RESOL DeltaSol A. Mounting Connection Operation Examples. Manual



Similar documents
RESOL DELTA Sol. universal temperature differential. regulator for solar- and heating systems Mounting instructions. page 1/11

1 General information

eltasol RESOL DeltaSol M Manual Installation Operation Commissioning Fault localisation for the professional

MOUNTING AND OPERATING INSTRUCTIONS

HERZ-Thermal Actuators

Installation and operating instructions. Solar charge controller Solarix MPPT Z Z

Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II

DeltaSol C Plus. RESOL DeltaSol C Plus * * B Manual. Mounting Connection Operation Troubleshooting Examples

Zenith Solar thermal 4.5m pump station Installation manual

SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS

Product and functional description

DeltaSol E. RESOL DeltaSol E. Mounting Connection Handling Fault localization. manual

Power Supply and Indicator Unit Type Fig. 1 Type Mounting and Operating Instructions EB 9539 EN

How To Use A Power Supply On A Powerline 2.2 (Ai)

SunMaxx Solar Filling Station Operating Instructions

Single-phase ( V) voltage monitoring: Undervoltage Overvoltage Window mode (overvoltage + undervoltage) Voltage fault memory selectable

Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw

ABB i-bus EIB / KNX Analogue Input AE/S 4.2

DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry

Table of Contents. 1 - Specifications Installation Wiring User controls...7

StorTrends 3400 Hardware Guide for Onsite Support

Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS

Install Guide CT100. Caution. Caution ENGLISH. disconnect the power supply before beginning work.

Operating Instructions. Room temperature controller

Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.

SERVICE MANUAL FOR 6535 SERIES TWO TON HIGH EFFICIENCY PACKAGED HEAT PUMPS

Material test chamber with mechanical convection

Brake module AX5021. Documentation. Please read this document carefully before installing and commissioning the brake module!

EPSOLAR LS0512R / LS0524R. Solar Light Controller INSTRUCTION MANUAL. Please read this manual carefully before using the product!

Regulators. Heat pumps. Qualified technician NIBE TM AP-CS2.0. Operating Instructions UK

DS DRTE. AIR ROOM TEMPERATURE SENSOR with fan speed control switches

Technical Data. General specifications Switching element function Rated operating distance s n 15 mm

Service manual. Website: CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.

EXLUX ECOLUX C-LUX LIGHTING. Explosion Protected Fluorescent Lighting Fixtures for Hazardous and Corrosive Applications

, User s Manual

Three-phase monitoring relay CM-PFE

ACS-30-EU-EMDR-10-MOD

Infrarot-Bewegungsmelder IP44

COMPACT eco For firmware version 1.8 Rev0

WIND ALARM. Wind Speed Alarm. Wind Speed. Set Point 2. Set Point 1 NEW BEDFORD, MA USA

its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.

How To Control A Power Supply With A Mini Transmitter And Switch (Power Supply)

Electronic Pressure Switch EDS 300

Dehumidifier D 850E. - Instruction manual version 02

OPL BASIC. Dosing System for Professional Laundry machines. Contents

KNX R. Rain Sensor. Installation and Adjustment

GAE953 Electrical Alarm Unit 19" with Indicator

Installation Instructions

DALI RC BASIC SO. Control unit Operating instructions

15 Series - Electronic step relay and dimmer. Features SERIE

V - JET. Counteflow System. V-JET Counterflow System Installation and Operation Manual

GL-235 Solar Pool Controller

Wind Sensor W-RS485 with RS485 Interface

RI-215A Operator s Manual. Part Number: RK Revision 0 Released: 10/3/05

DiwiTherm, Resistance Thermometers Model TR75, with digital Display Battery or Solar Powered

Advantium 2 Plus Alarm

Doc. No: Issue: 1 Date: Aug BTT-02 card printer manual THERMAL TRANSFER CARD PRINTER BTT-02

Installation and User Instructions Unvented Electric Storage Water Heater Models: S10UNV, S15UNV.

