1 RESOL DeltaSol C Plus * * Mounting Connection Operation Troubleshooting Examples Thank you for buying this RESOL product. Please read this manual carefully, to get the best performance from this unit. DeltaSol C Plus B Manual
2 Table of contents Safety advice... 2 Overview of functions and technical data Installation Mounting Electrical connection Data communication / bus Terminal allocation Arrangements Operation and function Buttons for adjustment System-Monitoring display Channel display Toolbar System-Screen Flashing codes Commissioning Control parameters and and display channels Overview of channels Display channels Adjustment channels Troubleshooting Various Accessory Imprint Safety advice Please pay attention to: - safety advice in order to avoid danger and damage to people and property. - the valid local standards, regulations and directives! Description of symbols WARNING! Warnings are indicated with a warning triangle! They contain information on how to avoid the danger described. Target group These instructions are exclusively addressed to authorised skilled personnel. Only qualified electricians should carry out electrical works. Initial installation must be effected by qualified personnel named by the manufacturer. Information about the product Proper usage The solar controller is designed for use in solar thermal and heating systems in compliance with the technical data specified in these instructions. Improper use excludes all liability claims. Signal words describe the danger that may occur, when it is t avoided. WARNING means that injury, possibly life-threatening injury, can occur. ATTENTION means that damage to the appliance can occur. Note Notes are indicated with an information symbol. Disposal Dispose of the packaging in an environmentally sound manner. Dispose of old appliances in an environmentally sound manner. Upon request we will take back your old appliances bought from us and guarantee an environmentally sound disposal of the devices. CE-Declaration of conformity The product complies with the relevant directives and is therefore labelled with the CE mark. The Declaration of Conformity is available upon request, please contact RESOL. Note Strong electromagnetic fields can impair the function of the controller. ÎÎMake sure the controller as well as the system are t exposed to strong electromagnetic fields. Subject to technical change. Errors excepted. 2
3 Functional overview! System-Monitoring display up to 4 temperature sensors Pt semiconductor relays for pump speed control 9 basic systems to choose from heat quantity measurement RESOL VBus function control thermostat function thermal disinfection real time clock user-friendly operation easy-to-mount housing and outstanding design Technical data Housing: plastic, PC-ABS and PMMA Protection type: IP 20 / DIN Ambient temp.: C Dimensions: 172 x 111 x 49 mm Mounting: wall mounting, mounting into patch panels is possible Display: system monitor for systems visualisation, 16-segment display, 7-segment display, pictograms Operation: 3 push buttons at the front of the housing Functions: Thermal disinfection, function control, operating hours counter, tube collector function, pump speed control, thermostat function and heat quantity measurement Inputs: for 4 temperature sensors Pt1000 Outputs: 2 semiconductor relays Bus: RESOL VBus Power supply: V~ Total switching capacity: 2 (2) A ( ) V~ Switching capacity per relay: semiconductor relay: 1 (1) A ( ) V~ 3
4 1. Installation 1.1 Mounting cover display push button WARNING! ÎÎAlways disconnect the controller from power supply before opening the housing! The unit must only be located in dry interior locations. It is t suitable for installation in hazardous locations and should t be placed close to any electromagnetic fields. The controller must additionally be supplied from a double pole switch with contact gap of at least 3 mm. Please pay attention to separate routing of sensor cables and mains cables. 1. Unscrew the cross-head screw from the cover and remove it along with the cover from the housing. 2. Mark the upper fastening point on the wall and drill and fasten the enclosed wall plug and screw leaving the head protruding. 3. Hang the housing from the upper fastening point and mark the lower fastening point through the hole in the terminal box (centres 130 mm). Drill and insert the lower wall plug. 4. Hang the housing from the upper fastening point and tighten lower fastening screw. cable conduit with strain relief 130 fastening base fuse fastening 1.2 Electrical connection sensor terminals 1 (1) A ( ) V~ 1 (1) A ( ) V~ VBus 9 10 VBus ground terminals IP 20 load terminals fuse T2A V~ Hz mains terminals Electrostatic discharge can cause damage of electronic components! High-voltage components! Note The relays are semiconductor relays for pump speed control. The minimum pump speed must be set to 100% when auxiliary relays or valves are connected. The power supply to the controller must be carried out via an external power switch (last step!) and the supply voltage must be V~ ( Hz). Flexible cables must be attached to the housing with the enclosed strain relief and the corresponding screws. The controller is equipped with 2 relays to which loads such as pumps, valves etc. can be connected: Relay 1 18 = conductor 17 = neutral conductor N 13 = ground terminal Relay 2 16 = conductor 15 = neutral conductor N 14 = ground terminal The temperature sensors ( to S4) have to be connected to the following terminals (either polarity): 1 / 2 = sensor 1 (e. g. sensor collector 1) 3 / 4 = sensor 2 (e. g. sensor store 1) 5 / 6 = sensor 3 (e. g. sensor collector 2) 7 / 8 = sensor 4 (e. g. sensor store TRF) The mains connection is at the terminals: 19 = neutral conductor N 20 = conductor L 12 = ground terminal 4
5 1.2.1 Data communication / bus IP 20 1 (1) A ( ) V~ 1 (1) A ( ) V~ VBus 9 10 T2A V~ Hz The controller is equipped with the RESOL VBus for data transfer with and energy supply to external modules. The connection is carried out at the two terminals 9 and 10 marked VBus (either polarity). One or more RESOL VBus modules can be connected via this data bus: GA3 large display, SD3 smart display DL2 datalogger VBus /USB or VBus /LAN interface adapter VBus /PWM interface adapter AM1 alarm module WMZ calorimeter module By means of a DL2 datalogger or an interface adapter, the controller can be connected to a PC or a computer network. With the RESOL ServiceCenter Software (RSC) the controller measurements can be read out, processed and visualised. The software allows easy function control of the system. For the remote parametrisation of the controller, a special software tool will be available for download, soon Terminal allocation Arr 1 Standard solar system with 1 store, 1 pump and 3 sensors. Sensor S4 / TRF can optionnally be used for heat quantity measurement. ARR 1 S4 / TRF Symbol Description collector sensor store sensor base store sensor top / (optional) S4 / TRF sensor for heat quantity measurement (optional) solar pump 5
6 1.2.3 Terminal allocation Arr 2 Solar system and heat exchange to existant store with 2 stores, 4 sensors and 2 pumps. ARR 2 store 1 store 2 S4 Symbol Description collector sensor store base sensor store top sensor S4 store sensor 2 solar pump pump for heat exchange Terminal allocation Arr 3 Solar system and after-heating with 1 store, 3 sensors and after-heating. Sensor S4 / TRF can optionnally be used for heat quantity measurement. ARR 3 S4 / TRF Symbol S4 / TRF Description collector sensor store sensor base store sensor top Sensor for heat quantity measurement (optional) solar pump charging pump after-heating 6
7 1.2.5 Terminal allocation Arr 4 Solar system and vertical store charging with 1 store, 3 sensors, 1 solar pump and 3-port valve for vertical store charging. Sensor S4 / TRF can optionnally be used for heat quantity measurement. ARR 4 S4 / TRF Symbol S4 / TRF Description collector sensor store sensor base store sensor top sensor for heat quantity measurement (optional) solar pump 3-port valve Terminal allocation Arr 5 2-store solar system with valve control with 2 stores, 3 sensors, 1 solar pump and 1 3-port valve. Sensor S4 / TRF can optionnally be used for heat quantity measurement. ARR 5 S4 / TRF store 1 store 2 Symbol Description collector sensor store sensor 1 store sensor 2 S4 / TRF sensor for heat quantity measurement (optional) solar pump 3-port valve 7
8 1.2.6 Terminal allocation Arr 6 2-store solar system with pump control with 2 stores, 3 sensors and 2 solar pumps. ARR 6 S4 store 1 store 2 Symbol Description collector sensor store sensor 1 store sensor 2 S4 sensor (optional) solar pump store 1 solar pump store Terminal allocation Arr 7 Solar system with east-/west collectors, 1 store, 3 sensors and 2 solar pumps. ARR 7 Symbol Description collector sensor 1 store sensor collector sensor 2 S4 sensor (optional) solar pump collector 1 solar pump collector 2 8
