PS161-6 Power Supply Installation Instructions

Similar documents
HM-W536 Install Guide

Video Surveillance UPS. Installation Guide

DORMA MODEL PS-406BB POWER SUPPLY INSTALLATION INSTRUCTIONS

HONEYWELL COMMERCIAL FIRE/BURG PANEL UL LISTING REQUIREMENTS (Compiled from VistaFBPT Installation Instructions V1 Rev A 11/12)

SECURITY / ACCESS / FIRE / SURVEILLANCE

INSTALLATION GUIDE. Card Reader & Controller with KIM Swipe Reader for Solitaire 850 / 950 / 850L Learnlok PK2930

AC-115 Compact Networked Single Door Controller. Installation and User Manual

CM705B - Universal Expander Module CM707B - Plug On Zone Expander Security Systems

Automatic Transfer Switch FT-10 Network Control Communications Module (CCM-T) Kit

Mobile Data Power Model: MDP-25

SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

Control Panels D9412GV3/D7412GV3/D7212GV3. UL Installation Instructions

SFC-200 SERIES FIRE ALARM CONTROL PANELS. SFC-200 Series Fire Alarm Control Panels. Features. Description

DTW Works Master Specification Version 2006

SECTION FIRE AND SMOKE ALARM SYSTEM. City of San Diego, CWP Guidelines

HAM841K ALARM CONTROL PANEL FOR COMMERCIAL AND RESIDENTIAL SECURITY SYSTEMS

FIREDEX Conventional Fire Panels

FIRE ALARM AND DETECTION SYSTEMS SECTION 16721

D287/D288/D292/D293A/D293E

SECTION DETECTION AND ALARM

BARDIC. 4 & 8 Zone Fire Panels Zircon range. Data, installation, operation and maintenance. by Honeywell

TS510 & TS500. Installation & User Guide. Compatible Equipment

FLORIDA ATLANTIC UNIVERSITY FIRE ALARM SYSTEM INSTALLATION MANUAL

INTELLIGENT FIRE ALARM CONTROL PANELS. MR-2100/MR-2200 Intelligent Fire Alarm Control Panels MEA. Features. Description

INTRUSION DETECTION SYSTEM Section

SP4-LOC SAFEPATH4 REMOTE MICROPHONE AND LOCAL OPERATOR CONSOLE

SILENT KNIGHT MODEL 5207

conventional system operation

MODEL 5010 DUAL CHANNEL SMOKE/FIRE DETECTION MODULE

CONTENTS. GST102A/104A/108A/116A Conventional Fire Alarm Control Panel Installation and Operation Manual

Fire Control Panels. Remote Annunciator Panels. UL, ULC, CSFM Listed; FM Approved; MEA (NYC) Acceptance* Features. Introduction

FIRERAY 2000 Installation Guide

2.0 Installation 1. Remove the cover using a small flat blade screwdriver. Figure 2: Cover Removal

A.1. a Division of Pittway Corporation. Documento: M MGAS-ENG. Edizione: 01/1997 Rev.:

PC4020CF v3.0 and higher Commercial Fire Installation Guide DLS-3 v1.3

DH100ACDCLP Air Duct Smoke Detector with Extended Air Speed Range

Fire Fighter Phone System Installation Instructions

INSTALLATION INSTRUCTIONS

Duct Humidity Transmitter

Residential Gateway (RG) Battery Backup

NC State University Design and Construction Guidelines Division 26 Fire Alarm Systems

