B5.2 9 th International Conference on Insulated Power Cables B5.2

Similar documents
INTERNATIONAL STANDARD

UGVCL/SP/591/11KV HT AB CABLE

R=Required by Lab S=May be subcontracted IEC SYSTEM FOR CONFORMITY TESTING AND CERTIFICATION OF ELECTRICAL EQUIPMENT COMMITTEE OF TESTING LABORATORIES

SCHEDULE ' A' TECHNICAL SPECIFICATION FOR 11/22/33KV H.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA (SPECIFICATION NO.

KNOW YOUR OPTIONS: 230 KV POWER CABLES

KNOW YOUR OPTIONS: 69 KV XLPE POWER CABLE

THE PATHWAY TO POWER HIGH-VOLTAGE CABLES

Section kv Power Cables

HV Submarine Cable Systems Design, Testing and Installation

MV CABLE TYPE C

High Voltage Systems. Today. The history of cables

Fault location on power cables. Fault location on power cables

Session Five: Modern XLPE Materials for Extruded Energy Cable Systems

IEEE POWER ENGINEERING SOCIETY CHICAGO CHAPTER THE OKONITE COMPANY WEDNESDAY JANUARY 11, 2006 JIM FITZGERALD ENGINEERING LINGO

INTERNATIONAL TELECOMMUNICATION UNION #/.3425#4)/. ).34!,,!4)/.!.$ 02/4%#4)/. /& #!",%3!.$ /4(%2 %,%-%.43 /& /543)$% 0,!.43

Network Standard Advice No. 1420C 9/6/2011

T A B L E T 1 T E S T S A N D I N S P E C T I O N C A B L E P C U T A N D P C U T - A

APPLICATION ORIENTED DESIGN OF CABLES

MEDIUM VOLTAGE CABLES Up to and including 36 KV

Development of a 500-kV DC XLPE Cable System

MODELING THE EFFECT OF TEMPERATURE AND FREQUENCY ON BITUMEN-COATED HELICAL CABLE ELEMENTS

International Electrotechnical Commission Standards

3.6/6 kv XLPE insulated cables 5. 6/10 kv XLPE insulated cables /15 kv XLPE insulated cables /20 kv XLPE insulated cables 35

NSW Submarine Power. Cables for the future, delivered today.

Removal of EP SP High Voltage Cable

NSW Submarine Power. Cables for the future, delivered today

MEASUREMENTS OF THRUST LOAD IN CABLE SYSTEMS SEMI-RIGIDLY INSTALLED IN DUCT / MANHOLE STRUCTURES

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m

CONFLEX ELECTRIC CABLE

MEDIUM VOLTAGE POWER CABLES

FLEXIBLE INDUSTRIAL CABLES H07RN-F TENAFLEX SR

ENERGY. TECWATER S1BN8-F 0,6/1 kv. Cable for Water Application

ZHONGTIAN TECHNOLOGIES CO., LTD ZHONGTIAN TECHNOLOGIES SUBMARINE CABLE CO., LTD

How To Monitor Water Penetration In A Cable Screen

The Quality Connection. Underwater cables for Oceanography & Seismic Systems

High Voltage Cable Systems

)454, !,5-).)5- #!",% 3(%!4(3 #/.3425#4)/. ).34!,,!4)/.!.$ 02/4%#4)/. /& #!",%3!.$ /4(%2 %,%-%.43 /& /543)$% 0,!.43. )454 Recommendation,

Flexible cables for submersible products

INTERNATIONAL TELECOMMUNICATION UNION SERIES L: CONSTRUCTION, INSTALLATION AND PROTECTION OF CABLES AND OTHER ELEMENTS OF OUTSIDE PLANT

CABLES FOR PHOTOVOLTAIC SOLAR ENERGY INSTALLATIONS FOR CLEAN ENERGY

Corporate Profile ROYAL. MODERN ROYAL ELECTRIC Ideal Power Solution MRE ELECTRICAL, INSTRUMENTATION & COMMUNICATION SYSTEMS

HIGH- AND EXTRA-HIGH-VOLTAGE GLOBAL CABLE SYSTEM SOLUTIONS Rely On Our Experience... Experience Our Capabilities

NSW OFFSHORE AND SPECIAL CABLES. Cables for the future, delivered today.

