SECTION A. Horsepower: Do not increase or decrease fan motor horsepower without written approval from Engineer.

UNIVERSITY OF ROCHESTER DESIGN STANDARDS OCTOBER 18, 2013

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

UPBLAST & HOODED PROPELLER ROOF VENTILATORS

Recirculating Roof Fans Models ESRMD, ESRMDF and ERD

SECTION COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER

Cooktop Low-Profile Ventilation Hoods

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

SECTION SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

CE6500 Energy Recovery Ventilator

Commercial Gas Furnace Upflow

SECTION HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

D Youville College July 31, 2008 New Academic Building Cannon Design Project No

Ventilation Solutions Kitchens. fantech

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION BLOWER COIL UNITS

ROOF TOP MOUNTED Air Handler Specification

AIR CONDITIONING PRODUCTS COMPANY

Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling

Roof Curbs, Extensions and Equipment Supports

Utility Distribution Systems

SECTION MORTUARY REFRIGERATORS

Gas Unit Heaters Duct Furnaces Horizontal - 60 HZ Form No. LF (10/2011) LF24 Standard

SECTION PACKAGED ROOFTOP AIR CONDITIONING UNITS

Explosion-Proof Electric Unit Heaters

Display hidden notes to specifier. (Don't know how? Click Here) A. Advanced Upcoiling Security Grilles, power operated.

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS

SECTION HEAT PUMPS

Installation. Centrifugal Roof and Wall Exhausters

UHIR Series. Horizontal or Vertical Mounting Industrial / Commercial Electric Unit Heater. Owner s Manual

DRYER VENTING SPECIFICATIONS DRYER SAFETY

Mechanical Rooftop Custom Capabilities

Johnson Air-Rotation Systems

SECTION HVAC AIR DISTRIBUTION

OPERATING MANUAL CONTRACTOR STYLE AXIAL FANS

Tube Axial Roof Upblast Model TAUB with Fabricated Steel Propeller

CEILING CASSETTE FAN COIL UNIT

FIRE ALARM SYSTEM. A. Shop drawings shall be submitted as follows: 1. Manufacturer's published literature. for aspproval.

Model 362A AURORA. 340A/360A Series SINGLE STAGE END SUCTION PUMPS.

Horizontal Jet Pumps 1/3-1-1/2 HP

LOADING DOCK EQUIPMENT. A. Section Concrete Forms and Accessories: Placement of anchors into concrete.

SECTION MediaStation Model 125 Electric Lateral Files (ELF)

DESIGN CLARIFICATION (DC)

Element D Services Heating, Ventilating, and Air Conditioning

Direct Gas Fired [Make-Up Air / Displacement Ventilation / Space Heating] System

product application guide

Cooling Capacity CFM in. w.c. (125 Pa)

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

SEWER CHEWER Wastewater / Sludge Grinder Submersible Gearmotor

CITYPLEX TOWERS BOILER INSTALLATION ORU RFP-1138

Evaluate, Clean, and Tune Guidance

SECTION AIR CONDITIONING UNIT

AABC Specifications for Testing and Balancing HVAC Systems

MODEL INSTALLATION INSTRUCTIONS

P.A.L. S SPECIFICATIONS

EDD-401. Stationary Louver Dual Drainable Blade. Application and Design. Standard Construction

Industrial Generator Set Accessories

A. Section includes air conditioning units, controls and control panels.

SECTION GENERAL PROVISIONS FOR HVAC WORK

We will discuss common industrial applications with guides for the proper use of electric motors on these.

VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6

300 Series PA Pump and Cooler Assemblies

A. Air-Conditioning and Refrigeration Institute: 1. ARI Commercial and Industrial Air Filter Equipment.

RPV - RP - RA air handling units

PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS

SECTION PIPE HANGERS AND SUPPORTS

security products metric sizes Redefine your comfort zone.

SERIES ASM NEOPRENE/EPMD FLANGED SINGLE SPHERE CONNECTOR CONNECTORS. Pressures to 225 PSIG (15.51 barg) Temperatures to 230ºF (110ºC)

A D D E N D U M # 3 QUESTIONS FROM BIDDERS: DATE: November 5, All Bidders. Jenne dos Santos, CBI Consulting Inc. City of Chelsea, MA

Miami-Dade Qualified Drainable Blade Louvered Penthouse

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

M7RL Series TECHNICAL SPECIFICATIONS. FEATURES and BENEFITS. High Efficiency / Direct Vent Condensing Downflow Gas Furnace

FIRE DAMPER APPLICATION GUIDE

Owners & Installation Manual for the Sheridan, Mountainair, Pine Valley and Old Forge Ceiling Fan Family

All work shall comply with applicable codes and ordinances. Work shall comply with the BOCA National Plumbing Code, latest edition.