9 1.2.8 Terminal allocation Arr 8 Solar system with after-heating with solid fuel boiler with 1 store 4 sensors, 1 solar pump and 1 pump for afterheating. ARR 8 S4 Symbol S4 Description collector sensor store sensor base store sensor top sensor for solid fuel boiler solar pump pump for solid fuel boiler Terminal allocation Arr 9 Solar system and heating circuit return preheating with 1 store, 4 sensors, 1 solar pump and 1 3-port valve for heating circuit return preheating. ARR 9 S4 Symbol S4 Description collector sensor store sensor base store sensor top heating circuit - return solar pump 3-port valve 9
10 2. Operation and function 2.1 Buttons for adjustment 1 forwards 3 2 SET (selection/adjustment mode) backwards Connect the controller to the mains. The controller is in an initialisation phase. After this phase, the controller is in automatic operation with factory settings. The controller is operated via the 3 push buttons below the display. The forward-button (1) is used for scrolling forward through the menu or to increase the adjustment values. The backward-button (2) is similarly used for scrolling backwards and reducing values. In order to access the adjustment mode, scroll down in the display menu and press the forward button (1) for approx. 2 seconds after you have reached the last display item. If an adjustment value is shown on the display, the icon is displayed. Now, you can access the adjustment mode by using button 3. Press buttons 1 and 2 in order to select a channel Briefly press button 3, appears (flashing) ( -mode) adjust the requested value by pressing the buttons 1 and 2 Briefly press button 3, so that permanently appears, the adjusted value will be saved. 2.2 System-Monitoring display! The system monitoring display consists of 3 ranges: The channel display, the toolbar and the system-screen (active arrangement). Monitoring-Display Channel display Toolbar channel display The channel display consists of 2 lines. The upper line is an alpha-numeric 16-segment display (text display) for displaying channel names and menu items. In the lower 7-segment display, the channel values and the adjustment parameters are displayed. Temperatures and temperature differences are indicated in or. The additional symbols in the toolbar indicate the actual system status. toolbar symbol rmal flashing relay 1 active relay 2 active store maximum limitation active / maximum store temperature exceeded collector cooling function active recooling function active collector minimum limitation antifreeze function active active antifreeze function active collector emergency shutdown active or store emergency shutdown active + sensor fault + manual mode change of adjustment channel SET-mode 10
11 2.2.3 System-Screen System screen The system screen (active arrangement) shows the scheme which has been selected. The screen consists of several system component symbols, which are - depending on the current status of the system - either flashing, permanently shown or hidden. sensor sensor store bottom heating circuit collector valve pumps store heat exchanger store store 2 or afterheating (with additional symbol) valve sensor additional symbol operation of the burner collectors with collector sensor store 1 and 2 with heat exchanger temperature sensor heating circuit pump 3-port valve the flow direction or the current switching position is shown after-heating with burner symbol 2.3 Flashing codes Pump symbols are flashing during the initialisation phase Sensor symbols are flashing when the corresponding sensor display channel is selected. Sensor symbols are flashing in the case of a sensor fault Burner symbol is flashing when the after-heating is active. 11
12 3. Commissioning When the controller is commissionend for the first time, the arrangement has to be selected first 1. Switch on power supply. After initialisation, the controller is in the automatic mode with typical settings. The preprogrammed system scheme is Arr Adjust the actual clock time in the TIME channel. Pressing the -key for 2 seconds will display the hours, pressing 1 forwards the button again will display the minutes (flashing). Time can be adjusted using buttons 1 and 2. Save the changes SET by pressing the -key. 3 (selection / 3. - Select the ARR channel adjustment mode) - Change into the -mode (see 2.1) 2 backwards - Selct the system arrangement via the ARR number - Save adjustments by pressing the -key Now the controller is ready for operation with typical settings to suit that system and rmally the factory settings will give close to optimum operation. ARR 1 ARR 2 ARR 3 ARR 4 ARR 5 ARR 6 Overview of arrangements: ARR 1 : standard solar thermal system ARR 2 : solar thermal system with heat exchange ARR 3 : solar thermal system with after-heating ARR 4 : solar thermal system with vertical store charging ARR 5 : 2-store solar thermal system with valve control ARR 6 : 2-store solar thermal system with pump control ARR 7 : solar thermal system with 2 collectors and 1 store ARR 8 : solar thermal system with after-heating with solid fuel boiler ARR 9 : solar thermal system heating circuit return preheating ARR 7 ARR 8 ARR 9 12
13 4. Control parameters and display channels 4.1 Overview of channels Legend: x Corresponding channel is available. x* Corresponding channel is available when the corresponding option is enabled Note Only if temperature sensors are connected, will and S4 be displayed. Only if the option heat quantity measurement is activated (OHQM), will the corresponding channel be available. Only if the option heat quantity measurement is deactivated (OHQM), will the corresponding channel be available. MEDT Only if an antifreeze (MEDT) other than water or Tyfocor LS / G-LS (MEDT 0 or 3) is used, will the channel antifreeze concentration (MED%) be displayed. The adjustment of the antifreeze concentration has only to be carried out when an antifreeze is used in the solar circuit. ARR channel descritption page COL x x x x x x x x temperature collector 1 15 COL 1 x temperature collector 1 15 TST x x temperature store 1 15 TSTU x x x x temperature store 1 base 15 TST1 x x x temperature store 1 base 15 TSTO x x x x x temperature store 1 top 15 TST2 x x x temperature store 2 base 15 TFSK x temperature solid fuel boiler 15 TREC x temperature heating circuit 15 COL2 x temperature collector 2 15 x temperature sensor 3 15 TRF temperature return temperature sensor 15 S4 x x temperature sensor 4 15 n % x x x x speed relay 1 15 n1 % x x x x x speed relay 1 15 n2 % x x x x speed relay 2 15 hp x x x x operating hours relay 1 16 h P1 x x x x x operating hours relay 1 16 h P2 x x x x x operating hours relay 2 16 CDIS x* Countdown of monitoring period 16 SDIS x* Starting time display 16 DDIS x* Heating period display 16 kwh heat quantity kwh 16 MWh heat quantity MWh 16 TIME x time 15 ARR 1-9 arrangement 12 DT O x x x x x x switch-on temperature difference 17 DT1O x x x switch-on temperature difference 1 17 DT F x x x x x x switch-off temperature difference 1 17 DT S x x x x x x set temperature difference 17 RIS x x x x x x rise 17 DT1F x x x switch-off temperature difference 17 RI x x x rise 1 17 DT1S x x x set temperature difference 1 17 S MX x x x x x x maximum temperature store 1 17 MX x x x maximum temperature store 1 17 DT2O x x x switch-off temperature difference 2 17 DT2F x x x switch-off temperature difference 2 17 DT2S x x x set temperature difference 2 17 RI x x x rise 2 17 MX x x x maximum temperature store
14 channel ARR description EM x x x x x x x x emergency temperature collector 1 18 EM1 x emergency temperature collector 1 18 OCX x x x x x x x x option collector cooling collector 1 18 OCX1 x option collector cooling collector 1 18 CMX x* x* x* x* x* x* x* x* maximum temperature collector 1 18 CMX1 x* maximum temperature collector 1 18 OCN x x x x x x x x option minimum limitation collector 1 18 OCN1 x option minimum limitation collector 1 18 CMN x* x* x* x* x* x* x* x* minimum temperature collector 1 18 CMN1 x* minimum temperature collector 1 18 OKF x x x x x x x x option frost protection collector 1 18 OKF1 x option frost protection collector 1 18 CFR x* x* x* x* x* x* x* x* frost protection temperature collector 1 18 CF x* frost protection temperature collector 1 18 EM2 x emergency temperature collector 2 18 OCX2 x option collector cooling collector 2 18 CMX2 x* maximum temperature collector 2 18 OCN2 x option minimum limitation collector 2 18 CMN2 x* minimum temperature collector 2 18 OCF2 x option frost protection collector 2 18 CF x* frost protection temperature collector 2 18 page PRIO x x x priority 19 tst x x x loading break time 19 tcirc x x x oscillating loading time 19 OREC x x x x x x x x x option recooling 19 O TC x x x x x x x x x option tube collector 19 DT3O x x switch-on temperature difference 3 17 DT3F x x switch-off temperature difference 3 17 DT3S x x set temperature DT3 17 RI x x rise DT3 17 MX3O x x switch-on threshold for maximum temp. 17 MX3F x x switch-off threshold for maximum temp. 17 MN3O x x switch-on threshold for minimum temp. 17 MN3F x x switch-off threshold for minimum temp.. 17 AH O x switch-on temperature thermostat 1 20 AH F x switch-off temperature thermostat 1 20 t1 O x switch-on time 1 thermostat 20 t1 F x switch-off time 1 thermostat 20 t2 O x switch-on time 2 thermostat 20 t2 F x switch-off time 2 thermostat 20 t3 O x switch-on time 3 thermostat 20 t3 F x switch-off time 3 thermostat 20 OtD x Option thermal disinfection 16 PDIS x* Monitoring period 20 DDIS x* Heating period 20 TDIS x* Disinfection temperature 16 SDIS x* Starting time 16 CDIS x* Countdown of monitoring period 16 n2mn x x x x minimum speed relay 2 20 HND1 x x x x x x x x x manual operation relay 1 20 HND2 x x x x x x x x x manual operation relay 2 20 LANG x x x x x x x x x Language 20 PROG XX.XX program number VERS X.XX version number 14
