1 FUSES Catalogue
2
3 CEF 9 CEF-S 23 CEF-VT 27 CMF 31 WBP 39 WBT 47 BPS 61
4 INTRODUCTION The main function of current limiting fuses is to protect electrical apparatus, such as distribution transformers, motors and capacitor banks against overload currents. The fuses can operate as sole devices or can be combined with air/sf6 insulated switch disconnectors. The choice depends on each application requirements and specific network conditions. One of the most critical factors for optimum protection is proper fuse selection. This can be done based on theoretical calculations but in many cases practical knowledge obtained from actual test results could make it easier and even more reliable. ABB, with its extensive apparatus product portfolio, has years of experience in this field. Our current limiting fuses have been designed to ensure safe operation in open air and for limited heat dissipation in installations such as that found in gas insulated switchgears. Fuse selection principles for the most common situations are presented in the following pages together with common definitions. Moreover we offer our support for each specific case where presented criteria are not sufficient. Before using our products, we encourage you to read the technical definitions and application principles presented below. MAIN DEFINITIONS Current limiting back-up fuses The current limiting fuse family is generally composed of three different fuse groups: back-up fuses, general purpose fuses and full range fuses. All of them limit the value of prospective short-circuit currents during the interruption process, thereby extending the life time of nearby installed electrical equipment. The main difference is in the minimum breaking current that characterizes the lowest fault current that fuses are capable of interrupting. This value is generally highest for back-up fuses, slightly smaller for general purpose fuses and smallest, with the value close to the minimum melting current, for full range fuses. But reaction time is critical for the protection function. That is why back-up fuses, with an interruption time for the minimum breaking current in the range of a few seconds down to a few tens of milliseconds, are the most commonly used. The total clearing time in cases of high short-circuit currents is even shorter i.e. only a few milliseconds. That is why back-up fuses can be used as typical overload protection elements. General purpose and full range fuses capable of interrupting even the smallest values of currents can only be considered as over current devices since the interruption time is greater than one hour. ABB current limiting fuses have low minimum breaking currents, i.e. close to three times the rated current, In. M-effect One of the structural means used to form the time-current characteristics of medium-voltage fuse links for ABB s CEF and CMF series is an overload spot located on the fuse elements. The M-effect is used to create this overload spot which is made by coating the silver fuse elements with a short segment of a metal which is characterized by a low melting point. The M-effect was first described by Professor Metcalf in the 1930s. It takes advantage of the effect of the melting of metals characterized by a higher melting point (e.g. copper, silver) by some metals in a liquid state which are characterized by a low melting point (e.g. tin, lead). Silver fuse elements coated with a segment of a metal with a low melting point (e.g. solder) fuse for current values that would otherwise not cause fusing if the overload spot were not present. The reason for this is as follows: As the fuse element is heated, the metal used to make the overload spot starts melting and diffuses into the fuse element metal, thus reducing the active cross-section of the main silver fuse element. As a result, the silver fuse element is melted at the moment when the other parts of the fuse element are, by comparison, still relatively cool. With this design the overload spot reduces both the minimum melting current and the minimum breaking current. Consequently, the operating range of the fuse link is extended. It must also be emphasized that in case of short-circuit currents, when fuse elements quickly heat up and practically no heat is dissipated into the surrounding arc-quenching medium (adiabatic heating), the fuse elements melt before the metal used for making the overload spot reaches its melting temperature. Therefore, the overload spot does not affect the fuse s characteristic for short-circuit currents. Additionally, a very important advantage of using the overload spot is the fact that an arc is always initiated at the same point on the fuse element, i.e. near the geometrical center of the fuse link. This solution therefore protects the end-caps from sustaining any damage. To sum up, the overload spot enables an increase in the useful operational range of the fuse link by extending the range of correct operation for small overload currents. Moreover, use of the overload spot prevents the arc from initializing near one of the fuse-link ends and, thus, makes the fuse link safer to use. Fuse-switch combination Back-up fuses are commonly used in fuse-switch combinations, both in open air and in gas insulated panels. When a fuse-switch combination operates as a protective device by tripping a system, the fuse assumes two different functions depending on the interrupted current value. When the fault current is greater than the transfer current, the fuse simply extends the breaking capability of the switch disconnector by completing the interruption operation faster than the incorporated switch. This happens when the fuse clearing time is shorter than the total opening time of the Load Break Switch (LBS). By the time the striker pin pops up, the fuse has already cleared the fault current and the switch opens in almost no load conditions. If the fault currents are less 4 ABB
5 than the nominal transfer current, the fuse then uses the striker pin to activate the switch, which in turn causes the system to trip. In other words, the interruption process is completed by the switch to prevent overloading of the fuses in situations where the fault current is low. Fuses used in fuse-switch combinations have to fulfill conditions specified in IEC (former IEC and IEC 420). Back-up fuses are specially designed for such an application. The use of general purpose or full range fuses in fuse-switch combinations is not reasonable due to coordination principles. ABB HV FUSES WITH TEMPERATURE CONTROL UNIT The Temperature Control Unit (TCU) is a tripping device which is integrated with the striker of high-voltage (HV) fuses. It is activated when the allowable temperature in the switchgear is exceeded. When the temperature is too high the TCU activates the striker by releasing the switch disconnector, which in turn opens the electric circuit and avoids further temperature increases. TCU parameters: a) Operation for approximately one hour at 150 C on the fuse end-cap b) Withstanding temperatures up to 125 C on the fuse end-cap c) I 1.1xIn - no operation With reference to the diagram above, the higher the temperature, the faster the striker operation. The high temperatures inside the switchgear interior may be caused by external conditions or by a high current passing through the fuse-link. Other possible reasons include: Reduced heat transfer inside the switchgear Over-heating of degraded conducting contacts Long-term fuse overloads Improper selection of the fuse rating Local melting of fuse elements caused by transformer inrush currents, starting currents of motors etc. Safety is significantly increased when fuses are equipped with a TCU. This is especially true in devices where fuses are located inside closed fuse holders, as is the case in SF6 switchgear. However, in gas insulated switchgear fuse canisters or in the narrow panels of air switchgear the risk of overheating is high because cooling is limited. High temperatures in switchgears cause degradation and oxidation of the metal contacts, degradation of switchgear equipment or enclosures, and insulator ageing. Unfavorable effects, i.e. temperature rise inside the switchgear, leads to internal short-circuit and further temperature increases. Fuse links equipped with a TCU are compatible with standard fuse links. Striker force and striker energy, as well as dimensions and all fuse ratings, are in accordance with CEF, CEF-S, CEF-VT and CMF type fuses manufactured to date and with IEC Standards. To differentiate fuses with a TCU from standard fuses, additional catalogue numbers have been generated and special markings on the fuse body are provided. Markings on the striker label and rating plate of a fuse with TCU: Temperature Control Unit ABB 5
6 GENERAL PRINCIPLES FOR FUSE LINK SELECTION Choice of rated current In To obtain the best possible current limitation and thereby protection, the rated current, In, must be as low as possible compared to the rated current of the object to be protected. However, the following limitations must be taken into consideration: The largest load current must not exceed In Cooling conditions (e.g. in compact switchgear) Inrush current of off load transformers Starting currents of motor circuits. (See Chapter CMF, special motor fuses) Protection of capacitor banks HRC fuses are normally connected in series with capacitor units or banks. They are activated when these units become faulty under normal operating voltages, including the transient voltage as the capacitors are being energized. That is why the chosen fuse-link rated voltage should not be less than 1.1 times that of the rated voltage of the capacitor unit. As recommended in IEC 60549, the rated current of the fuse should be at least 1.43 times that of the capacitor s rated current. In practice we can distinguish two general cases: Only one capacitor bank connected Selected rated current, In, for the fuses should be at least twice the rated current, Inc, of the capacitor bank. The rated voltage, Un, should also be at least twice Unc. In 2xInc Un 2xUnc Example 315 kvar capacitor bank with 10 kv Unc. Inc = 315 = 18,2 A 10 x 3 Selected fuses: In = 40 A; Un = 24 kv More than one capacitor connected in parallel While including the possibility of reloading i.e. transmitting from a load capacitor bank to an unloaded condition, very high transient currents may occur. The rated current, In, of the fuses should be selected so that it is more than three times the Inc of the capacitor banks. Because a wide variation in transient currents may occur, ABB recommends that the calculation be discussed with the supplier of the capacitors. Application in SF6 switchgears CEF fuses were designed to be applied inside gas insulated switchgears. The interaction between fuses and switch disconnectors when limited heat dissipation conditions occur is not an easy task. This knowledge has been obtained mainly from practical tests performed under different loading conditions. First the maximum allowable power losses should be defined for the fuses so as not to exceed temperature rise limits according to the referred standard. Therefore, the rated current of fuses with power losses above this limit are de-rated to a safe level that takes into consideration the fuse load factor. This procedure should be verified by temperature rise and breaking tests. ABB uses this standard approach for SF6 switchgear and CEF fuses. For detailed information regarding the correct choice of ABB fuses for transformer protection in SF6 switchgear please refer to switchgear catalogue data. Replacement of melted fuse links HRC fuse links cannot be regenerated. According to IEC Publication (IEC 282-1), all three fuse links should be replaced even if only one of them in a three phase system melts. Exceptions are allowed when it can be verified that the fuse link(s) have not experienced any overcurrent. INDICATOR AND STRIKER PIN CEF and CMF fuses are equipped with a combined indicator- and striker system which is activated immediately when the fuse element melts. CEF-VT is available with and without a striker pin please refer to the ordering tables. The force diagram is in accordance with the requirements of IEC (IEC 282-1) and DIN ABB
