RCC10U Room Temperature Controller for Two-pipe Fan Coil Units

Similar documents
Technical Instructions Document No P25 ET September 28, ET 141 High Limit Control Thermostat. Description.

features Electric Room Thermostats Description Applications Thermostats & Hygrostats

Powers Controls TH 192 S Single Temperature Room Thermostat

I nstallation. M100Q Series Proportional Actuator with R81Q Controller Board for Thermistor Sensor Applications. Tools Needed.

PRODUCT PRODUCT CODE TECHNICAL INSTRUCTIONS PAGE

Powers Controls TH 192 HC Heating/Cooling Room Thermostat

Electronic Control Devices The European Product Catalogue 2007

Building Technologies. Electronic Thermostats and Controllers Selection Guide

RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry

ETC TWO STAGE ELECTRONIC TEMPERATURE CONTROL

T5000 T000 LCD Digital Fan Coil Thermostat

Solid-State Timer H3G

RVL470. Heating Controller. Building Technologies HVAC Products. Series B

Electronic Control Devices The European Product Catalogue 2007

Flush-mounted room thermostats

Table of Contents. 1 - Specifications Installation Wiring User controls...7

T7079A,B Solid State Remote Temperature Controllers

T6861 Series Large LCD Digital Thermostat 110/220 VAC 2-pipe/4-pipe fan coil control

SKP Series SKP15U.. Gas Valve Actuator with Safety Shutoff Function

HERZ-Thermal Actuators

POWERS CONTROL RC 195 Single Input Receiver-Controller

Powers Controls Free Energy Band TH 193 HC Heating/Cooling Room Thermostat

12S, 14S, 15S Series. Time Delay Relays and Sequencers. Time Delay Relays and Sequencers. Features and Benefits. Switch Actions and Configurations

Adjustable room thermostat for heating only or cooling only systems

T7560A,B,C Digital Wall Module

2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal

Programmable Room Thermostat 7 Day (5-2 Day) Models: / Power Supply: Battery / Mains

Outdoor 33.6W Dual Port Passive Power-over-Ethernet Midspan For External Security Cameras and Wireless Access Points

MCR1900 Media Converter 19-Slot Chassis

FOXAIR 60/50 ALL MODELS

RC 195 Multiple Input Receiver-Controller

Drayton Digistat +2RF/+3RF

Thermostat with display

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

Installing the Tracer ZN517 Unitary Controller Ordering number: ,

HMI display Installation Guide

Heating Controller. Building Technologies HVAC Products

COMPUTHERM Q7 Programmable, digital room thermostat. Operating Instructions

TR21, TR22, TR23, and TR24 Wall Modules

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

Radiant Temperature Sensor TY7321

Operating Instructions. Room temperature controller

PT-6000 Power Tower INSTALLATION MANUAL SPECIFICATIONS

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

Electronic, Digital and Mechanical Vibration Switches

USER S MANUAL HSC-24A

DS DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches

TC-9102 Series Surface Mount Temperature Controllers

INSTALLATION INSTRUCTIONS MC95HAE-1 MASTER CONTROLLER

VC Series Zone Valves BALANCED 2-WAY AND 3-WAY HYDRONIC VALVES

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

Controls for fan coil units and cassettes

Install Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work.

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

Thermwire. Selection Guide. Freeze Protection Heating Cable. Thermwire -Wrap. Pre-Assembled. Thermwire-Comp. Thermwire-Melt.

