Specification for Cable Accessories, Termination and Jointing Materials for Underground Electrical Power Cables for Nominal System Voltage Up to 33kV
|
|
|
- Gilbert Todd
- 9 years ago
- Views:
Transcription
1 Ergon Energy Corporation Limited Specification for Cable Accessories, Termination and Jointing Materials for Underground Electrical Power Cables for Nominal System Voltage Up to 33kV Specification ETS Ver 1
2 Contents 1. Purpose and Scope References Ergon Energy Controlled Documents Other Sources Definitions, Acronyms and Abbreviations Definitions Acronyms and Abbreviations Security Drawings Environmental and Service conditions Environmental Conditions Service Conditions Operating Conditions Design and Construction Cable Types in the Ergon Energy System kV Joints, Terminations and Separable Insulated Connectors kV Joints, Terminations and Separable Insulated Connectors kV Joints, Terminations and Separable Insulated Connectors LV Joints and Terminations Ancillary Equipment Performance & Testing Joint and Termination Performance Requirements Type Test Compliance Batch and Routine Tests Acceptance Tests Witnessing of Test Service Performance Risk Assessment Legislation Documentation Quality Assurance Samples Packaging and Labelling Packing Check this is the latest Process Zone version before use. i Specification ETS Ver 1
3 14.2 Marking Reliability Training Environmental Considerations Special Tools, Guages & Accessories Information to be Provided General Drawings & Information to be supplied by the Successful Tenderer Quality of instructions Provided Instruction Title Page Instruction Revisions Instructions in Electronic Format Schedule A Technical Details 33kV Terminations (Indoor & Outdoor) Schedule B Technical Details 33kV Joints Schedule C Technical Details 22kV Terminations (Indoor & Outdoor) Schedule D Technical Details 22kV Joints Schedule E Technical Details 11kV Terminations (Indoor & Outdoor) Schedule F Technical Details 11kV Joints Schedule G Technical Details LV Terminations Schedule H Technical Details LV Joints Annex A. Cable Terminations Annex B. Annex C. Cable Joints Cable Cross Section Drawings C.1 33kV Cables C.2 22kV Cables C.3 11kV Cables C.4 LV Cables Annex D. Cable Termination Constructions D.1 33kV Cable Termination D.2 22kV Cable Termination D.3 11kV Cable Termination Check this is the latest Process Zone version before use. ii Specification ETS Ver 1
4 1. Purpose and Scope This specification sets out the requirements for the manufacture, testing, supply and delivery of cable accessories, terminating and jointing materials, for the use in the underground electricity distribution system of Ergon Energy. This specification includes heat shrink, cold shrink and cold applied joints and terminations for LV, 11kV, 22kV and 33kV cable. Included are dead-break separable connectors (elbows) and ancillary equipment for 11kV, 22kV and 33kV single phase or triplex cables that Ergon Energy may purchase to connect to specific 11kV, 22kV and 33kV switchgear and transformers. Suppliers are encouraged to submit alternative tenders based on their standard products provided that the accessories offered will provide electrical and mechanical in-service performance equivalent to the accessories conforming to this specification. Type Test Certificates or Qualification Test Reports shall be submitted to verify performance. Departures from this specification shall be fully documented in the tender. 2. References 2.1 Ergon Energy Controlled Documents 2.2 Other Sources The items shall be designed, manufactured and tested in accordance with the latest revision of all relevant Queensland Acts / Regulations and Australian Standards, and all amendments issues from time to time expect where varied by this specification. Should inconsistencies be identified between standards and / or this specification, the Tenderer shall iediately refer such inconsistencies to the Purchaser for resolution. STANDARD DESCRIPTION AS / NZS 1026 AS / NZS 1125 AS / NZS AS / NZS 1660 All parts Electric cables Impregnated paper insulated For working voltage up to and including 19/33 (36)kV Conductors in insulated electric cables and flexible cords Electric cables Polymeric insulated For working voltages 1.9/3.3 (3.6) kv up to and including 19/33 (36)kV Test methods for electric cables, cords and conductors Check this is the latest Process Zone version before use. Page 1 of 61 Specification ETS Ver 1
5 STANDARD DESCRIPTION AS / NZS 3808 AS / NZS 4026 AS / NZS AS / NZS 4805 AS / NZS AS / NZS ISO AS / NZS ISO 9001 AS 1931 AS 2629 AS 4068 AS 4169 AS AS AS ISO 1000 ASTM D1603 Electricity Association Services Ltd. Engineering Recoendation C.55/4 IEC Insulating and sheathing materials for electric cables Electric Cables For underground residential distribution systems Compression and mechanical connectors for power cables with copper or aluminium conductors Test methods and requirements Accessories for electric cables Test requirements Electric cables Polymeric insulated For working voltages up to and including 0.6/1 (1.2)kV Risk management Principles and guidelines Quality management systems - Requirements High-voltage test techniques Separable insulated connectors for power distribution system above 1kV Flat pallets for materials handling Electroplated coatings Tin and tin alloys (ISO 2093:1986, MOD) High-voltage test techniques Partial discharge measurements High voltage switchgear and controlgear Dimensional standardization of terminals The international system of units (SI) and its application Standard Test Method for Carbon Black Content in Olefin Plastic Insulated Sheath Power Cable Systems Electric cables - Tests on extruded oversheaths with a special protective function Check this is the latest Process Zone version before use. Page 2 of 61 Specification ETS Ver 1
6 STANDARD DESCRIPTION IEC IEC IEC IEC60721 IEEE 404 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (Um = 1,2 kv) up to 30 kv (Um = 36 kv) Part 4: Test requirements on accessories for cables with rated voltages from 6 kv (Um = 7,2 kv) up to 30 kv (Um = 36 kv) Flexible insulating sleeving Test methods for accessories for power cables with rated voltages from 6 kv (Um = 7,2 kv) up to 30 kv (Um = 36 kv) Classification of environmental conditions Extruded and Laminated Dielectric Shielded Cable Joints Rated 2.5 kv to 500 kv 3. Definitions, Acronyms and Abbreviations 3.1 Definitions For the purpose of this standard, the following definitions apply: Term Definition Materials Specification Items, goods or product This technical specification Shall Supplier 3.2 Acronyms and Abbreviations The following abbreviations and acronyms appear in this standard: Abbreviation or Acronym Definition Al CONSAC Cu CWS HDPE Aluminium conductor Sectored shaped aluminium conducted 0.6/1kV cable with concentric aluminium sheath Copper conductor Copper Wire Screen High density polyethylene Check this is the latest Process Zone version before use. Page 3 of 61 Specification ETS Ver 1
7 Abbreviation or Acronym Definition LY MDPE NJ PLY PVC SWA SWS TR-XPLE WB WBT XPLE Lead ally sheath Medium density polyethylene Nylon jacket Paper insulated lead alloy sheathed Polyvinyl chloride Galvanised steel wire armoured Steel wire armoured and oversheathed Tree retardant cross-linked polyethylene Water blocked Water blocking tape (and / or yarns) Cross-linked polyethylene 4. Security Nil 5. Drawings The drawings listed in Appendix A shall be read in conjunction with, and shall form part of this Specification. 6. Environmental and Service conditions 6.1 Environmental Conditions General Environmental Conditions The Conditions under which the terminating and jointing materials will be required to operate are: Ambient Temperatures 50 Suer day time (maximum) -5 Winter night time (minimum) Maximum Daily Variation 35 C Solar Radiation Level Precipitation 1100 watts per square metre with high ultraviolet content (IEC , Table 1) An annual rainfall in excess of 2000 (bureau of Meteorology) Check this is the latest Process Zone version before use. Page 4 of 61 Specification ETS Ver 1
8 Wind Speed Humidity Atmospheric Classification Isokeraunic Level Below Ground Soil Below Ground Temperatures Tropical suer storms with gust wind speeds above 160km/h Extended periods of relative humidity in excess of 90% R.H combined with rapid temperature drop (20 C in 20 minutes). Level IV very heavy (for installation in polluted ambient air with areas of costal salt spray and / or industrial pollution refer AS 4436). Equivalent salt deposit densities in the range of g/m² (AS 4436, Table 3) (Bureau of Meteorology) Installed directly buried in fine grain bedding material, at normal depth of up to C Suer day time (maximum) 18 C Winter night time (minimum) Note to Tenderers: Tenderers are to provide information on how the offered items will perform in the above conditions. 6.2 Service Conditions The underground power cables used within the Ergon Energy distribution system are 19.1/33kV, 12.7/22kV, 6.3/11kV and 240/415V, three phase, 50 hertz kV System Ergon Energy s 33kV network has the star point either effectively earthed or through a neutral earthing reactor. The maximum system voltage (phase to phase) is 36kV and the require impulse insulation level is 170kV p kV System The star point of Ergon Energy s 22kV network is effectively earthed. The maximum system voltage (phase-to phase) is 24kV and the required impulse insulation level is 125kV p kV System The star point of Ergon Energy s 11kV network is effectively earthed. The maximum system voltage (phase-to phase) is 12kV and the required impulse insulation level is 95kV p. Check this is the latest Process Zone version before use. Page 5 of 61 Specification ETS Ver 1
9 6.2.4 LV System The natural of the 240/415 volt system is effectively earthed. 6.3 Operating Conditions Assembled components forming part of a system shall perform without distress under the following conditions: Normal Conditions Extruded dielectric (Polymeric Insulated) cables Continuous operation at a conductor temperature of 90 C. Laminated dielectric (Paper Insulated) cables Continuous operation at a conductor temperature of 70 C Emergency Conditions Extruded dielectric (Polymeric Insulated) cables Operated for 2hrs at a conductor temperature of 105 C. Laminated dielectric (Paper Insulated) cables Operated for 2hrs at a conductor temperature of 85 C Fault Conditions The table below has the earth fault duty of the HV cables used by Ergon Energy. Table 6.1: Earth fault duty of HV cables Cable Earth Fault Duty 35² 185² & 240² 400² 630² 50² 300² 3.4kA for 1 Second 10kA for 1 Second 13.1kA for 1 Second 13.9kA for 1 Second 4.9kA for 1 Second 13.8kA for 1 Second Extruded dielectric (Polymeric Insulated) cables Operated for 5sec max. at a conductor temperature of 250 C. Check this is the latest Process Zone version before use. Page 6 of 61 Specification ETS Ver 1
10 7. Design and Construction 7.1 Cable Types in the Ergon Energy System The cables listed in Table 7.1 to Table 7.4 show the current standard cables being installed in the Ergon Energy s network and existing cables in the network that require jointing and terminating in conjunction with network alterations, extensions and maintenance work. The cross-sectional dimensions of the cables are shown in Annex C or are otherwise shown in the respective standards. Insulation screens on 11kV, 22kV and 33kV cables are hand-strippable. All HV cables are screened unless otherwise stated. Bold type in the following tables designates current standard cables. Table 7.1: 19 / 33 (36) kv Cables 19.1 / 33kV Cable Types and Applicable Standards Conductor Size (²) & Type Insulation / Oversheath No. of Cores Remarks Applicable Standard 50 stranded Al TR-XLPE / HDPE stranded Al TR-XLPE / HDPE 1 Nylon jacket for insect protection Nylon jacket for insect protection AS / NZS AS / NZS Table 7.2: 12.7 / 22 (24) kv Cables 12.7 / 22kV Cable Types and Applicable Standards Conductor Size (²) & Type Insulation / Oversheath No. of Cores Remarks Applicable Standard 630 Al TR-XLPE / HDPE 3 x 1C Triplex LAT water blocking layer AS / NZS Check this is the latest Process Zone version before use. Page 7 of 61 Specification ETS Ver 1
11 185 Al TR-XLPE / HDPE 3 x 1C Triplex 35 Al TR-XLPE / HDPE 3 x 1C Triplex LAT water blocking layer Nylon jacket for insect protection AS / NZS AS / NZS Table 7.3: 6.35 / 11 (12) kv Cables 6.35 / 11kV Cable Types and Applicable Standards Conductor Size (²) & Type Insulation / Oversheath No. of Cores Remarks Applicable Standard 400 stranded Cu TR - XPLE / HDPE stranded Al TR - XPLE / HDPE 3 x 1C Triplex Nylon Jacket for insect protection Nylon Jacket for insect protection AS / NZS AS / NZS stranded AL TR - XPLE / HDPE 3 x 1C Triplex AS / NZS stranded Cu TR-XLPE / HDPE 3 x 1C Triplex Nylon Jacket for insect protection AS stranded Cu TR-XLPE / HDPE 3 AS Stranded AL TR - XPLE / HDPE 3 x 1C Triplex Nylon Jacket for insect protection AS / NZS stranded Al TR - XPLE / HDPE 3 x 1C Triplex AS / NZS stranded AL TR - XPLE / HDPE 3 x 1C Triple Nylon Jacket for insect protection AS / NZS stranded Al TR - XPLE / HDPE 3 x 1C Triplex AS / NZS Table 7.4: 0.6 / 1kV (LV) Cables 0.6/ 1kV (LV) Cable Types and Applicable Standards Check this is the latest Process Zone version before use. Page 8 of 61 Specification ETS Ver 1
12 Conductor Size (²) & Type Insulation / Oversheath No. of Cores Remarks Applicable Standard 240 stranded Al XLPE / PVC 4 90 deg. Sector Nylon Jacket AS / NZS stranded Al XLPE / PVC 4 90 deg. Sector AS / NZS stranded Cu XPLE / PVC 4 16 Stranded Cu XLPE / PVC 4 16 Stranded Cu XLPE / PVC 4 16 Stranded Cu PVC / PVC 1 4 Stranded Cu PVC / PVC 1 Circular Conductors Nylon Jacket Circular Conductors Nylon Jacket Circular Conductors Neutral Screen Nylon Jacket Neutral Screen Nylon Jacket AS / NZS 4026 AS / NZS 4026 AS / NZS 4026 AS / NZS AS / NZS kV Joints, Terminations and Separable Insulated Connectors General All joints and terminations, except for separable insulated connectors shall be of the heat-shrink, cold-shrink, or cold-applied polymeric type design, manufactured and tested to meet the requirements of the relevant Standards, including AS/NZS 4805 Parts 1 and 2 or equivalent, and shall be suitable for application to Ergon Energy s 33 kv cables as described in Table 7.1 of this specification. All separable insulated connectors and accessories forming part of the connector system shall be of the dead-break shielded / screened type with a screen break, manufactured and tested to meet the relevant Standards, including AS The separable insulated connectors shall be suitable for connecting particular single core polymeric cables as described in Table 7.1 to provide 33kV test points adjacent to substation switchgear. All joint and termination kits shall be supplied complete in unit lots suitably packaged for storage containing all necessary materials. Full detailed installation instructions specific to the cables listed in Table 7.1 shall be supplied with the Tender and with the jointing kits that are subsequently supplied. Ergon Energy will approve all instructions for kits that are purchased for use in Ergon Energy. Ergon Energy will keep a copy of the instructions for their records and the supplier is to supply a copy of the instructions with each kit. Check this is the latest Process Zone version before use. Page 9 of 61 Specification ETS Ver 1
