189 FHB08X25 62 GE42 180 HTC-D72 154 JT400 154 L120-M 33 EXRM-0947 189 FHB08X30 62 GE43 180 HV1S-05 113 JTALLOW 88 L120PIN 31 EXRM-0969-39 FHB08X40 62 GE44 180 HV1S-10 113 JTS 88 L14-M 33 98, 104 FHB10X25 62 GE45 180 HV1S-TOOLS-01 113 JX-52 126 L150PIN 31 EXRM-1004 189 FHB10X30 62 GE46 180 HVBT-12-A 113 JX-52 126 L160-M 33 F380AH19 FHB10X40 62 GE61 180 HVBT-14-A 113 JX-72 126 L16PIN 31 50, 51, 52, 55, 56 FHB10X50 62 GE62 180 HVBT-15-A 113 K502 TOOL 196 L185PIN 31 F380AH23 FHB12X35 62 GE63 180 HVBT-16-A 113 KA 250 136 L19-M 33 50, 51, 52, 55, 56 FHB12X40 62 GE64 180 HVIA-STRIPPER KE0128 67 L2-M 33 F380AH29 FHB12X50 62 GE65 180 35-90 191 KE0138 67 L200-M 33 50, 51, 52, 55, 56 FHB12X70 62 GE66 180 HVIA-STRIPPER KE0148 67 L24-M 33 F380AH41 FHN06 62 GE81 180 75-150 191 KE0158 67 L240PIN 31 50, 51, 52, 55, 56 FHN08 62 GE82 180 HVRM 194 KE0168 67 L25PIN 31 F380AJ29 FHN10 62 GE83 180 IHVT-5212 112 KE0178 67 L3-M 33 50, 51, 52, 55, 56 FHN12 62 GE84 180 IHVT-72 112 KE0188 67 L30-M 33 F380AJ39 Fs005 168 GF-M 28 IN005 170 KE0228 67 L300PIN 31 50, 51, 52, 55, 56 FSW06 62 GF-P 28 IP 250 136 KE0238 67 L35PIN 31 F71003-02 88 FSW08 62 GF-PP 28 IP 630 134 KE0248 67 L37-M 33 FBB06X20 62 FSW10 62 GF-U 28 IT-1000-023 194 KE0258 67 L400PIN 31 FBB06X30 62 FSW12 62 GHM2X1 177 IXSU-F-3111 90 KE0268 67 L48-M 33 FBB08X25 62 FTR10 61 GHM2X2 177 IXSU-F-3121 90 KE0278 67 L5-M 33 FBB08X30 62 FTR12 61 GHM4X1 177 IXSU-F-3131 90 KE0328 67 L50PIN 31 FBB08X40 62 G101-123 114 GHM4X2 177 IXSU-F-3141 90 KE0338 67 L60-M 33 FBB10X25 62 G2X1 176 GUROFLEX 114 IXSU-F-3151 90 KE0348 67 L7-M 33 FBB10X30 62 G2X2 176 guroflex 5 LITRE 114 IXSU-F-3161 90 KE0358 67 L70PIN 31 FBB10X40 62 g38a 114 GWCX 95 IXSU-F-3301 90 KE0368 67 L80-M 33 FBB10X50 62 G4X1 176 GWCY 95 IXSU-F-3304 90 KE0378 67 L95PIN 31 FBB12X35 62 G4X2 176 H3366 195 IXSU-F-3311 90 KE0388 67 LA11 87 FBB12X40 62 G6X1 176 HAB 25 (3359) 195 IXSU-F-3314 90 KE0428 67 LC1 82 FBB12X50 62 G6X2 176 HAB32-15 (3349) 195 IXSU-F-3321 90 KE0438 67 LC2 82 FBB12X70 62 G6X3 176 HCPK4 173 IXSU-F-3324 90 KE0448 67 LC3 82 FBN06 62 g83m 114 HDC-A 12250 136 IXSU-F-3331 90 KE0458 67 LC4 82 FBN08 62 G8X1 176 HDC-A 12630-01 136 IXSU-F-3334 90 KE0468 67 LC5 82 FBN10 62 G8X2 176 HDC-A 12630-01 136 IXSU-F-3341 90 KE0478 67 LC6 82 FBN12 62 G8X3 176 HDC-A 12630-01 136 IXSU-F-3344 90 KE1128 67 LHA 191 FBSW06 62 G8X4 176 HDC-A 12630-02 136 J-640 152 KE1138 67 LHM1R30/45 190 FBSW08 62 GACW20 