Solid State Timers Type F

USER MANUAL WARNING! CONTENTS MODEL 1 SPECIFICATIONS READ ALL INSTRUCTIONS BEFORE PROCEEDING. Non-Programmable Single Stage Heat/Cool Thermostat

Lighting Controls ! WARNING RISK OF ELECTRIC SHOCK. Installation Instructions DESCRIPTION

HVAC Processes. Lecture 7

TABLE 1: Wiring Terminals. Connect to... 1C 1H 2C 2H 1H1C 2H1C 2H2C 3H2C

Advantium 2 Plus Alarm

DUCT SMOKE DETECTOR D4120

User Manual THR840DUK Digital Thermostat

SWITCH! DESCRIPTION. ENVIRONMENTAL SPECIFICATIONS Operating Temperature: 0 C to +40 C SPECIFICATION SHEET:

Applied Electronics. Commercial Dimming System UPDATE NOTICE

Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types

Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions

ACS-30-EU-EMDR-10-MOD

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

! WARNING. McDonnell & Miller Installation & Maintenance Instructions MM-217(I) Series 150S and 157S (Snap Switch, All Models except 157S-RB-P)

ABB i-bus KNX Fan Coil Controller FC/S 1.1

M9102-AGA-2S, -3S and M9104-xxA-2S, -3S Series Electric Non-Spring Return Actuators

! WARNING. Before using product, read and understand instructions.

Installation Manual. Rental Services. Air Handling Units CHS-SVN01A-EN. July 2008

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

SLIM LINE FUME HOOD MONITOR

PNEUMATIC CONTROLS Selection and Description

WE-350 Series ¼ Turn Electric Actuator

POWERS Controls No. 4 Pneumatic Damper Actuator

LIEBERT VNSA Installation Sheet

Install Guide 3M-50. Caution. Caution

HCS-3300/3302/3304 USB Remote Programmable Laboratory Grade Switching Mode Power Supply

IntesisBox KNX Mitsubishi Heavy Industries AC

OWNER S MANUAL FORCE 10 MARINE COMPANY HAMILTON ROAD RICHMOND, BC CANADA V6V 1C9 TEL: (604) FAX: (604)

Y7230A CO 2 Alarm System

IMPACT ALARM SYSTEM FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS INTRODUCTION

DIGITAL ALARM II FOR HOSPITALS AND LABORATORIES INSTALLATION AND OPERATING INSTRUCTIONS

430 Power/Electronics Replacement

Solid Core and Split Core Adjustable Current Status Switches CSS-O, CSS-C; CSP-O, CSP-C

2013 Wireless Video Intercom INSTALLATION GUIDE

Duct Humidity Transmitter

Diesel Engine Driven Generators Page 1 of 6

Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types

16/32 Channel 1U Rack Mount CCTV Power Supply

HEAT PUMP PROGRAMMABLE THERMOSTAT

T 3 Series VAV Diffusers Analog Diffuser Steel Square Panel Horizontal Pattern Model: T 3 SQ

PS6500 Storage Arrays Rack Mount Instructions

Communicating Wall Control Installation Manual TSTAT0101SC

Transcription:

Document No. 155-712 RCC10U Room Temperature Controller Description Features Application Room temperature controller for two-pipe fan coil units. Output for on/off valve actuator. Output for three-speed fan. Dual setpoint temperature scale. Control depending on the room or return air temperature. Automatic Heating/Cooling changeover. Operating modes: Normal, Energy Saving, Freeze Protection and Off. Operating mode changeover input for remote control. Selectable control parameters. Operating voltage 120 Vac. Typical use: Controlling room temperature in individual rooms that are heated or cooled with twopipe fan coil units. Opening or closing a valve Switching a three-speed fan. Suitable for use in systems with: Automatic Heating/Cooling changeover. Heating only/cooling only or Heating and Cooling applications. Product Number RCC10U With input for return air temperature sensor