13 Preference will be shown to the Tender offering bi-metal range taking kits suitable for either aluminium or copper conductors and utilising screwed connectors with shear head bolts or torque tightened bolts, in lieu of kits containing compression connectors. All joints and termination kits shall be supplied with the required cleansing solvents, cloth and abrasives. Tenderers shall provide with their tender Safety Data Sheets (SDS) for nominated solvents. No unapproved solvents shall be provided without prior agreement of the Purchaser. If required, sealants shall be supplied to effect seals on joints and terminations and shall be able to accoodate the creep or relaxation that may occur during installation of the accessories or during the normal cyclic loading of the cables. The sealant shall have adhesion properties to maintain hermetic seals at all times between components and the various cable sheath materials and connectors. Suitable lubricant shall be provided with the kits for separable connectors (elbows, tee connectors and plugs) to facilitate separation of the connector from the bushing or plug socket kv Straight Joints All joints shall meet the performance requirements of Clause 9.1 of this specification. Where cable joint descriptions in Table 7.1 include insect protection the purchaser requires the completed joint to afford protection for attack by the subterranean termite Mastotermes Darwinists and the coastal brown ant Pheidole Megacephala. The preference is for a fine woven stainless steel mesh cylindrical sleeve that is applied over the joint and clamped to the cable insect protection layer each side of the joint by a constant force spring arrangement. An outer tube is then provided to finish the joint. Due to insect damage to the joint components outside the insect protection layer it is necessary to provide the joint with a water / environmental seal to the cable as follows: For cables provided with Double Brass Tape (DBT) the PVC inner sheath below the DBT For cables provided with Nylon Jacket (NJ) the NJ. Alternative forms for insect protection may be considered by the Purchaser. Alternative offers shall be submitted with full details of the recoendations and supporting evidence of performance including service history. Where cable description in Table 7.1 includes an extruded water barrier comprised of an Aluminium / PE Laminate Tape the purchaser requires the water / environmental seal to the cable Check this is the latest Process Zone version before use. Page 10 of 61 Specification ETS Ver 1
14 to be to the LAT. It is the purchases preference that the LAT is either bridged through at the joint or clamped to the screen of the cable. Methods for achieving the environmental seal and managing induced voltages on the LAT shall be submitted with full details and supporting evidence of performance including service history. Mechanical connectors utilising a shear bolt connection are preferred and the connectors shall be supplied with all bolts, pre-greased with conductive grease inserted in the connector, which in turn shall be protected from corrosion. Where compression connectors are offered the connectors shall be capable of being installed using a standard 23 Tonne Hydraulic Crimper for up to 630 ². Connectors shall meet the requirements of AS/NZS All connectors shall be blocked internally to prevent water / oil migration between cables. Tenderers shall complete Schedule B to state overall length of the completed joint and the required cable pit length to make the joint kV Terminations Outdoor Type All terminations shall meet the performance requirements specified in Clause 9.1 of this specification. The terminations shall be suitable for terminating cables on to a low mount substation structure, or on to a pole using a bracket mounted with 36kV surge arresters for support of three single phase cable tails. The polymeric stress control sleeve and sheds shall withstand the electrical stress associated with continuous operation at 36kV under the environmental conditions described in Clauses 6.1 and 6.2 above. Where cable description in Table 7.1 includes an extruded water barrier comprised of an Aluminium / PE Laminate Tape the purchaser requires the water / environmental seal to the cable to be to the LAT. It is the purchases preference that the LAT is clamped to the screen of the cable. Methods for achieving the environmental seal and managing induced voltages on the LAT shall be submitted with full details and supporting evidence of performance including service history. The kits shall be supplied with phase identification components which can be applied to the phase cores and which are compatible with the terminating materials. Check this is the latest Process Zone version before use. Page 11 of 61 Specification ETS Ver 1
15 Fully sealed terminal connectors are to be supplied with the kits and shall be of the following type: - Lug palms shall be supplied with fully sealed palms and shall have one hole, suitable for a M12 blot. All lugs should preferably be screwed connectors with shear head bolts in lieu of compression lugs. TR-XPLE / XLPE Insulated cables shall have bi-metallic or tinned aluminium lugs for the phase conductors and tinned copper or brass lugs for the screen wires. Lugs shall meet the test requirements of AS/NZS Where offered, compression terminal connectors shall be capable of being installed using Ergon Energy s current hydraulic tooling, namely 23 Tonne Hydraulic Crimpers kV Joints, Terminations and Separable Insulated Connectors General All joints and terminations shall be manufactured and tested to meet the requirements of the relevant Standards, including AS/NZS 4805 Parts 1 and 2 or equivalent, and shall be suitable for application to Ergon Energy s 22kV cables as described in Table 7.2 of this specification. All joints and terminations shall be designed so that a phase cross can be made in the joint or termination without stressing the cable insulation or insulation components. All joint and termination kits shall be supplied complete in unit lots suitably packaged for storage containing all necessary materials. Full detailed installation instructions specific to the cables listed in Table 7.2 shall be supplied with the Tender and with the jointing kits that are subsequently supplied. Ergon Energy will approve all instructions for kits that are purchased for use in Ergon Energy. Ergon Energy will keep a copy of the instructions for their records and the supplier is to supply a copy of the instructions with each kit. Preference will be shown to the Tender with bi-metal range taking kits for either aluminium or copper conductors. All joint kits and termination kits shall be supplied complete with suitable connectors, including screen connectors and lugs, preferably utilising screwed connectors with shear head bolts or torque tightened bolts, in lieu of kits containing compression connectors. All bolts shall be pregreased with a conductive grease and inserted in the connector, which in turn shall be protected from corrosion All joints and termination kits shall be supplied with the required cleansing solvents, cloth and abrasives. Tenderers shall provide with their tender Safety Data Sheets (SDS) for nominated solvents. No unapproved solvents shall be provided without prior agreement of the Purchaser. Check this is the latest Process Zone version before use. Page 12 of 61 Specification ETS Ver 1
16 If required, sealants shall be supplied to effect seals on joints and terminations and shall be able to accoodate the creep or relaxation that may occur during installation of the accessories or during the normal cyclic loading of the cables. The sealant shall have adhesion properties to maintain hermetic seals at all times between components and the various cable sheath materials and connectors. Suitable lubricant shall be provided with the kits for separable connectors (elbows, tee connectors and plugs) to facilitate separation of the connector from the bushing or plug socket kv Straight & Transition Joints All joints shall have an outer serving which has mechanical strength properties equal to that of the HDPE over-sheath of the cable. Where cable joint descriptions in Table 7.2 include insect protection the purchaser requires the completed joint to afford protection for attach by the subterranean termite Mastotermes Darwinists and the coastal brown ant Pheidole Megacephala. The preference is for a fine woven stainless steel mesh cylindrical sleeve that is applied over the joint and clamped to the cable insect protection layer each side of the joint by a constant force spring arrangement. An outer tube is then provided to finish the joint. Due to insect damage to the joint components outside the insect protection layer it is necessary to provide the joint with a water / environmental seal to the cable as follows: For cables provided with Double Brass Tape (DBT) the PVC inner sheath below the DBT For cables provided with Nylon Jacket (NJ) the NJ. Alternative forms for insect protection may be considered by the Purchaser. Alternative offers shall be submitted with full details of the recoendations and supporting evidence of performance including service history. Where cable description in Table 7.2 includes an extruded water barrier comprised of an Aluminium / PE Laminate Tape the purchaser requires the water / environmental seal to the cable to be to the LAT. It is the purchases preference that the LAT is either bridged through at the joint or clamped to the screen of the cable. Methods for achieving the environmental seal and managing induced voltages on the LAT shall be submitted with full details and supporting evidence of performance including service history. Annex B show the required cable to cable joint requirement to be supplied in accordance with this specification. Check this is the latest Process Zone version before use. Page 13 of 61 Specification ETS Ver 1
17 Tenderers shall complete Schedule D to state overall length of the completed joint and the required cable pit length to make the joint kV Terminations Outdoor Type All terminations shall meet the performance requirements specified in Clause 9.1 of this specification. The polymeric stress control sleeve and sheds shall withstand the electrical stress associated with continuous operation at 24kV under the environmental conditions described in Clause 6.1 above. The termination shall be suitable for terminating cables on to a low mount substation structure and on to a pole using a bracket as per Drawing No mounted with 24kV surge arresters for support of the cable tails. The tail lengths of the terminating kits for three phase cables shall be a minimum of 800 long to allow a phase cross to be installed on the cable. A typical general arrangement is shown on Drawing No that is contained in Ergon Energy's Underground Construction Manual, HV Construction folder. A copy is attached with the other drawings included in this specification. Shorter lengths may be considered provided an assessment by Ergon Energy s field personnel indicate that the kits can be installed without undue difficulty and without stressing the conductor insulation. The kits shall be supplied with phase identification components which can be applied to the phase cores and which are compatible with the terminating materials. Terminal connectors, preferably with shear head bolts, are to be supplied with the kits and shall be of the following type: - TR-XPLE / XLPE insulated cables shall have bi-metal lugs or tinned aluminium shear bolt connectors for the phase conductors and tinned copper or brass lugs for the screen wires. Lug palms shall be supplied with fully sealed palms. Lugs shall meet the test requirements of AS/NZS Lugs shall have a clearance hole suitable for a 12 bolt for cable up to 300² and a clearance hole suitable for a 16 bolt for larger cables kV Terminations Indoor Type All terminations shall meet the requirements of AS/NZS and the performance requirements specified in Clause 9.1 of this specification. Check this is the latest Process Zone version before use. Page 14 of 61 Specification ETS Ver 1
18 The terminating kits shall be suitable for terminating in cable boxes of the switchgear listed in Table 7.5 below. Table 7.5: 24kV Switchgear Switchgear Manufacturer Type Cable Sizes Ormazabal F & G 1000 ² to 25 ² Merlin Gerin RM6 300 ² to 25 ² Schneider RM6 300 ² to 25 ² kV Terminations to Open Bushings The tail lengths of the terminating kits for three phase cables shall be of sufficient length to allow a phase cross to be installed on the cable. All 22kV single core cable kits shall have a maximum length of 330. Where the phase to phase and phase to earth clearance of the switchgear cable boxes are not sufficient for air clearance, tenderers shall supply a system of insulating the terminal and lug connection which suits both the cables listed in Table 7.2 and the switchgear listed in Table 7.5. The insulating system for the terminals shall be capable of withstanding an impulse level of 150kV BIL with the largest cable size from Table 7.2 terminated in the cable box. The insulating system offered shall be a cold applied (heat shrink is not acceptable) systems. Where insulating boots are required these shall be supplied as separate items and listed in the offer under ancillary equipment. The kits shall be supplied with phase identification components which can be applied to the phase cores and which are compatible with the terminating materials. Terminal lugs, preferably with shear head bolts, are to be supplied with all kits and shall be of the following type: - TR-XLPE / XLPE Insulated cables shall have bi-metal or tinned aluminium lugs for the phase conductors and tinned copper or brass lugs for the screen wires. Lug palms shall be supplied with fully sealed palms. For conductors up to 630 ² lug palms shall not exceed 35 in width and shall have a clearance hole suitable for a 12 bolt. Lugs shall meet the test requirements of AS/NZS Check this is the latest Process Zone version before use. Page 15 of 61 Specification ETS Ver 1
