KNIGHT WALL SYSTEMS GUIDE DETAILS:

Similar documents
DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS REPORT HOLDER: FIRESTONE BUILDING PRODUCTS COMPANY, LLC

Ver. 2. Guide to. Inspecting Residential Brick Veneer

Clad Direct Glaze Window Installation Instructions

Fig. 2 WALL-TO-WALL PANEL CONNECTIONS CORNER WALL CONNECTION

INSTALLATION OF A BAY WINDOW

Window Installation Instructions

CONSTRUCTION DETAILS & LOAD DESIGN CHARTS

GreenGuard Housewrap Installation Guide

Sun Windows General Information Sun New Construction Window Installation Instructions

Meeting the Fire Code with Continuous Foam Plastic Insulation

PART 1 GENERAL 1.1 SECTION INCLUDES

Envelope INSULATION BATT (2) Avoid Using Batt Insulation With Metal Framing. Pressure or Friction Fit

INSTALLATION INSTRUCTIONS for Vinyl Windows with Integral Nailing Fin (JII001)

300mm. 2mm MIN GAP. PLACE 100mm X 100mm. SO THAT IT IS 38mm INTO

Table of Contents. Western States RustWall Wall and Soffit Panels Installation, Flashings & Shop Drawing Detail Guide

SECTION STANDING SEAM METAL ROOF

March 14, Installation of Bay, Bow and Garden Windows

WINDOW INSTALLATION GUIDE

Residential Roofing Guide

TEST REPORT. Report No.: A Rendered to: BAMCO INC. Middlesex, New Jersey. PRODUCT TYPE: Wall Cladding System SERIES/MODEL: Dry Concept

WINDOW INSTALLATION GUIDE FOR NEW CONSTRUCTION - WOOD FRAMING

Storage Store the siding in a dry and ventilated area. Do not place it directly on the ground. Always cover the siding after a day s work.

Introduction...COMB-2 Design Considerations and Examples...COMB-3

Superform Products Ltd.

Replacement Window Installation Guide Non-Impact & Impact Resistant Windows without Nailing Fin

THE DOW CHEMICAL COMPANY Issued: August 1, LARKIN CENTER 1605 JOSEPH DRIVE MIDLAND MICHIGAN (989)

application instructions

INSTALLATION INSTRUCTIONS for Vinyl Windows with Integral Nailing Fin (JII001) IMPORTANT INFORMATION AND GLOSSARY ROUGH OPENINGS

Uncovered Decks & Porches

The better way to build TM. Installation Manual. EXTERIOR WALL SIPs

Installation Instructions Double-Hung, Single-Hung, Casement, Awning, Sliding, Picture & Shapes Non-Impact & Impact Resistant Nailing Fin Windows

The WANZ Guide to Window Installation

Basement Window Installation Guide Hopper and Sliding

Tundra Series Windows January 2016

Avoiding Air Barrier Pitfalls

PANELIZED HOME INSTALLATION GUIDELINE

DESIGN AND CONSTRUCTION GUIDELINES AND STANDARDS DIVISION 8 DOORS AND WINDOWS WINDOWS

Standard from CSI Part Section Format For Wood Framing For Metal Framing For Gypsum Sheathing

WINDOW PANNING AND TRIMS

PERFORMANCE TEST REPORT. Rendered to: ARCHITECTURAL METAL SOLUTIONS, INC.

The better way to build TM. Installation Manual. FOUNDATION SIPs & FROST WALLS SIPs

NCMA TEK CONCRETE MASONRY FOUNDATION WALL DETAILS. TEK 5-3A Details (2003)

This handout is a guide only and does not contain all of the requirements of the Minnesota State Building Code or city ordinances.

Barewood Octagon and Elongated Windows Installation Instructions

STANDARD PROCEDURES FOR INSTALLATION OF METAL ROOF SYSTEMS

Fire Barrier Duct Wrap 15A

MIAMI-DADE COUNTY PRODUCT CONTROL SECTION DEPARTMENT OF REGULATORY AND ECONOMIC RESOURCES (RER)

GYPSUM AREA SEPARATION FIREWALLS GA

Specifications. Preformed Metal Wall and Roof Panels. Alcoa Cladding Systems Manufacturing Plant 100 Industrial Boulevard Eastman, Georgia 31023

VA25014B0516 VA CINCINNATI PROJECT NO INPATIENT BED TOWER ADDITION (4 TH AND 5 TH FLOORS) SECTION GYPSUM BOARD

DE Frame with C Series Sidelight

RESIDENTIAL MASONRY A BEST PRACTICES GUIDE

Discipline: Structural Issued

SG Series 65mm Frame Windows (Fixed Lite Window Illustrated)

GYPSUM BOARD, GYPSUM PANEL PRODUCTS AND PLASTER

2.18 INTERIOR & EXTERIOR FINISHES VAPOR & AIR BARRIERS

LEGACY REPORT. (800) (562) A Subsidiary of the International Code Council RETAINED ON U.S.