Document Number 155-712 Accessories ARG70 Adapter plate, for 2-inch 4-inch or 4-inch 4-inch electrical wall boxes QAH11.1 Changeover/remote sensor 141-570 Lockable Thermostat Guard Ordering The QAH11.1 temperature sensor (which can be used as a return air temperature or changeover sensor), and valves must be ordered separately. An ARG70 Wall Box Adapter (used to mask the drywall when mounting the controller to a 2-inch 4-inch or 4-inch 4-inch electrical wall box) must also be ordered separately. Warning/Caution Notations Table 1. Equipment Combinations. Product Number Description Technical Instructions QAH11.1 Temperature Sensor 155-329P25 599 Series Two-way and Three-way Zone Valves 155-320P25 SF Series Zone Valve Actuator 155-321P25 WARNING: CAUTION: Personal injury, or loss of life may occur if you do not follow a procedure as specified. Equipment damage, or loss of data may occur if you do not follow a procedure as specified. Functions The controller measures the room temperature with its integrated sensor or external return air temperature sensor (QAH11.1) if used and maintains the setpoint by delivering control commands to the two-position (on/off) valve. The switching differential is adjustable; it can be 2 F (1 C) or 7 F (4 C) in Heating mode, or 1 F (0.5 C) or 3.5 F (2 C) in Cooling mode. Fan Operation The fan is switched to the selected speed via control output 11, 10 or 9 (Low, Medium or High). When the Temperature-dependent fan control function is activated (can be selected with DIP Switch No. 1), the fan and valve are switched ON or OFF depending on the temperature. It is switched OFF by: Leaving the Heating or Cooling sequence, if the function Temperature-dependent fan control is activated. Manually changing to Standby mode., if room conditions do not call for Freeze Protection Activating an external operating mode changeover switch, if installation conditions do not call for Energy Saving or Freeze Protection mode. Turning the controller s power supply OFF. Page 2

Technical Instructions Document Number 155-712 Heating/Cooling Mode Output terminals 7 and 5 (neutral) command the control valve. Output terminals 7 and 5 are open (0 Vac) when: 1. The measured room temperature is at half the switching differential below the setpoint (Heating mode), and 2. The valve has been fully closed for more than one minute. Output terminals 7 and 5 are closed (120 Vac) when: 1. The measured room temperature is at half the switching differential above the setpoint (Heating mode), and 2. The valve has been fully open for more than one minute. NOTE: Output terminals 7 and 5 deliver a control command only for fail-safe open (Normally Open) valve/actuator assemblies. Fail-safe closed (Normally Closed) valve/actuator assemblies cannot be used with the RCC10U Controller. Return Air Temperature The RCC10U provides control based on either the measured room temperature or the fan coil unit s return air temperature. Changeover is automatic if a QAH11.1 cable temperature sensor is connected to the device. Place the sensor in the return air duct and terminate to the controller. Order the QAH11.1 separately for return air sensing. Automatic Heating/Cooling Changeover CW = Chilled Water Cooling mode HW = Hot Water Heating mode M = Operating mode SDC = Switching differential, cooling SDH = Switching differential, heating T = Room temperature Tw = Water temperature W = Room temperature setpoint Y = Signal voltage The controller uses the water temperature measured by the changeover sensor (QAH11.1) to switch from Heating to Cooling mode, or vice versa. When the water temperature is above 82 F (28 C), the controller switches to Heating mode; below 61 F (16 C) it switches to Cooling mode. If the water temperature is between the two changeover points immediately after switching on, the controller will start in the Heating mode. The water temperature is measured at one-minute intervals and the operational status is updated. Heating Mode Cooling Mode Automatic Changeover Figure 1. Switch Action for Output Teminals 7 and 5. Remote Changeover Heating/Cooling An electric switch placed between input terminals 2 and 3 can facilitate remote changeover. Terminals 2 and 4 must be bridged. When the switch is closed, the Cooling mode is selected. When the switch is open, the Heating mode is selected. Up to ten thermostats can be connected in parallel. Heating only For heating only applications, input terminals 2 and 3 are open. Cooling only For cooling only applications, input terminals 2 and 3 must be bridged with wire. Page 3

