SECTION A. Horsepower: Do not increase or decrease fan motor horsepower without written approval from Engineer.

Size: px
Start display at page:

Download "SECTION 23 34 13. A. Horsepower: Do not increase or decrease fan motor horsepower without written approval from Engineer."

Transcription

1 PART 1 GENERAL SECTION HVAC FANS 1.01 SUMMARY A. Section Includes: 1. Exhaust fans. 2. Transfer fans. B. Related Documents: 1. Drawings and general provisions of the Contract, including General Conditions and Division 1 Specification Sections, apply to the work of this Section. 2. Where contradictions occur between this Section and Division 1, the more stringent of the two shall apply. Engineer shall determine which is more stringent. 3. Motors: Comply with requirements in Division 23 Common Motor Requirements for HVAC Equipment DESIGN REQUIREMENTS A. Horsepower: Do not increase or decrease fan motor horsepower without written approval from Engineer. B. Fans for smoke control systems shall comply with UL Power Ventilators for Smoke Control Systems 1.03 QUALITY ASSURANCE A. Quality Standards: 1. ARI Provide fans with AMCA Certified Rating Seal SUBMITTALS A. Submit manufacturer's product data including: 1. Performance data: a. Fan Curves. b. Sound Data. 2. Accessories descriptions. 3. Support requirements. 4. Operating weight. 5. Drawings showing: a. Dimensions of complete assembly. b. Curb if used. c. Sizes and locations of duct connections. d. Maintenance clearances. 6. Where called for in the schedule, include the fan moment of inertia (WR 2 ) and the (WR 2 ) capability of the fan motor corrected for the fan/motor speed ratio. Loveland Library HVAC FANS

2 PART 2 PRODUCTS 2.01 IN-LINE CENTRIFUGAL EXHAUST FANS A. Approved Manufacturers: 4. Jenn Air. 5. Penn. 6. Twin City. B. Performance: As scheduled. C. Housing: 1. Minimum 18 gauge galvanized steel with integral duct collars. 2. Bolted construction. 3. Corrosion resistant fasteners. 4. Bolted access doors on three sides. 5. Pivoting motor plate and engraved nameplate. D. Wheel: 1. Centrifugal backward inclined % aluminum. 3. Machined cast aluminum hub. 4. Balanced to AMCA Standard E. Bearings: 1. Heavy duty. 2. Greasable ball-type in pillow block cast iron housing. 3. Minimum L50 life in excess of 200,000 hours at maximum operating speed. F. Belts: Oil and heat resistant, non-static type. G. Drives: 1. Machined cast iron 2. Keyed to the wheel and rotor shafts. 3. Sized for 150% of the installed motor horsepower. 4. Variable pitch where scheduled. H. Accessories: As scheduled CABINET EXHAUST/TRANSFER FAN A. Approved Manufacturers: 4. Jenn air. 5. Nutone 6. Penn. 7. Twin City. B. Performance: As scheduled. C. Cabinet: Steel with internal acoustic liner. Loveland Library HVAC FANS

3 D. Grille: Aluminum, removable. E. Wheel: Centrifugal, steel. F. Damper: Integral, backdraft flapper type. G. Accessories: As scheduled CENTRIFUGAL ROOF EXHAUST FANS A. Manufacturers: 4. Jenn Air. 5. Penn. 6. Twin City. B. Model and Performance: As scheduled. C. Features: 1. Aluminum housing. 2. Ball bearings. 3. Factory-fabricated roof curb. D. Accessories: 1. Bird screen. 2. Disconnect switch. 3. Backdraft damper: 0.2 inches W.C. max. pd. 4. Motorized type backdraft damper where indicated. PART 3 EXECUTION 3.01 INSTALLATION A. Install units with clearances for service and maintenance. B. Label fans according to requirements specified in Division 23 Section Identification for HVAC Piping and Equipment LUBRICATION A. Insure that fans are properly lubricated NOISE AND VIBRATION A. Insure that fans are properly supported on vibration isolators. B. Insure that flexible duct connections are properly made. C. Check fan for improper balance. Re-balance if necessary. D. Check for proper rotation ACCESS A. Provide for proper access to all parts of fan needing inspection or service with access Loveland Library HVAC FANS

4 doors in fan or ductwork. Loveland Library HVAC FANS

5 3.05 ADJUSTING A. Adjust belt tension. END OF SECTION Loveland Library HVAC FANS