Residential Decks. Planning and Development Services Department

Preformed Metal Roofing and Siding

TABLE OF CONTENTS. Roof Decks 172 B, BA, BV Deck N, NA Deck. Form Decks FD,.6 FDV Deck 1.0 FD, 1.0 FDV Deck 1.5 FD Deck 2.0 FD Deck 3.

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

SECTION 6. Glass Storefront Doors:

Chapter 3 Pre-Installation, Foundations and Piers

first look at GigaCrete s revolutionary new New Construction GigaHouse GigaHouse Utilizing GigaPanel

CHAPTER 7: Building Systems ROOFING SYSTEMS

Metal Roofing Practical Design

GUIDELINE SPECIFICATIONS

CertainTeed. Shaftliner For A rea Separation Firewalls

BRIDGE & SUPPLY COMPANY. Installation Guide. Ultra Includes:

How To Repair A Boat Landing Deck With A Boat Bed

H-Stud Area Separation Wall System

AC-3200 ALUMINUM PLATE SYSTEM (DRY JOINT)

Free 12 x 8 Shed Plan With Illustrations, Blueprints & Step By Step Details

Nucor VR16 II TM Vertical Rib Standing Seam Roof System

MOCK-UP TEST REPORT. Rendered to: TUBELITE, INC. PROJECT: 200 Series Curtain Wall Mock-Up

MUNICODE SERVICES LTD.

ASTM E 1886 and ASTM E 1996 TEST REPORT. Rendered to: NORSE, INC.

Is Your Envelope Effective? Mark Lawton P.Eng Morrison Hershfield Limited Vancouver

HURRICANE MITIGATION RETROFITS FOR EXISTING SITE-BUILT SINGLE FAMILY RESIDENTIAL STRUCTURES

Installation Instructions For Slider Casement Air Conditioners

INSTALLATION INSTRUCTIONS for Vinyl Patio Doors with Integral Nailing Fin (JII006)

CF-Mesa, CF-Light Mesa, CF-Flute, CF-Metl-Plank, CF-Striated, CF-Santa Fe, CF-Architectural Flat, CF...

THIRD PARTY INSPECTION GUIDELINES FOR OWNERS AND GENERAL CONTRACTORS/CONSTRUCTION MANAGERS DS150

DuPont Tyvek Commercial Air Barrier Assemblies Exceed Air Barrier Association of America, ASHRAE 90.1

Metal Building Systems Installation and Flashings & Details Guide. Table of Contents

UL 580 TEST REPORT. Rendered to: ARMSTRONG WORLD INDUSTRIES. SERIES/MODEL: MW Vector PRODUCT TYPE: Ceiling System, 3' OC

Featuring TJ Rim Board and TimberStrand LSL

We urge you to read and follow the attached installation instructions. Failure to do so may void the warranty of this garden window unit.

For GREAT STUFF Pro Window & Door Insulating Foam Sealant

INSTALLATION INSTRUCTIONS IMPERVIA (Vent and Fixed) AWNING, CASEMENT, and LARGE AWNING WINDOW WITH FINS

REPORT NUMBER: COQ-003 ORIGINAL ISSUE DATE: July 19, 2013

!!!!!! !!! Decra Plus DPSW010 DPSTW011 DPSW012 DPSW013 DPSW014 DPSW015 DPSW016 DPSW020 DPSW021 DPSW024 DPSW030 DPSW031 DPSW035 DPSW030 DPSW031 DPSW035

Table of Contents. Western States Standing Seam SS675 Panel Installation, Flashings & Shop Drawing Detail Guide. Notes to Designer /Installers..

Standing Seam Roof Systems

Breakaway Walls

Detached accessory structures that contain no conditioned floor area are exempt.