7 The striker pin force diagram shown below is valid for CEF/CMF fuses and has been available since May The former version of the striker pin was rated for an initial force of 50N. NAMEPLATE The symbols on the nameplate have the following meaning: In = current Un = voltage I 3 = Minimum breaking current I 1 = Maximum short circuit current for which the fuse is tested The arrowhead on the nameplate indicates at which end of the fuse link the indicator and striker pin appears. Additionally this end contact of the fuse link is specially marked. CEF-U indicates an outdoor type. STRIKER - SCHLAGSTIFT Prod. year IEC CEF HV Back-up fuse link I N = 6A I 3 = 35A U = 12kV I 1 = 63kA N 60N Striker MADE by ABB INDOOR - INNENRAUM Cat. number 1YMB531002M0001 A typical ABB CEF fuse nameplate is shown above. The information presented varies for specific fuse types. All CEF and CMF fuses are marked with EAN 13 codes (on their carton boxes). These are specified in the ordering tables and are positioned to the right of the catalogue numbers. An example of this nameplate is presented below. FUSE-LINK CEF 7.2kV-6A EAN13 Bar code e/d: 192/65 Prod. year: 02/2007 Cat. no: 1YMB531001M0001 CURRENT LIMITATION All ABB fuse links presented are current limiting ones. A large short-circuit current will therefore not reach its full value. The cut-off characteristics show the relationship between the prospective short-circuit current and the peak value of the cut-off current. Substantial current limitation results in a considerable reduction in thermal and mechanical stress in a high-voltage installation. ABB 7
8
9 High voltage current limiting Fuse links type CEF Index 1. GENERAL OVERVOLTAGES PRE-ARCING TIMES CHOICE OF FUSE LINKS ORDERING TABLE ORDERING TABLE CEF-TCU 7. DATA AND DIMENSIONS CEF & CEF-TCU ACCESSORIES ORDERING TABLE DATA AND DIMENSION CEF-BS DATA AND DIMENSION CEF-BS ACC. TO IEC : ABB 9
10 High voltage current limiting Fuse links type CEF voltage: 3.6/ kv 1. GENERAL The HRC generation of fuse links type CEF is designed and tested according to IEC Publication (IEC 282-1). Dimensionally the fuse links are in accordance with DIN ABB s high-voltage fuse links have the following properties: Low minimum breaking current Low power losses Low arc voltage High breaking capacity up to 63 ka High current limitation. Low power losses permit installation of these fuse links in compact switchgear. CEF fuses are of a back-up type. They have a zone between the minimum melting current and the minimum breaking current where the fuse links may fail to interrupt. For CEF fuse links this zone is very narrow. The minimum breaking current, I 3, for any type is specified in the table on pages 17 and OVERVOLTAGES In order to be current limiting, the fuse link must generate an arc voltage that exceeds the instantaneous value of the operating voltage. The switching voltage generated by the CEF fuse link is below the maximum permissible value according to IEC (IEC 282-1). The CEF fuse link can safely be used if the system line voltage is % of the rated fuse-link voltage. 3. PRE-ARCING TIMES AND CUT-OFF CHARACTERISTICS The characteristics are equal for all rated voltages and are recorded under cold conditions. Dashed sections of the curves indicate an area of uncertain interruption Pre-arcing Time A 10A 16A 20A 25A 31.5A 40A 50A 63A 80A 100A A A 200A Remarks: 1. Characteristics show the average melting time as a function of the prospective current The deviation of 10% refers to the current The characteristics are valid for all rated voltages and are recorded from fuse-link cold condition Prospective current [A] Broken line indicates the uncertain interrupting zone. 10 ABB
11 High voltage current limiting Fuse links type CEF 10 0 ka Maximum cut-off current [ka] (peak) J p 100 ka Prospective current [ka] (rms) 4. CHOICE OF FUSE LINKS Choice of rated current In In order to choose the correct fuse-link rated current for transformer protection, the relation between the power rating of the transformers, and the operating voltage and rated current of the fuse link is given in the table overleaf. For the correct choice of fuse links for transformer protection in switchgear type SafeRing, SafePlus and SafeLink, see SF6 Insulated Compact Switchgear and Ring Main Unit catalogue. ABB 11
12 High voltage current limiting Fuse links type CEF Choice of fuse links for transformer protection Transformer rated voltage [kv] Transformer rating [kva] CEF Fuse-link In [A] Fuse rated voltage [kv] x x x x / x x x160 2x200 2x x160 2x x100 2x x100 2x x x25 2x x25 2x40 2x40 1 CMF fuse link The table was calculated according to standards IEC and IEC The following transformer work conditions were assumed: Maximum long-lasting overload 150% Magnetizing inrush current 12 In during 100ms Transformer short-circuit voltage according to IEC Standard ambient working conditions of fuses The table above details the rated current of a particular fuse link for a given line voltage and transformer rating. For different criteria, the fuse selection must be recalculated. 12 ABB
13 High voltage current limiting Fuse links type CEF 5. ORDERING TABLE High-voltage HRC fuse links Type voltage [kv] current [A] Length e [mm] Diameter D [mm] Catalogue No. EAN13 Codes CEF 3.6/ YMB531001M CEF 3.6/ YMB531001M CEF 3.6/ YMB531001M CEF 3.6/ YMB531001M CEF 3.6/ YMB531001M CEF 3.6/ YMB531001M CEF 3.6/ YMB531001M CEF 3.6/ YMB531001M CEF 3.6/ YMB531001M CEF 3.6/ YMB531034M CEF 3.6/ YMB531034M CEF 3.6/ YMB531034M CEF 3.6/ YMB531034M CEF 3.6/ YMB531034M CEF 3.6/ YMB531034M CEF 3.6/ YMB531034M CEF 3.6/ YMB531034M CEF 3.6/ YMB531034M CEF 3.6/ YMB531001M CEF 3.6/ YMB531001M CEF 3.6/ YMB531001M CEF 3.6/ YMB531034M CEF 3.6/ YMB531034M CEF 3.6/ YMB531034M CEF YMB531042M CEF YMB531002M CEF YMB531042M CEF YMB531002M CEF YMB531042M CEF YMB531002M CEF YMB531042M CEF YMB531002M CEF YMB531002M CEF YMB531002M CEF YMB531002M CEF YMB531002M CEF YMB531002M CEF YMB531002M CEF YMB531002M CEF YMB531002M CEF YMB531043M CEF YMB531047M CEF YMB531035M CEF YMB531047M CEF YMB531035M CEF YMB531047M CEF YMB531035M CEF YMB531047M CEF YMB531035M CEF YMB531035M CEF YMB531035M CEF YMB531035M CEF YMB531035M CEF YMB531035M CEF YMB531035M CEF YMB531035M CEF YMB531035M CEF YMB531002M CEF YMB531002M CEF YMB531002M CEF YMB531002M CEF YMB531035M CEF YMB531035M CEF YMB531035M CEF YMB531035M CEF YMB531003M CEF YMB531003M CEF YMB531003M CEF YMB531003M CEF YMB531003M CEF YMB531003M CEF YMB531003M CEF YMB531003M CEF YMB531003M CEF YMB531003M CEF YMB531003M Weight [kg] ABB 13
14 High voltage current limiting Fuse links type CEF Type voltage [kv] current [A] Length e [mm] Diameter D [mm] Catalogue No. EAN13 Codes CEF YMB531036M CEF YMB531036M CEF YMB531036M CEF YMB531036M CEF YMB531036M CEF YMB531036M CEF YMB531036M CEF YMB531036M CEF YMB531036M CEF YMB531036M CEF YMB531036M CEF YMB531038M CEF YMB531037M CEF YMB531037M CEF YMB531037M CEF YMB531037M CEF YMB531037M CEF YMB531037M CEF YMB531037M CEF YMB531037M CEF YMB531037M CEF YMB531037M CEF YMB531037M CEF YMB531003M CEF YMB531003M CEF YMB531003M CEF YMB531037M CEF YMB531037M CEF YMB531037M CEF YMB531044M CEF YMB531004M CEF YMB531044M CEF YMB531004M CEF YMB531044M CEF YMB531004M CEF YMB531044M CEF YMB531004M CEF YMB531004M CEF YMB531004M CEF YMB531004M CEF YMB531004M CEF YMB531004M CEF YMB531004M CEF YMB531004M CEF YMB531022M CEF YMB531022M CEF YMB531022M CEF YMB531004M CEF YMB531004M CEF YMB531004M CEF YMB531004M CEF YMB531004M CEF YMB531005M CEF YMB531005M CEF YMB531005M CEF YMB531005M CEF YMB531005M CEF YMB531005M CEF YMB531005M CEF YMB531005M CEF YMB531005M CEF YMB531006M CEF YMB531006M CEF YMB531006M CEF YMB531006M CEF YMB531006M Other ratings and dimensions on request. When ordering outdoor version pls. indicate CEF U. Weight [kg] 14 ABB
15 High voltage current limiting Fuse links type CEF 6. ORDERING TABLE CEF-TCU Type voltage [kv] current [A] Length e [mm] Diameter D [mm] Catalogue No. CEF-TCU 3.6/ YMB531851M CEF-TCU 3.6/ YMB531851M CEF-TCU 3.6/ YMB531851M CEF-TCU 3.6/ YMB531851M CEF-TCU 3.6/ YMB531851M CEF-TCU 3.6/ YMB531851M CEF-TCU 3.6/ YMB531851M CEF-TCU 3.6/ YMB531851M CEF-TCU 3.6/ YMB531851M CEF-TCU 3.6/ YMB531884M CEF-TCU 3.6/ YMB531884M CEF-TCU 3.6/ YMB531884M CEF-TCU 3.6/ YMB531884M CEF-TCU 3.6/ YMB531884M CEF-TCU 3.6/ YMB531884M CEF-TCU 3.6/ YMB531884M CEF-TCU 3.6/ YMB531884M CEF-TCU 3.6/ YMB531884M CEF-TCU 3.6/ YMB531851M CEF-TCU 3.6/ YMB531851M CEF-TCU 3.6/ YMB531851M CEF-TCU 3.6/ YMB531884M CEF-TCU 3.6/ YMB531884M CEF-TCU 3.6/ YMB531884M CEF-TCU YMB531892M CEF-TCU YMB531852M CEF-TCU YMB531892M CEF-TCU YMB531852M CEF-TCU YMB531892M CEF-TCU YMB531852M CEF-TCU YMB531892M CEF-TCU YMB531852M CEF-TCU YMB531852M CEF-TCU YMB531852M CEF-TCU YMB531852M CEF-TCU YMB531852M CEF-TCU YMB531852M CEF-TCU YMB531852M CEF-TCU YMB531852M CEF-TCU YMB531852M CEF-TCU YMB531897M CEF-TCU YMB531885M CEF-TCU YMB531897M CEF-TCU YMB531885M CEF-TCU YMB531897M CEF-TCU YMB531885M CEF-TCU YMB531897M CEF-TCU YMB531885M CEF-TCU YMB531885M CEF-TCU YMB531885M CEF-TCU YMB531885M CEF-TCU YMB531885M CEF-TCU YMB531885M CEF-TCU YMB531885M CEF-TCU YMB531885M CEF-TCU YMB531885M CEF-TCU YMB531852M CEF-TCU YMB531852M CEF-TCU YMB531852M CEF-TCU YMB531852M CEF-TCU YMB531885M CEF-TCU YMB531853M CEF-TCU YMB531853M CEF-TCU YMB531853M CEF-TCU YMB531853M CEF-TCU YMB531853M CEF-TCU YMB531853M CEF-TCU YMB531853M CEF-TCU YMB531853M CEF-TCU YMB531853M CEF-TCU YMB531853M CEF-TCU YMB531853M CEF-TCU YMB531886M CEF-TCU YMB531886M CEF-TCU YMB531886M CEF-TCU YMB531886M Weight [kg] ABB 15
16 High voltage current limiting Fuse links type CEF Type voltage [kv] current [A] Length e [mm] Diameter D [mm] Catalogue No. Weight [kg] CEF-TCU YMB531886M CEF-TCU YMB531886M CEF-TCU YMB531886M CEF-TCU YMB531886M CEF-TCU YMB531886M CEF-TCU YMB531886M CEF-TCU YMB531886M CEF-TCU YMB531888M CEF-TCU YMB531887M CEF-TCU YMB531887M CEF-TCU YMB531887M CEF-TCU YMB531887M CEF-TCU YMB531887M CEF-TCU YMB531887M CEF-TCU YMB531887M CEF-TCU YMB531887M CEF-TCU YMB531887M CEF-TCU YMB531887M CEF-TCU YMB531887M CEF-TCU YMB531853M CEF-TCU YMB531853M CEF-TCU YMB531853M CEF-TCU YMB531894M CEF-TCU YMB531854M CEF-TCU YMB531894M CEF-TCU YMB531854M CEF-TCU YMB531894M CEF-TCU YMB531854M CEF-TCU YMB531894M CEF-TCU YMB531854M CEF-TCU YMB531854M CEF-TCU YMB531854M CEF-TCU YMB531854M CEF-TCU YMB531854M CEF-TCU YMB531854M CEF-TCU YMB531854M CEF-TCU YMB531854M CEF-TCU YMB531872M CEF-TCU YMB531872M CEF-TCU YMB531872M CEF-TCU YMB531854M CEF-TCU YMB531854M CEF-TCU YMB531854M CEF-TCU YMB531854M CEF-TCU YMB531854M CEF-TCU YMB531855M CEF-TCU YMB531855M CEF-TCU YMB531855M CEF-TCU YMB531855M CEF-TCU YMB531855M CEF-TCU YMB531855M CEF-TCU YMB531855M CEF-TCU YMB531855M CEF-TCU YMB531855M CEF-TCU YMB531856M CEF-TCU YMB531856M CEF-TCU YMB531856M CEF-TCU YMB531856M CEF-TCU YMB531856M ABB
17 7. DATA AND DIMENSIONS CEF & CEF-TCU High voltage current limiting Fuse links type CEF Type voltage [kv] current [A] Length e [mm] Diameter D [mm] Short Circuit current I 1 [ka] Minimum breaking current I 3 [A] Power Pn [W] Resistance R O [mω] CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU 3.6/7/ CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU ABB 17
18 High voltage current limiting Fuse links type CEF Type voltage [kv] current [A] Length e [mm] Diameter D [mm] Short Circuit current I 1 [ka] Minimum breaking current I 3 [A] Power Pn [W] Resistance R O [mω] CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU CEF/CEF-TCU I 1 = maximum short-circuit current tested I 3 = minimum breaking current Pn = power loss at rated current R o = resistance at room temp. D Ø45 34 e 34 Ø45 D 18 ABB
19 45 High voltage current limiting Fuse links type CEF 8. ACCESSORIES Fuse-base type UCE Fuse clips Catalogue No. 1YMX000128M ORDERING TABLE voltage Current ratings Fuse length Type Dimensions in mm Weight Catalogue No. kv A mm A A1 A2 H K K1 B kg UCE / YMX052501M0001 UCE12 3.6/ YMX052503M0001 1YMX052503M0001 UCE 12L YMX052505M0001 UCE YMX052507M0001 UCE YMX052509M0001 1YMX052509M0001 UCE 24L YMX052511M0001 UCE YMX052513M0001 CEF test fuse-link 3.6/ kv for test of striker system. Catalogue No. Weight [kg] 1YMX300062M Dimension in mm e* Total lenght * ) Adjustable The striker has a force-travel characteristic as shown in the figure on page Operating tong for fuse links CEF 3.6/ kv Catalogue No. Test voltage [kv] Weight [kg] 1YMX053006M Dimensions in mm L1 L2 A3(Ø) ABB 19
20 High voltage current limiting Fuse links type CEF 10. DATA AND DIMENSION CEF-BS Type voltage [kv] current [A] L/D [mm] A [mm] Catalogue No. EAN13 Codes CEF-BS 3.6/ / YMB531007M CEF-BS 3.6/ / YMB531007M CEF-BS 3.6/ / YMB531007M CEF-BS 3.6/ / YMB531007M CEF-BS 3.6/ / YMB531007M CEF-BS 3.6/ / YMB531007M CEF-BS 3.6/ / YMB531007M CEF-BS 3.6/ / YMB531007M CEF-BS 3.6/ / YMB531007M CEF-BS 3.6/ / YMB531007M CEF-BS 3.6/ / YMB531007M CEF-BS 3.6/ / YMB531007M CEF-BS / YMB531008M CEF-BS / YMB531008M CEF-BS / YMB531008M CEF-BS / YMB531008M CEF-BS / YMB531008M CEF-BS / YMB531008M CEF-BS / YMB531008M CEF-BS / YMB531008M CEF-BS / YMB531008M CEF-BS / YMB531008M CEF-BS / YMB531008M CEF-BS / YMB531008M CEF-BS / YMB531009M CEF-BS / YMB531009M CEF-BS / YMB531009M CEF-BS / YMB531009M CEF-BS / YMB531009M CEF-BS / YMB531009M CEF-BS / YMB531009M CEF-BS / YMB531009M CEF-BS / YMB531009M CEF-BS / YMB531009M CEF-BS / YMB531010M CEF-BS / YMB531010M CEF-BS / YMB531010M CEF-BS / YMB531010M CEF-BS / YMB531010M CEF-BS / YMB531010M CEF-BS / YMB531010M CEF-BS / CEF-BS / CEF-BS / Dimension CEF-BS-B Dimension CEF-BS-C Dimension CEF-BS Dimension CEF-BS-D 20 ABB