CLEAR-DIVISIONS CENTERFOLD

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

Life Safety Dampers Selection and Application Manual. Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements

G26 Corp L11 Revised LENNOXOEMPARTS.COM. Service Literature G26 SERIES UNITS

Low Profile Unit Cooler

Pump Specifications 2448LSG, 2448LSGX Series Omnivore 2HP Simplex Grinder Packages

Arapahoe County Residential Water Heater Installation and Inspection Guide

SP H/M/L AFLR /1464/ /1469/ /22/ AFLR /8 1468/1209/ /6050/ /31/28 115

NAVIEN AMERICA INC FITCH AVENUE

INSTALLATION and OPERATION RANGE BALL CONVEYOR MODEL NO: BC-001AN

POWERS Controls No. 4 Pneumatic Damper Actuator

QT Residential Blower Metal Residential Blower

2010 Residential Water Heater Replacement Check List

Installation Manual CLIFC Fan & Coil Variable Speed

ELECTRICAL CONTRACTORS THE UNIVERSITY OF TENNESSEE KNOXVILLE, TENNESSEE SECTION PAGE 1

Industrial Generator Set Accessories

FAIRBANKS NIJHUIS FIRE PUMPS.

ASX7-4-IOM-7 J

MODEL HSR-007 Direct Drive Rolling Steel

Motor Accessories. C-Face Kits for Field Conversion NEMA AC Motors

SECTION HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

Transcription:

SECTION 23 34 00 HVAC FANS PART 1 GENERAL 1.1 SUMMARY A. Work Included: 1. Roof Exhaust Fans 2. Cabinet Fans 3. Ceiling Exhaust Fans 4. In-Line Centrifugal Fans 5. Destratification Fans for thermal equalization of buildings. 1.2 RELATED SECTIONS A. Contents of Division 23, HVAC and Division 01, General Requirements apply to this Section. 1.3 REFERENCES AND STANDARDS A. References and Standards per Section 23 00 00, HVAC Basic Requirements and Division 01, General Requirements. 1.4 SUBMITTALS A. Submittals as required by Section 23 00 00, HVAC Basic Requirements and Division 01, General Requirements. B. In addition, provide: 1. Certified fan performance curves with system operating conditions indicated. 2. Certified fan sound-power ratings. 3. Motor ratings and electrical characteristics, plus motor and electrical accessories. 4. Material gauges and finishes, including color charts. 5. Dampers, including housings, linkages, and operators. 1.5 QUALITY ASSURANCE A. Quality assurance as required by Section 23 00 00, HVAC Basic Requirements and Division 01, General Requirements. B. In addition, meet the following: 1. Motors: Premium efficiency per Section 23 05 13, Common Motor Requirements for HVAC Equipment. Electrically Commutated Motors (ECM) where scheduled on drawings. 2. Sound power levels as scheduled on Drawings. If not scheduled, within 5 percent of Basis of Design at design flow. 3. Project Altitude: Base air ratings on sea-level conditions for project sites below 2,000 feet in elevation. Base air ratings on actual site elevations for project sites above 2,000 feet in elevation. 4. Operating Limits: Classify according to AMCA 99. 5. Electrical Components, Devices, and Accessories: Listed and labeled as defined in NFPA 70, Article 100, by a testing agency acceptable to authorities having jurisdiction, and marked for intended use. 6. AMCA Compliance: Products are to comply with performance requirements and are to be licensed to use the AMCA-Certified Ratings Seal. 7. NEMA Compliance: Motors and electrical accessories are to comply with NEMA standards. HVAC FANS 23 34 00-1