Document Number 155-712 Purging Function Setpoint Limit Stops The changeover sensor initiates the change from Heating to Cooling mode even if the two-way valves are shut down for a long period of time. To ensure this function, the valves are opened for one minute at two-hour intervals. After power is reset to the controller, the heating and cooling valve will open for one minute to flush pipes, for accurate remote changeover sensing. When this function is completed, the changeover sensor will select the correct mode. The room temperature setpoint can be limited in increments of 2 F (1 C) by using the minimum and maximum setpoint limit stops. This prevents unauthorized setpoint adjustment. To set limit stops, remove the setpoint knob by pulling straight off the shaft. Reposition gray tabs for high and low stops in the holes around the perimeter of knob as required. See Figure 2. Figure 2. Setpoint Limit Stops. Operating Modes Normal Operating Mode Freeze Protection Mode The following operating modes are available: Heating or Cooling mode with automatic changeover and with manually selected fan speed: (Low), (Medium), (High). In Normal operation, the controller maintains the adjusted setpoint. The Freeze Protection function is activated only when DIP Switch No. 4 is set to OFF. Freeze Protection mode can be activated by: Manually switching to Standby. Activating the external operating mode changeover switch, if DIP Switch No. 2 is set to OFF. If the room temperature falls below 46 F (8 C), the controller will automatically switch to Freeze Protection mode. In that case, the heating valve opens and the fan operates at the selected speed. If the Standby mode is selected, the fan will operate at low speed. The room temperature is maintained at a setpoint of 46 F (8 C) and the setpoint adjusted by the user will be ignored. If Freeze Protection operation is locked (DIP Switch No. 4 in position ON), Standby is also locked, which means that the controller will switch to OFF instead of Standby. Page 4

Technical Instructions Document Number 155-712 Energy Saving Mode In Energy Saving mode, the heating setpoint is 61 F (16 C) and the cooling setpoint is 82 F (28 C), independent of the position of the setpoint knob. This operating mode will be activated when input D1 for operating mode changeover is active and DIP Switch No. 2 is set to ON. When the DIP switch is in Energy Saving mode and the fan speed control is set to Standby, the Energy Saving mode takes precedence over Standby mode. When the room temperature drops below the Energy Saving setpoint, the fan operates at low speed until the energy load is satisfied; then the fan turns off. Low fan speed will be selected even though the fan switch is on Standby. Operating Mode Changeover Switch A changeover switch can be connected to status input D1 GND. When the switch closes its contact (such as, caused by an open window), the operating mode will change from Normal operation to Energy Saving mode (if DIP Switch No. 2 is set to ON), or from Normal operation to Standby (if DIP Switch No. 2 is set to OFF). If the room temperature falls below 46 F (8 C) and if DIP Switch No. 4 is set to OFF, Freeze Protection mode will become active. The operating action of the switch (NC or NO) can be selected by DIP Switch 3. Mechanical Design The unit consists of two parts: A plastic housing which accommodates the electronics, the operating elements and the built-in room temperature sensor. A controller base. The housing snaps into the top of the mounting base and is secured with a screw at the bottom. The wire terminal block is mounted on the base; the DIP switches are located at the rear of the housing. To access the DIP switches, remove controller from controller base. See Figure 3. Figure 3. DIP Switch Setting. Page 5

Document Number 155-712 Table 2. DIP Switches. DIP Switch No. Description Position ON Position OFF 1 Fan control Fan control is temperaturedependent in all operating modes 2 Operating mode changeover via an external switch 3 Operating action of switch for external operating mode changeover Changeover between Normal operation and Energy Saving mode Changeover activated when contact of switch is closed (NO) 1 4 Standby Freeze Protection function disabled Fan control in Normal operation is temperatureindependent 1 Changeover between Normal operation and Standby 1 Changeover activated when contact of switch is open (NC) Freeze Protection function enabled 5 Switching differential 2 F (1 C) in Heating mode 1 1 F (0.5 C) in Cooling mode 1 7 F (4 C) in Heating mode 3.5 F (2 C) in Cooling mode 1. Factory setting Construction 1 Standby mode selector /fan speed switch: (Low), (Medium), (High). 2 LEDs for indicating Heating mode, Cooling mode and fan operation. 3 Setting for minimum setpoint limit stop (in increments of 2 F [1 C]). 4 Setting for maximum setpoint limit stop (in increments of 2 F [1 C]). 5 Room temperature setpoint knob. 6 Set of DIP switches (mounted on circuit board). Figure 4. Construction. Page 6