NRG 75 CRF NRG GREENBOARD WALL SYSTEM

Renovating Your Basement

Transcription:

KNIGHT WALL SYSTEMS GUIDE DETAILS: CI System (VERTICAL CI-Girt ) for CLADDING PANELS VERTICAL ORIENTED GIRT ONLY SYSTEM DEPTH: 0.75 INCHES or SYSTEM DEPTH: 1.5 INCHES (FACE OF RIGID INSULATION TO FACE OF RAIL) QUICK LINK: SECTION VIEW PLAN VIEW VERTICAL ORIENTED GIRT WITH OPTIONAL HORIZONTAL PanelRails SYSTEM DEPTH: 1.5 INCHES or SYSTEM DEPTH: 2.25 INCHES (FACE OF RIGID INSULATION TO FACE OF RAIL) QUICK LINK: SECTION VIEW PLAN VIEW & MW SHEET 1 of 24

GENERAL NOTES: KNIGHT WALL SYSTEMS (KWS) IS NOT RESPONSIBLE FOR INFORMATION SHOWN ON ALL DETAILS BEYOND KWS SPECIFIC SCOPE OF WORK (INDICATED AS "BY KWS"). ALWAYS CONSULT THE PANELS INSTALLATION & DESIGN MANUAL FOR FURTHER INFORMATION AND THE LATEST REQUIREMENTS ON ANY PANEL INSTALLATION. THESE DETAILS ARE ONLY TO COMMUNICATE HOW KWS ATTACHMENT SYSTEMS CAN BE USED WITH CLADDING PANELS/SIDING, NOT NECESSARILY THE PANEL/SIDING REQUIREMENTS AS THEY VARY FROM MANUFACTURER TO MANUFACTURER. SYSTEM MAY BE INSTALLED OVER STEEL STUDS, WOOD STUDS, CMU OR CONCRETE SUBSTRATES (WITH USE OF APPROPRIATE WALL ANCHORS). PROJECT SPECIFIC ENGINEERING CAN BE PROVIDED BY KWS AND IS REQUIRED FOR A 10 YEAR LIMITED WRITTEN WARRANTY. KWS PROJECT SPECIFIC ENGINEERING, IF SUPPLIED, IS LIMITED TO THE LOAD CARRYING COMPONENTS OF THE PRODUCTS AND FASTENERS SUPPLIED BY KWS. THE BACK-UP WALL, WALL CLADDING PANELS AND/OR RAILS SUPPLIED BY OTHERS ARE WITH OTHER PARTIES. PLEASE READ OUR INSTALLATION AND DESIGN RECOMMENDATIONS DOCUMENT FOR FURTHER INFORMATION THAT IS IMPORTANT FOR YOUR SPECIFIC PROJECT AND PROPER INSTALLATION. DETAILS OF ADJACENT WORK ARE SHOWN FOR COMPLETENESS, CLARITY AND CONVENIENCE AS AN EXAMPLE OF A BUILT ENVIRONMENT ONLY. THE STRUCTURAL SUPPORT, BACK-UP WALL AND SUPER STRUCTURE DESIGN IS WITH OTHER PARTIES (SUCH AS, BUT NOT LIMITED TO, STEEL STUD WALL, etc.). THE RESPONSIBILITY FOR THESE OTHER ASSEMBLIES TO ACCOMMODATE ALL LOADS IMPOSED UPON THEM BY KWS PRODUCTS, OR ANY ATTACHMENT OR PANEL SYSTEM, SHOULD BE CONSIDERED. SOFT JOINTS, SEALANT AND FLASHING SPECIFICATIONS, DESIGN AND INSTALLATION ARE WITH OTHER PARTIES. WEATHER RESISTANT/AIR BARRIER AND INSULATION SPECIFICATIONS, DETAILING AND INSTALLATION, INCLUDING PENETRATIONS, ARE WITH OTHER PARTIES. INTERACTION BETWEEN DISSIMILAR MATERIALS, SUCH AS ALUMINUM AND STEEL, MUST BE SEPARATED VIA PLASTIC SHIMS, TAPE OR COATING TO PREVENT GALVANIC REACTION. USE SHEARING INSTRUMENTS FOR CUTTING METAL FRAMING COMPONENTS. SAWS ARE NOT RECOMMENDED, AS THE SPARKS PRODUCED DURING CUTTING WILL DAMAGE THE ANTI-CORROSION COATING. IF SPARKS ARE GENERATED DURING CUTTING, BE SURE THE PORTION OF THE COMPONENT TO BE INSTALLED ON THE BUILDING IS PROTECTED FROM SPARKS. THE SYSTEMS COMPONENTS MUST NOT BE CUT WHILE INSTALLED ON THE BUILDING UNLESS USING A SHEARING INSTRUMENT (I.E. SNIPS, etc.). USE OF IMPACT DRIVERS IS NOT RECOMMENDED WHEN DRIVING ANY FASTENER FOR THE SYSTEM. EXTERIOR INSULATION MUST HAVE A MINIMUM OF 25 PSI COMPRESSIVE STRENGTH. CI, CI-Girt, HCI, HCI-Girt, RevealRail, Reveal-Girt, PanelRail and ThermaStop are trademarks of Knight Wall Systems, inc. THE DETAILS WITHIN THIS DRAWING PACKAGE ARE NOT INTENDED TO REPLACE PROJECT SPECIFIC ENGINEERING CALCULATIONS OR THE DESIGN SERVICES OF A REGISTERED PROFESSIONAL DESIGNER AND ARE SUBJECT TO CHANGE AT ANY TIME. NOTICE: No freedom from any patent owned by Knight Wall Systems or others is to be inferred. Because use conditions and applicable laws may differ from one location to another and may change with time, Customer is responsible for determining whether products and the information in this document are appropriate for Customer's use and for ensuring that Customer's workplace and disposal practices are in compliance with applicable laws and other government enactments. Knight Wall Systems assumes no obligation or liability for the information in this document. NO EXPRESS WARRANTIES ARE GIVEN EXCEPT FOR ANY APPLICABLE WRITTEN LIMITED WARRANTIES SPECIFICALLY PROVIDED BY KNIGHT WALL SYSTEMS. ALL IMPLIED WARRANTIES INCLUDING THOSE OF MERCHANTABILITY AND FITNESS FOR A PARTICULAR PURPOSE ARE EXPRESSLY EXCLUDED. Building and/or construction practices unrelated to building materials could greatly affect moisture and the potential for mold formation. No material supplier including Knight Wall Systems can give assurance that mold will not develop in any specific system. SHEET 2 of 24