21 High voltage current limiting 11. DATA AND DIMENSION CEF-BS ACC. TO IEC :1996 Fuse links type CEF Type voltage [kv] current [A] L/D [mm] A/d [mm] Catalogue No. EAN13 Codes CEF-BS-B 3.6/ /65 340/40 1YMB531007M CEF-BS-B 3.6/ /65 340/40 1YMB531007M CEF-BS-B 3.6/ /65 340/40 1YMB531007M CEF-BS-B 3.6/ /65 340/40 1YMB531007M CEF-BS-B 3.6/ /65 340/40 1YMB531007M CEF-BS-B 3.6/ /65 340/40 1YMB531007M CEF-BS-B 3.6/ /65 340/40 1YMB531007M CEF-BS-B 3.6/ /87 340/40 1YMB531007M CEF-BS-B 3.6/ /87 340/40 1YMB531007M CEF-BS-D 3.6/ /87 461/50.5 1YMB531007M CEF-BS-D 3.6/ /87 461/50.5 1YMB531007M CEF-BS-D 3.6/ /87 461/50.5 1YMB531007M CEF-BS-D /65 461/50.5 1YMB531008M CEF-BS-D /65 461/50.5 1YMB531008M CEF-BS-D /65 461/50.5 1YMB531008M CEF-BS-D /65 461/50.5 1YMB531008M CEF-BS-D /65 461/50.5 1YMB531008M CEF-BS-D /65 461/50.5 1YMB531008M CEF-BS-D /65 461/50.5 1YMB531008M CEF-BS-D /87 461/50.5 1YMB531008M CEF-BS-D /87 461/50.5 1YMB531008M CEF-BS-B /87 590/40 1YMB531008M CEF-BS-B /87 590/40 1YMB531008M CEF-BS-B /87 590/40 1YMB531008M CEF-BS-D /65 461/50.5 1YMB531009M CEF-BS-D /65 461/50.5 1YMB531009M CEF-BS-D /65 461/50.5 1YMB531009M CEF-BS-D /65 461/50.5 1YMB531009M CEF-BS-D /87 461/50.5 1YMB531009M CEF-BS-D /87 461/50.5 1YMB531009M CEF-BS-D /87 461/50.5 1YMB531009M CEF-BS-B /87 590/40 1YMB531009M CEF-BS-B /87 590/40 1YMB531009M CEF-BS-B /87 590/40 1YMB531009M CEF-BS-B /65 590/40 1YMB531010M CEF-BS-B /65 590/40 1YMB531010M CEF-BS-B /65 590/40 1YMB531010M CEF-BS-B /65 590/40 1YMB531010M CEF-BS-B /65 590/40 1YMB531010M CEF-BS-B /87 590/40 1YMB531010M CEF-BS-B /87 590/40 1YMB531010M CEF-BS-C 3.6/ /65 340/40 1YMB531007M CEF-BS-C 3.6/ /65 340/40 1YMB531007M CEF-BS-C 3.6/ /65 340/40 1YMB531007M CEF-BS-C 3.6/ /65 340/40 1YMB531007M CEF-BS-C 3.6/ /65 340/40 1YMB531007M CEF-BS-C 3.6/ /65 340/40 1YMB531007M CEF-BS-C 3.6/ /65 340/40 1YMB531007M CEF-BS-C 3.6/ /87 340/40 1YMB531007M CEF-BS-C 3.6/ /87 340/40 1YMB531007M CEF-BS-C 3.6/ /65 361/50.5 1YMB531007M CEF-BS-C 3.6/ /65 361/50.5 1YMB531007M CEF-BS-C 3.6/ /65 361/50.5 1YMB531007M CEF-BS-C 3.6/ /65 361/50.5 1YMB531007M CEF-BS-C 3.6/ /65 361/50.5 1YMB531007M CEF-BS-C 3.6/ /65 361/50.5 1YMB531007M CEF-BS-C 3.6/ /65 361/50.5 1YMB531007M CEF-BS-C 3.6/ /87 361/50.5 1YMB531007M CEF-BS-C 3.6/ /87 361/50.5 1YMB531007M CEF-BS-C 3.6/ /87 440/40 1YMB531007M CEF-BS-C 3.6/ /87 440/40 1YMB531007M CEF-BS-C 3.6/ /87 440/40 1YMB531007M CEF-BS-C /65 440/40 1YMB531008M CEF-BS-C /65 440/40 1YMB531008M CEF-BS-C /65 440/40 1YMB531008M CEF-BS-C /65 440/40 1YMB531008M CEF-BS-C /65 440/40 1YMB531008M CEF-BS-C /65 440/40 1YMB531008M CEF-BS-C /65 440/40 1YMB531008M CEF-BS-C /87 440/40 1YMB531008M CEF-BS-C /87 440/40 1YMB531008M CEF-BS-C /65 440/40 1YMB531009M CEF-BS-C /65 440/40 1YMB531009M CEF-BS-C /65 440/40 1YMB531009M CEF-BS-C /65 440/40 1YMB531009M CEF-BS-C /87 440/40 1YMB531009M CEF-BS-C /87 440/40 1YMB531009M CEF-BS-C /87 440/40 1YMB531009M ABB 21
22
23 High voltage current limiting Fuse links type CEF-S Index 1. GENERAL DIMENSIONS AND ELECTRICAL DATA TIME-CUERRENT CHARACTERISTICS FUSE SELECTION TABLE FOR TRANSFORMER PROTECTION FUSE POWER LOSSES AT TRANSFORMER RATED CURRENT ORDERING TABLE CEF-S & CEF-S-TCU 26 ABB 23
24 High voltage current limiting Fuse links type CEF-S 1. GENERALY As seen in the data table, high-voltage current limiting fuse links type CEF-S has a minimum current value (I 0.1sec ) which allows the fuse link to interrupt the fault current within 100 ms. This ensures very good protection and prevents faults in low-voltage switchgears. The current value for the different fuse-link types is shown for the total maximum breaking time of 100 ms. For bigger fault currents the maximum total breaking time will be shorter. CEF-S fuses are specially designed to achieve the lowest possible breaking current value at 100 ms. However, this results in a reduced margin, which for standard CEF fuses, prevents fuse-link operation due to inrush currents developed when an unloaded power transformer is energized. At any given value of I 0.1sec, the total breaking time is a maximum of 100ms this value includes maximum pre-arcing time, arcing time and production tolerance. 2. DIMENSIONS AND ELECTRICAL DATA CEF-S & CEF-S-TCU Un In e D I 1 I 3 I 0.1sec Pn V R o [kv] [A] [mm] [mm] [ka] [A] [A] [W] [kg] [m ] CEF Symbols ABB e = see figure D = see figure e I 1 = maximum rated breaking current I 0.1 sec = lowest current which gives maximum breaking time smaller than or equal to 100ms Pn = power losses at rated current V = weight = resistance at room temperature R o D 24 ABB
25 3. TIME-CURRENT CHARACTERISTICS High voltage current limiting Fuse links type CEF-S Pre-arcing time minutes seconds 1min Prospective current [A] Melting times The characteristic curves are the same for rated voltages of 12 and 24 kv taken under cold conditions. Maximum cut-off current [ka] (peak) 100 ka Ip 100 ka Prospective current [ka] (rms) ABB 25
26 High voltage current limiting Fuse links type CEF-S 4. FUSE SELECTION TABLE FOR TRANSFORMER PROTECTION. Transformer Transformer rating [kva] rated voltage [kv] CEF-S Fuse-link I N [A] Fuse rated voltage [kv] The table was calculated according to standards IEC and IEC The following transformer work conditions were assumed: Maximum long-lasting overload 150%; Magnetizing inrush current 12 I during 100ms; n Transformer short-circuit voltage according to IEC ; Standard ambient working conditions of fuses. For different criteria fuse selection must be recalculated. The table indicates the correct fuse-link rated current for a given line voltage and transformer rating FUSE POWER LOSSES AT TRANSFORMER RATED CURRENT. For different transformer ratings, power losses are shown in the table below. The table is valid for fuses selected according to the fuse selection table. The measurements were done at the rated transformer power and air cooling according to IEC :2005. The losses mentioned are per single fuse. If the fuse link is to be used in compact switchgears where cooling is limited, the supplier must be contacted regarding maximum permitted power losses and required fuse derating. Transformer Transformer rating [kva] rated voltage [kv] Power loss per single CEF-S fuse link at the transformer s rated current [W] ORDERING TABLE CEF-S & CEF-S-TCU 26 Type voltage current e/d Catalouge No EAN13 Codes [kv] [A] [mm] [kg] CEF-S /65 1YMB531011M CEF-S /65 1YMB531011M CEF-S /65 1YMB531011M CEF-S /65 1YMB531011M CEF-S /65 1YMB531011M CEF-S /65 1YMB531011M CEF-S /65 1YMB531012M CEF-S /65 1YMB531012M CEF-S /65 1YMB531012M CEF-S /65 1YMB531012M CEF-S /65 1YMB531012M CEF-S -TCU /65 1YMB531861M CEF-S -TCU /65 1YMB531861M CEF-S -TCU /65 1YMB531861M CEF-S -TCU /65 1YMB531861M CEF-S -TCU /65 1YMB531861M CEF-S -TCU /65 1YMB531862M CEF-S -TCU /65 1YMB531862M CEF-S -TCU /65 1YMB531862M CEF-S -TCU /65 1YMB531862M CEF-S -TCU /65 1YMB531862M Weight ABB
27 Voltage Transformer Fuses Fuse links type CEF-VT Index 1. GENERAL OVERVOLTAGES CHOICE OF FUSE LINKS ORDERING TABLE DATA AND DIMMENSIONS CEF-VT & CEF-VT-TCU 29 ABB 27
28 Voltage Transformer Fuses Fuse links type CEF-VT voltage: 7.2/24 kv current: A 1. GENERAL The new generation of fuse links type CEF-VT is designed and tested according to IEC :2002. Dimensionally the fuse links are in accordance with DIN CEF-VT fuses are applicable as voltage transformer fuses and in cases where current limiting back-up fuses are required. ABB s high-voltage fuse links have the following properties: Low minimum breaking current Low power losses Low arc voltage High breaking capacity High current limitation CEF-VT fuses are typically a back-up fuse type. They have a zone between the minimum melting current and the minimum breaking current where the fuse links may fail to interrupt. For CEF-VT fuse links this zone is very narrow. The minimum breaking current I 3 for any type is specified in the table on page OVERVOLTAGES In order to be current limiting, the fuses link must generate an arc voltage which exceeds the instantaneous value of the operating voltage. The switching voltage generated by the CEF-VT fuse link is below the maximum permissible value according to IEC :2002. The CEF-VT fuse link can be safely used for the system line voltage of 7.2/12 and 17/24 kv. 3. CHOICE OF FUSE LINKS Selection of voltage transformer fuses ABB recommends using voltage transformer fuses type WBP and CEF-VT in the energy supply systems of medium-voltage single/double insulated poles voltage transformers. Voltage transformer fuses provide: 1) Electrical shock protection in case of main insulation damage to the voltage transformer and high-voltage penetration into the low-voltage side of the voltage transformer. 2) Protection of the switchgear apparatus from internal short circuits. The main selection rules concerning voltage transformer fuses are similar to those specified for current limiting fuses (type CEF) used in the protection of distribution transformers. Choice of rated voltage - The rated current of the fuse links should be equal to or higher than the maximum operating system voltage of where it is installed. Choice of rated current - The rated voltage of the fuse links should be higher than the maximum continuous current of the voltage transformer (depends on voltage transformer load level). Moreover the following points should be observed: a) Starting conditions - Initial starting current of voltage transformer should not cause fuse tripping under normal working conditions. b) Short circuit conditions - breaking current of the fuse links should be higher than the prospective value of the short-circuit in its place of installation. c) Overvoltages - The ability of the electrical system (switchgear) to withstand impulses should exceed the switching overvoltages generated by the fuse links. Voltage transformer fuses do not protect a voltage transformer against overloading. 28 ABB
29 Voltage Transformer Fuses Fuse links type CEF-VT 4. ORDERING TABLE CEF-VT & CEF-VT-TCU High-voltage HRC fuse links Type voltage [kv] current [A] Striker Length e [mm] Diameter D [mm] Catalogue No. EAN13 Codes CEF-VT 7.2/12 2 no YMB531048M CEF-VT 7.2/12 2 no YMB531049M CEF-VT 7.2/12 2 yes YMB531048M CEF-VT 7.2/12 2 yes YMB531049M CEF-VT 7.2/ yes YMB531048M CEF-VT 7.2/ yes YMB531049M CEF-VT 17.5/24 2 no YMB531050M CEF-VT 17.5/24 2 no YMB531046M CEF-VT 17.5/ yes YMB531050M CEF-VT 17.5/ yes YMB531046M CEF-VT -TCU 17.5/24 2 yes YMB531896M CEF-VT -TCU 7.2/12 2 yes YMB531898M CEF-VT -TCU 7.2/ yes YMB531898M CEF-VT -TCU 7.2/12 2 yes YMB531899M CEF-VT -TCU 7.2/ yes YMB531899M CEF-VT -TCU 7.2/ yes YMB531900M DATA AND DIMENSIONS CEF-VT & CEF-VT-TCU Type Striker voltage [kv] current [A] Length e [mm] Diameter D [mm] Short circuit current I 1 [ka] Minimum breaking current I 3 [A] power losses Pn [W] Resistance R O [Ω] CEF-VT no 7.2/ CEF-VT no 7.2/ CEF-VT/CEF-VT-TCU yes 7.2/ CEF-VT/CEF-VT-TCU yes 7.2/ CEF-VT/CEF-VT-TCU yes 7.2/ CEF-VT/CEF-VT-TCU yes 7.2/ CEF-VT no 17.5/ CEF-VT no 17.5/ CEF-VT/CEF-VT-TCU yes 17.5/ CEF-VT/CEF-VT-TCU yes 17.5/ ØD 34 e 34 ABB 29
30
31 High voltage current limiting Fuse links for MOTOR circuit applications type CMF Index 1. GENERAL ORDERING TABLE CMF ORDERING TABLE UCM ORDERING TABLE TYPE CMF-BS ORDERING TABLE CMF-TCU PRE-ARCING TIMES CURRENT LIMITATION CHOICE OF FUSE LINKS THE K-FACTOR DATA AND DIMENSIONS CMF & CMF-TCU 37 ABB 31
32 High voltage current limiting Fuse links for MOTOR circuit applications type CMF 1. GENERAL The fuse links type CMF are specially designed for motor circuit applications. They are tested according to the IEC Publication (IEC 282-1) and Publication 644. IEC 644 applies to fuse links used with motors that are started direct-on-line in alternating current systems. High-voltage fuses used in motor circuits must be able to withstand, without deterioration, the repeated surges associated with motor starting. The dimensions are in accordance with DIN 43625, i.e. the 3.6 kv rating is realized in the normal 12 kv length (e = 292 mm). The 7.2 kv and 12 kv rating in the 24 kv length (e = 442 mm). Special connection elements can be delivered in cases where fuses have to be configured in parallel. ABB s motor fuses have the following properties: Higher current rating within single body dimensions Tested according to IEC 644, which guarantees excellent ability to withstand repeated motor starting conditions Low power losses Low minimum breaking current High breaking capacity and excellent short-circuit current limitation Although a motor fuse is normally run at a stationary current, which is much lower than the fuse rated current, the low-loss characteristics of the CMF fuses make them especially suitable in compact contactor compartments. 2. ORDERING TABLE TYPE CMF High-voltage fuse links Type voltage [kv] Current [A] e [mm] D [mm] Catalogue No. EAN13 Codes CMF YMB531028M CMF YMB531028M CMF YMB531028M CMF YMB531028M CMF YMB531028M CMF YMB531029M CMF YMB531029M CMF YMB531029M CMF YMB531029M CMF YMB531029M CMF YMB531029M CMF YMB531030M CMF YMB531030M CMF YMB531030M CMF YMB531030M Weight [kg] 3. ORDERING TABLE UCM Type Dimensions in mm Weight voltage [kg] [kv] A A 1 A 2 H K K 1 B Catalogue No. UCM YMX139037R001 UCM 7.2/ YMX139037R ABB