1.6 WARRANTY A. Warranty of materials and workmanship as required by Section 23 00 00, HVAC Basic Requirements and Division 01, General Requirements. 1.7 DELIVERY, STORAGE, AND HANDLING A. Deliver fans as factory-assembled unit, to the extent allowable by shipping limitations, with protective crating and covering. B. Disassemble and reassemble units, as required for moving to final location, according to manufacturer's written instructions. C. Lift and support units with manufacturer's designated lifting or supporting points. 1.8 COORDINATION A. Coordinate size and location of structural-steel support members. B. Coordinate size and location of concrete bases. Cast anchor-bolt inserts into bases. C. Coordinate installation of roof curbs, equipment supports, and roof penetrations. 1.9 EXTRA MATERIALS A. Furnish extra materials described below that match products installed and that are packaged with protective covering for storage and identified with labels describing contents. Belts: One set for each belt-driven unit. PART 2 PRODUCTS 2.1 ROOF EXHAUST FANS 1. Greenheck 2. Cook 3. Carnes 4. PennBarry 5. Twin City 6. Or approved equivalent. B. Description: Belt-driven or direct-driven centrifugal fans consisting of housing, wheel, fan shaft, bearings, motor and disconnect switch, drive assembly, curb base, and accessories. C. Wheel: 1. Single width, single inlet, backward inclined/airfoil blades 2. Aluminum hub and wheel with steel inlet bell. 3. Statically and dynamically balanced with its own bearings. D. Housing to match scheduled Basis of Design: 1. One piece heavy gauge spun aluminum dome, hinged for service. 2. Low silhouette type with arched heavy gauge galvanized hood 3. Louvered type with heavy gauge extruded aluminum louvers 4. Upblast discharge, heavy gauge spun aluminum, UL 762 for kitchen grease exhaust. Provide rain and snow drains. E. Bearings and Drives: 1. Bearings: Heavy duty pillow block type, self greasing ball bearings with ABMA 9 L-10 life at 100,000 hours. 2. Shafts: Hot rolled steel, ground and polished, with keyway, protectively coated with lubricating oil. F. Pulleys: Cast-iron, adjustable-pitch motor pulley. G. Fan and motor isolated from exhaust airstream. HVAC FANS 23 34 00-2

H. Curb: Prefabricated insulated roof curb, galvanized steel, mitered ad welded corners; 1-1/2-inch thick, rigid, fiberglass insulation adhered to inside walls; and 1-1/2-inch wood nailer, hinged with curb seal. Provide curb for flat, pitched or ridged roof as indicated. 1. Security grates in curb, 1/2-inch powder coated steel bars, 6 by 6-inch grid. Provide where scheduled. 2. Kitchen grease exhaust meeting NFPA-96 requirements with vented slots. Greenheck VPFV or equal. 3. Sound curb: Curb with sound-absorbing insulation matrix. Provide where scheduled. I. Motor: Integrally mounted, 1800 RPM maximum, with pre-lubricated sealed ball bearings. ODP for motors located indoors and TEFC for motors exposed to moisture. J. Accessories: 1. Inlet/Outlet Screens: Galvanized steel welded grid, removable. 2. Backdraft Damper: Parallel blade heavy duty steel or aluminum, where scheduled, damper assembly with blades constructed of two plates formed around and welded to shaft, channel frame, sealed ball bearings, with blades linked out of air stream to single control lever. Motorized where indicated and gravity actuated with counterweight, where motorized is not indicated. 3. AMCA 99 Type B spark proof construction where scheduled. 4. Protective coating on fan wheel and interior of fan housing where scheduled. Apply coating before balancing fans and repair any breaks in coating which occur during balancing. One 6 mil coat of white plastic #7122 and one 6 mil coat of black plastic #7122. 5. Variable-Speed Controller: Where scheduled on drawings, provide solid-state control to reduce speed from 100 percent to less than 50 percent. 6. Disconnect Switch: Where not shown on Division 26, Electrical Drawings, provide nonfusible type, with thermal-overload protection mounted inside fan housing factory wired through an internal aluminum conduit. 7. Vibration Isolation: Wheel and motor mounted on integral double deflection neoprene isolators. 2.2 CABINET FANS 1. Cook 2. Greenheck 3. Carnes 4. PennBarry 5. Twin City 6. Or approved equivalent. B. Description: Belt-driven or direct-driven centrifugal fans consisting of housing, wheel, fan shaft, bearings, motor and disconnect switch, drive assembly, and accessories. C. Wheel: 1. Double width, double inlet, forward curved blades. 2. Spun inlet cones. 3. Statically and dynamically balanced within its own bearings. D. Housing: Acoustically insulated steel casing, factory standard finish, bottom and side access, ducted inlet and outlet, backdraft damper. E. Bearings and Drives 1. Bearings: Heavy duty pillow block type, self greasing ball bearings with ABMA 9 life at 50,000 hours. 2. Shafts: Hot rolled steel, ground and polished, with keyway, protectively coated with lubricating oil. 3. Drive: Cast iron or steel sheaves, dynamically balanced, keyed. Variable and adjustable pitch sheaves obtained with sheaves set at mid-position. 4. Drive: Direct drive matched to fan loads with speed controller. F. Belts: Oil resistant, nonsparking, and nonstatic; matched sets for multiple belt drives. HVAC FANS 23 34 00-3

