Evaluate, Clean, and Tune Guidance

Size: px
Start display at page:

Download "Evaluate, Clean, and Tune Guidance"

Transcription

1 Evaluate, Clean, and Tune Guidance The Evaluate, Clean and Tune (ECT) process serves three essential purposes in the Weatherization Assistance Program (WAP). The first is to evaluate the existing system to determine its efficiency, safety, durability, and overall ability to perform as intended. The second function is the cleaning of the system to ensure that it is running as efficiently as possible, as well as to ensure durability of the components. The third is to tune the system to make it as efficient as possible for as long as possible. The listed standards have been set for those individuals performing the ECT as part of the North Carolina Weatherization Assistance Program. These standards borrow heavily from Air Conditioning Contractors of America (ACCA) Standard 4 as referenced in the North Carolina Weatherization Installation Standards. This standard is not meant to replace ACCA Standard 4, but rather to supplement and provide further guidance on what is expected in an ECT performed for the WAP program. This is meant as a technical assistance component and may aid in the establishment of a contracted service with HVAC professionals. In all cases, the NC Weatherization Installation Standards and applicable codes govern. This standard provides MINIMUM requirements for the inspection by appropriately licensed contractors of residential HVAC equipment. Relevant inspections of components are called out, along with the required corrections to be made as part of the ECT. Recommended repairs are also noted, and may be completed by the ECT contractor or another HVAC contractor, but are considered outside the scope of typical ECT measures. In all cases where cleaning of coils is recommended, an industry accepted solvent and water shall be used. Water alone shall not be used to clean coils. Air cleaning, using vacuum or compressed air, shall be done in such a way that does not spread lint and other particulates into sensitive compartments of the HVAC system. When feasible, removing components to clean them shall always be the preferred method. Identifying units as needing significant repair or replacement does not necessarily ensure that they will be replaced, due to budgetary and other programmatic restraints. It is for this reason that units, even those in a state of disrepair, are cleaned and tuned in addition to being evaluated. The obligation and objective of this program is to deliver the client the most efficient unit regardless of impending repairs or replacement. Inspect all equipment and components to ensure that they do not violate manufacturer s instructions, warranty requirements, building codes, health and safety standards, environmental regulations, and overall industry best practices. Identify the HVAC system inventory of equipment, controls, components, and accessories as outlined in the Heating Ventilation and Air Conditioning System Evaluation provided by the North Carolina Weatherization Assistance Program. No repair shall be made by the contractor performing the ECT that exceeds the contract defined scope of work without approval by the Weatherization Service Provider (WSP). All safety and maintenance concerns should be documented and presented to the WSP. Work identified as life threatening shall be corrected immediately so as to protect clients and staff regardless of contract terms. Evaluate, Clean, and Tune Guidance August 2012 Page 1 of 23

2 Air Distribution System ACCA Standard 4 Checklist 7.1 Inspection Task ECT Requirement Additional Work Clean and/or replace filters if accumulation results in airflow outside established operating limits Inspect filter for dirt / particulate accumulation on filters Inspect air filter housing integrity and air seal Inspect grilles, registers, and diffusers for dirt accumulation Inspect all accessible ductwork for areas of moisture accumulation or biological growth Inspect integrity of all accessible ductwork insulation Inspect the integrity of all accessible ductwork including duct strapping, hangers, sections, joints and seams Document observations Document observations Document observations Document observations Document observations Recommend to the WSP the relocation of filter (if difficult for client to access), installation of a filter grille, replacement of panned joist returns per NCWIS Section 8400 Recommend to WSP replace with filter grille, replace filter door or filter housing as needed Recommend to the WSP the replacing of grilles, registers as needed Notify the WSP if growth presents a Health and Safety risk to occupant Repair, replace duct insulation in accordance with NCWIS Section 8300 Repair, seal, and replace ductwork, hangers, joints, seams in accordance with NCWIS 8000 Evaluate, Clean, and Tune Guidance August 2012 Page 2 of 23

3 Controls and Safeties ACCA Standard 4 Checklist 7.1 Document observations, adjust as necessary Test modes of operation and control sequence. Test devices to ensure they are maintaining their expected range Test zoning controls modes of operation, zone control to ensure proper damper/ valve operation and test bypass dampers for proper function Test remote control thermostat in all modes of operation Initiate a test of the defrost control boards mode of operation, for those with this capability Test drain pan safety switches for Document observations, adjust as necessary Document observations, adjust as necessary Document observations, adjust as necessary Document observations Recommend to the WSP repair or replacement of components as needed Recommend to the WSP repair or replace as needed of components as needed Recommend repair or replacement in accordance with NCWIS 7900 Recommend to the WSP the repair, replacement as necessary. Recommend repairing wiring or switch, replacement if necessary Test unit safety switch Document observations Recommend repair or replacement if necessary Evaluate, Clean, and Tune Guidance August 2012 Page 3 of 23

4 Gas Furnace ACCA Standard 4 Checklist 7.3 Cabinet Inspect the required clearance for combustion around cabinet Recommend to the WSP corrections as required for combustion air, clearance to combustibles Electrical Inspect electrical disconnect box Inspect for proper equipment Tighten wiring nuts as needed grounding Measure and record line voltage Compare to Original Equipment Manufacturer (OEM) specifications or nameplate data Recommend that voltage be addressed if out of standard Inspect and test contactors and relays Inspect electrical connections Look for pitting or signs of damage Ensure wire size and type match load conditions. Tighten loose connections Replace contactors and relays demonstrating evidence of excessive contact Replace heat discolored connections and repair or replace any damaged electrical wiring Inspect all stand alone capacitors Replace those that are bulged, split, incorrectly sized, or do not meet OEM specifications Measure and record amperage draw to motor/nameplate data as available Blower Assembly Measure and record airflow across heat exchanger Test variable frequency drive for Inspect fan belt tension. Inspect belt and pulleys for wear and tear Confirm the fan blade or blower wheel has a tight connection to the blower motor shaft. Inspect fan for free rotation and minimal endplay. Measure and record amp draw when blower is operating. Test inducer fan motor and blower assembly If outside OEM specifications, inspect for cause Verify all grilles are open and free of obstruction. Adjust, repair, clean blower assembly and heat exchanger as necessary to ensure proper air flow Lubricate bearings as needed. If amp draw exceeds OEM specifications, then adjust motor speed to remedy cause Correct as needed Extensive repair or replacements conducted as necessary Repair or replace if necessary Condensate Removal Inspect condensate drain piping and traps for Clean, adjust as necessary Evaluate, Clean, and Tune Guidance August 2012 Page 4 of 23

5 Gas Combustion Inspect burner and flue for signs Identify cause and clean of water, corrosion, and blockage Inspect heat exchanger for signs of Identify cause and clean corrosion, fouling, structural problems and erratic flame operation during blower operation Visually inspect burners for signs Identify cause and clean of contamination Inspect the burner blower wheel Clean as needed Inspect hot surface igniter for cracks Replace if outside OEM specifications Measure and record inlet gas pressure at inlet pressure trap If gas pressure is not sufficient, document for utility company involvement Measure, record, and adjust manifold pressure as necessary Adjust the gas valve to provide proper manifold pressure Test main burner ignition Replace thermocouple or flame sensor assembly if outside OEM specifications Test burners Test inducer fan motor and blower assembly Test combustion air volume is correct Perform complete combustion analysis test Measure and record temperature difference (TD) across the heat exchanger Adjust air shutters per OEM specifications Correct as needed, clean as needed Confirm volume is correct per local code, document Measure and record test results per NCWIS Section Adjust as needed to conform to safety standards If TD is outside OEM specifications, identify cause. Clean, repair as needed Recommend additional combustion air per NCWIS Section 6500 Recommend corrective action and notify the WSP Evaluate, Clean, and Tune Guidance August 2012 Page 5 of 23

6 Gas Furnace ACCA Standard 4 Checklist 7.3 Venting Inspect vent exhaust system for signs of improper condensation, corrosion, cracks Inspect all vent connections for rust, discoloration, signs of condensate, proper material Inspect inlet and exhaust vent pipe for proper support, slope and termination Inspect for combustible materials placed too close to vent or pipe Document observations. Clean, remove blockages Ensure connectors are securely fastened Document observations Recommend relocation to safe place. Document observations Notify the WSP Evaluate, Clean, and Tune Guidance August 2012 Page 6 of 23