33 High voltage current limiting Fuse links for MOTOR circuit applications type CMF FUSE-BASE type UCM 4. ORDERING TABLE TYPE CMF-BS Type voltage [kv] Current [A] L/D [mm] A/d [mm] Catalogue No. EAN13 Codes Weight [kg] CMF-BS-C /65 440/40 1YMB531031M CMF-BS-C /65 440/40 1YMB531031M CMF-BS-C /87 440/40 1YMB531031M CMF-BS-C /87 440/40 1YMB531031M CMF-BS-C /87 440/40 1YMB531031M CMF-BS-D /65 461/50.5 1YMB531031M CMF-BS-D /65 461/50.5 1YMB531031M CMF-BS-D /87 461/50.5 1YMB531031M CMF-BS-D /87 461/50.5 1YMB531031M CMF-BS-D /87 461/50.5 1YMB531031M CMF-BS-B /65 590/40 1YMB531032M CMF-BS-B /65 590/40 1YMB531032M CMF-BS-B /65 590/40 1YMB531032M CMF-BS-B /87 590/40 1YMB531032M CMF-BS-B /87 590/40 1YMB531032M CMF-BS-B /87 590/40 1YMB531032M CMF-BS-B /65 590/40 1YMB531033M CMF-BS-B /87 590/40 1YMB531033M CMF-BS-B /87 590/40 1YMB531033M CMF-BS-B /87 590/40 1YMB531033M CMF-BS /65 440/40 1YMB531031M CMF-BS /65 440/40 1YMB531031M CMF-BS /87 440/40 1YMB531031M CMF-BS /87 440/40 1YMB531031M CMF-BS /87 440/40 1YMB531031M CMF-BS /65 590/40 1YMB531032M CMF-BS /65 590/40 1YMB531032M CMF-BS /65 590/40 1YMB531032M CMF-BS /87 590/40 1YMB531032M CMF-BS /87 590/40 1YMB531032M CMF-BS /87 590/40 1YMB531032M CMF-BS /65 590/40 1YMB531033M CMF-BS /87 590/40 1YMB531033M CMF-BS /87 590/40 1YMB531033M CMF-BS /87 590/40 1YMB531033M ABB 33
34 High voltage current limiting Fuse links for MOTOR circuit applications type CMF Dimension CMF-BS Dimension CMF-BS-B Dimension CMF-BS-C Dimension CMF-BS-D 5. ORDERING TABLE CMF-TCU Type voltage [kv] Current [A] e [mm] Catalogue No. CMF-TCU YMB531878M CMF-TCU YMB531878M CMF-TCU YMB531878M CMF-TCU YMB531878M CMF-TCU YMB531878M CMF-TCU YMB531879M CMF-TCU YMB531879M CMF-TCU YMB531879M CMF-TCU YMB531879M CMF-TCU YMB531879M CMF-TCU YMB531879M CMF-TCU YMB531880M CMF-TCU YMB531880M CMF-TCU YMB531880M CMF-TCU YMB531880M Weight [kg] 34 ABB
35 High voltage current limiting Fuse links for MOTOR circuit applications type CMF 6. PRE-ARCING TIMES The characteristics are equal for all rated voltages and were recorded under cold conditions. Prospective current [A] 7. CURRENT LIMITATION Maximum cut-off current [ka] (peak) Pre-arcing time Prospective current [ka] (rms) ABB 35
36 High voltage current limiting Fuse links for MOTOR circuit applications type CMF 8. CHOICE OF FUSE LINKS Choice of rated current In The minimum permissible current rating of the fuse links for motor protection may be determined from the selection charts I, II and III on pages 36 and 37. These three charts are for run-up times of 6, 15 and 60 seconds respectively. Each chart contains different characteristics, depending on the number of starts per hour. With reference to the number of starts per hour, the first two are in immediate succession while the rest are evenly spaced at intervals of one hour. The number of starts per hour indicates the time interval between separate starts. For example, four starts in 15 minutes are represented by 16 starts per hour. The horizontal axis of the selection chart indicates the motor starting current, while the current rating of the fuse link is found along the vertical axis. Selection procedure: Select the charts which are appropriate for the run-up time of the motor Select the starting current along the horizontal axis Depending on the number of starts per hour, select the correct characteristic (2, 4, 8, 16, 32) Read the correct fuse-link rating on the vertical axis. Because the main function of motor fuses is to protect against short circuits, fuses are selected to withstand start-up currents only. The minimum breaking current has only limited importance in such an application. Example: A B Starting current of the motor 850 A 250 A Run-up time 6 sec. 15 sec. Number of starts per hour 2 16 Chart number 3 2 current of fuse link 250 A 160 A Fuse link rating [A] Fuse link rating [A],, motor starting current [A],, motor starting current [A] 36 ABB
37 High voltage current limiting Fuse links for MOTOR circuit applications type CMF Fuse link rating [A],, motor starting current [A] 9. THE K-FACTOR According to the IEC 60644, the K-factor (less than unity) defines an overload characteristic to which the fuse link may be repeatedly subjected under specified motor starting conditions without deteriorating. The overload characteristic is obtained by multiplying the current on the pre-arcing characteristic (melting time characteristics) by K. The value of K given in the data table is chosen at 10 seconds melting time and is valid for melting times between 5 and 60 seconds. 10. DATA AND DIMENSIONS CMF & CMF-TCU Un In e D K* I 1 I 3 R O Pn [kv] [A] [mm] [mm] - [ka] [A] [mω] [W] Minimum I 2 x t Pre-arc A 2 s Maximum I 2 x t Interruption A 2 s x x x x x x x x x x x x x x x x x x x x x x x x x x x x x x 10 4 D e D Legends: e = see figure D = see figure K = K-factor acc. to IEC I 1 = max. short circuit current tested I 3 = minimum breaking current R 0 = resistance at room temperature Pn = power loss at rated current * ) The K-factor is referred to the average value of current. ABB 37
38
39 Voltage Transformer Fuses Indoor - WBP Outdoor - BRT Index 1. FEATURES APPLICATIONS ENVIRONMENTAL OPERATING CONDITIONS DESIGNATIONS AND VERSIONS COMPLIANCE WITH STANDARDS HOW TO ORDER SPECIFICATIONS DIMENSIONAL DRAWINGS 43 ABB 39
40 Voltage Transformer Fuses Indoor - WBP Outdoor - BRT 1. FEATURES High breaking capacity Short circuit current limiting Small dimensions. 2. APPLICATIONS The WBP fuse links are used to protect switchgear equipment against short circuits in voltage transformers. Protection of switchgear equipment is very effective thanks to the unlimited breaking capacity and short- circuit current limitation of this type of fuse link. In addition, their very small dimensions mean the WBP type fuse links can be used in various types of switchgear, including those that are flame proof. 3. ENVIRONMENTAL OPERATING CONDITIONS Type WBP and BRT... fuse links can be operated under the following environmental conditions: Table 1. Type of fuse links Temperature Relative humidity of ambient air at a temperature: N ºC T ºC Height of installation above sea level WBP BRT N3 T3 N1 T1 From -5 ºC to +40 ºC From -5 ºC to +50 ºC From - 25 ºC to +40 ºC From -10 ºC to +50 ºC to 80% to 95% to 100% to 100% Up to 1,000 m Designations: N Normal climate T Tropical wet and dry climate 1 Outdoor installation 3 Indoor installation 4. DESIGNATIONS AND VERSIONS 4.1 WBP indoor instrument transformer fuse links numbering system The numbering system for the WBP fuse links has two alphanumerical sections as shown in the following diagram. Indoor Fuse link type WBP - 6 Voltage kv kv kv kv 4.2 BRT outdoor instrument transforme fuse links numbering system. The numbering system for the BRT fuse links has two alphanumerical sections as shown in the following diagram. Outdoor Fuse link type BRT - 6 Voltage and 12 kv and 24 kv kv 4.3 Indoor fuse base numbering system The numbering system for indoor fuse bases has two alphanumerical sections as shown in the following diagram. PBPM - 6 Fuse base Voltage type kv kv kv kv 40 ABB
41 Voltage Transformer Fuses Indoor - WBP Outdoor - BRT 4.4 Outdoor fuse base numbering system The numbering system for outdoor fuse bases has four double alphanumerical sections as shown in the following diagram. A fuse link, when mounted on a fuse base, makes a complete fuse. Refer to Table 2 for the available fuse bases. Fuse base type PBPM - I 36 w.ii-1 Kind of fuse base I hanging type III standing type voltage 36 kv 5. COMPLIANCE WITH STANDARDS 5.1 The fuse links meet the requirements of the following standards: Polish Standard PN 77/E British Standard BS:2692:1956 Russian Standard GOST 2213: The fuse bases meet the requirements of the following standards: Polish Standard PN 77/E German Standard VDE 0670 Teil 4/ International Standard IEC of 1985 Additional designation 6. HOW TO ORDER Order by specifying the product name, type symbol, rated value, rated current and quantity. All additional demands not listed in this catalogue should be agreed with the manufacturer by means of an inquiry where the sources of requirements (regulations, standards, etc.) should to be specifi ed. 6.1 Order example 1. Type WBP 6 fuse link for a rated voltage of 7.2 kv and rated current of 0.7A 10 pcs 2. Type PBPM 6 Indoor fuse base for a rated voltage of 7.2 kv 20 pcs 1) Insulating tube is made from glass (WBP) or porcelain (BRT) 7. SPECIFICATIONS 7.1 Technical data of fuse links Table 2 Fuse-link Type Voltage current Breaking Current Breaking Capacity Frequency Overvoltages Weight Resistance Fuse-base Type Un f In I 1 S 1 UTRV Min. Max. kv Hz A ka MVA kv kg Ω Ω WBP < PBPM-6 WBP < PBPM or 60 >1,500 WBP < PBPM-20 WBP < PBPM-30 BRT-6 7.2/ ) /48 < BRT /24 50 or ) /24 >1,000 < PBPN-24-1 BRT < PBWMNI36 w.ii-1 PBWMNIII 36 w.ii-1 The resistance is to be measured using the electrical bridge method or technical method using a measuring instrument with an accuracy class not worse than 0.5% at an ambient temperature of t = 20 C ±2 C. 2) for Un = 12 kv I = 48 ka 1 3) for Un = 24 kv I = 24 ka 1 Note: In cases where WBP fuses are installed within an enclosed housing and/or similar equipment characterized by heat exchange (stabilized ambient air temperature exceeds +40 C), the value of the nominal current, In, should be reduced by 0.1 A. ABB 41
42 Voltage Transformer Fuses Indoor - WBP Outdoor - BRT 7.2 Technical data of fuse bases Table 3 Fuse-base type voltage Frequency Impulse withstand voltage of insulation 50 Hz withstand voltage of insulation Fuse-link type Un f to earth in pole to earth in pole kv Hz kv kv kv kv PBPM WBP-6 PBPM WBP-10 PBPM WBP-20 PBPM or WBP-30 PBPN BRT-15 PBWMNI 36 w.ii BRT-30 PBWMNIII 36 w.ii PBPM an indoor fuse base with resin insulators PBPN an outdoor suspended fuse base on 24 kv PBWMNI 36 w.ii 1 an outdoor suspended fuse base on 36 kv PBWMNIII 36 w.ii 1 an outdoor fuse base on 36 kv Recommendation of fuse-link selection for MV voltage transformer protection ABB Sp. z o.o. recommends using instrument transformer fuse element type WBT from our production portfolio as protection for ABB s voltage transformer types UMZ and UDZ equipped with a fuse holder. The use of instrument transformer fuses has two main functions: to protect distribution equipment when internal voltage transformer shortcircuits occur and to reduce the possibility of an explosion if the internal isolation of the voltage transformer has been damaged. The selection of a fuse element for voltage transformer protection primarily depends on the rated primary voltage of the voltage transformer*. The rated voltage of the fuse element should be equal to or higher than (phase to phase) the rated voltage of the voltage transformer s primary winding. For example, for a VT type UMZ 15-1 with a primary winding voltage of 3 kv, fuse-link type WBP-10, with a rated voltage is 10 kv should be selected. From the beginning of January 2001, the rated current of fuse-link type WBP was reduced from 0.8A to A (depending on Un). The reason for this change was to improve cooperation between the fuse link and voltage transformers. Therefore, ABB Sp. z o.o. now recommends the use of these new fuse links for the protection of voltage transformer types UMZ and UDZ. A comparison of the old voltage transformer fuse-link type WBP with the new one is presented in the table below: continuous (till ) Current continuous current (from ) Voltage Fuse-link Type Un In In kv A A WBP WBP WBP WBP ABB Sp. z o.o. recommends using new fuse links with limited rated current ( A) for protection voltage transformers type UMZ and UDZ instead of using former ones with rated current 0.8A * In rare cases when the following criteria have been fulfilled: 1) The instrument transformer is used with a rated primary voltage below 3,000 V. 2) The power taken from the instrument transformer is much higher than the rated power output and is close to the limit of the thermal power output; the user should contact the producer (ABB sp. z o.o.) for advice regarding the proper selection of voltage transformer protection. 42 ABB
43 Voltage Transformer Fuses Indoor - WBP Outdoor - BRT 8. DIMENSIONAL DRAWINGS Dimensional drawing of WBP type fuse links ÆA ÆB e D Notes: Connections: silver-plated cooper. Deviations of dimensions with no tolerance specified shall be within ±3%. Fuse-link type Dimensions [mm] e D ØA ØB WBP ± WBP ± WBP ± WBP-6 210± Dimensional drawing of BRT type fuse links A B C e D Notes: Connections: silver-plated cooper. Deviations of dimensions with no tolerance specified shall be within ±3%. Fuse-link type Dimensions [mm] e D ØA ØB ØC BRT ± BRT ± BRT-6 311± ABB 43