13 HDC-A 12630-02 136 J70131-02 88 KE1148 67 Lk004 170 FBSW10 62 GACW20LSF 13 HDC-A 12630-02 136 JACK PLINTH 150 KE1158 67 Lk205 170 FBSW12 62 GACW20S 13 HDC-A 12630-03 136 JAP 88 KE1168 67 LK207-10 170 FBW06 62 GACW20SLSF 13 HDC-A 12630-03 136 JBR-16 77 KE1178 67 LK207-12 170 FBW08 62 GACW25 13 HDC-A 12630-03 136 JBR-185 77 KE1188 67 LK207-16 170 FBW10 62 GACW25LSF 13 HDC-A 24250 136 JBR-300 77 KE1328 67 LK207-20 170 FBW12 62 GACW32 13 HDCW140/40 85 JBR-35 77 KE1338 67 LK207-24 170 FCNL06 62 GACW32LSF 13 HDCW55/15 85 JBR-6 77 KE1348 67 lk207-28 170 FCNL08 62 GACW40 13 HDCW80/25 85 JBR-95 77 KE1358 67 LK207-4 170 FCNL10 62 GACW40LSF 13 HM005 168 JEM 80, 108 KE1368 67 LK207-6 170 FCNL12 62 GACW50 13 HM010 168 JP1 39 KE1378 67 LK207-8 170 FCNN06 62 GACW50LSF 13 hpd72 154 JP1 40 KE1388 67 LK243-10 169 FCNN08 62 GACW50S 13 HT-TC051 188 JPS 88 KE9229 196 LK243-12 169 FCNN10 62 GACW50SLSF 13 HT-TC0851 188 JR391 88 KMS 189 LK243-16 169 FCNN12 62 GACW63 13 HT101-51 83 JS-52 126 KMS BLADE 189 LK243-20 169 FCNS06 62 GACW63LSF 13 HT12.7-6.4 83 JS-72 126 KT4 188 LK243-24 169 FCNS08 62 GACW75 13 HT131 184 JSA 126 KT45 188 LK243-28 169 FCNS10 62 GACW75LSF 13 HT19-9.5 83 JSSC 80, 108 KT5 188 LK243-4 169 FCNS12 62 GACWCIEL32 17 HT25.4-12.7 83 JST16 75 L-4-18ID-9-C 65 LK243-6 169 FFW06 62 GACWCIEL40 17 HT38-19 83 JST185 75 L-7-50ID-9-C 65 LK243-8 169 FFW08 62 GACWCIEL50 17 HT45-E 184 JST300 75 L03-M 33 LK245-10 169 FFW10 62 GACWCIEL63 17 HT51 184 JST35 75 L06-M 33 LK245-12 169 FFW12 62 GACWCIEL75 17 HT51-25.4 83 JST400 75 L1-M 33 LK245-16 169 FGUN 173 GAP-APED 126 HT6.4-3.2 83 JST6 75 L10-M 33 LK245-20 169 222
Index PART NUMBER INDEX Number Page Number Page Number Page Number Page Number Page Number Page LK245-24 169 MK20-C 187 MWTM95/29 83 PKH70 66 RF-P 28 RSTI-5828 131 LK245-28 169 MK22-C 187 MXSU-3111 105 PL03-M 28 RF-PP 28 RSTI-5829 131 LK245-4 169 MK25-C 187 MXSU-3121 105 PL06-M 28 RF-U 28 RSTI-5830 131 LK245-6 169 MK28-C 187 MXSU-3131 105 PL1-M 28 RHC131 184 RSTI-5831 131 LK245-8 169 MK32-C 187 MXSU-3132 105 PNX-C 187 RHU-520 184 RSTI-5832 131 LO41 87 MK38-3D 187 MXSU-3141 105 PO 7000 185 RKM145 126 RSTI-5833 131 LO42 87 MK42-3D 187 MXSU-3151 105 POH12 66 RM120WOC 178 RSTI-5834 131 LR120-M 32 MK44-3D 187 MXSU-3161 105 POH18 66 RM15 178 RSTI-5835 131 LR150-M 32 MK52-520 187 MXSU-3171 105 POH30 66 RM15/0 179 RSTI-5846 131 LR185-M 32 MK8-C 187 MXSU-3181 105 POH7 66 RM20 178 RSTI-5847 