SINGLE RAIL (LAYER) SYSTEM DOUBLE RAIL (2 LAYER) SYSTEM 1. TITLE PAGE 2. GENERAL NOTES 3. TABLE OF CONTENTS TABLE OF CONTENTS: 4. ISOMETRIC VIEW OF COMPONENTS BY KWS 5. TYPICAL SECTION VIEW - VERTICAL CI-Girt ONLY 6. TYPICAL PLAN VIEW - VERTICAL CI-Girt ONLY 7. TYPICAL SECTION VIEW - VERTICAL CI-Girt 150 ONLY 8. TYPICAL PLAN VIEW - VERTICAL CI-Girt 150 ONLY 9. TYPICAL OUTSIDE CORNER - VERTICAL CI-Girt ONLY 10. TYPICAL INSIDE CORNER - VERTICAL CI-Girt ONLY 11. TYPICAL JAMB CONDITION - VERTICAL CI-Girt ONLY 12. TYPICAL HEAD & SILL CONDITION - VERTICAL CI-Girt ONLY 13. TYPICAL BASE OF WALL CONDITION - VERTICAL CI-Girt ONLY 14. TYPICAL FLOOR DEFLECTION JOINT - VERTICAL CI-Girt ONLY 15. TYPICAL SECTION VIEW - VERTICAL CI-Girt + HORIZONTAL PanelRail 16. TYPICAL PLAN VIEW - VERTICAL CI-Girt + HORIZONTAL PanelRail 17. TYPICAL SECTION VIEW - VERTICAL CI-Girt 150 + HORIZONTAL PanelRail 18. TYPICAL PLAN VIEW - VERTICAL CI-Girt 150 + HORIZONTAL PanelRail 19. TYPICAL OUTSIDE CORNER - VERTICAL CI-Girt + HORIZONTAL PanelRail 20. TYPICAL INSIDE CORNER - VERTICAL CI-Girt + HORIZONTAL PanelRail 21. TYPICAL JAMB CONDITION - VERTICAL CI-Girt + HORIZONTAL PanelRail 22. TYPICAL HEAD/SILL CONDITION - VERTICAL CI-Girt + HORIZONTAL PanelRail 23. TYPICAL BASE OF WALL - VERTICAL CI-Girt + HORIZONTAL PanelRail PAGES HOTLINKED FOR EASY NAVIGATION! 24. TYPICAL DEFLECTION FLOOR JOINT - VERTICAL CI-Girt + HORIZONTAL PanelRail PLEASE FEEL FREE TO CONTACT KWS OR A LOCAL KWS REPRESENTATIVE FOR PROJECT SPECIFIC ASSISTANCE WITH DETAILS AND SPECIFYING. 1.855.KWS.WALL info@knightwallsystems.com SHEET 3 of 24

2" 3/4" 2" 1-1/2" FASTENER ACCESS HOLE ThermaStop ISOLATION SYSTEM ADJUSTMENT GUIDE SLOT TYPICALLY 18 gauge, 50 ksi, ASTM A1046 ZM40 Zn-Al-Mg ULTRA ANTI-CORROSION COATING, BY KWS FRONT VIEW BACK VIEW A CI-Girt (STANDARD) SCALE: NTS FRONT VIEW B CI-Girt 150 SCALE: NTS BACK VIEW 3/4" 2" - 5" STAINLESS STEEL SAE GRADE WASHER, BY KWS 2"-5" PanelRail (2" SHOWN), 18 gauge, 50 ksi, ASTM A1046 ZM40 Zn-Al-Mg ULTRA ANTI-CORROSION COATING, BY KWS C PanelRail SCALE: NTS D ThermaStop THERMAL ISOLATION WASHER ASSEMBLY SCALE: NTS ThermaStop WASHER, PRE-ASSEMBLED ON FASTENER, BY KWS ISOMETRIC VIEW OF COMPONENTS BY KWS 4 SCALE: NTS & MW SHEET 4 of 24