UNIVERSITY OF ROCHESTER DESIGN STANDARDS OCTOBER 18, 2013

UNIVERSITY OF ROCHESTER DESIGN STANDARDS OCTOBER 18, 2013 SECTION 233416 - CENTRIFUGAL HVAC FANS PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. Fans shall be dynamically balanced and factory-tested and certified in accordance with applicable AMCA test codes. All

More information

Ventilation Solutions Kitchens. fantech

Ventilation Solutions Kitchens. fantech Ventilation Solutions Kitchens 2 Kitchens Today s kitchens have become much more than a place for cooking and food preparation. The kitchen is the heart of the home. It s the center of activity for the

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

Evaluate, Clean, and Tune Guidance

Evaluate, Clean, and Tune Guidance Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system

More information

ROOF TOP MOUNTED Air Handler Specification

ROOF TOP MOUNTED Air Handler Specification ROOF TOP MOUNTED Air Handler Specification PART 1: GENERAL (Model RT) Mechanical Specification 1.01 WORK INCLUDED A. Provide complete air handling unit(s) suitable for outdoor installation. Contractor

More information

UFGS-23 34 23 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS

UFGS-23 34 23 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-23 34 23.00 40 (May 2014) ------------------------------ Preparing Activity: NASA Superseding UFGS-23 34 23 (February 2011) UNIFIED FACILITIES GUIDE SPECIFICATIONS References

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

CE6500 Energy Recovery Ventilator

CE6500 Energy Recovery Ventilator ADVANCED COMMERCIAL Energy Recovery Ventilator PRODUCT SPECIFICATIONS & TECHNICAL DATA Features NOMINAL CAPACITY 5500-7000 CFM CASING Double-wall cabinet White exterior paint, -gauge galvanized steel -gauge

More information

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION

More information

UPBLAST & HOODED PROPELLER ROOF VENTILATORS

UPBLAST & HOODED PROPELLER ROOF VENTILATORS The Industrial Choice. Model D53 / B53 Model HD53 / HB53 UPBLAST & HOODED ELLER ROOF VENTILATORS Direct Drive & Belt Driven Model D53 / B53 Upblast Exhaust Fans Model HD53 / HB53 Hooded Supply & Exhaust

More information

Installation. Centrifugal Roof and Wall Exhausters

Installation. Centrifugal Roof and Wall Exhausters This publication contains the installation, operation and maintenance instructions for standard units of the AC- Centrifugal Roof and Wall Exhausters. ACE-D / ACE-B ACW-D / ACW-B / ACW-HP / ACW-XP ACRU-D

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER

INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER INSTRUCTIONS FOR HOW TO PROPERLY SELECT A FAN OR BLOWER The instructions that follow are to assist you in completing the information required when making a fan or blower selection. If you need additional

More information

Tube Axial Roof Upblast Model TAUB with Fabricated Steel Propeller

Tube Axial Roof Upblast Model TAUB with Fabricated Steel Propeller Tube Axial Roof Upblast Model TAUB with Fabricated Steel Propeller Belt Drive Low and High Pressure October 009 Features Page Header Tube Axial Roof Upblast Fans Greenheck belt drive tube axial upblast

More information

Commercial Gas Furnace Upflow

Commercial Gas Furnace Upflow Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted

More information

SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK

SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK SECTION 23 05 12 GENERAL PROVISIONS FOR HVAC WORK 1 GENERAL 1.1 GENERAL REQUIREMENTS A. This Section is coordinated with and complementary to the General Conditions and Supplementary General Conditions

More information

product application guide

product application guide Understanding Fan System Effects Fan Application FA/101-99 product application guide A technical bulletin for engineers, contractors and students in the air movement and control industry. The air moving

More information

Mechanical Rooftop Custom Capabilities

Mechanical Rooftop Custom Capabilities Mechanical Rooftop Custom Capabilities Mechanical Construction Capabilities Price manufactures a wide range of custom gas heat and DX cooled units to meet your new construction and retrofit needs. In addition

More information

Roller Chain Coupling

Roller Chain Coupling Roller Chain Coupling Features 1. Simple structure A roller chain coupling consists of one duplex roller chain and two sprockets for a simplex chain. Handling is very simple as both the shafts (driving

More information

SECTION 15732 AIR CONDITIONING UNIT

SECTION 15732 AIR CONDITIONING UNIT SECTION 15732 AIR CONDITIONING UNIT PART 1 GENERAL 1.01 SUMMARY A. Section includes: 1. Packaged, split system air conditioning unit No. 1. 1.02 REFERENCES A. Air-Conditioning, Heating, and Refrigeration