131 LR240-M 32 MO16 117 MXSU-6111 110 POK10 66 RM20/0 179 RSTI-5848 131 LR300-M 32 MOULD 1 173 MXSU-6121 110 PP-C 187 RM30 178 RSTI-5849 131 LR50-M 32 MOULD 2 173 MXSU-6131 110 PSSK 1 136 RM30/0 179 RSTI-5851 131 LR70-M 32 MOULD 3 173 MXSU-6141 110 PSSK 2 136 RM40 178 RSTI-5851 131 LR95-M 32 MR2016 25 MXSU-6151 110 PSZ2 177 RM40/0 179 RSTI-5851 131 LSZ2 177 MR2520 25 MXSU-6161 110 PSZ4 177 RM60 178 RSTI-5851 131 LSZ4 177 MR3220 25 MXSU-6171 110 PSZ6 177 RM60/0 179 RSTI-5852 131 LSZ6 177 MR3225 25 Nn640 153 PSZ8 177 RM60WOC 178 RSTI-5853 131 LSZ8 177 MR4025 25 OCP2 Series 98, 104 PT004 167 RM90WOC 178 RSTI-5853 131 LVET120 38 MR4032 25 OHVT-5212 112 Pt005 167 RS100 178 RSTI-5854 131 LVET185 38 MR5032 25 OHVT-72 112 PT006 167 RS125 178 RSTI-5855 131 LVET300 38 MR5040 25 OHVT-72-L 112 PT007 167 RS25 178 RSTI-6811 132 LVI-1/2-PT 78 MR6350 25 OXSU-F-3111 91 Pt205 167 RS31 178 RSTI-6812 132 LVI-1/3-PT 78 MT120-TD 37 OXSU-F-3121 91 PTT-TLHD-05 153 RS43 178 RSTI-6813 132 LVI-1/4-PT 78 MT150-TD 37 OXSU-F-3131 91 PTT-TLMULTI-05 153 RS50 178 RSTI-6814 132 LVI-1/5-PT 78 MT16 116 OXSU-F-3141 91 PUADP 187 RS68 178 RSTI-6815 132 LVI-1/6-PT 78 MT16-TD 37 OXSU-F-3151 91 PZ02 66 RS75 178 RSTI-6816 132 LVI-3/2-C 79 MT185-TD 37 OXSU-F-3161 91 PZ1 66 RSES-5201 130 RSTI-6817 132 LVI-3/3-C 79 MT240-TD 37 OXSU-F-3301 91 PZ2 66 RSES-5202 130 RSTI-6818 132 LVI-3/4 79 MT25-TD 37 OXSU-F-3304 91 PZ3 66 RSES-5203 130 RSTI-6851 132 LVI-3/5 79 MT300-TD 37 OXSU-F-3311 91 R100 177 RSES-5205 130 RSTI-6852 132 LVI-3/6 79 MT35-TD 37 OXSU-F-3314 91 R125 177 RSES-5217 130 RSTI-6853 132 LVI-3/7 79 MT400-TD 37 OXSU-F-3321 91 R127 177 RSES-5219 130 RSTI-6854 132 LVI-3/8 79 MT50-TD 37 OXSU-F-3324 91 R150 177 RSES-5224 130 RSTI-CC-5810 131 LVRM6 194 MT500-TD 37 OXSU-F-3331 91 R200 177 RSES-6452 130 RSTI-CC-5811 131 LVRM9 194 MT630-TD 37 OXSU-F-3334 91 RB005 164 RSES-6453 130 RSTI-CC-5812 131 m503 tool 196 MT70-TD 37 OXSU-F-3341 91 RB205-FU 164 RSES-6455 130 RSTI-CC-5813 131 MA 250 136 MT95-TD 37 OXSU-F-3344 91 RB210 164 RSRB4022 RSTI-CC-5814 131 MA-3D 187 MTMA10-GC 34 P-H 187 RB215 164 (EAKT1505) 96 RSTI-CC-5815 131 MA-520 187 MTMA120-GC 34 PA-3D 187 RB220-FU 164 RSRB4024 RSTI-CC-5826 131 MA-C 187 MTMA150-GC 34 PA-520 187 RB225 164 (EAKT1506) 96 RSTI-CC-5827 131 MB63 119 MTMA16-GC 34 PA-C 187 RB235 164 RSRB4026 RSTI-CC-5828 131 MCB25 39 MTMA185-GC 34 PACK-A 173 RCAB-C-421 96 (EAKT1507) 96 RSTI-CC-5829 131 MCB50 39 