3 4 " BY OTHERS 4" MAX EXTERIOR SHEATHING NOT REQUIRED BY KWS (MAY BE REQUIRED FOR HOURLY FIRE RATING OR PER CD's), VERTICAL CI-GIRT, 18 gauge, 50 ksi, ASTM A1046 ZM40 Zn-Al-Mg ULTRA ANTI-CORROSION COATING, BY KWS BACK-UP WALL ASSEMBLY (STEEL STUD SHOWN, 18 GAUGE MIN.), CLADDING PANEL, <20 PSF, CLADDING TYPE & WIND PRESSURE DEPENDENT (16" O.C. TYP. - 8" O.C. FOR HEAVY CLADDING, HIGH WIND PRESSURES OR 32" O.C. GIRT SPACING) A/B OVER INSULATION OR OVER SHEATHING, STAINLESS STEEL TEK SCREW w/1,000 HR SALT SPRAY COATING AND ThermaStop THERMAL ISOLATION, BY KWS RIGID INSULATION, 25 PSI COMPRESSIVE STRENGTH, SYSTEM MAY BE INSTALLED OVER STEEL STUDS, WOOD STUDS, CMU OR CONCRETE SUBSTRATES (WITH USE OF APPROPRIATE WALL ANCHORS). TYPICAL SECTION VIEW - CI-Girt ONLY 5 SCALE: 3" = 1'-0" SHEET 5 of 24

SYSTEM MAY BE INSTALLED OVER STEEL STUDS, WOOD STUDS, CMU OR CONCRETE SUBSTRATES (WITH USE OF APPROPRIATE WALL ANCHORS). STAINLESS STEEL TEK SCREW w/1,000 HR SALT SPRAY COATING AND ThermaStop THERMAL ISOLATION, BY KWS 16" -24" O.C. (32" O.C. CI-GIRT SPACING POSSIBLE; CLADDING TYPE & WIND PRESSURES DEPENDENT) RIGID INSULATION, 25 PSI COMPRESSIVE STRENGTH, A/B OVER INSULATION OR OVER SHEATHING, 4" MAX 3 4 " BY OTHERS CLADDING PANEL, <20 PSF, VERTICAL CI-GIRT, 18 gauge, 50 ksi, ASTM A1046 ZM40 Zn-Al-Mg ULTRA ANTI-CORROSION COATING, BY KWS TYPICAL PLAN VIEW - CI-Girt ONLY 6 SCALE: 3" = 1'-0" SHEET 6 of 24

BY OTHERS 1 1 2 " 4" MAX VERTICAL CI-GIRT 150, 18 gauge, 50 ksi, ASTM A1046 ZM40 Zn-Al-Mg ULTRA ANTI-CORROSION COATING, BY KWS BACK-UP WALL ASSEMBLY (STEEL STUD SHOWN, 18 GAUGE MIN.), EXTERIOR SHEATHING NOT REQUIRED BY KWS (MAY BE REQUIRED FOR HOURLY FIRE RATING OR PER CD's), CLADDING PANEL, <20 PSF, A/B OVER INSULATION OR OVER SHEATHING, CLADDING TYPE & WIND PRESSURE DEPENDENT (16" O.C. TYP. - 8" O.C. FOR HEAVY CLADDING, HIGH WIND PRESSURES OR 32" O.C. GIRT SPACING) RIGID INSULATION, 25 PSI COMPRESSIVE STRENGTH, STAINLESS STEEL TEK SCREW w/1,000 HR SALT SPRAY COATING AND ThermaStop THERMAL ISOLATION, BY KWS SYSTEM MAY BE INSTALLED OVER STEEL STUDS, WOOD STUDS, CMU OR CONCRETE SUBSTRATES (WITH USE OF APPROPRIATE WALL ANCHORS). TYPICAL SECTION VIEW - CI-Girt 150 ONLY 7 SCALE: 3" = 1'-0" SHEET 7 of 24