More information

Recirculating Roof Fans Models ESRMD, ESRMDF and ERD

Recirculating Roof Fans Models ESRMD, ESRMDF and ERD Recirculating Roof Fans Models ESRMD, ESRMDF and ERD Four-Way Fan Exhaust Supply Mix Recirculate BUILDING VALUE IN AIR. October 2005 Recirculating Roof Fans Exhaust/Supply/Recirculation/Mix Model ESRMD

More information

SECTION 233000 HVAC AIR DISTRIBUTION

SECTION 233000 HVAC AIR DISTRIBUTION 1320 / Talent Community Center 233000-1 HVAC AIR DISTRIBUTION SECTION 233000 HVAC AIR DISTRIBUTION PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Ductwork. 2. Ductwork accessories. 3. Fans. 4. Air

More information

FAIRBANKS NIJHUIS FIRE PUMPS. www.fairbanksnijhuis.com

FAIRBANKS NIJHUIS FIRE PUMPS. www.fairbanksnijhuis.com FAIRBANKS NIJHUIS FIRE PUMPS www.fairbanksnijhuis.com FAIRBANKS NIJHUIS Long established as a leading fire pump manufacturer, Fairbanks Nijhuis offers a broad range of horizontal and vertical split case,

More information

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling

Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling Pump Specifications 250 Series Submersible Sump / Effluent Pump 2 Solids handling 250_P1 R10/7/2015 Copyright 2015 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice.

More information

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR LAUNDRY EQUIPMENT MAINTENANCE Maintenance Module 32 March 2011 issue This document has been compiled by the Engineering

More information

A. Section includes air conditioning units, controls and control panels.

A. Section includes air conditioning units, controls and control panels. SECTION 23 81 23 - COMPUTER-ROOM AIR-CONDITIONERS PART 1 - GENERAL 1.1 SUMMARY A. Section includes air conditioning units, controls and control panels. 1.2 REFERENCES A. Air-Conditioning, Heating, and

More information

POWERS Controls No. 4 Pneumatic Damper Actuator

POWERS Controls No. 4 Pneumatic Damper Actuator POWERS Controls No. 4 Pneumatic Damper Actuator Technical Instructions Document No. 155-032P25 AP 331-2 Actuator Assembly 331-2929 Typical Actuator Assembly 331-2904 Typical Actuator Assembly 331-3000

More information

Testing Capabilities. Worldwide Designers & Manufacturers of Air Moving Equipment

Testing Capabilities. Worldwide Designers & Manufacturers of Air Moving Equipment Testing Capabilities Twin Twin City City Fan Fan Companies, Companies, Ltd. Ltd. Worldwide Designers & Manufacturers of Air Moving Equipment TestingCapabilities Twin City Fan Companies, Ltd. In today s

More information

AC Electric Motors best practice

AC Electric Motors best practice If you want to learn more about best practice machinery maintenance, or world class mechanical equipment maintenance and installation practices, follow the link to our Online Store and see the Training

More information

MEMBRANE VACUUM MINI PUMPS

MEMBRANE VACUUM MINI PUMPS MEMBRANE VACUUM MINI PUMPS The mini pumps described in this page are membrane-type. They can be used both as vacuum pumps and compressors. In the latter version they can supply compressed air 100% oil-free

More information

D Youville College July 31, 2008 New Academic Building Cannon Design Project No. 002935.00

D Youville College July 31, 2008 New Academic Building Cannon Design Project No. 002935.00 SECTION 22 6119 - COMPRESSED-AIR EQUIPMENT FOR LABORATORY AND HEALTHCARE PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged, oilless scroll air compressors. 1.2 DEFINITIONS A. Actual Air: Air

More information

Air technology solutions for demanding applications. Product overview. www.elektror.com17

Air technology solutions for demanding applications. Product overview. www.elektror.com17 Air technology solutions for demanding applications Product overview www.elektror.com17 Set benchmarks now. Efficient and high-performance solutions from one source. For the past 9 years Elektror airsystems

More information

Element D Services Heating, Ventilating, and Air Conditioning

Element D Services Heating, Ventilating, and Air Conditioning PART 1 - GENERAL 1.01 OVERVIEW A. This section supplements Design Guideline Element D3041 on air handling distribution with specific criteria for projects involving design of a Data Center spaces B. Refer

More information

Tube Type Oil Skimmer Comparison

Tube Type Oil Skimmer Comparison Process Overview- Tube Type Oil Skimmers Oil flows down the face of the skimmer and into a sludge pan that is plumbed to a barrel. Model BG01 & BG34 or 6V Oil Skimmer 1.0 or 3/4 Diameter Collector Tube