15 4.1.1 Collector temperatures COL, COL1, COL2: Collector temperatures display range: C Store temperatures TST, TSTL, TSTU, TST1, TST2: Store temperatures Display range: C Sensors 3 and 4, S4: Sensor temperatures Display range: C Other temperatures TSFB, TREC, TRF: Other measured temperatures Display range: C Pump speed n %, n1 %, n2 %: Current pump speed Display range: % Time Displays the current collector temperature. COL : collector temperature (1-collector system) COL1 : collector temperature 1 COL2 : collector temperature 2 Displays the current store temperature. TST : store temperature (1-store system) TSTL : store temperature base TSTU : store temperaturer top TST1 : temperature store 1 TST2 : temperature store 2 Display of the current temperature at the corresponding additional sensor (without control function). : temperature sensor 3 S4 : temperature sensor 4 Note Only if temperature sensors are connected, will and S4 be displayed Display of the current temperature at the corresponding sensor. TSFB : temperature solid fuel boiler TREC : temperature heating return TRF : temperature return Display of the current speed of the corresponding pump. n % : actual pump speed (1-pump system) n1 % : actual speed pump 1 n2 % : actual speed pump 2 In this channel the current time is indicated. Press button for 2 seconds, the hours will then be displayed. Press the button again, the minutes will then be displayed (flashing). The time can be set using buttons 1 and 2 and saved by pressing the button Operating hours counter h P / h P1 / h P2: Operating hours counter Display channel The operating hours counter accumulates the solar operating hours of the respective relay (h P / h P1 / h P2). Full hours are displayed. The accumulated operating hours can be set back to zero. As soon as one operating hours channel is selected, the symbol is displayed. Press the SET (3) button for approx. 2 seconds in order to access the RESET-mode of the counter. The display symbol will flash and the operating hours will be set to 0. Confirm the reset with the button in order to finish the reset. In order to interrupt the RESET-process, do t press a button for about 5 seconds. The display returns to the display mode. 15
16 4.1.7 Thermal disinfection CDIS Countdown of monitoring period Display range: : (dd:hh) SDIS Starting time display Display range: 00: :00 (hh:mm) DDIS Heating period display Display range: 00: :00 (hh:mm) If the thermal disinfection option (OtD) is activated and the monitoring period is in progress, the remaining monitoring time will be displayed as CDIS (in days and hours) and counted backwards. If the thermal disinfection option (OtD) is activated and a starting delay time has been adjusted, the adjusted delay time is displayed (flashing) in this channel. If the thermal disinfection option (OtD) is activated and the heating period is in progress, the remaining time of the heating period is displayed (in hours and minutes) in this channel, counting backwards Heat quantity measurement OHQM: Heat quantity measurement Adjustment range: OFF...ON- Factory setting: OFF FMAX: Flow rate in l/min Adjustment range , in 0.1 steps Factory setting: 6,0 MEDT: Antifreeze type Adjustment range: Factory setting: 1 Heat quantity measurement is possible in systems (ARR) 1, 3, 4 and 5 if a flowmeter is used. For this purpose, the heat quantity measurement option OHQM has to be enabled. The flow rate should be read from the flowmeter (l/min) and has to be adjusted in the channel FMAX. Antifreeze type and concentration of the heat transfer medium have to be adjusted in the channels MEDT and MED%. Antifreeze type: 0 : water 1 : propylene glycol 2 : ethylene glycol 3 : Tyfocor LS / G-LS MED%: Antifreeze concentration in (Vol-) % When MEDT 0 or 3 is used, the parameter MED% is hidden. Adjustment range: Factory setting: 45 kwh/mwh:heat quantity kwh / MWh Display channel 16 The flow rate as well as the reference sensors (flow) and S4 (return) are used for calculating the heat quantity supplied. It is shown in kwh in the channel kwh uand in MWh in the channel MWh. The overall heat quantity results from the sum of both values. The accumulated operating hours can be set back to zero. As soon as one of the display channels of the heat quantity is selected, the symbol is displayed. Press the SET (3) button for approx. 2 seconds in order to access the RESETmode of the counter. The display symbol will flash and the heat quantity value will be set to 0. Confirm the reset with the button in order to finish the reset. In order to interrupt the RESET process, button should be pressed for about 5 seconds. The display returns to the display mode.
17 4.1.9 T-control DT O / DT1O / DT2O / DT3O: Switch-on temperature difference Adjustment range: 1, ,0 K Factory setting: 6.0 DT F / DT1F / DT2F / DT3F: Switch-off temperature difference Adjustment range: 0, ,5 K Factory setting: 4.0 K DT S / DT1S / DT2S / DT3S: Set temperature difference Adjustment range: 1, ,0 K Factory setting: 10.0 RIS / RI / RI / RI: Rise Adjustment range: K Factory setting: 2 K This function is a standard differential control. If the switchon differential is reached (DT O / DT1O / DT2O) the pump is operated. The pump runs at 100% speed for 10 seconds. After this period, the pump runs at minimum pump speed (nmn = 30 %) gefahren. f the temperature difference reaches the adjusted set value (DT S / DT1S / DT2S / DT3S), spump speed will increase by one step (10 %). If the difference increases by 2 K (RIS / RI / RI / RI) pump speed will increase by 10 % respectively until the maximum pump speed of 100 % is reached. The response of the controller can be adapted via the parameter Rise If the temperature difference falls below the adjusted switch-off temperature difference (DT F / DT1F / DT2F) the controller switches off. DT O and DT S are blocked against each other. DT S must be at least 0,5 K higher than DT O. Note Switch-on temperature difference must be at least 1 K higher than the switch-off tempe rature difference Maximum store temperature If the adjusted maximum temperature is exceeded, the store will longer be loaded in order to avoid damage caused by overheating. If the maximum store temperature is exceeded, (flashing) is shown on the display. S MX / MX / MX: Maximum store temperature Adjustment range: C Factory setting: 60 C T control (solid fuel boiler and heat exchange) Maximum temperature limitation MX3O / MX3F: Maximum temperature limitation Adjustment range: 0, ,0 C Factory setting: MX3E 60,0 C MX3A 58,0 C Note The controller is equipped with a store emergency shutdown function, which prevents the store from being loaded when the store temperature exceeds 95 C. The controller is equipped with an independent temperature differential control function for which minimum and maximum temperature limations as well as the corresponding switch-on and -off temperatures can be separately adjusted. For ARR = 2 and 8 only (solid fuel boiler and heat exchange control). Minimum temperature limitation MN3O / MN3F: Minimum temperature limitation Adjustment range: 0, ,0 C Factory setting: ARR = 2 MN3O 5,0 C MN3F 10,0 C ARR = 8 MN3O 60,0 C MN3F 65,0 C If the adjustet value MX3O is exceeded, relay 2 will be switched off. If the temperature falls below the value MX3F, the relay will be energised. Reference sensors: for ARR 8 (TSTU) S4 for ARR 2 (TST2). If the temperature falls below MN3O, relay 2 will be switched off. If the value MN3F is exceeded, the relay will be energised. Reference sensors: S4 for ARR 8 (TSFB) for ARR 2 (TSTU). The switch on- and switch off temperature differences DT3O and DT3F also apply to the maximum- and minimum temperature limitation. 17