Offshore Wind China 2010 Bergen, 15th March Olivier Angoulevant Nexans Norway AS

ScottishPower Distribution Cables & Equipment. Metal Theft

Cables, Cable Laying & Accessories Manual

CABLE ACCESSORIES kv

A Study of a MV Cable Joint

TECHNICAL SPECIFICATION FOR HIGH TENSION LINE HARDWARE AND ACCESSORIES FOR ACSR PANTHER & WOLF CONDUCTOR

Numerical Analysis of Independent Wire Strand Core (IWSC) Wire Rope

Comparison of Steel Tubes and Thermoplastic Hoses in Umbilical Service

home site map help ECMS Project: Standard / Federal Oversight Advertised

EDS KV TRIPLEX CABLE

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

Festoon 715 P PUR cable for flexible application in festoon systems

Feasibility Study of Deep Water Power Cable Systems. Enrico Colombo CESI S.p.A

The Quality Connection. BETAflam Fire Resistant Safety Cables

TARIFF CODE and updates standard

EVALUATION OF ON-SITE DIELECTRIC RESPONSE METHODS FOR NON- DESTRUCTIVE TESTING OF WATER TREED MV XLPE CABLES

WIRE AND CABLE ENGINEERING GUIDE

B05: Cable protection and sheathing

Strengthening of Large Storage Tank Foundation Walls in an Aggressive Environment by External Post-tensioning. May 7th 2013: Dominique Deschamps

Naue GmbH&Co.KG. Quality Control and. Quality Assurance. Manual. For Geomembranes

Offshore Transformer Platform. Technical Standard. Energinet.dk. HV, MV, LV and Signal Cables and Cable Routing

Aerial Fibre Optics. Complete One Stop Solution for Aerial Fibre Optics. OPGW Cable and Fittings for OPGW

SCHEDULE ' A ' TECHNICAL SPECIFICATION FOR SINGLE CORE,UNARMOURED L.T.XLPE POWER CABLE FOR DISTRIBUTION NETWORK IN MAHARASHTRA

6 ELECTRICAL PARAMETERS

The Suitability of CRA Lined Pipes for Flowlines Susceptible to Lateral Buckling SUT Global Pipeline Buckling Symposium, February 2011

The new 525 kv extruded HVDC cable system

HIGH VOLTAGE XLPE CABLE SYSTEMS. Technical User Guide

David O Brien, CMP Products (David.OBrien@cmp-products.com)

HINDUSTAN PETROLEUM CORPORATION LIMITED ENGINEERING & PROJECTS GRESHAM ASSURANCE HOUSE, 2 ND FLOOR, A-1595(3) 1-A, SIR P M ROAD, FORT MUMBAI

METHOD OF STATEMENT FOR STATIC LOADING TEST

building applications copper - redefined

XLPE Land Cable Systems User s Guide. Rev 5

Flygt flexible cables

Cable Installation Notes

Cable Selection for Medium Voltage Capacitor Banks and Harmonic Filter Banks

High-ohmic/high-voltage resistors

Unit 6: EXTRUSION. Difficult to form metals like stainless steels, nickel based alloys and high temperature metals can also be extruded.

CATHODIC PROTECTION SYSTEM DESIGN

CORNING CABLE SYSTEMS GENERIC SPECIFICATION FOR TIGHT BUFFER OPTICAL FIBER CABLES FOR INTER- AND INTRABUILDING APPLICATIONS.

ACCESSORIES FOR HV CABLES WITH EXTRUDED INSULATION

Development of 22-kV XLPE Cable and Joint with Reduced Insulation Thickness Having Water-Impervious Aluminum Layer

Specializing in the cable business for over 38 years, PT. SUPREME CABLE

TECHNICAL SPECIFICATION OF 11 / 22 KV XLPE POWER CABLE FOR SUB-STATION

6-36kV Medium Voltage Underground Power Cables. XLPE insulated cables

Oil and Gas Pipeline Design, Maintenance and Repair

VDE Information. Degree of Pollution, Clearances and Creepage Distances and Insulating Materials

144Fibre SM (G.652) Loose Tube Micro Lite Duct Optical Fibre Cable PRODUCT INFORMATION

XLPE PRODUCTION PLANT FOR THIRUVALLA UNIT OF TRACO CABLE LTD

Precision Miniature Load Cell. Models 8431, 8432 with Overload Protection

Offshore Wind Farm Export Cable Current Rating Optimisation

Gulf Cable & Electrical Ind. Co.

