Industrial Applications. Annex (by Dominik Pieniazek, P.E. VI Engineering, LLC)

Similar documents
100% Stator Ground Fault Detection Implementation at Hibbard Renewable Energy Center. 598 N. Buth Rd 3215 Arrowhead Rd

INTRODUCTION TO SYSTEM PROTECTION. Hands-On Relay School 2012

Motor Protection Principles. Craig Wester GE Multilin

CIRCUIT BREAKER INTERRUPTING CAPACITY AND SHORT-TIME CURRENT RATINGS

PHASOR DIAGRAMS HANDS-ON RELAY SCHOOL WSU PULLMAN, WA. RON ALEXANDER - BPA

Short Circuit Current Calculations

SPECIAL TOPICS ON GROUND FAULT PROTECTION AND PROTECTION COORDINATION IN INDUSTRIAL AND COMMERCIAL POWER SYSTEMS

GE Protection and Control Business Department. Page 1 Date 5/11/99

UL guidelines, chapter 6.2 / 6.3 Motor Branch Circuits acc. to UL

Electronic Trip Circuit Breaker Basics Circuit Breaker Application Guide Class 0600

Shunt Capacitor Bank Fundamentals and Protection

Generator Stator Protection, under/over voltage, under /over frequency and unbalanced loading. Ramandeep Kaur Aujla S.NO

System Grounding and Ground-Fault Protection Methods for UPS-Supplied Power Systems

Low Voltage Transformer Through-Fault Protection: A System Approach

HIGH VOLTAGE CALCULATIONS / EVALUATIONS. West Virginia Office of Miners Health, Safety & Training

HV Substation Design: Applications and Considerations

Grounding of AC generators and switching the neutral in emergency and standby power systems

Simple Methods for Calculating Short Circuit Current Without a Computer By Dennis McKeown, PE GE Senior System Application Engineer

High Efficiency Motor Protection. Industry White Paper

Motor Protection Voltage Unbalance and Single-Phasing

MOTOR PROTECTION AGAINST SINGLE-PHASING

Digital Energy ITI. Instrument Transformer Basic Technical Information and Application

Power System Selectivity: The Basics of Protective Coordination

CONDUCTOR SHORT-CIRCUIT PROTECTION

VOLTAGE REGULATOR AND PARALLEL OPERATION

Step Voltage Regulators

Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules.

Transformer protection

CT Application Guide for the 489 Generator Management Relay

STANDARDS AND RATINGS FOR THE APPLICATION OF MOLDED CASE, INSULATED CASE, AND POWER CIRCUIT BREAKERS

Transformerless UPS systems and the 9900 By: John Steele, EIT Engineering Manager

Current Transformers Ratio / Polarity / Types

Guidelines on the Short Circuit Current Rating for Industrial Control Panels

Sentron Series Circuit Breakers

Understanding Power Factor and How it Affects Your Electric Bill. Presented by Scott Peele PE

Short-circuit, Protective Device Coordination & Arc Flash Analysis. By Albert Marroquin Operation Technology, Inc.

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

Line to Ground Voltage Monitoring on Ungrounded and Impedance Grounded Power Systems

IAV. Time Delay Voltage. For AC and DC circuit applications. GE Multilin 1. Protection and Control. Features and Benefits.

Data Bulletin. Circuit Breaker Characteristic Trip Curves and Coordination Class 0600 TRIP CURVES AND COORDINATION CIRCUIT BREAKER TRIP CURVES

Simplified Guide To Understanding Short-Circuit Current Rating FIND IT, FIX IT, FORGET IT

Typical Data Requirements Data Required for Power System Evaluation

GE Multilin technical note

2a. IEM Indoor Metal Clad Medium Voltage Switchgear 15KV a. Section INDOOR METAL CLAD MEDIUM VOLTAGE SWTICHGEAR (Std.

Power Quality Issues, Impacts, and Mitigation for Industrial Customers

Overcurrent Protection for the IEEE 34 Node Radial Test Feeder

PacifiCorp Original Sheet No. 476 FERC Electric Tariff, Substitute 6 th Rev Volume No. 11 APPENDIX 2 TO SGIP

Impact of Distributed Resources on Distribution Relay Protection

Neutral Currents in Three Phase Wye Systems

How To Choose A Transformer

The following table shows approximate percentage wise the

Transformer Protection Application Guide

Earth Fault Detection Basics in Theory

Pilot-wire differential relay for lines with two or more terminals

SPECIFICATION COG-2007

DC TRANSMISSION BASED ON VOLTAGE SOURCE CONVERTERS

Medium voltage circuit breaker

DIMENSIONING OF CURRENT TRANSFORMERS FOR PROTECTON APPLICATION

Eaton s E-Series protective relay family

Electrical network protection. Protection guide. Guide

Part 1 System Modeling & Studies for Existing Systems

Application of Four-Pole Circuit Breakers within Data Centers

3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?

