UNIVERSITY OF ROCHESTER DESIGN STANDARDS OCTOBER 18, 2013
|
|
|
- Poppy Barker
- 9 years ago
- Views:
Transcription
1 SECTION CENTRIFUGAL HVAC FANS PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. Fans shall be dynamically balanced and factory-tested and certified in accordance with applicable AMCA test codes. All Fans shall be certified AMCA Class II or higher. Units shall arrive at the Project bearing Certification Seal. B. Fans shall be furnished complete with motors, wheels, drive assemblies, bearings, vibration isolation devices, and accessories required for specified performance and proper operation. Direct driven fans are preferred however for motors/assemblies using V-belt drives shall be furnished with adjustable rails or heavy duty double pull style (two bolt pull) bases. C. Fans shall be selected at design condition operating points with the design CFM falling in the range of 60 to 75%. In all cases, the professional service provider shall evaluate system conditions and select the optimum fan type and configuration based on efficiency, system curve, and fan characteristics at all anticipated design conditions. Fan motor BHP to account for drive losses and field conditions. D. Preferred Variable Frequency Drives, the design operating point shall be at or to the right of the peak efficiency point or peak efficiency system curve. Total Efficiency (TE) of the fan selection shall equal or exceed 55 percent at the design point. E. Air handling fan preference shall be double width, double inlet with backward inclined centrifugal airfoil blades. F. Use OSHA approved belt guards that totally enclose the entire drive and permit easy removal for replacement of belts. Construct guards of expanded metal to allow for ventilation and provide tachometer openings at shaft locations. Fan capacity shall account for restrictions caused by protected housing/screening. G. Provide AMCA spark resistant construction option: A, B, or C as required by project conditions for handling flammable or explosive vapors. Drive set shall be comprised of non-static belts for use in an explosive. Bearings located out of air or gas stream, fan equipped with explosion-proof motor. H. Provide a minimum of two coats epoxy coating finish as a minimum for non corrosive applications. Manufacturers paint and paint system shall meet the minimum specifications of: ASTM D1735 water fog; ASTM B117 salt spray; ASTM D3359 adhesion; and ASTM G152 and G153 for carbon arc light apparatus for exposure of non-metallic material. I. Fans exposed to fume and other corrosive exhaust air as required by project conditions shall be constructed of materials compatible with the chemicals being transported in the air through the fan. J. Exhaust Stack Discharge shall be in a vertical up-draft direction at a minimum of 10 ft. above adjacent roof lines and located with respect to surrounding air inlets as to avoid contaminant reentry. Exit velocity shall have a minimum exit velocity of 3000 fpm and a maximum velocity of 4000 fpm. Design discharge static pressure loss should strive to maintain one (1) inch water gauge or less. K. Provide latest standard NEMA Premium Efficiency rated motor for compatibility with variable frequency drives where applicable. Select non-overloading motors at all points on the RPM operating curve. Each fan and motor combination shall be capable of delivering 110% of air quantity scheduled at static pressure. Motor furnished with fan shall not operate into motor service factor in any of these cases. Section Centrifugal HVAC Fans Page 1 of 7
2 1.02 SUBMITTALS A. Product Data: Catalog sheets; include rated capacities of each unit, dimensional data, operating weights, accessories, material finishes and installation instructions. B. Shop Drawings: Manufacturer s detailed dimensional drawings showing equipment, assemblies, dimensions, loadings, required clearances, method of field assembly, components, and location and size of each field connection. C. Quality Control Submittals: 1) Certified fan performance curves. 2) Certified fan sound power levels of Fan in each of the 8 Octive Bands as per current AMCA Bulletin # for Sound Testing of Air Moving Devices. D. Contract Closeout Submittals: 1) Operation and Maintenance Data: Deliver 2 copies covering the installed products, to the Director s Representative. 2) Equipment vibration readings confirming vibration isolation schedule specified QUALITY ASSURANCE A. Regulatory Requirements: 1) Each fan shall bear AMCA Seal indicating that fans comply with AMCA 211, Certified Ratings Program - Air Performance, and AMCA 311, Certified Sound Ratings Program for Air Moving Devices. 2) Operating Limits: Classify according to AMCA ) Sound power level ratings shall comply with AMCA Standard 301, Method for Calculating Fan Sound Ratings from Laboratory Test Data. B. Field Quality Control 1) Provide equipment and apparatus required for performing inspections and tests. 2) Field Inspections: a) Prior to initial operation, inspect the vibration isolators for conformance to drawings, specifications, and manufacturer's data and instructions. b) Check for vibration and noise transmission through connections, piping, ductwork, foundations, and walls. c) Check connector alignment before and after filling of system and during operation. d) Correct misalignment without damage to connector and in accordance with manufacturer's recommendations. 3) Rebalance, adjust, or replace equipment with noise or vibration levels in excess of those given in the equipment specifications, or equipment manufacturer's data REFERENCES A. ABMA: American Bearing Manufacturer s Association Section Centrifugal HVAC Fans Page 2 of 7