7 Oil Furnace ACCA Standard 4 Checklist 7.4 Cabinet Inspect the required clearance for combustion around cabinet Recommend to the WSP corrections as required for combustion air, clearance to combustibles Electrical Inspect electrical disconnect box Test proper equipment grounding Tighten wiring nuts as needed Measure and record line voltage Inspect and test contactors and relays Inspect electrical connections Measure and record; compare to OEM specifications or nameplate data Look for pitting or signs of damage Ensure wire size and type match load conditions. Tighten loose connections Recommend that voltage be addressed if out of standard Replace contactors and relays demonstrating evidence of excessive contact Replace heat discolored connections and repair or replace any damaged electrical wiring Inspect all stand alone capacitors Replace those that are bulged, split, incorrectly sized, or do not meet OEM specifications Measure and record amperage draw to motor/nameplate data as available Blower Assembly Determine and record airflow across heat exchanger Test variable frequency drive for Inspect fan belt tension. Inspect belt and pulleys for wear and tear Confirm the fan blade or blower wheel has a tight connection to the blower motor shaft. Inspect fan for free rotation and minimal endplay. Measure and record amp draw. Oil Combustion Inspect combustion chamber for structural problems Inspect heat exchanger for signs of corrosion, fouling, structural problems and erratic flame Measure. If outside OEM specifications, inspect for cause Measure and record. Verify all grilles are open and free of obstruction. Adjust, repair, clean blower assembly and heat exchanger as necessary to ensure proper air flow Lubricate bearings as needed. If amp draw exceeds OEM specifications, then adjust motor speed to remedy cause Document observations, clean if possible Identify cause and clean Extensive repair or replacements conducted as necessary Evaluate, Clean, and Tune Guidance August 2012 Page 7 of 23

8 operation during blower operation Visually inspect burner gaskets Identify cause and clean Inspect the retention head, electrodes and ceramic insulation Clean retention head, electrodes and ceramic insulation of soot and Change electrodes with ceramic cracks or if tips are rounded carbon Inspect electrodes for proper positioning Position electrodes as necessary Change electrodes as necessary Measure and record photo cell resistance Clean combustion air inlet Verify burner head or nozzle type and location per OEM specifications Remove photocell, check resistance, clean as necessary. Check against OEM specifications. Remove lint or foreign material that may obstruct airflow Adjust as necessary Replace as necessary Replace oil burner nozzle Document observations Replace DO NOT ATTEMPT TO CLEAN Test inducer fan motor and blower Correct as needed, clean as assembly needed Test combustion air volume is correct Confirm volume is correct per local code, document Recommend additional combustion air per NCWIS 6500 Replace oil filter Replace oil filter Bleed oil line Remove any air from line N/A Measure, adjust and record oil Measure and adjust oil pressure as N/A pressure needed Inspect oil pump for proper pressure and leaks If pressure is below OEM specifications, or signs of leak, remove oil pump cover and gasket. Discard gasket. With fine brush and solvent, clean strainer and replace. Reassemble new gasket. Retest pump N/A Test fuel pump for proper operation, pressure, and cut off. Measure and record line vacuum Measure and record ignition transformer secondary voltage Perform complete combustion analysis test Check primary burner control safety timing Venting Inspect vent exhaust system for signs of improper condensation, corrosion, or cracks Inspect all vent connections for rust, discoloration, signs of condensate Record using pressure gauge. Measure and record test results per NCWIS Section Adjust if possible to meet compliance Document observations. Clean, remove blockages Ensure connectors are securely fastened. If pressure drops below OEM specifications, replace pump or add check valve Notify the WSP if Safety Issue Recommend repairs or replacements as needed Replace safety control if timing exceeds OEM specifications Evaluate, Clean, and Tune Guidance August 2012 Page 8 of 23

9 Inspect inlet and exhaust vent Document observations pipe for proper support, slope and termination Inspect for combustible materials Recommend relocation to safe Notify the WSP placed too close to vent or pipe place. Document observations Blower Assembly Determine and record airflow across heat exchanger Measure and record. Verify all grilles are open and free of Extensive repair or replacements conducted as necessary obstruction. Adjust and clean blower and heat exchanger as necessary to ensure proper air flow Test variable frequency drive for Replace if necessary Inspect fan belt tension. Inspect belt and pulleys for wear and tear Confirm the fan blade or blower wheel has a tight connection to the blower motor shaft. Inspect fan for free rotation and minimal endplay. Measure and record amp draw when blower operating Lubricate bearings as needed. If amp draw exceeds OEM specifications, then adjust motor speed to remedy cause Evaluate, Clean, and Tune Guidance August 2012 Page 9 of 23

10 Electric Furnace ACCA Standard 4 Checklist 7.5 Cabinet Inspect the required clearance around cabinet Recommend to the WSP corrections as required Electrical Inspect electrical disconnect box Replace as necessary Test proper equipment grounding Tighten, correct as necessary Measure and record line voltage Measure and record. If outside OEM specifications, inspect for cause Address if out of standard Inspect and test contactors and relays Inspect electrical connections Look for pitting or signs of damage. Ensure wire size and type match load conditions. Tighten loose connections Replace contactors and relays demonstrating evidence of excessive contact Replace heat discolored connections and repair or replace any damaged electrical wiring Inspect all stand alone capacitors Replace those that are bulged, split, incorrectly sized, or do not meet OEM specifications Measure and record amperage draw to motor/nameplate data as available Test electric heater s capacity and sequence of operation Measure and record. If outside OEM specifications, inspect for cause If outside OEM specifications, inspect for cause Evaluate, Clean, and Tune Guidance August 2012 Page 10 of 23

11 Evaporator Coil ACCA Standard 4 Checklist 7.6 Cabinet Inspect the required clearance for combustion cabinet Condensate Removal Inspect condensate drain piping and traps for Inspect for condensate blower from coil into cabinet Inspect drain pan and accessible drain line for biological growth Refrigeration Measure and record TD across evaporator coil Inspect coil fins Inspect accessible refrigerant lines, joints, components and coils for oil leaks Inspect refrigerant line insulation Measure pressure drop across the coil Clean and repair as necessary Adjust fan speed, clean coil fins, ensure OEM specifications supplied deflectors are in place, or replace coil as required to eliminator water carry over Clean as needed to remove biological growth and ensure Evaluate this measurement with airflow, refrigerant charge, and operation conditions Ensure fins are visibly clean, straight, and open. Clean and straightening if required Test all oil stained joints for leaks. Clean if required Repair or replace insulation as needed Adjust, clean to ensure proper air flow Recommend to the WSP corrections as required for combustion air, clearance to combustibles Add algae tablets or strips as necessary. Ensure algae tubes and cleaning agent are compatible with fin and tube material Add or recover refrigerant as needed Repair or replace heavily damaged fins N/A Repair as necessary Evaluate, Clean, and Tune Guidance August 2012 Page 11 of 23

12 Condensing Unit ACCA Standard 4 Checklist 7.7 Cabinet Inspect the required clearance for combustion around cabinet Recommend to the WSP corrections as required for combustion air, clearance to combustibles Electrical Inspect electrical disconnect box Replace as necessary Test proper equipment grounding Tighten, correct as necessary Measure and record line voltage Measure and record; compare to Address if out of standard OEM specifications or nameplate data Inspect and test contactors and relays Look for pitting or signs of damage Replace contactors and relays demonstrating evidence of excessive Inspect electrical connections Ensure wire size and type match load conditions. Tighten loose connections contact Replace heat discolored connections and repair or replace any damaged electrical wiring Inspect all stand alone capacitors Replace those that are bulged, split, incorrectly sized, or do not meet OEM specifications Measure and record amperage draw to motor/nameplate data as available Measure. If outside OEM specifications, inspect for cause Refrigeration Inspect accessible refrigerant lines, joints, components and coils for oil leaks If indoor air flow is within OEM specifications but TD is not, measure and record system refrigeration charge in cooling mode Condenser Fan Motor Confirm the fan blade or blower wheel has a tight connection to the blower motor shaft Test all oil stained joints for leaks. Clean Evaluate metering device for proper installation Lubricate bearings as needed, if recommended by OEM specifications. If amp draw exceeds OEM specifications then adjust motor speed or remedy Add or recover refrigerant as needed If due to motor failure, recommend replacement of blower motor Condenser Coil Inspect coil fins Clean and straighten fins Test reversing valve operation If indoor air flow is within OEM specifications but TD is not Measure and record system refrigeration in heating mode. Evaluate metering device Add or recover refrigerant as needed Test defrost cycle controls Adjust controls as needed Inspect outdoor unit condensate drain ports Ensure drain ports are open and unit is elevated above obstruction to allow free flow of condensate per local code Recommend repairs / adjustments as needed Evaluate, Clean, and Tune Guidance August 2012 Page 12 of 23