IEC gg & am STANDARD LOW VOLTAGE FUSE

7. Reactive energy compensation

TA Kahraman Yumak ELK412 - Distribution of Electrical Energy Lab. Notes v Spring web.itu.edu.tr/yumakk. Distance Protection

Protection of Phase Angle Regulating Transformers

EE 221 Circuits II. Chapter 13 Magnetically Coupled Circuits

SELECTION OF CURRENT TRANSFORMERS & WIRE SIZING IN SUBSTATIONS. Sethuraman Ganesan ABB Inc. Allentown, PA

Cold Load Pickup Issues

Unified requirements for systems with voltages above 1 kv up to 15 kv

Integration of Distributed Generation in the Power System. IEEE Press Series on Power Engineering

ASK THE EXPERTS. Resistance Grounding Q&A. with industry experts

WHITE PAPER MOTOR PROTECTION. The Importance of Effective Motor and Motor Circuit Protection

Bussmann. All-In-One Module. Bussmann Power Module Switch. How to configure Part Numbers: Step 1: Select Switch Amperage 1

101 BASICS SERIES LEARNING MODULE 3: FUNDAMENTALS OF ELECTRICAL DISTRIBUTION. Cutler-Hammer

Effective: September 10, 2006 Vermont Attachment 1 to Rule Public Service Board Page 1 of 6

Primary-Side Transformer Protection

Product Data Bulletin

Hyperlinks are Inactive

Selecting Current Transformers Part 1 By Darrell G. Broussard, P.E.

Type SA-1 Generator Differential Relay

CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61

Rule Fast Track Analysis for National Life Insurance Co.

1 Introduction. 2 The Symmetrical Component Transformation. J.L. Kirtley Jr.

Corner-Grounded Delta (Grounded B Phase) Systems

Electrical network protection. Protection guide. Guide G 51G 51G 51G 51G. network protection solutions

Alternate Methods to Short Circuit Breaker Coordination

How To Understand The Electrical Power Supply Of A Power Supply System

OVERCURRENT & EARTH FAULT RELAYS. To study the protection of equipment and system by relays in conjunction with switchgear.

AC-Synchronous Generator

Percentage Restrained Differential, Percentage of What?

FIT TIER 2 Application

21 st Century Facilities

HPS Universal. Single and Three Phase Potted. Buck-Boost Transformers. Buck-Boost Applications & Standard Specification... 80

Introduction to Short Circuit Analysis

DISTRIBUTION RELIABILITY USING RECLOSERS AND SECTIONALISERS

GENERATOR SELECTION. a. Three phase - 120/208V, 3 phase, 4W wye; 277/408, 3 phase, 4W wye; * 120/240V 3 phase, 4W Delta

SUBJECT: How to wire a motor starter Number: AN-MC-004 Date Issued: 2/08/2005 Revision: Original

Chapter 24. Three-Phase Voltage Generation

Transcription:

Overcurrent Protection & Coordination for Industrial Applications Annex (by Dominik Pieniazek, P.E. VI Engineering, LLC)

Current Transformer Basics 2 50 50 50 50 Don t let polarity marks fool you!

Current Transformer Basics 3 ia ib ic ia+ib+ic 50 N Residual CT connection Protected Bus Ia Ib Ic ia+ib+ic G Zero sequence CT Bus NOT Protected

Current Transformer Basics 4 Understand How CTs work! IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes - IEEE Std C37.110

5 Basic Guides for Protective Relay Settings Suggested Rules of Thumb for MV Equipment Transformers Bus Feeders Motors Capacitors

6 Basic Guides for Protective Relay Settings Suggested Rules of Thumb for MV Equipment The intent of this section is to provide a range of typical settings. It is the engineer s responsibility to verify the application on an individual basis. This section does NOT apply to equipment 600 V and below. Care must be taken when coordinating a microprocessor TOC element with an electromechanical relay downstream. The electromechanical relay may respond to a fundamental phasor magnitude, true RMS, or rectified magnitude.