MTMA240-GC 34 PC 630-3 134 RCT SPARE RSRB4042 RSTI-CC-5830 131 MCB70 39 MTMA25-GC 34 PC 630-3L 134 CHAIN 189 (EAKT1508) 96 RSTI-CC-5831 131 ME-3D 187 MTMA35-GC 34 PC 630/250 136 RCT155 189 RSRB4044 RSTI-CC-5832 131 ME-3D 187 MTMA50-GC 34 PCL 180 RDSS-100 182 (EAKT1509) 96 RSTI-CC-5833 131 ME-C 187 MTMA70-GC 34 PCS 180 RDSS-125 182 RSRB4046 RSTI-CC-5834 131 ME-C 187 MTMA95-GC 34 PE010 164 RDSS-150 182 (EAKT1510) 96 RSTI-CC-5835 131 MEH V0 122 MTMAD300-GC 34 PE020 164 RDSS-45 182 RSSS-5201 130 RSTI-CC-5846 131 MEH V1 122 MWTM10/3 83 PE110 164 RDSS-60 182 RSSS-5202 130 RSTI-CC-5847 131 MEH V2 122 MWTM115/34 83 PE120 164 RDSS-75 182 RSSS-5203 130 RSTI-CC-5848 131 MEH V3 122 MWTM140/42 83 PEC10 61 RDSS-AD-210 182 RSTI-CC-5849 131 RSSS-5205 130 MEH V4 122 MWTM16/5 83 RSTI-CC-5851 131 PEC12 61 RDSS-CLIP-100 182 RSSS-5217 130 MJ4-MJ5 173 RSTI-CC-5851 131 MWTM160/50 83 PFISTERER TOOL 129 RDSS-CLIP-125 182 RSSS-5219 130 RSTI-CC-5851 131 MK-520 187 MWTM180/60 83 PFISTERER TOOL 194 RDSS-CLIP-150 182 RSTI-5811 131 RSTI-CC-5851 131 MK-520 187 MWTM25/8 83 PG2-HTA 190 RDSS-CLIP-45 182 RSTI-5812 131 RSTI-CC-5852 131 MK10C 187 MWTM35/12 83 PG3-HTA 190 RDSS-CLIP-75 182 RSTI-5813 131 RSTI-CC-5853 131 MK12-C 187 MWTM50/16 83 PG4-HTA 190 RDSS-IT-16 182 RSTI-5814 131 RSTI-CC-5853 131 MK14-C 187 MWTM63/19 83 PIU-APED 126 RE-APED-M 126 RSTI-5815 131 RSTI-CC-5854 131 MK16-C 187 MWTM75/22 83 PJ-640 152 RE-APED-T 126 RSTI-5826 131 RSTI-CC-5855 131 MK18-C 187 MWTM85/25 83 PKH110 66 RF-M 28 RSTI-5827 131 223
Index PART NUMBER INDEX Number Page Number Page Number Page Number Page Number Page Number Page RSTI-CC-6811 132 Scotch35br 138 ST16C 30 TBJ-6 76 TSL1 180 VETB33-OHUTB 43 RSTI-CC-6812 132 Scotch35gr 138 ST25C 30 TBJ-70 76 TSL2 180 VETB37-OHUTB 43 RSTI-CC-6813 132 SCOTCH35OR 138 ST35C 30 TBJ-120-HDI 76 TT2352/1 190 VTPB21-UTB 43 RSTI-CC-6814 132 Scotch35re 138 ST50C 30 TBJ-16-HDI 76 TT2352/2 190 VTPB27-UTB 43 RSTI-CC-6815 132 SCOTCH35VI 138 ST70C 30 TBJ-185-HDI 76 TY232M 64 VTPC28-UTB 43 RSTI-CC-6816 132 Scotch35wh 138 STAINLESS STEEL TBJ-300-HDI 76 TY232MX 64 VTPC36-UTB 43 RSTI-CC-6817 132 Scotch35ye 138 CRIMPS 155 TBJ-35-HDI 76 TY23M 64 WAVELAY 155 RSTI-CC-6818 132 Scotch50-101 144 STM1-FU 173 TBJ-6-HDI 76 TY23MX 64 WBX D4 174 RSTI-CC-6821 132 Scotch50-152 144 SW1B10 55 TBJ-70-HDI 76 TY244M 64 WBX D8 174 RSTI-CC-6822 132 Scotch50-25 144 SW1B11 55 TC 120 188 TY244MX 64 WBX M2 174 RSTI-CC-6823 132 