9448 Installation and User Guide

ALARM ANNUNCIATOR ME INSTRUCTION MANUAL

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

CB200W Water Leak Detection Panel Application Guide

500r+ Installation and User Guide

SECTION FIRE ALARM AND DETECTION SYSTEM

Control Panel. D9412GV4/D7412GV4 v2.03. en UL Installation Instructions

TrueAlarm Fire Alarm Systems

EVC40 EMERGENCY VOICE COMMUNICATION SYSTEM

Advantium 2 Plus Alarm

FIRE ALARM SYSTEM TECHNICAL SPECIFICATIONS Page 1 of 10

Fire Alarm System Plans Review Checklist Property location Date of Review

Model 201 Wiegand Touchpad Reader Installation Guide

FC-72 SERIES FIRE ALARM SYSTEM

Fire Alarm System Plans Submittal Guidelines For New and Existing Systems

AM100 SECURITY SYSTEM INSTALLATION INSTRUCTIONS

DUCT SMOKE DETECTOR D4120

SECTION FIRE DETECTION AND ALARM SYSTEM PART 1 - GENERAL 1.01 DESCRIPTION

INSTALLATION & SERVICE MANUAL. Display Panel

DH100ACDCLWP Watertight Air Duct Smoke Detector with Extended Air Speed Range

PLAN REVIEW GUIDE FOR FIRE ALARM

4-Wire Air Duct Smoke Detector. Protection Systems. A UTC Fire & Security Company. Models DH-60 FEATURES APPLICATION DESCRIPTION SAMPLING TUBES

Contractors Guide Central Inverter System Installation

rpsa FIRE PROTECTION ENGINEERS

CLARK COUNTY FIRE DEPARTMENT Fire Hazard & Prevention Services

WD-AMX Water Detection Controllers

Reference & Installation Manual

Fire Alarm Control Panel. Family. Operating Manual

FA-300 Series. LCD Fire Alarm Control Panel. User Guide. LT-954 Rev. 0.1 February FA-300 SERIES Fire Alarm Control Panel

SECTION FIRE ALARM AND DETECTION SYSTEM

SPECIFICATION MICROMIST FIRE SUPPRESSION SYSTEM WITH CHEETAH Xi CONTROL PANEL

E-PDD Duct Smoke Detector Installation Sheet

EQUIPMENT SPECIFICATIONS

HERNANDO COUNTY FIRE ALARM GUIDELINES

3. MOUNTING THE FIRE ALARM PANEL PLANNING CABLE ENTRY 3.2 FIXING THE BACKBOX TO THE WALL

ACTIVE 5 ENGINEERING MANUAL

Field Charger/Power Supply FCPS-24FS6 & FCPS-24FS8 FCPS-24FS6E & FCPS-24FS8E FCPS-24FS6C & FCPS-24FS8C Installation Manual

T7560A,B,C Digital Wall Module

Manual for Fire Suppression & Methane Detection System

D9412GV3/D7412GV3. Approved Applications Compliance Guide. Control Panels

ARCHITECT AND ENGINEER SPECIFICATION SECTION DETECTION AND ALARM SECURITY ACCESS AND SURVEILLANCE. DSC MAXSYS PC4020 V3.

*.ppt 11/2/ :48 PM 1

Secure Keypads for access control

Self Monitoring Power Supply (BPSM)

9452/9453 Installation and User Guide

Detector transparent with Color Inserts. FAA 500 TR P Trim Ring transparent with Color Inserts. FCA 500 / FCA 500 E Detector Bases

FIRE ALARM SYSTEM CHECKLIST For Addressable Systems PRIOR TO INSPECTION

PLAN400 V6.6X. Networked Access Control Panel. Installation Guide

BATTERY BOX INSTALLATION WARNING WARNING CAUTION ATTENTION AVERTISSEMENT ADVERTENCIA PRECAUCIÓN SOLBBOX12V CARTON INVENTORY COMPLETED OVERVIEW

is then retained absolutely without interruption.

VFR-400 Installation, Operation, and Instruction Manual

SECTION FIRE DETECTION AND ALARM SYSTEM

SPECIFICATION FOR A TOTAL FLOOD HFC-227ea CLEAN AGENT FIRE SUPPRESSION SYSTEM FOR USE WITH THE Cheetah Xi CONTROL PANEL SYSTEM

Design and Construction Standards SECTION FIRE ALARM AND SMOKE DETECTION SYSTEMS

PFC-6030 Fire Alarm Control Panel

Small Building Life Safety Solutions. GE Security. Affordable FireShield Conventional Fire Alarm Control Panels. imagination at work

Infrastructure Management & Monitoring For Business-Critical Continuity. Liebert AC4. User Manual

8900 EMR (WITH DETECTOR)

Table of Contents. 1 - Specifications Installation Wiring User controls...7

Transcription:

Altronix Corp. 140 58th St. Brooklyn, Y PS161-6 Power Supply Installation Instructions Overview: PS161-6 converts a 120VAC / 60Hz input, to a 12VDC or 24VDC nominal output. PS161-6 comes with a power-limited power distribution module with 8 outputs. Class 1 wiring methods and separation of circuits must be considered when connecting DC power supply to the Delayed Egress hardware. UL Listings for US Installations: UL 294 - UL Listed for Access Control System Units. UL 603 - UL Listed for Power Supplies for Use with Burglar-Alarms Systems. UL 1481 - UL Listed for Power Supplies for Fire Protective Signaling Systems. UL Listings for Canadian Installations: ULC-S318-96 - Power Supplies for Burglar Alarm Systems. Also suitable for Access Control. California State Fire Marshal European Conformity Specifications: Input: Voltage: 120V AC, 60HZ Current: 3.5A AC Input fuse ratings:5a/250v Battery fuse ratings: 7.5A/32V Output: Voltage: 20.0-26.4V Total output: 6 amps Power limit/output: 2 amps/per channel Outputs: 8 (For Delayed Egress applications: use only 4) Ripple voltage: 910mV (Filtered and regulated outputs) Protection: Thermal and short circuit protection with auto reset overload protection. Battery Backup Built-in charger for sealed lead acid or gel type batteries Maximum charge current 1.54 amp Automatic switch over to stand-by is instantaneous with no interruption Enclosure Dimensions: 12.5 x 13 x 3.25 (3.18mm x 330.2mm x 82.55mm) Fire Alarm Disconnect: Supervised Fire Alarm disconnect (latching or non-latching) 10K EOL resistor. Operates on a normally open (O) or normally closed (C) trigger. Supervision AC fail supervision (form C contacts). Visual Indicators Green AC Power LED indicates 120VAC present. Additional Features Short circuit and overload protection. Unit is complete with power supply, enclosure, battery leads and cam lock. Enclosure Dimensions 12.5 x 13 x 3.25 (318mm x 330.2mm x 82.55mm) 1/9

Installation Instructions: Wiring methods shall be in accordance with the ational Electrical Code/FPA 70/FPA 72/ASI, The Canadian Electrical Code, Part 1 and with all local codes and authorities having jurisdiction. The product must be located indoors within the protected premises. 1. Mount unit in the desired location. Mark and predrill holes in the wall to line up with the top two keyholes in the enclosure. Install two upper fasteners and screws in the wall with the screw heads protruding. Place the enclosure s upper keyholes over the two upper screws, level and secure. Mark the position of the lower two holes. Remove the enclosure. Drill the lower holes and install the two fasteners. Place the enclosure s upper keyholes over the two upper screws. Install the two lower screws and make sure to tighten all screws (Enclosure Dimensions, pg. 8). 2. Secure enclosure to earth ground. 3. Set the DC output voltage to 24DC by setting SW1 to the open position on the power supply board (Figure 2-1a). 4. Connect unswitched AC power (120VAC 60Hz) to terminals marked [L, ] (Figure 1). Use 18 AWG for all power connections and 18 AWG to 22 AWG for power limited circuits (AC Fail/Low Battery reporting). Secure green wire lead to earth ground. Keep power-limited wiring separate from non power-limited wiring (120VAC 60Hz Input, Battery Wires). Minimum 0.25 spacing must be provided. 5. Measure output voltage before connecting devices. This helps avoid potential damage. 6. Connect the delayed egress exit device locking hardware positive leads to terminals marked 1 through 4 POS (+) on the PD8ULCB board and negative leads to the EG 1 terminals through 4 terminals. O Figure 1 - Wiring Diagram for Connecting DE Exit Devices to a PS161-6 Power Supply Separation of powerlimited wiring from non power-limited wiring must be at least 1/4 inch..c. Input from Fire Panel 10K EOL OR.O. Input from Fire Panel 10K EOL OR Green Lead (Ground) o Fire Connections 10K EOL Power-limited L G C C O C C O 2 hr. 1 min. Disable Enable AC1 BAT FAIL AC FAIL AC DC AC DELAY SHUTDOW AUX + GD O TRIGGER EOL RESET SUPERVISED 5A 250V 120VAC Power Mains (on Power-limited) Battery & AC Supervision Circuit (Power-limited) Battery Connections (on Power-limited) Power must be turned off before changing the voltage select switch. Switch Detail Open - 24V Closed - 12V Potentiometer Open - 24V Closed - 12V Divider 1 2 3 4 5 6 7 8 P D1 R1 LED FUSED POWER OUTPUTS DC Output to Devices (1P-8P Power Outputs) (1-8 Common Outputs) IPUT + 12VDC Rechargeable Battery C O M M O POWER O U T PUTS From Power Supply Board (Factory Installed) Delayed Egress Exit Device #4 12VDC Rechargeable Battery Delayed Egress Exit Device #3 Delayed Egress Exit Device #2 Delayed Egress Exit Device #1 + --- BAT + --- DC + ote A 10k EOL (End of Line) Resistor must be installed across terminals marked (Trigger EOL Supervised) on the PS161-6 board or the unit will remain in fire alarm condition. 7. For Access Control applications batteries are optional. When batteries are not used, a loss of AC will result in the loss of output voltage. Batteries must be lead acid or gel type if used. Use two 12VDC batteries connected in series for 24VDC operation (Battery leads included). 8. Connect battery to terminals marked [-- BAT + ] (Figure 2-1g). Use two (2) 12VDC batteries connected in series for 24VDC operation (battery leads included). Use batteries - Casil CL1270 (12V/7AH), CL12120 (12V/12AH), CL12400 (12V/40AH), CL12650 (12V/65AH) batteries or UL recognized BAZR2 batteries of an appropriate rating. 9. To trigger the power supply from a fire alarm control panel (FACP), connect signaling circuit of FACP to terminals marked Trigger End of Line Supervised. 10. To delay AC reporting for 2 hrs. set dip switch [AC Delay] to OFF position (Figure 2-1c). 11. To delay AC reporting for 1 min. set dip switch [AC Delay] to O position (Figure 2-1c). ote Must be set to O position for Burglar Alarm Applications. 2/9

