SPECIFICATION STANDARD GROUNDING AND BONDING

Similar documents
TC Grounding and Bonding for Telecommunications Systems

Minimum Standards for Data/Voice Infrastructure in New Building Construction

HOUSTON COMMUNITY COLLEGE HCC ALIEF CAMPUS MAIN BUILDING, FIRST, SECOND & FOURTH FLOORS RENOVATION ISSUE DATE:

Section Grounding and Bonding for Communications

NORTH ORANGE COUNTY COMMUNITY COLLEGE DISTRICT SECTION GROUNDING AND BONDING FOR COMMUNICATION SYSTEMS

GUIDELINES HAS/PDC/DESIGN DIVISION TITLE

TABLE OF CONTENT

This presentation to be used in conjunction with:

DIVISION 27 COMMUNICATIONS. A. System design shall be completed by a Registered Communications Distribution Designer (RCDD).

STREETLIGHT SYSTEM GROUNDING AND BONDING

800 Communications Circuits

SECTION TELECOMMUNICATION ROOMS

Standards. 5 ANSI/TIA/EIA-569-A (CSA T530)

ELECTRICAL SERVICE REQUIREMENTS FOR MOBILE HOME DEVELOPMENTS

SECTION 22 LIGHTNING PROTECTION SYSTEM

DIVISION 26 - ELECTRICAL SECTION CABLES FOR INSTRUMENTATION

Specification Standards Communications Underground Ducts, Raceways and Structures

ELECTRIC METERING COMMERCIAL & INDUSTRIAL

Chapter 9. Bonding and Grounding

East Central College HANSEN HALL LEVEL 300/400 RENOVATIONS PACKAGE

Building Telecommunications Infrastructure Requirements

David Brender Copper Development Association Inc. Miramar, March 8, 2013

Grounding & Bonding Why it is done And How to Install Properly

SECTION CABLE TRAYS FOR COMMUNICATIONS SYSTEMS

All work must conform to the National Electric Code, latest edition, and all other applicable codes and regulations.

CONTENTS. Yale University Design Standards. Underground Electrical Duct Bank. A. Summary. B. System Design and Performance Requirements

CDGRD-10. Grounding. Solutions For Comm/Data Applications

Application Bulletin NEC Reference Guide for SolarBridge-Enabled AC Module Installers

TS 813 GROUNDING AND BONDING TTD TRAFFIC SIGNAL INSTALLATION AND CONTROLLER CABINET GROUNDING SYSTEM TTD CONTROLLER CABINET GROUNDING

Telecommunications Systems Narrative Page 1 The Engineering Enterprise

Document Purpose: Document Scope:

AT&T Specifications Trenching Conduit Boxes and M anholes Aerial Entrance Masts Service Cabinets Bonding and Grounding

2014 NEC Guide Lines for Home Owner Doing Electrical Work on their Property

DEPARTMENTAL REGULATION

SECTION COMMON WORK RESULTS FOR ELECTRONIC SAFETY AND SECURITY

5.2. Overview. The better method to install solderless compression connectors on power cable

ATT-TP Grounding and Bonding Requirements for AT&T Internet Cloud, Internet Services, and Video Facilities

4 Installation Requirements

The National Armored Cable Manufacturers Association Presents. Installation Standard for Types AC and MC Cables

SECTION CABLE TRAYS. A. Continuous, rigid, welded steel or stainless steel wire mesh cable management system.

Specifications for Communication Cabling Distribution Systems

The Contractor shall furnish and install all shielded power cable suitable for use on this project.

Multiple Meter Installation Amperes Per Position -Single Phase, Self-contained

SPECIFICATION STANDARD OPTICAL FIBER BACKBONE CABLING

OFFICE OF INFORMATION TECHNOLOGY/ NETWORKING AND TELECOMMUNICATIONS SERVICES (OIT/NTS) EQUIPMENT, INFRASTRUCTURE, AND WIRING STANDARDS

Electrical Code Regulation

TCTC Cabling Specifications

Generic Category 5e Cabling Specification

SECTION COMMUNICATIONS OPTICAL FIBER OSP CABLING

Solar Power Solutions

Conduit Tubing Electrical Metallic Tubing (EMT) Intermediate Metal Conduit (IMC) Hot-Dip Galvanized Steel Rigid Metal Conduit (RMC)