G. Motor: Integrally mounted, 1800 RPM maximum, with pre-lubricated sealed ball bearings. ODP for motors located indoors and TEFC for motors exposed to moisture. Provide ECM motor. H. Accessories: 1. Discharge Dampers: Parallel or Opposed blade heavy duty steel or aluminum, where scheduled damper assembly with blades constructed of two plates formed around and welded to shaft, channel frame, sealed ball bearings, with blades linked out of air stream to single control lever. Motorized where indicated and gravity actuated with counterweight, where motorized is not indicated. 2. AMCA 99 Type B spark proof construction where scheduled. 3. Protective coating on fan wheel and interior of fan housing where scheduled. Apply coating before balancing fans and repair any breaks in coating which occur during balancing. One 6 mil coat of white plastic #7122 and one 6 mil coat of black plastic #7122. 4. Variable Speed Controller: Where scheduled on drawings, provide solid-state control to reduce speed from 100 percent to less than 50 percent. 5. Variable Speed Controller: Provide ECM motor. 6. Disconnect Switch: Where not shown on Division 26, Electrical Drawings, provide nonfusible type, with thermal-overload protection mounted inside fan housing factory wired through an internal aluminum conduit. 2.3 CEILING EXHAUST FANS 1. Cook 2. Greenheck 3. Carnes 4. Broan 5. PennBarry 6. Twin City 7. Or approved equivalent. B. Description: Centrifugal fan, direct drive, cabinet and exhaust grille. AMCA rated. Sound level as scheduled. Fan shrouds, motor, and fan wheel are to be removable for service. C. Wheel: Double width, double inlet, forward curved blades: D. Housing: Acoustically insulated steel casing, factory standard finish, bottom access through grille, ducted outlet, egg crate inlet grille. Provide stainless steel grille where scheduled. E. Drives: Direct drive. F. Back draft damper. G. Accessories: 1. Disconnect plug. 2. Flat roof cap. 3. Hooded wall cap. 4. Pitched roof cap. 5. Elbow discharge with grille. 6. Louvered wall discharge with bird screen. H. Motor: Integrally mounted with pre-lubricated sealed ball bearings. 1. Variable-Speed Controller: Where scheduled on drawings, provide solid-state control to reduce speed from 100 percent to less than 50 percent. 2. Disconnect Switch: Where not shown on Division 26, Electrical Drawings, provide nonfusible type, with thermal-overload protection mounted inside fan housing factory wired through an internal aluminum conduit. 3. Manual Starter Switch: Single-pole rocker switch assembly with cover and pilot light. 4. Time-Delay Switch: Assembly with single-pole rocker switch, timer, and cover plate. 5. Motion Sensor: Motion detector with adjustable shutoff timer. I. Filter: Washable aluminum to fit between fan and grille. HVAC FANS 23 34 00-4