Terminal Boxes Series 8146

with MERCURY FREE 1 HP Relays ! WARNING Before using this product read and understand instructions.

AIR CONDITIONER INSTALLATION MANUAL

MINI MCR-SL-R-UI(-SP)

Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions

Installation Instructions For Slider Casement Air Conditioners

Incubator with mechanical convection

SEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use

NO-FROST CUSTOMER SUPPORT INFORMATION INFORMATION ON THE NO-FROST TECHNOLOGY WHITE GOODS

For UK only RXL39.1 and the applications package SP-03 are sold in the United Kingdom only.

Type: EASY719 DC RC Article No.: Ordering information Relay outputs Quantity 6 Power supply V DC 24 V DC. Description

Roof Top Air Conditioner INSTALLATION AND OPERATING INSTRUCTIONS

Current Monitoring Kit QUICK START GUIDE

Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)

ELECTRICAL PLUG TYPE CONNECTIONS

Data logger. Installation and operating instructions. Read carefully before installation, commissioning and operation.

Relés e Contatores de Estado Sólido SIRIUS

RMM2 Heat-Tracing Remote Monitoring Module for the Raychem NGC Control System Installation Instructions

OEM Relative and differential pressure switch type 605

Modular I/O System Analog and Digital Interface Modules

Current Monitoring Kit

Technical Support Information No. 113 Revision 2.0 March 2005

Ergo-Pro Single Line Solar Station Installation and Operating Instructions

33.6W Power over Ethernet Waterproof Adapter PoE Plus Single Port Injector for Outdoor Application

KNX L. Brightness Sensor. Technical specifications and installation instructions Item number 70119

Install Guide 3M-50. Caution. Caution

Example of use: Fuse for a solenoid valve. If the fuse is defective, no information is sent to the electronic component.

Install Guide CT101. Caution. Caution

LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL

TRADE PRODUCTS Electronic systems for recreational vehicles Supplying controlling indicating

Please read operating instructions carefully before use and keep for further reference.

ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.

SMD Rework Station TABLE OF CONTENTS

Telis 4 Soliris RTS Operating and installation guide Ref A

PD30ETB20xxIS. Photoelectrics, Background Suppression reflective with IR light. Main features. Description

Thermistor motor protection

Pressure monitoring equipment for oil-sf 6. bushings, type GOEK

User Manual THR840DUK Digital Thermostat

Type: DILM115(RAC240) Article No.: Sales text Contactor,55kW/400V,AC operated. Ordering information

KESSEL KTP 500 Submersible Pump with lateral and vertical outlet connection Order Numbers 28710, 28810, 28850

HOSCH. Sprung blade scraper with heating system. Documentation Type B6C/H

Type: DILM32 10(24V50HZ) Article No.:

Transcription:

RESOL DeltaSol A Mounting Connection Operation Examples www.resol.dedeltasol A Manual Thanks for buying a RESOL controller. Read this manual carefully to get the best performance from this unit.