19 Annex A shows the indoor and outdoor terminations kit requirements to be supplied in accordance with this specification Dead-break Insulated Separable Connectors (Elbows) As an alternative to lugged connections to open bushings Ergon Energy will require dead-break screened elbows to connect 3 x 1 core triplex cables to transformers and switchgear with required current ratings as shown in Annex A. Separable elbow and tee connectors shall comply with the requirements of AS2629 and shall be suitable for all applications including padmount substations, subsurface, vault, indoor, outdoor, direct sunlight, direct buried and continuously submersed in water. Separable Elbow connectors shall be suitable for connection to DIN type bushings and be fitted with capacitor voltage indication, and shall have accessories available for: Earthing Testing Bypass Lightning Surge Protection Current Limiting Fusing Feed through Junctions / Piggy back Details of these accessories shall be included in the list ancillary items. The screened separable connectors shall include a screen break. The insulated plugs covering the capacitor voltage indicator shall have a moulded eyelet to enable it to be removed using an insulated hook stick kV Joints, Terminations and Separable Insulated Connectors General All joints and terminations, except for separable insulated connectors shall be of the heat-shrink, cold-shrink, or cold-applied polymeric type design, manufactured and tested to meet the requirements of the relevant Standards, including AS/NZS 4805 Parts 1 and 2 or equivalent, and shall be suitable for application to Ergon Energy s 11kV cables as described in Table 7.3 of this specification. All separable insulated connectors and accessories forming part of the connector system shall be of the dead-break shielded / screened type with a screen break, manufactured and tested to meet the relevant Standards, including AS The separable insulated connectors shall be suitable for connecting particular single core polymeric cables as described in Table 7.3 to provide 11kV test points adjacent to substation switchgear. Check this is the latest Process Zone version before use. Page 16 of 61 Specification ETS Ver 1
20 All joint and termination kits shall be supplied complete in unit lots suitably packaged for storage containing all necessary materials. Full detailed installation instructions specific to the cables listed in Table 7.3 shall be supplied with the Tender and with the jointing kits that are subsequently supplied. Ergon Energy will approve all instructions for kits that are purchased for use in Ergon Energy. Ergon Energy will keep a copy of the instructions for their records and the supplier is to supply a copy of the instructions with each kit. Preference will be shown to the Tender offering bi-metal range taking kits suitable for either aluminium or copper conductors and utilising screwed connectors with shear head bolts or torque tightened bolts, in lieu of kits containing compression connectors. All joints and termination kits shall be supplied with the required cleansing solvents, cloth and abrasives. Tenderers shall provide with their tender Safety Data Sheets (SDS) for nominated solvents. No unapproved solvents shall be provided without prior agreement of the Purchaser. If required, sealants shall be supplied to effect seals on joints and terminations and shall be able to accoodate the creep or relaxation that may occur during installation of the accessories or during the normal cyclic loading of the cables. The sealant shall have adhesion properties to maintain hermetic seals at all times between components and the various cable sheath materials and connectors. Suitable lubricant shall be provided with the kits for separable connectors (elbows, tee connectors and plugs) to facilitate separation of the connector from the bushing or plug socket. All joints and terminations shall be designed so that a phase cross can be made in the joint or termination without stressing the cable insulation or insulation components. All joint and termination kits shall be supplied complete in unit lots suitably packaged for storage containing all necessary materials. Full detailed installation instructions specific to the cables listed in Table 7.3 shall be supplied with the Tender and with the jointing kits that are subsequently supplied. Ergon Energy will approve and sign all instructions for kits that are purchased for use in Ergon Energy as an approved master check list, and a copy is to be inserted in each kit by the Supplier kv Straight & Transition Joints All joints shall have an outer serving which has mechanical strength properties equal to that of the HDPE over-sheath of the cable. Where cable joint descriptions in include insect protection the purchaser requires the completed joint to afford protection for attack by the subterranean termite Mastotermes Darwinists and the coastal brown ant Pheidole Megacephala. Check this is the latest Process Zone version before use. Page 17 of 61 Specification ETS Ver 1
21 The preference is for a fine woven stainless steel mesh cylindrical sleeve that is applied over the joint and clamped to the cable insect protection layer each side of the joint by a constant force spring arrangement. An outer tube is then provided to finish the joint. Due to insect damage to the joint components outside the insect protection layer it is necessary to provide the joint with a water / environmental seal to the cable as follows: For cables provided with Double Brass Tape (DBT) the PVC inner sheath below the DBT For cables provided with Nylon Jacket (NJ) the NJ. Alternative forms for insect protection may be considered by the Purchaser. Alternative offers shall be submitted with full details of the recoendations and supporting evidence of performance including service history. Annex B shows required cable to cable joint requirements to be supplied in accordance with this specification. Tenderers shall complete Schedule F to state overall length of the completed joint and the required cable pit length to make the joint kV Terminations Outdoor Type All terminations shall meet the performance requirements specified in Clause 9.1 of this specification. The polymeric stress control sleeve and sheds shall withstand the electrical stress associated with continuous operation at 12 kv under the environmental conditions described in Clauses 6.1. The termination shall be suitable for terminating cables on to a low mount substation structure and on to a pole using a bracket as per Drawing No mounted with 12kV surge arresters for support of the cable tails. The tail lengths of the terminating kits for three phase cables shall be a minimum of 800 long to allow a phase cross to be installed on the cable. A typical general arrangement is shown on Drawing No that is contained in Ergon Energy's Underground Construction Manual, HV Construction folder. A copy is attached with the other drawings included in this specification. Shorter lengths may be considered provided an assessment by Ergon Energy s field personnel indicate that the kits can be installed without undue difficulty and without stressing the cable insulation. The kits shall be supplied with phase identification components which can be applied to the phase cores and which are compatible with the terminating materials. Check this is the latest Process Zone version before use. Page 18 of 61 Specification ETS Ver 1
22 Terminal connectors, preferably with shear head bolts, are to be supplied with the kits and shall be of the following type: - TRXLPE / XLPE insulated cables shall have bi-metal lugs or tinned aluminium shear bolt connectors for the phase conductors and tinned copper or brass lugs for the screen wires. Lug palms shall be supplied with fully sealed palms. Lugs shall meet the test requirements of AS/NZS Lugs shall have a clearance hole suitable for a 12 bolt for cable up to 300² and a clearance hole suitable for a 16 bolt for larger cables kV Terminations Indoor Type All terminations shall meet the requirements of AS/NZS and the performance requirements specified in Clause 9.1 of this specification. The terminating kits shall be suitable for terminating in cable boxes of the switchgear listed in Table 7.6 below. Table 7.6: 12kV Switchgear Switchgear Manufacturer Type Cable Sizes ABB SafeLink 300² to 25² ABB SafeRing 300² to 25² ABB SafePlus 300² to 25² ABB SDAF 300² to 25² Eaton Magnefix MD4 240² to 25² Merlin Gerin RM6 300² to 25² Schneider RM6 300² to 25² Schneider FBX 300² to 25² kV Terminations to Open Bushings The tail lengths of the terminating kits for three phase cables shall be of sufficient length to allow a phase cross to be installed on the cable. All 11 kv single core cable kits shall have a maximum length of 330. Check this is the latest Process Zone version before use. Page 19 of 61 Specification ETS Ver 1
23 Where the phase to phase and phase to earth clearance of the switchgear cable boxes are not sufficient for air clearance, tenderers shall supply a system of insulating the terminal and lug connection which suits both the cables listed in Table 7.3 and the switchgear listed in Table 7.6. The insulating system for the terminals shall be capable of withstanding an impulse level of 95kV BIL with the largest cable size from Table 7.3 terminated in the cable box. The insulating system offered should be a cold applied (heat shrink is not acceptable) systems. Where insulating boots are required these shall be supplied as separate items and listed in the offer under ancillary equipment. The kits shall be supplied with phase identification components which can be applied to the phase cores and which are compatible with the terminating materials. Terminal lugs, preferably with shear head bolts, are to be supplied with all kits and shall be of the following type: - TR-XPLE / XLPE Insulated cables shall have bi-metal or tinned aluminium lugs for the phase conductors and tinned copper or brass lugs for the screen wires. Lug palms shall be supplied with fully sealed palms. For conductors up to 400 ² lug palms shall not exceed 35 in width and shall have a clearance hole suitable for a 12 bolt. Lugs shall meet the test requirements of AS/NZS Annex A shows indoor and outdoor termination kits required to be supplied in accordance with this specification Dead-break Insulated Separable Connectors (Elbows) As an alternative to lugged connections to open bushings Ergon Energy will require dead-break screened elbows to connect 3 x 1 core triplex cables to transformers and switchgear with required current ratings as shown in Annex A. Separable elbow shall comply with the requirements of AS2629 and shall be suitable for all applications including padmount substations, subsurface, vault, indoor, outdoor, direct sunlight, direct buried and continuously submersed in water. Separable Elbow connectors shall be suitable for connection to DIN type bushings and be fitted with capacitor voltage indication, and shall have accessories available for: Earthing Testing Bypass Check this is the latest Process Zone version before use. Page 20 of 61 Specification ETS Ver 1
24 Lightning Surge Protection Current Limiting Fusing Feed through Junctions / Piggy back Details of these accessories shall be included in the list ancillary items. The screened separable connectors shall include a screen break. The insulated plugs covering the capacitor voltage indicator shall have a moulded eyelet to enable it to be removed using an insulated hook stick. 7.5 LV Joints and Terminations General All joints and terminations shall meet the performance requirements of Clause 9.1 of this specification and shall be suitable for application to Ergon Energy s LV cables as described in Table 7.4 of this specification. Sealants shall be used to effectively seal joints and terminations and the properties of the sealants shall be able to accoodate the creep or relaxation that may occur during installation of the accessories or during the normal cyclic loading of the cables. The sealants shall have adhesion properties to maintain hermetic seals at all times between components and the various cable sheath materials and connectors. All joints and terminations shall be designed so that a phase cross can be made in the joint or termination without stressing the cable insulation or insulation components. Connectors shall be supplied with the kits. Connectors utilising a mechanical connection with shear head bolts with a range taking ability are preferred to compression connectors. Where compression connectors are supplied the connectors shall be capable of being installed using a standard 12 Tonne Hydraulic Crimper. Connectors shall meet the test requirements of AS/NZS All joint and terminations kits shall be supplied complete in unit lots suitably packaged for storage containing all necessary materials including cleansing solvents, cloths and abrasives. Tenderers shall provide with their tender Safety Data Sheets (SDS) for nominated solvents. No unapproved solvents shall be provided without prior agreement of the Purchaser. Full detailed installation instructions specific to the cables listed in Table 7.4 shall be supplied with the jointing kits. Ergon Energy will approve all instructions for kits that are purchased for use in Ergon Energy. Ergon Energy will keep a copy of the instructions for their records and the supplier is to supply a copy of the instructions with each kit. Check this is the latest Process Zone version before use. Page 21 of 61 Specification ETS Ver 1
25 7.5.2 LV Straight Joints All joints shall have an outer serving which has a mechanical strength equal to that of the oversheath of the cable. The outer serving shall provide a minimum insulation resistance of 1000MΩ LV Terminations Indoor and Outdoor type All terminations shall meet the performance requirements specified in Clause 9.1. The tail lengths of the terminating kits shall be of sufficient length to allow a phase cross to be installed on the cable. The minimum length for tails shall be 400. Terminal connectors are to be supplied with the kits and shall be of the following type:- Cable terminations with copper conductors shall have tinned copper lugs whilst aluminium conductor shall have aluminium lugs. Lug palms shall be supplied with fully sealed palms. For cables up to 300 ² lug palms shall not exceed 35 in width and shall have a clearance hole suitable for a 12 bolt. Lugs shall meet the test requirements of AS/NZS Connectors utilising a mechanical connection with shear head bolts with a range taking ability are preferred to compression connectors. Where offered, compression terminal connectors shall be capable of being installed using a standard 12 Tonne Hydraulic Crimper. 8. Ancillary Equipment All items necessary to this specification and not included in the items previously specified shall be termed Ancillary Equipment. The Tenderer shall list such items. A quantity and price shall be shown for each individual item to allow a review of requirements at the time of ordering. 9. Performance & Testing 9.1 Joint and Termination Performance Requirements Electrical The Tenderer shall supply joints and terminations that meet the test requirements of the relevant Standards, including AS/NZS 4085 Part 1 and 2, AS/NZS 1600 All Parts, AS/NZS and IEC61442, and shall complete Schedule A to Schedule H inclusive. Check this is the latest Process Zone version before use. Page 22 of 61 Specification ETS Ver 1