FIRE RESISTANT CABLE CONSTRUCTION OF CABLES

Flexible Control Cables

VIPERFLEX ELECTRIC CABLE

e-mobility Special cables for electric vehicles Coroplast Fritz Müller GmbH & Co. KG Tapes Cables Cable Assemblies

DEFECTS IN SHEET ROOFING THAT IMITATES ROOF TILES AS A RESULT OF THEIR ANCHORAGE

WIRE AND CABLE ENGINEERING GUIDE

Transcription:

Development of submarine MV-AC power cable with aluminum conductor Sven MUELLER-SCHUETZE, Heiner OTTERSBERG, Carsten SUHR, Ingo KRUSCHE, Norddeutsche Seekabelwerke GmbH/General Cable, Nordenham, Germany, sven.mueller-schuetze@nsw.com, heiner.ottersberg@nsw.com, carsten.suhr@nsw.com, ingo.krusche@nsw.com Daniel ISUS FEU, General Cable, Manlleu, Spain, disus@generalcables.es ABSTRACT A single armored MV-AC submarine power cable with an aluminum conductor was developed for offshore renewable energy, interconnections between offshore platforms, islands and shore. For the cable design process an intended installation in water depths up to 300 m and the application of additional cable protection methods such as rock dumping for on-bottom stabilization were considered. A type test has been successfully performed on 3x 800 mm² 19/33 (36) kv XLPE submarine power cable with an aluminum conductor. The qualification program was performed under consideration of the CIGRE Electra 171, CIGRE TB 490, IEC 60502-2 and CENELEC HD620-10C standards. KEYWORDS Submarine MV-AC power cable, subsea, offshore, aluminum conductor, XLPE insulation, type test, qualification, 300 m water depth, impact loads INTRODUCTION The reduction of construction cost is one of the biggest demands for today s offshore renewable energy sector. The need of cost reduction is not limited to the energy conversion system itself, it includes the interconnections between the single platforms and the connection to shore. Consequently cost of submarine power cable for infieldand export-connections needs to be reduced through the reduction of both production and material costs. Both the conductor material selection and the submarine power cable design play crucial roles and need to be reviewed under consideration of all relevant industrial standards such as IEC and Cenelec [1,2]. However, during that process all other major requirements have to be considered as well. Specifically, the cable design needs to be qualified to withstand high tensile loads and holding forces during cable installation as well as high impact forces during operation. The latter is a glaring need for all offshore renewable energy systems where scour formation or on-bottom stability are a major concern. In this case, additional cable protection methods such as rock dumping, concrete mattresses or others are required. In addition, the cable design is be suitable for installations in water depths of up to 300 m. The following sections outline the development considerations and qualification process for a MV-AC submarine power cable with aluminum conductor. The cable is developed for interconnections between offshore platforms, islands and shore. MATERIALS SELECTION Copper conductors are commonly used in submarine cables due to its very good conductivity. However, the high demand of copper material results in a very high market value. This was set to above 6000 $/ton at the beginning of April 2015. Aluminum has lower conductivity compared to copper resulting in the need to select larger conductor cross sections. Despite the larger conductor cross section, cost reduction is achieved due to the lower material price of aluminum compared to copper. At the beginning of April 2015 the market value for aluminum was oscillating around 1770 $/ton. Due to that market value difference aluminum is a cost-effective replacement for copper as conductor material. During the selection conductor material, both the electrical and mechanical material properties were reviewed for all aluminum alloy candidates to select the alloy which satisfies all specified requirements. Submarine power cable costs are mainly driven by the conductor material selection. However, other submarine power cable components such as the armoring layer, bedding layer or outer serving concept would also have a significant impact on cable price. Typical armor wire materials of submarine cables need to have good mechanical properties. Especially a high e- modulus and a high tensile strength are required given the fact that the armor layer shall support a mayor portion of the applied tensile load. Galvanized steel is the typical armor wire material used in submarine cables. Copper, nickel or titan are some of the possible replacement candidates although they share the drawback of limited mechanical properties and higher material acquisition costs compared to steel. The bedding and outer serving layer shall damp external forces which act on the submarine cable such as impact and pressure forces during cable handling and operation. Two different bedding layer and outer serving concepts are used for submarine power cables: extruded polyethylene jackets or stranded polypropylene (PP) yarn layers. Extruded PE jackets exhibit slightly superior mechanical functionality than PP yarn. Though it requires at least two additional productions steps. On the other hand, both PP yarn layers can be applied during the armoring process. Consequently PP yarn would be the cost effective solution compared to extruded PE jackets as bedding and outer serving layers. CABLE DESIGN A schematic drawing of the submarine power cable is shown in Fig. 1. The MV-AC submarine power cable is a three core design combined with fibre optic cable elements and PE fillers. All elements are laid up with a periodically reversed lay direction, forming a round and circular cable assembly. Although the assembly is dimensionally stable, additional binder tapes and yarns Jicable'15 - Versailles 21-25 June, 2015 1/6