Contents Imprint... 2 Security devices... 2 Technical data and function survey... 3 1. Installation... 4 1.1 Mounting... 4 1.2 Electrical connection... 4 2. Adjustments and commissioning... 5 3. Anti-freeze function...5 4. Blinking codes...5 5. Tips for fault diagstics...5 6. Application examples... 6 Annex: Fault diagstics...8 Safety regulations: Please read the following information carefully before installing and operating the controller. In this way damage to the solar system by wrong installation will be avoided. Please observe that the mounting is adapted to the characteristics of the building, that the local regulations are respected and is conform to the technical rules. DIN 4757, part 1 Solar heating systems with water and water mixtures as heat transfer medium; Demands to the safety realization. DIN 4757, part 2 Solar heating systems with organic heat transfer medium; Demands to safety realization. DIN 4757, part 3 Solar heating systems; solar collectors; Meanings; safety regulations; Testing of standstil temperature DIN 4757, part 4 Solar thermal systems; solar collectors; determination of efficiency, heat capacity and pressure loss. In addition to that European standards are worked out: PrEN 12975-1 Thermal solar systems and their components;collectors, part 1: General demands. PrEN 12975-2 Thermal solar systems and their components; collectors; part 2: Test processes PrEN 12976-1 Thermal solar systems and their components; prefabricated systems, part 1: General demands. PrEN 12976-2 Thermal solar systems and their components; prefabricated systems, part 2: Test processes PrEN 12977-1 Thermal solar systems and their components; Customer-designed manufactured systems, part 1: General demands. PrEN 12977-2 Thermal solar systems and their components; Customer-designed manufactured systems, part 2: Test processes PrEN 12977-3 Thermal solar systems and their components; Customer-designed manufactured systems, part 3: Performance test of warm water stores. This mounting- and operation manual including all parts is copyrighted. Ather use outside the copyright requires the approval of RESOL - Elektronische Regelungen GmbH. This especially applies for copies, translations, micro films and the storage into electronic systems. Editor: RESOL - Elektronische Regelungen GmbH Important tice: We took a lot of care over the texts and drawings of this manual and to the best of our kwledge and consent. As faults can never be excluded, please te: Your own calculations and plans under consideration of the current rms and DIN-directions should only be basis for your projects. We don t offer a guarantee for the completeness of the drawings and texts of this manual - they only represent some examples. They can only be used on own risk. No liability is assumed for incorrect, incomplete or false information and the resulting damages. Errors and technical changes excepted. 2 Scope of delivery: controller DeltaSol A (full kit incl. 2 temperature sensors) spare fuse under cover ccessory bag consisting of silicone sealing, fastening screws and dowels, strain relief clamp and srews manual

Technical data Housing: plug-in plastic PC-ABS Protection type: IP 20 / DIN 40050 Ambient temp.: 0... 40 C Size: Ø130 mm, 45 mm height Mounting: wall mounting Display: 1 function control lamp Inputs: 2 sensor inputs PT1000 Outputs: 1 standard relay (changeover contact) Switch-on difference: T 2... 16 K adjustable Switch-off difference: 1,6 K below switch-on difference Control range: -20... +150 C Power consumption: max. 4 A Powersupply: 210... 250 V~ 130 45 DeltaSol A Due to the tough and consciously simple designed concept for the controller DeltaSol A,this low-priced differential controller can be universally used in solar-, heating- and air conditioning systems. The huge control range and the adjustable temperature difference make an application in nearly all systems possible in which switching processes are realised by temperature differences. The housing is optionally available with a sealing, which protects the electronics against dripping water (IP22). The controller checks a temperature diffference T measured by one of two temperature sensors by comparing this difference with a preadjusted temperature difference (adjustable within the range of 2... 16 K). The control of the system is effected by a standard relay (= changeover contact), to which several motors or electrical valves can be connected. The controller switches- ON, if the adjusted temperature difference is exceeded; if this difference is underrun by 1,6 K, the controller switches-off. Order indications RESOL DeltaSol A 115 211 20 RESOL DeltaSol A - full kit - 115 211 30 incl. 2 temperature sensors Pt1000 (1 x FKP6, 1 x FRP6) Accessory Overvoltage protection It is highly recommended to connect the RESOL overvoltage protection SP1 to all collector sensors in order to avoid overvoltages (e.g. by lightning). RESOL SP1 180 110 10 Electrostatical discharges can lead to damages of electronic components! Dangerous voltage on contact! 3