26 The joints and terminations shall withstand the electrical stress associated with continuous operation at the highest system voltage under the environmental conditions described in Clause 6.2 of this specification Test Certificates The Tenderer shall provide test Certificates in duplicate for all test undertaken by the manufacturer under this specification. Such test certificates shall be signed by a properly authorised person and forwarded to Ergon Energy. Ergon Energy may appoint a representative to be present for inspection and witnessing of tests at any time during the manufacture of the accessories. 9.2 Type Test Compliance Note to Tenderers: Copies of original Type Test certificates / reports shall be included in full in accordance with IEC (including all drawings, revisions and test results as stipulated in the applicable standards as specified in this Specification) with the tender regardless of whether or not the equipment has been supplied previously to Ergon Energy. Where company details have changed with regard to the original Type Testing, and the original Type Testing is submitted, these company details changes shall be detailed in the tender submission, for every company change up to the time of submission of tender. Type Test certificates/reports shall be complete and copies of front pages only shall not be acceptable. Where items of a similar design to that previously tested are offered, consideration may be given to accepting previous Type Test reports. Tenderers are requested to substantiate their claims of equivalent Type Test performance with written engineering evaluation, where full Type Test documentation is not submitted for each of the items offered. Such evaluation must provide all relevant details such that Ergon Energy can establish the validity of existing Type Tests. Ergon Energy requires that all Type Test (for items offered) are certified by a laboratory accredited by an Accreditation Entity. An Accreditation Entity is a signatory to the International Laboratory Accreditation Cooperation (ILAC) Mutual Recognition Arrangement (MRA), for example; the National Association of Testing Authorities, Australia (NATA). Full accreditation details of the Type Testing facilities and the accreditation certifying entity and any mutual recognition arrangements with other accreditation entities shall be provided by the tenderer. Ergon Energy may request repeat of Type Tests to prove compliance to this technical specification where the materials used in the equipment offered and / or the manufacturing process and / or the place of manufacture have changed since the equipment was originally type tested. 9.3 Batch and Routine Tests Note to Tenderers: Check this is the latest Process Zone version before use. Page 23 of 61 Specification ETS Ver 1
27 If tenderers propose to offer items tested to Standards other than those specified in this Specification, full details of these Standards are to be provided at the time of tendering. 9.4 Acceptance Tests Ergon Energy may carry out acceptance tests on an item to prove it conforms to the requirements of this Specification. 9.5 Witnessing of Test Ergon Energy reserves the right to witness all testing. The Supplier shall give Ergon Energy reasonable notice of when testing will be carried out Electrical The Tenderer shall supply joints and terminations that meet the test requirements of the relevant Standards, including AS / NZS 4085 Part 1 and 2 or equivalent, AS / NZS 1660 All Parts, AS / NZS and IEC61442, and shall complete Attachments. The joints and terminations shall withstand the electrical stress associated with continuous operation at the highest system voltage under the environmental conditions described in Clause 6 of this specification. 10. Service Performance Note to Tenderers: Tenderers shall complete schedule L detailing current and previous experience within Australia. 11. Risk Assessment 11.1 Legislation Tenderers must comply with the requirements of the Workplace Health and Safety Act 2011, Queensland Electrical Safety Act 2002 and associated Regulations, Codes of Practice and compliance advisory to Attachment Documentation Tendered items shall be subject to a formal risk assessment. The Plant Code of Practice 2005 requires the Tenderer to perform a risk assessment and provide the resultant documentation to the Purchaser with their tender in accordance with the Risk Assessment schedule (Attachment 3) included with this specification. Where required in the attachment, full details to support answers must be furnished. If the complete risk assessment documentation is not provided with the tender, or does not meet the required standard, the tender may be rejected. Any documented risk assessment that accompanies the tender must meet the requirements of the Risk Management Advisory Standard 2000 as a minimum standard and address the five main steps of the risk management process. It is preferred that the risk assessment methodology uses and energy model to identify hazards. Check this is the latest Process Zone version before use. Page 24 of 61 Specification ETS Ver 1
28 The risk assessment/s shall both state recoended practices and identify hazards to the Corporation s personnel, public and property associated with items offered as follows: Installation Transport, handling and storage Operation and maintenance during life expectancy Dismantling / disposal at end of life The range of uses for which the offered items are intended Effects of environmental conditions The Risk Assessment schedule (Attachment 3) included with this specification shall be completed by the Tenderer. Where required by some questions, full details to support answers shall be furnished. 12. Quality Assurance Note to Tenderers: Tenderers shall complete Schedule MSI detailing their Management Systems (Quality Assurance Systems). 13. Samples Note to Tenderers: Tenderers must submit, when requested, one (1) production samples of each item tendered to assist in the evaluation of the tender. Samples shall be delivered to the address nominated within ten (10) working days of the request. The requirements for samples may be waived for the following conditions: The tendered item is currently under contract or has previously been supplied to Ergon Energy under contract and there have been no changes to the design or material. The tendered items have been supplied to Ergon Energy for approval prior to this tender and there have been no changes to the design or material. Each sample shall be delivered freight free, suitably packaged and labelled with the following information: a) Name of tenderer and this contract No. b) Contract Item Numbers c) Any supporting data on features or characteristics 14. Packaging and Labelling 14.1 Packing The packing requirements are set out in Schedule 10 of the contract (Packing and Transport Requirements). Check this is the latest Process Zone version before use. Page 25 of 61 Specification ETS Ver 1
29 14.2 Marking Each packaged lot and each kit within the packaged lot to be marked with the following information: Marking Required on Each Kit Names of Supplier / Manufacturer Product Code Item Description Purchaser s Stock Code Quantity: 1 Kit Date of Manufacture Use Before Date if applicable Marking Required on Each Packaged Lot Names of Supplier / Manufacturer Product Code Item Description Purchaser s Stock Code Pack Size: No. of Kits Date of Manufacture Pack Mass (kg) 15. Reliability It is expected that items are designed to have a service life of 35 years under the specified system and environmental conditions. Note to Tenderers: Tenderers shall provide evidence in support of the reliability and performance claimed including information of Failure Mode and Effect Analysis with the tender. 16. Training Training material in the form of jointing and terminating kits, drawings, instructions and / or audio visuals may be required for the items accepted under this offer. This material shall include but is not limited to the following topics: Handling Storage Application (particularly in areas of heavy coastal pollution) Installation (including insect protection where applicable) Maintenance Environmental performance Electrical performance Mechanical performance Disposal Check this is the latest Process Zone version before use. Page 26 of 61 Specification ETS Ver 1
30 Tenderers shall provide at their cost, qualified training instructors to undertake training of the Purchaser s cable jointers and other personnel at the coencement of the contract. The training shall be competency based with the successful tenderer being responsible for ensuring that trainees have obtained the required skill for installation of the jointing and terminating materials and that an accreditation certificate is issued to indicate successful completion of the training program. Training shall be allowed for at the following locations: Cairns Townsville Mackay Rockhampton Maryborough Toowoomba 17. Environmental Considerations Note to Tenderers: Tenderers shall complete Schedule R3 Product Environmental Responsibility Questionnaire detailing coents on the environmental soundness of the design / materials; recyclability and disposal at end of service life. 18. Special Tools, Gauges & Accessories Tenderers are advised that the Purchaser and Contractors to the Purchaser have a wide range of general equipment and special tools available to complete the installations. Tenderers shall submit separate details, including price, of any special tools, gauges or accessories that are identified as being necessary for installation and ongoing maintenance procedures. Tools, gauges and accessories that are available from normal coercial outlets should not be included. 19. Information to be Provided 19.1 General The specific technical requirements for the items offered shall be as stated in Schedule A to Schedule H inclusive of this specification. The Tenderer shall provide all details requested by Schedule A to Schedule H and shall guarantee such data. In addition to the completed schedules, Tenders shall submit with their tender one copy of a general jointing instruction together with drawings of not less than ¼ scale fully describing the joints offered. Check this is the latest Process Zone version before use. Page 27 of 61 Specification ETS Ver 1
31 The general jointing instructions shall state the shelf life of the joint kit. Tenderers shall supply one copy of a general terminating instruction including drawings of not less than ¼ scale fully describing the cable terminations with the tender documents. The information shall be of sufficient detail to identify what existing components can be re-used or whether modifications to or new components are required. Tenderers shall provide an estimate of labour hours to complete each joint and termination after cutting of cable(s), in a workshop situation, using experienced jointers Drawings & Information to be supplied by the Successful Tenderer All information to be supplied under this specification shall be in the English language and all drawings shall be dimensioned in metric units in accordance with AS ISO Where a drawing is dimensioned in imperial units, the equivalent metric units shall be shown in brackets adjacent to it. When requested by the Purchaser, the Supplier shall: Provide within two (2) weeks of the date of the formal execution of the Standing Order, a comprehensively detailed program of works indicating timing for all activities required to achieve contract performance. Within six (6) weeks from the date of the formal execution of the Standing Order, the Supplier will provide three copies of drawings and information necessary to enable the Purchaser to examine the general design and arrangement. The Purchaser will coent on drawings supplied under this contract in relation to how the equipment interfaces with the Purchaser s design, construction, operation, maintenance and other requirements. Coents about drawings by the Purchaser will not in any way absolve the Supplier of responsibility for the safety and reliability aspects of the plant or equipment supplied. The Supplier will amend the drawings as directed and resubmit them to the Purchaser within one (1) week. In the event of the Supplier proceeding with work before such coent has been given in writing, any necessary alterations and modifications will be carried out at the Tenderer s own expense. Drawings will include a fully dimensioned general arrangement drawing. If the drawings submitted for approval require modification by either the Supplier or the Purchaser, the Supplier shall carry out the modifications and submit the modified drawings for coent. This procedure shall continue until the Purchaser notifies the Supplier that the drawings are acceptable. When requested by the Purchaser, the Supplier shall supply no later than four weeks prior to the date of dispatch of the equipment from the supplier the following: Final copies of all drawings listed in this section of the specification. Check this is the latest Process Zone version before use. Page 28 of 61 Specification ETS Ver 1
32 Final Inspection and Test Plan covering at minimum the manufacturing and packaging procedures. Certified copies of test reports called for in this specification verifying compliance with this specification. 20. Quality of instructions Provided 20.1 Instruction Title Page The title page of the instructions shall include the following information: Unique document number for the instructions A title of the termination / joint kit. The title shall be a concise description of the kit, including the type of cable it is suitable for (e.g. Single Core XPLE) A table, or other concise form showing the following information: o Termination / joint kit number o Maximum cable diameter () o Insulation Diameter Range () o Cable size (²) o Connector Diameter Range () o Maximum connector length () Revision Number / Letter Revision Date 20.2 Instruction Revisions A revision space shall as a minimum be provided on the title page as per clause Revisions can be indicated by either a number or a letter. The original issue of the instruction is usually indicated as either A or 0, the first revision is therefore B or 1. A revision history shall be included with the instructions, with a description providing brief and concise information as to what has changed between the revisions. The revision history shall contain: The revision letter or number A brief description of the revision The author s initials An approval signature and date 20.3 Instructions in Electronic Format Tenderers shall provide final copies of instructions in electronic format. The purchaser has a preference for instructions to be suppled PDF format. Check this is the latest Process Zone version before use. Page 29 of 61 Specification ETS Ver 1