SECTION SIGNAL WIRE AND CABLE

Introduction to Data Centre Design

IRRIGATION PUMPING Table of Contents - Section 900

UT Southwestern Medical Center Information Resources Cable Installation Standard

SYSTIMAX SCS PowerSum and GigaSPEED XL Cabling Installation Guidelines

EARTHING AND BONDING AT SECONDARY SUBSTATIONS

2011/2008/2005 NATIONAL ELECTRICAL CODE SOLAR PV CODE COMPLIANCE REFERENCE

FIREFINDER XLS ADDRESSABLE FIRE ALARM SYSTEM SECTION 13851

TELECOMMUNICATIONS STRUCTURED CABLING GUIDELINES AND SPECIFICATIONS. University of Chicago IT Services Infrastructure Services October 2011

ONTRAC WIRE MESH CABLE TRAY SYSTEM

Conduit Fittings & Accessories Directional Drilling Conduit Utility Duct Telephone Duct Residential Boxes

Requirements for the Attachment of Communication Cable Facilities on PPL Poles

METER REQUIREMENTS GENERAL REQUIREMENTS SECTION D

Presenters Brett Weiss, Gabe Martinez, Brian Kroeger.

Please check with your local inspection authority for any additional requirements before installation.

Electrical Service Guidelines

DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS

RESIDENTIAL ELECTRICAL REQUIREMENTS (REVISED 3/28/2008) PERMIT REQUIREMENTS:

ANSI/TIA/EIA-606. Administration Standard for the Telecommunications Infrastructure of Commercial Buildings

Wire types and sizes

Division 27 Master Specification for

RAY-MAX Integrated Solar Power Strip

White Paper SolarEdge Three Phase Inverter System Design and the National Electrical Code. June 2015 Revision 1.5

B. Cross-Connect: A facility enabling the termination of cable elements and their interconnection or cross-connection.

AC and DC Drive System Installation Information

ELECTRICAL GUIDELINES FOR SINGLE-FAMILY HOME OWNERS:

ATTACHMENT F 050R CABLE AND WIRING SERVICES FUNCTIONAL AREA I PRICE PROPOSAL FORM Amendment 6

LEAD FREE FIREX. Interlock Armored Cables TECK90 and MC Industrial Cables. w w w. n e x a n s e n e r g y. c o m

Electrical Grounding. Appendix C

NEGRP TEST SUMMARY. Joseph A. Lanzoni, November 2005

SECTION 680 FIBER OPTIC CABLE DESCRIPTION

Figure 1 (end) Updated document to corporate requirements Added text to Paragraph 2.4

UNIFIED FACILITIES GUIDE SPECIFICATIONS

This Addendum forms a part of the Contract Documents and modifies the original Bidding Documents and Prior Addenda if any, as identified above.

Cable Runways & Accessories

FiberGuide Fiber Management Systems. 4th Edition

Coaxial Cable Entry Panels, Coax and Grounding Connectors. Technical Note

1 Campus Cabling Systems Introduction

Section 21. Telecommunication Hardware. BuyLog Catalog 21-1

Grounding of Electrical Systems NEW CODE: Grounding and Bonding

KSR-SK-DB In-Line Splice Kit KSR Snow Melting Cable INSTALLATION PROCEDURES

Canopy Surge. User Manual

Requirements for Electrical Installations

Transcription:

PART 1: GENERAL 1.01 SCOPE OF WORK SPECIFICATION STANDARD A. The grounding and bonding system refers to all electrodes required by NEC, as well as including made, supplementary, information technology and telecommunications system grounding electrodes B. Provide all labor, materials, tools, installation equipment, and test equipment required for the complete installation of grounding and bonding for fore mentioned systems within the structure. C. The Design Team and/or Contractor are held responsible to be familiar with the provisions contained herein and with other Sections of this Specification as applicable to the completion of the installation. The approved vendor, designated agent or employee is responsible to be familiar with the provisions contained herein and is assumed to posses the knowledge, manpower, and material applicable to completion of the installation. D. Work covered by this Section shall consist of furnishing labor, equipment, supplies, materials, and testing otherwise specified, and in performing the following operations recognized as necessary for the installation, termination, and labeling of ground and bonding infrastructure as described on the Drawing and /or required by these specifications. E. Listed manufacturers and products are required. UNM IT approved equivalent products and systems are also acceptable with prior written approval of submittals by UNM IT. F. The telecommunications main grounding bar (TMGB) is a dedicated extension of the building grounding electrode system for the telecommunications system. The TMGB should be located near the telecommunications service entrance and the electric service entrance. G. The TMGB shall be located to minimize the length of the bonding conductor for telecommunications from the TMGB to the electric service ground. H. The TMGB shall serve telecommunications equipment that is located in the same room or space. I. The TMGB shall be located in an area that is accessible to UNM IT personnel. J. A telecommunications grounding busbar (TGB) shall be provided in each area where telecommunications equipment is located. The TGB is the grounding connection point for telecommunications systems and equipment in each separate area. The University of New Mexico 802 Yale Blvd. NE Albuquerque, NM 87131-0001 Phone: 505.277.1111 www.unm.edu/its February 23, 2010 Page 1 of 9