44 Voltage Transformer Fuses Indoor - WBP Outdoor - BRT Dimensional drawing of PBPM-6 and PBPM-10 type fuse bases A3 A2 A1 2 øe M5 B2 B1 M10 20 two 1 mm dia.holes A4 A5 A ød Notes: Earthing Terminal; tinned steel. Connections: silver-plated brass Contact Springs: silver-plated brass Deviations of dimensions with no tolerance specified shall be within ±3%. Dimensions [mm] Fuse-base type A1 A2 A3 A4 A5 A6 B1 B2 ØD E PBPM-6 170±2 200± PBPM ±2 240± Dimensional drawing of PBPM-20 and PBPM-30 type fuse bases A3 A2 A1 øe M5 2 B2 B1 M10 20 ød two 1 mm dia. holes A4 A5 A Notes: Earthing Terminal; tinned steel. Connections: silver-plated brass Contact Springs: silver-plated brass Deviations of dimensions with no tolerance specified shall be within ±3%. Dimensions [mm] Fuse-base type A1 A2 A3 A4 A5 A6 B1 B2 ØD E PBPM ±2 300± PBPM ±2 375± ABB
45 Voltage Transformer Fuses Indoor - WBP Outdoor - BRT Dimensional drawing of PBPN-24-1 and PBWMNI 36 w.ii-1 type fuse bases two18mm dia.holes A5 A6 ød 100 A M12 B2 B1 5 A1 A2 A3 M12 Notes: Earthing Terminal; tinned steel. Connections: silver-plated brass Contact Springs: silver-plated brass Deviations of dimensions with no tolerance specified shall be within ±3%. Dimensions [mm] Fuse-base type A1 A2 A3 A4 A5 A6 B1 B2 ØD E PBPN ±2 357± PBWMNI 36 w.ii-1 375±2 435± Dimensional drawing of PBWMNIII 36 w.ii-1 type fuse bases A3 A2 A1 M12 5 B2 B1 M two 18 mm dia. holes A4 A5 A6 100 ød Notes: Earthing Terminal; tinned steel. Connections: silver-plated brass Contact Springs: silver-plated brass Deviations of dimensions with no tolerance specified shall be within ±3%. Dimensions [mm] Fuse-base type A1 A2 A3 A4 A5 A6 B1 B2 ØD E PBWMNIII 36 w.ii-1 375±2 435± ABB 45
46
47 Indoor Railway DC Fuses Type WBT Index 1. FEATURES APPLICATIONS CLIMATIC WORKING CONDITIONS DESIGNATIONS, VERSIONS TECHNICAL DATA COMPLIANCE WITH STANDARDS HOW TO ORDER ORDER EXAMPLE APPENDICES 51 ABB 47
48 Indoor Railway DC Fuses Type WBT 1. FEATURES High rupturing capacity Short circuit current limiting Low switching voltages R1, P1 fire-protection grade for the materials used - in accordance with PN-84/K APPLICATIONS The fuse links for traction applications are used to protect traction substation and electric traction rolling stock equipment against the effects of overloads greater than 2 x I, and of short-circuits at voltages of 1.9 kv DC and 4 kv DC. Please refer to Table 1 for application details for particular product types. 3. CLIMATIC WORKING CONDITIONS Fuse-base type PBWMI can be operated indoors at ambient temperatures ranging from -5 C to +50 C. Other parameters are presented below. The fuse links and fuse boards can be operated indoors or in sealed boxes secured under the railway car under the following environmental conditions: At ambient temperatures ranging from -30 C to +50 C, In ambient air with a relative humidity of 95% at a temperature of +20 C. At an altitude of 1,200 m. All other operating conditions first require approval from the manufacturer. 4. DESIGNATIONS, VERSIONS 4.1 Marking system The marking system for a particular fuse link, fuse base or fuse board has three alphanumerical sections as shown in the following diagram. WBTI - 3 / 3 Fuse-link type voltage current TBT2-3 / 20 Fuse-board voltage current base type current 5. TECHNICAL DATA The general technical data of the fuse links are presented in Table 3. The general technical data of the fuse boards are presented in Table COMPLIANCE WITH STANDARDS Fuse links for traction applications meet the requirements specified in Table HOW TO ORDER Order by specifying the following: Product name Type symbol voltage current Quantity All additional requirements not listed in this catalogue should be agreed with the manufacturer. 48 ABB
49 Indoor Railway DC Fuses Type WBT 8. ORDER EXAMPLE 1. Type WBTI-3/30 fuse link for traction applications with a rated voltage of 4 kv, rated current of 20 A - 20 pcs. 2. Type TBT2-3/20 fuse board for traction applications with a rated voltage of 4 kv, rated current of 20 A - 20 pcs. Table 1. Fuse link type Fuse base/board 1 type Applications WBTI-3/3 to 20 PBWMI-6/20 WBTI-3/25 to 50 PBWMI-6/50 Protection against the effects of short circuits and overloads in the electric circuits of railway traction substation equipment. WBTI-3/80 PBWMI-10/100-1 WBTI-3/3 to 20 TBT2-3/20 TBT2-3/20 & 50 TBTS2-3/20 TBTS2-3/20 & 50 Protection against the effects of short circuits and overloads in the electric circuits of traction vehicles, railcoach space heating equipment and electric locomotive. WBTI-3/25 to 50 TBT2-3/50 WBTG-3/3; 4; 6 WBTG-3/3-I TBTG1-3/6 TBG-3/3-I Protection against the effects of short circuits and overloads in electric single- and multi voltage circuits of railcoach space heating equipment. WBTGI-3/10; 16; 20 WBTS-3/0.6; 1 WBT-1.5/3; 15; 40 WBTS-3 WBTG-3 WBTGI-3 PBPM-6 TBTS1-3/1 PBT-1.5/40 TBTG3-3/1; 6; 15 TBTG4-3/1; 3; 6; 15 1) The specified fuse boards and fuse bases will operate with fuse links selected according to. Table 1. Other configurations should be agreed with the manufacturer. Table 2. Protection against the effects of short circuits and overloads in the electric single and multi voltage circuits of railcoach space heating equipment as well as other d.c. circuits in traction vehicles. The dimensions of these fuse links meet the requirements of German Standards DIN Protection against the effects of short circuits and overloads in the voltage measurement circuits and special electric equipment in traction vehicles, if the nominal loads are lower than 1 A. Protection against the effects of short circuits and overloads in the electric circuits of traction substation equipment and vehicles operating at a rated voltage not greater than 1,900 V DC A device for carrying replaceable parts in the form of types WBTS, WBTG, and WBTGI mounted outside electric circuits in electric locomotive. Product type WBTI-3/3 to 80 WBTG 3/3 to 6 WBTG 3/3 I WBTGI 3/10 to 20 WBTS 3/0.6; 1 WBT 1.5/3; 15; 40 PBT 1.5/40 Compilance with Standards PN 69/E in scope of environmental requirements and vibration and shock resistance. General Requirements according to BN 70/ IEC Publ. 77 of 1968 as well as UIC 552V Sheets, VII edition PN 69/E in scope of environmental requirements and vibration and shock resistance. General Requirements according to BN 70/ IEC Publ. 77 of 1968 as well as UIC 552 Sheets of 1993 VII edition PN 69/E in scope of environmental requirements and vibration and shock resistance. DIN in scope of dimensional requirements General Requirements according to BN 70/ IEC Publ. 77 of 1968 as well as UIC 552V Sheets, PN 69/E in scope of environmental requirements and vibration and shock resistance. General Requirements according to BN 70/ IEC Publ. 77 of 1968 WTO 67/ZPM Technical Requirements and AE/A The fuse boards for traction applications meet the requirements of the following Standards: PN 69/E and BN 70/ and IEC Publ. 77 of 1968 in the scope specified above. ABB 49
50 Indoor Railway DC Fuses Type WBT Table 3. General technical data of fuse links for traction applications Current Switching Fuse-link Voltage ace. ace. Breaking Weight Resistance Overvolt. BN UIC-552 Current Fuse-base type type Un In In UTRV I 1 Min. Max kv DC A DC A DC kv ka kg m m WBTtI-3/ PBWMI-6/20 WBTI-3/ TBT2-3/20 WBTI-3/ TBT2-3/20 & 50 WBTI-3/ TBTS2-3/20 WBTI-3/ TBTS2-3/20 & < WBTI-3/ PBWMI-6/50 WBTI-3/ TBT2-3/ WBTI-3/ TBT2-3/20 & 50 WBTI-3/ TBTS2-3/20 & 50 WBTI-3/ PBWMI-10/100-1 Current Switching Fuse-link Voltage ace. ace. Breaking Weight Resistance Overvolt. BN UIC-552 Current Fuse-base type type Un In In UTRV I 1 Min. Max kv DC A DC A DC kv ka kg mω mω WBTGI-3/ WBTGI-3/ < TBTG1A-3/15 WBTGI-3/ WBTG-3/3-I < PBPM-6 WBTG-3/ WBTG-3/ < TBTG1-3/6 WBTG-3/ WBTS-3/ ( ) 51.3( ) 4 < WBTS-3/ TBTS1-3/1 WBT-1.5/ WBT-1.5/ < PBT-1.5/40 WBT-1.5/ ) While testing the breaking capacity, satisfactory results were found for the short-circuit range at a recovery voltage of 4,000 V DC. For the overload currents at a recovery voltage of between 3,800-4,000 V DC, various values for particular fuse links were obtained. The resistances are measured using either an electrical bridge method or a measuring instrument with an accuracy class not worse than 0.5% at an ambient temperature of t = 20 C ±2 C. Table 4. General technical data of fuse boards Voltage Current test voltage at 50 Hz Number of poles Fuse-board Weight type Un In Ut Fuse - link type kv DC A DC kv pcs kg PBWMI-6/ WBTI-3/ ) 1 PBWMI-6/ WBTI-3/25 50 TBT2-3/ WBTI-3/3 20 (2 pcs) TBT2-3/20 & 50 2) 20& WBTI-3/3 20 (1 pcs) WBTI-3/25 50 (1 pcs) 2 TBT2-3/ WBTI-3/25 50 (2 pcs) TBTS2-3/ WBTI-3/3 20 (2 pcs) TBTS2-3/20 & 50 20& WBTI-3/3 20 (1 pcs) WBTI-3/25 50 (1 pcs) TBTG1A-3/ WBTGI-3/10; 16; 20 1 TBTG1-3/ WBTG-3/3;4;6 TBTG3-3/1;6; WBTS-3/1 WBTG-3/3;4;6 WBTGI-3/10; 16;20 TBTG4-3/1;3;6; WBTS-3/1 WBTG-3/3;4;6 WBTGI-3/10; 16;20 TBTS1-3/ WBTS-3/0.6;1 PBT-1.5/ ) 35 3) WBT-1.5/3 WBT-1.5/15 WBT-1.5/40 PBWMI-10/ WBTI-3/80 Note: Due to the introduction of improvements, we reserve the right to modify the products. 1) AC contact-to-contact insulation test voltage. 2) One pole is designed for fixing the type WBTI-3/3 to 20 fuse links and the second one for WBTI-3/25 to 50 fuse links. 50 3) AC earth insulation test voltage. ABB
51 Indoor Railway DC Fuses Type WBT 9. APPENDICES Fig.1 Cut-off current characteristics for fuse-link types WBTI-3... Ipeak [ka] 10 80A 40A 32A 25A 20A 16 A 10 A 6A Ip [ka] 40 Fig. 2 Time-current characteristics for fuse-link types WBTI-3... Current value deviations for any average pre-arcing period value as read from the diagram are presented within ±20% Pre-arcing time [s] A 10 A 16 A 20A 25A 32A 40A 80A Prospective current [A] ABB 51
52 Indoor Railway DC Fuses Type WBT Fig. 3 Cut off current characteristics fuse link types WBTGI 3... Ipeak [ka] 10 20A 16 A 10 A Ip [ka] Fig. 4 Time current characteristics for the fuse link types WBTGI 3... Current value deviations for any average pre-arcing period value as read from the diagram are presented within ±20% Pre-arcing time [s] A 16 A 20A , Prospective current [A] 52 ABB
53 Indoor Railway DC Fuses Type WBT Fig. 5 Cut off current characteristics for fuse link types WBTG 3/3; 4; 6... and WBTG 3/3 I Ipeak [ka] A 4A 3A Ip [ka] Fig. 6 Time current characteristics for fuse link types WBTG 3/3; 4; 6... and WBTG 3/3 I Current value deviations for any average pre arcing period value as read from the diagram are presented within ±20%. Pre-arcing time [s] A 4A 6A Prospective current [A] ABB 53
54 Indoor Railway DC Fuses Type WBT Fig. 7 Cut off current characteristics for fuse link types WBTS 3/0,6; 1 Ipeak [ka] A A Ip [ka] Fig. 8 Time current characteristics for fuse link types WBTS 3/0.6; 1 Current value deviations for any average pre arcing period value as read from the diagram are presented within ±20%. Pre-arcing time [s] A 1A Prospective current [A] 54 ABB
55 Indoor Railway DC Fuses Type WBT Fig. 9 Cut off current characteristics for fuse link types WBT 1.5/3; 15; 40 Ipeak [ka] A 15 A A Ip [ka] (rms) Fig. 10 Time current characteristics for fuse link types WBT 1.5/3; 15; 40 Current value deviations for any average pre arcing period value as read from the diagram are presented within ±20%. Pre-arcing time [s] A 15 A 40A Current [A] ABB 55
56 Indoor Railway DC Fuses Type WBT WBTI 3, WBTG 3, WBTGI 3, WBTG 3/3 I,WBTS 3 and WBT 1,5 fuse links for traction applications Dimensions [mm] Fuse-link type ØA ØD ØC K E e WBTI-3/3 to ±2 WBTI-3/25 to WBTGI-3/10 to ±2 WBTG-3/3-I ±2 WBTG-3/3 to ±2 WBTI-3/0.6; ±2 WBT-1,5/3; ±2 WBT-1,5/ ±2 BWT fuse links for traction applications DC fuse links for railway applications are characterized by their small dimensions, high rupturing capacity, current limitation and low switching voltage. Type tested according to Specifi ca Generale per la Fornitura di Valvole Fusibili A.T. per Circuiti C.C. at Trenitalia (Italian Railways) testing station in Empoli/Italy. Technical parameters: voltage Un 3 kv DC current In 3.15; 16; 20 A Switching voltage (max) UTRV 12 kv Minimum breaking current I 3 5 x In breaking current I 1 60 ka A D C A 45 D Type WBTI-3-3/...Fuse links e K E e Type WBT-1.5/40 Fuse links 30 e A K E D C O Type WBTGI-3/...; WBT-1.5/3... Fuse links 254-0,5 Type BWT Fuse links A D e K E E Type WBTG-3/3-6, WBTG-3/3-I,WBTS-3/... Fuse links 56 ABB
57 Indoor Railway DC Fuses Type WBT TBT2 3/...; TBT2 3/20&50; TBTS2 3/20 and TBTS2 3/20&50 fuse boards for traction applications 1. Connection screw, M12, for the board type TBT2 3/50 only. 2. Connection screw M8 for the ØD1 pole or M5 for the ØD2 pole for the board type TBT2 3/20 & 50 only. 3. Poles designed for the fuse links type WBT 3/20 50 fitted with extrathimble terminals. 4. Flat connections employing a screw, M8 are fitted in thetbts2 3/... only. Connections: silver plated brass Contact Springs: silver plated brass Deviations of dimensions with no tolerance specified shall be within ±3%. Dimensions [mm] Fuse-board type Ø A1 Ø A2 A3 B1 B2 B3 TBT2-3/ TBT2-3/ TBT2-3/20 & TBTS2-3/ TBTS2-3/20 & A1 A2 Note 3 400±3 360±3 A3 164 ± 3 B1 B3 B2 30 Note 2 Note 1 Note 4 4 x M12 200±3 410±3 450±3 ABB 57
