Galleon 6-10K Online UPS Voltronic Power Technology Corporation
Features Galleon online UPS series delivers optimal power quality, provides superior power management, resolves utility power protection problems to critical equipments and applications required clean, continuous power. True double conversion design DSP technology guarantees high performance Wide input voltage window (110-300 VAC) Active input power factor correction 0.99 Output power factor 0.8 Extra operation modes: frequency converter mode & ECO mode Emergency power off function (EPO) Programmable power management outlets/terminals
Additional Features Generator compatible Available in both standard & long-run Models Smart LCD with LED indicators available for quick view in minutes 3-Stage extendable charger design for prolonged battery lifecycle and optimized battery recharge time Adjustable battery numbers Maintenance bypass switch available N+X parallel redundancy available
Operating Mode Selection Galleon provides three operating modes to suit various applications. Normal Mode: Stabilize wide voltage fluctuations in a range of 110~300VAC with frequency synchronize with main within 46~54Hz to deliver clean pure sine wave power ECO Mode: Offers efficiency as high as 97% to cut energy usage & cost. UPS power application via static bypass, timely returning to online double conversion when the need arises. Frequency Converter Mode: Lock output frequency at 50Hz or 60Hz to suit power sensitive equipments
Outlook Front View Four LED indicators for quick view Four control buttons for UPS setting
Outlook LCD Display Input & Battery voltage information Backup time in pie chart Backup time in numbers/ Fault Fault code warning Mute operation Output & Battery voltage information Battery level Battery mode indicator Overload warning Load Level Low battery warning Mode Operation Information Short circuit warning
Rear Panel Overview EPO RS-232 Port USB Port Parallel Connection SNMP Slot Maintenance Bypass Switch Output Sockets Input Breaker Output Breaker Terminal Block
Specifications MODEL Galleon 6K (L) Galleon 10K (L) CAPACITY 6000 VA / 4800 W 10000 VA / 8000 W INPUT Voltage Range Frequency Range Phase Power Factor OUTPUT Low Line Transfer Low Line Comeback High Line Transfer High Line Comeback 176 VAC @ 100% load, 110 VAC @ 50% load 186 VAC @ 100% load, 120 VAC @ 50% load 300 VAC 290 VAC 46~54 Hz 50Hz / 56~64 Hz 60Hz Single phase with ground 0.99 @ 100%load AC Voltage Regulation (Batt. Mode) ± 1% Frequency Range (Synchronized Range) Frequency Range (Batt. Mode) 46~54 Hz 50 Hz / 56~64 Hz 60 Hz 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz Current Crest Ratio 3:1 Harmonic Distortion Transfer Time Waveform (Batt. Mode) AC Mode to Batt. Mode Inverter to Bypass 2 % THD (Linear Load) 6 % THD (Linear Load) Zero zero Pure Sine Wave
Specifications MODEL Galleon 6K (L) Galleon 10K (L) EFFICIENCY AC Mode 90% Battery Mode 88% BATTERY Standard Model Long-run Model INDICATORS LCD Panel ALARM Battery Mode Low Battery Overload Fault Battery Type 12 V / 7 AH 12 V / 9 AH Numbers 20 20 Typical Recharge Time 7 hours recover to 90% capacity 8 hours recover to 90% capacity Charging Current (max.) Charging Voltage Battery Type & Numbers Charging Current (max.) Charging Voltage 1.0 A 273.0 VDC Depending on the capacity of external batteries 4.0 A 273.0 VDC UPS status, Load level, Battery level, Input/Output voltage, Discharge timer, and Fault conditions Sounding every 4 seconds Sounding every second Sounding twice every second Continuously sounding
Specifications MODEL Galleon 6K (L) Galleon 10K (L) PHYSICAL Standard Model Long-run Model ENVIRONMENT Operation Humidity Noise Level MANAGEMENT Smart RS-232 USB Optional SNMP Dimension, D X W X H (mm) 592 X 250 X 576 Net Weight (kgs) 81 83 Dimension, D X W X H (mm) 592 X 250 X 576 Net Weight (kgs) 22 24 20-90 % RH @ 0-40 C (non-condensing) Less than 45dBA @ 1 Meter Supports Windows Windows family, Novell, Linux and FreeBSD Power management from SNMP manager and web browser
Comparison Table T Model Galleon Capacity (VA) 6K/10K 6K/10K Output Power Factor 0.7 0.8 Input Power Factor 0.98 0.99 Input Range 176 276 VAC 176 300 VAC 50Hz/60Hz frequency converter mode ECO mode No Yes EPO Function No Yes Programmable Management Output Terminal blocks Turn on UPS without battery when connecting to the mains No No No RS-232 or USB RS-232 only Both RS-232 and USB Yes Yes Yes
Comparison Table T Model Galleon LCD size (W x H mm) 22 x 23.5 55 x 27.5 Control Panel UPS setting via LCD control panel Battery charging Adjustable battery numbers LCD display only No 2-stage charging design No LCD and LED indicators available LED indicators for quick view Yes (Output voltage, output frequency, ECO mode setting, bypass enable/disable, Bypass/ECO mode output voltage range, Bypass/ECO mode output frequency range, programmable output outlet setting, second output shutdown, and Inverter output voltage calibration) 3-stage charging design for longer battery lifecycle and optimized battery recharge time Yes (18/19/20 pcs) Output connection Terminal block only Terminal block + socket type Material for Input Current Sensors Ferrite core Hall-effect Current Sensor (HCT) For quality reliable Dimension (D x W x H) 570x260x717 592 X 250 X 576 with Smaller Footprints