More information

ICQ Series - square centrifugal

ICQ Series - square centrifugal product ICQ Square Centrifugal (TEFC) dimensions mm 280-710 poles & duty 4-8 / up to 4,500 L/s application High performance centrifugal fans for medium to high pressure ducted systems. ICQ Series The ICQ

More information

COMMISSIONING OF HVAC SYSTEMS

COMMISSIONING OF HVAC SYSTEMS FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS

More information

Life Safety Dampers Selection and Application Manual. Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers

Life Safety Dampers Selection and Application Manual. Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers Life Safety Dampers Selection and Application Manual Ceiling Radiation Dampers Fire Dampers Combination Fire Smoke Dampers Smoke Dampers May 2014 1 2 Table of Contents HOW TO USE THIS MANUAL DAMPER APPLICATION

More information

AABC Specifications for Testing and Balancing HVAC Systems

AABC Specifications for Testing and Balancing HVAC Systems AABC Specifications for Testing and Balancing HVAC Systems The Associated Air Balance Council (AABC) Total System Balancing Specifications for HVAC Testing, Balancing and Performance Verification TOTAL

More information

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES

COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES COMMERCIAL COOKING HOODS, VENTILATION & FIRE SUPPRESSION SYSTEM GUIDELINES AND PROCEDURES These guidelines are to be used for ALL commercial cooking hoods, ventilation systems and related fire suppression

More information

Fire Pump Plan Review March 2010

Fire Pump Plan Review March 2010 Fire Pump Plan Review March 2010 Date of Review: / / Permit Number: Business/Building Name: Address of Project: Designer Name: Designer s Phone: Contractor: Contractor s Phone: Occupancy Classification:

More information

University of Houston Master Construction Specifications Insert Project Name

University of Houston Master Construction Specifications Insert Project Name SECTION 23 62 13 - AIR-COOLED SPLIT SYSTEM AIR CONDITIONING UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: A. The Conditions of the Contract and applicable requirements of Division 1, "General Requirements",

More information

Owner s Manual EFX. Explosion-Proof Exhaust Fan. This manual covers installations, maintenance, repair and replacement parts. WARNING!

Owner s Manual EFX. Explosion-Proof Exhaust Fan. This manual covers installations, maintenance, repair and replacement parts. WARNING! Heaters for the Harshest Environments Owner s Manual ISO 9001 EFX Explosion-Proof Exhaust Fan This manual covers installations, maintenance, repair and replacement parts. WARNING! READ ALL IMPORTANT NOTICES

More information

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS

INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS INSTALLATION AND MAINTENANCE INSTRUCTIONS FOR THREE PHASE INDUCTION MOTORS Frames 143T - 449TZ 5100 North IH 35 Round Rock, Texas 78681 Phone: 800-451-8798 512-255-4141 Fax: 512-244-5512 RECEIVING 1. Check

More information

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here)

SECTION 08332 COILING COUNTER DOORS. Display hidden notes to specifier. (Don't know how? Click Here) SECTION 08332 COILING COUNTER DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Coiling Metal Counter Doors. B. Coiling Counter Fire Doors. 1.2

More information

We will discuss common industrial applications with guides for the proper use of electric motors on these.

We will discuss common industrial applications with guides for the proper use of electric motors on these. INTRODUCTION: Baldor Electric Company has prepared this Specifiers Guide to help you cover all the bases when you are specifying electric motors. It will cover in a generic way most of the subjects which

More information

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations. DIVISION 16 ELECTRICAL SECTION 16100 - ELECTRICAL PART 1 - GENERAL SCOPE All electrical work as shown on the drawings and as necessary to provide a complete electrical system. Include primary service,

More information

DESIGN CLARIFICATION (DC)

DESIGN CLARIFICATION (DC) DESIGN CLARIFICATION (DC) Owner: Victor Valley Wastewater Reclamation Authority Date: 03/03/2015 Contractor: W M Lyles Carollo Project No.: 8299A.20 Project Name: Subregional WRPs DC No.: 001 DC Title:

More information

MAC-120HE-01 Air-Cooled Chiller

MAC-120HE-01 Air-Cooled Chiller MAC-120HE-01 Air-Cooled Chiller 10 Ton / 120,000 BTUH Air-Cooled Chiller 208/230-1-50/60 1 HVAC Guide Specifications Air-Cooled Liquid Chiller Nominal Size: 10 Tons Multiaqua Model Number: MAC-120HE-01

More information

Roof Curbs, Extensions and Equipment Supports

Roof Curbs, Extensions and Equipment Supports Roof s, Extensions and Equipment Supports December 2012 Roof Page s, Header Extensions and Equipment Supports Table of Contents Model GPI Standard and Optional Construction Features... 3 Model Number Code....