3 B. AMCA: Air Movement and Control Association. AMCA Operating Limits for Centrifugal Fans AMCA 203 AMCA Fan Application Manual Troubleshooting AMCA 204 Balance Quality and Vibration Levels for Fans AMCA 210 Laboratory Method of Testing Fans for Rating AMCA 300 Reverberant Room Method for Sound Testing of Fans C. ASHRAE: American Society of Heating, Refrigeration, and Air Conditioning Engineers, Inc. D. NFPA: National Fire Protection Association NFPA 45: Standard on Fire Protection for Laboratories Using Chemicals NFPA 70: National Electrical Code NFPA 79: Electrical Standard for Industrial Machinery NFPA 99: Health Care Facilities NFPA 90A: Standard for the Installation of Air-Conditioning and Ventilating Systems NFPA 91: Standard for Exhaust Systems for Air Conveying of Vapors, Gases, Mists, and Noncombustible Particulate Solids E. UL Compliance: Provide centrifugal fan electrical components which have been listed and labeled by UL. F. ASTM: American Society for Testing and Materials ASTM D1735 water fog ASTM B117 salt spray ASTM D3359 adhesion ASTM G152 and G153 for carbon arc light apparatus for exposure of non-metallic material DELIVERY, STORAGE, AND HANDLING A. Deliver fans as factory-assembled units to the extent allowable by shipping limitations, with protective crating and coverings. B. Disassemble and reassemble units as required for movement to the final locations in accordance with manufacturer s printed instructions. C. Lift and support units at the manufacturer s designated lifting or supporting points PROJECT CONDITIONS A. Do not operate fans until ductwork is clean, filters, if any, are in place and bearings are lubricated. B. Field Measurements: Verify dimensions and clearances by field measurements. PART 2 PRODUCTS 2.01 FANS A. Provide centrifugal fans built to AMCA Standard Class II construction (minimum) or higher. Section Centrifugal HVAC Fans Page 3 of 7
4 B. Provide factory-assembled and tested Direct Driven or Belt driven (project specific) centrifugal fans, factory fabricated, assembled, finished and tested; consisting of housing, wheel, fan shaft, bearings, motor, drive assembly, and support structures. C. Equip fan unit with unitary base HOUSINGS A. Materials and Fabrication: Formed and reinforced steel curved scroll housing panels, spun metal or die formed inlet cones to provide a streamlined flow into the wheel, and the doors or panels for access to internal parts and components. 1) Bracing: Steel angle or channel-iron member supports for mounting and supporting fan scroll, wheel, motor, and accessories. 2) Construct inlet and outlet of fan for project connection. 3) Scroll/Housing Drain Connection: One inch threaded steel pipe coupling welded to low point of fan scroll, with threaded steel plug and non-galling lubricant applied to threads. 4) Provide weather covers and weather-resistant enamel finish for fans installed outdoors WHEELS A. Fans to use airfoil blades welded to spun wheel cones unless otherwise indicated SHAFTS A. Turned, ground, and polished hot-rolled steel with keyway and drive end counter sunk for tachometer readings. Close tolerances shall be maintained where the shaft makes contact with the bearing. Ship with protective coating of lubricating oil. Statically and dynamically balanced and selected for continuous operation at maximum rated fan speed and motor horsepower. 1) Size shaft so that first critical speed is at least 25 percent over maximum operating speed. 2) Shaft heat slinger for fans handling high temperature air or gas BEARINGS A. Ball, roller, or taper roller type with double locking collars and split two-piece, cast iron housing. Select bearings in accordance with ABMA Standards for Ball and Roller Bearings and for maximum operating speed and horsepower for construction level. 1) All Bearings: Shall be Heavy Duty rated, grease lubricated, ball or roller self-aligning, pillow block type housing with grease seal. Bearings shall be selected for a minimum AMBA bearing rated life of not less than 200,000-hrs operation at maximum cataloged operating speed. Furnish bearings with pressure relief type external grease fittings. Bearings shall be factory lubricated. Both unit bearings shall have the same bore, type and manufacturer. At least one of the bearings shall be fixed. The bearing supports shall be removable for access to and removal of the fan wheel. 2) In addition to respective fan type bearing criteria, provide an auto-greaser on all applications in which bearings are inaccessible due to being platform mounted or physically located in a remote location, which would otherwise require special OSHA Section Centrifugal HVAC Fans Page 4 of 7