13 Fan Coil ACCA Standard 4 Checklist 7.8 Cabinet Inspect the required clearance for combustion around cabinet Recommend to the WSP corrections as required for combustion air, clearance to combustibles Electrical Inspect electrical disconnect box Replace as necessary Test proper equipment grounding Tighten, correct as necessary Measure and record line voltage Measure and record; compare to Address if out of standard OEM specifications or nameplate data Inspect and test contactors and relays Look for pitting or signs of damage Replace contactors and relays demonstrating evidence of excessive Inspect electrical connections Ensure wire size and type match load conditions. Tighten loose connections contact Replace heat discolored connections and repair or replace any damaged electrical wiring Inspect all stand alone capacitors Replace those that are bulged, split, incorrectly sized, or do not meet OEM specifications Measure and record amperage draw to motor/nameplate data as available Measure. If outside OEM specifications, inspect for cause Blower Assembly Shall determine and record airflow across heat exchanger Measure and record. Verify all grilles are open and free of obstruction. Adjust, clean as necessary to ensure proper air flow Extensive repair or replacements conducted as necessary Test variable frequency drive for Replace if necessary Inspect fan belt tension. Inspect belt and pulleys for wear and tear Confirm the fan blade or blower wheel Lubricate bearings as needed. If has a tight connection to the blower amp draw exceeds OEM motor shaft. Inspect fan for free specifications, then adjust motor rotation and minimal endplay. speed to remedy cause Measure and record amp draw Evaporator Coil Inspect coil fins Clean and straighten fins Measure and record TD across Add or recover refrigerant if necessary evaporator coil Inspect refrigerant line insulation Condensate Removal Inspect condensate drain piping and Clean and repair as necessary traps for Evaluate, Clean, and Tune Guidance August 2012 Page 13 of 23

14 Inspect for condensate blowing from coil into cabinet Adjust fan speed, clean coil fins, ensure OEM specifications supplied deflectors are in place Replace coil as necessary Inspect drain pan and drain line for biological growth Auxiliary or Supplemental Electric Heaters Test electric heater s capacity and sequence operation Clean as needed to remove biological growth an ensure If outside OEM specifications rating or sequencer specs, inspect for cause. Record Add algae tablets or a cleaning agent as needed compatible with OEM specifications Repair as necessary Evaluate, Clean, and Tune Guidance August 2012 Page 14 of 23

15 Gas Boiler ACCA Standard 4 Checklist 7.9 Cabinet Inspect cabinet, cabinet fasteners, and cabinet panels Inspect the required clearance for combustion around cabinet Adjust / repair fasteners as needed to ensure cabinet closes properly Recommend to the WSP repair or replace insulation to ensure. Replace lost fasteners as needed. Recommend to the WSP corrections as required for combustion air, clearance to combustibles Electrical Inspect electrical disconnect box Test proper equipment grounding Tighten wiring nuts as needed Measure and record line voltage Inspect and test contactors and relays Inspect electrical connections Measure and record; compare to OEM specifications or nameplate data Look for pitting or signs of damage Ensure wire size and type match load conditions. Tighten loose connections Recommend that voltage be addressed if out of standard Replace contactors and relays demonstrating evidence of excessive contact Replace heat discolored connections and repair or replace any damaged electrical wiring Inspect all stand alone capacitors Replace those that are bulged, split, incorrectly sized, or do not meet OEM specifications Measure and record amperage draw to motor/nameplate data as available Gas Combustion Inspect combustion chamber for structural problems Inspect heat exchanger for signs of corrosion, fouling, structural problems and erratic flame operation during blower operation Visually inspect burners for signs of contamination Measure. If outside OEM specifications, inspect for cause Document observations, clean if possible Identify cause and clean Identify cause and clean Inspect the burner blower wheel Clean as needed Inspect hot surface igniter for cracks Record Observations Replace if outside OEM specifications Shall measure and record in-set gas pressure at inlet pressure tap Record Observations If gas pressure is not sufficient, notify the WSP Measure, record, and adjust manifold pressure as necessary Adjust the gas valve to provide proper pressure Test main burner ignition Clean thermocouple or flame sensor Evaluate, Clean, and Tune Guidance August 2012 Page 15 of 23

16 Test burners Fire unit and adjust air shutters if used Test inducer fan motor and blower Clean as needed assembly Test combustion air volume is correct Ensure air volume is correct per code Notify WSP add combustion air per NCWIS 6500 Shall complete perform Measure and record test results combustion analysis test per NCWIS Section remedy issues if possible Measure and record TD across the Clean components or adjust heat exchanger airflow as necessary Hydronic Loop Inspect screen on reducing valve, pressure reducing valve, and Y Clean as necessary strainer if available Test bladder expansion tank for proper air cushion or proper air cushion on expansion tank Inspect water pump Measure and record TD of water entering to water leaving coil/ heat exchanger Measure and record pressure difference (PD) of the water loop across the water heat exchanger Venting Inspect vent exhaust system for signs of improper condensation, corrosion, or cracks Inspect all vent connections for rust, discoloration, signs of condensate Inspect inlet and exhaust vent pipe for proper support, slope and termination Inspect for combustible materials placed too close to vent or pipe Adjust to provide proper air cushion on expansion tank as per manufactures specifications Clean or clear as needed to reduce cavitation and ensure Adjust flow rate as necessary Adjust water pump or control valve as necessary Document observations. Clean, remove blockages Ensure connectors are securely fastened Document observations Recommend relocation to safe place. Document observations Notify the WSP Evaluate, Clean, and Tune Guidance August 2012 Page 16 of 23

17 Oil Boiler ACCA Standard 4 Checklist 7.9 Cabinet Inspect cabinet, cabinet fasteners, and cabinet panels Inspect the required clearance for combustion around cabinet Adjust / repair fasteners as needed to ensure cabinet closes properly Recommend to the WSP repair or replace insulation to ensure. Replace lost fasteners as needed Recommend to the WSP corrections as required for combustion air, clearance to combustibles Electrical Inspect electrical disconnect box Test proper equipment grounding Tighten wiring nuts as needed Measure and record line voltage Inspect and test contactors and relays Inspect electrical connections Measure and record; compare to OEM specifications or nameplate data Look for pitting or signs of damage Ensure wire size and type match load conditions. Tighten loose connections Recommend that voltage be addressed if out of standard Replace contactors and relays demonstrating evidence of excessive contact Replace heat discolored connections and repair or replace any damaged electrical wiring Inspect all stand alone capacitors Replace those that are bulged, split, incorrectly sized, or do not meet OEM specifications Measure and record amperage draw to motor/nameplate data as available Oil Combustion Inspect combustion chamber for structural problems Inspect heat exchanger for signs of corrosion, fouling, structural problems and erratic flame operation during blower operation Measure. If outside OEM specifications, inspect for cause Document observations, clean if possible Identify cause and clean Visually inspect burner gaskets Identify cause and clean Inspect the retention head, electrodes and ceramic insulation Clean retention head, electrodes and ceramic insulation of soot and Change electrodes with ceramic cracks or if tips are rounded carbon Inspect electrodes for proper positioning Position electrodes as necessary Change electrodes as necessary Measure and record photo cell resistance Clean combustion air inlet Remove photocell, check resistance, clean as necessary. Check against OEM specifications Remove lint or foreign material that may obstruct airflow Evaluate, Clean, and Tune Guidance August 2012 Page 17 of 23