1. Installation Warning! 1.1 Mounting Switch-off power supply before opening the housing. housing 2 cover 3 base The unit must only be located internally. It is t suitable for installation in hazardous locations and should t be sited near to any electromagnetic field. Please pay attention to a separate laying of the cable lines and installation of ac power supply. 1. Choose a mounting place, drill two holes of Ø 6 mm side by side with a distance of 113 mm and fit in the enclosed dowels. 2. Fix the controller by means of the enclosed screws (4 x 40 mm)(pos. 1). 3. The electrical connection must be effected w. Power supply of the controller (210... 250 V ) must be effected by external power switch. 4 1 1.2 Electrical connection fuse T4A Connection of the sensors at the clamps: 1 / 2 = sensor 1 (e. g. collector sensor) 3 / 4 = sensor 2 (e. g. store sensor) Connection of the consumer to the clamps: 7 = rmally open contact relay (RO) 8 = break contact relay (RC) 9 = neutral contact relay (N) ground clamp collective terminal strip ac power supply to the clamps: 10 = neutral conductor N 11 = conductor L ground clamp (collective terminal strip) sensor 1 sensor 2 ground clamp (collective terminal strip) ac power supply relay (consumer) Insert sealing band without strain into the nut The guides of the required insertion channels must be broken away at the bottom side of the cover. The lines are to be fixed to the housing by enclosed strain relief supports and screws (pos.2). If necessary, activate anti-freeze function by jumper. Instert enclosed silicone sealing in base nut (without strain), if dripping water protection is necessary. Put on the cover and screw it (pos. 3). If necessary, adjust temperature difference T. Put on housing cover and screw it (pos. 4). 4

2. Adjustments and commissioning operating control lamp potentiometer for temperature difference 3. Anti-freeze function The controller comes with a deactivated anti-freeze function (by RESOL.) 4. Blinking codes Before closing the housing, the specific temperature difference T must be adjusted at the potentiometer within a scale of 2 K... 16 K. In practice, values between 6K...8K have proved. The controller comes with a switch-off delay (hysteresis) adjusted by RESOL to 1,6 K and cant be changed. The controller switches over the relay if the temperature difference between the sensors S1 and S2 is reached or exceeded. The controller switches the relay back, if the adjusted temperature difference is again underrun by 1,6 K. The controller RESOL DeltaSol A is equipped with antifreeze function. Solar systems are rmally run with a glycolwater mixture. Due to the chemichal features of this mixture an aditional anti-freeze protection is t necessary. But in some cases, solar systems are only operated with water. The anti-freeze function responds to the temperature of sensor S1 (collector sensor). As soon as this sensor measures a temperature below +4 C, warmer water from the store is pumped into the collector in order to avoid damages at the collector. If a temperature of +5 C is reached at S1, the pump switches-off. Please te that due to the limited heat reserve of the store, this function is only appropriated for those regions in which temperatures around freezing point are only reached few days per year. The jumper must be set to the position marked correspondingly in order to activate (on) or deactivate (off) the anti-freeze function. Relay active Anti-freeze protection active green green (blinking) The LED shows the actual operating status of the controller. 5. Tips for fault diagstics If the controller does t work perfectly, please check the following items: bracket for spare fuse (interior part of cover) C -10-5 0 5 10 15 20 25 30 If the controller does t switch-on correctly, even if ac power supply is impressed, please check the fuses (see 1.2). The controller is guarded by a fine fuse T4A, which can be replaced after having removed the housing and the cover. A spare fuse is enclosed on the backside of the cover. Please check the sensors. Sensors which are t connected, must have the following resistance values depending on the given temperature. Ω 961 980 1000 1019 1039 1058 1078 1097 1117 C 35 40 45 50 55 60 65 70 75 Ω 1136 1155 1175 1194 1213 1232 1252 1271 1290 C 80 85 90 95 100 105 110 115 Ω 1309 1328 1347 1366 1385 1404 1423 1442 Resistance values of Pt1000-sensors 5