18 Collector-limit temperature Collector emergency shutdown EM / EM1 / EM2: Collector emergeny shutdown temperature Adjustment range: C Factory setting: 140 C If the adjusted collector emergency shutdown temperature (NOT / NOT1 / NOT2) is exceeded, the controller will switch off the solar pump ( / ) in order to protect the system against overheating (collector emergency shutdown). The factoring setting is 140 C but it can be changed within the adjustment range of C. If the temperature is exceeded, (flashing) is shown on the display System cooling When the adjusted maximum store temperature is reached, the system stagnates. If the collector temperature increases OCX / OCX1 / OCX2: to the adjusted maximum collector temperature (CMX System cooling option / CMX1 / CMX2) the solar pump is activated until the Adjustment range: OFF... ON collector temperature falls below the maximum collector Factory setting: OFF temperature. The store temperature may increase (subordinate active maximum store temperature), but only up CMX / CMX1 / CMX2: to 95 C (emergency shutdown of the store). If the store Maximum collector temperature is higher than the maximum store temperature temperature (S MX / MX / MX) and if the collector temperature Adjustment range: C is at least 5 K below the store temperature, the solar system Factory setting: 120 C remains activated until the store is cooled down below the adjusted maximum temperature (S MX / MX / MX) via the collector and the pipework (only if the OREC function is activated). If the system cooling function is enabled, (flashing) is shown on the display. Due to the cooling function, the system will have a longer operation time on hot summer days and guarantees thermal relief of the collector field and the heat transfer fluid Collector minimum limitation option OCN / OCN1 / OCN2: Collector minimum limitation Adjustment range: OFF / ON Factory setting: OFF CMN / CMN1 / CMN2: Collector minimum temperature Adjustment range: C Factory setting: 10 C The minimum collector temperature is the minimum temperature which must be exceeded for the solar pump ( / ) to switch on. The minimum temperature prevents the pump from being switched on too often at low collector temperatures. If the temperature falls below the minimum temperature, (flashing) is shown on the display Frost protection function option OCF / OCF1 / OCF2: Frost protection function Adjustment range: OFF / ON Factory setting: OFF CFR / CF / CF: Frost protection temperature Adjustment range: C Factory setting: 4,0 C Store sequence control Corresponding adjustment values: 18 The antifreeze function activates the loading circuit between the collector and the store when the temperature falls below the adjusted antifreeze temperature. This will protect the fluid against freezing or coagulating. If the adjusted antifreeze temperature is exceeded by 1 C, the loading circuit will be deactivated. Note Since this function uses the limited heat quantity of the store, the antifreeze function should be used in regions with few days of temperatures around the freezing point. Factory setting Priority [PRIO] (1 / ARR 5,6) (2 / ARR 4) 0-2 Loading break time [tsp] 2 min min. Oscillating loading time [tumw] 15 min min. Adjustment range
19 The DeltaSol C Plus priority logic: Priority: Loading break time / store sequence control: / collector rise temperature: The options and parameters mentioned above are used in multi-store systems only (system ARR = 4, 5, 6). If priority is set to 0, the stores with a temperature difference to the collector are loaded in numerical order (store 1 or 2; ARR= 4, 5). Basically, only one store can be loaded at a time. In ARR the stores can be loaded in parallel. When the priority store cant be loaded, the subordinate stores are checked. If a subordinate store can be loaded, it will be loaded for the oscillating loading time ( t-circ. ). After this period of time, the loading process stops. The controller monitors the increase in collector temperature.if it increases by the collector rise temperature ( T-col 2 K, software value) within the loading break time (t-st) the elapsed break time is set to 0. The break time starts again.the switch-on condition of the priority store is t fulfilled, loading of the subordinate store will be continued. If the priority store reaches its maximum temperature, oscillating loading will t be carried out Recooling function If the adjusted maximum store temperature (S MX, MX, MX) is reached, the controller keeps the solar pump OREC: Recooling option Adjustment range: OFF... ON Factory setting: OFF Tube collector function O TC: Tube collector function Adjustment range: OFF... ON Factory setting: OFF running in order to prevent the collector from being overheated. The store temperature may increase, but only up to 95 C (emergency shutdown of the store). The solar pump is switched on as soon as possible (depending on weather conditions). It is switched off when the store is cooled down to the adjusted maximum temperature via the collector and the pipework. If the controller detects an increase in collector temperature by 2 K compared to the previously stored collector temperature, the solar pump will be switched-on for about 30 seconds in order to detect the fluid temperature. After this, the current collector temperature will be saved as a new reference value. If the measured temperature (new reference value) is exceeded by 2 K, the solar pump will run for 30 seconds. If the switch-on difference between the collector and the store is exceeded during the runtime of the solar pump or the standstill of the system, the controller will automatically switch to solar loading. If the collector temperature deacreases by 2 K during standstill, the switch-on value for the tube collector function will be recalculated Thermostat function (ARR = 3) afterheating use of surplus heat The thermostat function works independently from the solar operation and can be used for using surplus energy or for after-heating. AH O < AH F thermostat function for after-heating AH O > AH F thermostat function for using surplus energy When the 2nd relay output is active, is displayed AH O: Thermostat switch-on temp. Adjustment range: 0, ,0 C Factory setting: 40,0 C AH F: Thermostat switch-off tem p. Adjustment range: 0, ,0 C Factory setting: 45,0 C 19
20 t1 O t2 O, t3 O: Thermostat switch-on time Adjustment range: 00: :45 Factory setting: 00:00 t1 F, t2 F, t3 F: Thermostat switch-off time Adjustment range: 00: :45 Factory setting: 00:00 In order to block the thermostat function for a certain period of time, there are 3 time frames t1... t3. If the function should be activated only between e.g. 6:00 and 9:00, set t1 O to 6:00 and t1 F to 09:00. The thermostat function is continuously activated (factory setting). If all time frames are set to 00:00, the thermostat function is continuously activated (factory setting). Thermal disinfection OtD: Thermal disinfection function Adjustment range: ON / OFF Factory setting: OFF PDIS: Monitoring period Adjustment range: : h (dd:hh) Factory setting: 01:00 DDIS Heating period Adjustment range: 00: :59 (hh:mm) Factory setting: 01:00 TDIS Disinfection temperature Adjustment range: C in steps of 1 K Factory setting: 60 C This function helps to contain the spread of Legionella in DHW stores by systematically activating the afterheating. For thermal disinfection, the temperature at the allocated sensor has to be monitored. This protection is ensured when, during the monitoring period, the disinfection temperature is continuously exceeded for the entire disinfection period. The monitoring period starts as soon as the temperature at the allocated sensor falls below the disinfection temperature. When the monitoring period ends, the allocated reference relay activates the afterheating. The disinfection period starts, if the temperature at the allocated sensor exceeds the disinfection temperature. Thermal disinfection can only be completed when the disinfection temperature is exceeded for the duration of the disinfection period without any interruption. Thermal disinfection with starting delay SDIS Starting time Adjustment range: 00: :00 (o clock) Factory setting: 00:00 If the starting delay option is activated, a starting time for the thermal disinfection with starting delay can be adjusted. The activation of the afterheating is then delayed until that starting time after the monitoring period has ended. If the monitoring period ends, for example, at 12:00 o clock, and the starting time has been set to 18:00, the reference relay will be energised with a delay of 6 hours at 18:00 instead of 12:00 o clock. Note: If the thermal disinfection option is activated, the display channels TDIS, CDIS, SDIS, and DDIS will be displayed. 20
21 Pump speed control A relative minimum pump speed is allocated to the output nmn, n1mn, n2mn: and via the adjustment channel nmn, n1mn, and n2mn. Pump speed control ATTENTION: Adjustment range: When loads which are t speed controlled (e.g. Factory setting: 30 valves) are used, the value must be changed to 100 % in order to deactivate pump speed control Operating mode HND1/HND2: Operating mode Adjustment range: OFF, AUTO, ON Factory setting: AUTO Language (LANG) LANG: Language choice Adjustment range: de, En, It, Fr Factory setting: En For control and service work, the operating mode of the controller can be manually adjusted. For this purpose, select the adjustment value HND1, The following adjustments can be carried out: HND1 / HND2 operating mode OFF : relay off (flashing) + AUTO : relay in automatic operation ON : relay on (flashing) + In this channel, different languages are available. de : German En : English It : Italian Fr : French 5. Troubleshooting fuse T2A On the display appears the symbol and the symbol. IP 20 1 (1) A ( ) V~ 1 (1) A ( ) V~ VBus 9 10 T2A V~ Hz Sensor defect. An error code is shown on the relevant sensor indication channel instead of a temperature Line break. Check the line. Short-circuit. Check the line. If a malfunction occurs, a tification is given on the display of the controller: Pt1000-temperature sen sors pinched off can be checked with an ohmmeter. In the following the resistance values corresponding to different temperatures are listed. Warning symbol Resistance values of the Pt1000-sensors 21