SYSTEM MAY BE INSTALLED OVER STEEL STUDS, WOOD STUDS, CMU OR CONCRETE SUBSTRATES (WITH USE OF APPROPRIATE WALL ANCHORS). STAINLESS STEEL TEK SCREW w/1,000 HR SALT SPRAY COATING AND ThermaStop THERMAL ISOLATION, BY KWS 16" -24" O.C. (32" O.C. CI-GIRT SPACING POSSIBLE; CLADDING TYPE & WIND PRESSURES DEPENDENT) RIGID INSULATION, 25 PSI COMPRESSIVE STRENGTH, A/B OVER INSULATION OR OVER SHEATHING, 4" MAX 1 1 2 " BY OTHERS CLADDING PANEL, <20 PSF, VERTICAL CI-GIRT 150, 18 gauge, 50 ksi, ASTM A1046 ZM40 Zn-Al-Mg ULTRA ANTI-CORROSION COATING, BY KWS TYPICAL PLAN VIEW - CI-Girt 150 ONLY 8 SCALE: 3" = 1'-0" SHEET 8 of 24

BACKING ('L') MAY BE REQUIRED AT OUTSIDE CORNER. CONSULT CLADDING MANUFACTURER FOR DETAILS & REQUIREMENTS. THIS IS NOT REQUIRED OR SUPPLIED BY KWS. TYPICAL OSC CONDITION 9 SCALE: 3" = 1'-0" SHEET 9 of 24

BACKING ('L') MAY BE REQUIRED AT INSIDE CORNER. CONSULT CLADDING MANUFACTURER FOR DETAILS & REQUIREMENTS. THIS IS NOT REQUIRED OR SUPPLIED BY KWS. TYPICAL ISC CONDITION 10 SCALE: 3" = 1'-0" SHEET 10 of 24

ENSURE THE FULL WIDTH OF THE CI-Girt RESTS ON INSULATION. DO NOT ALLOW CI-Girt TO OVERHANG INSULATION. * FLASHING DETAILS VARY BASED ON WINDOW TYPE, POSITION (INSET VS FLUSH) AND CLADDING TYPE. FLASHING IS. TYPICAL JAMB CONDITION 11 SCALE: 3" = 1'-0" SHEET 11 of 24

4" O.C. MAX TYPICALLY 4" O.C. MAX TYPICALLY ENSURE THE CI-Girt DOES NOT EXTEND/CANTILEVER PAST INSULATION. * FLASHING DETAILS VARY BASED ON WINDOW TYPE, POSITION (INSET VS FLUSH) AND CLADDING TYPE. FLASHING IS. TYPICAL HEAD & SILL CONDITION 12 SCALE: 3" = 1'-0" SHEET 12 of 24

A/B SEALANT, 4" O.C. MAX TYPICALLY 3 4 " MIN. SHEET METAL DRIP FLASHING, PRE-FINISHED, * CLEAR & UNRESTRICTED VENTILATION & DRAINAGE REQUIRED AT BASE OF WALL TYPICAL BASE OF WALL CONDITION 13 SCALE: 3" = 1'-0" SHEET 13 of 24

VERTICAL CI-GIRT, 18 gauge, 50 ksi, ASTM A1046 ZM40 Zn-Al-Mg ULTRA ANTI-CORROSION COATING, BY KWS FIBER OR OPEN CELL FOAM COMPRESSIBLE INSULATION, CONSULT INSULATION MANUFACTURER FOR DETAILS, A BREAK/MOVEMENT JOINT IN CLADDING MUST COINCIDE WITH BREAK IN ATTACHMENT SYSTEM AND FLOOR DEFLECTION JOINTS TO PREVENT DAMAGE AND STRESS ON WALL SYSTEM, CONSULT CLADDING MANUFACTURER FOR DETAILS, GAP BETWEEN RAILS TYPICALLY EQUALS 1.5x THE EXPECTED FLOOR MOVEMENT, MINIMUM OF 3 8" AND MAXIMUM OF 1.5" CI-Girt WALL ANCHOR MUST NOT INFRINGE ON STEEL STUD FLOOR DEFLECTION TRACK MOVEMENT FLOOR DEFLECTION TRACK, BY OTHERS TYPICAL FLOOR DEFLECTION JOINT 14 SCALE: 3" = 1'-0" SHEET 14 of 24