6. Application examples Standard solar system with 1 store 1 2 3 4 7 8 9 10 11 S1 S2 RO RC N N L S1 RO S2 Use ground clamp collective terminal strip! If the current temperature difference T between collector sensor S1 and store sensor S2 exceeds the temperature difference adjusted at the controller, the solar pump is switched-on. Heat is transported from the collector to the store; in doing so, the temperature difference is reduced. If the adjusted temperature difference is underrun by a difference of 1,6 K (hysteresis, cant be changed), the pump is switched-off again. S1 = collector sensor S2 = store sensor RO = solar pump Heating circuit reverse raising 1 2 3 4 7 8 9 10 11 S1 S2 RO RC N N L S1 S2 R0 Use ground clamp collective terminal strip! If the temperature difference T between store sensor S1 and heating circuit reverse sensor S2 exceeds the temperature difference adjusted at the controller, the 3- way-valve is switched-over. The reverse temperature of the heating circuit is raised by the heat of the store so that less conventional enery is necessary for reaching the feed flow temperature; in doing so, the temperature difference 6 is reduced. If the adjusted temperature difference is underrun by a difference of 1,6 K (hysteresis, cant be changed), the valve is switched to initial position. S1 = store sensor S2 = heating circuit reverse sensor RO = 3-way-valve

Heat exchange (between two stores) 1 2 3 4 7 8 9 10 11 S1 S2 RO RC N N L S1 R0 S2 Use ground clamp collective terminal strip! If the temperature difference T between store (1) sensor S1 and store (2) sensor S2 exceeds the temperature adjusted at the controller, the circulation pump is switched-on. Heat is transported from the store (1) into store (2); in doing so, the temperature difference is reduced. If the adjusted temperature difference is underrun by a difference of 1,6 K (hysteresis, cant be changed), the pump is switched-off again. S1 = store (1) sensor S2 = store (2) sensor RO = circulation pump 7

Annex: Fault diagstics Pump is overheated, but heat transfer from collector to the store, feed flow and return flow are equally warm, perhaps also bubble in the lines. Pump starts for a short moment, switches-off, switches-on again, etc. ( controller hunting ) Air in the system? Is the collector circuit plugged at the dirt trap? Exhaust the system; increase system pressure to at least static primary pressure plus 0,5 bar; if necessary continue to increase, switch the pump for a short time off and on. Is the temperature difference at the controller too small? Wrong placing of the collector sensor? Change Ton and Toff accordingly. o.k. Clean the dirt trap Plausibility control of the option tube collector special function? Mount the collector sensor at solar feed flow (warmest collector output); use the immersion sleeve of the respective collector. Pump starts up very late and soon stops working soon. The temperature difference between store and collector increases ermously during operation; the collector circuit cant dissipate the heat. Switch-on-temperature difference Ton too large? Collector circuit pump defect? Change Ton and Toff accordingly. Control / replacement Collector sensor unfavourable placed (e.g. contact sensor instead of immersion sleeve sensor? Heat exchanger calcified? Decalification If necessary activate tube collector function. o.k. Heat exchanger plugged? Cleaning Heat exchanger too small? New calculation of the dimension. 8

Stores are cooled during the night. The solar circuit pump does t work although the collector is obviously warmer than the store. Does collector circuit pump run during the night? Check the controller functions Does the control LED flash? There is current; check fuses / replace them and check power supply. Collector temperature is at night higher than ambient temperature. Check the return flow preventer in feed flow and return flow with regard to the functional efficiency. Does the pump start up in manual operation? The adjusted temperature difference for starting the pump is too high; choose a value which makes more sense. Is store insulation sufficient? Intensify the insulation. Is the current of the pump released by the controller? Is the pump stuck? Is store insulation close eugh to the store? Replace or intensify the insulation. Put the pump into operation by means of a screwdriver; is it passable w? Are the store connections insulated? Insulate connections. Are the fuses of the controller o.k.? Is the pump defective - replace it. Warm water outflow upwards? Change connection and let the water flow sidewards or through a siphon (bow downwards); less store losses w? Replace the fuses. Controller seems to be defective - replace it. o.k. Control the return flow preventer in warm water circulation- o.k. Please also check further pumps which are connected to the solar store. Cleaning or replacement. 9