More information

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES

NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES NEBB STANDARDS SECTION-8 AIR SYSTEM TAB PROCEDURES 8.1 INTRODUCTION Testing, adjusting, and balancing of HVAC systems can best be accomplished by following a series of systematic procedures. The NEBB TAB

More information

26 3213.13 Diesel Engine Driven Generators Page 1 of 6

26 3213.13 Diesel Engine Driven Generators Page 1 of 6 Last Update: December 8, 2014 A. Description of System Consultant s Handbook Page 1 of 6 1. Provide a diesel engine driven electric generating unit, factory assembled, tested and certified to operate at

More information

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION 238221 - BLOWER COIL UNITS

SPECIFICATION DIVISION 23 SECTION DESCRIPTION DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING (HVAC) SECTION 238221 - BLOWER COIL UNITS ARCHITECTURE, ENGINEERING AND CONSTRUCTION P00000000 0000 DOCUMENTS ARCHITECTURE & ENGINEERING 326 East Hoover, Mail Stop B Ann Arbor, MI 48109-1002 Phone: 734-764-3414 Fax: 734-936-3334 SPECIFICATION

More information

Johnson Air-Rotation Systems

Johnson Air-Rotation Systems AR Series TM Johnson Air-Rotation Systems Solution TM D Series TM FF Series TM 80/20 PR Series TM Johnson Air-Rotation systems announces a major addition to its product line, completing its line of high

More information

RPV - RP - RA air handling units

RPV - RP - RA air handling units APPLICATIONS Heating, ventilation, cooling >> FACTORIES >> WAREHOUSES >> HALLS >> DISTRIBUTION CENTRES >> COMMERCIAL PREMISES >> PLACES OF WORSHIP RPV - RP - RA air handling units www.reznor.eu RPV - RP

More information

Mechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories

Mechanical Heating Ventilation and Air Conditioning Ductwork and Duct Accessories Basis of Design This section applies to the design and installation of ductwork, air terminal boxes, air outlets and inlets, volume dampers, pressure relief dampers, smoke/fire dampers, and smoke/fire

More information

Horizontal Jet Pumps 1/3-1-1/2 HP

Horizontal Jet Pumps 1/3-1-1/2 HP Horizontal Jet s 1/3-1-1/2 FW01 0909 Supersedes 0409 The CPJ, CPH and EK models feature the famous Flint and Walling Service Plus motor, available in either NEMA J or Uni-frame flange construction. The

More information

city of edmonds development information

city of edmonds development information #B17 city of edmonds development information Commercial Kitchen Hood & Hood Fire Suppression System Permit Submittal Requirements PERMIT REQUIRED: CODES: FEES: A Commercial Kitchen Hood Mechanical Permit

More information

CHILLED WATER DATA ROOM UNITS

CHILLED WATER DATA ROOM UNITS Critical Infrastructure for the World s Leading Data Centers CHILLED WATER DATA ROOM UNITS Downflow Net Sensible Cooling 79 220kW Upflow Net Sensible Cooling 66 206kW A Nortek Company DATA CENTER COOLING

More information

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION

MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION MOBILE FIRE - RESCUE DEPARTMENT FIRE CODE ADMINISTRATION Fire Pump Plan Review 2009 International Fire Code and NFPA 20 Date of Review / / BLD201 - Project Address: Project Name: Contractor s Business

More information

SINGLE PACKAGE VERTICAL AIR CONDITIONERS

SINGLE PACKAGE VERTICAL AIR CONDITIONERS SINGLE PACKAGE VERTICAL AIR CONDITIONERS AIR CONDITIONERS l HEAT PUMPS l ELECTRIC HEAT QUIETER BY DESIGN SIMPLE TO INSTALL CONCEALED INSTALLATION www.friedrich.com VERT-I-PAK ideal for extended stay properties,

More information

Operation and Installation Manual. Max Series

Operation and Installation Manual. Max Series Operation and Installation Manual Max Series Models 95MAX 155MAX 155ECM 155MAXRX 200MAX 200MAXRX MAXTOP 195DCS 300DCS 200ERV 200ERVD New Auto Dehumidistat Function prevents unwanted use of the dehumidistat