58 Indoor Railway DC Fuses Type WBT TBTG3 3/1; 6; 15 and TBTG4 3/1; 3; 6; 15 fuse boards for traction applications A1 A2 A3 A4 A5 B1 B2 10 B3 B4 B6 B5 Notes: 1. Connections: silver plated brass 2. Contact Springs: silver plated brass 3. Deviations of dimensions with no tolerance specified shall be within ±3%. Dimensions [mm] Fuse-board type A1 A2 A3 A4 A5 B1 B2 B3 B4 B5 B6 TBTG3-/1,6, ±1 180± TBT4-3/1,3,6, ±1 180± TBTG1 3/6; TBTG1A 3/15; TBTS1 3/1 Fuse boards for traction applications A1 A D A Note 2 Note 1 Note 1 B2 10 A2 A3 A4 C1 C2 C3 B1 1. The Ø10 holes are to be used for installation 2. Fuse link stops for Type TBTG1 3/6 and TBTS1 3/1 Fuse boards are to be installed in the panels Connections: silver plated brass Contact springs: silver plated brass Deviations of dimensions with no tolerance specified shall be within ±3%. Dimensions [mm] Fuse-board type A1 A2 A3 A4 B1 B2 C1 C2 C3 C4 TBTG1-3/6 165± ±3 395± ±2 M5 70± TBTG1A-3/15 205± ±3 440± ±2 M8 70± TBTS1-3/1 105±1 120±3 394± M ABB
59 Indoor Railway DC Fuses Type WBT Type PBT-1.5/40 Fuse base for traction application M M Notes: Earthing Terminal; tinned steel. Connectors: silver-plated brass Contact Springs: silver-plated brass Deviations of dimensions with no tolerance specified shall be within ±3%. Note: Due to the introduction of improvements, ABB reserve the right to modify the products. Two 15 mm dia. holes Note: Design and specifications are subject to change without notice. 55 ABB 59
60
61 Indoor Fuse Bases Fuse base type BPS Index 1. FEATURES APPLICATION OPERATING CONDITIONS VERSIONS AND MARKING DESINGN AND PRINCIPLE OF OPERATION CHARACTERISTICS CONFORMITY WITH STANDARDS ORDERING METHOD ORDER EXAMPLE ENCLOSURES 65 ABB 61
62 Indoor Fuse Bases Fuse base type BPS 1. FEATURES Suitable for all types of high power fuse links fitted with a Ø45mm contact May co-operate with switching station auxiliary and control circuits Small overall dimensions 2. APPLICATION The fuse-bases BPS-type are intended for fixing medium-voltage fuse links fitted with a striker. The base can be applied in cases where fuse links are used to protect transformer circuits as well as motor circuits. By using these bases, the signaling circuits in the switching station can see that a particular fuse has blown. 3. OPERATING CONDITIONS The fuse-bases BPS-type are designed for indoor applications where temperate climate conditions exist. The fuse-bases BPS-type can be mounted vertically or horizontally, and this enables easy replacement of the fuse link. 4. VERSIONS AND MARKING The marking denoting a three-pole fuse base with a rated voltage of 7.2 kv is composed of two letter-digit segments: BPS-01. The two-piece base is powder painted and fitted with a resin insulator. The base pole pitch is 112 mm. The catalogue number of this base is: 1YMB207101M0001. The table below presents the different versions of single pole BPS-type fuse bases. Table 1 Fuse-base type volgage [kv] Version Coating Post-insulators Fuse link - e- dimension [mm] Catalogue number 1 BPS 7.2 1(*) zinc resin 192 1YMB507102M BPS 7.2 1(*) zinc resin 292 1YMB507102M BPS 12 1(*) zinc resin 292 1YMB507102M BPS 12 1(*) zinc porcelain 292 1YMB507102M BPS 12 1(*) zinc resin 442 1YMB507102M BPS 12 1(*) zinc porcelain 442 1YMB507102M BPS (*) zinc resin 292 1YMB507102M BPS (*) zinc porcelain 292 1YMB507102M BPS 24 1(*) zinc resin 442 1YMB507102M BPS 24 1(*) zinc porcelain 442 1YMB507102M BPS 24 1(*) zinc resin 537 1YMB507102M BPS 24 1(*) zinc porcelain 537 1YMB507102M BPS 27 1(*) zinc resin 442 1YMB507102M BPS 27 1(*) zinc porcelain 442 1YMB507102M BPS 36 1(*) zinc resin 537 1YMB507102M BPS 36 1(*) zinc porcelain 537 1YMB507102M BPS 7.2 1(*) powder paint resin 192 1YMB507102M BPS 7.2 1(*) powder paint resin 292 1YMB507102M BPS 12 1(*) powder paint resin 292 1YMB507102M BPS 12 1(*) powder paint porcelain 292 1YMB507102M BPS 12 1(*) powder paint resin 442 1YMB507102M BPS 12 1(*) powder paint porcelain 442 1YMB507102M BPS (*) powder paint resin 292 1YMB507102M BPS (*) powder paint porcelain 292 1YMB507102M BPS 24 1(*) powder paint resin 442 1YMB507102M BPS 24 1(*) powder paint porcelain 442 1YMB507102M BPS 24 1(*) powder paint resin 537 1YMB507102M ABB
63 Indoor Fuse Bases Fuse base type BPS Fuse-base type volgage [kv] Version Coating Post-insulators Fuse link - e- dimension [mm] Catalogue number 27 BPS 24 1(*) powder paint resin 537 1YMB507102M BPS 24 1(*) powder paint porcelain 537 1YMB507102M BPS 27 1(*) powder paint resin 442 1YMB507102M BPS 27 1(*) powder paint porcelain 442 1YMB507102M BPS 36 1(*) powder paint resin 537 1YMB507102M BPS 36 1(*) powder paint porcelain 537 1YMB507102M BPS 7.2 2(**) zinc resin any 1YMB507103M BPS 12 2(**) zinc resin any 1YMB507103M BPS 12 2(**) zinc porcelain any 1YMB507103M BPS 24 2(**) zinc resin any 1YMB507103M BPS 24 2(**) zinc porcelain any 1YMB507103M BPS 36 2(**) zinc resin any 1YMB507103M BPS 36 2(**) zinc porcelain any 1YMB507103M BPS 7.2 2(**) powder paint resin any 1YMB507103M BPS 12 2(**) powder paint resin any 1YMB507103M BPS 12 2(**) powder paint porcelain any 1YMB507103M BPS 24 2(**) powder paint resin any 1YMB507103M BPS 24 2(**) powder paint porcelain any 1YMB507103M BPS 36 2(**) powder paint resin any 1YMB507103M BPS 36 2(**) powder paint porcelain any 1YMB507103M0022 Remarks: (*)- single pole one-piece fuse base (**)- single pole two-piece fuse base The single pole two-piece fuse base makes it possible to use fuse links with any e overall dimension. 5. DESIGN AND PRINCIPLE OF OPERATION 5.1 The three-pole fuse base The three-pole fuse base, BPS-type, is composed of two separated steel bars fitted with M10 earthing terminals, and three fixed indoor resin post-insulators. Spring contacts and a terminal strip (fitted with M12 screw terminals for easy connection to an electrical circuit) are mounted on these insulators. The insulators are separated by insulating barriers, which ensure appropriate insulation between poles. In addition, these barriers help to reduce the overall dimensions of the fuse base. A tripping mechanism is fixed to one of the bars and consists of a lever system and a separate microswitch for each pole. The NC contacts of each microswitch are connected in series, while the circuit ends are connected to terminals 1 and 2 of the terminal strip. If three operating fuse links are mounted onto the base, the microswitch NC contacts are closed and the circuit between terminals 1 and 2 of the terminal strip has continuity. The NO contacts of each microswitch are connected in parallel, while the circuit ends are connected to terminals 3 and 4 of the terminal strip. If three operational fuse links are mounted onto the fuse base, the microswitch NO contacts are opened and the circuit between terminals 3 and 4 of the terminal strip has no continuity. If any of the fuse links is missing or if the striker of one of the three fuse links is triggered, the circuit between terminals 1 and 2 will open and the circuit between terminals 3 and 4 will simultaneously close. 5.2 The single pole fuse base Single pole fuse bases, BPS-type, are manufactured in two basic versions i.e. as one- and two-piece devices. Two-piece bases consist of two steel bars fitted with M10 earthing terminals. Indoor resin post-insulators are fixed to these bars. Spring contacts and a terminal strip (with M12 screw terminals for easy connection to an electrical circuit) are mounted onto these insulators. In the one-piece version, the bars with the insulators are joined to a steel bar to make a single assembly. A tripping mechanism consisting of a lever system and a microswitch is fixed to one of the bars. The NC contacts of the microswitch are connected to terminals 1 and 2, whereas the NO contacts are connected to terminals 3 and 4 of the terminal strip. If an operating fuse link is mounted onto the base, the microswitch NC contacts are closed and the NO contacts are opened. If, however, the fuse link is missing or the fuse link striker is triggered, the NC contacts will open while the NO contacts will close. ABB 63
64 Indoor Fuse Bases Fuse base type BPS 6. CHARACTERISTICS Table 2. Fuse-base type Fuse-base voltage voltage BPS-01 Three-pole 7.2 Frequency current Un f In [kv] [Hz] [A] BPS7.2 Single pole BPS12 Single pole or Types of suitable fuse links BWMW-7.2/ CEF-7.2/ CMF - 7.2/ BWMW-7.2/ CEF-7.2/6-200 CMF-7.2/ BWMW-12/ CEF-12/6-200 CMF-12/ BPS17.5 Single pole CEF-17.5/6-63 BPS 24 Single pole BWMW-24/ CEF-24/6-125 BPS27 Single pole CEF-27/6-63 BPS36 Single pole Note: We reserve the right to make changes due to technological development. 7. CONFORMITY WITH STANDARDS The BPS fuse bases meet the requirements of the following standards: Polish Standard PN-77/E International Standard IEC BWMW-36/ CEF-36/ ORDERING METHOD The order must contain the following information: product name, type symbol, rated voltage, catalogue number and quantity of fuse-bases. All additional requirements not stated in this catalogue sheet must be agreed with the manufacturer. All inquiries must be made in writing and must state the source of the requirements (Regulations, Standards, etc.). 9. ORDER EXAMPLE Three pole fuse-base BPS-01 type, rated voltage 7.2 kv, catalogue number 1YMB207101M pcs. Single pole one-piece fuse base with resin insulators, type BPS 12, rated voltage 12 kv, zinc plated, for fuse links with dimension e=292 mm, catalogue number 1YMB507102M0005, 10 pcs. 64 ABB
65 Indoor Fuse Bases Fuse base type BPS 10. ENCLOSURES 1. Dimensioned drawings Single pole one-piece fuse base e screw M12 screw M12 H B A e 0 8 D D earthing screw M C Dimensions Un Fuse link dimension A B C H [kv] e/d [mm] [mm] [mm] [mm] [mm] /Ø53, 192/Ø65, 192/Ø /Ø53, 292/Ø65, 292/Ø ±1(resin post-insulators) /Ø53, 292/Ø65, 292/Ø ±1(resin post-insulators) 442/Ø53, 442/Ø65, 442/Ø ±1(porcelain post-insulators) /Ø53, 292/Ø65, 292/Ø ±1(resin post-insulators) 312±1(porcelain post-insulators) /Ø53, 442/Ø65, 442/Ø ±1(resin post-insulators) 537/Ø65, 537/Ø ±1(porcelain post-insulators) /Ø65, 442/Ø /Ø65, 537/Ø ±1(resin post-insulators) 389±1(p) 388±1(resin post-insulators) 389±1(porcelain post-insulators) ABB 65
66 Indoor Fuse Bases Fuse base type BPS Single pole two-piece fuse base e screw M12 screw M12 D H 80 e earthing screw M10 earthing screw M10 D Dimensions Un Fuse link dimension H [kv] e/d [mm] [mm] /Ø53, 192/Ø65, 192/Ø87 292/Ø53, 292/Ø65, 292/Ø87, 367/Ø87 192/Ø53, 292/Ø53, 292/Ø65, 292/Ø87 442/Ø53, 442/Ø65, 442/Ø87, 537/Ø65, 537/Ø87 442/Ø53, 442/Ø65, 442/Ø87, 292/Ø53 537/Ø53, 537/Ø87 192±1(resin post-insulator) 217±1(resin post-insulator) 218±1(porcelain post-insulators) 297±1(resin post-insulator) 312±1(porcelain post-insulators) /Ø53, 537/Ø87 388±1(resin post-insulator) 389±1(porcelain post-insulators) 66 ABB
67 Indoor Fuse Bases Fuse base type BPS 2. Wiring diagrams of fuse-base auxiliary circuits. K1 X1:3 3 (no) 4 (no) X1:4 X1:1 1 (nz) 2 (nz) X1:2 X1:3 X1:1 3 (no) 1 (nz) K1 4 (no) 2 (nz) X1:4 X1:2 NOTES for single pole BPS 1. Contacts 1 and 2 of one of the auxiliary switches, K1, are open, and contacts 3 and 4 are closed: a) After the fuse-link striker has been triggered b) If the fuse link is missing from the fuse holder 2. Contacts 1 and 2 of the auxiliary switches, K1, are closed, and contacts 3 and 4 are opened when fuse links in the fuse holder are operational. 3. Use fuse links with striker only. X1 K1:1 K1:2 K1:3 K1: xDY750V-1x1.5mm 2 4. Install fuse links with striker in the fuse holder in a manner that will allow the striker to be directed to the insulator with pull insulator. 5. K 1: type 83135, Ui = 380 V; Ue = 380 V, Ie = 6A, AC15; Ue = 220 V, Ie = 0.25A, DC13 6. X1: type LZ-B4/6, Ui = 500 V; 4mm 2 Cu, IEC K1 K2:3 3 (no) 4 (no) K2:4 X1:1 1 (nz) 2 (nz) K2:2 K2 K1:3 3 (no) 4 (no) K1:4 K3:3 K3:4 K3:1 1 (nz) 2 (nz) K1:2 K3 K2:3 3 (no) 4 (no) K2:4 X1:3 X1:4 NOTES for three poles BPS 1. Contacts 1 and 2 of one of the auxiliary switches K1, K2, K3 are open and contacts 3 and 4 are closed: a) After the fuse-link striker has been triggered, b) If the fuse link is missing from the fuse holder. 2. Contacts 1 and 2 of the auxiliary switches K1, K2, K3 are closed, and contacts 3 and 4 are opened when all three fuse links in the fuse holder are operational. K2:1 1 (nz) 2 (nz) X1:2 3. Use fuse links with striker only. X1 K1:1 K3:2 K3:3 K3: xDY750V-1x1.5mm 2 4. Install fuse links with striker in the fuse holder in a manner that will allow the striker to be directed to the insulator with pull insulator. 5. K1: type 83135, Ui = 380 V; Ue = 380 V, Ie = 6A, AC15; Ue = 220 V, Ie = 0.25A, DC13 6. X1: type LZ-B4/6, Ui = 500 V; 4mm 2 Cu, IEC ABB 67
68 We reserve the right to make technical changes or modify the contents of this document without prior notice. With regard to purchase orders, the agreed particulars shall prevail. Copyright 2006 ABB. Catalogue 3405PL004-W2-en. Edition ABB Sp. z o.o. Headquarters ul. Żeganska Warsaw, Poland phone: /831 fax.: ABB Sp. z o.o. Branch Offi ce ul. Leszno Przasnysz, Poland phone: /240 fax.:
Medium voltage products. Fuses
Medium voltage products Fuses Index Introduction... 3 Main definitions... 4 ABB HV Fuses with Temperature Control Unit... 5 General principles for fuse link selection... 6 CEF... 8 CEF-S... 16 CEF-VT...