Fig. 1: Schematic drawing of the submarine power cable design. are applied helically on the assembly to fix the shape of the cable. The armor bedding is made of a PP yarn layer. One layer of galvanized steel wires is applied over the bedding layer and selected according to EN 10257-2 and EN 10244-2 [3,4]. The armoring is flushed with bitumen compound to improve corrosion resistance. To protect the armoring one layer of polypropylene yarn is applied as outer sheath around the armoring. The power core design is based on Cenelec HD-620 10C and IEC 60502-2 standards [1,2]. Aluminum alloy wires were stranded into class 2 type conductor design with a circular shape as per IEC 60228 [5]. A semi-conducting sealing compound was applied in the interstices of the conductor strand to prevent longitudinal water penetration is case of cable damage. The semiconducting conductor screen, crosslinked polyethylene (XLPE) insulation and semiconducting insulation screen are applied around the conductor by a triple-extrusion process. The metallic screen is made out of helically applied copper wires and a contra helically applied copper tape. Underneath and on top of the metallic screen semiconducting swellable tapes are applied as longitudinal water barrier. The metallic screen is enclosed by a longitudinal applied Aluminum foil which is glued to the outer high density polyethylene (HDPE) jacket. A 3x 800 mm² 19/33 (36) kv XLPE submarine power cable (for details see Tab. 1) was used to verify the cable performance by test and a full cable qualification. Tab. 1: Design details of the 3x 800 mm² 19/33 (36) kv XLPE submarine power cable Design Parameter Nominal overall diameter Nominal cable mass in air Nominal cable weight in water Maximum pulling force Value 171 mm 38.8 kg/m 15.1 dan/m 195 kn MECHANICAL CABLE PERFORMANCE To evaluate the mechanical performance of the submarine power cable design development test were performed to verify the ability of the cable to withstand all mechanical forces during and after cable installation. All development test were performed on different cable samples from 3x 800 mm² 19/33 (36) kv XLPE submarine power cable. All samples were extracted from that cable after the FAT and the coiling test which is summarized below. Crush load analysis The crush test simulate the pressure forces which are exerted onto the cable during cable handling or installation by caterpillars. In order to simulate pressure force under realistic conditions original caterpillar track pads were utilized. To avoid deformations of the track pads, each element was placed in a metal form reproducing the installation on typical caterpillar designs. Fig. 2 shows an overview of the complete crush test setup including the cable sample placed between the two track pads and inside a hydraulic press. Fig. 2: Crush test with original caterpillar track pads The specimens were first subjected to different pressure loads and then electrically tested and dissected. No defects or an irreversible ovality were detected. Impact load analysis The objective of the impact resistance test is to confirm the cable ability to withstand high impact loads during cable handling, installation and operation. The impact test was performed by dropping a specific weight m from a defined height h, the resulting impact load is consequently defined by the equation: E = m. g. h [1] The weight slides down on a hammer. It shaped as a wedge, i.e. two a 90 faces joined by a 2 mm radius fillet. The cable sample is placed on a steel base frame underneath the hammer (see Fig. 3). For each weight the impact was performed in succession at 3 different points along the cable sample. The impact loads, which were applied during the impact test, were selected on basis of typical rock sizes which could affect submarine power cables. Jicable'15 - Versailles 21-25 June, 2015 2/6