Scotch50-50 144 SW1B12 55 TC030 158 TY24M 64 WBX M4 174 RSTI-CC-6824 132 Scotch51-101 144 SW1B2 55 TC040 158 TY24MX 64 WCSM110/30 84 RSTI-CC-6825 132 Scotch51-152 144 SW1B3 55 TC065 158 TY253M 64 WCSM12/3 84 RSTI-CC-6826 132 Scotch51-25 144 SW1B4 55 TC066 158 TY253MX 64 WCSM130/35 84 RSTI-CC-6827 132 Scotch51-50 144 SW1B5 55 TC075 158 TY26M 64 WCSM16/4 84 RSTI-CC-6828 132 Scotch69-12 145 SW1B6 55 TC080 158 TY26MX 64 WCSM160/50 84 RSTI-CC-6851 132 Scotch69-15 145 SW1B7 55 TC105-FU 158 TY27M 64 WCSM180/50 84 RSTI-CC-6852 132 Scotch69-19 145 SW1B8 55 TC110 158 TY27MX 64 WCSM24/6 84 RSTI-CC-6853 132 Scotch69-25 145 SW1B9 55 TC111-FU 158 TY28M 64 WCSM34/8 84 RSTI-CC-6854 132 Scotch69-38 145 SXAW-3121 105 TC115-FU 158 TY28MX 64 WCSM48/12 84 S102-S111 173 Scotch69-50 145 SXAW-3131 105 TC120-FU 158 TY29M 64 WCSM56/16 84 S1061-8-500 113 Scotch69-6 145 SXAW-3141 105 TC125-FU 158 TY29MX 64 WCSM70/20 84 S108A-S111A 173 Scotch69-9 145 SXAW-6132 110 TC130 158 TYD-50R 65 WCSM90/25 84 SCK 126 Scotch70 140 SXAW-6142 110 TC140-FU 158 TYD-LH 65 WK120 179 SCOTCFIL 141 Scotch88-19 139 SXAW3151 105 TC145 158 U-CHEX 187 WK60 179 Scotch 2200 Scotch88-25 139 SXSU-3111 105 TC910 158 U-H 187 WT163M-1 65 Pads 142 Scotch88-38 139 SXSU-3121 105 TC940 158 UB100A-B 64 ZHCP-NR-1-0 71 Scotch 2210-19 142 SCOTCHRAP 144 SXSU-3131 105 TC980 158 UB100A-N 64 ZHCP-NR-2-0 71 Scotch 2210-38 142 SFB28 (334791) 195 SXSU-3141 105 THG1 119 UB140A-B 64 ZHCP-NR-3-0 71 Scotch 77-38 144 SFB38 (334191) 195 SXSU-6122 110 THG2 119 UB140A-N 64 ZHCP-NR-4-0 71 Scotch 77-76 144 SFB50 (334891) 195 SXSU-6132 110 THGS1 (Cold UB150A-B 64 ZHCP-NR-6-0 71 SCOTCH13 141 SG1 194 SXSU-6141 110 shrink seal) 119 UB150A-N 64 ZHMPJ-2 79 SCOTCH130C-19 140 SHSS-12A-IND 107 SXSU-6142 110 THGS2 (Cold UB160C-B 64 ZHMPJ-3 79 SCOTCH130C-25 140 SHSS-12B-IND 107 SXSU-6151 110 shrink seal) 119 UB160C-N 64 ZHMPJ-4 79 SCOTCH130C-38 140 Sl-R 143 SXSU-6161 110 TILE 152-12 156 UB200A-B 64 ZHMPJ-5 79 SCOTCH130C-50 140 Sl-Rw 143 T1700pl 143 TILE 152-6 156 UB200A-N 64 ZHMPJ-6 79 SCOTCH1600 146 Sl1-R 143 T1700pl1 143 TILE 244-12 156 UB200B-B 64 ZHMPJ-7 79 SCOTCH1601 146 Sl1-Rw 143 T1700pl2 143 TILE 300-12 156 UB200B-N 64 ZHMPJ-8 79 SCOTCH1605 146 Sl2-R 143 T1700pl3 143 TOL/GTK 195 UB200C-B 64 SCOTCH1609 146 Sl2-Rw 143 T1700pn 143 TR5 150 UB200C-N 64 SCOTCH1617 147 Sl3-R 143 TA030 160 TRN76 150 UB250C-B 64 SCOTCH1625 147 Sl3-Rw 143 TA105 160 TRS-B70 185 UB250C-N 64 