K. All metal conduits or raceways for telecommunications cabling located within the same room or space as the TMGB shall be bonded to the TMGB. L. Where an electric power panel for telecommunications equipment is located in the same room or space as the TGB, the panel ground bus or panel enclosure shall be bonded to the TGB. M. The telecommunications backbone (TBB) is a conductor that originates at the TMGB and extends throughout the building interconnecting all telecommunications grounding busbars (TGBs) with the TMGB. N. Where there are multiple telecommunications rooms or spaces with multiple TBBs, the TBBs shall be interconnected with a Grounding Equalizer (GE) conductor at the TGBs. O. In structural steel frame buildings, where the steel framework is accessible within the room; the TMGB and each TGB shall be bonded to the structural steel frame using a minimum No. 6 AWG conductor. 1.02 RELATED SECTIONS A. Division 27, Section 27 00 00 Communications General. B. Division 27, Section 27 05 28 Pathway for Communicants Systems. C. Division 27, Section 27 05 43 Underground Ducts and Raceways for Communications. D. Division 27, Section 27 05 53 Identification for Communications Systems. E. Division 27, Section 27 11 13 Communications Entrance Protection. F. Division 27, Section 27 11 16 Communications Cabinets, Racks, Frames, and Enclosures. G. Division 27, Section 27 11 19 Communications Termination Block and Patch Panels. H. Division 27, Section 27 11 23 Communications Cable Management and Ladder Rack. I. Division 27, Section 27 13 13 Communications Copper Backbone Cabling. J. Division 27, Section 27 13 23 Communications Optical Fiber Backbone Cabling. K. Division 27, Section 27 13 33 Communications Coaxial Backbone Cabling. L. Division 27, Section 27 15 13 Communications Copper Horizontal Cabling. M. Division 27, Section 27 15 23 Communications Optical Fiber Horizontal Cabling. N. Division 27, Section 27 15 33 Communications Coaxial Horizontal Cabling. O. Division 27, Section 27 15 43 Communications Faceplates and Connections. P. Division 27, Section 27 21 33 Data Communications Wireless Access Points. Q. Division 26, Section 26 41 00 Facility Lightning Protection 1.03 REFERENCES A. Publications listed below (including amendments, addenda, revisions, supplements, and errata) form a part of this specification to the extent referenced. Publications are referenced in the text by the basic designation only. The bonding and grounding system shall be compliant with the following references. The University of New Mexico 802 Yale Blvd. NE Albuquerque, NM 87131-0001 Phone: 505.277.1111 www.unm.edu/its February 23, 2010 Page 2 of 9

1.04 Quality Assurance 1. Institute of Electrical and Electronics Engineers, Inc. (IEEE): 81-1983 - IEEE Guide for Measuring Earth Resistivity, Ground Impedance, and Earth Surface Potentials of a Ground System 2. National Fire Protection Association (NFPA): National Electrical Code (NEC) 3. Telecommunications Industry Association, (TIA) J-STO-607-A- Commercial Building Grounding (Earthing) and Bonding Requirements for Telecommunications 4. Underwriters Laboratories, Inc. (UL): 467 - Grounding and Bonding Equipment 5. ANSI T1.333-2001 Grounding and Bonding of Telecommunications Equipment 6. UNM Physical Plant Department Electrical Standards 7. Manufacturer Installation Specifications 1. The materials and their installation shall conform to the requirements of ANSI-J-STD-607-A-2002 and the National Electrical Code 2. Use adequate numbers of skilled work-persons thoroughly trained and experienced on the necessary crafts and completely familiar with the specified requirements and methods needed for the proper performance of the work of this Section. 3. UNM IT will inspect, test and or commission the system upon completion. The Contractor is required to make modifications to any work found to be in non compliance with this Standard. PART 2: PRODUCTS 2.01 MATERIALS A. All materials used in the installation shall be new and shall comply in weight, size and composition as required by manufacturer and shall be labeled or listed by Underwriters Laboratories Inc. for use in electrical grounding. 2.02 GOUNDING BUSBARS The University of New Mexico 802 Yale Blvd. NE Albuquerque, NM 87131-0001 Phone: 505.277.1111 www.unm.edu/its February 23, 2010 Page 3 of 9