18 Verify burner head or nozzle type Adjust as necessary Replace as necessary and location per OEM specifications Replace oil burner nozzle Document observations Replace DO NOT ATTEMPT TO CLEAN Test inducer fan motor and blower Correct as needed, clean as assembly needed Test combustion air volume is correct Confirm volume is correct per local code, document Recommend additional combustion air per NCWIS 6500 Replace oil filter Replace oil filter Bleed oil line Remove any air from line N/A Measure, adjust and record oil Measure and adjust oil pressure as N/A pressure needed Inspect oil pump for proper pressure and leaks If pressure is below OEM specifications, or signs of leak, remove oil pump cover and gasket. Discard gasket. With fine brush and solvent, clean strainer and replace. Reassemble new gasket. Retest pump N/A Test fuel pump for proper operation, pressure, and cut off. Measure and record line vacuum Measure and record ignition transformer secondary voltage Perform complete combustion analysis test Check primary burner control safety timing Hydronic Loop Inspect screen on reducing valve, pressure reducing valve, and Y strainer if available Test bladder expansion tank for proper air cushion or proper air cushion on expansion tank Inspect water pump Measure and record TD of water entering to water leaving coil/ heat exchanger Measure and record pressure difference (PD) of the water loop across the water heat exchanger Record using pressure gauge Measure and record test results per NCWIS Section Adjust if possible to meet compliance Clean as necessary Adjust to provide proper air cushion on expansion tank as per manufactures specifications Clean or clear as needed to reduce cavitation and ensure Adjust flow rate as necessary Adjust water pump or control valve as necessary If pressure drops below OEM specifications, replace pump or add check valve Notify the WSP if Safety Issue Recommend repairs or replacements as needed Replace safety control if timing exceeds OEM specifications N/A N/A Evaluate, Clean, and Tune Guidance August 2012 Page 18 of 23

19 Venting Inspect vent exhaust system for signs of improper condensation, corrosion, or cracks Inspect all vent connections for rust, discoloration, signs of condensate Inspect inlet and exhaust vent pipe for proper support, slope and termination Inspect for combustible materials placed too close to vent or pipe Document observations. Clean, remove blockages Ensure connectors are securely fastened Document observations Recommend relocation to safe place. Document observations Notify the WSP Evaluate, Clean, and Tune Guidance August 2012 Page 19 of 23

20 Package Units ACCA Standard 4 Checklist 7.12 Cabinet Inspect cabinet, cabinet fasteners, and cabinet panels Inspect the required clearance for combustion and service around cabinet Adjust / repair fasteners as needed to ensure cabinet closes properly Recommend to the WSP repair or replace insulation to ensure proper operation. Replace lost fasteners as needed Recommend to the WSP corrections as required for combustion air, clearance to combustibles Electrical Inspect electrical disconnect box Replace as necessary Test proper equipment grounding Tighten, correct as necessary Measure and record line voltage Measure and record; compare to Address if out of standard OEM specifications or nameplate data Inspect and test contactors and relays Look for pitting or signs of damage Replace contactors and relays demonstrating evidence of excessive contact Inspect electrical connections Ensure wire size and type match load conditions. Tighten loose connections Replace heat discolored connections and repair or replace any damaged electrical wiring Inspect all stand alone capacitors Replace those that are bulged, split, incorrectly sized, or do not meet OEM specifications Measure and record amperage draw to motor/nameplate data as available Blower Assembly Shall determine and record airflow across heat exchanger Test variable frequency drive for Inspect fan belt tension. Inspect belt and pulleys for wear and tear Confirm the fan blade or blower wheel has a tight connection to the blower motor shaft. Inspect fan for free rotation and minimal endplay. Measure and record amp draw Indoor Blower Motor Determine and record airflow across heat exchanger Measure. If outside OEM specifications, inspect for cause Measure and record. Verify all grilles are open and free of obstruction. Adjust and clean as necessary to ensure proper air flow Lubricate bearings as needed. If amp draw exceeds OEM specifications, then adjust motor speed to remedy cause Measure and record. Verify all grilles are open and free of obstruction. Adjust and clean as necessary to ensure proper air flow Extensive repair or replacements conducted as necessary Replace if necessary Extensive repair or replacements conducted as necessary Evaluate, Clean, and Tune Guidance August 2012 Page 20 of 23

21 Test variable frequency drive for Replace if necessary Inspect fan belt tension. Inspect belt and pulleys for wear and tear Confirm the fan blade or blower wheel Lubricate bearings as needed. If has a tight connection to the blower motor shaft. Inspect fan for free rotation and minimal endplay. Measure and record amp draw amp draw exceeds OEM specifications, then adjust motor speed to remedy cause Evaporator Coil Section Inspect coil fins Clean, straighten, open as required Replace fins as necessary Inspect for condensate blowing from coil Inspect accessible refrigerant connecting lines, joints, and coils for oil leaks Measure and record TD across evaporator coil Condensate Removal Inspect for condensate blowing from coil into cabinet Inspect condensate drains (and traps) for Inspect drain pan and accessible drain line for biological growth Condenser Blower Motor Shall confirm the fan blade or blower wheel has a tight connection to the blower motor shaft. Inspect fan for free rotation. Measure and record amp draw when blower operating Condenser Coil Section Inspect coil fins Inspect accessible refrigerant connecting lines, joints, and coils for oil leaks Refrigeration Inspect accessible refrigerant connection lines, joints, and coils for oil leaks If indoor airflow is within OEM, but TD is not, measure and record system refrigeration in COOLING MODE Adjust fan speed, clean coil fins, or replace coil as necessary to eliminate water carry over Test all oil stained joints for leak. Clean Adjust fan speed, clean coils fins, confirm deflectors meet OEM specification are in place Clean and repair as needed Clean as needed to remove biological growth and ensure Lubricate bearings as needed, if recommended by OEM specifications. If amp draw exceeds OEM specifications, adjust motor speed Ensure fins are clean, straight, and open Test all oil stained joints for leaks. Clean and repair Test all oil stains for leaks. Clean as needed Record Observations N/A N/A Replace coil as necessary Replace as necessary Add algae tablets or use cleaning solution as necessary If motor failure, recommend replacement Replace fins as necessary Repair and replace as necessary Add or recover refrigerant as necessary Evaluate, Clean, and Tune Guidance August 2012 Page 21 of 23

22 Auxiliary or Supplemental Electric Heaters Test electric heater s capacity and sequence of operation If outside OEM specifications rating or sequencer specs, inspect for cause and repair Replace as necessary Tasks for Package Heat Pumps ACCA Standard 4 Checklist 7.12-HP Test reversing valve operation If indoor air flow is within OEM Evaluate for proper installation Add or recover refrigerant as necessary specifications but TD is not, measure and record system refrigeration in HEATING mode and operation Test defrost cycle Adjust controls as needed Inspect condenser section condensate drain ports Ensure drain ports are open and elevated above obstructions Recommend rework as necessary Evaluate, Clean, and Tune Guidance August 2012 Page 22 of 23

23 Tasks for Gas Package Units ACCA Standard 4 Checklist 7.12-GP Gas Combustion Inspect combustion chamber, burner Record Observations and flue Inspect heat exchanger for signs of Clean as needed corrosion, fouling, structural problems Visually inspect burners for signs of Clean as needed contamination Inspect the burner blower wheel Clean as needed Inspect hot surface igniter for cracks Replace if outside OEM specifications Measure and record in-set gas pressure at inlet pressure tap If gas pressure is not sufficient, notify the WSP Measure, record, and adjust manifold Adjust the gas valve to provide N/A pressure as necessary proper pressure Test main burner ignition Clean thermocouple or flame sensor Test burners Fire unit and adjust air shutters if used Test inducer fan motor and blower Clean as needed assembly Test combustion air volume is correct Ensure air volume is correct per code Notify the WSP add combustion air per NCWIS 6500 Perform complete combustion Measure and record test results analysis test per NCWIS Section 6500 remedy issues if possible Measure and record TD across the heat exchanger Clean components or adjust airflow as necessary Venting Inspect vent exhaust system for signs of improper condensation, corrosion, cracks Inspect all vent connections for rust, discoloration, signs of condensate Inspect inlet and exhaust vent pipe for proper support, slope and termination Inspect for combustible materials placed too close to vent or pipe Document observations. Clean or remove blockages Ensure connectors are securely fastened Document observations Recommend relocation to safe place. Document observations Notify the WSP Evaluate, Clean, and Tune Guidance August 2012 Page 23 of 23

Attachment J-C18.1. HVAC Work Instructions

Attachment J-C18.1. HVAC Work Instructions . RFP: Attachment J-C18.1 HVAC Work Instructions NNC13ZFD017J SOW Item No. Title Page C18-02 Control Air Systems Annual PM 2 C18-03 Split System AC Indoor Section Annual PM 3 C18-04 Condensing Unit Semi-Annual