5 regulated access. Extended copper lube lines may be used to allow line of sight connection between bearing and auto-greaser. 3) Pillow Block type bearings to be similar to SKF Concentra ball bearing pillow block or Dodge grip tight BELT DRIVEN FANS A. Unless otherwise indicated, Original Equipment Manufacturer (OEM) Serial number matched oil resistant, non-sparking, and non-static V-belt drive set(s) shall be selected and provided. Belts shall be applied in matched sets. V-belts shall be matched multiple A, B or C belts having a rating of not less than 150 percent of the motor nameplate horsepower. (Multi-groove pulleys using 2, 3 or 4 grooves shall be provided with matching companion pulleys such that the belts are properly aligned.) B. Service Factor: 1) Design belt drive to operate at the horsepower equivalent to the highest BHP of the fan multiplied by service factor of 1.5. C. Fan Pulleys: Cast iron or cast steel with interchangeable split, tapered bushing, dynamically balanced at factory prior to assembly. D. Motor Pulleys: 1) No adjustable pitch adjustment type, only fixed pitch type. 2) Distance between fan shaft and motor shaft : a. Minimum sheave size nothing under four inches (4 ). b. Distance two and a haft times the largest sheave size. E. Belt Guards: Comply with OSHA and SMACNA requirements. 1. Include provision for adjustment of belt tension, lubrication, and use of tachometer with guard in place. F. Motor Mount: Heavy duty double pull style (two bolt pull) adjustable for belt tensioning VIBRATION LIMITS A. Each fan \ wheel shall be statically and dynamically Factory balanced to grade G6.3 per ANSI S2.19 or better. Complete fan assembly shall be factory balanced statically and dynamically in accordance with AMCA Standard 204. B. Each Complete fan assembly shall be Field balanced statically and dynamically in accordance with AMCA Standard 204 and shall be statically and dynamically Field balanced to the equivalent balance grade based on the conditions stated as follows. 1) Each Constant Volume fan assembly shall be test run at the factory at the specified fan RPM and vibration signatures shall be taken on each bearing in three planes; horizontal, vertical, and axial. The maximum allowable fan vibration shall be the lower of either that stated under this sub-paragraph entitled Balancing Fan and Drive Assemblies or 0.20 in./sec peak velocity, filter-out reading as measured at the fan RPM. This report shall be provided concurrently with the unit shipment. Section Centrifugal HVAC Fans Page 5 of 7
6 2) Fans incorporating variable frequency drives shall be balanced for inverter duty operation. The fan shall be balanced over the entire range of fan operation i.e. 30 percent to 110 percent of design operation to the more stringent of: a) Grade G2.5 per ANSI S2.19. b) Complete fan assembly shall be factory balanced statically and dynamically in accordance with AMCA Standard Filter-in measurement (all fan assemblies) shall be taken in the horizontal and vertical planes on the drive and opposite-drive sides of the fan shaft. a. Fans using variable frequency drives - Measurements shall not exceed 2.0 mils in any plane at or below 750 rpm and shall not exceed.0785 inches/sec in any plane beyond 750 rpm for inverter duty fans. 2. Filter-out measurements (all fan assemblies) shall be taken in the horizontal, vertical and axial planes on the drive and opposite-drive sides of the fan shaft. a. Fans using variable frequency drives - Measurements shall not exceed 2.8 mils in any plane at or below 750 rpm and shall not exceed.110 inches/sec in any plane beyond 750 rpm for inverter duty fans ACCESSORIES A. Provide accessories per the following requirements: 1) Access Doors: Provide access door in scroll housing, with latch-type handles, flush mounted for un-insulated housings, and raised-mounted for insulated housings. 2) Backdraft Dampers: Provide gravity-actuated dampers on fan discharge, counterweighted, with interlocking aluminum blades with felt edges in steel frame. 3) Drain Connections: Provide minimum 1 inch threaded coupling drain connection at lowest point of housing. 4) Extended Grease Lines: Extend grease lines from bearings to outside of inlet duct flange, terminate with grease fitting. 5) Heat Slingers: Provide metal disc between bearings and fan wheel, to dissipate heat from shaft. 6) Split Housings: Provide flanged, horizontally split housings as required by project conditions. 7) Weather Hoods: Provide protective weather hood with stamped vents over motor and drive compartment. 8) Screens: Provide manufacturer s standard screens on fan inlet and outlet where exposed to operating and maintenance personnel for safety. 9) Fan Guards: Specify guards on inlets and outlets not connected to ductwork, constructed of expanded metal in removable frame. Section Centrifugal HVAC Fans Page 6 of 7