33 Schedule A Technical Details 33kV Terminations (Indoor & Outdoor) Note to Tenderer: A separate schedule it to be provided for each item offered. Item No. (Refer Annex A) Response Manufacturer s Name and Address Country of Manufacturers Manufacturer s Catalogue No. Type Test Certificate No. Particulars Unit Specified Value / Requirement Response / Guaranteed Value Type Offered Cold / Heat / Premoulded Rated Voltage kv 15 minute dry A.C. Voltage Withstand 15 min at 2.5 U 0 (45kV) No breakdown or flashover 5 minute dry A.C. Voltage Withstand 5 min. at 4.5 U 0 (81kV) No breakdown or flashover (Outdoor Only) A.C. Voltage withstand wet 1 min at 4 U 0 (72kV) No breakdown or flashover 15 minute dry D.C. Voltage Withstand 15 min at 4 U 0 (72kV) No breakdown or flashover Partial Discharge maximum 1.73 U 0 (30kV) 10 pc max. Impulse Level Type of Lug Lug Manufacturer 170kV Mechanical / Compression No breakdown or flashover Check this is the latest Process Zone version before use. Page 30 of 61 Specification ETS Ver 1
34 Lug Manufacturer s part number (Compression Lug Only) Across Flat Distance of the Die Lug Conductor diameter range Tail Lengths Creepage Distance Colour of housing / Sheds Diameter over cable insulation range Detailed Instructions to suit type and voltage included in kits (Indoor Only) Terminal insulation available to suit cable sizes listed in Table 7.1, plus compatible with cable termination components Terminal insulation removable and reusable for testing of switchgear Yes / No Yes / No Yes / No Pack Size Pack Mass Shelf Life Labour estimate to complete termination kg Years hours Name of Tenderer: Signature of Tenderer: Date: Check this is the latest Process Zone version before use. Page 31 of 61 Specification ETS Ver 1
35 Schedule B Technical Details 33kV Joints Note to Tenderer: A separate schedule it to be provided for each item offered. Response Item No. (Refer Annex B) Supplier s Name and Address: Manufacturer s Name and Address Country of Manufacturers Manufacturer s Catalogue No. Applicable drawings including lugs: Type Test Certificate No. Particulars Unit Specified Value / Requirement Response / Guaranteed Value Type Offered Cold / Heat / Premoulded Rated Voltage kv 15 minute dry A.C. Voltage Withstand 15 min at 2.5 U 0 (45kV) No breakdown or flashover 5 minute dry A.C. Voltage Withstand 5 min. at 4.5 U 0 (81kV) No breakdown or flashover 15 minute dry D.C. Voltage Withstand 15 min at 4 U 0 (72kV) No breakdown or flashover Partial Discharge maximum 1.73 U 0 (30kV) 10 pc max. Impulse Level 170kV No breakdown or flashover Check this is the latest Process Zone version before use. Page 32 of 61 Specification ETS Ver 1
36 Type of Connector Mechanical / Compression Connector Manufacturer Connector Manufacturer s part number (Compression Connector Only) Across Flat Distance of the Die Connector Conductor diameter range Creepage Distance Colour of housing / Sheds Diameter over cable insulation range Overall Length of joint Required Pit Length Detailed Instructions to suit type and voltage included in kits Yes / No Pack Size Pack Mass Shelf Life Labour estimate to complete termination kg Years hours Name of Tenderer: Signature of Tenderer: Date: Check this is the latest Process Zone version before use. Page 33 of 61 Specification ETS Ver 1
37 Schedule C Technical Details 22kV Terminations (Indoor & Outdoor) Note to Tenderer: A separate schedule it to be provided for each item offered. Response Item No. (Refer Annex A) Manufacturer s Name and Address Country of Manufacturers Manufacturer s Catalogue No. Type Test Certificate No. Particulars Unit Specified Value / Requirement Response / Guaranteed Value Type Offered Cold / Heat / Premoulded Rated Voltage kv 15 minute dry A.C. Voltage Withstand 15 min at 2.5 U 0 (30kV) No breakdown or flashover 5 minute dry A.C. Voltage Withstand 5 min. at 4.5 U 0 (54kV) No breakdown or flashover (Outdoor Only) A.C. Voltage withstand wet 1 min at 4 U 0 (48kV) No breakdown or flashover 15minute dry D.C. Voltage Withstand 15 min at 4 U 0 (48kV) No breakdown or flashover Partial Discharge maximum 1.73 U 0 (20kV) 10 pc max. Impulse Level Type of Lug Lug Manufacturer 125kV Mechanical / Compression No breakdown or flashover Check this is the latest Process Zone version before use. Page 34 of 61 Specification ETS Ver 1
38 Lug Manufacturer s part number (Compression Lug Only) Across Flat Distance of the Die Lug Conductor diameter range Tail Lengths Creepage Distance Colour of housing / Sheds Diameter over cable insulation range Detailed Instructions to suit type and voltage included in kits (Indoor Only) Terminal insulation available to suit all switchgear listed in Table 7.5and cable sizes listed in Table 7.2, plus compatible with cable termination components Terminal insulation removable and reusable for testing of switchgear Yes / No Yes / No Yes / No Pack Size Pack Mass Shelf Life Labour estimate to complete termination kg Years hours Name of Tenderer: Signature of Tenderer: Date: Check this is the latest Process Zone version before use. Page 35 of 61 Specification ETS Ver 1
39 Check this is the latest Process Zone version before use. Page 36 of 61 Specification ETS Ver 1
40 Schedule D Technical Details 22kV Joints Note to Tenderer: A separate schedule it to be provided for each item offered. Response Item No. (Refer Annex B) Manufacturer s Name and Address Country of Manufacturers Manufacturer s Catalogue No. Type Test Certificate No. Particulars Unit Specified Value / Requirement Response / Guaranteed Value Type Offered Cold / Heat / Premoulded Rated Voltage kv 15 minute dry A.C. Voltage Withstand 15 min at 2.5 U 0 (30kV) No breakdown or flashover 5 minute dry A.C. Voltage Withstand 5 min. at 4.5 U 0 (54kV) No breakdown or flashover 15 minute dry D.C. Voltage Withstand 15 min at 4 U 0 (48kV) No breakdown or flashover Partial Discharge maximum 1.73 U 0 (20kV) 10 pc max. Impulse Level Type of Connector Connector Manufacturer Connector Manufacturer s part number 125kV Mechanical / Compression No breakdown or flashover Check this is the latest Process Zone version before use. Page 37 of 61 Specification ETS Ver 1
41 (Compression Connector Only) Across Flat Distance of the Die Connector Conductor diameter range Creepage Distance Colour of housing / Sheds Diameter over cable insulation range Overall length Required Pit Length Detailed Instructions to suit type and voltage included in kits Yes / No Pack Size Pack Mass Shelf Life Labour estimate to complete termination kg Years hours Name of Tenderer: Signature of Tenderer: Date: Check this is the latest Process Zone version before use. Page 38 of 61 Specification ETS Ver 1
42 Schedule E Technical Details 11kV Terminations (Indoor & Outdoor) Note to Tenderer: A separate schedule it to be provided for each item offered. Response Item No. (Refer Annex A) Manufacturer s Name and Address Country of Manufacturers Manufacturer s Catalogue No. Type Test Certificate No. Particulars Unit Specified Value / Requirement Response / Guaranteed Value Type Offered Cold / Heat / Premoulded Rated Voltage kv 15 minute dry A.C. Voltage Withstand 15 min at 2.5 U 0 (15kV) No breakdown or flashover 5 minute dry A.C. Voltage Withstand 5 min. at 4.5 U 0 (27kV) No breakdown or flashover (Outdoor Only) A.C. Voltage withstand wet 1 min at 4 U 0 (24kV) No breakdown or flashover 15 minute dry D.C. Voltage Withstand 15 min at 4 U 0 (24kV) No breakdown or flashover Partial Discharge maximum 1.73 U 0 (10kV) 10 pc max. Impulse Level Type of Lug Lug Manufacturer 95kV Mechanical / Compression No breakdown or flashover Check this is the latest Process Zone version before use. Page 39 of 61 Specification ETS Ver 1
43 Lug Manufacturer s part number (Compression Lug Only) Across Flat Distance of the Die Lug Conductor diameter range Tail Lengths Creepage Distance Colour of housing / Sheds Diameter over cable insulation range Detailed Instructions to suit type and voltage included in kits (Indoor Only) Terminal insulation available to suit all switchgear listed in Table 7.6 and cable sizes listed in Table 7.3, plus compatible with cable termination components Terminal insulation removable and reusable for testing of switchgear Yes / No Yes / No Yes / No Pack Size Pack Mass Shelf Life Labour estimate to complete termination kg Years hours Name of Tenderer: Signature of Tenderer: Date: Check this is the latest Process Zone version before use. Page 40 of 61 Specification ETS Ver 1
44 Check this is the latest Process Zone version before use. Page 41 of 61 Specification ETS Ver 1
45 Schedule F Technical Details 11kV Joints Note to Tenderer: A separate schedule it to be provided for each item offered. Response Item No. (Refer Annex B) Manufacturer s Name and Address Country of Manufacturers Manufacturer s Catalogue No. Type Test Certificate No. Particulars Unit Specified Value / Requirement Response / Guaranteed Value Type Offered Cold / Heat / Premoulded Rated Voltage kv 15 minute dry A.C. Voltage Withstand 15 min at 2.5 U 0 (15kV) No breakdown or flashover 5 minute dry A.C. Voltage Withstand 5 min. at 4.5 U 0 (27kV) No breakdown or flashover 15 minute dry D.C. Voltage Withstand 15 min at 4 U 0 (24kV) No breakdown or flashover Partial Discharge maximum 1.73 U 0 (10kV) 10 pc max. Impulse Level Type of Connector Connector Manufacturer Connector Manufacturer s part number 95kV Mechanical / Compression No breakdown or flashover Check this is the latest Process Zone version before use. Page 42 of 61 Specification ETS Ver 1
46 (Compression Connector Only) Across Flat Distance of the Die Connector Conductor diameter range Creepage Distance Colour of housing / Sheds Diameter over cable insulation range Overall Length Required Pit Length Detailed Instructions to suit type and voltage included in kits Yes / No Pack Size Pack Mass Shelf Life Labour estimate to complete termination kg Years hours Name of Tenderer: Signature of Tenderer: Date: Check this is the latest Process Zone version before use. Page 43 of 61 Specification ETS Ver 1
47 Schedule G Technical Details LV Terminations Note to Tenderer: A separate schedule it to be provided for each item offered. Response Item No. (Refer Annex B) Manufacturer s Name and Address Country of Manufacturers Manufacturer s Catalogue No. Type Test Certificate No. Particulars Unit Specified Value / Requirement Response / Guaranteed Value Type Offered Cold / Heat / Premoulded Rated Voltage kv 5 minute dry A.C. Voltage Withstand 5 min. at 3.5kV No breakdown or flashover Insulation Resistance MΩ 1000 MΩ Type of Connector Mechanical / Compression Connector Manufacturer Connector Manufacturer s part number (Compression Connector Only) Across Flat Distance of the Die Connector Conductor diameter range Creepage Distance Check this is the latest Process Zone version before use. Page 44 of 61 Specification ETS Ver 1
48 Colour of housing / Sheds Diameter over cable insulation range Detailed Instructions to suit type and voltage included in kits Yes / No Pack Size Pack Mass Shelf Life Labour estimate to complete termination kg Years hours Name of Tenderer: Signature of Tenderer: Date: Check this is the latest Process Zone version before use. Page 45 of 61 Specification ETS Ver 1
49 Schedule H Technical Details LV Joints Note to Tenderer: A separate schedule it to be provided for each item offered. Response Item No. (Refer Annex B) Manufacturer s Name and Address Country of Manufacturers Manufacturer s Catalogue No. Type Test Certificate No. Particulars Unit Specified Value / Requirement Response / Guaranteed Value Type Offered Cold / Heat / Premoulded Rated Voltage kv 5 minute A.C. Voltage Withstand 5 min. at 3.5kV No breakdown or flashover Insulation Resistance MΩ 1000 MΩ Type of Connector Mechanical / Compression Connector Manufacturer Connector Manufacturer s part number (Compression Connector Only) Across Flat Distance of the Die Connector Conductor diameter range Creepage Distance Check this is the latest Process Zone version before use. Page 46 of 61 Specification ETS Ver 1
50 Colour of housing / Sheds Diameter over cable insulation range Overall Length Required Pit Length Detailed Instructions to suit type and voltage included in kits Yes / No Pack Size Pack Mass Shelf Life Labour estimate to complete termination kg Years hours Name of Tenderer: Signature of Tenderer: Date: Check this is the latest Process Zone version before use. Page 47 of 61 Specification ETS Ver 1
51 and Jointing Materials for Underground Electrical Annex A. Cable Terminations Normative Item Stock code Termination to Suit Ellipse description Cable description Notes: 0.6 / 1kV Indoor Termination Indoor termination Neutral screened PVC cable. TERMINATION KIT,ELECTRICAL CABLE Underground, Indoor, LV, Cu, Neutral Screened PVC Insulated, Nylon Jacket, Insect Protection, PVC Sheathed Cable (scm) 0.6/1kV Cu, Neutral Screened PVC Insulated, Nylon Jacket, Insect Protection, PVC Sheathed , / 1kV Outdoor Terminations Outdoor termination includes cable termination, Cu links TERMINATION KIT,ELECTRICAL CABLE Outdoor, 0.6/1kV, 162, 4C XLPE Cable, Insect Protected, Containing 4 Way Glove 4 x Tubing, Colour Coding Red White & Blue, 4 x 162 Cu Crimp Links, 162 Cu 4 core XLPE with and without insect protection & IP Contains accessories to provide Insect Protection to completed joint Outdoor termination includes cable termination, bi-metal lugs, lug seals. TERMINATION KIT,ELECTRICAL CABLE Outdoor, Heat Shrink, 0.6/1kV, 502, 4 Core XLPE, Nylon Jacket Cable (incl. insect protected) c/w 4 Way Glove, 4 x Tubing, Red White & Blue Colour core Cu XLPE with insect protection Contains accessories to provide Insect Protection to completed joint Outdoor termination includes cable termination, bi-metal lugs, lug seals. TERMINATION KIT,ELECTRICAL CABLE Outdoor, LV, 2402 Al, 4 Core Sector XLPE Cable, Insect Protected c/w Cable Term kit Solvent Wipes, Cable Lugs, EPS0021 ver2 (scm) 2402 Al 4 core XLPE with or without insect protection & IP 6.35 / 11kV Indoor Terminations Check this is the latest Process Zone version before use. Page 48 of 61 Specification ETS Ver 1
52 and Jointing Materials for Underground Electrical Item Stock code Termination to Suit Ellipse description Cable description Notes: Feeder cables ABB Safelink Switchgear includes cable termination, cable conductor bi-meatal lugs (or Cu lugs for Cu cable) c/w bolts, nuts and washers, and cable screen lugs c/w/ bolts, nuts and washers TERMINATION KIT INDOOR 11kV, 352, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, 11kV ABB SafeLink RMU, Inc Cable Term Kit, Cable Core & Screen Lugs Fixings, Spec EPS0075 (scm) 352 Al Triplex XLPE Not suitable for DBT cable (perhaps could be made to be?) (in Manual) Feeder cables - ABB SD Series Switchgear. Includes cable termination, bushing insulation, cable conductor bi-metal lugs (or Cu lugs for CU cable) c/w bolts nuts and washers and cable screen lugs c/w bolts nuts and washers. TERMINATION KIT INDOOR 11kV, 352, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, 11kV ABB SD Series RMU, Inc Cable Term Kit, Solvent Wipes Bushing Insulation, Cable Core & Screen 352 Al Triplex XLPE Not suitable for cable Feeder cables ABB Safelink Switchgear includes cable termination, cable conductor bi-meatal lugs c/w bolts, nuts and washers, and cable screen lugs c/w/ bolts, nuts and washers TERMINATION KIT INDOOR 11kV, 352, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, Insect Protected, 11kV ABB SafeLink RMU, Inc Cable Term Kit, Cable Core & Screen Lugs & Fixings, 352 Al Triplex XLPE with insect protection Bushing insulation supplied with padmount not with termination kit. Not suitable for DBT cable Feeder cables - Transformer bushing connection - padmounted substation (no HV Switchgear) includes cable termination, connection kit, cable screen lugs c/w bolts nuts and washers. Feeder cables - ABB SD Series Switchgear. Includes cable termination, bushing insulation, cable conductor bi-metal lugs c/w/bolts nuts and washers and cable screen lugs c/w bolts nuts and washers TERMINATION KIT INDOOR 11kV, 352, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, Insect Protected, 11kV ABB SD Series RMU, Inc Cable Term Kit, Bush Insulation, Cable Core &Screen 352 Al Triplex XLPE with insect protection Not suitable for DBT cable Check this is the latest Process Zone version before use. Page 49 of 61 Specification ETS Ver 1