Fig. 3: Impact Test, the impact hammer had a curvature radius of 2 mm. Both the impact test and the subsequent performed electrical test and dissections showed no defects or any other flaws for any of the selected impact loads on the power core or fibre optical elements. The crush load and impact load analysis assess the performance of PP yarn, both as bedding and outer serving layer material. Cable Stiffness Estimation The number and extent of submarine cable installation as well as on-bottom stability studies increases from project to project. Consequently the number and level of detail of required cable properties is growing steadily as well. In addition to the cable properties specified in Tab. 1 more detailed mechanical cable properties are required including the cable bending stiffness. An experimental method to determine the cable bending stiffness is summarized by Vaz et al. [6]. A straight cable specimen is bent to progressively increasing maximum curvature of interest. The cable bend is induced by a chain hoist which is attached close to both ends of the Fig. 4: Test arrangement to measure the bending moment and curvature to investigate the bend stiffness. Fig. 5: Bend stiffness vs. curvature of the 3x 800 mm² 19/33 (36) kv XLPE submarine power cable cable test specimen (see Fig. 4). To measure the applied bending forces a load cell instrument is integrated in the chain hoist. In addition to the bending force the geometrical configuration is measured through coordinates of lateral displacements as summarized by Vaz et al. [6]. The bend stiffness test has been done continuously in both directions with no waiting time in between the steps for several times. In Fig. 5 the experimental estimated cable bending stiffness (EI) of 3x 800 mm² 19/33 (36) kv XLPE submarine power cable is represented as function of the applied cable curvature. An potential function as mean function is used to illustrate the change of the cable bending stiffness due to the change of the cable curvature. TYPE TEST A type test was performed on the 3x 800 mm² 19/33 (36) kv XLPE submarine power cable which was summarized above. The type test program was performed under consideration of the Cenelec HD620-10C and IEC 60502-2 in agreement with CIGRE Electra 171 and CIGRE TB 490 [1,2,7,8]. The qualification of submarine power cables by the type test program recommended by the CIGRE Electra 171 and CIGRE TB 490 is divided into three parts: a mechanical, an electrical and a non-electrical type test [7,8]. Part I: Mechanical Type Test During the mechanical type test mechanical loads acting on submarine power cables during handling, installation and operation are simulated. Coiling Test MV-AC submarine power cables are commonly stored in static tanks during the single production steps as well as for transportation and cable installation. The coiling test as part of the type test simulates the torsional load applied to a coiled cable and validates the coiling ability of a submarine power cable. Jicable'15 - Versailles 21-25 June, 2015 3/6