More information

Boiler and Burner Cleaning and Servicing Specifications

Boiler and Burner Cleaning and Servicing Specifications Boiler and Burner Cleaning and Servicing Specifications The Town of Groton of Public Works Department is requesting bids to provide manufacturers recommended maintenance, repairs and emergency service

More information

Preventive Maintenance. State Energy Assessment Workshop By: DTE Energy Partnership & Services

Preventive Maintenance. State Energy Assessment Workshop By: DTE Energy Partnership & Services Preventive Maintenance State Energy Assessment Workshop By: DTE Energy Partnership & Services Do you know? World wide research has shown that one of the reasons causing 80% of the accidents is deficient

More information

Trouble Shooting. Pump

Trouble Shooting. Pump Trouble Shooting Pump Trouble Possible Cause Remedy Oil leaking in the area of water pump crankshaft Worn crankshaft seal, bad bearing, grooved shaft, or failure of retainer o-ring. Excessive play on crankshaft

More information

ACCA Standard 4. Maintenance of Residential HVAC Systems

ACCA Standard 4. Maintenance of Residential HVAC Systems Air Conditioning Contractors of America 2800 Shirlington Road Suite 300 Arlington, VA 22206 703.575.4477 Fax 703.575.8107 www.acca.org ACCA Standard 4 Standard Number: ANSI/ACCA 4 QM 2013 Maintenance of

More information

RESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00

RESIDENTIAL HEATING OIL SERVICE CONTRACT ANNUAL COST $276.00 RESIDENTIAL HEATING OIL SERVICE CONTRACT This service contract covers all routine service and maintenance of your residential oil fired furnace or boiler. In addition this contract covers all service calls

More information

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR)

Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) Heating, Ventilation, Air Conditioning and Refrigeration (HVACR) I. Demonstrate safety skills in typical HVACR work situations to NATE Core Installer Knowledge Areas for Technician Excellence for Safety

More information

Preventive Maintenance. Learning Objectives: Howdy! Learning Objectives Cont:

Preventive Maintenance. Learning Objectives: Howdy! Learning Objectives Cont: Preventive Maintenance Fountain of Youth for HVAC Successful Learning Environment Bonus Strategies James D. McClure, P.E. Action Planning Guide As you listen to this presentation, use the chart in your

More information

Air Conditioning Sign-Off Sheet

Air Conditioning Sign-Off Sheet Air Conditioning Sign-Off Sheet Printed Technician Name Address Social Security Number Telephone Number City State Zip Code Install Or Verify The Accuracy Of An Air Conditioner s Installation The candidate

More information

Action Plan Template HVAC Page 1

Action Plan Template HVAC Page 1 Action Plan Template HVAC Page 1 Once Establish expected HVAC system efficiency - Write down the expected efficiency of HVAC systems to use as a baseline - Add this information to maintenance plan documentation

More information

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM

SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM SECTION 23 81 03 - PACKAGED ROOFTOP AIR CONDITIONING UNITS NON-CUSTOM PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop air conditioning unit (5 tons and smaller). 2. Roof curb. 1.2

More information

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR BOILER SERVICING MAINTENANCE Maintenance Module 11 March 2012 issue This document has been compiled by the Engineering

More information

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes

Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Heating Ventilation and Air Conditioning Diagnostics for Single Family Homes Vincent Pedalino FSL Home Improvements Phoenix, AZ 1 HVAC Basics Ways to improve the performance of existing air conditioning

More information

SMITH PLUMBING & HEATING 2012 Home Care SERVICE PLAN AGREEMENT. A. Silver Plan

SMITH PLUMBING & HEATING 2012 Home Care SERVICE PLAN AGREEMENT. A. Silver Plan SMITH PLUMBING & HEATING 2012 Home Care SERVICE PLAN A. Silver Plan AGREEMENT Priority Emergency Plumbing / Heating Repair Service: All service labor will be billed at our prevailing labor rate with no

More information

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL

USER S, MAINTENANCE and SERVICE INFORMATION MANUAL CONTENTS SAFETY INFORMATION................ 2 FOR YOUR SAFETY....................... 2 SYSTEM OPERATION.................. 2 THERMOSTATS........................... 2 INTERMITTENT IGNITION DEVICE...........

More information

SL280UHV SERIES GAS FURNACE WARNING

SL280UHV SERIES GAS FURNACE WARNING 2010 Lennox Industries Inc. Dallas, Texas, USA 506677 01 11/2010 Supersedes 506409 01 SL280UHV SERIES GAS FURNACE Litho U.S.A. FIRE OR EXPLOSION HAZARD. Failure to follow safety warnings exactly could

More information

First irst Co. Products

First irst Co. Products First irst Co. Products Recommended Maintenance Program PM1193 FIRST OPERATIONS,LP - P.O. Box 270969 - Dallas, Texas 75227 - www.firstco.com Table of Contents Introduction... 3 General Precautions... 3

More information

HVAC Scheduled Maintenance Program

HVAC Scheduled Maintenance Program (DATE) HVAC Scheduled Maintenance Program Designed Especially for: Company Name: Address: Nick Savio Commercial Sales Manager ADVANTAGE AIR LLC. What Advantage Air can do for you? 1) PROVIDE 28 YEARS OF

More information

Annual Service Agreement

Annual Service Agreement Annual Service Agreement 462 Main Street P.O. Box 130 Royersford, PA 19468 610-948-7220 www.plottsenergy.com GAS OIL HEAT PUMP AIR CONDITIONING A family owned and operated business since 1949. We are here

More information

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT)

SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) SPECIFICATION TECHNICAL AIR-CONDITIONING UNITS SINGLE AND SPLIT (DUCTED) (AIR COOLED PACKAGED UNIT) MAINTENANCE TYPE: STATUTORY 1.0 SCOPE OF SERVICES The Contractor shall provide maintenance Services for

More information

Protect your home s major mechanical systems with Main Street Mechanical s Home Service Agreement.

Protect your home s major mechanical systems with Main Street Mechanical s Home Service Agreement. Protect your home s major mechanical systems with Main Street Mechanical s Home Service Agreement. The benefits of a Home Service Agreement Provides peace of mind Regularly scheduled maintenance will keep

More information

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION

BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION Air Conditioning Central Heating & Cooling BC & BCH SERIES INDOOR / OUTDOOR INSTALLATION INSTALLATION AND SERVICE MANUAL 2 PROJECT: ADDRESS: MODEL: SERIAL NUMBER: INSTALLER: ADDRESS: PHONE NUMBER: INSTALLATION

More information

SERVICE DIAGNOSIS Modine heating & ventilating equipment

SERVICE DIAGNOSIS Modine heating & ventilating equipment 75-551.5 December, 2003 SERVICE DIAGNOSIS Modine heating & ventilating equipment A Problem/Remedy Guide for Modine: Gas-Fired Unit Heaters Gas-Fired Duct Furnaces Steam/Hot Water Unit Heaters Electric

More information

PLP - TERMS AND CONDITIONS

PLP - TERMS AND CONDITIONS PLP - TERMS AND CONDITIONS 2014-2015 Philadelphia Gas Works Residential Parts & Labor Plan Contract This Residential Parts & Labor Plan Contract (this Plan ) is available to customers of the Philadelphia

More information

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS

SECTION 15750 PACKAGED ROOFTOP AIR CONDITIONING UNITS SECTION 15750 PART 1 - GENERAL 1.01 DESCRIPTION A. Section includes requirements for roof mounted, self-contained units, with electric cooling, and electric or reverse refrigeration cycle (heat pump) heating

More information

COMMISSIONING OF HVAC SYSTEMS

COMMISSIONING OF HVAC SYSTEMS FORM CL-01 SYSTEMS / EQUIPMENT INCLUDED : SYSTEM STARTUP CHECKLIST I - PRE - STARTUP INSPECTION EQUIPMENT MOUNTING & SETTING CONTROL, INTERLOCK & POWER WIRING ALIGNMENT OF MOTORS & DRIVES PIPING, CONNECTIONS

More information

Fossil fuel heating equipment

Fossil fuel heating equipment Fossil fuel heating equipment principles and troubleshooting techniques Application Note This application note was written to provide you with an understanding of the basic principles of fossil fuel heating

More information

HVAC Checklist - Long Form

HVAC Checklist - Long Form HVAC Checklist - Long Form Page 1 of 14 Appendix B discusses HVAC system components in relation to indoor air quality. utside Air Intake Location pen during occupied hours? Unobstructed? Standing water,

More information

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm.