J. Isolation: Rubber-in-shear vibration isolators. K. Motor: Integrally mounted with pre-lubricated sealed ball bearings. 2.4 IN-LINE CENTRIFUGAL FANS 1. Greenheck 2. Cook 3. Carnes 4. PennBarry 5. Twin City 6. Or approved equivalent. B. Description: In-line, belt-driven, centrifugal fans consisting of housing, wheel, outlet guide vanes, fan shaft, bearings, motor and disconnect switch, drive assembly, mounting brackets, and accessories. C. Wheel: Cast aluminum backward inclined with inlet cone statically and dynamically balanced within its own bearings. D. Housing: 1. Heavy gauge steel or aluminum flat roof cap, hooded wall cap, pitched roof cap, elbow discharge with grille, and louvered wall discharge housing, factory standard finish. 2. Removable panels for access to all interior components. 3. Horizontal or vertical configuration, as indicated. 4. Inlet and discharge duct collars. 5. 1-inch thick, 1.5 pounds per cubic foot density fiberglass liner. 6. Aluminum straightening vanes. 7. Support bracket adaptable to floor, sidewall, or ceiling mounting. E. Bearings and Drives: 1. Bearings: Heavy duty pillow block type, self greasing ball bearings with ABMA 9 life at 50,000 hours. 2. Shafts: Hot rolled steel, ground and polished, with keyway, protectively coated with lubricating oil. 3. Drive: Cast iron or steel sheaves, dynamically balanced, keyed. Variable and adjustable pitch sheaves for motors 5 hp and under, selected so required rpm is obtained with sheaves set at mid-position. Fixed sheave for 7.5 hp and over, matched belts, and drive rated as recommended by manufacturer or minimum 1.5 times nameplate rating of motor. Motor mounted on adjustable base, with adjustable sheaves, enclosure around belts within fan housing, and lubricating tubes from fan bearings extended to outside of fan housing. 4. Drive: Direct drive matched to fan loads with speed controller. Motor encased in housing outside of airstream, factory wired to disconnect switch located on outside of fan housing. F. Accessories: 1. Belt guard. 2. Motor cover for outdoor applications. 3. Inlet and outlet guard. 4. AMCA 99 Type B spark proof construction where scheduled. 5. Variable-Speed Controller: Where scheduled on drawings, provide solid-state control to reduce speed from 100 percent to less than 50 percent. 6. Discharge Dampers: Parallel blade heavy duty steel or aluminum, where scheduled, damper assembly with blades constructed of two plates formed around and welded to shaft, channel frame, sealed ball bearings, with blades linked out of air stream to single control lever. Motorized where indicated and gravity actuated with counterweight, where motorized is not indicated. G. Inlet/Outlet Screens: Galvanized steel welded grid, removable. H. Vibration Isolation: Wheel and motor mounted on integral double deflection neoprene isolators. I. Vibration isolation as scheduled and specified. Reference Section 23 05 48 Vibration and Seismic Controls for HVAC Piping and Equipment. HVAC FANS 23 34 00-5

1. Motor: Integrally mounted, 1800 RPM maximum, with pre-lubricated sealed ball bearings. ODP for motors located indoors and TEFC for motors exposed to moisture. 2.5 DESTRATIFICATION FANS 1. Airius, LLC B. Destratification Fan, General: Axial fan capable of producing columnar laminar flow of air. 1. Performance: Must be able to deliver a minimum 110 fpm at center of column at grade level. 2. Housing: a. Intake: Grill guard. b. Motor Mounting: Enclosed in housing, above stator. c. Stator: Patented multiple-vane fixed blade assembly, coordinated with fan design for optimal air flow. d. Material: PC/ABS 5VA resin, rated 5VA for flame resistance. e. Color: Off White. f. Seismic restraint point, integrated in housing. 3. Power Cord: 6 foot, 300-volt AC, UL rated. 4. Mounting: Free hanging. 5. Certification: UL Standard 507 for Safety Electric Fans, as certified by nationally recognized testing laboratory. a. Acceptable Testing: ETL, CSA, UL. 6. Identification: Permanently affixed manufacturer's nameplate including the following: a. Model Number. b. Serial Number. c. Motor Power Specifications. d. County of Manufacture. e. Safety Marks: ETL (US & CA). C. Circulation/Destratification Fan (CF-1): Air Pear Thermal Equalizer Model 45. 1. Size: 24 inch height to bail. 18 inch height to rim. 15 inch diameter. 2. Weight: 14 lb (6.4 kg). 3. Decibels: Less than 79 db, at peak fan output. 4. Characteristics: a. Electrical Requirements: 1) 100-130V AC, single phase, 50/60 Hz.; 0-2.2 Amps; 0-170 watts b. Air Speed: 1290 cfm at full power c. Fan Speed: 3050 rpm at full power d. Mounting Height: Up to 45 feet (up to 13.7 m) from finished floor to top of intake. e. Area Coverage: Up to 1500 sq. ft (140 sq. m); 22 feet (6.75 m) from the fan's center in all directions. D. Destratification Fan Motors: 1. Motor: a. Model: 45-EC. b. Motor: Electrically commutated variable speed, 92 percent energy efficient axial type. c. Speed Control: 0-10V DC analog input. d. Ball Bearings: Permanently lubricated, sealed. e. Fan Blades: 1) Material: Steel. 2) Fabrication: Blades welded to steel hub. f. Thermally Protected Motor Temperatures: 1) Operating Range: -13 degrees F (-25 degrees C) to +160 degrees F (+70 degrees C). 2) Shutoff: 275 degrees F (135 degrees C). 3) Reset: 255 degrees F (125 degrees C). HVAC FANS 23 34 00-6