Rules of Thumb (above 600 V) Power Transformers Phase Relays (delta wye) Primary Phase Settings CT Ratio: 200% FLA Set pickup to comply with NEC 450-3, but as a rule of thumb setting should be less than 300% of transformer self cooled rating or 150% of transformer maximum rating. Try to set the time dial such that pickup time for maximum through fault is in the neighborhood of 1.0 seconds or less. If higher, ensure that ANSI damage points are not exceeded. d Set instantaneous at between 160% and 200% of maximum through fault (assume infinite bus). Ensure that available system short circuit allows this. Time Dial set at 1.0 to 1.5 seconds at maximum fault. Do not exceed 2.0 seconds which is the mechanical damage point.

Rules of Thumb (above 600 V) Power Transformers Primary Ground Relay Settings Primary Ground Settings Set 50G if primary winding is delta connected. Provide time delay (approx 20 msec) when setting digital relays with zero sequence CTs. No time delay when using elecro-mechanical relays with zero sequence CTs. CT considerations: Residually connected neutral. CT mismatch and residual magnetization will not allow the most sensitive setting. Recommend to delay above inrush. Zero sequence CT. Care must be taken to ensure that cables are properly placed and cable shields are properly terminated. Ia Ib Ic ia ib ia+ib+ic ic Ia ia+ib+icib i Ib 50 50 Ic G 50 N Residual CT connection Zero sequence CT

Rules of Thumb ( above 600 V) Power Transformers Primary Fuse Phase Protection Primary Fuse Rating of power transformer: 135% FLA < Fuse < 250% FLA. Try to stay in the range of 150%. Primary fuse rating of power transformer should be approximately 200% FLA if transformer has a secondary main. Generally use E-rated fuses. Note that TOC characteristics of fuses are not all the same.

Rules of Thumb ( above 600 V) Power Transformers Secondary Resistance Grounded Secondary Low-Resistance Grounded Set pickup for 20% to 50% of maximum ground fault. Note that ground resistors typically have a continuous rating of 25-50% of nominal. This value can be specified when purchasing the equipment. Example: 2000 A main breaker (2000:5 CTs), it may make sense to specify an 400 A ground resistor with a continuous rating of 50% (200 A) such that a 2000:5 residually connected CT input can be used with a minimum pickup (0.1 x CT = 0.5 A secondary, 200 A primary). Set the time dial such that at the time to trip is 2.0 seconds at maximum ground fault Protect resistor using I²t curve Typical resistor is rated for 10 seconds at Protect resistor using I t curve. Typical resistor is rated for 10 seconds at nominal current (to be specified at time of order).

Rules of Thumb ( above 600 V) Power Transformers Secondary Solidly Grounded Secondary Solidly Grounded (for balanced three phase industrial loads) If secondary is solidly grounded and neutral relay is available (using CT on X0 bushing), set pickup at approximately 50% of phase element and ensure transformer 2 second damage point is protected. Coordinate TOC with main breaker (or partial differential) ground relay. Decrease the primary phase element by 58% (to account for transformer damage curve shift). This is the equivalent current seen on the primary (delta) for a secondary ground fault (refer to the Symmetrical Components presentation ti on Feb 2-3, 2010 by Dr. Kurt Ederhoff).

Rules of Thumb ( above 600 V) Phase-Gnd 87T 50T T Protection for Transformer Secondary Faults on Solidly Grounded Systems It is certainly preferable to rely on the transformer primary phase overcurrent relay for backup of transformer secondary ground faults. However, downstream coordination does not always afford us that NT luxury (shifting the transformer damage curve and associated transformer primary relay 58%). Main N For solidly grounded transformer secondary installations, an argument can be made that the 87T is the primary protection and NT is the backup protection for a transformer secondary ground fault. This will allow you to set the 50T/T relay without consideration of the 58% shift.

Rules of Thumb ( above 600 V) Power Transformers Primary Neutral (wye delta) Pi Primary Side Wye-Grounded d Transformer If primary is solidly grounded and neutral relay is available, set pickup at approximately 50% of phase element. This must coordinate with upstream line protection devices (i.e. 21P, 21G, 67, 67G ). If it s at the utility level, they will review and provide settings. For generator step-up transformers (GSU), the HV NT should typically be the g p p ( ), yp y last device to trip for upstream ground faults. Ensure that the GSU damage curve and the H0 grounding conductor is protected.