7 PART 3 EXECUTION 3.01 EXAMINATION A. Examine areas and conditions for compliance with requirements for installation tolerances and other conditions affecting performance of fans. Do not proceed with installation until unsatisfactory conditions have been corrected INSTALLATION A. Fans shall be installed with the applicable NFPA standard and in accordance with manufacturer s printed installation instructions. B. Fans shall be located, arranged and installed with clearances for inspection and maintenance. 1) Provide clearance for complete wheel and shaft removal as per manufacturer s manual recommendations and structural support clearance. 2) Provide ancillary equipment. C. Floor Mounted Fans: Support fans on concrete mechanical equipment pads with vibration isolation devices. D. Provide inlet screens on fans with non-ducted fan inlets. If fan has inlet bearing, install screen on inboard side of bearing. E. Vibration Isolation Bases: 1. Coordinate size and location of bases with the Work of related contracts. F. Electrically connect Fan motor per latest National Electrical Safety Code and other applicable codes as a guide in establishing wiring. Provide motor disconnect box on site adjacent to motor FIELD QUALITY CONTROL A. Inspect exposed finish. Remove burrs, dirt, and construction debris, and repair damaged finishes including chips, scratches, and abrasions. B. Pre-start Up: 1) Remove shipping blocking, and bracing. 2) Verify lubrication for grease bearings and other moving parts. 3) Set dampers in connected ductwork in proper position. 4) Belt Driven Fans: Disconnect fan drive from motor, verify proper motor rotation direction, and verify fan wheel free rotation and smooth bearing operation. Reconnect fan drive system, align and adjust belts, and install belt guard. C. Start Up: 1) Energize motor, verify proper operation of drive system, and fan wheel. 2) Belt Driven Fans: a) Adjust fan pulley to indicate initial rpm, further adjust pulley to obtain system design conditions if required. Align fan and motor sheaves to allow belts to run true and straight. b) Replace fan and motor pulleys if required to achieve design conditions. c) Replace variable sheaves with fixed permanent sheaves after air balance. d) Measure and record motor voltage and amperage. END OF SECTION Section Centrifugal HVAC Fans Page 7 of 7
SECTION 23 34 13. A. Horsepower: Do not increase or decrease fan motor horsepower without written approval from Engineer.
PART 1 GENERAL SECTION 23 34 13 HVAC FANS 1.01 SUMMARY A. Section Includes: 1. Exhaust fans. 2. Transfer fans. B. Related Documents: 1. Drawings and general provisions of the Contract, including General
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER
INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER The instructions that follow are to assist you in completing the information required when making a fan or blower selection. If you need additional
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM
SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2
Recirculating Roof Fans Models ESRMD, ESRMDF and ERD
Recirculating Roof Fans Models ESRMD, ESRMDF and ERD Four-Way Fan Exhaust Supply Mix Recirculate BUILDING VALUE IN AIR. October 2005 Recirculating Roof Fans Exhaust/Supply/Recirculation/Mix Model ESRMD
UPBLAST & HOODED PROPELLER ROOF VENTILATORS
The Industrial Choice. Model D53 / B53 Model HD53 / HB53 UPBLAST & HOODED ELLER ROOF VENTILATORS Direct Drive & Belt Driven Model D53 / B53 Upblast Exhaust Fans Model HD53 / HB53 Hooded Supply & Exhaust
Fire Pump Plan Review March 2010
Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT
SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled
SECTION 15732 AIR CONDITIONING UNIT
SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration
SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS
SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES
COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION
MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business
ROOF TOP MOUNTED Air Handler Specification
ROOF TOP MOUNTED Air Handler Specification PART 1: GENERAL (Model RT) Mechanical Specification 1.01 WORK INCLUDED A. Provide complete air handling unit(s) suitable for outdoor installation. Contractor
Tube Axial Roof Upblast Model TAUB with Fabricated Steel Propeller
Tube Axial Roof Upblast Model TAUB with Fabricated Steel Propeller Belt Drive Low and High Pressure October 009 Features Page Header Tube Axial Roof Upblast Fans Greenheck belt drive tube axial upblast
Spray Booth Guideline
Department of Development Service 135 North D Street, Perris CA. 92570 Phone: (951) 443-1029 Fax: (951) 943-3293 PURPOSE The intent of this guideline is to provide the information necessary to ensure that
SECTION 23 81 43 HEAT PUMPS
SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:
Mechanical Installation
Page -1-1. INTRODUCTION AND PURPOSE 1.1. This specification covers the installation, testing and precommissioning of mechanical equipment. Work is to be performed in conjunction with the manufacturer s
VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6
- B 1 Product Detail Engineering Data... B2 Structural Support... B6 Engineering Specifications... B9 - B 2 Engineering Data REMARK: Do not use for construction. Refer to factory certified dimensions &
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling
Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)
SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2
Commercial Gas Furnace Upflow
Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted
DRYER VENTING SPECIFICATIONS DRYER SAFETY
DRYER VENTING SPECIFICATIONS Table of Contents DRYER SAFETY...1 INSTALLATION REQUIREMENTS...4 Venting Requirements...5 DRYER INSPECTION AND CLEANING...7 Frequency of Exhaust System Cleaning...7 Inspecting
SECTION 11 78 13 MORTUARY REFRIGERATORS
PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS
INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS Frames 143T - 449TZ 5100 North IH 35 Round Rock, Texas 78681 Phone: 800-451-8798 512-255-4141 Fax: 512-244-5512 RECEIVING 1. Check
Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association
Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-
University of Houston Master Construction Specifications Insert Project Name
SECTION 23 62 13 - AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",
Fire Pump Applications
Fire Pump Applications Installation & Maintenance Manual Universal Joint Driveshafts www.cumminsfirepower.com Table of Contents Section 1 General 1.1 Introduction 1.2 Safety Precautions 1.3 Warranty Statement
D Youville College July 31, 2008 New Academic Building Cannon Design Project No. 002935.00
SECTION 22 6119 - COMPRESSED-AIR EQUIPMENT FOR LABORATORY AND HEALTHCARE PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged, oilless scroll air compressors. 1.2 DEFINITIONS A. Actual Air: Air
Cooktop Low-Profile Ventilation Hoods
INSTALLATION GUIDE Cooktop Low-Profile Ventilation Hoods Contents Wolf Cooktop Low-Profile Ventilation Hoods........ 3 Cooktop Low-Profile Hood Specifications.......... 4 Cooktop Low-Profile Hood Installation............
TOP RUNNING SINGLE GIRDER BRIDGE CRANE
SECTION 14630 TOP RUNNING SINGLE GIRDER BRIDGE CRANE 1.01 SUMMARY PART 1- GENERAL A. The work required under this section shall include the designing, manufacturing, shipping, installing and field testing
Installation. Centrifugal Roof and Wall Exhausters
This publication contains the installation, operation and maintenance instructions for standard units of the AC- Centrifugal Roof and Wall Exhausters. ACE-D / ACE-B ACW-D / ACW-B / ACW-HP / ACW-XP ACRU-D
CEILING CASSETTE FAN COIL UNIT
CEILING CASSETTE FAN COIL UNIT Operation and Installation Manual MHCFC4W-04, 08, 12, 16 Four way ceiling cassette fan coil unit Please read this manual before using the fan coil unit. Installation and
Horizontal Jet Pumps 1/3-1-1/2 HP
Horizontal Jet s 1/3-1-1/2 FW01 0909 Supersedes 0409 The CPJ, CPH and EK models feature the famous Flint and Walling Service Plus motor, available in either NEMA J or Uni-frame flange construction. The
SECTION 15076 CEMENT-MORTAR LINED AND COATED STEEL PIPE
SECTION 15076 CEMENT-MORTAR LINED AND COATED (CML&C) STEEL PIPE PART 1 GENERAL 1.01 DESCRIPTION This section designates the requirements for steel pipe fabrication, test in shop, installation of steel
Geismar Site Reviewed: 07/05/16 Effective: 07/05/16 Supersedes: 08/04/14 Preparer: Owner: Approver: S/IH Team Leader S/IH Team Leader Manager LA Hub
BASF Corporation Title: LOCAL EXHAUST VENTILATION Individual Unit Function: Industrial Hygiene Procedure No.: IH-3 Page: 1 of 12 Geismar Site Reviewed: 07/05/16 Effective: 07/05/16 Supersedes: 08/04/14
FAIRBANKS NIJHUIS FIRE PUMPS. www.fairbanksnijhuis.com
FAIRBANKS NIJHUIS FIRE PUMPS www.fairbanksnijhuis.com FAIRBANKS NIJHUIS Long established as a leading fire pump manufacturer, Fairbanks Nijhuis offers a broad range of horizontal and vertical split case,
SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION 238221 - BLOWER COIL UNITS
ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS
SECTION 08360 SECTIONAL OVERHEAD DOORS 521 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word
DESIGN CLARIFICATION (DC)
DESIGN CLARIFICATION (DC) Owner: Victor Valley Wastewater Reclamation Authority Date: 03/03/2015 Contractor: W M Lyles Carollo Project No.: 8299A.20 Project Name: Subregional WRPs DC No.: 001 DC Title:
Element D Services Heating, Ventilating, and Air Conditioning
PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer
An SPX Process Equipment Operation. Universal II Industrial Series Rotary Positive Displacement ECP Pumps
An SPX Process Equipment Operation Universal II Industrial Series Rotary Positive Displacement ECP Pumps New levels of performance. Reduced operational and maintenance costs. For more than half a century,
Evaluate, Clean, and Tune Guidance
Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system
Table of Contents. Overview 1. Pump Disassembly 2. Control Disassembly / Reassembly 7. Pump Reassembly 13. Adjustment Procedures DR Control 19
Table of Contents Overview 1 Pump Disassembly 2 Control Disassembly / Reassembly 7 Pump Reassembly 13 Adjustment Procedures DR Control 19 Adjustment Procedures DRG Control 20 Adjustment Procedures DFR
Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling
Pump Specifications 405 Series Commercial Drain Pump (High-Temp) 2 Solids handling 405_P1 R1/27/2012 Copyright 2012 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.