22 5.1 Various Pump is overheated, but heat transfer from collector to the store, feed flow and return flow are equally warm, perhaps also bubble in the lines. Pump starts for a short moment, switches-off, switches-on again, etc. ( controller hunting ) Air in the system? Is the collector circuit plugged at the dirt trap? Exhaust the system; increase system pressure to at least static primary pressure plus 0,5 bar; if necessary continue to increase, switch the pump for a short time off and on. Is the temperature difference at the controller too small? Wrong placing of the collector sensor? Change Ton and Toff accordingly. o.k. Clean the dirt trap Plausibility control of the option tube collector special function? Mount the collector sensor at solar feed flow (warmest collector output); use the immersion sleeve of the respective collector. Pump starts up very late and soon stops working soon. The temperature difference between store and collector increases ermously during operation; the collector circuit cant dissipate the heat. Switch-on-temperature difference Ton too large? Collector circuit pump defect? Change Ton and Toff accordingly. Control / replace Collector sensor un favourable placed (e.g. contact sensor instead of immersion sleeve sensor? Heat exchanger calcified? Decalification If necessary activate tube collector function. Heat exchanger plugged? o.k. Cleaning Heat exchanger too small? Replace with correctly sized one. 22
23 Stores are cooled during the night. a Control the return flow preventer in warm water circulation- o.k. b Please also check further pumps which are connected to the solar store. Does collector circuit pump run during the night? Collector temperature is at night higher than ambient temperature. Is store insulation sufficient? Check the controller functions Check the return flow preventer in feed flow and return flow with regard to the functional efficiency. The gravitation circu lation in the circulation line is too strong; insert a stronger return flow pre venter or an electrical 2-way valve behind the circulation pump; the 2-way valve is open in pump operation, other wise it is closed, conect pump and 2-way Cleaning or replacement. valve in parallel; activate the circulation again! Intensify the insulation. The solar circuit pump does t work although the collector is obviously warmer than the store. Is store insulation close eugh to the store? Are the store connections insulated? Replace or intensify the insulation. Does the pump start up in manual operation? The adjusted tempe rature difference for starting the pump is too high; choose an matching setting Insulate connections. Warm water outflow upwards? Change connection and let the water flow sidewards or through a siphon (bow downwards); less store losses w? Is the current of the pump released by the controller? Is the pump stuck? Turn the pump shaft using a screwdriver; is it passable w? Does warm water circulation run for a very long time? o.k. Use the circulation pump with timer and switch-off thermostat (energy efficient circulation) Are the fuses of the controller o.k.? Is the pump defective - replace it. Switch-off the circulation pump and the blocking valve for 1 night; less store losses? a Check the pumps of the after-heating circuit according to nightly run and defect return flow preventer; problem solved? b Replace the fuses. Controller might be defective - replace it. 23
24 6. Accessories Sensors Our product range includes high-precision platinum temperature sensors, flatscrew sensors, outdoor temperature sensors, indoor temperature sensors, cylindrical clip-on sensors, also as complete sensors with immersion sleeve. For more information, see our catalogue and price list. Overvoltage protection device In order to avoid overvoltage damage at collector sensors (e.g. caused by local lightning storms), we recommend the overvoltage protection RESOL SP10. VBus / USB interface adapter The new VBus / USB interface adapter is the interface between the controller and a personal computer. With its standard mini-usb port it enables a fast transmission of system data via the VBus for processing, visualizing and archiving. A full version of the RESOL ServiceCenter software is included. Distributed by: RESOL - Elektronische Regelungen GmbH Heiskampstraße Hattingen / Germany Tel.: +49 (0) / Fax: +49 (0) / [email protected] Important tice: We took a lot of care with the texts and drawings of this manual and to the best of our kwledge and consent. As faults can never be excluded, please te: Your own calculations and plans, under consideration of the current standards and DIN-directions should only be basis for your projects. We don t offer a guarantee for the completeness of the drawings and texts of this manual - they only represent some examples. They can only be used at your own risk. No liability is assumed for incorrect, incomplete or false information and / or the resulting damages. Please te: The design and the specifications are to be changed without tice. The illustrations may differ from the original product. Reprinting / copying This mounting- and operation manual including all parts is copyrighted. Ather use outside the copyright requires the approval of RESOL - Elektronische Regelungen GmbH. This especially applies for copies, translations, micro films and the storage into electronic systems. Editor: RESOL - Elektronische Regelungen GmbH 24
RESOL DeltaSol A. Mounting Connection Operation Examples. Manual
RESOL DeltaSol A Mounting Connection Operation Examples www.resol.dedeltasol A Manual Thanks for buying a RESOL controller. Read this manual carefully to get the best performance from this unit. Contents
DeltaSol BS Plus *48005931* Solar controller Manual for the specialised craftsman. Installation Operation Functions and options Troubleshooting
DeltaSol BS Plus (Version 2) Solar controller Manual for the specialised craftsman Installation Operation Functions and options Troubleshooting The ctuvus certification confirms that the controller is
Contents. Operation manual of solar water controller SR868C8/SR868C8Q
Contents Contents----------------------------------------------------------------------------------------------------1 1. Safety information ----------------------------------------------------------------------------------3
1. Safety information
---- Contents 1. Safety information... 4 1.1 Installation and commissioning... 4 1.2 About this manual... 4 1.3 Liability waiver... 4 1.4 Important remark... 5 1.5 Description of symbols... 5 1.6 Description
1 General information
1 General information 1.1 About this manual This manual describes the installation, function and operation of an integrated solar control system, which is suitable for split pressurized solar heating system.
8 716 473 216-00.3O. Gas boiler. Gaz 6000 W WBN 6000-30-H-E-N/L-S2400. Operating instructions for the end customer. 8 716 473 217 (2014/07) en
8 716 473 216-00.3O Gas boiler WBN 6000-30-H-E-N/L-S2400 Operating instructions for the end customer en 2 Contents Contents 1 Key to symbols and safety instructions................... 2 1.1 Key to symbols..................................
Drayton Digistat +2RF/+3RF
/+3RF Programmable Room Thermostat Wireless Model: RF700/22090 Model: RF701/22092 Power Supply: Battery - Thermostat Mains - Digistat SCR Invensys Controls Europe Customer Service Tel: 0845 130 5522 Customer
MOUNTING AND OPERATING INSTRUCTIONS
MOUNTING AND OPERATING INSTRUCTIONS CF 51/55 1. Delivery CF 51/55-1 calculator with battery (optionally with mains power supply) - 1 wall mounting bracket - package with material for sealing, screws, wall
ecomax Instructions for use Wall hung room sealed fan assisted condensing boilers For the user
For the user Instructions for use ecomax Wall hung room sealed fan assisted condensing boilers ecomax 63/ E ecomax 68/ E ecomax 6/ E ecomax 635 E ecomax 84/ E ecomax 88/ E ecomax 835 E GB Table of contents
DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS. Construction Automotive Industry
DUAL SENSING DIGITAL THERMOSTAT PRODUCT INSTRUCTIONS www.rehau.com Construction Automotive Industry SCOPE This guide gives instruction regarding REHAU Programmable Digital Thermostat installation and operation.
Manual of Solar Pump Station SR882 for Split Pressurized Solar Hot water System 2011.07.07
Manual of Solar Pump Station SR882 for Split Pressurized Solar Hot water System 2011.07.07 Contents Solar pump station installation and operation manual Contents... 1 Solar pump station installation and
Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains
Drayton Programmable Room Thermostat 7 Day (5-2 Day) Models: 22083 / 22087 Power Supply: Battery / Mains Invensys Controls Europe Technical Helpline: +44 (0) 845 130 7722 www.draytoncontrols.co.uk Installation
Data logger. Installation and operating instructions. Read carefully before installation, commissioning and operation.