g. Controls: 1) 0-10V DC analog control signal. Daisy chained control wires link to a DDC. PART 3 EXECUTION 3.1 EXAMINATION A. Do not begin installation until supporting structure and interior work have been properly completed. B. Installation of miscellaneous support, if required, electrical wire and wiring, conduit, fuses, and disconnect switches other than those provided by fan manufacturer are specified in other sections. C. Examine the substrate and conditions under which the fan is to be installed. Notify the Architect in writing of any conditions detrimental to the proper and timely completion of the work. Do not proceed with the work until unsatisfactory conditions have been corrected. 3.2 INSTALLATION A. Install in accordance with manufacturer's instructions. B. Install power ventilators level and plumb. C. Fans used for exhaust of moist air is to be constructed of aluminum construction and be warranted for their application in moist conditions. D. Secure roof exhaust fans to roof curbs with cadmium-plated hardware. E. Ceiling Exhaust Fans: Suspend units from structure; use steel wire or metal straps. F. Units using vibration isolation devices are scheduled on drawings. G. Support suspended units from structure threaded steel rods and vibration isolation device scheduled on drawings. H. In seismic zones, restrain support units. I. Install units with clearances for service and maintenance. J. Provide fixed sheaves required for final air balance. K. Provide safety screen where inlet or outlet is exposed. L. Pipe scroll drains to nearest floor drain. M. Provide backdraft dampers on discharge of exhaust fans and as indicated on drawings. N. Duct installation and connection requirements are specified in other Division 23, HVAC Sections. Drawings indicate general arrangement of ducts and duct accessories. Make final duct connections with flexible connectors per Section 23 33 00, Air Duct Accessories. O. Install ducts adjacent to power ventilators to allow service and maintenance. P. Ground equipment. Q. Tighten electrical connectors and terminals according to manufacturer's published torque-tightening values. If manufacturer's torque values are not indicated, use those specified in UL 486A and UL 486B. R. Install destratification fan according to manufacturer's written recommendations. 3.3 FIELD QUALITY CONTROL A. Equipment Startup Checks: 1. Verify that shipping, blocking, and bracing are removed. 2. Verify that unit is secure on mountings and supporting devices and that connections to ducts and electrical components are complete. Verify that proper thermal-overload protection is installed in motors, starters, and disconnect switches. 3. Verify that cleaning and adjusting are complete. HVAC FANS 23 34 00-7

4. Disconnect fan drive from motor, verify proper motor rotation direction, and verify fan wheel free rotation and smooth bearing operation. Reconnect fan drive system, align and adjust belts, and install belt guards. 5. Verify lubrication from bearings and other moving parts. 6. Verify that manual and automatic volume control and fire and smoke dampers in connected ductwork systems are in fully open position. 7. Disable automatic temperature-control operators. B. Starting Procedures: 1. Energize motor and adjust fan to indicated rpm. 2. Measure and record voltage and amperage. C. Operational Test: After electrical circuitry has been energized, start units to confirm proper motor rotation and unit operation. Remove malfunctioning units, replace with new units, and retest. D. Test and adjust controls and safeties. Replace damaged and malfunctioning controls and equipment. E. Shut unit down and reconnect automatic temperature-control operators. F. Replace fan and motor pulleys as required to achieve design airflow. G. Repair or replace malfunctioning units. Retest as specified above after repairs or replacements are made. 3.4 ADJUSTING A. Adjust damper linkages for proper damper operation. B. Adjust belt tension. C. Lubricate bearings. 3.5 CLEANING A. On completion of installation, internally clean fans according to manufacturer's written instructions. Remove foreign material and construction debris. Vacuum fan wheel and cabinet. B. After completing system installation, including outlet fitting and devices, inspect exposed finish. Remove burrs, dirt, and construction debris and repair damaged finishes. 3.6 PROTECTION A. Protect installed products until completion of project. B. Touch-up, repair or replace damaged products before substantial completion. 3.7 DEMONSTRATION A. Engage a factory-authorized service representative to train Owner's maintenance personnel to adjust, operate, and maintain HVAC fans. Train Owner's maintenance personnel on procedures and schedules for starting and stopping, troubleshooting, servicing, and maintaining equipment and schedules. END OF SECTION HVAC FANS 23 34 00-8