Ventilation Solutions Kitchens. fantech
Ventilation Solutions Kitchens 2 Kitchens Today s kitchens have become much more than a place for cooking and food preparation. The kitchen is the heart of the home. It s the center of activity for the
IEC Three Phase AC Motors (Aluminum Frame) Installation & Operating Manual
IEC Three Phase AC Motors (Aluminum Frame) Installation & Operating Manual 7/09 MN301 Table of Contents Section 1 General Information.................................................. 1-1 Overview........................................................
BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION
Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION
SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing
Model 362A AURORA. 340A/360A Series SINGLE STAGE END SUCTION PUMPS. www.aurorapump.com
Model 62A MODEL 41A MODEL 44A AURORA 40A/60A Series SINGLE STAGE END PUMPS www.aurorapump.com SINGLE STAGE END PUMPS AURORA 40A/60A Series Single Stage End Suction Pumps Capacities to 4500 G.P.M. (1022
LAKE COUNTY ANIMAL SERVICES EXPANSION SECTION 15459
SECTION 15459 PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work
A. Section includes air conditioning units, controls and control panels.
SECTION 23 81 23 - COMPUTER-ROOM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes air conditioning units, controls and control panels. 1.2 REFERENCES A. Air-Conditioning, Heating, and
All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.
DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,
Packaged Terminal Air Conditioner Wall Sleeve Installation
Installation & Maintenance Data IM 1196 Group: PTAC Part Number: 910141799 Date: October 2013 Packaged Terminal Air Conditioner Installation x 42" PGAN with Top-Mounted Hydronic Heat Note: Installation
Model 1210C Battery Powered Pump Shown. Description
12 Volt DC Rotary Vane Pump Series 1200C Model 1210C Battery Powered Pump Shown Description of Included Models Model Number FR1205C FR1210C FR1211C FR2410C FR2411C Description Basic 12 volt DC pump with
Mechanical Rooftop Custom Capabilities
Mechanical Rooftop Custom Capabilities Mechanical Construction Capabilities Price manufactures a wide range of custom gas heat and DX cooled units to meet your new construction and retrofit needs. In addition
PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS
PRE-ASSEMBLED INSTALLATION INSTRUCTIONS FOR PACB SERIES COAL FIRED OVENS OVENS MANUFACTURED BY: EARTHSTONE OVENS-6717 SAN FERNANDO RD GLENDALE CA 91201 TELEPHONE: 800-840-4915 818-553-1134 FAX: 818-553-1133
Parts Replacement Manual For DODGE TORQUE-ARM Speed Reducers Straight Bore & Taper Bushed
Parts Replacement Manual For TORQUE-ARM Speed Reducers Straight Bore & Taper Bushed TXT815A - TXT825A SIZES: TXT915A - TXT926A TXT1015A - TXT1024A WARNING: Because of the possible danger to person(s) or
USER S, MAINTENANCE and SERVICE INFORMATION MANUAL
CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........