3 3 4 " 4 " BY OTHERS 4" MAX STAINLESS STEEL TEK SCREW w/1,000 HR SALT SPRAY COATING, BY KWS 2"-5" PanelRail (2" SHOWN), 18 gauge, 50 ksi, ASTM A1046 ZM40 Zn-Al-Mg ULTRA ANTI-CORROSION COATING, BY KWS VERTICAL CI-GIRT, 18 gauge, 50 ksi, ASTM A1046 ZM40 Zn-Al-Mg ULTRA ANTI-CORROSION COATING, BY KWS DETERMINED BY DESIGN WIND PRESSURE (AND AS REQUIRED BY PANEL MANUFACTURER) BACK-UP WALL ASSEMBLY (STEEL STUD SHOWN, 18 GAUGE MIN.), EXTERIOR SHEATHING NOT REQUIRED BY KWS (MAY BE REQUIRED FOR HOURLY FIRE RATING OR PER CD's), CLADDING PANEL, <20 PSF, A/B OVER INSULATION OR OVER SHEATHING, RIGID INSULATION, 25 PSI COMPRESSIVE STRENGTH, CLADDING TYPE & WIND PRESSURE DEPENDENT (16" O.C. TYP. - 8" O.C. FOR HEAVY CLADDING, HIGH WIND PRESSURES OR 32" O.C. GIRT SPACING) STAINLESS STEEL TEK SCREW w/1,000 HR SALT SPRAY COATING AND ThermaStop THERMAL ISOLATION, BY KWS SYSTEM MAY BE INSTALLED OVER STEEL STUDS, WOOD STUDS, CMU OR CONCRETE SUBSTRATES (WITH USE OF APPROPRIATE WALL ANCHORS). TYPICAL SECTION VIEW - CI-Girt + PanelRail 15 SCALE: 3" = 1'-0" SHEET 15 of 24

SYSTEM MAY BE INSTALLED OVER STEEL STUDS, WOOD STUDS, CMU OR CONCRETE SUBSTRATES (WITH USE OF APPROPRIATE WALL ANCHORS). STAINLESS STEEL TEK SCREW w/1,000 HR SALT SPRAY COATING AND ThermaStop THERMAL ISOLATION, BY KWS 16" -24" O.C. (32" O.C. CI-GIRT SPACING POSSIBLE; CLADDING TYPE & WIND PRESSURES DEPENDENT) RIGID INSULATION, 25 PSI COMPRESSIVE STRENGTH, A/B OVER INSULATION OR OVER SHEATHING, 4" MAX 3 4 " 3 4 " BY OTHERS STAINLESS STEEL TEK SCREW w/1,000 HR SALT SPRAY COATING, BY KWS 2"-5" PanelRail, 18 gauge, 50 ksi, ASTM A1046 ZM40 Zn-Al-Mg ULTRA ANTI-CORROSION COATING, BY KWS VERTICAL CI-GIRT, 18 gauge, 50 ksi, ASTM A1046 ZM40 Zn-Al-Mg ULTRA ANTI-CORROSION COATING, BY KWS CLADDING PANEL, <20 PSF, TYPICAL PLAN VIEW - CI-Girt + PanelRail 16 SCALE: 3" = 1'-0" SHEET 16 of 24

BY OTHERS 3 4 " 1 1 2 " 4" MAX STAINLESS STEEL TEK SCREW w/1,000 HR SALT SPRAY COATING, BY KWS 2"-5" PanelRail (2" SHOWN), 18 gauge, 50 ksi, ASTM A1046 ZM40 Zn-Al-Mg ULTRA ANTI-CORROSION COATING, BY KWS VERTICAL CI-GIRT 150, 18 gauge, 50 ksi, ASTM A1046 ZM40 Zn-Al-Mg ULTRA ANTI-CORROSION COATING, BY KWS DETERMINED BY DESIGN WIND PRESSURE (AND AS REQUIRED BY PANEL MANUFACTURER) BACK-UP WALL ASSEMBLY (STEEL STUD SHOWN, 18 GAUGE MIN.), EXTERIOR SHEATHING NOT REQUIRED BY KWS (MAY BE REQUIRED FOR HOURLY FIRE RATING OR PER CD's), CLADDING PANEL, <20 PSF, A/B OVER INSULATION OR OVER SHEATHING, RIGID INSULATION, 25 PSI COMPRESSIVE STRENGTH, CLADDING TYPE & WIND PRESSURE DEPENDENT (16" O.C. TYP. - 8" O.C. FOR HEAVY CLADDING, HIGH WIND PRESSURES OR 32" O.C. GIRT SPACING) STAINLESS STEEL TEK SCREW w/1,000 HR SALT SPRAY COATING AND ThermaStop THERMAL ISOLATION, BY KWS SYSTEM MAY BE INSTALLED OVER STEEL STUDS, WOOD STUDS, CMU OR CONCRETE SUBSTRATES (WITH USE OF APPROPRIATE WALL ANCHORS). TYPICAL SECTION VIEW - CI-Girt 150 + P.R. 17 SCALE: 3" = 1'-0" SHEET 17 of 24