Technical Instructions Document Number 155-712 Mounting, Installation and Commissioning The unit can be located on a wall or inside a fan coil unit. Do not mount in direct sunlight or near other heat or refrigeration sources. Mounting height is approximately 60 inches (150 cm) above the floor, when using the wall mounting option. See Figure 5. The unit can be fitted to most commercially available recessed electrical wall boxes or directly on the wall. A Wall Box Adapter Kit (ARG70), ordered separately, is recommended but not required to mount an RCC10U controller to a 2-inch 4-inch electrical wall box. An ARG70 is required for 4-inch 4-inch electrical wall box mounting. The wall plate will cover the drywall cutout. Check the settings of the DIP switches and change them, if required. After applying power, the controller makes a reset during which the fan LED flashes indicating that the reset has been accomplished. This takes about three seconds. When the LED stops flashing, the controller is ready to operate. Figure 5. Acceptable Mounting Height in Inches. Prior to fitting the changeover sensor, apply thermal conductive paste on the pipe where the sensor is to be placed. Secure with plastic cable ties. The sensor is not position sensitive. The cables used must meet the insulation requirements for live voltage. The control valve is fully open for one minute upon start-up to determine if it is in Heating or Cooling mode (purging function). User input via setpoint knob or operating mode/fan speed selector results in instantaneous response. There is a one-minute delay before changes made to temperature sensing and changeover are implemented. WARNING: Sensor inputs 1, 2 and 3 carry live voltage potential. If the sensor s cables must be extended, the cables used must be suited for live voltage. Installation Instructions are included with the controller. Page 7

Document Number 155-712 Installation Instructions 4-inch 4-inch Electrical Wall Box Mounting An ARG70 wall plate adapter is required to mount an RCC10U controller to a 4-inch 4-inch electrical wall box. 1. Loosen the screw at the bottom of the controller with a small screwdriver. 2. Lift the bottom of the controller from the controller base and push up to remove. Figure 6. Controller Separation. 3. Fasten the wall box adapter (3) to plaster ring (2), supplied by others, using the four screws provided with the ARG70. 4. Flex adapter mask (4) and snap in place inside wall box adapter (3). 5. Pull wires through plaster ring (2). 6. Fasten controller base (5), to wall box adapter assembly (3) and (4) with the two screws provided. Figure 7. 4-inch 4-inch Electrical Wall Box Installation. 1 Electrical wall box 2 Plaster ring 3 Wall box adapter* 4 Adapter mask* 5 Controller base 6 Controller * Included with ARG70 Page 8

Technical Instructions Document Number 155-712 4-inch 4-inch Electrical Wall Box Mounting, Continued 7. Terminate wires per wiring instructions located above the terminal block. Figure 8. Wiring Termination. 8. Reattach the controller to the controller base. 9. Secure by tightening the screw at the bottom of the controller. The installation is now complete. Figure 9. Controller Reattachment. Page 9

Document Number 155-712 2-inch 4-inch Electrical Wall Box Mounting An ARG70 wall plate adapter is recommended, but not required to mount an RCC10U controller to a 2-inch 4-inch electrical wall box. 1. Loosen the screw at the bottom of the controller with a small screwdriver. 2. Lift the bottom of the controller from the controller base and push up to remove. See Figure 6. 3. Fasten the wall box adapter (3) to plaster ring (2), supplied by others, using the two screws provided. 4. Flex adapter mask (4) and snap in place inside wall box adapter (3). 5. Pull wires through plaster ring (2). 6. Fasten controller base (5), to wall box adapter assembly (3) and (4) with the two screws provided. 7. Follow Steps 7 through 9 of the 4-inch 4-inch Electrical Wall Box Mounting section. The installation is now complete. Figure 10. 2-inch 4-inch Electrical Wall Box Installation. 1 Electrical wall box 3 Wall box adapter* 4 Adapter mask* 5 Controller base 6 Controller * Included with ARG70 Page 10