SINGLE PHASE MOTORS. INSTALLATION AND MAINTENANCE MANUAL March 21, 2006
SINGLE PHASE MOTORS INSTALLATION AND MAINTENANCE MANUAL March 21, 2006 Irvine, California (800) 474-0520 Indianapolis, Indiana (800) 866-7973 Hamilton, Ontario (800) 809-0330 e-mail: [email protected]
SECTION 15140 - PIPE HANGERS AND SUPPORTS
Part I - GENERAL 1.01 SECTION INCLUDES A. The work covered under this section consists of the furnishing of all necessary labor, supervision, materials, equipment, and services to completely execute the
IMPORTANT SAFETY NOTICE
IMPORTANT SAFETY NOTICE To: Our Valued Customers User safety is a major focus in the design of our products. Following the precautions outlined in this manual will minimize your risk of injury. ITT Goulds
Installation, Safety, Operation & Maintenance Instructions And Parts List
Installation, Safety, Operation & Maintenance Instructions And Parts List For Model BAF, Belt Drive Tube Axial Fan Arrangement 9 NOTE READ ENTIRE MANUAL INCLUDING SECTION IV. INITIAL UNIT STARTUP BEFORE
NFPA 2001: Standard for Clean Agent Fire Extinguishing Systems NFPA 70: National Electrical Code (NEC) NFPA 72: National Fire Alarm Code
Part 1 - GENERAL 1.1 DESCRIPTION OF WORK A. Design and installation of an engineered Kidde ECS Advanced Delivery Systems (ADS), clean agent/waterless fire suppression system employing DuPont FM-200 agent,
1300 MAXTRAK SPECIFICATION
CONE CRUSHER Crusher type: Liners: Standard concave: Lubrication: Adjustment: Control: Concave options: 1300 Automax Crusher. Manganese steel alloy mantle and concave. Medium Coarse. Pumped system having
BSM MOTOR DRIVEN CENTRIFUGAL PUMPS
PRINCIPLE OF OPERATION A hydraulically and dynamically balanced impeller with raised vane sections discharges liquid as a result of the centrifugal force developed in rotation. The head developed is entirely
AABC Specifications for Testing and Balancing HVAC Systems
AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL
CE6500 Energy Recovery Ventilator
ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge
We will discuss common industrial applications with guides for the proper use of electric motors on these.
INTRODUCTION: Baldor Electric Company has prepared this Specifiers Guide to help you cover all the bases when you are specifying electric motors. It will cover in a generic way most of the subjects which
Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE
Industrial Process Pump Safety Manual IMPORTANT SAFETY NOTICE To: Our Valued Customers User safety is a major focus in the design of our products. Following the precautions outlined in this manual will
Transformer oil cooler ALFA A02
A02 Transformer oil cooler ALFA Transformer oil cooler ALFA The transformer oil cooler ALFA is used to cool power transformers by means of forced air and oil flow. The oil in the cooler is circulated using
ASX7-4-IOM-7 J30-08579
INSTALLATION INSTRUCTIONS 4" COMBUSTION AIR INLET KIT TUBULAR GAS FIRED DIRECT SPARK PROPELLER UNIT HEATERS UNIT CONVERSION & CATEGORY III VENTING FOR SEPARATED COMBUSTION For 30,000 to 75,000 BTU/HR SUPPLEMENT
300 Series PA Pump and Cooler Assemblies
Type 300 Series PA Sizes 300 thru 370 (Page 1 of 9) 300 Series PA Pump and Cooler Assemblies Pump and Cooler Assemblies with Air/Oil Heat Exchanger When compact gear drives require assistance to dissipate
Q&A Session for Advanced Ball Screws 102: Troubleshooting for Design Engineers
Q&A Session for Advanced Ball Screws 102: Troubleshooting for Design Engineers Topic: Noise Q: Is there a way to predict/calculate noise on a ball screw? A: No, there is no way to calculate the noise of
Fans and Air Handling Units. Will Rea and Paul Pilutti February 16 th, 2011
Fans and Air Handling Units Will Rea and Paul Pilutti February 16 th, 2011 HTS Lunch and Learns Available Online Visit www.htseng.com Engineering Tools Resource Center Contents Fans Fan Curves Fan Laws
LOADING DOCK EQUIPMENT. A. Section 03100 - Concrete Forms and Accessories: Placement of anchors into concrete.