Data logger Installation and operating instructions SOREL Connect Read carefully before installation, commissioning and operation 1.1. - Specifications Description of data logger Electrical specifications:
Technical Information
Technical Information Interface with DDC 6 720 642 841-00.1RS Logamatic LON-Gateway For heating contractors during project planning 6 720 643 554 (11/2010) US/CA Contents Contents 1 Explanation of symbols
Operating manual For split pressurized solar hot water system controller
Operating manual For split pressurized solar hot water system controller Model SR1188 2011.03.26 Contents Contents... 1 1. Safety information... 4 1.1 Installation and commissioning... 4 1.2 About this
RESOL DELTA Sol. universal temperature differential. regulator for solar- and heating systems Mounting instructions. page 1/11
page 1/11 universal temperature differential regulator for applicati in solar- and heating systems plastic housing with easy mounting and compact dimensis digital display temperature user-friendly handling
Installation instructions. For the competent person. Installation instructions. VRT 350f. VRT 350f GB, IE
Installation instructions For the competent person Installation instructions VRT 350f VRT 350f GB, IE Legal information Document type: Product: Target group: Language: Installation instructions VRT 350f
eltasol RESOL DeltaSol M Manual Installation Operation Commissioning Fault localisation for the professional
RESOL DeltaSol M Manual for the professional Installation Operation Commissioning Fault localisation Thanks for buying a RESOL. Read this manual carefully to get the best perfomance from this unit. DeltaS
B/S/H/ Error codes and service programmes PH
1 ERROR CODES AND APPLIANCE MESSAGES... 3 1.1 Complete overview of all error codes (in order)... 3 Automatic switch-off... 3 Display is dark and any individual LEDs are lit... 3 E 005... 3 E 011... 3 E
RDJ10RF/SET. Wireless room temperature controller with 24-hour time switch and LCD. Programmable, for heating systems
3 072 RDJ10RF RCR10/433 Wireless room temperature controller with 24-hour time switch and LCD Programmable, for heating systems RDJ10RF/SET Operating modes: Automatic, Comfort, Energy Saving, and Frost
Service manual. Website: www.andico.com.au CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL.
Website: www.andico.com.au Service manual CAUTION - BEFORE SERVICING THE UNIT, READ THE SAFETY - PRECAUTIONS IN THIS MANUAL. - ONLY FOR AUTHORISED SERVICE PERSONNEL. MODELS: MPK1-09CR-QB8 MPK1-12ER-QB6
Remote control station WCM-FS 2.0 and solar controller WCM-SOL 1.0 home 83277602 3/2012-10
Remote control station WCM-FS 2.0 and solar controller WCM-SOL 1.0 home 83277602 3/2012-10 1 User instructions... 6 1.1 User guide... 6 1.1.1 Symbols... 6 1.1.2 Target group... 6 1.2 Guarantee and Liability...
Alpha Climatic Programmable Modulating Boiler Energy Manager. Installation and User Instructions
Alpha Climatic Programmable Modulating Boiler Energy Manager Part No 3.022144 (Hard Wired) Part No 3.022143 (Radio Frequency) Installation and User Instructions 1. Description The Alpha Climatic energy
Installation and Service Instructions for use by heating contractor SM1 SOLAR CONTROL MODULE IMPORTANT
Installation and Service Instructions for use by heating contractor Solar Control Module for solar connections to the Vitotronic control SM1 SOLAR CONTROL MODULE Product may not be exactly as shown IMPORTANT
How To Use A Power Supply On A Powerline 2.2 (Ai)
KNX/EIB Product documentation Issue: 05.08.2010 629x1220 Push button sensor 3 comfort 1-gang Push button sensor 3 comfort 2-gang (1+1) Push button sensor 3 comfort 3-gang Push button sensor 3 comfort 4-gang
For installation guide see reverse of book
USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance
USERS GUIDE. LOGIC Combi 24, 30, 35. For installation guide see reverse of book
USERS GUIDE LOGIC Combi 24, 30, 35 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance
Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS
Art.S001-S002 SOLAR MODULE WITH DELIVERY AND RETURN CONNECTIONS Technical Information sheet 0001/07/Rev01 ENG FUNCTION Series S001 and S002 circulation units are applied to the primary circuit of solar
Installation and maintenance instructions. Danfoss Vent
Installation and maintenance instructions Danfoss Vent 1 Unit design... 2 2 Project planning and installation instructions... 3 2.1 Ventilation...3 2.2 Piping installation....3 2.3 Condensation line...4
OZW30. Central Unit SYNERGYR
2 841 SYNERGYR Central Unit OZW30 Collects billing data from the apartments. Generates an image of each apartment's heat consumption and makes it available for readout. Acts on room temperature control
AN500T, AN1000, AN1000T, AN1500, AN1500T AN2000, AN2000T
Product Instruction Manual Accona AN500T, AN1000, AN1000T, AN1500, AN1500T AN2000, AN2000T Panel heater v16.5/5 Version 3.2 Jan 2015 Contents 1. Important safety points 2. Installation 2.1. Wall mounting
RVR Hybrid System Installer Instructions - 10052012. RVR Hybrid System Controller Installation Instructions
RVR Hybrid System Controller Installation Instructions 1 Introduction to Hybrid Systems The RVR Hybrid system uses a combination of the Immergas Audax range of heat pumps with gas or oil boilers to create
DALI RC BASIC SO. Control unit Operating instructions
DALI RC BASIC SO Control unit Operating instructions Contents Safety... 4 General instructions 4 Safety instructions 4 Description... 5 Purpose and application 5 Function 5 Light control 5 Brightness
Regulators. Heat pumps. Qualified technician NIBE TM AP-CS2.0. Operating Instructions UK
Operating Instructions UK Heat pumps Regulators Qualified technician NIBE TM AP-CS2.0 We reserve the right to make technical changes. 83052306bUK Translation of the operating manual Please read first This
ELECTRIC CENTRAL HEATING FLOW BOILER
ELECTRIC CENTRAL HEATING FLOW BOILER EKCO.T Used product can t be treated as general communal waste. Disassembled appliance has to be delivered to the collection point of electrical and electronic equipment
Installation and operating instructions. Solar charge controller Solarix MPPT 2010 730927 Z03 1242 730927 Z03 1242
Installation and operating instructions Solar charge controller Solarix MPPT 2010 EN 730927 Z03 1242 730927 Z03 1242 1 Contents 1. About these instructions...3 1.1 Applicability...3 1.2 Users...3 1.3.
RVL470. Heating Controller. Building Technologies HVAC Products. Series B
2 522 Heating Controller Series B RVL470 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones
User manual. 086U6297 Rev. 9 EN
User manual Atria Atria Duo Atria Duo Optimum Atria Optimum Comfort Diplomat Diplomat Duo Diplomat Duo Optimum Diplomat Duo Optimum G2 Diplomat Optimum Diplomat Optimum G2 086U6297 Rev. 9 EN Thermia Värme
SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS
SHOWER WATER HEATER MODEL BS 35 / 45 / 60 BS 35 E / 45 E / 60 E OPERATION AND INSTALLATION INSTRUCTIONS 2 This water heater must be installed (water and electrical installation), commissioned and serviced
KNX R. Rain Sensor. Installation and Adjustment
EN KNX R Rain Sensor Installation and Adjustment 1 Content 1. Description... 3 1.1. Technical specifications... 3 2. Installation and commissioning... 4 2.1. Installation notes... 4 2.2. Location... 4
Max primary circuit temperature 90ºC Max primary circuit temp. 90ºC Max secondary circuit temperature 45ºC Max secondary circuit temp.