More information

A. Air-Conditioning and Refrigeration Institute: 1. ARI 850 - Commercial and Industrial Air Filter Equipment.

A. Air-Conditioning and Refrigeration Institute: 1. ARI 850 - Commercial and Industrial Air Filter Equipment. SECTION 23 40 00 - HVAC AIR CLEANING DEVICES PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Activated carbon filters. 2. Extended surface rigid air filter with synthetic media. 3. Disposable panel

More information

CORROSION RESISTANT FRP FANS & BLOWERS

CORROSION RESISTANT FRP FANS & BLOWERS CORPORATION CORROSION RESISTANT FRP FANS & BLOWERS Superior Quality High Efficiency Low Noise Level Competitive Pricing Fans in Stock Dedicated to detail, precision and quality control Welcome to M.K.

More information

DIVISION 23 - HVAC 23 30 00 HVAC Air Distribution

DIVISION 23 - HVAC 23 30 00 HVAC Air Distribution PART 1 - GENERAL 1.01 GENERAL CRITERIA A. General Design Criteria 1. System standards require that buildings be fully ducted (supply, exhaust and return air). 2. Provide positive exhaust ventilation for

More information

Heating, Ventilation and Air Conditioning

Heating, Ventilation and Air Conditioning Heating, Ventilation and Air Conditioning The Montgomery County Students Construction Trades Foundation, Inc has developed a comprehensive construction technology program designed to prepare students for

More information

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following:

A. Manufacturers: Subject to compliance with requirements, provide products by one of the following: SECTION 238219 - PART 1 - GENERAL 1.1 SUMMARY A. This Section includes fan-coil units and accessories. 1.2 SUBMITTALS A. Product Data: For each model indicated, provide dimensions, weights, capacities

More information

CFM @.0 SP H/M/L AFLR-12 12 3.033 1565/1464/1309 60 1836/1469/1175 24/22/20 115 AFLR-20 20 3 1/8 1468/1209/1063 60 7562/6050/4840 34/31/28 115

CFM @.0 SP H/M/L AFLR-12 12 3.033 1565/1464/1309 60 1836/1469/1175 24/22/20 115 AFLR-20 20 3 1/8 1468/1209/1063 60 7562/6050/4840 34/31/28 115 Air Circulators High Velocity Floor Fans Circulate Large Volumes of Air Product Specifications Size Spd HP HZ CFM/WATT @.0 SP AFLR-12 12 3.033 1565/1464/1309 60 1836/1469/1175 24/22/20 115 AFLR-20 20 3

More information

Pump Maintenance - Repair

Pump Maintenance - Repair Pump Maintenance - Repair Brian Trombly Mo Droppers Cummins Bridgeway, Gaylord, Mi The basic centrifugal pump consists of two main elements: 1. The rotating element which includes an impeller and a shaft.

More information

RKE. Heat recovery unit. heat recovery unit RKE. from 200 to 6800 m 3 /h. General features

RKE. Heat recovery unit. heat recovery unit RKE. from 200 to 6800 m 3 /h. General features RKE Heat recovery unit from 200 to 6800 m 3 /h General features RKE heat recovery units are suitable for residential and commercial applications and offer a real energy saving in forced ventilation plants,

More information

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for

More information

Pump Skid Fabrication for Magnetic Coupling. Rick Soltis Chief Mechanic City of Bedford

Pump Skid Fabrication for Magnetic Coupling. Rick Soltis Chief Mechanic City of Bedford Pump Skid Fabrication for Magnetic Coupling Rick Soltis Chief Mechanic City of Bedford Contents Magnetic Couplings What They Are, How They Work, Where They re Used Fabrication and Manufacturing of Pump

More information

VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6

VXT. Open Cooling Towers. Open Cooling Towers. Product Detail VXT - B 1. Engineering Data... B2. Structural Support... B6 - B 1 Product Detail Engineering Data... B2 Structural Support... B6 Engineering Specifications... B9 - B 2 Engineering Data REMARK: Do not use for construction. Refer to factory certified dimensions &

More information

Ø5/16" HOLES FOR FASTENING TO CURB

Ø5/16 HOLES FOR FASTENING TO CURB I/IG ERIE IDE INTKE UPPLY UNIT / IDE INTKE GLVNIZED UPPLY UNIT OPERTION INTRUCTION ND PRT MNUL I ERIE MODEL: I-9, I-10, I-12, I-15, I-18, I-20 IG ERIE MODEL: IG-9, IG-10, IG-12, IG-15 GENERL FETY Rotating