LOADING DOCK EQUIPMENT PART 1 GENERAL 1.1 SECTION INCLUDES A. Loading dock equipment of the following types: 1. Dock lifts. 2. Control stations. 1.2 RELATED SECTIONS A. Section 03100 - Concrete Forms and
CRN5-5 A-FGJ-G-E-HQQE 3x230/400 50HZ
GRUNDFOS DATA BOOKLET CRN5-5 A-FGJ-G-E-HQQE 3x23/4 5HZ Grundfos Pump 96517184 Thank you for your interest in our products Please contact us for more information, or visit our website http://www.lenntech.com/grundfos/crn5/96517184/crn-5-5-a-fgj-g-e-hqqe.html
Pipe Cutting and Beveling Clamshells
Pipe Cutting and Beveling Clamshells Who We Are One Company, Total Support, Complete Solutions For more than a century, Hydratight has provided world-class bolted joint solutions and continues to set international
SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT
SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)
SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for
Pump Skid Fabrication for Magnetic Coupling. Rick Soltis Chief Mechanic City of Bedford
Pump Skid Fabrication for Magnetic Coupling Rick Soltis Chief Mechanic City of Bedford Contents Magnetic Couplings What They Are, How They Work, Where They re Used Fabrication and Manufacturing of Pump
CLEAR-DIVISIONS CENTERFOLD
CLEAR-DIVISIONS CENTERFOLD Introduction: The following three (3) part specification offers the Standard and Optional features for the CLEAR-DIVISIONS CENTERFOLD moveable The yellow highlighted areas in
COMMISSIONING OF HVAC SYSTEMS
FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS
2010 Residential Water Heater Replacement Check List
2010 Residential Water Heater Replacement Check List The intent of this check list is to provide installers a general reference for the enforcement of code requirements in the Greater San Diego Area. This
LU6X-130 Instructions and Parts List (including LU6X Basic) Operating Instructions
LORTONE LU6X-130 Item # 061-092 LU6X Basic Item # 061-090 LU6X-130 Instructions and Parts List (including LU6X Basic) Operating Instructions Introduction The LU6X is one the most versatile pieces of equipment
Tube Type Oil Skimmer Comparison
Process Overview- Tube Type Oil Skimmers Oil flows down the face of the skimmer and into a sludge pan that is plumbed to a barrel. Model BG01 & BG34 or 6V Oil Skimmer 1.0 or 3/4 Diameter Collector Tube
CITY AND COUNTY OF DENVER POLICY DENVER FIRE DEPARTMENT SUBMITTAL OF CONVEYANCE INSTALLATION/ALTERATION PLANS
Subject: SUBMITTAL OF CONVEYANCE INSTALLATION/ALTERATION PLANS Reference: Denver Fire Code Section 105.7.29 Approved: Joseph L. Gonzales, Division Chief, Fire Prevention Division Number: 105-1 Effective
Design & Construction Standards, Revised January 2013 5.21.30-1
PART 1 GENERAL 1.01 Scope of Standard A. This standard provides general requirements of The University of Texas at Austin for fire pumps. This document is not intended to serve as a guide specification.
Chapter 3.5: Fans and Blowers
Part I: Objective type questions and answers Chapter 3.5: Fans and Blowers 1. The parameter used by ASME to define fans, blowers and compressors is a) Fan ration b) Specific ratio c) Blade ratio d) Twist
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS
TYPICAL FIRE SAFETY INSPECTION VIOLATIONS The following is a list of typical violations often found by inspectors and a generic solution. You can use this list to improve the safety of your facility, to
Autobody/Collision and Repair Technology/Technician CIP 47.0603 Task Grid
1 Secondary Task List 100 ORIENTATION 101 Identify opportunities in the auto body field. 102 Identify basic auto body construction. 103 Identify program rules and policies. 104 Identify government agencies
SECTION 02630 STORM DRAINAGE SYSTEM
SECTION 02630 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes specifications for storm drainage systems including modifications and connections to existing storm drainage systems. 1.02 REFERENCE
Johnson Air-Rotation Systems
AR Series TM Johnson Air-Rotation Systems Solution TM D Series TM FF Series TM 80/20 PR Series TM Johnson Air-Rotation systems announces a major addition to its product line, completing its line of high
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013
ARCO Electric Products Installation and Maintenance Manual Low Voltage Automatic Power Factor Correction Capacitor Systems 2013 READ CAREFULLY These instructions are intended to cover good practices in
UFGS-23 34 23 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-23 34 23.00 40 (May 2014) ------------------------------ Preparing Activity: NASA Superseding UFGS-23 34 23 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References
AC Electric Motors best practice
If you want to learn more about best practice machinery maintenance, or world class mechanical equipment maintenance and installation practices, follow the link to our Online Store and see the Training
SECTION 15936 AIR INLETS AND OUTLETS
SECTION 15936 AIR INLETS AND OUTLETS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Diffusers. 2. Registers. 3. Grilles. 4. Louvers. 5. Lowered Penthouses. 6. Gravity Roof Hoods. 7. Gravity Roof
SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK
SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK 1 GENERAL 1.1 GENERAL REQUIREMENTS A. This Section is coordinated with and complementary to the General Conditions and Supplementary General Conditions
UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS
UB1 AIR CONDITIONING UNIT INSTALLATION INSTRUCTIONS INSTALLATION INSTRUCTIONS: Carefully read these instructions before installing your new air-conditioner. AUSTRALIAN AUTOMOTIVE AIR AL00500054E 1 Table
SECTION 233000 HVAC AIR DISTRIBUTION
1320 / Talent Community Center 233000-1 HVAC AIR DISTRIBUTION SECTION 233000 HVAC AIR DISTRIBUTION PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Ductwork. 2. Ductwork accessories. 3. Fans. 4. Air
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES
NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB
Fan Selection Application
Fan Selection Application Instructions for Air Turbine Propeller s Axial Fan Selection website www.axialfanselection.com \ Air Turbine Propeller Company 22329 Perry Highway - Zelienople, PA 16037 (724)