ABB Fuses Competitive Advantages
GPMM Tomasz Komalski 2009 ABB Fuses Competitive Advantages May 14, 2009 Slide 1 Basic comments ABB is a global manufacturer of both current limiting and expulsion (non-current limiting) fuses for medium
Protection from Short-circuit
Protection from Short-circuit Back-up Fuse-Link with ÜLA (controlled power dissipation) Test device for tripping device Special version with threat High-voltage Fuse-Link for voltage transformers (HSW)
How To Build A Low Voltage Capacitor Lvcp
Low Voltage Capacitor LVCP The new choice for Power Factor Correction LVCP : the new choice for Power Factor Correction The LVCP is a compact and powerful capacitor. It offers high modularity, unmatched
CAS 36 Ring Main Unit
Power distribution networks Ring Main Unit Catalogue 2008 A new path for achieving your electrical installations A comprehensive offer The range is part of a comprehensive offer of products that are perfectly
Fuse Selection Method Module 2. Date of the presentation
Fuse Selection Method Module 2 Date of the presentation Fuse Selection When selecting LV fuses certain important information must be known. 1.System Voltage This is the voltage of the system or distribution
BRITISH STYLE SEMICONDUCTOR PROTECTION FUSES
The Edison British Style semiconductor protection fuses include a 660VAC line utilizing new filler technology. These new fuses have greatly reduced peak let-through current and energy under fault conditions
Medium Voltage (MV) & High Voltage (HV) Training Module 6. Date of the presentation
Medium Voltage (MV) & High Voltage (HV) Training Module 6 Date of the presentation Electrical System Basics MV vs. HV - Definitions Differences between USA and the rest of the world IEC define a high voltage
5SV Residual Current Protective Devices
s Siemens AG 2013 SENTRON 5SV Residual Current Protective Devices New portfolio for reliable personnel, material and fire protection Safe protection against residual currents Residual current protective
The standards mentioned in this document
The standards mentioned in this document Where can you order IEC publications? Central Offices of the International Electrotechnical Commission 1, rue de Varembé Geneva - Switzerland. The documentation
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS
MEDIUM AND HIGH VOLTAGE CAPACITORS, CAPACITOR BANKS AND SYSTEMS Meher Capacitors offers reliable and innovative products and solutions in the fields of Reactive Power Compensation, Power Quality and Energy
How To Choose A Transformer
Consider open loop MV network as an example source 1 source 2 NC NC NC or NO main MV switchboard A B Detail design of substation NC NC NC NO NC NC switchboard 1 switchboard 2 switchboard 3 MV MV MV LV
High-ohmic/high-voltage resistors
FEATURES High pulse loading capability Small size. APPLICATIONS Where high resistance, high stability and high reliability at high voltage are required High humidity environment White goods Power supplies.
Fuse Selection Guide
Fuse Selection Guide Although care is taken to properly design electrical and electronic circuits; overcurrents in the form of short-circuits and overload can occur. The sole purpose of fuses and circuit
GS Semiconductor Fuselinks. GE Power Controls. GS Semiconductor fuselinks
GE Power Controls GS Semiconductor fuselinks TYPE GS Semiconductor Fuselinks Technical information Full GS range of fuselinks are designed to the requirements of IEC269 -IV (1986) Precise Pre-determined
Fuseology. Medium Voltage Fuses. Continuous Current-Carrying Capacity. General. Interrupting Rating. Additional Rules.
Fuseology Medium Voltage Fuses General Fuses above are classified under one of three classifications as defined in ANSI/IEEE C37.40. 1. General Purpose Current-Limiting Fuse: A fuse capable of interrupting
Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation
Modular Systems, PPMV, 2014 UniPack-G Glass Fiber Reinforced Polyester Compact Secondary Substation Index News Introduction Applications & Segments Main Components Applicable Standards Technical characteristics
Fuses for Semiconductor Protection - Cylindrical Fuses. Class: Voltage ratings: Current ratings: Standards: Approvals: Features and Benefits
Fuses for Semiconductor Protection - Cylindrical Fuses SIBA cylindrical Ultra-Rapid fuses are available in six different sizes They can be ordered with an integral striker for blown fuse indication or
Unified requirements for systems with voltages above 1 kv up to 15 kv
(1991) (Rev.1 May 2001) (Rev.2 July 2003) (Rev.3 Feb 2015) Unified requirements for systems with voltages above 1 kv up to 15 kv 1. General 1.1 Field of application The following requirements apply to
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS
LIMITING SHORT-CIRCUIT CURRENTS IN MEDIUM-VOLTAGE APPLICATIONS Terence Hazel Senior Member IEEE Schneider Electric 38050 Grenoble France Abstract The power requirements for large industrial sites is increasing.
SF 6 Gas Insulated Switchgear Type SDF for 170 kv
Three Phase Encapsulated Type SF 6 Gas Insulated Switchgear Type SDF for 170 kv 06B1-E-0001 With Trustworthy Technology, Structure Fuji Electric as a manufacturer of comprehensive substation equipment
High-ohmic/high-voltage resistors
FEATURES These resistors meet the safety requirements of: UL1676 (range 510 kω to 11 MΩ) EN60065 BS60065 (U.K.) NFC 92-130 (France) VDE 0860 (Germany) High pulse loading capability Small size. APPLICATIONS
Three-phase monitoring relay CM-PFE
Data sheet Three-phase monitoring relay CM-PFE The CM-PFE is a three-phase monitoring relay that monitors the phase parameter phase sequence and phase failure in three-phase mains. 2CDC 251 005 S0012 Characteristics
BETA Protecting SITOR Semiconductor Fuses
BETA Protecting SITOR Semiconductor Fuses /2 Product overview /3 /17 SITOR, cylindrical fuse design /22 SILIZED, NEOZED and DIAZED design Siemens ET B1 /2008 Product overview Overview Devices Page Field
Secondary Unit Substations
14 SWITCHGEAR Secondary Unit Substations Overview Siemens offers a wide variety of unit substation designs to meet customer requirements. A unit substation consists of one or more transformers mechanically
High-Voltage Circuit-Breakers 3AP1/2 72.5 kv up to 550 kv. Power Transmission and Distribution
High-Voltage Circuit-Breakers AP/ 7.5 kv up to 550 kv Power Transmission and Distribution The AP/ High-Voltage Circuit-Breakers Now Applicable for 550 kv Decades of our experience in high-voltage switching
Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection
Technical Data Mini Circuit Breakers, Fuse Blocks, and Electronic Circuit Protection Topic Page 1489-M Miniature Circuit Breakers 2 1492-SP Supplementary Protectors 15 1492-D Circuit Breakers 27 188 Regional
Motor Protection Voltage Unbalance and Single-Phasing
Motor Protection Voltage Unbalance and Single-Phasing Cooper Bussmann contributes the following information, which is an excerpt from their 190-page handbook SPD Selecting Protective Devices Based on the
ABB 1. Three-phase monitoring relay CM-PFS. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories. Application.
1SR 430 824 F9300 Features Monitoring of three-phase mains for phase sequence and failure Powered by the measuring circuit 2 c/o (SPDT) contacts 1 LED for status indication Approvals R: yellow LED - relay
AutoLink Three-Phase Sectionalizer Specifications. Scope. General. Applicable Standards. Operating principle
Scope This specification stipulates the minimum requirements for mechanically linked three-phase electronic sectionalizers, for use on outdoor medium voltage overhead lines of 15, 27, and 38 kv. Electronic
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany. www.siemens.
Siemens AG Power Transmission and Distribution Medium Voltage Division Mozartstr. 31c 91052 Erlangen Germany www.siemens.com/energy For questions on power transmission and distribution, please contact
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU
ALTERNATIVE METHODS FOR INTERNAL ARC TESTS ON 12 KV AND 24 KV METAL-ENCLOSED SWITCHGEARS WITH COMPACT RMU George CURCANU, Constantin ILINCA, Ilie SBORA ICMET Craiova, Romania, Calea Bucuresti 144, phone:
High-Voltage Compact Switchgear 3AP1 DTC for 145 kv and 245 kv
High-Voltage Compact Switchgear AP1 DTC for 1 kv and kv Answers for energy. The AP1 DTC Complying with our Customers demands Experience you can rely on - at anytime, anywhere Decades of experience in high-voltage
UFES Active protection for switchgear
Active protection for switchgear ABB AG Oberhausener Strasse 4047 Ratingen, Germany Phone: +49 0-0 Fax: +49 0-7 77 Note: We reserve the right to make technical changes or modify the contents of this document
Low Voltage Products. Switches Automatic Transfer Switches
Low Voltage Products Switches Automatic Transfer Switches Growing importance of a secure power supply Standby power is an integral part of many industrial and domestic electrical systems. High energy prices,
Electronic timer CT-VBS.17+18 OFF-delayed without auxiliary voltage, for DC contactors Data sheet
Characteristics Single-function OFF-delay timer for DC contactors, without auxiliary voltage Width.5 mm CDC 5 6 F3 Approvals A culus E CCC CT-VBS a Circuit diagram b Marker label Marks a CE b C-Tick Order
PRODUCT GUIDE. SL Medium Voltage IEC Vacuum Contactors
PRODUCT GUIDE SL Medium Voltage IEC Vacuum Contactors Table of Contents 1 Overview Introduction....................................................2 Features........................................................2
Low voltage Direct Current Network. Compact NSX DC PV. Circuit breakers and switch disconnectors for solar application.
Low voltage Direct Current Network Compact NSX DC PV Circuit breakers and switch disconnectors for solar application Catalogue 2012 Compact NSX DC PV A complete DC offer for solar application from 80
MNS is Switchgear System Technical Overview
Switchgear System Technical Overview Innovative Design ABB s innovative MNS is concept combines the long term experience, energy efficiency, grid reliability and industrial productivity of the well-known
High Speed Fuses. High Speed Fuses
Section Contents Page General Applications........................ 9-95 North American fuses & accessories............9-113 DFJ - High speed Class J fuse...................97 Square Body fuses & accessories............
Power Supplies 3. SDN-P DIN Rail Series
SDN-P DIN Rail Series The SDN DIN Rail power supplies provide industry leading performance. Sag Immunity, transient suppression and noise tolerant, the SDN series ensures compatibility in demanding applications.
Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection)
Data sheet Temperature monitoring relays CM-TCS Monitoring relays for monitoring temperatures with a PT100 sensor (2- or 3-wire connection) The temperature monitoring relays CM-TCS monitor overtemperature,
Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
High Ohmic (up to 68 MΩ)/ High Voltage (up to 10 kv) Resistors
High Ohmic (up to 68 MΩ)/ A metal glazed film is deposited on a high grade ceramic body. After a helical groove has been cut in the resistive layer, tinned electrolytic copper wires are welded to the end-caps.