EGLISH 1 Product description exchanger equipped with an electronic control unit and circulation pump for the primary circuit. All Aqua-Mex variants can be ordered with an interior coil of either titanium
Operating Manual for the Electronic Built-in Interval Timer. Micro II (Countdown Timer)
Operating Manual for the Electronic Built-in Interval Timer Micro II (Countdown Timer) Note: This document has been designed for our OEM customers. They can use it as supporting material when creating
HERZ-Thermal Actuators
HERZ-Thermal Actuators Data Sheet 7708-7990, Issue 1011 Dimensions in mm 1 7710 00 1 7710 01 1 7711 18 1 7710 80 1 7710 81 1 7711 80 1 7711 81 1 7990 00 1 7980 00 1 7708 11 1 7708 10 1 7708 23 1 7709 01
Infrarot-Bewegungsmelder IP44
Infrarot-Bewegungsmelder IP44 infrared motion sensors IP44 ODA (weiß) slim ODA (schwarz) slim 95174 96000 ODA (weiß) ODA (schwarz) 95175 96001 Betriebsanleitung User s Manual User s Manual infrared motion
Operating ambient temperature range: 5ºC to 50ºC Storage temperature range: -30ºC to 70ºC
HOJA TÉCNICA 1400H101 Edición 01 (02 de 08) www.ako.es GENERAL TECHNICAL SPECIFICATIONS Temperature range: -50ºC to +99ºC type: NTC Total accuracy ( + controller): ±1ºC lead extension with cable AKO-15586:
SEZ220. Signal Converter. Synco 200. With preprogrammed standard applications Freely programmable Menu-driven operation. Use
s 5 146 Synco 200 Signal Converter SEZ220 With preprogrammed standard applications Freely programmable enu-driven operation Use The signal converter is for use in HVAC plant to provide minimum / maximum
KNX TH65-AP. Thermo-Hygrometer. Technical specifications and installation instructions Item number 70184
EN KNX TH65-AP Thermo-Hygrometer Technical specifications and installation instructions Item number 70184 Elsner Elektronik GmbH Control and Automation Engineering Herdweg 7 D 75391 Gechingen Phone +49
Heating Controller. Building Technologies HVAC Products
2 474 Heating Controller RVP300 Multifunctional heating controller for use in residential and non-residential buildings; suitable for weather-dependent flow temperature control of heating zones with or
ECL Comfort 110 Application 130. Weather compensated flow temperature control of heating and boiler systems. Instructions
Instructions *087R9781* *VIKTG202* Danfoss can accept no responsibility for possible errors in catalogues, brochures and other printed material. Danfoss reserves the right to alter its products without
Operating instructions. RCD flat 4-fold, 6-fold
Operating instructions 1. Safety instructions Electrical equipment must be installed and fitted by qualified electricians only. Observe the current accident prevention regulations. Failure to observe the
its ELECTRIC POSITION for electric heat, or set the units fan control appropriately to ELECTRIC or another appropriate setting.
Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please
ACCESSORIES VISUALISATION
CONTROLLERS PUMP STATIONS ACCESSORIES VISUALISATION MADE IN GERMANY CONTROL TECHNOLOGY Discover our product portfolio all around heating and solar thermal control technology www.resol.com SOLAR CONTROLLERS
User Manual. Interface Adapter IA1 / Computer Interface EFOY 600 / EFOY 900 / EFOY 1200 / EFOY 1600
User Manual Interface Adapter IA1 / Computer Interface EFOY 600 / EFOY 900 / EFOY 1200 / EFOY 1600 2 1. Introduction 1. Introduction 1.1 Introduction Thank you for choosing an EFOY product. Please read
User manual. Solid (FR 98,),
User manual Solid (FR 98,), If these instructions are not followed during installation and service, Thermia Värme ABliability according to the applicable warranty is not binding. Thermia Värme AB retains
USERS GUIDE. LOGIC Heat 12, 15, 18, 24, 30. For installation guide see reverse of book
USERS GUIDE LOGIC Heat 12, 15, 18, 24, 30 For installation guide see reverse of book When replacing any part on this appliance, use only spare parts that you can be assured conform to the safety and performance
T0118 T2118 T3118. Instruction Manual
Programmable indoor transmitter of temperature T0118 Programmable indoor transmitter of atmospheric pressure T2118 Programmable indoor transmitter of temperature, relative humidity and other derived humidity
User Manual. Gas fired condensing wall hung boiler. G.C.N : 41-116 - 30 (12 kw) G.C.N : 41-116 - 31 (18 kw) G.C.N : 41-116 - 32 (24 kw)
User Manual Gas fired condensing wall hung boiler G.C.N : 41-116 - 30 (12 kw) G.C.N : 41-116 - 31 (18 kw) G.C.N : 41-116 - 32 (24 kw) CLAS HE R 12 CLAS HE R 18 CLAS HE R 24 Country of destination GB, IE
Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II
Installation and Commissioning Manual Solar Stations FlowCon Max Evolution II 1 For your safety Table of Contents 1 For your safety... 3 1.1 About this manual... 3 1.2 Designated use... 3 1.3 Qualification
EasyStart R + Operating instructions. Comfort radio remote control with integrated timer for parking heaters and more.
EasyStart R + Operating instructions. Comfort radio remote control with integrated timer for parking heaters and more. 22 1000 32 80 06 03.2009 Contents Introduction Please read first... 3 Purpose... 3
SunMaxx Solar Filling Station Operating Instructions
SunMaxx Solar Filling Operating Instructions Content 1. Declaration of conformity... 2 2. Introduction... 2 3. Transportation and unpacking... 4 4. Mounting and commissioning... 5 5. End of operation...
Split Controller. User Manual SM-SS-F 2009/01/04
Split Controller SM-SS-F User Manual 2009/01/04 Table of contents 1. Parts illustration.... 1 2. Electrical technical data...... 2 3. Electrical connection...3 4. Assemble parts...4 4.1 Assemble the fixed
Wireless 7 Day Programmable Room Thermostat
Wireless 7 Day Programmable Room Thermostat Cat. No. TRT037 Transmitter Receiver Operating & Installation Instructions What is a programmable room thermostat? an explanation for householders A programmable
Rain+Birdt. Simple To Set Timer (SST) Setup & Operation Instructions. English. 1-800- RAIN BIRD (800-724-6247) or visit www.rainbird.
Rain+Birdt Simple To Set r (SST) Setup & Operation Instructions English Installation...2 Tools and Supplies Needed...2 Step 1. Mount r...2 Step 2. Connect Power...2 Indoor r...2 Outdoor r...2 Step 3. Connect
Maxi Pressurisation Units (Maxi, Maxi Plus & HP)
Maxi Pressurisation Units (Maxi, Maxi Plus & HP) Installation and Maintenance Instructions Contents 1 Dimensions 3 1.1 Installation 4 1.1 Mains/boosted cold water inlet 4 1.2 Connection to the system 5
VIESMANN. Installation and service instructions VITOTROL 100. for contractors
Installation and service instructions for contractors VIESMANN Vitotrol 100 Type UTDB-RF2 Room temperature controller with digital time switch and wireless receiver For applicability, see the last page
GL-235 Solar Pool Controller
GL-235 Solar Pool Controller Installation & Operation Manual G LDLINE CON TROLS www.goldlinecontrols.com Description The GL-235 is a differential temperature control for solar heating of pools, spas, and
FL ballasts Electronic dimming. PCA T5 BASIC lp Y II, 14 80 W BASIC T5
T5 TC-L PCA T5 BASIC lp Y II, 1 80 W BASIC T5 Product description Processor-controlled ballast with y II inside Highest possible energy class CELMA EEI = A1 BAT 1 Noise-free precise control via DSI signal,
Inwall Room Temperature Unit
Inwall Room Temperature Unit TM11B01KNX TM11B11KNX TM11B21KNX Product Handbook Product: Inwall Room Temperature Unit Order Code: TM11B01KNX TM11B11KNX TM11B21KNX Application Program ETS: TM11B_1KNX Inwall
Ambient Temperature Sensor TEMPSENSOR-AMBIENT
Ambient Temperature Sensor TEMPSENSOR-AMBIENT Installation Guide TempsensorAmb-IEN110610 98-0042210 Version 1.0 EN SMA Solar Technology AG Table of Contents Table of Contents 1 Notes on this Guide...............................
TYXIA. *2702178_Rev.1* Installation and User Guide. Wireless receiver. TYXIA RF 642-1 channel
Installation and User Guide TYXIA Wireless receiver TYXIA RF 642-1 channel DELTA DORE Bonnemain - 35270 COMBOURG - France E-mail : [email protected] Unit compliant with the requirements of directives:
Current valve. for AC 24 V pulse/pause control of electrical loads up to 30 kw
4 937 DESIO Current valve for AC 24 V pulse/pause control of electrical loads up to 30 kw SEA45.1 Use The current valve is used for the control of electric heating elements in heating, ventilation and
ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS
ENGLISH INSTRUCTION & INSTALLATION MANUAL DUCTLESS MINI SPLIT AIR CONDITIONING SYSTEMS Céliera Corporation. All rights reserved. Unauthorized duplication, reproduction prohibited. CONTENTS SAFETY PRECAUTIONS...