53 and Jointing Materials for Underground Electrical Item Stock code Termination to Suit Ellipse description Cable description Notes: Feeder cables - Magnefix MD Series switchgear includes cable termination, connection kit, cable screen lugs c/w bolts nuts and washers and cable support clamps TERMINATION KIT INDOOR 11kV, 352, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, Insect Protected, 11kV Magnefix MD Series RMU, Inc Cable Term Kit Holec /3 Connection Kit 352 Al triplex XLPE with insect protection Not suitable for DBT cable Feeder Cables - Areva FBX Switchgear. Includes cable termination elbows, shear bolt connectors c/w cable screen lugs, bolts nuts and washers CONNECTOR ELBOW Set of 3, 630A, Bolted, suit 11kV 1 Core XLPE Cable, Shear Bolt Connectors, for Areva HV Switchgear (scm) 352 Al triplex XLPE Al triplex XLPE with insect protection NJ, , DBT, Feeder cables ABB Safelink Switchgear includes cable termination, cable conductor bi-metal lugs c/w bolts, nuts and washers, and cable screen lugs c/w/ bolts, nuts and washers TERMINATION & CONNECTION KIT 11kV 1852 Al (1C wound 3 in hand) XLPE Cable IINo for 11kV ABB SafeLink RMU Including Cable Termination Kit Cable Core & Screen Lugs Fixings EPS0077 (scm) 1852 Al triplex & Bushing insulation supplied with padmount not with termination kit Feeder cables - Transformer bushing connection - padmounted substation (no HV Switchgear) includes cable termination, connection kit, cable screen lugs c/w bolts nuts and washers. Also Feeder cables - Magnefix MD Series switchgear includes cable termination, connection kit, cable screen lugs c/w bolts nuts and washers and cable support TERMINATION & CONNECTION KIT 11kV 1852 Al Triplex (1C wound 3 in hand) XLPE Cable for 11kV Magnefix MD Series RMU &SFU. Inc Cable Term kit solv wipes Holec Connection Kit Cable (scm 1852 Al triplex & Feeder cables - ABB SD Series Switchgear. Includes cable termination, bushing insulation, cable conductor bi-metal lugs (or Cu lugs for CU cable) c/w/bolts nuts and washers and cable screen lugs c/w bolts nuts and washers. TERMINATION & CONNECTION KIT, 11kV, 1852 Al, Triplex (1C wound 3 in hand) XLPE Cable, for 11kV ABB SD Series RMU, Inc Cable Termination kit & Bushing Insulation, Cable Core & Screen Lugs 1852 Al triplex & Check this is the latest Process Zone version before use. Page 50 of 61 Specification ETS Ver 1
54 and Jointing Materials for Underground Electrical Item Stock code Termination to Suit Ellipse description Cable description Notes: Feeder cables ABB Safelink Switchgear includes cable termination, cable conductor bi-meatal lugs (or Cu lugs for Cu cable) c/w bolts, nuts and washers, and cable screen lugs c/w/ bolts, nuts and washers TERMINATION & CONNECTION KIT 11kV 1852 Al (1C wound 3 in hand) XLPE Insect Protected Cable IINo for 11kV ABB SafeLink RMU Including Cable Termination Kit Cable Core & Screen Lugs 1852 Al triplex with insect protection DBT & NJ Bushing insulation supplied with padmount not with termination kit Feeder cables - ABB SD Series Switchgear. Includes cable termination, bushing insulation, cable conductor bi-metal lugs (or Cu lugs for CU cable) c/w bolts nuts and washers and cable screen lugs c/w bolts nuts and washers. TERMINATION & CONNECTION KIT, 11kV, 1852 Alu, Triplex (1C wound 3 in hand) XLPE Cable Insect Protected, for 11kV ABB SD Series RMU, Inc. Cable Term kit & Bushing Insulation, Cable Core & (scm) 1852 Al triplex with insect protection DBT & NJ Feeder Cables - Areva FBX Switchgear. Includes cable termination elbows, shear bolt connectors c/w cable screen lugs, bolts nuts and washers CONNECTOR ELBOW Set of 3, 630A, Bolted, suit 11kV 1 Core XLPE Cable, Shear Bolt Connectors, for Areva HV Switchgear (scm) 1852 Al triplex XLPE Al triplex XLPE with insect protection & IP Feeder cables - Magnefix MD Series switchgear includes cable termination, connection kit, cable screen lugs c/w bolts nuts and washers and cable support clamps. Also Feeder cables - Transformer bushing connection - padmounted substation (no HV Switchgear) includes cable termination, connection kit, cable screen lugs c/w bolts nuts and washers. TERMINATION&CONNECTION KIT 11kV 1852 Al Triplex (1C wound 3 in hand) XLPE Cable Insect Protected, for 11kV Magnefix MD Series RMU, Inc Cable Term kit, Holec Connection Kit Cable 1852 Al triplex XLPE with insect protection. Provided with extra mastic to allow use with DBT or Nylon IP & Check this is the latest Process Zone version before use. Page 51 of 61 Specification ETS Ver 1
55 and Jointing Materials for Underground Electrical Item Stock code Termination to Suit Ellipse description Cable description Notes: Feeder cables ABB Safelink Switchgear includes cable termination, cable conductor bi-meatal lugs (or Cu lugs for Cu cable) c/w bolts, nuts and washers, and cable screen lugs c/w/ bolts, nuts and washers TERMINATION KIT,ELECTRICAL CABLE 11kV, 4002, Al, 3 x 1 Core Triplex, TR-XLPE Cable (3 per Set) to suit Cable IIN for 11kV ABB SafeLink RMU incl Cable Termination Kit, Cable Core & 4002 Al Triplex Feeder cables ABB Safelink Switchgear includes cable termination, cable conductor bi-meatal lugs c/w bolts, nuts and washers, and cable screen lugs c/w/ bolts, nuts and washers TERMINATION KIT,ELECTRICAL CABLE 11kV, 4002, Al, 3 x 1 Core Triplex, TR-XLPE Cable, Insect Protected (3 per Set) to suit Cable IIN for 11kV ABB SafeLink RMU incl Cable Termination 4002 Al Triplex with insect protection Feeder Cables - Areva FBX Switchgear. Includes cable termination elbows, shear bolt connectors c/w cable screen lugs, bolts nuts and washers CONNECTOR ELBOW Set of 3, 630A, Bolted, suit 11kV 1 Core 4002 XLPE Cable, Compression Type Connectors, for Areva HV Switchgear (scm) 4002 Al triplex Al triplex with insect protection & IP Feeder cables - Transformer bushing connection - padmounted substation (no HV Switchgear) includes cable termination, connection kit, cable screen lugs c/w bolts nuts and washers. TERMINATION&CONNECTION KIT 11kV 2402 Cu Triplex (1C wound 3 in hand) XLPE Cable Insect Protected, connect to 11kV Bushings of P/mounted Sub, Inc Cable Term kit, Holec /3 Kit Cable 2402 Cu Triplex XLPE with insect protection. Provided with extra mastic to allow use with DBT or Nylon IP NJ, , DBT Feeder cables ABB Safelink Switchgear includes cable termination, cable conductor, Cu lugs for Cu cable c/w bolts, nuts and washers, and cable screen lugs c/w/ bolts, nuts and washers TERMINATION & CONNECTION KIT 11kV 2402 Cu 1C XLPE Insect Protected Cable IINo for 11kV ABB SafeLink RMU Including Cable Termination Kit Cable Core & Screen Lugs Fixings EPS0078 (scm) 2402 Cu Triplex XLPE with insect protection DBT, NJ Check this is the latest Process Zone version before use. Page 52 of 61 Specification ETS Ver 1
56 and Jointing Materials for Underground Electrical Item Stock code Termination to Suit Ellipse description Cable description Notes: Feeder cables - ABB SD Series Switchgear. Includes cable termination, bushing insulation, cable conductor bi-metal lugs (or Cu lugs for CU cable) c/w bolts nuts and washers and cable screen lugs c/w bolts nuts and washers. TERMINATION & CONNECTION KIT 11kV 2402 Cu Triplex (1 C wound 3 in hand) XLPE Cable Insect Protected for 11kV ABB SD Series RMU, Inc Cable Termination kit & Bushing Insulation, Cable Core & (scm) 11kV 2402 Cu Triplex (1 C wound 3 in hand) XLPE Cable Insect Protected. This kit has a special 240 lug which has a longer palm DBT, NJ This kit has a special 240 lug which has a longer palm Feeder cables ABB Safelink Switchgear includes cable termination, cable conductor, Cu lugs c/w bolts, nuts and washers, and cable screen lugs c/w/ bolts, nuts and washers TERMINATION & CONNECTION KIT 11kV 4002 Cu 1C XLPE Insect Protected Cable IINo for 11kV ABB SafeLink RMU Including Cable Termination Kit & Bushing Insulation Cable Core & Screen 4002 Cu 1 core XLPE Insect protected & Contains accessories to suit Nylon Jacket insect protection and semiconductive oversheath / 11kV Outdoor Terminations Outdoor Termination includes cable termination, cable conductor bi-metal lugs, cable screen lugs TERMINATION KIT OUTDOOR 11kV, 352, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, Inc Cable Term Kit Solvent Wipes, Cable Core & Screen Lugs, Spec EPS0025 (scm) 352 Al triplex Outdoor Termination includes cable termination, cable conductor bi-metal lugs, cable screen lugs TERMINATION KIT OUTDOOR 11kV, 352, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, Insect Protected, Inc Cable Term Kit Solvent Wipes, Cable Core & Screen Lugs, Spec EPS0035 (scm) 352 Al triplex with insect protection Outdoor Termination includes cable termination, cable conductor bi-metal lugs, cable screen lugs TERMINATION KIT OUTDOOR 11kV 1852 Al Triplex (1 C wound 3 in hand) XLPE Cable. Including Cable Termination kit solvent wipes Cable Core Lugs Cable Screen Lug, Ergon Purchasing Spec. (scm) 1852 Al triplex XLPE Check this is the latest Process Zone version before use. Page 53 of 61 Specification ETS Ver 1
57 and Jointing Materials for Underground Electrical Item Stock code Termination to Suit Ellipse description Cable description Notes: Outdoor Termination includes cable termination, cable conductor bi-metal lugs, cable screen lugs Outdoor Termination includes cable termination, cable conductor bi-metal lugs, cable screen lugs Outdoor Termination includes cable termination, cable conductor bi-metal lugs, cable screen lugs Outdoor Termination includes cable termination, cable conductor lugs, Cu lugs for Cu cable, cable screen lugs TERMINATION KIT OUTDOOR 11kV, 1852, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, Insect Protected, Inc Cable Term Kit Solvent Wipes, Cable Core & Screen Lugs, Spec EPS0036 (scm) TERMINATION KIT,ELECTRICAL CABLE Outdoor, 11kV, 4002, Al, 3 x 1 Core Triplex, TR-XLPE Cable (3 per Set) c/w Cable Term Kit Solvent Wipes, Cable Core & Screen Lugs, For cable (scm) TERMINATION KIT,ELECTRICAL CABLE Outdoor, 11kV, 4002, Al, 3 x 1 Core Triplex, TR-XLPE Cable, Insect Protected (3 per Set) c/w Cable Term Kit Solvent Wipes, Cable Core & Screen Lugs TERMINATION KIT,ELECTRICAL CABLE Outdoor, 11kV, 2402 Cu Triplex, 1 C wound 3 in hand, XLPE Cable Insect Protected c/w Cable Term Kit Solvent Wipes, Cable Core Lugs, Cable Screen lugs 1852 Al triplex XLPE with insect protection Al Triplex XLPE Al Triplex XLPE with insect protection kV 2402 Cu Triplex (1 C wound 3 in hand) XLPE Cable Insect Protected. Provided with extra mastic to allow use with DBT or Nylon IP DBT, NJ Outdoor Termination includes cable termination, cable conductor Cu lugs, cable screen lugs TERMINATION KIT,ELECTRICAL CABLE Outdoor, 11kV, 4002 Cu, 1 Core, XLPE Insect Protected c/w Cable Term Kit Cable Core & Screen Lugs, EPS0055, suit Cable (scm) 4002 Cu 1 core XLPE Insect protected NJ, NJ 12.7 / 22kV Indoor Terminations (Connector Elbows & Deadbreak Elbow Kits) Feeder Cable - Transformer bushing connection - padmounted substation (no HV Switchgear) 200A Deadbreak elbow CONNECTOR ELBOW 200A, to suit QESI 22kV 352 Al, 3 x 1C XLPE Cable (Single Elbow Kit Only) Transformer & RMU Terminations, Elastimold 156LR-F-220 (scm) 352 AL Triplex XLPE with insect protection (DBT) , NJ Check this is the latest Process Zone version before use. Page 54 of 61 Specification ETS Ver 1
58 and Jointing Materials for Underground Electrical Item Stock code Termination to Suit Ellipse description Cable description Notes: Feeder cables - F&G/Ormazabal switchgear connection. 630A Deadbreak bolted elbow connector assembly. Feeder Cable - Transformer bushing connection - padmounted substation (no HV Switchgear) 200A Deadbreak elbow Feeder cables - F&G/Ormazabal switchgear connection. 630A Deadbreak bolted elbow connector assembly. Feeder cables - F&G/Ormazabal switchgear connection. 630A Deadbreak bolted elbow connector assembly. CONNECTOR ELBOW Set of 3, 630A, Bolted, suit 22kV 1 Core 352 Al, XLPE Cable, Insect Protected Cable Double Brass Tape, F & G Type CB (scm) CONNECTOR ELBOW 400A to suit 1852 Cable (Single Elbow) Elastimold K400LRG-HB- 185km-12-1 CONNECTOR ELBOW Set of 3, 630A, Bolted, suit 22kV 1 Core 1852 Al XLPE Cable, Sudkabel (scm) CONNECTOR ELBOW 200A Deadbreak, to suit 22kV 1852 Al 1C XLPE Cable, Transformer Termination Lug suit 952 Conductor (Single Elbow Kit Only) Elastimold 156LR-J-260 (scm) CONNECTOR ELBOW Set of 3, 630A, Bolted, suit 22kV 1 Core 1852 Al XLPE Cable, Sudkabel (scm) CONNECTOR ELBOW Set of 3, 630A, Bolted, suit 22kV 1C 6302 Al XLPE Cable, F & G Type AST20/630, w/o Metal Housing Code No (scm) 352 AL Triplex XLPE with insect protection (DBT) AL Triplex XLPE with Laminated Aluminium Tape (LAT) , AL Triplex XLPE with Laminated Aluminium Tape (LAT) , AL Triplex XLPE with Laminated Aluminium Tape (LAT). Earthing of LAT is not required , AL Triplex XLPE with Laminated Aluminium Tape (LAT). Earthing of LAT is not required , AL Triplex XLPE with Laminated Aluminium Tape (LAT). Earthing of LAT is not required & Earthing of LAT is not required. Earthing of LAT is not required. Earthing of LAT is not required / 22kV Outdoor Terminations Check this is the latest Process Zone version before use. Page 55 of 61 Specification ETS Ver 1