Medium voltage products. V-Contact VSC Medium voltage vacuum contactors
Medium voltage products V-Contact VSC Medium voltage vacuum contactors Index 4 1. Description 10 2. Contactor selection and ordering 20 3. Specific product characteristics 35 4. Overall dimensions 39
Submit shop drawings for equipment provided under this section Shop drawings shall indicate:
Section 16435 - SWITCHBOARDS Introduction Part 1 - General Reference The work under this section is subject to requirements of the Contract Documents including the General Conditions, Supplementary Conditions,
(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS
(PREVIEW) Indian Standard COMMON SPECIFICATION FOR HIGH-VOLTAGE SWITCHGEAR AND CONTROLGEAR STANDARDS IS 12729:2004 IEC 60694(2002) 1.1 Scope This International Standard applies to a.c. switchgear and controlgear,
Electronic overload relay EF19 and EF45
Data sheet Electronic overload relay EF19 and EF45 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays. Motor
PTC-Resistor Temperature-Sensors MINIKA to DIN 44 081 and DIN 44 082
PTC-Resistor Temperature-Sensors MINIKA to DIN 44 081 and DIN 44 082 General PTC-resistor temperature sensors (also called PTC-resistors or thermistors) are temperatur dependent semiconductor resistors
Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M
Uncompromising safety and comfort The next generation of miniature circuit breakers MCB S 200/S 200 M The details make the difference MCB S 200/S 200 M A range designed to ensure efficiency and protection
7. Reactive energy compensation
593 7. Reactive energy compensation 594 7. REACTIVE ENERGY COMPENSATION Reactive energy compensation is an important element for reducing the electricity bill and improving the quality of the electrical
Comparative study for cables and busbars
Comparative study for cables and busbars Preliminary considerations To compare the prices of two categories of product as different as traditional cables and busbars, it is necessary to make some preliminary
Safe and reliable distribution network ABB portfolio for medium-voltage indoor applications
Safe and reliable distribution network ABB portfolio for medium-voltage indoor applications Complete solution for indoor applications ABB s products provides safe, reliable and smart technologies for the
AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals
Technical Datasheet 1SBC101403D0201 24/03/11 AF09-30-22-.. / AF09Z-30-22-.. 2-stack 3-pole Contactors AC / DC Operated - with Screw Terminals AF09(Z) contactors are used for controlling power circuits
High Efficiency Motor Protection. Industry White Paper
High Efficiency Motor Protection Industry White Paper 2 High Efficiency Motor Protection High Efficiency Motor Protection - An Overview Electric motor protection depends on the accurate selection of overloads,
Fuses. Introduction. Measuring is knowing. Who chooses?
Fuses Introduction. There are many theories going around about the necessity for protecting PDUs (Power Distribution Unit / multiple socket / socket, etc.). A fuse is by definition a Single Point of Failure
R.C.C.B. s two-pole LEXIC
87045 LIMOGES Cedex Telephone : (+33) 05 55 06 87 87 Fax : (+ 33) 05 55 06 88 88 R.C.C.B. s two-pole LEXIC 089 06/09/10/11/12/15/16/17/18/ 27/28/29/30/35, CONTENTS PAGES 1. Electrical and mechanical characteristics...
Molded Case Circuit Breaker Specifications Bulletin Number 140U-D
Technical Data Molded Case Circuit Breaker Specifications Bulletin Number 140U-D Topic Page Product Line Overview 2 Specifications 3 Trip Curves 4 Approximate Dimensions 6 Additional Resources These documents
Medium voltage arc flash eliminator units VAM 3ED,
Medium voltage arc flash eliminator units VAM 3ED,, Medium voltage arc flash eliminator units Medium voltage arc flash eliminator units The new innovative arc eliminator VAM 3ED is an extremely fast acting
Medium Voltage Products. ZN1 12 kv arc-proof air-insulated switchgear for primary distribution
Medium Voltage Products ZN1 12 kv arc-proof air-insulated switchgear for primary distribution ZN1 an innovative switchgear for power distribution requirements ABB ZN1 primary distribution switchgear is
IEC 60269 gg & am STANDARD LOW VOLTAGE FUSE
IEC 60269 gg & am STANDARD LOW VOLTAGE FUSE. INTRODUCTION 2. INTRODUCTION TO THE IEC 60269 STANDARD 3. COMPARISON OF THE TIME CURRENT CURVES OF DIFFERENT FUSE TYPES 3.. Comparison of IEC and UL fuses 3.2.
Digital Energy ITI. Instrument Transformer Basic Technical Information and Application
g Digital Energy ITI Instrument Transformer Basic Technical Information and Application Table of Contents DEFINITIONS AND FUNCTIONS CONSTRUCTION FEATURES MAGNETIC CIRCUITS RATING AND RATIO CURRENT TRANSFORMER
Circulating Current Relay. Type IRXm
Circulating Current Relay Type IRXm ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering
Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.2 For single-phase AC/DC voltages The CM-ESS.2 is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of
UniGear ZS1. Medium voltage, arc proof, air insulated switchgear for primary distribution
UniGear ZS1 Medium voltage, arc proof, air insulated switchgear for primary distribution UniGear ZS1: an innovative solution for all installation requirements ABB UniGear is medium voltage metal-clad,
Mylar polyester film. Electrical Properties. Product Information. Dielectric Strength. Electrode Size. Film Thickness
Product Information Mylar polyester film Electrical Properties Mylar offers unique design capabilities to the electrical industry due to the excellent balance of its electrical properties with its chemical,
Electronic overload relay EF65, EF96 and EF146
Data sheet Electronic overload relay EF65, EF96 and EF146 Electronic overload relays offer reliable protection in case of overload and phase-failure. They are the alternative to thermal overload relays.
Technical catalogue. Modular DIN rail components Installation contactors
Technical catalogue Modular DIN rail components Installation contactors Installation Contactors Overview... ESB Installation Contactors 0 A / AC-/AC-7a ESB0...4 4 A / AC-/AC-7a ESB4...5 40 A / AC-/AC-7a
Current transformer selection guide
The selection of a current transformer is a simple task. There are four phases in the selection procedure. Current transformer selection guide KEEP IN MIND efine customer requirements based on the primary
Trip circuit supervision relay. Type RXTCS
Trip circuit supervision relay Type RXTCS ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while
Pressure monitoring equipment for oil-sf 6. bushings, type GOEK
Pressure monitoring equipment for oil-sf 6 bushings, type GOEK Installation and maintenance guide 5693 827-6 en, Rev. 3, 2002-01-30 This document must not be copied without our written permission, and
MTE SERIES RLW. World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930. 2009 MTE Corporation
MTE SERIES RLW World REACTORS USER MANUAL PART NO. INSTR 030 REL. 090930 2009 MTE Corporation IMPORTANT USER INFORMATION NOTICE MTE Series RLW reactors are components designed to improve the reliability
13. Electrical network design methodology and application example
873 13. Electrical network design methodology and application example 874 13. ELECTRICAL NETWORK DESIGN METHODOLOGY AND APPLICATION EXAMPLE The profitability of an industrial installation is directly linked
Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A.
Current Limiting Protector For Systems rated 2.8-38kV and continuous currents through 5000A. Arc Flash and Arc Blast reduction Network protection SCADA adaptable Indoor/outdoor application Professional
Current transformers (CT) & Shunts
Current transformers (CT) & Shunts Genreal overview LV CURRENT TRANSFORMERS Product selection guide Standard industrial transformers?????? TCR - TCRO range NEW 9 9 9 Current summation JVM 0 9 TCR usbar
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies
The Importance of the X/R Ratio in Low-Voltage Short Circuit Studies DATE: November 17, 1999 REVISION: AUTHOR: John Merrell Introduction In some short circuit studies, the X/R ratio is ignored when comparing
Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact
Data sheet Electronic timer CT-AHD.12 OFF-delayed with 1 c/o (SPDT) contact The CT-AHD.12 is an electronic time relay with OFF-delay. It is from the CT-D range. With their MDRC profile and a width of only
Part 1 System Modeling & Studies for Existing Systems
Part 1 System Modeling & Studies for Existing Systems Operation Technology, Inc. Copyright 2009 Result of rapid release of energy due to an arcing fault between two conductors. Bus voltages > 208V Temperatures
Enhanced Quality with a Touch of Style
Rudolf Current Transformer Enhanced Quality with a Touch of Style Current Transformer Enhanced Quality with a Touch of Style New Products Rudolf launched our new encapsulated current transformer. Portraying
Power Supply Unit, Primary Switched, Narrow Design MINI-PS-12-24DC/24DC/1
Power Supply Unit, Primary Switched, Narrow Design MINI POWER provides: Extra narrow design with widths of 22.5 mm, 45 mm, and 67.5 mm (0.886, 1.772, and 2.657 in.) Global use due to a wide-range input
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems. Safe energy distribution that meets the highest industrial requirements
NATUS NES / NES-H Draw-out Type Medium Voltage Switchgear Systems Safe energy distribution that meets the highest industrial requirements NATUS switchgear systems your advantages minimal use of insulant
ABB 1 NEW. Three-phase monitoring relay for grid feeding CM-UFS.1. Data sheet. Features. Approvals. Marks. Order data. Order data - Accessories
2CDC 251 014 F0t09 Features Monitoring of three-phase mains for grid feeding Type-tested in accordance with DIN V VDE V 0126-1-1: February 2006 Neutral conductor connection configurable Can also be used
STEP-PS/1AC/12DC/1.5. Extract from the online catalog. Order No.: 2868567. DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase
Extract from the online catalog STEP-PS/1AC/12DC/1.5 Order No.: 2868567 DIN rail power supply unit 12 V DC/1.5 A, primary switched-mode, 1- phase Commercial data EAN 4046356292924 Pack 1 pcs. Customs tariff
08. SEK IDC CONNECTORS
. IDC CONNECTORS connectors for flat cables enable simple and, cost-optimized device configuration. connectors are preferably used for connection within the device. HARTING offers a broad range of these
Bulletin 150 Smart Motor Controllers SMC-3 Smart Motor Controller
Overview/Modes of Operation Bulletin 150 Smart Motor Controller The SMC-3 is a compact, simple to use, solid-state motor controller designed to operate 3-phase motors. It features a built-in overload relay
www.siemens.com/energy High Voltage Circuit Breakers 3AP Type 72.5 kv to 800 kv Answers for energy.
s www.siemens.com/energy High Voltage Circuit Breakers AP Type 7.5 kv to 800 kv Answers for energy. The AP High Voltage Circuit Breakers Available up to 800 kv Decades of our experience in high voltage
Guidelines on the Short Circuit Current Rating for Industrial Control Panels
usa.siemens.com/sccr Guidelines on the Short Circuit Current Rating for Industrial Control Panels Technical Paper for Practical Applications White Paper I October 2014 As per NEC Edition 2014, and UL508A
Thermistor motor protection
Thermistor motor protection CM-E Range Thermistor motor protection Thermistor motor protection relays Benefits and advantages Selection table Operating principle and fields of application for thermistor
How To Select A Solid State Relay For A Three Phase Resistive Load
pero 1 Three Phase Solid State Relays & Their Application in Three Phase Heating Circuits By Paul Bachman, Fellow Engineer, Dr. Oscar Montero, R&D Manager, and Doug Sherman, FSAE Manager, Crydom, Inc.
3) What is the difference between "Insulating", "Isolating", and "Shielded Winding" transformers?
Tyco Electronics Corporation Crompton Instruments 1610 Cobb International Parkway, Unit #4 Kennesaw, GA 30152 Tel. 770-425-8903 Fax. 770-423-7194 1) What is a transformer and how does it work? A transformer
DS1 Diode-based transient-free capacitor switch
Medium voltage products DS1 Diode-based transient-free capacitor switch Power and productivity for a better world TM Compensation of reactive power DS1 the future of switches Compensation of reactive power
Sentron Series Circuit Breakers
Sentron Series Circuit Breakers Siemens Sentron Series circuit breakers are available in nine frame sizes: ED, FD, JD, LD, LMD, MD, ND, PD, and RD. Sentron Series circuit breakers have a wide range of
Series 8146/5-V37 and Series 8150/5-V37
www.stahl.de > Clear assignment safe technology easy installation > Intelligent structure only one rotary actuator for frequency-controlled drives ) 20 ms leading auxiliary contact for safe motor disconnection
Auxiliary Relay. Type P8n, PQ8n, PN8n
Auxiliary Relay Type P8n, PQ8n, PN8n ABB a global technology leader ABB is a global leader in Power and Automation technologies that enable utility and industry customers to improve performance while lowering
High Ohmic/High Voltage Metal Film Leaded Resistors
, High Ohmic/High Voltage FEATURES Metal film technology High pulse loading (up to 10 kv) capability Small size (0207/0411) Compatible with lead (Pb)-free and lead containing soldering processes Compliant
However, industrial applications may utilize a relay, which short-circuits the ICL path after the inrush sequence.
Application note for Inrush Current Limiters (ICL) Turning on electrical devices generally cause high inrush currents which can damage electronic components and cause interruption of the line voltage if
Packaging: MOQ: NIT, NET, TIA and TIS 20 per pack TCP and TFP 10 per pack Packaging 100% recyclable. Technical Data:
Packaging: MOQ: NIT, NET, TIA and TIS 20 per pack TCP and TFP 10 per pack Packaging 100% recyclable Catalogue Symbol: Class of Operation: Fuse Size: NIT (amp rating) NET (amp rating) TIA (amp rating) TIS
3.1.1 Full Type Tests & Routine Tests according to Clause 8 2 & 8 3. 4.0 Instructions For Installation, Operation & Maintenance
SPECIFICATION FOR LOW VOLTAGE SWITCHBOARD SEN I N D E X Description 10 STANDARD TECHNICAL REQUIREMENTS 11 Standards 12 General Operating Conditions 13 General Description Of Switchboard 131 Structure 132
Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages
Data sheet Voltage monitoring relays CM-ESS.M For single-phase AC/DC voltages The CM-ESS.M is an electronic voltage monitoring relay that provides reliable monitoring of voltages as well as detection of