12. To enable Low Output Power Shutdown set dip switch [Shutdown] to O position (Figure 2-1c). 13. To disable Low Output Power Shutdown set dip switch Shutdown] to OFF position (Figure 2-1c). 14. Trigger terminals are end of a line resistor supervised (10k ohms). Opening or shorting trigger terminals will cause [DC] output to shutdown (Figure 2-1d). 15. Place a jumper for non-latching FACP. A momentary short on these terminals resets FACP latching [Trigger EOL Shutdown] (Figure 2-1e). 16. For Access Control Applications: mount UL Listed tamper switch (Sentrol model 3012 or equivalent) at the top of the enclosure. Slide tamper switch bracket onto the edge or the enclosure approx. 2 from the right side (Figure 4 or Figure 5). Connect tamper switch wiring to the Access Control Panel input or the appropriate UL Listed reporting device. Wiring: Use 18 AWG or larger for all low voltage power connections. ote Take care to keep power-limited circuits separate from non power-limited wiring (120VAC, Battery). Maintenance: Unit should be tested at least once a year for the proper operation as follows: Output Voltage Test: Under normal load conditions, the DC output voltage should be checked for proper voltage level PS161-6: 24VDC nominal rated @ 6 amp max. Battery Test: Under normal load conditions check that the battery is fully charged, check specified voltage (24VDC @ 26.4) both at the battery terminal and at the board terminals marked [-- BAT + ] to ensure that there is no break in the battery connection wires. ote Maximum charging current under discharges is 1.54 amp. ote Expected battery life is 5 years, however it is recommended changing batteries in 4 years or less if needed. LED Diagnostics: Power Supply/Charger Red (DC) Green (AC/AC1) Power Supply Status O O ormal operating condition. O OFF Loss of AC, Stand-by battery supplying power. OFF O o DC output. OFF OFF Loss of AC. Discharged or no stand-by battery. o DC output. Power Distribution Module Green (AC) O OFF Power Distribution Module Status ormal operating condition. o Power Output. Terminal Identification: Power Supply/Charger Terminal Legend Function/Description L, Connect 120VAC 60Hz to these terminals: L to hot, to neutral (non power-limited) (Figure 2-1a). DC + 12VDC or 24VDC nominal @ 6 amp continuous output (non power-limited output) (Figure 2-1h). Trigger EOL Supervised O, GD RESET Fire Alarm Interface trigger input from a short or FACP. Trigger inputs can be normally open, normally closed from an FACP output circuit (power-limited input) (Figure 2-1d). FACP interface latching or non-latching (power-limited) (Figure 2-1e). + AUX Auxiliary Power-Limited output rated @ 1 amp (unswitched) (power-limited output) (Figure 2-1f). AC Fail C, C, O Indicates loss of AC power, e.g. connect to audible device or alarm panel. Relay normally energized when AC power is present. Contact rating 1 amp @ 30VDC (power-limited) (Fig. 1b). 3/9