Table V. Troubleshooting Checklist for Refrigeration Systems. Air or non-condensable gas in system. Inlet water warm. Table V Troubleshooting Checklist for Refrigeration Systems TROUBLE POSSIBLE CAUSE CORRECTIVE MEASURE High condensing pressure. Low condensing pressure. Air or non-condensable gas in system. Inlet water

More information

Training Syllabus to Instruct/Prepare for the ASE Transit Bus HVAC Test

Training Syllabus to Instruct/Prepare for the ASE Transit Bus HVAC Test APTA STANDARDS DEVELOPMENT PROGRAM RECOMMENDED PRACTICE American Public Transportation Association 1666 K Street, NW, Washington, DC, 20006-1215 APTA BTS-BMT-RP-001-10 Approved October, 2010 APTA Bus Maintenance

More information

Energy Efficiency in Industrial HVAC Systems

Energy Efficiency in Industrial HVAC Systems Energy Efficiency in Industrial HVAC Systems Heating, ventilation and air conditioning (HVAC) constitutes up to 35 percent of energy used in manufacturing facilities. This fact sheet is geared towards

More information

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales

Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales Consortiwm Awdurdodau Lleol Cymru Consortium Local Authorities Wales SPECIFICATION FOR LAUNDRY EQUIPMENT MAINTENANCE Maintenance Module 32 March 2011 issue This document has been compiled by the Engineering

More information

WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler

WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler WMSLW / WMBLWH Series Hydronic Upflow/Horizontal Left or Right, Heating and Cooling Air Handler Installation Operation Maintenance The WMSLW/WMBLW series is designed for installation in a closet, utility

More information

Table Z. Troubleshooting Chart for Air Conditioners. Cause

Table Z. Troubleshooting Chart for Air Conditioners. Cause Troubleshooting Chart for Air Conditioners Type of Unit Complaint Cause With open-type compressor Electric motor will not start Power failure Check circuit for power source Compressor stuck Locate cause

More information

123 street Salt Lake City, Utah 84092

123 street Salt Lake City, Utah 84092 Salt Lake City, Utah 84092 Prepared for: Sample AC inspection Prepared by: Page 1 of 8 Table of Contents Definitions 2 General Information 2 Air Conditioning 3 Heating System 6 Summary 8 Page 2 of 8 Definitions

More information

HVAC Preventative Maintenance Basics. Presented by Mike Crawley

HVAC Preventative Maintenance Basics. Presented by Mike Crawley HVAC Preventative Maintenance Basics Presented by Mike Crawley Air Handlers/Package Units: Coils have to be clean! The main purpose of any coil is to absorb or reject heat If coils are dirty; air flow

More information

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM

QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM QUESTIONS TO ASK WHEN REPLACING YOUR HVAC TOGETHERWESAVE.COM TOGETHERWESAVE.COM IS IT TIME TO REPLACE YOUR HVAC SYSTEM? If your heating and cooling system is 15 to 20 years old and is experiencing problems,

More information

Diagnostics for Mobile Homes: HVAC

Diagnostics for Mobile Homes: HVAC Diagnostics for Mobile Homes: HVAC Adam Harris NYSWDA Wade Thompson - IWTC Objectives Identify different types of HVAC used in mobile homes Provide an overview of duct systems Demonstrate various tests

More information

USER S INFORMATION MANUAL

USER S INFORMATION MANUAL USER S INFORMATION MANUAL UPFLOW, DOWNFLOW, UPFLOW/HORIZONTAL & HORIZONTAL ONLY INDUCED DRAFT GAS FURNACES Recognize this symbol as an indication of Important Safety Information If the information in this

More information

B.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation

B.C. Buildings Corporation. Mandatory Preventive Maintenance Standard. To Meet Section 4.78 of the WCB OH & S Regulation B.C. Buildings Corporation Mandatory Preventive To Meet Section 4.78 of the WCB OH & S Regulation Prepared by: BCBC WCB-IAQ Steering Committee Mandatory Preventive TABLE OF CONTENTS Page no. INTRODUCTION...1

More information

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace)

Circuit breaker panel. Power supply for condensing unit. Power supply for furnace. Air handler (Furnace) UNIT OBJECTIVES Describe the concept of year-round air conditioning List three typical year-round air conditioning system types List the five ways to condition the air Determine airflow for a cooling system

More information

Basics of HVAC Cleaning

Basics of HVAC Cleaning Basics of HVAC Cleaning Seminar Outline Residential 1. Types of systems used and why 2. Types of air distribution systems 3. System components 4. Determining the need for cleaning (ACR2002) 5. Project

More information

Glossary of Heating, Ventilation and Air Conditioning Terms

Glossary of Heating, Ventilation and Air Conditioning Terms Glossary of Heating, Ventilation and Air Conditioning Terms Air Change: Unlike re-circulated air, this is the total air required to completely replace the air in a room or building. Air Conditioner: Equipment

More information

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook

National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook National Competency Based Skill Training Refrigeration and Air-conditioning Mechanic Logbook Trainee:... Training Provider:... Year:... Trainee Contact no:... Competency Based Skill Training Logbook Introduction

More information

CHAPTER 3 UTILITY SYSTEMS-HEATING & AIR CONDITIONING. Utility and General System Notes. Heating and Air Conditioning

CHAPTER 3 UTILITY SYSTEMS-HEATING & AIR CONDITIONING. Utility and General System Notes. Heating and Air Conditioning CHAPTER 3 UTILITY SYSTEMS-HEATING & AIR CONDITIONING Utility and General System Notes This is where your homework starts. Take time to read these chapters. They contain important information about the

More information

heating 3 & cooling heating and cooling 2010 PulteGroup, Inc. All Rights Reserved.

heating 3 & cooling heating and cooling 2010 PulteGroup, Inc. All Rights Reserved. 3 & cooling 17 heating 2010 PulteGroup, Inc. All Rights Reserved. condensation The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. Air conditioning

More information

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT

SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT SECTION 23 00 01 HEATING, VENTILATION AND AIR CONDITIONING EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION A. The Work specified in this Section consists of designing, furnishing and installing factory-assembled

More information

THREE. Heating and Cooling

THREE. Heating and Cooling THREE Heating and Cooling 17 Condensation Drain Line The line that drains condensed moisture away from your heating and/or cooling unit needs periodic maintenance. If your unit is located in the attic,

More information

Heating, Ventilation and Air Conditioning

Heating, Ventilation and Air Conditioning Heating, Ventilation and Air Conditioning The Montgomery County Students Construction Trades Foundation, Inc has developed a comprehensive construction technology program designed to prepare students for

More information

SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING

SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING SYLLABUS For BASIC TRADE COURSE (360 Hours) On REFRIGERATION AND AIR CONDITIONING INDEX 1. Introduction 3 2. Objectives 3 3. Employment Opportunity 4 4. Course Structure 4 5. Entry Qualification 4 6. List

More information

A Guide to Trouble-Free Cooling Towers

A Guide to Trouble-Free Cooling Towers A Guide to Trouble-Free Cooling Towers A basic understanding of cooling tower operation and maintenance will help keep a cooling water system running in top condition, year after year By David M. Suptic

More information

Service Guide. Appliance Protection Plan. Home Warranty APPLIANCE PROTECTION PLANS. Nobody covers you like Home Warranty.

Service Guide. Appliance Protection Plan. Home Warranty APPLIANCE PROTECTION PLANS. Nobody covers you like Home Warranty. Home Warranty APPLIANCE PROTECTION PLANS Service Guide Appliance Protection Plan a product of Request service at (877) 977-4949 Nobody covers you like Home Warranty. Plan Options (877) 977-4949 Essentials

More information

HVAC Design Requirements

HVAC Design Requirements Maintenance of HVAC HVAC Design Requirements Air Flow Diagram แบบ Recirculation Air Flow Diagram แบบ Once Through Definition Of Conditions As built At rest In operation air air air Maintenance GMP Requirements

More information

Preventative Maintenance Plan. Guide. The Simple, Smart Way To Properly Care For Home Systems And Appliances.