SCOTCH1626 147 SMOE50383 102 TA110 160 TS1025-HF 65 UB270C-B 64 SCOTCH1633 147 SMOE61171 92 TA115 160 TS1435-HF 65 UB270C-N 64 Scotch2000 143 SMOE61172 92 TA120 160 TS2405-HF 65 UB300C-B 64 Scotch22-12 139 SMOE61173 93 TA125 160 TS2845-HF 65 UB300C-N 64 Scotch22-19 139 SMOE61174 93 TA130 160 TS3645-HF 65 UB385C-B 64 Scotch22-25 139 SMOE61202 92 TAPEBLACK 138 TS3675-HF 65 UB385C-N 64 Scotch22-38 139 SMOE61203 TAPEBLUE 138 TSJ-120 74 UB760E-B 64 Scotch22-50 139 (MEC5) 96 TAPEBROWN 138 TSJ-16 74 UB760E-N 64 SCOTCH2220 141 SMOE61219 93 TAPECAUTION 155 TSJ-185 74 UBR185 40 SCOTCH2228 142 SMOE61987 107 TAPEGREEN/ TSJ-300 74 UBR300 40 SCOTCH2229 142 SMOE61988 107 YELLOW 138 TSJ-35 74 UBR95 40 Scotch23-19 140 SMOE62668 107 TAPEGREY 138 TSJ-6 74 UKRA 90 136 Scotch23-25 140 SMOE62803 96 TAPERED 138 TSJ-70 74 UNIAL 88 Scotch23-38 140 SMOE82051 82 TAPEWHITE 138 TSJ-120-HDI 74 UNX-C 187 Scotch23-50 140 SMOE82231 82 TAPEYELLOW 138 TSJ-16-HDI 74 UP-C 187 Scotch2510 145 SMOE82244 82 TB100-FU 173 TSJ-185-HDI 74 UST185 39 SCOTCH27 145 Sn-R 143 TBJ-120 76 TSJ-300-HDI 74 UST300 39 Scotch33-19 138 Sn-Rw 143 TBJ-16 76 TSJ-35-HDI 74 UST400 39 Scotch33-25 138 SPARE BATTERY 185 TBJ-185 76 TSJ-6-HDI 74 UST95 39 SCOTCH33-38 138 SSZ 177 TBJ-300 76 TSJ-70-HDI 74 VETB21-OHUTB 43 Scotch33+ 139 ST10C 30 TBJ-35 76 VETB28-OHUTB 43 224
Terms & Conditions of Sale PRICING Prices are subject to discount where applicable and are quoted exclusive of VAT. All prices listed are correct at time of publication however Jointing Technologies reserves the right to amend such pricing without notice when prevailing circumstances dictate that such action is required. CARRIAGE Jointing Technologies provides a carriage paid, next day service to all mainland U.K customers for all orders over 150.00 nett received and processed by 4.00pm. If the customer requires a timed delivery or any special delivery requirements Jointing Technologies reserves the right to pass on the additional cost of any such services. All orders from customers outside mainland U.K will be subject to an additional carriage charge. A minimum order charge of 10.00 is levied on all order below 150.00 to cover the cost of the carriage. Jointing Technologies are not responsible for consequential damages due to late delivery or in circumstances beyond our control. DISCOUNT Any preferential discounts applicable to prices shown in this catalogue will be advised