59 and Jointing Materials for Underground Electrical Item Stock code Termination to Suit Ellipse description Cable description Notes: Outdoor termination. Includes cable termination, cable conductor, bi-metal lugs, cable screen lug Outdoor termination. Includes cable termination, cable conductor, bi-metal lugs, cable screen lug Outdoor termination. Includes cable termination, cable conductor, bi-metal lugs, cable screen lug TERMINATION KIT OUTDOOR 22kV, 352, Al, Triplex (1C wound 3 in hand) TR-XLPE Cable, Insect Protected, Inc Cable Term Kit Solvent Wipes, Cable Core & Screen Lugs, Spec EPS0005 (scm) TERMINATION KIT,ELECTRICAL CABLE Outdoor, 22kV, 1852 Al Triplex 1C Cable wound 3 in hand, XLPE Cable c/w Cable Term Kit Solvent Wipes, Cable Core Lugs, Cable Screen Lug (scm) TERMINATION KIT,ELECTRICAL CABLE Outdoor, 22kV, 6302, Al, 1 Core Cable XLPE Cable c/w Cable Termination Kit Solvent Wipes, Cable Core Lugs, Cable Screen Lug, EPS 0037 (scm) 352 Al Triplex XLPE with insect protection AL Triplex XLPE with Laminated Aluminium Tape (LAT). Earthing of LAT is not required , AL Triplex XLPE with Laminated Aluminium Tape (LAT). Earthing of LAT is not required & Earthing of LAT is not required. Earthing of LAT is not required / 33kV Outdoor Terminations Outdoor termination. Includes cable termination, cable conductor, bi-metal lugs, cable screen lug TERMINATION KIT,ELECTRICAL CABLE Outdoor, 19.1/33kV, 502, Al, 1 Core, TR-XLPE Cable, Insect Protected (3 per Set) c/w Cable Term Kit Solvent Wipes, Cable Core & Screen Lugs, 502 Al 1 core Outdoor termination. Includes cable termination, cable conductor, bi-metal lugs, cable screen lug TERMINATION KIT,ELECTRICAL CABLE Outdoor, 19.1/33kV, 3002, Al, 1 Core, TR- XLPE Cable, Insect Protected, (3 per Set) c/w Cable Term Kit Solvent Wipes, Cable Core & Screen Lugs, 3002 Al 1 core Check this is the latest Process Zone version before use. Page 56 of 61 Specification ETS Ver 1
60 and Jointing Materials for Underground Electrical Annex B. Cable Joints Normative Item Stock code 0.6/1kV Joint Straight Joints Joint to Suit Ellipse description Cable Description Notes: Underground straight joint includes cable joint kit, links. JOINT ELECTRICAL CABLE UNDERGROUND LV, 2402 Al 4 Core Sector XLPE Cable Insect Protected c/w Cable Joint Kit, Cable Links, EE Purchase Spec. EPS0011 (scm) 2402 Al 4 core XLPE with insect protection Underground straight joint includes cable joint kit, links. JOINT ELECTRICAL CABLE UNDERGROUND LV, 2402 Al 4 Core Sector XLPE Cable, c/w Cable Joint Kit, Cable Links, EE Purchase Spec. EPS0009 (scm) 2402 Al 4 core XLPE Underground straight joint includes cable joint kit, links. JOINT ELECTRICAL CABLE UNDERGROUND LV, 162 Stranded Cu 4 Core XLPE Cable, c/w Cable Joint kit Cable Crimp Links Suit 6.3 A/F Hex Dies Kit, Include Solvent Wipes, Installation Instructions 162 Cu 4 core XLPE Underground straight joint includes cable joint kit, links. JOINT ELECTRICAL CABLE UNDERGROUND LV, 162 Cu 4 Core Sector XLPE Cable Insect Protected c/w Cable Joint Kit, Cable Links, EE Purchase Spec. EPS0030 (scm) 162 Cu 4 core XLPE with insect protection cable 6.35/11kV Joints Check this is the latest Process Zone version before use. Page 57 of 61 Specification ETS Ver 1
61 and Jointing Materials for Underground Electrical Item Stock code Joint to Suit Ellipse description Cable Description Notes: JOINT,ELECTRICAL POWER CABLE 11kV, 352 Al Triplex, 1C wound 3 in hand, XLPE Cable c/w Cable Joint Kit Solvent Wipes, Mechanical Cable Connectors, Cable Screen Links (scm) JOINT,ELECTRICAL POWER CABLE 11kV, 352 Al Triplex, 1C wound 3 in hand, XLPE Cable, Insect Protected c/w Cable Joint Kit Solvent Wipes, Mechanical Cable Connectors, Cable Screen Links JOINT,ELECTRICAL POWER CABLE 11kV, 1852 Al Triplex, 1C wound 3 in hand, XLPE Cable c/w Cable Joint Kit Solvent Wipes, Connectors, Cable Screen Links, EPS 0015 JOINT,ELECTRICAL POWER CABLE 11kV, 1852 Al Triplex, 1C wound 3 in hand, XLPE Cable, Insect Protected c/w Cable Joint Kit Solvent Wipes, Connectors, Cable Screen Links JOINT ELECTRICAL CABLE UNDERGROUND 11kV, 4002 Al, 3 x 1 Core Triplex, TR-XLPE Cable (3 per Set)c/w Cable Joint Kit Solvent Wipes, Cable Links, Cable Screen Links, suit cable (scm) JOINT ELECTRICAL CABLE UNDERGROUND 11kV, 4002 Al, 3 x 1 Core Triplex, TR-XLPE Cable, Insect Protected (3 per Set) c/w Cable Joint Kit Solvent Wipes, Cable Links, Cable Screen Links, 352 AL Triplex XLPE , AL Triplex XLPE with insect protection , Al triplex XLPE , Al triplex XLPE with insect protection , Al triplex Al triplex with insect protection Check this is the latest Process Zone version before use. Page 58 of 61 Specification ETS Ver 1
62 and Jointing Materials for Underground Electrical Item Stock code Joint to Suit Ellipse description Cable Description Notes: JOINT ELECTRICAL CABLE UNDERGROUND 11kV, 2402 Cu Triplex 1 C wound 3 in hand XLPE Cable Insect Protected c/w Cable Joint kit solvent wipes Cable Links Cable Screen Links (scm) JOINT,ELECTRICAL POWER CABLE 11kV, 4002 Cu, 1C, XLPE, Insect Protected (Set of 3), Cable Joint Kit 4002 Cu, Connectors, EPS 0080 (scm) 11kV 2402 Cu Triplex (1 C wound 3 in hand) XLPE Cable Insect Protected. Provided with extra mastic to allow use with DBT or Nylon IP DBT, NJ 4002 Cu 1 Core XLPE insect protected , / 22kV Joint JOINT,ELECTRICAL POWER CABLE 22kV, 352 Al Triplex, 1C wound 3 in hand, XLPE Cable, Insect Protected c/w Cable Joint Kit Solvent Wipes, Mechanical Cable Connectors, Cable Screen Links 352 Al triplex XLPE with insect protection JOINT,ELECTRICAL POWER CABLE 22kV, 1852 Al Triplex, 1C wound 3 in hand, XLPE Cable c/w Cable Joint Kit Solvent Wipes, Mechanical Cable Connectors, Cable Screen Links (scm) 1852 Al triplex XLPE Transition joint 1852 Paper lead to 1852 XLPE JOINT,ELECTRICAL POWER CABLE 22kV, 6302 Al Triplex, 1C, XLPE Cable, Insect Protected c/w Cable Joint Kit Solvent Wipes, Mechanical Cable Connectors, Cable Screen Links (scm) JOINT KIT 3M, Cold Shrink, Transition Joint, T/S 1C, 22kV, 185SQMM, PLY/XLPE 6302 Al 1 core XLPE Paper lead to kV XLPE cable joint Transition Joint 19.1/33kV Joints Check this is the latest Process Zone version before use. Page 59 of 61 Specification ETS Ver 1
63 and Jointing Materials for Underground Electrical Item Stock code Joint to Suit Ellipse description Cable Description Notes: JOINT ELECTRICAL CABLE UNDERGROUND 19.1/33kV, 502 Al, 1 Core, TR-XLPE Cable, Insect Protected (3 per Set) c/w Cable Joint Kit Solvent Wipes, Cable Links, Cable Screen Links, 502 Al 1 core insect protected JOINT ELECTRICAL CABLE UNDERGROUND 19.1/33kV, 3002 Al, 1 Core, TR-XLPE Cable, Insect Protected (3 per Set) c/w Cable Joint Kit Solvent Wipes, Cable Links, Cable Screen Links, 3002 Al 1 core insect protected Check this is the latest Process Zone version before use. Page 60 of 61 Specification ETS Ver 1
64 Annex C. Cable Cross Section Drawings C.1 33kV Cables 33kV pdf 33kV pdf C.2 22kV Cables 22kV pdf 22kV pdf 22kV XLNA18TB003.pdf 22kV pdf C.3 11kV Cables 11kV pdf 11kV pdf 11kV Midland Metals 2010v 11kV pdf 11kV pdf 11kV pdf 11kV pdf 11kV pdf 11kV XJNA18TB003.pdf 11kV XJNA25TB003.pdf 11kV XJNP26TB003.pdf 11kV 2402 Cu 3core IP.pdf C.4 LV Cables LV pdf LV pdf LV pdf LV pdf LV XDDS23AA004CXAA.p LV pdf LV pdf Check this is the latest Process Zone version before use. Page 61 of 61 Specification ETS Ver 1
65 Annex D. Cable Termination Constructions D.1 33kV Cable Termination 33kV Cable Termination Construc D.2 22kV Cable Termination 22kV Cable Termination Construc D.3 11kV Cable Termination 11kV Cable Termination Construc Check this is the latest Process Zone version before use. Page 62 of 61 Specification ETS Ver 1
Network Standard Advice No. 1420C 9/6/2011
Network Standard Advice No. 1420C 9/6/2011 TO: Customers, Service Providers and Ausgrid Staff. Advisory Note on Changes to the Use of 11kV Cable Types. Introduction This Network Standard Advice (NSA) provides
SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.
SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/HTXLPE/2006) MAHARASHTRA STATE ELECTRICITY DISTRIBUTION CO.LTD.
UGVCL/SP/591/11KV HT AB CABLE
TECHNICAL SPECIFICATION FOR 11KV AERIAL BUNCHED CABLES FOR OVERHEAD LINES (CROSSED LINKED POLYTHENE DRY GAS CURED) 1. SCOPE This specification covers requirements of XLPE insulated, 11 KV Aerial Bunched
ScottishPower Distribution Cables & Equipment. Metal Theft
ScottishPower Distribution Cables & Equipment Metal Theft April 2012 As an aid to deterring to metal theft this booklet has been put together to help identify the types of utility power cables and associated
Cables, Cable Laying & Accessories Manual
Distribution Business Cables, Cable Laying & Accessories Manual Database ref: File Ref: Title Page & Revision Log For Cables & Access v4 - Nov 2003.doc Manual Name: Cables & Accessories Manual Version
CONFLEX ELECTRIC CABLE
CONFLEX ELECTRIC CABLE CONFLEX - 0.6/1kV Flexible VSD/EMC Cables Applications WW VSD/EMC cables are manufactured for use where electrical interference distorts signal transmission in electric motors. Standard
ELECTRICAL INSULATION TESTING OF HV EQUIPMENT UP TO 33kV
1. SCOPE This document details PowerSystems requirements for electrical testing of HV Equipment up to and including 33kV. 2. ISSUE RECORD This is a Reference document. The current version of Controlled
Gulf Cable & Electrical Ind. Co.
CONTENTS INTRODUCTION PRODUCT RANGE I PRODUCT DATA TABLES XLPE INSULATED 600/1000V CABLES Two Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 1 Three Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC 2 Four Core Cables CU/XLPE/PVC/LC/PVC/SWA/PVC
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE
LV MCC LOW VOLTAGE SWITCHGEAR MOTOR CONTROL CENTRE PRODUCT GUIDE 380/415/690 Volt AC 50/65/80/100 ka 1. Product Guide Low Voltage Motor Control Centre CONTSTRUCTION Continuous "poured in place" gasket
Fault location on power cables. Fault location on power cables
Fault location on power cables Fault location on power cables Contents: 1. Introduction 2. Construction of power cables 3. Cable faults 01. Introduction Fault location on communication and power cables
SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA
SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.MM/I/ 1 X C-UA- LTXLPE/2006) MAHARASHTRA STATE ELECTRICITY
TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR
TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR 1.1.0 SCOPE : This specification covers design, manufacture, testing at manufacture s works before
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
FAQs-Main switchboard design criteria
FAQs-Main switchboard design criteria Q: What is the Australian standard for main switchboards? Current Australian standard is AS/NZS 3439.1: 2002 originating from IEC 60439. The new series of standard
LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS
Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEYLON ELECTRICITY BOARD SRI LANKA Specification for LOW VOLTAGE RING TYPE MEASURING CURRENT TRANSFORMERS CEB Standard 027: 1998 CEYLON
2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G
Seattle Cit y Light 1 of 4 2 8 k V, 1 / C, T R X L P E I N S U L A T E D, F L A T S T R A P S H I E L D E D C A B L E, C O M P R E S S E D S T R A N D I N G 1. Scope This standard covers the detailed requirements
OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd
OUTDOOR DISCONNECTORS A division of ACTOM (Pty) Ltd ACTOM OUTDOOR DISCONNECTORS Single Side Break (SSB) Disconnector 22-132 kv, 800-1 A, 25 ka - 3s Typical bearing assembly. Voltage range 11 kv to 132
3.6/6 kv XLPE insulated cables 5. 6/10 kv XLPE insulated cables 15. 8.7/15 kv XLPE insulated cables 25. 12/20 kv XLPE insulated cables 35
CONTENTS INTRODUCTION 1 Cable selection, cable specification, cable services CABLES Constructional data: 3.6/6 kv XLPE insulated cables 5 SECTION 1 6/10 kv XLPE insulated cables 15 SECTION 2 8.7/15 kv
Operating Instructions
Operating Instructions Cable Glands Ex d and Ex e with Compound > Contents 1 Contents 1 Contents...2 2 General Information...2 3 General Safety Information...3 4 Designated Use...4 5 Technical Data...4
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES
PPS-PPQ-BT-PIAS RESIN INSULATORS FOR OIL INSULATED ELECTRICAL MACHINES BUSHING WITH PLUG CONNECTION WITH OUTER CONE PPS CHARACTERISTICS The PPS bushing can be used as a fixed section for the entry of medium
HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities
HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities RELY ON OUR EXPERIENCE... EXPERIENCE OUR CAPABILITIES For close to half a century, Silec
Contents. All Rights Reserved
Electricity Specification 400C8 Issue 6 October 2015 LV Service Cables Contents 1 Scope 2 Definitions 3 General Requirements for Approvals and Assurance 4 Conditions of Installation 5 Conditions of Operation
VIPERFLEX ELECTRIC CABLE
VIPERFLEX Flexible Low Voltage Electric Cable - 0.6/1kV (Rubber insulated) H07 RN-F & H07 BN-F Single Core 2-Core 2-Core and Earth 3-Core and Earth 4-Core and Earth Multi-Core and Earth H07 RCN-F & H07
White paper. SACE Tmax XT Circuit-Breaker Terminals and Connection
White paper SACE Tmax XT Circuit-Breaker Terminals and Connection Circuit-Breaker Terminals and Connections Index Introduction... 2 1. Components used for wiring... 3 1.1. Electrical...3 1.2. Flexibility
Removal of EP 20 10 00 02 SP High Voltage Cable
TN 018: 2014 Technical Note For queries regarding this document [email protected] www.asa.transport.nsw.gov.au TN 018: 2014 Issued date 12 March 2014 Effective dates 12 March 2014 Subject:
6-36kV Medium Voltage Underground Power Cables. XLPE insulated cables
6-36kV Medium Voltage Underground Power Cables XLPE insulated cables Cable solutions to ensure the reliability of your energy network 2 With energy as the basis of its development, Nexans, the worldwide
T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A
T A B L E T 1 1 of 7 Tests & Inspection Cable PCUT & PCUT-A (Table T1) T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A No. Test Scale MOC Requirements G 20:10:001:01 Defined Test
APPLICATION ORIENTED DESIGN OF CABLES
APPLICATION ORIENTED DESIGN OF CABLES Mrs. Rohini Bhattacharyya, Dubai cables Ltd.P. O. Box 11529,Dubai. [email protected] Mr. Nawaf Ahmad Al Mohaideb Dubai Cables Ltd. P. O. Box 11529, Dubai. [email protected]
Section 21. Telecommunication Hardware. www.geindustrial.com BuyLog Catalog 21-1
Introduction...21-1 Fiber Closure Hardware...21-2 Cable Location Surge Protectors...21-4 Introduction GE has been manufacturing Telecommunication Hardware products for over 20 years and has become a leader
THE PATHWAY TO POWER HIGH-VOLTAGE CABLES
THE PATHWAY TO POWER HIGH-VOLTAGE CABLES TABLE OF CONTENTS HIGH-VOLTAGE CABLES 3 Advantages of XLPE-insulated cable systems 3 PROPOSAL 4 Cable systems 4 Providing System Solutions 4 Continuous temperature
VDE Information. Degree of Pollution, Clearances and Creepage Distances and Insulating Materials
VDE Information General Information The voltage which can be applied to a terminal depends on the relevant regulations, the installation conditions and, of course, the dimensions and insulating materials
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
1ZSE 2750-105 en, Rev. 8. Transformer bushings, type GOE and GOE(2) Technical guide
1ZSE 2750-105 en, Rev. 8 Transformer bushings, type GOE and GOE(2) Technical guide Original instruction The information provided in this document is intended to be general and does not cover all possible
RE-ENTERABLE SPLICE CLOSURE KITS. (For Air Core None Pressurized Cable)
Triple T Broadband Public Co., Ltd. Outside Plant Standard Sector Specification No. OES-001-027-04 Issued: RE-ENTERABLE SPLICE CLOSURE KITS (For Air Core None Pressurized Cable) 1. SCOPE 1.1. This specification
David O Brien, CMP Products ([email protected])
David O Brien, CMP Products ([email protected]) 1) Main Function of Cable Glands 2) Common Issues with Cable Glands 3) Compliance / Standards, changing times 4) How do we select Cable Glands?