Trip Direc ction Rules of Thumb ( above 600 V) 67 50T T B N.C. 67 B Set 67 pickup at 40% of transformer FLA. Coordinate with time curve with 50T/T 50T T Trip Dire ection Directional Overcurrent Consideration for transformer secondary fault For a fault between the transformer and main breaker, the partial differential bus relays will not detect current (other than motor contribution). Both transformer primary overcurrent relays will detect see the same current. A directional overcurrent relay is required to prevent tripping of both transformers via 50T/T.

Rules of Thumb ( above 600 V) 50T T M Tie 50T T M Directional Overcurrent Consideration for transformer secondary fault For a fault between the transformer and main breaker, the main and tie breaker relays will all see the same current (other than motor contribution). Trip Direction 67 N.C. 67 Trip Directio on The tie breaker will trip followed by the respective transformer primary overcurrent. A directional overcurrent relay is required to prevent loss of one bus. Set 67 pickup at 40% of transformer FLA. Coordinate with time curve with Tie

Rules of Thumb ( above 600 V) Bus and Feeders Bus Relays (Main Breaker or Partial Differential): Pickup set between 100% and 125% FLA (150% FLA maximum) Set to coordinate with transformer primary protective relaying Do not enable the instantaneous overcurrent element on main breaker relays! Feeder Relays: Set pickup to comply with NEC 240-100 (limited to 600% of rated ampacity of conductor). Actually, pickup permitted by NEC is slightly higher. Keep it down in the neighborhood of 200%. The intent is NOT to provide overload protection. The intent is to provide short-circuit protection. Set time dial as required to coordinate with downstream devices while protecting conductor against damage. Enable instantaneous element only if the load has a notable impedance (i.e. transformer, motor, capacitor, etc) or if the load is the end of a radial circuit.

Rules of Thumb ( above 600 V) Induction Motors Pickup set at 101% - 120% Nameplate Rating depending on Service Factor and normal load. Motor < 1,500 hp Motor > 1,500 hp Set at 1.15 x FLA Set just above FLA x S.F. Instantaneous Trip set at 200% LRC. A higher pickup p may be used depending on system available short circuit, however, do not lower below 160% LRC unless you know that the relay filters/removes the DC component. Ensure that the instantaneous trip setting will not cause a motor starter to attempt interrupting a fault beyond its rating. Ground Overcurrent. For Zero Sequence CT (BYZ) set ground Trip at 10A primary and Alarm at 5A primary. Set for instantaneous if using electromechanical and set at 20 msec delay y( (minimum) if using digital relays. For solidly grounded systems, ensure that the ground trip setting will not cause a motor starter to attempt interrupting a fault beyond its rating. Mechanical Jam set 150% FLA at 2 sec, unless application does not allow this (i.e. grinder, pp ( g crusher, etc).

Rules of Thumb ( above 600 V) Capacitors Capacitor Bank: For individual protection, the Fuse protecting the capacitor is chosen such that its continuous current capability is greater than or equal to 135% of rated capacitor current. The feeder cable should be sized as such for continuous operation. This over rating is due to 10% for allowable overvoltage conditions, 15% for capacitor kvar rating tolerance (this correlates to 15% percent deviation from nominal capacitance) and 10% for overcurrent due to harmonics. For unbalance, set Alarm for loss of one capacitor, set Trip for overvoltage of 110% rated (nameplate). For feeder protection, set Pickup at 135% of FLA, set Time Dial at 1.0, set 50P element above maximum inrush and include a slight time delay to coordinate with individual fuse clear time. Plot TOC to protect the capacitor case rupture curve. Note: Systems with high harmonic content require special attention.

Recommended d References

Recommended References Applied Protective Relaying Westinghouse Protective P t ti Relaying Theory and Applications ABB Power T&D Company, Edited d by Walter Elmore Protective Relaying for Power Systems IEEE Press, Edited by Stanley H. Horowitz Protective Relaying for Power Systems II IEEE Press, Edited by Stanley H. Horowitz Protective Relaying, Principles and Applications J. Lewis Blackburn AC Motor Protection Stanley E. Zocholl Industrial and Commercial Power System Applications Series ABB Power T&D Company Analyzing and Applying Current Transformers - Stanley E. Zocholl