Technical Instructions Document Number 155-712 Specifications Power Supply Operating voltage 120 Vac +10/-15% Frequency Power consumption Control Outputs (Fan) 11, 10, 9 (Valve) 7 50/60 Hz Maximum 10A 120 Vac max./5 res./3.5 FLA/7.0 LRA 120 Vac max./5 res./3.5 FLA/7.0 LRA Signal Input 1 for return air sensor QAH11.1, Class 2 NTC resistor 3K Ω @ 77 F (25 C) Signal Input 3 for changeover sensor QAH11.1, Class 2 NTC resistor 3K Ω @ 77 F (25 C) Permissible number of thermostats in parallel, Signal Input 3 Status Input D1 and GND Contact sensing Ten 6 to 15 Vdc/3 to 6 ma Operating action Single-pole, Single-throw (SPST) Permissible cable length with copper 262 feet (80 m) cable 16 AWG for connection to Terminals 1, 3, D1, and GND Operational Data Setpoint setting range 50 F to 85 F (10 C to 30 C) Switching differential in Heating mode SDH 2 F or 7 F (1 C or 4 C) (selectable) General Ambient Conditions Switching differential in Cooling mode SDC 1 F or 3.5 F (0.5 C or 2 C) (selectable) Setpoint (Energy Saving mode ), 61 F (16 C) heating Setpoint (Energy Saving mode ), 82 F (28 C) Cooling Setpoint (Freeze Protection ) 46 F (8 C) Operation Temperature 32 F to 122 F (0 C to 50 C) Humidity <95% rh Shipping and storage Temperature 13 F to 158 F ( 25 C to 70 C) Humidity <95% rh Agency Approvals UL Listing UL 873 cul certification C22.2 No. 24-93 Conforms to CE requirements Degree of housing protection NEMA 1 General Connection terminals Solid wires or prepared standard wires 2 16 AWG or 1 14 AWG Minimum 20 AWG Weight 0.55 lb (0.25 kg) Housing color Cover White and gray Base Gray Degree of housing protection NEMA 1 Page 11

Document Number 155-712 Wiring Terminals 1 Status input, Return air temperature sensor 2 Measuring neutral, Return air temperature sensor and changeover sensor 3 Status input, Changeover sensor 4, 5 Neutral 6 Operating voltage 120 Vac 7 Control output, Valve, 120 Vac 9 Control output, Fan speed III, 120 Vac (High) 10 Control output, Fan speed II, 120 Vac (Medium) 11 Control output, Fan speed I, 120 Vac (Low) D1, GND Status input for potential-free operating mode changeover switch (operating action can be selected) Figure 11. Wiring Terminals. Wiring Diagram B1 B2 G M1 G0 N1 S1 Y1 Return air temperature sensor (QAH11.1) Changeover sensor (QAH11.1) Operating voltage 120 Vac Three-speed fan Neutral External operating mode changeover switch 599 Series Zone Valve Figure 12. Wiring Diagram. Page 12

Technical Instructions Document Number 155-712 Dimensions Figure 13. RCC10U and Base Plate in Inches (Millimeters). Figure 14. ARG70 Dimensions in Inches (Millimeters). Information in this publication is based on current specifications. The company reserves the right to make changes in specifications and models as design improvements are introduced. Product or company names mentioned herein may be the trademarks of their respective owners. 2007 Building Technologies Division 1000 Deerfield Parkway Buffalo Grove, IL 60089 + 1 847-215-1000 Your feedback is important to us. If you have comments about this document, please send them to SBT_technical.editor.us.sbt@siemens.com Document No. 155-712 Printed in the USA Page 13