Electrical Safety Products
Electrical Safety Products Trelleborg Electrical Safety Products A safe working environment is important in all industries, but in the electrical generation and supply industry, it is paramount. Trelleborg
ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION
ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION Ref: WG 21.06 (TB 177) JTF 21.15 (TB 210) TF B1.10 (Electra 212) Henk Geene Presentation overview Accessories function Accessory design Accessory types
KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE
Know Your Options: 69 kv XLPE Power Cable 3 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both
Explosion proof enclosures
1 of 7 Explosion proof enclosures DE8 C 2 of 7 The Ex d enclosures are rugged and designed for harsh environment like: Oil and gas industry Chemical industry Pharmaceutical industry Agribusiness Without
Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD)
Guidance for upgrading to GB4943.1-2011 (IEC 60950-1: 2005, MOD) Note: This guidance document is a translation of official Chinese document which is issued by CQC (China Quality Certification Center) on
INTERNATIONAL STANDARD
INTERNATIONAL STANDARD IEC 60502-1 Second edition 2004-04 Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) Part 1: Cables
Catalog May 2015. Cable Accessories < 1 kv
Catalog May 2015 Cable Accessories < 1 kv Table of content Cable Accessories 1 Cable Accessories 1 kv Product range 2 Universal cleats 3 List of content 4 Notes 5 We reserve the right to make technical
IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO
IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO WHEN YOU HEAR AN ENGINEER SAY A NUMBER OF DIFFERENT APPROACHES ARE BEING IMPLEMENTED
EDITION 2012 CABLE SYSTEMS
EDITION 2012 CABLE SYSTEMS Cable fittings for high voltage networks Welcome to the CABLE SYSTEMS Centre of Competence. Our range of cable accessories offers solutions for virtually all applications in
Lightning Arresters P30027 18 KVA P30038 10 KVA. Description & Installation
Lightning Arresters P30027 18 KVA P30038 10 KVA Description & Installation Printed in USA 09/11 TO330 Rev. B Table of Contents Page 1.0 SCOPE 2 2.0 PRODUCT OVERVIEW 2 2.1 Intended Uses 2 2.2 Lightning
KNOW YOUR OPTIONS: 230 KV POWER CABLES
KNOW YOUR OPTIONS: 230 KV POWER CABLES 71 CONDUCTOR MATERIAL AND SIZE Conductor material is a matter of both customer preference and required current carrying capacity At 230 kv, copper is most common
Corporate Profile ROYAL. MODERN ROYAL ELECTRIC Ideal Power Solution MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS
Corporate Profile MODERN ROYAL ELECTRIC Ideal Power Solution ROYAL MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS MAJOR STOCKIST >>> CATHODIC PROTECTION CABLES >>> LOW VOLTAGE CABLES >>> MEDIUM
25-kV Apparatus Bushings B Series (bolt-in) for Elbow to Air-Insulated Service 200 Amp, 600 Amp and 1250 Amp
Page 1 2015 Grounded Metal Equipment Plate Equipment Connection Bus Bar or Other Component 15 kv or 25 kv Separable Insulated Connector (elbow) Equipment Connection Power Cable Power Cable Grounded Metal
HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & PROJECTS GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI-400 001
NEW POL DEPOT AT HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & S GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI-400 001 TECHNICAL SPECIFICATION OF XLPE, FRLS LT CABLES
Presentation of the France Transfo factories
Presentation of the France Transfo factories France Transfo's internationally recognised and highly esteemed expertise is today exported to more than 80 countries throughout the world. Over the past 15
Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW
Complete One Stop Solution for OPGW Cable and Fittings for OPGW 53, Justice Chandra Madhav Road, Kolkata - 700020. India. Phone: 91-33-24748575 / 7565 Fax: 91-33-2476-1955 Email: [email protected] Website:
SPECIFICATIONS FOR 220KV CAPACITOR VOLTAGE TRANSFORMER. The equipment is required for 220KV system. The system data is given as under:
REQUIREMENT : The equipment offered shall be highly reliable suitable to operate satisfactorily in hot humid and polluted climate. The equipments offered shall work satisfactorily within temperature range
Section 5 161 kv Power Cables
Know Your Options: 161 kv Power Cable 61 material and size material is a matter of both customer preference and required current carrying capacity Copper conductor common for larger loads When both copper
Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks
Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks Introduction This document presents the fundamental aspects of cable and conductor selection for connecting pad mounted shunt
Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation
Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Index News Introduction Applications & Segments Main Components Applicable Standards Technical characteristics
Medium Voltage Terminations, 5 kv 46 kv
Medium Voltage Terminations, 5 kv 46 kv Over 30 years ago, 3M pioneered cold shrink technology. Since then, field use and laboratory analysis have repeatedly proven its merits and reliability. Through
High Voltage Systems. Today. The history of cables
High Voltage Cables High Voltage Systems Today Prysmian Cables and Systems B.V. is part of the Prysmian Group, a leading player in the industry of high-technology cables and systems for energy and telecommunications,
<< Previous Page Next Page >>
> CONTENTS INTRODUCTION 01 INDUSTRIAL CABLE GLANDS 03-09 COMPRESSION TERMINALS 10-22 CABLE CLEATING & FIXING SYSTEMS 23-33 STANDARD SELECTOR CHARTS 34-37
Flexible cables for submersible products
Flexible cables for submersible products Standards SUBCAB cables complies with the following general standards: IEC 6045 (general) IEC 608 class 5 (conductor) IEC 608-- CLAUSE 9 (oil resistant) IEC 608--
EARTHING AND BONDING AT SECONDARY SUBSTATIONS
DISTRIBUTION CONSTRUCTION MANUAL SECTION 4 - SUBSTATIONS ISSUE B SEPT 1996 4.4.4 EARTHING AND BONDING AT SECONDARY SUBSTATIONS 1 SCOPE This section of the Distribution Construction Manual lays down the
a Nexans company Catalogue 2013
a Nexans company Catalogue 03 Nexans Network Solutions Div. Euromold COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated
CLAMPS CONNECTORS & EQUIPOTENTIAL RING
CLAMPS CONNECTORS & EQUIPOTENTIAL RING March 2015 Engineering Department WEST BENGAL STATE ELECTRICITY TRANSMISSION COMPANY LIMITED Regd. Office: VidyutBhawan, Block DJ, Sector-II, Bidhannagar, Kolkata
COMMISSIONING TESTS FOR HV UNDERGROUND CABLES (UP TO 33KV) SWP
1. PURPOSE AND SCOPE The purpose of this Standard Work Practice (SWP) is to standardise and prescribe the method for pre commissioning and commissioning tests on high voltage underground cables. Where
Medium Voltage Joints & Terminations
Medium Voltage Joints & Terminations 59 Medium Voltage - Cold Shrink Joints Supporting Core Radially shinkable elastomeric splice Semi-conductive layer High permitivity insulation layer Semi-conductive
CABLE ACCESSORIES 110-220 kv
CABLE ACCESSORIES 110-220 kv Termination 110 kv Technical description Termination MKB 126 / 145 with composite type insulator uses for cable line joints with other elements of power-supply systems. Termination
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy
MEDIUM VOLTAGE POWER CABLES
MEDIUM VOLTAGE POWER CABLES CONTENTS 1 GENERAL INTRODUCTION 4 TECHNICAL INFORMATION 15 25 35 45 Single Core XLPE Insulated PVC Sheathed Cables UNARMOURED CABLES COPPER UNARMOURED CABLES ALUMINUM ALUMINUM
Cable Accessories. for Extruded Dielectric Cable 69kV - 230kV Rated. Catalog Python13
Cable Accessories for Extruded Dielectric Cable 69kV - 230kV Rated Components used in cable systems 100% Tested Factory Molded For outdoor applications through 230kV For gas insulated substations and transformers
Givare NC-SRS 280 och 880
Givare NC-SRS 280 och 880 Aratron AB/Nordic Control, 02 03 SRS280SEALED ROTARY SENSOR PERFORMANCE ±2 Resistance ±20% Hysteresis (repeatability) Accuracy Applied voltage maximum Resolution Output smoothness
Flygt flexible cables
Flygt flexible cables Contents Standards General SUBCAB 4 Screened SUBCAB 6 Rubber cable type: NSSHÖU-J 7 Screened rubber cable type: NSSHÖU../E + ST 8 FGB screened rubber cable 9 PUR control cable 0 HCR
SECTION 16461 DRY-TYPE TRANSFORMERS
SECTION 16461 PART 1 - GENERAL 1.1 SECTION INCLUDES A. Furnishing and installation of and testing of cast resin dry type MV/LV distribution transformer in accordance with specifications and drawings. Any
Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva
to 1250 kva Page 1/10 Technical Specification for Oil insulated Transformers U m < 24 kv up to 1250 kva This technical specification is valid for the business unit E.ON Sweden of the market unit E.ON Nordic.
www.klmtechgroup.com TABLE OF CONTENT
Page : 1 of 13 Project Engineering Standard www.klmtechgroup.com KLM Technology #03-12 Block Aronia, Jalan Sri Perkasa 2 Taman Tampoi Utama 81200 Johor Bahru Malaysia ELECTIRAL GROUNDING TABLE OF CONTENT
4 IX D N E P P A Installation methods Current-carrying capacity and voltage drop for cables Reference method IET Wiring Matters
8 Appendix 4 of BS 7671 by Mark Coles Appendix 4, Current-carrying capacity and voltage drop for cables and flexible cords, has seen significant changes with the publishing of BS 7671:2008. This article
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1. 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.
2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV 16346-1 2a. Section 16346 INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std. Relays) Part 1 General 1.1 CONDITIONS AND REQUIREMENTS: A. Refer to
Transformer Bushings for GIS
Transformer Bushings for GIS Oil to SF6 Connections GARIP RTKG 725-55 kv SQS certified ISO 91 / ISO 141 Bushings RIP - Technology for SF6 / Oil - Bushings In modern metal enclosed switchgear SF6 -gas is
XLPE Land Cable Systems User s Guide. Rev 5
XLPE Land Cable Systems User s Guide Rev 5 CONTENT XLPE Land Cable Systems Introduction... 3 Design, installation and testing... 4 XLPE cables... 4 Cable accessories... 4 Installation of XLPE cable systems...
CATHODIC PROTECTION SYSTEM DESIGN
CATHODIC PROTECTION SYSTEM DESIGN Presented By DENIS L ROSSI P.E. CORROSION ENGINEER New England C P Inc. Corrosion Fundamentals What is corrosion? It is defined as the degradation or deterioration of
FLEXIBLE COPPER & ALUMINIUM CONNECTIONS. Product Range 1 VGL - ALLIED CONNECTORS
Product Range ROUND STRANDED COPPER CABLE Electrolytic Copper / Oxygen Free Copper Conforms to DIN 46438 Standards Finish: Bare Copper / Tinned / Silver-plated ROUND BRAID / ROUND STRANDED CABLE WITH OVERALL
International Electrotechnical Commission Standards
International Electrotechnical Commission Standards Standard IEC 60028 IEC 60038 IEC 60050-461 IEC 60055-1 IEC 60055-2 IEC 60092-101 IEC 60092-350 IEC 60092-351 IEC 60092-352 IEC 60092-353 IEC 60092-354
DELHI METRO RAIL CORPORATION LIMITED. (A Joint Venture of Govt. of India & GNCTD) MASS RAPID TRANSPORT SYSTEM PHASE III. Contract: - CE -16 VOLUME-6
DELHI METRO RAIL CORPORATION LIMITED (A Joint Venture of Govt. of India & GNCTD) MASS RAPID TRANSPORT SYSTEM PHASE III TURNKEY PROJECT OF DESIGN, SUPPLY, LAYING, JOINTING, TESTING AND COMMISSIONING OF
AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle
Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic
a Nexans company Catalogue 2014
a Nexans company Catalogue 2014 Nexans Network Solutions Div. Euromold COMPANY PRESENTATION EUROMOLD Euromold is the leading European specialised designer, manufacturer and distributor of prefabricated
Session Five: Modern XLPE Materials for Extruded Energy Cable Systems
Session Five: Modern XLPE Materials for Extruded Energy Cable Systems Abstract Hakan Lennartsson Senior Technical Service Manager, Borouge Hong Kong Pte. Ltd. The first medium voltage cables using extruded
Installation Guide of Sunrise Solartech PV Modules. Term 2013. Contents. Purpose of this guide. General. Safety precaution for installing a solar
Installation Guide of Sunrise Solartech PV Modules Term 2013 Contents Purpose of this guide General Safety precaution for installing a solar Photovoltaic system Product Identification Mechanical Installation
(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS
(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS IS 12729:2004 IEC 60694(2002) 1.1 Scope This International Standard applies to a.c. switchgear and controlgear,
Electrical Practices for Construction Work
1. Purpose Electrical Practices for Construction Work The purpose of this Code is to provide practical guidance and set minimum safety requirements for electrical practices on all construction sites in
Offshore Transformer Platform. Technical Standard. Energinet.dk. HV, MV, LV and Signal Cables and Cable Routing
Offshore Transformer Platform Technical Standard Energinet.dk HV, MV, LV and Signal Cables and Cable Routing ETS - 03 Rev. 1 Acadre doc. 44858-09 Revision survey Chpt. Description Revision Date Resp. -
No Heat. No Flames. No Shoving. No Special Tools. 3M Cold Shrink. 3M Cold Shrink. Medium Voltage Joints & Terminations. 3M Cold Shrink Joint
M Cold Shrink Medium Voltage Joints & Terminations M Cold Shrink Joint Splice bodies 00% factory tested - ensures reliability Capacitive Stress Relief No Heat No Flames No Special Tools No Shoving Unique
MiCAFIL. 1 RIP Technology. Bushings. Z. Zic 09/2003
MiCAFIL 1 RIP Technology Z. Zic 09/2003 )XQFWLRQRI+LJK9ROWDJH%XVKLQJ Uncontrolled (natural) electrical field Capacity-controlled electrical field %XVKLQJV0DLQ,QVXODWLRQ6\VWHPV 7\SH 0DLQ,QVXODWLRQ +RXVLQJFRYHU
EDS 02-0027 11KV TRIPLEX CABLE
THIS IS AN UNCONTROLLED DOCUMENT, THE READER MUST CONFIRM ITS VALIDITY BEFORE USE Document Number: EDS 02-0027 ENGINEERING DESIGN STANDARD EDS 02-0027 11KV TRIPLEX CABLE Network(s): EPN, LPN, SPN Summary:
Type K current limiting fuse canister Technical information and installation guide
Transformer components Type K current limiting fuse canister Technical information and installation guide The Type K current limiting fuse canister provides an air-insulated receptacle for general-purpose
08. SEK IDC CONNECTORS
. IDC CONNECTORS connectors for flat cables enable simple and, cost-optimized device configuration. connectors are preferably used for connection within the device. HARTING offers a broad range of these
DESCRIPTION DWG DESCRIPTION DWG
DESCRIPTION DWG DESCRIPTION DWG Ferroresonance 3451/1 3451/2 3451/3 Electro-magnetic Fields (EMF) 3462/1 HV & LV Insulators (Links) 3463/1 A ORIGINAL ISSUE B 14.07.09 APPROVED DATE J. Brooks 25.02.03 INDEX
1ZSC000563-AAC en, Rev. 7. Resin impregnated paper bushing, oil to air, type GSB Technical guide
1ZSC000563-AAC en, Rev. 7 Resin impregnated paper bushing, oil to air, type GSB Technical guide Original instruction The information provided in this document is intended to be general and does not cover
Standard Buccaneer - Ethernet
IP6 rated compliant PUR jacket on cable Shielded system shielded coupler Shroud on RJ45 Screw coupling Rewireable flex connector PCB mounted panel connector IDC termination panel connector Earth lead version
TECHNICAL SPECIFICATIONS OF 66 KV 1C 300 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. Sardar Patel Vidyut Bhavan, Race Course, Vadodara: 390 007 TECHNICAL SPECIFICATIONS OF 66 KV 1C 300 SQ.MM. XLPE POWER CABLE FOR UNDER GROUND LINE GETCO/E /TS
How To Build A Low Voltage Capacitor Lvcp
Low Voltage Capacitor LVCP The new choice for Power Factor Correction LVCP : the new choice for Power Factor Correction The LVCP is a compact and powerful capacitor. It offers high modularity, unmatched
Anodes and Misc Equipment
Anodes and Misc Equipment Application: Platinised Titanium Anodes Platinised titanium anodes are recommended for use in the following electrolytic processes:- Precious metal electroplating - e.g. Au, Pt,