Bat Fail C, C, O Indicates low battery condition, e.g. connect to alarm panel. Relay normally energized when DC power is present. Contact rating 1 amp @ 30VDC. A removed battery is reported within 5 minutes. Battery reconnection is reported within 1 minute (power-limited) (Figure 2-1b). BAT + Stand-by battery connections. Maximum charge current 1.54 amp (non power-limited) (Figure 2-1g). Terminal Identification: Power Distribution Module Terminal Legend 1P to 8P 1 to 8 Function/Description Positive DC power outputs egative DC power outputs Figure 2 - PS161-6 Board configuration OPE --- 24V CLOSED --- 12V 1i --- DC + 1h --- BAT + 1g 5A 250V AC1 AC FAIL BAT FAIL AC DELAY SHUTDOW O L G C C O C C O AC DC 1 min. 2 hr. enable disable TRIGGER EOL SUPERVISED O GD RESET + AUX 1a 1b 1c 1d 1e 1f Trouble/Time Limited Warning of Stand-by Batteries: For compliance with ULC S318-96, the Time Limited Warning circuit must be connected for local or remote annunciation with an Amber or Red LED to indicate DC Trouble (low battery, loss of battery or when 95% of the stand-by battery has been depleted). Connect the circuit to the Batt Fail relay contacts to an appropriate input of a UL Listed Burglar Alarm or Access Control Panel. The following figure shows the circuitry needed for local annunciation. 4/9

Figure 3 - Battery trouble indication For Canadian use, a red indicating lamp must be visible from the exterior of this enclosure. Wire one leg of a UL Listed, power-limited power source to the indicating lamp. Wire the second leg of the power source to the indicating lamp in series with the battery fail relay contact terminals marked [BAT FAIL - C, O]. Power Distribution Module: AC FAIL BAT FAIL POWER SOURCE C C O C C O RED IDICATIG LAMP Figure 4 - PD8ULCB - Power Distribution Board Power-Limited Outputs P 1 2 3 4 5 6 7 8 FUSED POWER OUTPUTS D1 R1 LED COMMO POWER OUTPUTS IPUT DC Output to devices 1P-8P Power Outputs, 1-8 Common Outputs ( ) From Power Supply Board (Factory Installed) 5/9

Figure 5 5A 250V O Edge of Enclosure Enclosure Sentrol model # 3012 Tamper Switch or equivalent (ot Included) to Access Control Panel or U.L. Listed Reporting Device Door Wire Strap (from Enclosure to Door) Green Lead (ground) L G 120VAC power mains on Powerlimited PD8UL/PD8ULCB PD16W/ PD16WCB Switch Detail AC1 C C O C C O BAT FAIL AC FAIL Battery & AC Supervision Circuit (Power-limited) OPE 24V CLOSED 12V DC Output to devices* (refer to Fig. 3a, 3b, 4a or 4b for board configuration pg. 6) AC OPE --- 24V CLOSED --- 12V DC 2 hr. 1 min. AC DELAY disable enable SHUTDOW Powerlimited RESET TRIGGER EOL AUX + GD O SUPERVISED Battery Connections (on Power-limited) --- BAT + --- DC + Optional Rechargeable Stand-by Battery for UL294 Applications. ote: 12V batteries required for UL603, UL1481 and Canadian installations. Optional Rechargeable Stand-by Battery for UL294 Applications. ote: 12V batteries required for UL603, UL1481 and Canadian installations. CAUTIO: When power supply board is set for 12VDC use only one (1) 12VDC stand-by battery. Keep power-limited wiring separate from non power-limited. Use minimum 0.25" spacing. 7AH Rechargeable batteries are the largest batteries that can fit in this enclosure. 6/9