A. Telecommunications Grounding Main Grounding Busbar (TMGB). 1. Predrilled, copper, non anodized BICSI/TIA/EIA/ANSI approved (4 W x 1/4 H x 12 L) ground bus bar with insulators and standoffs. (Chatsworth 40153-012 or UNM IT approved equivalent) B. Telecommunications Grounding Busbar (TGB) 1. Predrilled, copper, non anodized BICSI/TIA/EIA/ANSI approved (2 W x 1/4 H x 12 L) ground bus bar with insulators and standoffs. (Chatsworth 13622-012 or UNM IT approved equivalent). C. Equipment Rack Busbar 1. Panduit #TRGK672 Telecommunications Rack Grounding Kit or UNM IT approved equivalent. 2.03 GROUNDING JOINTS AND SPLICES A. Grounding conductor splices shall be joined with mechanical crimped sleeve designed to have two crimps per side with proper indents markings. Crimp sleeves shall be copper alloy. B. Grounding conductor shall be terminated with a mechanical crimped type lug designed to have two crimps, spade section of have two bolts and made of copper alloy. 2.04 BONDING CONDUCTORS A. Cable Tray Bonding Conductor 1. Green # 6 AWG insulated bonding jumper with appropriate lugs or manufactured braided copper grounding jumper equal to a # 6 AWG cable. B. Equipment Fame Bonding Conductor 1. Bonding Conductor shall be run neatly and uniformly to the equipment, racks and trays. C. Bonding Conductor (BC) 1. Green insulated copper bonding conductor, size as requires by NEC. 2. The BC shall be, as a minimum the same as the TBB. D. Telecommunications Bonding Backbone (TBB) The University of New Mexico 802 Yale Blvd. NE Albuquerque, NM 87131-0001 Phone: 505.277.1111 www.unm.edu/its February 23, 2010 Page 4 of 9

1. Green insulated copper conductor, minimum as specified in the table below, size 6 AWG. The TBB shall be sized at 2 kcmil per linear foot of conductor length up to a maximum size of 3/) AWG Insulation shall meet fire ratings of its pathway. TABLE 1 Sizing of Telecommunication Bonding Backbone (TBB) TBB length FT Grounding Conductor Size (AWG) DC Resistance Per 100 Ft (Copper Conductor) Short- Time Rating (A) 8 0.0778 391 < 13 Ft 6 0.0491 621 14-20 Ft 4 0.0308 988 21-26 Ft 3 0.0245 1245 27-33 Ft 2 0.194 1571 34-41 Ft 1 0.0154 1981 42-52 Ft 1/O 0.0122 2499 53-66 Ft 2/O 0.00967 3150 > 66 FT 3/O 0.00766 3972 4/O 0.00608 5008 Kcmil 250 0.00515 5917 300 0.00429 7101 350 0.00367 8284 400 0.00321 9467 500 0.00258 11834 AWG = American Wire Gauge DC = Direct Current kcmil = Thousand circular mils 2.05 GROUND RODS A. Copper clad steel, 19 mm (3/4-inch) diameter by 3000 mm (10 feet) long, conforming to UL 467. The University of New Mexico 802 Yale Blvd. NE Albuquerque, NM 87131-0001 Phone: 505.277.1111 www.unm.edu/its February 23, 2010 Page 5 of 9

B. Quantity of rods shall be as required to obtain the specified ground resistance. 2.06 SPLICES AND TERMINATION COMPONENTS A. Components shall meet or exceed UL 467 and be clearly marked with the manufacturer, catalog number, and permitted conductor size(s). 2.07 GROUND CONNECTIONS A. Below Grade: 1. Exothermic-welded type connectors. B. Above Grade: 1. Bonding Jumpers: compression type connectors, using zinc-plated fasteners and external tooth lock washers. 2. Ground Busbar: Two-hole compression type lugs using tin-plated copper or copper alloy bolts and nuts. 3. Rack and Cabinet Ground Bars: one-hole compression-type lugs using zincplated or copper alloy fasteners. 4. Cable Shields: Make ground connections to multi-pair communications cables with metallic shields using shield bonding connectors with screw stud connection. PART 3: EXECUTION 3.01 GROUNDING AND BONDING INSTALLATION A. Bond and ground all conduits, cable trays, enclosures, cables, protectors and other conductive infrastructure as per the NEC and TIA 607 and other references to the main building ground. 1. Clean surfaces nonconductive coatings (such as paint, lacquer, and enamel) on equipment to be grounded shall be removed from threads and other contacts surfaces to ensure good electrical continuity or be connected by means of fittings designed so as to make such removal unnecessary. Install all parts as specified by the manufacturer. Do not daisy chain bonding conductors from device to devices. 2. Install all cable tray to meet the grounding and bonding requirements of NEC Articles 110.3, 250.96, 250.102, 392.3, 392.7 and all applicable codes. 3. Connections to the TMGB shall be made by exothermic welding or by listed two-hole compression lugs. The University of New Mexico 802 Yale Blvd. NE Albuquerque, NM 87131-0001 Phone: 505.277.1111 www.unm.edu/its February 23, 2010 Page 6 of 9