at quotation stage or at time of ordering. RETURNS POLICY Jointing Technologies will not accept goods that have been supplied correctly back for credit without prior agreement by an authorised member of staff. Such items must be returned in the original packaging and in a saleable condition, but Jointing Technologies reserves the right to enforce a handling charge where deemed appropriate. Where goods have been dispatched direct by a manufacturer to the client, and that manufacturer places a returns charge on ourselves, we reserve the right to pass on any such charges. Please note LV heatshrink sleeving cut from a spool cannot be returned. Any credits applicable will not be raised until the goods have been returned to us and been inspected. Any errors in supply by Jointing Technologies must be notified to us within 14 days of receipt of the goods. HIRE CHARGES All hire charges will be calculated from the delivery date of the goods and will be levied on a weekly or daily basis quoted at the time of order. Such charges will continue to be levied until such time as the client receives an Off Hire Number from Jointing Technologies. DAMAGED OR LOST EQUIPMENT All tooling is checked and calibrated before dispatch and also on return. Where such tooling is returned in a damaged condition due to misuse, Jointing Technologies reserve the right to pass on all repair costs to the hirer. Any lost tooling will be charged to the client at the FULL replacement cost. SELECTION CHARTS Jointing Technologies have reproduced all selection guides within this catalogue in good faith and with the consent of the manufacturers. All information should be used as a guide only and where applicable actual dimensions on cables etc may be required at time of ordering. Jointing Technologies will not be held responsible for any error in selection derived from the information used in this catalogue Full Terms & Conditions are AVAILABLE on request 225
JOINTING TECHNOLOGIES BRANCHES AT WOKING Unit 19, Woking Business Park, Albert Drive, Woking. GU21 5JY Tel: 01483 747747 Fax: 01483 747001 BRISTOL The Alpha Centre, Armstrong Way, Great Western Business Park, Yate, Bristol. BS37 5NG Tel: 01454 322555 Fax: 01454 323555 NORTON CANES Unit 15-16, Bellsize Close Norton Canes, Staffordshire WS11 9TQ Tel: 01543 450555 Fax: 01543 450600 Registered Supplier ID 16470 TOOLOUT LIMITED Registered in London No. 2281668 09/12