Fig. 6: Coiling test of the 3x 800 mm² 19/33 (36) kv XLPE submarine power cable into a fixed static tank The 3x 800 mm² 19/33 (36) kv XLPE submarine power cable was coiled into fixed static tanks after the stranding process as well as after the armoring process. A cable sample of about 700 m length was used for the coiling test. The test cable was wounded from a turn table storage device and coiled into a static tank (see Fig. 6). Its end was fixed in the coiling core with a minimum of 4 layers on the bottom of the static tank. The cable was then rewound through a linear engine back into the turn table. The coiling and rewinding process was performed ten times. After the coiling test, samples for the following tensile bending test and electrical type test were extracted from the coiled sample. Tensile Bending Test The tensile bending test simulates the mechanical loads acting on the cable during both installation and cable repair. The test was performed on a 30 m long 3x 800 mm² 19/33 (36) kv XLPE submarine power cable sample which was cut from the coiling test sample. Cable pulling heads were installed at both ends of cable samples ensuring that the resulting forces were equivalent to the distribution of forces during laying operations. The cable sample was bend around a sheave under tensile load as specified in the Cigre Electra 171 [7] (see Fig. 7). The test tension was calculated on basis of the Cigre Electra 171 recommendation assuming maximum installation water depth of 300 m and demanding weather conditions [7]. Part II: Electrical Type Test During the electrical type test part the cable performance under both electrical and thermal load cycles is tested. The extent of the electrical type test is summarized in the Cigre TB 490 [8]. As specified in the Cigre TB 490 test was performed on the 30 m long 3x 800 mm² 19/33 (36) kv XLPE submarine power cable sample after it was subjected to the tensile bending test. The sample was laid out on the floor of the test laboratory and heating transformers were applied at one end of the submarine power cable over each of the three power cores. A reference sample was also prepared exactly in the same arrangement to validate the conductor temperature during all tests where heating was required. The tested cable sample was equipped with outdoor terminations (a schematic drawing of the test loop setup is illustrated in Fig. 8). All electrical type test were performed according to the test parameters specified in Cenelec HD620 10C and IEC 60502-2 [1,2]. For each test the more severe test conditions specified in both standards were selected: 1. Partial discharge test at ambient temperature: The test voltage was gradually raised to and held at 2.4 x U 0 for 60 s and then slowly reduced to 2.0 U0. At a test Fig. 7: Tensile bending test of the 3x 800 mm² 19/33 (36) kv XLPE submarine power cable around a 5.4 m sheave. Fig. 8: Schematic drawing of the test loop setup for the electrical type test. Jicable'15 - Versailles 21-25 June, 2015 4/6

Tab. 2: Non-electrical type test sequence. Test Description IEC, DIN EN 60811 Test on inner semi-conduktive layer Thickness IEC 60811-201 Irregularity IEC 60811-100 Test on the insulation Measurment of thickness of insulation IEC 60811-201 Irregularity IEC 60811-100 Determination of the mechanical properties of insulation before and after ageing IEC 60811 401,501 Hot set test IEC 60811-507 Water absorption test on insulation IEC 60811 402 Shrinkage test IEC 60811 502 Strippability test for insulation screen IEC 60811 503 Test on outer semi-conductive layer Thickness IEC 60811 201 Irregularity IEC 60811-100 Test on the outer sheath Measurment of thickness of non-metall sheaths IEC 60811 202 Determination of the mechanical properties of the outersheath before and after ageing IEC 60811 401, 501 and HD 620 Shrinkage test for PE oversheaths IEC 60811 503 Measurment of carbon black content of black PE oversheaths IEC 60811 605 Pressure test at high temperature IEC 60811 508 Shore D hardness HD 605 clause 2.2.1 Test of the complete cable Additional ageing test on pieces of completed cables voltage of 2 x U 0 the maximum partial discharge level should be 2 pc. 2. Tan δ measurement at ambient temperature: 0.004 at a test voltage of U 0. 3. Tan δ measurement at maximum conductor temperature in normal operation: 0.008 at a test voltage of U 0. 4. Heat Cycle Test followed by partial discharge test: 20 heating cycle with a heating duration of at least 8 h at the maximum conductor temperature were executed on that sample. 5. Partial discharge test at maximum conductor temperature in normal operation: The test voltage was gradually raised to and held at 2.4 x U 0 for 60 s and then slowly reduced to 2.0 U 0. At a test voltage of 2 x U 0 the maximum partial discharge level should be 2 pc. 6. Impulse Withstand Test: The sample was heated to a conductor temperature of 95 to 100 C. Ten positive as well as ten negative impulses were applied on the test sample with an impulse voltage of 170 kv. 7. High Voltage Test at ambient temperature: An AC test voltage of 4 x U 0 was applied on the test sample for a duration of 4 h. During that time no breakdown was observed. After completion of all electrical tests the test loop was dismantled. The construction of the cable was visually inspected and did not reveal any sign of deterioration e.g. leakage, corrosion or harmful shrinkage and electrical degradation which could affect the system in service operation. A cable sample of approximately 0.5 m was selected for more detailed analysis. The conductor was inspected and the measurement of the insulation, outer sheath, and metallic sheath thickness were performed without any sign of deterioration. Part III: Non Electrical Type Test EN 60811-401 and HD 620 table 2a, 4B The International Standard IEC 60811 and the national Standard DIN EN 60811 specifies a non-electrical test sequence (see Tab. 2) on insulation, on the conductor Fig. 9: Longitudinal water penetration test setup on the metallic screen of the power core. and insulation screen as well as the outer sheath [9]. During those test the different material qualities were analyzed by hot set test, shrinkage test, aging test, pressure test and purity test. All test were done on an additional 3x 800 mm² 19/33 (36) kv XLPE submarine power cable sample taken from the coiling test sample. Both Cigre Electra 171 and Cigre TB 490 recommend the implementation of longitudinal water penetration test on conductor and on the metallic screen of the power core as part of the non-electrical type test sequence [7,8]. For that purpose the selected samples were pre-treated by mechanical tests 1 as per CIGRE ELECTRA 171 clause 2.2 and consecutively 3 heating cycles as specified in the Cigre recommendations [7,8]. The pre-treated test samples were place inside the water pressure test chambers according to the test setup specified in Cigre TB 490 (see Fig. 9) [8]. The water penetration test on the conductor and the metallic screen were performed with a test pressure of 30 bar for a duration of ten days. The applied test pressure corresponds to a maximum considered installation water depth of 300 m for submarine power cable design. The cable sample of the water penetration test on the metallic screen test sample was treated by 10 heating cycles while the test pressure of 30 bar was applied on the sample and the water temperature was equal to the ambient temperature. The test reveals a water penetration depth below 0.3 m inside the Aluminum conductor of the 1x 800 mm² 19/33 (36) kv XLPE power core after a test duration of ten days. Inside the metallic screen a water penetration depth below 1.5 m was measured after the same time duration. SUMMARY The reduction of submarine power cable cost is achieved by utilization of Aluminum as conductor material instead of copper. A MV-AC submarine power cable design with an Aluminum conductor was developed and qualified as per Cigre Electra 171 and Cigre TB 490 for a maximum water 1 As recommended in the Cigre TB 490 the mechanical pre-treatment was not performed on the sample used for the water penetration test on the metallic screen. Jicable'15 - Versailles 21-25 June, 2015 5/6