4. All metal conduits or raceways for telecommunications cabling located within the same room or space as the TMGB shall be bonded to the TMGB. B. Installation of the TMGB in ER/TR. 1. Install the TMGB at the bottom of the plywood backboard near the outside plant entrance conduits within the UNM IT Telecommunications Space. 2. TMGB shall be installed so that the BC is as short and straight as possible, with the proper bend radius. All bend radiuses shall be 90 degrees. 3. The BC shall be Green insulated conductor installed exposed per Table 1 in PART 2. 4. Busbar shall be predrilled for future connections. 5. Provide label (Do Not Disconnect) on connection to main electrical service ground. C. Installation of TGB in TR. 1. Install the TGB at the bottom of plywood backboard near the copper riser terminations within the UNM IT Telecommunications Space. 2. TGB shall be installed so that the TBB for telecommunications is as short and straight as possible, with the proper 90 degree bend radius. 3. The BC shall be a green insulated conductor sized from Table 1 in Part 2. 4. Busbar shall be predrilled for future connections. D. Installation of the TBB. 1. Installation mechanical type, copper alloy, with minimum of two bolts and separate sections for each conductor or copper compression type with two (2) indents. E. Installation of Grounding Conductor Joints/Splices. 1. Install manufactured insulating cover or heavy tape insulation over joints /splices. F. Grounding of Cable Tray/Ladder Rack/Basket Tray 1. Install Green #6 AWG bonding jumper (12 inches max) with manufacturer approved devices at each cable tray joint or install manufacture braid copper grounding The University of New Mexico 802 Yale Blvd. NE Albuquerque, NM 87131-0001 Phone: 505.277.1111 www.unm.edu/its February 23, 2010 Page 7 of 9

jumper. In lieu of bonding jumpers, use manufactures approved grounding type connectors to connect sections of cable tray will be permitted. 2. Install Green #6 AWG grounding conductor with manufacturer approved devices from side of cable tray down to TMGB or TGB. Drill the side of the cable tray and install a ¼ / 20 appropriate length bolt, making sure that the bolt does not extend into wire management part of the tray. G. Ground of Equipment Frame 1. Install a ground busbar at the top of the equipment frame to ground cable tray, TMGB or TGB. H. Grounding of Telecommunications Ductbanks. 1. Provide a continuous # 4/0 bare stranded copper conductor within the concrete at the bottom of all duct banks. Terminate to the bonding ribbon in telecommunications maintenance holes. I. Grounding of Telecommunications Maintenance Holes and Handholes. 1. Provide bonding jumper to reinforcing steel in each section. 2. Install a bonding ribbon horizontally around the bottom of each maintenance hole and attached to all cable rack and metallic hardware within the maintenance hole. Continue installation vertically between bonding clamps so both top and bottom halves are bonded together on each side. (The bonding ribbon will be used to bond and ground all future splice cases and hardware placed within the maintenance hole). 3. Provide a ground rod near a corner within 6 inches of the corner in each maintenance hole and handhole. Bond to the ribbon in maintenance hole. J. Grounding of Protectors 1. Install grounding as per manufacturer instructions. 3.02 Testing the Grounding and Bonding System 1. Visually inspect all grounds and bonds for loose connections. 2. Test the potential difference between the TMGB and the electrical ground and between the TMGB and each TGB. The University of New Mexico 802 Yale Blvd. NE Albuquerque, NM 87131-0001 Phone: 505.277.1111 www.unm.edu/its February 23, 2010 Page 8 of 9

3. Connection at TMGB from main electrical service ground shall be installed to meet NEC 250.94 and TIA/EIA requirements type. Ground resistance shall not exceed 2 ohms, unless approved by UNM IT. 4. Ohm resistance testing shall be done between the TGB and all racks, cable tray, and electronic equipment to identify any high resistance connections. 5. The difference in ground potential between the telecommunications and electrical system at the workstation should not exceed 1.0 volt. End of Section The University of New Mexico 802 Yale Blvd. NE Albuquerque, NM 87131-0001 Phone: 505.277.1111 www.unm.edu/its February 23, 2010 Page 9 of 9