More information

Direct Gas-Fired Indoor and Outdoor Heating and Make-Up Air Units

Direct Gas-Fired Indoor and Outdoor Heating and Make-Up Air Units Direct Gas-Fired Indoor and Outdoor Heating and Make-Up Air Units horizontal configuration vertical configuration 7-150.3 MAY, 2015 Table of Contents Direct-fired make-up units are designed to provide

More information

SINGLE PHASE MOTORS. INSTALLATION AND MAINTENANCE MANUAL March 21, 2006

SINGLE PHASE MOTORS. INSTALLATION AND MAINTENANCE MANUAL March 21, 2006 SINGLE PHASE MOTORS INSTALLATION AND MAINTENANCE MANUAL March 21, 2006 Irvine, California (800) 474-0520 Indianapolis, Indiana (800) 866-7973 Hamilton, Ontario (800) 809-0330 e-mail: sales@sterlingelectric.com

More information

SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT

SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT SECTION 23 05 29 - HANGERS AND SUPPORTS FOR HVAC PIPING AND EQUIPMENT PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Equipment

More information

CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS

CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS CROWN BOILER COMPANY BWF SERIES BOILER CATEGORY I VENT KIT INSTALLATION AND OPERATING INSTRUCTIONS WARNING Improper installation, adjustment, alteration, service, or maintenance of this product can cause

More information

SUSPENSION DIAGNOSIS

SUSPENSION DIAGNOSIS SECTION 2A SUSPENSION DIAGNOSIS TABLE OF CONTENTS Diagnosis... 2A-2 General Diagnosis... 2A-2 Hub and Bearing... 2A-7 2A-2 SUSPENSION DIAGNOSIS DIAGNOSIS GENERAL DIAGNOSIS Problems in the steering, the

More information

ORTHOBLOC 3000. Drive systems. Installation. This manual is to be given to the end user. 3996 en - 2013.04 / k. R max - 5 mm.

ORTHOBLOC 3000. Drive systems. Installation. This manual is to be given to the end user. 3996 en - 2013.04 / k. R max - 5 mm. en - 01.0 / k 1 en This manual is to be given to the end user --> B7 (0 to 0 ) R max - mm R min + mm ORTHOBLOC 000 Installation LEROY-SOMER Ot 000 en - 01.0 / k NOTE LEROY-SOMER reserves the right to modify

More information

Rotary Phase Converters

Rotary Phase Converters FACTS from Ronk Electrical Industries, Inc. Bulletin 11981 Rotary Phase Converters ROTOVERTER Pat. No. 3,670,238 ROTO-CON Pat. No. 4,158,225 What are the ROTO-CON and ROTOVERTER power converters? The ROTO-CON

More information

HVAC Design Requirements

HVAC Design Requirements Maintenance of HVAC HVAC Design Requirements Air Flow Diagram แบบ Recirculation Air Flow Diagram แบบ Once Through Definition Of Conditions As built At rest In operation air air air Maintenance GMP Requirements

More information

Installation, Safety, Operation & Maintenance Instructions And Parts List

Installation, Safety, Operation & Maintenance Instructions And Parts List Installation, Safety, Operation & Maintenance Instructions And Parts List For Model BAF, Belt Drive Tube Axial Fan Arrangement 9 NOTE READ ENTIRE MANUAL INCLUDING SECTION IV. INITIAL UNIT STARTUP BEFORE

More information

Acoustical Design Guidelines for HVAC Systems in Schools

Acoustical Design Guidelines for HVAC Systems in Schools Acoustical Design Guidelines for HVAC Systems in Schools Seminar 9, ASHRAE Summer Meeting Albuquerque, New Mexico Sponsor: TC 2.6 Sound and Vibration Robert M. Lilkendey Associate Principal Consultant

More information

BUYERS GUIDE. IMPORTANT: Spoken promises are difficult to enforce. Ask the dealer to put all promises in writing. Keep this form.