SYSTEM MAY BE INSTALLED OVER STEEL STUDS, WOOD STUDS, CMU OR CONCRETE SUBSTRATES (WITH USE OF APPROPRIATE WALL ANCHORS). STAINLESS STEEL TEK SCREW w/1,000 HR SALT SPRAY COATING AND ThermaStop THERMAL ISOLATION, BY KWS 16" -24" O.C. (32" O.C. CI-GIRT SPACING POSSIBLE; CLADDING TYPE & WIND PRESSURES DEPENDENT) RIGID INSULATION, 25 PSI COMPRESSIVE STRENGTH, A/B OVER INSULATION OR OVER SHEATHING, 4" MAX 1 1 2 " 3 4 " BY OTHERS STAINLESS STEEL TEK SCREW w/1,000 HR SALT SPRAY COATING, BY KWS 2"-5" PanelRail, 18 gauge, 50 ksi, ASTM A1046 ZM40 Zn-Al-Mg ULTRA ANTI-CORROSION COATING, BY KWS VERTICAL CI-GIRT 150, 18 gauge, 50 ksi, ASTM A1046 ZM40 Zn-Al-Mg ULTRA ANTI-CORROSION COATING, BY KWS CLADDING PANEL, <20 PSF, TYPICAL PLAN VIEW - CI-Girt 150 + PanelRail 18 SCALE: 3" = 1'-0" SHEET 18 of 24

BACKING ('L') MAY BE REQUIRED AT OUTSIDE CORNER. CONSULT CLADDING MANUFACTURER FOR DETAILS & REQUIREMENTS. THIS IS NOT REQUIRED OR SUPPLIED BY KWS. MAXIMUM PanelRail CANTILEVER BEYOND CI-Girt VARIES PER PROJECT. TYPICALLY IT WILL RANGE FROM 6"-14". TYPICAL OSC CONDITION 19 SCALE: 3" = 1'-0" SHEET 19 of 24

BACKING ('L') MAY BE REQUIRED AT INSIDE CORNER. CONSULT CLADDING MANUFACTURER FOR DETAILS & REQUIREMENTS. THIS IS NOT REQUIRED OR SUPPLIED BY KWS. TYPICAL ISC CONDITION 20 SCALE: 3" = 1'-0" SHEET 20 of 24

ENSURE THE FULL WIDTH OF THE CI-Girt RESTS ON INSULATION. DO NOT ALLOW CI-Girt TO OVERHANG INSULATION. * FLASHING DETAILS VARY BASED ON WINDOW TYPE, POSITION (INSET VS FLUSH) AND CLADDING TYPE. FLASHING IS. TYPICAL JAMB CONDITION 21 SCALE: 3" = 1'-0" SHEET 21 of 24

4" O.C. MAX TYPICALLY 4" O.C. MAX TYPICALLY ENSURE THE CI-Girt DOES NOT EXTEND/CANTILEVER PAST INSULATION. * FLASHING DETAILS VARY BASED ON WINDOW TYPE, POSITION (INSET VS FLUSH) AND CLADDING TYPE. FLASHING IS. TYPICAL HEAD & SILL CONDITION 22 SCALE: 3" = 1'-0" SHEET 22 of 24

A/B SEALANT, 4" O.C. MAX TYPICALLY 3 4 " MIN. SHEET METAL DRIP FLASHING, PRE-FINISHED, * CLEAR & UNRESTRICTED VENTILATION & DRAINAGE REQUIRED AT BASE OF WALL TYPICAL BASE OF WALL CONDITION 23 SCALE: 3" = 1'-0" SHEET 23 of 24

VERTICAL CI-GIRT, 18 gauge, 50 ksi, ASTM A1046 ZM40 Zn-Al-Mg ULTRA ANTI-CORROSION COATING, BY KWS FIBER OR OPEN CELL FOAM COMPRESSIBLE INSULATION, CONSULT INSULATION MANUFACTURER FOR DETAILS, A BREAK/MOVEMENT JOINT IN CLADDING MUST COINCIDE WITH BREAK IN ATTACHMENT SYSTEM AND FLOOR DEFLECTION JOINTS TO PREVENT DAMAGE AND STRESS ON WALL SYSTEM, CONSULT CLADDING MANUFACTURER FOR DETAILS, GAP BETWEEN RAILS TYPICALLY EQUALS 1.5x THE EXPECTED FLOOR MOVEMENT, MINIMUM OF 3 8" AND MAXIMUM OF 1.5" CI-Girt WALL ANCHOR MUST NOT INFRINGE ON STEEL STUD FLOOR DEFLECTION TRACK MOVEMENT FLOOR DEFLECTION TRACK, BY OTHERS TYPICAL FLOOR DEFLECTION JOINT 24 SCALE: 3" = 1'-0" SHEET 24 of 24