Preventative Maintenance Plan. Guide. The Simple, Smart Way To Properly Care For Home Systems And Appliances. Preventative Maintenance Plan Guide The Simple, Smart Way To Properly Care For Home Systems And Appliances. Protect. Prevent. Preserve. Prolong. What AHS Preventative Maintenance Plans Can Do For Your

More information

Heat Pump Water Heater IOM Manual

Heat Pump Water Heater IOM Manual Heat Pump Water Heater IOM Manual Installation Operation & Maintenance This manual is intended as an aid to qualified service personnel for proper installation, operation and maintenance of the heat pump

More information

USF St. Petersburg Operations & Maintenance of Facilities Preventative Maintenance Guide

USF St. Petersburg Operations & Maintenance of Facilities Preventative Maintenance Guide USF St. Petersburg Operations & Maintenance of Facilities Preventative Maintenance Guide GUIDE EQUIPMENT TYPE & TASKS FREQUENCY A-1 Air Dryer 1. Lubricate valves and replace packing, if necessary 2. Check

More information

Oil and Coolant Circulating Heating System. Model - OCSM

Oil and Coolant Circulating Heating System. Model - OCSM Oil and Coolant Circulating Heating System Model - OCSM Installation & Operation Manual 216280-000 REV 2 Identifying Your System The HOTSTART heating system is designed to heat fluids for use in marine

More information

Test Code: 8297 / Version 1

Test Code: 8297 / Version 1 Blueprint HVAC Maintenance Technology PA Test Code: 8297 / Version 1 Copyright 2014. All Rights Reserved. General Assessment Information HVAC Maintenance Technology PA Blueprint Contents General Assessment

More information

Commercial Gas Furnace Upflow

Commercial Gas Furnace Upflow Commercial Gas Furnace Upflow Model G24-200 80% A.F.U.E. 200,000 Btuh Input Heating Cap. 7.5 or 10 Tons Nominal Add-On Cooling GUK FEATURES Certified by A.G.A./C.G.A. Laboratories. Heavy gauge painted

More information

Rinnai Tankless. Water Heater. Troubleshooting Manual

Rinnai Tankless. Water Heater. Troubleshooting Manual Rinnai Tankless Water Heater Troubleshooting Manual WARNING There are a number of live tests that are required when fault finding this product. Extreme care should be used at all times to avoid contact

More information

SECTION 23 81 43 HEAT PUMPS

SECTION 23 81 43 HEAT PUMPS SECTION 23 81 43 HEAT PUMPS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Packaged rooftop heat pumps. 1.2 REFERENCES A. American Society of Heating, Refrigerating and Air-Conditioning Engineers:

More information

01-3 6820-11 6820-11 AIR CONDITIONER GENERAL 1. SPECIFICATIONS AIR CONDITIONER REXTON 2010.01

01-3 6820-11 6820-11 AIR CONDITIONER GENERAL 1. SPECIFICATIONS AIR CONDITIONER REXTON 2010.01 682011 013 GENERAL 1. SPECIFICATIONS 682011 014 682011 2. REPAIR INSTRUCTIONS 1) Precautions for Working with R134a R12 refrigerant and R134a refrigerant are not compatible. These refrigerants must never

More information

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715,

Subpart 1. Installation. All plumbing systems must be. installed and tested according to this chapter and chapter 4715, 4658.4500 PLUMBING SYSTEMS; NEW CONSTRUCTION. Subpart 1. Installation. All plumbing systems must be installed and tested according to this chapter and chapter 4715, the Minnesota Plumbing Code. Subp. 2.

More information

DEPARTMENT OF CODES AND BUILDING SAFETY FLOOD RECOVERY INFORMATION

DEPARTMENT OF CODES AND BUILDING SAFETY FLOOD RECOVERY INFORMATION May 2010 DEPARTMENT OF CODES AND BUILDING SAFETY FLOOD RECOVERY INFORMATION GUIDELINES FOR PERMITS ASSOCIATED WITH THE REPAIR OF FLOOD DAMAGED HOMES AND BUILDINGS The Department of Codes and Building Safety

More information

Certification Information. Qualifications. Test Specifications. Gas Furnaces Industry References

Certification Information. Qualifications. Test Specifications. Gas Furnaces Industry References GAS FURNACES SERVICE CERTIFICATION Certification Information Scope - Tests a candidate's knowledge of the installation, service, maintenance, and repair of HVAC systems. System sizes are limited to 400,000

More information

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project.

A. The Commissioning Authority (CxA) has been contracted or will be contracted directly with the Owner for this project. DIVISION 23 HEATING, VENTILATING, AND AIR CONDITIONING (HVAC) SECTION 23 08 02 PART 1 GENERAL 1.01 AUTHORITY (CxA) A. The Commissioning Authority (CxA) has been contracted or will be contracted directly

More information

CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg)

CDS TROUBLESHOOTING SECTION I. VACUUM. 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) CDS TROUBLESHOOTING SECTION I. VACUUM 1.0. Weak vacuum at wand. Gauge reads normal (10hg to 14hg) 1.1. Clogged hoses or wand tube. Disconnect hoses and carefully check for an obstruction. 1.2. Excessive

More information

Service Guide. Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines. ORDER No: UN-SVG001A-EN DATE: October 9, 2007

Service Guide. Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines. ORDER No: UN-SVG001A-EN DATE: October 9, 2007 Service Guide Evaporator Coil Cleaning and Condensate Drain Maintenance Guidelines ORDER No: UN-SVG001A-EN DATE: October 9, 2007 Introduction This document defines American Standard and Trane s recommendations

More information

Tankless. Water Heater. Troubleshooting Manual

Tankless. Water Heater. Troubleshooting Manual Tankless Water Heater Troubleshooting Manual WARNING There are a number of live tests that are required when fault finding this product. Extreme care should be used at all times to avoid contact with energized

More information

ASK THE EXPERT: Burner Troubleshooting Information & Maintenance

ASK THE EXPERT: Burner Troubleshooting Information & Maintenance ASK THE EXPERT: Burner Troubleshooting Information & Maintenance The burner is the heart of your BBQ. It is subject to a number of conditions that can cause damage, and lead to potential safety issues.

More information

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI).

C. Burner management system to follow requirements of Industrial Risk Insurers (IRI). SECTION 23 52 30 PART 1 - GENERAL 1.01 RELATED WORK A. Section 23 05 00: Common Work Results for HVAC B. Section 23 25 00: Chemical Water Treatment C. Section 23 51 23: Flue Piping 1.02 QUALITY ASSURANCE

More information

Low Profile Unit Cooler

Low Profile Unit Cooler Super-Flo Now available with EC Motors High Efficiency / High Reliability Low Profile Unit Cooler Publication No. 411.4 November, 2008 S A N I T A T I O N F O U N D A T I O N A L N A T I O N Air Defrost

More information

How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page.

How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. Demystifying HVAC Test Your HVAC Knowledge By Ron Prager How much do you know about HVAC? Try testing yourself with the following questions and then take a look at the answers on the following page. 1)

More information

Maintaining Conventional Residential Oil-Fired Heating Systems

Maintaining Conventional Residential Oil-Fired Heating Systems Maintaining Conventional Residential Oil-Fired Heating Systems Greg Tuttle, Graduate Student, Department of Agricultural Engineering Susan Mireley, Associate Professor and Extension Housing Specialist

More information

SECTION 11 78 13 MORTUARY REFRIGERATORS

SECTION 11 78 13 MORTUARY REFRIGERATORS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 11 78 13 MORTUARY REFRIGERATORS SPEC WRITER NOTE: Delete between //---// if not applicable to project. Also delete any other item or paragraph not applicable in

More information

http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html

http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html TECHNICAL SERVICE DEPARTMENT Removal, Cleaning, & Reinstallation of the Burner Assembly For models 74 & GT199 Required tools -

More information

ENGINE COOLING SYSTEM

ENGINE COOLING SYSTEM ENGINE COOLING SYSTEM 1988 Toyota Celica 1987-88 TOYOTA Engine Cooling Systems Celica DESCRIPTION The basic liquid cooling system consists of a radiator, water pump, thermostat, cooling fan, pressure cap,