EC Power-Limited Wiring Requirements: Power-limited and non power-limited circuit wiring must remain separated in the cabinet. All power-limited circuit wiring must remain at least 0.25 away from any non power-limited circuit wiring. Furthermore, all power-limited circuit wiring and non power-limited circuit wiring must enter and exit the cabinet through different conduits. One such example of this is shown below. Your specific application may require different conduit knockouts to be used. Any conduit knockouts may be used. For power- limited applications, use of conduit is optional. All field wiring connections must be made employing suitable gauge CM or FPL jacketed wire (or equivalent substitute). Optional UL Listed battery enclosure must be mounted adjacent to the power supply via Class 1 wiring methods. For Canadian installations use shielded wiring for all connections. ote Refer to wire handling drawing below for the proper way to install the CM or FPL jacketed wire, (Figure 5). Figure 5 Incorrect Wire Handling Correct Wire Handling Figure 6 External Jacketed Shield Wire Insulation Solid Copper Conductors Pull back external jacketed shield approx. 1/2. 7/9

Enclosure Dimensions: 12.5 x 13 x 3.25 (318mm x 330.2mm x 82.55mm) Figure 7 - Power Supply Enclosure Template 1.40 (36mm) 4.85 (123mm) 4.85 (123mm) 1.40 (36mm) Edge of Enclosure 1.20 (31mm) 3.25 (83mm) Sentrol Model # 3012 Tamper Switch or equivalent (ot Included) Enclosure To Access Control Panel or U.L. Listed Reporting Device 1.20 (31mm) 0.75 (19mm) 12.5 (318mm) 1.20 (31mm) 1.40 (36mm) 0.94 (24mm) 1.40 (36mm) 11.0 (279mm) 0.75 (19mm) 5.10 (130mm) 5.10 (130mm) 13.0 (330mm) 5.10 (130mm) 6.57 (167mm) 0.94 (24mm) 3.25 (83mm) 3.25 (83mm) 1.0 (25mm) 1.0 (25mm) 10.5 (267mm) 1.0 (25mm) 1.0 (25mm) 3.25 (83mm) otes 1 Separation of power limited wiring from non-power limited wiring must be at least 1/4 inch. 2 Power must be turned off before changing the voltage select switch. 8/9

Appendix A - UL Listed Compatible Devices A.1 Four (4) Wire Smoke Detectors Table A-1 below lists four (4) wire smoke detectors compatible with PS161-6 output. System Sensor Smoke Detector/Base Detector Type Max Stand-by Current (ma) B112LP Base 0.12 36 DH100ACDC Photoelectric 0.15 0.70 DH100ACDCLP Photoelectric 0.15 0.70 DH100ACDCLPW Photoelectric 0.15 0.70 DH400ACDCI Ionization Duct 25 95 DH400ACDCP Photoelectric Duct 25 95 1112/24/D Ionization 0.05 50 1424 Ionization 0.10 41 1451 (w/b402b Base) Ionization 0.10 39 2112/24ATR Photoelectric 0.50 60/70 2112/24AITR Photoelectric 0.50 60/70 2112/24/D Photoelectric 0.05 50 2112/24T/D Photoelectric w/135o Thermal 0.05 50 2112/24TSRB Photoelectric w/135o Thermal Supervisory Relay 15 45 2312/24TB Photoelectric 0.12 50 2412 (12 volt) Photoelectric 0.12 77 2424 Photoelectric 0.10 41 2451 Photoelectric 0.10 39 2451TH (with/b402b Base) Photoelectric 0.10 39 2W-MOD Loop Test/Maintenance Mod. 30 50 4W-B (12/24 volt) Photoelectric I3.05 23 4WT-B (12/24 volt) Photoelectric I3 w/therm.05 23 4WTA-B (12/24 volt) I3 Photo w/therm/sounder.05 35 4WTR-B (12/24 volt) I3 Photo w/therm/relay.05 35 4WITAR-B (12/24 volt) I3 Photo w/isolated Therm/Sounder/Relay.05 50 6424 Projected Beam 10 28.4 Beam 1224(S) Projected Beam 17 38.5 A.2 Relays Table A-2 below lists relays compatible with PS161-6 output. Manufacturer Model Current (ma) Manufacturer System Sensor EOLR-1 30 System Sensor Alarm Current (ma) For assistance or warranty information: Call 1-855-365-2407 or visit www.stanleysecurity.com/precision Warning: This Manufacturer advises that no lock can provide complete security by itself. This lock may be defeated by forcible or technical means, or evaded by entry elsewhere on the property. o lock can substitute for caution, awareness of your environment, and common sense. Builder s hardware is available in multiple performance grades to suit the application. In order to enhance security and reduce risk, you should consult a qualified locksmith or other security professional. 9/9