BUYERS GUIDE. IMPORTANT: Spoken promises are difficult to enforce. Ask the dealer to put all promises in writing. Keep this form. BUYERS GUIDE IMPORTANT: Spoken promises are difficult to enforce. Ask the dealer to put all promises in writing. Keep this form. VEHICLE MAKE MODEL YEAR VIN NUMBER DEALER STOCK NUMBER (Optional) WARRANTIES

More information

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association

Air-Conditioning, Heating, and Refrigeration Institute. Sheet Metal and Air-Conditioning Contractors National Association Air-Conditioning, Heating, and Refrigeration Institute Sheet Metal and Air-Conditioning Contractors National Association GUIDELINE B-1997 ACKNOWLEDGEMENT These guidelines for Roof Mounted Outdoor Air-

More information

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Vincent Pedalino FSL Home Improvements Phoenix, AZ 1 HVAC Basics Ways to improve the performance of existing air conditioning

More information

Single Package Vertical Air Conditioners. Vert-I-Pak

Single Package Vertical Air Conditioners. Vert-I-Pak Single Package Vertical Air Conditioners Vert-I-Pak Installs easily in a closet for quiet operation and provides a more homelike appearance for your guests. THE EXPERTS IN ROOM AIR CONDITIONING A Better

More information

Défumair XR. ventilation and cmv. fire grade - label CE. smoke-extraction fan extraction casing for kitchen at F400-120. advantages.

Défumair XR. ventilation and cmv. fire grade - label CE. smoke-extraction fan extraction casing for kitchen at F400-120. advantages. Défumair XR smoke-extraction fan extraction casing for kitchen at F400-120 Personalisation : - Phonic insulation version by insulated double-skin panels through 25 mm glass wool, class M1. advantages Originally

More information

Eurovacuum EV Series. Single Stage Oil Sealed Rotary Vane Pump

Eurovacuum EV Series. Single Stage Oil Sealed Rotary Vane Pump Eurovacuum EV Series Single Stage Oil Sealed Rotary Vane Pump Eurovacuum EV Series Single Stage Oil Sealed Rotary Vane Pumps Eurovacuum Company is offering its various products to meet industrial vacuum

More information

New 27 hp 2 Cylinder Liquid-Cooled Engine

New 27 hp 2 Cylinder Liquid-Cooled Engine New 27 hp 2 Cylinder Liquid-Cooled Engine Introducing the new 27 hp Liquid-Cooled Vanguard 2/LC Engine A cooler, smoother, longer running commercial engine. That s the liquid-cooled advantage of the Vanguard

More information

systemair Smoke Extract Fans Keep Your Cool: Smoke Extraction with Systemair

systemair Smoke Extract Fans Keep Your Cool: Smoke Extraction with Systemair Fans Air Handling Units Air Distribution Products Fire Safety Air Curtains and Heating Products Tunnel Fans Smoke Extract Fans Keep Your Cool: Smoke Extraction with Systemair systemair Disclose the secret

More information

1.2 Refrigerant Equipment. General

1.2 Refrigerant Equipment. General Part 1 General 1.1 Summary.1 Unless otherwise indicated, follow the standards below when specifying heating, ventilation and air conditioning (HVAC) work. These standards are not intended to restrict or

More information

LU6X-130 Instructions and Parts List (including LU6X Basic) Operating Instructions

LU6X-130 Instructions and Parts List (including LU6X Basic) Operating Instructions LORTONE LU6X-130 Item # 061-092 LU6X Basic Item # 061-090 LU6X-130 Instructions and Parts List (including LU6X Basic) Operating Instructions Introduction The LU6X is one the most versatile pieces of equipment

More information

Attachment J-C18.1. HVAC Work Instructions

Attachment J-C18.1. HVAC Work Instructions . RFP: Attachment J-C18.1 HVAC Work Instructions NNC13ZFD017J SOW Item No. Title Page C18-02 Control Air Systems Annual PM 2 C18-03 Split System AC Indoor Section Annual PM 3 C18-04 Condensing Unit Semi-Annual

More information

300 Series PA Pump and Cooler Assemblies

300 Series PA Pump and Cooler Assemblies Type 300 Series PA Sizes 300 thru 370 (Page 1 of 9) 300 Series PA Pump and Cooler Assemblies Pump and Cooler Assemblies with Air/Oil Heat Exchanger When compact gear drives require assistance to dissipate

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com

Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Crawford Inspection Services C.C.B. # 76914 www.crawfordinspections.com Portland Area PO Box 665 West Linn, OR 97068 Ph: (503) 650-6957 Salem Area 5434 River Rd. N; #192 Keizer, OR 97303 Ph: (503) 362-5809

More information

SECTION 15936 AIR INLETS AND OUTLETS

SECTION 15936 AIR INLETS AND OUTLETS SECTION 15936 AIR INLETS AND OUTLETS PART 1 - GENERAL 1.01 SUMMARY A. Section Includes: 1. Diffusers. 2. Registers. 3. Grilles. 4. Louvers. 5. Lowered Penthouses. 6. Gravity Roof Hoods. 7. Gravity Roof

More information