depth of 300 m. In addition it could be presented that this cable design can withstand required impact loads as well as high crush forces. REFERENCES [1] Cenelec, 2010, Distribution cables with extruded insulation for rated voltages from 3.6 / 6 (7.2) kv up to and including 20.8 / 36 (42) kv, Cenelec HD620 10C / DIN VDE 0276-620 S2 [2] IEC, 2014, Power cables with extruded insulation and their accessories for rated voltages from 1 kv (U m = 1,2 kv) up to 30 kv (U m = 36 kv) - Part 2: Cables for rated voltages from 6 kv (U m = 7,2 kv) up to 30 kv (U m = 36 kv), IEC 60502-2 edition 3.0 [3] EN, 2012, Zinc or zinc alloy coated non-alloy steel wire for armouring either power cables or telecommunication cables - Part 2: Submarine cables, EN 10257-2:2012-02 [4] EN, 2009, Steel wire and wire products - Non-ferrous metallic coatings on steel wire - Part 2: Zinc or zinc alloy coatings, EN 10244-2:2009-08 [5] IEC, 2004, Conductors of insulated cables IEC 60228 edition 3.0 [6] M. A. Vaz, L. A. D. Agular, S. F. Estefen, and M. Brack, "Experimental determination of axial, torsional and bending stiffness of umbilical cables", presented at the OMAE98, 1998. [7] Cigre, 1997 Recommendations for Mechanical tests on submarine cables Electra no. 171, 59-65 [8] Cigre, 2012 Recommendations for testing of long AC submarine cables with extruded insulation for system voltage above 30 (36) to 500 (550) kv, TB 490 [9] IEC, 2012 Electric and optical fibre cables - Test methods for non-metallic materials - Part 100: General, IEC 60811 Jicable'15 - Versailles 21-25 June, 2015 6/6