More information

MAINTENANCE OF WHEELMOVE IRRIGATION SYSTEMS

MAINTENANCE OF WHEELMOVE IRRIGATION SYSTEMS MAINTENANCE OF WHEELMOVE IRRIGATION SYSTEMS F. Richard Beard, Agricultural Equipment, Structures and Electricity Robert W. Hill, Biological & Irrigation Engineering Boyd Kitchen, Uintah County Extension

More information

BUILDING PERFORMANCE INSTITUTE TECHNICAL STANDARDS

BUILDING PERFORMANCE INSTITUTE TECHNICAL STANDARDS BUILDING PERFORMANCE INSTITUTE TECHNICAL STANDARDS FOR THE HEATING PROFESSIONAL Health and Safety Personal Safety All technicians performing diagnostic tests, inspections, or installations, must have access

More information

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now

Air Conditioning. The opportunity for energy efficiency. Low cost actions to reduce energy usage now Fact Sheet #6 Air Conditioning In this fact sheet you will discover: The opportunity for energy efficiency How air conditioning works Low cost actions to reduce energy usage now Investments to reduce costs

More information

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION

SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION SECTION 23 05 93 TESTING, ADJUSTING, AND BALANCING FOR HVAC INTRODUCTORY INFORMATION The purpose of this guide specification is to assist the specifier in correctly specifying Mechanical System Testing

More information

Condensing Boiler Efficiency

Condensing Boiler Efficiency Condensing Boiler Efficiency Date: July 17, 2012 PRES E NT ED BY DO N L E O NA RDI LE O N A RD I I NC. HV AC T RAI N I N G & C ON SU LT IN G Concepts 1 The current state of evolution in boiler design 2

More information

CARING FOR YOUR WATER HEATER

CARING FOR YOUR WATER HEATER http://waterheatertimer.org/troubleshoot-rheem-tankless-water-heater.html Water Heater Inspections CARING FOR YOUR WATER HEATER Venting System (Direct Vent Only) The venting system should be inspected

More information

WALL MOUNTED PACKAGE HEAT PUMPS REPLACEMENT PARTS MANUAL WH483 WH602. Contents. General Notes. Important. Description

WALL MOUNTED PACKAGE HEAT PUMPS REPLACEMENT PARTS MANUAL WH483 WH602. Contents. General Notes. Important. Description REPLACEMENT PARTS MANUAL WALL MOUNTED PACKAGE HEAT PUMPS Models: WH421 WH483 WH602 General Notes Contents Ø Ø Revised and/or additional pages may be issued from time to time. A complete and current manual

More information

HVAC. (w) HVAC SYSTEM. Blower unit. (See BLOWER UNIT REMOVAL/INSTALLATION.) (See BLOWER UNIT DISASSEMBLY/ASSEMBLY.) Air filter

HVAC. (w) HVAC SYSTEM. Blower unit. (See BLOWER UNIT REMOVAL/INSTALLATION.) (See BLOWER UNIT DISASSEMBLY/ASSEMBLY.) Air filter HVAC HVAC SYSTEM Blower unit 1 (See BLOWER UNIT REMOVAL/INSTALLATION.) (See BLOWER UNIT DISASSEMBLY/ASSEMBLY.) Air filter 2 3 (See AIR FILTER REMOVAL/INSTALLATION.) (See AIR FILTER INSPECTION.) A/C unit

More information

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model GENUS PREMIUM FS CUENOD. R8216470-01EN - Edition 01-26/10/2009

SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model GENUS PREMIUM FS CUENOD. R8216470-01EN - Edition 01-26/10/2009 Instantaneous Gas Water Heaters Storage Gas Water Heaters SPARE PARTS EXPLODED VIEW GAS WALL BOILERS Model R8216470-01EN - Edition 01-26/10/2009 Boilers CUENOD Renewable 3121488 12 EAA1...... 3124527 25

More information

REQUEST FOR BIDS 2013-12 HVAC PREVENTATIVE MAINTENANCE AND SERVICE JANUARY 18, 2013. Issued by: NH Liquor Commission. PO Box 503, Concord, NH 03302

REQUEST FOR BIDS 2013-12 HVAC PREVENTATIVE MAINTENANCE AND SERVICE JANUARY 18, 2013. Issued by: NH Liquor Commission. PO Box 503, Concord, NH 03302 REQUEST FOR BIDS 2013-12 HVAC PREVENTATIVE MAINTENANCE AND SERVICE JANUARY 18, 2013 Issued by: NH Liquor Commission PO Box 503, Concord, NH 03302 This Page intentional left blank TABLE OF CONTENTS EXHIBITS...

More information

Gas-Fired, Residential Storage Type Water Heaters

Gas-Fired, Residential Storage Type Water Heaters Consulting, Resource, Education, Training, and Support Services for Home Inspectors A candle loses no light when it lights another candle. Gas-Fired, Residential Storage Type Water Heaters Most inspectors

More information

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE

ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE ESPD8-301R MODEL ESP-D FAN COIL UNIT TROUBLESHOOTING GUIDE Protected by one or more of the following U.S. Patents (3,507,354; 3,575,234; 3,596,936; 3,605,797; 3,685,329; 4,045,977; 4,698,982; 926,673 and

More information

FREQUENTLY ASKED QUESTIONS about HERS and CHEERS Provided by the California Energy Commission Consumer Energy Center

FREQUENTLY ASKED QUESTIONS about HERS and CHEERS Provided by the California Energy Commission Consumer Energy Center http://www.energy.ca.gov/ FREQUENTLY ASKED QUESTIONS about HERS and CHEERS Provided by the California Energy Commission Consumer Energy Center Relevant Standard The Residential Manual for Compliance with

More information

ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS. HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport.

ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS. HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport. ADDENDUM NO. 1 TO THE BIDDING DOCUMENTS DATE: May 6, 2016 HVAC SERVICE AND MAINTENANCE Saint Clair County MidAmerica Saint Louis Airport BIDS CLOSE: May 12, 2016, at 2:30 p.m., Local Time TO ALL BIDDERS

More information

Medical Air Systems: Scroll

Medical Air Systems: Scroll GENERAL The Chemetron skid mount scroll medical air system is designed to provide medical breathing air for hospital and medical institutions. This system meets NFPA 99 requirements for Level 1 breathing

More information

Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06

Heater and Air Conditioner, Blend Air System, Troubleshooting 83.06 A/C Performance Diagnosis Problem Warm Airflow When the Air Conditioner is On, A/C Not Working, or Poor A/C Performance (dash outlet temperature is too high) Problem Warm Airflow When the Air Conditioner

More information

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT

2 STEPS TO CONDUCTING YOUR HVAC ASSESSMENT Presentation Synopsis Heating, Ventilating and Air Conditioning Building Condition Assessment Vancouver, B.C. Prepared for: EPIC Prepared by: Douglas Spratt, P.Eng Douglas Spratt & Associates Ltd. www.dspratt-associates.com

More information

THE CASE FOR A REFRIGERATION PREVENTATIVE MAINTENACE PROGRAM

THE CASE FOR A REFRIGERATION PREVENTATIVE MAINTENACE PROGRAM THE CASE FOR A REFRIGERATION PREVENTATIVE MAINTENACE PROGRAM Prepared and Presented By: Don Langston President & CEO, Aire Rite Air Conditioning & Refrigeration Inc Setting the Foundation The Refrigeration

More information

Tankless Water Heater

Tankless Water Heater Tankless Water Heater USER S INFORMATION MANUAL Models WGRTNG199 / WGRTLP199 WGRTCNG199 / WGRTCLP199 NOTICE: Westinghouse reserves the right to make product changes or updates without notice and will not

More information

Center for Energy Education Laboratory

Center for Energy Education Laboratory Paper ID #7072 Center for Energy Education Laboratory Dr. Robert Gilbert, Sinclair Community College Robert B. Gilbert, Ph.D., LEED AP, BA, is an Associate Professor of Energy Management Technology, and

More information

Preventing Overheated Boiler Incidents

Preventing Overheated Boiler Incidents Preventing Overheated Boiler Incidents PSE&G Appliance Service October 2012 Runaway Boiler Explosion Review Items Hazard Background Past Incidents PSE&G Emergency Response Future Process Improvements What

More information

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53%

1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 1 1. What percent of a commercial business s energy usage comes from their HVAC system? A. 13% B. 23% C. 33% D. 43% E. 53% 2. How much money do commercial facilities spend per square foot on energy costs

More information