FLEXIT S4 R S6 R S7 R
94111E-05 2005-10 FLEXIT S4 R S6 R S7 R User Manual Air Handling Unit Cabinet Models with Heat Recovery - Rotor Contents 1 Important Safety Instructions... 3 2 Method of Operation - System... 3 2.1 Heating
AIR CONDITIONER INSTALLATION MANUAL
INSTALLATION MANUAL AIR CONDITIONER Please read this installation manual completely before installing the product. Installation work must be performed in accordance with the national wiring standards by
Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify
Comfort Control Center 2 Thermostat Operating Instructions Programmable Thermostat MODEL 3312026.XXX With Dehumidify 3312024.XXX With Out Dehumidify TABLE OF CONTENTS About your new thermostat Features...2
MIC-WKT and MIC-WKT-IR
MIC-WKT and MIC-WKT-IR Installation Manual Bosch Security Systems EN Installation and Operation Manual MIC-WKTI and MIC-WKT-IR Installation Manual EN 2 MIC-WKT and MIC-WKT-IR Washer Pump Drive Card Kits
ELECTRONIC THERMOSTAT AND THERMOMETER With SPEED CONTROL
148 OLD CONCORD TURNPIKE, BARRINGTON NH 03825 USA TEL (603) 868-5720 FAX (603) 868-1040 1-800-435-6708 E-Mail:[email protected] www.seafrost.com ELECTRONIC THERMOSTAT AND THERMOMETER With SPEED CONTROL
User Manual THR840DUK Digital Thermostat
User Manual THR840DUK Digital Thermostat 50051982-001 Rev. A WARNING: This product must be correctly installed and configured to work properly (see pages 12-24). If you are not experienced in wiring electrical
MAKING MODERN LIVING POSSIBLE. living connect. Installation and User Guide. Danfoss Heating Solutions
MAKING MODERN LIVING POSSIBLE living connect Installation and User Guide Danfoss Heating Solutions 2 living connect Thank you for buying a Danfoss product Danfoss Heating Solutions 3 Contents 1. System
LS1024B / LS2024B/ LS3024B. Solar Charge Controller USER MANUAL
EPSOLAR LS1024B / LS2024B/ LS3024B Solar Charge Controller USER MANUAL Thank you very much for selecting our product! This manual offers important information and suggestions with respect to installation,
SET1E. Installation & User Instructions. Electronic timeswitch for heating & hot water. Certification Mark
SET1E Electronic timeswitch for heating & hot water Installation & User Instructions Certification Mark Index INDEX Installation Product specification 3 Installation 4-5 Wiring 5-10 Replacement 11-13 User
DeltaSol E. RESOL DeltaSol E. Mounting Connection Handling Fault localization. manual
RESOL DeltaSol E Mounting Connection Handling Fault localization DeltaSol E B manual Thank you for buying this RESOL product. Read this manual carefully to get the best perfomance from this unit. www.resol.de
Antenna Splitter ASA 1. Instruction manual
Antenna Splitter ASA 1 Instruction manual Contents Important safety instructions... 2 The ASA 1 active antenna splitter... 4 Delivery includes... 4 Operating elements... 5 Putting the ASA 1 into operation...
Installation Guide. VisionPRO. TH8000 Series. Need Help? This manual covers the following models. System Types
Installation Guide VisionPRO TH8000 Series Touch-screen Programmable Thermostat This manual covers the following models TH8110U: For 1 Heat/1 Cool systems TH8320U: For up to 3 Heat/2 Cool systems TH8321U:
StorTrends 3400 Hardware Guide for Onsite Support
StorTrends 3400 Hardware Guide for Onsite Support MAN-3400-SS 11/21/2012 Copyright 1985-2012 American Megatrends, Inc. All rights reserved. American Megatrends, Inc. 5555 Oakbrook Parkway, Building 200
REMOTE TERMOMETER TE 219 LED USER MANUAL
INTRODUCTION REMOTE TERMOMETER TE 219 LED USER MANUAL Thank you for purchasing this unit with indoor thermometer, wireless thermometer sensor and radiocontrolled clock. This device is also equipped with
HVAC-32A. Operation Manual. Specifications. Digital Multistage Air Conditioning Controller with inbuilt Outside Air Economy function
Specifications Supply Voltage 240VAC @ 0.07Amps or 24VAC @ 0.380Amps Relays 240V @ 12A max (resistive) / Comp1,2,3, Aux Ht, Rv O/B) Fuses (Equipment) 15 Amps Maximum 3AG Control Range Minus 10 to 50C Control
RF 1. Contents: Connecting diagram. Detailed information:
Contents: Introduction UFH-ZONE-R UFH-EXTRAZONE -R Connection of a thermostat (UFH-THERM-R) o Joining of a thermostat with UFH-ZONE-R or UFH-EXTRAZONE-R Connection of a digital thermostat (UFH-THERM -RD)
Electronic Pressure Switch EDS 300
Electronic Pressure Switch EDS 300 User manual Page 2 of 16 Content 1. Functions of the EDS 300...3 2. Mounting...3 3. Operating keys on the membrane keypad...4 4. Digital display...4 5. Output function...5
REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16
REB 1 REB 3 REB 5 REB 6 REB 8 REB 10 REB 12 REB 16 Manually Operated Electronic Speed Controller Single Phase For all applications using suitably specified single-phase induction motor fans 1 GENERAL The
NÜVE SANAYİ MALZEMELERİ İMALAT VE TİCARET A.Ş. OT 020 BENCH TOP STEAM STERILIZER USER S MANUAL
NÜVE SANAYİ MALZEMELERİ İMALAT VE TİCARET A.Ş. OT 020 BENCH TOP STEAM STERILIZER USER S MANUAL NÜVE SANAYİ MALZEMELERİ İMALAT VE TİCARET A.Ş. Esenboğa Yolu 22 km Akyurt - ANKARA / TURKEY Tel : (00 90 312)
MAKING MODERN LIVING POSSIBLE. living connect. Installation and User Guide. Danfoss heating
MAKING MORN LIVING POSSIBLE Danfoss heating living connect Installation and User Guide Contents 1.0 System overview... 3 2.0 Overview of display and control buttons... 3 3.0 Installation - step by step...
ELECTRIC POSITION for electric heat, then confirm with Fan Test below.
Troubleshooting Poor Temperature Regulation This page lists problems that may affect the temperature performance of your LUX thermostat with suggested resolutions. For more detailed information please
Time Recorder. User Manual. PDF created with FinePrint pdffactory trial version www.pdffactory.com
Time Recorder User Manual 1 (1) Specifications: 1. Power supply 100, 110, 200, 220, 230 V AC (as designated), 50/60 Hz, single phase. 2. Power consumption Normal 2W (MAX 30W) 3. Standard time signal Quartz
T7560A,B,C Digital Wall Module
T7560A,B,C Digital Wall Module HONEYWELL EXCEL 5000 OPEN SYSTEM BEFORE INSTALLATION All wiring must comply with local electrical codes and ordinances or as specified on installation wiring diagrams. Digital
Table of Contents. 1 - Specifications...3. 2 - Installation...3. 3 - Wiring...5. 4 - User controls...7
THERMOSTATS Table of Contents Page 1 - Specifications...3 1.1 - Product range...3 ARTTH001 (DSL-610)...3 ARTTH002 (DSL-700)...3 ARTTH003 (DSL-600)...3 1.2 - Technical data...3 1.3 - Power failures...3
ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
Installation Guide. LR-HWLV-HVAC TouchPRO Wireless. System Types
Installation Guide LR-HWLV-HVAC TouchPRO Wireless Touchscreen Thermostat System Types Gas, oil, or electric heat with air conditioning Warm air, hot water, high efficiency furnaces, heat pumps, steam,
GeyserWise TSE. thermostat instruction manual. SANS 181 compliant
GeyserWise TSE thermostat instruction manual SANS 181 compliant Before operating and installation, carefully read all instructions. Do not discard this manual. Index Warranty Components About the GeyserWise
Product and Application Description
Technical Product - Information Product and Application Description The room temperature controller UP 237K and UP 252K are available in the following colors, matching the design of the wall switch design